International FireStop

Handbook

Contacts Your dealer

fischerwerke GmbH & Co. KG Phone: +49 7443 12-0


Klaus-Fischer-Straße 1 E-mail [email protected]
72178 Waldachtal www.fischer.de
Germany

fischer fixings UK Ltd. Phone: +44 1491 827900


Whitely Road Fax: +44 1491 827953
Oxon OX10 9AT Wallingford E-mail [email protected]
Great Britain www.fischer.co.uk

fischer Systems Asia Pte. Ltd. Phone: +65 62 85 22 07


150 Kampong Ampat Fax: +65 62 85 83 10
#04-03 KA Centre E-mail [email protected]
Singapore 368324
536316 (4) · 06/2019 · V-MKS/EL · Printed in Germany

www.fischer-international.com 4 048962 247251


The information in this catalogue is non-binding. Our technical service
department can provide you with additional information and advice.
However you will need to provide an accurate description of your particular
application.
All information in this catalogue must be adjusted to local conditions and
materials used. If individual items and types are not listed with detailed
performance specifications, please contact your local fischer representative
for further consultation.
Subject to errors, technical and product line changes, liability for printing
errors and omissions is excluded.
Product details are correct at time sent to print.

© fischerwerke GmbH & Co. KG


Dear Partners,

Construction fire prevention plays a crucial role in case of fire, which is why the fischer
Group of Companies has developed the fischer FireStop range. The wide range of
passive fire protection products helps to reduce the spread of fire, smoke and toxic
gasses while protecting the lives of occupants as well as the infrastructure. The
development of the product range is the result of over 70 years of experience in the
construction industry and suggestions which arose from close cooperation with
customers and other industry experts. The systems have been tested to both European
and international standards, with many achieving European Technical Approval (ETA)
as well as Underwriters Laboratories (UL) certification.

The broad FireStop range comprises particularly easy to install solutions for effective
fire protection in all relevant fields of application in modern construction projects.
These include facade applications for curtain walls and rainscreen cladding, service
penetrations and solutions for linear gap sealing.

With its numerous services fischer also provides support throughout all construction
phases – from consultations, layout design and training to on-site installation support.
fischer is therefore a reliable partner for passive fire protection for all those involved in
the project.

This international FireStop catalogue serves as your guide for construction fire
protection. Intuitively find the right solutions and the most suitable sealing systems for
simple and more complex applications. The updated catalogue features a clear
overview of the latest products, installation graphics, calculation tables and an index for
approvals and testing.

We hope you enjoy discovering and using our products.

Marc-Sven Mengis
CEO of the fischer Group of Companies

3
4
Content

Service 1
Good reasons to choose fischer 6-7
Basic knowledge FireStop 8-9
Standards and certifications 10
Advanced product selection guide 11
FireStop in practice 12 - 13

Products 2
Intumescent Acoustic Mastic FiAM 14-15
Intumescent Acoustic Mastic FiAM US 16-17
Fire Rated Silicone Sealant FFRS 18-19
Rapid Fire Seal RFS 640 20-21
Fire | Barr ElastoSeal FFB-ES 22-23
Universal FireStopping Sealant UFS 310 24-25
Intumescent Graphite Mastic FiGM 26-27
Foam Barrier System PLUS 28-29
Intumescent Pipe Wrap FIPW 30-31
Intumescent Wrap Strip FiWS 32-33
Fire Collar FFC 34-35
Cast in Device FCID 36-37
Intumescent Pillows FIP 38-39
Intumescent Putty Pad FiPP 40-41
Coated Panel System FCPS 42-43
FireStop Compound FFSC 44-45
VentiStop Cavity Barrier FFB VS 46-47
Cavity FireStop Clad FCFcl 48-49
FireStop Foam 50-51
Thermal Defense Wrap TDW 52-53
Cable Coating FCC 54-55
Tools and accessories 56

Additional information 3
Sprinkler systems 58-59
Fireproof mounting 60-61
Fixings guide 58-69
Calculation of consumption guide 70-71
Training certification 72
Engineering judgement request form 73

5
Good reasons to choose fischer

A brand and its promise to perform


Whoever chooses fischer receives more than a range of safe With the fischer ProcessSystem (fPS), we ensure that we are
products. The aim is to always develop the best solutions for our adapting and optimising our processes in line with customer
customers across the globe. requirements in a flexible manner and on a continuous basis.
Besides the innovative products, this predominantly concerns
support that is focused on the customer, and services designed to
improve customer benefit.

Always with its finger on the pulse of the times


At fischer, innovation is more than just a sum of the patents. We Be it new production procedures or materials, such as renewable
are open to new things and are prepared for change – always with raw materials: We are carrying out the research for your safety and
the aim of offering our customers the greatest possible benefits. will continue to do so in the future. This gives us such great
Over the years, our own development and production sites have flexibility that we can even develop tailor-made customer
been developing numerous fixing solutions for the most wide- solutions. This power to innovate has seen fischer become market
ranging applications. leader in anchor technology and the fixing industry.

Safety that connects – Decisive quality


We don’t make any compromises when it comes to the safety of
our products. A whole host of our products are
distinguished by comprehensive, up-to-date and international ap-
provals. The fischer product range is well-positioned in all sectors
of fixing technology –
Steel, Nylon and Chemical fixings.
In award-winning quality which
ETA-98/004
continues to impress both ETAG 001- 3

professional clients and private Option 1 für gerissenen Beton

customers with equal measure.

6
Good reasons to choose fischer

We take responsibility
Our active environment management policy means that we are
helping to maintain an intact environment for our generation and
for those that follow. The environment management policy at the
Tumlingen site has been certified in line with DIN EN ISO 14001.
We are a member of the German Sustainable Building Council
(DGNB), and our products have been successively certified in line
with the guidelines provided by the Institute for Construction and
the Environment (IBU). With our greenline products, we have
introduced the first fixing assortment in the market, based on over
50% of regrowing raw materials.

Our service to you


We are a reliable partner, one that will stand at your side and „„ Qualified technical consulting for economical and compliant
address your individual requirements with advice and action: fastening solutions. Also on-site at the construction site
„„ Our products range from chemical systems to steel anchors requested.
through to plastic anchors. „„ Training sessions, some with accreditation, at your premises or
„„ Competence and innovation through own research, at the fischer ACADEMY.
development and production. „„ Design and construction software for demanding applications.
„„ Global presence and active sales service in over 100 countries.

7
Basic knowledge FireStop

1
Fire prevention
Basic knowledge FireStop

Fire prevention is a critical consideration for those who are responsible for creating the design, specification and construction of new
buildings, with consideration in the ongoing maintenance of occupied premises.
As the causes of fire vary and are often unpredictable, construction measures are being designed to influence the formation and spread
of fire, smoke and toxic gases, by minimising the available factors needed to create a fire or to limit the spread of fire once it has started.
Effective fire fighting within a building is generally achieved through a combination of active and passive FireStop systems and, when
used in conjunction with each other, provide a balanced fire protection strategy.

Active FireStop systems


Active fire prevention systems are designed to react to the outbreak of a fire, which is then suppressed with the help of sprinkler sys-
tems, halogen installations, fire extinguishers or other proactive mechanical systems. The effects of the fire may also be lessened by the
removal of smoke from the equation. By including alarms and emergency lighting, active systems also serve to provide escape paths for
people inside the building.

Passive fire prevention systems


Passive fire prevention is an integral component, which is designed and built in to the fabric of the structure. It is also an essential
element of the fire safety of a building. The risk of fire can be minimised by dividing the building into a series of compartment/cells
bounded by fire rated walls and floors.
To maintain the firestopping integrity of a compartment/cells, any gaps, openings, void or channels within the fire rated walls or floors
must be sealed with an approved or certfied system to prevent the passage of fire, smoke and toxic gases.

Building codes and national regulations


Most model building codes have very clear requirements on passive fire protection.
“Fire investigation reports have consistently shown that unprotected or improperly protected penetrations and joints cause millions
in property damage and contribute to the loss of life and injuries due to the uncontrolled migration of fire, smoke and toxic gases.” In
order to promote life safety and property protection, the national building codes include fire testing and performance requirements for
penetration firestop and fire resistive joint systems.
The following regulations are published as statutory instruments by Parliament with respect to life safety purposes:

ENGLAND AND WALES: 1991 BS 7671: 2008: UNITED KINGDOM


Section 11.2 of Approved Document B3 states: “If a fire The 17th edition of the IEE Wiring Regulations (BS
separating element is to be effective, then every joint, or im- 7671:2008) is the national standard in the United Kingdom
perfection of fit, or opening to allow services to pass through for all commercial, domestic and industrial wiring installa-
the element, should be adequately protected by sealing or tions.
fire stopping so that the fire resistance of the element is not Section: 527-02-01 states “Where a wiring system passes
impaired” through elements of building construction such as floors,
Section 11.12 adds, under the heading of ‘Fire stopping’, a walls, roofs, ceilings, partitions or cavity barriers the open-
requirement that: “Joints between fire separating elements ings remaining after passage of the wiring systems shall be
should be fire stopped; and all openings for pipes, ducts, sealed according to the degree of fire resistance required of
conduits or cables to pass through any part of a fire separat- the element concerned.”
ing element should be: Section: 527-02-02 states “where a wiring system such
Kept as few in number as possible and kept as small as prac- as conduit, cable ducting, cable trunking, busbar or busbar
tical fire-stopped (which in the case of a pipe or duct, should trunking penetrates an element of building construction
allow for thermal movement)” having specified fire resistance it shall be internally sealed so
as to maintain the degree of fire resistance of the respective
element as well as being externally sealed to maintain the
required fire resistance.”

8
Basic knowledge FireStop

Basic knowledge FireStop


GERMANY: FEDERAL STATE BUILDING ORDER Conference of Building Officials (ICBO) covered the West
In Germany, the Federal State Building Order is regulated Coast and across to most of the Midwest. After three years
at the level of the federal states. Therefore, there are 16 of extensive research and development, the first edition of
regional state building codes with their own regulations and the International Building Code was published in 1997.
guidelines. The 2002 Directive Building Code and the 2005 The code was patterned on three legacy codes previously
Directive Guidelines for conduit and ventilation systems form developed by the organizations (BOCA, SBCCI, ICBO) that
the basis for further consideration. The list of the Technical constitute IBC. By the year 2000, ICC had completed the
Building Regulations – M-ETB, includes other codes, such as International Codes series. Relevant firestop requirements
the MLAR and the German Ventilation Systems Directive – can be found in below mentioned references:
MLüAR. Once guidelines are adopted into the list at regional 702 Definitions
state level List of Technical Building Regulations–LTB, the 704.9 Separation of Vertical Openings - Sprinkler Exception
guidelines become legally binding. 708 Fire Partitions 1 Hour Rating
709 Smoke Barriers 1 Hour Rating
NFPA 101 LIFE SAFETY CODE: UNITED STATES 710 Horizontal Assemblies
Life Safety Code addresses those construction, protection, 711 Penetrations (General)
and occupancy features necessary to minimise danger to 711.3.2 Sprinkler Heads Electrical Boxes
life from the effects of fire, including smoke, heat, and toxic 711.4.1.2 „F“ & „T“ Rating Requirements
gases created during a fire. The Code establishes minimum 712 Fire-Resistant Joint Systems
criteria for the designs of egress facilities, so as to allow 712.4 Curtain Wall to Edge of Slab
prompt escape of occupants from buildings or, where desira-
ble, into safe areas within buildings. The Code also addresses OTHER RELEVANT CODES FROM IBC:
protective features and systems, building services, operating UNITED STATES
features, maintenance activities, and other provisions in The International Building Code and International Residential
recognition of the fact that achieving an acceptable degree Code are just a few of the comprehensive I-Codes the Code
of life safety depends on additional safeguards to provide Council has created. The publications of the codes allow for
adequate egress time or protection for people exposed to easier following from members and allow them to observe
fire. Relevant firestop requirements can be found in below and study the model code. Some of these codes have spe-
mentioned references: cific practices, such as the International Fire Code and the
8.2.2 Compartmentation Continuity International Green Construction Code, or the IGCC. Here is
8.2.3.2.4 Penetrations and Openings In Fire barriers the current list of I-Codes developed and published by the
8.2.4.4 Penetrations and Openings In Smoke Partitions Code Council:
8.3.2 Continuity of Smoke Barriers International Building Code
International Residential Code
NFPA 5000 BUILDING CONSTRUCTION AND International Fire Code
SAFETYCODE International Plumbing Code
NFPA 5000 – Building Construction and Safety Code is a International Mechanical Code
model building code developed by the National Fire Pro- International Fuel Gas Code
tection Association. For the most part, the requirements International Energy Conservation Code
for fire stops are the same in NFPA 5000 as they are in the IBC Performance Code
IBC. It also addresses joints between assemblies in a similar International Wildland Urban Interface Code
manner to the IBC. NFPA 5000 states openings must be International Existing Building Code
protected by „a system or material capable of restricting the International Property Maintenance Code
transfer of smoke“. It addresses protection for through-pen- International Private Sewage Disposal Code
etrations and membrane penetrations in Section 8.8 using International Zoning Code
the same test methods as the IBC. The requirements for F International Green Construction Code
and T ratings are also the same. Joint systems, including
perimeter joints at curtain walls, are addressed in the same OTHER RELEVANT CODE
manner as the IBC. NFPA is responsible for 300 codes and standards that are
designed to minimize the risk and effects of fire by estab-
IBC INTERNATIONAL BUILDING CODE: lishing criteria for building, processing, design, service, and
UNITED STATES installation.
In the Past: The Regional Model codes developed by the Some of the other widely used NFPA codes are:
Building Officials Code Administrators International (BOCA) NFPA 70 NEC – National Electrical Code
were used on the East Coast and throughout the Midwest NFPA 96 - Standard for Ventilation Control and Fire Protec-
of the United States, while the codes from the Southern tion of Commercial Cooking Operations.
Building Code Congress International (SBCCI) were used in NFPA 221 - Standard for High Challenge Fire Walls, Fire
the Southeast and the codes published by the International Walls, and Fire Barrier Walls

9
Standards and certifications

1
Approvals, markings and their importance
Standards and certifications

British Standard BS 476-20:1987 BS EN ISO 10140:2010


BS EN ISO 10140
Fire tests on building materials and The laboratory measurement
BS 476-20 structures. Method for determination of airborne sound insulation of
of the fire resistance of elements of buildng elements.
construction (general principles).

BS EN 1026: 2000
BS EN 1026
BS EN13501-1 EN13501-1:2007+A1:2009 Air permeability test method.
Fire classification of construction
products and building elements.
Reaction to Fire. BS EN 1027: 2000
BS EN 1027
Water permeability test method.

EN13501-2:2007+A1:2009
BS EN13501-2
Fire classification of construction CE marking is a declaration
products and building elements. by the manufacturer (through
Resistance to Fire. verified testing) that the product
ETA-XX/XXXX
ETAG XXX- X meets all the appropriate provi-
XXX
sions of the relevant legislations
EN1366-3:2004 implementing certain European
BS EN1366-3: 2004 Directives. ETA - The European
Fire resistance tests for service
installations - Penetration seals. Technical Assessment provides
information about the construc-
tion product to be declared in
relation to its essential charac-
EN1366-4:2006 teristics.
BS EN1366-4: 2006
Fire resistance tests for service
installations - Linear joint seals.
UL is an abbreviation for Under-
writers Laboratories Inc. which
DIN 4102:Part1 is an independant, not for profit
product safety testing and certifi-
DIN Fire behaviour of building material
cation organisation.
and elements - Part 1: Building
materials, concepts.

UL-EU Mark is intended for use


ASTM E 84 on products destined for the
American Standard European marketplace.
Test method for Surface Burning
ASTM E 84 (UL 723) Characteristics of Building materials.
The test evaluates the spread of
flame along the surface of the FM Approvals is an international
material. It is not a resistance test. leader in third-party certification
and approval of commercial and
industrial products.

