Fire Stop
Fire Stop
Handbook
Construction fire prevention plays a crucial role in case of fire, which is why the fischer
Group of Companies has developed the fischer FireStop range. The wide range of
passive fire protection products helps to reduce the spread of fire, smoke and toxic
gasses while protecting the lives of occupants as well as the infrastructure. The
development of the product range is the result of over 70 years of experience in the
construction industry and suggestions which arose from close cooperation with
customers and other industry experts. The systems have been tested to both European
and international standards, with many achieving European Technical Approval (ETA)
as well as Underwriters Laboratories (UL) certification.
The broad FireStop range comprises particularly easy to install solutions for effective
fire protection in all relevant fields of application in modern construction projects.
These include facade applications for curtain walls and rainscreen cladding, service
penetrations and solutions for linear gap sealing.
With its numerous services fischer also provides support throughout all construction
phases – from consultations, layout design and training to on-site installation support.
fischer is therefore a reliable partner for passive fire protection for all those involved in
the project.
This international FireStop catalogue serves as your guide for construction fire
protection. Intuitively find the right solutions and the most suitable sealing systems for
simple and more complex applications. The updated catalogue features a clear
overview of the latest products, installation graphics, calculation tables and an index for
approvals and testing.
Marc-Sven Mengis
CEO of the fischer Group of Companies
3
4
Content
Service 1
Good reasons to choose fischer 6-7
Basic knowledge FireStop 8-9
Standards and certifications 10
Advanced product selection guide 11
FireStop in practice 12 - 13
Products 2
Intumescent Acoustic Mastic FiAM 14-15
Intumescent Acoustic Mastic FiAM US 16-17
Fire Rated Silicone Sealant FFRS 18-19
Rapid Fire Seal RFS 640 20-21
Fire | Barr ElastoSeal FFB-ES 22-23
Universal FireStopping Sealant UFS 310 24-25
Intumescent Graphite Mastic FiGM 26-27
Foam Barrier System PLUS 28-29
Intumescent Pipe Wrap FIPW 30-31
Intumescent Wrap Strip FiWS 32-33
Fire Collar FFC 34-35
Cast in Device FCID 36-37
Intumescent Pillows FIP 38-39
Intumescent Putty Pad FiPP 40-41
Coated Panel System FCPS 42-43
FireStop Compound FFSC 44-45
VentiStop Cavity Barrier FFB VS 46-47
Cavity FireStop Clad FCFcl 48-49
FireStop Foam 50-51
Thermal Defense Wrap TDW 52-53
Cable Coating FCC 54-55
Tools and accessories 56
Additional information 3
Sprinkler systems 58-59
Fireproof mounting 60-61
Fixings guide 58-69
Calculation of consumption guide 70-71
Training certification 72
Engineering judgement request form 73
5
Good reasons to choose fischer
6
Good reasons to choose fischer
We take responsibility
Our active environment management policy means that we are
helping to maintain an intact environment for our generation and
for those that follow. The environment management policy at the
Tumlingen site has been certified in line with DIN EN ISO 14001.
We are a member of the German Sustainable Building Council
(DGNB), and our products have been successively certified in line
with the guidelines provided by the Institute for Construction and
the Environment (IBU). With our greenline products, we have
introduced the first fixing assortment in the market, based on over
50% of regrowing raw materials.
7
Basic knowledge FireStop
1
Fire prevention
Basic knowledge FireStop
Fire prevention is a critical consideration for those who are responsible for creating the design, specification and construction of new
buildings, with consideration in the ongoing maintenance of occupied premises.
As the causes of fire vary and are often unpredictable, construction measures are being designed to influence the formation and spread
of fire, smoke and toxic gases, by minimising the available factors needed to create a fire or to limit the spread of fire once it has started.
Effective fire fighting within a building is generally achieved through a combination of active and passive FireStop systems and, when
used in conjunction with each other, provide a balanced fire protection strategy.
8
Basic knowledge FireStop
9
Standards and certifications
1
Approvals, markings and their importance
Standards and certifications
BS EN 1026: 2000
BS EN 1026
BS EN13501-1 EN13501-1:2007+A1:2009 Air permeability test method.
Fire classification of construction
products and building elements.
Reaction to Fire. BS EN 1027: 2000
BS EN 1027
Water permeability test method.
EN13501-2:2007+A1:2009
BS EN13501-2
Fire classification of construction CE marking is a declaration
products and building elements. by the manufacturer (through
Resistance to Fire. verified testing) that the product
ETA-XX/XXXX
ETAG XXX- X meets all the appropriate provi-
XXX
sions of the relevant legislations
EN1366-3:2004 implementing certain European
BS EN1366-3: 2004 Directives. ETA - The European
Fire resistance tests for service
installations - Penetration seals. Technical Assessment provides
information about the construc-
tion product to be declared in
relation to its essential charac-
EN1366-4:2006 teristics.
BS EN1366-4: 2006
Fire resistance tests for service
installations - Linear joint seals.
UL is an abbreviation for Under-
writers Laboratories Inc. which
DIN 4102:Part1 is an independant, not for profit
product safety testing and certifi-
DIN Fire behaviour of building material
cation organisation.
and elements - Part 1: Building
materials, concepts.
ASTM E 1966
American Standard
Test method for Fire-Resistive Joint
ASTM E 1966 Certifire is an independant Third
Systems. This test is used to evaluate
(UL 2079) Party Certification organisation.
the performance of a joint after a
The scheme undertakes require-
cyclic movement test and fire
ments such as the manufacturing
exposure test.
of products under a Third Party
UL 2079 - equivalent. APPROVED PRODUCT
CF xxxx Quality Management System,
Independent Audit Testing, and a
Comprehensive Field of Applica-
ASTM E 814 tions document based on careful
American Standard chosen test that helps to ensure
Test method for Fire Tests of Through
the products and systems are
ASTM E 814 (UL 1479) Penetrations Fire Stops. This test is
used within their approval scope.
used to evaluate the performance of
a firestop system, following fire expo-
sure a hose stream test is conducted.
UL 1479 - equivalent.
10
Advanced product selection guide
Non-metallic pipes
Construction joint
ETA/CE marking
Perimeter joints
Insulated pipes
BS EN 1366-3
BS EN 1366-4
Metallic pipes
FM approval
UL approved
DIN 4102
AS 1530
Air ducts
Intumescent Acoustic Mastic ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ 14
FiAM
Intumescent Acoustic Mastic ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ 16
FiAM US
Fire Rated Silicone Sealant ■ ■ ■ ■ ■ 18
FFRS
Universal FireStopping ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ 24
Sealant UFS 310
Intumescent Graphite Mastic ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ 26
FiGM
FireStop Foam ■ ■ ■ ■ 50
11
FireStop in practice
FireStop Foam
FiAM (US) Intumescent Acoustic Mastic Page 14 / 16 UFS 310 Universal FireStopping Sealant Page 24
FFRS Fire Rated Silicone Sealant Page 18 FiGM Intumescent Graphite Mastic Page 26
RFS 640 Rapid Fire Seal Page 20 FiPW Intumescent Pipe Wrap Page 30
12 FFB-ES Fire | Barr ElastoSeal Page 22 FiWS Intumescent Wrap Strip Page 32
FireStop in practice
FFB VS / FCFcL
FCID
FiWS / FFC
14
Intumescent Acoustic Mastic FiAM
INSTALLATION
1. Clean all surfaces free from loose debris and contaminants and install required backing material.
2. Apply FiAM to required parameters as per approved system, making sure that it is in contact with all surfaces to provide maximum adhesion.
3. Tool sealant to a defect-free finish using a wetted trowel or putty knife.
SPECIFICATIONS
Item Art.-No. Languages on the cartridge Contents Suitable for use with Sales unit
[ml] [pcs]
FiAM 310 053011 DE, FR, EN, IT 310 — 25
FiAM 310 538152 DK, FI, SE, NO 310 — 25
FiAM 310 538150 TR, PT, ES, NL 310 — 25
FiAM 310 538151 PL, SK, CZ, HU 310 — 25
FiAM 600 056006 — 600 —
FiAM 310, FFRS 310, UFS
25 2
KP M2 053117 — — 1
310, FiGM 310
Products
Applicator gun 600 ml 097967 — — FiAM 600 1
All items are available in grey and are subject to minimum order requirement.
