Star Auto-Evaluation Report: Project: Location: Contract: Engineer: Filename: Date

This auto-evaluation report summarizes the protection and coordination analysis of an example project in Irvine, California. It finds that some zones have no protective devices, including Cable2, Line4, and the secondary side of Transformer T4. It also warns that the pickup value of the protective device on the primary side of Transformer T4 is below the transformer's full load amps. Overall, the protective devices on Bus1 are found to coordinate between 55 amps and 28,359 amps.

Uploaded by

Andres Vergara
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
75 views5 pages

Star Auto-Evaluation Report: Project: Location: Contract: Engineer: Filename: Date

This auto-evaluation report summarizes the protection and coordination analysis of an example project in Irvine, California. It finds that some zones have no protective devices, including Cable2, Line4, and the secondary side of Transformer T4. It also warns that the pickup value of the protective device on the primary side of Transformer T4 is below the transformer's full load amps. Overall, the protective devices on Bus1 are found to coordinate between 55 amps and 28,359 amps.

Uploaded by

Andres Vergara
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 5

Star Auto-Evaluation Report

Project: Example
Location: Irvine, California
Contract: OTI-12345678
Engineer: Operation Technology, Inc.
Filename: C:\ETAP 2100\Example-ANSI\Example-ANSI.oti
Date: 10/25/2021

Revision: Base
Configuration: Normal
Study Case: SM
Evaluation*: Protection& Coordination
Fault Type*: Phase& Ground
Rule: ETAP Default (ANSI/NEC)
Rule Reference: IEEE/ANSI and NEC Standards
Rule Description: Reference Standards:
NFPA 70 (NEC), IEEE Std 242, IEEE Std 446, IEEE Std C37.91, IEEE Std C37.96

* 1/2 cycle symmetrical short circuit current used for evaluation.

Evaluation Report: 552653677.xls Page 1 of 5


Classification Zone ID Zone Type Device ID Type Condition
Pass Bus1 Bus Bus1 Bus Passed phase protective device evaluation
The Bus Continuous Amps is zero or Bus Type is set to Other.
Warning Bus9 Bus
Continuous Amps
Selected zone is not
is part evaluated
of loop or connected to multiple sources of
- Cable12 Cable
supply and skipped in evaluation.
Alert Cable2 Cable No valid protective device found within the zone
Alert Line4 Line No valid protective device found within the zone
Sub 3 Bus Selected zone is part of loop or connected to multiple sources of
- Sub 3 Bus
supply and skipped in evaluation.
Alert No valid protective device found for some of Feeder(s)
Sub3 Swgr Bus
Warning No valid protective device found as Main(s)
Alert T4 Transformer Does not pass phase protective device evaluation

[General] Evaluation Report: 552653677.xls Page 2 of 5


Protective Device Bus Protection Max Fault Reference
Bus ID 3Ph-Amps
Location Device ID Type Cont. Amp Condition kV
Bus1 Main CB22 SST-LT Pass Bus is protected by Main 28359 0.48

[Bus Protection] Evaluation Report: 552653677.xls Page 3 of 5


Transformer Protective Device Transformer Protection Max Fault Reference
ID Device Pickup Damage 3Ph-Amps kV
Location Type FLA Inrush Condition
ID Limit Curve No valid protective device found on
Primary Alert Alert Alert Alert
source
LT Pickup 900 side min. limit of
A below
LT 1804
PickupA 900
= BaseFLA
A belowxthe 100%
FLA =
SST-LT Alert Warning - Pass
T4 1804 A the damage
Trip curve protects
Secondary CB22 28359 0.48
Not consideredcurve
for limit evaluation
SST-ST - - - Pass basedprotects
Trip curve on rule the
setting
damage
curve

[Transformer Protection] Evaluation Report: 552653677.xls Page 4 of 5


Zone Upstream Downstream Max Fault Reference Coordination Amp Range
Zone ID Condition
Type PD PD Type Amp kV Status From To Devices are coordinated
3Ph 28359 0.48 Pass 55 28359 between are
Devices ampcoordinated
range of 55
Bus1 Bus CB22 CB23 A to 28359A
L-G 29557 0.48 Pass 55 29557 between amp@ 0.48 of
range kV55
A to 29557A @ 0.48 kV

[Coordination] Evaluation Report: 552653677.xls Page 5 of 5