ASTM E 1966
American Standard
Test method for Fire-Resistive Joint
ASTM E 1966 Certifire is an independant Third
Systems. This test is used to evaluate
(UL 2079) Party Certification organisation.
the performance of a joint after a
The scheme undertakes require-
cyclic movement test and fire
ments such as the manufacturing
exposure test.
of products under a Third Party
UL 2079 - equivalent. APPROVED PRODUCT
CF xxxx Quality Management System,
Independent Audit Testing, and a
Comprehensive Field of Applica-
ASTM E 814 tions document based on careful
American Standard chosen test that helps to ensure
Test method for Fire Tests of Through
the products and systems are
ASTM E 814 (UL 1479) Penetrations Fire Stops. This test is
used within their approval scope.
used to evaluate the performance of
a firestop system, following fire expo-
sure a hose stream test is conducted.
UL 1479 - equivalent.

10
Advanced product selection guide

Advanced product selection guide


Tested to Approved to Application Page
Product ■ ■ ■

ASTM E 1966 (UL 2079)


ASTM E 814 (UL 1479)

Cable and cable trays


ASTM E84 (UL 723)

Non-metallic pipes
Construction joint

Insulated air ducts


Certifire approved
BS 476: Part 20

ETA/CE marking

Perimeter joints

Insulated pipes
BS EN 1366-3

BS EN 1366-4

Metallic pipes
FM approval
UL approved
DIN 4102

AS 1530

Air ducts
Intumescent Acoustic Mastic ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ 14
FiAM
Intumescent Acoustic Mastic ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ 16
FiAM US
Fire Rated Silicone Sealant ■ ■ ■ ■ ■ 18
FFRS

Rapid Fire Seal RFS 640 ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ 20

Fire | Barr ElastoSeal FFB-ES ■ ■ ■ ■ ■ 22

Universal FireStopping ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ 24
Sealant UFS 310
Intumescent Graphite Mastic ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ 26
FiGM

Foam Barrier System PLUS ■ ■ ■ ■ 28

Intumescent Pipe Wrap FiPW ■ ■ ■ ■ ■ ■ 30

Intumescent Wrap Strip FiWS ■ ■ ■ ■ ■ ■ ■ 32

Fire Collar FFC ■ ■ ■ ■ ■ 34

Cast in Device FCID ■ ■ ■ 36

Intumescent Pillows FiP ■ ■ ■ ■ ■ ■ ■ 38

Intumescent Putty Pad FiPP ■ ■ ■ 40

Coated Panel System FCPS ■ ■ ■ ■ ■ ■ ■ ■ ■ 42

FireStop Compound FFSC ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ 44

VentiStop Cavity Barrier ■ ■ ■ ■ 46


FFB VS

Cavity FireStop Clad FCFcl ■ ■ ■ ■ ■ ■ 48

FireStop Foam ■ ■ ■ ■ 50

Thermal Defense Wrap DTW ■ ■ ■ ■ ■ ■ ■ ■ 52

11
FireStop in practice

FCPS / FPC / FiAM / FFC

RFS 640 / FBB-ES

FireStop Foam

UFS 310 / FiAM (US) /


FiGM

FiAM (US) / FFRS /


FiPP / UFS 310 / FiGM FiP FBB-ES / RFS 640 /
FireStop Foam

FiAM (US) Intumescent Acoustic Mastic Page 14 / 16 UFS 310 Universal FireStopping Sealant Page 24
FFRS Fire Rated Silicone Sealant Page 18 FiGM Intumescent Graphite Mastic Page 26
RFS 640 Rapid Fire Seal Page 20 FiPW Intumescent Pipe Wrap Page 30
12 FFB-ES Fire | Barr ElastoSeal Page 22 FiWS Intumescent Wrap Strip Page 32
FireStop in practice

FFB VS / FCFcL

RFS 640 / UFS 310 /


FiGM / FCPS

FCID

FiWS / FFC

RFS 640 / UFS 310 / FiWS / FiPW / FFSC /


FFSC / FCPS FiAM
FiGM / FCPS

FFC Fire Collar Page 34 FCPS Coated Panel System Page 42


FCID Cast in Device Page 36 FFSC FireStop Compound Page 44
FiP Intumescent Pillows Page 38 FFB VS VentiStop Cavity Barrier Page 46
FiPP Intumescent Putty Pad Page 40 FCFcl Cavity FireStop Clad Page 48 13
Intumescent Acoustic Mastic FiAM

Flexible fire resistant acoustic mastic

2 Construction joints Non combustible services

BUILDING MATERIALS ASSESSMENT/APPROVAL


Products

▪▪ Flexible wall constructions


▪▪ Rigid floor and wall constructions
▪▪ Masonry
▪▪ Concrete
▪▪ Timber
▪▪ Steel
▪▪ FCPS System

ADVANTAGES APPLICATIONS FUNCTIONING


▪▪ Water based ▪▪ Metallic pipes: 6“ (159 mm) ▪▪ FiAM is a one-part water-based acrylic
▪▪ Low VOC ▪▪ Cable trays: 18“ x 2“ (450 x 50 mm) emulsion.
▪▪ Movement capability ± 25 % ▪▪ Cable bunches: 3“ (80 mm) ▪▪ It has a fire resistance of up to 5 hours
▪▪ Excellent acoustic properties ▪▪ Linear joints: flexible and rigid con- when used in construction joints and
▪▪ Approved for infinite linear gap length struction elements services in both vertical and horizontal
▪▪ Halogen and solvent free ▪▪ Joints between FCPS coated panel applications.
▪▪ Paintable and excellent slump charac- system ▪▪ When exposed to fire, it reacts to form
teristics a highly insulative char that slows
down heat transfer and provides a
barrier to fire seal.
▪▪ It is suitably compatible in a variety
of materials, and is utilised within the
FCPS which is designed to seal large
openings in fire rated floors and walls.

14
Intumescent Acoustic Mastic FiAM

INSTALLATION

1. Clean all surfaces free from loose debris and contaminants and install required backing material.
2. Apply FiAM to required parameters as per approved system, making sure that it is in contact with all surfaces to provide maximum adhesion.
3. Tool sealant to a defect-free finish using a wetted trowel or putty knife.

SPECIFICATIONS
Item Art.-No. Languages on the cartridge Contents Suitable for use with Sales unit
[ml] [pcs]
FiAM 310 053011 DE, FR, EN, IT 310 — 25
FiAM 310 538152 DK, FI, SE, NO 310 — 25
FiAM 310 538150 TR, PT, ES, NL 310 — 25
FiAM 310 538151 PL, SK, CZ, HU 310 — 25
FiAM 600 056006 — 600 —
FiAM 310, FFRS 310, UFS
25 2
KP M2 053117 — — 1
310, FiGM 310

Products
Applicator gun 600 ml 097967 — — FiAM 600 1
All items are available in grey and are subject to minimum order requirement.

TECHNICAL DATA
Chemical base Water-based acrylic
Relative gravity Approx 1.6 g/cm3
Skin-forming time Approx 10 minutes at 23 °C RH
Curing rate Approx 1.5 mm per 24 hours*
Storage temperature +5 °C to +25 °C
Movement capability ± 25 %
Slump Nil up to 30 mm
Shelf-life 18 months (under recommended conditions)
pH Value 8 - 9.5
Sound transmission class (Rw partition and specimen) 63 dB
Yield per l/m Depending on application
Colour White, grey
European Technical Approval ETA 14-0378, ETA 14-0379
CE marking 1121-CPR-JA5044
* Curing rate is dependent on substrate, air humidity and weather conditions.

APPLICATION DATA
Joint width Joint depth Yield per linear metres
B A B
A [mm] [mm]
30 20 0.5
A 20 15 1
B
15 8 1.25
10 10 3
6 6 4.25

Substrate Max. joint width Fire ratings


Integrity rating Insulation rating
[mm] [minutes] [minutes]
Concrete/concrete 60 240 240
Brick/concrete 25 240 30
Steel/blockwork 50 300 90
Hardwood/blockwork 50 60 60
Softwood/blockwork 25 30 30
Drywall/concrete/head detail 20 120 120

Service type size Fire ratings


Integrity rating Insulation rating*
[minutes] [minutes]
Copper/steel/metal pipes 14 - 159 mm diam. Up to 120 Up to 90
Loaded cable tray 450 x 50 (tray) cables to 21 mm Up to 120 Up to 90
Single/bunched cables 30 - 80 mm diam. cables Up to 90 Up to 90
* Copper, steel and metal pipes with an insulation rating of up to 90 minutes are in conjunction with the Thermal Defense Wrap (TDW).

15
Intumescent Acoustic Mastic FiAM US

General purpose fire resistant sealant designed for UL specific


applications

2 Non combustible services Top of wall construction joint

BUILDING MATERIALS ASSESSMENT/APPROVAL


Products

▪▪ Flexible wall constructions


▪▪ Rigid floor and wall constructions
▪▪ Masonry
▪▪ Concrete
▪▪ Steel

ADVANTAGES APPLICATIONS FUNCTIONING


▪▪ Water based ▪▪ Linear joints: flexible and rigid ▪▪ The FiAM US is a one-part water
▪▪ Excellent acoustic properties construction elements with dynamic based fire resistant sealant designed
▪▪ Low VOC movement for a wide range of UL listed applica-
▪▪ Halogen and solvent free ▪▪ Metallic pipes tions.
▪▪ Various applications with two products ▪▪ Insulated metallic pipes ▪▪ The FiAM US can be used in con-
only ▪▪ Conduits struction joint and service penetration
▪▪ Age resistant ▪▪ Cable and cable bunches applications.
▪▪ Smoke resistant ▪▪ Cable trays ▪▪ The FiAM US can be used in both
▪▪ Excellent adhesion vertical and horizontal orientation and
▪▪ F-rating up to 3 hrs can be used in conjunction with the
▪▪ T-rating up to 3 hrs FiWS for a wide range of combustible
services.

16
Intumescent Acoustic Mastic FiAM US

INSTALLATION

1. Clean all surfaces free from loose debris and contaminants and install required backing material.
2. Apply FiAM US to required parameters as per approved system, making sure that it is in contact with all surfaces to provide maximum adhesion.
3. Tool sealant to a defect-free finish using a wetted towel or putty knife.

SPECIFICATIONS
Item Art.-No. Languages on the cartridge Contents Suitable for use with Sales unit
[ml] [pcs]
FiAM US 546487 DE, EN, ES, TR 310 — 12
FiAM 310, FFRS 310, UFS
KP M2 053117 — — 1
310, FiGM 310

TECHNICAL DATA 2
Chemical base Water-based elastomeric

Products
Density 12.5 +&/ 0.5 lbs.&gal.
Application temperature 4 °C - 49 °C
Skin-forming time Approx. 20 - 30 min.
Curing rate 3 to 4 weeks at 25 °C
Storage temperature 2 °C - 49 °C
Movement capability Up to 33%
Shelf-life Up to 36 months (under recommended conditions)
pH Value 7-8
Sound translission class (dB)
65 dB (STC)
Tested in a UL 411 wall assembly to ASTM E90
Surface burning characteristics Flame spread: 10
ASTM E84 UL 723 Tunnel Test Smoke: 10
Colour Red

APPLICATION DATA
Joint width Joint depth Linear metres per cartridge
B A B
A [mm] [mm]
30 20 0.5
A 20 15 1
B
15 8 2.6
10 10 3
6 10 5.1

17
Fire Rated Silicone Sealant FFRS

Elastomeric fire resistant sealant

2 Wall to wall construction joint Top of wall construction joint

BUILDING MATERIALS ASSESSMENT/APPROVAL


Products

▪▪ Concrete
▪▪ Masonry
▪▪ Steel
▪▪ Timber

ADVANTAGES APPLICATIONS FUNCTIONING


▪▪ Excellent acoustic properties ▪▪ General construction joints in floor ▪▪ FFRS is a one part silicone based
▪▪ Primerless adhesion to most substra- to floor, wall to wall, floor to wall and sealant that can provide up to 5 hours
tes head of wall 2” (50 mm) fire resistance when used in construc-
▪▪ Approved for infinite linear gap length ▪▪ Internal and external applications tion joints.
▪▪ Halogen and solvent free ▪▪ It provides primerless adhesion to a
▪▪ Excellent slump characteristics wide range of porous and non-porous
▪▪ Movement capability ± 25 % substrates.

18
Fire Rated Silicone Sealant FFRS

INSTALLATION

1. Clean all surfaces free from loose debris and contaminants and install required backing material.
2. Apply FFRS to required parameters as per approved system, making sure that it is in contact with all surfaces to provide maximum adhesion.
3. Tool sealant to a defect-free finish using a wetted trowel or putty knife.

SPECIFICATIONS
Item Art.-No. Languages on the cartridge Contents Suitable for use with Sales unit

[ml] [pcs]
FFRS White 310 ml 512374 DE, FR, EN, IT 310 — 12
FFRS White 310 ml 538140 DK, FI, SE, NO 310 — 12
FFRS White 310 ml 538138 TR, PT, ES, NL 310 — 12
FFRS White 310 ml 538139 PL, SK, CZ, HU 310 — 12 2
FiAM 310, FFRS 310, UFS
KP M2 053117 — — 1
310, FiGM 310

Products
All items are available in grey and are subject to minimum order requirement.

TECHNICAL DATA
Cure system Alcoxy
Relative gravity 1.17 kg/m3
Skinning time Approx. 5/10 minutes (at 25 °C and 50 % relative humidity)
Tack free time Approx. 20 minutes (at 25 °C and 50 % relative humidity)
Full cure Approx. 2 - 3 mm per 24 hours (at 25 °C and 50 % relative humidity)
Shore a hardness 16
Extrudability g/min 55 (standard NMRPS 495A 3 mm/3 bars)
Movement accommodation ± 25 %
Application temperature range +5 °C to +40 °C
Service temperature range Range: -50 °C to +150 °C - must not be stored above 35 °C
Shelf life Up to 12 months when stored in unopened cartridges under cool, dry conditions
Colour White, grey, black
European Technical Approval ETA 15-0799
Elastic recovery > 90 %
Slump Nil up to 30 mm
Sound transmission class (Rw partition and specimen) 38 dB
The cured sealant is unaffected by water, dilute acids and alkalis, soap and household detergents. Certain solvents may soften and swell the cured rubber on prolonged contact.

APPLICATION DATA
Joint width Joint depth Yield per linear metres
A B
A B [mm] [mm]
30 20 0.5
A 20 15 1
B 15 8 1.25
10 10 3
6 6 4.25
Above provides approx. yield from 1 x 310 ml cartridge

Substrate Max. joint width Depth of sealant Fire ratings


Integrity rating Insulation rating
[mm] [mm] [minutes] [minutes]
Concrete/concrete 12 6 300 122
Concrete/concrete 30 15 300 86
Concrete/concrete 50 25 300 65
Steel/concrete 12 6 300 48
Steel/concrete 20 15 300 43
Steel/concrete 50 25 300 33
Softwood/concrete 12 6 199 5
Softwood/concrete 30 15 143
Softwood/concrete 12 6 300 69

19
Rapid Fire Seal RFS 640

Rapid fire resistant sealant

2 Head of wall application Curtain wall application

BUILDING MATERIALS ASSESSMENT/APPROVAL


Products

▪▪ Flexible wall constructions


▪▪ Rigid floor and wall constructions
▪▪ Flexible wall
▪▪ Masonry
▪▪ Concrete

ADVANTAGES APPLICATIONS FUNCTIONING


▪▪ Water based ▪▪ Curtain wall/slab edge: 8“ (200 mm) ▪▪ RFS 640 is a spray grade one-part
▪▪ Flexible set ▪▪ Head of wall: 4“ (100 mm) water-based, fire rated sealant, which
▪▪ Contains mould growth inhibitor ▪▪ General construction joints: 8“ (200 has been designed to provide smoke
▪▪ Freeze - thaw capabilities mm) and fire protection on construction
▪▪ Paintable ▪▪ Cable tray: 24“ x 4“ (600 mm x 100 joints and service penetrations in both
▪▪ Accelerated age and humidity tested mm) vertical and horizontal applications.
▪▪ Low VOC ▪▪ Steel pipes: 8“ (200 mm) ▪▪ Provides up to 3 hours fire rating (also
▪▪ Spray or brush applied in accordance with ASTM E 2307).
▪▪ Excellent smoke seal ▪▪ Meeting the new requirements of
▪▪ Water resistant ASTM E 1399, RFS 640 has been
▪▪ Asbestos and solvent free cycled tested up to 500 times.
▪▪ Can be used for internal applications ▪▪ Can be used for internal applications
and for conditions where dynamic and for conditions where dynamic
movement may occur. movement may occur.
▪▪ RFS 640 has also been tested at posi-
tive pressure with a minimum 0.01in.
(2.5 mPa) water i.a.w UL 2079 test
standards.

