Coldroom: Cold Room Type

The document provides specifications for an industrial cold room used to store beef at -1°C. It details the dimensions and insulation of the cold room, the type and quantity of product stored, ventilation and defrost settings. Based on the specifications, the cooling needs were calculated over a 24 hour period to be approximately 2.5 million kJ. The necessary cooling capacity for preserving the goods is 11206W, with a total cooling capacity needed of 38514W.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
64 views2 pages

Coldroom: Cold Room Type

The document provides specifications for an industrial cold room used to store beef at -1°C. It details the dimensions and insulation of the cold room, the type and quantity of product stored, ventilation and defrost settings. Based on the specifications, the cooling needs were calculated over a 24 hour period to be approximately 2.5 million kJ. The necessary cooling capacity for preserving the goods is 11206W, with a total cooling capacity needed of 38514W.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

11/24/21, 9:11 AM Cooling calculator

Coldroom

Cold room type

industrial room
Insulation thickness: 100 mm
Floor insulation: yes
Length (inner): 10.00 m
Width (inner): 11.00 m
Height (inner): 5.00 m
Inner volume: 550.00 m³

Application
Room temperature: 10.0 ºC
pre-cold room

Product type
Storage temperature: -1.0 ºC
beef on rails
Storage humidity: 90 % Freezing point: -2.0 ºC
Water content: 69 % Specific heat capacity: 3.2 kJ/kg·K
Respiration heat: 0.0 kJ/kg Specific heat below freezing point: 1.7 kJ/kg·K

Product loading
Load rate: 250 kg/m³ Total load: 137500 kg
Daily turnover rate: 12 %/24h Daily turnover: 16000 kg/24h
Inlet temperature: 35.0 ºC

Product cooling
Product shape: Weight per piece: 200.00 kg
cylinder
Product length: 100 mm Product thickness: 10 mm
Mass density: 876 kg/m³ Thermal conductivity: 0.4 W/m·K
Air speed: 1.0 m/s Final inner temperature: 0.0 ºC
Cooling time: 0.25 h Air temperature: -6.3 ºC

Location
Altitude: 9m
within a building
Ambient temperature: 34.0 ºC Ambient relative humidity: 50 %

Thermal insulation
Walls: area: 216.2 m² thickness: 100 mm
Injected polyurethane
Roof: Injected polyurethane area: 112.1 m² thickness: 100 mm
Floor: Injected polyurethane area: 112.1 m² thickness: 100 mm

Door: Injected polyurethane area: 8.0 m² thickness: 75 mm

Ventilation through
Door openings per day: 8.5 /24h Air volume renewal rate: 8.5 /24h
doors

Defrost
Defrost type:
electrical

Fans
Airflow rate: 11000 m³/h Input power: 1.330 kW

https://intarcon.calcooling.com/#coldroom 1/2
11/24/21, 9:11 AM Cooling calculator

Cooling needs
Calculation time period: 24.0 h
Products
Refrigeration of goods: 1769600 kJ
H. Transfer
Heat transfer: 206049 kJ
Air renewal
Air renewal: 287014 kJ
Loads
Thermal loads: 233077 kJ
TOTAL: 2495740 kJ
Working hours: 18.0 h

Necessary cooling
Necessary capacity for 11206 W Total cooling capacity: 38514 W
capacity preservation of goods:

https://intarcon.calcooling.com/#coldroom 2/2