Altivar 58F Telemecanique: Variateurs de Vitesse CVF Pour Moteurs Asynchrones
Altivar 58F Telemecanique: Variateurs de Vitesse CVF Pour Moteurs Asynchrones
Guide de programmation
Telemecanique
Programming Manual Variateurs de vitesse CVF pour
Programmieranleitung
Guía de programación moteurs asynchrones,
Variable speed controllers FVC
for asynchronous motors,
FVC Frequenzumrichter
für Drehstrom-Asynchronmotoren,
Variadores de velocidad CVF
para motores asíncronos
Altivar 58F
FRANÇAIS
ENGLISH
Variable speed controllers FVC for asynchronous motors Page 72
DEUTSCH
ESPAÑOL
2
Warning
This document relates to use of the Altivar 58F
ENGLISH
exclusively with:
72
Contents
Introduction _____________________________________________________________________ 74
Access to menus_________________________________________________________________ 81
Macro-Configurations _____________________________________________________________ 83
Control Menu____________________________________________________________________ 98
ENGLISH
Configurable I/O Application Functions_______________________________________________ 105
Communication and Application Menus - Assistance During Operation - Maintenance __________ 130
73
Introduction
The display module may be connected and disconnected with the power on. If the display module is
disconnected when control of the speed controller via the display module is enabled, the speed controller locks
in fault modeSLF.
74
Introduction
ENGLISH
Scroll through menus or parameters and set a value.
Return to the previous menu or abort the current adjustment and return to
ESC the original value
STOP Command to stop the motor or reset the fault. The key’s “STOP” function
RESET can be inhibited via the program (“CONTROL” menu).
Rear view
Connector:
- for direct connection of the display module to the speed
controller
- for remote operation, the display module can be connected
via a cable provided in the VW3A58103 kit.
75
Practical Advice - Minimum Setup
Practical advice:
Before starting your programming, first fill in the configuration and settings record tables (at the end of this
document).
Programming the Altivar 58F is made easier by the use of internal sequence selections and interlocks. In order
to maximize this ease of use, we recommend that you access the menus in the following order. Not all steps
are essential in every case.
LANGUAGE
MACRO-CONFIG
CONTROL (for 3-wire control only)
I/O
CONTROL
DRIVE
FAULT
COMMUNICATION or APPLICATION if a card is used
ADJUST
CAUTION: The user must ensure that the programmed functions are compatible with the wiring
diagram used. This check is particularly important if the factory configuration is modified; the
diagram may also require modification.
ENGLISH
Minimum setup:
This procedure can be used:
- in simple applications where the speed controller factory settings are suitable, in open loop mode.
- during commissioning where it is necessary to rotate the motor initially before fully commissioning.
Procedure:
1 Follow the recommendations in the User’s Manual supplied with the speed controller, most importantly
setting the 50/60 Hz selector switch to the nominal frequency of the motor.
2 Ensure that the factory macro-configuration is suitable, otherwise change it in the “MACRO-CONFIG”
menu.
3 To ensure the required level of safety, check that the wiring diagram is compatible with the macro-
configuration, otherwise modify the diagram.
4 Check in the “DRIVE” menu that the factory parameters are compatible with those given on the motor
rating plate.
5 Check in the “DRIVE” menu that the control mode is set to open loop (Ctr = SVC).
7 If necessary, adjust the parameters in the “ADJUST” menu (ramps, motor current, etc).
76
Performance optimization
Operating modes
The Altivar ATV-58F has two operating modes:
• Open loop mode (SVC), with no speed feedback from the encoder. Speed correction is still possible in this
operating mode, using tachogenerator feedback (option card VW3-A58201).
• Closed loop mode with flux vector control (FVC) using speed feedback by incremental encoder. In this mode
high-performance speed and torque accuracy at very low speed can be achieved.
The required operating mode can be selected by configuration (parameter CTR) or by an assignable logic
input. In both cases the change of mode only takes effect once the motor has stopped, with the speed
controller locked.
ENGLISH
3 Perform an auto tune in the DRIVE menu. The auto tune adapts the speed controller to the motor. An auto
tune performed in one operating mode remains valid in the other; there is no need to repeat if the mode is
changed.
4 Configure the number of encoder pulses (PGI) and select the “encoder test” function (EnC = YES) in the
DRIVE menu to test the entire feedback sequence.
6 Start the motor and keep it running for at least 3 seconds at a stabilized speed over 10 Hz, ensure that the
motor is running correctly.
If fault SPF is displayed, check that the mechanical and electrical components of the encoder are operating
correctly, that it is connected, switched on and rotating in the correct direction (if necessary reverse 2 motor
phases or A and A-) and that the number of pulses has been configured correctly.
Correct and reset, then keep trying until the fault has been rectified.
7 Return to the DRIVE menu; parameter EnC should automatically be set to “DONE”.
8 Finally configure the FVC operating mode (Ctr = FVC) in the DRIVE menu.
77
Performance optimization
Manual adjustment is recommended if the auto-tuning procedure cannot be performed or if it does not perform
as expected. The essential parameters in FVC mode are the no-load current and the nominal slip.
The DISPLAY menu can be used to view current, voltage, frequency, etc. on the display module without the
need for measuring devices.
Nominal motor slip (adjusted by nominal speed nSP, DRIVE menu and SLP,
ADJUST menu)
• nominal speed: configure the value shown on the motor rating plate.
• run the motor at approximately nominal torque, with frequency = nominal frequency / 2, then adjust SLP to
obtain the lowest motor current (parameter LCr in the DISPLAY menu close to nominal current).
ENGLISH
Loop adjustment
The DRIVE menu offers a choice between two types of speed loop ( see page_97 ):
Procedure
With the ramps set to the minimum, apply a speed reference of 5 to 10 Hz then start and stop the motor,
observing the change in speed (response time, stability, overspeed). Depending on the results observed,
follow the steps below until the optimum performance is obtained.
IP loop adjustment
1 gradually increase FLG (gain) to improve the loop response time (passband); reduce in the event of
instability
2 gradually increase StA (stability) to avoid any overspeed.
PI loop adjustment
1 set SIG (integral gain) to 0
2 gradually increase SPG (proportional gain) as far as possible before oscillation begins and note the value
obtained: SPGmax
3 adjust SPG to 0.7 x SPGmax
4 gradually increase SIG (to reduce the speed error) as far as possible before oscillation begins.
