Underground
double-skinned tanks
Outer surface: Technical data:
Abrasive grit-blasted to grade Sa 2,5 according • Design norms: EN 12285-1 class A or class B, DIN 6608
to PN-ISO 8501-1 and external anticorrosion • Technical documentation approved by Notified body
Polyurethane coating puncture tested at 10 kV/14 kV
• Material – S235JR according to EN10025-1 or stainless steel
Optional equipment: • Single or multi-chamber tank
• Street covers in class C 250 kN and D 400 KN • Working pressure: max 0,5 bar
• Steel sumps • Working temperature: from -20°C to + 50°C
• Central filling points – Aluminium and Stainless steel Purpose:
• Galvanized anchoring bands Storage of flammable and non-flammable, liquids harmful to the
• Leak detection systems GOK, Afriso, SGB environment with a density up to 1,1 kg/dm3 for EN 12285 class A
• Monitoring systems OPW and others and to 1,9 kg/dm3 for tanks EN 12285 class B and DIN 6608.
Tightness:
Pressure test of both inner tank and interspace according
to the norm:
EN 12285-1 class A 0,3 bar/0,4 bar
EN 12285-1 class B 2,0 bar/0,6 bar
DIN 6608 – 2,0 bar/0,6 bar
Tank on Speed Chassis
CGH Polska Sp. z o.o.
85-461 Bydgoszcz, ul. Srebrna 39, e-mail:
[email protected] • tel. +48 52 370-66-54 www.cgh.com.pl
Underground double-skinned steel tanks meet the norms for
storage of inflammable and hazardous liquids. For years they
have met all the requirements established by European countries
regarding environmentally harmful liquid storage. Two solid and
at the same time flexible steel jackets, insulated with
a probe
a Polyurethane layer on the outside, along with interstitial adaptor
space monitoring, constitute safe and ecological solution for DN 80 camlock DN 50
fuel storage. Our industrial series production is constantly
supervised by a Technical Inspection Office, which guarantees
that each tank manufactured fulfills all technical requirements extensions
of gauge
and high quality.
connections
anchoring
system
Underground storage means safety
and space saving.
overfill prevention valve
One of the greatest advantage of underground storage is
the possibility of using a high capacity tank, up to 120 000 inner skin - steel
litres. interstitial space
outer skin - steel
anti-corrosive layer
Standard tank equipment:
Depending on the client’s requirements, a tank is equipped with:
• manual gauge connection
• a filling pipe with an overfill prevention valve
• automatic gauge connection (for a measuring probe)
• suction pipes
• vent connection
• drain pipe for pumping out the water from the bottom
of the tank • spare connection
• gauge pipe for measuring the level with a dipstick • VRS connection
Underground double-skinned tanks
for storage of inflammable and hazardous liquids
V V V
"A" "B" "C"
Basic technical data
Weight of Wall thickness
additional Length Height
chamber Inside
Volume Diameter Length Weight* of the dished Manhole Handle
class A class B ring
class class cylinder -ends
A B
V Dz Lo Lp Lp h DN S1 S2 S1 S2 T 80
[m ]
3
[mm] [mm]1 [kg] [kg] [kg] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [pcs] [pcs]
3 1600 2250 1050 351 351 1500 270 1 –
5 1600 3250 1350 351 351 2500 270 1 –
8 1600 4750 1800 351 351 4000 270 600 5 3 5 3 1 –
10 1600 5750 2150 351 351 5000 270 2 –
13 1600 7250 2600 351 351 6500 270 2 –
16 1600 8750 3050 351 351 8000 270 2 –
10 2000 3900 2150 522 522 3000 330 –
13 2000 4900 2600 522 522 4000 330 –
16 2000 5900 3050 522 522 5000 330 –
20 2000 6900 3450 522 522 6000 330 600 6 3 6 3 2 –
25 2000 8900 4350 522 522 8000 330 1
30 2000 10400 5050 522 522 9500 330 1
35 2000 11900 5700 522 522 11000 330 1
20 2500 5050 3950 730 818 4000 400 –
25 2500 6050 4600 730 818 5000 400 –
30 2500 7050 5250 730 818 6000 400 –
40 2500 9050 6650 730 818 8000 400 600 6 4/5 7 4/5 2 1
50 2500 11050 7950 730 818 10000 400 1
60 2500 13050 9350 730 818 12000 400 2
70 2500 15050 10650 730 818 14000 400 2
40 2900 7150 6850 1045 1279 6000 450 2 –
50 2900 8650 8150 1045 1279 7500 450 2 1
60 2900 10150 9400 1045 1279 9000 450 2 2
70 2900 11650 10650 1045 1279 10500 450 600 7 4/5 9 4/5 4 2
80 2900 13150 12000 1045 1279 12000 450 4 2
100 2900 16150 14500 1045 1279 15000 450 4 2
120 3000 17900 16900 1200 1470 17000 450 4 3
* Approximate weight of a tank with one compartment
Tank equipment
ensuring proper functioning of a petrol station
Water tight heavy-duty Heavy-duty sump QNA4
Sump QTA1 (for lawn areas) 1200 x 1200 mm
cover with a concrete frame (for concrete covers) 1200 x 1200 mm
Steel sump 1200 x 1200 with aluminium cover Steel sump 1200 x 1200 mm with galwanized Steel sump 1200 x 2200 mm with galwanized
860 x 860 mm cover 1080 x 1080 mm covers 1080 x 1080 mm
wema grid
optional
Central filling point Light cover located at the dispencers island Anchoring band
Monitoring system - PetroVend (OPW) Monitoring system GOK/Afriso Monitoring system SGB
DO
D Z
Ñ
OR
U RZ
U
TE
C
G
HN E
ICZN
CGH Polska Sp. z o.o.
85-461 Bydgoszcz, ul. Srebrna 39, e-mail:
[email protected] • tel. +48 52 370-66-54 www.cgh.com.pl