Buckling Behavior of Split Mullion
Buckling Behavior of Split Mullion
c The Author(s)
This work is covered by copyright. Unless the document is being made available under a
Creative Commons Licence, you must assume that re-use is limited to personal use and
that permission from the copyright owner must be obtained for all other uses. If the docu-
ment is available under a Creative Commons License (or other specified license) then refer
to the Licence for details of permitted re-use. It is a condition of access that users recog-
nise and abide by the legal requirements associated with these rights. If you believe that
this work infringes copyright please provide details by email to [email protected]
Notice: Please note that this document may not be the Version of Record
(i.e. published version) of the work. Author manuscript versions (as Sub-
mitted for peer review or as Accepted for publication after peer review) can
be identified by an absence of publisher branding and/or typeset appear-
ance. If there is any doubt, please refer to the published source.
https://doi.org/10.1177/1369433218795118
Buckling Behaviour and Design of Complex-shaped Aluminium
Mullion Sections
1
Abstract: Thin-walled aluminium mullions are the vertical framing members of the façade
systems used in buildings. This paper investigates the buckling behaviour of these complex-
shaped aluminium mullions. For this purpose, the aluminium mullion sections were
simplified into elements of varying thickness, and modelled using CUFSM finite strip
analysis program. Elastic buckling analyses were performed with and without considering the
availability of glass panel restraints for both negative and positive wind actions, and the
results are presented in this paper. The effect of providing return flanges to enable a good
connectivity between the male and female mullions was also evaluated. The lateral restraints
provided by glass panels were simulated using the spring stiffness option available in
CUFSM, and the analyses were performed for spring stiffness values in the range of 0-1
N/mm/mm. The applicability of the buckling analysis results to the design of aluminium
mullions was then evaluated using the Direct Strength Method (DSM). For this purpose the
section moment capacities of mullions were determined from finite element analyses and
compared with the DSM predictions using the CUFSM buckling analysis results. This
comparison showed that DSM based design can be adopted for the complex-shaped
aluminium mullions provided their elastic buckling capacities are available. Overall, this
study has provided good understanding of the buckling behaviour of mullion sections under
both positive and negative wind actions and has proposed the use of DSM for the design of
Keywords: Aluminium mullions; Façade systems; Buckling; Finite strip analysis; Direct
Strength Method
2
Corresponding author’s email address: [email protected], Phone number: 61 73138 2543,
Fax: 61 73138 1170
2
3
1. Introduction
Façade systems are important components of both low- and high-rise buildings as they form
the building envelope that protects the buildings against the environmental hazards while
providing an aesthetic appearance to buildings (Fig. 1). Present-day façade systems are
framing is used in these façade systems due to the capability of aluminium being extruded
into complex shapes, which provide the versatility required to build elegant and complex
building enclosures. Aluminium also has higher strength to weight ratio than steel, and is
about 65% lighter than steel. Generally, aluminium alloy 6063-T6 is used to fabricate these
extruded aluminium framing members. The mullions are the vertical structural members of
aluminium framing, which resists the wind forces acting on the building envelope through
bending actions.
Curtain wall system is one kind of façade system, popularly used in high rise buildings. There
are mainly two types of curtain wall installations, which are stick and unitised panel wall
systems. In the stick wall system (the first generation curtain walls), the vertical aluminium
framing is installed first, which is followed by the installation of horizontal members and
then the glass panels. This system allows for greater flexibility during construction, where
site modification is possible, and it is also economical if correctly designed and installed. But
this takes excessive time to assemble on site, and could be a barrier in present day fast track
projects. The unitised wall system (the second generation curtain walls) is assembled in
factories as a series of panels (Fig. 1), and are then brought to site and assembled through
interlocking mullions and transoms. The unitised panels allow the benefits of factory
modern high rise buildings (Russell, 2006 and Allana and Carter, 2012). To allow for easier
4
assembly, a pair of extrusion mullion sections is used. These mullions are a pair (male and
female) of aluminium extrusions, which fit together as shown in Fig. 2. The connectivity
between these pairs must allow for expansion and shortening of the panel caused by
temperature variations and wind actions. Therefore male and female mullions are not clipped
or screwed together in most cases. This current practice of Australian façade industry allows
the movement of panels during temperature variation and building deflections. It also allows
easier alteration during fabrication if any problems are found in the constructed façade
assembly as panels can be easily isolated or removed from the curtain wall. Provision of
interlocking clips would make the removal of panels from the constructed façade assembly
difficult. Therefore until there is a need to provide clips or screw connections, the male and
female mullions are not connected by any external mechanisms. The mullions are also
These individual aluminum mullions are thin-walled members with complex cross-sections.
