NEXGEN 20 Tech Guide ChlorkIng 02.03.2014
NEXGEN 20 Tech Guide ChlorkIng 02.03.2014
NEX-GEN 20
The NEX-GEN system monitors all aspects of its operation and will display information,
events, faults and alarms on an EVENT screen. This allows the operator to determine
system performance, monitor current and past conditions, and troubleshoot abnormal system
operation. This manual was designed to troubleshoot the NEX-GEN system using the
information displayed on the EVENT screen of the touch-screen. A list of EVENTS is
accompanied by a description of the EVENT and a section on troubleshooting the EVENT.
WARNING
Note: This manual is subject to change at any time based on system improvements,
design changes, authorized modifications or new information. Please consult ChlorKing
for the latest revision.
Manufacturer:
ChlorKing Inc
6767 Peachtree Industrial Blvd.
Norcross, GA 30092
1-800-536-8180
EVENTS displayed in BLACK are current EVENTS that need to be addressed or cleared.
EVENTS displayed in GREEN are cleared. GREEN events are visible only as a record of what has
happened in the past.
This event must be cleared by adjusting the current level the first time the system is
operated. This event is cleared at the factory and will not normally be encountered in the
field. In the event a replacement touch screen or software update has been done, this event
may need to be cleared. Call ChlorKing at 800-536-8180 for the Current Adjustment
Procedure.
pH CALIBRATED
This event is cleared at the factory prior to delivery of equipment and not normally required in
the field. In the event that a replacement pH probe has been installed, pH calibration may be
required. Call ChlorKing at 800-536-8180 for pH Calibration Procedure.
This EVENT will automatically clear when the NEX-GEN is turned on. To turn the NEX-GEN
on, press and hold the on/off switch until the ON indicator is displayed.
On/Off
Indicator
On/Off
Switch
This event will be displayed any time a user has selected CLEAN CELLS from the service menu.
Once the cell cleaning process has been completed, CLEAN MODE will automatically clear. In the
event of a fault during cell cleaning, cell cleaning can be finished manually (call ChlorKing at 800-
536-8180 for instructions on operating clean mode from the test screen) or CLEAN MODE can be
manually cleared (for instructions on clearing a CLEAN MODE event, call ChlorKing at 800-536-
8180).
This event is displayed any time the water cooled heat-sink found inside of the control cabinet has
exceeded 170° F. If this event is displayed the heat-sink is currently above 170° F and chlorine
production will stop until the heat-sink temperature has fallen below the 170° set-point. When the
heat-sink cools to less than 170° F system operation will automatically resume and this event will
clear.
This event is displayed if the water level in the production tank falls below the salt sensor for more
than 30 seconds. If the water level recovers to a level above the salt sensor within 1 hour, the
system will resume normal operation.
This event is displayed if pH drops below 6.0. The system will flush the production tank with pool
water for up to 1 hour in an attempt to bring pH above 6.0. Once pH is above 6.0 the system
operation will resume.
This EVENT will automatically clear when the NEX-GEN has received a signal from an
external source asking for chorine to be fed to a body of water. If the EVENT does not clear,
the pool 1 icon is not active and the NEX-GEN system does not start to produce chorine
when an external source is active, perform the following steps.
1. Check that 120 VAC is available at the blue power cord on the NEX-GEN control box.
If 120 VAC is not available, check the external source for faults.
Pool 1
Relay,
Terminal 8 Power
Supply
Negative
Pool 1
Relay,
Terminals
13 and 14
Terminal
Block 1,
Terminals
1 and 2
3. Check for 120 VAC across pool 1 relay terminals 13 and 14.
If 120 VAC is not measured, repair or replace the wires from terminal block 1,
terminals 1 and 2 to pool 1 relay terminals 13 and 14.
4. With a volt meter set on the DC scale, check for 24 VDC from power supply negative
to the blue wire on pool 1 relay, terminal 8.
If 24 VDC is not measured repair or replace the blue wires from the power supply
positive connection to pool relay 1, terminal 8.
Pool I1
Relay 1,
Terminal 5
Pool 1 Power
Relay, Supply
Terminal 12 Negative
6. Check for 24 VDC from power supply negative to the blue wire on pool 1 relay,
terminal 9.
If 24 VDC is not measured repair or replace the blue wire from pool relay 1, terminal 9
to pool relay 1, terminal 12.
7. Check for 24 VDC from power supply negative to the white wire on pool 1 relay,
terminal 5.
8. Check for 24 VDC from power supply negative to the white wire I1.
If 24 VDC is not measured repair or replace the wire from pool relay 1, terminal 5 to I1.
