TrueAlarm Analog Sensing
UL, ULC, CSFM Listed; FM Approved; TrueAlarm Analog Sensors – Photoelectric
MEA (NYC) Acceptance* and Heat; Standard Bases and Accessories
Features
TrueAlarm analog sensing provides:
Digital transmission of analog sensor values via IDNet or
MAPNET II two-wire communications
For use with the following Simplex® products:
4007ES, 4010, 4010ES, 4100ES, and 4100U Series control
panels; and 4008 Series control panels with reduced feature
set (refer to data sheet S4008-0001 for details)
4020, 4100, and 4120 Series control panels, Universal
Transponders, and 2120 TrueAlarm CDTs equipped for 4098-9714 TrueAlarm Photoelectric
MAPNET II operation Sensor Mounted in Base
Fire alarm control panel provides:
Peak value logging allowing accurate analysis of each Description
sensor for individual sensitivity selection
Sensitivity monitoring satisfying NFPA 72 sensitivity Digital Communication of Analog Sensing. TrueAlarm
testing requirements; automatic individual sensor calibration analog sensors provide an analog measurement digitally
check verifies sensor integrity communicated to the host control panel using Simplex
addressable communications. At the control panel, the data is
Automatic environmental compensation, multi-stage alarm
analyzed and an average value is determined and stored. An
operation, and display of sensitivity directly in percent per alarm or other abnormal condition is determined by comparing
foot the sensor’s present value against its average value and time.
Ability to display and print detailed sensor information in
plain English language Intelligent Data Evaluation. Monitoring each sensor’s
average value provides a continuously shifting reference point.
Photoelectric smoke sensors provide: This software filtering process compensates for environmental
Seven levels of sensitivity from 0.2% to 3.7% factors (dust, dirt, etc.) and component aging, providing an
(refer to additional information on page 3) accurate reference for evaluating new activity. With this
Heat sensors provide: filtering, there is a significant reduction in the probability of
false or nuisance alarms caused by shifts in sensitivity, either up
Three fixed temperature sensing thresholds: 135° F, 155° F
or down.
and 190° F
Rate-of-rise temperature sensing Control Panel Selection. Peak activity per sensor is stored to
assist in evaluating specific locations. The alarm set point for
Utility temperature sensing
each TrueAlarm sensor is determined at the host control panel,
Listed to UL 521 and ULC-S530 selectable as more or less sensitive as the individual application
General features: requires.
Operation is for ceiling or wall mounting Timed/Multi-Stage Selection. Sensor alarm set points can be
Listed to UL 268 and ULC-S529 programmed for timed automatic sensitivity selection (such as
Louvered smoke sensor design enhances smoke capture by more sensitive at night, less sensitive during day). Control panel
directing flow to chamber; entrance areas are minimally programming can also provide multi-stage operation per sensor.
visible when ceiling mounted For example, a 0.2% level may cause a warning to prompt
investigation while a 2.5% level may initiate an alarm.
Designed for EMI compatibility
Magnetic test feature is provided Sensor Alarm and Trouble LED Indication. Each sensor
base’s LED pulses to indicate communications with the panel. If
Different bases are available to support a supervised or
the control panel determines a sensor is in alarm, or is dirty or
unsupervised output relay, and/or a remote LED alarm
has some other type of trouble, the details are annunciated at the
indicator control panel and that sensor base’s LED will be turned on
Additional base reference: steadily. During a system alarm, the control panel will control
For isolator bases, refer to data sheet S4098-0025 the LEDs such that an LED indicating a trouble will return to
For sounder bases, refer to data sheet S4098-0028 pulsing to help identify the alarmed sensors.
For photo/heat sensors, refer to data sheet S4098-0024
(single address) and S4098-0033 (dual address)
* These products have been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listings
7272-0026:218, 7271-0026:231, 7270-0026:216, and 7300-0026:217 for allowable values
and/or conditions concerning material presented in this document. Accepted for use – City of
New York Department of Buildings – MEA35-93E. Additional listings may be applicable,
contact your local Simplex product supplier for the latest status. Listings and approvals under
Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.