20
Rapid Fire Seal RFS 640

INSTALLATION

1. Clean all surfaces free from loose debris and contaminants, and install required backing material as per approved system.
2. Apply RFS 640 to the required parameters making sure that it is in contact with all surfaces to provide maximum adhesion.
3. Tool sealant to a defect-free finish using a wetted trowel or putty knife.

SPECIFICATIONS
Item Art.-No. Contents Sales unit
[l] [pcs]
RFS 640 516539 19 1

TECHNICAL DATA
Chemical base Water-based 2
Density Approx 1.25 g/cm3
Application temperature +5 °C to +40 °C

Products
Skin-forming time at 25 °C Approx. 30 - 45 minutes*
Curing time at 25 °C Approx. 5 - 7 days*
Storage temperature +2 °C to +49 °C
Movement capability Up to 50 %**
Water resistant Yes***
Shelf life 36 months from manufacturing (under recommended conditions)
pH Value 7 to 8
Sound transmission class (dB)
65 dB
Tested in a UL 411 wall assembly to ASTM E90
Surface burning characteristics Flame spread: 0
ASTM E 84 UL 723 Tunnel Test Smoke index: 0
Colour Red
* Skin-forming and curing time is dependant on substrate, air humidity and weather conditions.
** Movement capability depends on UL listed system and configuration.
*** Is water resistant in accordance with UL 2079.

APPLICATION DATA
Joint width Joint width Ft/gallon Ft/pail LM/gallon LM/pail

[inch] [mm]
0.25 6 198 1,325 89 404
0.50 13 164 1,099 74 335
0.75 19 141 941 63 287
1.00 25 124 830 56 253
1.25 32 109 731 49 223
2.00 51 82 548 37 167
4.00 102 49 328 22 100
6.00 152 35 233 16 71
8.00 203 27 180 12 55
The above table provides an approx. yield for a coverage of 1/16“ (1.5 mm WFT) with a 1/2“ (12.5 mm) overlap.

21
Fire I Barr ElastoSeal FFB-ES

Elastomeric fire resistant coating for construction joint and


assemblies

2 Curtain wall application Construction joints application

BUILDING MATERIALS ASSESSMENT/APPROVAL


Products

▪▪ Flexible wall constructions


▪▪ Rigid floor and wall constructions
▪▪ Concrete
▪▪ Masonry

ADVANTAGES APPLICATIONS FUNCTIONING


▪▪ Openings up to 20“ (500 mm) wide ▪▪ Linear joints in construction elements ▪▪ FFB-ES is a one-part water-based acry-
▪▪ Movement capabilities of 50 % ▪▪ Floor to floor lic coating, which has been designed
▪▪ Working temperature between -10 °C ▪▪ Wall to wall to provide smoke and fire protection
and 95 °C ▪▪ Head of wall on construction joints in both vertical
▪▪ Can be spray or brush applied ▪▪ Bottom of wall and horizontal applications.
▪▪ Air permability ▪▪ Curtain wall ▪▪ Developed for use on 80 kg/m³ stone
▪▪ Acoustic performance wool base.
▪▪ 80 kg/m³ stone wool base ▪▪ Once applied, it prevents the passage
▪▪ 2.5 mm WFT required of fire and smoke and can contribute
to the acoustic value of a structure bet-
ween fire rated compartments giving
a fire resistance for up to EI 240.

22
Fire I Barr ElastoSeal FFB-ES

INSTALLATION

1. Use rubber gloves and eye protection to avoid skin and eye contact.
2. Cut 80 kg/m3 x 100 mm thick rock wool to suit opening. Allow a minimum of 10 mm compression or 30 % for movement joints.
3. Install Z Brackets at mid section of stone wool for openings in excess of 250 mm.
4. Compress stone wool into opening, ensuring all joints are butted tightly and surface is flush to slab.
5. Apply FFB-ES via spray, brush or trowel, to minimum 2.5 mm WFT, ensuring a minimum of 12 mm overlap to slab and rear of panel/wall.

SPECIFICATIONS
Item Art.-No. Content Colour Sales unit
[kg] [pcs]
FFB-ES/White 520753 20 white 1
FFB-ES/Grey 520755 20 grey 1
FFB-ES/Red 520756 20 red 1 2
Quantity per box is subject to minimum order requirement.

Products
TECHNICAL DATA
Description Water-based, flexible acrylic coating
Colour White = standard/grey and red to order only
Density 1.25 – 1.3 g/cm³
Coating thickness 2.5 mm nominal, wet film thickness
Sealant coverage 2.8 kg/m², 2.24 l/m²
Fire resistance EN1366-4:2006 120 EI
43 dB when installed with one 100 mm thick 80 kg/m³ stone wool and tested to EN10140
Acoustic performance
52 dB when installed with 200 mm thick 80 kg/m³ stone wool and testedTested to EN10140
Air permeability 600 PA positive and negative pressure and tested to EN1026
Water permeability 450 PA positive pressure and tested to EN1027
Container size 20 kg
For optimum results, an airless sprayer should be utilised at a pressure of 90 psi using a spray tip of approx.
Spraying guidance
29 - 35 thou. +5 °C and +32 °C
For long term storage and ease of installation, it is recommended that ElastoSeal be stored indoors and in
Application temperature
dry conditions
Storage temperature between -5 °C and +25 °C. For health and safety details, refer to fischer technical
Storage and disposal
department
Shelf life 12 months from date of manufacture
European Technical Approval ETA 15-0203
CE marking 1121-CPR-JA5065

APPLICATION DATA
Joint width Joint width Ft/gallon Ft/pail LM/gallon LM/pail

[inch] [mm]
0.25 6 119 800 54 244
0.50 13 99 683 44 202
0.75 19 85 567 38 173
1.00 25 73 492 33 150
1.25 32 66 443 30 135
2.00 51 49 328 22 100
4.00 102 31 207 14 63
6.00 152 22 148 10 45
8.00 203 16 108 7 33
The above table provides an approx. yield for a coverage of 2.5 mm Wet Film Thickness (WFT) with a 12.5 mm overlap.
Figures above are approx. guide only.

23
Universal FireStopping Sealant UFS 310

Universal firestopping sealant which is suitable for metallic,


non-metallic services and construction joints

2 Electrical applications Metallic and non-metallic pipes

BUILDING MATERIALS ASSESSMENT/APPROVAL


Products

▪▪ Wall constructions - linear joints


▪▪ Floor constructions - linear joints
▪▪ Flexible wall
▪▪ Masonry
▪▪ Concrete

ADVANTAGES APPLICATIONS FUNCTIONING


▪▪ Water based ▪▪ Metallic services: steel and cast iron ▪▪ UFS 310 is a one-part water-based
▪▪ Flexible set 20“ (500 mm) - copper 6“ (150 mm) intumescent sealant which is used for
▪▪ Contains mould growth inhibitor ▪▪ Non metallic service: PVC 2“ (51 mm sealing construction joints and service
▪▪ Freeze - thaw capabilities open) 3“ (75 mm closed) penetration in both vertical and hori-
▪▪ Paintable ▪▪ Insulated service: 20“ (500 mm) zontal applications.
▪▪ Accelerated age and humidity tested ▪▪ Construction joints: 4“ (100 mm) ▪▪ Up to 4 hours of fire rating can be
▪▪ Low VOC ▪▪ HVAC 100“ (2500 mm) provided.
▪▪ Excellent acoustic properties ▪▪ Cable bunches 4“ (100 mm): busway ▪▪ It exhibits excellent slump characte-
  27“ (686) ristics, is easy to apply and cures to
a flexible set. It is suitable for internal
applications and conditions where
dynamic movement may occur.
▪▪ UFS 310 can be used for most appli-
cation properties.

24
Universal FireStopping Sealant UFS 310

INSTALLATION

1. Clean all contact surfaces so they are free from loose debris and contaminants such as oil, dirt, grease, wax, old sealant, etc.
2. Install the required backing material as per the detailed instruction or approved system under compression.
3. Apply UFS 310 to required parameters as per detailed instruction or approved system, making sure that it is in contact with all surfaces to provide maximum
adhesion.
4. Tool sealant to a defect-free finish using a wetted towel or putty knife.

SPECIFICATIONS
Item Art.-No. Languages on the Contents Contents Suitable for use with Sales unit
cartridge
[ml] [l] [pcs]
UFS 310 516538 DE, FR, EN, NL 310 — — 12
UFS 310 538137 DK, FI, SE, NO 310 — — 12 2
UFS 310 538135 TR, PT, ES, IT 310 — — 12
UFS 310 538136 PL, SK, CZ, HU 310 — — 12

Products
UFS 19 liter bucket 533889 — — 19 — 1
FiAM 310, FFRS 310,
KP M2 053117 — — — 1
UFS 310, FiGM 310

TECHNICAL DATA
Chemical base Water-based elastomeric
Density Approx. 1.31 g/cm3
Application temperature +5 °C to +40 °C
Skin-forming time Approx. 20 - 30 min.
Curing rate Approx. 4 mm in 72 hours*
Storage temperature +2 °C to +49 °C
Movement capability Up to 50 %**
Intumescent activation From 190 °C to 593 °C
Shelf life Up to 36 months (under recommended conditions)
pH Value 6.5 to 7
Sound transmission class (dB)
62 dB
Tested in a UL 411 wall assembly to ASTM E90
Surface burning characteristics Flame spread: 0
ASTM E 84 UL 723 Tunnel Test Smoke index: 0
Colour Red
* Curing rate is dependant on substrate, air humidity and weather conditions.
** Movement capability depends on UL listed system and configuration.

APPLICATION DATA
Services Fire ratings (minutes)

Types Sizes Integrated rating Insulation rating


PVC/CPVC closed pipe systems 3“ (75 mm) 120 120
PVC/CPVC open pipe systems 2“ (50 mm) 120 120
Steel and cast iron pipes 20“ (508 mm) 180 0
Copper pipes 6“ (152 mm) 180 0
Insulated services 20“ (508 mm) 120 120
Construction joints 4“ (100 mm) 120 120
HVAC 100“ (2,500 mm) 120 120
Cable bunches 4“ (100 mm) 120 120
Cable tray/ladder 24“ (600 mm) 120 45
Bus bar 27“ (686 mm) 120 45

25
Intumescent Graphite Mastic FiGM

High performance intumescent graphite fire resistant mastic

2 Cable tray through wall Non-metallic pipes

BUILDING MATERIALS ASSESSMENT/APPROVAL


Products

▪▪ Concrete
▪▪ Masonry
▪▪ Steel
▪▪ Timber

ADVANTAGES APPLICATIONS FUNCTIONING


▪▪ Low VOC ▪▪ Metallic pipes: 6“ (159 mm) ▪▪ FiGM is a one-part water-based flexible
▪▪ Excellent acoustic properties ▪▪ Non-metallic pipes: 5“ (125 mm) acrylic emulsion containing a high
▪▪ Halogen and solvent free ▪▪ Cable bunches: 1“ (21 mm) pressure intumescent graphite, which
▪▪ Excellent slump characteristics ▪▪ Insulated service: 6“ (159 mm) is used to seal service penetrations in
▪▪ Construction joints: 1“ (25 mm) both vertical and horizontal applica-
▪▪ Mixed services tions.
▪▪ It can expand up to 20 times its own
volume and cures to form a resilient,
flexible fire seal.

26
Intumescent Graphite Mastic FiGM

INSTALLATION

1. Clean all contact surfaces so they are free from loose debris and contaminants.
2. Install the required backing material as per the detailed instruction or approved system.
3. For best application results, FiGM should be at room temperature.
4. Apply FiGM to required parameters as per detailed instruction or approved system, making sure that it is in contact with all surfaces to provide maximum
adhesion.
5. Tool sealant to a defect-free finish using a wetted towel or putty knife.
6. Clean all equipment with water immediately after use.

SPECIFICATIONS
Item Art.-No. Languages on the cartridge Contents Suitable for use with Sales unit
[ml] [pcs]
FiGM 310 ml 508765 DE, FR, EN, IT 310 — 25 2
FIGM 310 ml 538147 TR, PT, ES, NL 310 — 25

Products
FiGM 310 ml 538148 PL, SK, CZ, HU 310 — 25
FiGM 310 ml 538149 DK, FI, SE, NO 310 — 25
FiAM 310, FFRS 310, UFS
KP M2 053117 — — 1
310, FiGM 310

TECHNICAL DATA
Form Aqueous thixotropic paste
Density Ca. 1.3g/cm3
Cure rate 1.7 mm per 24 hours dependent on conditions
Application temperature +5 °C to +35 °C
Tack free 30 minutes
Cure system Water-based
U.V. resistance Good
Expansion onset temperature Ca. 180 °C
Expansion Up to 20 times
Skinning time 15 minutes at 25 °C / 50 % RH
Service temp range Store in cool dry conditions between ±5 °C and ±25 °C
Sound transmission (Rw partition and specimen) 64 dB
Shelf life Up to 18 months unopened
European Technical Approval ETA 14/0381
CE marking 1121-CPR-JA5047
The cured sealant is unaffected by water, dilute acids and alkalis, soap and household detergents. Contains a
Chemical and water resistance plasticised acrylic polymer, fire retardant fillers, blowing agents and mirror additives. No component labelled
as dangerous under EEC directives criteria.

APPLICATION DATA
Services Fire ratings (minutes)

Types Sizes Integrated rating Insulation rating


PVC pipe Up to 125 mm diam. 120 120
HDPE pipe Up to 90 mm diam. 120 120
ABS pipe Up to 90 mm diam. 180 120
Insulated copper pipe Up to 60 mm diam. pipe + up to 32 mm insulation 180 120
Cables Up to 21 mm diam. x bunches 10 max 120 120
Mixed Up to 63 mm diam. HDPE + 21 mm diam cables x 10 120 120
Minimum wall thickness = 100 mm

27
Foam Barrier System PLUS

FireStop Foam and FireStop Block for use in a System. Or


individually. ETA approved and UL listed applications.

Mixed penetrations through wall or floor


2 assembly
Cable tray through wall or floor assembly

BUILDING MATERIALS ASSESSMENT/APPROVAL


Products

▪▪ Concrete (wall and floors)


▪▪ Masonry
▪▪ Flexible wall

ADVANTAGES APPLICATIONS FUNCTIONING


▪▪ Easy access for difficult to reach ▪▪ Metallic pipes up to 8 in. (203 mm) ▪▪ FBS is a two component polyurethane
openings ▪▪ Insulated metallic pipes expanding sound, smoke and firestop-
▪▪ Low VOC ▪▪ Conduits ping seal for hard to reach locations
▪▪ Various applications with two products ▪▪ Cable and cable bunches which expands to up to 5 times of its
only ▪▪ Cable trays volume.
▪▪ Age resistant ▪▪ Mixed multiple penetrations ▪▪ FBB are highly elastic mouldable
▪▪ Smoke resistant blocks.
▪▪ Resistant to damp ▪▪ FIB is a glass fiber reinforced intu-
▪▪ Re-enterable and repairable mescent wrap to enhance the insula-
▪▪ Excellent adhesion tion value of ETA applications.
▪▪ No backing material required ▪▪ Tested in accordance with ASTM E
▪▪ F-rating / E-rating up to 2 hours 814 (UL 1479), ASTM E84 (UL 723)
▪▪ T-rating / I-rating up to 2 hours as well as EN 1366-3, EN 13501
the Barrier System PLUS allows an
easy application which saves time and
costs on site.

