The Design Is Adequate.: W F F X X X y X

This document provides a seismic design summary for an intermediate moment resisting steel frame based on codes IBC 06, AISC 341-05, and AISC 358-05. Key elements of the design include W8x48 columns, W14x48 beams, and a required 1-5/8 inch thick doubler plate due to insufficient panel zone thickness. All analyzed aspects of the design such as member properties, connection requirements, and code checks are satisfactory according to the referenced codes and standards.

Uploaded by

xuankhoi doanvan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
374 views3 pages

The Design Is Adequate.: W F F X X X y X

This document provides a seismic design summary for an intermediate moment resisting steel frame based on codes IBC 06, AISC 341-05, and AISC 358-05. Key elements of the design include W8x48 columns, W14x48 beams, and a required 1-5/8 inch thick doubler plate due to insufficient panel zone thickness. All analyzed aspects of the design such as member properties, connection requirements, and code checks are satisfactory according to the referenced codes and standards.

Uploaded by

xuankhoi doanvan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd

PROJECT : PAGE :

CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Seismic Design for Intermediate/Ordinary Moment Resisting Frames Based on IBC 06, AISC 341-05 & AISC 358-05

INPUT DATA & DESIGN SUMMARY


COLUMN SECTION => W8X48
A d tw bf tf Sx Ix rx ry Zx k
14.1 8.5 0.40 8.11 0.69 43.2 184 3.61 2.08 49 1.08
BEAM SECTION => W14X48
A d tw bf tf Sx Ix rx ry Zx k
14.1 13.8 0.34 8.03 0.60 70.2 484 5.86 1.91 78 1.19

STRUCTURAL STEEL YIELD STRESS Fy = 50 ksi


THE FACTOR AXIAL LOAD ON THE COLUMN Pu = 27 kips
BEAM LENGTH BETWEEN COL. CENTERS L= 33 ft
AVERAGE STORY HEIGHT OF ABOVE & BELOW h= 9 ft

THE DESIGN IS ADEQUATE.


(Continuity column stiffeners 0.75 x 4
with 1/4" fillet weld to web & CP to flanges.
A doubler plate is required with thickness of 1-5/8 in. )

ANALYSIS
THE SEISMIC DESIGN FACTOR COMPARISON (ASCE 7-05, Table 12.2-1)
FRAME TYPE R Wo Cd
SMRF 8 3 5 1/2
IMRF 4.5 3 4
OMRF 3.5 3 3

CHECK BEAM LOCAL BUCKLING LIMITATION (AISC 341-05 Tab. I-8-1)


bf / (2tf ) = 6.75 < 0.3 (Es / Fy)0.5 = 7.22 [Satisfactory]
[ 52 / (Fy)0.5 for AISC Seismic 97, Tab. I-9-1]

Where Es = 29000 ksi


h / tw = 33.59 < 2.45 (Es / Fy)0.5 = 59.00 [Satisfactory]
[ 418 / (Fy)0.5 for FEMA Sec. 3.3.1.2]
CHECK COLUMN LOCAL BUCKING LIMITATION (AISC 341-05 Tab. I-8-1)
bf / (2tf ) = 5.92 < 0.3 (Es / Fy)0.5 = 7.22 [Satisfactory]
[ 52 / (Fy)0.5 for AISC Seismic 97, Tab. I-9-1]
3.14(Es/Fy)0.5(1-1.54Pu/fbPy) = 70.67 , for Pu/fbPy < 0.125
h / tw = 15.85 < [ 520 / (Fy)0.5(1-1.54Pu/fbPy) for AISC Seismic 97, Tab. I-9-1]
(Es/Fy)0.5 MAX[1.49, 1.12(2.33 - Ca)] = N/A , for Pu/fbPy > 0.125
{ MAX[ 191 / (Fy)0.5(2.33-Pu/fbPy) , 253 / (Fy)0.5] for AISC Seismic 97, Tab. I-9-1}

[Satisfactory] Where fb = 0.9 , Py = FyA = 705 kips

CHECK CONTINUITY PLATE REQUIREMENT (AISC 358-05 Sec. 2.4.4)


tcf = MIN{ bbf / 6 , 0.4[1.8bbf tbf (FybRyb) / (FybRyb)] 0.5 }= 1.17 in > actual tcf
(The continuity plates required.)
tst = tbf for interior connection, or (tbf /2) for exterior connection = 0.60 in,USE 0.75 in
bst = 4 in < 1.79 (Es / Fyst )0.5 tst = 38.10 in, (LRFD Sec. K1.9)
[Satisfactory]
fcPn,st = fcFcr A = 288.0 kips
Where fc = 0.9 hst = dc - 2k = 6.34
K = 0.75 K hst / rst < 200 (AISC 360, E2) [Satisfactory]
I = tst (2bst + twc) 3 / 12 = 36 in 4 lc = 0.026
A = 2bsttst + 25(twc) 2 = 9 in2 Fcr = 35.99 ksi
rst = ( I / A )0.5 = 2.02 in Fyst = 36 kips, plate yield stress
Pu,st = Ryb Fyb bfb tfb = 262.8 kips < fcPn,st [Satisfactory]

The best fillet weld size (AISC 360-05 Sec.J2.2b)


> wMIN = 0.1875 in
w= 1/4 in
< wMAX = 0.3125 in
[Satisfactory]
The required weld length between A36 continuity plates and column web (AISC 360-05 Sec.J2.2b)
Lw = 0.6tstLnstFy / [(2) f Fw (0.707 w)] = (0.75 x 3.3) x 36 / [(2) 0.75 (0.6x70)(0.707x1/4)] = 3.44 in
Where Lnet = dc - 2(k + 1.5) = 3.3 < 2(Lnet -0.5) [Satisfactory]
(Use complete joint penetration groove welds between continuity plates & column flanges.)
(cont'd)

CHECK PANEL ZONE THICKNESS REQUIREMENT (AISC 341-05 Sec. 10.2d)


tReqD = MAX (t1, t2) = 2.02 in
t1 = Cy Mpr (h - db ) / [0.9 (0.6) Fyc Ryc dc (db - tfb) h] = 2.02 in
Where Cy = Sb / (Cpr Zb) = 0.78
Cpr = 1.15 (AISC 341-05 Sec. 9.6 & AISC 358-05 Sec. 2.4.3)
Ry = 1.1 (AISC 341-05 Tab. I-6-1)
Sb = 2Ib / db = 70 in2
Ib = Ix = 484 in4

Mpr = Nb CprRyFyb Zb = 826 ft-kips


Nb = 2 , (if double side connection of beams, input 2)
t2 = (dz + wz ) / 90 = (db -2tst + dc - 2k) / 90 = 0.21 in

Since twc = 0.40 in < tReqD , a doubler plate is


required with thickness of 1-5/8 in.

Technical References:
1. AISC 341-05: "Seismic Provisions for Structural Steel Buildings", American Institute of Steel Construction, Nov. 16, 2005.
2. AISC 360-05: "Specification for Structural Steel Buildings", American Institute of Steel Construction, March 9, 2005.
3. AISC 358-05: "Prequalified Connections for Special and Intermediate Steel Moment Frames for Seismic Applications",
American Institute of Steel Construction, Dec 13, 2005.
4. Thomas A. Sabol, Ph.D., S. E.: "2005 AISC Seismic Provisions and Seismic Design Manual Seminar", AISC, Oct. 12, 2006.