Compatibility With Different Grid Types: Y Configuration Delta Configuration

This document discusses the compatibility of GoodWe solar inverters with different grid types. Most grids use 230V/400V at 50Hz or 60Hz, but some areas use 120V split-phase supply, 230V three-phase grids, or other voltages. The document outlines solutions for using GoodWe inverters on split-phase and three-phase 230V grids, such as connecting two grid phases to the inverter or using low-voltage three-phase inverters. Future single-phase inverters from GoodWe will be compatible with 120V split-phase grids without special wiring.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
149 views3 pages

Compatibility With Different Grid Types: Y Configuration Delta Configuration

This document discusses the compatibility of GoodWe solar inverters with different grid types. Most grids use 230V/400V at 50Hz or 60Hz, but some areas use 120V split-phase supply, 230V three-phase grids, or other voltages. The document outlines solutions for using GoodWe inverters on split-phase and three-phase 230V grids, such as connecting two grid phases to the inverter or using low-voltage three-phase inverters. Future single-phase inverters from GoodWe will be compatible with 120V split-phase grids without special wiring.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Compatibility With Different Grid Types

VER: 01, UPDATED ON AUGUEST 22nd , 2019

Most of the world population (Europe, Africa, Asia, Australia, New Zealand) and much of South America use a supply of standard
230 V (phase voltage) and 400V (line voltage) with neutral cables at 50Hz or 60Hz. Or there might be a Delta grid pattern for power
transportation and industrial use for special machines. And as a corresponding result, most of the solar inverters for house use or
commercial rooftops are designed on such basis.

Figure. 1 Figure. 2

Y configuration Delta configuration


L1 L1

L2
L2

L3

L3
Neutral
But there are exceptions. Here we will talk how to use the normal solar inverters in such exception grid types.

1.SPLIT-PHASE SUPPLY
Like in the United States and Canada they use a supply voltage of 120 volts ± 6%. Japan, Taiwan, North America, Central America 
and some parts of northern South America use a voltage between 100 V and 127 V for normal house supply. For house use, the
grid supply pattern we call it split-phase electricity supply.

Figure. 3 Figure. 4

V1
V1
N V1+V2
V2
V2
V2 V1
N
EXAMPLE USA
V1,V2=120 Volts
V1+V2=240 Volts

[email protected] [email protected] @GoodWeSolarAcademy 1-3


Compatibility With Different Grid Types
VER: 01, UPDATED ON AUGUEST 22nd , 2019

Solar Inverter Connections

As the nominal output voltage of most GoodWe single-phase solar inverters are 230V with neutral wire, so it does not connect as
usual.
Solutions as below:
By connecting two phases of the grid (phase voltage is 100V, 110V, 120V, or 170V etc.) to the inverter to fit for a 220V/230Vac
voltage, the solar inverter could work normally.

Figure. 5

On-Grid Loads
(110V)

L
L1
110V
220V N
N L2
PV Utility

Note:
A. This solution is only suitable for single-phase grid-tied or hybrid inverters.
B. If it has requirement for special functions like zero export function, please contact GoodWe for details.

2.230V THREE PHASE GRID

Like in North America and part South American countries, there also use three phase 230Vac grid as below. And it could be delta
connection or wye connection depending on different use.

Secondary B

Primary B

240V
208V

PA PC

SA SC

Center Tap

120V 120V
240V

Figure.6 Figure.7

[email protected] [email protected] @GoodWeSolarAcademy 2-3


Compatibility With Different Grid Types
VER: 01, UPDATED ON AUGUEST 22nd , 2019

GoodWe Solutions
To fit for such electricity system, GoodWe provides a solution by LV version grid-tied 3-phase solar inverters, which include
GW12KLV-DT, GW15KLV-DT, GW30KLV-MT, GW35KLV-MT and GW50KLV-MT, which could use with both Star Grid or Delta Grid
(Fig.7) by commissioning on inverter display.

Technical Data GW30KLV-MT GW35KLV-MT


Max. Output Power(W) [240VAC] 33000 39900
AC Output Data

Max. Output Apparent Power(VA) 33000 39900

Nominal Output Voltage (V) 150-300 150-300

Nominal Output Frequency (Hz) 50/60 50/60


Max.Output Current (A) 80 96

Output Power Factor ~1(Adjustable from 0.8 leading to 0.8lagging)

Figure.8

In a short future, GoodWe will also have single-phase solar inverters with standard output voltage 120V, which is totally fit for SPLIT
grid with no special wiring. Let us keep updated.

Notice
The information in this document is subject to change without notice, all information in this document do not constitute any kind of warranty.

Please check with GoodWe Solar Academy '[email protected]' for the latest version. 

[email protected] [email protected] @GoodWeSolarAcademy 3-3