28
Foam Barrier System PLUS

INSTALLATION

1. Clean all contact surfaces so they are free from loose debris and contaminants.
2. Install the required backing material as per the detailed instruction or approved system.
3. Unscrew cap from cartridge and insert into the dispensing gun.
4. Discard non-uniform initial material.
5. Fill the opening from back to front. Build up the foam from bottom to top.
6. After 2 minutes, tool foam to a defect-free finish using a suitable knife.
7. Cables or pipes that will be installed retroactively can be routed through the existing foam. Refill gaps due to removed cables or pipes with FBS foam.

SPECIFICATIONS
Item Art.-No. Languages on the cartridge Contents Dimensions Sales unit
[ml] [mm] [pcs]
FBS-UL 544079 — 380 — 6 2
FBB-UL FireStop Block 544083 — — 200 mm x 130 mm x 60 mm 12
FBS-EN 544084

Products
DE, FR, EN, IT 380 — 6
FBS-EN 544085 DK, FI, SE, NO 380 — 6
FBS-EN 544086 PL, SK, CZ, HU 380 — 6
FBS-EN 544087 TR, PT, ES, NL 380 — 6
FBB-EN FireStop Block 544088 — — 200 mm x 144 mm x 60 mm 4
FIB Insulating Bandage 544089 — — 5000 mm x 150 mm 1
FFBD Foam Barrier Dispenser 544090 — — — 1

TECHNICAL DATA
Criteria FBS-UL FBS-EN FBB-UL FBB-EN
Density ≥ 215 kg/m³ 240 kg/m³ to 300 kg/m³
Temperature resistance ≤ 80 °C ≤ 80 °C ≤ 80 °C ≤ 80 °C
Construction material class B2 - as per DIN 4102 B2 - as per DIN 4102
Cartridge content 380 ml 380 ml
Yield ≤ 1.9 l ≤ 2.1 l
Cure time Approx. 90 s Approx. 90 s
Colour Red-brown Red-brown Red-brown Red-brown
Pack size Boxed in 6 Boxed in 6 Boxed in 4 Boxed in 18
12 months from date of 12 months from date of
Shelf life
manufacturing manufacturing
Storage Temperature +5 °C to +30 °C +5 °C to +30 °C
Sound Transmission Class 43.5 dB - 66 dB 45.5 dB - 68 dB
Application Temp Range +15 °C to +30 °C +15 °C to +30 °C

APPLICATION DATA - UL
Blank Opening Metallic Pipes and Cables / Cable Trays Insulated Metal Pipes Mixed Penetrations
Conduits

Max 24 in. (610 mm) wide Max 8 in. (203 mm)


Max 32 in. x 32 in. Max 8 in.
Max. possible sizes of penetrants by max 6 in. diameter with 1 in. See listed system
(813 x 813 mm) (203 mm) diameter
(152 mm) deep cable tray (25 mm) insulation
C-AJ-3341; C-AJ-4110;
Barrier System PLUS UL C-AJ-0158, W-L-0052 C-AJ-1669 C-AJ-5383 C-AJ-8260; C-AJ-8261
W-L-4091

APPLICATION DATA - ETA


Seal thickness 144 mm Seal thickness 200 mm

Sheated electrical cables up to 80 mm


Wall: E120 / EI60 - Floor: EI60 Wall / Floor: E120 / EI90
Cable / Cable Trays and Ladders Tied cable bundles up to 100mm
Non-sheated electrical cables Wall: E120 / EI45 - Floor: E60 / EI30 Wall/ Floor E120 / EI60
Condiuts Conduits / pipes of plastic up to a max. diameter of 40 mm Wall: E120 / EI60 - Floor: E60 / EI30 Wall / Floor EI120
Insulated metal pipes with max. diameter of 54 mm Wall: E120 / EI90 - Floor: EI60 Wall / Floor E120 / EI90
Non-insulated metal pipes with max. diameter of 28 mm Wall: E120 / EI60 - Floor: EI60 Wall / Floor E120 / EI90
Pipes Insulated metal pipes with AF/Armaflex insulation up to
Wall: E120 / EI90 - Floor: EI60 Wall / Floor EI120
88.9 mm diameter
Combustible pipes with max. 50 mm diameter Wall: EI120 - Floor: EI60 Wall / Floor EI120
For detailled information please refer to ETA 17/0845. Remaining space around penetrants can be filled with FBB FireStop Block.

29
Intumescent Pipe Wraps FiPW

An intumescent single or endless wrap for sealing flammable


pipes

2 Wall applications Floor application

ASSESSMENT/APPROVAL
Products

ADVANTAGES APPLICATIONS FUNCTIONING


▪▪ Efficient and effective for sealing of ▪▪ Non-metallic pipes ▪▪ FiPW is a flexible composite strip,
pipe openings in floors and walls ▪▪ Polyvinyl Chloride PVC which is composed of thermoplastic
▪▪ Easy to fit ▪▪ Chlorinated Polyvinyl Chloride cPVC component containing intumescent
▪▪ Moisture resistant ▪▪ Medium-density Polyethylene MDPE graphite in a synthetic compound and
▪▪ No mechanical fixing required ▪▪ High-density Polyethylene HDPE enclosed in an outer polyethylene
▪▪ Economical solution ▪▪ Acrylonitrile Butadiene ABS cover.
▪▪ Up to 4 hours fire resistance ▪▪ Can also be used as a cast-in solution.
▪▪ Asbestos and halogen free For large openings, use in conjunction
▪▪ Available on a roll for more flexibility in with FCPS or FFSC.
pipe diameters

30
Intumescent Pipe Wraps FiPW

INSTALLATION

1. Clean all contact surfaces so they are free from loose debris and contaminants.
2. Ensure services are sufficiently supported as per approved system or local building codes.
3. Choose the correct size of FiPW or FiPW-E in accordance with the pipe diameter.
4. Wrap FiPW or FiPW-E around the pipe and fix tightly in required position.
5. Backfill with FiAM or FFSC as per detailed instruction or approved system.

SPECIFICATIONS
Item Art.-No. Fits pipe-Ø Fire rating Sales unit
[pcs]
FiPW E / 2 mm (25 meter roll) 539608 30 - 200 2 1
FIPW 2/30-32 052546 30 - 32 2 20
FIPW 2/38-40 052547 38 - 40 2 20 2
FIPW 2/55 052548 55 2 20
FIPW 2/63 052560

Products
63 2 20
FIPW 2/75 052561 75 2 20
FIPW 2/82 052562 82 2 20
FIPW 2/110 052563 110 2 20
FIPW 2/125 052890 125 2 20
FIPW 2/160 052891 160 2 20
FIPW 2/200 053000 200 2 20

TECHNICAL DATA
State Solid
Colour Black inner component in outer red carrier
Odour Odourless
Density 1.3 kg/m3
Expansion ratio 1 : 25
Significant expansion occurs at temperature > 180 °C
Application temperature -40 °C to 130 °C minutes
Available sizes > 30 mm and max. up to 200 mm
Storage temperature N/a
Shelf life 60 months
Dimensions (thickness x diameter) 4 mm up to 63 mm - 6 mm up to 110 mm - 10 mm thereafter ...; 2 mm for 25 meter roll.

APPLICATION DATA
Configuration for up to 120 min.
Outer pipe diam. No. wraps Thickness Length (theoretically) for FiPW E
[mm] [mm]
40 1 2 126
55 2 4 352
63 2 4 402
Partitions 2 x FiPW 75 2 4 478
82 2 4 521
90 3 6 867
110 3 6 1055
125 4 8 1608
160 4 8 2047
200 5 10 3203

Partitions 2 x FiPW

31
Intumescent Wrap Strip FiWS

Universal intumescent wrap strip for sealing combustible


services

2 Floor application Universal Collar 2

ASSESSMENT/APPROVAL
Products

ADVANTAGES APPLICATIONS FUNCTIONING


▪▪ Efficient and effective for sealing of ▪▪ Non-metallic service: PVC 14“ (355 ▪▪ FiWS is a flexible, intumescent
pipe openings in floors and walls mm), cPVC 8“ (203 mm), ABS 6“ graphite-based synthetic compound
▪▪ Easy to fit (152 mm), FRPP 4“ (102 mm) strip, which has been designed to be
▪▪ Moisture resistant ▪▪ Insulated service: Steel 10“ (254 installed in both vertical and horizontal
▪▪ Freeze-thaw characteristics mm), Iron 10“ (254 mm), Copper 4“ applications.
▪▪ No mechanical fixing required (102 mm), Glass fibre 3“ (75 mm), ▪▪ FiWS has been developed as a PRE or
▪▪ Economical solution AB/PVC flexible foam 1“ (25 mm) cast-in FireStop solution, and has been
▪▪ Up to 4 hours fire resistance ▪▪ Cable bunches: 3“ (76 mm) designed to work with the fischer Uni-
▪▪ Asbestos and halogen free versal Collar for retro fitting or surface
mounted applications.
▪▪ For large openings, the FiWS can be
used in conjunction with the FFSC.

32
Intumescent Wrap Strip FiWS

INSTALLATION

1. Clean all contact surfaces so they are free from loose debris and contaminants.
2. Ensure services are sufficiently supported as per approved system or local building codes.
3. Choose the correct size of FiWS in accordance with the pipe diameter.
4. Wrap FiWS around the pipe and fix it tightly.
5. Backfill with FiAM or FFSC as per approved system.

SPECIFICATIONS
Item Art.-No. Dimensions Sales unit
[mm / inch] [pcs]
FiWS-2 531397 50 mm x 6 mm x 3.66 m / 2˝x 1/4˝ x 12˝ 1
Universal Collar 2 536053 51 mm x 15 m / 2“ x 50 ft 1
2
TECHNICAL DATA

Products
State Solid
Colour Black inner component in outer red carrier
Odour Odourless
Density 1.3 kg/m3
Expansion ratio 1 : 40
Significant expansion occurs at temperature > 190 °C
Application temperature -40 °C to 130 °C
Max. Pipe diameter Max. < 355 mm (14“)
Flame spread (ASTM E 84 - UL723) 5
Smoke index (ASTM E 84 - UL723) 5
Shelf life 5 years = 60 months

APPLICATION DATA
FiWS 2 - typical configuration
Pipe diameter No. of layers No. of stacks for 2“ wraps Length
[mm] [m]
50 1 1 0,34
75 2 1 1,1
100 2 1 1,42
150 3 1 3,18
200 4 1 5,64
305 4 2 16,56
Both sides of the wall

Bottom of floor
Note: For detailled information please refer to the appropriate UL listed systems.

33
Fire Collar FFC

Collar for sealing a wide range of combustible pipes where


passing through fire rated walls and floors

2 Floor applications Wall applications

BUILDING MATERIALS ASSESSMENT/APPROVAL


Products

▪▪ Flexible and rigid wall constructions


▪▪ Solid concrete floors
▪▪ Hollow precast floors

ADVANTAGES APPLICATIONS FUNCTIONING


▪▪ Easy retrofit at any time ▪▪ Non-metallic pipes: like PVC, HDPE, ▪▪ FFC is a powder coated cylindrical
▪▪ Water resistant MDPE, ABS of various sizes through steel sleeve, which contains a heat
▪▪ No minimum annular service required fire rated walls and floor assemblies reactive graphite-based intumescent
▪▪ Pre-fixed attachment lugs material that expands during fire.
▪▪ Fold back tag for secure fixture around ▪▪ Designed to be securely fitted around
pipe the pipe and held in position with a
retaining bolt.
▪▪ Any gaps up to 10 mm around FFC
should be backfilled with FiAM or
larger annular space should be closed
with FCPS or FFSC.

34
Fire Collar FFC

INSTALLATION

1. Clean all contact surfaces so they are free from loose debris and contaminants.
2. Ensure services are sufficiently supported as per approved system or local building codes.
3. Close the annular space as per requirement with FiAM, FCPS or FFSC and choose the correct size of FFC in accordance with the pipe diameter.
4. Open the toggle clip, place FFC around the pipe with its fixing lugs pointing towards the building element.
5. Lock the toggle clip and push it tightly against the surface of building element.
6. Attach the collar to the building element through the mounting lugs with a minimum anchoring depth of 32 mm and minimum 8 mm diameter fixing (please
refer to fischer fire rated fixing section for correct anchor).
7. For vertical applications, repeat installation on both sides as per the instruction in the approved system.

SPECIFICATIONS
Item Art.-No. Dimensions
BxLxH
Sales unit
2
[mm / inch] [pcs]

Products
FFC 2/30-32 052456 30 - 32 1
FFC 2/38-40 052480 38 - 40 1
FFC 2/55 052481 55 1
FFC 2/63 052482 63 1
FFC 2/75 052483 75 1
FFC 2/82 052486 82 1
FFC 2/90 052487 90 1
FFC 2/110 052488 110 1
FFC 2/125 052489 125 1
FFC 2/160 052500 160 1
FFC 2/200 052501 200 1

TECHNICAL DATA
State Solid
Colour Red sleeve with black inner component
Odour Odourless
Fire rating Up to 4 hours
Available sizes > 30 mm and max up to 200 mm
Significant expansion occurs at temperature > 180 °C
Storage temperature N/a
Shelf life N/a

35
Cast in Device FCID

Fast and efficient solution for forming service penetrations


through concrete floors

Installation of FCID within reinforced concrete


2 floor
Installed pipe through FCID device

BUILDING MATERIALS ASSESSMENT/APPROVAL


Products

▪▪ Reinforced cast concrete slabs


▪▪ Some prefabricated slab systems
(subject to design)

ADVANTAGES APPLICATIONS FUNCTIONING


▪▪ Quick installation ▪▪ Sealing and firestopping PVC and ▪▪ FCID is a pass through system, which
▪▪ Watertight seal HDPE pipes up to 6˝ (160 mm) is constructed from a highly resilient
▪▪ Higher tolerance ▪▪ Forms holes up to 10˝ (200 mm) polypropylene material and contains a
▪▪ Easily extendable thick concrete floors powerful intumescent graphite band.
▪▪ Wider base for further connections ▪▪ FCID and MRF creates recesses in ▪▪ The FCID is rugged enough to with-
▪▪ No further collars or wraps required slabs for lower positioning of soil stand the force and load of a concrete
▪▪ Reduce working at heights ▪▪ Manifold units in wet room applicati- pour, yet lightweight enough to permit
▪▪ Cost saving ons easy placement and handling.
▪▪ Reduced foot plate
▪▪ Eco-friendly extension tube
▪▪ Closer proximity positioning

36
Cast in Device FCID

INSTALLATION

1. Position FCID as required and attach to formwork.


For concrete slab thickness greater than 250 mm:
i) Remove end cap from FCID.
ii) Using FCID extension sleeve FCID – E Extension Tube, mark and cut using a fine tooth saw to required length.
iii) Slide extension sleeve over FCID unit until it contacts side ribs.
iv) Apply FCID - E/C Extension Cap to top of the extension sleeve.
v) Position FCID and extension assembly as required and attach to formwork.
For concrete slab thickness less than 250 mm:
i) Cut FCID to required depth of concrete slabs.
ii) Place cover cap FCID - CP Cap Plug on top of FCID.
iii) Position FCID as required and attach to formwork.
2. Pour concrete to required depth.
3. On completion of concrete curing, remove all formwork and shuttering as necessary. 2
4. Remove cap from top of FCID and place pipe through FCID as required.