78
Performance optimization
Motor fluxing
The Motor Flux function FLU (ADJUST menu) is used to achieve and maintain nominal flux in the motor when
no FW or RV movement has been requested. The presence of flux before the motor is started ensures
maximum performance in the starting dynamics. This function applies to both the SVC and FVC operating
modes.
ENGLISH
the end of TDC the motor is no longer controlled and the flux disappears automatically.
If a logic input is assigned to the motor fluxing function:
When this input is operated, it functions in the same way as with FLU = FCT, continuous flux.
Note:
• The prefluxing period depends on the motor power.
• The functions Freewheel stop by LI or Freewheel stop by pressing the STOP button have priority over the
Motor fluxing function.
• The value of the prefluxing current will always be that of the speed controller limiting current, to minimize
the prefluxing period.
79
Unlocking menus before programming
• To perform all the operations which are possible in the previous position
• ADJUST menu: To set all the parameters which can be accessed while the motor is rotating
ENGLISH
• To perform all the operations which are possible in the previous positions
• MACRO-CONFIG menu: To change the macro-configuration
• DRIVE menu: To adjust the performance of the motor-speed controller
• CONTROL menu: To configure control of the speed controller, for control via the terminals, the display
module or the integrated RS485 serial link
• I/O menu: To change the I/O assignment
• FAULT menu: To configure the motor and speed controller protection and operation in the event of a fault.
• FILES menu: To save and restore the speed controller configurations stored in the display module, return
to the factory settings or protect your configuration
• COMMUNICATION menu, if a communication card is installed: To adjust the parameters of a
communication protocol
• APPLICATION menu, if a “customer application” card is installed. Please refer to the documentation
specific to this card.
80
Access to menus
The number of menus which can be accessed depends on the position of the access locking switch.
Each menu is made up of a number of parameters.
LnG
LANGUAGE
ESC
CFG
MACRO-CONFIG
rEF
0.75 kW 380/500 V
Identification
SUP
ENGLISH
1-DISPLAY
2-ADJUST
SEt
3-DRIVE
drC
CtL
4-CONTROL
5-I/O
I-O displayed on
the module
6-FAULT
FLt
7-FILES
FLS
can only be accessed if can only be accessed if
a “customer application”
card is installed
APP
8-APPLICATION
SL
8-COMMUNICATION
a protocol card is
installed
Note:
If an access code has already been programmed, it may be impossible to modify some menus; these may not
even be visible. In this case, see the section entitled “FILES menu” explaining how to enter the access code.
81
Access to Menus - Programming Principle
Language:
This menu can be accessed whatever position the access switch is in, and can be modified in stop or run
mode.
Example:
ENT
LnG
LANGUAGE
LnG
English
LnG
Italiano
Save the new Return to the previously
ESC selection saved selection
ENT ESC
LnG LnG
ENGLISH
Italiano English
Programming principle:
The principle is always the same, with 1 or 2 levels:
ENT ENT
SEt
2.SETTINGS
ACC
Acceleration s
3.0
Acceleration s
3.1
Acceleration s
ENT ESC
3.1
Acceleration s
3.0
Acceleration s
82
Macro-Configurations
This parameter can always be displayed but can only be modified in programming mode (switch in position
) and in stop mode with the speed controller locked.
A macro-configuration automatically assigns the I/O and parameters, activating the functions required for the
application. Parameters related to the programming functions are available.
ENGLISH
Logic input LI3 2 preset speeds jog operation
Logic input LI4 4 preset speeds freewheel stop (1)
Analog input AI1 speed ref. speed ref.
Analog input AI2 summing ref. summing ref.
Relay R1 controller fault controller fault
Relay R2 not assigned not assigned
Analog output AO1 motor frequency motor frequency
Extension cards:
(1) In order to start, the logic input must be linked to the + 24 V (function active at 0)
Caution:
Ensure that the programmed macro-configuration is compatible with the wiring diagram
used. This check is particularly important if the factory configuration is modified; the circuit diagram
may also require modification.
83
Macro-Configurations
Drive identification
CHG
WIRING OK? ENT
ENT to confirm the modification
ESC to return to the previous configuration
CFG
CUS:Customized
is displayed
ENGLISH
Drive identification
This parameter can always be displayed. It indicates the speed controller power and voltage as indicated on
the identification label.
rEF
0.75 kW 380/500 V The power is displayed in kW if the 50/60 Hz selector switch on the speed
controller is set to 50 Hz, and in HP if it is set to 60 Hz.
84
Display Menu
ENGLISH
the control menu
Freq. Ref. FrH Frequency reference Hz
Output Freq. rFr Output frequency applied to the motor Hz
Motor Speed SPd Motor speed estimated by the speed controller RPM
MotorCurrent LCr Motor current A
Machine Spd. USP Machine speed estimated by the speed controller. This is proportional to rFr, –
according to a coefficient USC which can be regulated in the adjust menu.
Displays a value corresponding to the application (metres / second, for
example).
Caution, if USP becomes greater than 9999 the display is divided by 1000.
Output Power OPr Power supplied by the motor, estimated by the controller. %
100 % corresponds to nominal power.
MainsVoltage ULn Line voltage V
MotorThermal tHr Thermal state: 100 % corresponds to the nominal thermal state of the motor. %
Above 118 %, the speed controller triggers an OLF fault (motor overload)
DriveThermal tHd Thermal state of the speed controller: 100 % corresponds to the nominal %
thermal state of the speed controller. Above 118 %, the speed controller
triggers an OHF fault (speed controller overheating). It can be reset below 70
%.
Last Fault LFt Displays the last fault which occurred. –
Motor volt. UOP Voltage applied to the motor V
85
Adjust Menu
This menu can be accessed when the switch is in positions and . Adjustment parameters
can be modified in stop mode OR during operation. Ensure that any changes made during
operation are not dangerous; changes should preferably be made in stop mode.
The list of adjustment parameters is made up of a fixed part and a changeable part (shaded
parameters) which varies according to:
- the selected macro-configuration
- the presence of an I/O extension card
- the reassignment of I/O
- the selection of certain functions.
86
Adjust Menu
Speed prop.g - % SPG Proportional speed loop gain for PI-type loop (SSL 0 to 1000 40 %
= PI in DRIVE menu)
Speed int.g. - % SIG Integral speed loop gain for PI-type loop (SSL = PI 0 to 1000 40 %
in DRIVE menu)
ENGLISH
ThermCurrent - A ItH Current used for motor thermal protection. Set ItH 0.25 to 1.36 Acc. to
to the nominal current on the motor rating plate. In (1) controller
rating
(1) In corresponds to the speed controller nominal current indicated in the catalogue and on the speed
controller identification label.