The complex cross-sections are based on industry driven studies to allow adequate thermal
movements and to have easier connectivity between the vertical (mullions) and horizontal
(transoms) members. Fig. 3 shows the panel system of mullion sections and glass as used in
the Australian curtain walls subject to positive (pressure) and negative (suction) wind actions.
Importantly, they are asymmetric sections. The vertical mullion sections are subject to
bending stresses when resisting the wind forces applied to the building envelope, and no
other forces are carried by these mullions. In Australia, these mullions are designed based on
the design rules given in AS/NZS 1664.1 (1997) and AS/NZS 1664.2 (1997), which is similar
to the Aluminium Association Design Manual (ADM, 2010). These standards and manuals
do not cover the complete design of these complex aluminium cross-sections, thus design
5
The current method adapted in designing the aluminium mullion sections is based on the
allowable stress method given in the ADM (2010) or AS/NZS 1664.1 (1997). To determine
the bending capacity, it is checked first to determine whether any individual element buckles
and if it does, the critical stress is determined and then the section moment and flexural
torsional buckling capacity are found by using complex formulae (ADM, 2010). Currently
the popular trend to design these thin-walled members of complex cross-sections is based on
the Direct Strength Method (DSM) proposed by Schafer (2008). Zhu and Young (2009)
investigated the applicability of DSM to design the tubular aluminium members under
bending and compression actions. This method relates the elastic buckling capacity to the
section and member capacities. Therefore as the first step in this design method, it is
in Fig. 2.
It is a cumbersome task to find the buckling loads of these complex cross-sections using hand
solutions, and adapting a finite element approach would also be time consuming. Finite strip
analysis is the most suitable approach to examine the instability/buckling behaviour of these
complex aluminium members subject to longitudinal stresses (bending and axial). Li and
Schafer (2010) developed an open source programme, CUFSM, based on finite strip analysis
method, and this application facilitates easy determination of the various buckling loads and
modes of thin-walled members of different lengths and sizes (Schafer and Adany, 2006).
Previously Wang (2006) has used the CUFSM software to determine the buckling load of E-
type mullion section. The mullion sections subject to bending action could undergo three
types of instabilities; local, distortional and flexural torsional buckling. The buckling modes
and load factor versus half wave length plots could be different for aluminium extrusion
6
sections compared to steel sections. Furthermore, due to the asymmetric nature of these
mullions, and the lower elastic modulus of aluminium, buckling could occur at lower stress
levels. This study uses CUFSM software to analyze the various buckling modes of complex-
shaped male and female mullion sections restrained by glass as used in curtain walls, and
then investigates the applicability of DSM based design approach for them.
The 650 series - 027 section (650-027 in Fig. 2), which is commonly used among leading
glass suppliers in Australia, was considered. It does not have a uniform thickness. In the
CUFSM software, the thickness of a particular element cannot be varied. Hence the male
mullion section shown in Fig. 2 was idealized into sections of different elements as shown in
Fig. 4(a). The AutoCAD drawing has more than 30 co-ordinates, and no facility is available
in CUFSM to directly import the AutoCAD drawings or the co-ordinates of those drawings.
