Assignment On Corona
Assignment On Corona
1. Estimate the corona loss for a three phase 110 kV,50 Hz 150km long transmission line
consisting of three conductor each 10mm dia and spaced 2.5m apart in an equilateral
triangle formation. The temperature of air is 30 degree C and the atmospheric pressure
is 750mm of Hg. Take irregularity factor 0.85. Ionisation of air may be assumed to take
place at maximum voltage gradient of 30 kV/cm.
2. Find the critical disruptive voltage and the critical voltages for local and general corona
on a three phase overhead transmission line, consisting of three stranded copper
conductors spaced 2.5m apart at the corners of an equilateral triangle. Air temperature
and pressure are 21 degree C and 73.6 cm Hg respectively. The conductor dia,
irregularity factor and surface factors are 10.4mm, 0.85, 0.7 and 0.8 respectively.
3. Determine the critical disruptive voltage and corona loss for a three phase line operating
at 110 kV which has conductor of 1.25cm dia arranged in a 3.05 metre delta. Assume
air density factor 1.07 and the dielectric strength of air to be 21kV/cm
4. Determine the corona characteristics of a three phase , 50Hz 132 kV transmission line
100 km long running through terrain at an altitude 600 metres, temp of 30 degree C and
barometric pressure 74 cm. The conductors are 1.5 cm diameter and spaced with
equilateral spacing of 2.75 meters. Assume surface irregularity factor of 0.9 and
mv=0.75.
5. A three phase ,50Hz,132kV transmission line consists of conductors of 1.17 cm dia and
spaced equilaterally at a distance of three metres, the line conductors have smooth
surface with value m= 0.96, the barometric pressure is 72cm of Hg and temperature of
20 degree C. Determine the fair and foul weather corona loss per km per phase.
6. A three phase 50 Hz Transmission line has conductors in equilateral formation spaced
2.5 metres apart, the conductor diameter is 1.04 cm and the surface factor is 0.85, the
air pressure and temperature are 74cm of Hg and 21 degree C respectively. Determine
the critical visual voltage for corona and corona loss per km per phase of the line,
mv=0.72.
7. A single phase transmission line has conductors of diameter 1.25 cm and spaced 2.5
metres apart. Derive the expression for the potential gradient at any point on a line
joining the centres of the conductor if the operating voltage of the line is 60 kV.
Calculate the voltage at which corona will start.
8. Determine the corona characteristics of a three phase line 160 km long conductor
diameter 1.036cm,2.44m delta spacing , air temperature 26.67 degree, altitude
2440m,corresponding to an approximate barometric pressure of 73.15cm,operating
voltage 110kV at 50Hz.