0% found this document useful (0 votes)
375 views6 pages

HV Surge Counter Tester Guide

The document introduces the HZJS-3KV HV Surge Counter Tester. It discusses how lightning arresters are important for protecting power equipment and how surge counters are used to monitor arresters. It then provides details on the operating principles, technical parameters, and inspection methods of the HV Surge Counter Tester to check that surge counters are operating reliably.

Uploaded by

rio
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
375 views6 pages

HV Surge Counter Tester Guide

The document introduces the HZJS-3KV HV Surge Counter Tester. It discusses how lightning arresters are important for protecting power equipment and how surge counters are used to monitor arresters. It then provides details on the operating principles, technical parameters, and inspection methods of the HV Surge Counter Tester to check that surge counters are operating reliably.

Uploaded by

rio
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

HZJS-3KV

HV Surge Counter Tester

Huazheng Electric Manufacturing (Baoding) Co., Ltd


Dear user:

Thank you for choosing HZJS- 3 KV HV Surge Counter Tester.

We hope that this instrument can make your work easier and more

enjoyable, so that you can get the feeling of office automation in the test and

analysis work.

Before using the instrument, please read this manual, and operate and

maintain the instrument according to the manual to prolong its service li fe.

"Just a light press, the test will be completed automatically" is the operating

characteristics of this instrument.

If you are satisfied with this instrument, please tell your colleagues;

if you are not satisfied with this instrument, please call (0312 ) 6775656 to

tell you to serve you at all times- Baoding Huazheng Electric Manufacturing

Co., Ltd., our company will definitely make you satisfied !


Contents

I. Overview ........................................................................................................................................ 1

II. Principle ........................................................................................................................................ 1

III. Technical Parameter ................................................................................................................. 2

IV.Inspection Methods And Principles......................................................................................... 2


I. Overview
Lightning arrester is an important electrical equipment in power network to protect

power equipment from over-voltage. Normally, the action of the arrester and leakage

current are monitored through the arrester monitor. Due to poor sealing, the monitor may

enter water or moisture during operation, causing internal element corrosion, or other

reasons, the monitor counter cannot operate normally, and the leakage current indication

is not accurate. Therefore, according to 《The Regulations》, the arrester monitor should

be checked once a year。

The reliability of counter operation is very important for power system. It is an important

parameter to record the number of lightning strikes received by the arrester in normal

operation. It can provide an important basis for the power system workers to inspect the

arresters.

II. Principle
Figure 1 shows the principle wiring diagram of HZJS action counter. Figure 1 (a) is

the basic structure of HZJS-type action register, namely the dual-disc structure.

Figure 1. Schematic wiring of hzjs-type action register

(a)HZJS Type; (b)HZJS-3KV Type

R1、R2-Non-linear resistance;C-Energy storage capacitor

L-Register coil; D1~4Silicon diode

When the arrester operates, the discharge current flows through the valve sheet R1,

the voltage drop on the valve sheet R2 charges the capacitor C, and then C discharges

1
the inductance coil L of the electromagnetic counter, making it rotate one grid and record

one time. Changing the resistance of R1 and R2 can make the recorder have different

sensitivity. The general minimum action current is 100A (8/20 s) impulse current. Because

there is a certain pressure drop on R1, it will increase the residual voltage of arrester, so it

is mainly used for high voltage arrester over 40 kV.

Fig. 1 (b) represents the structure of the type of motion recorder, which is a rectifying

structure. When the arrester operates, the voltage drop on the high temperature valve

sheet R1 is charged to capacitor C by full wave rectification, and then C discharges L of

the electromagnetic counter to make it count. The resistance value of the valve piece R1

of the counter is small (the pressure drop at 10 kA is 1.1 kV), the flow capacity is large

(1200 A square wave), and the minimum operating current is 100 A (8/20s) impulse

current.

III. Technical Parameter


1、Output voltage:DC3000V ±5%

2、Interval time:≥30s

3、Power supply:AC200V±10% 50Hz±2%

4、Shock current:≥100A(8/20μs)

5、Dimension:380×250×180mm

6、Weight:3kg

IV. Inspection Methods And Principles


Due to poor sealing, the action counter may enter moisture or moisture in operation,

which causes the internal components to rust, leading to the normal operation of the

counter. Therefore, the "Regulations" stipulate that the meter should be checked once a

year. There are direct current method, alternating current method and standard impulse

current method. The research shows that the standard impulse current method is the most

reliable and its principle wiring is shown in Figure 2.

2
Fig. 2 principle wiring of standard impulse current detection method

(The part of the dotted box is an impulse current generator)

C-Charge capacitance;R-Charging resistance;L-Damped inductor

D-Silicon diode rectifier;r-Shunt;B-Testing transformer

V-Electrostatic voltmeter;CRO-High voltage oscilloscope

If the impulse current wave of 8/20s and 100A produced by the impulse current

generator acts on the action recorder, if the action of the recorder is normal, the

instrument is good, otherwise it should be dismantled and repaired. For example, a power

bureau has used this method to detect 27 counting devices, of which 3 are not moving,

and the internal components are found damped and damaged after disintegration.

The Regulations stipulate that continuous testing should be carried out 3 to 5 times,

each time should be normal, and each time interval should be no less than 30 seconds.

After testing, the recorder should be adjusted to 0.