Manually entering each of the node and element number in CUFSM for a particular mullion
section is a cumbersome task since there are about 40 different nodes and elements in each
mullion section. To facilitate this, a small AutoCAD application (PLIST) was loaded in
AutoCAD, which enabled the transfer of nodal co-ordinates of the drawn polyline to an excel
file. An excel spreadsheet was developed, which lists the node and element numbers based on
the imported AutoCAD co-ordinates. The list could be copied and pasted to the cells of
CUFSM. Supplementary data is provided with this paper for the idealized 650-027 mullion
section.
The section properties of the male mullion were determined from the software ShapeDesigner
(refer Supplementary Data). Similarly the section properties of the idealized section were
7
found from the CUFSM software and are given in Fig. 4(b). There are some differences,
especially in the torsional constant values, but they are small, and the area and the second
moment of areas about the X and Z axes are about the same.
The mechanical properties of aluminium sections (6063-T6 alloy) used in the modelling are
summarized as follows (AS/NZS 1664.1, 1997): Yield strength – 172 MPa, Elastic modulus
– 70000 MPa, Poisson’s ratio – 0.32 and Shear modulus – 26515 MPa. These are the
As seen in Fig. 3, the glass is connected to one side of the mullion along its length. It is
assumed that the glass provides a continuous lateral restraint along the section length when
designing the mullion sections. In this study, analyses of the mullion sections were performed
with and without glass restraints, and then also with varying spring stiffness. In asymmetric
sections, the principal axes are different to those axes where the forces are applied. However,
if the sections are restrained against movement in one direction (X-X axis), the bending
stresses (f) about that axis can be found from the basic equation (Eq. 1) without finding the
stress components in the principal axis. More details can be found in Ing and Trahair (1984).
The restrained bending option available in the CUFSM was used for these mullion sections.
𝑀𝑦
𝑓= ………………………………………………………………………………………(1)
𝐼𝑥
where,
f is the bending stress, M is the bending moment about the x axis, Ix is the second moment of
area about the x axis, and y is the perpendicular distance from the centroidal x axis to the
point considered.
8
2.2. Buckling behaviour of unrestrained male mullion sections
The first series of analyses was performed for 650–027 male mullion sections subject to
positive action. In the first set, lateral restraint provided by the glass was omitted in the
analyses. In CUFSM analyses, a uniform moment can be applied. However, a member with
different moment distributions other than uniform moment cannot be modelled. The stress
distribution and the tension/compression sides are shown in Fig. 5(a) for positive wind action.
The yield moment about the X-X axis is 3.95 kNm. Beam lengths of 1 to 4000 mm were
considered in the analyses. The buckling analysis results for the positive wind action (Fig.
3(a)) are given in Figs. 6(a) and (b). Fig. 6(a) presents the load factor versus half wave
buckling length plot to show the variation of load ratio with increasing member length. Here,
load factor is the ratio of the buckling and yield moments. The minima buckling occurs at a
half wave length of 90 mm, where the load factor is 3.51 (buckling stress of 603.7 MPa in Fig.
6(b) and Table 1). Fig. 6(b) also shows that the buckling mode at this length is local. At a
length of 300 mm also, local buckling is the critical mode, and the corresponding load factor
is 5.0989. The buckling load factor is high, and hence most likely this member might not
undergo any component buckling before yielding failure. At a length of 900 mm, the
buckling mode is flexural torsional buckling, and the corresponding load factor is 0.989
(buckling stress of 170.1 MPa), and this shows that these sections can undergo flexural
torsional buckling at very low stress levels. For 3000 and 3600 mm lengths, global buckling –
flexural torsional buckling is the critical buckling mode, where the load factors are 0.125 and
0.0967, respectively.