If the NEX-GEN is equipped to feed multiple bodies of water, this EVENT will clear when the
NEX-GEN has received a signal from an additional external source asking for an additional
body of water to be fed chlorine. If the EVENT does not clear, the pool 2 icon is not active
and the NEX-GEN system does not start to produce chorine when an external source is
active, perform the following steps.
1. Check for 120 VAC across terminal block 3, terminal 10 and terminal block 4, terminal
1.
If 120 VAC is not measured, troubleshoot the external source that supplies the 120
VAC.
Terminal
Block 3,
Terminal 10
Terminal
Block 4,
Terminal 1
If 120 VAC is not measured, repair or replace the wires from terminal block 3, terminal
10 and terminal block 4, terminal 1 to pool 2 relay terminals 13 and 14.
Pool 2
Relay, Power
Terminal 8 Supply
Negative
Pool 2 Pool 2
Relay, Relay,
Terminal 14 Terminal 13
Pool 2
Relay,
Terminal 12
3. Check for 24 VDC from power supply negative to pool 2 relay, terminal 8.
If 24 VDC is not measured, repair or replace the wire from power supply positive to
pool 2 relay, terminal 8.
4. Check for 24 VDC from power supply negative to pool 2 relay, terminal 12.
If 24 VDC is not measured, repair or replace the wire from pool 2 relay, terminal 12 to
9.
I2
Pool 2
Relay,
Terminal 5
Power
Supply
Negative
Pool 2
Relay,
Terminal 9
6. Check for 24 VDC from power supply negative to pool 2 relay, terminal 5.
7. Check for 24 VDC from power supply negative to microcontroller terminal I2.
If 24 VDC is not measured repair or replace the wire from pool 2 relay, terminal 5 to I2.
This EVENT is displayed if the booster pump is off and the booster pump flow switch indicates the
booster pump is on. When this occurs, the system will shut down and will require the EVENT to be
acknowledged and cleared before the system will resume operation. If the EVENT cannot be
cleared troubleshoot as follows.
1. Ensure that there is no flow across the venturi with the booster pump off.
If flow is present, correct the installation. See page 11 of the Installation Manual for
plumbing guidelines.
2. Look through the clear T and check that the flow switch blade is not up against the reed
switch.
If the blade is not against the reed switch, go to the next step.
If the blade is against the reed switch, replace the flow switch.
Clear T
Blade Reed
Switch
Power
Supply I3
Negative
This EVENT is displayed if the booster pump is on and the booster pump flow switch is off. When
this occurs, the system will shut down and will require the event to be acknowledged and cleared
before the system will resume operation. If the EVENT cannot be cleared troubleshoot as follows.
1. From the Touch Screen on the NEX-GEN, select MENU then SERVICE then TEST to
pull up the test screen. Select and press the BOOSTER PUMP button.
If the booster pump does not start, go to Troubleshoot Booster Pump Flow Failure –
Booster Pump is Not Running
.
1. Ensure that there is adequate water available to the booster pump and no restrictions
back to the return line.
2. Look through the clear T and check that the flow switch blade is pressed up against the
reed switch.
If the blade is pressed against the reed switch, go to the next step.
If the blade is not pressed up against the reed switch, replace the booster pump.
Clear T
Blade Reed
Switch
If 24 VDC is not measured, repair or replace the blue wire between power supply positive
and terminal block 2, terminal 1.
4. Check for 24 VDC across power supply negative and the white wire at terminal block 2,
terminal 2.
5. Check for 24 VDC across power supply negative and the white wire at microcontroller I3.
If 24 VDC is not measured, repair or replace the white wire from terminal block 2, terminal
2 to microcontroller I3.
I3
Power
Supply
Negative
Terminal
Block 2,
Terminal 1
Terminal
Block 2,
Terminal 2
1. From the Touch Screen on the NEX-GEN, select MENU then SERVICE then TEST
to pull up the test screen. Select and press the BOOSTER PUMP button. The
booster pump output will be energized for 40 minutes in order to troubleshoot the
circuit.
3. Check for 208/240 VAC across the power supply L connection and the booster
pump contactor coil red wire.
If 208/240 VAC is not present, repair or replace the red wire from the incoming
terminal block to the booster pump contactor coil.
Power
Supply L
Connection
Booster
Pump
Circuit
Breaker
Booster Pump
Contactor Coil
Red Wire
Incoming
Terminal
Block Red
NEX-GEN Troubleshooting Guide Wire
2/10/2014 15
4. Check for 208/240 VAC across the microcontroller output C and the booster pump
contactor coil red wire.
If 208/240 VAC is not present, repair or replace the black jumper wires from power
supply L and microcontroller output C connections.