87
Adjust Menu
Jog Delay - s JGt Anti-repeat delay between two consecutive jog 0 to 2 s 0.5 s
operations
BrRelease I - A Ibr Brake release current 0 to 1.36 In 0A
(1)
ENGLISH
no: while the brake is released the torque is in the requested direction of rotation.
Tacho Coeff. dtS Multiplication coefficient of the feedback 1 to 2 1
associated with the tachogenerator function:
9
dtS =
feedback voltage at HSP
PI Prop.Gain rPG Proportional gain of the PID regulator 0.01 to 100 1
PI Int.Gain rIG Integral gain of the PID regulator 0.01 to 100 / 1 / s
s
PID der.g. rdG Derivative gain of the PID regulator 0.00 to 0.00
100.0
PI Inversion PIC Reversal of the direction of correction of the PID no - YES no
regulator
no: normal
YES: reverse
(1) In corresponds to the speed controller nominal current indicated in the catalogue and on the speed
controller identification label.
88
Adjust Menu
Machine Coef USC Coefficient applied to parameter rFr (output 0.01 to 100 1
ENGLISH
frequency applied to the motor), the machine
speed is displayed via parameter USP in the
DISPLAY menu.
USP = rFr x USC
LSP Time - s tLS Operating time at low speed. 0 to 999.9 0 (no time
After operating at LSP for a given time, the motor limit)
is stopped automatically. The motor restarts if the
frequency reference is greater than LSP and if a
run command is still present.
Caution: value 0 corresponds to an unlimited time
(1) In corresponds to the speed controller nominal current indicated in the catalogue and on the speed
controller identification label.
(2) 100% corresponds to the nominal torque of a motor with power equal to that associated with the speed
controller.
89
Adjust Menu
Process max and Process min correspond to the customer’s adjustment range in customer units.
Example: set between 5 bar and 12 bar.
Process max: process value to be set when the signal is maximum (10 V, 20 mA) on the analog input selected for
the PID setpoint. Example: 12 bar for 10 V on 0-10 V input.
ENGLISH
Process min: process value to be set when the signal is minimum (0 V, 0 mA, 4 mA) on the analog input
selected for the PID setpoint. Example: 5 bar for 0 V on 0-10 V input.
Process max.
Adjustment range
PID setpoint
10 V
0V 20 mA
0 mA
4 mA
Process min.
Signal range
Note:
The reference value and the feedback value should always be positive, even if a bipolar analog input is used,
for example AI1 or AI3 (-10 V, +10 V). Negative values are not taken into consideration.
90
Adjust Menu
Min feedback and Max feedback correspond to the sensor feedback range in customer units.
Min feedback: value measured for the minimum signal on the analog input (0 V, 0 mA, 4 mA) selected for the
PID feedback. Example: 0 bar measured at 4 mA on 4-20 mA input.
Max feedback: value measured for the maximum signal on the analog input (10 V, 20 mA) selected for the PID
feedback. Example: 15 bar measured at 20 mA on 4-20 mA input.
Max feedback
Process max
Adjustment range
Sensor feedback
10 V
0V
20 mA
0 mA
ENGLISH
4 mA
Process min
Min feedback
Adjustment range
Sensor range
Note: The adjustment range (Process min and Process max) should be included within the sensor range [Min
feedback and Max feedback]
2 The user selects the desired input AI1: min signal = 0 V, max signal = 10 V
The user wishes to set the volume to between 100 m 3 and 10 m3.
Signal set by input AI1 Corresponding process value
Min signal 0 V 10 m3 = Min process reference
Max signal 10 V 100 m3 = Max process reference
3 Scaling.
91
Adjust Menu
PID error - % PEr Error value above which the output assigned to 0 to 100 % 100 %
PID error changes to 1.
100 % = max feedback - min feedback
0%=0
PID Preset 2 - % PI2 2nd preset PID setpoint, when a logic input has 0 to 100 % 30 %
been assigned to the function 4 preset PID
setpoints.
100 % = process max
0 % = process min
PID Preset 3 - % PI3 3rd preset PID setpoint, when a logic input has 0 to 100 % 60 %
been assigned to the function 4 preset PID
setpoints.
100 % = process max
0 % = process min
PID Limit r. -% PLr Limiting of the output from the PID regulator as a 0 to 100 % 20 %
% of the output signal from the speed input
multiplier.
Deadband
Hz
PLr
PLb
Speed input
x PSR
PLb
PID base lim - Hz PLb Base limit for the output from the PID regulator 0.0 Hz to HSP
HSP
Motor fluxing FLU Selects motor fluxing mode ( see page_79 ) FNC-FCT FNC
FNC : non-continuous
FCT : continuous
92
Drive Menu
ENGLISH
Nom.Mot.Curr - A nCr Nominal motor current given on the rating plate 0.25 to 1.36 according to
In (1) controller
rating
Nom.MotSpeed - RPM nSP Nominal motor speed given on the rating plate 0 to 9999 according to
RPM controller
rating
Mot. Cos Phi CoS Motor Cos Phi given on the rating plate 0.5 to 1 according to
controller
rating
Control mode Ctr Selects the control mode: SVC - FVC SVC
- Open loop SVC
- Closed loop FVC
Enc pulse No PGI Number of pulses per encoder revolution 100 to 5000 1024
(control card)
Auto Tuning tUn Used to auto-tune motor control once this no - YES no
parameter has been set to “YES”.
Once auto-tuning is complete, the parameter automatically returns to “DONE”
or “no” in the event of a fault.
Caution:
• Auto-tuning is only performed if no command has been activated. If a
“freewheel stop” or “fast stop” function is assigned to a logic input, this input
must be set to 1 (active at 0).
• Auto-tuning may last for 1 minute. Do not interrupt; wait for the display to
change to “DONE” or “no”.
• It is essential that all the motor parameters (UnS, FrS, nCr, nSP, COS) are
correctly configured before performing the auto-tuning.
• During auto-tuning the motor is under nominal current.
(1) In corresponds to the speed controller nominal current indicated in the catalogue and on the speed
controller identification label.
93
Drive Menu
general use.
If relay R2 is assigned to the brake sequence
function, the parameter brA remains locked on no.
SwitchRamp2 - Hz Frt Ramp switching frequency. 0 to HSP 0 Hz
Once the output frequency exceeds Frt, the ramp
times taken into account are AC2 and dE2.
94
Drive Menu
S-shape ramps
f (Hz) f (Hz)
GV GV The curve coefficient is fixed,
with t2 = 0.6 x t1
with t1 = set ramp time.