9
The second series of analyses was performed for 650-027 male mullion section subject to
negative wind action (Fig. 3(b)), and the lateral restraints were omitted. Fig. 5(b) shows the
stress distribution across the cross-section and the tension/compression sides, and the yield
moment is 3.95 kNm. The load factor versus half wave buckling length plot obtained from
The minimum local buckling stress occurs at a half wave length of 150 mm, where the load
factor is 1.25 (buckling stress of 216 MPa) – Table 1 and Fig. 7(b). But a closer look at Fig.
7(b) shows minor distortion of the flange element also, which is not common in thin-walled
members. Importantly the flange elements (Elements 1 and 2) buckle together rather than
buckling as two individual elements. At a half wave length of 450 mm, it is subjected to local
and distortional buckling as evident from Fig. 7(b). At a length of 950 mm, the buckling
mode is flexural torsional buckling, and the load factor is 0.991 (buckling stress of 170 MPa).
For 3000 and 3600 mm lengths, flexural torsional buckling is the critical mode, where the
Overall, buckling analyses of unrestrained mullions show that these sections are more prone
to flexural torsional buckling under both positive and negative wind actions if they are not
restrained. Hence the potential lateral restraints provided by the glass panel should be
In curtain walls as shown in Fig. 3, the glass is connected to the flanges on one side of the
mullions through sealant or gasket connection. The glass will restrain the lateral movement of
these flanges during wind action. During positive wind action, the load will be applied or
10
concentrated on the inner flange (Fig. 3(a)), and thus the lateral restraint is expected to be
mobilized at the loading point through friction. In this analysis, the lateral restraint was
simulated at Point A as shown in Fig. 8(a). The analysis results are provided in Table 2 and
Figs. 9(a) and 10. The half wave length versus load factor plot of sections without lateral
restraints are also shown in Fig. 9(a). There are significant differences between both plots.
The positive wind action induces compressive stresses on the outer flange, which is restrained
by the glass. Therefore the compression flange is unable to move laterally, thus eliminating
the flexural torsional buckling of mullions. As evident from Fig. 9(a), the buckling plots of
both mullions (laterally restrained and unrestrained) almost coincide up to a length of 350
mm. Thereafter the plot of unrestrained mullion slopes down while that of restrained mullion
goes up due to the elimination of flexural torsional buckling. Buckling modes for varying
lengths are shown in Fig. 10. As evident from Fig. 10, flexural torsional buckling was not
observed in the 3000 and 3600 mm long mullions with lateral restraints, whereas Fig. 6(b)
showed severe flexural torsional buckling in the 3000 and 3600 mm long unrestrained
2.3.2. Influence of lateral restraint location on the buckling behaviour of male mullion
Buckling analyses were conducted to determine whether the location of the lateral restraint
along the flange width has any influence on the load factor versus half wave length plot. For
this purpose lateral restraint was applied at two different locations as shown in Fig. 8 (Points
A and B). The analyses were performed, and the results are plotted in Fig. 9(b). This figure
demonstrates that the lateral restraint location along the flange width did not affect the
11
2.3.3. Restrained male mullions subject to negative wind action
During the negative wind action, the load is mainly transferred to the outer flange (Fig. 3(b))
through the glass panels, and the lateral restraint is expected to be acting on that flange.
Therefore for the negative wind action the restraint was defined in CUFSM at the outer
flange of the mullion as shown in Fig. 11(a). Fig. 11(b) compares the buckling plots of
mullions with and without lateral restraints. It depicts that there are no significant differences
in the plots since the compressive stresses occur at the inner flange, which is unrestrained.
