1MRK504164-UEN - en - N - Technical Manual, Transformer Protection RET670 Version 2.2 IEC
1MRK504164-UEN - en - N - Technical Manual, Transformer Protection RET670 Version 2.2 IEC
The software and hardware described in this document is furnished under a license and may be used
or disclosed only in accordance with the terms of such license.
This product includes software developed by the OpenSSL Project for use in the OpenSSL Toolkit.
(https://www.openssl.org/) This product includes cryptographic software written/developed by: Eric
Young (eay@cryptsoft.com) and Tim Hudson (tjh@cryptsoft.com).
Trademarks
ABB is a registered trademark of ABB Asea Brown Boveri Ltd. Manufactured by/for a Hitachi Power
Grids company. All other brand or product names mentioned in this document may be trademarks or
registered trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest Hitachi Power Grids representative.
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or product
description and are not to be deemed as a statement of guaranteed properties. All persons
responsible for applying the equipment addressed in this manual must satisfy themselves that each
intended application is suitable and acceptable, including that any applicable safety or other
operational requirements are complied with. In particular, any risks in applications where a system
failure and/or product failure would create a risk for harm to property or persons (including but not
limited to personal injuries or death) shall be the sole responsibility of the person or entity applying
the equipment, and those so responsible are hereby requested to ensure that all measures are taken
to exclude or mitigate such risks.
This document has been carefully checked by Hitachi Power Grids but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested to notify the
manufacturer. Other than under explicit contractual commitments, in no event shall Hitachi Power
Grids be responsible or liable for any loss or damage resulting from the use of this manual or the
application of the equipment.
Conformity
This product complies with the directive of the Council of the European Communities on the
approximation of the laws of the Member States relating to electromagnetic compatibility (EMC
Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits
(Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by Hitachi Power
Grids in accordance with the product standard EN 60255-26 for the EMC directive, and with the
product standards EN 60255-1 and EN 60255-27 for the low voltage directive. The product is
designed in accordance with the international standards of the IEC 60255 series.
1MRK 504 164-UEN Rev. N Table of contents
Table of contents
Section 1 Introduction..................................................................................................49
1.1 This manual.........................................................................................................................49
1.1.1 Presumptions for Technical Data.......................................................................................49
1.2 Intended audience...............................................................................................................49
1.3 Product documentation....................................................................................................... 50
1.3.1 Product documentation set................................................................................................50
1.3.2 Document revision history................................................................................................. 51
1.3.3 Related documents........................................................................................................... 52
1.4 Document symbols and conventions...................................................................................53
1.4.1 Symbols.............................................................................................................................53
1.4.2 Document conventions......................................................................................................53
1.5 IEC 61850 edition 1 / edition 2 mapping............................................................................. 56
5.2.1 Identification...................................................................................................................... 91
5.2.2 Function block................................................................................................................... 91
5.2.3 Signals...............................................................................................................................92
5.3 Basic part for LED indication module.................................................................................. 92
5.3.1 Identification...................................................................................................................... 92
5.3.2 Function block................................................................................................................... 92
5.3.3 Signals...............................................................................................................................93
5.3.4 Settings............................................................................................................................. 93
5.4 LCD part for HMI function keys control module ..................................................................94
5.4.1 Identification...................................................................................................................... 94
5.4.2 Function block................................................................................................................... 94
5.4.3 Signals...............................................................................................................................94
5.4.4 Settings............................................................................................................................. 95
5.5 Operation principle.............................................................................................................. 96
5.5.1 Local HMI.......................................................................................................................... 96
5.5.1.1 Keypad......................................................................................................................... 97
5.5.1.2 Display......................................................................................................................... 99
5.5.1.3 LEDs.......................................................................................................................... 101
5.5.2 LED configuration alternatives........................................................................................ 102
5.5.2.1 Functionality .............................................................................................................. 102
5.5.2.2 Status LEDs............................................................................................................... 102
5.5.2.3 Indication LEDs.......................................................................................................... 103
5.5.3 Function keys.................................................................................................................. 110
5.5.3.1 Functionality .............................................................................................................. 110
5.5.3.2 Operation principle .................................................................................................... 110
5.5.3.3 Enabling and Disabling Authority on Function keys....................................................111
17.1.5 Signals...........................................................................................................................1040
17.1.6 Settings......................................................................................................................... 1041
17.1.7 Operation principle........................................................................................................ 1041
17.1.7.1 Blocking scheme...................................................................................................... 1041
17.1.7.2 Delta blocking scheme............................................................................................. 1042
17.1.7.3 Permissive underreaching scheme.......................................................................... 1043
17.1.7.4 Permissive overreaching scheme............................................................................ 1043
17.1.7.5 Unblocking scheme..................................................................................................1043
17.1.7.6 Intertrip scheme....................................................................................................... 1044
17.1.7.7 Simplified logic diagram........................................................................................... 1044
17.1.8 Technical data............................................................................................................... 1045
17.2 Phase segregated scheme communication logic for distance protection ZPCPSCH .... 1046
17.2.1 Function revision history................................................................................................1046
17.2.2 Identification.................................................................................................................. 1046
17.2.3 Functionality ................................................................................................................. 1047
17.2.4 Function block............................................................................................................... 1047
17.2.5 Signals...........................................................................................................................1048
17.2.6 Settings......................................................................................................................... 1049
17.2.7 Operation principle........................................................................................................ 1049
17.2.7.1 Blocking scheme...................................................................................................... 1049
17.2.7.2 Permissive underreach scheme...............................................................................1050
17.2.7.3 Permissive overreach scheme................................................................................. 1050
17.2.7.4 Unblocking scheme..................................................................................................1050
17.2.7.5 Intertrip scheme....................................................................................................... 1050
17.2.7.6 Simplified logic diagram........................................................................................... 1051
17.2.8 Technical data............................................................................................................... 1052
17.3 Current reversal and Weak-end infeed logic for distance protection 3-phase
ZCRWPSCH ...................................................................................................................1052
17.3.1 Function revision history................................................................................................1052
17.3.2 Identification.................................................................................................................. 1052
17.3.3 Functionality ................................................................................................................. 1052
17.3.4 Function block............................................................................................................... 1053
17.3.5 Signals...........................................................................................................................1053
17.3.6 Settings......................................................................................................................... 1054
17.3.7 Operation principle........................................................................................................ 1054
17.3.7.1 Current reversal logic............................................................................................... 1054
17.3.7.2 Weak-end infeed logic..............................................................................................1055
17.3.8 Technical data............................................................................................................... 1056
17.4 Current reversal and weak-end infeed logic for phase segregated communication
ZPCWPSCH ...................................................................................................................1057
17.4.1 Function revision history................................................................................................1057
17.4.2 Identification.................................................................................................................. 1057
17.4.3 Functionality ................................................................................................................. 1057
17.4.4 Function block............................................................................................................... 1058
17.4.5 Signals...........................................................................................................................1058
17.4.6 Settings......................................................................................................................... 1059
18.11.4 Signals...........................................................................................................................1123
18.11.5 Monitored data...............................................................................................................1124
18.11.6 Settings..........................................................................................................................1124
18.11.7 Operation principle........................................................................................................ 1124
18.11.8 Technical data................................................................................................................1125
18.12 Boolean to integer conversion with logical node representation, 16 bit BTIGAPC..........1125
18.12.1 Identification.................................................................................................................. 1125
18.12.2 Functionality ................................................................................................................. 1125
18.12.3 Function block............................................................................................................... 1125
18.12.4 Signals...........................................................................................................................1126
18.12.5 Settings..........................................................................................................................1126
18.12.6 Monitored data...............................................................................................................1126
18.12.7 Operation principle........................................................................................................ 1126
18.12.8 Technical data................................................................................................................1127
18.13 Integer to boolean 16 conversion IB16............................................................................1127
18.13.1 Identification.................................................................................................................. 1127
18.13.2 Functionality ................................................................................................................. 1127
18.13.3 Function block............................................................................................................... 1128
18.13.4 Signals...........................................................................................................................1128
18.13.5 Setting parameters ....................................................................................................... 1129
18.13.6 Operation principle........................................................................................................ 1129
18.13.7 Technical data................................................................................................................1130
18.14 Integer to Boolean 16 conversion with logic node representation ITBGAPC.................. 1130
18.14.1 Identification.................................................................................................................. 1130
18.14.2 Functionality ................................................................................................................. 1130
18.14.3 Function block............................................................................................................... 1130
18.14.4 Signals...........................................................................................................................1131
18.14.5 Settings..........................................................................................................................1131
18.14.6 Operation principle........................................................................................................ 1131
18.14.7 Technical data................................................................................................................1132
18.15 Elapsed time integrator with limit transgression and overflow supervision TEIGAPC.....1133
18.15.1 Identification.................................................................................................................. 1133
18.15.2 Functionality.................................................................................................................. 1133
18.15.3 Function block............................................................................................................... 1133
18.15.4 Signals...........................................................................................................................1134
18.15.5 Settings..........................................................................................................................1134
18.15.6 Operation principle........................................................................................................ 1134
18.15.6.1 Operation accuracy.................................................................................................. 1135
18.15.6.2 Memory storage....................................................................................................... 1136
18.15.7 Technical data................................................................................................................1136
18.16 Comparator for integer inputs INTCOMP........................................................................ 1136
18.16.1 Identification.................................................................................................................. 1136
18.16.2 Functionality ................................................................................................................. 1136
18.16.3 Function block............................................................................................................... 1136
18.16.4 Signals...........................................................................................................................1137
18.16.5 Settings..........................................................................................................................1137
Section 20 Metering....................................................................................................1307
20.1 Pulse-counter logic PCFCNT.......................................................................................... 1307
20.1.1 Identification.................................................................................................................. 1307
20.1.2 Functionality ................................................................................................................. 1307
20.1.3 Function block............................................................................................................... 1307
20.1.4 Signals...........................................................................................................................1307
20.1.5 Settings......................................................................................................................... 1308
20.1.6 Monitored data.............................................................................................................. 1308
20.1.7 Operation principle........................................................................................................ 1308
20.1.8 Technical data............................................................................................................... 1310
20.2 Function for energy calculation and demand handling ETPMMTR................................. 1310
20.2.1 Identification.................................................................................................................. 1310
20.2.2 Functionality ................................................................................................................. 1310
20.2.3 Function block............................................................................................................... 1311
20.2.4 Signals...........................................................................................................................1311
20.2.5 Settings......................................................................................................................... 1312
20.2.6 Monitored data.............................................................................................................. 1313
20.2.7 Operation principle........................................................................................................ 1313
20.2.8 Technical data............................................................................................................... 1316
Section 24 Security.....................................................................................................1463
24.1 Authority check ATHCHCK..............................................................................................1463
24.1.1 Identification.................................................................................................................. 1463
24.1.2 Functionality ................................................................................................................. 1463
24.1.3 Operation principle ....................................................................................................... 1463
24.1.3.1 Authorization with Central Account Management enabled IED............................... 1465
24.2 Authority management AUTHMAN................................................................................. 1467
Section 1 Introduction
1.1 This manual GUID-AB423A30-13C2-46AF-B7FE-A73BB425EB5F v20
The technical manual contains operation principle descriptions, and lists function blocks, logic
diagrams, input and output signals, setting parameters and technical data, sorted per function. The
manual can be used as a technical reference during the engineering phase, installation and
commissioning phase, and during normal service.
The technical data stated in this document are only valid under the following circumstances:
1. Main current transformers with 1 A or 2 A secondary rating are wired to the IED 1 A rated CT
inputs.
2. Main current transformer with 5 A secondary rating are wired to the IED 5 A rated CT inputs.
3. CT and VT ratios in the IED are set in accordance with the associated main instrument
transformers. Note that for functions which measure an analogue signal which do not have
corresponding primary quantity the 1:1 ratio shall be set for the used analogue inputs on the
IED. Example of such functions are: HZPDIF, ROTIPHIZ and STTIPHIZ.
4. Parameter IBase used by the tested function is set equal to the rated CT primary current.
5. Parameter UBase used by the tested function is set equal to the rated primary phase-to-phase
voltage.
6. Parameter SBase used by the tested function is set equal to:
• √3 × IBase × UBase
7. The rated secondary quantities have the following values:
• Rated secondary phase current Ir is either 1 A or 5 A depending on selected TRM.
• Rated secondary phase-to-phase voltage Ur is within the range from 100 V to 120 V.
• Rated secondary power for three-phase system Sr = √3 × Ur × Ir
8. For operate and reset time testing, the default setting values of the function and BOM module
are used if not explicitly stated otherwise.
All reset times are measured using BOM output contacts if not explicitly stated otherwise. The
operate/reset times are determined by characteristics of the output module used.
9. During testing, signals with rated frequency have been injected if not explicitly stated otherwise.
10. All declared operate times are with BOM module unless specified. All the declared operate (trip)
times can be reduced by 3-4 ms when using SOM module.
This manual addresses system engineers and installation and commissioning personnel, who use
technical data during engineering, installation and commissioning, and in normal service.
The system engineer must have a thorough knowledge of protection systems, protection equipment,
protection functions and the configured functional logic in the IEDs. The installation and
commissioning personnel must have a basic knowledge in handling electronic equipment.
Decommissioning
Commissioning
Maintenance
Engineering
Operation
Installing
Engineering manual
Installation manual
Commissioning manual
Operation manual
Application manual
Technical manual
Communication
protocol manual
Cyber security
deployment guideline
IEC07000220-4-en.vsd
IEC07000220 V4 EN-US
The installation manual contains instructions on how to install the IED. The manual provides
procedures for mechanical and electrical installation. The chapters are organized in the chronological
order in which the IED should be installed.
The commissioning manual contains instructions on how to commission the IED. The manual can
also be used by system engineers and maintenance personnel for assistance during the testing
phase. The manual provides procedures for the checking of external circuitry and energizing the IED,
parameter setting and configuration as well as verifying settings by secondary injection. The manual
describes the process of testing an IED in a substation which is not in service. The chapters are
organized in the chronological order in which the IED should be commissioned. The relevant
procedures may be followed also during the service and maintenance activities.
The operation manual contains instructions on how to operate the IED once it has been
commissioned. The manual provides instructions for the monitoring, controlling and setting of the
IED. The manual also describes how to identify disturbances and how to view calculated and
measured power grid data to determine the cause of a fault.
The application manual contains application descriptions and setting guidelines sorted per function.
The manual can be used to find out when and for what purpose a typical protection function can be
used. The manual can also provide assistance for calculating settings.
The technical manual contains operation principle descriptions, and lists function blocks, logic
diagrams, input and output signals, setting parameters and technical data, sorted per function. The
manual can be used as a technical reference during the engineering phase, installation and
commissioning phase, and during normal service.
The communication protocol manual describes the communication protocols supported by the IED.
The manual concentrates on the vendor-specific implementations.
The point list manual describes the outlook and properties of the data points specific to the IED. The
manual should be used in conjunction with the corresponding communication protocol manual.
The cyber security deployment guideline describes the process for handling cyber security when
communicating with the IED. Certification, Authorization with role based access control, and product
engineering for cyber security related events are described and sorted by function. The guideline can
be used as a technical reference during the engineering phase, installation and commissioning
phase, and during normal service.
The electrical warning icon indicates the presence of a hazard which could result in
electrical shock.
The warning icon indicates the presence of a hazard which could result in personal
injury.
The caution hot surface icon indicates important information or warning about the
temperature of product surfaces.
Class 1 Laser product. Take adequate measures to protect the eyes and do not view
directly with optical instruments.
The caution icon indicates important information or warning related to the concept
discussed in the text. It might indicate the presence of a hazard which could result in
corruption of software or damage to equipment or property.
The information icon alerts the reader of important facts and conditions.
The tip icon indicates advice on, for example, how to design your project or how to
use a certain function.
Although warning hazards are related to personal injury, it is necessary to understand that under
certain operational conditions, operation of damaged equipment may result in degraded process
performance leading to personal injury or death. It is important that the user fully complies with all
warning and cautionary notices.
• Abbreviations and acronyms in this manual are spelled out in the glossary. The glossary also
contains definitions of important terms.
• Push button navigation in the LHMI menu structure is presented by using the push button icons.
For example, to navigate between the options, use and .
• HMI menu paths are presented in bold.
For example, select Main menu/Settings.
• LHMI messages are shown in Courier font.
For example, to save the changes in non-volatile memory, select Yes and press .
• Parameter names are shown in italics.
For example, the function can be enabled and disabled with the Operation setting.
• Each function block symbol shows the available input/output signal.
• the character ^ in front of an input/output signal name indicates that the signal name may
be customized using the PCM600 software.
• the character * after an input signal name indicates that the signal must be connected to
another function block in the application configuration to achieve a valid application
configuration.
• Dimensions are provided both in inches and millimeters. If it is not specifically mentioned then
the dimension is in millimeters.
• Logic diagrams describe the signal logic of the function block and are bordered by dashed lines.
In a logic diagram, input and output signal paths are shown as lines that touch the outer border
of the diagram. Input signals are always on the left-hand side and output signals are on the
right-hand side.
Input and output signals can be configured using PCM600. They can be connected to the inputs
and outputs of other functions and to binary inputs and outputs. Examples of input signals are
BLKTR, BLOCK, and VTSZ. Examples of output signals are TRIP, START, STL1, STL2, and
STL3.
• Frames with a shaded area on the right-hand side represent setting parameters. These
parameters can only be set via the PST or LHMI. Their values are high (1) only when the
corresponding setting parameter is set to the symbolic value specified within the frame.
Example is the signal Timer tPP=On. Their logical values correspond automatically to the
selected setting value.
• Internal signals are illustrated graphically and end approximately 2 mm from the frame
edge. If an internal signal path cannot be drawn with a continuous line, the same signal
name is used where the signal should continue, see figure 2 and figure 3. Example of the
internal signal is BLK.
• Signal paths that extend beyond the logic diagram and continue in another diagram will be
approximately 2 mm from the frame edge, see figure 3 and figure 4. Examples are
STNDL1N, STNDL2N, STNDL3N, STNDL1L2, STNDL2L3, and STNDL3L1.
STZMPP
OR
STCND
AND STNDL1L2
L1L2
STNDL2L3
L2L3 AND
AND STNDL1N
L1N
AND STNDL2N
L2N
STNDL3N
L3N AND
OR STPE
OR
VTSZ STND
OR AND
BLOCK
BLOCFUNC BLK
99000557-2.vsd
IEC99000557-TIFF V3 EN-US
IEC00000488-TIFF V1 EN-US
Timer tPP=On
STZMPP AND tPP
AND
t
BLOCFUNC
OR OR
tPE
t
AND
Timer tPE=On AND
STZMPE 15ms
BLKTR AND t
TRIP
BLK OR
IEC09000887-3-en.vsdx
IEC09000887 V3 EN-US
Illustrations are used as an example and might show other products than the one the
manual describes. The example that is illustrated is still valid.
Function block names are used in ACT and PST to identify functions. Respective function block
names of Edition 1 logical nodes and Edition 2 logical nodes are shown in the table below.
The following tables list all the functions available in the IED. Those functions that
are not exposed to the user or do not need to be configured are not described in this
manual.
RET670 (A10)
RET670 (B30)
RET670 (B40)
RET670 (A25)
RET670
(Customized)
Differential protection
T2WPDIF 87T Transformer differential protection, two 1-3 1
winding
T3WPDIF 87T Transformer differential protection, three 1-3 1
winding
HZPDIF 87 High impedance differential protection, single 0-6 1 3-A02 3-A02
phase
REFPDIF 87N Restricted earth fault protection, low 0-3 1 2 2B
impedance 1-A01
LDRGFC 11REL Additional security logic for differential 0-1
protection
PSTPDIF 87T Self-adaptive differential protection for two- 1
winding power transformers
Impedance protection
ZMQPDIS, 21 Distance protection zone, quadrilateral 0-5
ZMQAPDIS characteristic
ZDRDIR 21D Directional impedance quadrilateral 0-2
ZMCPDIS, 21 Distance measuring zone, quadrilateral 0-5
ZMCAPDIS characteristic for series compensated lines
ZDSRDIR 21D Directional impedance quadrilateral, including 0-2
series compensation
FDPSPDIS 21 Phase selection, quadrilateral characteristic 0-2
with fixed angle
ZMHPDIS 21 Full-scheme distance protection, mho 0-5
characteristic
Table continues on next page
RET670 (A10)
RET670 (B30)
RET670 (B40)
RET670 (A25)
RET670
(Customized)
RET670 (A10)
RET670 (B30)
RET670 (B40)
RET670 (A25)
RET670
(Customized)
Current protection
PHPIOC 50 Instantaneous phase overcurrent protection 0-8 3 2 3 2-C19
OC4PTOC 51_671) Directional phase overcurrent protection, 0-8 3 2 3 2-C19
four steps
EFPIOC 50N Instantaneous residual overcurrent 0-8 3 2 3 2-C19
protection
EF4PTOC 51N_67N Directional residual overcurrent protection, 0-8 3 3 3 2-C19
four steps
NS4PTOC 46I2 Directional negative phase sequence 0-8 2-C42 2-C42 3-C43 2-C19
overcurrent protection, four steps
SDEPSDE 67N Sensitive directional residual overcurrent 0-3 1 1-C16 1-C16 1-C16
and power protection
LCPTTR 26 Thermal overload protection, one time 0-2
constant, Celsius
LFPTTR 26 Thermal overload protection, one time 0-2
constant, Fahrenheit
TRPTTR 49 Thermal overload protection, two time 0-6 1 1B 2B
constants 1-C05 1-C05
CCRBRF 50BF Breaker failure protection 0-6 3 4 6
STBPTOC 50STB Stub protection 0-3 3-B26 3-B26 3-B26
CCPDSC 52PD Pole discordance protection 0-6 3 4 6
GUPPDUP 37 Directional underpower protection 0-2 1-C35 1-C35 1-C35
GOPPDOP 32 Directional overpower protection 0-2 1-C35 1-C35 1-C35
BRCPTOC 46 Broken conductor check 1 1 1 1 1
CBPGAPC Capacitor bank protection 0-6
NS2PTOC 46I2 Negative sequence time overcurrent 0-2
protection for machines, two steps
VRPVOC 51V Voltage restrained overcurrent protection 0-3 1-C35 1-C35 1-C35
APPTEF 67NT Average power transient earth fault 0-2 1-C54 1-C54 1-C54
protection
BRPTOC 50 Overcurrent protection with binary release 0-8 3 2 3 2-C19
Voltage protection
UV2PTUV 27 Two step undervoltage protection 0-3 1-D01 1B 1B 2-D02
1-D01 2-D02
OV2PTOV 59 Two step overvoltage protection 0-3 1-D01 1B 1B 2-D02
1-D01 2-D02
Table continues on next page
RET670 (A10)
RET670 (B30)
RET670 (B40)
RET670 (A25)
RET670
(Customized)
ROV2PTOV 59N Residual overvoltage protection, two steps 0-4 1-D01 1B 1B 2-D02
1-D01 2-D02
OEXPVPH 24 Overexcitation protection 0-2 2-D04 1-D03 2-D04
VDCPTOV 60 Voltage differential protection 0-2 2 2 2 2
LOVPTUV 27 Loss of voltage check 1 1 1 1 1
Unbalance protection
SCCFPVOC 51V Cascading failure protection for shunt 0-3
capacitor bank
SCUCPTOC 60N Current unbalance protection for shunt 0-3
capacitor bank
SCPDPTOV 87V Phase voltage differential based capacitor 0-3
bank unbalanced protection
SCUVPTOV 60V Voltage unbalance protection for shunt 0-3
capacitor bank
Frequency protection
SAPTUF 81 Underfrequency protection 0-10 6-E01 6-E01 6-E01
SAPTOF 81 Overfrequency protection 0-6 6-E01 6-E01 6-E01
SAPFRC 81 Rate-of-change of frequency protection 0-6 6-E01 6-E01 6-E01
Multipurpose protection
CVGAPC General current and voltage protection 0-9 6-F02 6-F02
General calculation
SMAIHPAC Multipurpose filter 0-6
1) 67 requires voltage
RET670 (B30)
RET670 (B40)
RET670 (A25)
RET670
(Customized)
Control
SESRSYN 25 Synchrocheck, energizing check and 0-6 1 1B 1B
synchronizing 2-H01 4-H03
SMBRREC 79 Autorecloser 1
Table continues on next page
RET670 (A10)
RET670 (B30)
RET670 (B40)
RET670 (A25)
RET670
(Customized)
APC30 3 Control functionality for up to 6 bays, max 30 0-1 1-H39 1-H39 1-H39
objects (6CBs), including interlocking (see
Table 4)
QCBAY Bay control 1+5/APC30 1 1+5/ 1+5/ 1+5/
APC30 APC30 APC30
LOCREM Handling of LR-switch positions 1+5/APC30 1 1+5/ 1+5/ 1+5/
APC30 APC30 APC30
LOCREMCTRL LHMI control of PSTO 1 1 1 1 1
SXCBR Circuit breaker 18 12 18 18 18
TR1ATCC 90 Automatic voltage control for tap changer, 0-4 1 2 2B
single control 2-H16
TR8ATCC 90 Automatic voltage control for tap changer, 0-4 1-H15 1-H15 2B
parallel control 2-H18 2-H18
TCMYLTC 84 Tap changer control and supervision, 6 binary 0-4 4 4 4
inputs
TCLYLTC 84 Tap changer control and supervision, 32 binary 0-4 4 4 4
inputs
SLGAPC Logic rotating switch for function selection and 15 15 15 15 15
LHMI presentation
VSGAPC Selector mini switch 30 30 30 30 30
DPGAPC Generic communication function for Double 32 32 32 32 32
Point indication
SPC8GAPC Single point generic control function, 8 signals 5 5 5 5 5
AUTOBITS Automation bits, command function for DNP3.0 3 3 3 3 3
SINGLECMD Single command, 16 signals 8 8 8 8 8
I103CMD Function commands for 1 1 1 1 1
IEC 60870-5-103
I103GENCMD Function commands generic for 50 50 50 50 50
IEC 60870-5-103
I103POSCMD IED commands with position and select for 50 50 50 50 50
IEC 60870-5-103
I103POSCMDV IED direct commands with position for 50 50 50 50 50
IEC 60870-5-103
I103IEDCMD IED commands for 1 1 1 1 1
IEC 60870-5-103
I103USRCMD Function commands user defined for 4 4 4 4 4
IEC 60870-5-103
Secondary
system
supervision
CCSSPVC 87 Current circuit supervision 0-6 4 6 4
FUFSPVC Fuse failure supervision 0-4 1 3 3
VDSPVC 60 Fuse failure supervision based on voltage 0-2 1-G03 1-G03 1-G03 1-G03
difference
Table continues on next page
RET670 (A10)
RET670 (B30)
RET670 (B40)
RET670 (A25)
RET670
(Customized)
RET670 (A10)
RET670 (B30)
RET670 (B40)
RET670 (A25)
RET670
(Customized)
RET670 (A10)
RET670 (B30)
RET670 (B40)
RET670 (A25)
RET670
(Customized)
Monitoring
CVMMXN Power system measurement 6 6 6 6 6
CMMXU Current measurement 10 10 10 10 10
VMMXU Voltage measurement phase-phase 6 6 6 6 6
CMSQI Current sequence measurement 6 6 6 6 6
VMSQI Voltage sequence measurement 6 6 6 6 6
VNMMXU Voltage measurement phase-earth 6 6 6 6 6
AISVBAS General service value presentation of analog 1 1 1 1 1
inputs
EVENT Event function 20 20 20 20 20
DRPRDRE, Disturbance report 1 1 1 1 1
A1RADR-
A4RADR,
B1RBDR-
B22RBDR
SPGAPC Generic communication function for single point 96 96 96 96 96
indication
SP16GAPC Generic communication function for single point 16 16 16 16 16
indication, 16 inputs
MVGAPC Generic communication function for measured 60 60 60 60 60
values
BINSTATREP Logical signal status report 3 3 3 3 3
Table continues on next page
RET670 (A10)
RET670 (B30)
RET670 (B40)
RET670 (A25)
RET670
(Customized)
RET670 (B30)
RET670 (B40)
RET670 (A25)
RET670
(Customized)
Station communication
ADE LON communication protocol 1 1 1 1 1
HORZCOMM Network variables via LON 1 1 1 1 1
PROTOCOL Operation selection between SPA and 1 1 1 1 1
IEC60870-5-103 for SLM
RS485PROT Operation selection for RS485 1 1 1 1 1
RS485GEN RS485 1 1 1 1 1
DNPGEN DNP3.0 communication general protocol 1 1 1 1 1
CHSERRS485 DNP3.0 for EIA-485 communication protocol 1 1 1 1 1
CH1TCP, CH2TCP, DNP3.0 for TCP/IP communication protocol 1 1 1 1 1
CH3TCP, CH4TCP
CHSEROPT DNP3.0 for TCP/IP and EIA-485 1 1 1 1 1
communication protocol
MSTSER DNP3.0 serial master 1 1 1 1 1
Table continues on next page
RET670 (A10)
RET670 (B30)
RET670 (B40)
RET670 (A25)
RET670
(Customized)
RET670 (A10)
RET670 (B30)
RET670 (B40)
RET670 (A25)
RET670
(Customized)
PMUCONF Synchrophasor report, 24 phasors (see Table 0-1 1-P33 1-P33 1-P33 1-P33
PMUREPORT 7)
PHASORREPORT1
PHASORREPORT2
PHASORREPORT3
ANALOGREPORT1
BINARYREPORT1
SMAI1 - SMAI12
3PHSUM
PMUSTATUS
AP_1-AP_6 AccessPoint_ABS 1 1 1 1 1
AP_FRONT Access point front 1 1 1 1 1
PTP Precision time protocol 1 1 1 1 1
ROUTE_1-ROUTE_6 Route_ABS 1 1 1 1 1
FRONTSTATUS Access point diagnostic for front Ethernet port 1 1 1 1 1
SCHLCCH Access point diagnostic for non-redundant 6 6 6 6 6
Ethernet port
RCHLCCH Access point diagnostic for redundant 3 3 3 3 3
Ethernet ports
DHCP DHCP configuration for front access point 1 1 1 1 1
QUALEXP IEC 61850 quality expander 96 96 96 96 96
Remote communication
BinSignRec1_1 Binary signal transfer, receive 3/3/6 3/3/6 3/3/6 3/3/6 3/3/6
BinSignRec1_2
BinSignReceive2
BinSignTrans1_1 Binary signal transfer, transmit 3/3/6 3/3/6 3/3/6 3/3/6 3/3/6
BinSignTrans1_2
BinSignTransm2
BSR2M_305 Binary signal transfer, 2Mbit receive 1 1 1 1 1
BSR2M_312
BSR2M_322
BSR2M_306
BSR2M_313
BSR2M_323
BST2M_305 Binary signal transfer, 2Mbit transmit 1 1 1 1 1
BST2M_312
BST2M_322
BST2M_306
BST2M_313
BST2M_323
LDCMTRN Transmission of analog data from LDCM 1 1 1 1 1
LDCMTRN_2M_305 Transmission of analog data from LDCM, 1 1 1 1 1
LDCMTRN_2M_306 2Mbit
LDCMTRN_2M_312
LDCMTRN_2M_313
LDCMTRN_2M_322
LDCMTRN_2M_323
LDCMRecBinStat1 Receive binary status from remote LDCM 6/3 6/3 6/3 6/3 6/3
LDCMRecBinStat3
LDCMRecBinStat2 Receive binary status from LDCM 3 3 3 3 3
Table continues on next page
RET670 (A10)
RET670 (B30)
RET670 (B40)
RET670 (A25)
RET670
(Customized)
Analog input channels must be configured and set properly in order to get correct measurement
results and correct protection operations. For power measuring, all directional and differential
functions, the directions of the input currents must be defined in order to reflect the way the current
transformers are installed/connected in the field ( primary and secondary connections ). Measuring
and protection algorithms in the IED use primary system quantities. Setting values are in primary
quantities as well and it is important to set the data about the connected current and voltage
transformers properly.
An AISVBAS reference PhaseAngleRef can be defined to facilitate service values reading. This
analog channel's phase angle will always be fixed to zero degrees and remaining analog channel's
phase angle information will be shown in relation to this analog input. During testing and
commissioning of the IED, the reference channel can be changed to facilitate testing and service
values reading.
The IED has the ability to receive analog values from primary equipment, that are
sampled by Merging units (MU) connected to a process bus, via the IEC 61850-9-2
LE protocol.
The hardware channels appear in the signal matrix tool (SMT) and in ACT when a
TRM is included in the configuration with the hardware configuration tool. In the SMT
or the ACT, they can be mapped to the desired virtual input (SMAI) of the IED and
used internally in the configuration.
3.3 Signals
PID-3920-OUTPUTSIGNALS v6
PID-3921-OUTPUTSIGNALS v7
PID-3922-OUTPUTSIGNALS v6
PID-3923-OUTPUTSIGNALS v7
PID-3924-OUTPUTSIGNALS v7
PID-6598-OUTPUTSIGNALS v6
3.4 Settings
SEMOD129840-4 v2
Dependent on ordered IED type.
PID-4153-SETTINGS v8
PID-3920-SETTINGS v7
PID-3921-SETTINGS v7
PID-3922-SETTINGS v7
PID-3923-SETTINGS v7
PID-3924-SETTINGS v7
PID-6598-SETTINGS v6
PID-3920-MONITOREDDATA v6
PID-3921-MONITOREDDATA v6
PID-3922-MONITOREDDATA v6
PID-3923-MONITOREDDATA v6
PID-3924-MONITOREDDATA v6
PID-6598-MONITOREDDATA v6
The direction of a measured current depends on the connection of the CT. The main CTs are typically
star connected and can be connected with the star point towards the object or away from the object.
This information must be set in the IED.
Once the CT direction settings is correctly entered the internal IED convention of the directionality is
defined as follows:
• Positive value of current or power means that the quantity has the direction into the protected
object.
• Negative value of current or power means that the quantity has the direction out from the
protected object.
For directional functions the directional conventions are defined as follows (see Figure 5)
en05000456.vsd
IEC05000456 V1 EN-US
The settings of the IED is performed in primary values. The ratios of the main CTs and VTs are,
therefore, basic data for the IED. The user has to set the rated secondary and primary currents and
voltages of the CTs and VTs to provide the IED with their rated ratios.
The CT and VT ratio and the name on respective channel is done under Main menu /Hardware /
Analog modules in the Parameter Settings tool or on the HMI.
M16988-1 v11
Table 30: TRM - Energizing quantities, rated values and limits for protection transformer
Description Value
Frequency
Rated frequency fr 50/60 Hz
Current inputs
Rated current Ir 1 or 5 A
Description Value
Dynamic withstand 250 × Ir one half wave
Table 31: TRM - Energizing quantities, rated values and limits for measuring transformer
Description Value
Frequency
Rated frequency fr 50/60 Hz
Current inputs
Rated current Ir 1A 5A
Voltage inputs *)
Rated voltage Ur 110 or 220 V
SEMOD53376-2 v6
The debounce filter eliminates bounces and short disturbances on a binary input.
A time counter is used for filtering. The time counter is increased once in a millisecond when a binary
input is high, or decreased when a binary input is low. A new debounced binary input signal is
forwarded when the time counter reaches the set DebounceTime value and the debounced input
value is high or when the time counter reaches 0 and the debounced input value is low. The default
setting of DebounceTime is 1 ms.
The binary input ON-event gets the time stamp of the first rising edge, after which the counter does
not reach 0 again. The same happens when the signal goes down to 0 again.
Binary input wiring can be very long in substations and there are electromagnetic fields from for
example nearby breakers. An oscillation filter is used to reduce the disturbance from the system
when a binary input starts oscillating.
An oscillation counter counts the debounced signal state changes during 1 s. If the counter value is
greater than the set value OscBlock, the input signal is blocked. The input signal is ignored until the
oscillation counter value during 1 s is below the set value OscRelease.
4.1.3 Settings
GUID-07348953-4A72-444B-A31A-030ABEA8E0C4 v1
OscBlock must always be set to a value greater than OscRelease. If this is not done,
oscillation detection will not function correctly, and the resulting behaviour will be
undefined.
5.1.1 Identification
GUID-84392EFF-4D3F-4A67-A6ED-34C6E98574D6 v1
5.1.2 Settings
PID-7235-SETTINGS v1
5.2.1 Identification
GUID-03AB7AEE-87D3-4F3C-B6B9-B1EB1B538E38 v1
LHMICTRL
CLRLEDS HMI-ON
RED-S
YELLOW-S
YELLOW-F
CLRPULSE
LEDSCLRD
IEC09000320-1-en.vsd
IEC09000320 V1 EN-US
5.2.3 Signals
PID-3992-INPUTSIGNALS v6
PID-3992-OUTPUTSIGNALS v6
5.3.1 Identification
GUID-6E36C0BC-F284-4C88-A4A8-9535D3BE8B14 v2
GRP2_LED1 -
GRP2_LED15
GRP3_LED1 -
GRP3_LED15
LEDGEN
BLOCK NEWIND
RESET ACK
IEC09000321-1-en.vsd
IEC09000321 V1 EN-US
GRP1_LED1
^HM1L01R
^HM1L01Y
^HM1L01G
IEC09000322 V1 EN-US
5.3.3 Signals
PID-4114-INPUTSIGNALS v5
PID-4114-OUTPUTSIGNALS v5
PID-1697-INPUTSIGNALS v18
5.3.4 Settings
PID-4114-SETTINGS v6
PID-1697-SETTINGS v18
5.4 LCD part for HMI function keys control module GUID-EECAE7FA-7078-472C-A429-F7607DB884EB v2
5.4.1 Identification
GUID-E6611022-5EA3-420D-ADCD-9D1E7604EFEB v1
FNKEYMD1
ENABLE ^FKEYOUT1
^LEDCTL1
IEC09000327 V2 EN-US
5.4.3 Signals
PID-7424-INPUTSIGNALS v1
PID-7424-OUTPUTSIGNALS v1
5.4.4 Settings
PID-7424-SETTINGS v1
PID-7606-SETTINGS v1
GUID-BCE87D54-C836-40EE-8DA7-779B767059AB v2
For setting ReqAuthority, when users are configured through local or central account
management, the default behavior of the function keys are to only operate if a user is
logged in, and the user have the required rights. This authentication check can be
configured to be bypassed per function key by changing the ReqAuthority from ON
to OFF. To be able to change this, the user changing it have to have the Security
advanced right.
MenuShortcut values are product dependent and created dynamically depending on the product
main menu.
IEC13000239-3-en.vsd
IEC13000239 V3 EN-US
• Keypad
• Display (LCD)
• LED indicators
• Communication port for PCM600
The LHMI keypad contains push-buttons which are used to navigate in different views or menus. The
push-buttons are also used to acknowledge alarms, reset indications, provide help and switch
between local and remote control mode.
The keypad also contains programmable push-buttons that can be configured either as menu
shortcut or control buttons.
24
1
23
2
18
3
19
4
6 20
21
7 22
8 9 10 11 12 13 14 15 16 17
IEC15000157-2-en.vsd
IEC15000157 V2 EN-US
Figure 11: LHMI keypad with object control, navigation and command push-buttons and
RJ-45 communication port
22 Communication port
23 Programmable indication LEDs
24 IED status LEDs
The LHMI includes a graphical monochrome liquid crystal display (LCD) with a resolution of 320 x
240 pixels. The character size can vary. The amount of characters and rows fitting the view depends
on the character size and the view that is shown.
IEC15000270-1-en.vsdx
IEC15000270 V1 EN-US
1 Path
2 Content
3 Status
4 Scroll bar (appears when needed)
• The path shows the current location in the menu structure. If the path is too long to be shown, it
is truncated from the beginning, and the truncation is indicated with three dots.
• The content area shows the menu content.
• The status area shows the current IED time, the user that is currently logged in and the object
identification string which is settable via the LHMI or with PCM600.
• If text, pictures or other items do not fit in the display, a vertical scroll bar appears on the right.
The text in content area is truncated from the beginning if it does not fit in the display
horizontally. Truncation is indicated with three dots.
IEC15000138-1-en.vsdx
IEC15000138 V1 EN-US
The function key button panel shows on request what actions are possible with the function buttons.
Each function button has a LED indication that can be used as a feedback signal for the function
button control action. The LED is connected to the required signal with PCM600.
IEC13000281-1-en.vsd
GUID-C98D972D-D1D8-4734-B419-161DBC0DC97B V1 EN-US
IEC13000240-1-en.vsd
GUID-5157100F-E8C0-4FAB-B979-FD4A971475E3 V1 EN-US
The LHMI includes three status LEDs above the display: Ready, Start and Trip.
There are 15 programmable indication LEDs on the front of the LHMI. Each LED can indicate three
states with the colors: green, yellow and red. The texts related to each three-color LED are divided
into three panels.
There are 3 separate panels of LEDs available. The 15 physical three-color LEDs in one LED group
can indicate 45 different signals. Altogether, 135 signals can be indicated since there are three LED
groups. The LEDs are lit according to priority, with red being the highest and green the lowest priority.
For example, if on one panel there is an indication that requires the green LED to be lit, and on
another panel there is an indication that requires the red LED to be lit, the red LED takes priority and
is lit. The LEDs can be configured with PCM600 and the operation mode can be selected with the
LHMI or PCM600.
Information panels for the indication LEDs are shown by pressing the Multipage button. Pressing that
button cycles through the three pages. A lit or un-acknowledged LED is indicated with a highlight.
Such lines can be selected by using the Up/Down arrow buttons. Pressing the Enter key shows
details about the selected LED. Pressing the ESC button exits from information pop-ups as well as
from the LED panel as such.
The Multipage button has a LED. This LED is lit whenever any LED on any panel is lit. If there are
un-acknowledged indication LEDs, then the Multipage LED blinks. To acknowledge LEDs, press the
Clear button to enter the Reset menu (refer to description of this menu for details).
There are two additional LEDs which are next to the control buttons and . These LEDs can
indicate the status of two arbitrary binary signals by configuring the OPENCLOSE_LED function
block. For instance, OPENCLOSE_LED can be connected to a circuit breaker to indicate the breaker
open/close status on the LEDs.
IEC16000076-1-en.vsd
IEC16000076 V1 EN-US
The function blocks LEDGEN and GRP1_LEDx, GRP2_LEDx and GRP3_LEDx (x=1-15) controls
and supplies information about the status of the indication LEDs. The input and output signals of the
function blocks are configured with PCM600. The input signal for each LED is selected individually
using SMT or ACT. Each LED is controlled by the GRPn_LEDx (n=1-3) function block that controls
the color and the operating mode.
Each indication LED on local HMI can be set individually to operate in 6 different sequences; two as
follow type and four as latch type. Two of the latching sequence types are intended to be used as a
protection indication system, either in collecting or restarting mode, with reset functionality. The other
two are intended to be used as signalling system in collecting mode with acknowledgment
functionality.
There are three status LEDs above the LCD in front of the IED: green, yellow and red.
The green LED has a fixed function that presents the healthy status of the IED. The yellow and red
LEDs are user configured. The yellow LED can be used to indicate that a disturbance report is
triggered (steady) or that the IED is in test mode (flashing). The red LED can be used to indicate a
trip command.
• Green LED: unlit > no power; blinking > startup or abnormal situation (IED is not in service);
steady > IED is in service
• Yellow LED: unlit > no attention required; blinking > IED is in Testmode (IED is not in normal
service); steady > at least one of the signals configured to turn the yellow LED on has been
active
• Red LED: unlit > no attention required; blinking > user performs a common write from PCM600;
steady > at least one of the signals configured to turn the red LED on has been active
The yellow and red status LEDs are configured in the disturbance recorder function, DRPRDRE, by
connecting a start or trip signal from the actual function to a BxRBDR binary input function block
using the PCM600, and configuring the setting to Off, Start or Trip for that particular signal.
Collecting mode
• LEDs that are used in the collecting mode of operation are accumulated continuously until the
unit is acknowledged manually. This mode is suitable when the LEDs are used as a simplified
alarm system. When all three inputs (red, yellow and green) are connected to different sources
of events for the same function block, collecting mode shows the highest priority LED color that
was activated since the latest acknowledgment was made. If a number of different indications
were made since the latest acknowledgment, it is not possible to get a clear view of what
triggered the latest event without looking at the sequence of events list. A condition for getting
the sequence of events is that the signals have been engineered in the disturbance recorder.
Re-starting mode
• In the re-starting mode of operation each new start resets all previous active LEDs and activates
only those which appear during one disturbance. Only LEDs defined for re-starting mode with
the latched sequence type 6 (LatchedReset-S) will initiate a reset and a restart at a new
disturbance. A disturbance is defined to end a settable time after the reset of the activated input
signals or when the maximum time limit has elapsed. In sequence 6, the restarting or reset
mode means that upon occurrence of any new event, all previous indications will be reset. This
facilitates that only the LED indications related to the latest event is shown.
Acknowledgment/reset GUID-E6727E8F-C28B-4295-AE21-BC5643363805 v3
• Automatic reset
• The automatic reset can only be performed for LED indications defined for re-starting
mode with the latched sequence type 6 (LatchedReset-S). When the automatic reset of
the LEDs has been performed, still persisting indications will be indicated with a steady
light.
The figures below show the function of available sequences selectable for each LED separately. The
following 6 sequences are available:
• Sequence 1: Follow-S
• Sequence 2: Follow-F
• Sequence 3: LatchedAck-F-S
• Sequence 4: LatchedAck-S-F
• Sequence 5: LatchedColl-S
• Sequence 6: LatchedReset-S
For sequence 1 and 2, which are of the Follow type, the acknowledgment (Ack ) /reset function is not
applicable because the indication shown by the LED follows its input signal. Sequence 3 and 4,
which are of the Latched type with acknowledgement, are only working in collecting (Coll) mode.
Sequence 5 is working according to Latched type and collecting mode while Sequence 6 is working
according to Latched type and re-starting (Reset) mode. The letters S and F in the sequence names
have the meaning S = Steady and F = Flash.
At the activation of the input signal to any LED, the indication on the corresponding LED obtains a
color that corresponds to the activated input, and operates according to the selected sequence
diagrams shown below.
In the sequence diagrams the different statuses of the LEDs are shown using the following symbols:
Activating
signal
LED
IEC01000228_2_en.vsd
IEC01000228 V2 EN-US
Activating
signal GREEN
Activating
signal RED
LED G G R G
IEC09000312_1_en.vsd
IEC09000312 V1 EN-US
Activating
signal
LED
Acknow.
en01000231.vsd
IEC01000231 V1 EN-US
The sequence described below is valid only if the same function block is used for all
three colour LEDs.
When an acknowledgment is performed, all indications that appear before the indication with higher
priority has been reset, will be acknowledged, independent of if the low priority indication appeared
before or after acknowledgment. In figure 21 it is shown the sequence when a signal of lower priority
becomes activated after acknowledgment has been performed on a higher priority signal. The low
priority signal will be shown as acknowledged when the high priority signal resets.
Activating
signal GREEN
Activating
signal RED
R R G
LED
Acknow
IEC09000313_1_en.vsd
IEC09000313 V1 EN-US
Activating
signal GREEN
Activating
signal YELLOW
Activating
signal RED
LED G Y R R Y
Acknow.
IEC09000314-1-en.vsd
IEC09000314 V1 EN-US
Activating
signal GREEN
Activating
signal YELLOW
Activating
signal RED
LED G G R R Y
Acknow.
IEC09000315-1-en.vsd
IEC09000315 V1 EN-US
Activating
signal
LED
Reset
IEC01000235_2_en.vsd
IEC01000235 V2 EN-US
Activating
signal GREEN
Activating
signal RED
R G
LED
Reset
IEC09000316_1_en.vsd
IEC09000316 V1 EN-US
Disturbance
tRestart
Activating
signal 1
Activating
signal 2
LED 1
LED 2
Automatic
reset
Manual
reset
IEC01000239_2-en.vsd
IEC01000239 V2 EN-US
Figure 26: Operating sequence 6 (LatchedReset-S), two indications within same disturbance
Figure 27 shows the timing diagram for a new indication after tRestart time has elapsed.
Disturbance Disturbance
tRestart tRestart
Activating
signal 1
Activating
signal 2
LED 1
LED 2
Automatic
reset
Manual
reset
IEC01000240_2_en.vsd
IEC01000240 V2 EN-US
Disturbance
tRestart
Activating
signal 1
Activating
signal 2
LED 1
LED 2
Automatic
reset
Manual
reset
IEC01000241_2_en.vsd
IEC01000241 V2 EN-US
Figure 28: Operating sequence 6 (LatchedReset-S), two indications within same disturbance
but with reset of activating signal between
Figure 29 shows the timing diagram for manual reset.
Disturbance
tRestart
Activating
signal 1
Activating
signal 2
LED 1
LED 2
Automatic
reset
Manual
reset
IEC01000242_2_en.vsd
IEC01000242 V2 EN-US
Local Human-Machine-Interface (LHMI) has five function buttons, directly to the left of the LCD, that
can be configured either as menu shortcut or control buttons. Each button has an indication LED that
can be configured in the application configuration.
When used as a menu shortcut, a function button provides a fast way to navigate between default
nodes in the menu tree. When used as a control, the button can control a binary signal.
Each output on the FNKEYMD1 - FNKEYMD5 function blocks can be controlled from the LHMI
function keys. By pressing a function button on the LHMI, the output status of the actual function
block will change. These binary outputs can in turn be used to control other function blocks, for
example, switch control blocks, binary I/O outputs etc.
FNKEYMD1 - FNKEYMD5 function block also has a number of settings and parameters that control
the behavior of the function block. These settings and parameters are normally set using the PST.
Setting OFF
Input value
Output value
IEC09000330-2-en.vsd
IEC09000330 V2 EN-US
In this mode the output toggles each time the function key has been pressed for more than 500ms.
Note that the input attribute is reset each time the function block executes. The function block
execution is marked with a dotted line below.
Input value
500ms 500ms 500ms
Output value
IEC09000331_1_en.vsd
IEC09000331 V2 EN-US
In this mode the output sets high (1) when the function key has been pressed for more than 500ms
and remains high according to set pulse time. After this time the output will go back to 0. The input
attribute is reset when the function block detects it being high and there is no output pulse.
Note that the third positive edge on the input attribute does not cause a pulse, since the edge was
applied during pulse output. A new pulse can only begin when the output is zero; else the trigger
edge is lost.
Input value
500ms 500ms 500ms 500ms
IEC09000332_2_en.vsd
IEC09000332 V2 EN-US
When users are configured through local or central account management, the default behavior of the
function keys are to only operate if a user is logged in, and the user have the required rights. This
authentication check can be configured to be bypassed per function key by changing the
ReqAuthority from ON to OFF. To be able to change this, the user changing it have to have the
Security advanced right.