0 0
t t
t2 t2
t1 t1
ENGLISH
U-shape
f (Hz) f (Hz)
GV GV The curve coefficient is fixed,
with t2 = 0.5 x t1
with t1 = set ramp time.
0 0
t t
t2 t2
t1 t1
Customized ramps
f (Hz) f (Hz)
GV GV tA1: can be set between 0 and 100 %
(of ACC or AC2)
tA2: can be set between 0 and (100 %
- tA1) (of ACC or AC2)
0 0 tA3: can be set between 0 and 100 %
t t (of dEC or dE2)
tA1 tA2 tA3 tA4
ACC or AC2 dEC or dE2 tA4: can be set between 0 and (100 %
- tA3) (of dEC or dE2)
Parameters tA1, tA2, tA3 and tA4 can
be set in the ADJUST menu
95
Drive Menu
controller rating. When the thermal state of the speed controller drops back to
70 %, the selected switching frequency is re-established. HF2 switching is
designed for applications with a high load factor with derating of the speed
controller by one rating: the drive parameters are scaled automatically (torque
limit, thermal current, etc).
SFr(kHz) 0.5 1 2 4 8 12 16
tFr (Hz) 62 125 250 450 450 450 450
Noise Reduct nrd This function modulates the switching frequency no-YES YES (3)
randomly to reduce motor noise. no (4)
(1) 100% corresponds to the nominal torque of a motor of a power equal to that associated with the speed
controller.
(2) In corresponds to the speed controller nominal current indicated in the catalogue and on the speed
controller identification label.
(3) if SFT = LF,
(4) if SFt = HF1 or HF2
96
Drive Menu
ENGLISH
speed reference
motor speed
t
0
speed reference
motor speed
t
0
97
Control Menu
This menu can be accessed when the switch is in position . The parameters can only be modified in stop
mode with the speed controller locked.
The I/O with a grey background can be accessed if an I/O extension card has
been installed.
3-wire control (pulse control: one pulse is sufficient to control start-up). This
option inhibits the “automatic restart” function.
Wiring example:
ATV-58F control terminals
LI1: stop 24 V LI1 LI2 LIx
LI2: forward
LIx: reverse
98
Control Menu
ENGLISH
HSP
Pedestal
(BNS)
LSP
Reference
0
100 %
F : motor frequency
HSP
Deadband
(BLS)
LSP
Reference
0
100 %
This parameter appears only when an analog input
is assigned to the PID feedback.
AI2 min Ref. - mA CrL Minimum value of the signal on input AI2. 0 to 20 mA 4 mA
AI2 Max Ref. - mA CrH Maximum value of the signal on input AI2. 4 to 20 mA 20 mA
These two parameters are used to define the
signal sent to AI2. There are several configuration
possibilities, one of which is to configure the input
for a 0-20 mA, 4-20 mA, 20-4 mA, etc signal.
Frequency
HSP
LSP
0
AI 2
CrL CrH 20
(mA)
99
Control Menu
Max.
AO (mA)
0
AOL AOH 20
Save Ref. Str Associated with the - speed function, this function NO-RAM NO
ENGLISH
100
I/O Menu
The inputs and outputs available in the menu depend on the I/O cards installed (if any) in the speed controller,
as well as the selections made previously in the control menu.
The “factory” configurations are preassigned by the selected macro-configuration.
Summary table of the logic input assignments (exc. 2-wire / 3-wire option)
I/O extension option cards 2 logic inputs LI5-LI6
Speed controller without option 3 logic inputs LI2 to LI4
NO :Not assigned (Not assigned) X
RV :Reverse (Reverse) X
RP2:Switch ramp2 (Ramp switching) X
ENGLISH
JOG (Jog operation) X
+SP:+ Speed (+ speed) X
-SP:- Speed (- speed) X
PS2:2 Preset SP (2 preset speeds) X
PS4:4 Preset SP (4 preset speeds) X
PS8:8 Preset SP (8 preset speeds) X
NST:Freewhl Stop (Freewheel stop) X
DCI:DC inject. (Injection stop) X
FST:Fast stop (Fast stop) X
CHP:Multi. Motor (Open / closed loop switching) If Ctr = FVC X
TL2:Trq.Limit 2 (Second torque limit) X
FLO:Forced Local (Forced local mode) X
RST:Fault Reset (Fault reset) X
RFC:Auto/Manu (Reference switching) X
ATN:Auto Tuning (Auto-tuning) X
SPM:Ref.memory (Reference saved) X
FLI:Motor fluxing (Motor fluxing) X
PAU:PID Auto/Man (PID Auto/Manu) If one AI = PIF X
PIS:PIDint.reset (PID integral shunting) If one AI = PIF X
PR2:PID 2 Preset (2 preset PID setpoints) If one AI = PIF X
PR4:PID 4 Preset (4 preset PID setpoints) If one AI = PIF X
If a logic input is assigned to “Freewheel stop” or “Fast stop”, start-up can only be performed by
linking this input to the +24V, as these stop functions are active when inputs are at state 0.
101
I/O Menu
(1) NB: The menu for assigning encoder input A+, A-, B+, B- is called “Assign AI3”.
CAUTION: If relay R2 is assigned to the “brake sequence” function, AI3 is automatically assigned in
the factory setting to Tacho Feedback, if the card is present. However, it is still possible to reassign
AI3.
102
I/O Menu
ENGLISH
OPI:PID Integral (PID integral output) If one AI = PIF X
Once the I/O have been reassigned, the parameters related to the function automatically appear in the menus,
and the macro-configuration indicates “CUS: Customized”.
Some reassignments result in new adjustment parameters which the user must not forget to set in the adjust
menu:
103
I/O Menu
Some reassignments result in new adjustment parameters being added which the user must configure in the
control, drive or fault menu:
104
Configurable I/O Application Functions
Reference saved
Closed loop FVC
Summing inputs
Freewheel stop
tachogenerator
Preset speeds
Jog operation
PID regulator
+/- speed
Fast stop
DC injection braking
Summing inputs
PID regulator
+/- speed
Reference switching
ENGLISH
Freewheel stop
Fast stop
Jog operation
Preset speeds
Speed regulation with
tachogenerator
Torque limitation via AI3
Torque limitation via LI
Reference saved
Closed loop FVC
Open / closed loop switching
The function indicated by the arrow has priority over the other.
105
Logic Input Application Functions
2-wire control:
Run (forward or reverse) and stop are controlled by the same logic input, for which state 1 (run) or 0 (stop), or
a change in state is taken into account (see the 2-wire control menu).