Buckling modes for varying lengths are shown in Fig. 12, and at 3000 and 3600 mm lengths,
flexural torsional buckling modes are observed. They are the same as shown in Fig. 7(b) for
2.4. Comparison of the buckling behaviour of mullions with and without return lips
This analysis compares the buckling behavior of the aluminium mullion Sections 1 and 2
(Figs. 13(a) and (b)). The difference between these sections is that Section 2 has a straight
flange which is similar to the flange of a channel section. This will depict the benefit of the
return lip of Section 1 (Fig. 13(a)). Analyses were conducted and the load factor versus
buckling half wave length plots of Sections 1 and 2 are shown in Fig. 13(c). Both plots
coincide after a length of 450 mm. After this length the flexural torsional buckling becomes
the dominant buckling mode, and the results show that return lip does not provide any
benefits for flexural torsional buckling as this is apparent since this return lip will not
significantly alter the second moment of area, torsion constant and warping constant.
However, for lengths less than 450 mm, the return lip provides significant benefit as evident
from Fig. 13(c). The critical load factor for Section 2 is 1.02, and hence the critical buckling
stress is 175.4 MPa, while that of Section 1 is about 23% higher (215 MPa) than Section 1.
This shows the benefit of the increased local buckling capacity due to the provision of the
12
return lip. Fig. 13(d) shows the local buckling mode of Section 2. In conclusion, although this
return lip is provided to increase the connectivity between the couple mullions, it also
2.5. Buckling behaviour of mullions with lateral restraints provided via spring elements
Although façade engineers assume that full lateral restraints are provided by the glass to the
1N/mm/mm is assumed to simulate the lateral restraints provided by the glass. Glass restraint
is continuous along the mullion length, and continuous spring constraints can also be
simulated in CUFSM where a spring can be attached to any node (Fig. 14(a)). The spring
constant can be applied as a constant value or as varying with member length. In this study
different spring stiffness values (1, 0.1 and 0.01 N/mm/mm) were used in CUFSM, and the
analyses were performed. Negative wind action was not considered as it was shown in
Section 2.3.3 that even assuming full lateral restraint did not affect the buckling
behavior/plot. For a male mullion section subject to positive wind action with spring stiffness
(1N/mm/mm), the minimum load factor for flexural torsional buckling is about 2.67. Hence
most likely this mode of buckling cannot be expected in this 650-027 mullion section. The
half wave length versus load factor plots of unrestrained mullion section, and mullion section
with spring lateral restraint – 0.01 N/mm/mm are almost the same. Figure 14(b) provides a
good understanding of the buckling behaviour of mullion sections with lateral restraints
spring stiffness in the range of 0.1 to 1.0 is most suitable to simulate glass panel restraints. As
a conservative approach, 0.1 N/mm/mm can be used. Full scale façade test results are needed
to confirm this.
13
3. Modelling and analyses of 650 series sections - Female mullions
In the unitised panel system, male and female mullions are locked together to form the
building envelope. The female mullion section (650-028) commonly used is shown in Fig. 2.
Buckling analyses were performed with and without considering the lateral restraints from
the glass. The methodology used was identical to that described for male mullions in Section
2. The buckling analysis results showed that the behavior of female mullions is similar to that
described for male mullions. Hence only the selected results of load factor versus the half
wave buckling length plots and buckling modes are presented without detailed explanations
(Figs. 15-17).