Products
SPECIFICATIONS
Item Art.-No. Fits pipe-Ø Hight x Shell diam. Sales unit
[pcs]
FCID 65 Cast in Device 509532 Nom 3”/75 mm Pipe 95 mm OD x 250 mm high - base = 154 mm x 154 mm 1
FCID 100 Cast in Device 506324 Nom 4”/110 mm Pipe 140 mm OD x 250 mm high - base = 198 mm x 198 mm 1
FCID 150 Cast in Device 509533 Nom 6”/160 mm Pipe 194 mm OD x 250 mm high - base = 253 mm x 253 mm 1
FCID 65-E/1000 Extension Tube 509791 FCID 65 CI 95 mm ID x 101 mm OD x 1000 mm long 1
FCID 100-E/1000 Extension Tube 509792 FCID 100 CI 140 mm ID x 147 mm OD x 1000 mm long 1
FCID 150-E/1000 Extension Tube 509793 FCID 150 CI 194 mm ID x 201 mm OD x 1000 mm long 1
FCID 65-C Extension Cap 511450 FCID 65-E/1,000 93.5 mm - 96.5 mm tapered OD x 19 mm high 1
FCID 100-C Extension Cap 509794 FCID 100-E/1,000 139 mm - 142.5 mm tapered OD x 25.4 mm high 1
FCID 150-C Extension Cap 511451 FCID 150-E/1,000 194.5 mm - 199 mm tapered OD x 25.4 mm high 1
FCID-MRF Manifold Recess Former 517846 FCID 100 CI 250 mm - 220 mm x 250 mm - 220 mm x 60 mm tapered recess 1
88 mm - 91.5 mm tapered OD x 19.5 mm high
FCID 65-CP Cap Plug 510878 FCID 65 CI 1
131.5 mm - 136 mm tapered OD x 25.4 mm high
FCID 100-CP Cap Plug 510879 FCID 100 CI 131.5 mm - 136 mm tapered OD x 25.4 mm high 1
FCID 150-CP Cap Plug 510880 FCID 150 CI 186 mm - 194 mm tapred OD x 25.4 mm high 1
Note: Details on 4 hours fire rated wraps are available on request.

TECHNICAL DATA
State Solid
Colour Fluorescent yellow
Odour Odourless
Shell material Polyethylene
Fire rating 4 hours - BS 476: Part 20 and AS 1530: Part 4
Suitable for pipe diameter Max up to 150 mm
Standard height 250 mm
Extension or reduction in height possible Yes
Standard flange width Min. 154 mm and max 254 mm
Significant expansion occur at temperature > 160 °C
Storage temperature N/a
Shelf life N/a

37
Intumescent Pillows FiP

FireStop solution for temporary and permanent service


penetrations in both vertical and horizontal applications

2 Wall application Floor application

ASSESSMENT/APPROVAL
Products

ADVANTAGES APPLICATIONS FUNCTIONING


▪▪ Approved as permanent fire barrier ▪▪ Metal pipes ▪▪ FiP is an intumescent graphite and
▪▪ Reusable ▪▪ Cables/cable trays mineral fibre blend covered in a glass
▪▪ Dry installation fibre PVC coated cloth bag.
▪▪ Quick and easy installation ▪▪ FiP is suitable for applications where
▪▪ No shelf life temporary and permanent fire barriers
▪▪ Moisture resistant are required.
▪▪ Up to 2 hours fire protection

38
Intumescent Pillows FiP

INSTALLATION

1. Clean all contact surfaces so they are free from loose debris and contaminants.
2. Ensure services are sufficiently supported as per approved system or local building code.
3. Shake the pillows to make the infill material uniform before installation.
4. Push the pillow into the hole so that the longest dimension spans across the wall. If installing in floor, mechanically fix galvanised steel mesh 50 x 50 x 5
mm to the underside of the opening with a 100 mm overlap of the floor slab.
5. Pack the pillows in a brick bond fashion, to ensure the joints between the pillows are staggered. Use small-sized pillows in between to pack the hole tight
against the edges.
6. For electrical trunking, remove the lid and install a pillow inside so it aligns with the depth of the wall. Replace the lid on the electrical trunking.

SPECIFICATIONS
Item Art.-No. Dimensions
[mm]
Sales unit
[pcs]
2
FiP/S 516960 330 mm x 50 mm x 20 mm 50

Products
FiP/Std 533890 330 mm x 100 mm x 20 mm 25
FiP/M 516959 330 mm x 200 mm x 25 mm 50
FiP/L 516958 330 mm x 200 mm x 45 mm 25

TECHNICAL DATA
State Solid
Colour Black
Odour Odourless
Weight per pillow FiP/S - 80 g, FiP/Std - 120 g, FiP/M - 230 g, FiP/L - 420 g
Volumetric expansion 3 times
Significant expansion occurs at temperature > 140 °C
Remain flexible between -20 °C to 130 °C
European Technical Approval ETA 14-0380
CE marking 1121-CPR-JA5046

ESTIMATION QUANTITIES
Width Length [mm]

Size Large Medium Large Medium Large Medium Large Medium Large Medium Large Medium
[mm] Seal type 100 300 500 700 900 1,000
Wall 3 5 7 13 12 22 17 31 21 39 24 47
200
Floor 2 3 4 7 6 12 9 17 11 22 12 27
Wall 5 9 14 26 24 44 33 61 42 78 47 95
400
Floor 3 5 7 15 12 24 17 34 22 43 24 52
Wall 7 13 21 39 35 65 49 91 63 117 70 143
600
Floor 4 7 11 22 18 36 25 51 33 65 36 79
Wall 9 18 28 52 47 87 66 122 84 157 94 192
800
Floor 5 10 15 29 24 48 34 67 33 87 48 107
Wall 10 22 35 65 59 109 82 152 105 196 117 217
1,000
Floor 6 12 18 36 30 60 42 84 54 108 60 120

39
Intumescent Putty Pad FiPP

Intumescent Putty Pad FiPP

2 External application Internal application

BUILDING MATERIALS ASSESSMENT/APPROVAL


Products

▪▪ Most flexible wall partitions con-


structed from plasterboard/gypsum
board, timber and steel studs

ADVANTAGES APPLICATIONS FUNCTIONING


▪▪ Excellent acoustic properties ▪▪ Most flexible partition assemblies ▪▪ Can maintain the fire resistance and
▪▪ Internal and external versions available ▪▪ Fire and insulation resistance insulation of flexible wall partitions,
▪▪ Primerless adhesion to most sub-▪ ▪▪ Acoustic sealing where they are penetrated by plastic
strates ▪▪ Air permeability or metal electrical outlets and cables.
▪▪ Robust detail part E handbook▪ ▪▪ Plastic and metal electrical outlets ▪▪ FiPP can also be used for upgrading
accepted the acoustic performance of flexible
▪▪ No electrical conductivity partitions.
▪▪ Air permeability
▪▪ Quick and simple installation

40
Intumescent Putty Pad FiPP

INSTALLATION

Internal
1. Remove the face-plates of the electrical outlet.
2. Clean all contact surfaces so they are free from loose debris and contaminants.
3. Mould the preformed putty pads into the back of the box and around the cables.
4. Replace the face-plate.
External
1. Clean all contact surfaces so they are free from loose debris and contaminants.
2. Mould the preformed putty pads onto the back of the box and around the cables.

SPECIFICATIONS
Item Art.-No. Dimensions
[mm]
Colour Fire rating Sales unit
[pcs]
2
FiPP/I-S 053578 170 x 170 red 2 25

Products
FiPP/I-D 054757 230 x 170 red 2 50
FiPP/E-S 506261 155 x 155 red 2 25
FiPP/E-D 506262 210 x 180 red 2 —

TECHNICAL DATA
Base material Drywall
Specific gravity 1.55 kg/m3
Sound transmission class (Rw of partition and specimen) 66 dB
Slump Nil
Application temperature range +4 °C to 40 °C
Service temperature rate -70 °C to 120 °C
Shelf life 18 months

41
Coated Panel System FCPS

FireStop coated panel system for multiple service penetrations

2 Mixed penetration through wall Mixed penetration through floor

ASSESSMENT/APPROVAL
Products

ADVANTAGES APPLICATIONS FUNCTIONING


▪▪ Approved for light partition walls ▪▪ Small and large openings ▪▪ FCPS is a rock fibre core coated with
▪▪ Can be installed dry ▪▪ Cables/cable trays ablative sealant FPC for use in both
▪▪ No coatback required for services ▪▪ Metallic or non-metallic pipes vertical and horizontal applications.
▪▪ Excellent acoustic properties ▪▪ It maintains the sound reduction index
▪▪ Asbestos and halogen free of a structure.
▪▪ The FCPS will allow additional services
to be added or removed and will
accommodate thermal and mechani-
cal movement of services.
▪▪ FPC can be used to adhere sections
of FCPS board when jigsaw assembly
is required and can also be used to
enhances smoke and acoustic perfor-
mance.

42
Coated Panel System FCPS

INSTALLATION

1. If opening size is greater than 1,200 x 1,200 mm then a steel angle for mechanical support should be installed as per detailed instruction or approved
system.
2. Clean all contact surfaces so they are free from loose debris and contaminants.
3. Cut FCPS as per the required opening size, so that it can be fitted under friction into aperture with as few joints as possible.
4. Prior to installation, coat all exposed areas of FCPS with FPC.
5. Install FCPS section into aperture so it is compression fitted.
6. For multiple or mixed services passing through opening please use appropriate fire stopping device:
a. Use FiAM for metallic pipes, cables, cable trays and ducts.
b. Use FiPW for non-metallic pipes.

SPECIFICATIONS
Item Art.-No. Dimensions Contents Contents Suitable for use with Sales unit
2
DxsxLxB

Products
[mm] [l] [ml] [pcs]
FCPS/50 053252 1200 mm x 600 mm x 50 mm — — — 1
FPC/5lt 053253 — 5 — — 1
FiAM 310 053011 — — 310 — 25
FiAM 310, FFRS 310,
KP M2 053117 — — — 1
UFS 310, FiGM 310

TECHNICAL DATA
Dimensions 1200 mm x 600 mm x 50 mm
Density of board 140 kg/m3
Coating thickness 1 mm DFT
Fire resistance Depending on application
23 dB mean reduction up to 56 dB reduction (with one 50 mm FCPS board). 29 dB mean reduction up to
Acoustic performance
65 dB reduction (with two 50 mm FCPS board)
Thermal conductivity (U value) 0.034 W/mK at 10 °C
Maximum size of seal Wall 5.76 m2, floor 2.88 m2
Maximum size unsupported 1.2 m x 1.2 m (no services)
Mechanical support 30 mm x 30 mm x 1.6 mm steel angle
Density of panel coating FPC 1.25 - 1.3 g/cm3
Panel coating FPC coverage 3.5 litres/m2
Shelf life of board N/a
Shelf life of panel coating FPC 12 months
European Technical Approval ETA 14-0388 and ETA 14-0382
CE marking 1121-CPR-JA5050
Note: Please refer to the appropriate approvals for details.

APPLICATION DATA
Services Rigid partition walls Flexible partition walls Concrete floors

[Fire rating - hours] [Fire rating - hours] [Fire rating - hours]


Cable ladder/tray/basket up to 2 up to 2 up to 2
Cables up to 26 mm diameter up to 2 up to 2 up to 2
Cables up to 80 mm diameter up to 2 up to 2 up to 2
Steel/Copper pipes up to 159 mm diameter up to 2 up to 2 n/a
PVC pipes* up to 110 mm diameter up to 1 up to 1 n/a
Blank seals up to 2 up to 2 up to 2
PVC Pipes must be protected in conjunction with FiPW, which must be securely sealed in place within the FCPS.

43
FireStop Compound FFSC

Structural fire resistant seal for floors and walls

2 Mixed service penetrations Mixed service penetrations

ASSESSMENT/APPROVAL
Products

ADVANTAGES APPLICATIONS FUNCTIONING


▪▪ Water based ▪▪ Metallic services with steel and cast ▪▪ FFSC is a specially formulated gypsum
▪▪ Low VOC iron pipes based compound, which when mixed
▪▪ Load bearing ▪▪ Non-metallic services with FiP intu- with water can be trowelled or poured.
▪▪ Excellent acoustic proper-ties mescent pipe wrap or FFC ▪▪ FFSC can provide up to 4 hours inte-
▪▪ Both vertical and horizontal applica- ▪▪ Voids or cavities in floors or walls grity and insulation.
tions ▪▪ Cable bunches ▪▪ Set within 45 min depending on
▪▪ Halogen and asbestos free ambient temperature.
▪▪ Capable of accommodating foot traffic
within 72 hours.

44
FireStop Compound FFSC

INSTALLATION

1. Service penetrations should be rigidly supported as per local building codes or approved standards.
2. Clean all contact surfaces so they are free from loose debris and contaminants such as oil, dirt, grease, wax, old sealant, etc.
3. Pouring: Mix compound with water in 2.5:1 parts by volume. Do not mix weaker than 2:1.
4. Shutter into the opening to ensure a tight fit so that once the required depth of compound is installed, it finishes flush with the floor.
5. Mix and pour compound until the required thickness is achieved.
6. If the opening is greater than 1,200x1,200 mm, appropriate reinforcement may be required.

SPECIFICATIONS
Item Art.-No. Weight Sales unit

[kg] [pcs]
FFSC/20 kg 533247 20 1 2

Products
TECHNICAL DATA
Chemical base Gypsum
Colour Off white
Weight 20 kg
Bulk density 950 kg/m3
Wet density 1,850 kg/m3
Setting time (min) 20
Application temperature range +5 °C to +40 °C
Temperature resistance -5 °C to +100 °C
Compressive strength 17 N/mm2
Sound insulation (Rw partition and specimen) 59 dB
Reaction to fire (EN13501-1) Class F
Shelf life 12 months
European Technical Approval ETA 14-0387
Tensile strength 30/mm2
Thermal conductivity – EN1745 0.57 W/mK at 50 % /0.65 W/mK at 90 %
Average yield 4 bags per M2 at 100 mm thickness

APPLICATION DATA
By volume

Powder to water ratio


Pourable grade 2.5:1
Trowelable grade 3:01
* These are approximate calculations based on 20 kg bags. The coverage does not take into account the percentage of the hole filled with services.
** As a further safety margin, we would recommend that all floor seals with clear areas greater than 1,100 mm x 1,100 mm must be reinforced.
Load bearing note: the open area free of services: Thickness of seal ratios for non-reinforced seals given above allow an ample safety margin for normal foot traffic, e.g., loads of two men
plus equipment with a combined weight up to 200 kg.

45
VentiStop Cavity Barrier - FFB VS

Effective ventilated fire barrier designed to close the void


between the inner and outer construction elements

2 FFB-VS Ventistop installed with Multi-Purpose


Bracket
FFB-VS Ventistop installed with DHM Anchor

BUILDING MATERIALS ASSESSMENT/APPROVAL


Products

▪▪ Concrete slabs, columns and walls


▪▪ Curtain wall assemblies
▪▪ Stone cladding, etc.

ADVANTAGES APPLICATIONS FUNCTIONING


▪▪ Tested up to 120 minutes integrity ▪▪ Horizontal cavities between the inner ▪▪ FFB-VS a foil-faced stone wool
and 90 minutes insulation utilising and outer construction elements pre-cut unit, which has a powerful
the heating and pressure conditions of intumescent graphite strip bonded to
EN 1363-1: 2012 and ASFP TDG19: the exposed face. The intumescent
2014 - Open State Cavity Barriers. graphite strip is pre-wrapped with a
▪▪ Suitable to close 25 & 50 mm venti- durable polythene adhesive sheet to
lation gap prevent water ingress.
▪▪ Voids up to 350 mm wide ▪▪ FFB-VS has been designed to provide
▪▪ Free of halogens, asbestos, fi bres and a 25 & 50 mm ventilation gap, that
silica and is non-toxic allows air fl ow and moisture to pass
▪▪ Long life expectancy down the back of the cladding. Under
▪▪ Contributes to green building fire conditions, the powerful intu-
mescent along the front edge expands
horizontally to close the gap and
prevent the passage of fire.