Microcontroller
Output C
Booster Pump
Contactor Coil
Red Wire
Microcontroller
Output 08
Booster Pump
Contactor Coil
Red Wire
If 208/240 VAC is not present, repair or replace the wire from the microcontroller
output 8 (08) and the booster pump contactor coil black wire.
Booster Pump
Contactor
Input Black Booster Pump
Wire Contactor
Input Red
Wire
Booster Pump
Booster Pump Contactor Coil
Contactor Coil Red Wire
Black Wire
7. Check for 208/240 VAC across the booster pump contactor input black wire and
the booster pump contactor input red wire. Be sure the booster pump is still
energized from step 1.
Booster Pump
Contactor
Booster Pump Output Red
Contactor Wire
Output Black
Wire
If 208/240 VAC is not present, repair or replace the wiring between the contactor
and terminal block 6, terminals 9 and 10.
Terminal Terminal
Block 6, Block 6,
Terminal Terminal 10
9
This EVENT is displayed if the circulation pump is off and the circulation pump flow switch indicates
the circulation pump is on. When this occurs, the system will shut down and will require the EVENT
to be acknowledged and cleared before the system will resume operation. If the EVENT cannot be
cleared troubleshoot as follows.
1. Look through the clear T and check that the flow switch blade is not up against the reed
switch.
If the blade is not against the reed switch, go to the next step.
If the blade is against the reed switch, replace the flow switch.
Clear T
Blade
Reed
Switch
Power
Supply I4
Negative
This event is displayed if the circulation pump is on and the circulation pump flow switch is off.
When this occurs, the system will shut down and will require the event to be acknowledged and
cleared before the system will resume operation. If the EVENT cannot be cleared troubleshoot as
follows.
1. From the Touch Screen on the NEX-GEN, select MENU then SERVICE then TEST to
pull up the test screen. Select and press the CIRCULATION PUMP button.
If the circulation pump does not start, go to Troubleshoot Circulation Pump Flow Failure –
Circulation Pump is Not Running
1. Ensure that there is adequate water in the production tank and that water is available to
the circulation pump and no restrictions from valve 7 and 8 are present.
If there are no restrictions and the production tank is full of water, go to the next step.
2. Look through the clear T and check that the flow switch blade is pressed up against the
reed switch.
If the blade is pressed against the reed switch, go to the next step.
If the blade is not pressed up against the reed switch, replace the circulation pump.
Clear T
Blade
Reed
Switch
If 24 VDC is not measured, repair or replace the blue wire between power supply positive
and terminal block 2, terminal 3.
4. Check for 24 VDC across power supply negative and the white wire at terminal block 2,
terminal 4.
5. Check for 24 VDC across power supply negative and the white wire at microcontroller I4.
If 24 VDC is not measured, repair or replace the white wire from terminal block 2, terminal
4 to microcontroller I4.
Power
Supply
Negative
Blue Wire
Terminal
Block 2,
Terminal 3
1. From the Touch Screen on the NEX-GEN, select MENU then SERVICE then TEST
to pull up the test screen. Select and press the CIRCULATION PUMP button. The
circulation pump output will be energized for 1 minute in order to troubleshoot the
circuit. Restart the circulation pump for each test if necessary.
3. Check for 208/240 VAC across the power supply L connection and the circulation
pump contactor coil red wire.
If 208/240 VAC is not present, repair or replace the red wire from the incoming
terminal block to the circulation pump contactor coil.
Power
Supply L
Connection
Circulation
Pump Circuit
Breaker
Circulation
Pump
Contactor Coil
Red Wire
Incoming
Terminal
Block Red
NEX-GEN Troubleshooting Guide 2/10/2014
Wire 25
4. Check for 208/240 VAC across the microcontroller output 6 (06) and the circulation
pump contactor coil red wire.
If 208/240 VAC is not present, repair or replace the black jumper wires from power
supply L and microcontroller output 6 (O6) connections.
Microcontroller
Output 6 (O6)
Circulation Pump
Contactor Coil
Red Wire
Microcontroller
Output 6 (O6)
Circulation Pump
Contactor Coil Red
Wire
If 208/240 VAC is not present, repair or replace the wire from the microcontroller
output 6 (O6) and the circulation pump contactor coil black wire.
Circulation
Pump
Contactor Input Circulation
Black Wire Pump
Contactor Input
Red Wire
7. Check for 208/240 VAC across the circulation pump contactor input black wire and
the circulation pump contactor input red wire. Be sure the circulation pump is still
energized from step 1.
Circulation
Pump Contactor
Circulation Output Red
Pump Contactor Wire
Output Black
Wire
If 208/240 VAC is not present, repair or replace the wiring between the contactor
and terminal block 6, terminals 7 and 8.
Terminal Terminal
Block 6, Block 6,
Terminal Terminal 8
7
This EVENT is displayed if the fan flow switch is indicating a fan that is on when the fan is off.