3-wire control:
Run (forward or reverse) and stop are controlled by 2 different logic inputs.
LI1 is always assigned to the stop function. A stop is obtained on opening (state 0).
The pulse on the run input is stored until the stop input opens.
During power-up or manual or automatic fault resetting, the motor can only be supplied with power after a reset
prior to the “forward”, “reverse”, and “injection stop” commands.
ENGLISH
Ramp switching: 1st ramp: ACC, DEC ; 2nd ramp: AC2, DE2
Two types of activation are possible:
- activation of a logic input LIx
- detection of an adjustable frequency threshold.
If a logic input is assigned to the function, ramp switching can only be performed by this input.
106
Logic Input Application Functions
Description: 1 button pressed twice for each direction of rotation. Each action closes a contact.
Wiring example:
LI1: forward
ATV-58F control terminals
LIx: reverse
LI1 LIx LIy + 24
LIy: + speed
b d
ENGLISH
a c
Motor
frequency
LSP
0
LSP
Forward
Press 2
b b
Press 1
a a a a a a a
0
Reverse
Press 2
Press 1 d
c c
0
This type of +/- speed is incompatible with 3-wire control. In this case, the - speed function is automatically
assigned to the logic input with the highest index (for example: LI3 (+ speed), LI4 (- speed)).
In this case, the maximum speed is given by the references applied to the analog inputs. For example,
connect AI1 to +10V.
107
Logic Input Application Functions
This function accesses the STr save reference parameter in the CONTROL menu.
• If Str = No, RAM or EEP, the maximum rotation speed is fixed by the analog references (for example,
connect AI1 to +10V). If the reference decreases and drops below the rotation speed, the rotation speed
follows the reference. The rate of increase is given by the valid acceleration parameter (ACC, DEC or AC2,
DC2).
• If Str = SRE, the maximum rotation speed is fixed by HSP. When the run command is issued, the speed
controller changes to the setpoint reference following the ACC / DEC ramps. Pressing + speed / - speed
varies the speed around this setpoint following the AC2 / DE2 ramps.
• + or - speed adjustment around the setpoint is limited by parameter SRP (ADJUST menu). This parameter
ENGLISH
• If the reference changes, the ratio between the reference and the setpoint resulting from the + speed / -
speed correction is fixed.
108
Logic Input Application Functions
Wiring examples:
LI1: forward
LIx: reverse
LI1 LIx LIy LIz
LIy: + speed
LIz: - speed
F : Motor frequency
Reference
LSP
t
0
ENGLISH
LSP
Reference
LI faster
1
t
0
LI slower
1t
0 t
LI forward
1
0 t
LI reverse
1
0 t
109
Logic Input Application Functions
Str = RAM (saved in RAM): the reference is saved on each + speed / - speed falling edge. Thus, after a stop
without the speed controller being powered down, when a run command appears the frequency increases to
the saved value if the + speed / - speed commands are not active. + speed / - speed still have priority.
Str = EEP (saved in EEPROM): the reference is saved on each + speed / - speed falling edge. Thus, after a
stop with or without the speed controller being powered down, when a run command appears the frequency
increases to the saved value if the + speed / - speed commands are not active. + speed / - speed still have
priority.
F : Motor frequency
Reference
LSP
t
0
ENGLISH
LSP
Reference
LI faster
1
t
0
LI slower
1t
0 t
LI forward
1
0 t
LI reverse
1
0 t
110
Logic Input Application Functions
F : Motor frequency
HSP
SRP
Reference
SRP
LSP
t
0
LSP
Reference
SRP
HSP
LI faster
1
t
0
ENGLISH
LI slower
1t
0 t
LI forward
1
0 t
LI reverse
1
0 t
Adjustments around the setpoint using + speed and - speed are made following the AC2 and dE2 ramps.
111
Logic Input Application Functions
Preset speeds:
2, 4 or 8 speeds can be preset, requiring 1, 2 or 3 logic inputs respectively.
The following order of assignments must be observed: PS2 (LIx), then PS4 (LIy), then PS8 (LIz).
To unassign the logic inputs, the following order must be observed: PS8 (LIz), then PS4 (LIy), then PS2 (LIx).
Connection diagram
LI x + 24 COM AI 1 +10 AI 2
Open contact, reference = AI2
Closed contact, reference = AI1
0-20mA
4-20mA
Freewheel stop:
Causes the motor to stop using the resistive torque only. The motor power supply is cut.
A freewheel stop is obtained when the logic input opens (state 0).
DC injection stop:
An injection stop is obtained when the logic input closes (state 1).
This function cannot be accessed in closed loop mode.
Fast stop:
Braked stop with the deceleration ramp time reduced by a reduction factor dCF which appears in the drive
menu.
A fast stop is obtained when the logic input opens (state 0).
112
Logic Input Application Functions
After a change in the state of the logic input assigned to this function, switching does not actually take effect
until the next time the drive is stopped and locked.
Fault reset:
Two types of reset are available: partial or general (parameter rSt in the “fault” menu).
ENGLISH
Used to clear the stored fault and reset the speed controller if the cause of the fault has disappeared.
Faults affected by partial clearing:
This inhibits all faults (forced operation) except SCF (motor short circuit) while the assigned logic input
is closed.
Auto-tuning:
When the assigned logic input changes to 1 an auto-tuning operation is triggered, in the same way as
parameter tUn in the “drive” menu.
Caution:
• Auto-tuning is only performed if no command has been activated. If a “freewheel stop” or “fast stop” function
is assigned to a logic input, this input must be set to 1 (active at 0).
• Auto-tuning may last for 1 minute. It should not be interrupted.
• The motor parameters (UnS, FrS, nCr, nSP, COS) must be configured before auto-tuning is performed.
• During auto-tuning the motor absorbs its nominal current.
113
Logic Input Application Functions
Reference saving:
Saving the speed reference value of the analog input using a logic input when the command lasts longer than
0.1 s.
• This function is used to control the speed of several speed controllers alternately via a single analog setpoint
and a logic input for each controller.
• It is also used to confirm a line reference (serial link) on several speed controllers via a logic input. This
allows movements to be synchronized by getting rid of variations when the reference is sent.
• The setpoint is acquired 100 ms after the rising edge of the request. A new reference is not then acquired
until a new request is made.
F : motor frequency
Analog
setpoint
t
ENGLISH
Run command
t
0
LIx (saving)
0 t
100 ms 100 ms 100 ms
Motor fluxing:
In order to obtain rapid high torque on start-up, magnetic flux needs to be already established in the motor.