This section investigates the applicability of CUFSM buckling analysis results to determine
the structural capacity of mullions. To consider a larger range of section slenderness, a simple
mullion with geometry similar to 650-027 mullion, but with uniform thickness, was
considered (Fig. 18(a)). The thickness of this mullion was changed from 0.8 to 8 mm, which
Therefore, the investigated-mullion sections included compact sections, and sections subject
to elastic and inelastic local buckling. The CUFSM buckling analyses were performed and
the obtained critical local buckling stresses are summarized in Table 3. The load factor versus
The use of these critical local buckling stress values in determining the ultimate section
moment capacity of mullions is evaluated in this study. These critical buckling stresses were
used in the direct strength method given in ADM (2015). The mullion section moment
capacities were determined from finite element analyses (FEA) using ABAQUS under
14
negative wind action. Details of the finite element modelling procedure are given next,
The finite element models developed were similar to the ones developed to determine the
section moment capacity of cold-formed steel beams in Anapayan et al. (2011) and Siahaan
et al. (2016). The developed models represented a four point bending setup. The aluminium
mullions were modelled using S4R shell elements with 4 mm x 4 mm mesh. Figure 19
presents the finite element models including the support and symmetric boundary conditions
and the loading points. Furthermore, in order to prevent any X-axis displacement, a
continuous lateral restraint was defined at the outer flange along the mullion length to
simulate the restraint provided by the glass panels. The geometric imperfection was applied
in the shape of the critical local buckling mode according to Schafer and Pekoz (1998). A
local geometric imperfection value of 0.004b was used, based on the allowable tolerance
given in Aluminium standards and data metric SI (2013). The limitation of the developed
The yield strength, ultimate strength and elastic modulus of mullion were taken as 172, 207
and 70000 MPa, respectively from AS/NZS 1664.1 (1997). Eurocode stress-strain model
(Eurocode 9 Part 1.1, 2007) was used to determine the engineering stress-strain model (Eqs. 2
and 3). The corresponding true stress and logarithmic plastic strain data were used as input in
ABAQUS.
𝜎 𝜎 𝑛
𝜀= + 0.002 ( ) …………………………………………………………………(2)
𝐸 𝑓0.2
𝜀𝑜,𝑥 𝑓𝑥
𝑛 = log ( ) / log ( ) ………………………………………………………………... (3)
𝜀𝑜,𝑒 𝑓𝑒
where: n is the strain hardening exponent, fx is the reference stress, fe is the conventional limit
of elasticity, ɛo,x is the reference strain and ɛo,e is the strain corresponding to the stress fe
15
Finite element analyses were performed under negative wind action using Modified Riks
analysis method, and the results are summarized in Table 3. The mullions failed by section
yielding where local buckling was observed in slender sections or in sections subjected to
inelastic buckling. The section moment capacities of mullions were predicted using the direct
strength method (DSM) given in ADM (2015), where the buckling stresses obtained from
CUFSM analyses were used to determine the cross-sectional slenderness of mullions. The
DSM equations (ADM, 2015) to calculate the section moment capacity (Mnl) are given next.
The allowable stress (Fb) is found using the following equations and limits:
For 𝜆𝑒𝑞 ≤ 𝜆1
𝐹𝑏 =
𝑀𝑛𝑝
……………………………………………………………………………………...(5)
𝑆𝑥𝑐
𝜆𝑒𝑞 =
𝐸
𝜋√𝐹 …………………...………………..…………………………………………….(6)
𝑐𝑟
For 𝜆𝑒𝑞 ≥ 𝜆2
𝑘2 √𝐵𝑝 𝐸
𝐹𝑏 = ………………………………………………………………………………….(8)
𝜆𝑒𝑞
where 𝜆𝑒𝑞 is the equivalent numerical slenderness, 𝐹𝑐𝑟 is the critical buckling stress, 𝐸 is the
𝐵𝑝 − 𝐹𝑐𝑦
𝜆1 = , 𝜆2 = 𝐶𝑝
𝐷𝑝
16
Cp, Bp, and Dp are buckling coefficients which are given in Table B.4.2 of the ADM (2015).
Sxc is the section modulus about the compression side of the X-axis.