When this occurs, the system will shut down and will require the EVENT to be acknowledged and
cleared before the system will resume operation. If the EVENT cannot be cleared troubleshoot as
follows.
1. Look through the clear Y and check that the fan flow switch blade is in the down position
and that the reed switch is not making contact.
If the blade is in the down position with no reed switch contact, go to the next step.
If the blade is in the up position with reed switch contact, replace the fan flow switch.
Switch in
Down
Position
Reed
Switch No
Contact
Reed
Switch
Contact
Switch in
Up
Position
I5
Power
Supply
Negative
This EVENT is displayed if the fan should be on and fan flow switch is off. When this occurs, the
system will shut down and will require the EVENT to be acknowledged and cleared before the
system will resume operation. If the EVENT cannot be cleared troubleshoot as follows.
1. From the Touch Screen on the NEX-GEN, select MENU then SERVICE then TEST
then NEXT to pull up the test screen for the fan motor. Select and press the FAN
MOTOR button.
If the fan motor starts, go to Troubleshoot Fan Flow Failure – Fan is Running.
If the fan does not start, go to Troubleshoot Fan Flow Failure – Fan is Not Running
1. Look through the clear Y and check that the fan flow switch blade is in the up position and
that the reed switch is making contact.
If the blade is in the up position with the reed switch making contact, go to the next step.
If the blade is in the down position with no reed switch contact, replace the fan flow
switch.
Switch in
Down
Position
Reed
Switch No
Contact
Reed
Switch
Contact
Switch in
Up
Position
If 24 VDC is not measured, repair or replace the blue wire from power supply positive to
terminal block 2, terminal 5.
3. Check for 24 VDC from the power supply negative connection to the white wire on
terminal block 2, terminal 6.
Power
Power Supply
Supply Negative
Positive
Terminal
Block 2,
Terminal 5
Terminal
Block 2,
Terminal 6
If 24 VDC is not measured, replace the white wire from terminal block 2, terminal 6 to
microcontroller I5.
I5
Power
Supply
Negative
1. From the Touch Screen on the NEX-GEN, select MENU then SERVICE then TEST
then NEXT to pull up the test screen. Select and press the FAN MOTOR button.
The fan motor output will be energized for 1 minute in order to troubleshoot the
circuit. Restart the fan motor for each test if necessary.
If 208/240 VAC is not present, repair or replace the red wire from the incoming
terminal block to the fan relay terminal 14.
Power
Supply L
Connection
Fan Relay
Terminal 14
Incoming
Terminal
Block
If 208/240 VAC is not present, repair or replace the black wire from the power
supply L connection to the microcontroller O1 connection.
4. Check for 208/240 VAC across the microcontroller connection O1 output and the
red wire on fan relay terminal 14. Be sure to repeat step 1 if it has been more than
1 minute since the fan was last started.
5. Check for 208/240 VAC across the fan relay terminal 13 and the red wire on fan
relay terminal 14. Be sure to repeat step 1 if it has been more than 1 minute since
the fan was last started.
If 208/240 VAC is not present, repair or replace the black wire from the
microcontroller O1 output to the fan relay terminal 13.
O1 Input
O1 Output
If 24 VDC is not present, repair or replace the blue wire from the power supply
positive to the bottom of the fan fuse.
7. Check for 24 VDC across the fan relay terminal 12 and the blue wire on the bottom
of the fan fuse.
If 24 VDC is not present, repair or replace the white wire from the power supply
negative connection to the fan relay terminal 12.
8. Check for 24 VDC across the fan relay terminal 12 and the blue wire at the top of
the fan fuse.
Power
Supply
Negative
Blue Wire
Top of Fan Fan Relay
Fuse Terminal 12
Fan Fuse
If 24 VDC is not present, repair or replace the wire between the fan fuse and the
fan relay terminal 9.
10. Check for 24 VDC across the fan relay terminal 5 and 8. Be sure to repeat step 1 if
it has been more than 1 minute since the fan was last started.
Blue Wire
Fan Relay
Terminal 9
Fan Relay
Terminal 12
This EVENT is displayed if the pool circulation system is not circulating water. Once the pool
circulation system is restarted the system will resume normal operation and the EVENT will clear. If
the EVENT will not clear troubleshoot as follows.
2. Check that the pressure switch is connected to the pool circulation system and any
isolation valves used during installation are open. Check that water pressure is
available at the Pressure Switch Connection.
Pressure
Switch
Connection
3. Turn the power to the system off. Pull the safety boot back from the pressure switch.
Check for continuity across the 2 electrical connections on the pressure switch with
the pool circulation system operating. Continuity should be present.
