Understanding Insulation Resistance Testing: Maintenance, Repair & Operations Test & Measurement
Understanding Insulation Resistance Testing: Maintenance, Repair & Operations Test & Measurement
Insulation starts to age as soon as it's made. As it ages, its insulating performance deteriorates.
Any harsh installation environments, especially those with temperature extremes and/or chemical
contamination, accelerates this process. This deterioration can result in dangerous conditions in
power reliability and personnel safety. As such, it's important to identify this deterioration
quickly so that corrective steps can be taken. One of the simplest tests and its required test
instrument are not universally understood. To help eliminate this lack of understanding, let's
discuss in detail Insulation Resistance (IR) testing and the megohmmeter.
The megohmmeter
First, the megohmmeter's output is much higher than that of a multimeter. Voltages of 100, 250,
500, 1,000, 2500, 5,000, and even 10,000V are used (Table 1 below). The most common
voltages are 500V and 1,000V. Higher voltages are used to stress an insulation to a greater
degree and thus obtain more accurate results.
Second, the range of a megohmmeter is in megohms, as its name implies, instead of ohms as in a
multimeter.
Third, a megohmmeter has a relatively high internal resistance, making the instrument less
hazardous to use in spite of the higher voltages.
Testing connections
A megohmmeter usually is equipped with three terminals. The "LINE" (or "L") terminal is the
so-called "hot" terminal and is connected to the conductor whose insulation resistance you are
measuring. Remember: These tests are performed with the circuit deenergized.
The "EARTH" (or "E") terminal is connected to the other side of the insulation, the ground
conductor.
The "GUARD" (or "G") terminal provides a return circuit that bypasses the meter. For example,
if you are measuring a circuit having a current that you do not want to include, you connect that
part of the circuit to the "GUARD" terminal.
Figs. 2, 3, and 4 show connections for testing three common types of equipment. Fig. 2
shows a connection for testing a transformer bushing, without measuring the surface leakage.
Only the current through the insulation is measured, since any surface current will be returned on
the "GUARD" lead.
Basically, there are three different tests that can be done using a megohmmeter.
This is the simplest of the tests. After the required connections are made, you apply the test
voltage for a period of one min. (The one-min interval is an industry practice that allows
everyone to take the reading at the same time. In this way, comparison of readings will be of
value because, although taken by different people, the test methods are consistent.) During this
interval, the resistance should drop or remain relatively steady. Larger insulation systems will
show a steady decrease, while smaller systems will remain steady because the capacitive and
absorption currents drop to zero faster on smaller insulation systems. After one min, read and
record the resistance value.
Note that IR is temperature sensitive. When the temperature goes up, IR goes down, and vice
versa. Therefore, to compare new readings with previous readings, you need to correct the
readings to some base temperature. Usually, 20°C or 40°C are used as comparison temperatures;
tables are available for any correction. However, a common rule of thumb is that IR changes by a
factor of two for each 10°C change.
For example, suppose we obtained an IR reading of 100 megohms with an insulation temperature
of 30°C. The corrected IR (at 20°C) would be 100 megohms times 2, or 200 megohms.
Also note that acceptable values of IR will depend upon the equipment. Historically, field
personnel have used the questionable standard of one megohm per kV plus one. The
international Electrical Testing Assoc. (NETA) specification NETA MTS-1993, Maintenance
Testing Specifications for Electrical Power Distribution Equipment and Systems, provides much
more realistic and useful values.
Test results should be compared with previous readings and with readings taken for similar
equipment. Any values below the NETA standard minimums or sudden departures from previous
values should be investigated.
This test recognizes the fact that "good" insulation will show a gradually increasing IR after the
test voltage is applied. After the connections are made, the test voltage is applied, and the IR is
read at two different times: Usually either 30 and 60 sec, or 60 sec and 10 min. The later reading
is divided by the earlier reading, the result being the dielectric absorption ratio. The 10 min./60
sec. ratio is called the polarization index (PI).
For example, let's assume we apply the megohmmeter as described earlier with the appropriate
test voltage impressed. The one min. IR reading is 50 megohms, and the 10 min. IR reading is
125 megohms. Thus, the PI is 125 megohms divided by 50 megohms, or 2.5.
Various sources have tables of acceptable values of dielectric absorption ratios (see Table 2
below).
10/1-min Ratio
Insulation Condition 60/30-sec Ratio
(Polarization Index)
Dangerous - Less than 1
Questionable 1.0 to 1.25 1.0 to 2*
Good 1.4 to 1.6 2 to 4
Excellent Above 1.6** Above 4**
Table 2. Listing of conditions of insulation as indicated by Dielectric Absorption Ratios. These
values must be considered tentative and relative, subject to experience with the time-resistance
method over a period of time.
*These results would be satisfactory for equipment with very low capacitance, such as short runs
of house wiring.
**In some cases with motors, values approximately 20% higher than shown here indicate a dry,
brittle winding that may fail under shock conditions or during starts. For preventative
maintenance, the motor winding should be cleaned, treated, and dried to restore winding
flexibility.
This test is particularly useful in evaluating aged or damaged insulation not necessarily having
moisture or contamination. A dual voltage test instrument is required here. After the connections
are made, the IR test is done at a low voltage, say 500V. The test specimen then is discharged
and the test is done again, this time at a higher voltage, say 2500V. If more than a 25%
difference exists between the two IR readings, age deterioration or damaged insulation should be
suspected.
SIDEBAR: Basic Theory
An equivalent circuit for electrical insulation is shown in Fig. 5 (right). The top terminal
might be the center conductor of a power cable, and the bottom terminal, its shield. The current
flowing through the cable's insulation would be that current noted as "total current" in the
diagram. As you can see, the total current is equal to the sum of the "capacitive current" plus the
"absorption current" plus the "leakage current."
Note that the total current is not the load current flowing through the system. Rather, it's the
current that flows from the energized conductor through the insulation to ground.
Capacitive current. A capacitor is created when two conductors are separated by an insulator.
This is the situation in a power system.
If a DC voltage is suddenly applied (closing the switch in Fig. 5), electrons will rush into
the negative plate and be drawn from the positive plate. Initially, this current flow will be very
large, but it will gradually reduce to a much smaller value, eventually approaching zero. The
current labeled "capacitive charging current" in Fig. 6 (right) shows how this current varies with
time after DC voltage is applied.
Leakage current. No insulation is perfect; even new insulation will have some leakage current,
albeit small. This leakage current will increase as the insulation ages. It also will worsen when
the insulation is wet or contaminated.
Absorption current. The charges that form on the plates of the capacitor attract charges of the
opposite polarity in the insulation, causing these charges to move and, thus, drawing current. The
largest charge motion occurs in the initial moments and then gradually tapers off to near zero.
This current is called dielectric absorption, or just absorption current. A time plot of this current,
labeled "absorption current," also is shown in Fig. 6.
Total current. The total current flowing in the circuit is equal to the sum of the components
shown in Fig. 6. The total current flow, when a DC voltage is applied, starts at a relatively high
value and then drops, settling at a value just slightly above the leakage current. In bad or
deteriorated insulation, the total current will drop slowly, or may even increase.