TECHNICAL DATA
Chemical base Water-based acrylic
Relative gravity Approx 1.6 g/cm3
Skin-forming time Approx 10 minutes at 23 °C RH
Curing rate Approx 1.5 mm per 24 hours*
Storage temperature +5 °C to +25 °C
Movement capability ± 25 %
Slump Nil up to 30 mm
Shelf-life 18 months (under recommended conditions)
pH Value 8 - 9.5
Sound transmission class (Rw partition and specimen) 63 dB
Yield per l/m Depending on application
Colour White, grey
European Technical Approval ETA 14-0378, ETA 14-0379
CE marking 1121-CPR-JA5044
* Curing rate is dependent on substrate, air humidity and weather conditions.
APPLICATION DATA
Joint width Joint depth Yield per linear metres
B A B
A [mm] [mm]
30 20 0.5
A 20 15 1
B
15 8 1.25
10 10 3
6 6 4.25
15
Intumescent Acoustic Mastic FiAM US
16
Intumescent Acoustic Mastic FiAM US
INSTALLATION
1. Clean all surfaces free from loose debris and contaminants and install required backing material.
2. Apply FiAM US to required parameters as per approved system, making sure that it is in contact with all surfaces to provide maximum adhesion.
3. Tool sealant to a defect-free finish using a wetted towel or putty knife.
SPECIFICATIONS
Item Art.-No. Languages on the cartridge Contents Suitable for use with Sales unit
[ml] [pcs]
FiAM US 546487 DE, EN, ES, TR 310 — 12
FiAM 310, FFRS 310, UFS
KP M2 053117 — — 1
310, FiGM 310
TECHNICAL DATA 2
Chemical base Water-based elastomeric
Products
Density 12.5 +&/ 0.5 lbs.&gal.
Application temperature 4 °C - 49 °C
Skin-forming time Approx. 20 - 30 min.
Curing rate 3 to 4 weeks at 25 °C
Storage temperature 2 °C - 49 °C
Movement capability Up to 33%
Shelf-life Up to 36 months (under recommended conditions)
pH Value 7-8
Sound translission class (dB)
65 dB (STC)
Tested in a UL 411 wall assembly to ASTM E90
Surface burning characteristics Flame spread: 10
ASTM E84 UL 723 Tunnel Test Smoke: 10
Colour Red
APPLICATION DATA
Joint width Joint depth Linear metres per cartridge
B A B
A [mm] [mm]
30 20 0.5
A 20 15 1
B
15 8 2.6
10 10 3
6 10 5.1
17
Fire Rated Silicone Sealant FFRS
▪▪ Concrete
▪▪ Masonry
▪▪ Steel
▪▪ Timber
18
Fire Rated Silicone Sealant FFRS
INSTALLATION
1. Clean all surfaces free from loose debris and contaminants and install required backing material.
2. Apply FFRS to required parameters as per approved system, making sure that it is in contact with all surfaces to provide maximum adhesion.
3. Tool sealant to a defect-free finish using a wetted trowel or putty knife.
SPECIFICATIONS
Item Art.-No. Languages on the cartridge Contents Suitable for use with Sales unit
[ml] [pcs]
FFRS White 310 ml 512374 DE, FR, EN, IT 310 — 12
FFRS White 310 ml 538140 DK, FI, SE, NO 310 — 12
FFRS White 310 ml 538138 TR, PT, ES, NL 310 — 12
FFRS White 310 ml 538139 PL, SK, CZ, HU 310 — 12 2
FiAM 310, FFRS 310, UFS
KP M2 053117 — — 1
310, FiGM 310
Products
All items are available in grey and are subject to minimum order requirement.
TECHNICAL DATA
Cure system Alcoxy
Relative gravity 1.17 kg/m3
Skinning time Approx. 5/10 minutes (at 25 °C and 50 % relative humidity)
Tack free time Approx. 20 minutes (at 25 °C and 50 % relative humidity)
Full cure Approx. 2 - 3 mm per 24 hours (at 25 °C and 50 % relative humidity)
Shore a hardness 16
Extrudability g/min 55 (standard NMRPS 495A 3 mm/3 bars)
Movement accommodation ± 25 %
Application temperature range +5 °C to +40 °C
Service temperature range Range: -50 °C to +150 °C - must not be stored above 35 °C
Shelf life Up to 12 months when stored in unopened cartridges under cool, dry conditions
Colour White, grey, black
European Technical Approval ETA 15-0799
Elastic recovery > 90 %
Slump Nil up to 30 mm
Sound transmission class (Rw partition and specimen) 38 dB
The cured sealant is unaffected by water, dilute acids and alkalis, soap and household detergents. Certain solvents may soften and swell the cured rubber on prolonged contact.
APPLICATION DATA
Joint width Joint depth Yield per linear metres
A B
A B [mm] [mm]
30 20 0.5
A 20 15 1
B 15 8 1.25
10 10 3
6 6 4.25
Above provides approx. yield from 1 x 310 ml cartridge
19
Rapid Fire Seal RFS 640
20
Rapid Fire Seal RFS 640
INSTALLATION
1. Clean all surfaces free from loose debris and contaminants, and install required backing material as per approved system.
2. Apply RFS 640 to the required parameters making sure that it is in contact with all surfaces to provide maximum adhesion.
3. Tool sealant to a defect-free finish using a wetted trowel or putty knife.
SPECIFICATIONS
Item Art.-No. Contents Sales unit
[l] [pcs]
RFS 640 516539 19 1
TECHNICAL DATA
Chemical base Water-based 2
Density Approx 1.25 g/cm3
Application temperature +5 °C to +40 °C
Products
Skin-forming time at 25 °C Approx. 30 - 45 minutes*
Curing time at 25 °C Approx. 5 - 7 days*
Storage temperature +2 °C to +49 °C
Movement capability Up to 50 %**
Water resistant Yes***
Shelf life 36 months from manufacturing (under recommended conditions)
pH Value 7 to 8
Sound transmission class (dB)
65 dB
Tested in a UL 411 wall assembly to ASTM E90
Surface burning characteristics Flame spread: 0
ASTM E 84 UL 723 Tunnel Test Smoke index: 0
Colour Red
* Skin-forming and curing time is dependant on substrate, air humidity and weather conditions.
** Movement capability depends on UL listed system and configuration.
*** Is water resistant in accordance with UL 2079.
APPLICATION DATA
Joint width Joint width Ft/gallon Ft/pail LM/gallon LM/pail
[inch] [mm]
0.25 6 198 1,325 89 404
0.50 13 164 1,099 74 335
0.75 19 141 941 63 287
1.00 25 124 830 56 253
1.25 32 109 731 49 223
2.00 51 82 548 37 167
4.00 102 49 328 22 100
6.00 152 35 233 16 71
8.00 203 27 180 12 55
The above table provides an approx. yield for a coverage of 1/16“ (1.5 mm WFT) with a 1/2“ (12.5 mm) overlap.
21
Fire I Barr ElastoSeal FFB-ES
22
Fire I Barr ElastoSeal FFB-ES
INSTALLATION
1. Use rubber gloves and eye protection to avoid skin and eye contact.
2. Cut 80 kg/m3 x 100 mm thick rock wool to suit opening. Allow a minimum of 10 mm compression or 30 % for movement joints.
3. Install Z Brackets at mid section of stone wool for openings in excess of 250 mm.
4. Compress stone wool into opening, ensuring all joints are butted tightly and surface is flush to slab.
5. Apply FFB-ES via spray, brush or trowel, to minimum 2.5 mm WFT, ensuring a minimum of 12 mm overlap to slab and rear of panel/wall.
