Lec-7 Bus Switching Schemes Double Main & Transfer (DMT) One and Half CB Schemes in English
Lec-7 Bus Switching Schemes Double Main & Transfer (DMT) One and Half CB Schemes in English
This is an example of Single Bus Single CB scheme. The major disadvantage of this
scheme is if fault occurred then it will lose power supply to all feeder.
As this scheme has no isolator between CB & Busbar, the major disadvantage is
that it is not possible to do Maintenance work in the CB without shutting down
the Busbar.
To overcome this issue one isolator is used to isolate CB in case of Maintenance.
This Isolator is used in all scheme like: Single, Single with sectionalizer, Double
Main, Double Main with sectionalizer, Ring, One & Half, One & Half with
sectionalizer, One & Half with series reactance. In all the busbar scheme isolator
provided at both side of the circuit breaker.
This isolator is a no load switch.
During the transfer bus operation the Line Isolator of feeder 89L will be remained in opened
condition.
However, during the whole operation the CVT & CT output will feed to protection relay.
In DMT scheme normally STUB protection is not required.
One & Half Breaker Scheme:
Two element will share 3 Circuit Breaker.
In one & half scheme the CVT is installed after 89L. And in case of 89L opened condition CVT
voltage will not feed to Distance Protection and in that case relay will not operate correctly. In
that condition some protection functions need to be disabled like STUB.