Power I6
Supply
Negative
If 24 VDC is available, repair or replace the white wire from the pressure switch to the
micro controller I6.
Power
Supply
Negative
Pressure
Switch
White
Wire
Power
Supply
Negative
Pressure
Switch
Blue Wire
If 24 VDC is available, repair or replace the blue wire from the current/voltage sensor
to the pressure switch.
Power
Supply
Negative
Current/
Voltage
Sensor
Blue Wire
If 24 VDC is available repair or replace the blue wire from the current voltage sensor
to terminal block 1, terminal 5.
Power
Supply
Negative
Terminal
Block 1,
Terminal 5
blue wire
If 24 VDC is available, repair or replace the blue wire from terminal block 1, terminal 5
to pool 1 relay upper left screw.
Pool 1 Power
Relay Supply Power
Upper Left Positive Supply
Terminal Negative
Pool 2
Relay
Upper Left
Terminal
10. Connect the voltmeter to the power supply negative terminal and the blue wire on pool
2 relay upper left screw.
If 24 VDC is available, repair or replace the blue wire from pool 1relay to pool 2 relay.
11. Connect the voltmeter to the power supply negative terminal and the blue wire on
power supply positive terminal.
If 24 VDC is available, repair or replace the blue wire from pool 2 relay to the power
supply.
This EVENT is displayed if VALVE 1 does not respond to an open or close command but VALVE 2
has responded to its command. When this occurs the system will shut down unless VALVE 2 has
responded to an open command and will require the EVENT to be acknowledged and cleared
before the system will resume operation. If the EVENT cannot be cleared troubleshoot as follows.
1. From the Touch Screen on the NEX-GEN, select MENU then SERVICE then TEST
then NEXT to pull up the test screen for valve 1. This will turn the NEX-GEN off and
valve 1 should close and display a green dot next to the word CLOSED on the display.
If valve 1 closed and a green dot appeared next to the word CLOSED on the screen,
go to the next step.
If valve 1 closed but a green dot did not appear next to the word CLOSED on the
screen, go to Troubleshoot Valve 1 Did Not Respond – Feedback Circuit Close.
If valve 1 does not close, go to Troubleshoot Valve 1 Did Not Respond - Close.
Valve 1
If valve 1 opened and a green dot appeared next to the word OPEN on the screen,
valve 1 is working as designed.
If valve 1 opened but a green dot did not appear next to the word OPEN on the
screen, go to Troubleshoot Valve 1 Did Not Respond – Feedback Circuit Open.
If valve 1 does not open, go to Troubleshoot Valve 1 Did Not Respond - Open.
1. With valve 1 in the open position check for 24 VDC from the power supply negative
terminal to the blue wire on terminal block 2, terminal 9.
If 24 VDC is not available repair or replace the blue wire from power supply positive to
terminal block 2, terminal 9.
2. With valve 1 in the open position check for 24 VDC from the power supply negative
terminal to terminal block 3, terminal 1.
Power
Supply
Negative
Terminal
Block 2,
Terminal 9
Terminal
Block 3,
Terminal 1
If 24 VDC is not available repair or replace the white wire from terminal block 3,
terminal 1 to microcontroller terminal I8.
Power I8
Supply
Negative
Terminal
Block 2,
Terminal 9
Terminal
Block 3,
Terminal 1
1. With valve 1 in the closed position check for 24 VDC from the power supply negative
terminal to the blue wire on terminal block 2, terminal 9.
If 24 VDC is not available repair or replace the blue wire from power supply positive to
terminal block 2, terminal 9.
2. With valve 1 in the closed position check for 24 VDC from the power supply negative
terminal to terminal block 2, terminal 10.
Power
Supply
Negative
Terminal
Block 2,
Terminal 9
Terminal
Block 2,
Terminal 10
If 24 VDC is not available repair or replace the white wire from terminal block 2,
terminal 10 to microcontroller terminal I8.
Power I7
Supply
Negative
Terminal
Block 2,
Terminal 9
Terminal
Block 2,
Terminal 10
1. Check for 240 VAC across the red wire on terminal block 6, terminal 1 and the black
wire on the incoming terminal block.
If 240 VAC is not available repair or replace the red wire from terminal block 6,
terminal 1 to the incoming terminal block.
Black Wire
Incoming
Terminal Block
Red Wire
Terminal Bock
6, Terminal 1
If 240 VAC is not available repair or replace the black wire from the top of the main
fuse to the bottom of the valve 1 fuse.
Bottom of
Valve 1
Fuse
Top of
Main
Fuse
Red Wire
Terminal Bock
6, Terminal 1
Top of
Valve 1
Fuse
Red Wire
Terminal Bock
6, Terminal 1
If 240 VAC is not available repair or replace the wire from the top of valve 1 fuse to
valve 1 relay, terminal 9.