SPECIFICATIONS
Item Art.-No. Content Colour Sales unit
[kg] [pcs]
FFB-ES/White 520753 20 white 1
FFB-ES/Grey 520755 20 grey 1
FFB-ES/Red 520756 20 red 1 2
Quantity per box is subject to minimum order requirement.
Products
TECHNICAL DATA
Description Water-based, flexible acrylic coating
Colour White = standard/grey and red to order only
Density 1.25 – 1.3 g/cm³
Coating thickness 2.5 mm nominal, wet film thickness
Sealant coverage 2.8 kg/m², 2.24 l/m²
Fire resistance EN1366-4:2006 120 EI
43 dB when installed with one 100 mm thick 80 kg/m³ stone wool and tested to EN10140
Acoustic performance
52 dB when installed with 200 mm thick 80 kg/m³ stone wool and testedTested to EN10140
Air permeability 600 PA positive and negative pressure and tested to EN1026
Water permeability 450 PA positive pressure and tested to EN1027
Container size 20 kg
For optimum results, an airless sprayer should be utilised at a pressure of 90 psi using a spray tip of approx.
Spraying guidance
29 - 35 thou. +5 °C and +32 °C
For long term storage and ease of installation, it is recommended that ElastoSeal be stored indoors and in
Application temperature
dry conditions
Storage temperature between -5 °C and +25 °C. For health and safety details, refer to fischer technical
Storage and disposal
department
Shelf life 12 months from date of manufacture
European Technical Approval ETA 15-0203
CE marking 1121-CPR-JA5065
APPLICATION DATA
Joint width Joint width Ft/gallon Ft/pail LM/gallon LM/pail
[inch] [mm]
0.25 6 119 800 54 244
0.50 13 99 683 44 202
0.75 19 85 567 38 173
1.00 25 73 492 33 150
1.25 32 66 443 30 135
2.00 51 49 328 22 100
4.00 102 31 207 14 63
6.00 152 22 148 10 45
8.00 203 16 108 7 33
The above table provides an approx. yield for a coverage of 2.5 mm Wet Film Thickness (WFT) with a 12.5 mm overlap.
Figures above are approx. guide only.
23
Universal FireStopping Sealant UFS 310
24
Universal FireStopping Sealant UFS 310
INSTALLATION
1. Clean all contact surfaces so they are free from loose debris and contaminants such as oil, dirt, grease, wax, old sealant, etc.
2. Install the required backing material as per the detailed instruction or approved system under compression.
3. Apply UFS 310 to required parameters as per detailed instruction or approved system, making sure that it is in contact with all surfaces to provide maximum
adhesion.
4. Tool sealant to a defect-free finish using a wetted towel or putty knife.
SPECIFICATIONS
Item Art.-No. Languages on the Contents Contents Suitable for use with Sales unit
cartridge
[ml] [l] [pcs]
UFS 310 516538 DE, FR, EN, NL 310 — — 12
UFS 310 538137 DK, FI, SE, NO 310 — — 12 2
UFS 310 538135 TR, PT, ES, IT 310 — — 12
UFS 310 538136 PL, SK, CZ, HU 310 — — 12
Products
UFS 19 liter bucket 533889 — — 19 — 1
FiAM 310, FFRS 310,
KP M2 053117 — — — 1
UFS 310, FiGM 310
TECHNICAL DATA
Chemical base Water-based elastomeric
Density Approx. 1.31 g/cm3
Application temperature +5 °C to +40 °C
Skin-forming time Approx. 20 - 30 min.
Curing rate Approx. 4 mm in 72 hours*
Storage temperature +2 °C to +49 °C
Movement capability Up to 50 %**
Intumescent activation From 190 °C to 593 °C
Shelf life Up to 36 months (under recommended conditions)
pH Value 6.5 to 7
Sound transmission class (dB)
62 dB
Tested in a UL 411 wall assembly to ASTM E90
Surface burning characteristics Flame spread: 0
ASTM E 84 UL 723 Tunnel Test Smoke index: 0
Colour Red
* Curing rate is dependant on substrate, air humidity and weather conditions.
** Movement capability depends on UL listed system and configuration.
APPLICATION DATA
Services Fire ratings (minutes)
25
Intumescent Graphite Mastic FiGM
▪▪ Concrete
▪▪ Masonry
▪▪ Steel
▪▪ Timber
26
Intumescent Graphite Mastic FiGM
INSTALLATION
1. Clean all contact surfaces so they are free from loose debris and contaminants.
2. Install the required backing material as per the detailed instruction or approved system.
3. For best application results, FiGM should be at room temperature.
4. Apply FiGM to required parameters as per detailed instruction or approved system, making sure that it is in contact with all surfaces to provide maximum
adhesion.
5. Tool sealant to a defect-free finish using a wetted towel or putty knife.
6. Clean all equipment with water immediately after use.
SPECIFICATIONS
Item Art.-No. Languages on the cartridge Contents Suitable for use with Sales unit
[ml] [pcs]
FiGM 310 ml 508765 DE, FR, EN, IT 310 — 25 2
FIGM 310 ml 538147 TR, PT, ES, NL 310 — 25
Products
FiGM 310 ml 538148 PL, SK, CZ, HU 310 — 25
FiGM 310 ml 538149 DK, FI, SE, NO 310 — 25
FiAM 310, FFRS 310, UFS
KP M2 053117 — — 1
310, FiGM 310
TECHNICAL DATA
Form Aqueous thixotropic paste
Density Ca. 1.3g/cm3
Cure rate 1.7 mm per 24 hours dependent on conditions
Application temperature +5 °C to +35 °C
Tack free 30 minutes
Cure system Water-based
U.V. resistance Good
Expansion onset temperature Ca. 180 °C
Expansion Up to 20 times
Skinning time 15 minutes at 25 °C / 50 % RH
Service temp range Store in cool dry conditions between ±5 °C and ±25 °C
Sound transmission (Rw partition and specimen) 64 dB
Shelf life Up to 18 months unopened
European Technical Approval ETA 14/0381
CE marking 1121-CPR-JA5047
The cured sealant is unaffected by water, dilute acids and alkalis, soap and household detergents. Contains a
Chemical and water resistance plasticised acrylic polymer, fire retardant fillers, blowing agents and mirror additives. No component labelled
as dangerous under EEC directives criteria.
APPLICATION DATA
Services Fire ratings (minutes)
27
Foam Barrier System PLUS
28
Foam Barrier System PLUS
INSTALLATION
1. Clean all contact surfaces so they are free from loose debris and contaminants.
2. Install the required backing material as per the detailed instruction or approved system.
3. Unscrew cap from cartridge and insert into the dispensing gun.
4. Discard non-uniform initial material.
5. Fill the opening from back to front. Build up the foam from bottom to top.
6. After 2 minutes, tool foam to a defect-free finish using a suitable knife.
7. Cables or pipes that will be installed retroactively can be routed through the existing foam. Refill gaps due to removed cables or pipes with FBS foam.