The ratios between the section moment capacities obtained from FEA and DSM design rules
are also given in Table 3 and Fig. 20. The DSM (ADM, 2015) predictions agree well with the
FEA results of compact mullion sections, and those subject to inelastic buckling, as reflected
by the mean FEA to design rule prediction ratios of 1.08 and 1.04, respectively. However, the
predictions were conservative for slender mullion sections with a mean FEA to DSM
prediction ratio of 1.40. The mean and COV for the FEA to design rule prediction ratios
considering all the mullion sections are 1.17, and 0.16, respectively. This shows that the
DSM in ADM (DSM, 2015) can be conservatively used to predict the section moment
This section has demonstrated the direct applicability of buckling analysis results from
CUFSM to determine the section moment capacity of aluminium mullion sections. Similarly,
the member moment capacity can also be determined using the same approach. The use of
sections, compared to the other approaches such as the limiting stress method and the total
moment capacity approach (ADM, 2015 and Kim and Pekoz, 2003). The CUFSM buckling
analysis software can be easily used to find the buckling stresses of complex-shaped mullion
5. Conclusion
17
This paper has presented an investigation into the buckling behaviour of complex-shaped
aluminium mullion sections, where the finite strip analysis software “CUFSM” was used. The
aluminium mullion sections were simplified into elements of different thicknesses, and were
modelled using CUFSM. Two commonly used sections, 650-027 male and 650-028 female
mullions, were considered. Analyses were performed with and without considering the
availability of glass panel restraints for both negative and positive wind actions. The results
showed that the potential lateral restraints provided by the glass panels can significantly
improve the flexural buckling behaviour of mullion sections subject to positive wind action
as compression flanges are restrained. The mullions with a spring constant of 1 N/mm/mm
appeared to simulate fully restrained conditions. An appropriate spring stiffness in the range
of 0.1 to 1 N/mm/mm can be used in CUFSM to simulate the glass panel restraint to mullions.
Furthermore, it was found that the provision of return flanges to enable a good connectivity
between the male and female mullions contributed to the increase in local buckling capacity
of mullion sections.
Due to the increasing usage of complex-shaped thin-walled steel and aluminium members,
the use of direct strength method is becoming popular, which requires a good understanding
of the buckling behaviour of mullion sections. This study has provided good understanding of
the buckling behaviour of male and female mullion sections under both positive and negative
wind actions including buckling plots and modes. Importantly, it has demonstrated the direct
applicability of buckling analysis results from CUFSM to determine the moment capacities of
Acknowledgements
The authors would like to thank QUT for providing all the necessary support with the
computing facilities.
18
References
1. ADM (2010), Aluminium Design Manual, Specification for Aluminium Structures, The
2. ADM (2015), Aluminium Design Manual, Specification for Aluminium Structures, The
3. Aluminium Association (2013). Aluminium standards and data Metric SI, The
4. Allana, P. K. and Carter, D. (2012). Curtain Walls Issues, Problems and Solutions, Proc.
Brussels, Belgium.
7. Ings, N.L. and Trahair, N.S. (1984), Lateral buckling of Restrained roof Purlins, Thin-
8. Kim, Y. and Pekoz, T. (2003), Ultimate flexural strength of aluminium sections, Thin-
9. Li, Z. and Schafer, B.W. (2010), Buckling analysis of cold-formed steel members with
general boundary conditions using CUFSM: conventional and constrained finite strip
19
10. Russell, M.S. (2006), Curtain Walls: Not Just another Pretty Façade, Journal of
12. Schafer, B.W. and Adany, S. (2006), Buckling analysis of cold-formed steel members
using CUFSM: conventional and constrained finite strip methods, Proc. of the 18th
USA.
13. Schafer, B.W. (2008), The Direct Strength Method of Cold-formed Steel Member
14. Siahaan, R., Keerthan, P. and Mahendran, M. (2016). Finite element modeling of rivet
fastened rectangular hollow flange channel beams subject to local buckling. Engineering
15. Standards Australia (1997), Aluminium Structures, Part 1: Limit State Design, AS/NZS
16. Standards Australia (1997), Aluminium Structures, Part 2: Allowable Stress Design,
17. Wang, Y. (2006). Structural Behavior and Design of Two Custom Aluminum Extruded
Shapes in Custom Unitized Curtain Wall Systems, MSc thesis, School of Civil
18. Zhu, J. and Young, B. (2009), Design of Aluminium Flexural Members using Direct
Strength Method, Journal of Structural Engineering ASCE, Vol. 135(5), pp. 558-566.