Valve 1
Relay
Terminal 9
Red Wire
Terminal Bock
6, Terminal 1
Valve 1
Relay
Terminal 1
Red Wire
Terminal Bock
6, Terminal 1
If 240 VAC is not available repair or replace the wire from valve 1 relay terminal 1 to
terminal block 5, terminal 2.
Terminal
Block 5,
Terminal 2
Red Wire
Terminal Bock
6, Terminal 1
1. Check for 240 VAC across the red wire on valve 1 relay, terminal 14 and the black
wire on the incoming terminal block.
If 240 VAC is not available repair or replace the red wire from valve 1 relay terminal 14
to the incoming terminal block.
Black Wire
Incoming
Terminal
Block
If 240 VAC is not available repair or replace the wire from power supply terminal L to
microcontroller terminal O4.
O4
Power
Supply
Terminal L
O4
If 240 VAC is not available repair or replace the black wire from microcontroller
terminal O4 to valve 1 relay, terminal 13.
O4
Valve 1 Relay,
Terminal 13 Red Wire Valve
1 Relay,
Terminal 14
If 240 VAC is not available repair or replace the red wire from terminal block 6,
terminal 1 to the incoming terminal block.
Black Wire
Incoming
Terminal Block
Red Wire
Terminal Bock
6, Terminal 1
If 240 VAC is not available repair or replace the black wire from the top of the main
fuse to the bottom of the valve 1 fuse.
Bottom of
Valve 1
Fuse
Top of
Main
Fuse
Red Wire
Terminal Bock
6, Terminal 1
Top of
Valve 1
Fuse
Red Wire
Terminal Bock
6, Terminal 1
If 240 VAC is not available repair or replace the wire from the top of valve 1 fuse to
valve 1 relay, terminal 9.
Valve 1
Relay
Terminal 9
Red Wire
Terminal Bock
6, Terminal 1
Valve 1
Relay
Terminal 5
Red Wire
Terminal Bock
6, Terminal 1
If 240 VAC is not available repair or replace the wire from valve 1 relay terminal 5 to
terminal block 5, terminal 1.
Terminal
Block 5,
Terminal 2
Red Wire
Terminal Bock
6, Terminal 1
The opening or closing of valve 2 is controlled by an external device; however the valve is
monitored by the NEX-GEN. This EVENT is displayed if VALVE 2 does not respond to an open or
close command but VALVE 1 has responded to its command. When this occurs the system will
shut down unless VALVE 1 has responded to an open command and will require the EVENT to be
acknowledged and cleared before the system will resume operation. If the EVENT cannot be
cleared troubleshoot as follows.
1. Confirm that the external devise is calling for pool 2 to feed. From the Touch Screen
on the NEX-GEN, select MENU then SERVICE then TEST then NEXT to pull up the
test screen for valve 2. This will turn the NEX-GEN off and valve 2 should close and
display a green dot next to the word CLOSED on the display.
If valve 2 closed and a green dot appeared next to the word CLOSED on the screen,
go to the next step.
If valve 2 closed but a green dot did not appear next to the word CLOSED on the
screen, go to Troubleshoot Valve 2 Did Not Respond – Feedback Circuit Close.
If valve 2 does not close, troubleshoot the external control device for valve 2.
2. Confirm that the external devise is calling for pool 2 to feed. From the Touch Screen
on the NEX-GEN, press VALVE 2. Valve 2 should open and a green dot should
appear next to the word OPEN on the screen.
If valve 2 opened and a green dot appeared next to the word OPEN on the screen,
valve 2 is working as designed.
If valve 2 opened but a green dot did not appear next to the word OPEN on the
screen, go to Troubleshoot Valve 2 Did Not Respond – Feedback Circuit Open.
If valve 2 does not open, go to Troubleshoot Valve 2 Did Not Respond - Open.
1. With valve 2 in the open position check for 24 VDC from the power supply negative
terminal to the blue/red wire on terminal block 2, terminal 9.
If 24 VDC is not available repair or replace the blue wire from power supply positive to
terminal block 2, terminal 9.
Power
Supply
Negative
Terminal
Block 2,
Terminal 9
If 24 VDC is not available repair or replace the red wire from terminal block 2, terminal
9 to terminal block 4, terminal 4.
Power
Supply
Negative
Terminal
Block 4,
Terminal 4
If 24 VDC is not available troubleshoot the external control device for valve 2.
Power
Supply
Negative
Terminal
Block 4,
Terminal 3
If 24 VDC is not available repair or replace the orange wire from terminal block 4,
terminal 3 to microcontroller terminal IA.