114
Analog Input Application Functions
Input AI1 is always the speed reference. Analog inputs AI2 and AI3 can be assigned.
ENGLISH
Total resistance of the probe circuit at 20 °C = 750 Ω.
PID regulator:
Used to regulate a process with a reference and a feedback given by a sensor. A speed input gives an initial
(or predictive) setpoint for start-up. In PID mode the ramps are all linear, even if they are configured differently.
Note:
PID regulator mode is active if an AI input is assigned to PID feedback.
115
Analog Input Application Functions
Predictive
speed input
ACC
PSr
dEC
Error alarm
Multiplier Linear ramp
PEr
PID
PID regulator
setpoint + + RPG PLr +
PrG X PIC +
RIG X±1
RdG PLb
Multiplier + –
Deadband PID
rEO f (speed) reversal
AC2
Offset Ramp
dE2
PID Reference
ENGLISH
Integral shunting
Auto / man
116
Analog Input Application Functions
Speed input:
• Line setpoint (serial link)
• or analog input AI3.
PID setpoint:
• Line setpoint (serial link)
• or 2 or 4 setpoints preset via logic input
• or analog input AI1 ( ± AI2 ± AI3).
PID feedback:
• Analog input AI2
• or analog input AI3.
Manual setpoint:
(speed regulation mode)
• Analog input AI3.
Integral shunting:
• Logic input LI: integral shunted if LIx =1.
Auto/man:
• Logic input LI for switching operation to speed regulation (man) if LIx = 1, or PID regulation (auto) if LIx = 0.
• In automatic mode the following actions are possible:
- Adapt the setpoint input to the process feedback: GAIN (PrG) and OFFSET (rEO).
ENGLISH
- Correct PID inversion.
- Adjust the proportional, integral and derivative gain (RPG, RIG and RdG).
- Use the “alarm” on logic output if a threshold is exceeded (Max. feedback, Min. feedback and PID error).
- Assign an analog output for the PID setpoint, PID feedback and PID error.
- Limit the action of the PID according to the speed, with an adjustable base and ratio:
Speed
Deadband
- Apply a ramp to establish the action of the PID (AC2) on start-up and a ramp (dE2) on stopping.
• The motor speed is limited to between LSP and HSP.
• It is displayed as a percentage.
Preset setpoints:
2 or 4 preset setpoints require the use of 1 or 2 logic inputs respectively:
2 preset setpoints 4 preset setpoints
Assign: LIx to Pr2 Assign: LIx to Pr2, then LIy to Pr4
LIx Reference LIy LIx Reference
0 Analog reference 0 0 Analog reference
1 Process max 0 1 PI2 (adjustable)
1 0 PI3 (adjustable)
1 1 Process max
Torque limit:
(Only with an I/O extension card with analog input AI3). The signal applied at AI3 operates in a linear fashion
on the internal torque limit (parameter TLI in the “drive” menu):
- If AI3 = 0V: limit = TLI x 0 = 0
- If AI3 = 10 V: limit = TLI.
117
Encoder Input Application Functions
Applications:
• Synchronization of the speed of a number of speed controllers. Parameter PLS on the DRIVE menu is used
to adjust the speed ratio of one motor in relation to that of another.
• Setpoint via encoder.
This relates to the encoder for the control card. It is used for fine speed adjustments, irrespective of the state
of the load, and for control optimization (flux vector control mode in closed loop: Ctr = FVC, DRIVE menu).
ENGLISH
• Consistency between the motor frequency and the speed feedback is monitored in the speed controller fault
management system.
• If there is no PG signal (FVC mode) or in the event of inconsistency, the speed controller locks in fault mode
SPF.
• During operation, if the difference between the motor frequency and the speed feedback is greater than 5
Hz, the speed controller locks in fault mode SPF.
• If the speed feedback is greater than 1.2 x tFr, the speed controller changes to default mode SOF.
CAUTION: The encoder input terminals on the I/O extension card are identified in the same way as
the encoder input terminals on the control card (A, A-, B, B-). Suitable precautions should be taken
to avoid any possible confusion, and the terminals should be checked before setup.
118
Logic Output Application Functions
If a DC injection braking function is configured, it should not be left operating too long in stop mode,
as the contactor only opens at the end of braking.
If continuous flux is configured (in closed loop mode), the contactor does not open.
ENGLISH
The logic output is at state 1 if the motor frequency is greater than or equal to the frequency threshold set by
Ftd in the adjust menu.
119
Logic Output Application Functions
Principle:
Vertical movement:
Maintain motor torque in an upward direction when the brake is being opened and closed, in order to hold the
load, and start smoothly as soon as the brake is released.
Horizontal movement:
Synchronize the opening of the brake with the build-up of torque during start-up and the closing of the brake
at zero speed on stopping, to prevent jolting.
ENGLISH
120
Logic Output Application Functions
V : motor speed
Speed
reference
t
0
R2 relay
t
0
Motor current
brt
ENGLISH
Ibr
0 t
tdC
F : motor frequency
bEt
Speed
reference
bEn
0 t
LI forward
or reverse
1
0 t
121
Logic Output Application Functions
t
0
R2 relay
t
0
Motor current
brt
ENGLISH
Ibr
0 t
tdC
F : motor frequency
bEt
Speed
reference
0 t
LI forward
or reverse
1
0 t
122
Logic Output Application Functions
Recommended settings for brake control, for a vertical lifting application (for a horizontal application set Ibr to
zero and BIP to “no”):
1 Brake pulse (bIP): YES. Ensure that the direction of rotation FW corresponds to lifting the load.
3 Acceleration time:
For lifting applications it is advisable to set the acceleration ramps to more than 0.5 seconds. Ensure that
the speed controller does not exceed the current limit.
The same recommendation applies for deceleration.
Note: for a lifting movement, a braking resistor should be used. Ensure that the settings and configurations
selected cannot cause a drop or a loss of control of the lifted load.
5 Brake engage frequency (bEn): in open loop mode (Ctr = SVC, DRIVE menu)
ENGLISH
Set to twice the nominal slip. Then adjust according to the result.
123
Analog Output Application Functions
Analog outputs AO1 and AO are current outputs, from AOL (mA) to AOH (mA), AOL and AOH being
configurable from 0 to 20 mA. The configuration of AOL and AOH is common to both outputs.
Motor current (Code OCR): the image of the motor rms current.
AOH corresponds to twice the nominal speed controller current. AOL corresponds to zero current.