S4098-0019-23 8/2017
TrueAlarm Sensor Bases and Accessories Description
Sensor Base Features TrueAlarm sensor bases contain integral addressable
electronics that constantly monitor the status of the
Base mounted address selection:
detachable photoelectric or heat sensors. Each sensor’s
Address remains with its programmed location
output is digitized and transmitted to the system fire alarm
Accessible from front (DIP switch under sensor) control panel every four seconds.
General features:
Automatic identification provides default sensitivity when Since TrueAlarm sensors use the same base, different
substituting sensor types sensor types can be easily interchanged to meet specific
Integral red LED for power-on (pulsing), or alarm or trouble location requirements. This feature also allows intentional
(steady on) sensor substitution during building construction. When
Locking anti-tamper design mounts on standard outlet box conditions are temporarily dusty, instead of covering the
smoke sensors (causing them to be disabled), heat sensors
Magnetically operated functional test
may be installed without reprogramming the control
Sensor Bases panel. Although the control panel will indicate an
incorrect sensor type, the heat sensor will operate at a
4098-9792, Standard Sensor Base
default sensitivity providing heat detection for building
4098-9789, Sensor Base with wired connections for: protection at that location.
2098-9808 Remote LED alarm indicator or 4098-9822 relay
(relay is unsupervised and requires separate 24 VDC) Mounting Reference
Supervised Relay Bases (not compatible with 2120 CDT):
4098-9791, 4-Wire Sensor Base, use with remote or Electrical Box Requirements: (boxes are by others)
locally mounted 2098-9737 relay, requires separate 24 VDC Without relay in the box: 4" octagonal or 4" square, 1-1/2" deep;
4098-9780, 2-Wire Sensor Base, use with remote or single gang, 2" deep
locally mounted 4098-9860 relay, no separate power With relay in the box : 4" octagonal or 4" square, 1-1/2" deep,
required with 1-1/2" extension ring
Supervised relay operation is programmable and can be 4" (102 mm) Square Box 4" (102 mm) Octagonal Box
manually operated from control panel
Surface mount reference
Includes wired connections for remote LED alarm indicator
or 4098-9822 relay (relay is unsupervised and requires
separate 24 VDC)
Sensor Base Options
1-1/2" (38 mm)
2098-9737, Remote or local mount supervised relay: minimum box depth Flush mount reference, mount even with final
surface, or with up to 1/4" (6.4 mm) maximum recess
DPDT contacts for resistive/suppressed loads, power limited
rating of 3 A @ 28 VDC; non-power limited rating of 3 A
2098-9737 Supervised Relay 4098-9822 Relay (mounts
@ 120 VAC (requires external 24 VDC coil power) (mounts in base electrical box or in base electrical box)
4098-9860, Remote or local mount supervised relay: remotely)
SPDT dry contacts, power limited rating of 2 A @ 30 VDC,
resistive; non-power limited rating of 0.5 A @ 125 VAC,
resistive Relay Size: 2-1/2" X 1-1/2" X 1"
(3.75 in3 ) (64 mm X 38 mm X 25.4 mm)
4098-9822, LED Annunciation Relay:
Activates when base LED is on steady, indicating local
alarm or trouble 4098-9860 Supervised Relay (mounts in base
electrical box or remotely; 2-3/8" X 1-1/4" X 11/32"
DPDT contacts for resistive/suppressed loads, power limited (1 in3 ) (60.4 mm X 31.8 mm X 8.6 mm)
rating of 2 A @ 28 VDC; non-power limited rating of
1/2 A @ 120 VAC, (requires external 24 VDC coil power) NOTE: Review total wire count, wire size, and accessories being
4098-9832, Adapter plate: wired to determine required box volume.
Required for surface or semi-flush mounting to 4” square
6-3/8" (162 mm)
electrical box and for surface mounting to 4” octagonal box
Can be used for cosmetic retrofitting to existing 6-3/8”
4098-9832 Adapter Plate, required for
diameter base product 1/4" mounting to surface mounted boxes
2098-9808, Remote red LED Alarm (6.4 mm) and 4" square flush box
Indicator: 4-7/8" (124 mm)
Mounts on single gang box (shown in
15/16"
illustration to right) ALARM
(24 mm)
TrueAlarm Bases
4098-9780, 4098-9789, 4098-9791, & 4098-9792
2 S4098-0019-23 8/2017
TrueAlarm Sensors
Features Rate-of-rise temperature detection is selectable at the
control panel for either 15° F (8.3° C) or 20° F (11.1° C)
Sealed against rear air flow entry per minute. Fixed temperature sensing is independent of
Interchangeable mounting rate-of-rise sensing and programmable to operate at
EMI/RFI shielded electronics 135° F (57.2° C) or 155° F (68° C). The 4098-9734
Heat sensors: sensor provides an additional 190° F (88° C) set point.
