HZJS-3KV
HV Surge Counter Tester
Huazheng Electric Manufacturing (Baoding) Co., Ltd
Dear user:
Thank you for choosing HZJS- 3 KV HV Surge Counter Tester.
We hope that this instrument can make your work easier and more
enjoyable, so that you can get the feeling of office automation in the test and
analysis work.
Before using the instrument, please read this manual, and operate and
maintain the instrument according to the manual to prolong its service li fe.
"Just a light press, the test will be completed automatically" is the operating
characteristics of this instrument.
If you are satisfied with this instrument, please tell your colleagues;
if you are not satisfied with this instrument, please call (0312 ) 6775656 to
tell you to serve you at all times- Baoding Huazheng Electric Manufacturing
Co., Ltd., our company will definitely make you satisfied !
Contents
I. Overview ........................................................................................................................................ 1
II. Principle ........................................................................................................................................ 1
III. Technical Parameter ................................................................................................................. 2
IV.Inspection Methods And Principles......................................................................................... 2
I. Overview
Lightning arrester is an important electrical equipment in power network to protect
power equipment from over-voltage. Normally, the action of the arrester and leakage
current are monitored through the arrester monitor. Due to poor sealing, the monitor may
enter water or moisture during operation, causing internal element corrosion, or other
reasons, the monitor counter cannot operate normally, and the leakage current indication
is not accurate. Therefore, according to 《The Regulations》, the arrester monitor should
be checked once a year。
The reliability of counter operation is very important for power system. It is an important
parameter to record the number of lightning strikes received by the arrester in normal
operation. It can provide an important basis for the power system workers to inspect the
arresters.
II. Principle
Figure 1 shows the principle wiring diagram of HZJS action counter. Figure 1 (a) is
the basic structure of HZJS-type action register, namely the dual-disc structure.
Figure 1. Schematic wiring of hzjs-type action register
(a)HZJS Type; (b)HZJS-3KV Type
R1、R2-Non-linear resistance;C-Energy storage capacitor
L-Register coil; D1~4Silicon diode
When the arrester operates, the discharge current flows through the valve sheet R1,
the voltage drop on the valve sheet R2 charges the capacitor C, and then C discharges
1
the inductance coil L of the electromagnetic counter, making it rotate one grid and record
one time. Changing the resistance of R1 and R2 can make the recorder have different
sensitivity. The general minimum action current is 100A (8/20 s) impulse current. Because
there is a certain pressure drop on R1, it will increase the residual voltage of arrester, so it
is mainly used for high voltage arrester over 40 kV.
Fig. 1 (b) represents the structure of the type of motion recorder, which is a rectifying
structure. When the arrester operates, the voltage drop on the high temperature valve
sheet R1 is charged to capacitor C by full wave rectification, and then C discharges L of
the electromagnetic counter to make it count. The resistance value of the valve piece R1
of the counter is small (the pressure drop at 10 kA is 1.1 kV), the flow capacity is large
(1200 A square wave), and the minimum operating current is 100 A (8/20s) impulse
current.
III. Technical Parameter
1、Output voltage:DC3000V ±5%
2、Interval time:≥30s
3、Power supply:AC200V±10% 50Hz±2%
4、Shock current:≥100A(8/20μs)
5、Dimension:380×250×180mm
6、Weight:3kg
IV. Inspection Methods And Principles
Due to poor sealing, the action counter may enter moisture or moisture in operation,
which causes the internal components to rust, leading to the normal operation of the
counter. Therefore, the "Regulations" stipulate that the meter should be checked once a
year. There are direct current method, alternating current method and standard impulse
current method. The research shows that the standard impulse current method is the most
reliable and its principle wiring is shown in Figure 2.
2
Fig. 2 principle wiring of standard impulse current detection method
(The part of the dotted box is an impulse current generator)
C-Charge capacitance;R-Charging resistance;L-Damped inductor
D-Silicon diode rectifier;r-Shunt;B-Testing transformer
V-Electrostatic voltmeter;CRO-High voltage oscilloscope
If the impulse current wave of 8/20s and 100A produced by the impulse current
generator acts on the action recorder, if the action of the recorder is normal, the
instrument is good, otherwise it should be dismantled and repaired. For example, a power
bureau has used this method to detect 27 counting devices, of which 3 are not moving,
and the internal components are found damped and damaged after disintegration.
The Regulations stipulate that continuous testing should be carried out 3 to 5 times,
each time should be normal, and each time interval should be no less than 30 seconds.
After testing, the recorder should be adjusted to 0.