Fire Pump Room Requirement

The document outlines general requirements for firefighting pump rooms, including that the room must be accessible to fire departments and have sufficient space for maintenance of equipment. It lists 10 specific requirements for pump rooms, such as coordinating the location with fire departments, ensuring fire rated doors and walls, providing proper lighting and ventilation, installing water taps and power outlets, and including sprinkler fire protection. The pump room is described as containing the most important equipment for protecting the building in case of fire.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views1 page

Fire Pump Room Requirement

The document outlines general requirements for firefighting pump rooms, including that the room must be accessible to fire departments and have sufficient space for maintenance of equipment. It lists 10 specific requirements for pump rooms, such as coordinating the location with fire departments, ensuring fire rated doors and walls, providing proper lighting and ventilation, installing water taps and power outlets, and including sprinkler fire protection. The pump room is described as containing the most important equipment for protecting the building in case of fire.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 1

FIRST LESSON IN FIRE FIGHTING PUMP ROOM REQUIREMENTS

Firefighting pump room is the most important room since it’s the room contain the
most important equipment protecting the building in case of fire and this
equipment needs an accessible location for easy maintenance and operation.

This is important to the architectural engineers HVAC and firefighting engineers

General Requirements:

1. Pump room location shall be coordinated with the fire departments. Access
shall be as per NFPA 20 Paragraph 4.12.2.1( Under ramps ,Under stairs
locations are not preferable)
2. Minimum accessible dimensions for maintenance all around the equipment's
as per NFPA20 (2013) Paragraph 4.12.1.1.6 (Room heights room
dimensions shall be enough to accommodate the pumps).
3. Fire rated doors and walls as per NFPA20 table 4.12.1.1.2
4. Proper lighting and emergency lighting according to NFPA 101
5. Proper ventilation including air supply and up to 10 air change /hour exhaust
6. Water taps for cleaning and washing during maintenance.
7. Power supply socket for maintenance and cleaning equipment's.
8. Sufficient drain outlet nearby fire pumps controllers and pumps engines
(gutter drain connected to nearby drain point).
9. Area radio coverage as per NFPA 5000 Paragraph F3.2.1.
10.Sprinkler system fire protection in accordance to NFPA13 and to be
considered as Extra hazard group 2 space.