Motor frequency (Code OFR): the motor frequency estimated by the speed controller.
AOH corresponds to the maximum frequency (parameter tFr). AOL corresponds to zero frequency.
Ramp output (Code ORP): the image of the ramp output frequency.
ENGLISH
AOH corresponds to the maximum frequency (parameter tFr). AOL corresponds to zero frequency.
Motor torque (Code TRQ): the image of the motor torque as an absolute value.
AOH corresponds to twice the nominal motor torque. AOL corresponds to zero torque.
Signed motor torque (Code STQ): the image of the motor torque and direction:
• AOL corresponds to a braking torque = twice the nominal torque
• AOH corresponds to a motor torque = twice the nominal torque
AOH + AOL
• --------------------------------- corresponds to zero torque.
2
Signed ramp (Code ORS): the image of the ramp output frequency and direction.
• AOL corresponds to the maximum frequency (parameter tFr) in the reverse direction.
• AOH corresponds to the maximum frequency (parameter tFr) in the forward direction.
AOH + AOL
• --------------------------------- corresponds to zero frequency.
2
PID setpoint (Code OPS): the image of the PID regulator setpoint
• AOL corresponds to the minimum setpoint.
• AOH corresponds to the maximum setpoint.
PID feedback (Code OPF): the image of the PID regulator feedback
• AOL corresponds to the minimum feedback.
• AOH corresponds to the maximum feedback.
124
Analog Output Application Functions
PID error (Code OPE): the image of the PID regulator error as a % of the sensor range (maximum
feedback - minimum feedback).
PID integral (Code OPI): the image of the PID regulator error integral.
• AOL corresponds to LSP.
• AOH corresponds to HSP.
ENGLISH
125
Fault Menu
Ohms)
When the function is activated and after stopping, the fault relay
remains closed on one or more of these faults, and when the
conditions for restarting are correct (disappearance of the fault) the
speed controller attempts a start after a 30 s delay.
A maximum of 6 attempts are made when the speed controller
cannot start. If all 6 fail, the speed controller remains locked
definitively with the fault relay open, until it is reset by being
switched off.
This function requires the associated sequence to be
maintained. Ensure that accidental restarting will not
pose any danger to either equipment or personnel.
Reset Type rSt This function can be accessed if the fault reset is assigned to a logic RSP
input.
2 possible options: partial reset (RSP), general reset (RSG).
Faults affected by a partial reset (rSt = RSP)
- line overvoltage - DC bus overvoltage
- motor overheating - loss of 4-20 mA
- motor overload - overhauling
- motor phase loss - speed controller overheating
- serial link fault - external fault
- communication fault - overspeed
Faults affected by a general reset (rSt = RSG):
all faults. The general reset actually inhibits all the faults (forced
operation).
To configure rSt = RSG:
1 - Display RSG
2 - Press the “ENT” key
3 - The speed controller displays “ See manual ”
4 - Press ▲ then ▼ then “ENT”
126
Fault Menu
ENGLISH
LossFollower LFL Used to enable the loss of 4-20 mA reference fault. no
This fault can only be configured if the min/max AI2 reference
parameters (CrL and CrH, CONTROL menu) are greater than 3 mA.
YES/no options. If CrL>CrH, LFL is locked on YES.
Catch On Fly FLr Used to enable a smooth restart after one of the following events: no
- loss of line supply or simple power off
- fault reset or automatic restart
- freewheel stop or injection stop with logic input.
- uncontrolled loss downstream of the speed controller.
YES/no options
If relay R2 is assigned to the brake sequence function, the
parameter FLr remains locked on no.
If closed loop mode has been selected (Ctr = FVC, DRIVE menu),
parameter FLr is inactive and the system naturally starts smoothly
in all cases, even if FLr = no.
Cont. Stop StP Controlled stop on a line phase loss. This function is only no
operational if parameter IPL is set to no. If IPL is set to YES, leave
StP in position no. Possible options:
no: locking on loss of line supply
MMS: maintain DC bus: voltage for the speed controller control is
maintained by the kinetic energy restored by the inertia, until the
USF fault (undervoltage) occurs
FRP: follow ramp: deceleration following the programmed dEC or
dE2 ramp until a stop or until the USF fault (undervoltage) occurs.
RampNotFoll Sdd This function can be accessed in closed loop mode (Ctr = FVC, no
DRIVE menu) or with the I/O option card if feedback via
tachogenerator is configured. When enabled, it is used to lock the
speed controller if a speed error is detected (difference between the
stator frequency and the measured speed).
YES/no options.
127
Files Menu
The display module is used to store 4 files containing the speed controller configurations.
Operating mode
At the end of each operation the display returns to the “Operat.Type” parameter set to “NO”
128
Files Menu
CAUTION: THIS PARAMETER SHOULD BE USED WITH CAUTION. IT MAY PREVENT ACCESS TO ALL
PARAMETERS. ANY MODIFICATION TO THE VALUE OF THIS PARAMETER MUST BE CAREFULLY
NOTED AND SAVED.
The code value is given by four figures, the last of which is used to define the level of accessibility required by
the user.
8888
This figure gives the access level permitted,
without having the correct code.
Access to the menus according to the position of the access locking switch on the rear of the display module
is always operational, within the limits authorised by the code.
ENGLISH
The value Code 0000 (factory setting) does not restrict access.
The table below defines access to the menus according to the last figure in the code.
For access to the APPLICATION menu, refer to the application card documentation.
COd
Password fault
After pressing the ENT or ESC key on the keypad, the value displayed for the Code parameter changes to
0000: the level of accessibility does not change. The operation should be repeated.
To access menus protected by the access code, the user must first enter this code which can always be
accessed in the Files menu.
129
Communication and Application Menus - Assistance
During Operation - Maintenance
Communication menu
This menu is only displayed if a communication card is installed. It can be accessed when the switch
is in position . Configuration is only possible in stop mode with the speed controller locked.
For use with a communication option card, refer to the document provided with this card.
For communication via the RS485 link on the base product, refer to the document provided with the RS485
connection kit.
Application menu
This menu is only displayed if a “customer application” card is installed. It can be accessed when the switch
is in position . Configuration is only possible in stop mode with the speed controller locked.
Maintenance
Before working on the speed controller, switch off the power supply and wait for the
capacitors to discharge (approximately 3 minutes): the green LED on the front panel of the
speed controller is no longer illuminated.
CAUTION: the DC voltage at the + and - terminals or PA and PB terminals may reach 900 V depending
on the line voltage.