Authority can be disabled using parameter Authority. Each function key has the parameter Authority,
which can be enabled or disabled using LHMI or PCM 600. User must have Security Advanced rights
to configure the Authority parameter of the function key.
6.1.1 Identification
GUID-1E140EA0-D198-443A-B445-47CEFD2E6134 v2
PMUCONF contains the PMU configuration parameters for both IEC/IEEE 60255-118 (C37.118) and
IEEE 1344 protocols. This means all the required settings and parameters in order to establish and
define a number of TCP and/or UDP connections with one or more PDC clients (synchrophasor
client). This includes port numbers, TCP/UDP IP addresses, and specific settings for IEC/IEEE
60255-118 (C37.118) as well as IEEE 1344 protocols.
The Figure 33 demonstrates the communication configuration diagram. As can be seen, the IED can
support communication with maximum 8 TCP clients and 6 UDP client groups, simultaneously. Every
client can communicate with only one instance of the two available PMUREPORT function block
instances at a time. It means that one client cannot communicate with both PMUREPORT:1 and
PMUREPORT:2 at the same time. However, multiple clients can communicate with the same
instance of PMUREPORT function block at the same time. For TCP clients, each client can decide to
communicate with an existing instance of PMUREPORT by knowing the corresponding PMU ID for
that PMUREPORT instance. Whereas, for UDP clients, the PMUREPORT instance for each UDP
channel is defined by the user in the PMU and the client has to know the PMU ID corresponding to
that instance in order to be able to communicate. More information is available in the sections Short
guidance for the use of TCP and Short guidance for the use of UDP.
IED
PMU ID
1344/C37.118
PMUREPORT: 1 PMUREPORT: 2 TCP Client_1
1344/C37.118
TCP Client_2
1344/C37.118
TCP Client_3
PMU ID: X
1344/C37.118
TCP IP TCP Client_4
PMU ID: Y 1344/C37.118
TCP Port TCP Client_5
1344/C37.118 TCP Client_6
1344/C37.118 TCP Client_7
1344/C37.118 TCP Client_8
PMU ID
IEC140000117-1.en.vsd
IEC140000117 V2 EN-US
Four message types are defined in IEEE C37.118 standard: data, configuration, header, and
command frames. The first three message types are transmitted from the PMU/PDC that serves as
the data source, and the last one (command frame) is received by the PMU/PDC.
These four message types are defined in IEEE C37.118 standard as follows:
There is a default header file, named "ieee1344header.txt", located in the "tools" folder in the IED.
The user is allowed to access and update this text file and write it back to the IED using a FTP client
(e.g. Filezilla).
If the user-defined (updated) header file is larger than 1400 bytes, then it will be truncated to 1400
bytes in both IEEE C37.118 and IEEE1344 protocols.
Both PMU reporting instances are using the same header file (ieee1344header.txt) and this header
file is used for both IEEE C37.118 and IEEE1344 protocols.
• Commands are machine-readable codes sent to the PMU/PDC for control or configuration.
Port 7001 is used by the SPA on TCP/IP (field service tool). If the port is used for any
other protocol, for example C37.118, the SPA on TCP/IP stops working.
The IED supports 8 concurrent TCP connections using IEEE1344 and/or C37.118 protocol. The
following parameters are used to define the TCP connection between the IED and the TCP clients:
1. 1344TCPport– TCP port for control of IEEE 1344 data for TCP clients
2. C37.118TCPport – TCP port for control of IEEE C37.118 data for TCP clients
As can be seen, there are two separate parameters in the IED for selecting port numbers for TCP
connections; one for IEEE1344 protocol (1344TCPport) and another one for C37.118 protocol
(C37.118 TCPport). Client can communicate with the IED over IEEE1344 protocol using the selected
TCP port defined in 1344TCPport, and can communicate with the IED over IEEE C37.118 protocol
using the selected TCP port number in C37.118TCPport.
All the frames (the header frame, configuration frame, command frame and data frame) are
communicated over the same TCP port. The client can request (by sending a command frame) a
configuration and/or header via the TCP channel and the requested configuration and/or header will
be sent back to the client (as Configuration frame/Header frame) over the same TCP channel.
Once the TCP client connects to the IED, the client has to necessarily send a command frame to
start a communication. As shown in Figure 33, the IED can support 2 PMUREPORT instances and
the client has to specify the PMU ID Code in order to know which PMUREPORT data needs to be
sent out to that client. In this figure, X and Y are referring to the user-defined PMU ID Codes for
PMUREPORT instances 1 or 2, respectively. It is up to the TCP client to decide which PMUREPORT
function block shall communicate with that client. Upon successful reception of the first command by
the IED, the PMU ID will be extracted out of the command; if there is a PMUREPORT instance
configured in the IED with matching PMU ID, then the client connection over TCP with the IED will be
established and further communication will take place. Otherwise, the connection will be terminated
and the TCPCtrlCfgErrCnt is incremented in the PMU Diagnostics on the Local HMI under Main
menu /Diagnostics /Communication /PMU diagnostics /PMUSTATUS:1
It is possible to turn off/on the TCP data communication by sending a IEEE1344 or C37.118
command frame remotely from the client to the PMU containing RTDOFF/RTDON command.
At any given point of time maximum of 8 TCP clients can be connected to the IED for IEEE1344/
C37.118 protocol. If there is an attempt made by the 9th client, the connection to the new client will
be terminated without influencing the connection of the other clients already connected. A list of
active clients can be seen on the Local HMI in the diagnostics menu under Main menu /
Diagnostics /Communication /PMU diagnostics /PMUSTATUS:1
The IED supports maximum of 6 concurrent UDP streams. They can be individually configured to
send IEEE1344 or C37.118 data frames as unicast / multicast. Note that [x] at the end of each
parameter is referring to the UDP stream number (UDP client group) and is a number between 1 and
6. Each of the 6 UDP groups in the IED has the following settings:
It is possible to turn off/on the UDP data communication either by setting the parameter
SendDataUDP[x] to Off/On locally in the PMU or by sending a C37.118 or IEEE1344 command
frame (RTDOFF/RTDON) remotely from the client to the PMU as defined in IEEE 1344/C37.118
standard.
However, such a remote control to stop the streams from the client is only possible when the
parameter SendDataUDP[x] is set to SetByProtocol. The command RTDOFF/RTDON sent by the
client is stored in the IED, i.e. if the IED is rebooted for some reason, the state of the stream will
remain the same.
If the parameter SendDataUDP[x] is set toOn the RTDOFF/RTDON commands received from the
clients are ignored in the IED.
The UDP implementation in the IED is a UDP_TCP. This means that by default, only the data frames
are sent out on UDP stream and the header frame, configuration frame and command frame are sent
over TCP. This makes the communication more reliable especially since commands are sent over
TCP which performs request/acknowledgment exchange to ensure that no data (command in this
case) is lost.
However, by setting the parameter SendCfgOnUDP[x] to On, the configuration frame 2 (CFG-2) of
IEEEC37.118 data stream is cyclically sent on the corresponding UDP stream (UDP client group[x])
once per minute. This is useful in case of multicast UDP data stream when a lot of PMU clients are
receiving the same UDP stream from the same UDP group (UDP client group[x]).
As shown in Figure 33, there are maximum 2 instances of PMUREPORT function blocks available in
the IED. Each UDP client group[x] can only connect to one of the PMUREPORT instances at the
same time. This is defined in the PMU by the parameter PMUReportUDP[x] which is used to define
the instance number of PMUREPORT function block that must send data on this UDP stream (UDP
client group[x]).
The data streams in the IED can be sent as unicast or as multicast. The user-defined IP address set
in the parameter UDPDestAddress[x] for each UDP stream defines if it is a Unicast or Multicast. The
address range 224.0.0.0 to 239.255.255.255 (Class D IP addresses) is treated as multicast. Any
other IP address outside this range is treated as unicast and the UDP data will be only sent to that
specific unicast IP address. In addition to UDPDestAddress[x] parameter, UDPDestPort[x] parameter
is used to define the UDP destination port number for UDP client group[x].
In case of multicast IP, it will be the network switches and routers that take care of replicating the
packet to reach multiple receivers. Multicast mechanism uses network infrastructure efficiently by
requiring the IED to send a packet only once, even if it needs to be delivered to a large number of
receivers.
If there are more than one UDP client group defined as multicast, the user shall set different multicast
IP addresses for each UDP group.
The PMU clients receiving the UDP frames can also connect to the IED to request (command frame)
config frame 1, config frame 2, config frame 3, or header frame, and to disable/enable real time data.
This can be done by connecting to the TCP port selected in TCPportUDPdataCtrl[x] for each UDP
group. This connection is done using TCP. The IED allows 4 concurrent client connections for every
TCPportUDPdataCtrl[x] port (for each UDP client group[x]).
If the client tries to connect on TCPportUDPdataCtrl[x] port using a PMU-ID other than what is
configured for that PMUREPORT instance (PMUReportUDP[x]), then that client is immediately
disconnected and the UDPCtrlCfgErrCnt is incremented in PMU Diagnostics on LHMI at Main
menu /Diagnostics /Communication /PMU diagnostics /PMUSTATUS:1
Even if the parameter SendDataUDP[x] is set to Off it is still possible for the clients to connect on the
TCP port and request the configuration frames.
PID-6710-SETTINGS v4
6.2.1 Identification
GUID-0090956B-48F1-4E8B-9A40-90044C71DF20 v1
The phasor measurement reporting block moves the phasor calculations into an IEC/IEEE
60255-118 (C37.118) and/or IEEE 1344 synchrophasor frame format. The PMUREPORT block
contains parameters for PMU performance class and reporting rate, the IDCODE and Global PMU
ID, format of the data streamed through the protocol, the type of reported synchrophasors, as well as
settings for reporting analog and digital signals.
The message generated by the PMUREPORT function block is set in accordance with the IEC/IEEE
60255-118 (C37.118) and/or IEEE 1344 standards.
There are settings for Phasor type (positive sequence, negative sequence or zero sequence in case
of 3-phase phasor and L1, L2 or L3 in case of single phase phasor), PMU's Service class (Protection
or Measurement), Phasor representation (polar or rectangular) and the data types for phasor data,
analog data and frequency data.
Synchrophasor data can be reported to up to 8 clients over TCP and/or 6 UDP group clients for
multicast or unicast transmission of phasor data from the IED. More information regarding
synchrophasor communication structure and TCP/UDP configuration is available in section IEC/IEEE
60255-118 (C37.118) Phasor Measurement Data Streaming Protocol Configuration.
Multiple PMU functionality can be configured in the IED, which can stream out same or different data
at different reporting rates or different performance (service) classes. There are 2 instances of PMU
functionality available in the IED. Each instance of PMU functionality includes a set of PMU reporting
function blocks tagged by the same instance number (1 or 2). As shown in the following figures, each
set of PMU reporting function blocks includes PMUREPORT, PHASORREPORT1-4,
ANALOGREPORT1-3, and BINARYREPORT1-3 function blocks. In general, each instance of PMU
functionality has 32 configurable phasor channels (PHASORREPORT1–4 blocks), 24 analog
channels (ANALOGREPORT1-3 blocks), and 28 digital channels (24 digital-report channels in
BINARYREPORT1-3 and 4 trigger-report channels in PMUREPORT function block). Special rules
shall be taken into account in PCM600 for Application Configuration and Parameter Settings of
multiple PMUREPORT blocks. These rules are explained in the Application Manual in section PMU
Report Function Blocks Connection Rules.
Figure 34 shows both instances of the PMUREPORT function block. As seen, each PMUREPORT
instance has 4 predefined binary input signals corresponding to the Bits 03-00: Trigger Reason
defined in STAT field of the Data frame in IEC/IEEE 60255-118 (C37.118) standard. These are
predefined inputs for Frequency Trigger, Rate of Change of Frequency trigger, Magnitude High and
Magnitude Low triggers.
IEC140000118-2-en.vsd
IEC140000118 V2 EN-US
IEC140000119-2-en.vsd
IEC140000119 V2 EN-US
IEC140000120-2-en.vsd
IEC140000120 V2 EN-US
block). These binary signals can be for example dis-connector or breaker position indications or
internal/external protection alarm signals.
IEC140000121-2-en.vsd
IEC140000121 V2 EN-US
PMUREPORT
BLOCK TIMESTAT
^FREQTRIG
^DFDTTRIG
^MAGHIGHTRIG
^MAGLOWTRIG
IEC140000102-1_en.vsd
IEC140000102 V1 EN-US
ANALOGREPORT1
^ANALOG1
^ANALOG2
^ANALOG3
^ANALOG4
^ANALOG5
^ANALOG6
^ANALOG7
^ANALOG8
IEC140000107-1_en.vsd
IEC140000107 V1 EN-US
ANALOGREPORT2
^ANALOG9
^ANALOG10
^ANALOG11
^ANALOG12
^ANALOG13
^ANALOG14
^ANALOG15
^ANALOG16
IEC140000108-1_en.vsd
IEC140000108 V1 EN-US
ANALOGREPORT3
^ANALOG17
^ANALOG18
^ANALOG19
^ANALOG20
^ANALOG21
^ANALOG22
^ANALOG23
^ANALOG24
IEC140000109-1_en.vsd
IEC140000109 V1 EN-US
BINARYREPORT1
^BINARY1
^BINARY2
^BINARY3
^BINARY4
^BINARY5
^BINARY6
^BINARY7
^BINARY8
IEC140000110-1_en.vsd
IEC140000110 V1 EN-US
BINARYREPORT2
^BINARY9
^BINARY10
^BINARY11
^BINARY12
^BINARY13
^BINARY14
^BINARY15
^BINARY16
IEC140000111-1_en.vsd
IEC140000111 V1 EN-US
BINARYREPORT3
^BINARY17
^BINARY18
^BINARY19
^BINARY20
^BINARY21
^BINARY22
^BINARY23
^BINARY24
IEC140000112-1_en.vsd
IEC140000112 V1 EN-US
PHASORREPORT1
^PHASOR1
^PHASOR2
^PHASOR3
^PHASOR4
^PHASOR5
^PHASOR6
^PHASOR7
^PHASOR8
IEC140000103-1_en.vsd
IEC140000103 V1 EN-US
PHASORREPORT2
^PHASOR9
^PHASOR10
^PHASOR11
^PHASOR12
^PHASOR13
^PHASOR14
^PHASOR15
^PHASOR16
IEC140000104-1_en.vsd
IEC140000104 V1 EN-US
PHASORREPORT3
^PHASOR17
^PHASOR18
^PHASOR19
^PHASOR20
^PHASOR21
^PHASOR22
^PHASOR23
^PHASOR24
IEC140000105-1_en.vsd
IEC140000105 V1 EN-US
PHASORREPORT4
^PHASOR25
^PHASOR26
^PHASOR27
^PHASOR28
^PHASOR29
^PHASOR30
^PHASOR31
^PHASOR32
IEC140000106-1_en.vsd
IEC140000106 V1 EN-US
PID-6244-INPUTSIGNALS v2
PID-6244-OUTPUTSIGNALS v2
PID-6238-INPUTSIGNALS v2
PID-6239-INPUTSIGNALS v2
PID-6240-INPUTSIGNALS v2
PID-6241-INPUTSIGNALS v3
PID-6242-INPUTSIGNALS v2
PID-6243-INPUTSIGNALS v2
PID-6252-INPUTSIGNALS v3
PID-6253-INPUTSIGNALS v2
PID-6254-INPUTSIGNALS v2
PID-6255-INPUTSIGNALS v2
PID-6895-SETTINGS v2
PID-6238-SETTINGS v2
PID-6239-SETTINGS v2
PID-6240-SETTINGS v2
PID-6252-SETTINGS v2
PID-6253-SETTINGS v3
PID-6254-SETTINGS v2
PID-6255-SETTINGS v2
PID-6238-MONITOREDDATA v2
PID-6239-MONITOREDDATA v2
PID-6240-MONITOREDDATA v2
PID-6241-MONITOREDDATA v2
PID-6242-MONITOREDDATA v2
PID-6243-MONITOREDDATA v2
PID-6252-MONITOREDDATA v3
PID-6253-MONITOREDDATA v2
PID-6254-MONITOREDDATA v2
PID-6255-MONITOREDDATA v2
The Phasor Measurement Unit (PMU) features three main functional principles:
• To measure the power system related AC quantities (voltage, current) and to calculate the
phasor representation of these quantities.
• To synchronize the calculated phasors with the UTC by time-tagging, in order to make
synchrophasors (time is reference).
• To publish all phasor-related data by means of TCP/IP or UDP/IP, following the standard IEEE
C37.118 protocol.
The C37.118 standard imposes requirements on the devices and describes the communication
message structure and data. The PMU complies with all the standard requirements with a specific
attention to the Total Vector Error (TVE) requirement. The TVE is calculated using the following
equation:
2
( X r ( n ) - X r )2 + ( X i ( n ) - X i )
TVE =
X r2 + X i2
GUID-80D9B1EA-A770-4F50-9530-61644B4DEBBE V1 EN-US (Equation 1)
where,
In order to comply with TVE requirements, special calibration is done in the factory on the analog
input channels of the PMU, resulting in increased accuracy of the measurements. The IEEE C37.118
standard also imposes a variety of steady state and dynamic requirements which are fulfilled in the
IED with the help of high accuracy measurements and advanced filtering techniques.
Figure 38 shows an overview of the PMU functionality and operation. In this figure, only one instance
of PMUREPORT (PMUREPORT1) is shown. Note that connection of different signals to the
PMUREPORT, in this figure, is only an example and the actual connections and reported signals on
the IEEEC37.118/1344 can be defined by the user.
U/I samples
PMUREPORT1
MU PHASOR1
PHASOR2 8 TCP
U IEEEC37.118 / 1344
TRM SMAI messages NUM
I
U 6 UDC
TRM PHASOR32
I
ANALOG1
I/P MIM SMMI ANALOG2
MEAS. ANALOG24
BINARY1
BINARY2
BIM
OR
BINARY24
PROTECTION
GPS / OP
IRIG-B FREQTRIG
UP
DFDTTRIG
OC
PPS time data MAGHIGHTRIG
MAGLOWTRIG
UV
IEC140000146-1-en.vsd
IEC140000146 V2 EN-US
The TRM modules are individually AC-calibrated in the factory. The calibration data is stored in the
prepared area of the TRM EEProm. The pre-processor block is extended with calibration
compensation and a new angle reference method based on timestamps. The AI3P output of the
preprocessor block is used to provide the required information for each respective PMUREPORT
phasor channel. More information about preprocessor block is available in the section Signal matrix
for analog inputs SMAI.
By using patented algorithm the IED can track the power system frequency in quite wide range from
9 Hz to 95 Hz. In order to do that, the three-phase voltage signal shall be connected to the IED. Then
IED can adapt its filtering algorithm in order to properly measure phasors of all current and voltage
signals connected to the IED. This feature is essential for proper operation of the PMUREPORT
function or for protection during generator start-up and shut-down procedure.
This adaptive filtering is ensured by proper configuration and settings of all relevant pre-processing
blocks, see Signal matrix for analog inputs in the Application manual. Note that in all preconfigured
IEDs such configuration and settings are already made and the three-phase voltage are used as
master for frequency tracking. With such settings the IED will be able to properly estimate the
magnitude and the phase angle of measured current and voltage phasors in this wide frequency
range.
One of the important functions of a PMU is reporting a very accurate system frequency to the PDC
client. In the IED, each of the PMUREPORT instances is able to report an accurate frequency. Each
voltage-connected preprocessor block (SMAI block) delivers the frequency data, derived from the
analog input AC voltage values, to the respective voltage phasor channel. Every phasor channel has
a user-settable parameter (PhasorXUseFreqSrc) to be used as a source of frequency data for
reporting to the PDC client. It is very important to set this parameter to On for the voltage-connected
phasor channels. There is an automatic frequency source selection logic to ensure an uninterrupted
reporting of the system frequency to the PDC client. In this frequency source selection logic, the
following general rules are applied:
As a result, the first voltage phasor is always the one delivering the system frequency to the PDC
client and if, by any reason, this voltage gets disconnected then the next available voltage phasor is
automatically used as the frequency source and so on. If the first voltage phasor comes back, since it
has a higher priority compare to the currently selected phasor channel, after 500 ms it will be
automatically selected again as the frequency source. There is also an output available on the
component which shows if the reference frequency is good, error or reference channel unavailable.
It is possible to monitor the status of the frequency reference channel (frequency source) for the
respective PMUREPORT instance on Local HMI under Test /Function status /Communication /
Station Communication /PMU Report /PMUREPORT:1 /Outputs , where the FREQREFCHSEL
output shows the selected channel as the reference for frequency and FREQREFCHERR output
states if the reference frequency is good, or if there is an error or if the reference channel is
unavailable. For more information refer to the table PMUREPORT monitored data.
PID-6244-MONITOREDDATA v2
The PMUREPORT function block implements the reporting filters designed to avoid aliasing as the
reporting frequency is lower than the sample/calculation frequency. This means, the synchrophasor
and frequency data which are included in the C37.118 synchrophasor streaming data are filtered in
order to suppress aliasing effects, as the rate of the C37.118 data is slower than the data rate for
internal processing. For this purpose, there is an anti-aliasing filter designed for each reporting rate.
The correct anti-aliasing filter will be automatically selected based on the reporting rate and the
performance class (P/M) settings. The filters are designed to attenuate all aliasing frequencies to at
least -40 dB (a gain of 0.01) at M class.
For example, when the synchrophasor measurement follows the fundamental frequency beyond the
fixed Nyquist limits in C37.118 standard, the anti-aliasing filter stopband moves with the measured
fundamental frequency. This has to be considered in connection with C37.118, where the passband
is defined relative to a fixed nominal frequency as shown in the equation 2.
Fs
f0 ±
2
IECEQUATION2418 V1 EN-US (Equation 2)
where,
The internal calculation of analog values in the IED is based on 32 bit floating point. Therefore, if the
user selects to report the analog data (AnalogDataType) as Integer, there will be a down-conversion
of a 32 bit floating value to a new 16 bit integer value. In such a case, in order to optimize the
resolution of the reported analog data, the user-defined analog scaling is implemented in the IED.
The analog scaling in the IED is automatically calculated by use of the user-defined parameters
AnalogXRange for the respective analog channel X. The analog data value on the input X will have a
range between -AnalogXRange and +AnalogXRange. The resulting scale factor will be applied to the
reported analog data where applicable.
AnalogXRange ´ 2
S calefactor =
65535.0
offset = 0.0
65535.0 = 16 bit integer range
IECEQUATION2443 V1 EN-US
According to the IEEE C37.118.2 standard, the scale factors (conversion factor) for analog channels
are defined in configuration frame 2 (CFG-2) and configuration frame 3 (CFG-3) frames as follows:
• CFG-2 frame: The field ANUNIT (4 bytes) specifies the conversion factor as a signed 24 bit
word for user defined scaling. Since it is a 24 bit integer, in order to support the floating point
scale factor, the scale factor itself is multiplied in 10, so that a minimum of 0.1 scale factor can
be sent over the CFG-2 frame. The resulting scale factor is rounded to the nearest decimal
value. The clients receiving the Analog scale factor over CFG-2 should divide the received scale
factor by 10 and then apply it to the corresponding analog data value.
• CFG-3 frame: The field ANSCALE (8 bytes) specifies the conversion factor as X’ = M * X + B
where; M is magnitude scaling in 32 bit floating point (first 4 bytes) and B is the offset in 32 bit
floating point (last 4 bytes).
The server uses CFG-3 scale factor to scale the analog data values. As a result, the clients which
use scale factors in CFG-3 in order to recalculate analog values, will get a better resolution than
using the scale factors in CFG-2.
Example 1:
AnalogXRange = 3277.0
IECEQUATION2446 V1 EN-US
(3277.0 ´ 2.0 )
sc alefac tor = = 0.1 a nd offse t = 0.0
65535.0
IECEQUATION2447 V1 EN-US
The scale factor will be sent as 1 on configuration frame 2, and 0.1 on configuration frame 3. The
range of analog values that can be transmitted in this case is -0.1 to -3276.8 and +0.1 to +3276.7.
Example 2:
AnalogXRange = 4915.5
IECEQUATION2448 V1 EN-US
(4915.5 ´ 2.0 )
s c alefac tor = = 0.15 a nd offse t = 0.0
65535.0
IECEQUATION2449 V1 EN-US
The scale factor will be sent as 1 on configuration frame 2, and 0.15 on configuration frame 3. The
range of analog values that can be transmitted in this case is -0.15 to -4915.5 and +0.15 to +4915.5.
Example 3:
(10000000000 ´ 2.0)
sc alefac tor = = 305180.43 and offse t = 0.0
65535.5
IECEQUATION2451 V1 EN-US
The scale factor will be sent as 3051804 on configuration frame 2, and 305180.43 on configuration
frame 3. The range of analog values that can be transmitted in this case is -305181 to -10000000000
and +305181 to +10000000000.
GUID-F0BAEBD8-E361-4D50-9737-7DF8B043D66A v5
Signal magnitude:
Voltage phasor (0.1–1.2) x Ur
Current phasor (0.5–2.0) x Ir
7.1.1 Identification
M15074-1 v5
SYMBOL-BB V1 EN-US
SYMBOL-BB V1 EN-US
The Transformer differential protection is provided with internal CT ratio matching, vector group
compensation and settable zero sequence current elimination.
The function can be provided with up to six three-phase sets of current inputs if enough HW is
available. All current inputs are provided with percentage bias restraint features, making the IED
suitable for two- or three-winding transformer in multi-breaker station arrangements.
Two-winding applications
two-winding power
transformer
xx05000048.vsd
IEC05000048 V1 EN-US
two-winding power
transformer with
unconnected delta
xx05000049.vsd tertiary winding
IEC05000049 V1 EN-US
two-winding power
transformer with two
circuit breakers and
xx05000050.vsd two CT-sets on one
IEC05000050 V1 EN-US
side
two-winding power
transformer with two
circuit breakers and
two CT-sets on both
sides
xx05000051.vsd
IEC05000051 V1 EN-US
Three-winding applications
three-winding power
transformer with all
three windings
connected
xx05000052.vsd
IEC05000052 V1 EN-US
three-winding power
transformer with two
circuit breakers and
two CT-sets on one
side
xx05000053.vsd
IEC05000053 V1 EN-US
Autotransformer with
two circuit breakers
and two CT-sets on
two out of three sides
xx05000057.vsd
IEC05000057 V1 EN-US
The setting facilities cover the application of the differential protection to all types of power
transformers and auto-transformers with or without load tap changer as well as shunt reactors and
local feeders within the station. An adaptive stabilizing feature is included for heavy through-fault
currents. By introducing the load tap changer position, the differential protection pick-up can be set to
optimum sensitivity thus covering internal faults with low fault current level.
Stabilization is included for inrush and overexcitation currents respectively, cross-blocking is also
available. Adaptive stabilization is also included for system recovery inrush and CT saturation during
external faults. A high set unrestrained differential current protection element is included for a very
high speed tripping at high internal fault currents.
Included is an sensitive differential protection element based on the theory of negative sequence
current component. This element offers the best possible coverage of power transformer windings
turn to turn faults.
SEMOD54397-4 v5
T2WPDIF
I3PW1CT1* TRIP
I3PW1CT2* TRIPRES
I3PW2CT1* TRIPUNRE
I3PW2CT2* TRNSUNR
TAPOLTC1 TRNSSENS
OLTC1AL START
BLOCK STL1
BLKRES STL2
BLKUNRES STL3
BLKNSUNR BLK2H
BLKNSSEN BLK2HL1
BLK2HL2
BLK2HL3
BLK5H
BLK5HL1
BLK5HL2
BLK5HL3
BLKWAV
BLKWAVL1
BLKWAVL2
BLKWAVL3
IDALARM
OPENCT
OPENCTAL
IDL1
IDL2
IDL3
IDL1MAG
IDL2MAG
IDL3MAG
IBIAS
IDNSMAG
IEC06000249_2_en.vsd
IEC06000249 V2 EN-US
T3WPDIF
I3PW1CT1* TRIP
I3PW1CT2* TRIPRES
I3PW2CT1* TRIPUNRE
I3PW2CT2* TRNSUNR
I3PW3CT1* TRNSSENS
I3PW3CT2* START
TAPOLTC1 STL1
TAPOLTC2 STL2
OLTC1AL STL3
OLTC2AL BLK2H
BLOCK BLK2HL1
BLKRES BLK2HL2
BLKUNRES BLK2HL3
BLKNSUNR BLK5H
BLKNSSEN BLK5HL1
BLK5HL2
BLK5HL3
BLKWAV
BLKWAVL1
BLKWAVL2
BLKWAVL3
IDALARM
OPENCT
OPENCTAL
IDL1
IDL2
IDL3
IDL1MAG
IDL2MAG
IDL3MAG
IBIAS
IDNSMAG
IEC06000250_2_en.vsd
IEC06000250 V2 EN-US
7.1.4 Signals
PID-6758-INPUTSIGNALS v1
PID-6758-OUTPUTSIGNALS v1
PID-6757-INPUTSIGNALS v1
PID-6757-OUTPUTSIGNALS v1
7.1.5 Settings
PID-6758-SETTINGS v1
PID-6757-SETTINGS v1
PID-3713-MONITOREDDATA v6
The main CTs are normally supposed to be star connected. The main CTs can be earthed in anyway
(that is, either "ToObject" or "FromObject"). However internally the differential function will always use
reference directions towards the protected transformer as shown in Figure 42. Thus the IED will
always internally measure the currents on all sides of the power transformer with the same reference
direction towards the power transformer windings as shown in Figure 42. For more information see
the Application manual.
IW1 IW2
Z1S1 Z1S2
E1S1 E1S2
IW1 IW2
IED
en05000186.vsd
IEC05000186 V1 EN-US
First, compensation for the protected transformer transformation ratio and connection group is made,
and only then are the currents compared phase-wise. This makes external auxiliary (interposing)
current transformers unnecessary. Conversion of all currents to the common reference side of the
power transformer is performed by pre-programmed coefficient matrices, which depends on the
protected power transformer transformation ratio and connection group. Once the power transformer
vector group, rated currents and voltages have been entered by the user, the differential protection is
capable to calculate off-line matrix coefficients required in order to perform the on-line current
comparison by means of a fixed equation.
For all differential functions it is the common trip that is used to initiate a trip of a
breaker. The separate trip signals from the different parts lacks the safety against
maloperation. This will in some cases result in a 6 ms time difference between, for
example restrained trip is issued and common trip is issued. The separate trip
signals are only used for information purpose of which part that has caused the trip.
To make a differential IED as sensitive and stable as possible, restrained differential characteristics
have been developed and is now adopted as the general practice in the protection of power
transformers. The protection should be provided with a proportional bias, which makes the protection
operate for a certain percentage differential current related to the current through the transformer.
This stabilizes the protection under through fault conditions while still permitting the system to have
good basic sensitivity. The following chapters explain how these quantities are derived.
Before any differential current can be calculated, the power transformer phase shift, and its
transformation ratio, must be accounted for. Conversion of all currents to a common reference is
performed in two steps:
• all current phasors are phase-shifted to (referred to) the phase-reference side, (whenever
possible the first HV winding with star connection)
• all currents magnitudes are always referred to the first winding of the power transformer
(typically transformer high-voltage side)
The two steps of conversion are made simultaneously on-line by the pre-programmed coefficient
matrices, as shown in equation 3 for a two-winding power transformer, and in equation 4 for a three-
winding power transformer.
These are the internal compensation within the differential function. The protected
power transformer data is always entered per its nameplate. The Differential function
will correlate nameplate data and select proper reference windings.
1 2 3
EQUATION1880 V1 EN-US (Equation 3)
where:
1. is the resulting Differential Currents
2. is the current contribution from the W1 side
3. is the current contribution from the W2 side
1 2 3 4
EQUATION1556 V2 EN-US (Equation 4)
where:
1. is the resulting Differential Currents
2. is the current contribution from the W1 side
3. is the current contribution from the W2 side
4. is the current contribution from the W3 side
1. The Power transformer winding connection type, such as star (Y/y) or delta (D/d)
2. The Transformer vector group such as Yd1, Dy11, YNautod5, Yy0d5 and so on, which introduce
phase displacement between individual windings currents in multiples of 30°.
3. The Settings for elimination of zero sequence currents for the individual windings.
When the end user enters all these parameters, transformer differential function automatically
calculates the matrix coefficients. During this calculations the following rules are used:
For the phase reference, the first winding with set star (Y) connection is always used. For example, if
the power transformer is a Yd1 power transformer, the HV winding (Y) is taken as the phase
reference winding. If the power transformer is a Dy1, then the LV winding (y) is taken for the phase
reference. If there is no star connected winding, such as in Dd0 type of power transformers, then the
HV delta winding (D) is automatically chosen as the phase reference winding.
The fundamental frequency differential currents are in general composed of currents of all
sequences, that is, the positive-, the negative-, and the zero-sequence currents. If the zero-sequence
currents are eliminated (see section "Optional Elimination of zero sequence currents"), then the
differential currents can consist only of the positive-, and the negative-sequence currents. When the
zero-sequence current is subtracted on one side of the power transformer, then it is subtracted from
each individual phase current.
As it can be seen from equation 3 and equation 4 the first entered winding (W1) is always taken for
ampere level reference (current magnitudes from all other sides are always transferred to W1 side).
In other words, within the differential protection function, all differential currents and bias current are
always expressed in HV side primary Amperes.
It can be shown that the values of the matrix A, B & C coefficients (see equation 3 and equation 4)
can be pre-calculated in advance depending on the relative phase shift between the reference
winding and other power transformer windings.
Table 93 summarizes the values of the matrices for all standard phase shifts between windings.
Matrix with Zero Sequence Matrix with Zero Sequence Reduction set to
Reduction set to On Off
Matrix for Reference Winding
é 2 -1 -1ù é1 0 0 ù
1 ê
× -1 2 -1ú ê0 1 0 ú
3 ê ú ê ú
êë -1 -1 2 úû êë0 0 1 úû
EQUATION1227 V1 EN-US (Equation 5) EQUATION1228 V1 EN-US (Equation 6)
Matrix for winding with 30° Not applicable. Matrix on the left used.
lagging é 1 -1 0 ù
1 ê
× 0 1 -1ú
3 ê ú
êë -1 0 1 úû
EQUATION1229 V1 EN-US (Equation 7)
Matrix for winding with 60°
lagging é1 -2 1ù é 0 -1 0 ù
1 ê
× 1 1 -2 ú ê 0 0 -1ú
3 ê ú ê ú
êë -2 1 1 úû êë -1 0 0 úû
EQUATION1230 V1 EN-US (Equation 8) EQUATION1231 V1 EN-US (Equation 9)
Matrix for winding with 90° Not applicable. Matrix on the left used.
lagging é 0 -1 1 ù
1
× ê 1 0 -1ú
3 ê ú
êë -1 1 0 úû
EQUATION1232 V1 EN-US (Equation 10)
Matrix for winding with 120°
lagging é -1 -1 2 ù é0 0 1 ù
1 ê
× 2 -1 -1ú ê1 0 0 ú
3 ê ú ê ú
êë -1 2 -1úû ëê0 1 0 úû
EQUATION1233 V1 EN-US (Equation 11) EQUATION1234 V1 EN-US (Equation 12)
Matrix for winding with 150° Not applicable. Matrix on the left used.
lagging é-1 0 1 ù
1
× ê 1 -1 0 ú
3 ê ú
ëê 0 1 -1ûú
EQUATION1235 V1 EN-US (Equation 13)
Matrix for winding which is in
opposite phase é -2 1 1ù é -1 0 0 ù
1 ê
× 1 -2 1 ú ê 0 -1 0 ú
3 ê ú ê ú
ëê 1 1 -2 ûú ëê 0 0 -1ûú
EQUATION1236 V1 EN-US (Equation 14) EQUATION1237 V1 EN-US (Equation 15)
Matrix for winding with 150° Not applicable. Matrix on the left used.
leading é-1 1 0 ù
1
× ê 0 -1 1 ú
3 ê ú
ëê 1 0 -1ûú
EQUATION1238 V1 EN-US (Equation 16)
Matrix for winding with 120°
leading é -1 2 -1ù é0 1 0 ù
1 ê
× -1 -1 2 ú ê0 0 1 ú
3 ê ú ê ú
ëê 2 -1 -1ûú ëê1 0 0 úû
EQUATION1239 V1 EN-US (Equation 17) EQUATION1240 V1 EN-US (Equation 18)
Matrix with Zero Sequence Matrix with Zero Sequence Reduction set to
Reduction set to On Off
Matrix for winding with 90° Not applicable. Matrix on the left used.
leading é 0 1 -1ù
1
× ê -1 0 1 ú
3 ê ú
ëê 1 -1 0 úû
EQUATION1241 V1 EN-US (Equation 19)
Matrix for winding with 60°
leading é1 1 -2 ù é 0 0 -1ù
1 ê ê -1 0 0 ú
× -2 1 1ú
3 ê ú ê ú
ëê 1 -2 1 ûú ëê 0 -1 0 úû
EQUATION1242 V1 EN-US (Equation 20) EQUATION1243 V1 EN-US (Equation 21)
Matrix for winding with 30° Not applicable. Matrix on the left used.
leading é 1 0 -1ù
1
× ê -1 1 0 ú
3 ê ú
ëê 0 -1 1 úû
EQUATION1244 V1 EN-US (Equation 22)
By using this table complete equation for calculation of fundamental frequency differential currents
for two winding power transformer with YNd5 vector group and enabled zero sequence current
reduction on HV side will be derived. From the given power transformer vector group the following is
possible to be concluded:
1. The HV star (Y) connected winding will be used as the reference winding and zero sequence
currents shall be subtracted on that side
2. The LV winding is lagging for 150°
With the help of table 93, the following matrix equation can be written for this power transformer:
where:
IDL1 is the fundamental frequency differential current in phase L1 (in W1 side primary
amperes)
IDL2 is the fundamental frequency differential current in phase L2 (in W1 side primary
amperes)
IDL3 is the fundamental frequency differential current in phase L3 (in W1 side primary
amperes)
IL1_W1 is the fundamental frequency phase current in phase L1 on the W1 side
IL2_W1 is the fundamental frequency phase current in phase L2 on the W1 side
IL3_W1 is the fundamental frequency phase current in phase L3 on the W1 side
IL1_W2 is the fundamental frequency phase current in phase L1 on the W2 side
IL2_W2 is the fundamental frequency phase current in phase L2 on the W2 side
IL3_W2 is the fundamental frequency phase current in phase L3 on the W2 side
Ur_W1 is transformer rated phase-to-phase voltage on the W1 side (setting parameter)
Ur_W2 is transformer rated phase-to-phase voltage on the W2 side (setting parameter)
As marked in equation 3 and equation 4, the first term on the right hand side of the equation,
represents the total contribution from the individual phase currents from the W1 side to the
fundamental frequency differential currents, compensated for eventual power transformer phase
shift. The second term on the right hand side of the equation, represents the total contribution from
the individual phase currents from the W2 side to the fundamental frequency differential currents,
compensated for eventual power transformer phase shift and transferred to the power transformer
W1 side. The third term on the right hand side of the equation, represents the total contribution from
the individual phase currents from the W3 side to the fundamental frequency differential currents,
compensated for eventual power transformer phase shift and transferred to the power transformer
W1 side. These current contributions are important, because they are used for calculation of
common bias current.
The fundamental frequency differential currents are the "usual" differential currents, the magnitudes
which are applied in a phase-wise manner to the operate - restrain characteristic of the differential
protection. The magnitudes of the differential currents can be read as service values from the
function and they are available as outputs IDL1MAG, IDL2MAG, IDL3MAG from the differential
protection function block. Thus they can be connected to the disturbance recorder and automatically
recorded during any external or internal fault condition.
Differential currents are calculated as shown in equation and equation . By setting parameters, the
winding location of the OLTC is defined. Also, the voltage change of each step. Thus, if for example
the load tap changer is located within winding 1 the no-load voltage Vn_W1 will be treated as a
function of the actual load tap changer position in equation and equation . Thus for every load tap
changer position a corresponding value for Ur_W1 will be calculated and used in the above
mentioned equations. By doing this, complete on-line compensation for load tap changer movement
is achieved. Differential protection will be ideally balanced for every load tap changer position and no
false differential current will appear irrespective of actual load tap changer position.
Typically the minimum differential protection pickup for power transformer with load tap changer is
set between 30% to 40%. However with this load tap changer compensation feature it is possible to
set the differential protection in the IED more sensitive with a pickup value of 15% to 20%.
Load tap changer position is measured within the IED by Tap changer control and supervision,
(TCLYLTC). Within this function block, the load tap changer position value is continuously monitored
to insure its integrity.
When any error in the load tap changer position is detected an alarm is given. This signal shall be
connected to the OLTCxAL input of the differential function block. While OLTCxAL input has a logical
value of one the differential protection minimum pickup, originally defined by setting parameter IdMin,
will be increased by the set range of the load tap changer. Alternatively the differential current alarm
feature can be used to alarm for any problems in the whole load tap changer compensation chain.
• two-winding differential protection in the IED can on-line compensate for one load tap changer
within the protected power transformer
• three-winding differential protection in the IED can on-line compensate for up to two load tap
changers within the protected power transformer
It shall be noted that if the zero-sequence currents are subtracted from the separate contributions to
the total differential current, then the zero-sequence component is automatically eliminated from the
bias current as well. This ensures that for secondary injection from just one power transformer side
the bias current is always equal to the highest differential current regardless of the fault type. During
normal through-load operation of the power transformer, the bias current is equal to the maximum
load current from two (three) -power transformer windings.
The magnitudes of the common bias (restrain) current expressed in HV side amperes can be read as
service value from the function. At the same time it is available as an output IBIAS from the
differential protection function block. It can be connected to the disturbance recorder and
automatically recorded during any external or internal fault condition.
For application with so called "T" configuration, that is, two restraint CT inputs from one side of the
protected power transformer, such as in the case of breaker-and-a-half schemes the primary CT
ratings can be much higher than the rating of the protected power transformer. In order to determine
the bias current for such T configuration, the two separate currents flowing in the T-side are scaled
down to the protected power transform level by means of additional settings. This is done in order to
prevent unwanted de-sensitizing of the overall differential protection. In addition to that, the resultant
currents (the sum of two currents) into the protected power transformer winding, which is not directly
measured is calculated, and included in the common bias calculation. The rest of the bias calculation
procedure is the same as in protection schemes without breaker-and-a-half arrangements.
The zero sequence currents can be explicitly eliminated from the differential currents and common
bias current calculation by special, dedicated parameter settings, which are available for every
individual winding.
• the protected power transformer cannot transform the zero sequence currents to the other side.
• the zero sequence currents can only flow on one side of the protected power transformer.
In most cases, power transformers do not properly transform the zero sequence current to the other
side. A typical example is a power transformer of the star-delta type, for example YNd1.
Transformers of this type do not transform the zero sequence quantities, but zero sequence currents
can flow in the earthed star- connected winding. In such cases, an external earth-fault on the star-
side causes zero sequence current to flow on the star-side of the power transformer, but not on the
other side. This results in false differential currents - consisting exclusively of the zero sequence
currents. If high enough, these false differential currents can cause an unwanted disconnection of the
healthy power transformer. They must therefore be subtracted from the fundamental frequency
differential currents if an unwanted trip is to be avoided.
For delta windings this feature shall be enabled only if an earthing transformer exists within the
differential zone on the delta side of the protected power transformer.
Removing the zero sequence current from the differential currents decreases to some extent the
sensitivity of the differential protection for internal earth -faults. In order to counteract this effect to
some degree, the zero sequence current is subtracted not only from the three fundamental frequency
differential currents, but from the bias current as well.
The unrestrained (that is, non-stabilized, "instantaneous") part of the differential protection is used for
very high differential currents, where it should be beyond any doubt, that the fault is internal. This
settable limit is constant and not proportional to the bias current. Neither harmonic, nor any other
restrain is applied to this limit, which is therefore allowed to trip the power transformer
instantaneously.
The restrained (stabilized) part of the differential protection compares the calculated fundamental
differential (operating) currents and the bias (restrain) current, by applying them to the operate -
restrain characteristic. Practically, the magnitudes of the individual fundamental frequency differential
currents are compared with an adaptive limit. This limit is adaptive because it is dependent on the
bias (that is, restrain) current magnitude. This limit is called the operate - restrain characteristic. It is
represented by a double-slope, double-breakpoint characteristic, as shown in figure 43. The
restrained characteristic is determined by the following 5 settings:
1. IdMin (Sensitivity in section 1, multiple of trans. HV side rated current set under the parameter
RatedCurrentW1)
2. EndSection1 (End of section 1, as multiple of transformer HV side rated current set under the
parameter RatedCurrentW1)
3. EndSection2 (End of section 2, as multiple of transformer HV side rated current set under the
parameter RatedCurrentW1)
4. SlopeSection2 (Slope in section 2, as multiple of transformer HV side rated current set under the
parameter RatedCurrentW1)
5. SlopeSection3 (Slope in section 2, as multiple of transformer HV side rated current set under the
parameter RatedCurrentW1)
For three-winding transformer, if the HV winding is not the one with highest power rating, the
parameters of operate-bias characteristic (Idmin, EndSection1 and EndSection2) will be adapted by
multiplying a scale factor Smax/S1 so that the winding with highest power rating is taken into
account. Smax and S1 can be calculated from the rated voltage and current for each winding.
1. IdMin
2. EndSection1
3. EndSection2
4. SlopeSection2
5. SlopeSection3
operate current
[ times IBase ]
Operate
5
unconditionally
UnrestrainedLimit
4
Operate
3
conditionally
2
Section 1 Section 2 Section 3
SlopeSection3
1
IdMin
SlopeSection2 Restrain
0
0 1 2 3 4 5
en05000187-2.vsd
IEC05000187 V2 EN-US
Figure 43: Description of the restrained, and the unrestrained operate characteristics
where:
The operate - restrain characteristic is tailor-made and can be designed freely by the user after his
needs. The default characteristic is recommended to be used. It gives good results in a majority of
applications. The operate - restrain characteristic has in principle three sections with a section-wise
proportionality of the operate value to the bias (restrain) current. The reset ratio is in all parts of the
characteristic equal to 0.95.
Section 1: This is the most sensitive part on the characteristic. In section 1, normal currents flow
through the protected circuit and its current transformers, and risk for higher false differential currents
is relatively low. An un-compensated on-load tap-changer is a typical reason for existence of the
false differential currents in this section. The slope in section 1 is always zero percent.
Section 2: In section 2, a certain minor slope is introduced which is supposed to cope with false
differential currents proportional to higher than normal currents through the current transformers.
Section 3: The more pronounced slope in section 3 is designed to result in a higher tolerance to
substantial current transformer saturation at high through-fault currents, which may be expected in
this section.
The operate - restrain characteristic should be designed so that it can be expected that:
• for internal faults, the operate (differential) currents are always with a good margin above the
operate - restrain characteristic
• for external faults, the false (spurious) operate currents are with a good margin below the
operate - restrain characteristic
The differential protection can be temporarily desensitized by applying the adaptive DC biasing
method. When the external fault is detected, this adaptive DC biasing method will temporarily shift
the operate-bias characteristic by adding DC components to the operate level IdMin. The DC
component is extracted online form the instantaneous differential currents and the highest DC in all
three phases is selected to be added to IdMin. This feature improves the security of the differential
function against the CT errors during heavy external faults followed by CT saturation. The adaptive
DC biasing will be reset if either of the conditions below is fulfilled:
• The external fault signal disappears and no DC components exist in the phase currents.
• The differential currents become higher than the bias current.
For power transformer differential protection applications, the negative sequence based differential
currents are calculated by using exactly the same matrix equations, which are used to calculate the
traditional phase-wise fundamental frequency differential currents. The same equation shall be fed by
the negative sequence currents from the two power transformer sides instead of individual phase
currents, as shown in matrix equation 25 for a case of two-winding, YNd5 power transformer.
1 2 3
where:
1. is the Negative Sequence Differential Currents
2. is the Negative Sequence current contribution from the W1 side
3. is the Negative Sequence current contribution from the W2 side
and where:
IDL1_NS is the negative sequence differential current in phase L1 (in
W1 side primary amperes)
IDL2_NS is the negative sequence differential current in phase L2 (in
W1 side primary amperes)
IDL3_NS is the negative sequence differential current in phase L3 (in
W1 side primary amperes)
INS_W1 is the negative sequence current on the W1 side in primary
amperes (phase L1 reference)
INS_W2 is the negative sequence current on the W2 side in primary
amperes (phase L1 reference)
Ur_W1 is the transformer rated phase-to-phase voltage on the W1
side (setting parameter)
Ur_W2 is the transformer rated phase-to-phase voltage on W2
side (setting parameter)
j ×120
o 1 3
a=e =- + j×
2 2
EQUATION1248 V1 EN-US (Equation 26)
Because the negative sequence currents always form the symmetrical three phase current system
on each transformer side (that is, negative sequence currents in every phase will always have the
same magnitude and be phase displaced for 120 electrical degrees from each other), it is only
necessary to calculate the first negative sequence differential current that is, IDL1_NS.
As marked in equation 25, the first term on the right hand side of the equation, represents the total
contribution of the negative sequence current from the W1 side compensated for eventual power
transformer phase shift. The second term on the right hand side of the equation, represents the total
contribution of the negative sequence current from the W2 side compensated for eventual power
transformer phase shift and transferred to the power transformer W1 side. These negative sequence
current contributions are phasors, which are further used in directional comparisons, to characterize
a fault as internal or external. See section "Internal/external fault discriminator" for more information.
The magnitudes of the negative sequence differential current expressed in the HV side A can be
read as service values from the function. In the same time it is available as outputs IDNSMAG from
the differential protection function block. Thus, it can be connected to the disturbance recorder and
automatically recorded during any external or internal fault condition.
The internal/external fault discriminator responds to the magnitudes and the relative phase angles of
the negative-sequence fault currents at the different windings of the protected power transformer.
The negative sequence fault currents must first be referred to the same phase reference side, and
put to the same magnitude reference. This is done by the matrix expression (see equation ).