Power
Supply IA
Negative
Terminal
Block 4,
Terminal 3
1. With valve 2 in the closed position check for 24 VDC from the power supply negative
terminal to the blue/red wire on terminal block 2, terminal 9.
If 24 VDC is not available repair or replace the blue wire from power supply positive to
terminal block 2, terminal 9.
Power
Supply
Negative
Terminal
Block 2,
Terminal 9
If 24 VDC is not available repair or replace the red wire from terminal block 2, terminal
9 to terminal block 4, terminal 4.
Power
Supply
Negative
Terminal
Block 4,
Terminal 4
If 24 VDC is not available troubleshoot the external control device for valve 2.
Power
Supply
Negative
Terminal
Block 4,
Terminal 2
If 24 VDC is not available repair or replace the orange wire from terminal block 4,
terminal 3 to microcontroller terminal IA.
Power
Supply I9
Negative
Terminal
Block 4,
Terminal 2
1. Confirm that an external devise is calling for pool 2 to feed and that the EVENT
WAITING FOR ORP 2 is green.
2. Check for 120 VAC across Pool 2 relay terminal 14 and microcontroller terminal O5.
If 120 VAC is not available, repair or replace the white wire from pool 2 relay, terminal
13 to microcontroller terminal O5.
O5
Pool 2
Relay,
Terminal 14
O5
Pool 2
Relay,
Terminal 14
If 120 VAC is not available, repair or replace the purple wire from microcontroller
terminal 5 to terminal block 4, terminal 5.
Pool 2
Relay,
Terminal 14
O5
This EVENT is displayed if VALVE 1 or VALVE 2 did not responded to an open command and both
valves are closed. When this occurs, the system will shut down and will require the EVENT to be
acknowledged and cleared before the system will resume operation. If the EVENT cannot be
cleared troubleshoot using the steps in Valve 1 Did Not Respond or Valve 2 Did Not Respond
depending on which valve is not responding.
This EVENT is displayed if the water level in the production tank falls below the salt sensor for more
than 30 seconds five times in 1 hour. When this occurs, the system will shut down and will require
the EVENT to be acknowledged and cleared before the system will resume operation. If the
EVENT cannot be cleared troubleshoot as follows.
1. Check Valve 3, Tank Fill Valve to make sure it is all the way open.
Valve 3
This EVENT is displayed if the water level in the production tank is below the salt sensor for more
than 1 hour with the booster pump running. When this occurs, the system will shut down and will
require the EVENT to be acknowledged and cleared before the system will resume operation. If the
EVENT cannot be cleared troubleshoot as follows.
1. Check Valve 3, Tank Fill Valve to make sure it is all the way open.
Valve 3
2. Check the float inside the production tank for mechanical damage or obstructions and
repair or replace the float.
This EVENT is displayed if the salt concentration in the production tank falls below 3000 PPM or if
the salt concentration set-point cannot be reached in 15 minutes. When this occurs, the system will
shut down and will require the EVENT to be acknowledged and cleared before the system will
resume operation. If the EVENT cannot be cleared troubleshoot as follows.
1. Check that the Saturated Salt Feeder is full of rock or pellet salt. Only use rock or
pellet salt in the ChlorKing Saturated Salt Feeder. Fine salt can clog the suction of the
feeder. The Saturated Salt Feeder may require cleaning at regular intervals to remove
debris introduced with the salt.
If the Saturated Salt Feeder is full of rock or pellet salt, go to the next step.
If the Saturated Salt Feeder is not full or has the wrong type of salt, add or replace salt
as necessary.
2. Check that the Saturated Salt Feeder float tank has a source of water and is
approximately ¼ full of water.
If the Saturated Salt Feeder has a source of water, go to the next step.
If the Saturated Salt Feeder has no water, correct this condition. See the NEX-GEN
Installation and Operating Manual for details on Saturated Salt Feeder installation and
operation.
3. Check that the peristaltic salt pump is plugged in, turned on, and the suction and
discharge lines are connected to the Saturated Salt Feeder and NEX-GEN.
If the salt pump runs, replace all salt pump tubing and the injection check valve.
6. Unplug the salt pump from the electrical plug and check for 208/240 VAC at the plug.
Be sure to restart the salt pump outlined in step 5 if it has been more than 1 minute
since it was last started.
If 208/240 is not available, repair or replace the red wire from the incoming terminal
block to the salt relay, terminal 14.
If 208/240 is not available, repair or replace the wire from the power supply L terminal
to output 2, left side connection.
Black Wire
Output 2, left
Power side connection
Supply
Terminal L
Black Wire
Output 2, right
side connection
If 208/240 is not available, repair or replace the wire from output 2, right side
connection to the salt relay, terminal 13.