If a problem arises during setup or operation, ensure that the recommendations relating to the environment,
mounting and connections have been observed. Refer to the Altivar User’s Manual.
Servicing
The Altivar does not require any preventive maintenance. It is nevertheless advisable to perform the following
regularly:
• check the condition and tightness of connections
• ensure that the temperature around the unit remains at an acceptable level and that ventilation is effective
(average service life of fans: 3 to 5 years depending on the operating conditions)
• remove any dust from the speed controller.
In some cases there may be an automatic restart once the fault has disappeared, if this function has been
programmed.
130
Fault Display - Causes / Remedies
ENGLISH
ObF • braking too sudden or driving load • increase the deceleration time, add a
Overbraking braking resistor if necessary.
OPF • one phase open-circuit at the speed • check the motor connections
Motor Phase Loss controller output
LFF • loss of the 4-20 mA setpoint on input AI2 • check the connection of the setpoint
LossFollower circuits
OCF • ramp too short • check the settings
Overcurrent • inertia or load too high • check the size
of the motor/speed controller/load
• mechanical locking • check the state of the mechanism
SCF • short-circuit or grounding at the speed • check the connection cables with the
Short Circuit controller output speed controller disconnected, and the
motor insulation. Check the speed
controller transistor bridge
CrF • load relay control fault • check the connectors in the speed
Precharge Fault • damaged load resistor controller and the load resistor
SLF • incorrect connection on the speed • check the connection on the speed
Serial Link Flt controller connector port controller connector port
OtF • motor temperature too high • check the motor ventilation and
Motor Overheated (PTC probes) the ambient temperature, monitor
the motor load
• check the type of probes used
tSF • incorrect connection of probes to the • check the connection of the probes to
PTC Therm Sensor speed controller the speed controller
• check the probes
EEF • error saving in EEPROM • cut the power supply to the speed
EEprom Fault controller and reset
InF • internal fault • check the connectors in the speed
Internal Fault • connector fault controller
131
Fault Display - Causes / Remedies
CnF • communication fault on the fieldbus • check the network connection to the
Network Fault speed controller
• check the time-out
ILF • communication fault between the option • check the connection of the option card
Int. Comm. Flt card and the control card to the control card
CFF Error probably caused when changing the • check the hardware configuration of the
card: speed controller (power card, others)
Rating Fault-ENT • change of rating of the power card • cut the power supply to the speed
controller then reset
Option Fault-ENT • change of the type of option card or • save the configuration in a file on the
installation of an option card if there was display module
not one already and if the macro-config • press ENT twice to return to the factory
is CUS settings (when ENT is pressed the first
Opt. Missing-ENT • option card removed time the following message appears:
CKS Fault - ENT • inconsistent configuration saved Fact.Set? ENT/ESC).
CFI • inconsistent configuration sent to speed • check the configuration sent previously
Config. Fault controller via serial link • send a consistent configuration
132
Fault Display - Causes / Remedies
ENGLISH
133
Record of Configuration and Settings
Adjustment parameters:
Code Factory setting Customer setting (1) Code Factory setting Customer setting (1)
Inr 0.1 s s ItH Acc. to controller rating A
ACC 3s s IdC Acc. to controller rating A
dEC 3s s tdC 0.5 s s
AC2 5s s SdC Acc. to controller rating A
dE2 5s s UFr 100 % %
tA1 10 % SLP 100 % %
tA2 10 % SP2 10 Hz Hz
tA3 10 % SP3 15 Hz Hz
tA4 10 % SP4 20 Hz Hz
LSP 0 Hz Hz SP5 25 Hz Hz
HSP 50/60 Hz Hz SP6 30 Hz Hz
FLG 20 % SP7 35 Hz Hz
StA 20 % JOG 10 Hz Hz
SPG 40 % JGt 0.5 s s
SIG 40 % Ibr 0A A
134
Record of Configuration and Settings
ENGLISH
tL2 200 % % PLb HSP Hz
JPF 0 Hz Hz FLU FNC
USC 1
135
Record of Configuration and Settings
136
Summary of menus
ENGLISH
Drive State --- BrEngage Lev- Hz bEn
Freq. Ref. LFr BrEngageTime- Hz bEt
Freq. Ref. FrH Brake impul. bIP
Output Freq. rFr Tacho Coeff. dtS
Motor Speed SPd PI Prop.Gain rPG
MotorCurrent LCr PI Int.Gain rIG
Machine Spd USP PID der.g. rdG
Output Power OPr PI Inversion PIC
MainsVoltage ULn Freq.Lev.Att- Hz Ftd
MotorThermal tHr Curr.Lev.Att - A Ctd
DriveThermal tHd ThermLev.Att - % ttd
Last Fault LFt Trq. Limit 2 - % tL2
Motor volt. UOP Jump Freq. - Hz JPF
Machine Coef USC
LSP Time - s tLS
2 - ADJUST menu +/-SpeedLim. - % SrP
PID ref.off. rEO
Name Code Ref. gain PI PrG
Freq. Ref. - Hz LFr PID Speed r. PSr
Ramp Incr. - s Inr PID Filter - s PSP
Acceleration - s ACC Min.feed.PID - % PAL
Deceleration - s dEC Max.feed.PID - % PAH
Accelerate2 - s AC2 PID error - % PEr
Decelerate2 - s dE2 PID Preset 2 - % PI2
Beg ACC Rnd. - % tA1 PID Preset 3 - % PI3
End ACC Rnd. - % tA2 PID Limit r. - % PLr
Beg DEC Rnd. - % tA3 PID base lim.- Hz PLb
End DEC Rnd. - % tA4 Motor fluxing FLU
Low Speed - Hz LSP
High Speed - Hz HSP
Gain - % FLG
Stability - % StA
Speed prop.g - % SPG
Speed int.g. - % SIG
137
Summary of menus
5 - I/O menu
Name Code
LI2 Assign. LI2
LI3 Assign. LI3
LI4 Assign. LI4
LI5 Assign. LI5
LI6 Assign. LI6
138
Summary of menus
ENGLISH
ORP:Output ramp Operat.Type FOt
TRQ:Motor torque Password COd
STQ:Signed Torq.
ORS:Signed ramp 8 - COMMUNICATION menu
OPS:PID ref.
OPF:PID Feedback Refer to the documentation provided with the
OPE:PID Error communication card.
OPI:PID Integral
8 - APPLICATION menu
139
Index
140
Index
ENGLISH
141
VVDED399094 W9 1598250 01 11 A01
29023 2000-03