Operation of the internal/external fault discriminator is based on the relative position of the two
phasors representing the winding one (W1) and winding two (W2) negative sequence current
contributions, respectively, defined by expression shown in equation . It performs a directional
comparison between these two phasors. First, the LV side phasor is referred to the HV side (W1
side): both the magnitude, and the phase position are referred to the HV (W1 side). Then the relative
phase displacement between the two negative sequence current phasors is calculated. In case of
three-winding power transformers, a little more complex algorithm is applied, with two directional
tests. The overall directional characteristic of the internal/external fault discriminator is shown in
figure 44, where the directional characteristic is defined by two setting parameters:
1. IMinNegSeq
2. NegSeqROA
90 deg
120 deg
If one or the Internal/external
other of fault boundary
currents is too
low, then no
measurement
NegSeqROA
is done, and
(Relay
120 degrees
Operate
is mapped
Angle)
IMinNegSeq
External Internal
fault fault
region region
If the above condition concerning magnitudes is fulfilled, the internal/external fault discriminator
compares the relative phase angle between the negative sequence current contributions from W1
and W2 sides of the power transformer using the following two rules:
• If the negative sequence current contributions from the W1 and the W2 sides are in phase, the
fault is internal (that is, both phasors are within protected zone)
• If the negative sequence currents contributions from W1 and W2 sides are 180 degrees out of
phase, the fault is external (that is, W1 phasors is outside protected zone)
For example, for any unsymmetrical external fault, ideally the respective negative sequence current
contributions from the W1 and W2 power transformer sides will be exactly 180 degrees apart and
equal in magnitude, regardless the power transformer turns ratio and phase displacement. An
example is shown in figure 45, which shows trajectories of the two separate phasors representing the
negative sequence current contributions from the HV and LV sides of an Yd5 power transformer
(after compensation of the transformer turns ratio and phase displacement) by using equation ) for an
unsymmetrical external fault. Observe that the relative phase angle between these two phasors is
180 electrical degrees at any point in time. No current transformer saturation was assumed for this
case.
"steady state"
for HV side 90
neg. seq. phasor
60
150 30
10
ms
180 0
0.1 kA
0.2 kA
0.3 kA
10 0.4 kA
ms
210 330
"steady state"
240 for LV side
270 neg. seq. phasor
en05000189.vsd
IEC05000189 V1 EN-US
Figure 45: Trajectories of Negative Sequence Current Contributions from HV and LV sides of
Yd5 power transformer during external fault
Under external fault conditions, the relative angle is theoretically equal to 180 degrees. During
internal faults, the angle shall ideally be 0 degrees, but due to possible different negative sequence
source impedance angles on the W1 and W2 sides of the protected power transformer, it may differ
somewhat from the ideal zero value. However, during heavy faults, CT saturation might cause the
measured phase angle to differ from 180 degrees for an external, and from 0 degrees for an internal
fault. See figure 46 for an example of a heavy internal fault with transient CT saturation.
Dire ctiona l Compa ris on Crite rion: Inte rna l fa ult a s s e e n from the HV s ide
90
e xcurs ion
120 60
from 0 de gre e s
35 ms due to CT
s a tura tion
150 30
de finite ly
a n inte rna l
fa ult
180 0
trip c o mmand
in 12 ms
e xte rna l
fa ult Inte rna l fa ult
0.5 kA de cla re d 7 ms
re gion
210 330 a fte r inte rna l
fa ult occure d
1.0 kA
240 300
1.5 kA
270
HV s ide contribution to the tota l ne ga tive s e que nce diffe re ntia l curre nt in kA
Dire ctiona l limit (within the re gion de limite d by ± 60 de gre e s is inte rna l fa ult)
en05000190.vsd
IEC05000190 V1 EN-US
Figure 46: Operation of the internal/external fault discriminator for internal fault with CT
saturation
It shall be noted that additional security measures are implemented in the internal/external fault
discriminator algorithm in order to guarantee proper operation with heavily saturated current
transformers. The trustworthy information on whether a fault is internal or external is typically
obtained in about 10ms after the fault inception, depending on the setting IminNegSeq, and the
magnitudes of the fault currents. During heavy faults, approximately 5ms time to full saturation of the
main CT is sufficient in order to produce a correct discrimination between internal and external faults.
If the same fault has been positively recognized as internal, then the unrestrained negative sequence
differential protection places its own trip request.
Any block signals by the harmonic and/or waveform criteria, which can block the traditional
differential protection are overridden, and the differential protection operates quickly without any
further delay.
This logic guarantees a fast disconnection of a faulty power transformer for any internal fault.
If the same fault has been classified as external, then generally, but not unconditionally, a trip
command is prevented. If a fault is classified as external, further analysis of the fault conditions is
initiated. If all the instantaneous differential currents in phases where start signals have been issued
are free of harmonic pollution, then a (minor) internal fault, simultaneous with a predominant external
fault can be suspected. This conclusion can be drawn because at external faults, major false
differential currents can only exist when one or more current transformers saturate. In this case, the
false instantaneous differential currents are polluted by higher harmonic components, the 2nd, the 5th
etc.
The instantaneous differential currents are calculated using the same matrix expression as shown in
equation and equation . The same matrices A, B and C are used for these calculations. The only
difference is that the matrix algorithm is fed by instantaneous values of currents, that is, samples.
The magnetizing currents of a power transformer flow only on one side of the power transformer and
are therefore always the cause of false differential currents. The harmonic analysis (the 2nd and the
5th harmonic) is applied to the instantaneous differential currents. Typical instantaneous differential
currents during power transformer energizing are shown in figure 47. The harmonic analysis is only
applied in those phases where start signals have been set. For example, if the content of the 2nd
harmonic in the instantaneous differential current of phase L1 is above the setting I2/I1Ratio, then a
block signal is set for that phase, which can be read as BLK2HL1 output of the differential protection.
After the transformer has been energized (the energizing period has elapsed and the inrush currents
have disappeared), the 2nd harmonic blocking is conditionally activated if NegSeqDiffEn is set to On.
When the fault cannot be identified as internal or external, the 2nd harmonic blocking signal is
activated only if the differential current is smaller than the bias current. If the differential current
becomes equal to or higher than the bias current, the differential function will be released regardless
of the 2nd harmonic blocking signal.
The 2nd harmonic analysis always supervises the restrained differential criterion if
NegSeqDiffEn is set to Off.
IEC05000343 V1 EN-US
Figure 47: Inrush currents to a transformer as seen by a protective IED. Typical is a high
amount of the 2nd harmonic, and intervals of low current, and low rate-of-change of
current within each period.
When parameter CrossBlockEn=On cross blocking between phases is introduced. There is no time
settings involved, but the phase with the operating point above the set bias characteristic (in the
operate region) will be able to cross-block the other two phases if it is itself blocked by any of the
previously explained restrained criteria. As soon as the operating point for this phase is below the set
bias characteristic (that is, in the restrain region) cross blocking from that phase will be inhibited. In
this way cross-blocking of a temporary nature is achieved. It should be noted that this is the default
setting value for this parameter.
When parameter CrossBlockEn=Off, any cross blocking between phases will be disabled. It is
recommended to use the value Off with caution in order to avoid the unwanted tripping during initial
energizing of the power transformer.
under the first 4 cycles, 80 ms for 50Hz and 66.7 ms for 60Hz. When the switch onto fault feature is
disabled by the setting parameter SOTFMode, the waveblock and second harmonic blocking
features work in parallel and are completely independent from each other.
A sudden inadvertently opened CT circuit may cause an unexpected and unwanted operation of the
Transformer differential protection under normal load conditions. Damage of secondary equipment
may occur due to high voltage from open CT circuit outputs. It is always an advantage, from the point
of view of security and reliability, to have the open CT detection function to block the transformer
differential protection function in case of an open CT condition, and produce an alarm signal to the
operational personnel to quickly correct the open CT condition.
The built-in open CT feature can be enabled or disabled by the setting parameter OpenCTEnable
(Off/On). When enabled, this feature tries to prevent mal-operation when a loaded main CT
connected to Transformer differential protection is by mistake open circuited on the secondary side.
Note that this feature can only detect interruption of one CT phase current at a time. If two or even all
three-phase currents of one set of CTs are accidentally interrupted at precisely the same time, this
feature cannot operate. Transformer differential protection generates a trip signal if the false
differential current is sufficiently high. An open CT circuit is typically detected in 12–14 ms, and if the
load in the protected circuit is relatively high, about the nominal load, the unwanted trip cannot
always be prevented. Still, the information about what was the cause of the open CT secondary
circuit, is vital.
The principle applied to detect an open CT is a simple pattern recognition method, similar to the
waveform check used by the Power transformer differential protection in order to detect the
magnetizing inrush condition. The open CT detection principle is based on the fact that for an open
CT, the current in the phase with the open CT suddenly drops to zero (that is, as seen by the
protection), while the currents of the other two phases continue as before.
The open CT function is supposed to detect an open CT under normal conditions, that is, with the
protected multi-terminal circuit under normal load (10...110% of the rated load). If the load currents
are very low or zero, the open CT condition cannot be detected. In addition to load condition
requirement, Open CT function also checks the differential current on faulty phase. If the differential
current is lower than 50% of IdMin, the open CT condition cannot be detected. Therefore, the Open
CT algorithm only detects an open CT if the load on the power transformer is 10...110% of rated load
and the differential current is higher than 50% of IdMin on that phase. The search for an open CT
starts 60 seconds (50 seconds in 60 Hz systems) after the transformer is energized. The Open CT
detection feature can also be explicitly deactivated by setting: OpenCTEnable = 0 ( Off).
If an open CT is detected and the output OPENCT set to 1, then all the differential functions are
blocked, except the unrestrained (instantaneous) differential. An alarm signal is also produced after a
settable delay (tOCTAlarmDelay) to report to operational personnel for quick remedy actions once
the open CT is detected. When the open CT condition is removed (that is, the previously open CT is
reconnected), the functions remain blocked for a specified interval of time, which is also defined by a
setting (tOCTResetDelay). This is to prevent an eventual mal-operation after the reconnection of the
previously open CT secondary circuit.
The open CT algorithm provides detailed information about the location of the defective CT
secondary circuit. The algorithm clearly indicates the IED side, CT input and phase in which an open
CT condition has been detected. These indications are provided via the following outputs from the
Transformer differential protection function:
1. Output OPENCT provides instant information to indicate that an open CT circuit has been
detected.
2. Output OPENCTAL provides a time-delayed alarm that the open CT circuit has been detected.
Time delay is defined by the parameter tOCTAlarmDelay.
3. Integer output OPENCTIN provides information on the local HMI regarding which open CT
circuit has been detected (1=CT input No 1; 2=CT input No 2).
4. Integer output OPENCTPH provides information on the local HMI regarding in which phase an
open CT circuit has been detected (1=Phase L1; 2= Phase L2; 3= Phase L3).
Once the open CT condition is declared, the algorithm stops to search for further open CT circuits. It
waits until the first open CT circuit has been corrected. Note that once the open CT condition has
been detected, it can be reset automatically within the differential function. It is not possible to
externally reset an open CT condition. To reset the open CT circuit alarm automatically, the following
conditions must be fulfilled:
If an open CT has been detected in a separate group of three CTs, the algorithm is reset either when
the missing current returns to the normal value, or when all three currents become zero. After the
reset, the open CT detection algorithm starts again to search for open CT circuits within the protected
zone.
The simplified internal logics, for transformer differential protection are shown in the following figures.
IDL2
individual windings
Open CT logic on W2 side
phase current
IDL1MAG
Fundamental frequency (phasor
based) Diff current, phase L1 &
ratio
IDL2MAG
Fundamental frequency (phasor
based) Diff current, phase L2 &
phase current contributions from
individual windings
IDL3MAG
Fundamental frequency (phasor
based) Diff current, phase L3 &
phase current contributions from
individual windings
MAX IBIAS
en06000554-3-en.vsd
IEC06000544 V3 EN-US
Figure 48: Treatment of measured currents within IED for transformer differential function
Figure 48 shows how internal treatment of measured currents is done in case of a two-winding
transformer.
The following currents are inputs used in the power transformer differential protection function. They
must all be expressed in power system (primary) A.
1. Instantaneous values of currents (samples) from the HV, and LV sides for two-winding power
transformers, and from the HV, the first LV, and the second LV side for three-winding power
transformers.
2. Currents from all power transformer sides expressed as fundamental frequency phasors with
their real and imaginary parts. These currents are calculated within the protection function by the
fundamental frequency Fourier filters.
3. Negative sequence currents from all power transformer sides expressed as phasors. These
currents are calculated within the protection function by the symmetrical components module.
1. Calculates three fundamental frequency differential currents and one common bias current. The
zero-sequence component can optionally be eliminated from each of the three fundamental
frequency differential currents and at the same time from the common bias current.
2. Calculates three instantaneous differential currents. They are used for harmonic, and waveform
analysis. Instantaneous differential currents are useful for post-fault analysis using disturbance
recording
3. Calculates negative-sequence differential current. Contributions to it from both (all three) power
transformer sides are used by the internal/external fault discriminator to detect and classify a
fault as internal or external.
BLKUNRES
IdUnre a TRIPUNREL1
b>a AND
b
IDL1MAG
IBIAS STL1
AND
BLOCK
BLKRES
TRIPRESL1
AND
OR 1
IDL1
to fault logic
2nd BLK2HL1
Switch on
Harmonic
Wave BLKWAVL1
block
5th BLK5HL1
Harmonic
Cross Block
Cross Block to L2 or L3
from L2 or L3 AND
OR
AND
OpCrossBlock=On
en06000545.vsd
IEC06000545 V1 EN-US
Figure 49: Transformer differential protection simplified logic diagram for Phase L1
Internal/ EXTFAULT
Neg.Seq. Diff External INTFAULT
Current Fault
Contributions discrimin
ator TRNSSENS
t
&
OpNegSeqDiff=On
IBIAS
a
b>a
b
Constant
TRNSUNR
STL1 &
STL2
>1
STL3
IEC05000167-2-en.vsd
IEC05000167-TIFF V2 EN-US
Figure 50: Transformer differential protection simplified logic diagram for external/internal fault
discriminator
TRIPRESL1
TRIPRESL2 TRIPRES
OR
TRIPRESL3
TRIPUNREL1
TRIPUNREL2 TRIPUNRE
OR
TRIPUNREL3
TRIP
TRNSSENS OR
TRNSUNR
en05000278.vsd
IEC05000278 V1 EN-US
STL1
STL2 START
OR
STL3
BLK2HL1
BLK2HL2 BLK2H
OR
BLK2HL3
BLK5HL1
BLK5HL2 BLK5H
OR
BLK5HL3
BLKWAVL1
BLKWAVL2 BLKWAV
OR
BLKWAVL3
IEC05000279-2-en.vsd
IEC05000279-TIFF V2 EN-US
1. The three fundamental frequency differential currents are applied in a phase-wise manner to two
limits. The first limit is the operate-restrain characteristic, while the other is the high-set
unrestrained limit. If the first limit is exceeded, a start signal START is set. If the unrestrained
limit is exceeded, an immediate unrestrained trip TRIPUNRE and common trip TRIP are issued.
2. If a start signal is issued in a phase the harmonic and the waveform block signals are checked.
Only a start signal, which is free of all of its block signals can result in a trip command. If the
cross-block logic scheme is applied, then only if all phases with set start signal are free of their
respective block signals, a restrained trip TRIPRES and common trip TRIP are issued
3. If a start signal is issued in a phase, and the fault has been classified as internal, then any
eventual block signals are overridden and unrestrained negative-sequence trip TRNSUNR and
common trip TRIP are issued without any further delay. This feature is called the unrestrained
negative-sequence protection 110% bias.
4. The sensitive negative sequence differential protection is independent of any start signals. It is
meant to detect smaller internal faults such as turn-to-turn faults, which are often not detected
by the traditional differential protection. The sensitive negative sequence differential protection
starts whenever both contributions to the total negative sequence differential current (that must
be compared by the internal/external fault discriminator) are higher than the value of the setting
IMinNegSeq. If a fault is positively recognized as internal, and the condition is stable with no
interruption for at least one fundamental frequency cycle the sensitive negative sequence
differential protection TRNSSENS and common trip TRIP are issued. This feature is called the
sensitive negative sequence differential protection.
5. If a start signal is issued in a phase (see signal STL1), even if the fault has been classified as an
external fault, the instantaneous differential current of that phase (see signal IDL1) is analyzed
for the 2nd and the 5th harmonic contents (see the blocks with the text inside: 2nd Harmonic;
Wave block and 5th Harmonic). If there is less harmonic pollution. than allowed by the settings
I2/I1Ratio, and I5/I1Ratio, (then the outputs from the blocks 2nd harmonic and 5th harmonic is
0) then it is assumed that a minor simultaneous internal fault must have occurred. Only under
these conditions a trip command is allowed (the signal TRIPRESL1 is = 1). The cross-block logic
scheme is automatically applied under such circumstances. (This means that the cross block
signals from the other two phases L2 and L3 is not activated to obtain a trip on the TRIPRESL1
output signal in figure 49)
6. All start and blocking conditions are available as phase segregated as well as common (that is
three-phase) signals.
IDL1 MAG
a
a>b
I Diff Alarm b
IDL3 MAG
a
a>b
I Diff Alarm b
en06000546.vsd
IEC06000546 V1 EN-US
M13046-1 v15
SYMBOL-CC V2 EN-US
High impedance differential protection, single phase (HZPDIF) functions can be used when the
involved CT cores have the same turns ratio and similar magnetizing characteristics. It utilizes an
external CT secondary current summation by wiring. Actually all CT secondary circuits which are
involved in the differential scheme are connected in parallel. External series resistor, and a voltage
dependent resistor which are both mounted externally to the IED, are also required.
The external resistor unit shall be ordered under IED accessories in the Product Guide.
HZPDIF
ISI* TRIP
BLOCK ALARM
BLKTR MEASVOLT
IEC05000363-2-en.vsd
IEC05000363 V2 EN-US
PID-6990-INPUTSIGNALS v1
PID-6990-OUTPUTSIGNALS v1
PID-6990-SETTINGS v1
M13075-3 v11
High impedance protection system is a simple technique which requires that all CTs, used in the
protection scheme, have relatively high knee point voltage, similar magnetizing characteristic and the
same ratio. These CTs are installed in all ends of the protected object. In order to make a scheme all
CT secondary circuits belonging to one phase are connected in parallel. From the CT junction points
a measuring branch is connected. The measuring branch is a series connection of one variable
setting resistor (or series resistor) RS with high ohmic value and an over-current element. Thus, the
high impedance differential protection responds to the current flowing through the measuring branch.
However, this current is result of a differential voltage caused by this parallel CT connection across
the measuring branch. Non-linear resistor (that is, metrosil) is used in order to protect entire scheme
from high peak voltages which may appear during internal faults. Typical high impedance differential
scheme is shown in Figure 55. Note that only one phase is shown in this figure.
RS
3 U
I
1
I> (50) 5
2
GUID-5CEAF088-D92B-45E5-B98F-3083894A694C V1 EN-US
1. shows one main CT secondary winding connected in parallel with all other CTs, from the same
phase, connected to this scheme.
2. shows the scheme earthing point.
It is of utmost importance to insure that only one earthing point exists in such
protection scheme.
3. shows the setting (stabilizing) resistor RS.
4. shows the over-current measuring element.
Due to the parallel CT connections the high impedance differential relay can only measure one
current and that is the relay operating quantity. That means that there is no any stabilizing quantity
(that is, bias) in high-impedance differential protection schemes. Therefore in order to guaranty the
stability of the differential relay during external faults the operating quantity must not exceed the set
pickup value. Thus, for external faults, even with severe saturation of some of the current
transformers, the voltage across the measuring branch shall not rise above the relay set pickup
value. To achieve that a suitable value for setting resistor RS is selected in such a way that the
saturated CT secondary winding provides a much lower impedance path for the false differential
current than the measuring branch. In case of an external fault causing current transformer
saturation, the non-saturated current transformers drive most of the spill differential current through
the secondary winding of the saturated current transformer and not through the measuring brunch of
the relay. The voltage drop across the saturated current transformer secondary winding appears also
across the measuring brunch, however it will typically be relatively small. Therefore, the pick-up value
of the relay has to be set above this false operating voltage.
See the application manual for operating voltage and sensitivity calculation.
The logic diagram shows the operation principles for the 1Ph High impedance differential protection
function HZPDIF, see Figure 56.
The function utilizes the raw samples from the single phase current input connected to it. Thus the
twenty samples per fundamental power system cycle are available to the HZPDIF function. These
current samples are first multiplied with the set value for the used stabilizing resistor in order to get
voltage waveform across the measuring branch. The voltage waveform is then filtered in order to get
its RMS value. Note that used filtering is designed in such a way that it ensures complete removal of
the DC current component which may be present in the primary fault current. The voltage RMS value
is then compared with set Alarm and Trip thresholds. Note that the TRIP signal is intentionally
delayed on drop off for 30 ms within the function. The measured RMS voltage is available as a
service value from the function. The function has block and trip block inputs available as well.
IEC05000301 V1 EN-US
Figure 56: Logic diagram for 1Ph High impedance differential protection HZPDIF
M13081-1 v13
1) The value U2Trip/ R should always be lower than Stabilizing resistor thermal rating to allow continuous activation
during testing. If this value is exceeded, testing should be done with a transient faults. Typical value for the thermal
rating of the resistor is 100W.
7.3.2 Identification
M14843-1 v6
SYMBOL-AA V1 EN-US
M13047-3 v20
Restricted earth-fault protection, low-impedance function (REFPDIF) can be used on all directly or
low-impedance earthed windings. The REFPDIF function provides high sensitivity and high speed
tripping as it protects each winding separately and thus does not need inrush stabilization.
The REFPDIF function is a percentage biased function with an additional zero sequence current
directional comparison criterion. This gives excellent sensitivity and stability during through faults.
REFPDIF can also protect autotransformers. Five currents are measured at the most complicated
configuration as shown in Figure 57.
CT CT
YNdx
CT CB CB
Y d
CB CB
Autotransformer
CT
IED
IEC05000058-2-en.vsd
IEC05000058-2 V1 EN-US
REFPDI F
I3P* TRIP
I3PW1CT1* START
I3PW1CT2* DIROK
I3PW2CT1* BLK2H
I3PW2CT2* IRES
BLOCK IN
IBIAS
IDIFF
ANGLE
I2RATIO
IEC06000251-3-en.vsdx
IEC06000251 V3 EN-US
PID-7411-INPUTSIGNALS v1
PID-7411-OUTPUTSIGNALS v1
PID-7411-SETTINGS v1
7.3.8.1 Fundamental principles of the restricted earth fault protection M5447-3 v16
Restricted earth fault protection, low impedance function (REFPDIF) detects earth faults on earthed
power transformer windings, most often an earthed star winding. REFPDIF is a unit protection of the
differential type. Since REFPDIF is based on the zero sequence current, which theoretically only
exists in case of an earth fault, REFPDIF can be made very sensitive regardless of normal load
currents. It is the fastest protection a power transformer winding can have. The high sensitivity and
the high speed tend to make such a protection unstable. Special measures must be taken to make it
insensitive to conditions for which it should not operate, for example, heavy through faults of phase-
to-phase type or heavy external earth faults.
REFPDIF is a differential protection of the low impedance type. All three-phase currents, and the
neutral point current, must be fed separately to REFPDIF. The fundamental frequency components of
all currents are extracted from all input currents, while other eventual zero sequence components,
such as the 3rd harmonic currents, are fully suppressed. Then the residual current phasor is
calculated from the three line current phasors. This zero sequence current phasor is added to the
neutral current vectorially, in order to obtain differential current.
The following facts may be observed from Figure 59 and Figure 60, where the three line CTs are
shown as connected together in order to measure the residual 3Io current, for the sake of simplicity.
Power Izs1
L2 L2
system
Izs1 L3
L3
3Izs1
zone of protection
Izs2 Izs1
L1 L1
Power Izs2 Izs1
L2 L2
system
Izs2 Izs1 L3
L3
3Izs1
1. For an external earth fault (Figure 59), the residual current 3Io and the neutral current IN have
equal magnitude, but they are seen within the IED as 180 degrees out-of-phase if the current
transformers are connected as in Figure 59, which is the Hitachi Power grids recommended
connection. The differential current becomes zero as both CTs ideally measure exactly the same
component of the earth fault current.
2. For an internal fault, the total earth fault current is composed generally of two zero sequence
currents. One zero sequence current (3IZS1) flows towards the power transformer neutral point
and into the earth, while the other zero sequence current (3IZS2) flows into the connected power
system. These two primary currents can be expected to have approximately opposite directions
(about the same zero sequence impedance angle is assumed on both sides of the earth fault).
However, on the secondary CT sides of the current transformers, they will be approximately in
phase if the current transformers are oriented as in Figure 57, which is the orientation
recommended by Hitachi Power grids. The magnitudes of the two currents may be different,
dependent on the magnitudes of zero sequence impedances on both sides. No current can flow
towards the power system, if the only point where the system is earthed, is at the protected
power transformer. Likewise, no current can flow into the power system, if the winding is not
connected to the power system (circuit breaker open and power transformer energized from the
other side).
3. For both internal and external earth faults, the current in the neutral connection IN always has
the same direction, which is towards the earth (except in case of autotransformers where the
direction can vary).
4. The two internally processed zero sequence currents are 3Io and IN. The vectorial sum is the
REFPDIF differential current, which is equal to Idiff = IN +3Io .
The line zero sequence (residual) current is calculated from 3 line (terminal) currents. A bias quantity
must give stability against false operations due to high through fault currents. To stabilize REFPDIF
at external faults, an operate-bias characteristic is used.
REFPDIF should also be stable against heavy phase-to-phase internal faults, not including earth.
These faults may also give false zero sequence currents due to saturated line CTs. Such faults,
however are without neutral current, and can thus be eliminated as a source of danger.
As an additional measure against unwanted operation, a directional check is made in agreement with
the above points 1 and 2. Operation is only allowed if the currents 3Io and IN (as shown in Figure 59
and Figure 60) are both within the operating region. By taking a smaller ROA, REFPDIF can be
made more stable under heavy external fault conditions, as well as under the complex conditions,
when external faults are cleared by other protections.
7.3.8.2 Restricted earth fault protection, low impedance differential protection M5447-20 v14
Restricted earth fault protection, (REFPDIF) is a protection of low impedance differential type, a unit
protection, whose settings are independent of any other protection. It has some advantages
compared to the transformer differential protection. It is less complicated, as no current phase
correction or magnitude correction is needed, not even in the case of an eventual on-load tap
changer (OLTC). REFPDIF is not sensitive to inrush and overexcitation currents. The thing to take
into account is an eventual current transformer saturation.
The differential protection REFPDIF calculates a differential current and a bias current. In case of
internal earth faults, the differential current is theoretically equal to the total earth fault current. The
bias to give stability to REFPDIF. The bias current is a measure of how high the currents are and how
difficult the conditions are under which the CTs operate. With a high bias, difficult conditions can be
suspected, and it will be more likely that the calculated differential current has a component of a false
current, primarily due to CT saturation. This “law” is formulated by the operate-bias characteristic.
This characteristic divides the Idiff - Ibias plane in two areas. The area above the operate-bias
characteristic is the operate area (trip), while the one below is the restrain (block) area, see Figure
62.
End of zone 1:
Endzone1 = 125%
End of zone 2:
Endzone2 =
(100 − IdMin)
EndZone2 = 125 +
0.7
IECEQUATION20201 V1 EN-US (Equation 26)
SlopeSection2:
The slope in section 2 (see Figure 62) of operate-restrain characteristic is fixed to 70%. The slope
section 2, starts at end of zone 1, continues until end of zone 2.
SlopeSection3:
The slope in section 3 (see Figure 62) of operate-restrain characteristic is fixed to 100%. The slope
section 3, starts at end of zone 2 and continues.
REFPDIF uses an operate-bias characteristic shown in Figure 62, using a setting IdMin see Table 7.
IdMin default IdMin min (zone IdMin max (zone End of zone 1 Slope section 2 Slope section 3
(zone 1) 1) 1) (fixed) (fixed) (fixed)
% of IBase % of IBase % of IBase % of IBase % of IBase % of IBase
10 4 100 125 70 100
IEC20000410-1-en.vsdx
IEC20000410 V1 EN-US
The highest individual current contribution is taken as a common bias (restrain) current among all
phase currents or neutral current. This "maximum principle" makes the differential protection more
secure, with less risk to operate for external faults and in the same time brings more meaning to the
breakpoint settings of the operate-restrain characteristic.
The differential current (operate current), as a fundamental frequency phasor, is calculated as (with
designations as in Figure 59 and Figure 60):
Idiff = IN + 3 Io
EQUATION1533 V1 EN-US (Equation 27)
where:
If there are two three-phase CT inputs, as in breaker-and-a-half configurations, then their respective
residual currents are added within the REFPDIF function so that:
where the signals are defined in the input and output signal tables for REFPDIF.
The bias current is a measure (expressed internally as a true fundamental frequency current in
Amperes) of how difficult the conditions are under which the instrument current transformers operate.
Dependent on the magnitude of the bias current, the corresponding zone (section) of the operate-
bias characteristic is applied, when deciding whether to trip, or not to trip. In general, the higher the
bias current, the higher the differential current required to produce a trip.
The bias current is the highest current of all separate input currents to REFPDIF, that is, of current in
phase L1, phase L2, phase L3, and the current in the neutral point (designated as IN in Figure and
in Figure Figure).
If there are two feeders included in the zone of protection of REFPDIF, as in case of an auto-
transformer with two feeders included on both sides, then the respective bias current is found as the
relatively highest of the following currents:
1
current 1 = max( I 3PW 1CT1)
CTFactor Pr i1
EQUATION1526 V2 EN-US (Equation 28)
1
current 2 = max( I 3PW 1CT 2)
CTFactor Pr i 2
EQUATION1527 V2 EN-US (Equation 29)
1
current 3 = max( I 3PW 2CT1)
CTFactorSec1
EQUATION1528 V2 EN-US (Equation 30)
1
current 4 = max( I 3PW 2CT 2)
CTFactorSec2
EQUATION1529 V2 EN-US (Equation 31)
current 5 = IN
EQUATION1530 V2 EN-US (Equation 32)
The bias current is thus generally equal to none of the input currents. If all primary ratings of the CTs
were equal to IBase, then the bias current would be equal to the highest current in Amperes. IBase
shall be set equal to the rated current of the protected winding where REFPDIF function is applied.
External faults are more common than internal earth faults for which the restricted earth fault
protection should operate. It is important that the restricted earth fault protection remains stable
during heavy external earth and phase-to-phase faults, and also when such a heavy external fault is
cleared by some other protection such as overcurrent, or earth fault protection. The conditions during
a heavy external fault, and particularly immediately after the clearing of such a fault may be complex.
The circuit breaker’s poles may not open exactly at the same moment, some of the CTs may still be
highly saturated, and so on.
The detection of external earth faults is based on the fact that for such a fault a high neutral current
appears first, while a false differential current only appears if one or more current transformers
saturate.
An external earth fault is thus assumed to have occurred when a high neutral current suddenly
appears, while at the same time the differential current Idiff remains low, at least for a while. This
condition must be detected before a trip request is placed within REFPDIF. Any search for external
fault is aborted if a trip request has been placed. A condition for a successful detection is that it takes
not less than 4ms for the first CT to saturate.
For an internal earth fault, a true differential current develops immediately, while for an external fault
it only develops if a CT saturates. If a trip request comes first, before an external fault could be
positively detected, then it must be an internal fault.
If an external earth fault has been detected, then the REFPDIF is temporarily desensitized.
For an external earth faults with no CT saturation, the residual current in the lines (3Io) and the
neutral current (IN in Figure 59) are theoretically equal in magnitude and are 180 degrees out-of-
phase. The current in the neutral (IN) serves as a directional reference because it has the same
direction for both internal and external earth faults. The directional criterion in REFPDIF protection
makes it a current-polarized protection.
However, if one or more CTs saturate under external fault conditions, then the measured currents 3Io
and IN may no longer be equal, nor will their positions in the complex plane be exactly 180 degrees
apart. There is a risk that the resulting false differential current Idiff enters the operate area of the
operate-restrain characteristic under external fault conditions. If this happens, a directional test may
prevent a malfunction.
1. a trip request signal has been issued (REFPDIF function START signal set to 1)
2. the residual current in lines (3Io) is at least 3% of the IBase current.
If a directional check is either unreliable or not possible to do, due to too small currents, then the
direction is cancelled as a condition for an eventual trip.
If a directional check is executed, the REFPDIF protection operation is only allowed if currents 3Io
and IN (as seen in Figure 59 and Figure 60) are both within the operating region determined by the
set value of ROA, in degrees.
ROA = 60 to 119 deg; where ROA stands for Relay Operate Angle.
long duration, but the current through the neutral CT does not have either the same DC component
or the same amplitude and the risk for saturation of this CT is not as high. As a result, the differential
current due to the saturation may be so high that it reaches the operate characteristic. A calculation
of the content of 2nd harmonic in the neutral current is made when the neutral current, residual
current and bias current are within some windows and some timing criteria are fulfilled. If the ratio
between second and fundamental harmonic exceeds the preset value of 40% 40%, REFPDIF is
blocked.
1. Check if current in the neutral Ineutral (IN) is less than 50% of the base sensitivity Idmin. If yes,
only service values are calculated, and rest of the REFPDIF algorithm is not executed.
2. If current in the Ineutral (IN) is more than 50% of Idmin, then determine the bias current Ibias.
3. Determine the differential (operate) current Idiff as a phasor, and calculate its magnitude.
4. Check if the point P(Ibias, Idiff) is above the operate-bias characteristic. If yes, increment the trip
request counter by 1. If the point P(Ibias, Idiff) is found to be below the operate-bias
characteristic, then the trip request counter is reset to zero.
5. If the trip request counter is still zero, search for an eventual heavy external earth fault. The
search is only made if the neutral current is at least 50% of the Idmin current. If an external earth
fault has been detected, a flag is set which remains set until the external fault has been cleared.
The external fault flag is reset to zero when Ineutral falls below 50% of the base sensitivity
Idmin. Any search for an external fault is aborted if trip request counter is greater than zero.
6. As long as the external fault persists, an additional temporary trip condition is introduced. This
means that REFPDIF is temporarily desensitized.
7. If point P(Ibias, Idiff) is found to be above the operate-bias characteristic), so that trip request
counter is greater than zero, a directional check can be made. The directional check is made
only if Iresidual (3Io) is more than 3% of the IBase current. If the result of the check means
“external fault”, then the internal trip request is reset. If the directional check cannot be
executed, then direction is no longer a condition for a trip.
8. When neutral current, residual current and bias current are within some windows and some
timing criteria are fulfilled, the ratio of 2nd to fundamental harmonic is calculated. If it is found to
be above 40%, the trip request counter is reset and TRIP remains zero.
9. If point P(Ibias, Idiff) is found to be above the operate-bias characteristic), a directional check
can be made. The directional check is made only if Iresidual (3Io) is more than 3% of the IBase
current. If the result of the check means “external fault”, then the internal trip request is reset. If
the directional check cannot be executed, then the direction is no longer a condition for a trip.
10. Finally, the trip request counter is checked. If the trip request counter is greater or equal than 2
and at the same time the actual bias current is at least 50% of the highest bias current Ibiasmax
(Ibiasmax is the highest recording of any of the three phase currents measured during the
disturbance), REFPDIF will set output TRIP to 1. Otherwise, the TRIP signal remains zero.
11. Finally, a check is made if the trip request counter is equal to, or higher than 2. If yes, and at the
same instance of time tREFtrip, the actual bias current at this instance of time tREFtrip is at least
50% of the highest bias current Ibiasmax (Ibiasmax is the highest recording of any of the three
phase currents measured during the disturbance), then REFPDIF sets output TRIP to 1. If the
counter is less than 2, the TRIP signal remains zero.
M13062-1 v23
7.4.1 Identification
GUID-3081E62B-3E96-4615-97B8-2CCA92752658 v2
Additional security logic for differential protection (LDRGFC) can help the security of the protection
especially when the communication system is in abnormal status or for example when there is
unspecified asymmetry in the communication link. It helps to reduce the probability for mal-operation
of the protection. LDRGFC is more sensitive than the main protection logic to always release
operation for all faults detected by the differential function. LDRGFC consists of four sub functions:
Phase-to-phase current variation takes the current samples as input and it calculates the variation
using the sampling value based algorithm. Phase-to-phase current variation function is a major one
to fulfill the objectives of the startup element.
Zero sequence criterion takes the zero sequence current as input. It increases the security of
protection during the high impedance fault conditions.
Low voltage criterion takes the phase voltages and phase-to-phase voltages as inputs. It increases
the security of protection when the three-phase fault occurred on the weak end side.
Low current criterion takes the phase currents as inputs and it increases the dependability during the
switch onto fault case of unloaded line.
The differential function can be allowed to trip as no load is fed through the line and protection is not
working correctly.
Features:
• Startup element is sensitive enough to detect the abnormal status of the protected system
• Startup element does not influence the operation speed of main protection
• Startup element would detect the evolving faults, high impedance faults and three phase fault on
weak side
• It is possible to block the each sub function of startup element
• Startup signal has a settable pulse time
LDRGFC
I3P* START
U3P* STCVL1L2
BLOCK STCVL2L3
BLKCV STCVL3L1
BLKUC STUC
BLK3I0 ST3I0
BLKUV STUV
REMSTUP
IEC14000015-1-en.vsd
IEC14000015 V1 EN-US
7.4.4 Signals
PID-3558-INPUTSIGNALS v9
PID-3558-OUTPUTSIGNALS v9
7.4.5 Settings
PID-3558-SETTINGS v9
The additional security logic for differential protection (LDRGFC) takes the current samples, current
RMS values, phase voltage values, phase-to-phase voltage values, zero sequence current and
remote side startup signals as inputs.
Startup signal becomes activated when any one of the current variation startup signal, zero
sequence current startup signal, voltage startup signal, and current startup signal is activated.
Phase-to-phase current variation takes current samples and generates the startup signal by
comparing with the start value.
If the zero sequence current value is greater than the start value of zero sequence current then the
zero sequence current startup signal will be activated.
Voltage startup signal becomes activated when the any of phase voltage and line voltage is less than
the voltage start value and the remote startup signal has to be activated.
Current startup signal becomes activated when the current value in all phases is less than current
start value.
The phase-to-phase current variation is the main startup element. It covers most of the abnormal
conditions of the system. The phase-to-phase current variation fails in high impedance faults, three-
phase faults on weak side and switch onto fault on unloaded line because of low sensitivity in these
cases.
Phase-to-phase current variation takes the current samples as input and the signal is evaluated
using the sampling value based algorithm.
Where:
ΔiФФ sampling value of phase-to-phase current variation
ΔIZD setting of fixed threshold, which corresponds to setting ICV>. The default value for the setting is
0.2·IBase, where IBase is the base current.
ΔIT float threshold
1 2T -1
DI T = å | DiFF (t - n) |
T n =T
EQUATION2256 V1 EN-US
Where:
T count of sample values in one cycle
Di (k ) = [i ( k ) - i (k - N )] - [i (k - N ) - i (k - 2 N )]
= i ( k ) - 2i ( k - N ) + i (k - 2 N )
EQUATION2257 V1 EN-US
tCV
STCVL1L2
t
cont
OR STCV
cont
IEC10000295-1-en.vsd
IEC10000295 V1 EN-US
Zero sequence criterion is mainly for detection of remote IED high resistance faults or some gradual
faults. The criterion takes the zero sequence current as input. Zero sequence current is compared
with I3I0> for the t3I0 time to generate the zero sequence current startup signal.
I3P a
a>b t3I0
I3IO> b ST3I0
AND t
BLK3I0
BLOCK OR
IEC09000778-2-en.vsd
IEC09000778 V2 EN-US
t3I0 is the time setting for the zero sequence current criterion.
The zero sequence current criterion can be blocked by activating the BLK3I0 input signal.
Low voltage criterion is mainly for detection of the three phase faults occurring on weak side with pre-
fault no load condition. The low voltage criterion takes the voltage phase values, voltage phase-to-
phase values and remote startup signals as inputs. The logic for low voltage criterion is shown below:
U3P (UPhN) a
a<b
UPhN< b
OR
U3P (UPhPh) a
a<b
UPhPh< b
tUV STUV
REMSTUP (Recived)
AND t
BLKUV
BLOCK OR
IEC09000779-2-en.vsd
IEC09000779 V2 EN-US
If there are more than one remote IED, all the startup signals of the remote ends are logically OR to
obtain the REMSTUP signal from the remote side as input.
The current in each phase is compared to the set current level. If all currents are below setting IUC<,
the STUC output is activated after the set delay tUC.
I3P
a
a<b tUC
IUC< b STUC
AND t
BLKUC
BLOCK OR
IEC09000780-2-en.vsd
IEC09000780 V2 EN-US
The configuration for the additional security logic for differential protection is shown in Figure 68. The
function will release tripping of the line differential protection up to the end of timer tStUpReset.
Phase-phase STCV
i
current variation
IEC10000296-3-en.vsd
IEC10000296 V3 EN-US
Figure 68: Additional security logic for differential protection. Logic diagram for start up
element.
7.5.1 Identification
GUID-BB53C1B5-E5D4-4351-83E7-FFEDD54AE584 v1
SYMBOL-BB V1 EN-US
The PSTPDIF function can be used as a differential protection for any two-winding three-phase
power transformers. It is especially suitable for the differential protection of phase-shifting
transformers (PST), which is also called phase-angle regulating transformers (PAR). This function is
similar to the standard transformer differential protection function T2WPDIF (or 87T), but it can be
applied to any type and construction of PST.
The differential protection is self-adaptive. It automatically learns and adopts to the actual
transformation ratio and phase-angle shift across the protected transformer. Thus, any PST
regardless of its construction principles (that is, symmetrical or asymmetrical) and design details (that
is, single-core, double-core or even of complex design) can be entirely protected by using the
PSTPDIF function.
The function is provided with two sets of three-phase current inputs (one from each side of the PST).
Therefore, either the CTs located in bushings of the PST or in series with them shall be used. Both
current inputs are provided with percentage bias restraint features. Note that two VT inputs, one from
each side, shall also be connected to the function. Either single-phase or three-phase VT inputs can
be used.
two-winding PST
transformer
IEC18000153-1-en.vsdx
IEC18000153 V1 EN-US
IEC18000154-1-en.vsdx
IEC18000154 V1 EN-US
Stabilization is included for inrush and over-excitation currents, and cross-blocking is also included.
Adaptive stabilization is included for the system recovery inrush and CT saturation during external
faults. A high set unrestrained differential current protection element is included for higher speed
tripping at high internal fault currents.
In order for all theoretical explanation given in this document to be true, the following CT and VT
connection rules shall be adopted:
• Currents and voltages from the source side (S-side) should be connected to winding one (W1)
inputs on the PSTPDIF function block. Individual phases of the connected current and voltage
signals should be connected in the same sequence as the PST bushing markings on the
source-side of the PST, for example, S1, S2, or S3.
• Currents and voltages from the load side (L-side) should be connected to winding two (W2)
inputs on the PSTPDIF function block. Individual phases of the connected current and voltage
signals should be connected in the same sequence as the PST bushing markings on the load-
side of the PST, for example, L1, L2, or L3.
PSTPDIF
I3PW1* TRIP
I3PW2* TRIPRES
U3PW1* TRIPUNRE
U3PW2* TRNSUNR
BLOCK TRNSSENS
BLKRES START
BLKUNRES STL1
BLKNSUNR STL2
BLKNSSEN STL3
USEDFLT INTFAULT
STOPCOMP EXTFAULT
BLK2H
BLK2HL1
BLK2HL2
BLK2HL3
BLK5H
BLK5HL1
BLK5HL2
BLK5HL3
BLKWAV
BLKWAVL1
BLKWAVL2
BLKWAVL3
IDALARM
IDL1
IDL2
IDL3
IDL1MAG
IDL2MAG
IDL3MAG
IBIAS
IDNSMAG
IRATIO
IANGLE
URATIO
UANGLE
SELMEAS
DIFRATIO
DIFANGLE
IEC18000102-1-en.vsdx
IEC18000102 V1 EN-US
7.5.4 Signals
PID-7109-INPUTSIGNALS v1
PID-7109-OUTPUTSIGNALS v1
7.5.5 Settings
PID-7109-SETTINGS v1
PSTPDIF function is used to determine whether a fault is within the protected zone or outside of the
protected zone. The protected zone is limited by the position of current transformers (see Figure 71),
and in principle, it can include more objects than one transformer. For example, a series connection
of two transformers can be protected. If an internal fault occurs, the faulty part must be disconnected
immediately from the power system.
The main CTs should be star connected. The main CTs can be earthed either as ToObject or
FromObject. However, internally the differential function uses reference directions towards the
protected transformer on both sides (see Figure 71). Thus, the IED will always internally measure the
currents on both sides of the protected transformer with the same reference direction towards the
transformer windings as shown in Figure 71. For more information, see the Application manual.
PST
IW1 IW2
S L
Z1S1 Z1S2
E1S1 E1S2
Differential Relay
IEC18000155-1-en.vsdx
IEC18000155 V1 EN-US
For standard power transformers, the transformation ratio and the phase-angle shift is fixed by the
transformer design. These parameters are typically then entered as setting parameters into the
differential protection function for standard power transformers. The transformation ratio for a
standard power transformer may vary slightly if an on-load tap-changer (OLTC) is built inside the
protected power transformer. Some differential functions may also compensate for such ratio
variations utilizing additional setting parameter and actual position of the OLTC.
However, for a PST, both the transformation ratio and the phase-angle shift may vary considerably
during different operating conditions. These variations are typically achieved by using one or more
OLTCs inside the protected PST. Therefore, it is much more difficult to set the PST differential
function to accurately compensate for such variations. The PSTPDIF function utilizes the connected
voltages and currents from the two sides of the PST to estimate on-line these two parameters, that
is, transformation ratio and phase-angle shift. Note that the position of any built-in OLTCs is not
required for this estimation. By using current and voltage signals only the function becomes self-
adaptive and learns on-line the actual transformation ratio and phase-angle shift across the protected
PST.
Only when correct compensation for the protected transformer actual transformation ratio and phase
angle shift is made, the phase-wise differential currents can be calculated. Use of any external
auxiliary (interposing) current transformers is not required.
As per the default settings, the PSTPDIF function expects that connected voltages and currents from
the power system has direct phase rotation, that is, L1-L2-L3. For a power system that has an
inverse phase rotation, that is, L3-L2-L1, do the following settings to ensure proper operation of the
function:
• Connect individual phases of the connected current and voltage signals in the same sequence
as the PST bushing markings on both sides (that is, with inverse rotation).
• Change the global setting PhaseRotation from the default value Normal=L1L2L3 to
Inverse=L3L2L1. Note that the PhaseRotation setting is common for all analog preprocessing
function blocks. It is located under Primary system values in the setting tool.
• Change the PSTPDIF setting ReverseAngle from the default value Off to On.
Where,
S, U, I are the base (that is, rated) quantities for the respective sides.
Note that the base currents and voltages are typically entered for an OLTC position, which
corresponds to zero degree phase-angle shift across the PST. Namely, the PST is typically energized
at this tap position. These current and voltage values shall be entered as stated on the protected
transformer rating plate for this zero degree tap. For a standard two-winding transformer, the base
currents and voltages are typically entered for an OLTC position, which corresponds to the middle
position of OLTC.
Also, these quantities define the default PST transformation ratio in accordance with the following
equation:
The base quantities for the PSTPDIF function are set under Global Base Values in the Parameter
Setting tool.
Before calculating any differential current, the power transformer actual phase shift and actual
transformation ratio must be accounted for. This is done using the following equation.
Where,
IDL1 is the differential current phasor in phase L1 (in W1 side primary amperes)
IDL2 is the differential current phasor in phase L2 (in W1 side primary amperes)
IDL3 is the differential current phasor in phase L3 (in W1 side primary amperes)
IL1_W1 is the W1 current phasor in phase L1 (in W1 side primary amperes)
IL2_W1 is the W1 current phasor in phase L2 (in W1 side primary amperes)
IL3_W1 is the W1 current phasor in phase L3 (in W1 side primary amperes)
IL1_W2 is the W2 current phasor in phase L1 (in W2 side primary amperes)
IL2_W2 is the W2 current phasor in phase L2 (in W2 side primary amperes)
IL3_W2 is the W2 current phasor in phase L3 (in W2 side primary amperes)
MW1 and MW2 are 3×3 matrices with numerical coefficients
When zero-sequence current shall not be removed, Matrix M(θ) can be calculated as:
When zero-sequence current shall be removed from the respective side, Matrix M0(θ) can be
calculated as:
In Equation 33, the first winding (W1) is always taken as reference side both for current magnitudes
(W2 sides are transferred to W1 sides by a ratio factor) and for phase angle (W2 currents are rotated
towards the W1 currents by an angle θ).
The fundamental frequency differential currents are, in general, composed of currents of all
sequences, that is, positive-, negative-, and zero-sequence currents. If the zero-sequence currents
are eliminated from individual phase currents on any side (see "Optional elimination of zero-
sequence currents") by choosing appropriate calculation for matrix M(θ), then the differential currents
may consist only of positive- and negative-sequence currents.
As the W2 matrix coefficients (see Equation 34 or Equation 35) are dependent on the actual phase-
angle shift, they shall be calculated on-line all the time.
The fundamental frequency differential currents are the usual differential currents and their
magnitudes are applied phase-wise to the operate-restrain characteristic of the differential protection.
The magnitudes of the differential currents can be read as service values from the function and they
are available as outputs IDL1MAG, IDL2MAG, and IDL3MAG from the PSTPDIF function block. Note
that the service values are given in percent. To do that, the values obtained from Equation 33 are
multiplied by the factor 100/IBaseW1. These service values given in percent can also be connected to
the disturbance recorder and automatically recorded during any external or internal fault condition.
In Equation 33, the first term on the right hand side of the equation represents the total contribution
from the individual phase currents from the W1 side to the fundamental frequency differential
currents. The second term on the right hand side of the equation represents the total contribution
from the individual phase currents from the W2 side to the fundamental frequency differential
currents, compensated for transformer phase shift and transferred to the power transformer W1 side.
These current contributions are important because they are used for calculating the common bias
current.
There are totally six current contributions, which are the candidates for the common bias current. The
highest individual current contribution is considered as a common bias (restrain) current for all three
phases. This maximum principle makes the differential protection more secure, with less risk to
operate for external faults and brings more meaning to the breakpoint settings of the operate-restrain
characteristic and the cross-blocking logic.
If the zero-sequence currents are subtracted from the separate contributions to the total differential
current, then the zero-sequence component is automatically eliminated from the bias current. This
ensures that for secondary injection from one power transformer side the bias current is equal to the
highest differential current regardless of the fault type. During normal through-load operation of the
power transformer, the bias current is equal to the maximum load current from two transformer sides.