If 208/240 is not available, repair or replace the wire from terminal block 6, terminal 3
to the red wire on the incoming terminal block.
If 208/240 is not available, repair or replace the wire from the incoming terminal block
to the bottom of the salt fuse.
Black Wire
Bottom of Salt
Fuse
Black Wire
Incoming
Terminal Block
Red Wire
Terminal Block
6, Terminal 3
NEX-GEN Troubleshooting Guide 2/10/2014 90
13. Check for 208/240 VAC from the black wire at the top of the salt fuse to the red wire
on terminal block 6, terminal 3.
Black Wire
Top of Salt
Fuse
Red Wire
Terminal Block
6, Terminal 3
If 208/240 is not available, repair or replace the wire from the top of the salt fuse to the
terminal 9 on the salt relay.
Terminal 9
Salt Relay
Red Wire
Terminal Block
6, Terminal 3
NEX-GEN Troubleshooting Guide 2/10/2014 92
15. Check for 208/240 VAC from the black wire at terminal 5 on the salt relay to the red
wire on terminal block 6, terminal 3. Be sure to restart the salt pump outlined in step 5
if it has been more than 1 minute since it was last started.
Terminal 5
Salt Relay
Red Wire
Terminal Block
6, Terminal 3
NEX-GEN Troubleshooting Guide 2/10/2014 93
16. Check for 208/240 VAC from the black wire at terminal block 6, terminal 2 to the red
wire on terminal block 6, terminal 3. Be sure to restart the salt pump outlined in step 5
if it has been more than 1 minute since it was last started.
If 208/240 is not available, repair or replace the wire from the salt relay terminal 5 to
terminal block 6, terminal 2.
Red Wire
Black Wire Terminal Block
Terminal Block 6, Terminal 3
6, Terminal 2
This EVENT is displayed if the water temperature in the production tank is below 40° F or if the
water temperature is between 40° F and 59° F and the system has operated for 1 hour in attempt to
raise the water temperature. The NEX-GEN system is not designed to operate in temperatures
below 59° F. When this occurs, the system will shut down and will require the EVENT to be
acknowledged and cleared before the system will resume operation.
This EVENT is displayed if the water temperature in the production tank is above 110° F. The
system will shut down and attempt to cool the water for 1 hour to a temperature below 110° F.
Once the water has cooled to a temperature below 110° F, the system will automatically restart. In
the event that the water does not cool to a temperature below 110° F in 1 hour, the system will shut
down and will require the EVENT to be acknowledged and cleared before the system will resume
operation.
This EVENT is displayed if the salt sensor indicates the production tank is full and the low level
switch indicates the production tank is empty. When this occurs, the system will shut down and will
require the EVENT to be acknowledged and cleared before the system will resume operation. If the
EVENT cannot be cleared troubleshoot as follows.
1. Check for 24 VDC from the power supply negative to terminal block 1, terminal 5.
If 24 VDC is not available, repair or replace the blue wire from power supply positive to
terminal block 1, terminal 5.
Power
Supply
Negative
Terminal
Block 1,
Terminal 5
Terminal Power IF
Block 1, Supply
Terminal 4 Negative
3. Check for 24 VDC from the power supply negative to microcontroller terminal IF.
This event is displayed if the salt sensor indicates the production tank is full and the acid wash
switch indicates the system is empty. This event will not stop system production however the cell
cleaning procedure will not function. If the EVENT cannot be cleared troubleshoot as follows.
1. Check for 24 VDC from the power supply negative to terminal block 3, terminal 7.
If 24 VDC is not available, repair or replace the blue wire from power supply positive to
terminal block 3, terminal 7.
Power
Supply
Negative
Terminal
Block 3,
Terminal 7
Power IG
Supply
Negative
Terminal
Block 3,
Terminal 9
3. Check for 24 VDC from the power supply negative to microcontroller terminal IG.
This EVENT will be displayed if the system pH is below 6.0 for more than 1 hour. When this occurs,
the system will shut down and will require the EVENT to be acknowledged and cleared before the
system will resume operation. The Low pH Alarm EVENT will only become active after the system
has flushed the production tank for 1 hour under the Low pH EVENT.
1. Acknowledge and clear the event to force the system into Low pH flushing. During
flushing verify that Tank Fill Valve 3 is open, Flow Adjust Valve 4 is adjusted properly,
Actuated Feed Valve 1 is open, and the Flow Meter has fluid being drawn though it.
If the above items are not correct, correct them and allow the system to flush for 1
hour.
Flow
Adjust
Valve 4
Actuated
Feed
Valve 1
If the supply water has a pH greater than 6.0, replace the pH probe.
If the supply water has a pH less than 6.0, correct the water supply.