46
VentiStop Cavity Barrier - FFB VS

SPECIFICATIONS FFB-VS
Item Art.-No. To suit cavity void width Colour Sales unit
[mm] [pcs]
FFB-VS/25-50 521520 25 - 50 Red/silver/black 48
FFB-VS/51-100 521521 51 - 100 Red/silver/black 24
FFB-VS/101-150 521522 101 - 150 Red/silver/black 48
FFB-VS/151-200 521523 151 - 200 Red/silver/black 14
FFB-VS/201-250 521524 201 - 250 Red/silver/black 11
FFB-VS/251-300 521525 251 - 300 Red/silver/black 11
FFB-VS/301-350 521526 301 - 350 Red/silver/black TBA
FFB-VS/351-400 521527 315 - 400 Red/silver/black 9
FFB-VS/401-450 521528 401 - 450 Red/silver/black 6
IMPORTANT: Please provide TOTAL cavity width for your application, excluding any insulation there might be.

2
SPECIFICATIONS FFB-VS50

Products
Item Art.-No. To suit cavity void width Colour Sales unit
[mm] [pcs]
FFB-VS50/51-100        545628 51 - 100 Red/silver/black 48
FFB-VS50/101-150     545629 101 - 150 Red/silver/black 24
FFB-VS50/151-200     545630 151 - 200 Red/silver/black 48
FFB-VS50/201-250       545631 201 - 250 Red/silver/black 14
FFB-VS50/251-300     545632 251 - 300 Red/silver/black 11
FFB-VS50/301-350     545633 301 - 350 Red/silver/black 11
FFB-VS50/351-400     545634 351 - 400 Red/silver/black TBA
FFB-VS50/401-450       545635 401 - 450 Red/silver/black 9
IMPORTANT: Please provide TOTAL cavity width for your application, excluding any insulation there might be.

TECHNICAL DATA
Description Foil faced stone with a black intumescent leading edge
Fire resistance - FFB-VS Up to 120 minutes
Closure time - FFB-VS needs to be < 5 min
Activation Approx. 180 °C (intumescent material)
Expansion pressure Approx. 07 N/mm2
Density Stone wool - 80 kg/m3 intumescent 1.3 g/cm3
Weather resistance Yes
Sag 0%
Open void size - FBB-VS 25 mm to 50 mm
Dimensions 80 mm Thick 1000 mm Long
Width FBB-VS (30 mm to 450 mm)
Fixing points (Brackets or DHM Anchor) FBB-VS (300 mm Centres)

MULTI PURPOSE BRACKET


Item Art.-No. To suit cavity void width Colour Fire rating Sales unit
[mm] [pcs]
Multi Purpose Bracket 551868 390 x 25 x 1 (A2) silver N/A 1
Multi Purpose Bracket 551954 500 x 25 x 1 (A2) silver N/A 1

47
Cavity FireStop Clad FCFcl

Designed to protect the building void between the inner and


outer construction elements

2 FCFcl Cavity Clad - Horizontal application FCFcl Cavity Clad - Vertical application

BUILDING MATERIALS ASSESSMENT/APPROVAL


Products

▪▪ Concrete slabs, columns and walls


▪▪ Curtain wall assemblies
▪▪ Stone cladding, etc.

ADVANTAGES APPLICATIONS FUNCTIONING


▪▪ Tested to EN 1366-4 & BS 476 ▪▪ Horizontal and vertical cavities bet- ▪▪ FCFcl Cavity Clad comprises of a one
▪▪ Classification to EN 13501-2, EN ween the inner and outer construction piece closed dimension stone wool
13501-1 elements core.
▪▪ Air Permeability to EN 1026 to 600Pa ▪▪ Ceiling Cavity Barriers ▪▪ The product is encased with an alumi-
▪▪ Acoustic Isolation to EN 10140 to ▪▪ Under Floor Cavity Barriers num foil face which provides class ‘O’
31dB ▪▪ Slab Edge Barriers rating and exhibits excellent resistance
▪▪ GWP of 0% Global Warming Potential to smoke.
▪▪ ODP of 0% Ozone Depletion Potential ▪▪ The FCFcl Cavity Clad provides a
▪▪ Superior Level of Sustainability resilient lateral compression which is
▪▪ Encased Fibre Migration for Air Ple- required to ensure a tight fit.
num Use
▪▪ Long life expectancy
▪▪ Contributes to Green Building
▪▪ Floor & Wall voids up to 500 mm
wide

48
Cavity FireStop Clad FCFcl

SPECIFICATIONS FCFCL
Item Art.-No. To suit cavity void width Colour Fire rating Sales unit
[hours]
[mm] [pcs]
FCFcl 75 546210 1200 x 600 x 75 silver up to 2* 1
FCFcl 100 053046 1200 x 600 x 100 silver up to 2* 1
FCFcl 1200 546209 1200 x 1200 x 100 silver up to 2* 1
IMPORTANT: Please provide TOTAL cavity width for your application, excluding any insulation there might be.
FCFcl Cavity Clad shall be cut 10 mm (3/8 in.) over size.
* Depending on design & configuration of the FCFcl Cavity Clad.

MULTI PURPOSE BRACKET


Item Art.-No. To suit cavity void width Fire rating Sales unit
[hours] 2
[mm] [pcs]
Multi Purpose Bracket 551868

Products
390 x 25 x 1 (A2) N/A 1
Multi Purpose Bracket 551954 500 x 25 x 1 (A2) N/A 1

TECHNICAL DATA
Description Foil faced structural stone wool composite
Fire resistance - FCFcl BS467 20 / EN1366-4 up to 120min
Classification EN 13501-2:2007 + A1:2009, ETAG 026
Thermal 0.35 to 0.36W/mk
Density 80 kg/m3
Build Stone wool - 80 kg/m3 intumescent 1.3 g/cm3
Acoustic (EN10140) 31db
Air permeability (EN1026) 600 pa - 100 pa 2.6/4.2 m3/h/m2
Thickness 75 mm & 100 mm
Dimensions 1200 x 600 & 1200 x 1200
Compression Min 10 mm
Brackets Required over cavity of 150 mm (2 per meter)

49
FireStop Foam

A single component filler foam with effective fire resistance

2 Construction joints Back filling material

BUILDING MATERIALS ASSESSMENT/APPROVAL


Products

▪▪ Concrete
▪▪ Masonry
▪▪ Steel as backing material
▪▪ Timber as backing material

ADVANTAGES APPLICATIONS FUNCTIONING


▪▪ High foam yield ▪▪ Construction joints in walls and floors ▪▪ FireStop Foam is a single component,
▪▪ No post shrinkage or expansion ▪▪ Insulating and sealing doors and self expanding polyurethane foam,
▪▪ CFC free propellant windows: non-fire rated application which has been designed to be self
▪▪ Effective seal against smoke ▪▪ Backfilling material only for service curing via the  absorption of moisture
▪▪ Rendered, cut, painted or sanded penetrations from the atmosphere.
▪▪ High bond strength ▪▪ Filling general voids and cavities: ▪▪ The foam has excellent adhesion
▪▪ Good adhesion to most building nonfire rated application properties  and can adhere to most
materials building materials. When the foam
▪▪ Excellant acoustic and thermal sets it cures to a semi-rigid structure,
properties which accommodates low movement
and vibration.

50
FireStop Foam

INSTALLATION

1. Clean all contact surfaces so they are free from loose debris and contaminants such as oil, dirt, grease, wax, old sealant etc.
2. Dampen the substrate surfaces with clean water before application to improve adhesion and curing rate.
3. Protect adjacent surfaces with paper of a plastic film.
4. Shake the canister vigorously at least 20 time before use, and again periodically during application.
5. Remove the cap and screw the nozzle firmly into the connector on the top of the valve.
6. Gently pull the trigger to dispense foam, whilst holding the canister inverted.
7. Fill approximately half of the required depth of the cavity to allow for expansion of the foam. Should gaps be more than 30 mm then, apply the foam in
beads and pre-moisten between layers.
8. On horizontal surfaces always work away from the bead and work upwards on all vertical surfaces.
9. Please note that cured foam is adversely effected by UV light and should be protected with a suitable paint or sealant.

SPECIFICATIONS 2
Item Art.-No. Contents Sales unit

Products
[ml] [pcs]
FireStop Foam Hand 042757 750 12
FireStop Foam Gun 043712 750 12

TECHNICAL DATA
Base Polyurethane
Consistency Stable foam
Curing system Moisture-cure
Yield 1,000 ml yields 35 - 40 l cured foam when extruded in beads
Specific gravity Ca. 27 kg/m3 extruded, fully cured
Skinning formation (20 °C/65 % R.H.) 10 min
Drying time (20 °C/65 % R.H.) Non tacky after approx. 8 min
Curing rate (20 °C/65 % R.H.) hr for 30 mm bead
Shrinkage None
Post expansion None
Cellular structure 70 % closed cells, fine cellular structure
Temperature resistance -40 °C to +90 °C when cured
Colour Light red
Packaging 750 ml can
Storage temperature +5 °C to +25 °C
Shelf life Up to 12 months when stored in unopened cartridges under cool, dry conditions
Construction material as per DIN 4102 B1
STC rating 58 dB

51
Thermal Defense Wrap TDW

Thermal defense wrap for high insulation and temperature


stability

2 Cable tray application in wall Cable tray application in floor

ASSESSMENT/APPROVAL
Products

ADVANTAGES APPLICATIONS FUNCTIONING


▪▪ Remains flexible -10 to +160 ▪▪ Metallic services with steel and cast ▪▪ TDW is ceramic-based technology of
▪▪ Low VOC iron pipes bio-soluble vitreous fibres and flexible
▪▪ High insulation and temperature ▪▪ General construction joints: wall to organic builders, and has been desi-
stability floor to head of wall gned to maintain the compartmentali-
▪▪ Pre-formed 300 mm roll ▪▪ Drywall partitions, connections sation of a fire-rated assembly.
▪▪ Fast and efficient installation ▪▪ FCPS joints ▪▪ The unique design of the TDW allows
▪▪ Remains flexible without aging for movement of services, maintain
the necessary insulation of the
services and prevents temperature,
rise of the services at the cold face. At
normal temperature the TDW remains
flexible and permits thermal and
mechanical movement.
▪▪ It provides up to 2 hours integrity and
insulation.

52
Thermal Defense Wrap TDW

INSTALLATION

1. Clean all contact surfaces so they are free from loose debris and contaminants such as oil, dirt, grease, wax, old sealant, etc.
2. Measure and mark the TDW to the required service configuration.
3. Cut TDW as per requirements with a standard pair of scissors or snips.
4. Wrap TDW around service configuraion and apply alufoil tape to secure in place.

SPECIFICATIONS
Item Art.-No. Dimensions Sales unit
[mm] [pcs]
TDW 1 531398 300 x 15,000 1

TECHNICAL DATA
2
Odor and appearance White, fibrous material with aluminium foil face

Products
Chemical family Calcium magnesium silicate fibres
Boiling point N/a
Water solubility (%) Less than 1 mg/l > 1200 °C
Relative density 180Kg/m3 - 250Kg/m3
Alufoil thickness 0.25 mm normal
Dimension (thickness mm) 6
Size (width x length mm) 300 x 15,000 long roll or 1,200 x 500 sheet
Shelf life 36 months (under recommended conditions)
Storage temperature -5 °C to +25 °C
Colour White, silver

53
Cable Coating FCC

Ablative firestop coating design to prevent the propagation of


fire along internal and external electrical cable

2 Cable assignment through wall Application of FCC coating

BUILDING MATERIALS ASSESSMENT/APPROVAL


Products

▪▪ Drywall
▪▪ Concrete
▪▪ Masonry

ADVANTAGES APPLICATIONS FUNCTIONING


▪▪ Water based, odorless and solvent free ▪▪ Power plants (IEC 332 Pt3) ▪▪ Can be sprayed, painted, or brush
▪▪ Suitable for internal and external ▪▪ Telecommunication applied.
applications ▪▪ Industrial plants ▪▪ Multiple layers and overhead appli-
▪▪ Quick curing ▪▪ Petrochemical plants cation possible due to its thixotropic
▪▪ Spray or brush applied ▪▪ Factories and production facilities consistency.
▪▪ Halogen, fibres and asbestos free ▪▪ Base surface should be clean, dry and
▪▪ High yield suitably prepared.
▪▪ Thickness of application: see approval
or test.
▪▪ When exposed to fire, it reacts to form
a highly isolative char that slows down
heat transfer, and provides a protective
fire barrier. ▪
When spray applied:▪
Min. 170 bar▪
Nozzle spray angle 40°▪
Flow rate 0,78 mm▪
Liters/minute 3,5

54
Cable Coating FCC

SPECIFICATIONS
Item Art.-No. Content Sales unit
[kg] [pcs]
FCC 539609 12.5 1

TECHNICAL DATA
Chemical base Water-based
Density 1,55 g/cm³
Application temperature + 5 °C to + 40 °C
Storage temperature +5 °C to +30 °C to be protected from frost and direct sunlight
Odour slight
Water resistant yes
Shelf life 1 year 2
pH Value approx. 8
Coating thickness 0.5 - 0.8 mm (IEC 60332-3)

Products
(Dry film) 1.6 mm (Factory Mutual)
Colour White
Curing time at room temperature 1 - 3 days*
* Depending on humidity, air and ambiant temperature.

55
Tools and accessories

FOAM GUNS

Skeleton dispenser KP M1 Dispenser KP M2 Dispenser KP M3


Item Art.-No. Adapted for Sales unit
[pcs]
KP M1 053115 FIAM, FFRS, UFS 310 1
2 KP M2 053117 FIAM, FFRS, UFS 310 1

FOAM GUNS
Products

Applicator gun KP M600


Item Art.-No. Adapted for Sales unit
[pcs]
KP M600 540941 FIAM 600 ml 1

FOAM GUNS

Plastic dispenser PUP K2


Item Art.-No. Sales unit
[pcs]
PUP K2 062400 1

FOAM GUN CLEANER

PUR 500 foam cleaner PUR 150 foam cleaner


Item Art.-No. Contents Adapted for Sales unit
[ml] [pcs]
PUR 500 (DE/EN) 053085 500 PUP K2 gun 12
PUR 150 (DE) 053083 150 PUP K2 gun 12

56
2

57
Products
Sprinkler systems

A guide to supporting sprinkler systems

APPLICATIONS APPROVALS
▪▪ Industrial companies
▪▪ High-bay warehouses
▪▪ Office buildings VdS
▪▪ Logistics areas
▪▪ Public buildings and institutions Sign of conformity VdS CEA 4001
▪▪ Sales entities in concrete ceilings:

▪▪ High-rises
▪▪ Underground garages
▪▪ Museums
▪▪ Congress and conference centres

FUNCTIONING
Sprinkler systems fall into the category of active fire protection (AFP) and could be considered as detection and suppression sys-
tems, which usually covers the complete floor plan. This means that sprinklers are usually installed in all rooms of a building and
are designed in accordance with the actual fire hazard, the temperature - dependent opening of the sprinkler normally activates
an acoustic sound and sends a signal to the fire control system. Over the past decade, sprinkler systems extinguishing rates have
been high and, as a result, are standard in some types of buildings.
Sprinkler systems

In general, sprinkler systems are designed in accordance with the following standards: VdS CEA 4001 Section 15.2.4 Anchorage
in Concrete Ceilings, FM 1951 Section 3.2 Technical and Constructional Properties, UL 203 Section 11.3 Pipe Hangers for Fire
Protection Systems, NFPA 13 Section 9.1.3 Fixings in Concrete and/or to EN 12845,which is an identical standard to CEA 4001.