The magnitudes of the common bias (restrain) current expressed in HV side amperes can be read as
a service value from the function. At the same time, it is available as an output IBIAS from the
differential protection function block. Note that the service value is given in percent. To do that, the
maximum value obtained from Equation 33 is multiplied by the factor 100/IBaseW1. IBIAS can be
connected to the disturbance recorder and automatically recorded during any external or internal
fault condition.
PSTPDIF function continuously estimates the actual transformation ratio and phase-angle shift
across the PST by using positive-sequence currents and settable voltage phasors from two sides.
where IW1 and IW2 are positive sequence current phasors from two sides.
Due to used internal reference direction for currents, the W2 positive sequence
current phasor must be rotated for 180° before calculating the complex current ratio.
Now, the current based transformation ratio (I_Ratio), can be determined as a reciprocal value of the
magnitude of the complex current ratio and the phase-angle shift (I_Angle) as the phase angle of the
current complex ratio.
where UW1 and UW2 are two selected voltage phasors (one from each side).
Note that the function automatically compensate for √3 factor, which may be required depending on
whether phase-to-earth or phase-to-phase voltages from the two sides are used. Also, the function
automatically compensate for inherent phase shift between the selected phasors if voltages from
different phases are selected (for example, UL1 from W1 and UL3 from W2). For simplicity, such
compensation factors are not shown in the above equation.
Now, the voltage based transformation ratio (U_Ratio), can be determined as the magnitude of the
complex voltage ratio and the phase-angle shift (U_Angle) as the phase angle of the complex voltage
ratio.
Once these four values are known, the following logic is used to determine the actual transformation
ratio and the phase-angle shift across the protected PST:
USEDFLT
Selection SELMEAS
STOPCOMP Logic #1
DiffRatioMax*(UBW2/UBW1)
Default_Ratio (UBW2/UBW1)
U_Ratio (|UW2|/UW1|)
DIFRATIO
Low Pass Filter Value Limiter
I_Ratio (|IW2|/IW1|)
Freeze_Old_Value
DiffRatioMin* (UBW2/UBW1)
q-1
BLOCK
ReverseAngle
T=8 ms
+1 DiffAngleMax+DefaultPhShift
T=500 ms
-1
DefaultPhShift
Freeze_Old_Value
DiffAngleMin+DefaultPhShift
U_Ratio URATIO
-1
q
U_Angle UANGLE
I_Ratio IRATIO
I_Angle IANGLE
IEC18000156-1-en.vsdx
IEC18000156 V1 EN-US
Figure 72: Simplified logic to determine the actual transformation ratio and phase-angle shift
Selection Logic #1 shown in Figure 72 works with the priorities, as described below:
• If any of the two positive-sequence current magnitudes is greater than 160%, the old ratio and
phase angle are selected (that is, values are frozen).
• If both of the two positive-sequence current magnitudes are in between 10% and 160%, the
values obtained from the current calculation is used.
• If any of the two positive-sequence current magnitudes is less than 10%, the values obtained
from the voltage measurement shall be used if the voltages have appropriate magnitudes.
• If any of the two voltage phasor magnitudes is greater than 120%, the old ratio and phase angle
are selected (that is, values are frozen).
• If both of the two voltage phasor magnitudes are in between 70% and 120%, the values
obtained from the voltage calculation shall be used. Note that the automatic compensation for
√3 difference between phase-to-phase and phase-to-earth voltages is performed within the
function.
• If any of the two voltage phasor magnitudes is less than 70%, the default values that are
determined by the parameter settings are used.
The function provides service values through the integer output SELMEAS regarding which selection
is active at the time. This output has the following possible integer values:
Additionally, certain level of bias and differential current magnitudes can also
temporarily force use of old values. In this case, the output SELMEAS will have a
value eight.
If the binary input USEDFLT into the function has a logical value TRUE, it will force use of default
values, that is, determined by the settings, for the transformation ratio and the phase-angle shift as
inputs into the low-pass filter. In this case, the output SELMEAS will have a value one. For example,
this input can be used if the PSTPDIF function is used to protect a standard two-winding power
transformer with fixed values for the transformation ratio and the phase-angle shift.
If the binary input STOPCOMP into the function has a logical value TRUE, it will unconditionally force
use of old values (values are frozen), for the transformation ratio and the phase-angle shift as inputs
into the low-pass filter. In this case, the output SELMEAS will have a value sixteen. The input
STOPCOMP shall be used to test, for example, the operating characteristic of the PSTPDIF function
for a specific transformation ratio and phase-angle shift. This will prevent the function to compensate
ratio and angle by using injected currents during testing, which typically do not have any real
correlation to the protected transformer transformation ratio and phase-angle shift.
The calculated values from two positive-sequence current phasors are also available as service
values via outputs IRATIO and IANGLE. Angle value is given in degrees. When these two values
cannot be calculated, the output IRATIO has value ‘0’ and IANGLE has value ‘1000’.
Similarly, the calculated values using two voltage phasors are also available as service values via
outputs URATIO and UANGLE. Angle value is given in degrees. When these two values cannot be
calculated, the output URATIO has value ‘0’ and UANGLE has value ‘1000’.
When W2 phasor is leading W1 phasor, the angle will have positive sign and consequently, when W2
phasor is lagging the W1 phasor, the angle will have negative sign. These rules are applicable for
either current or voltage phasors and corresponds to the IEC/IEEE standard definition for phase
shifting transformers. Thus, the I_Angle when PST is loaded and U_Angle when PST is not loaded
will be positive for advanced mode of operation and negative for retard mode of operation. Therefore,
they typically shall have the same value and sign as stated on the PST rating plate for individual
OLTC positions. However, these conventions are valid only if positive-sequence voltages and
currents, that is, with phase rotation L1-L2-L3, are connected to the protected power transformer.
Once values for the transformation ratio and the phase angle are selected, they are further filtered
using a low-pass filter. Typically, this filter is quite slow and has a time constant of 500 ms.
Theoretically, approximately five times constants must elapse before the filter output values have
new and correct values after the step change of the filter input. On the other side, one OLTC
operation can take up to five seconds. Such filter time delay does not cause any practical issue for
the PSTPDIF function and ensures its proper operation under external and internal fault conditions.
However, when the function is blocked, either externally via dedicated binary input BLOCK or
internally from the IED, the time constant is reduced to 8 ms. By doing this, the function is practically
forced to learn the actual transformation ratio and phase-angle shift values faster. The time constant
reduction feature ensures that the function behaves correctly during the following circumstances:
• When the protection IED power supply is interrupted while the protected transformer is in
service (internal blocking will be active for a while)
• Any setting parameter within the IED is changed while the protected transformer is in service
(internal blocking will be active for a while)
• IED shall be tested on a real time digital simulator
• IED shall be tested by playing-back captured recording files from an existing PST installation
For the third and fourth cases, the IED configuration shall be arranged such that the PSTPDIF
function binary input BLOCK shall be pulsed for 50 ms at the beginning of the injection (that is, during
the pre-fault stage) to learn the actual transformation ratio and phase-angle shift before either
internal or external fault conditions are injected into the IED. The only pre-request is that the pre-fault
currents and voltages last longer than the blocking time (for example, longer than 50 ms).
• The filtered value for the transformation ratio is limited within the range defined by settings
DiffRatioMin and DiffRatioMax. This value is then given as a service value from the function
through the output DIFRATIO.
• The filtered value for an angle is multiplied by -1 (that is, sign of the angle is changed) when
setting ReverseAngle is set to Off. This default value shall be used when the direct sequence of
currents and voltages (that is, phase rotation L1-L2-L3), are connected to the protected
transformer. However, if the power system has inverse rotation (that is, phase rotation L3-L2-
L1), then ReverseAngle shall be set to On. In this case, the filtered value for the angle will not be
changed. This is required to get the correct direction for compensation in Equation 33 for the
phase-angle shift across PST depending on the actual phase rotation in the connected power
system. This angle value is also given as a service value from the function via the output
DIFANGLE in degrees.
The following values are considered from the algorithm of the PSTPDIF function:
• DIFRATIO is used as Ratio in the Equation 33, that is, Ratio = DIFRATIO.
• DIFANGLE is used as the angle θ in the equation 1 (that is, θ = DIFANGLE).
All service value outputs that are available from the function can be connected to the disturbance
recorder and automatically recorded during any external or internal fault condition. The SELMEAS
integer value shall be converted into separate binary signals using the integer to binary converter
function block and then connected as an individual binary signals into the disturbance recorder.
The zero-sequence currents can be explicitly eliminated from the differential currents and common
bias current calculation by dedicated parameter settings that are available for each sides separately.
• If a protected PST incorporates a closed, tertiary, delta winding, then enable subtraction of the
zero-sequence current on both sides.
• If a protected PST is of an asymmetrical design, then enable subtraction of the zero-sequence
current on both sides.
• If a protected PST is of a symmetrical design, then possibly the zero-sequence current
subtraction can be disabled on both sides.
Removing the zero-sequence current from the differential currents reduces the sensitivity of the
differential protection to some extent for internal earth faults. To counteract this effect to some extent,
the zero-sequence current is subtracted from the three fundamental frequency differential currents
and the bias current.
The unrestrained (that is, non-stabilized or instantaneous) part of the differential protection is used
for very high differential currents, where it should be beyond any doubt, that the fault is internal. This
settable limit is constant and not proportional to the bias current. Harmonic or any other restrain is
not applied to this limit, which is therefore allowed to trip the transformer instantaneously.
The restrained (stabilized) part of the differential protection compares the calculated fundamental
differential (operating) currents and the bias (restrain) current by applying them to the operate-
restrain characteristic. Practically, the magnitudes of the individual fundamental frequency differential
currents are compared with an adaptive limit. This limit is adaptive because it is dependent on the
bias (restrain) current magnitude. This limit is called the operate-restrain characteristic. It is
represented by a double-slope, double-breakpoint characteristic, as shown in Figure 73.
The restrained characteristic shown in Figure 73, is determined by the following five settings:
• IdMin (Sensitivity in section 1, as a multiple of transformer W1 side rated current set under the
parameter IBase in the GBASVAL group selected by parameter GlobalBaseSelW1)
• EndSection1 (End of section 1, as a multiple of transformer W1 side rated current set under the
parameter IBase in the GBASVAL group selected by parameter GlobalBaseSelW1)
• EndSection2 (End of section 2, as a multiple of transformer W1 side rated current set under the
parameter IBase in the GBASVAL group selected by parameter GlobalBaseSelW1)
• SlopeSection2 (Slope in section 2, operate current divided by restrain current in percent)
• SlopeSection3 (Slope in section 3, operate current divided by restrain current in percent)
1200
PROTECTION SETTINGS (Default): RATED CURRENT (A):
Idiff (operate
IdMin 0.20 200.00 W1 IBaseW1 1000.00
current) in %
EndSection1 1.25 1250.00
EndSection2 3.00 3000.00 Operate
SlopeSection2
SlopeSection3
40.0%
80.0%
40%
80% unconditionally
IdUnre 10.00 10000.00
1000
Operate
800
conditionally
600
No operation
400
Restrained limit
IdMin
EndSection2
SlopeSection2
EndSection1
0
0 200 400 600 800 1000 1200
IEC18000162-1-en.vsdx
IEC18000162 V1 EN-US
Figure 73: Description of the restrained and the unrestrained operate characteristics
Where,
DI operate
slope 100 0 0
DI restrain
IECEQUATION18042 V1 EN-US
The operate-restrain characteristic can be customized by the user. It is recommended to use the
default characteristic because it provides better results in most of the applications. The operate-
restrain characteristic has mainly three sections with a section-wise proportionality of the operate
value to the bias (restrain) current. The reset ratio in all parts of the characteristic is equal to 0.95.
Section 1: This section is the most sensitive part on the characteristic. Normal currents flow through
the protected circuit and its current transformers, and the risk for higher false differential currents is
relatively low. The slope in section 1 is always zero percent.
Section 2: In this section, a certain minor slope is introduced, which should cope with false differential
currents proportional to higher than normal currents through the current transformers.
Section 3: In this section, more pronounced slope is designed to result in a higher tolerance to the
substantial current transformer saturation at high through-fault currents, which may be expected.
• For internal faults, the operate (differential) currents are always with a good margin above the
operate-restrain characteristic.
• For external faults, the false operate currents are with a good margin below the operate-restrain
characteristic.
The differential protection can be temporarily desensitized by applying the adaptive DC biasing
method. When an external fault is detected, the adaptive DC biasing method will temporarily shift the
operate-restrain characteristic by adding DC components to the operate level IdMin. The DC
component is extracted online from the instantaneous differential currents and the highest DC in all
three phases is selected to be added to IdMin. This feature improves the security of the function for
external faults followed by CT saturation. The adaptive DC biasing will be reset if either of the
following conditions is fulfilled:
• The external fault signal disappears and DC components do not exist in the phase currents.
• The fundamental frequency differential currents become greater than the bias current.
As the negative-sequence currents form the symmetrical three-phase current system on each
transformer side (that is, negative-sequence currents in each phase will have the same magnitude
and phase angle displaced with 120 degrees from each other), it is only necessary to calculate one
negative-sequence differential current for the first phase.
The negative-sequence based differential current is calculated by using the fact that it is rotated by
the same angle, but in the opposite direction as the positive sequence currents. The negative-
sequence fault currents must first be referred to the same phase reference side and put to the same
magnitude reference. This can be calculated by using the following complex (that is, phasor)
equation:
where,
IDNS is the negative-sequence differential current phasor (in W1 side primary amperes)
INS_W1 is the W1 negative-sequence current phasor for phase L1 (in W1 side primary amperes)
INS_W2 is the W2 negative-sequence current phasor for phase L1 (in W2 side primary amperes)
ɵ is the actual phase angle shift across PST in degrees
Ratio is the actual transformation ratio among two sides of the PST
The magnitudes of the negative-sequence differential current can be read as service values from the
function. It is also available as the output IDNSMAG from the differential protection function block
and its value is given in percent. To get that, the value obtained from Equation 36 is multiplied by a
factor 100/IBaseW1. Thus, it can be connected to the disturbance recorder and automatically
recorded during any external or internal fault condition.
The internal/external fault discriminator responds to the magnitudes and the relative phase angles of
the two negative-sequence differential current contributions, see Equation 36.
Operation of the internal/external fault discriminator is based on the relative position of the two
phasors representing winding one (W1) and winding two (W2) negative-sequence current
contributions, respectively. It performs a directional comparison between these two phasors. The
overall directional characteristic of the internal/external fault discriminator is shown in Figure 74,
where the directional characteristic is defined by two setting parameters: IMinNegSeq and
NegSeqROA.
90 deg
120 deg
If one or the Internal/external
other of fault boundary
currents is too
low, then no
measurement
NegSeqROA
is done, and
(Relay
120 degrees
Operate
is mapped
Angle)
IMinNegSeq
External Internal
fault fault
region region
To perform directional comparison of the two phasors, their magnitudes must be high enough to
ensure that they are due to a fault. On the other hand, to ensure a good sensitivity of the internal/
external fault discriminator, the value of the minimum limit must not be too high. Therefore, the limit
value IminNegSeq is settable in the range of 0.04 to 0.80 times the IBase for winding one. The
default value is 0.08. Note that, to enhance stability at higher fault currents, the set threshold value
IminNegSeq is dynamically increased at currents greater than rated current. If the bias current is
greater than 110% of IBase, then the negative-sequence threshold IminNegSeq is increased
internally. If the magnitudes of both negative-sequence current contributions are more than the actual
limit, then the relative position between these two phasors is checked. If either of the negative-
sequence current contributions, which should be compared, is too small (that is, less than the set
value for IminNegSeq), then the directional comparison is not made to avoid the possibility in taking a
wrong decision. This magnitude check ensures the stability of the algorithm when the transformer is
energized. The setting NegSeqROA represents the relay operate angle, which determines the
boundary between the internal and external fault regions. It can be selected in a range from ±30
degrees to ±120 degrees, with an incremental value of 0.1 degree. The default value is ±60 degrees.
The default setting ±60 degree supports the security in comparison with dependability.
If the above condition concerning magnitudes is fulfilled, then the internal/external fault discriminator
compares the relative phase angle between the negative-sequence current contributions from W1
and W2 sides of the transformer by using the following two rules:
• If the negative-sequence current contributions from W1 and W2 sides are approximately in-
phase, the fault is internal, that is, both phasors are within the internal fault region.
• If the negative-sequence current contributions from W1 and W2 sides are 180 degrees out of
phase, the fault is external, that is, one phasor is within the external fault region.
For example, for any unsymmetrical external fault, ideally, the respective negative-sequence current
contributions from the W1 and W2 transformer sides will be exactly 180 degrees apart and equal in
magnitude regardless the transformer turns ratio and phase displacement.
Note that additional security measures are implemented in the internal/external fault discriminator
algorithm to ensure proper operation with heavily saturated current transformers. The reliable
information on whether a fault is internal or external is typically obtained within 10 ms after the fault
inception, depending on the setting IminNegSeq and the magnitudes of the fault currents. During
heavy faults, approximately 5 ms time to full saturation of the main CT is sufficient to produce a
correct discrimination between internal and external faults.
If the same fault has been positively recognized as internal, then the unrestrained negative-sequence
differential protection places its own trip request.
Any block signals by the harmonic, waveform, or both criteria, which can block the traditional
differential protection, are overridden, and the differential protection operates instantly without any
further delay.
This logic ensures fast disconnection of a faulty transformer for any internal fault.
If the same fault is classified as external, then generally but not unconditionally, a trip command is
prevented. If a fault is classified as external, further analysis of the fault conditions is initiated. If all
the instantaneous differential currents in phases, where the start signals are issued, are free of
harmonic pollution, then a minor internal fault simultaneous with a predominant external fault can be
suspected. This conclusion can be made because at external faults, major false differential currents
can only exist when one or more current transformers saturate. In this case, the false instantaneous
differential currents are polluted by higher harmonic components, the 2nd, the 5th, and so on.
The instantaneous differential currents are calculated using the same matrix expression as shown in
Equation 33. The same matrices are used for these calculations. The only difference is that the
matrix algorithm is fed by instantaneous values of currents, that is, raw samples instead of phasors.
The magnetizing currents of a transformer flow only on one side of the transformer and are,
therefore, always the cause of false differential currents. The harmonic analysis (the 2nd and the 5th
harmonic) is applied to the instantaneous differential currents. The harmonic analysis is applied only
in the phases where start signals have been set. For example, if the content of the 2nd harmonic in
the instantaneous differential current of phase L1 is above the setting I2/I1Ratio, then a block signal
is set for that phase, which can be read as BLK2HL1 output from the differential protection.
After the transformer has been energized (the energizing period has elapsed and the inrush currents
have disappeared), the second harmonic blocking is conditionally activated if NegSeqDiffEn is set to
On. When a fault cannot be identified as an internal or an external, the second harmonic blocking
signal is activated only if the differential current is smaller than the bias current. If the differential
current becomes equal to or greater than the bias current, the differential function will be released
regardless of the second harmonic blocking signal.
When CrossBlockEn is set to On, cross-blocking between phases is introduced. There is no time
settings involved, but the phase with an operating point above the set bias characteristic (in the
operate region) will be able to cross-block the other two phases if it is blocked by the harmonic or
waveform restrained criteria. As soon as the operating point for this phase is below the set bias
characteristic (that is, in the restrain region), cross-blocking from that phase will be inhibited. In this
way, the cross-blocking of temporary nature is achieved. It should be noted that this is the default
setting value for this parameter.
When the parameter CrossBlockEn is set to Off, any cross-blocking between phases will be disabled.
It is recommended to use the value Off with a caution to avoid the unwanted tripping during initial
energizing of the transformer.
idL1
VT
Phasor calculation of individual phase currents and
IDL1MAG
Fundamental frequency (phasor based)
Diff current, phase L1 and phase current idL2Mag
contributions from individual windings
IDL2MAG
Phasor calculation of individual phase currents and
DIFRATIO
DIFANGLE
IRATIO
IANGLE
URATIO
UANGLE
IEC18000157-1-en.vsdx
IEC18000157 V1 EN-US
Figure 75: Treatment of measured currents within IED for PSTPDIF function
Figure 75 shows how an internal treatment of measured currents is done in case of a two-winding
transformer.
The following currents are inputs used in the PSTPDIF function. They must all be expressed in power
system (primary) A.
1. Instantaneous values of currents (samples) from W1 and W2 sides for two-winding transformers
2. Currents from all transformer sides expressed as fundamental frequency phasors with their real
and imaginary parts. These currents are calculated within the protection function by the
fundamental frequency Fourier filters.
3. Negative sequence currents from all transformer sides expressed as phasors. These currents
are calculated within the protection function by the symmetrical components module.
1. Calculates the three fundamental frequency differential currents and one common bias current.
The zero-sequence component can optionally be eliminated from each of the three fundamental
frequency differential currents and also from the common bias current.
2. Calculates the three instantaneous differential currents. They are used for harmonic and
waveform analysis. Instantaneous differential currents are useful for post-fault analysis using
disturbance recording.
3. Calculates the negative-sequence differential current. Contributions to it from both transformer
sides are used by the internal/external fault discriminator to detect and classify a fault as internal
or external.
BLKUNRES
IdUnre a tripUnreL1
b>a AND
b
idL1Mag
block
STL1
AND
BLOCK stL1
BLKRES
tripResL1
AND
OR
blk2HL1
BLK2HL1
2n d Harmonic
blkWavL1
blk5HL1
Cross block
Cross block to L2 or L3
from L2 or L3 AND
OR
AND
CrossBlock
IEC18000158-1-en.vsdx
IEC18000158 V1 EN-US
IMinNegSeq
EXTFAULT
NegSeqROA
Internal/ External
fault discriminator INTFAULT
Neg. Seq. Diff
Current
Contributions
tTripNSSenS
t TRNSSENS
AND AND
NegSegDiffEn
trNsSens
iBias a block
Constant a<b
b
TRNSUNR
stL1 AND
AND
stL2 OR trNsUnr
stL3
IEC18000152-1-en.vsdx
IEC18000152 V1 EN-US
Figure 77: PSTPDIF function simplified logic diagram for internal/external fault discriminator
tripResL1
tripResL2 TRIPRES
OR
tripResL3
tripUnreL1
tripUnreL2 TRIPUNRE
OR
tripUnreL3
TRIP
trNsSens OR
trNsUnr
IEC18000151-1-en.vsdx
IEC18000151 V1 EN-US
stL1
stL2 START
OR
stL3
blk2HL1
blk2HL2 OR BLK2H
blk2HL3
blk5HL1
blk5HL2 BLK5H
OR
blk5HL3
blkWavL1
blkWavL2 OR BLKWAV
blkWavL3
IEC18000070-1-en.vsdx
IEC18000070 V1 EN-US
1. The three fundamental frequency differential currents are applied phase-wise to two limits. The
first limit is the operate-restrain characteristic while the other is the high-set unrestrained limit. If
the first limit is exceeded, a start signal START is set. If the unrestrained limit is exceeded, an
immediate unrestrained trip TRIPUNRE and a common trip TRIP are issued.
2. If a start signal is issued in a phase, the harmonic and the waveform block signals are checked.
Only a start signal, which is free from all of its block signals, can result in a trip command. If the
cross-block logic scheme is applied, then only if all phases with the set start signal are free of
their respective block signals, a restrained trip TRIPRES and a common trip TRIP are issued.
3. If a start signal is issued in a phase and the fault has been classified as internal, then any
eventual block signals are overridden and an unrestrained negative-sequence trip TRNSUNR
and a common trip TRIP are issued without any further delay. This feature is called the
unrestrained negative-sequence protection 110% bias.
4. The sensitive negative-sequence differential protection is independent of any start signals. It is
meant to detect smaller internal faults such as, turn-to-turn faults, that are often not detected by
the traditional differential protection. The sensitive negative-sequence differential protection
starts whenever both contributions to the total negative-sequence differential current (that must
be compared by the internal/external fault discriminator) are higher than the value of the setting
IMinNegSeq. If a fault is positively recognized as internal and the condition is stable with no
interruption for at least one fundamental frequency cycle, then the sensitive negative-sequence
differential protection TRNSSENS and a common trip TRIP are issued. This feature is called the
sensitive negative-sequence differential protection.
5. If a start signal is issued in a phase (see signal STL1) though the fault has been classified as an
external fault, the instantaneous differential current of that phase (see signal IDL1) is analyzed
for the second and the fifth harmonic contents. If there is a less harmonic pollution than allowed
by the settings I2/I1Ratio and I5/I1Ratio, then it is assumed that a minor simultaneous internal
fault has occurred and the outputs from the blocks 2nd harmonic and 5th harmonic are 0. Only
under these conditions, a trip command is allowed (see signal TRIPRES=1). The cross-block
logic scheme is automatically applied under such circumstances. This means that the cross
block signals from the other two phases L2 and L3 are not activated to obtain a trip on the
TRIPRES output signal in Figure 76.
6. All start and block conditions are available as phase-wise and common (that is, three-phase)
signals.
idL1Mag
a
a>b
IDiffAlarm b
idL2Mag tAlarmDelay
a IDALARM
a>b AND t
b
idL3Mag
a
a>b
b
IEC18000069-1-en.vsdx
IEC18000069 V1 EN-US
Z<->
IEC09000167 V1 EN-US
The line distance protection is an up to five (depending on product variant) zone full scheme
protection function with three fault loops for phase-to-phase faults and three fault loops for phase-to-
earth faults for each of the independent zones. Individual settings for each zone in resistive and
reactive reach gives flexibility for use as back-up protection for transformer connected to overhead
lines and cables of different types and lengths.
Distance measuring zone, quadrilateral characteristic (ZMQPDIS) together with Phase selection with
load encroachment (FDPSPDIS) has functionality for load encroachment, which increases the
possibility to detect high resistive faults on heavily loaded lines, as shown in figure 81.
Forward
operation
Reverse
operation
en05000034.vsd
IEC05000034 V1 EN-US
Figure 81: Typical quadrilateral distance protection zone with Phase selection with load
encroachment function FDPSPDIS activated
The independent measurement of impedance for each fault loop together with a sensitive and
reliable built-in phase selection makes the function suitable in applications with single-phase
autoreclosing.
Built-in adaptive load compensation algorithm prevents overreaching of zone 1 at load exporting end
at phase-to-earth faults on heavily loaded power lines.
The distance protection zones can operate independently of each other in directional (forward or
reverse) or non-directional mode. This makes them suitable, together with different communication
schemes, for the protection of power lines and cables in complex network configurations, such as
parallel lines, multi-terminal lines.
SEMOD115983-4 v8
ZMQPDIS
I3P* TRIP
U3P* TRL1
BLOCK TRL2
VTSZ TRL3
BLKTR START
STCND STL1
DIRCND STL2
STL3
STND
IEC06000256-2-en.vsd
IEC06000256 V2 EN-US
ZMQAPDIS
I3P* TRIP
U3P* TRL1
BLOCK TRL2
VTSZ TRL3
BLKTR START
STCND STL1
DIRCND STL2
STL3
STND
IEC09000884-1-en.vsd
IEC09000884 V1 EN-US
The two inputs I3P — Three phase group signal for current and U3P — Three phase
group signal for voltage, must be connected to non-adaptive SMAI blocks if ANY OF
THE ZONES are set for directional operation. That is, the parameter DFTReference
in used SMAI must be set to InternalDFTRef. If adaptive SMAI block is used this
might result in a wrong directional and reach evaluation.
SEMOD54537-4 v5
ZDRDIR
I3P* STDIRCND
U3P*
IEC10000007-2-en.vsd
IEC10000007 V2 EN-US
8.1.4 Signals
PID-3651-INPUTSIGNALS v6
PID-3651-OUTPUTSIGNALS v6
PID-3650-INPUTSIGNALS v6
PID-3650-OUTPUTSIGNALS v6
PID-3545-INPUTSIGNALS v6
PID-3545-OUTPUTSIGNALS v5
8.1.5 Settings
GUID-62142086-79A9-46FF-A14F-BA0CDD6B6466 v1
Signals and settings for ZMQPDIS are valid for zone 1 while signals and settings for
ZMQAPDIS are valid for zone 2 - 5
PID-3651-SETTINGS v6
PID-3650-SETTINGS v6
PID-3545-SETTINGS v6
The execution of the different fault loops within the IED are of full scheme type, which means that
each fault loop for phase-to-earth faults and phase-to-phase faults for forward and reverse faults are
executed in parallel.
Figure 85 presents an outline of the different measuring loops for up to five, impedance-measuring
zones. There are 3 to 5 zones depending on product type and variant.
IEC05000458‐3‐en.vsdx
IEC05000458 V3 EN-US
Figure 85: The different measuring loops at phase-to-earth fault and phase-to-phase fault.
The use of full scheme technique gives faster operation time compared to switched schemes which
mostly uses a start element to select correct voltages and current depending on fault type. Each
distance protection zone performs like one independent distance protection IED with six measuring
elements.
The distance measuring zone includes six impedance measuring loops; three intended for phase-to-
earth faults, and three intended for phase-to-phase as well as, three-phase faults.
The distance measuring zone will essentially operate according to the non-directional impedance
characteristics presented in figure 86 and figure 87. The phase-to-earth characteristic is illustrated
with the full loop reach while the phase-to-phase characteristic presents the per phase reach.
X (Ohm/loop)
R1+Rn
RFPE RFPE
X0-X1
Xn =
3
X1+Xn R0-R1
Rn =
3
jN jN
R (Ohm/loop)
RFPE RFPE
X1+Xn
RFPE RFPE
IEC11000427-1-en.vsd
R1+Rn
IEC11000427 V1 EN-US
X (Ohm/phase)
RFPP R1 RFPP
2 2
X 0 PE - X 1RVPE
XNRV =XX00PEPG--X31XRVPE
1RVPG
XNRV =
XNRV =
3 3
XX
X00PE
0PE
PG --1X
-X 11FWPE
XFWPE
FWPG
XNFW =
=
XNFW =
XNFW
X1 3
3 3
j j
R (Ohm/phase)
RFPP RFPP
2 2
X1
RFPP R1 RFPP
2 2
IEC11000428-1-en.vsd
IEC11000428 V1 EN-US
IL1 R1 + j X1
Phase-to-earth
UL1
element
Phase-to-earth
fault in phase L1 RFPE
(Arc + tower
resistance)
0
IN (R0-R1)/3 +
j (X0-X1)/3 )
IL1 R1 + j X1 Phase-to-phase
UL1 element L1-L2
Phase-to-phase
fault in phase RFPP
L1-L2 IL2
UL2 (Arc resistance)
R1 + j X1
Regarding the illustration of three-phase fault in Figure 88, there is of course fault current flowing
also in the third phase during a three-phase fault. The illustration merely reflects the loop
measurement, which is made phase-to-phase.
The zone can be set to operate in Non-directional, Forward or Reverse direction through the setting
OperationDir . The result from respective set value is illustrated in Figure. The impedance reach is
symmetric, in the sense that it conforms for forward and reverse direction. Therefore, all reach
settings apply to both directions.
X X X
R R R
IEC05000182-2-en.vsdx
IEC05000182 V2 EN-US
The estimated impedance needs to be inside both characteristics for the zone to start or trip. (The
non-directional start STND is an exception however. It is only dependent on the quadrilateral
characteristic.)
In the following figure, the zone with the shorter reactive reach follows the directional line (R∙tan(15⁰))
only up to X1PP, where the quadrilateral characteristic will start to limit the reach.
X (ohm)
X1PP’
X1PP
15° R (ohm)
RFPP/2
-X1PP
R· tan15°
-X1PP’
Line distance protection=IEC19000141=2=en-us=Original.vsdx
IEC19000141 V2 EN-US
The operation of Distance measuring zones, quadrilateral characteristic (ZMQPDIS) is blocked if the
magnitude of input currents fall below certain threshold values.
For zone 1 with load compensation feature the additional criterion applies, that all phase-to-earth
loops will be blocked when IN < IMinOpIN, regardless of the phase currents.
ILn is the RMS value of the current in phase Ln. IN is the RMS value of the vector sum of the three-
phase currents, that is, residual current 3I0.
ILmLn is the RMS value of the vector difference between phase currents Lm and Ln.
All three current limits IMinOpPE, IMinOpIN and IMinOpPP are automatically
reduced to 75% of regular set values if the zone is set to operate in reverse
direction, that is, OperationDir = Reverse.
Fault loop equations use the complex values of voltage, current, and changes in the current.
Apparent impedances are calculated and compared with the set limits. The apparent impedances at
phase-to-phase faults follow equation 37 (example for a phase L1 to phase L2 fault).
UL1 – UL2
Zapp = -------------------------
I L1 – IL2
EQUATION1222 V1 EN-US (Equation 37)
Here U and I represent the corresponding voltage and current phasors in the respective phase Ln (n
= 1, 2, 3)
The earth return compensation applies in a conventional manner to phase-to-earth faults (example
for a phase L1 to earth fault) according to equation 38.
U L1
Z app =
I L1 + I N × KN
EQUATION1223 V2 EN-US (Equation 38)
Where:
are the phase voltage, phase current and residual current present to the IED
U L1
I L1
IN
KN
is defined as:
Z 0 - Z1
KN =
3 × Z1
EQUATION-2105 V2 EN-US
Z 0 = R 0 + jX 0
EQUATION2106 V2 EN-US
Z 1 = R1 + jX 1
EQUATION2107 V2 EN-US
Where
R0 is setting of the resistive zero sequence reach
X0 is setting of the reactive zero sequence reach
R1 is setting of the resistive positive sequence reach
X1 is setting of the reactive positive sequence reach
Here IN is a phasor of the residual current in IED point. This results in the same reach along the line
for all types of faults.
The apparent impedance is considered as an impedance loop with resistance R and reactance X.
The formula given in equation 38 is only valid for radial feeder application without load. When load is
considered in the case of single phase-to-earth fault, conventional distance protection might
overreach at exporting end and underreach at importing end. The IED has an adaptive load
compensation which increases the security in such applications.
Measuring elements receive current and voltage information from the A/D converter. The check sums
are calculated and compared, and the information is distributed into memory locations. For each of
the six supervised fault loops, sampled values of voltage (U), current (I), and changes in current
between samples (DI) are brought from the input memory and fed to a recursive Fourier filter.
The filter provides two orthogonal values for each input. These values are related to the loop
impedance according to equation 39,
X Di
U = R × i + ------ × -----
w 0 Dt
EQUATION1224 V1 EN-US (Equation 39)
X D Re ( I )
Re ( U ) = R × Re ( I ) + ------ × ------------------
w0 Dt
X DIm ( I )
Im ( U ) = R × Im ( I ) + ------ × -----------------
w0 Dt
with
w0 = 2 × p × f 0
EQUATION356 V1 EN-US (Equation 42)
where:
Re designates the real component of current and voltage,
Im designates the imaginary component of current and voltage and
f0 designates the rated system frequency
The algorithm calculates Rm measured resistance from the equation for the real value of the voltage
and substitutes it in the equation for the imaginary part. The equation for the Xm measured reactance
can then be solved. The final result is equal to:
Im ( U ) × DRe ( I ) – Re ( U ) × D Im ( I )
R m = ------------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – D Im ( I ) × Re ( I )
EQUATION357 V1 EN-US (Equation 43)
Re ( U ) × Im ( I ) – Im ( U ) × Re ( I )
Xm = w 0 × Dt × -------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – DIm ( I ) × Re ( I )
EQUATION358 V1 EN-US (Equation 44)
The calculated Rm and Xm values are updated each sample and compared with the set zone reach.
The adaptive tripping counter counts the number of permissive tripping results. This effectively
removes any influence of errors introduced by the capacitive voltage transformers or by other factors.
The directional evaluations are performed simultaneously in both forward and reverse directions, and
in all six fault loops. Positive sequence voltage and a phase locked positive sequence memory
voltage are used as a reference. This ensures unlimited directional sensitivity for faults close to the
IED point.
The evaluation of the directionality takes place in Directional impedance quadrilateral function
ZDRDIR. Equation 45 and equation 46 are used to classify that the fault is in forward direction for
phase-to-earth fault and phase-to-phase fault.
For the L1-L2 element, the equation in forward direction is according to.
where:
ArgDir is the setting for the lower boundary of the forward directional characteristic, by default set to 15 (= -15
degrees) and
ArgNegRes is the setting for the upper boundary of the forward directional characteristic, by default set to 115
degrees, see figure 91.
is positive sequence phase voltage in phase L1
U 1L1
is positive sequence memorized phase voltage in phase L1
U 1L1M
is phase current in phase L1
I L1
is voltage difference between phase L1 and L2 (L2 lagging L1)
U 1L1L 2
is memorized voltage difference between phase L1 and L2 (L2 lagging L1)
U 1L1L 2 M
is current difference between phase L1 and L2 (L2 lagging L1)
I L1L 2
The setting of ArgDir and ArgNegRes is by default set to 15 (= -15) and 115 degrees respectively (as
shown in figure 91). It should not be changed unless system studies have shown the necessity.
ZDRDIR gives binary coded directional information per measuring loop on the output STDIRCND.
STDIR= STFWL1*1+STFWL2*2+STFWL3*4+STFWL1L2*8+
+STFWL2L3*16+STFWL3L1*32+STRVL1*64+STRVL2*128+
+STRVL3*256+STRVL1L2*512+STRVL2L3*1024+STRVL3L1*2048
ArgNegRes
ArgDir
R
en05000722.vsd
IEC05000722 V1 EN-US
Figure 91: Setting angles for discrimination of forward and reverse fault in Directional
impedance quadrilateral function ZDRDIR
The reverse directional characteristic is equal to the forward characteristic rotated by 180 degrees.
The polarizing voltage is available as long as the positive sequence voltage exceeds 5% of the set
base voltage UBase. So the directional element can use it for all unsymmetrical faults including
close-in faults.
For close-in three-phase faults, the U1L1M memory voltage, based on the same positive sequence
voltage, ensures correct directional discrimination.
The memory voltage is used for 100 ms or until the positive sequence voltage is restored.
• If the current is still above the set value of the minimum operating current (between 10 and 30%
of the set IED rated current IBase), the condition seals in.
• If the fault has caused tripping, the trip endures.
• If the fault was detected in the reverse direction, the measuring element in the reverse
direction remains in operation.
• If the current decreases below the minimum operating value, the memory resets until the
positive sequence voltage exceeds 10% of its rated value.
Phase-to-earth related signals are designated by L1N, L2N and L3N. The phase-to-phase signals are
designated by L1L2, L2L3, and L3L1.
Fulfillment of two different measuring conditions is necessary to obtain the one logical signal for each
separate measuring loop:
• Zone measuring condition, which follows the operating equations described above.
• Group functional input signal (STCND), as presented in figure 92.
Two types of function block, ZMQPDIS and ZMQAPDIS, are used in the IED. ZMQPDIS is used for
zone 1 and ZMQAPDIS for zone 2 - 5.
The STCND input signal represents a connection of six different integer values from Phase selection
with load encroachment, quadrilateral characteristic function FDPSPDIS within the IED, which are
converted within the zone measuring function into corresponding boolean expressions for each
condition separately. Input signal STCND is connected to FDPSPDIS or FMPSPDIS function output
STCNDZ.
The input signal DIRCND is used to give condition for directionality for the distance measuring zones.
The signal contains binary coded information for both forward and reverse direction. The zone
measurement function filters out the relevant signals depending on the setting of the parameter
OperationDir. It must be configured to the STDIR output on ZDRDIR function.
STZMPP
OR
STCND
AND STNDL1L2
L1L2
STNDL2L3
L2L3 AND
AND STNDL1N
L1N
AND STNDL2N
L2N
STNDL3N
L3N AND
OR STPE
OR
VTSZ STND
OR AND
BLOCK
BLOCFUNC BLK
99000557-2.vsd
IEC99000557-TIFF V3 EN-US
Figure 92: Conditioning by a group functional input signal STCND, external start condition
Composition of the phase start signals for a case, when the zone operates in a non-directional mode,
is presented in figure 93.
IEC00000488-TIFF V1 EN-US
STNDL1N
AND
DIRL1N
STZMPE.
OR
STNDL2N
DIRL2N AND
STNDL3N 15 ms
OR STL1
AND AND t
DIRL3N
STNDL1L2
DIRL1L2 AND 15 ms
OR STL2
AND t
STNDL2L3
DIRL2L3 AND
15 ms
OR STL3
STNDL3L1 AND t
DIRL3L1 AND
STZMPP
OR
BLK
15 ms
OR START
AND t
IEC09000888-2-en.vsd
IEC09000888 V2 EN-US
Timer tPP=On
STZMPP AND tPP
AND
t
BLOCFUNC
OR OR
tPE
t
AND
Timer tPE=On AND
STZMPE 15ms
BLKTR AND t
TRIP
BLK OR
IEC09000887-3-en.vsdx
IEC09000887 V3 EN-US
M13842-1 v15
8.2.1 Identification
SYMBOL-DD V1 EN-US
The operation of transmission networks today is in many cases close to the stability limit. Due to
environmental considerations, the rate of expansion and reinforcement of the power system is
reduced, for example, difficulties to get permission to build new power lines. The ability to accurately
and reliably classify the different types of fault, so that single pole tripping and autoreclosing can be
used plays an important role in this matter. Phase selection, quadrilateral characteristic with fixed
angle (FDPSPDIS) is designed to accurately select the proper fault loop in the distance function
dependent on the fault type.
The heavy load transfer that is common in many transmission networks may make fault resistance
coverage difficult to achieve. Therefore, FDPSPDIS has a built-in algorithm for load encroachment,
which gives the possibility to enlarge the resistive setting of both the phase selection and the
measuring zones without interfering with the load.
The extensive output signals from the phase selection gives also important information about faulty
phase(s), which can be used for fault analysis.
A current-based phase selection is also included. The measuring elements continuously measure
three phase currents and the residual current and, compare them with the set values.
FDPSPDIS
I3P* TRIP
U3P* START
BLOCK STFWL1
DIRCND STFWL2
STFWL3
STFWPE
STRVL1
STRVL2
STRVL3
STRVPE
STNDL1
STNDL2
STNDL3
STNDPE
STFW1PH
STFW2PH
STFW3PH
STPE
STPP
STCNDZ
STCNDLE
IEC14000047-1-en.vsd
IEC10000047 V2 EN-US
8.2.4 Signals
PID-3642-INPUTSIGNALS v7
PID-3642-OUTPUTSIGNALS v7
8.2.5 Settings
PID-3642-SETTINGS v7
The difference, compared to the distance zone measuring function, is in the combination of the
measuring quantities (currents and voltages) for different types of faults.
A current-based phase selection is also included. The measuring elements continuously measure
three phase currents and the residual current, and compare them with the set values. The current
signals are filtered by Fourier's recursive filter, and separate trip counter prevents too high
overreaching of the measuring elements.
The characteristic is basically non-directional, but FDPSPDIS uses information from the directional
function to discriminate whether the fault is in forward or reverse direction.
1. Residual current criteria, that is, separation of faults with and without earth connection
2. Regular quadrilateral impedance characteristic or current based criteria
3. Load encroachment characteristics is always active but can be switched off by selecting a high
setting.
The STCNDLE output is non-directional. The directionality is determined by the distance zones
directional function. There are outputs from FDPSPDIS that indicate whether a start is in forward or
reverse direction or non-directional, for example STFWL1, STRVL1 and STNDL1.
These directional indications are based on the sector boundaries of the directional function and the
impedance setting of FDPSPDIS function. Their operating characteristics are illustrated in figure 97.
X X X
R
R R
en08000286.vsd
IEC08000286 V1 EN-US
Figure 97: Characteristics for non-directional, forward and reverse operation of Phase
selection with load encroachment, quadrilateral characteristic FDPSPDIS
The setting of the load encroachment function may influence the total operating characteristic, (for
more information, refer to section "Load encroachment").
The input DIRCND contains binary coded information about the directional coming from the
directional function . It shall be connected to the STDIR output on ZDRDIR, directional measuring
block. This information is also transferred to the input DIRCND on the distance measuring zones,
that is, the ZMQPDIS, distance measuring block.
STDIR= STFWL1*1+STFWL2*2+STFWL3*4+STFWL1L2*8+
+STFWL2L3*16+STFWL3L1*32+STRVL1*64+STRVL2*128+
+STRVL3*256+STRVL1L2*512+STRVL2L3*1024+STRVL3L1*2048
If the binary information is 1 then it will be considered that we have start in forward direction in phase
L1. If the binary code is 3 then we have start in forward direction in phase L1 and L2, binary code
192 means start in reverse direction in phase L1 and L2A and B etc.
The STCNDZ or STCNDLE output contains, in a similar way as DIRCND, binary coded information,
in this case information about the condition for opening correct fault loop in the distance measuring
element. It shall be connected to the STCND input on the ZMQPDIS, distance measuring block.
The code built up for release of the measuring fault loops is as follows:
For a phase-to-earth fault, the measured impedance by FDPSPDIS will be according to equation 47.
Index PHS in images and equations reference settings for Phase selection with load
encroachment function FDPSPDIS.
ULn
ZPHSn =
ILn
EQUATION1255 V1 EN-US (Equation 47)
where:
n corresponds to the particular phase (n=1, 2 or 3)
The characteristic for FDPSPDIS function at phase-to-earth fault is according to figure 98. The
characteristic has a fixed angle for the resistive boundary in the first quadrant of 60°.
The resistance RN and reactance XN are the impedance in the earth-return path defined according
to equation 48 and equation 49.
R0 - R1
RN =
3
EQUATION1256 V1 EN-US (Equation 48)
X 0 - X1
XN =
3
EQUATION1257 V1 EN-US (Equation 49)
X (ohm/loop)
Kr·(X1+XN)
RFRvPE RFFwPE
X1+XN
60 deg
RFFwPE
RFRvPE R (Ohm/loop)
60 deg
X1+XN
1
Kr =
tan(60deg)
RFRvPE RFFwPE
Kr·(X1+XN)
en06000396.vsd
IEC06000396 V2 EN-US
Figure 98: Characteristic of FDPSPDIS for phase-to-earth fault (setting parameters in italic),
ohm/loop domain (directional lines are drawn as "line-dot-dot-line")
Besides this, the 3I0 residual current must fulfil the conditions according to equation 50 and
equation 51.
3 × I0 ³ 0.5 × IMinOpPE
EQUATION2108 V1 EN-US (Equation 50)
3 × I0 ³ INReleasePE
------------------------------------ × Iphmax
100
EQUATION766 V1 EN-US (Equation 51)
where:
IMinOpPE is the minimum operation current for forward zones
INReleasePE is the setting for the minimum residual current needed to enable operation in the phase-to-earth fault
loops (in %).
Iphmax is the maximum phase current in any of three phases.
For a phase-to-phase fault, the measured impedance by FDPSPDIS will be according to equation 52.
ULm - ULn
ZPHS =
-2 × ILn
EQUATION1258 V1 EN-US (Equation 52)
ULm is the leading phase voltage, ULn the lagging phase voltage and ILn the phase current in the
lagging phase n.
X (W / phase)
0.5·RFRvPP 0.5·RFFwPP
Kr·X1
X1
0.5·RFFwPP
60 deg
R (W / phase)
60 deg
0.5·RFRvPP
X1
1
Kr =
tan(60 deg)
Kr·X1
0.5·RFRvPP 0.5·RFFwPP
IEC09000047-2-en.vsd
IEC09000047 V2 EN-US
Figure 99: The operation characteristics for FDPSPDIS at phase-to-phase fault (setting
parameters in italic, directional lines drawn as "line-dot-dot-line"), ohm/phase
domain
In the same way as the condition for phase-to-earth fault, there are current conditions that have to be
fulfilled in order to release the phase-to-phase loop. Those are according to equation 53 or
equation 54.
3I 0 < IMinOpPE
EQUATION2109 V1 EN-US (Equation 53)
INBlockPP
3I 0 < × Iph max
100
EQUATION2110 V1 EN-US (Equation 54)
where:
IMinOpPE is the minimum operation current for earth measuring loops,
INBlockPP is 3I0 limit for blocking phase-to-phase measuring loop and
The operation conditions for three-phase faults are the same as for phase-to-phase fault, that is
equation , equation and equation are used to release the operation of the function.
However, the reach is expanded by a factor 2/√3 (approximately 1.1547) in all directions. At the same
time the characteristic is rotated 30 degrees, counter-clockwise. The characteristic is shown in
figure 100.
X (ohm/phase)
4 × X1
3
90 deg
0.5·RFFwPP·K3
X1·K3 4 × RFFwPP
6
R (ohm/phase)
0.5·RFRvPP·K3
2
K3 =
3 30 deg
IEC05000671-5-en.vsd
IEC05000671 V5 EN-US
Figure 100: The characteristic of FDPSPDIS for three-phase fault (setting parameters in italic)
Each of the six measuring loops has its own load encroachment characteristic based on the
corresponding loop impedance. The load encroachment functionality is always active, but can be
switched off by selecting a high setting.
The outline of the characteristic is presented in figure 101. As illustrated, the resistive blinders are set
individually in forward and reverse direction while the angle of the sector is the same in all four
quadrants.
RLdFw
ArgLd ArgLd
R
ArgLd ArgLd
RLdRv
IEC09000042-1-en.vsd
IEC09000042 V1 EN-US
When output signal STCNDLE is selected, the operation characteristic will be as the right illustration
in figure 102. The reach will in this case be limit by the minimum operation current and the distance
measuring zones.
X X
R R
STCNDZ STCNDLE
IEC10000099-1-
en.vsd
IEC10000099 V1 EN-US
Figure 102: Difference in operating characteristic depending on operation mode when load
encroachment is activated
When FDPSPDIS is set to operate together with a distance measuring zone the resultant operate
characteristic could look like in figure 103. The figure shows a distance measuring zone operating in
forward direction. Thus, the operating area is highlighted in black.
"Phase selection"
"quadrilateral" zone
Load encroachment
characteristic
Directional line
en05000673.vsd
IEC05000673 V1 EN-US
Figure 103: Operating characteristic in forward direction when load encroachment is activated
Figure 103 is valid for phase-to-earth. During a three-phase fault, or load, when the quadrilateral
phase-to-phase characteristic is subject to enlargement and rotation the operate area is transformed
according to figure 104. Notice in particular what happens with the resistive blinders of the "phase
selection" "quadrilateral" zone. Due to the 30-degree rotation, the angle of the blinder in quadrant
one is now 90 degrees instead of the original 60 degrees. The blinder that is nominally located to
quadrant four will at the same time tilt outwards and increase the resistive reach around the R-axis.
Consequently, it will be more or less necessary to use the load encroachment characteristic in order
to secure a margin to the load impedance.