SPECIFICATIONS
Item Art.-No. Languages on the cartridge Contents Dimensions Sales unit
[ml] [mm] [pcs]
FBS-UL 544079 — 380 — 6 2
FBB-UL FireStop Block 544083 — — 200 mm x 130 mm x 60 mm 12
FBS-EN 544084
Products
DE, FR, EN, IT 380 — 6
FBS-EN 544085 DK, FI, SE, NO 380 — 6
FBS-EN 544086 PL, SK, CZ, HU 380 — 6
FBS-EN 544087 TR, PT, ES, NL 380 — 6
FBB-EN FireStop Block 544088 — — 200 mm x 144 mm x 60 mm 4
FIB Insulating Bandage 544089 — — 5000 mm x 150 mm 1
FFBD Foam Barrier Dispenser 544090 — — — 1
TECHNICAL DATA
Criteria FBS-UL FBS-EN FBB-UL FBB-EN
Density ≥ 215 kg/m³ 240 kg/m³ to 300 kg/m³
Temperature resistance ≤ 80 °C ≤ 80 °C ≤ 80 °C ≤ 80 °C
Construction material class B2 - as per DIN 4102 B2 - as per DIN 4102
Cartridge content 380 ml 380 ml
Yield ≤ 1.9 l ≤ 2.1 l
Cure time Approx. 90 s Approx. 90 s
Colour Red-brown Red-brown Red-brown Red-brown
Pack size Boxed in 6 Boxed in 6 Boxed in 4 Boxed in 18
12 months from date of 12 months from date of
Shelf life
manufacturing manufacturing
Storage Temperature +5 °C to +30 °C +5 °C to +30 °C
Sound Transmission Class 43.5 dB - 66 dB 45.5 dB - 68 dB
Application Temp Range +15 °C to +30 °C +15 °C to +30 °C
APPLICATION DATA - UL
Blank Opening Metallic Pipes and Cables / Cable Trays Insulated Metal Pipes Mixed Penetrations
Conduits
29
Intumescent Pipe Wraps FiPW
ASSESSMENT/APPROVAL
Products
30
Intumescent Pipe Wraps FiPW
INSTALLATION
1. Clean all contact surfaces so they are free from loose debris and contaminants.
2. Ensure services are sufficiently supported as per approved system or local building codes.
3. Choose the correct size of FiPW or FiPW-E in accordance with the pipe diameter.
4. Wrap FiPW or FiPW-E around the pipe and fix tightly in required position.
5. Backfill with FiAM or FFSC as per detailed instruction or approved system.
SPECIFICATIONS
Item Art.-No. Fits pipe-Ø Fire rating Sales unit
[pcs]
FiPW E / 2 mm (25 meter roll) 539608 30 - 200 2 1
FIPW 2/30-32 052546 30 - 32 2 20
FIPW 2/38-40 052547 38 - 40 2 20 2
FIPW 2/55 052548 55 2 20
FIPW 2/63 052560
Products
63 2 20
FIPW 2/75 052561 75 2 20
FIPW 2/82 052562 82 2 20
FIPW 2/110 052563 110 2 20
FIPW 2/125 052890 125 2 20
FIPW 2/160 052891 160 2 20
FIPW 2/200 053000 200 2 20
TECHNICAL DATA
State Solid
Colour Black inner component in outer red carrier
Odour Odourless
Density 1.3 kg/m3
Expansion ratio 1 : 25
Significant expansion occurs at temperature > 180 °C
Application temperature -40 °C to 130 °C minutes
Available sizes > 30 mm and max. up to 200 mm
Storage temperature N/a
Shelf life 60 months
Dimensions (thickness x diameter) 4 mm up to 63 mm - 6 mm up to 110 mm - 10 mm thereafter ...; 2 mm for 25 meter roll.
APPLICATION DATA
Configuration for up to 120 min.
Outer pipe diam. No. wraps Thickness Length (theoretically) for FiPW E
[mm] [mm]
40 1 2 126
55 2 4 352
63 2 4 402
Partitions 2 x FiPW 75 2 4 478
82 2 4 521
90 3 6 867
110 3 6 1055
125 4 8 1608
160 4 8 2047
200 5 10 3203
Partitions 2 x FiPW
31
Intumescent Wrap Strip FiWS
ASSESSMENT/APPROVAL
Products
32
Intumescent Wrap Strip FiWS
INSTALLATION
1. Clean all contact surfaces so they are free from loose debris and contaminants.
2. Ensure services are sufficiently supported as per approved system or local building codes.
3. Choose the correct size of FiWS in accordance with the pipe diameter.
4. Wrap FiWS around the pipe and fix it tightly.
5. Backfill with FiAM or FFSC as per approved system.
SPECIFICATIONS
Item Art.-No. Dimensions Sales unit
[mm / inch] [pcs]
FiWS-2 531397 50 mm x 6 mm x 3.66 m / 2˝x 1/4˝ x 12˝ 1
Universal Collar 2 536053 51 mm x 15 m / 2“ x 50 ft 1
2
TECHNICAL DATA
Products
State Solid
Colour Black inner component in outer red carrier
Odour Odourless
Density 1.3 kg/m3
Expansion ratio 1 : 40
Significant expansion occurs at temperature > 190 °C
Application temperature -40 °C to 130 °C
Max. Pipe diameter Max. < 355 mm (14“)
Flame spread (ASTM E 84 - UL723) 5
Smoke index (ASTM E 84 - UL723) 5
Shelf life 5 years = 60 months
APPLICATION DATA
FiWS 2 - typical configuration
Pipe diameter No. of layers No. of stacks for 2“ wraps Length
[mm] [m]
50 1 1 0,34
75 2 1 1,1
100 2 1 1,42
150 3 1 3,18
200 4 1 5,64
305 4 2 16,56
Both sides of the wall
Bottom of floor
Note: For detailled information please refer to the appropriate UL listed systems.
33
Fire Collar FFC
34
Fire Collar FFC
INSTALLATION
1. Clean all contact surfaces so they are free from loose debris and contaminants.
2. Ensure services are sufficiently supported as per approved system or local building codes.
3. Close the annular space as per requirement with FiAM, FCPS or FFSC and choose the correct size of FFC in accordance with the pipe diameter.
4. Open the toggle clip, place FFC around the pipe with its fixing lugs pointing towards the building element.
5. Lock the toggle clip and push it tightly against the surface of building element.
6. Attach the collar to the building element through the mounting lugs with a minimum anchoring depth of 32 mm and minimum 8 mm diameter fixing (please
refer to fischer fire rated fixing section for correct anchor).
7. For vertical applications, repeat installation on both sides as per the instruction in the approved system.
SPECIFICATIONS
Item Art.-No. Dimensions
BxLxH
Sales unit
2
[mm / inch] [pcs]
Products
FFC 2/30-32 052456 30 - 32 1
FFC 2/38-40 052480 38 - 40 1
FFC 2/55 052481 55 1
FFC 2/63 052482 63 1
FFC 2/75 052483 75 1
FFC 2/82 052486 82 1
FFC 2/90 052487 90 1
FFC 2/110 052488 110 1
FFC 2/125 052489 125 1
FFC 2/160 052500 160 1
FFC 2/200 052501 200 1
TECHNICAL DATA
State Solid
Colour Red sleeve with black inner component
Odour Odourless
Fire rating Up to 4 hours
Available sizes > 30 mm and max up to 200 mm
Significant expansion occurs at temperature > 180 °C
Storage temperature N/a
Shelf life N/a
35
Cast in Device FCID
36
Cast in Device FCID
INSTALLATION
Products
SPECIFICATIONS
Item Art.-No. Fits pipe-Ø Hight x Shell diam. Sales unit
[pcs]
FCID 65 Cast in Device 509532 Nom 3”/75 mm Pipe 95 mm OD x 250 mm high - base = 154 mm x 154 mm 1
FCID 100 Cast in Device 506324 Nom 4”/110 mm Pipe 140 mm OD x 250 mm high - base = 198 mm x 198 mm 1
FCID 150 Cast in Device 509533 Nom 6”/160 mm Pipe 194 mm OD x 250 mm high - base = 253 mm x 253 mm 1
FCID 65-E/1000 Extension Tube 509791 FCID 65 CI 95 mm ID x 101 mm OD x 1000 mm long 1
FCID 100-E/1000 Extension Tube 509792 FCID 100 CI 140 mm ID x 147 mm OD x 1000 mm long 1
FCID 150-E/1000 Extension Tube 509793 FCID 150 CI 194 mm ID x 201 mm OD x 1000 mm long 1
FCID 65-C Extension Cap 511450 FCID 65-E/1,000 93.5 mm - 96.5 mm tapered OD x 19 mm high 1
FCID 100-C Extension Cap 509794 FCID 100-E/1,000 139 mm - 142.5 mm tapered OD x 25.4 mm high 1
FCID 150-C Extension Cap 511451 FCID 150-E/1,000 194.5 mm - 199 mm tapered OD x 25.4 mm high 1
FCID-MRF Manifold Recess Former 517846 FCID 100 CI 250 mm - 220 mm x 250 mm - 220 mm x 60 mm tapered recess 1
88 mm - 91.5 mm tapered OD x 19.5 mm high
FCID 65-CP Cap Plug 510878 FCID 65 CI 1
131.5 mm - 136 mm tapered OD x 25.4 mm high
FCID 100-CP Cap Plug 510879 FCID 100 CI 131.5 mm - 136 mm tapered OD x 25.4 mm high 1
FCID 150-CP Cap Plug 510880 FCID 150 CI 186 mm - 194 mm tapred OD x 25.4 mm high 1
Note: Details on 4 hours fire rated wraps are available on request.