APPLICATION DATA
Concrete Aircrete Trapezoidal ceiling Steel construction
Building material
and anchor base
FBS EA II FAZ II FH II-I FZA FPX-I TZH TZ TZA TKL TKLS

Anchor or
hanger

3 plus

Threaded rod or G/GS

threaded stud

FRSP plus FRSL


Sprinkler clamp
or -loop
VdS

58
Sprinkler systems

SPECIFICATIONS

Item Type Art.-no. [Zoll] / [mm] Item Type Art.-no. [Zoll] / [mm]
FRSL 34 513302 1“ G8 079740 1000
FRSL 43 513303 1 1/4“ G 10 079744 1000
FRSL 49 513304 1 1/2“ G 12 020957 1000
FRSL 60 513307 2“ G 16 020958 1000
FRSL 76 513308 2 1/2“ G 8/2 079741 2000
FRSL 90 513309 3“ G 10/2 079745 2000
FRSL 115 513310 4“ G 12/2 579746 2000
FRSL 140 513311 5“ G 10/3 557092 3000
FRSL 170 513312 6“ G 12/3 064056 3000
FRSP 1/2'' 524035 1/2“ GS 8/25 079750 25
FRSP 3/4'' 524036 3/4“ GS 8/40 079751 40
FRSP 1" 524037 1“ GS 8/50 079752 50
FRSP 1 1/4'' 524038 1 1/4“ GS 8/60 079753 60
FRSP 1 1/2'' 524039 1 1/2“ GS 8/70 079754 70
FRSP 2'' 524040 2“ GS 8/80 079755 80
FRSP 2 1/2'' 524041 2 1/2“ GS 8/90 079756 90
FRSP 3'' 524042 3“ GS 8/100 079757 100
FRSP 4'' 524043 4“ GS 8/150 079758 150
FRSP 5'' 524044 5“ GS 8/200 079759 200
FRSP 6'' 524045 6“ GS 10/25 079765 25
FRSP 8'' 524046 8“ GS 10/40 079766 40
ETR 8 - 13 024415 M6 GS 10/60 079767 60
ETR 12 - 17 024416 M6 GS 10/80 079768 80
ETR 15 - 21 024417 M6 GS 10/100 079769 100
ETR 20 - 27 024418 M8 GS 10/120 079770 120
ETR 26 - 34 024419 M8 GS 10/150 079771 150
ETR 33 - 42 024420 M8 GS 10/200 079772 200
ETR 40 - 49 024421 M8 TKL L M 8 064055 M8
ETR 50 - 60 024422 M8 TKL M 8 079687 M8
ETR 60 - 70 024423 M 10 TKL L Ø 9 077605 Ø9
ETR 66 - 76 024424 M 10 TKL M 10 079688 M 10

Sprinkler systems
ETR 70 - 82 024425 M 10 TKL Ø 11 079689 Ø 11
ETR 80 - 90 024426 M 10 TKL M 12 020949 M 12
ETR 90 - 102 024427 M 12 TKL Ø 13 043275 Ø 13
ETR 100 - 108 024428 M 12 SS-TKL M10/M12 048154 M10/M12
ETR 102 - 114 024429 M 12 TKLS Ø 9 531134 Ø9
ETR 121 - 127 024430 M 12 TKLS Ø 11 531136 Ø 11
ETR 126 - 133 024431 M 12 TKLS Ø 13 531137 Ø 13
ETR 131 - 140 024432 M 14 TKLS Ø 17 531138 Ø 17
1) This article is delivery on ETR 143 - 153 0244331) M 14 TZ M 8 064094 M8
request only.
ETR 150 - 159 024434 M 14 TZ M 10 064095 M 10
ETR 168 024435 M 14 TZH M 8 079825 M8
ETR 193.7 024436 M 14 TZH M 10 079826 M 10
ETR 219 024437 M 14 TZA M 10 524047 M 10
Please refer to our comprehensive main catalogue or our online web catalogue updated daily at www.fischer.de for information on further additions to our product and entire range.

ANCHOR APPROVAL OVERVIEW VdS

ETA ETA ETA air crete VdS-compliant VdS-approved FM-approved


3
Item concrete single concrete multiple
FAZ II Option 1  
FBS Option 1 (FBS 6) 
FH II Option 1  
FZA Option 1  
FZEA II Option 1  
EA II Option 7   
FNA II  
FPX-I  
ETA concrete, single, option 1 = suited for cracked and non-cracked concrete ETA concrete, single, option 7 = suited for non-cracked concrete ETA concrete, multiple = suited for cracked and non-cracked concrete

59
Fireproof mounting

Fire protection inspections for SaMontec products

TEST CURVE ADVANTAGES APPROVALS


Reduction factors kθ ▪▪ Single, multi or uniform load tested MLAR MLAR
▪▪ Full range of pipe clamps
German standard regulations for German standard regulations for
1.0 fire safety requirements fire safety requirements
for piping systems (11/2005) for piping systems (11/2005)
0.9 Yield strength
▪▪ Rails and supports F 30 R 30
0.8 kγ,θ = fγ,θ / fγ Certificate of compliance of the Certificate of compliance of the
minimum distance ≤ 50 mm minimum distance ≤ 50 mm
0.7
0.6 Elasticity module Fire resistance Fire resistance
0.5 kΕ,θ = Εа,θ / Εа classification classification
0.4 F 120 R 120
according according
0.3 DIN 4102-2 DIN EN 1363-1
0.2 Proportional limit
0.1 kρ,θ = fρ,θ / fρ
0.0
0 200 400 600 800 1000 1200

Steel temperature [°C]


Dependency of the yield strength, proportional limit and elasticity module
on the temperature (basis: EN1993-1-2:2012-12 Eurocode 3).

FUNCTIONING
Fire protection in buildings covers the safety of occupants, fire fighters and contents, and is regulated by the local building codes
or standards. This is particularly evident in the installation of fire protection systems such as a detection or suppression, as
approved or recognized components must be used. The key message is to ensure the safety of the escape route by ensuring the
Fireproof mounting

functioning of the supports and sub frames will remain integral for a set period of time.
The necessity for these considerations arises from the properties of the steel, which is subjected to a loss of yield when it reaches
a temperature of > 600 °C and therefore components can undergo a series of resistence testing. The same information is docu-
mented in the inspection reports for a fire resistance with ratings of R30, R90 and R120, based on the standard pipe systems
directive of 2005 (MLAR 2005) and according to EN-1363-1 and DIN4102-2

SPECIFICATION

FRS FUS 41 FUS 62 FCA SB SBS PDH-K


3 Item Document no. MLAR R30 - R120 F30 - F120
FRS MFPA Leipzig-GS3.2/14-175-2
FUS MFPA Leipzig-GS3.2/14-175-4
FCA MFPA Leipzig-GS3.2/14-175-4
SB MPA-NRW- 210005109 - 7
SBS MPA-NRW- 210005109 - 4
PDH-K MPA-NRW- 210005109 - 6

60
Fireproof mounting

FUS-Channel / FCA-Cantilever arm - Load table based on the


advisory opinion no. GS 3.2/14-175-4
FUS/FCA 41/2.5 (picture1-3) MLAR - loads Max. Loads Pict.
1
Threaded rods ≥ 4.8 strain F-resistance Max. strain Fire resistance time [minute]
ls min a 1) 30 min a 2) 30 60 90 120
Load case
[mm] [mm] [kN] [mm] [kN] [kN] [kN] [kN]
≤ 400 ≤ 50 0.90 278 2.40 1.33 0.92 0.72
Point load
≤ 700 ≤ 50 - 320 1.61 1.04 0.80 0.67
multiple ≤ 400 ≤ 50 0.90 278 2.40 1.33 0.92 0.72
load 3) ≤ 700 ≤ 50 - 320 1.61 1.04 0.80 0.67
≤ 400 ≤ 50 1.50 258 3.00 2.10 1.41 1.06
Uniformly
≤ 700 ≤ 50 0.60 299 2.44 1.57 1.21 1.00
distributed load
≤ 1.250 ≤ 50 - 468 3.29 1.81 1.27 0.98
Pict.
2
FUS / FCA 62/2.5 (Pict. 1–3) MLAR Max. Loads
Threaded rods ≥ 4.8 strain F-resistance Max. strain Fire resistance time [minute]
ls min a1) 30 min a2) 30 60 90 120
Load case
[mm] [mm] [kN] [mm] [kN] [kN] [kN] [kN]
≤ 400 ≤ 50 1.76 25 1.76 1.06 0.78 0.62
Point load
≤ 1,000 ≤ 50 - 460 2.27 1.31 0.93 0.72
≤ 400 ≤ 50 1.76 25 1.76 1.06 0.78 0.62 Pict.
multiple
≤ 9604) ≤ 50 4.30 550 4.30 2.14 1.39 1.01 3
load 3)
≤ 1,000 ≤ 50 0.55 661 2.52 1.60 1.21 0.99
≤ 400 ≤ 50 1.76 25 1.76 1.06 0.78 0.62
Uniformly ≤ 9604) ≤ 50 4.30 550 4.30 2.14 1.39 1.01
distributed load ≤ 1,000 ≤ 50 0.55 661 2.52 1.60 1.21 0.99
≤ 50 0.50 592 2.41 1.65 1.31 1.11

FUS 62/2.5 (picture 4) MLAR - loads Max. Loads


Vertical FUS 41/2.5 strain F-resistance Max. strain Fire resistance time [minute]
ls min a1) 30 min a2) 30 60 90 120
Load case
[mm] [mm] [kN] [mm] [kN] [kN] [kN] [kN] Pict.
Point load ≤ 1,000 ≤ 50 0.57 369 1.33 0.87 0.68 0.57 4
multiple
≤ 1,000 ≤ 50 0.62 649 1.92 1.34 1.08 0.92
load 3)
Uniformly
≤ 1,000 ≤ 50 0.62 649 1.92 1.34 1.08 0.92
ditributed load

Fireproof mounting
The following figures are valid for FUS channels and FCA cantilever arms, galvanized, hdg and stainless steel.
1) Valid for a suspension height ha ≤ 500 mm
2) Based on suspension height ha = 250mm, Expansion length of threaded rods in case of fire ~ 10mm/m
3) Given load values apply for multiple loads as summated point loads symmetrical allocated.
4) This values are valid for FCA 62/2,5 with additional support by threaded rod.

APPLICATION POSSIBILITIES
Point load = Multiple load = Uniformly distributed load =
Spot load, e.g. a pipe More than one load Uniform distribution of load on the
clamp on the rail. point on the rail, e.g. rails, e.g. bend-proof ventilation duct.
several pipe clamps.

F=qxl F=qxl

Strichstärke 1

F=qxl F=qxl

Strichstärke 1,25

61
Fixings guide

Fire tests of fasteners and anchors in concrete


The fire tests on anchors and fasteners is carried out into C20/25 cracked and uncracked
concrete or masonry, following the standard time/temperature curve (ETK) according to
DIN 4102 or ISO 834.

The anchors and fasteners have pre defined load applied and are exposed to flames
without insulation or protective measures. The fire resistance is indicated by the time the
anchor or fastener resist without failure.

——— (ETK), ——— Hydrocarbon curve, ——— RABT Tunnel curve,


Additional ETKs can be adopted for special applications such as RABT ZTV tunnel curve. ——— Riikswaaterstaat Tunnel curve

TECHNICAL DATA

Zykon anchor FZA

Material Permissible tensile load in case of a fire [kN] Test report Approval Certificate Application
no.

Item gvz A4 C R30 R60 R90 R120 RWS VdS FM


FZA M6 ■ 1.0 0.5 0.35 0.25
FZA M8 ■ 1.5 0.8 0.5 0.4 ■

FZA M10 ■ 4.5 2.2 1.3 0.9 ■ ■

FZA M12 ■ 8.5 3.5 2.0 1.5 3277/0531-1 ■ ■

FZA M16 ■ 13.5 6.5 4.0 3.0 (of 28.02.2013) ■ ■ Cracked and non-
FZA M6 A4/C ■ ■ 2.1 1.2 0.85 0.7 Text: 3091/2013 cracked concrete
FZA M8 A4/C ■ ■ 10.0 4.0 1.8 1.0 ■

FZA M10 A4/C ■ ■ 18.0 7.0 3.5 2.0 ■ ■


Fixings guide

FZA M12 A4/C ■ ■ 22.0 9.0 5.0 3.5 ■ ■

FZA M16 A4/C ■ ■ 24.0 12.0 7.5 6.0 ■ ■

TECHNICAL DATA

Zykon anchor FZA

3
Material Permissible tensile load in case of a fire [kN] Test report Approval Certificate Application
no.

Item gvz A4 C R30 R60 R90 R120 RWS VdS FM


FZEA II 10x40 M8 ■ ■ ■ 1.0 0.9 0.8 0.7 ■
Cracked and non-
FZEA II 12x40 M10 ■ ■ ■ 1.8 1.8 1.6 1.2 ETA-06/0271 ■
cracked concrete
FZEA II 14x40 M12 ■ ■ ■ 1.8 1.8 1.8 1.5 ■

62
Fixings guide

TECHNICAL DATA

Bolt anchor FAZ II

Material Permissible tensile load in case of a fire [kN] Test report Approval Certificate Application
no.

Item gvz A4 C R30 R60 R90 R120 RWS VdS FM


FAZ II M8/A4/C ■ ■ ■ 1,4 1,2 0,9 0,8 ■

FAZ II M10/A4/C ■ ■ ■ 2,8 2,3 1,9 1,6 ETA-05/0069 ■ ■ Cracked and non-
FAZ II M12/A4/C ■ ■ ■ 5,0 4,1 3,2 2,8 ■ ■ cracked concrete
FAZ II M16/A4/C ■ ■ ■ 7,1 7,1 6,0 5,2 ■ ■

TECHNICAL DATA

High performance anchor FH II-S


with hexagonal head

High performance anchor FH II-SK


with countersunk head

Material Permissible tensile load in case of a fire [kN] Test report Approval Certificate Application
no.

Item gvz A4 C R30 R60 R90 R120 RWS VdS FM


FH II 10 B/S/ H ■ 0.2 0.2 0.1 0.1 ■

Fixings guide
FH II 12 B/S/H/SK ■ 2.0 1.3 0.6 0.2 ■
ETA-07/0025 Cracked and non-
FH II 15 B/S/H/SK ■ 3.2 2.3 1.4 1.0 ■
cracked concrete
FH II 18 B/S/H ■ 4.8 3.9 3.0 2.6 ■

FH II 24 B/S/H ■ 8.9 7.3 5.6 4.8 ■

63
Fixings guide

TECHNICAL DATA

Bolt anchor FBN II

Material Permissible tensile load in case of a fire [kN] Test report Approval Certificate Application
no.

Item gvz A4 C R30 R60 R90 R120 RWS VdS FM


FBN II 8 ■ 1,4 1,1 0,7 0,6
FBN II 10 ■ 4,2 3,1 2,0 1,4
PD III/B-07-444 Non-cracked
FBN II 12 ■ 9,5 6,8 4,2 2,8 (of 29.11.2007)
concrete
FBN II 16 ■ 17,7 12,7 7,8 5,3
FBN II 20 ■ 27,6 19,9 12,2 8,4

TECHNICAL DATA

Injection mortar FIS V Injection mortar FIS V

Static mixer FIS MR

Material Permissible tensile load in case of a fire [kN] Test report Approval Certificate Application
no.

Item gvz A4 C R30 R60 R90 R120 RWS VdS FM


FIS A M8 1.9 0.8 0.3 0.15
Fixings guide

FIS A M10 ■ 4.5 2.1 1.0 0.6


FIS A M12 ■ 8.5 3.6 2.1 1.5
FIS A M16 ■ 13.5 6.4 4.0 3.0
FIS A M20 ■ 21.0 10.0 6.0 4.5
FIS A M24 ■ 30.0 14.0 9.0 6.5
FIS A M30 ■ 45.0 22.0 14.0 10.0 3038/8141-3 Non-cracked
FIS A M8 A4/C ■ ■ 4.3 0.8 0.3 0.15 (of10.01.2002) concrete
FIS A M10 A4/C ■ ■ 7.5 2.1 1.0 0.6
FIS A M12 A4/C ■ ■ 11.0 5.7 3.9 3.0
FIS A M16 A4/C ■ ■ 25.0 10.0 5.8 4.0
FIS A M20 A4/C ■ ■ 32.0 15.0 9.0 6.0
FIS A M24 A4/C ■ ■ 45.0 22.0 13.0 9.0
3 FIS A M30 A4/C ■ ■ 70.0 35.0 20.0 14.0

64
Fixings guide

TECHNICAL DATA

Hollow-ceiling anchor FHY

Material Permissible tensile load in case of a fire [kN] Test report Approval Certificate Application
no.