X (W / phase)
Phase selection
”Quadrilateral” zone
R (W / phase)
IEC09000049-1-en.vsd
IEC09000049 V1 EN-US
Figure 104: Operating characteristic for FDPSPDIS in forward direction for three-phase fault,
ohm/phase domain
The result from rotation of the load characteristic at a fault between two phases is presented in fig
105. Since the load characteristic is based on the same measurement as the quadrilateral
characteristic, it will rotate with the quadrilateral characteristic clockwise by 30 degrees when subject
to a pure phase-to-phase fault. At the same time the characteristic will "shrink", divided by 2/√3, from
the full RLdFw and RLdRv reach, which is valid at load or three-phase fault.
IEC08000437.vsd
IEC08000437 V1 EN-US
Figure 105: Rotation of load characteristic for a fault between two phases
There is a gain in selectivity by using the same measurement as for the quadrilateral characteristic
since not all phase-to-phase loops will be fully affected by a fault between two phases. It should also
provide better fault resistive coverage in quadrant one. The relative loss of fault resistive coverage in
quadrant four should not be a problem even for applications on series compensated lines.
The operation of the Phase selection with load encroachment function (FDPSPDIS) is blocked if the
magnitude of input currents falls below certain threshold values.
The phase-to-earth loop Ln is blocked if ILn<IMinOpPE, where ILn is the RMS value of the current in
phase Ln.
Figure 106 presents schematically the general logic diagram for phase-selection function.
INMag Residual current
based PhSel.
INReleasePE
STPP
PP
INBLOCKPP STPE
PE
Imin
I3P PP
PE STZPHLmn AND
PHSLmn
X
OR
U3P STZPHLm
R,X settings R
LEPHLm AND PHSLm
OR
Binary to word
LEPHLmn
OperationZ< Enable
b1 – b3
word
b4 – b6
IPELm
IL1 IRELPE
Set level
IPh> T
IRELPP STCNDZ
IN> AND 63 F
t
OperationI> Binary to word
b1 – b3
OR
STCNDLE
word
Relative current AND b4 – b6
IPELm RELPHLmn AND
based PP release
detection
IEC18000010-2-en.vsdx
m = L1G, L2G, L3G
mn = L1L2, L2L3, L3L1
IEC18000010 V2 EN-US
OperationZ<
AND
LDEblock
& 15 ms
AND t STPE
INReleasePE
3I 0 Iphmax
100 STCNDLE
Bool to AND
BLOCK integer
15 ms
3I 0 IMinOpPE 10 ms 20 ms & t STPP
OR AND t t
IRELPP
INBlockPP
3I 0 Iphmax
100
IEC09000149-3-en.vsd
IEC09000149 V3 EN-US
Figure 107: Phase-to-phase and phase-to-earth operating conditions (residual current criteria)
A special attention is paid to correct phase selection at evolving faults. A STCNDLE output signal is
created as a combination of the load encroachment characteristic and current criteria, refer to
figure 107. This signal can be configured to STCND functional input signals of the distance protection
zone and this way influence the operation of the phase-to-phase and phase-to-earth zone measuring
elements, residual current and the load encroachment characteristic.
Figure 108 presents schematically the composition of non-directional phase selective signals
STNDLn. Internal signals ZMLnN and ZMLmLn (m and n change between one and three according
to the phase number) represent the fulfilled operating criteria for each separate loop measuring
element, that is, within the impedance characteristic. These signals are released if the setting
OperationZ< is set to On. Similarly, another group of internal signals ILm and ILn represent the
fulfilled phase current measurement criteria, which are released by setting the OperationI> parameter
to On.
INDL1N
INDL2N
INDL3N
15 ms
STNDPE
IRELPE OR t
LDEblockL1N
IL1 AND 15 ms
OR STNDL1
ZML1N OR t
LDEblockL2N
IL2 AND
OR
ZML2N 15 ms
LDEblockL3N STNDL2
OR t
IL3 AND
OR
ZML3N
LDEblockL1L2 15 ms
STNDL3
IL1 & IL2 AND OR t
OR
ZML1L2
LDEblockL2L3
IL2 & IL3 AND INDL1L2
OR
ZML2L3 INDL2L3
LDEblockL3L1
IL3 & IL1 AND
OR INDL3L1
ZML3L1
IRELPP 15 ms
STNDPP
OR t
IEC00000545-4-en.vsd
IEC00000545-TIFF V4 EN-US
Figure 109 presents additionally a composition of a STCNDZ output signal, which is created on the
basis of the continuation of the impedance measuring conditions and the load encroachment
characteristic. This signal can be configured to STCND functional input signals of the distance
protection zone and this way influence the operation of the phase-to-phase and phase-to-earth zone
measuring elements and their phase related starting and tripping signals.
INDL1N
AND
DRVL1N
INDL1L2 15 ms STRVL1
AND OR t
DRVL1L2
INDL3L1
AND
DRVL3L1 15 ms
STRVPE
INDL2N OR t
AND
DRVL2N
INDL1L2 15 ms
STRVL2
AND OR t
INDL2L3 INDL1N
AND INDL2N
DRVL2L3
INDL3N Bool to STCNDZ
INDL3N INDL1L2 integer
AND INDL2L3
DRVL3N INDL3L1
INDL2L3 15 ms
STRVL3
AND OR t
INDL3L1
15 ms
AND STRVPP
OR t
IEC00000546_2_en.vsd
IEC00000546-TIFF V2 EN-US
AND
INDL1N
AND 15 ms 15 ms
DFWL1N STFW1PH
AND OR t t
INDL1L2
15 ms STFWL1
AND OR t
DFWL1L2
INDL3L1
AND
AND
DFWL3L1 15 ms
STFWPE
INDL2N OR t
AND
DFWL2N
AND 15 ms
INDL1L2 STFWL2
t
AND OR
15 ms 15 ms
INDL2L3 STFW2PH
AND OR t t
AND
DFWL2L3
INDL3N
AND AND
DFWL3N 15 ms
STFWL3
t
INDL2L3
AND OR
15 ms
INDL3L1 STFW3PH
AND t
AND
15 ms
STFWPP
OR t
IEC05000201_2_en.vsd
IEC05000201 V2 EN-US
Figure 111 presents the composition of output signals TRIP and START, where internal signals
STNDPP, STFWPP and STRVPP are the equivalent to internal signals STNDPE, STFWPE and
STRVPE, but for the phase-to-phase loops.
TimerPP=Off
tPP
AND AND
t
TRIP
OR OR
tPE
TimerPE=Off
t
AND AND
STNDPP
STFWPP OR
STRVPP
START
OR
STNDPE
STFWPE OR
STRVPE
IEC08000441_2_en.vsd
IEC08000441-1 V2 EN-US
8.3.1 Identification
SEMOD168165-2 v2
IEC09000167 V1 EN-US
The line distance protection is an up to five (depending on product variant) zone full scheme
protection with three fault loops for phase-to-phase faults and three fault loops for phase-to-earth
fault for each of the independent zones. Individual settings for each zone resistive and reactive reach
give flexibility for use on overhead lines and cables of different types and lengths.
Distance measuring zone, quadrilateral characteristic for series compensated lines (ZMCPDIS)
function has functionality for load encroachment which increases the possibility to detect high
resistive faults on heavily loaded lines.
Forward
operation
Reverse
operation
en05000034.vsd
IEC05000034 V1 EN-US
Figure 112: Typical quadrilateral distance protection zone with load encroachment function
activated
The distance protection zones can operate, independent of each other, in directional (forward or
reverse) or non-directional mode. This makes them suitable, together with different communication
schemes, for the protection of power lines and cables in complex network configurations, such as
parallel lines, multi-terminal lines.
SEMOD168198-4 v2
ZMCPDIS
I3P* TRIP
U3P* TRL1
BLOCK TRL2
VTSZ TRL3
BLKTR START
STCND STL1
DIRCND STL2
STL3
STND
IEC07000036-2-en.vsd
IEC07000036 V2 EN-US
ZMCAPDIS
I3P* TRIP
U3P* TRL1
BLOCK TRL2
VTSZ TRL3
BLKTR START
STCND STL1
DIRCND STL2
STL3
STND
IEC09000890-1-en.vsd
IEC09000890 V1 EN-US
ZDSRDIR
I3P* STFW
U3P* STRV
STDIRCND
IEC07000035-2-en.vsd
IEC07000035 V2 EN-US
Input and output signals is shown for zone 1, zone 2 - 5 are equal.
PID-3639-INPUTSIGNALS v6
PID-3639-OUTPUTSIGNALS v6
PID-3637-INPUTSIGNALS v6
PID-3637-OUTPUTSIGNALS v6
PID-3547-INPUTSIGNALS v6
PID-3547-OUTPUTSIGNALS v6
Settings for ZMCPDIS are valid for zone 1, while settings for ZMCAPDIS are valid
for zone 2 - 5
PID-3639-SETTINGS v6
PID-3637-SETTINGS v6
PID-3547-SETTINGS v6
The execution of the different fault loops within the IED are of full scheme type, which means that
earth fault loop for phase-to-earth faults and phase-to-phase faults for forward and reverse faults are
executed in parallel.
Figure 116 presents an outline of the different measuring loops for the basic five, impedance-
measuring zones.
IEC05000458‐3‐en.vsdx
IEC05000458 V3 EN-US
Figure 116: The different measuring loops at phase-to-earth fault and phase-to-phase fault
The use of full scheme technique gives faster operation time compared to switched schemes which
mostly uses a start element to select correct voltages and current depending on fault type. Each
distance protection zone performs like one independent distance protection IED with six measuring
elements.
Distance measuring zone, quadrilateral characteristic for series compensated lines (ZMCPDIS)
include six impedance measuring loops; three intended for phase-to-earth faults, and three intended
for phase-to-phase as well as, three-phase faults.
The distance measuring zone operates according to the non-directional impedance characteristics
presented in figure 117 and figure 118. The phase-to-earth characteristic is illustrated with the full
loop reach while the phase-to-phase characteristic presents the per-phase reach.
X (Ohm/loop)
R1PE+RNFw
X 0 PE - X 1FwPE
RFRvPE RFFwPE XNFw =
3
X 0 PG
X 0 PE = - X 1RVPG
1RVPE ×
- XXNFw
X 1RvPE
XNRV XNRv
XNRV ==
33 X 1FwPE
XX0 PE - X-1X
0 PG FWPE
1FWPG
XNFW==
XNFW
X1FwPE+XNFw 3 3 R0 PE - R1PE
RNFw =
jN jN 3
R (Ohm/loop)
RFRvPE RFFwPE
X1RvPE+XNRv
jN
RFRvPE RFFwPE
IEC09000625-1-en.vsd
IEC09000625 V1 EN-US
Figure 117: Characteristic for the phase-to-earth measuring loops, ohm/loop domain
X (Ohm/phase)
j j
jN R (Ohm/phase)
RFRvPP RFFwPP
2 2
X1RvPP
jN
RFRvPP RFFwPP
2 2
IEC09000632-1-en.vsd
IEC09000632 V1 EN-US
IL1 R1 + j X1
Phase-to-earth
UL1
element
Phase-to-earth
fault in phase L1 RFPE
(Arc + tower
resistance)
0
IN (R0-R1)/3 +
j (X0-X1)/3 )
IL1 R1 + j X1 Phase-to-phase
UL1 element L1-L2
Phase-to-phase
fault in phase RFPP
L1-L2 IL2
UL2 (Arc resistance)
R1 + j X1
Regarding the illustration of three-phase fault in figure 119, there is of course fault current flowing
also in the third phase during a three-phase fault. The illustration merely reflects the loop
measurement, which is made phase-to-phase.
The zone may be set to operate in Non-directional, Forward or Reverse direction through the setting
OperationDir. The result from respective set value is illustrated in figure 120. It may be convenient to
once again mention that the impedance reach is symmetric, forward and reverse direction.
Therefore, all reach settings apply to both directions.
X X X
R R R
IEC05000182-2-en.vsdx
IEC05000182 V2 EN-US
The operation of Distance measuring zone, quadrilateral characteristic for series compensated lines
(ZMCPDIS,ZMCAPDIS) is blocked if the magnitude of input currents fall below certain threshold
values.
For zone 1 with load compensation feature the additional criterion applies, that all phase-to-earth
loops will be blocked when IN < IMinOpIN, regardless of the phase currents.
ILn is the RMS value of the current in phase Ln. IN is the RMS value of the vector sum of the three
phase currents, that is, residual current 3I0.
ILmLn is the RMS value of the vector difference between phase currents Lm and Ln.
All three current limits IMinOpPE, IMinOpIN and IMinOpPP are automatically
reduced to 75% of regular set values if the zone is set to operate in reverse
direction, that is, OperationDir=Reverse.
Fault loop equations use the complex values of voltage, current, and changes in the current.
Apparent impedances are calculated and compared with the set limits. The calculation of the
apparent impedances at ph-ph faults follows equation 55 (example for a phase L1 to phase L2 fault).
UL1 – UL2
Zapp = -------------------------
I L1 – IL2
EQUATION1222 V1 EN-US (Equation 55)
Here U and I represent the corresponding voltage and current phasors in the respective phase.
The earth return compensation applies in a conventional manner to ph-E faults (example for a phase
L1 to earth fault) according to equation 56.
U L1
Z app =
I L1 + I N × KN
EQUATION1223 V2 EN-US (Equation 56)
Where:
UL1, IL1 and IN are the phase voltage, phase current and residual current present to the IED
KN is defined as:
Z 0 - Z1
KN =
3 × Z1
EQUATION-2105 V2 EN-US
Z 0 = R 0 + jX 0
EQUATION2106 V2 EN-US
Z 1 = R1 + jX 1
EQUATION2107 V2 EN-US
Where
R0 is setting of the resistive zero sequence reach
X0 is setting of the reactive zero sequence reach
R1 is setting of the resistive positive sequence reach
X1 is setting of the reactive positive sequence reach
Here IN is a phasor of the residual current at the IED point. This results in the same reach along the
line for all types of faults.
The apparent impedance is considered as an impedance loop with resistance R and reactance X.
The formula given in equation 56 is only valid for no loaded radial feeder applications. When load is
considered in the case of single phase-to-earth fault, conventional distance protection might
overreach at exporting end and underreach at importing end. IED has an adaptive load
compensation which increases the security in such applications.
Measuring elements receive current and voltage information from the A/D converter. The check sums
are calculated and compared, and the information is distributed into memory locations. For each of
the six supervised fault loops, sampled values of voltage (U), current (I), and changes in current
between samples (DI) are brought from the input memory and fed to a recursive Fourier filter.
The filter provides two orthogonal values for each input. These values are related to the loop
impedance according to equation 57,
X Di
U = R × i + ------ × -----
w 0 Dt
EQUATION1224 V1 EN-US (Equation 57)
X D Re ( I )
Re ( U ) = R × Re ( I ) + ------ × ------------------
w0 Dt
X DIm ( I )
Im ( U ) = R × Im ( I ) + ------ × -----------------
w0 Dt
with
w0 = 2 × p × f 0
EQUATION356 V1 EN-US (Equation 60)
where:
Re designates the real component of current and voltage,
Im designates the imaginary component of current and voltage and
f0 designates the rated system frequency
The algorithm calculates Rm measured resistance from the equation for the real value of the voltage
and substitute it in the equation for the imaginary part. The equation for the Xm measured reactance
can then be solved. The final result is equal to:
Im ( U ) × DRe ( I ) – Re ( U ) × D Im ( I )
R m = ------------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – D Im ( I ) × Re ( I )
EQUATION357 V1 EN-US (Equation 61)
Re ( U ) × Im ( I ) – Im ( U ) × Re ( I )
Xm = w 0 × Dt × -------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – DIm ( I ) × Re ( I )
EQUATION358 V1 EN-US (Equation 62)
The calculated Rm and Xm values are updated each sample and compared with the set zone reach.
The adaptive tripping counter counts the number of permissive tripping results. This effectively
removes any influence of errors introduced by the capacitive voltage transformers or by other factors.
The directional evaluations are performed simultaneously in both forward and reverse directions, and
in all six fault loops. Positive sequence voltage and a phase locked positive sequence memory
voltage are used as a reference. This ensures unlimited directional sensitivity for faults close to the
IED point.
In the basic distance protection function, the control of the memory for polarizing voltage is
performed by an undervoltage control. In case of series compensated line, a voltage reversal can
occur with a relatively high voltage also when the memory must be locked. Thus, a simple
undervoltage type of voltage memory control can not be used in case of voltage reversal. In the
option for series compensated network the polarizing quantity and memory are controlled by an
impedance measurement criterion.
The polarizing voltage is a memorized positive sequence voltage. The memory is continuously
synchronized via a positive sequence filter. The memory is starting to run freely instantaneously
when a voltage change is detected in any phase. A non-directional impedance measurement is used
to detect a fault and identify the faulty phase or phases.
At a three phase fault when no positive sequence voltage remains (all three phases are
disconnected) the memory is used for direction polarization during 100 ms.
The memory predicts the phase of the positive sequence voltage with the pre-fault frequency. This
extrapolation is made with a high accuracy and it is not the accuracy of the memory that limits the
time the memory can be used. The network is at a three phase fault under way to a new equilibrium
and the post-fault condition can only be predicted accurately for a limited time from the pre-fault
condition.
In case of a three phase fault after 100 ms the phase of the memorized voltage can not be relied
upon and the directional measurement has to be blocked. The achieved direction criteria are sealed-
in when the directional measurement is blocked and kept until the impedance fault criteria is reset
(the direction is stored until the fault is cleared).
This memory control allows in the time domain unlimited correct directional measurement for all
unsymmetrical faults also at voltage reversal. Only at three phase fault within the range of the set
impedance reach of the criteria for control of the polarization voltage the memory has to be used and
the measurement is limited to 100 ms and thereafter the direction is sealed-in. The special
impedance measurement to control the polarization voltage is set separately and has only to cover
(with some margin) the impedance to fault that can cause the voltage reversal.
The evaluation of the directionality takes place in Directional impedance quadrilateral, including
series compensation (ZDSRDIR) function. Equation 63 and equation 64 are used to classify that the
fault is in forward direction for phase-to-earth fault and phase-to-phase fault.
U 1L1M
- ArgDir < arg < ArgNeg Re s
I L1
EQUATION2004 V2 EN-US (Equation 63)
For the L1-L2 element, the equation in forward direction is according to:
U 1L1L 2 M
- ArgDir < arg < ArgNeg Re s
I L1L 2
EQUATION2006 V2 EN-US (Equation 64)
where:
ArgDir is the setting for the lower boundary of the forward directional characteristic, by default set to 15 (= -15
degrees) and
ArgNegRes is the setting for the upper boundary of the forward directional characteristic, by default set to 115
degrees, see Figure 121.
U1 L1M is positive sequence memorized phase voltage in phase L1
U1 L1L2M is memorized voltage difference between phase L1 and L2 (L2 lagging L1)
The setting of ArgDir and ArgNegRes is by default set to 15 (= -15) and 115 degrees respectively,
see Figure 121, and it should not be changed unless system studies have shown the necessity.
ZDSRDIR generates a binary coded signal on the output STDIR depending on the evaluation where
STFWL1N=1 adds 1, STRVL1N=1 adds 2, STFWL2N=1 adds 4.
ArgNegRes
ArgDir
R
en05000722.vsd
IEC05000722 V1 EN-US
Figure 121: Setting angles for discrimination of forward and reverse fault
The reverse directional characteristic is equal to the forward characteristic rotated by 180 degrees.
Phase-to-earth related signals are designated by Ln, where n represents the corresponding phase
number (L1, L2, and L3). The phase-to-phase signals are designated by LnLm, where n and m
represent the corresponding phase numbers (L1L2, L2L3, and L3L1).
Fulfillment of two different measuring conditions is necessary to obtain the one logical signal for each
separate measuring loop:
• Zone measuring condition, which follows the operating equations described above.
• Group functional input signal (STCND), as presented in figure 122.
Two types of function block, ZMCPDIS and ZMCAPDIS, are used in the IED. ZMCPDIS is used for
zone 1 and ZMCAPDIS for zone 2 - 5.
The STCND input signal represents a connection of six different integer values from the phase
selection function within the IED, which are converted within the zone measuring function into
corresponding boolean expressions for each condition separately. It is connected to Phase selection
with load enchroachment, quadrilateral characteristic (FDPSPDIS) function output STCNDZ.
STZMPP
OR
STCND
AND STNDL1L2
L1L2
STNDL2L3
L2L3 AND
AND STNDL1N
L1N
AND STNDL2N
L2N
STNDL3N
L3N AND
OR STPE
OR
VTSZ STND
OR AND
BLOCK
BLOCFUNC BLK
99000557-2.vsd
IEC99000557-TIFF V3 EN-US
IEC00000488-TIFF V1 EN-US
STNDL1N
AND
DIRL1N
STZMPE.
OR
STNDL2N
DIRL2N AND
STNDL3N 15 ms
OR STL1
AND AND t
DIRL3N
STNDL1L2
DIRL1L2 AND 15 ms
OR STL2
AND t
STNDL2L3
DIRL2L3 AND
15 ms
OR STL3
STNDL3L1 AND t
DIRL3L1 AND
STZMPP
OR
BLK
15 ms
OR START
AND t
IEC09000888-2-en.vsd
IEC09000888 V2 EN-US
Timer tPP=On
STZMPP AND tPP
AND
t
BLOCFUNC
OR OR
tPE
t
AND
Timer tPE=On AND
STZMPE 15ms
BLKTR AND t
TRIP
BLK OR
IEC09000887-3-en.vsdx
IEC09000887 V3 EN-US
Figure 125: Tripping logic for the distance protection zone one
SEMOD173239-2 v10
8.4.1 Identification
SEMOD154447-2 v2
Z
S00346 V2 EN-US
The numerical mho line distance protection is an up to five (depending on product variant) zone full
scheme protection of short circuit and earth faults.
The full scheme technique provides back-up protection of power lines with high sensitivity and low
requirement on remote end communication.
The zones have fully independent measuring and settings, which gives high flexibility for all types of
lines.
The function can be used as under impedance back-up protection for transformers and generators.
ZMHPDIS
I3P* TRIP
U3P* TRL1
CURR_INP* TRL2
VOLT_INP* TRL3
POL_VOLT* TRPE
BLOCK TRPP
BLKZ START
BLKZMTD STL1
BLKHSIR STL2
BLKTRIP STL3
BLKPE STPE
BLKPP STPP
EXTNST STTIMER
INTRNST
DIRCND
STCND*
LDCND
IEC06000423-2-en.vsd
IEC06000423 V3 EN-US
PID-3552-INPUTSIGNALS v7
PID-3552-OUTPUTSIGNALS v7
PID-3552-SETTINGS v7
The execution of the different fault loops within the IED are of full scheme type, which means that
each fault loop for phase-to-earth faults and phase-to-phase faults are executed in parallel for all
zones.
The use of full scheme technique gives faster operation time compared to switched schemes which
mostly uses a start element to select correct voltages and current depending on fault type. So each
distance protection zone performs like one independent distance protection function with six
measuring elements.
The Mho distance function ZMHPDIS is present with four instances so that four separate zones could
be designed. Each instance can be selected to be either forward or reverse with positive sequence
polarized mho characteristic; alternatively self polarized offset mho characteristics is also available.
One example of the operating characteristic is shown in Figure 127 A) where zone 5 is selected
offset mho.
The directional mho characteristic of Figure 127 B) has a dynamic expansion due to the source
impedance. Instead of mho characteristic crossing origin, which is only valid where the source
impedance is zero, the crossing point is moved to the coordinates of the negative source impedance
giving an expansion of the circle of Figure 127 B).
A B
jx X
Mho, zone4
Mho, zone2 R
Mho, zone1
Zs=Z1
Zs=2Z1
R
Offset mho, zone5
IEC09000143-3-en.vsd
IEC09000143 V3 EN-US
Figure 127: Mho, offset mho characteristic and the source impedance influence on the mho characteristic
The polarization quantities used for the mho circle are 100% memorized positive sequence voltages.
This will give a somewhat less dynamic expansion of the mho circle during faults than a plain cross
polarized characteristic. However, if the source impedance is high, the dynamic expansion of the
mho circle might lower the security of the function too much with high loading and mild power swing
conditions.
The mho distance element has a load encroachment function which cuts off a section of the
characteristic when enabled. The function is enabled by setting the setting parameter
LoadEnchMode to On. Enabling of the load encroachment function increases the possibility to detect
high resistive faults without interfering with the load impedance. The algorithm for the load
encroachment is located in the Faulty phase identification with load encroachment for mho function
FMPSPDIS, where also the relevant settings can be found. Information about the load encroachment
from FMPSPDIS to the zone measurement is given in binary format to the input signal LDCND.
Each impedance zone can be switched On and Off by the setting parameter Operation.
Each zone can be set to Non-directional, Forward or Reverse by setting the parameter DirMode .
The operation for phase-to-earth and phase-to-phase fault can be individually switched On and Off
by the setting parameter OpModePE and OpModePP.
For critical applications such as for lines with high SIRs as well as CVTs, it is possible to improve the
security by setting the parameter ReachMode to Underreach. In this mode the reach for faults close
to the zone reach is reduced by 20% and the filtering is also introduced to increase the accuracy in
the measuring. If the ReachMode is set to Overreach no reduction of the reach is introduced and no
extra filtering introduced. The latter setting is recommended for overreaching pilot zone, zone 2 or
zone 3 elements and reverse zone where overreaching on transients is not a major issue either
because of less likelihood of overreach with higher settings or the fact that these elements do not
initiate tripping unconditionally.
The offset Mho characteristic can be set in Non-directional, Forward or Reverse by the setting
parameter OffsetMhoDir. When Forward or Reverse is selected a directional line is introduced.
Information about the directional line is given from the directional element and given to the measuring
element as binary coded signal to the input DIRCND.
The zone reach for phase-to-earth fault and phase-to-phase fault is set individually in polar
coordinates.
The impedance is set by the parameters ZPE and ZPP and the corresponding arguments by the
parameters ZAngPE and ZAngPP.
Compensation for earth -return path for faults involving earth is done by setting the parameter
KNMag and KNAng where KNMag is the magnitude of the earth-return path and KNAng is the
difference of angles between KNMag and ZPE .
Z0-Z1
KNMag =
3 × Z1
EQUATION1579 V1 EN-US (Equation 65)
KNAng = arg
( Z 0 - Z1
3 × Z1
)
EQUATION1580 V1 EN-US (Equation 66)
where
Z0 is the complex zero sequence impedance of the line in Ω/phase
Z1 is the complex positive sequence impedance of the line in Ω/phase
The phase-to-earth and phase-to-phase measuring loops can be time delayed individually by setting
the parameter tPE and tPP respectively. To release the time delay, the operation mode for the timers,
OpModetPE and OpModetPP, has to be set to On. This is also the case for instantaneous operation.
The operate timers triggering input depends on the parameter ZnTimerSel setting. The parameter
ZnTimerSel can be set to:
• Timers separated: Phase-to-earth and phase-to-phase timers are triggered by the respective
measuring loop start signals.
• Timers linked: Start of any of the phase-to-earth or phase-to-phase loops will trigger both the
phase-to-earth or phase-to-phase timers.
• Internal start: Phase-to-earth and phase-to-phase timers are triggered by the INTRNST input.
• Start from PhSel: The phase-to-earth and phase-to-phase timers are triggered by the STCND
and LDCND inputs. Each of the two inputs consist binary status information related to the six
measuring loops. Hence if any of the measuring loop status is high in both two inputs STCND
and LDCND, then the timers will be triggered. In case when LoadEnchMode is off then only
STCND enables the timer.
It is not recommended to use this timer setting for the Zone instance where
LoadEnchMode is off.
• External start: Phase-to-earth and phase-to-phase timers are triggered by the EXTNST input.
The activation of input signal BLKZ can be made by external fuse failure function or from the loss of
voltage check in the Mho supervision logic (ZSMGAPC). In both cases the output BLKZ in the Mho
supervision logic shall be connected to the input BLKZ in the Mho distance function block
(ZMHPDIS)
The input signal BLKZMTD is activated during some ms after fault has been detected by ZSMGAPC
to avoid unwanted operations due to transients. It shall be connected to the BLKZMTD output signal
of ZSMGAPC function.
At SIR values >10, the use of electronic CVT might cause overreach due to the built-in resonance
circuit in the CVT, which reduce the secondary voltage for a while. The input BLKHSIR is connected
to the output signal HSIR on ZSMGAPC for increasing of the filtering and high SIR values. This is
valid only when permissive underreach scheme is selected by setting ReachMode=Underreach.
The mho algorithm is based on the phase comparison of an operating phasor and a polarizing
phasor. When the operating phasor leads the reference polarizing phasor by 90 degrees or more, the
function operates and gives a trip output.
Mho SEMOD154224-217 v5
The plain Mho circle has the characteristic as in Figure 128. The condition for deriving the angle β is
according to equation 67.
where
The polarized voltage consists of 100% memorized positive sequence voltage (UL1L2 for phase L1
to L2 fault). The memorized voltage will prevent collapse of the Mho circle for close in faults.
IL1L2·X
Ucomp = UL1L2 - IL1L2 • ZPP
IL1L2 • ZPP
ß
Upol
UL1L2
IL1L2·R
en07000109.vsd
IEC07000109 V1 EN-US
Figure 128: Simplified mho characteristic and vector diagram for phase L1-to-L2 fault
The condition for operation at phase-to-phase fault is that the angle β between the two compensated
voltages Ucomp1 and Ucomp2 is greater than or equal to 90° (figure 129). The angle will be 90° for
fault location on the boundary of the circle.
The angle β for L1-to-L2 fault can be defined according to equation 68.
æ ö
U -IL1L2 × ZPP
b = arg ç ÷
è U-(-IL1L2 × ZRevPP) ø
EQUATION1792 V1 EN-US (Equation 68)
where
ZRevPP is the positive sequence impedance setting for phase-to-phase fault in reverse direction
IL1L2jX
U
Ucomp2 = U = IF•ZF=UL1L2
IL1L2R
- IL1L2 • Z RevPP
en07000110.vsd
IEC07000110 V1 EN-US
Figure 129: Simplified offset mho characteristic and voltage vectors for phase L1-to-L2 fault.
Operation occurs if 90≤β≤270.
where
ArgDir is the setting parameter for directional line in fourth quadrant in the directional element,
ZDMRDIR.
ArgNegRes is the setting parameter for directional line in second quadrant in the directional element,
ZDMRDIR.
β is calculated according to equation
The directional information is brought to the mho distance measurement from the mho directional
element as binary coded information to the input DIRCND. See Directional impedance element for
mho characteristic (ZDMRDIR) for information about the mho directional element.
IL1L2jX
ZPP
UL1L2
ArgNegRes f
IL1L2
ArgDir
en07000111.vsd
IEC07000111 V1 EN-US
Figure 130: Simplified offset mho characteristic in forward direction for phase L1-to-L2 fault
The β is derived according to equation for the mho circle and φ is the angle between the voltage and
current.
ZPP
ArgNegRes
ϕ
IL1L2
ArgDir R
UL1L2
ZRevPP
en06000469.eps
IEC06000469 V1 EN-US
Mho SEMOD154224-120 v5
The measuring of earth faults uses earth-return compensation applied in a conventional way. The
compensation voltage is derived by considering the influence from the earth-return path.
For an earth fault in phase L1, the compensation voltage Ucomp can be derived, as shown in Figure
132.
where
U pol is the polarizing voltage (memorized UL1 for Phase L1-to- earth
fault)
Zloop is the loop impedance, which in general terms can be expressed as
(
Z1+ZN = Z 1 × 1 + KN )
where
Z1 is the positive sequence impedance of the line (Ohm/phase)
The angle β between the Ucomp and the polarize voltage Upol for a L1-to-earth fault is
(
β = arg U L1 − I L1 + 3I 0 ⋅ KN ⋅ ZPE − arg (Upol )
)
GUID-A9492CDF-D3B7-4DC5-8E06-6638BEE2540B V2 EN-US (Equation 70)
where
UL1 is the phase voltage in faulty phase L1
KN Z0-Z1
3 × Z1
the setting parameter for the zero sequence compensation
consisting of the magnitude KN and the angle KNAng.
Upol is the 100% of positive sequence memorized voltage UL1
IL1·X
IL1·ZN
Ucomp
IL1 • Zloop
IL1·ZPE
Upol
f
IL1 (Ref) IL1·R
en06000472_2.vsd
IEC06000472 V2 EN-US
Figure 132: Simplified offset mho characteristic and vector diagram for phase L1-to-earth fault
Operation occurs if 90≤β≤270.
The condition for operation at phase-to-earth fault is that the angle β between the two compensated
voltages Ucomp1 and Ucomp2 is greater or equal to 90° see figure 133. The angle will be 90° for
fault location on the boundary of the circle.
IL1L 2 • jX
UL1
U comp2 = UL1 - (-IL1 • ZRevPE)
IL1L2 • R
- I L1 • Z Re vPe
en 06000465.vsd
IEC06000465 V1 EN-US
Figure 133: Simplified offset mho characteristic and voltage vector for phase L1-to-earth fault
Operation occurs if 90≤β≤270.
where
ArgDir is the setting parameter for directional line in fourth quadrant in the directional element,
ZDMRDIR.
ArgNegRes is the setting parameter for directional line in second quadrant in the directional element,
ZDMRDIR.
β is calculated according to equation
IL1 jX
UL1
ArgNegRes f
IL1 IL1·R
ArgDir
en 06000466.vsd
IEC06000466 V1 EN-US
Figure 134: Simplified characteristic for offset mho in forward direction for L1-to-earth fault
The conditions for operation of offset mho in reverse direction for L1-to-earth fault is 90≤β≤270 and
180°-Argdir≤φ≤ArgNegRes+180°.
The β is derived according to equation for the offset mho circle and φ is the angle between the
voltage and current.
ZPE
ArgNegRes
ϕ
IL
1
ArgDir R
UL1
ZRevPE
en06000470.eps
IEC06000470 V1 EN-US
Figure 135: Simplified characteristic for offset mho in reverse direction for L1-to-earth fault
Phase-to-earth related signals are designated by L1N, L2N and L3N. The phase-to-phase signals are
designated by L1L2, L2L3, and L3L1.
Fulfillment of two different measuring conditions is necessary to obtain the one logical signal for each
separate measuring loop:
• Zone measuring condition, which follows the operating equations described above.
• Group functional input signal (STCND), as presented in figure 136.
The ZMHPDIS function block is used in the IED for each zone.
The STCND input signal represents a connection of six different integer values from Phase selection
with load encroachment function FMPSPDIS within the IED, which are converted within the zone
measuring function into corresponding boolean expressions for each condition separately. Input
signal STCND is connected from FMPSPDIS function output signal STCNDPHS.
The input signal DIRCND is used to give condition for directionality for the distance measuring zones.
The signal contains binary coded information for both forward and reverse direction. The zone
measurement function filters out the relevant signals depending on the setting of the parameter
DirMode. Input signal DIRCND must be configured to the STDIRCND output signal on ZDMRDIR
function.
OffsetMhoDir=
Non-directional
AND AND
DirMode=Offset
STCND T
AND F
AND
LoadEnchMode=
On/Off
LDCND
T
True F
AND Release
DIRCND
OffsetMhoDir=
Forward/Reverse
AND
DirMode=
Forward/Reverse
BLKZ
BLOCK OR
IEC11000216-1-en.vsd
IEC11000216 V1 EN-US
Results of the directional measurement enter the logic circuits when the zone operates in directional
(forward or reverse) mode, as shown in figure 136.
Release STPE
OR
AND
STL1N STL1
OR
AND
STL2N
AND
STL3N
STL2
OR
AND
STL1L2
AND
STL2L3
STL3
OR
AND
STL3L1
START
OR
STPP
OR
IEC11000217-1-en.vsd
IEC11000217 V1 EN-US
15ms
AND TRIP
BLKTRIP t
AND TRL2
STL2
IEC11000218-1-en.vsd
IEC11000218 V1 EN-US
STPE
BLOCK
TRPE
&
tON
& ³1 t
a
Internal a=b
start b STTIMER
&
Internal
a
a<b
start b
tON
³1 t && TRPP
&
STPP
ZnTimerSel
FALSE 1 timers seperated
³1 2 timers linked
internalCommonStart
3 internal start
phSelStart 4 start from phSel
externalCommonStart
5 external start
IEC12000463-3-en.vsd
IEC12000463 V2 EN-US
SEMOD173242-2 v14
8.5.1 Identification
SEMOD154542-2 v2
The line distance protection is an up to five (depending on product variant) zone full scheme
protection function with three fault loops for phase-to-earth fault for each of the independent zones.
Individual settings for each zone resistive and reactive reach give flexibility for use on overhead lines
and cables of different types and lengths.
The Full-scheme distance protection, quadrilateral for earth fault functions have functionality for load
encroachment, which increases the possibility to detect high resistive faults on heavily loaded lines ,
see Figure 140.
Forward
operation
Reverse
operation
en05000034.vsd
IEC05000034 V1 EN-US
Figure 140: Typical quadrilateral distance protection zone with Phase selection, quadrilateral
characteristic with settable angle function FRPSPDIS activated
The independent measurement of impedance for each fault loop together with a sensitive and
reliable built in phase selection makes the function suitable in applications with single phase auto-
reclosing.
Built-in adaptive load compensation algorithm prevents overreaching of zone1 at load exporting end
at phase to earth faults on heavily loaded power lines.
The distance protection zones can operate, independent of each other, in directional (forward or
reverse) or non-directional mode. This makes them suitable, together with different communication
schemes, for the protection of power lines and cables in complex network configurations, such as
parallel lines, multi-terminal lines.
ZMMPDIS
I3P* TRIP
U3P* TRL1
BLOCK TRL2
BLKZ TRL3
BLKTR START
STCND STL1
DIRCND STL2
STL3
STND
IEC06000454-2-en.vsd
IEC06000454 V2 EN-US
ZMMAPDIS
I3P* TRIP
U3P* TRL1
BLOCK TRL2
BLKZ TRL3
BLKTR START
STCND STL1
DIRCND STL2
STL3
STND
IEC09000947-1-en.vsd
IEC09000947 V1 EN-US
8.5.4 Signals
PID-3645-INPUTSIGNALS v6
PID-3645-OUTPUTSIGNALS v6
PID-3640-INPUTSIGNALS v6
PID-3640-OUTPUTSIGNALS v6
8.5.5 Settings
PID-3645-SETTINGS v6
PID-3640-SETTINGS v6
The different fault loops within the IED are operating in parallel in the same principle as a full scheme
measurement.
Figure 143 presents an outline of the different measuring loops for the basic five, impedance-
measuring zones l.
en07000080.vsd
IEC07000080 V1 EN-US
Figure 143: The different measuring loops at line-earth fault and phase-phase fault.
The distance measuring zone include three impedance measuring loops; one fault loop for each
phase.
The distance measuring zone will essentially operate according to the non-directional impedance
characteristics presented in Figure 144. The characteristic is illustrated with the full loop reach.
X (Ohm/loop)
R1PE+Rn
RFPE RFPE
X0PE-X1PE
Xn =
3
X1PE+Xn R0PE-R1PE
Rn =
3
jN jN
R (Ohm/loop)
RFPE RFPE
X1PE+Xn
RFPE RFPE
en08000280-2-en.vsd
R1PE+Rn
IEC08000280 V1 EN-US
Figure 144: Characteristic for the phase-to-earth measuring loops, ohm/loop domain.
The fault loop reach may also be presented as in Figure 145.
ILn R1 + j X1
Phase-to-earth
UL1
element
Phase-to-earth
fault in phase L1 RFPE
(Arc + tower
resistance)
0
IN (R0-R1)/3 +
j (X0-X1)/3 ) en06000412.vsd
IEC06000412 V1 EN-US
The zone may be set to operate in Non-directional, Forward, Off or Reverse direction through the
setting OperationDir. The result from respective set value is illustrated in Figure 146. The impedance
reach is symmetric, in the sense that it is conform for forward and reverse direction. Therefore, all
reach settings apply to both directions.
X X X
R R R
IEC05000182-2-en.vsdx
IEC05000182 V2 EN-US
The operation of the distance measuring zone is blocked if the magnitude of input currents fall below
certain threshold values.
For zone 1 with load compensation feature the additional criterion applies, that all phase-to-earth
loops will be blocked when IN < IMinOpIN, regardless of the phase currents.
ILn is the RMS value of the current in phase Ln. IN is the RMS value of the vector sum of the three
phase currents, that is, residual current 3I0.
Both current limits IMinOpPE and IMinOpIN are automatically reduced to 75% of
regular set values if the zone is set to operate in reverse direction, that is,
OperationDir=Reverse.
Fault loop equations use the complex values of voltage, current, and changes in the current.
Apparent impedances are calculated and compared with the set limits.
Here U and I represent the corresponding voltage and current phasors in the respective phase Ln (n
= 1, 2, 3).
U L1
Z app =
I L1 + I N × KN
EQUATION1223 V2 EN-US (Equation 72)
Where:
UL1, IL1 and IN are the phase voltage, phase current and residual current present to the IED
KN is defined as:
Z 0 - Z1
KN =
3 × Z1
EQUATION-2105 V2 EN-US
Z 0 = R 0 + jX 0
EQUATION2106 V2 EN-US
Z 1 = R1 + jX 1
EQUATION2107 V2 EN-US
Where
R0 is setting of the resistive zero sequence reach
X0 is setting of the reactive zero sequence reach
R1 is setting of the resistive positive sequence reach
X1 is setting of the reactive positive sequence reach
Here IN is a phasor of the residual current in IED point. This results in the same reach along the line
for all types of faults.
The apparent impedance is considered as an impedance loop with resistance R and reactance X.
The formula given in equation 72 is only valid for no loaded radial feeder applications. When load is
considered in the case of single phase-to-earth fault, conventional distance protection might
overreach at exporting end and underreach at importing end. IED has an adaptive load
compensation which increases the security in such applications.
Measuring elements receive current and voltage information from the A/D converter. The check sums
are calculated and compared, and the information is distributed into memory locations. For each of
the six supervised fault loops, sampled values of voltage (U), current (I), and changes in current
between samples (DI) are brought from the input memory and fed to a recursive Fourier filter.
The filter provides two orthogonal values for each input. These values are related to the loop
impedance according to equation 73,
X Di
U = R × i + ------ × -----
w 0 Dt
EQUATION1224 V1 EN-US (Equation 73)
X D Re ( I )
Re ( U ) = R × Re ( I ) + ------ × ------------------
w0 Dt
X DIm ( I )
Im ( U ) = R × Im ( I ) + ------ × -----------------
w0 Dt
with
w0 = 2 × p × f 0
EQUATION356 V1 EN-US (Equation 76)
where:
Re designates the real component of current and voltage,
Im designates the imaginary component of current and voltage and
f0 designates the rated system frequency
The algorithm calculates Rm measured resistance from the equation for the real value of the voltage
and substitute it in the equation for the imaginary part. The equation for the Xm measured reactance
can then be solved. The final result is equal to:
Im ( U ) × DRe ( I ) – Re ( U ) × D Im ( I )
R m = ------------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – D Im ( I ) × Re ( I )
EQUATION357 V1 EN-US (Equation 77)
Re ( U ) × Im ( I ) – Im ( U ) × Re ( I )
Xm = w 0 × Dt × -------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – DIm ( I ) × Re ( I )
EQUATION358 V1 EN-US (Equation 78)
The calculated Rm and Xm values are updated each sample and compared with the set zone reach.
The adaptive tripping counter counts the number of permissive tripping results. This effectively
removes any influence of errors introduced by the capacitive voltage transformers or by other factors.
The directional evaluations are performed simultaneously in both forward and reverse directions, and
in all six fault loops. Positive sequence voltage and a phase locked positive sequence memory
voltage are used as a reference. This ensures unlimited directional sensitivity for faults close to the
IED point.
The evaluation of the directionality takes place in the Directional impedance element for mho
characteristic ZDMRDIR function. Equation 79 is used to classify that the fault is in forward direction
for line-to-earth fault.
where:
ArgDir is the setting for the lower boundary of the forward directional characteristic, by default set to 15 (= -15
degrees) and
ArgNegRes is the setting for the upper boundary of the forward directional characteristic, by default set to 115
degrees, see figure 147.
U1 L1 is positive sequence phase voltage in phase L1
The setting of ArgDir and ArgNegRes is by default set to 15 (= -15) and 115 degrees respectively
(see figure 147) and it should not be changed unless system studies have shown the necessity.
ZDMRDIR gives a binary coded signal on the output STDIRCND depending on the evaluation where
STFWL1N=1 adds 1, STRVL1N=1 adds 2, STFWL2N=1 adds 4 etc.
ArgNegRes
ArgDir
R
en05000722.vsd
IEC05000722 V1 EN-US
Figure 147: Setting angles for discrimination of forward and reverse fault
The reverse directional characteristic is equal to the forward characteristic rotated by 180 degrees.
The polarizing voltage is available as long as the positive-sequence voltage exceeds 5% of the set
base voltage UBase. So the directional element can use it for all unsymmetrical faults including
close-in faults.
For close-in three-phase faults, the U1L1M memory voltage, based on the same positive sequence
voltage, ensures correct directional discrimination.
The memory voltage is used for 100 ms or until the positive sequence voltage is restored.
• If the current is still above the set value of the minimum operating current (between 10 and 30%
of the set IED rated current IBase), the condition seals in.
• If the fault has caused tripping, the trip endures.
• If the fault was detected in the reverse direction, the measuring element in the reverse
direction remains in operation.
• If the current decreases below the minimum operating value, the memory resets until the
positive sequence voltage exceeds 10% of its rated value.
Phase-to-earth related signals are designated by LnE, where n represents the corresponding phase
number (L1E, L2E, and L3E).
Fulfillment of two different measuring conditions is necessary to obtain the one logical signal for each
separate measuring loop:
• Zone measuring condition, which follows the operating equations described above.
• Group functional input signal (STCND), as presented in figure 148.
The STCND input signal represents a connection of six different integer values from the phase
selection function within the IED, which are converted within the zone measuring function into
corresponding boolean expressions for each condition separately. It is connected to the Phase
selection with load enchroachment, quadrilateral characteristic (FDPSPDIS) function output
STCNDZ.
The input signal DIRCND is used to give condition for directionality for the distance measuring zones.
The signal contains binary coded information for both forward and reverse direction. The zone
measurement function filter out the relevant signals on the DIRCND input depending on the setting of
the parameter OperationDir. It shall be configured to the DIRCND output on the Directional
impedance element for mho characteristic (ZDMRDIR) function.
STCND
AND STNDL1N
L1N
AND STNDL2N
L2N
STNDL3N
L3N AND
OR STNDPE
OR
BLKZ STND
OR AND
BLOCK
BLK
en06000408-2.vsd
IEC06000408 V2 EN-US
STNDL1N 15 ms
AND t STL1
STNDL2N 15 ms
AND t STL2
STNDL3N 15 ms
AND t STL3
15 ms
AND t START
OR
BLK
en06000409.vsd
IEC06000409 V1 EN-US
STNDL1N
DIRL1N AND
OR STZMPE.
&
STNDL2N
DIRL2N AND
STNDL3N 15 ms
STL1
& t
DIRL3N AND
15 ms
STL2
& t
15 ms
STL3
& t
BLK
15 ms
OR START
& t
en07000081.vsd
IEC07000081 V1 EN-US
en07000082.vsd
IEC07000082 V1 EN-US
Figure 151: Tripping logic for the distance protection zone one
8.6.1 Identification
SEMOD155886-2 v2
GUID-39299546-12A2-4D9D-86D0-A33F423944E4 v2
ZDMRDIR
I3P* DIR_CURR
U3P* DIR_VOLT
DIR_POL
STFW
STRV
STDIRCND
IEC06000422_2_en.vsd
IEC06000422 V2 EN-US
ZDARDIR
I3P* STFWPE
U3P* STRVPE
I3PPOL* DIREFCND
DIRCND
IEC06000425-2-en.vsd
IEC06000425 V2 EN-US
8.6.4 Signals
PID-3546-INPUTSIGNALS v7
PID-3546-OUTPUTSIGNALS v7
PID-3564-INPUTSIGNALS v7
PID-3564-OUTPUTSIGNALS v7
8.6.5 Settings
PID-3546-SETTINGS v7
PID-3564-SETTINGS v7
The evaluation of the directionality takes place in Directional impedance element for mho
characteristic (ZDMRDIR). Equation 80 and equation 81 are used to classify that the fault is in the
forward direction for phase-to-earth fault and phase-to-phase fault respectively.
Where:
ArgDir Setting for the lower boundary of the forward directional characteristic, by default set to
15 (= -15 degrees)
ArgNegRes Setting for the upper boundary of the forward directional characteristic, by default set to
115 degrees, see figure 154 for mho characteristics.
Table continues on next page
U1 L1L2M Memorized voltage difference between phase L1 and L2 (L2 lagging L1)
The default settings for ArgDir and ArgNegRes are 15 (= -15) and 115 degrees respectively (see
figure 154) and they should not be changed unless system studies show the necessity.
If one sets DirEvalType to Comparator (which is recommended when using the mho characteristic)
then the directional lines are computed by means of a comparator-type calculation, meaning that the
directional lines are based on mho-circles (of infinite radius). The default setting value Impedance
otherwise means that the directional lines are implemented based on an impedance calculation
equivalent to the one used for the quadrilateral impedance characteristics.
X
Zset reach point
ArgNegRes
-ArgDir R
-Zs
en06000416.vsd
IEC06000416 V1 EN-US
The code built up for release of the measuring fault loops is as follows: STDIRCND = L1N*1 + L2N*2
+ L3N*4 + L1L2*8 + L2L3*16 + L3L1*32
Example: If only L1N start, the value is 1, if start in L1N and L3N are detected, the value is 1+4=5.
The polarizing voltage is available as long as the positive-sequence voltage exceeds 5% of the set
base voltage UBase, thus the directional element can use it for all unsymmetrical faults including
close-in faults.
For close-in three-phase faults, the U1L1M memory voltage, based on the same positive sequence
voltage, ensures correct directional discrimination.
The memory voltage is used for 100ms or until the positive sequence voltage is restored. After
100ms, the following occurs:
• If the current is still above the set value of the minimum operating current the condition seals in.
• If the fault has caused tripping, the trip continues.
• If the fault was detected in the reverse direction, the measuring element in the reverse
direction remains in operation.
• If the current decreases below the minimum operate value, no directional indications will be
given until the positive sequence voltage exceeds 10% of its rated value.