TECHNICAL DATA
State Solid
Colour Fluorescent yellow
Odour Odourless
Shell material Polyethylene
Fire rating 4 hours - BS 476: Part 20 and AS 1530: Part 4
Suitable for pipe diameter Max up to 150 mm
Standard height 250 mm
Extension or reduction in height possible Yes
Standard flange width Min. 154 mm and max 254 mm
Significant expansion occur at temperature > 160 °C
Storage temperature N/a
Shelf life N/a
37
Intumescent Pillows FiP
ASSESSMENT/APPROVAL
Products
38
Intumescent Pillows FiP
INSTALLATION
1. Clean all contact surfaces so they are free from loose debris and contaminants.
2. Ensure services are sufficiently supported as per approved system or local building code.
3. Shake the pillows to make the infill material uniform before installation.
4. Push the pillow into the hole so that the longest dimension spans across the wall. If installing in floor, mechanically fix galvanised steel mesh 50 x 50 x 5
mm to the underside of the opening with a 100 mm overlap of the floor slab.
5. Pack the pillows in a brick bond fashion, to ensure the joints between the pillows are staggered. Use small-sized pillows in between to pack the hole tight
against the edges.
6. For electrical trunking, remove the lid and install a pillow inside so it aligns with the depth of the wall. Replace the lid on the electrical trunking.
SPECIFICATIONS
Item Art.-No. Dimensions
[mm]
Sales unit
[pcs]
2
FiP/S 516960 330 mm x 50 mm x 20 mm 50
Products
FiP/Std 533890 330 mm x 100 mm x 20 mm 25
FiP/M 516959 330 mm x 200 mm x 25 mm 50
FiP/L 516958 330 mm x 200 mm x 45 mm 25
TECHNICAL DATA
State Solid
Colour Black
Odour Odourless
Weight per pillow FiP/S - 80 g, FiP/Std - 120 g, FiP/M - 230 g, FiP/L - 420 g
Volumetric expansion 3 times
Significant expansion occurs at temperature > 140 °C
Remain flexible between -20 °C to 130 °C
European Technical Approval ETA 14-0380
CE marking 1121-CPR-JA5046
ESTIMATION QUANTITIES
Width Length [mm]
Size Large Medium Large Medium Large Medium Large Medium Large Medium Large Medium
[mm] Seal type 100 300 500 700 900 1,000
Wall 3 5 7 13 12 22 17 31 21 39 24 47
200
Floor 2 3 4 7 6 12 9 17 11 22 12 27
Wall 5 9 14 26 24 44 33 61 42 78 47 95
400
Floor 3 5 7 15 12 24 17 34 22 43 24 52
Wall 7 13 21 39 35 65 49 91 63 117 70 143
600
Floor 4 7 11 22 18 36 25 51 33 65 36 79
Wall 9 18 28 52 47 87 66 122 84 157 94 192
800
Floor 5 10 15 29 24 48 34 67 33 87 48 107
Wall 10 22 35 65 59 109 82 152 105 196 117 217
1,000
Floor 6 12 18 36 30 60 42 84 54 108 60 120
39
Intumescent Putty Pad FiPP
40
Intumescent Putty Pad FiPP
INSTALLATION
Internal
1. Remove the face-plates of the electrical outlet.
2. Clean all contact surfaces so they are free from loose debris and contaminants.
3. Mould the preformed putty pads into the back of the box and around the cables.
4. Replace the face-plate.
External
1. Clean all contact surfaces so they are free from loose debris and contaminants.
2. Mould the preformed putty pads onto the back of the box and around the cables.
SPECIFICATIONS
Item Art.-No. Dimensions
[mm]
Colour Fire rating Sales unit
[pcs]
2
FiPP/I-S 053578 170 x 170 red 2 25
Products
FiPP/I-D 054757 230 x 170 red 2 50
FiPP/E-S 506261 155 x 155 red 2 25
FiPP/E-D 506262 210 x 180 red 2 —
TECHNICAL DATA
Base material Drywall
Specific gravity 1.55 kg/m3
Sound transmission class (Rw of partition and specimen) 66 dB
Slump Nil
Application temperature range +4 °C to 40 °C
Service temperature rate -70 °C to 120 °C
Shelf life 18 months
41
Coated Panel System FCPS
ASSESSMENT/APPROVAL
Products
42
Coated Panel System FCPS
INSTALLATION
1. If opening size is greater than 1,200 x 1,200 mm then a steel angle for mechanical support should be installed as per detailed instruction or approved
system.
2. Clean all contact surfaces so they are free from loose debris and contaminants.
3. Cut FCPS as per the required opening size, so that it can be fitted under friction into aperture with as few joints as possible.
4. Prior to installation, coat all exposed areas of FCPS with FPC.
5. Install FCPS section into aperture so it is compression fitted.
6. For multiple or mixed services passing through opening please use appropriate fire stopping device:
a. Use FiAM for metallic pipes, cables, cable trays and ducts.
b. Use FiPW for non-metallic pipes.
SPECIFICATIONS
Item Art.-No. Dimensions Contents Contents Suitable for use with Sales unit
2
DxsxLxB
Products
[mm] [l] [ml] [pcs]
FCPS/50 053252 1200 mm x 600 mm x 50 mm — — — 1
FPC/5lt 053253 — 5 — — 1
FiAM 310 053011 — — 310 — 25
FiAM 310, FFRS 310,
KP M2 053117 — — — 1
UFS 310, FiGM 310
TECHNICAL DATA
Dimensions 1200 mm x 600 mm x 50 mm
Density of board 140 kg/m3
Coating thickness 1 mm DFT
Fire resistance Depending on application
23 dB mean reduction up to 56 dB reduction (with one 50 mm FCPS board). 29 dB mean reduction up to
Acoustic performance
65 dB reduction (with two 50 mm FCPS board)
Thermal conductivity (U value) 0.034 W/mK at 10 °C
Maximum size of seal Wall 5.76 m2, floor 2.88 m2
Maximum size unsupported 1.2 m x 1.2 m (no services)
Mechanical support 30 mm x 30 mm x 1.6 mm steel angle
Density of panel coating FPC 1.25 - 1.3 g/cm3
Panel coating FPC coverage 3.5 litres/m2
Shelf life of board N/a
Shelf life of panel coating FPC 12 months
European Technical Approval ETA 14-0388 and ETA 14-0382
CE marking 1121-CPR-JA5050
Note: Please refer to the appropriate approvals for details.
APPLICATION DATA
Services Rigid partition walls Flexible partition walls Concrete floors
43
FireStop Compound FFSC
ASSESSMENT/APPROVAL
Products
44
FireStop Compound FFSC
INSTALLATION
1. Service penetrations should be rigidly supported as per local building codes or approved standards.
2. Clean all contact surfaces so they are free from loose debris and contaminants such as oil, dirt, grease, wax, old sealant, etc.
3. Pouring: Mix compound with water in 2.5:1 parts by volume. Do not mix weaker than 2:1.
4. Shutter into the opening to ensure a tight fit so that once the required depth of compound is installed, it finishes flush with the floor.