20
Installation
Male Female
mullion mullion
21
Mullion
Restraint to the inner
Z flange during positive wind
action
X
Gasket
Inner flange
Positive wind
Outer flange
22
(a) Idealised model
Note: In this figure, A is the area (mm2), J is the torsion constant (mm4), Xcg and Zcg are the
distances along the X and Z axes to the centroid of the cross-section (mm) from the origin, Ixx
and Izz are the second moments of area about X- and Z- axes (mm4), Ixz is the polar moment
of area (mm4), θ is the angle of the major and minor principal axes from the X and Y-axes, I11
and I22 are the second moments of area about the major and minor principal axes, Xs and Zs
are the distances to the shear centre from the centroid (mm) along the X- and Z-axis
directions, Cw is the warping constant (mm4), and β is the mono-symmetry constant about X-
and Y-axes.
23
Tension side
Compression side
Compression side
Tension side
24
Lo
ad
fac
tor
Figure 6: Buckling analysis results of unrestrained male mullion (650-027) subject to positive
wind action
Note: *LF – Load factor
25
Load factor
Element 1 Element 2
LF – 1.254 at 150 mm
26
Lateral restraint –
Point B
Lateral restraint –
Point A
Figure 8: Lateral restraints provided to the male mullion section during positive wind action
Restrained
mullion
Load factor
Unrestrained
mullion
(a) Mullion with and without lateral restraints during positive wind action
27
Plots of mullions with lateral restraint
at Points A and B coincide
Load factor
(b) Mullion with lateral restraints at different locations during positive wind action
Figure 9: Load factor versus half wave buckling length plot of restrained male mullion (650-
027) subject to positive wind action
Figure 10: Buckling modes of laterally restrained 650-027 male mullion subject to positive
wind action
28
Lateral restraint
29
LF – 1.254 LF – 2.848 LF – 0.143 LF – 0.112
at 150 mm at 450 mm at 3000 mm at 3600 mm
Figure 12: Buckling modes laterally restrained 650-027 male mullion subject to negative
wind action
Return lips
30
Section 2
Load factor
Section 1
(d) Buckling mode of Section 2 at local buckling half wave length of 100 mm
31
1 N/mm/mm
Load factor
0.1 N/mm/mm
0.01 N/mm/mm
No lateral restraint
Half-wave buckling length (mm)
Figure 14: Buckling analysis results of 650-027 mullion under positive wind action, and with
spring restraints
32
Load factor
Figure 15: Buckling analysis results of unrestrained female mullions (650-028) subject to
negative wind action
33
Load factor
Figure 16: Buckling analysis results of unrestrained female mullions (650-028) subject to
positive wind action
34
Laterally restrained
mullion
Load factor
Unrestrained
mullion
35
40 mm
150
mm
17 mm
26 mm 10 mm
23 mm
Note: centre line dimensions are shown
in this figure
(a) Mullion geometry considered in the parametric study
Local
buckling
Load factor
(b) CUFSM Buckling analysis plot and critical buckling mode of 1 mm thick section
Figure 18: CUFSM Buckling analysis plot and critical buckling mode of 1 mm thick section
used in the parametric study
36
Boundary of symmetry at mid-span
150 mm
(U3=UR1=UR2=0)
Inner flange Mullion-S4R
400 mm elements
50 mm
Loading point
(U1=UR3=0)
Stiffeners-
R3D4 elements
Support
(U1=U2=UR3=0)
Outer flange
Slender section
(λ≥73.8)
Full Inelastic
compact (73.8>λ>36.6)
(λ≤36.6)
37
Table 1: CUFSM buckling analysis results for unrestrained male mullions (650-027) subject
to positive and negative wind action
Table 2: CUFSM buckling analysis results for restrained male mullions (650-027) subject to
positive wind action
38
1
Table 3: Comparisons of section moment capacities of mullions from FEA and DSM (ADM, 2015)