The Directional impedance element for mho characteristic (ZDMRDIR) function has the following
output signals:
The STDIRCND output provides an integer signal that depends on the evaluation and is derived from
a binary coded signal as follows:
The STFW output is a logical signal with value 1 or 0. It is made up as an OR-function of all the
forward starting conditions, that is, STFWL1N, STFWL2N, STFWL3N, STFWL1L2, STFWL2L3 and
STFWL3L1. The STRV output is similar to the STFW output, the only difference being that it is made
up as an OR-function of all the reverse starting conditions, that is, STRVL1N, STRVL2N, STRVL3N,
STRVL1L2, STRVL2L3 and STRVL3L1.
• The greatest amount of expansion for improved resistive coverage. These elements always
expand back to the source.
• Memory action for all fault types. This is very important for close-in three-phase faults.
• A common polarizing reference for all six distance-measuring loops. This is important for single-
pole tripping, during a pole-open period.
There are however some situations that can cause security problems like reverse phase to phase
faults and double phase-to-earth faults during high load periods. To solve these, additional directional
element is used.
For phase-to-earth faults, directional elements using sequence components are very reliable for
directional discrimination. The directional element can be based on one of following types of
polarization:
• Zero-sequence voltage
• Negative-sequence voltage
• Zero-sequence current
These additional directional criteria are evaluated in the Additional distance protection directional
function for earth faults (ZDARDIR).
Zero-sequence voltage polarization is utilizing the phase relation between the zero-sequence voltage
and the zero-sequence current at the location of the protection. The measurement principle is
illustrated in figure 155.
- 3U 0
AngleOp
AngleRCA
3I 0
en06000417.vsd
IEC06000417 V1 EN-US
Figure 155: Principle for zero-sequence voltage polarized additional directional element
Negative-sequence voltage polarization is utilizing the phase relation between the negative-
sequence voltage and the negative-sequence current at the location of the protection.
Zero-sequence current polarization is utilizing the phase relation between the zero-sequence current
at the location of the protection and some reference zero-sequence current, for example, the current
in the neutral of a power transformer.
Z0 SA I0 I0
Z0 Line Z0 SB
Charac te ris tic
ang le
U0 U0
K*I0
U0 + K*I0
IF
en06000418.vsd
IEC06000418 V1 EN-US
These polarization quantities, voltage and current, are stabilized against minimum polarizing voltage
(UPOL>) and current (IPOL>). That means if polarizing voltage is greater than UPOL> setting, and if
polarizing current is greater than IPol>, then only they are used for direction determination.
Normal
directional Release of distance
element measuring element
L1N, L2N, L3N L1N, L2N, L3N
AND
Additional
directional AND per
element phase
en06000419.vsd
IEC06000419 V1 EN-US
8.7.1 Identification
GUID-030C086A-8301-481E-BA0A-6550A9C1482E v2
The Mho impedance supervision logic (ZSMGAPC) includes features for fault inception detection and
high SIR detection. It also includes the functionality for loss of potential logic as well as for the pilot
channel blocking scheme.
ZSMGAPC
I3P* BLKZMTD
U3P* BLKCHST
BLOCK CHSTOP
REVSTART HSIR
BLOCKCS
CBOPEN
IEC06000426-2-en.vsd
IEC06000426 V2 EN-US
8.7.4 Signals
PID-6718-INPUTSIGNALS v1
PID-6718-OUTPUTSIGNALS v1
8.7.5 Settings
PID-6718-SETTINGS v1
The aim for the fault inception detector is to quickly detect that a fault has occurred in the system.
The fault detector detects a fault when there is a sufficient change in at least one current and at the
same time there is a sufficient change in at least one voltage. A change is defined roughly by the
difference between the present instantaneous value and the one from one power system cycle
before. The change is sufficient if it exceeds the related threshold value. DeltaI and DeltaU for phase
currents and voltages. Delta3I0 and Delta3U0 for residual current and voltage.
If the setting PilotMode is set to On in blocking scheme and the fault inception function has detected
a system fault, a block signal BLKCHST is issued and send to remote end in order to block the
overreaching zones. Different criteria has to be fulfilled for sending the BLKCHST signal:
If it is later detected that it was an internal fault that made the function issue the BLKCHST signal, the
function issues a CHSTOP signal to unblock the remote end. The criteria that have to be fulfilled for
this are:
1. The function has to be in pilot mode, that is, the setting PilotMode has to be set to On
2. The carrier send signal should be blocked, that is, input signal BLOCKCS is On and,
3. A reverse fault should not have been detected while the carrier send signal was not blocked,
that is, input REVSTART should not have been activated before BLOCKCS.
If loss of voltage is detected, but not a fault inception, the distance protection function is blocked.
This is also the case if a fuse failure is detected by the external fuse failure function and activate the
input FUSEFAIL. Those blocks are generated by activating the output BLKZ, which are connected to
the input BLKZ on the distance Mho function block.
During fault inception a lot of transients are developed which in turn might cause the distance
function to overreach. The Mho supervision logic (ZSMGAPC) increases the filtering during the most
transient period of the fault. This is done by activating the output BLKZMTD, which is connected to
the input BLKZMTD on mho distance function block.
The SIR function calculates the SIR value as the source impedance divided by the setting Zreach
and activates the output signal HSIR if the calculated value for any of the six basic shunt faults
exceed the setting SIRLevel. The HSIR signal is intended to block the delta based mho impedance
function.
8.8.1 Identification
SEMOD155879-2 v3
The ability to accurately and reliably classify different types of fault so that single phase tripping and
autoreclosing can be used plays an important roll in today's power systems.
The phase selection function is design to accurately select the proper fault loop(s) in the distance
function dependent on the fault type.
The heavy load transfer that is common in many transmission networks may in some cases interfere
with the distance protection zone reach and cause unwanted operation. Therefore the function has a
built in algorithm for load encroachment, which gives the possibility to enlarge the resistive setting of
the measuring zones without interfering with the load.
The output signals from the phase selection function produce important information about faulty
phase(s), which can be used for fault analysis as well.
FMPSPDIS
I3P* STL1
U3P* STL2
BLOCK STL3
ZSTART STPE
TR3PH STCNDPHS
1POLEAR STCNDPLE
STCNDLE
START
IEC06000429-2-en.vsd
IEC06000429 V2 EN-US
8.8.4 Signals
PID-3541-INPUTSIGNALS v9
PID-3541-OUTPUTSIGNALS v9
8.8.5 Settings
PID-3541-SETTINGS v9
Faulty phase identification with load encroachment for mho (FMPSPDIS) function can be
decomposed into six different parts:
The aim of the delta based phase selector is to provide very fast and reliable phase selection for
releasing of tripping from the high speed Mho measuring element and is essential to Directional
Comparison Blocking scheme (DCB), which uses Power Line Carrier (PLC) communication system
along the protected line.
The current and voltage samples for each phase passes through a notch filter that filters out the
fundamental components. Under steady state load conditions or when no fault is present, the output
of the filter is zero or close to zero. When a fault occurs, currents and voltages change resulting in
sudden changes in the currents and voltages resulting in non-fundamental waveforms being
introduced on the line. At this point the notch filter produces significant non-zero output. The filter
output is processed by the delta function. The algorithm uses an adaptive relationship between
phases to determine if a fault has occurred, and determines the faulty phases.
The current and voltage delta based phase selector gives a real output signal if the following criterion
is fulfilled (only phase L1 shown):
Max(ΔUL1,ΔUL2,ΔUL3)>DeltaUMinOp
Max(ΔIL1,ΔIL2,ΔIL3)>DeltaIMinOp
where:
ΔUL1, ΔUL2 and ΔUL3 are the voltage change between sample t and sample t-1
DeltaUMinOp and are the minimum harmonic level settings for the voltage and current
DeltaIMinOp filters to decide that a fault has occurred. A slow evolving fault may not
produce sufficient harmonics to detect the fault; however, in such a
case speed is no longer the issue and the sequence components
phase selector will operate.
The delta voltages ΔULn and delta current ΔILn (n index for phase order) are the voltage and current
between sample t and sample t-1.
The delta phase selector employs adaptive techniques to determine the fault type. The logic
determines the fault type by summing up all phase values and dividing by the largest value. Both
voltages and currents are filtered out and evaluated. The condition for fault type classification for the
voltages and currents can be expressed as:
FaulType =
∑ ( ∆UL1, ∆UL2, ∆UL3)
MAX ( ∆UL1, ∆UL 2, ∆UL3)
EQUATION1621 V2 EN-US (Equation 82)
FaulType =
∑ ( ∆IL1, ∆IL2, ∆IL3)
MAX ( ∆IL1, ∆IL 2, ∆IL3)
EQUATION1622 V2 EN-US (Equation 83)
The output signal is 1 for single phase-to-earth fault, 2 for phase-to-phase fault and 3 for three-phase
fault. At this point the filter does not know if earth was involved or not.
Typically there are induced harmonics in the non-faulted lines that will affect the result. This method
allows for a significant tolerance in the evaluation of FaultType over its entire range.
When a single phase-to-earth fault has been detected, the logic determines the largest quantity, and
asserts that phase. If phase-to-phase fault is detected, the two largest phase quantities will be
detected and asserted as outputs.
The faults detected by the delta based phase selector are coordinated in a separate block. Different
phases of faults may be detected at slightly different times due to differences in the angles of
incidence of fault on the wave shape. Therefore the output is forced to wait a certain time by means
of a timer. If the timer expires, and a fault is detected in one phase only, the fault is deemed as
phase-to-earth. This way a premature single phase-to-earth fault detection is not released for a
phase-to-phase fault. If, however, earth current is detected before the timer expires, the phase-to-
earth fault is released sooner.
If another phase picks up during the time delay, the wait time is reduced by a certain amount. Each
detection of either phase-to-earth or additional phases further reduce the initial time delay and allow
the delta phase selector output to be faster. There is no time delay if all three phases are faulty.
The delta function is released if the input DELTAREL is activated at the same time as input
DELTABLK is not activated. Activating the DELTABLK input blocks the delta function. The release
signal has an internal pulse timer of 100 ms. When the DELTAREL signal has disappeared the delta
logic is reset. In order not to get too abrupt change, the reset is decayed in pre-defined steps.
The complementary based zero-sequence current function evaluates the presence of earth fault by
calculating the 3I0 and comparing the result with the setting parameter INRelPE. The output signal is
used to release the earth-fault loop. It is a complement to the earth-fault signal built-in in the
sequence based phase selector. The condition for releasing the phase-to-earth loop is as follows:
The output from this detection is used to release the earth-fault loop.
|3I0|>maxIph × INRelPE
where:
|3I0| is the magnitude of the zero sequence current 3I0
The earth-fault loop is also released if the evaluation of the zero sequence current by the main
sequence function meets the following conditions:
|3I0|>IBase × 0.5
|3I0|>maxIph ×INRelPE
where:
maxIph is the maximal current magnitude found in any of the three phases
INRelPE is the setting of 3I0 limit for release of phase-to-earth measuring loop in % of IBase
IBase is the global setting of the base current (A)
In systems where the source impedance for zero sequence is high the change of zero sequence
current may not be significant and the above detection may fail. In those cases the detection enters
the second level, with evaluation of zero and negative sequence voltage. The release of the earth-
fault loops can then be achieved if all of the following conditions are fulfilled:
|3U0|>|U2| × 0.5
|3U0|>|U1| × 0.2
and
3I0<0.1 × IBase
or
3I0<maxIph × INRelPE
where:
3U0 is the magnitude of the zero sequence voltage
U2 is the magnitude of the negative sequence voltage at the relay measuring point
k5 is design parameter
ILmax is the maximal phase current
IMinOp is the setting of minimum operate phase current in % of IBase
IEC06000383-2-en.vsd
IEC06000383 V2 EN-US
|U1|>U1MinOP
|U2|>U2MinOp
where:
U1MinOP and U2MinOp are the setting parameters for positive sequence and negative sequence
minimum operate voltages
If there is a three-phase fault, there will not be any release of the individual phase signals, even if the
general conditions for U2 and U1 are fulfilled.
The condition 1 determines faulty phase at single phase-to-earth fault by evaluating the argument
between U2 and I0.
80°
200°
L1-E sector
320°
IEC06000384_2_en.vsd
IEC06000384 V3 EN-US
Figure 161: Condition 1: Definition of faulty phase sector as angle between U2 and I0
The angle is calculated in a directional function block and gives the angle in radians as input to the
U2 and I0 function block. The input angle is released only if the fault is in forward direction. This is
done by the directional element. The fault is classified as forward direction if the angle between U0
and I0 lies between 20 to 200 degrees, see figure 162.
Forward 20°
200° Reverse
en06000385.vsd
IEC06000385 V1 EN-US
Figure 162: Directional element used to release the measured angle between Uo and I0
The input radians are summarized with an offset angle and the result evaluated. If the angle is within
the boundaries for a specific sector, the phase indication for that sector will be active see figure 161.
Only one sector signal is allowed to be activated at the same time.
The sector function for condition 1 has an internal release signal which is active if the main sequence
function has classified the angle between U0 and I0 as valid. The following conditions must be fulfilled
for activating the release signals:
|U2|>U2MinOp
|3I0|>maxIph · INRelPE
where:
U2 and IN are the magnitude of the negative sequence voltage and zero-
sequence current (3I0)
The angle difference is phase shifted by 180 degrees if the fault is in reverse direction.
The condition 2 looks at the angle relationship between the negative sequence voltage U2 and the
positive sequence voltage U1. Since this is a phase-to-phase voltage relationship, there is no need
for shifting phases if the fault is in reverse direction. A phase shift is introduced so that the fault
sectors will have the same angle boarders as for condition 1. If the calculated angle between U2 and
U1 lies within one sector, the corresponding phase for that sector will be activated. The condition 2 is
released if both the following conditions are fulfilled:
|U2|>U2MinOp
|U1|>U1MinOP
where:
|U1| and |U2| are the magnitude of the positive and negative sequence voltages.
U1MinOP and U2MinOp are the setting parameters for positive sequence and negative sequence
minimum operating voltages.
140°
L3-E sector
20°
U1L1
(Ref)
L1-E sector
L2-E sector
260° IEC06000413_2_en.vsd
IEC06000413 V2 EN-US
The sequence phase selector is blocked when earth is not involved or if a three-phase fault is
detected.
|U1|<U1Level
and
|I1|>I1LowLevel
or
|I1|>IMaxLoad
where:
|U1| and |I1| are the positive sequence voltage and current magnitude
U1Level , are the setting of limits for positive sequence voltage and current
I1LowLevel
IMaxLoad is the setting of the maximum load current
The output signal for detection of three-phase fault is only released if not earth fault and phase-to-
phase fault in the main sequence function is detected.
The conditions for not detecting earth fault are the inverse of equation 5 to 10.
The condition for not detecting phase-to-phase faults is determined by three conditions. Each of them
gives condition for not detecting phase-to-phase fault. Those are:
1:
earth fault is detected
or
|3I0|> 0.05 · IBase
and
|3I0|>maxIph ·INRelPE
2:
phase-to-earth and phase-to-phase faults are not fulfilled
and
maxIph<0.1 · IBase
and
|I2|<0.1 · maxIph
3:
|3I0|>maxIph · INBlockPP
or
|I2|<maxIph · I2ILmax
where:
maxIph is the maximum of the phase currents IL1, IL2 and IL3
INRelPE is the setting parameter for 3I0 limit for release of phase-to-earth fault loops
|I2| is the magnitude of the negative sequence current
I2ILmax is the setting parameter for the relation between negative sequence current
to the maximum phase current in percent of IBase
INBlockPP is the setting parameter for 3I0 limit for blocking phase to phase measuring
loops
a a>b FaultPriority
DeltaIL1 then c=a c Adaptive release
b else c=b dependent on result
from Delta logic
DeltaUL1
Sequence based
function a<b
a
L1L2 fault
then c=b c
OR b else c=a OR
L1N fault
3 Phase fault
STL1
IL1Valid &
BLOCK
IEC06000386-2-en.vsd
IEC06000386 V2 EN-US
The outline of the characteristic is presented in figure 165. As illustrated, the resistive reach in
forward and reverse direction and the angle of the sector is the same in all four quadrants. The reach
for the phase selector will be reduced by the load encroachment function, as shown in figure 165.
Blinder
Blinder provides a mean to discriminate high load from a fault. The operating characteristic is
illustrated in figure 165. There are six individual measuring loops with the blinder functionality. Three
phase-to-earth loops which estimate the impedance according to
Zn = Uph / Iph
The start operations from respective loop are binary coded into one word and provides an output
signal STCNDPLE.
X jX
RLd
ArgLd ArgLd
R
ArgLd R
ArgLd
RLd
Operation area
en06000414.vsd
IEC06000414 V1 EN-US
Outputs SEMOD153832-327 v7
The output of the sequence components based phase selector and the delta logic phase selector
activates the output signals STL1, STL2 and STL3. If an earth fault is detected the signal STPE gets
activated.
The phase selector also gives binary coded signals that are connected to the zone measuring
element for opening the correct measuring loop(s). This is done by the signal STCNDPHS. If only
one phase is started (L1, L2 or L3), the corresponding phase-to-earth element is enabled. STPE is
expected to be made available for two-phase and three-phase faults for the correct output to be
selected. The fault loop is indicated by one of the decimal numbers below.
The output STCNDPHS provides release information from the phase selection part only. STCNDLE
provides release information from the load encroachment part only. STCNDPLE provides release
information from the phase selection part and the load encroachment part combined, that is, both
parts have to issue a release at the same time (this signal is normally not used in the zone
measuring element). In these signals, each fault type has an associated value, which represents the
corresponding zone measuring loop to be released. The values are presented in table 191.
0= no faulted phases
1= L1E
2= L2E
3= L3E
4= -L1L2E
5= -L2L3E
6= -L3L1E
7= -L1L2L3E
8= -L1L2
Table continues on next page
9= -L2L3
10= -L3L1
11= L1L2L3
An additional logic is applied to handle the cases when phase-to-earth outputs are to be asserted
when the earth input G is not asserted.
The output signal STCNDPLE is activated when the load encroachment is operating.
STCNDPLE is connected to the input STCND for selected quadrilateral impedance measuring zones
to be blocked. The signal must be connected to the input LDCND for selected mho impedance
measuring zones .
The load encroachment at the measuring zone must be activated to release the
blocking from the load encroachment function.
8.9.1 Identification
GUID-420DD49A-C65B-4F04-B317-9558DCCE7A52 v1
GUID-119120A5-8600-44C6-9C85-81136DBBE280 v1
The line distance protection is up to five zone full scheme protection with three fault loops for phase-
to-phase faults and three fault loops for phase-to-earth fault for each of the independent zones.
Individual settings for each zone in resistive and reactive reach gives flexibility for use as back-up
protection for transformer connected to overhead lines and cables of different types and lengths.
Distance protection zone, quadrilateral characteristic (ZMRPDIS) together with Phase selection,
quadrilateral characteristic with settable angle (FRPSPDIS) has functionality for load encroachment,
which increases the possibility to detect high resistive faults on heavily loaded lines.
The distance protection zones can operate, independent of each other, in directional (forward or
reverse) or non-directional mode.
ZMRPDIS
I3P* TRIP
U3P* TRL1
BLOCK TRL2
BLKZ TRL3
BLKTR START
STCND STL1
DIRCND STL2
STL3
STND
IEC08000248-1-en.vsd
IEC08000248 V1 EN-US
ZMRAPDIS
I3P* TRIP
U3P* TRL1
BLOCK TRL2
BLKZ TRL3
BLKTR START
STCND STL1
DIRCND STL2
STL3
STND
IEC08000290_1_en.vsd
IEC08000290 V1 EN-US
ZDRDIR
I3P* STDIRCND
U3P*
IEC10000007-2-en.vsd
IEC10000007 V2 EN-US
8.9.4 Signals
PID-3649-INPUTSIGNALS v6
PID-3649-OUTPUTSIGNALS v6
PID-3648-INPUTSIGNALS v6
PID-3648-OUTPUTSIGNALS v6
PID-726-INPUTSIGNALS v3
PID-726-OUTPUTSIGNALS v3
8.9.5 Settings
PID-3649-SETTINGS v6
PID-3648-SETTINGS v6
PID-3545-SETTINGS v6
The execution of the different fault loops within the IED are of full scheme type, which means that
each fault loop for phase-to-earth faults and phase-to-phase faults for forward and reverse faults are
executed in parallel.
Figure 168 presents an outline of the different measuring loops for up to five, impedance-measuring
zones. There are 3 to 5 zones depending on product type and variant.
IEC05000458‐3‐en.vsdx
IEC05000458 V3 EN-US
Figure 168: The different measuring loops at phase-to-earth fault and phase-to-phase fault.
The use of full scheme technique gives faster operation time compared to switched schemes which
mostly uses a start element to select correct voltages and current depending on fault type. Each
distance protection zone performs like one independent distance protection IED with six measuring
elements.
The distance measuring zone includes six impedance measuring loops; three intended for phase-to-
earth faults, and three intended for phase-to-phase as well as, three-phase faults.
The distance measuring zone will essentially operate according to the non-directional impedance
characteristics presented in figure 169 and figure 170. The phase-to-earth characteristic is illustrated
with the full loop reach while the phase-to-phase characteristic presents the per phase reach.
X (Ohm/loop)
R1PE+Rn
RFPE RFPE
X0PE-X1PE
Xn =
3
X1PE+Xn R0PE-R1PE
Rn =
3
jN jN
R (Ohm/loop)
RFPE RFPE
X1PE+Xn
RFPE RFPE
en08000280-2-en.vsd
R1PE+Rn
IEC08000280 V1 EN-US
X (Ohm/phase)
j j
R (Ohm/phase)
RFPP RFPP
2 2
X1PP
IL1 R1 + j X1
Phase-to-earth
UL1
element
Phase-to-earth
fault in phase L1 RFPE
(Arc + tower
resistance)
0
IN (R0-R1)/3 +
j (X0-X1)/3 )
IL1 R1 + j X1 Phase-to-phase
UL1 element L1-L2
Phase-to-phase
fault in phase RFPP
L1-L2 IL2
UL2 (Arc resistance)
R1 + j X1
Regarding the illustration of three-phase fault in figure 171, there is of course fault current flowing
also in the third phase during a three-phase fault. The illustration merely reflects the loop
measurement, which is made phase-to-phase.
The zone can be set to operate in Non-directional, Forward or Reverse direction through the setting
OperationDir . The result from respective set value is illustrated in figure 172. The impedance reach
is symmetric, in the sense that it conforms for forward and reverse direction. Therefore, all reach
settings apply to both directions.
X X X
R R R
IEC05000182-2-en.vsdx
IEC05000182 V2 EN-US
The operation of Distance measuring zones, quadrilateral characteristic (ZMRPDIS) is blocked if the
magnitude of input currents fall below certain threshold values.
For zone 1 with load compensation feature the additional criterion applies, that all phase-to-earth
loops can be blocked when IN < IMinOpIN, regardless of the phase currents.
ILn is the RMS value of the current in phase Ln. IN is the RMS value of the vector sum of the three-
phase currents, that is residual current 3I0.
ILmLn is the RMS value of the vector difference between phase currents Lm and Ln.
All three current limits IMinOpPE, IMinOpIN and IMinOpPP are automatically
reduced to 75% of regular set values if the zone is set to operate in reverse
direction, that is OperationDir=Reverse
Fault loop equations use the complex values of voltage, current, and changes in the current.
Apparent impedances are calculated and compared with the set limits. The apparent impedances at
phase-to-phase faults follow equation 84 (example for a phase L1 to phase L2 fault).
UL1 – UL2
Zapp = -------------------------
I L1 – IL2
EQUATION1222 V1 EN-US (Equation 84)
Here U and I represent the corresponding voltage and current phasors in the respective phase Ln (n
= 1, 2, 3)
The earth return compensation applies in a conventional manner to phase-to-earth faults (example
for a phase L1 to earth fault) according to equation 85.
U L1
Z app =
I L1 + I N × KN
EQUATION1223 V2 EN-US (Equation 85)
Where:
are the phase voltage, phase current and residual current present to the IED
U L1
I L1
IN
KN
is defined as:
Z 0 - Z1
KN =
3 × Z1
EQUATION-2105 V2 EN-US
Z 0 = R 0 + jX 0
EQUATION2106 V2 EN-US
Z 1 = R1 + jX 1
EQUATION2107 V2 EN-US
Where
R0 is setting of the resistive zero sequence reach
X0 is setting of the reactive zero sequence reach
R1 is setting of the resistive positive sequence reach
X1 is setting of the reactive positive sequence reach
Here IN is a phasor of the residual current in IED point. This results in the same reach along the line
for all types of faults.
The apparent impedance is considered as an impedance loop with resistance R and reactance X.
The formula given in equation 85 is only valid for radial feeder application without load. When load is
considered in the case of single phase-to-earth fault, conventional distance protection might
overreach at exporting end and underreach at importing end. The IED has an adaptive load
compensation which increases the security in such applications.
Measuring elements receive current and voltage information from the A/D converter. The check sums
are calculated and compared, and the information is distributed into memory locations. For each of
the six supervised fault loops, sampled values of voltage (U), current (I), and changes in current
between samples (DI) are brought from the input memory and fed to a recursive Fourier filter.
The filter provides two orthogonal values for each input. These values are related to the loop
impedance according to equation 86,
X Di
U = R × i + ------ × -----
w 0 Dt
EQUATION1224 V1 EN-US (Equation 86)
X D Re ( I )
Re ( U ) = R × Re ( I ) + ------ × ------------------
w0 Dt
X DIm ( I )
Im ( U ) = R × Im ( I ) + ------ × -----------------
w0 Dt
with
w0 = 2 × p × f 0
EQUATION356 V1 EN-US (Equation 89)
where:
Re designates the real component of current and voltage,
Im designates the imaginary component of current and voltage and
f0 designates the rated system frequency
The algorithm calculates Rm measured resistance from the equation for the real value of the voltage
and substitutes it in the equation for the imaginary part. The equation for the Xm measured reactance
can then be solved. The final result is equal to:
Im ( U ) × DRe ( I ) – Re ( U ) × D Im ( I )
R m = ------------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – D Im ( I ) × Re ( I )
EQUATION357 V1 EN-US (Equation 90)
Re ( U ) × Im ( I ) – Im ( U ) × Re ( I )
Xm = w 0 × Dt × -------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – DIm ( I ) × Re ( I )
EQUATION358 V1 EN-US (Equation 91)
The calculated Rm and Xm values are updated each sample and compared with the set zone reach.
The adaptive tripping counter counts the number of permissive tripping results. This effectively
removes any influence of errors introduced by the capacitive voltage transformers or by other factors.
The directional evaluations are performed simultaneously in both forward and reverse directions, and
in all six fault loops. Positive sequence voltage and a phase locked positive sequence memory
voltage are used as a reference. This ensures unlimited directional sensitivity for faults close to the
IED point.
The evaluation of the directionality takes place in Directional impedance quadrilateral function
ZDRDIR. Equation 92 and equation 93 are used to classify that the fault is in forward direction for
phase-to-earth fault and phase-to-phase fault.
For the L1-L2 element, the equation in forward direction is according to.
where:
ArgDir is the setting for the lower boundary of the forward directional characteristic, by default set to 15 (= -15
degrees) and
ArgNegRes is the setting for the upper boundary of the forward directional characteristic, by default set to 115
degrees, see figure 173.
is positive sequence phase voltage in phase L1
U 1L1
is positive sequence memorized phase voltage in phase L1
U 1L1M
is phase current in phase L1
I L1
is voltage difference between phase L1 and L2 (L2 lagging L1)
U 1L1L 2
is memorized voltage difference between phase L1 and L2 (L2 lagging L1)
U 1L1L 2 M
is current difference between phase L1 and L2 (L2 lagging L1)
I L1L 2
The setting of ArgDir and ArgNegRes is by default set to 15 (= -15) and 115 degrees respectively (as
shown in figure 173). It should not be changed unless system studies have shown the necessity.
ZDRDIR gives binary coded directional information per measuring loop on the output STDIRCND.
STDIR= STFWL1*1+STFWL2*2+STFWL3*4+STFWL1L2*8+
+STFWL2L3*16+STFWL3L1*32+STRVL1*64+STRVL2*128+
+STRVL3*256+STRVL1L2*512+STRVL2L3*1024+STRVL3L1*2048
ArgNegRes
ArgDir
R
en05000722.vsd
IEC05000722 V1 EN-US
Figure 173: Setting angles for discrimination of forward and reverse fault in Directional
impedance quadrilateral function ZDRDIR
The reverse directional characteristic is equal to the forward characteristic rotated by 180 degrees.
The polarizing voltage is available as long as the positive sequence voltage exceeds 5% of the set
base voltage UBase. So the directional element can use it for all unsymmetrical faults including
close-in faults.
For close-in three-phase faults, the U1L1M memory voltage, based on the same positive sequence
voltage, ensures correct directional discrimination.
The memory voltage is used for 100 ms or until the positive sequence voltage is restored.
• If the current is still above the set value of the minimum operating current (between 10 and 30%
of the set IED rated current IBase), the condition seals in.
• If the fault has caused tripping, the trip endures.
• If the fault was detected in the reverse direction, the measuring element in the reverse
direction remains in operation.
• If the current decreases below the minimum operating value, the memory resets until the
positive sequence voltage exceeds 10% of its rated value.
Phase-to-earth related signals are designated by L1N, L2N and L3N.. The phase-to-phase signals
are designated by L1L2, L2L3, and L3L1.
Fulfillment of two different measuring conditions is necessary to obtain the one logical signal for each
separate measuring loop:
• Zone measuring condition, which follows the operating equations described above.
• Group functional input signal (STCND), as presented in figure 92.
The STCND input signal represents a connection of six different integer values from Phase selection
with load encroachment, quadrilateral characteristic function FRPSPDIS within the IED, which are
converted within the zone measuring function into corresponding boolean expressions for each
condition separately. Input signal STCND is connected to FRPSPDISfunction output STCNDZ.
The input signal DIRCND is used to give condition for directionality for the distance measuring zones.
The signal contains binary coded information for both forward and reverse direction. The zone
measurement function filter out the relevant signals depending on the setting of the parameter
OperationDir. It must be configured to the STDIRCND output on directional function ZDRDIR
function.
STZMPP
OR
STCND
AND STNDL1L2
L1L2
STNDL2L3
L2L3 AND
AND STNDL1N
L1N
AND STNDL2N
L2N
STNDL3N
L3N AND
OR STPE
OR
VTSZ STND
OR AND
BLOCK
BLOCFUNC BLK
99000557-2.vsd
IEC99000557-TIFF V3 EN-US
Figure 174: Conditioning by a group functional input signal STCND, external start condition
Composition of the phase start signals for a case, when the zone operates in a non-directional mode,
is presented in figure 93.
STNDL1N
OR
STNDL2N 15 ms
AND t STL1
STNDL3N
STNDL1L2 OR 15 ms
AND t STL2
STNDL2L3
15 ms
STNDL3L1 AND t STL3
OR
15 ms
AND t START
OR
BLK
IEC09000889-1-en.vsd
IEC09000889 V1 EN-US
STNDL1N
AND
DIRL1N
STZMPE.
OR
STNDL2N
DIRL2N AND
STNDL3N 15 ms
OR STL1
AND AND t
DIRL3N
STNDL1L2
DIRL1L2 AND 15 ms
OR STL2
AND t
STNDL2L3
DIRL2L3 AND
15 ms
OR STL3
STNDL3L1 AND t
DIRL3L1 AND
STZMPP
OR
BLK
15 ms
OR START
AND t
IEC09000888-2-en.vsd
IEC09000888 V2 EN-US
Timer tPP=On
STZMPP AND tPP
AND
t
BLOCFUNC
OR OR
tPE
t
AND
Timer tPE=On AND
STZMPE 15ms
BLKTR AND t
TRIP
BLK OR
IEC09000887-3-en.vsdx
IEC09000887 V3 EN-US
8.10.1 Identification
GUID-07DB9506-656C-4E5F-A043-3DAA624313C7 v2
SYMBOL-DD V1 EN-US
The ability to accurately and reliably classify the different types of fault, so that single pole tripping
and autoreclosing can be used plays an important role in today's power systems. Phase selection,
quadrilateral characteristic with settable angle FRPSPDIS is designed to accurately select the proper
fault loop in the distance function dependent on the fault type.
The heavy load transfer that is common in many transmission networks may make fault resistance
coverage difficult to achieve. Therefore, FRPSPDIS has a built-in algorithm for load encroachment,
which gives the possibility to enlarge the resistive setting of both the phase selection and the
measuring zones without interfering with the load.
The extensive output signals from the phase selection gives also important information about faulty
phase(s) which can be used for fault analysis.
A current-based phase selection is also included. The measuring elements continuously measure
three phase currents and the residual current and, compare them with the set values.
FRPSPDIS
I3P* TRIP
U3P* START
BLOCK STFWL1
DIRCND STFWL2
STFWL3
STFWPE
STRVL1
STRVL2
STRVL3
STRVPE
STNDL1
STNDL2
STNDL3
STNDPE
STFW1PH
STFW2PH
STFW3PH
STPE
STPP
STCNDZ
STCNDLE
IEC08000430-2-en.vsd
IEC08000430 V2 EN-US
8.10.4 Signals
PID-3643-INPUTSIGNALS v7
PID-3643-OUTPUTSIGNALS v7
8.10.5 Settings
PID-3643-SETTINGS v7
The basic impedance algorithm for the operation of the phase selection measuring elements is the
same as for the distance zone measuring function. Phase selection, quadrilateral characteristic with
settable angle (FRPSPDIS) includes six impedance measuring loops; three intended for phase-to-
earth faults, and three intended for phase-to-phase as well as for three-phase faults.
The difference, compared to the distance zone measuring function, is in the combination of the
measuring quantities (currents and voltages) for different types of faults.
The characteristic is basically non-directional, but FRPSPDIS uses information from the directional
function ZDRDIR to discriminate whether the fault is in forward or reverse direction.
• Residual current criteria, that is, separation of faults with and without earth connection
• Regular quadrilateral impedance characteristic
• Load encroachment characteristics is always active but can be switched off by selecting a high
setting.
The STCNDLE output is non-directional. The directionality is determined by the distance zones
directional function ZDRDIR.
There are output from FRPSPDIS that indicate whether a start is in forward or reverse direction or
non-directional, for example STFWL1, STRVL1 and STNDL1.
These directional indications are based on the sector boundaries of the directional function and the
impedance setting of FRPSPDIS function. Their operating characteristics are illustrated in figure 179.
X X X
R
R R
en08000286.vsd
IEC08000286 V1 EN-US
Figure 179: Characteristics for non-directional, forward and reverse operation of Phase
selection, quadrilateral characteristic with settable angle (FRPSPDIS)
The setting of the load encroachment function may influence the total operating characteristic, for
more information, refer to section "Load encroachment".
The input DIRCND contains binary coded information about the directional coming from the
directional function ZDRDIR. It shall be connected to the STDIR output on ZDRDIR. This information
is also transferred to the input DIRCND on the distance measuring zones, that is, the ZMRPDIS
block.
STDIR= STFWL1*1+STFWL2*2+STFWL3*4+STFWL1L2*8+
+STFWL2L3*16+STFWL3L1*32+STRVL1*64+STRVL2*128+
+STRVL3*256+STRVL1L2*512+STRVL2L3*1024+STRVL3L1*2048
If the binary information is 1 then it will be considered that we have start in forward direction in phase
L1. If the binary code is 3 then we have start in forward direction in phase L1 and L2 etc.
The STCNDZ or STCNDLE output contains, in a similar way as DIRCND, binary coded information,
in this case information about the condition for opening correct fault loop in the distance measuring
element. It shall be connected to the STCND input on the ZMRPDIS distance measuring zones
block.
The code built up for release of the measuring fault loops is as follows:
For a phase-to-earth fault, the measured impedance by FRPSPDIS is according to equation 94.
Index PHS in images and equations reference settings for Phase selection,
quadrilateral characteristic with settable angle (FRPSPDIS).
ULn
ZPHSn =
ILn
EQUATION1255 V1 EN-US (Equation 94)
where:
n corresponds to the particular phase (n=1, 2 or 3)
The characteristic for FRPSPDIS function at phase-to-earth fault is according to figure 180. The
characteristic has a settable angle for the resistive boundary in the first quadrant of 70°.
The resistance RN and reactance XN are the impedance in the earth-return path defined according
to equation 97 and equation 98.
R 0 PE - R1PE
RN =
3
EQUATION-2125 V1 EN-US (Equation 95)
R0 - R1
RN =
3
EQUATION1256 V1 EN-US (Equation 95)
X 0 - X1
XN =
3
EQUATION1257 V1 EN-US (Equation 96)
X (ohm/loop)
R1PE+RN
RFRvPE RFFwPE
X1+XN
RFFwPE
RFRvPE R (Ohm/loop)
X1+XN
RFRvPE RFFwPE
R1PE+RN
IEC09000633-1-en.vsd
IEC09000633 V1 EN-US
Figure 180: Characteristic of FRPSPDIS for phase to earth fault (directional lines are drawn as
"line-dot-dot-line")
Besides this, the 3I0 residual current must fulfil the conditions according to equation 97 and
equation 98.
3 × I0 ³ 0.5 × IMinOpPE
EQUATION2108 V1 EN-US (Equation 97)
3 × I0 ³ INReleasePE
------------------------------------ × Iphmax
100
EQUATION766 V1 EN-US (Equation 98)
where:
IMinOpPE is the minimum operation current for forward zones
INReleasePE is the setting for the minimum residual current needed to enable operation in the phase-to-earth fault
loops (in %).
Iphmax is the maximum phase current in any of three phases.
For a phase-to-phase fault, the measured impedance by FRPSPDIS is according to equation 99.
ULm - ULn
ZPHS =
-2 × ILn
EQUATION1258 V1 EN-US (Equation 99)
ULm is the leading phase voltage, ULn the lagging phase voltage and ILn the phase current in the
lagging phase n.
X (ohm/phase)
0.5·FRvPP
R1PP 0.5·RFFwPP
X1
0.5·RFFwPP
R (ohm/phase)
0.5·RFRvPP
X1
R1PP
0.5·RFRvPP 0.5·RFFwPP
IEC09000634-1-en.vsd
IEC09000634 V1 EN-US
Figure 181: The operation characteristic for FRPSPDIS at phase-to-phase fault (directional
lines are drawn as "line-dot-dot-line")
In the same way as the condition for phase-to-earth fault, there are current conditions that have to be
fulfilled in order to release the phase-to-phase loop. Those are according to equation 100 or
equation 101.
3I 0 < IMinOpPE
EQUATION2109 V1 EN-US (Equation 100)
INBlockPP
3I 0 < × Iph max
100
EQUATION2110 V1 EN-US (Equation 101)
where:
IMinOpPE is the minimum operation current for forward earth measuring loops,
INBlockPP is 3I0 limit for blocking phase-to-phase measuring loop and
The operation conditions for three-phase faults are the same as for phase-to-phase fault, that is
equation 99, equation 100 and equation 101 are used to release the operation of the function.
However, the reach is expanded by a factor 2/√3 (approximately 1.1547) in all directions. At the same
time the characteristic is rotated 30 degrees, counter-clockwise. The characteristic is shown in
figure 182.
X (ohm/phase)
4 × X1PP
3
0.5·RFFwPP·K3
X1·K3 30 deg 2
RFwPP ×
3
R (ohm/phase)
0.5·RFRvPP·K3
K3 = 2 / sqrt(3)
30 deg
IEC09000635-1-en.vsd
IEC09000635 V2 EN-US
Figure 182: The characteristic of FRPSPDIS for three-phase fault (set angle 70°)
Each of the six measuring loops has its own load encroachment characteristic based on the
corresponding loop impedance. The load encroachment functionality is always active, but can be
switched off by selecting a high setting.
The outline of the characteristic is presented in figure 184. As illustrated, the resistive blinders are set
individually in forward and reverse direction while the angle of the sector is the same in all four
quadrants.
RLdFw
ArgLd ArgLd
R
ArgLd ArgLd
RLdRv
IEC09000042-1-en.vsd
IEC09000042 V1 EN-US
When output signal STCNDI is selected, the operation characteristic will be as in figure 184. The
reach will in this case be limit by the minimum operation current and the distance measuring zones.
X X
R R
STCNDZ STCNDLE
IEC10000099-1-
en.vsd
IEC10000099 V1 EN-US
Figure 184: Difference in operating characteristic depending on operation mode when load
encroachment is activated
When FRPSPDIS is set to operate together with a distance measuring zone the resultant operate
characteristic could look like in figure 185. The figure shows a distance measuring zone operating in
forward direction. Thus, the operating area of the zone together with the load encroachment is
highlighted in black.
"Phase selection"
"quadrilateral" zone
Load encroachment
characteristic
Directional line
en05000673.vsd
IEC05000673 V1 EN-US
Figure 185: Operating characteristic in forward direction when load encroachment is activated
Figure 185 is valid for phase-to-earth. During a three-phase fault, or load, when the quadrilateral
phase-to-phase characteristic is subject to enlargement and rotation the operate area is transformed
according to figure 186. Notice in particular what happens with the resistive blinders of the "phase
selection" "quadrilateral" zone. Due to the 30-degree rotation, the angle of the blinder in quadrant
one is now 100 degrees instead of the original 70 degrees (if the angle setting is 70 degrees). The
blinder that is nominally located to quadrant four will at the same time tilt outwards and increase the
resistive reach around the R-axis. Consequently, it will be more or less necessary to use the load
encroachment characteristic in order to secure a margin to the load impedance.
X (W / phase)
Phase selection
”Quadrilateral” zone
R (W / phase)
IEC09000049-1-en.vsd
IEC09000049 V1 EN-US
Figure 186: Operating characteristic for FRPSPDIS in forward direction for three-phase fault,
ohm/phase domain
The result from rotation of the load characteristic at a fault between two phases is presented in fig
187. Since the load characteristic is based on the same measurement as the quadrilateral
characteristic, it will rotate with the quadrilateral characteristic clockwise by 30 degrees when subject
to a pure phase-to-phase fault. At the same time the characteristic will "shrink" by 2/√3, from the full
RLdFw and RLdRv reach, which is valid at load or three-phase fault.
IEC08000437.vsd
IEC08000437 V1 EN-US
Figure 187: Rotation of load characteristic for a fault between two phases
There is a gain in selectivity by using the same measurement as for the quadrilateral characteristic
since not all phase-to-phase loops will be fully affected by a fault between two phases. It should also
provide better fault resistive coverage in quadrant one. The relative loss of fault resistive coverage in
quadrant four should not be a problem even for applications on series compensated lines.
The operation of Phase selection, quadrilateral characteristic with settable angle (FRPSPDIS) is
blocked if the magnitude of input currents falls below certain threshold values.
The phase-to-earth loop Ln is blocked if ILn<IMinOpPE, where ILn is the RMS value of the current in
phase Ln.
Figure 188 presents schematically the creation of the phase-to-phase and phase-to-earth operating
conditions. Consider only the corresponding part of measuring and logic circuits, when only a phase-
to-earth or phase-to-phase measurement is available within the IED.
OperationZ<
AND
LDEblock
& 15 ms
AND t STPE
INReleasePE
3I 0 Iphmax
100 STCNDLE
Bool to AND
BLOCK integer
15 ms
3I 0 IMinOpPE 10 ms 20 ms & t STPP
OR AND t t
IRELPP
INBlockPP
3I 0 Iphmax
100
IEC09000149-3-en.vsd
IEC09000149 V3 EN-US
Figure 188: Phase-to-phase and phase-to-earth operating conditions (residual current criteria)
A special attention is paid to correct phase selection at evolving faults. A STCNDLE output signal is
created as a combination of the load encroachment characteristic and current criteria, refer to
figure 188. This signal can be configured to STCND functional input signals of the distance protection
zone and this way influence the operation of the phase-to-phase and phase-to-earth zone measuring
elements and their phase related starting and tripping signals.
Figure 189 presents schematically the composition of non-directional phase selective signals
STNDLn. Internal signals ZMLnN and ZMLmLn (m and n change between one and three according
to the phase number) represent the fulfilled operating criteria for each separate loop measuring
element, that is within the characteristic.
INDL1N
INDL2N
INDL3N
15 ms
STNDPE
IRELPE OR t
LDEblockL1N
IL1 AND 15 ms
OR STNDL1
ZML1N OR t
LDEblockL2N
IL2 AND
OR
ZML2N 15 ms
LDEblockL3N STNDL2
OR t
IL3 AND
OR
ZML3N
LDEblockL1L2 15 ms
STNDL3
IL1 & IL2 AND OR t
OR
ZML1L2
LDEblockL2L3
IL2 & IL3 AND INDL1L2
OR
ZML2L3 INDL2L3
LDEblockL3L1
IL3 & IL1 AND
OR INDL3L1
ZML3L1
IRELPP 15 ms
STNDPP
OR t
IEC00000545-4-en.vsd
IEC00000545-TIFF V4 EN-US
Composition of the directional (forward and reverse) phase selective signals is presented
schematically in figure 190 and figure 191. The directional criteria appears as a condition for the
correct phase selection in order to secure a high phase selectivity for simultaneous and evolving
faults on lines within the complex network configurations. Internal signals DFWLn and DFWLnLm
present the corresponding directional signals for measuring loops with phases Ln and Lm.
Designation FW (figure 191) represents the forward direction as well as the designation RV
(figure 190) represents the reverse direction. All directional signals are derived within the
corresponding digital signal processor.
Figure 190 presents additionally a composition of a STCNDZ output signal, which is created on the
basis of impedance measuring conditions. This signal can be configured to STCND functional input
signals of the distance protection zone and this way influence the operation of the phase-to-phase
and phase-to-earth zone measuring elements and their phase related starting and tripping signals.
INDL1N
AND
DRVL1N
INDL1L2 15 ms STRVL1
AND OR t
DRVL1L2
INDL3L1
AND
DRVL3L1 15 ms
STRVPE
INDL2N OR t
AND
DRVL2N
INDL1L2 15 ms
STRVL2
AND OR t
INDL2L3 INDL1N
AND INDL2N
DRVL2L3
INDL3N Bool to STCNDZ
INDL3N INDL1L2 integer
AND INDL2L3
DRVL3N INDL3L1
INDL2L3 15 ms
STRVL3
AND OR t
INDL3L1
15 ms
AND STRVPP
OR t
IEC00000546_2_en.vsd
IEC00000546-TIFF V2 EN-US
AND
INDL1N
AND 15 ms 15 ms
DFWL1N STFW1PH
AND OR t t
INDL1L2
15 ms STFWL1
AND OR t
DFWL1L2
INDL3L1
AND
AND
DFWL3L1 15 ms
STFWPE
INDL2N OR t
AND
DFWL2N
AND 15 ms
INDL1L2 STFWL2
t
AND OR
15 ms 15 ms
INDL2L3 STFW2PH
AND OR t t
AND
DFWL2L3
INDL3N
AND AND
DFWL3N 15 ms
STFWL3
t
INDL2L3
AND OR
15 ms
INDL3L1 STFW3PH
AND t
AND
15 ms
STFWPP
OR t
IEC05000201_2_en.vsd
IEC05000201 V2 EN-US
TimerPP=Off
tPP
AND AND
t
TRIP
OR OR
tPE
TimerPE=Off
t
AND AND
STNDPP
STFWPP OR
STRVPP
START
OR
STNDPE
STFWPE OR
STRVPE
IEC08000441_2_en.vsd
IEC08000441-1 V2 EN-US
Z
S00346 V2 EN-US
The High speed distance protection (ZMFPDIS) is providing sub-cycle, down towards half-cycle,
operate time for basic faults within 60% of the line length and up to around SIR 5.
The ZMFPDIS function is a seven zone full scheme protection with three fault loops for phase-to-
phase faults and three fault loops for phase-to-earth faults for each of the independent zones, which
makes the function suitable for applications with single-phase autoreclosing.
In each measurement zone, ZMFPDIS function is designed with the flexibility to operate in either
quadrilateral or mho characteristic mode for separate phase-to-earth or phase-to-phase loops.
A built-in adaptive load compensation algorithm prevents overreaching of the distance zones in the
load exporting end during phase-to-earth faults on heavily loaded power lines. It also reduces
underreach in the importing end.
The ZMFPDIS function block itself incorporates a phase-selection element and a directional element,
contrary to previous designs in the 600-series, where these elements were represented with
separate function-blocks.
The operation of the phase-selection element is primarily based on current change criteria (i.e. delta
quantities), with significantly increased dependability. There is also a phase selection criterion
operating in parallel which bases its operation only on voltage and current phasors.
The directional element utilizes a set of well-established quantities to provide fast and correct
directional decision during various power system operating conditions, including close-in three-phase
faults, simultaneous faults and faults with only zero-sequence in-feed.
The ZMFPDIS function is also equipped with the parallel line mutual coupling compensation feature
based on the parallel line residual current.
ZMFPDIS
I3P* TRIP
U3P* TRZ1
BLOCK TRL1Z1
VTSZ TRL2Z1
BLKZ1 TRL3Z1
BLKZ2 TRZ2
BLKZ3 TRL1Z2
BLKZ4 TRL2Z2
BLKZ5 TRL3Z2
BLKZRV TRZ3
BLKZBU TRZ4
BLKTRZ1 TRZ5
BLKTRZ2 TRZRV
BLKTRZ3 TRZBU
BLKTRZ4 START
BLKTRZ5 STZ1
BLKTRZRV STNDZ1
BLKTRZBU STZ2
EXTNST STL1Z2
ORCND STL2Z2
RELCNDZ1 STL3Z2
RELCNDZ2 STNDZ2
RELCNDZ3 STZ3
RELCNDZ4 STNDZ3
RELCNDZ5 STZ4
RELCNDZRV STNDZ4
RELCNDZBU STZ5
STNDZ5
STZRV
STL1ZRV
STL2ZRV
STL3ZRV
STNDZRV
STZBU
STNDZBU
STND
STNDL1
STNDL2
STNDL3
STNDPE
STFWL1
STFWL2
STFWL3
STFWPE
STRVL1
STRVL2
STRVL3
STRVPE
STFW1PH
STFW2PH
STFW3PH
STPE
STPP
IEC11000433-6-en.vsdx
IEC11000433 V5 EN-US
IEC11000433 V6 EN-US
8.11.5 Signals
PID-7600-INPUTSIGNALS v1
PID-7600-OUTPUTSIGNALS v1
8.11.6 Settings
PID-7600-SETTINGS v1
Settings, input and output names are sometimes mentioned in the following text
without its zone suffix (i.e. BLKZx instead of BLKZ3) when the description is equally
valid for all zones.
Practically all voltage, current and impedance quantities used within the ZMFPDIS function are
derived from fundamental frequency phasors filtered by a half cycle filter.