5. Mix and pour compound until the required thickness is achieved.
6. If the opening is greater than 1,200x1,200 mm, appropriate reinforcement may be required.
SPECIFICATIONS
Item Art.-No. Weight Sales unit
[kg] [pcs]
FFSC/20 kg 533247 20 1 2
Products
TECHNICAL DATA
Chemical base Gypsum
Colour Off white
Weight 20 kg
Bulk density 950 kg/m3
Wet density 1,850 kg/m3
Setting time (min) 20
Application temperature range +5 °C to +40 °C
Temperature resistance -5 °C to +100 °C
Compressive strength 17 N/mm2
Sound insulation (Rw partition and specimen) 59 dB
Reaction to fire (EN13501-1) Class F
Shelf life 12 months
European Technical Approval ETA 14-0387
Tensile strength 30/mm2
Thermal conductivity – EN1745 0.57 W/mK at 50 % /0.65 W/mK at 90 %
Average yield 4 bags per M2 at 100 mm thickness
APPLICATION DATA
By volume
45
VentiStop Cavity Barrier - FFB VS
46
VentiStop Cavity Barrier - FFB VS
SPECIFICATIONS FFB-VS
Item Art.-No. To suit cavity void width Colour Sales unit
[mm] [pcs]
FFB-VS/25-50 521520 25 - 50 Red/silver/black 48
FFB-VS/51-100 521521 51 - 100 Red/silver/black 24
FFB-VS/101-150 521522 101 - 150 Red/silver/black 48
FFB-VS/151-200 521523 151 - 200 Red/silver/black 14
FFB-VS/201-250 521524 201 - 250 Red/silver/black 11
FFB-VS/251-300 521525 251 - 300 Red/silver/black 11
FFB-VS/301-350 521526 301 - 350 Red/silver/black TBA
FFB-VS/351-400 521527 315 - 400 Red/silver/black 9
FFB-VS/401-450 521528 401 - 450 Red/silver/black 6
IMPORTANT: Please provide TOTAL cavity width for your application, excluding any insulation there might be.
2
SPECIFICATIONS FFB-VS50
Products
Item Art.-No. To suit cavity void width Colour Sales unit
[mm] [pcs]
FFB-VS50/51-100 545628 51 - 100 Red/silver/black 48
FFB-VS50/101-150 545629 101 - 150 Red/silver/black 24
FFB-VS50/151-200 545630 151 - 200 Red/silver/black 48
FFB-VS50/201-250 545631 201 - 250 Red/silver/black 14
FFB-VS50/251-300 545632 251 - 300 Red/silver/black 11
FFB-VS50/301-350 545633 301 - 350 Red/silver/black 11
FFB-VS50/351-400 545634 351 - 400 Red/silver/black TBA
FFB-VS50/401-450 545635 401 - 450 Red/silver/black 9
IMPORTANT: Please provide TOTAL cavity width for your application, excluding any insulation there might be.
TECHNICAL DATA
Description Foil faced stone with a black intumescent leading edge
Fire resistance - FFB-VS Up to 120 minutes
Closure time - FFB-VS needs to be < 5 min
Activation Approx. 180 °C (intumescent material)
Expansion pressure Approx. 07 N/mm2
Density Stone wool - 80 kg/m3 intumescent 1.3 g/cm3
Weather resistance Yes
Sag 0%
Open void size - FBB-VS 25 mm to 50 mm
Dimensions 80 mm Thick 1000 mm Long
Width FBB-VS (30 mm to 450 mm)
Fixing points (Brackets or DHM Anchor) FBB-VS (300 mm Centres)
47
Cavity FireStop Clad FCFcl
2 FCFcl Cavity Clad - Horizontal application FCFcl Cavity Clad - Vertical application
48
Cavity FireStop Clad FCFcl
SPECIFICATIONS FCFCL
Item Art.-No. To suit cavity void width Colour Fire rating Sales unit
[hours]
[mm] [pcs]
FCFcl 75 546210 1200 x 600 x 75 silver up to 2* 1
FCFcl 100 053046 1200 x 600 x 100 silver up to 2* 1
FCFcl 1200 546209 1200 x 1200 x 100 silver up to 2* 1
IMPORTANT: Please provide TOTAL cavity width for your application, excluding any insulation there might be.
FCFcl Cavity Clad shall be cut 10 mm (3/8 in.) over size.
* Depending on design & configuration of the FCFcl Cavity Clad.
Products
390 x 25 x 1 (A2) N/A 1
Multi Purpose Bracket 551954 500 x 25 x 1 (A2) N/A 1
TECHNICAL DATA
Description Foil faced structural stone wool composite
Fire resistance - FCFcl BS467 20 / EN1366-4 up to 120min
Classification EN 13501-2:2007 + A1:2009, ETAG 026
Thermal 0.35 to 0.36W/mk
Density 80 kg/m3
Build Stone wool - 80 kg/m3 intumescent 1.3 g/cm3
Acoustic (EN10140) 31db
Air permeability (EN1026) 600 pa - 100 pa 2.6/4.2 m3/h/m2
Thickness 75 mm & 100 mm
Dimensions 1200 x 600 & 1200 x 1200
Compression Min 10 mm
Brackets Required over cavity of 150 mm (2 per meter)
49
FireStop Foam
▪▪ Concrete
▪▪ Masonry
▪▪ Steel as backing material
▪▪ Timber as backing material
50
FireStop Foam
INSTALLATION
1. Clean all contact surfaces so they are free from loose debris and contaminants such as oil, dirt, grease, wax, old sealant etc.
2. Dampen the substrate surfaces with clean water before application to improve adhesion and curing rate.
3. Protect adjacent surfaces with paper of a plastic film.
4. Shake the canister vigorously at least 20 time before use, and again periodically during application.
5. Remove the cap and screw the nozzle firmly into the connector on the top of the valve.
6. Gently pull the trigger to dispense foam, whilst holding the canister inverted.
7. Fill approximately half of the required depth of the cavity to allow for expansion of the foam. Should gaps be more than 30 mm then, apply the foam in
beads and pre-moisten between layers.
8. On horizontal surfaces always work away from the bead and work upwards on all vertical surfaces.
9. Please note that cured foam is adversely effected by UV light and should be protected with a suitable paint or sealant.
SPECIFICATIONS 2
Item Art.-No. Contents Sales unit
Products
[ml] [pcs]
FireStop Foam Hand 042757 750 12
FireStop Foam Gun 043712 750 12
TECHNICAL DATA
Base Polyurethane
Consistency Stable foam
Curing system Moisture-cure
Yield 1,000 ml yields 35 - 40 l cured foam when extruded in beads
Specific gravity Ca. 27 kg/m3 extruded, fully cured
Skinning formation (20 °C/65 % R.H.) 10 min
Drying time (20 °C/65 % R.H.) Non tacky after approx. 8 min
Curing rate (20 °C/65 % R.H.) hr for 30 mm bead
Shrinkage None
Post expansion None
Cellular structure 70 % closed cells, fine cellular structure
Temperature resistance -40 °C to +90 °C when cured
Colour Light red
Packaging 750 ml can
Storage temperature +5 °C to +25 °C
Shelf life Up to 12 months when stored in unopened cartridges under cool, dry conditions
Construction material as per DIN 4102 B1
STC rating 58 dB
51
Thermal Defense Wrap TDW
ASSESSMENT/APPROVAL
Products
52
Thermal Defense Wrap TDW
INSTALLATION
1. Clean all contact surfaces so they are free from loose debris and contaminants such as oil, dirt, grease, wax, old sealant, etc.
