Industrial UPS Specifications

This document provides specifications for several models of online double conversion uninterruptible power supply (UPS) systems ranging in capacity from 10kVA to 80kVA. It lists the key features and technical specifications for each model including input voltage range, output voltage regulation, battery specifications, communication options, environmental limits, dimensions, and certifications. The UPS systems can provide backup power from internal lead-acid batteries during utility power outages or disturbances and have overload, short circuit, and ECO modes of operation.

Uploaded by

GermanYP
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
423 views2 pages

Industrial UPS Specifications

This document provides specifications for several models of online double conversion uninterruptible power supply (UPS) systems ranging in capacity from 10kVA to 80kVA. It lists the key features and technical specifications for each model including input voltage range, output voltage regulation, battery specifications, communication options, environmental limits, dimensions, and certifications. The UPS systems can provide backup power from internal lead-acid batteries during utility power outages or disturbances and have overload, short circuit, and ECO modes of operation.

Uploaded by

GermanYP
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Panel LCD

CARACTERÍSTICAS
- Online Doble conversión
- Corrector de PFC
- Control Digital DSP
- Factor de potencia de salida 0,9
- Función ECO
- Baterías incorporadas para UPS 20, 30 KVA
- Puerto de comunicación USB/RS232/Dry Contact
- Placa SNMP opcional
- LCD/LED doble Display
- Cargador Inteligente
- Puede trabajar con cargas desbalanceadas
ESPECIFICACIONES TÉCNICAS
MODEL YDC3310S/H YDC3315S/H YDC3320S/H YDC3330S/H YDC3340 YDC3360 YDC3380
Capacity (VA/Watts) 10k / 9k 15k / 13.5k 20k / 18k 30k / 27k 40k / 36k 60k / 54k 80k / 72k
INPUT
Nominal voltage 380/400/415Vac, (3Ph+N+PE)
Operating voltage range 208 - 478Vac
Operating frequency range 45 - 55Hz at 50Hz / 54 - 66Hz at 60Hz (auto sensing) 40 - 70Hz
Power factor ≥0.99
380Vac Max.voltage: +25%(optional +10%,+15%,+20% )
400Vac Max.voltage: +20%(optional +10%,+15% )
Bypass voltage range
415Vac Max.voltage: +15%(optional +10% )
Min. voltage: -45% (optional -20%,-30%)
Bypass frequency range Frequency synchronize tracing range: ±10%
ECO range Same as bypass
Harmonic distortion (THDi) ≤3% (100%non-linear load )
OUTPUT
Output voltage 380/400/415Vac (3Ph+N+PE)
Power factor 0.9
Voltage regulation ±1%
Line Mode ±1%/±2%/±4%/±5%/±10% of the rated frequency(optional)
Frequency
Bat. Mode 50/60(±0.1)Hz
Crest factor 3:1
≤2% with linear load
Harmonic distortion (THD)
≤5% with non linear load
Efficiency 93.50% 94.5%
BATTERY

Standard unit: Standard unit:


Standard unit: ±120Vdc (2x20pcs ±120Vdc(3x20pcs
±120Vdc (20pcs
12V9AH); 12V9AH); 12V9AH); Optional Voltage:±192V/±204V/±216V/±228V/
Battery voltage Long run unit Optional Long run unit Optional
Long run unit : ±240Vdc(32/34/36/38/40pcs optional)
Voltage:±96V/±108V/±120Vdc Voltage:±96V/±108V
±96V/±108V/
(16/18/20pcs optional) /±120Vdc (16/18/
±120Vdc (16/18 /
20pcs optional) 20pcs optional)

Charge Current(A) Standard unit: Standard unit:


1.35A Standard unit: 2.7A 4.05A
(charge current can be set according Max.current 15A Max.current 30A Max.current 30A
Long run unit: Long run unit: Max.current 10A Long run unit:
to battery capacity installed) Max.current 10A Max.current 15A
SYSTEM FEATURES
Transfer time Utility to Battery : 0ms; Utility to bypass: 0ms
Overload Load≤110%: last 60min,≤125%: last 10min,≤150%: last 1min,≥150% change to bypass.
Short circuit Hold Whole Syetem
USB,RS232, RS485, Parallel port, REPO port, Coupler dry contact, Intelligent slot,
Communication
SNMP card (optional), Relay card (optional).LBS port (only 60~80k)
ENVIRONMENTAL
Operating temperature 0 - 40 ℃
Storage temperature -25 - 55 ℃(No battery)
Humidity range 0 - 95% (Non condensing)
Altitude < 1500m.When>1500m,lower the rated power for use
Noise level <55dB <58dB <63dB
PHYSICAL
Dimension D×W×H (mm) 828x250x868 828x360x868
Net weight (kg) 115/57 170/63 171/64 223/71 73 118 122
STANDARDS
Safety IEC/EN62040-1,IEC/EN60950-1
EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8