The phasor filter is frequency adaptive in the sense that its coefficients are changed based on the
estimated power system frequency.
A half cycle filter will not be able to reject both even and odd harmonics. So, while odd harmonics will
be completely attenuated, accuracy will be affected by even harmonics. Even harmonics will not
cause the distance zones to overreach however; instead there will be a slightly variable underreach,
on average in the same order as the magnitude ratio between the harmonic and fundamental
component.
The different fault loops within the IED are of full scheme type, which means that earth fault loop for
phase-to-earth faults and phase-to-phase faults for forward and reverse faults are executed in
parallel.
Figure 194 presents an outline of the different measuring loops for the seven distance zones.
IEC05000458‐3‐en.vsdx
IEC05000458 V3 EN-US
Figure 194: The different measuring loops at phase-to-earth fault and phase-to-phase fault
Each distance protection zone performs like one independent distance protection function with seven
measuring elements.
Transients from CVTs may have a significant impact on the transient overreach of a distance
protection. At the same time these transients can be very diverse in nature from one type to the
other; in fact, more diverse than can be distinguished by the algorithm itself in the course of a few
milliseconds. So, a setting (CVTtype) is introduced in order to inform the algorithm about the type of
CVT applied and thus providing the advantage of knowing how performance should be optimized,
even during the first turbulent milliseconds of the fault period.
There are two types of CVTs from the function point of view, the passive and the active type, which
refers to the type of ferro-resonance suppression device that is employed. The active type requires
more rigorous filtering which will have a negative impact on operate times. However, this will be
evident primarily at higher source impedance ratios (SIRs), SIR 5 and above, or close to the reach
limit.
The IEC 60044-5 transient classification is of little or no use in relation to this. It is not primarily the
damping of transients that is important; it is the frequency content of the transients that is decisive,
i.e. how difficult it is to filter out the specific frequency. So, even if two CVTs, one passive and the
other active type, comply with the same transient class, the active type requires more extensive
filtering in order to avoid transient overreach.
To avoid overreach and at the same time achieve fast operate times, a supplementary circular
characteristic is implemented. A circular characteristic exists for every measuring loop and
quadrilateral/mho characteristic. There are no specific reach settings for this circular zone. It uses the
normal quadrilateral/mho zone settings to determine a reach that will be appropriate. This implies
that the circular characteristic will always have somewhat shorter reach than the quadrilateral/mho
zone.
The operation of the phase-selection element is primarily based on current change criteria (i.e. delta
quantities) with significantly increased dependability. To handle this, there is also a phase selection
criterion operating in parallel which bases its operation only on voltage and current phasors.
This continuous criteria will, in the vast majority of cases, operate in parallel and carry on the fault
indication after the current change phase has ended. Only in some particularly difficult faults on
heavily loaded lines, the continuous criteria might not be sufficient, for example, when the estimated
fault impedance resides within the load area defined by the load encroachment characteristic. In this
case, the indication will be restricted to a pulse lasting for one or two power system cycles.
The phase-selection element can, owing to the current change criteria, distinguish faults with
minimum influence from load and fault impedance. In other words, it is not restricted by a load
encroachment characteristic during the current change phase. This significantly improves
performance for remote phase-to-earth faults on heavily loaded lines. One exception, however, are
three-phase faults to which the load encroachment characteristic always has to be applied in order to
distinguish fault from load.
Phase-to-phase-earth faults (also called double earth faults) will practically always activate phase-to-
phase zone measurements. Measurement in two phase-to-earth loops at the same time is
associated with so-called simultaneous faults: two earth faults at the same time, one each on the two
circuits of a double line, or when the zero sequence current is relatively high due to a source with low
Z0/Z1 ratio. In these situations zone measurement will be released both for the related phase-to-
earth loops and the phase-to-phase loop simultaneously. On the other hand, simultaneous faults
closer to the remote bus will gradually take on the properties of a phase-to-phase-earth fault and the
function will eventually use phase-to-phase zone measurements also here.
In cases where the fault current infeed is more or less completely of zero sequence nature (all phase
currents in phase), the measurement will be performed in the phase-to-earth loops only for a phase-
to-phase-earth fault.
AND
2-phase Fault
I3P detected by
Impedance/ current
2-phase fault
U3P based Phase PHSLy
AND
selection
PHSLxLy
AND
OR
a
b a>b
250%
OR
a
b a>b
50% AND OR
a
b a<b
INMag
IL1Mag IN / Imax
IL2Mag
MAX
IL3Mag a ForcePE
b a<b
INReleasePE
IEC17000230-2-en.vsdx
IEC17000230 V2 EN-US
Figure 195 explains the release of two-phase faults (including simultaneous faults as
well as cross-country faults for high impedance earthed networks. This is not valid
for single-phase faults.
However, should it be desirable to use phase-to-earth (and only phase-to-earth) zone measurement
for phase-to-phase-earth faults, there is a setting INReleasePE that can be lowered from its
excessive default value to the level above which phase-to-earth measurement should be activated.
Several criteria are employed when making the directional decision. The basis is provided by
comparing a positive sequence based polarizing voltage with phase currents. For extra security,
especially in making a very fast decision, this method is complemented with an equivalent
comparison where, instead of the phase current, the change in phase current is used. Moreover, a
basic negative sequence directional evaluation is taken into account as a reliable reference during
high load condition. Finally, a zero sequence directional evaluation is used whenever there is more or
less exclusive zero sequence in-feed.
The directional sectors that represent forward direction, one per measuring loop, are defined by the
following equations.
U PolL1
ArgDir arg ArgNegRes
I L1
U PolL1L 2
ArgDir arg ArgNegRes
I L1L 2
Where:
UPolL1L2 is the polarizing voltage difference between phase L1 and L2 (L2 lagging L1).
IL1L2 is the current difference between phase L1 and L2 (L2 lagging L1).
Since the polarizing voltage is also used for the Mho distance characteristics, the magnitude of the
voltage is just as interesting as the phase. If there are symmetrical conditions and the measured per
phase positive sequence voltage magnitude is above 75% of the base voltage before the fault, the
pre-fault magnitude will be memorized and used as long as there is a fault. The phase angle however
will only be memorized (locked) for 75 ms at a time, not to lose synchronism with the real system
voltage.
Should the positive sequence voltage drop below 2% of the base voltage, it will be considered
invalid. In this situation, directional signals and starts from Mho elements will be sealed-in and kept
static as long as there is a fault.
For ZMFCPDIS, when option SeriesComp is chosen for OperationSC, the voltages of faulty phases
will be discarded in order not to affect the polarizing voltage with voltage reversal.
The ZMFPDIS function has to be blocked by an additional function like the Fuse failure supervision
(FUFSPVC) or an equivalent external device. Typically, the binary input VTSZ is used for this
purpose.
A built-in supervision feature within high-speed distance protection itself, based on phase current
change, will ensure that the FUFSPVC blocking signal is received in time. Namely, an intentional
time delay will be introduced if no current magnitude change greater than 5% of IBase has been
detected for any of the three phase currents.
All ZMFPDIS zones operate according to the non-directional impedance characteristics presented in
figure 197 and figure 196. The phase-to-earth characteristic is given in ohms-per-loop domain while
the phase-to-phase characteristic is given in ohms-per-phase domain.
The voltage and current phasors after the half-cycle filter are used in fault loop equations.
For phase-to-phase faults (Figure 198, lower part), the calculated impedances from the relay to the
fault Z calc Rcalc j X calc follow Equation 104 (example is given for a phase L1 to phase L2 fault).
U L1 U L 2 I L1 I L 2 Z calc
IECEQUATION18003 V1 EN-US (Equation 104)
Where and represents the corresponding voltage and current phasors in the respective
phase Ln (n = 1, 2, 3).
The calculated Rcalc and Xcalc are compared with the non-directional phase-to-phase quadrilateral
characteristics. If is inside the non-directional phase-to-phase characteristic, the STNDZx output
is set to TRUE.
For phase-to-earth faults (Figure 198, upper part), the earth return compensation applies according
to Equation 105 (example for a phase L1 to earth fault).
U L1 I L1 K N 3I 0 p Z1 I F RF
IECEQUATION18007 V1 EN-US (Equation 105)
Where,
p is the fault location and RF is the calculated fault resistance. p and RF are unknown and needs to
be solved.
Z 0 Z1
KN
3 Z1
Z 0 R 0 Zx j X 0 Zx
Z1 R1Zx j X 1Zx
IECEQUATION18010 V1 EN-US
Where,
is the positive sequence reactance reach of the line in Ω/phase for phase-to-earth fault for zone
x (x = 1 to 5, BU or RV).
is the positive sequence resistive reach of the line in Ω/phase for phase-to-earth fault for zone x
(x = 1 to 5, BU or RV).
is the zero-sequence reactance reach of the line in Ω/phase for zone x (x = 1 to 5, BU or RV).
is the zero-sequence resistive reach of the line in Ω/phase for zone x (x = 1 to 5, BU or RV).
Table 218: Settings of positive and zero-sequence impedances for different zones
is the fault current. It is chosen among phase, zero or negative sequence currents automatically
by the built-in adaptive load compensation algorithm. If the system behind the relay cannot contribute
enough zero-sequence current, only phase or negative sequence current will be chosen.
The calculated impedances from the relay to the fault Z calc Rcalc j X calc can be represented as:
X calc p X 1Zx
IECEQUATION18017 V1 EN-US
Rcalc p R1Zx RF
IECEQUATION18018 V1 EN-US
When the two unknowns p and RF are solved from the equation 105 then the calculated Rcalc and
Xcalc values are compared with the non-directional phase-to-earth quadrilateral characteristics. If
is inside the non-directional phase-to-earth characteristic and the phase selection algorithm enables
this loop, the STNDZx output is set to TRUE.
The load compensation for zone 1 is achieved by estimating the impedance with three different
values of the IF current with:
• neutral current
• negative sequence current
• phase current.
Impedance estimation is based on the neutral current or negative sequence current essentially that
excludes the current component that causes the over-reach. The reactance values from all the
calculations shall effectively be within the zone reactive boundary in order to get the non-directional
start signal from the zone. This means that the under-reach, that is caused by the load import, is not
compensated.
For the other zones, it is enough in effect if the median value of the three is within the zone reach. If
the neutral current is not sufficient, then the negative sequence current based reactance will
represent the median value. If the negative sequence current is not sufficient, then the other
reactance has to be within the reach.
Zone 1 has individual positive sequence impedance settings for phase-to-phase and phase-to-earth
(X1PPZ1, R1PPZ1 and X1PEZ1, R1PEZ1). For the other zones, the positive sequence impedance
reach is common for phase-to-phase and phase-to-earth (X1Zx, R1Zx).
X (Ohm/phase)
X1Zx
R (Ohm/phase)
RFPPZx RFPPZx
2 2
X1Zx
X (Ohm/loop)
R1Zx+RNZx
RFPEZx RFPEZx
X0Zx-X1Zx
XNZx=
3
X1Zx+XNZx R0Zx-R1Zx
RNZx=
3
φN φN
R (Ohm/loop)
RFPEZx RFPEZx
X1Zx+XNZx
RFPEZx RFPEZx
R1Zx+RNZx IEC11000415-2-en.vsdx
IEC11000415 V2 EN-US
Phase-to-earth
RFPEZx
fault in phase L1
(Arc + tower
resistance)
0
IN (R0Zx-R1Zx)/3 +
j (X0Zx-X1Zx)/3 )
The estimated impedance needs to be inside both characteristics for the zone to start or trip. (The
non-directional start STNDZx is an exception however. It is only dependent on the quadrilateral
characteristic.)
In the following figure, it is shown how the X1PP setting can influence the shape of the quadrilateral
characteristic in the fourth quadrant for short line applications.
X (ohm)
X1PP’
X1PP
15° R (ohm)
RFPP/2
-X1PP
R· tan15°
-X1PP’
Line distance protection=IEC19000141=2=en-us=Original.vsdx
IEC19000141 V2 EN-US
Figure 199: Influence of X1PP setting on the quadrilateral shape in the fourth quadrant
The quadrilateral phase-to-earth element is added with the parallel line mutual coupling
compensation feature based on the parallel line residual current. The additional current signal must
be connected to the function through the INP group input. The parallel line residual current hardware
channel must be connected to the residual quantity input of the corresponding SMAI block. The
compensation feature can be switched On/Off with the EnPar setting.
When the parallel compensation is switched On (EnPar is On), the phase-to-earth loop Equation 105
is modified according to Equation 106 (example is given for phase L1 to earth fault).
U L1 ( I L1 K N 3I 0 K Nm 3I 0 p ) p Z1 I F RF
IECEQUATION20296 V1 EN-US (Equation 106)
Z0m
K Nm =
3 Z1
IECEQUATION20299 V1 EN-US
Z 0 m = R0MZx + j X 0MZx
IECEQUATION20300 V1 EN-US
Where,
Z 0m is the set complex zero-sequence mutual impedance between parallel lines in Ω/phase.
is the zero-sequence resistance between parallel lines in Ω/phase for the phase-to-earth
fault in zone direction for zone x (where x = 1 to 2).
is the zero-sequence reactance between parallel lines in Ω/phase for the phase-to-earth
fault in zone direction for zone x (where x = 1 to 2).
The compensation feature will only be active when the parallel line residual current is not significantly
higher than the protected line residual current. The deactivation limit of this parallel line
compensation feature is set with the INPRatio setting. Compensation is deactivated when:
3I0p
INPRatio
3I0
IECEQUATION20302 V1 EN-US
The mutual compensation is also deactivated when the protected line residual current is less than
50% of IMinOp according to the below relation:
3I 0 0.5 IMin0 p
IECEQUATION20303 V1 EN-US
Zones 2 to 5 and BU can be selected to be either forward or reverse with positive sequence
polarized mho characteristic; alternatively self polarized offset mho characteristics. The operating
characteristic is in accordance to figure 200 where zone 5 is selected offset mho.
X
ZBU X
Z4
Z3
ZS=0
Z2
Z1 R
Z5 R
ZS=Z1
ZRV
ZS=2Z1
IEC150000 56-2-en.vsdx
IEC15000056 V2 EN-US
Figure 200: Mho, offset mho characteristics and the source impedance influence on the mho
characteristic
The mho characteristic has a dynamic expansion due to the source impedance. Instead of crossing
the origin, as for the mho to the left of figure 200, which is only valid where the source impedance
(Zs) is zero, the crossing point is moved to the coordinates of the negative source impedance given
an expansion of the circle shown to the right of figure 200. Z1 denotes the complex positive
sequence impedance.
The magnitude of the polarizing voltage is determined completely by the positive sequence voltage
magnitude from before the fault. This will give a somewhat less dynamic expansion of the mho circle
during faults. However, if the source impedance is high, the dynamic expansion of the mho circle
might lower the security of the function too much with high loading and mild power swing conditions.
ZMFPDIS fixes zone 1 in Forward mode and zone RV in Reverse mode. Zone 2 to 5 and BU can be
set to Non-directional, Forward or Reverse by setting the parameter DirModeZx (where x = 2 to 5 or
BU depending on selected zone).
X X X
(a) Rset (b) (c) Rset
Xset Xset
R R R
Xset
(a)-(f)
Rset For phase-to-phase fault
Rset = R1Zx
Forward Reverse Non-directional Xset = X1Zx
R R R
IEC15000055 V4 EN-US
The ZMFPDIS function has only one set of reach setting so the reverse will be the same as for the
forward reach, meaning that the non-directional offset mho characteristic will always be centered
around the origin. In detail, for Zone 1, the resistive and reactance reaches for phase-to-earth fault
and phase-to-phase fault are set individually using the settings R1PPZ1, X1PPZ1, R1PEZ1,
X1PEZ1, X0Z1 and R0Z1. In Zone 2-5, BU and RV, the same zone reach settings are used for
phase-to-earth fault and phase-to-phase (R1Zx, X1Zx, X0Zx and R0Zx, x = 2 to 5, BU or RV).
(
β = arg U L1L 2 − I L1L 2 ⋅ Z 1set − arg U pol ) ( )
IECEQUATION15027 V1 EN-US (Equation 107)
where
is the positive sequence impedance setting for phase-to-phase fault in zone direction
Z 1set
For Zone 1,
where
R1PPZ1 is the positive sequence resistive reach for phase-to-phase fault for zone 1
X1PPZ1 is the positive sequence reactance reach for phase-to-phase fault for zone 1
where
R1Zx is the positive sequence resistive reach for zone x (x = 2-5, BU and RV)
X1Zx is the positive sequence reactance reach for zone x (x = 2-5, BU and RV)
is the polarizing voltage
Upol
IL1L2 jX
I L1L 2 Z1set
UcompUL1L2 IL1L2 Z1set
UL1L2
U pol
I L1L 2 R
IEC15000060-1-en.vsdx
IEC15000060 V1 EN-US
Figure 202: Simplified mho characteristic and vector diagram for phase L1-to-L2 fault
Offset Mho GUID-3E13E6D5-0832-4386-9677-9A40BFF42F8F v2
The characteristic for offset mho is a circle with origin as the center and magnitude of Z 1set as the
radius, where Z 1set is settable through the resistance and reactance settings.
The condition for operation at phase-to-phase fault is that the angle β between the two compensated
voltages is greater than or equal to 90° (figure 203). The angle will be 90° for fault location on the
boundary of the circle.
U
L1L 2 I L1L 2 Z 1set
arg
U L1L 2 I L1L 2 Z1set
IECEQUATION15008 V2 EN-US (Equation 110)
I L1L 2 jX
I L1L 2 Z1set
U L1L 2
I L1L 2 R
I L1L 2 Z1set
IEC15000058-2-en.vsdx
IEC15000058 V2 EN-US
Figure 203: Simplified offset mho characteristic and voltage vector for phase L1 to L2 fault
Operation occurs if 90°≤β≤270 °.
Compensation for earth return path for faults involving earth is done by setting the positive and zero
sequence impedance of the line. It is known that the earth compensation factor KN is,
Z 0set − Z 1set
KN =
3 ⋅ Z 1set
IECEQUATION15017 V1 EN-US
Z 0set = R 0Zx + j ⋅ X 0 Zx
IECEQUATION15018 V1 EN-US
For Zone 1,
Z 1set = R1PEZ 1 + j ⋅ X 1PEZ 1
IECEQUATION15019 V1 EN-US
where
is the complex zero sequence impedance of the line in Ω/phase
Z 0set
is the complex positive sequence impedance of the line in Ω/phase
Z 1set
R1PEZ1 is the positive sequence resistive reach of the line in Ω/phase for
phase-to-earth fault for zone 1
X1PEZ1 is the positive sequence reactance reach of the line in Ω/phase for
phase-to-earth fault for zone 1
R0Zx is the zero sequence resistive reach of the line in Ω/phase for zone
x (x=2 to 5, BU or RV)
X0Zx is the zero sequence reactance reach of the line in Ω/phase for
zone x (x=2 to 5, BU or RV)
For an earth fault in phase L1, the angle β between the compensation voltage and the polarizing
where
is the phase voltage in faulty phase L1
UL1
is the phase current in faulty phase L1
IL1
3I 0 is the zero-sequence current in faulty phase L1
IL1•jX
U L1
I L1 Z1set
U pol
IL1•R
IEC15000059-1-en.vsdx
IEC15000059 V1 EN-US
Figure 204: Simplified offset mho characteristic and vector diagram for phase L1-to-earth fault
Operation occurs if 90°≤β≤270°.
arg U L1 ( I L1 3I 0 K N ) Z1set arg U L1 ( I L1 3I 0 K N ) Z1set
IL1• jX
U comp1 U L1 ( I L1 3I 0 K N ) Z1set
( I L1 3I 0 K N ) Z1set
U L1
IL1• R
( I L1 3I 0 K N ) Z1set
IEC15000057-2-en.vsdx
IEC15000057 V2 EN-US
Figure 205: Simplified offset mho characteristic and voltage vector for phase L1-to-earth fault
Operation occurs if 90 °≤β≤270 °.
In some cases the measured load impedance might enter the set zone characteristic without any
fault on the protected line. This phenomenon is called load encroachment and it might occur when an
external fault is cleared and high emergency load is transferred onto the protected line. The effect of
load encroachment is illustrated on the left in figure 206. A load impedance within the characteristic
would cause an unwanted trip. The traditional way of avoiding this situation is to set the distance
zone resistive reach with a security margin to the minimum load impedance. The drawback with this
approach is that the sensitivity of the protection to detect resistive faults is reduced.
The IED has a built-in feature which shapes the under-impedance starting characteristic according to
the characteristic shown in figure 206. The load encroachment algorithm will increase the possibility
to detect high fault resistances, especially for phase-to-earth faults at the remote line end. For
example, for a given setting of the load angle ArgLd, the resistive blinder for the zone measurement
can be set according to figure 206 affording higher fault resistance coverage without risk for
unwanted operation due to load encroachment. Separate resistive blinder settings are available in
forward and reverse direction.
The use of the load encroachment feature is essential for long heavily loaded lines, where there
might be a conflict between the necessary emergency load transfer and necessary sensitivity of the
distance protection. The function can also preferably be used on heavy loaded, medium long lines.
For short lines, the major concern is to get sufficient fault resistance coverage. Load encroachment is
not a major problem.
The built-in phase selection is based on current change criteria and has no user defined settings.
However, a traditional under-impedance-based phase selector is always working in parallel with it.
This under-impedance-based criterion is defined by the two setting parameters XStart and RStart, as
shown in Figure 206. These two settings are common for both Ph-Ph and Ph-Gnd measurement
loops. In order to ensure proper operation of the distance zones the under-impedance based starting
element shall be set in such a way to always cover (i.e. be larger than) all used distance zones for
both Ph-Ph and Ph-Gnd loops. Consequently, the following settings are recommended:
Parameter XStart shall be set to a value which is at least 20% bigger than the value obtained by
formula (2*X1FwPEZx+X0FwPEZx)/3 applied for the longest reaching zone.
It is recommended that the RStart setting shall not exceed the load impedance, which is typically
defined as UBase/sqrt(3)/IBase in primary ohms. It is recommended to reduce the RStart set value to
maximum 80% of the above defined load impedance value. However, the RLdRvFactor and RLdFw
settings can be utilized to get an additional non-operation sector for emergency load, like for when a
parallel line is opened, as shown in Figure 206.
Distance Zones
RStart
XStart
RLdFw
ArgLd
RLdRvFactor
XStart
* RLdFw
100
RStart
IEC09000248-5-en-us.vsdx
IEC09000248 V5 EN-US
PHSL1, PHSL2,...PHSL3L1 are internal binary logical signals from the Phase-selection element.
They correspond directly to the six loops of the distance zones and determine which loops should be
released to operate.
[1] RLdRv=RLdRvFactor*RLdFw
The ORCND input enables the use of external elements to supplement the internal phase selection
in specialized applications, like unblocking of the distance protection during power swings. Like with
the other CND signals, each bit of its binary encoded integer number corresponds to one of the six
measuring loops to be enabled. See Figure 207.
PHSL1, PHSL2,… PHSL3L1
Phase selection Zone1
Internal
criteria bitwise
OR bitwise release
AND
Zone2
RELCNDZ1
bitwise release
RELCNDZ2 AND
RELCNDZ3
Zone3
IEC19000323-1-en-us.vsdx
IEC19000323 V1 EN-US
FWL1, FWL2,...FWL3L1 and RVL1, RVL2,...RVL3L1 are the internal binary signals from the
Directional element. An FW signal is activated if the criteria for a forward fault or load is fulfilled for its
particular loop. The equivalent applies to the reverse (RV) signals.
The internal input 'IN present' is activated if the residual current (3I0) exceeds 10% of the maximum
phase current magnitude and at the same time is above 5% of IBase. However, if current transformer
saturation is detected, this criterion is changed to residual voltage (3U0) exceeding 5% of UBase/
sqrt(3) instead.
DirModeZ3-5, BU
TRUE (1)
FW(Ln & LmLn) Forward
RV(Ln & LmLn) Reverse
IEC12000137-4-en.vsd
IEC12000137 V4 EN-US
ZML1Zx PEZx
OR
PHSL1
AND
DIRL1Zx AND
ZML2Zx
PHSL2
AND
DIRL2Zx AND
ZML3Zx L1Zx
OR
PHSL3
AND
DIRL3Zx AND
ZML1L2Zx L2Zx
PHSL1L2 OR
AND
DIRL1L2Zx AND
ZML2L3Zx
PHSL2L3 L3Zx
AND OR
DIRL2L3Zx AND
ZML3L1Zx
PHSL3L1
AND
DIRL3L1Zx AND
L1N
PPZx
L2N OR
L3N
RELCNDZx Integer L1L2
to Bool
L2L3
NDZx
L1L3 OR
IEC12000140-2-en.vsdx
IEC12000140 V2 EN-US
TimerModeZx =
Enable PhPh or
Ph-E PhPh
PPZx AND tPPZx
OR AND
AND t
PEZx
AND tPEZx OR
TimerModeZx = OR
AND t
Enable Ph-E or AND
Ph-E PhPh
VTSZ
BLKZx OR
OR
TimerLinksZx
ZoneLinkStart
LoopLink (tPP-tPE)
Phase Selection
LoopLink & ZoneLink
1st starting zone OR
No Links
LNKZx
FALSE (0) AND
OR
TimerLinksZx =
LoopLink & ZoneLink
EXTNST
IEC12000139-6-en.vsdx
IEC12000139 V6 EN-US
15 ms
TZx
t TRIPZx
AND
TRL1Zx
OR AND
BLOCK
VTSZ TRL2Zx
OR AND
BLKZx
TRL3Zx
AND
15 ms
L1Zx
t STL1Zx
AND
15 ms
L2Zx
t STL2Zx
AND
15 ms
t STL3Zx
AND
PPZx 15 ms
PEZx OR t STARTZx
AND
15 ms
NDZx
t STNDZx
AND
IEC12000138-2-en.vsd
IEC12000138 V2 EN-US
15 ms
OR t STPE
AND
15 ms
OR t
AND
15 ms
OR t STNDL2
PHSL1L2 AND
15 ms
OR t STNDL3
AND
15 ms
OR t STPP
AND
BLOCK STARTND
OR
VTSZ OR
STPHS
STNDPE
AND
IEC12000133-3-en.vsdx
IEC12000133 V3 EN-US
PHSL1
FWL1 AND
15 ms
FWL2 AND OR t
AND
FWL3 AND 15 ms
PHSL1L2 OR t STFWL2
AND
FWL1L2 AND
PHSL2L3 15 ms
FWL2L3 AND OR t STFWL3
AND
FWL3L1 AND
OR
STFWPE
IN present AND
STFW1PH
=1
BLOCK
VTSZ OR
STFW2PH
=2
STFW3PH
=3
IEC12000134-2-en.vsd
IEC12000134 V2 EN-US
PHSL1
RVL1 AND
15 ms
RVL2 AND OR t
AND
RVL3 AND 15 ms
PHSL1L2 OR t STRVL2
AND
RVL1L2 AND
PHSL2L3 15 ms
RVL2L3 AND OR t STRVL3
AND
RVL3L1 AND
OR
STRVPE
IN present AND
BLOCK
VTSZ OR
IEC12000141-2-en.vsdx
IEC12000141 V2 EN-US
8.11.8.9 Measurement
Measurement supervision SEMOD54417-130 v4
The protection, control, and monitoring IEDs have functionality to measure and further process
information for currents and voltages obtained from the pre-processing blocks. The number of
processed alternate measuring quantities depends on the type of IED and built-in options.
The information on measured quantities is available for the user at different locations:
• Overfunction, when the measured quantity exceeds the High limit (XHiLim) or High-high limit
(XHiHiLim) pre-set values
• Underfunction, when the measured quantity decreases under the Low limit (XLowLim) or Low-
low limit (XLowLowLim) pre-set values.
X_RANGE = 3
High-high limit
X_RANGE= 1 Hysteresis
High limit
X_RANGE=0
X_RANGE=0 t
Low limit
X_RANGE=2
Low-low limit
X_RANGE=4
IEC05000657-3-en.vsdx
IEC05000657 V3 EN-US
The logical value of the functional output signals changes according to figure 215.
The user can set the hysteresis (XLimHyst), which determines the difference between the operating
and reset value at each operating point, in wide range for each measuring channel separately. The
hysteresis is common for all operating values within one channel.
In addition to the normal cyclic reporting the IED also report spontaneously when measured value
passes any of the defined threshold limits.
Y
Value Reported Value Reported
Value Reported Value Reported
(1st)
Y3 Value Reported
Y2 Y4
Y1 Y5
t
Value 1
Value 2
Value 3
Value 4
Value 5
IEC05000500 V2 EN-US
Value Reported
Y
IEC99000529-2-en.vsdx
IEC99000529 V2 EN-US
The last value reported, Y1 in figure 218 serves as a basic value for further measurement. A
difference is calculated between the last reported and the newly measured value and is multiplied by
the time increment (discrete integral). The absolute values of these integral values are added until
the pre-set value is exceeded. This occurs with the value Y2 that is reported and set as a new base
for the following measurements (as well as for the values Y3, Y4 and Y5).
The integral dead-band supervision is particularly suitable for monitoring signals with small variations
that can last for relatively long periods.
Y A1 >=
A >= pre-set value
A2 >=
pre-set value pre-set value
Y3 A3 + A4 + A5 + A6 + A7 >=
pre-set value
Y2 A1 A2
A4 A6
Value Reported Y4 A3 A5 A7
Value
(1st) Value
A Reported Y5
Reported Value
Reported Value
Y1 Reported
t
IEC99000530-2-en.vsdx
IEC99000530 V2 EN-US
Additionally, if a measuring value has changed from the last reported value, and the change is larger
than ±ΔY predefined limits that are set by user (XDbRepInt), then the measuring channel reports the
new value to a higher level immediately irrespective of cyclic trigger. See Figure 219 for example.
Value
Value
Reported
Y5 Y6
+ΔY
-ΔY
Y”
Y’
Y1 Y2 Y7
Y4
Y3
Δt Δt Δt Δt Δt Δt
Time
IEC16000109-2-en.vsdx
IEC16000109 V2 EN-US
Figure 219: Example of value reporting in mode dead band and xx cyclic (xx : 5 sec , 30 sec, 1
min)
The term <deadband> is used to describe the maximum deviation between the current value of a
signal and the last reported value.
The current value will be reported when the absolute value of the deviation is larger than the
computed deadband. The set value is entered in percent (as relative deadband), the absolute
deadband is calculated with the set value and the last reported value or actual measured value
(dynamic deadband computation).
Dynamic deadband computation will use smaller of the deadband computed from current value and
deadband computed from the last reported value. As a result, deadband of the last reported value
will be used for values moving away from the critical range, while the current value deadband will be
used when the measured value is approaching the critical range.
The effective deadband is always over 0.1% of the total range to prevent excessive reporting of
values close to the minimum value. It is restricted to dB*range using the setting ZdbRepInt, even if
the input value exceeds the configured maximum range value.
A minimum report interval of 250 milli-Seconds is applied to prevent high frequency noise with
amplitudes larger than computed deadband, in the most sensitive value range, from creating
excessive communication load.
Like other deadband profiles, a minimum report rate of 5, 30 or 60 seconds can be specified in the
parameter ZRepTyp. When this time has elapsed, since last report time, the new value will be
reported regardless of deadband or limits.
The applied minimum dead-band for all dead-band types is restricted to 0.1% of the range.
A deadband monitored value will also be reported if the limit value exceeds or when the value cross
over the configure range boundaries.
Rmin
IEC20000216 V1 EN-US
<Curr-Rep value> (dashed line) is the absolute value of the difference between current value and last
reported value.
IEC20000217 V1 EN-US
IEC20000218 V1 EN-US
IEC20000219 V1 EN-US
IEC20000220 V1 EN-US
• When one signal belonging to a group triggers a sending, then all other signals in the group will
be sent together.
• All cyclic transmission time and dead bands will be reset at transmission.
• The event grouping is only used for IEC 61850 events.
Phase-to-earth impedance measurement is calculated based on UL1/ IL1 , UL2 / IL2 , UL3 / IL3 and
When the operating current is too low, the impedance measurement can be erroneous. To avoid such
error, minimum operating current will be checked. For phase-earth currents or phase-phase currents
lower than 2% of IBase, the resistance and reactance of the impedance are forced to 99 999 ohm,
corresponding to a magnitude at 141419 (99 999*√2) ohm and an angle at 45 degree.
High speed distance protection (ZMFCPDIS) provides sub-cycle, down towards half-cycle, operate
time for basic faults within 60% of the line length and up to around SIR 5. At the same time, it is
specifically designed for extra care during difficult conditions in high voltage transmission networks,
like faults on long heavily loaded lines and faults generating heavily distorted signals. These faults
are handled with utmost security and dependability, although sometimes with reduced operating
speed.
High speed distance protection ZMFCPDIS is fundamentally the same function as ZMFPDIS but
provides more flexibility in zone settings to suit more complex applications, such as series
compensated lines. In operation for series compensated networks, the parameters of the directional
function are altered to handle voltage reversal.
The ZMFCPDIS function is a seven-zone full scheme protection with three fault loops for phase-to-
phase faults and three fault loops for phase-to-earth faults for each of the independent zones, which
makes the function suitable in applications with single-phase autoreclosing.
In each measurement zone, ZMFCPDIS function is designed with the flexibility to operate in either
quadrilateral or mho characteristic mode for separate phase-to-earth or phase-to-phase loops.
A new built-in adaptive load compensation algorithm prevents overreaching of the distance zones in
the load exporting end during phase-to-earth faults on heavily loaded power lines. It also reduces
underreach in the importing end.
The ZMFCPDIS function block incorporates a phase-selection element and a directional element,
contrary to previous designs in the IED series, where these elements were represented with separate
function blocks.
The operation of the phase-selection element is primarily based on current change criteria, with
significant increased dependability. There is also an impedance based part operating as continuous
criteria in parallel.
The directional element utilizes a set of well-established quantities to provide fast and correct
directional evaluation during various conditions, including close-in three-phase faults, simultaneous
faults and faults with only zero-sequence in-feed.
The ZMFCPDIS function has another transient components based directional element with phase
segregated outputs STTDFwLx and STTDRVLx (where, x = 1-3), which are intended for permissive
overreaching transfer trip (POTT) scheme. It provides directionality with high speed, dependability
and security, which is also suitable for extra high voltage and series compensated lines where the
fundamental frequency signals are distorted.
The ZMFCPDIS function is also equipped with the parallel line mutual coupling compensation feature
based on the parallel line residual current.
ZMFCPDIS
I3P* TRIP
U3P* TRZ1
BLOCK TRL1Z1
VTSZ TRL2Z1
BLKZ1 TRL3Z1
BLKZ2 TRZ2
BLKZ3 TRL1Z2
BLKZ4 TRL2Z2
BLKZ5 TRL3Z2
BLKZRV TRZ3
BLKZBU TRZ4
BLKTRZ1 TRZ5
BLKTRZ2 TRZRV
BLKTRZ3 TRZBU
BLKTRZ4 START
BLKTRZ5 STZ1
BLKTRZRV STNDZ1
BLKTRZBU STZ2
BLKTD STL1Z2
EXTNST STL2Z2
ORCND STL3Z2
RELCNDZ1 STNDZ2
RELCNDZ2 STZ3
RELCNDZ3 STNDZ3
RELCNDZ4 STZ4
RELCNDZ5 STNDZ4
RELCNDZRV STZ5
RELCNDZBU STNDZ5
STZRV
STL1ZRV
STL2ZRV
STL3ZRV
STNDZRV
STZBU
STNDZBU
STND
STNDL1
STNDL2
STNDL3
STNDPE
STFWL1
STFWL2
STFWL3
STFWPE
STRVL1
STRVL2
STRVL3
STRVPE
STFW1PH
STFW2PH
STFW3PH
STPE
STPP
STTDFWL1
STTDFWL2
STTDFWL3
STTDRVL1
STTDRVL2
STTDRVL3
IEC11000422-6-en.vsdx
IEC11000433 V5 EN-US
IEC11000422 V6 EN-US
8.12.5 Signals
PID-7497-INPUTSIGNALS v1
PID-7497-OUTPUTSIGNALS v1
8.12.6 Settings
PID-7497-SETTINGS v1
Settings, input and output names are sometimes mentioned in the following text
without its zone suffix (i.e. BLKZx instead of BLKZ3) when the description is equally
valid for all zones.
Practically all voltage, current and impedance quantities used within the ZMFCPDIS function are
derived from fundamental frequency phasors filtered by a half-cycle filter.
The phasor filter is frequency adaptive in the sense that its coefficients are changed based on the
estimated power system frequency.
A half-cycle filter will not be able to reject both even and odd harmonics. While odd harmonics will be
completely attenuated, accuracy will be affected by even harmonics. Even harmonics will not cause
the distance zones to overreach; instead there will be a slightly variable underreach, on average in
the same order as the magnitude ratio between the harmonic and the fundamental component.
The different fault loops within the IED are of full scheme type, which means that earth fault loop for
phase-to-earth faults and phase-to-phase faults for forward and reverse faults are executed in
parallel.
Figure 226 presents an outline of the different measuring loops for the seven distance zones.
IEC05000458‐3‐en.vsdx
IEC05000458 V3 EN-US
Figure 226: The different measuring loops at phase-to-earth fault and phase-to-phase fault
Transients from CVTs may have a significant impact on the transient overreach of a distance
protection. At the same time these transients can be very diverse in nature from one type to the
other; in fact, more diverse than can be distinguished by the algorithm itself in the course of a few
milliseconds. So, a setting is introduced in order to inform the algorithm about the type of CVT
applied and thus providing the advantage of knowing how performance should be optimized, even
during the first turbulent milliseconds of the fault period.
There are two types of CVTs from the function point of view, the passive and the active type, which
refers to the type of ferro-resonance suppression device that is employed. The active type requires
more rigorous filtering which will have a negative impact on operate times. However, this will be
evident primarily at higher source impedance ratios (SIRs), SIR 5 and above, or close to the reach
limit.
The IEC 60044-5 transient classification is of little or no use in relation to this. It is not primarily the
damping of transients that is important; it is the frequency content of the transients that is decisive,
i.e. how difficult it is to filter out the specific frequency. So, even if two CVTs, one passive and the
other active type, comply with the same transient class, the active type requires more extensive
filtering in order to avoid transient overreach.
To avoid overreach and at the same time achieve fast operate times, a supplementary circular
characteristic that includes some alternative processing is implemented. One such circular
characteristic exists for every measuring loop and quadrilateral/mho characteristic. There are no
specific reach settings for this circular zone. It uses the normal quadrilateral/mho zone settings to
determine a reach that will be appropriate. This implies that the circular characteristic will always
have somewhat shorter reach than the quadrilateral/mho zone.
The operation of the phase-selection element is primarily based on current change criteria. The
current change criteria itself can however only be relied on for a short period following the fault
inception (during what we will call the current change phase). Subsequent switching in the network
may render the change in current invalid. To handle this, the phase-selection element also operates
on impedance based continuous criteria.
The phase-selection element can, owing to the current change criteria, distinguish faults with
minimum influence from load and fault impedance. In other words, it is not restricted by a load
encroachment characteristic during the current change phase. This significantly improves
performance for remote phase-to-earth faults on heavily loaded lines. One exception, however, is
three-phase faults, for which the load encroachment characteristic always has to be applied, in order
to distinguish fault from load.
The continuous criteria will in the vast majority of cases operate in parallel and carry on the fault
indication after the current change phase has ended. Only in some particularly difficult faults on
heavily loaded lines the continuous criteria might not be sufficient, for example, when the estimated
fault impedance resides within the load area defined by the load encroachment characteristic. In this
case, the indication will be restricted to a pulse lasting for one or two power system cycles.
Phase-to-phase-earth faults (also called double earth faults) will practically always activate phase-to-
phase zone measurements. Measurement in two phase-to-earth loops at the same time is
associated with so-called simultaneous faults: two earth faults at the same time, one each on the two
circuits of a double line, or when the zero sequence current is relatively high due to a source with low
Z0/Z1 ratio. In these situations zone measurement will be released both for the related phase-to-
earth loops and the phase-to-phase loop simultaneously. On the other hand, simultaneous faults
closer to the remote bus will gradually take on the properties of a phase-to-phase-earth fault and the
function will eventually use phase-to-phase zone measurements also here.
In cases where the fault current infeed is mostly of zero sequence nature (all phase currents in
phase), the measurement will be performed in the phase-to-earth loops only for a phase-to-phase-
earth fault.
However, should it be desirable to use phase-to-earth (and only phase-to-earth) zone measurement
for phase-to-phase-earth faults, there is a setting INReleasePE that can be lowered from its
excessive default value to the level above which phase-to-earth measurement should be activated.
AND
2-phase Fault
I3P detected by
Impedance/ current
2-phase fault
U3P based Phase PHSLy
AND
selection
PHSLxLy
AND
OR
a
b a>b
250%
OR
a
b a>b
50% AND OR
a
b a<b
INMag
IL1Mag IN / Imax
IL2Mag
MAX
IL3Mag a ForcePE
b a<b
INReleasePE
IEC17000230-2-en.vsdx
IEC17000230 V2 EN-US
Several criteria are employed when making the directional decision. The basis is provided by
comparing a positive sequence based polarizing voltage with phase currents. For extra security,
especially in making a very fast decision, this method is complemented with an equivalent
comparison where, instead of the phase current, the change in phase current is used. Moreover, a
basic negative sequence directional evaluation is taken into account as a reliable reference during
high load condition. Finally, a zero sequence directional evaluation is used whenever there is more or
less exclusive zero sequence in-feed.
The directional sectors that represent forward direction, one per measuring loop, are defined by the
following equations.
U PolL1
ArgDir arg ArgNegRes
I L1
U PolL1L 2
ArgDir arg ArgNegRes
I L1L 2
Where:
UPolL1 is the polarizing voltage for phase L1.
UPolL1L2 is the polarizing voltage difference between phase L1 and L2 (L2 lagging L1).
IL1L2 is the current difference between phase L1 and L2 (L2 lagging L1).
Since the polarizing voltage is also used for the Mho distance characteristics, the magnitude of the
voltage is just as interesting as the phase. If there are symmetrical conditions and the measured per
phase positive sequence voltage magnitude is above 75% of the base voltage before the fault, the
pre-fault magnitude will be memorized and used as long as there is a fault. The phase angle however
will only be memorized (locked) for 75 ms at a time, not to lose synchronism with the real system
voltage.
Should the positive sequence voltage drop below 2% of the base voltage, it will be considered
invalid. In this situation, directional signals and starts from Mho elements will be sealed-in and kept
static as long as there is a fault.
For ZMFCPDIS, when option SeriesComp is chosen for OperationSC, the voltages of faulty phases
will be discarded in order not to affect the polarizing voltage with voltage reversal.
The ZMFCPDIS function has another directional element with phase segregated outputs STTDFwLx
and STTDRVLx (where, x=1-3), which are intended for the permissive overreaching transfer trip
(POTT) scheme. It provides directionality with high speed, dependability and security. It is also
suitable for extra high voltage and series compensated lines where the fundamental frequency
signals are distorted. The transient directional element is based on the changes in voltage and
current signals due to a fault. The changes can be calculated by subtracting the pre-fault voltage and
current from the measured quantiles due to a fault as shown below:
u t u t u p t
i t i t i p t
IECEQUATION18056 V1 EN-US (Equation 116)
Where,
∆u(t) and ∆i(t) are the changes in voltage and current due to the fault.
u(t) and i(t) are the measured voltage and current during the fault.
up(t) and ip(t) are the pre-fault voltage and pre-fault current.
When the power network is under stable operation, ∆u(t) and ∆i(t) are negligible. When a fault
occurs, ∆u(t) and ∆i(t) become visible due to the changes in electrical state of the power network.
According to the superposition principle, after a forward fault, ∆u(t) and ∆i(t) are opposite in sign.
While after a reverse fault, ∆u(t) and ∆i(t) are of equal sign.
By inserting a proper replica impedance ZR into the measurement path, a replica delta voltage
ΔuR(t), which is approximately proportional to ∆i(t), is obtained by ΔuR(t) = Δi(t)*ZR. The replica
impedance is optimized in the design to make the relay characteristic angle at 60 degree.
Δu(t)*ΔuR(t) is negative for a forward fault, and positive for a reverse fault.
The operating quantity can be obtained using a simple waveform integration function:
N
2
F t u t u t dt
0
R
Where, Th– and Th+ are the thresholds for negative and positive polarities of F(t).
To enable good security, the reverse detector is more sensitive compared to the forward one by a
much lower magnitude of Th+ than Th–.
Due to the transient nature, directionality decisions are required to be made after a short duration
when the phase-selection element has detected a fault. Once the decision is made, it issues
directional indications with pulses of duration at about 3-4 cycles.
The transient element has a good sensitivity for the initial fault. In certain cases, for example, a fault
with extremely high fault resistance, where Δu(t) or Δi(t) are very low and the transient directional
element is not active, the fundamental frequency component based directional elements (see Section
Directional criteria) will be available after a certain delay.
The ZMFCPDIS function has to be blocked by an additional function like the Fuse failure supervision
(FUFSPVC) or an equivalent external device. Typically, the binary input VTSZ is used for this
purpose.
However, to guarantee that also very fast operation is blocked in a fuse failure situation, there is a
built-in supervision based on change in current that will delay operation before the FUFSPVC
blocking signal is received. The delay will be introduced if no (vector) magnitude change greater than
5% of IBase has been detected in any of the phase currents.
There is need for external blocking of the ZMFCPDIS function during power swings, either from the
Power Swing Blocking function (ZMRPSB) or an external device.
All ZMFCPDIS zones operate according to the non-directional impedance characteristics presented
in figure 228 and figure 229. The phase-to-earth characteristic is illustrated with the full loop reach
while the phase-to-phase characteristic presents the per-phase reach.
The voltage and current phasors after the half-cycle filter are used in fault loop equations.
For phase-to-phase faults (Figure 230, lower part), the calculated impedances from the relay to the
fault Z calc Rcalc j X calc follow Equation 118 (example is given for a phase L1 to phase L2 fault).
U L1 U L 2 I L1 I L 2 Z calc
IECEQUATION18003 V1 EN-US (Equation 118)
Where and represents the corresponding voltage and current phasors in the respective
phase Ln (n = 1, 2, 3).
The calculated Rcalc and Xcalc are compared with the non-directional phase-to-phase quadrilateral
characteristics. If is inside the non-directional phase-to-phase characteristic, the STNDZx output
is set to TRUE.
For phase-to-earth faults (Figure 230, upper part), the earth return compensation applies according
to Equation 119 (example for a phase L1 to earth fault).
U L1 I L1 K N 3I 0 p Z1 I F RF
IECEQUATION18007 V1 EN-US (Equation 119)
Where,
p is the fault location and RF is the calculated fault resistance. p and RF are unknown and needs to
be solved.
Z 0 Z1
KN
3 Z1
Z 0 R0 FwPEZx j X 0 FwPEZx
Z1 R1FwPEZx j X 1FwPEZx
IECEQUATION18020 V1 EN-US
Where,
R1FwPEZx is the positive sequence resistive reach of the line in Ω/phase for phase-to-earth fault in
zone direction for zone x (x = 1 to 5, BU or RV).
X1FwPEZx is the positive sequence reactance reach of the line in Ω/phase for phase-to-earth fault in
zone direction for zone x (x = 1 to 5, BU or RV).
R0FwPEZx is the zero-sequence resistive reach of the line in Ω/phase for phase-to-earth fault in
zone direction for zone x (x = 1 to 5, BU or RV).
X0FwPEZx is the zero-sequence reactance reach of the line in Ω/phase for phase-to-earth fault in
zone direction for zone x (x = 1 to 5, BU or RV).
is the fault current. It is chosen among phase, zero or negative sequence currents automatically
by the built-in adaptive load compensation algorithm. If the system behind the relay cannot contribute
enough zero-sequence current, only phase or negative sequence current will be chosen.
The calculated impedances from the relay to the fault Z calc Rcalc j X calc can be represented as:
X calc p X 1FwPEZx
Rcalc p R1FwPEZx RF
IECEQUATION18021 V1 EN-US
When the two unknowns p and RF are solved from the Equation 118 then the calculated Rcalc and
Xcalc values are compared with the non-directional phase-to-earth quadrilateral characteristics. If
is inside the non-directional phase-to-earth characteristic, the STNDZx output is set to TRUE.
The load compensation for zone 1 is achieved by estimating the impedance with three different
values of the IF current with:
• neutral current
• negative sequence current
• phase current.
Impedance estimation is based on the neutral current or negative sequence current essentially that
excludes the current component that causes the over-reach. The reactance values from all the
calculations shall effectively be within the zone reactive boundary in order to get the non-directional
start signal from the zone. This means that the under-reach, that is caused by the load import, is not
compensated.
For the other zones, it is enough in effect if the median value of the three is within the zone reach. If
the neutral current is not sufficient, then the negative sequence current based reactance will
represent the median value. If the negative sequence current is not sufficient, then the other
reactance has to be within the reach.
X (Ohm/loop)
X0FwPEZx , X1FwPEZx
XNFwZx <
R1FwPEZx+RNFwZx 3
X1RvPEZx
XNRvZx < XNFwZx √
RFRvPEZx RFFwPEZx X1FwPEZx
R0FwPEZx , R1FwPEZx
RNFwZx <
3
X1RvPEZx
RNRvZx < RNFwZx √
X1FwPEZx
X1RvPEZx
X1FwPEZx+XNFwZx R1RvPEZx < R1FwPEZx √
X1FwPEZx
ιN ιN
R (Ohm/loop)
1) 1)
RFRvPEZx RFFwPEZx
X1RvPEZx+XNRvZx
ιN
RFRvPEZx RFFwPEZx
Figure 228: ZMFCPDIS Characteristic for phase-to-earth measuring loops, ohm/loop domain
R1FwPPZx
X (Ohm/phase)
RFRvPPZx RFFwPPZx
2 2
X1FwPPZx
ιN
R (Ohm/phase)
1) 1)
RFRvPPZx RFFwPPZx
2 2
X1RvPPZx
ιN
RFRvPPZx RFFwPPZx
2 2
X1RvPPZx IEC11000418-3-en.vsd
R1FwPPZx √
X1FwPPZx
Figure 229: ZMFCPDIS Characteristic for the phase-to-phase measuring loops, ohm/phase
domain
Note that for ZMFCPDIS, the reverse zone ZRV, as well as any of zones 3-5, that
are set to DirMode=Reverse will get their operating impedances inverted (rotated
180 degrees) internally in order to make use of the main settings, which are the
settings designated ‘Fw’. Therefore, a reverse zone will have its Fw-settings
(RFFwPPZRV, X1FwPEZ3, and so on) applied in the third quadrant, that is, towards
the busbar instead of the line.