2. Measure and mark the TDW to the required service configuration.
3. Cut TDW as per requirements with a standard pair of scissors or snips.
4. Wrap TDW around service configuraion and apply alufoil tape to secure in place.
SPECIFICATIONS
Item Art.-No. Dimensions Sales unit
[mm] [pcs]
TDW 1 531398 300 x 15,000 1
TECHNICAL DATA
2
Odor and appearance White, fibrous material with aluminium foil face
Products
Chemical family Calcium magnesium silicate fibres
Boiling point N/a
Water solubility (%) Less than 1 mg/l > 1200 °C
Relative density 180Kg/m3 - 250Kg/m3
Alufoil thickness 0.25 mm normal
Dimension (thickness mm) 6
Size (width x length mm) 300 x 15,000 long roll or 1,200 x 500 sheet
Shelf life 36 months (under recommended conditions)
Storage temperature -5 °C to +25 °C
Colour White, silver
53
Cable Coating FCC
▪▪ Drywall
▪▪ Concrete
▪▪ Masonry
54
Cable Coating FCC
SPECIFICATIONS
Item Art.-No. Content Sales unit
[kg] [pcs]
FCC 539609 12.5 1
TECHNICAL DATA
Chemical base Water-based
Density 1,55 g/cm³
Application temperature + 5 °C to + 40 °C
Storage temperature +5 °C to +30 °C to be protected from frost and direct sunlight
Odour slight
Water resistant yes
Shelf life 1 year 2
pH Value approx. 8
Coating thickness 0.5 - 0.8 mm (IEC 60332-3)
Products
(Dry film) 1.6 mm (Factory Mutual)
Colour White
Curing time at room temperature 1 - 3 days*
* Depending on humidity, air and ambiant temperature.
55
Tools and accessories
FOAM GUNS
FOAM GUNS
Products
FOAM GUNS
56
2
57
Products
Sprinkler systems
APPLICATIONS APPROVALS
▪▪ Industrial companies
▪▪ High-bay warehouses
▪▪ Office buildings VdS
▪▪ Logistics areas
▪▪ Public buildings and institutions Sign of conformity VdS CEA 4001
▪▪ Sales entities in concrete ceilings:
▪▪ High-rises
▪▪ Underground garages
▪▪ Museums
▪▪ Congress and conference centres
FUNCTIONING
Sprinkler systems fall into the category of active fire protection (AFP) and could be considered as detection and suppression sys-
tems, which usually covers the complete floor plan. This means that sprinklers are usually installed in all rooms of a building and
are designed in accordance with the actual fire hazard, the temperature - dependent opening of the sprinkler normally activates
an acoustic sound and sends a signal to the fire control system. Over the past decade, sprinkler systems extinguishing rates have
been high and, as a result, are standard in some types of buildings.
Sprinkler systems
In general, sprinkler systems are designed in accordance with the following standards: VdS CEA 4001 Section 15.2.4 Anchorage
in Concrete Ceilings, FM 1951 Section 3.2 Technical and Constructional Properties, UL 203 Section 11.3 Pipe Hangers for Fire
Protection Systems, NFPA 13 Section 9.1.3 Fixings in Concrete and/or to EN 12845,which is an identical standard to CEA 4001.
APPLICATION DATA
Concrete Aircrete Trapezoidal ceiling Steel construction
Building material
and anchor base
FBS EA II FAZ II FH II-I FZA FPX-I TZH TZ TZA TKL TKLS
Anchor or
hanger
3 plus
threaded stud
58
Sprinkler systems
SPECIFICATIONS
Item Type Art.-no. [Zoll] / [mm] Item Type Art.-no. [Zoll] / [mm]
FRSL 34 513302 1“ G8 079740 1000
FRSL 43 513303 1 1/4“ G 10 079744 1000
FRSL 49 513304 1 1/2“ G 12 020957 1000
FRSL 60 513307 2“ G 16 020958 1000
FRSL 76 513308 2 1/2“ G 8/2 079741 2000
FRSL 90 513309 3“ G 10/2 079745 2000
FRSL 115 513310 4“ G 12/2 579746 2000
FRSL 140 513311 5“ G 10/3 557092 3000
FRSL 170 513312 6“ G 12/3 064056 3000
FRSP 1/2'' 524035 1/2“ GS 8/25 079750 25
FRSP 3/4'' 524036 3/4“ GS 8/40 079751 40
FRSP 1" 524037 1“ GS 8/50 079752 50
FRSP 1 1/4'' 524038 1 1/4“ GS 8/60 079753 60
FRSP 1 1/2'' 524039 1 1/2“ GS 8/70 079754 70
FRSP 2'' 524040 2“ GS 8/80 079755 80
FRSP 2 1/2'' 524041 2 1/2“ GS 8/90 079756 90
FRSP 3'' 524042 3“ GS 8/100 079757 100
FRSP 4'' 524043 4“ GS 8/150 079758 150
FRSP 5'' 524044 5“ GS 8/200 079759 200
FRSP 6'' 524045 6“ GS 10/25 079765 25
FRSP 8'' 524046 8“ GS 10/40 079766 40
ETR 8 - 13 024415 M6 GS 10/60 079767 60
ETR 12 - 17 024416 M6 GS 10/80 079768 80
ETR 15 - 21 024417 M6 GS 10/100 079769 100
ETR 20 - 27 024418 M8 GS 10/120 079770 120
ETR 26 - 34 024419 M8 GS 10/150 079771 150
ETR 33 - 42 024420 M8 GS 10/200 079772 200
ETR 40 - 49 024421 M8 TKL L M 8 064055 M8
ETR 50 - 60 024422 M8 TKL M 8 079687 M8
ETR 60 - 70 024423 M 10 TKL L Ø 9 077605 Ø9
ETR 66 - 76 024424 M 10 TKL M 10 079688 M 10
Sprinkler systems
ETR 70 - 82 024425 M 10 TKL Ø 11 079689 Ø 11
ETR 80 - 90 024426 M 10 TKL M 12 020949 M 12
ETR 90 - 102 024427 M 12 TKL Ø 13 043275 Ø 13
ETR 100 - 108 024428 M 12 SS-TKL M10/M12 048154 M10/M12
ETR 102 - 114 024429 M 12 TKLS Ø 9 531134 Ø9
ETR 121 - 127 024430 M 12 TKLS Ø 11 531136 Ø 11
ETR 126 - 133 024431 M 12 TKLS Ø 13 531137 Ø 13
ETR 131 - 140 024432 M 14 TKLS Ø 17 531138 Ø 17
1) This article is delivery on ETR 143 - 153 0244331) M 14 TZ M 8 064094 M8
request only.
ETR 150 - 159 024434 M 14 TZ M 10 064095 M 10
ETR 168 024435 M 14 TZH M 8 079825 M8
ETR 193.7 024436 M 14 TZH M 10 079826 M 10
ETR 219 024437 M 14 TZA M 10 524047 M 10
Please refer to our comprehensive main catalogue or our online web catalogue updated daily at www.fischer.de for information on further additions to our product and entire range.
59
Fireproof mounting
FUNCTIONING
Fire protection in buildings covers the safety of occupants, fire fighters and contents, and is regulated by the local building codes
or standards. This is particularly evident in the installation of fire protection systems such as a detection or suppression, as
approved or recognized components must be used. The key message is to ensure the safety of the escape route by ensuring the
Fireproof mounting
functioning of the supports and sub frames will remain integral for a set period of time.
The necessity for these considerations arises from the properties of the steel, which is subjected to a loss of yield when it reaches
a temperature of > 600 °C and therefore components can undergo a series of resistence testing. The same information is docu-
mented in the inspection reports for a fire resistance with ratings of R30, R90 and R120, based on the standard pipe systems
directive of 2005 (MLAR 2005) and according to EN-1363-1 and DIN4102-2
SPECIFICATION
60
Fireproof mounting
Fireproof mounting
The following figures are valid for FUS channels and FCA cantilever arms, galvanized, hdg and stainless steel.
1) Valid for a suspension height ha ≤ 500 mm
2) Based on suspension height ha = 250mm, Expansion length of threaded rods in case of fire ~ 10mm/m
3) Given load values apply for multiple loads as summated point loads symmetrical allocated.
4) This values are valid for FCA 62/2,5 with additional support by threaded rod.
APPLICATION POSSIBILITIES
Point load = Multiple load = Uniformly distributed load =
Spot load, e.g. a pipe More than one load Uniform distribution of load on the
clamp on the rail. point on the rail, e.g. rails, e.g. bend-proof ventilation duct.
several pipe clamps.