Selectable rate compensated, fixed temperature In a slow developing fire, the temperature may not
sensing with or without rate-of-rise operation increase rapidly enough to operate the rate-of-rise feature.
Rated spacing distance between sensors: However, an alarm will be initiated when the temperature
reaches its rated fixed temperature setting.
Fixed Temp. UL & ULC FM Spacing, Either Fixed
Setting Spacing Temperature Setting TrueAlarm heat sensors can be programmed as a utility
135° F / 190° F* 60 ft x 60 ft 20 ft x 20 ft (6.1 m) for fixed device to monitor for temperature extremes in the range
(57.2° C / 88° C) (18.3 m) temperature only; RTI = Quick
from 32° F to 155° F (0° C to 68° C). This feature can
50 ft x 50 ft (15.2 m) for fixed
temperature with either
provide freeze warnings or alert to HVAC system
155° F 40 ft x 40 ft
(68° C) (12.2 m) rate-of-rise selection; RTI = Ultra problems. Refer to specific panels for availability.
Fast
*Note: 190° F (88° C) ratings apply only to the 4098-9734 sensor.
4-7/8" (124 mm)
Smoke Sensors: LED status indicator
Photoelectric technology sensing 2-3/8"
360° smoke entry for optimum response (60 mm)
Built-in insect screens
4098-9714 Photoelectric Sensor
TrueAlarm photoelectric sensors use a stable, pulsed
infrared LED light source and a silicon photodiode 4098-9733 Heat Sensor with Base
receiver to provide consistent and accurate low power
smoke sensing. Seven levels of sensitivity are available
for each individual sensor, ranging from 0.2% to 3.7% per
foot of smoke obscuration. Sensitivities of 0.2%, 0.5%,
and 1% are for special applications in clean areas.
Standard sensitivities are 1.5%, 2.0%, 2.5%, 3.0%, and
3.7%. Application type and sensitivity are selected and
then monitored at the fire alarm control panel.*
The sensor head design provides 360° smoke entry for
optimum response to smoke from any direction. Due to its
photoelectric operation, air velocity is not normally a 4098-9734 High Temperature Heat Sensor with Base
factor, except for impact on area smoke flow.
WARNING: In most fires, hazardous levels of smoke
and toxic gas can build up before a heat detection
4-7/8" (124 mm) device would initiate an alarm. In cases where Life
Safety is a factor, the use of smoke detection is highly
LED status indicator recommended.
2-1/8"
(54 mm) Application Reference
Sensor locations should be determined only after careful
consideration of the physical layout and contents of the
area to be protected. Refer to NFPA 72, the National Fire
4098-9714 Photoelectric Sensor with Base Alarm and Signaling Code. On smooth ceilings, smoke
sensor spacing of 30 ft (9.1 m) may be used as a guide.*
4098-9733 and 4098-9734 Heat Sensors * For detailed application information including sensitivity
selection, refer to Installation Instructions 574-709.
TrueAlarm heat sensors are self-restoring and provide rate
compensated, fixed temperature sensing, selectable with
or without rate-of-rise temperature sensing. Due to its
small thermal mass, the sensor accurately and quickly
measures the local temperature for analysis at the fire
alarm control panel.
3 S4098-0019-23 8/2017
TrueAlarm Analog Sensing Product Selection Chart
TrueAlarm Sensor Bases (for use with Sensors 4098-9714 and 4098-9733)
(Refer to Application Manual 574-709 and Installation Instructions 574-707 for additional information)
Model* Color Description Compatibility Mounting Requirements
4098-9792 White 4” octagonal or 4” square box, 1-1/2”
Standard Sensor Base No options min. depth; or single gang box, 2”
4098-9776 Black
min. depth
4098-9789 White
Sensor Base with connections for
4098-9789 IND 2098-9808 Remote Alarm Indicator or 4” octagonal or 4” square box
White Remote LED Alarm Indicator or
4098-9822 Unsupervised Relay Note: Box depth requirements
4098-9775 Unsupervised Relay
Black depend on total wire count and
4-Wire Sensor Supervised Relay 2098-9737 Supervised Remote Relay wire size, refer to accessories
4098-9791** White Base with connections for LED 2098-9808 Remote Alarm Indicator or list below for reference.