Item gvz A4 C R30 R60 R90 R120 RWS VdS FM


FHY M6 ■ 0.9 0.45 0.28 0.2 Prestressed concrete
FHY M8 ■ 0.9 0.9 0.75 0.6 3566/3321 and hollow plate
(of 21.06.2002)

FHY M10 ■ 1.2 1.2 1.2 1.1 ceilings min. C45/55

TECHNICAL DATA

Ceiling nail FDN

Material Permissible tensile load in case of a fire [kN] Test report Approval Certificate Application
no.

Item gvz A4 C R30 R60 R90 R120 RWS VdS FM


FDN 6/35 ■ 0.8 0.7 0.6 0.4
ETA-07/0144 Suspended ceilings
FDN 6/65 ■ 0.8 0.7 0.6 0.4

Fixings guide

65
Fixings guide

TECHNICAL DATA

Nail anchor FNA II with nail head

Material Permissible tensile load in case of a fire [kN] Test report Approval Certificate Application
no.

Item gvz A4 C R30 R60 R90 R120 RWS VdS FM


FNA II 6x25 ■ 0.6 0.61 0.5 0.3
FNA II 6x25 M6 ■ 0.6 0.35 0.3 0.3 ■

FNA II 6x25 M8 ■ 0.6 0.35 0.3 0.5 Manifold fixing of


FNA II 6x25 OE ■ 0.3 0.2 0.2 0.1 ETA-06/0175 non-load-bearing
FNA II 6x30 ■ 0.9 0.8 0.5 0.3 systems
FNA II 6x30 M6 ■ ■ ■ 0.6 0.35 0.3 0.3
FNA II 6x30 M8 ■ ■ ■ 0.6 0.35 0.3 0.3 ■

TECHNICAL DATA

Hammerset anchor EA II. Not suitable


for diamond drilling appliances and
diamond saws.

Material Permissible tensile load in case of a fire [kN] Test report Approval Certificate Application
no.
Fixings guide

Item gvz A4 C R30 R60 R90 R120 RWS VdS FM


EA II M6 3) ■ ■ ■ 0,5 0,5 0,4 0,3 ▯
Suspended ceilings
EA II M8x40 ■ 1,3 0,9 0,6 0,5 ▯ ▯
ETA-07-0142 and non-cracked
EA II M10x30 ■ 0,9 0,9 0,9 0,6 ▯ ▯ concrete
EA II M12x25 ■ 0,6 0,6 0,6 0,5

66
Fixings guide

fischer metal insulation fixing - fire resistance classification - R120

TECHNICAL DATA

Insulation support metal DHM, Insulation retaining metal washer DTM 80,
washer-ø 35 mm washer-ø 80 mm, inside-ø 11 mm
Art.No. Drill-Ø Min. drill-hole depth Effect. anchorage Anchor length Max. usable length Qty. per box pcs.
depth
d0 td hef I tfix

Item [mm] [mm] [mm] [mm] [mm]


DHM 30 088801 8 60 50 90 0 - 40 250
DHM 60 088802 8 60 50 110 30 - 60 250
DHM 90 088803 8 60 50 140 60 - 90 250
DHM 120 061581 8 60 50 170 90 - 120 250
DHM 135 503131 8 60 50 185 135 250
DHM 150 061582 8 60 50 200 120 - 150 250
DHM 30 INOX 506135 8 60 50 90 0 - 40 250
DHM 60 INOX 506136 8 60 50 110 30 - 60 250
DHM 90 INOX 506137 8 60 50 140 60 - 90 250
DHM 120 INOX 506138 8 60 50 170 90 - 120 250
DHM 150 INOX 506140 8 60 50 200 120 - 150 250
DHM 80 088806 - - - - - 250
DHM 80 INOX 506141 - - - - - 250

Fixings guide

67
Fixings guide

fischer fixings for drywall

TECHNICAL DATA

HM-S with metric screw

HM-SS with hexagon headed screw

Art.No. Drill-Ø Min. drill-hole depth Effect. anchorage Anchor length Max. usable length Qty. per box pcs.
depth
d0 td hef I tfix

Item [mm] [mm] [mm] [mm] [mm]


HM 4 x 32 S 062306 8 42 32 M 4 x 40 0 - 40 3 - 13
HM 4 x 46 S 062307 8 56 46 M 4 x 53 30 - 60 5 - 18
HM 4 x 59 S 062308 8 69 59 M 4 x 66 60 - 90 35 - 42
HM 5 x 37 S 062310 10 47 37 M 5 x 45 90 - 120 6 - 15
HM 5 x 52 S 062311 10 62 52 M 5 x 60 135 7 - 21
HM 5 x 65 S 062312 10 75 65 M 5 x 73 120 - 150 20 -34
HM 6 x 37 S 062314 12 47 37 M 6 x 45 0 - 40 6 - 15
HM 6 x 52 S 062315 12 62 52 M 6 x 60 30 - 60 10 -21
HM 6 x 65 S 062328 12 75 65 M 6 x 70 60 - 90 20 - 34
HM 6 x 80 S 062316 12 90 80 M 6 x 88 90 - 120 38 - 50
HM 8 x 55 SS 062329 12 65 55 M 8 x 60 120 - 150 10 -21

TECHNICAL DATA

Plasterboard fixing metal GKM


Fixings guide

Art.No. Anchor length Min. thickness to first supporting layers Max. usable length Screw Qty. per box pcs.

I tfix ds Xls

Item [mm] [mm] [mm] [mm]


GKM 024556 31 35 - 4-5 100
GKM 12 040432 31 35 12 4.5 x 35 100
GKM 27 040434 31 35 27 4.5 x 50 100
3

68
Fixings guide

fischer bracket system

TECHNICAL DATA

Quick-fix strap

Art.No. Qty. per box pcs. lenth Profile Profile thickness

Item [mm] [mm]


Quick-fix strap 1 m 42975 10 1.000 3/50 3
Quick-fix strap 2 m 48179 10 2.000 3/50 3

TECHNICAL DATA

Quick-fix back plates

Art.No. Qty. per box pcs. lenth Profile Profile thickness

Item [mm] [mm]


Quick-fix back plates 42974 50 50 x 70 3/50 3

Fixings guide
TECHNICAL DATA

Quick fix pliers

Art.No. Qty. per box pcs. lenth Profile Profile thickness

Item [mm] [mm]


3
Quick-fix pliers 42974 1 - - -

69
Calculation of consumption guide

Calculation for mastic/sealant


a = Hole diameter in mm
b = Depth of sealant in mm/wet film thickness for spray material (see recommendations)
c = Pipe or bunched cables diameter in mm
d = Annular space in mm (see recommendations)
l = Length of square opening/joint
w = Width of square opening/joint
h = Cartridge or spray bucket size in ml
n = Number of holes
e = Area of hole in mm2 = π(a ÷ 2)2
f = area of pipe in mm2 = π (a ÷ 2)2
g = Amount of mastic needed per hole in ml = ((e-f) x b) ÷ 1,000

Round holes Square holes Linear joints


g g g
No. of cartridges needed = n x ( h ) No. of cartridges needed = n x ( h ) No. of cartridges/buckets = ( h )
Area of hole e = π x (a ÷ 2)2 mm2 Area of hole e = l x w mm2 Area of joint = e = l x w mm2
Area of pipe f = π x (c ÷ 2)2 mm2
Calculation of consumption guide

Area of pipe f = π x (c ÷ 2) mm
2 2 Mastic volume = ((e-f) x b) ÷ 1000 ml
Mastic volume = g = ((e-f) x b) ÷ 1,000 ml Mastic volume = g = ((e-f) x b) ÷ 1,000 ml =g
Example for mastic/sealant:
Example: Example: w = 20 mm
a = 90 mm l = 90 mm l = 30m = 30,000 mm b = 10 mm
b = 40 mm w = 100 mm h = 310 ml
c = 50 mm b = 40 mm
h = 310 ml c = 50 ml
e = 20 x 30,000 = 60,000 mm2
n = 20 h = 310 ml
g = (60,000 x 10) ÷ 1,000 = 6,000 ml
n = 20
No. of cartridges = ( 6,000 )
310
e = 90 x 100 = 9,000 mm2 = 19.4 cartridges
e = 3.14 x 452 = 6,361.73 mm2 Example of joint Spray:
f = 3.14 x 252 = 1,963.50 mm2
f = 3.14 x 252 = 1,963.50 mm2 w = 100 mm, w1 = 125 mm (with overspray)
g = ((9,000 - 1,963.50) x 40) ÷ 1,000
g = ((6,361.73 - 1,963.50) x 40) ÷ 1,000 = l = 300 m = 300,000 mm
= 281.46 ml
175.92 ml b = 1.5 mm
h = 19 litres = 19,000 ml
No. of cartridges = 20 x ( 281.46 ) = 18.1 e = 125 x 300,000 = 37,500,000 mm2
310
No. of cartridges = 20 x ( 175.92
310 ) cartridges g = (37,500,000 x 1.5) ÷ 1,000 = 56,250 ml
= 11.35 cartridges No. of buckets = ( 56,250 ) = 2.96 buckets
19,000

Calculations for FireStop Block FBB


a = block length = 230 mm = 0.23 m b = block width = 130 mm = 0.13 m t = block thickness = 60 mm = 0.06 m
3 l = length of opening w = width of opening c = % penetrant area

Area to be covered/filled by blocks = l x b x (1-c/100) = A


Fire rating up to 60 minutes Fire rating up to 120 minutes
No. of blocks required = A =A
axt bxt
Example:
l = 500 mm = 0.5 m w = 500 mm = 0.5 m c = 30%
Area to be covered/filled by blocks = 0.5 x 0.5 x (1 - 0.3) = 0.175m2
Fire rating up to 60 minutes Fire rating up to 120 minutes
No. of blocks required 0.175. 0.175
(0.23 x 0.06) (0.13 x 0.06)
12.68 22.4
70
Calculation of consumption guide

Calculation for compound


l = length of the opening b = width of the opening
d = depth as per required fire rating C = penetrant area or cross sectional area of services
Y = coverage/yield of 1 bag in litres
Volume of compound required = volume of opening - volume of services
= [(lxbxd) - (Cxd)] m3
= [(lxbxd) - (Cxd)] x 1,000 litres
=V
=V
Y
Example
l = 1,000 mm = 1 m b = 500 mm = 0.5 m
d = 100 mm = 0.1 m C = 20 % of opening = l x b x 20 % = 1 x 0.5 x 0.2 = 0.1
Y = 24 litres per 22 kg bag
Volume of compound required = [(1 x 0.5 x 0.1) - (0.1 x 0.1)] x 1,000 litres
V = 40 litres
Numbers of bags required = 40

Calculation of consumption guide


24
= 1.67 bags

Calculation for FIP


Estimation of large and medium size pillows in walls and floors openings of size up to 1 sq. meter.

Length [mm]
Size Large Medium Large Medium Large Medium Large Medium Large Medium Large Medium
Width [mm]
Seal type 100 300 500 700 900 1,000
Wall 3 5 7 13 12 22 17 31 21 39 24 47
200
Floor 2 3 4 7 6 12 9 17 11 22 12 27
Wall 5 9 14 26 24 44 33 61 42 78 47 95
400
Floor 3 5 7 15 12 24 17 34 22 43 24 52
Wall 7 13 21 39 35 65 49 91 63 117 70 143
600
Floor 4 7 11 22 18 36 25 51 33 65 36 79
Wall 9 18 28 52 47 87 66 122 84 157 94 192
800
Floor 5 10 15 29 24 48 34 67 33 87 48 107
Wall 10 22 35 65 59 109 82 152 105 196 117 217
1,000
Floor 6 12 18 36 30 60 42 84 54 108 60 120

Calculation for FBS


Material use as reference value for 40 % degree of seal use - number of cartridges for seal thickness 200 mm and 100
mm for 90 minutes and 30 minutes fire rating respectively.

Seal
surface
Volume @
200 mm depth
Cartridge
Volume @
100 mm depth
Cartridge
Core
boring
Volume @
200 mm depth
Cartridge
Volume @
200 mm depth
Cartridge 3
m2 [m3] 180 g [m3] 180 g [mm] [m3] 180 g [m3] 180 g
0.005 0.001 0.92 0.0005 0.48 50 0.0004 0.36 0.0002 0.18
0.01 0.002 1.85 0.001 0.98 60 0.0006 0.52 0.0003 0.26
0.02 0.004 3.69 0.002 1.85 70 0.0008 0.71 0.0004 0.36
0.03 0.006 5.54 0.003 2.77 80 0.001 0.93 0.0005 0.47
0.04 0.008 7.38 0.004 3.69 100 0.0016 1.45 0.0008 0.73
0.048 0.0096 8.92 0.0048 4.46 120 0.0023 2.09 0.0011 1.05
0.0625 - 0.0063 5.81 160 0.004 3.71 0.002 1.85
200 0.0062 5.8 0.0031 2.9
* The above calculations do not consider wastage of material. Please consider an appropriate factor.

71
Training certification

fischer Training
Fire protection seminars with certificate for professionals.

Show your competence.


Become a trusted specialist of your work!

▪ Do the right thing quickly and safely


▪ Competently assess legal issues and resolve them

We will show you the options for the individual systems,


tips and tricks for handling, and give you a clear, compe-
titive advantage.

We will bring you and your employees up-to-speed in


preventative fire protection.

▪ Basic introduction to fire protection fischerwerke Academy


▪ Model building codes 01th Feb 2017
▪ Fire testing standards
▪ Product selection criteria
▪ Trade and a Application areas
▪ Practical installations

Constantin Wiegert fischerwerke GmbH & Co. KG


Locations and dates
Training certification

Product Manager Klaus-fischer-Str. 1


FireStop 72178 Waldachtal
Deutschland
Please contact your fischer representative for further
details on course dates.

The entire range of knowledge is shared with


you by fischer fire protection experts.

72
Engineering judgement request form

Project name: Requested by:


Consultant: Company:
Contactor: Email:
Contact: Phone:
Email: Fax:
Phone: Supplier:
Fax: fischer engineer:

Fire rating requirements

Frating (hours): Trating (hours): Approval type:

Through penetration

Engineering judgement request form


Assembly details: Wall Floor

Base material: Concrete Blocks Drywall

Thickness:

Other please specify:

Opening details: Circular Sleeved Yes Size


Rectangular No Sleeve type PVC Steel

Annular Space: Min: Max:

Penetration details: Pipe Duct Cables Cable trays/ladders Bus Bars


Size Size Size Size Size
Type Type Type Type Type
Insulation Insulation Insulation Insulation Insulation
Type Type Type Type Type
Thick Thick % fill Nos

Joint

Joint type: Head of wall Bottom of wall Floor to floor Floor to wall
Wall to wall Perimeter joint

Base material: Concrete Blocks Concrete Blocks


Drywall Steeldeck Drywall Steeldeck

Joint details: Static Width


Dynamic

Movement required:

Curtain wall details: 3

Special conditions / comments / drawings / standards

Request form · Version 2 · 2017-06-22 Reference No.:

73
74
The information in this catalogue is non-binding. Our technical service
department can provide you with additional information and advice.
However you will need to provide an accurate description of your particular
application.
All information in this catalogue must be adjusted to local conditions and
materials used. If individual items and types are not listed with detailed
performance specifications, please contact your local fischer representative
for further consultation.
Subject to errors, technical and product line changes, liability for printing
errors and omissions is excluded.
Product details are correct at time sent to print.

© fischerwerke GmbH & Co. KG


International FireStop
Handbook

Contacts Your dealer

fischerwerke GmbH & Co. KG Phone: +49 7443 12-0


Klaus-Fischer-Straße 1 E-mail [email protected]
72178 Waldachtal www.fischer.de
Germany

fischer fixings UK Ltd. Phone: +44 1491 827900


Whitely Road Fax: +44 1491 827953
Oxon OX10 9AT Wallingford E-mail [email protected]
Great Britain www.fischer.co.uk

fischer Systems Asia Pte. Ltd. Phone: +65 62 85 22 07


150 Kampong Ampat Fax: +65 62 85 83 10
#04-03 KA Centre E-mail [email protected]
Singapore 368324