F=qxl F=qxl
Strichstärke 1
F=qxl F=qxl
Strichstärke 1,25
61
Fixings guide
The anchors and fasteners have pre defined load applied and are exposed to flames
without insulation or protective measures. The fire resistance is indicated by the time the
anchor or fastener resist without failure.
TECHNICAL DATA
Material Permissible tensile load in case of a fire [kN] Test report Approval Certificate Application
no.
FZA M16 ■ 13.5 6.5 4.0 3.0 (of 28.02.2013) ■ ■ Cracked and non-
FZA M6 A4/C ■ ■ 2.1 1.2 0.85 0.7 Text: 3091/2013 cracked concrete
FZA M8 A4/C ■ ■ 10.0 4.0 1.8 1.0 ■
TECHNICAL DATA
3
Material Permissible tensile load in case of a fire [kN] Test report Approval Certificate Application
no.
62
Fixings guide
TECHNICAL DATA
Material Permissible tensile load in case of a fire [kN] Test report Approval Certificate Application
no.
FAZ II M10/A4/C ■ ■ ■ 2,8 2,3 1,9 1,6 ETA-05/0069 ■ ■ Cracked and non-
FAZ II M12/A4/C ■ ■ ■ 5,0 4,1 3,2 2,8 ■ ■ cracked concrete
FAZ II M16/A4/C ■ ■ ■ 7,1 7,1 6,0 5,2 ■ ■
TECHNICAL DATA
Material Permissible tensile load in case of a fire [kN] Test report Approval Certificate Application
no.
Fixings guide
FH II 12 B/S/H/SK ■ 2.0 1.3 0.6 0.2 ■
ETA-07/0025 Cracked and non-
FH II 15 B/S/H/SK ■ 3.2 2.3 1.4 1.0 ■
cracked concrete
FH II 18 B/S/H ■ 4.8 3.9 3.0 2.6 ■
63
Fixings guide
TECHNICAL DATA
Material Permissible tensile load in case of a fire [kN] Test report Approval Certificate Application
no.
TECHNICAL DATA
Material Permissible tensile load in case of a fire [kN] Test report Approval Certificate Application
no.
64
Fixings guide
TECHNICAL DATA
Material Permissible tensile load in case of a fire [kN] Test report Approval Certificate Application
no.
TECHNICAL DATA
Material Permissible tensile load in case of a fire [kN] Test report Approval Certificate Application
no.
Fixings guide
65
Fixings guide
TECHNICAL DATA
Material Permissible tensile load in case of a fire [kN] Test report Approval Certificate Application
no.
TECHNICAL DATA
Material Permissible tensile load in case of a fire [kN] Test report Approval Certificate Application
no.
Fixings guide
66
Fixings guide
TECHNICAL DATA
Insulation support metal DHM, Insulation retaining metal washer DTM 80,
washer-ø 35 mm washer-ø 80 mm, inside-ø 11 mm
Art.No. Drill-Ø Min. drill-hole depth Effect. anchorage Anchor length Max. usable length Qty. per box pcs.
depth
d0 td hef I tfix
Fixings guide
67
Fixings guide
TECHNICAL DATA
Art.No. Drill-Ø Min. drill-hole depth Effect. anchorage Anchor length Max. usable length Qty. per box pcs.
depth
d0 td hef I tfix
TECHNICAL DATA
Art.No. Anchor length Min. thickness to first supporting layers Max. usable length Screw Qty. per box pcs.
I tfix ds Xls
68
Fixings guide
TECHNICAL DATA
Quick-fix strap
TECHNICAL DATA
Fixings guide
TECHNICAL DATA
69
Calculation of consumption guide
Area of pipe f = π x (c ÷ 2) mm
2 2 Mastic volume = ((e-f) x b) ÷ 1000 ml
Mastic volume = g = ((e-f) x b) ÷ 1,000 ml Mastic volume = g = ((e-f) x b) ÷ 1,000 ml =g
Example for mastic/sealant:
Example: Example: w = 20 mm
a = 90 mm l = 90 mm l = 30m = 30,000 mm b = 10 mm
b = 40 mm w = 100 mm h = 310 ml
c = 50 mm b = 40 mm
h = 310 ml c = 50 ml
e = 20 x 30,000 = 60,000 mm2
n = 20 h = 310 ml
g = (60,000 x 10) ÷ 1,000 = 6,000 ml
n = 20
No. of cartridges = ( 6,000 )
310
e = 90 x 100 = 9,000 mm2 = 19.4 cartridges
e = 3.14 x 452 = 6,361.73 mm2 Example of joint Spray:
f = 3.14 x 252 = 1,963.50 mm2
f = 3.14 x 252 = 1,963.50 mm2 w = 100 mm, w1 = 125 mm (with overspray)
g = ((9,000 - 1,963.50) x 40) ÷ 1,000
g = ((6,361.73 - 1,963.50) x 40) ÷ 1,000 = l = 300 m = 300,000 mm
= 281.46 ml
175.92 ml b = 1.5 mm
h = 19 litres = 19,000 ml
No. of cartridges = 20 x ( 281.46 ) = 18.1 e = 125 x 300,000 = 37,500,000 mm2
310
No. of cartridges = 20 x ( 175.92
310 ) cartridges g = (37,500,000 x 1.5) ÷ 1,000 = 56,250 ml
= 11.35 cartridges No. of buckets = ( 56,250 ) = 2.96 buckets
19,000
Length [mm]
Size Large Medium Large Medium Large Medium Large Medium Large Medium Large Medium
Width [mm]
Seal type 100 300 500 700 900 1,000
Wall 3 5 7 13 12 22 17 31 21 39 24 47
200
Floor 2 3 4 7 6 12 9 17 11 22 12 27
Wall 5 9 14 26 24 44 33 61 42 78 47 95
400
Floor 3 5 7 15 12 24 17 34 22 43 24 52
Wall 7 13 21 39 35 65 49 91 63 117 70 143
600
Floor 4 7 11 22 18 36 25 51 33 65 36 79
Wall 9 18 28 52 47 87 66 122 84 157 94 192
800
Floor 5 10 15 29 24 48 34 67 33 87 48 107
Wall 10 22 35 65 59 109 82 152 105 196 117 217
1,000
Floor 6 12 18 36 30 60 42 84 54 108 60 120
Seal
surface
Volume @
200 mm depth
Cartridge
Volume @
100 mm depth
Cartridge
Core
boring
Volume @
200 mm depth
Cartridge
Volume @
200 mm depth
Cartridge 3
m2 [m3] 180 g [m3] 180 g [mm] [m3] 180 g [m3] 180 g
0.005 0.001 0.92 0.0005 0.48 50 0.0004 0.36 0.0002 0.18
0.01 0.002 1.85 0.001 0.98 60 0.0006 0.52 0.0003 0.26
0.02 0.004 3.69 0.002 1.85 70 0.0008 0.71 0.0004 0.36
0.03 0.006 5.54 0.003 2.77 80 0.001 0.93 0.0005 0.47
0.04 0.008 7.38 0.004 3.69 100 0.0016 1.45 0.0008 0.73
0.048 0.0096 8.92 0.0048 4.46 120 0.0023 2.09 0.0011 1.05
0.0625 - 0.0063 5.81 160 0.004 3.71 0.002 1.85
200 0.0062 5.8 0.0031 2.9
* The above calculations do not consider wastage of material. Please consider an appropriate factor.
71
Training certification
fischer Training
Fire protection seminars with certificate for professionals.
72
Engineering judgement request form
Through penetration
Thickness:
Joint
Joint type: Head of wall Bottom of wall Floor to floor Floor to wall
Wall to wall Perimeter joint
Movement required:
73
74
The information in this catalogue is non-binding. Our technical service
department can provide you with additional information and advice.
However you will need to provide an accurate description of your particular
application.
All information in this catalogue must be adjusted to local conditions and
materials used. If individual items and types are not listed with detailed
performance specifications, please contact your local fischer representative
for further consultation.
Subject to errors, technical and product line changes, liability for printing
errors and omissions is excluded.
Product details are correct at time sent to print.