Indicator or Unsupervised Relay 4098-9822 Unsupervised Relay ** NOTE: 4098-9791 and 4098-
9780 are NOT compatible
2-Wire Sensor Supervised Relay 4098-9860 Supervised Remote Relay with the 2120 CDT
4098-9780** White Base with connections for LED 2098-9808 Remote Alarm Indicator or
Indicator or Unsupervised Relay 4098-9822 Unsupervised Relay
TrueAlarm Sensors
Model* Model* Description Compatibility Mounting Requirements
4098-9714
White
4098-9714 IND Photoelectric Smoke Sensor
Bases 4098-9775, 4098-9776, 4098-9792,
4098-9774 Black Refer to base requirements
4098-9789, 4098-9791, and 4098-9780
4098-9733 White Heat Sensor
4098-9734 White High Temperature Heat Sensor
TrueAlarm Sensor/Base Accessories
Model Description Compatibility Mounting Requirements
Supervised Relay, mounts remote or in base Remote Mounting requires 4” octagonal or
2098-9737 For use with 4098-9791 base
electrical box 4” square box, 1-1/2” minimum depth
Supervised Relay, mounts remote or in base Base Mounting requires 4” octagonal box, 2-
4098-9860 For use with 4098-9780 base
electrical box 1/8” deep with 1-1/2” extension ring
Remote Red LED Alarm Indicator on single gang Bases 4098-9789, 4098-9791, and 4098-
2098-9808 Single gang box, 1-1/2” minimum depth
stainless steel plate 9780
Unsupervised Relay, tracks base LED status; Bases 4098-9789, 4098-9791, and 4098- 4” octagonal box, 2-1/8” deep with 1-1/2”
4098-9822
Note: Mounts only in base electrical box 9780 extension ring
Required for surface or semi-flush mounted 4”
Bases 4098-9792, 4098-9789,
4098-9832 Adapter Plate square box and for surface mounted
4098-9791, and 4098-9780
4” octagonal box
* Note: Model numbers ending in IND are assembled in India.
Specifications
General Operating Specifications
Communications and Sensor Supervisory Power IDNet or MAPNET II communications, auto-selected, 1 address per base
Communications Connections Screw terminals for in/out wiring, 18 to 14 AWG (0.82 mm2 to 2.08 mm2)
Remote LED Alarm Indicator Current 1 mA typical, no impact to alarm current
Remote LED Alarm Indicator and Relay Connections Color coded wire leads, 18 AWG (0.82 mm2 )
UL Listed Operating Temperature Range 32° to 100° F (0° to 38° C)
with 4098-9733 Heat Sensor 32° to 122° F (0° to 50° C)
Operating Temperature
with 4098-9714 Smoke Sensor 15° to 122° F (-9° to 50° C)
Range
With 4098-9734 Heat Sensor 32° to 150° F (0° to 66° C)
Storage Temperature Range 0° F to 140° F (-18° C to 60° C)
Humidity Range 10 to 95% RH
4098-9714 Smoke Sensor Air Velocity Rating 0-4000 ft/min (0-1220 m/min)
Housing Color Frost White or Black
4098-9791 Base With Supervised Remote Relay 2098-9737 (see page 2 for contact ratings)
Externally Supplied Relay Coil Voltage 18-32 VDC (nominal 24 VDC)
Supervisory Current 270 A, from 24 VDC supply
Alarm Current with 2098-9737 Relay 28 mA, from 24 VDC supply
4098-9780 Base With Supervised Remote Relay 4098-9860 (see page 2 for contact ratings)
Power Supplied from communications
4098-9822 Unsupervised Relay, Requirements for Bases 4098-9789. 4098-9791, and 4098-9780 (see page 2 for contact ratings)
Externally Supplied Relay Coil Voltage 18-32 VDC (nominal 24 VDC)
Supervisory Current Supplied from communications
Alarm Current 13 mA from separate 24 VDC supply