The fault loop reach in relation to each fault type may also be presented as in figure 230. The main
intention with this illustration is to make clear how the fault resistive reach should be interpreted. Note
in particular that the setting RFPP [2] always represents the total fault resistance of the loop, even
while the fault resistance (arc) may be divided into parts like for three-phase or phase-to-phase-to-
earth faults. R1Zx and jX1Zx represent the positive sequence impedance from the measuring point to
the fault location.
Phase-to-earth
RFPEZx
fault in phase L1
(Arc + tower
resistance)
0
IN (R0Zx-R1Zx)/3 +
j (X0Zx-X1Zx)/3 )
The estimated impedance needs to be inside both characteristics for the zone to start or trip. (The
non-directional start STNDZx is an exception however. It is only dependent on the quadrilateral
characteristic.)
In the following figure, it is shown how the X1PP setting can influence the shape of the quadrilateral
characteristic in the fourth quadrant for short line applications.
X (ohm)
X1PP’
X1PP
15° R (ohm)
RFPP/2
-X1PP
R· tan15°
-X1PP’
Line distance protection=IEC19000141=2=en-us=Original.vsdx
IEC19000141 V2 EN-US
Figure 231: Influence of X1PP setting on the quadrilateral shape in the fourth quadrant
The quadrilateral phase-to-earth element is added with the parallel line mutual coupling
compensation feature based on the parallel line residual current. The additional current signal must
be connected to the function through the INP group input. The parallel line residual current hardware
channel must be connected to the residual quantity input of the corresponding SMAI block. The
compensation feature can be switched On/Off with the EnPar setting.
When the parallel compensation is switched On (EnPar is On), the phase-to-earth loop Equation 119
is modified according to Equation 120 (example is given for phase L1 to earth fault).
U L1 ( I L1 K N 3I 0 K Nm 3I 0 p ) p Z1 I F RF
IECEQUATION20296 V1 EN-US (Equation 120)
Z0m
K Nm =
3 Z1
IECEQUATION20299 V1 EN-US
Z 0 m = R0MZx + j X 0MZx
IECEQUATION20300 V1 EN-US
Where,
Z 0m is the set complex zero-sequence mutual impedance between parallel lines in Ω/phase.
is the zero-sequence resistance between parallel lines in Ω/phase for the phase-to-earth
fault in zone direction for zone x (where x = 1 to 2).
is the zero-sequence reactance between parallel lines in Ω/phase for the phase-to-earth
fault in zone direction for zone x (where x = 1 to 2).
The compensation feature will only be active when the parallel line residual current is not significantly
higher than the protected line residual current. The deactivation limit of this parallel line
compensation feature is set with the INPRatio setting. Compensation is deactivated when:
3I0p
INPRatio
3I0
IECEQUATION20302 V1 EN-US
The mutual compensation is also deactivated when the protected line residual current is less than
50% of IMinOp according to the below relation:
3I 0 0.5 IMin0 p
IECEQUATION20303 V1 EN-US
Zones 2 to 5 and BU can be selected to be either forward or reverse with positive sequence
polarized mho characteristic; alternatively self polarized offset mho characteristics. The operating
characteristic is in accordance to figure 232 where zone 5 is selected offset mho.
X
ZBU X
Z4
Z3
ZS=0
Z2
Z1 R
Z5 R
ZS=Z1
ZRV
ZS=2Z1
IEC150000 56-2-en.vsdx
IEC15000056 V2 EN-US
Figure 232: Mho, offset mho characteristics and the source impedance influence on the mho
characteristic
The mho characteristic has a dynamic expansion due to the source impedance. Instead of crossing
the origin, as for the mho to the left of figure 232, which is only valid where the source impedance
(Zs) is zero, the crossing point is moved to the coordinates of the negative source impedance given
an expansion of the circle shown to the right of figure 232. Z1 denotes the complex positive
sequence impedance.
The magnitude of the polarized voltage is determined completely by the positive sequence voltage
magnitude from before the fault. This will give a somewhat less dynamic expansion of the mho circle
during faults. However, if the source impedance is high, the dynamic expansion of the mho circle
might lower the security of the function too much with high loading and mild power swing conditions.
ZMFCPDIS fixes zone 1 in Forward mode and zone RV in Reverse mode. Zone 2 to 5 and BU can
be set to Non-directional, Forward or Reverse by setting the parameter DirModeZx (where x = 2 to 5
or BU depending on selected zone).
X X
(a) Rset
X (c)
(b) Rset
Rset
Mho Characteristics
(a) and (d) are for Zone 1, Zone 2 and Zone 3-5 when DirModeZ2-BU = Forward
(b) and (e) are for ZoneRV and Zone 3-5 when DirModeZ2-BU = Reverse
(c) and (f) are for Zone 3-5 when DirModeZ2-BU = Non-Directional
X=2 to 5 or BU IEC150000 65-4-en-us.vsdx
IEC15000065 V4 EN-US
ZMFCPDIS function uses separate sets of reach settings in forward and reverse directions for phase-
to-earth fault and phase-to-phase fault. These settings are R1FwPPZx, X1FwPPZx, X1RvPPZx,
R1FwPEZx, X1FwPEZx, X1RvPEZx, R0FWPEZx, X0FwPPZx (x= 1 to 5, BU or RV). Thus, the
center of the Non-directional offset mho circle can be arbitrarily located in the circle (figure 233).
Note that the reverse ZoneRV, as well as any of zones 3 to 5 and BU, that are set to
DirModeZx=Reverse will get their operating impedances inverted (rotated 180 degrees) internally in
order to make use of the main settings, which are the settings designated ‘Fw’. Therefore, a reverse
zone will have its Fw-settings (R1FwPPZRV, X1FwPEZ3, and so on) applied in the third quadrant,
that is, towards the busbar instead of the line.
In Non-directional mode, for both Mho and Quad, the reach settings are equal to Forward mode in
this respect. The ‘Fw’ settings apply in the first quadrant and the ‘Rv’ settings apply in the third
quadrant.
( )
β = arg U L1L 2 − I L1L 2 ⋅ Z 1set − arg U pol ( )
IECEQUATION15027 V1 EN-US (Equation 121)
where
is the positive sequence impedance setting for phase-to-phase fault in zone direction
Z 1set
where:
R1FwPPZx is the positive sequence resistive reach for phase-to-phase fault in zone direction for zone x (x=1 to 5,
BU and RV)
X1FwPPZx is the positive sequence reactance reach for phase-to-phase fault in zone direction for zone x (x=1 to 5
BU and RV)
The polarized voltage consists of 100% memorized positive sequence voltage (UL1L2 for phase L1 to
L2 fault). The memorized voltage will prevent collapse of the mho circle for close in faults.
IL1L2 jX
I L1L 2 Z1set
UcompUL1L2 IL1L2 Z1set
UL1L2
U pol
I L1L 2 R
IEC15000060-1-en.vsdx
IEC15000060 V1 EN-US
Figure 234: Simplified mho characteristic and vector diagram for phase L1-to-L2 fault
Offset Mho GUID-2E84AD28-CA5F-4D19-B189-57354C8F7CF9 v3
The characteristic for offset mho is a circle where two points on the circle are given by the two
vectors Z 1set and Z 1RVset where Z 1set and Z 1RVset are settable through the resistance and
reactance settings in forward and reverse directions.
The condition for operation at phase-to-phase fault is that the angle β between the two compensated
voltages is greater than or equal to 90° (figure 235). The angle will be 90° for fault location on the
boundary of the circle.
U
L1L 2 I L1L 2 Z 1set
arg
U L1L 2 I L1L 2 Z1set
IECEQUATION15008 V2 EN-US (Equation 124)
where
is the positive sequence impedance setting for phase-to-phase fault
Z 1RVset opposite to zone direction and is defined as
where
X1RvPPZx is the positive sequence reactance reach for phase-to-phase fault
opposite to zone direction for zone x (x=1 to 5, BU or RV)
R1RvPPZx is the positive sequence resistive reach for phase-to-phase fault
opposite to zone direction for zone x (x=1 to 5, BU or RV) and is
internally calculated according to the equation below,
R1FwPPZx
R1RvPPZx = X 1RvPPZx ⋅
X 1FwPPZx
IECEQUATION15014 V1 EN-US (Equation 126)
IL1L 2 jX
IL1L 2 Z1set
UL1L 2
Ucomp 2 UL1L 2 IL1L 2 Z1RVset
IL1L 2 R
IL1L 2 Z1RVset
IEC16000207-1-en.vsdx
IEC16000207 V1 EN-US
Figure 235: Simplified offset mho characteristic and voltage vector for phase L1 to L2 fault
Operation occurs if 90°≤β≤270 °.
Compensation for earth return path for faults involving earth is done by setting the positive and zero
sequence impedance of the line. It is known that the earth compensation factor KN is,
Z 0set − Z 1set
KN =
3 ⋅ Z 1set
IECEQUATION15017 V1 EN-US
where
For an earth fault in phase L1, the angle β between the compensation voltage and the polarizing
where
is the phase voltage in faulty phase L1
UL1
is the phase current in faulty phase L1
IL1
3I 0 is the zero-sequence current in faulty phase L1
IL1•jX
U L1
I L1 Z1set
U pol
IL1•R
IEC15000059-1-en.vsdx
IEC15000059 V1 EN-US
Figure 236: Simplified offset mho characteristic and vector diagram for phase L1-to-earth fault
Operation occurs if 90 °≤β≤270 °.
arg U L1 ( I L1 3I 0 K N ) Z1set arg U L1 ( I L1 3I 0 K N ) Z1set
where
is the complex positive sequence impedance of the line in Ω/phase
Z 1RVset for phase-to-earth fault opposite to zone direction and is defined as,
where
X1RvPEZx is the positive sequence reactance reach for phase-to-earth fault
opposite to zone direction for zone x (x=1-5, BU and RV)
R1RvPEZx is the positive sequence resistive reach for phase-to-earth fault
opposite to zone direction for zone x (x=1-5 and RV) and expressed
by,
R1FwPEZx
R1RvPEZx = X 1RvPEZx ⋅
X 1FwPEZx
IECEQUATION15024 V1 EN-US (Equation 131)
In some cases the load impedance might enter the zone characteristic without any fault on the
protected line. The phenomenon is called load encroachment and it might occur when an external
fault is cleared and high emergency load is transferred on the protected line. The effect of load
encroachment is illustrated in the left part of figure 237. A load impedance within the characteristic
would cause an unwanted trip. The traditional way of avoiding this situation is to set the distance
zone resistive reach with a security margin to the minimum load impedance. The drawback with this
approach is that the sensitivity of the protection to detect resistive faults is reduced.
The IED has a built-in function which shapes the under-impedance starting characteristic according
to the right part of figure 237. The load encroachment algorithm will increase the possibility to detect
high fault resistances, especially for phase-to-earth faults at the remote line end. For example, for a
given setting of the load angle ArgLd the resistive blinder for the zone measurement can be
expanded according to the right part of the figure 237, given higher fault resistance coverage without
risk for unwanted operation due to load encroachment. This is valid in both directions.
The use of the load encroachment feature is essential for long heavily loaded lines, where there
might be a conflict between the necessary emergency load transfer and necessary sensitivity of the
distance protection. The function can also preferably be used on heavy loaded medium long lines.
For short lines, the major concern is to get sufficient fault resistance coverage. Load encroachment is
not a major problem. Nevertheless, always set RLdFw, RLdRv [3] and ArgLd according to the
expected maximum load since these settings are used internally in the function as reference points to
improve the performance of the phase selection.
As already explained the built-in phase selection is mostly based on current change criteria and has
no user defined settings. However, a traditional under-impedance-based phase selector is always
working in parallel with it. This under-impedance-based criterion is defined by the two setting
parameters XStart and RStart, as shown in Figure 237. These two settings are common for both Ph-
Ph and Ph-Gnd measurement loops. In order to ensure proper operation of the distance zones the
under-impedance based starting element shall be set in such a way to always cover (i.e. be larger
than) all used distance zones for both Ph-Ph and Ph-Gnd loops. Consequently, the following settings
are recommended:
Parameter XStart shall be set to a value which is at least 20% bigger than the value obtained by
formula (2*X1FwPEZx+X0FwPEZx)/3 applied for the longest reaching zone.
It is recommended that the RStart setting shall not exceed the load impedance, which is typically
defined as UBase/sqrt(3)/IBase in primary ohms. It is recommended to reduce the RStart set value to
maximum 80% of the above defined load impedance value. However, the RLd settings can be
utilized to get an additional non-operation sector for emergency load, like for when a parallel line is
opened, as shown in Figure 237.
[3] RLdRv=RLdRvFactor*RLdFw.
Distance Zones
RStart
XStart RLdFw
ArgLd
RLdRvFactor
XStart
* RLdFw
100
RStart
IEC09000248-5-en-us.vsdx
IEC09000248 V5 EN-US
PHSL1, PHSL2,...PHSL3L1 are internal binary logical signals from the phase-selection element.
They correspond directly to the six loops of the distance zones and determine which loops should be
released to possibly issue a start or a trip.
The ORCND input enables the use of external elements to supplement the internal phase selection
in specialized applications, like unblocking of the distance protection during power swings. Like with
the other CND signals, each bit of its binary encoded integer number corresponds to one of the six
measuring loops to be enabled. See Figure 238.
PHSL1, PHSL2,… PHSL3L1
Phase selection Zone1
Internal
criteria bitwise
OR bitwise release
AND
Zone2
RELCNDZ1
bitwise release
RELCNDZ2 AND
RELCNDZ3
Zone3
IEC19000323-1-en-us.vsdx
IEC19000323 V1 EN-US
FWL1, FWL2,...FWL3L1 and RVL1, RVL2,...RVL3L1 are the internal binary signals from the
directional element. An FW signal is set true if the criteria for a forward fault or load is fulfilled for its
particular loop. The same applies to the reverse (RV) signals.
The internal input 'IN present' is true if the residual current (3I0) exceeds 7% of IBase. However, if
current transformer saturation is detected, this criterion is changed to residual voltage (3U0)
exceeding 5% of UBase/sqrt(3) instead.
DirModeZ3-5, BU
TRUE (1)
FW(Ln & LmLn) Forward
RV(Ln & LmLn) Reverse
IEC12000137-4-en.vsd
IEC12000137 V4 EN-US
ZML1Zx PEZx
OR
PHSL1
AND
DIRL1Zx AND
ZML2Zx
PHSL2
AND
DIRL2Zx AND
ZML3Zx L1Zx
OR
PHSL3
AND
DIRL3Zx AND
ZML1L2Zx L2Zx
PHSL1L2 OR
AND
DIRL1L2Zx AND
ZML2L3Zx
PHSL2L3 L3Zx
AND OR
DIRL2L3Zx AND
ZML3L1Zx
PHSL3L1
AND
DIRL3L1Zx AND
L1N
PPZx
L2N OR
L3N
RELCNDZx Integer L1L2
to Bool
L2L3
NDZx
L1L3 OR
IEC12000140-2-en.vsdx
IEC12000140 V2 EN-US
TimerModeZx =
Enable PhPh or
Ph-E PhPh
PPZx AND tPPZx
OR AND
AND t
PEZx
AND tPEZx OR
TimerModeZx = OR
AND t
Enable Ph-E or AND
Ph-E PhPh
VTSZ
BLKZx OR
OR
TimerLinksZx
ZoneLinkStart
LoopLink (tPP-tPE)
Phase Selection
LoopLink & ZoneLink
1st starting zone OR
No Links
LNKZx
FALSE (0) AND
OR
TimerLinksZx =
LoopLink & ZoneLink
EXTNST
IEC12000139-6-en.vsdx
IEC12000139 V6 EN-US
15 ms
TZx
t TRIPZx
AND
TRL1Zx
OR AND
BLOCK
VTSZ TRL2Zx
OR AND
BLKZx
TRL3Zx
AND
15 ms
L1Zx
t STL1Zx
AND
15 ms
L2Zx
t STL2Zx
AND
15 ms
t STL3Zx
AND
PPZx 15 ms
PEZx OR t STARTZx
AND
15 ms
NDZx
t STNDZx
AND
IEC12000138-2-en.vsd
IEC12000138 V2 EN-US
15 ms
OR t STPE
AND
15 ms
OR t
AND
15 ms
OR t STNDL2
PHSL1L2 AND
15 ms
OR t STNDL3
AND
15 ms
OR t STPP
AND
BLOCK STARTND
OR
VTSZ OR
STPHS
STNDPE
AND
IEC12000133-3-en.vsdx
IEC12000133 V3 EN-US
PHSL1
FWL1 AND
15 ms
FWL2 AND OR t
AND
FWL3 AND 15 ms
PHSL1L2 OR t STFWL2
AND
FWL1L2 AND
PHSL2L3 15 ms
FWL2L3 AND OR t STFWL3
AND
FWL3L1 AND
OR
STFWPE
IN present AND
STFW1PH
=1
BLOCK
VTSZ OR
STFW2PH
=2
STFW3PH
=3
IEC12000134-2-en.vsd
IEC12000134 V2 EN-US
PHSL1
RVL1 AND
15 ms
RVL2 AND OR t
AND
RVL3 AND 15 ms
PHSL1L2 OR t STRVL2
AND
RVL1L2 AND
PHSL2L3 15 ms
RVL2L3 AND OR t STRVL3
AND
RVL3L1 AND
OR
STRVPE
IN present AND
BLOCK
VTSZ OR
IEC12000141-2-en.vsdx
IEC12000141 V2 EN-US
TDFWL1 AND
15 ms
TDFWL2 AND OR t
AND
PHSL3
TDFWL3 AND 15 ms
PHSL1L2 OR t STTDFWL2
AND
AND
AND 15 ms
PHSL2L3 OR t STTDFWL3
AND AND
AND
PHSL3L1
AND
AND
PHSL1
TDRVL1 AND
15 ms
TDRVL2 AND OR t
AND
AND 15 ms
OR t STTDRVL2
AND
AND
AND 15 ms
PHSL2L3 OR t STTDRVL3
AND AND
AND
PHSL3L1
AND
AND
VTSZ
OR
BLOCKTD
IEC18000241-1-en.vsdx
IEC18000241 V1 EN-US
8.12.8.11 Measurement
Measurement supervision SEMOD54417-130 v4
The protection, control, and monitoring IEDs have functionality to measure and further process
information for currents and voltages obtained from the pre-processing blocks. The number of
processed alternate measuring quantities depends on the type of IED and built-in options.
The information on measured quantities is available for the user at different locations:
• Overfunction, when the measured quantity exceeds the High limit (XHiLim) or High-high limit
(XHiHiLim) pre-set values
• Underfunction, when the measured quantity decreases under the Low limit (XLowLim) or Low-
low limit (XLowLowLim) pre-set values.
X_RANGE = 3
High-high limit
X_RANGE= 1 Hysteresis
High limit
X_RANGE=0
X_RANGE=0 t
Low limit
X_RANGE=2
Low-low limit
X_RANGE=4
IEC05000657-3-en.vsdx
IEC05000657 V3 EN-US
The logical value of the functional output signals changes according to figure 247.
The user can set the hysteresis (XLimHyst), which determines the difference between the operating
and reset value at each operating point, in wide range for each measuring channel separately. The
hysteresis is common for all operating values within one channel.
In addition to the normal cyclic reporting the IED also report spontaneously when measured value
passes any of the defined threshold limits.
Y
Value Reported Value Reported
Value Reported Value Reported
(1st)
Y3 Value Reported
Y2 Y4
Y1 Y5
t
Value 1
Value 2
Value 3
Value 4
IEC05000500 V2 EN-US
Value Reported
Y
IEC99000529-2-en.vsdx
IEC99000529 V2 EN-US
The last value reported, Y1 in figure 250 serves as a basic value for further measurement. A
difference is calculated between the last reported and the newly measured value and is multiplied by
the time increment (discrete integral). The absolute values of these integral values are added until
the pre-set value is exceeded. This occurs with the value Y2 that is reported and set as a new base
for the following measurements (as well as for the values Y3, Y4 and Y5).
The integral dead-band supervision is particularly suitable for monitoring signals with small variations
that can last for relatively long periods.
Y A1 >=
A >= pre-set value
A2 >=
pre-set value pre-set value
Y3 A3 + A4 + A5 + A6 + A7 >=
pre-set value
Y2 A1 A2
A4 A6
Value Reported Y4 A3 A5 A7
Value
(1st) Value
A Reported Y5
Reported Value
Reported Value
Y1 Reported
t
IEC99000530-2-en.vsdx
IEC99000530 V2 EN-US
Phase-to-earth impedance measurement is calculated based on UL1/ IL1 , UL2 / IL2 , UL3 / IL3 and
When the operating current is too low, the impedance measurement can be erroneous. To avoid such
error, minimum operating current will be checked. For phase-earth currents or phase-phase currents
lower than 2% of IBase, the resistance and reactance of the impedance are forced to 99 999 ohm,
corresponding to a magnitude at 141419 (99 999*√2) ohm and an angle at 45 degree.
8.13.2 Identification
GUID-69401D58-00EB-4560-8C35-72AF417E5441 v1
SYMBOL-EE V1 EN-US
Power swings may occur after disconnection of heavy loads or trip of big generation plants.
Power swing detection, blocking and unblocking function (ZMBURPSB ) is used to detect power
swings and initiate blocking of all distance protection zones.
Also, fault identification and its classification for various types of fault occurrences during the power
swing are available in the ZMBURPSB function. So, six measuring loops used in each distance
protection zone, if blocked during power swing, can be unblocked/released for distance
measurement depending upon the fault type and thereby, reliable fault clearance can be achieved for
faults during power swing.
It is still possible to inhibit the ZMBURPSB function for earth-fault currents during a power swing
without activating power swing unblocking functionality.
ZMBURPSB
I3P* START
U3P* ZOUT
BLOCK ZIN
BLKI01 FLTL1
BLKI02 FLTL2
BLK1PH FLTL3
REL1PH FLT1PH
BLK2PH FLT2PH
REL2PH FLT3PH
I0CHECK STCND
TRSP RELCND
EXTERNAL
IEC01000323 V1 EN-US
8.13.5 Signals
PID-7380-INPUTSIGNALS v2
PID-7380-OUTPUTSIGNALS v1
8.13.6 Settings
PID-7380-SETTINGS v1
The power swing detection, blocking and unblocking (ZMBURPSB ) function comprises an inner and
an outer quadrilateral measurement characteristic with load encroachment, as shown in figure 252.
Its principle of operation is based on the measurement of the time it takes for a power swing transient
impedance to pass through the impedance area between the outer and the inner characteristics. The
power swings are identified by transition times longer than a transition time set in corresponding
timers. The impedance measuring principle is the same as that used for the distance protection
zones. The impedance and the characteristic passing times are measured in all three phases
separately.
X1OutFw jX ZL R1LIn
X1InFw DFw
j
DRv
R1FInRv R1FInFw
DFw
ArgLd j
ArgLd
DRv
DFw
DFw
R
DFw
DRv
RLdInRv RLdInFw
DFw
DRv
RLdOutRv RLdOutFw
j DRv X1InRv
X1OutRv
IEC09000222_1_en.vsd
IEC09000222 V1 EN-US
Figure 252: Operating characteristic for ZMBURPSB function (setting parameters in italic)
The impedance measurement within ZMBURPSB function is performed by solving equation 132 and
equation 133 (n = 1, 2, 3 for each corresponding phase L1, L2 and L3).
æ ULn ö
Re çç ÷÷ £ Rset
è ILn ø
EQUATION1183 V2 EN-US (Equation 132)
æ ULn ö
Imçç ÷÷ £ Xset
è ILn ø
EQUATION1184 V2 EN-US (Equation 133)
RLdInFw = kLdRFw·RLdOutFw
EQUATION1185 V2 EN-US (Equation 134)
where:
kLdRFw is a settable multiplication factor less than 1
The slope of the load encroachment inner and outer boundary is defined by setting the parameter
ArgLd.
The load encroachment in the fourth quadrant uses the same settings as in the first quadrant (same
ArgLd and RLdOutFw and calculated value RLdInFw).
The quadrilateral characteristic in the first quadrant is tilted to get a better adaptation to the distance
measuring zones. The angle is the same as the line angle and derived from the setting of the
reactive reach inner boundary X1InFw and the line resistance for the inner boundary R1LIn. The fault
resistance coverage for the inner boundary is set by the parameter R1FInFw.
From the setting parameter RLdOutFw and the calculated value RLdInFw a distance between the
inner and outer boundary, DFw, is calculated. This value is valid for R direction in first and fourth
quadrant and for X direction in first and second quadrant.
RLdInRv = kLdRRv·RLdOutRv
EQUATION1187 V2 EN-US (Equation 135)
where:
kLdRRv is a settable multiplication factor less than 1
From the setting parameter RLdOutRv and the calculated value RLdInRv, a distance between the
inner and outer boundary, DRv, is calculated. This value is valid for R direction in second and third
quadrant and for X direction in third and fourth quadrant.
The inner resistive characteristic in the second quadrant outside the load encroachment part
corresponds to the setting parameter R1FInRv for the inner boundary. The outer boundary is
internally calculated as the sum of DRv+R1FInRv.
The inner resistive characteristic in the third quadrant outside the load encroachment zone consist of
the sum of the settings R1FInRv and the line resistance R1LIn. The argument of the tilted lines
outside the load encroachment is the same as the tilted lines in the first quadrant. The distance
between the inner and outer boundary is the same as for the load encroachment in reverse direction,
that is DRv.
where:
DFw = RLdOutFw - KLdRFw · RLdOutFw
The inner characteristic for the reactive reach in reverse direction correspond to the setting
parameter X1InRv for the inner boundary and the outer boundary is defined as X1InRv + DRv.
where:
DRv = RLdOutRv - KLdRRv · RLdOutRv
• The 1 out of 3 operating mode is based on detection of power swing in any of the three phases.
Figure 253 presents a composition of an internal detection signal DET-L1 in this particular
phase.
• The 2 out of 3 operating mode is based on detection of power swing in at least two out of three
phases. Figure 254 presents a composition of the detection signals DET1of3 and DET2of3.
Signals ZOUTLn (outer boundary) and ZINLn (inner boundary) in figure 253 are related to the
operation of the impedance measuring elements in each phase separately (n represents the
corresponding L1, L2 and L3). They are internal signals, calculated by ZMBURPSB function.
The tP1 timer in figure 253 serve as detection of initial power swings, which are usually not as fast as
the later swings are. The tP2 timer become activated for the detection of the consecutive swings, if
the measured impedance exit the operate area and returns within the time delay, set on the tW
waiting timer. The upper part of figure 253 (internal input signal ZOUTL1, ZINL1, AND-gates and tP-
timers) are duplicated for phase L2 and L3. All tP1 and tP2 timers in the figure have the same
settings.
ZOUTL1 AND
0-tP1
ZINL1 0 OR
-loop
0-tP2
-loop
AND
0
OR DET-L1
AND AND
ZOUTL2 OR
ZOUTL3
detected 0
0-tW
IEC05000113-2-en.vsd
IEC05000113 V2 EN-US
DET-L1
DET-L2 DET1of3 - int.
>1
DET-L3
&
DET2of3 - int.
& >1
&
IEC01000057-2-en.vsd
IEC01000057-TIFF V2 EN-US
Figure 254: Detection of power swing for 1-of-3 and 2-of-3 operating mode
ZOUTL1 ZOUT
OR
ZOUTL2 ZINL1
ZIN
ZOUTL3 AND ZINL2 OR
ZINL3
tEF
TRSP
t AND
I0CHECK
10 ms
AND t
BLKI02 OR
tR1
AND t INHIBIT
OR
-loop
tR2
BLKI01 AND t
BLOCK
-loop
DET1of3 - int.
REL1PH
AND
BLK1PH
tH
DET2of3 - int. OR t
REL2PH
AND
BLK2PH OR START
AND
EXTERNAL
en05000114.vsd
IEC05000114 V1 EN-US
Selection of the operating mode is possible by the proper configuration of the functional input signals
REL1PH, BLK1PH, REL2PH, and BLK2PH.
The load encroachment characteristic can be switched off by setting the parameter OperationLdCh =
Off, but notice that the DFw and DRv will still be calculated from RLdOutFw and RLdOutRv. The
characteristic will in this case be only quadrilateral.
There are four different ways to form the internal INHIBIT signal:
• Logical 1 on functional input BLOCK inhibits the output START signal instantaneously.
• The INHIBIT internal signal is activated, if the power swing has been detected and the
measured impedance remains within its operate characteristic for the time, which is longer than
the time delay set on tR2 timer. It is possible to disable this condition by connecting the logical 1
signal to the BLKI01 functional input.
• The INHIBIT internal signal is activated after the time delay, set on tR1 timer, if an earth-fault
appears during the power swing (input IOCHECK is high) and the power swing has been
detected before the earth-fault (activation of the signal I0CHECK). It is possible to disable this
condition by connecting the logical 1 signal to the BLKI02 functional input.
• The INHIBIT logical signals becomes logical 1, if the functional input I0CHECK appears within
the time delay, set on tEF timer activated by the input signal TRSP and the impedance has been
seen within the outer characteristic of ZMBURPSB operate characteristic in all three phases.
This function prevents the operation of ZMBURPSB function in cases, when the circuit breaker
closes onto persistent single-phase fault after single-phase autoreclosing dead time, if the initial
single-phase fault and single-phase opening of the circuit breaker causes the power swing in the
remaining two phases.
Operation of power swing unblocking feature is set to On/Off by a configurable setting parameter
OpModePSU. Power swing unblocking enables reliable phase selection (i.e. accurate selection of
faulty phases) for various types of faults that occur during power swing and keeps healthy phase(s)
remain blocked during power swing.
Filtering GUID-04D2D0B4-98CB-44E0-95A2-955687EB9F76 v1
The calculation of current change criteria (i.e. delta quantities) is implemented from a sample-based
algorithm. The algorithm yields zero changes in currents irrespective of regular load flow and power
swing conditions, while it gives significant changes in currents during power system faults.
The phase selection element consists of three phase-to-earth loops and three phase-to-phase loops
which are executed in parallel. Phase-to-phase-earth faults (also called double earth faults)
practically activate phase-to-phase loop for distance measurement.
Since delta quantities exist for a short period, the internal signal, FLTL1E is sealed-in as long as
either negative sequence current is above 12.0% IB or residual current is above 20.0% IB.
or
The above logic is also valid for the remaining two phase-to-earth loops. Output FLT1PH is set to the
logical 1 if any of three phase-to-earth loops detects a fault during power swing. In case of phase-to-
phase-earth on the protected line, no output from the phase-to-earth loops is shown to avoid
overreaching or underreaching of the distance measuring zones.
If the input signal BLOCK is high during the fault period, output FLT1PH is reset to a logical 0.
Since delta quantities exist for a short period, the internal signal, FLTL12 is sealed-in as long as
negative sequence current is above 12.0% IB.
or
The above logic is also valid for the remaining two phase-to-phase loops. Output FLT2PH is set to
the logical 1 if any of three phase-to-phase loops detects a fault during power swing.
If the input signal BLOCK is high during the fault period, output FLT2PH is reset to a logical 0.
Since delta quantities exist for a short period, the internal signal, FLTL12 is sealed-in as long as
either negative sequence current is above 12.0% IB or residual current is above 20.0% IB.
or
The above logic is also valid for the remaining two phase-to-phase loops. Output FLT2PH is set to
the logical 1 if any of three phase-to-phase loops detects a fault during power swing.
If the input signal BLOCK is high during the fault period, output FLT2PH is reset to a logical 0.
Output FLT3PH is set high and sealed-in if the rate of change in impedance angle is lower than 5.73
deg and voltage magnitude in all phases restore above 75.0% UB.
or
Output FLT3PH is set high and sealed-in if the rate of change in impedance angle is lower than 5.73
deg.
or
Detected three-phase fault activates all phase-to-phase loops for distance measurement i.e. output
STCND shows 56.
If the input signal BLOCK is high during the fault period, output FLT3PH is reset to a logical 0.
Code build up for the output STCND to release the measuring fault loops is as follows:
Also, outputs FLTL1, FLTL2 and FLTL3 are shown to indicate the faulty phases during power swing.
The logical diagram of the phase selection logic implemented in ZMBURPSB is depicted in Figure
256.
BLOCK
FLTL12
&
FLTL23
&
FLT2PH
FLTL31 1
&
FLTL1E
&
&
FLTL2E
& FLT1PH
& 1
FLTL3E
&
&
Bit to word
FLT3PH
b0
&
1 b1
STCND
b2
b3
b4
1 b5
1
FLTL1
1
FLTL2
1
FLTL3
1
IEC19000324 V1 EN-US
START
&
OpModePSU
STCND RELCND
T
63 F
IEC19000325 V1 EN-US
Figure 257: Logical diagram of a releasing logic for distance protection function
If the setting parameter OpModePSU is set to On and the output START (i.e. power swing is
detection) is high, RELCND indicates the faulty loop(s) information for the power system faults during
power swing and releases the measuring loops for faults.
If either the setting parameter OpModePSU is set to Off or the output START (no power swing
detection) is low, RELCND indicates 63, i.e. all six loops are released for distance measuring. It
means that no phase selection is performed inside the ZMBURPSB function. However, phase
selection is performed in ZMF(C)PDIS function to release the distance measuring loop for distance
measurement.
Power swing detection operate time (0.000-60.000) s ±0.2% or ±10 ms whichever is greater
Second swing reclaim operate time (0.000-60.000) s ±0.2% or ±20 ms whichever is greater
Minimum operate current, Ph-E (5-1000)% of IBase ±1.0% of Ir
8.14.2 Identification
SEMOD155890-2 v4
Automatic switch onto fault logic ZCVPSOF is a function that gives an instantaneous trip when
closing the breaker onto a fault. A dead-line detection check is provided to activate ZCVPSOF when
the line is de-energized.
Mho distance protections cannot operate for switch onto fault conditions when the phase voltages
are close to zero. An additional logic based on UI Level is used for this purpose.
ZCVPSOF is a complementary function to the distance protection function. It is enabled for operation
either by the closing command to the circuit breaker (normally closed auxiliary contact of the circuit
breaker) to the BC input or automatically by the dead-line detection. Once enabled, it remains active
for tSOTF duration after the enabling signal is reset. The protection function can be enabled for
tripping during the activated time by connecting the functions included in the terminal to the ZACC
input. Therefore, the start of the selected protection functions connected to ZACC during the enabled
condition results in an immediate TRIP output from the function.
IEC06000459 V3 EN-US
PID-3875-INPUTSIGNALS v11
PID-3875-OUTPUTSIGNALS v10
PID-3875-SETTINGS v11
The automatic switch onto fault logic ZCVPSOF can be activated externally (by the breaker-closed
input) or internally (automatically) with the dead-line detection using the UI level-based logic. When
the setting AutoInitMode is DLD disabled, ZCVPSOF is activated by an external binary input BC.
When the setting AutoInitMode is set to Voltage, Current or Current & Voltage modes, ZCVPSOF is
activated by the dead-line detection.
The activation from the dead-line detection function is released if the internal signal DeadLine from
the UILevel Detector function is activated at the same time as the inputs ZACC and START_DLYD
are not activated at least for the duration of tDLD. The internal signal DeadLine from the UILevel
Detector function is activated under any of the following conditions:
• If all three-phase currents are below the setting IPh< and the AutoInitMode setting is set to
Current
• If all three-phase voltages are below the setting UPh< and the AutoInitMode setting is set to
Voltage
• If all three-phase currents and voltages are below the settings IPh< and UPh< and the
AutoInitMode setting is set to Current & Voltage
Once the dead line drops off after energization or once BC drops off, the activated signal is extended
for the duration of tSOTF.
The internal signal SOTFUILevel is activated if the phase voltage is below the set UPh< and the
corresponding phase current is above the set IPh< for a time longer than the duration set by
tDuration.
To get the TRIP signal, one of the different operate modes must also be selected with the Mode
parameter:
• Mode = Impedance; TRIP is released if either the ZACC input (connected normally to a
nondirectional distance protection start zone) or the START_DLYD input is activated. If
START_DLD is activated, TRIP is released after a delay of tOperate.
• Mode = UILevel; TRIP is released if UILevel detector is activated
• Mode = UILvl&Imp; TRIP is released based either on the impedance-measured criteria or
UILevel detection
The measured phase voltages and currents are provided as service values.
BLOCK
15ms
BC TRIP
& t
ZACC tSOTF
tDLD t
START_DLYD ≥1
& t
≥1
tOperate
t
I3P
U3P
DeadLine
IPh< UILevel tDuration
Detector t
UPh<
AutoInitMode
&
Mode = Impedance
SOTFUILevel
& ≥1
Mode = UILevel
≥1
&
Mode = UILvl&Imp
IEC07000084 V3 EN-US
Figure 259: Simplified logic diagram for Automatic switch onto fault logic
M16043-1 v14
Time delay to operate for the switch (0.03-120.00) s ±0.2% or ±30 ms whichever is greater
onto fault function
Table continues on next page
8.15.2 Identification
SEMOD175682-2 v3
Power Swing Logic (PSLPSCH) provides possibility for selective tripping of faults on power lines
during system oscillations (power swings or pole slips), when the distance protection function should
normally be blocked. The complete logic consists of two different parts:
• Communication and tripping part: provides selective tripping on the basis of special distance
protection zones and a scheme communication logic, which are not blocked during the system
oscillations.
• Blocking part: blocks unwanted operation of instantaneous distance protection zone 1 for
oscillations, which are initiated by faults and their clearing on the adjacent power lines and other
primary elements.
PSLPSCH
BLOCK TRIP
STZMUR STZMURPS
STZMOR BLKZMUR
STPSD BLKZMOR
STDEF CS
STZMPSD
CACC
AR1P1
CSUR
CR
IEC07000026-3-en.vsd
IEC07000026 V3 EN-US
8.15.5 Signals
PID-3664-INPUTSIGNALS v7
PID-3664-OUTPUTSIGNALS v7
8.15.6 Settings
PID-3664-SETTINGS v6
Communication and tripping logic as used by the power swing distance protection zones is
schematically presented in figure 261.
STDEF
AR1P1 &
STPSD tCS
CS
BLOCK & t &
CSUR
BLKZMPS
tBlkTr &
tTrip t
t
CACC TRIP
>1
CR &
en06000236.vsd
IEC06000236 V1 EN-US
Figure 261: Simplified logic diagram – power swing communication and tripping logic
The complete logic remains blocked as long as there is a logical one on the BLOCK functional input
signal. Presence of the logical one on the STDEF functional input signal also blocks the logic as long
as this block is not released by the logical one on the AR1P1 functional input signal. The functional
output signal BLKZMPS remains logical one as long as the function is not blocked externally (BLOCK
is logical zero) and the earth-fault is detected on protected line (STDEF is logical one), which is
connected in three-phase mode (AR1P1 is logical zero). Timer tBlkTr prolongs the duration of this
blocking condition, if the measured impedance remains within the operate area of the Power Swing
Detection (ZMRPSB) function (STPSD input active). The BLKZMPS can be used to block the
operation of the power-swing zones.
Logical one on functional input CSUR, which is normally connected to the TRIP functional output of a
power swing carrier sending zone, activates functional output CS, if the function is not blocked by
one of the above conditions. It also activates the TRIP functional output.
Initiation of the CS functional output is possible only, if the STPSD input has been active longer than
the time delay set on the security timer tCS.
Simultaneous presence of the functional input signals PLTR_CRD and CR (local trip condition) also
activates the TRIP functional output, if the function is not blocked by one of the above conditions and
the STPSD signal has been present longer then the time delay set on the trip timer tTrip.
Figure 262 presents the logical circuits, which control the operation of the underreaching zone (zone
1) at power swings, caused by the faults and their clearance on the remote power lines.
&
BLKZMH
&
STZML tZL
STZMLL
BLOCK & t >1
&
STMZH tDZ
STZMPSD & t
>1
STPSD
&
-loop
en06000237.vsd
IEC06000237 V1 EN-US
Figure 262: Control of underreaching distance protection (Zone 1) at power swings caused by
the faults and their clearance on adjacent lines and other system elements
The logic is disabled by a logical one on functional input BLOCK. It can start only if the following
conditions are simultaneously fulfilled:
• STPSD functional input signal must be a logical zero. This means, that Power swing detection
(ZMRPSB) function must not detect power swinging over the protected power line.
• STZMPSD functional input must be a logical one. This means that the impedance must be
detected within the external boundary of ZMRPSB function.
• STZMOR functional input must be a logical one. This means that the fault must be detected by
the overreaching distance protection zone, for example zone 2.
The STZMURPS functional output, which can be used in complete terminal logic instead of a normal
distance protection zone 1, becomes active under the following conditions:
• If the STZMUR signal appears at the same time as the STZMOR or if it appears with a time
delay, which is shorter than the time delay set on timer tDZ.
• If the STZMUR signal appears after the STZMOR signal with a time delay longer than the delay
set on the tDZ timer, and remains active longer than the time delay set on the tZL timer.
The BLKZMOR functional output signal can be used to block the operation of the higher distance
protection zone, if the fault has moved into the zone 1 operate area after tDZ time delay.
SEMOD171935-5 v5
8.16.1 Identification
SEMOD158949-2 v4
8.16.2 Functionality
SEMOD143246-17 v7
Sudden events in an electric power system such as large changes in load, fault occurrence or fault
clearance, can cause power oscillations referred to as power swings. In a non-recoverable situation,
the power swings become so severe that the synchronism is lost, a condition referred to as pole
slipping. The main purpose of the pole slip protection (PSPPPAM) is to detect, evaluate, and take the
required action for pole slipping occurrences in the power system.
PSPPPAM
I3P* TRIP
U3P* TRIP1
BLOCK TRIP2
BLKGEN START
BLKMOTOR ZONE1
EXTZONE1 ZONE2
GEN
MOTOR
SFREQ
SLIPZOHM
SLIPZPER
UCOS
UCOSPER
IEC10000045-1-en.vsd
IEC10000045 V1 EN-US
8.16.4 Signals
PID-3526-INPUTSIGNALS v3
PID-3526-OUTPUTSIGNALS v3
8.16.5 Settings
PID-3526-SETTINGS v3
If the generator is faster than the power system, the rotor movement in the impedance and voltage
diagram is from right to left and generating is signaled. If the generator is slower than the power
system, the rotor movement is from left to right and motoring is signaled (the power system drives
the generator as if it were a motor).
The movements in the impedance plane can be seen in Figure 264. The transient behavior is
described by the transient EMF's EA and EB, and by X'd, XT and the transient system impedance ZS.
Zone 1 Zone 2
EB X’d XT XS EA
IED
B A
jX
XS
Pole slip
impedance XT
d Apparent generator
movement impedance R
X’d
IEC06000437_2_en.vsd
IEC06000437 V2 EN-US
where:
X'd = transient reactance of the generator
• the minimum current exceeds 0.10 IN (IN is IBase parameter set under general setting).
• the maximum voltage falls below 0.92 UBase
• the voltage Ucosφ (the voltage in phase with the generator current) has an angular velocity of
0.2...8 Hz and
• the corresponding direction is not blocked.
en07000004.vsd
IEC07000004 V1 EN-US
Figure 265: Different generator quantities as function of the angle between the equivalent
generators
An alarm is given when movement of the rotor is detected and the rotor angle exceeds the angle set
for 'WarnAngle'.
When the impedance crosses the slip line between ZB and ZC it counts as being in zone 1 and
between ZC and ZA in zone 2. The entire distance ZA-ZB becomes zone 1 when signal EXTZONE1
is high (external device detects the direction of the centre of slipping).
After the first slip, the signals ZONE1 or ZONE2 and – depending on the direction of slip - either GEN
or MOTOR are issued.
Every time pole slipping is detected, the impedance of the point where the slip line is crossed and the
instantaneous slip frequency are displayed as measurements.
Further slips are only detected, if they are in the same direction and if the rate of rotor movement has
reduced in relation to the preceding slip or the slip line is crossed in the opposite direction outside
ZA-ZB. A further slip in the opposite direction within ZA-ZB resets all the signals and is then signalled
itself as a first slip.
The TRIP1 tripping command and signal are generated after N1 slips in zone 1, providing the rotor
angle is less than TripAngle. The TRIP2 signal is generated after N2 slips in zone 2, providing the
rotor angle is less than TripAngle.
START
AND
0.2 Slip.Freq. 8 Hz
startAngle
ZONE1
AND
Z cross line ZC - ZB
ZONE2
AND
Z cross line ZA - ZC
Counter
a
ab
N1Limit b TRIP1
AND
tripAngle OR
TRIP
Counter
a
ab
N2Limit b TRIP2
AND
IEC07000005.vsd
IEC07000005 V2 EN-US
Figure 266: Simplified logic diagram for pole slip protection PSPPPAM
GUID-88E02516-1BFE-4075-BEEB-027484814697 v2
8.17.1 Identification
GUID-BF2F1533-BA39-48F0-A55C-0B13A393F780 v2
<
The out-of-step protection (OOSPPAM ) function in the IED can be used for both generator protection
and as well for line protection applications.
The main purpose of the OOSPPAM function is to detect, evaluate, and take the required action
during pole slipping occurrences in the power system.
The OOSPPAM function detects pole slip conditions and trips the generator as fast as possible, after
the first pole-slip if the center of oscillation is found to be in zone 1, which normally includes the
generator and its step-up power transformer. If the center of oscillation is found to be further out in
the power system, in zone 2, more than one pole-slip is usually allowed before the generator-
transformer unit is disconnected. A parameter setting is available to take into account the circuit
breaker opening time. If there are several out-of-step relays in the power system, then the one which
finds the center of oscillation in its zone 1 should operate first.
Two current channels I3P1 and I3P2 are available in OOSPPAM function to allow the direct
connection of two groups of three-phase currents; that may be needed for very powerful generators,
with stator windings split into two groups per phase, when each group is equipped with current
transformers. The protection function performs a simple summation of the currents of the two
channels I3P1 and I3P2.
OOSPPAM
I3P1* TRIP
I3P2* TRIPZ1
U3P* TRIPZ2
BLOCK START
BLKGEN GENMODE
BLKMOT MOTMODE
EXTZ1 R
X
SLIPFREQ
ROTORANG
UCOSPHI
IEC12000188-3-en.vsd
IEC12000188 V3 EN-US
8.17.4 Signals
PID-3539-INPUTSIGNALS v10
PID-3539-OUTPUTSIGNALS v10
8.17.5 Settings
PID-3539-SETTINGS v10
General
Under balanced and stable conditions, a generator operates with a constant rotor angle (power
angle), delivering active electrical power to the power system, which is approximately equal to the
input mechanical power on the generator axis.The currents and voltages are constant and stable. An
out-of-step condition is characterized by periodic changes in the rotor angle, that leads to a wild flow
of the synchronizing power; so there are also periodic changes of rotational speed, currents and
voltages. When displayed in the complex impedance plane, these changes are characterized by a
cyclic change in the complex load impedance Z(R, X) as measured at the terminals of the generator,
or at the location of the instrument transformers of a power line connecting two power subsystems.
This is shown in Figure 268.
1.5 ← trajectory
of Z(R, X)
to the 3rd
The 2nd pole-slip
Imaginary part (X) of Z in Ohms
-1
-1.5 -1 -0.5 0 0.5 1 1.5
Real part (R) of Z in Ohms
IEC10000109-1-en.vsd
IEC10000109 V1 EN-US
Figure 268: Loci of the complex impedance Z(R, X) for a typical case of generator losing step
after a short circuit that was not cleared fast enough
Under typical, normal load conditions, when the protected generator supplies the active and the
reactive power to the power system, the complex impedance Z(R, X) is in the 1st quadrant, point 0 in
Figure 268. One can see that under a three-phase fault conditions, the centre of oscillation is at the
point of fault, point 1, which is logical, as all three voltages are zero or near zero at that point. Under
the fault conditions the generator accelerated and when the fault was finally cleared, the complex
impedance Z(R, X) jumped to the point 2. By that time, the generator has already lost its step, Z(R,
X) continues its way from the right-hand side to the left-hand side, and the 1st pole-slip cannot be
avoided. If the generator is not immediately disconnected, it will continue pole-slipping — see Figure
268, where two pole-slips (two pole-slip cycles) are shown. Under out-of-step conditions, the centre
of oscillation is where the locus of the complex impedance Z(R, X) crosses the (impedance) line
connecting the points SE (Sending End), and RE (Receiving End). The point on the SE – RE line
where the trajectory of Z(R, X) crosses the impedance line can change with time and is mainly a
function of the internal induced voltages at both ends of the equivalent two-machine system, that is,
at points SE and RE.
Rotor (power) angle δ can be thought of as the angle between the two lines, connecting point 0 in
Figure 268, that is, Z(R, X) under normal load, with the points SE and RE, respectively. These two
lines are not shown in Figure 268. Normal values of the power angle, that is, under stable, steady-
state, load conditions, are from 30 to 60 electrical degrees. It can be observed in Figure 269 that the
angle reaches 180 degrees when the complex impedance Z(R, X) crosses the impedance line SE –
RE. It then changes the sign, and continues from -180 degrees to 0 degrees, and so on. Figure 269
shows the rotor (power) angle and the magnitude of Z(R, X) against time for the case from Figure
268.
4
|Z| in Ohms
rotor (power)
3 normal angle in rad
angle
Impe dance Z in Ohm and rotor a ngle in radian ®
load
Z(R, X) unde r fa ult lies |Z|
2
on the impe dance line
or nea r (for 3-ph faults )
1
0
0
fault 500 ms
-1 fa ult
occ urrs
Unde r 3-pha s e fa ult
condition rotor a ngle 3
-2
of a pp. ±180 de gre e s
is m e a s ure d ...
2
-3 Z(R,X) cros s e d
1 1 the im pe da nce line , Z-line ,
conne cting points S E - RE
-4
0 200 400 600 800 1000 1200 1400
Time in millis econds ®
IEC10000110-2-en.vsd
IEC10000110 V2 EN-US
Figure 269: Rotor (power) angle and magnitude of the complex impedance Z(R, X) against the
time
In order to be able to fully understand the principles of OOSPPAM, a stable case, that is, a case
where the disturbance does not make a generator to go out-of-step, must be shown.
1
SE RE
G X [Ohm]
0.8 Z(R,X) 20 ms
fault
relay after line out
- - - RE - - -
0.6 - - --
-- ----------- - pre-fault
Imaginary part (X) of Z in Ohms → - ---- - - 4 -
zone 2 -
-- -- ---
- - Z(R,X)
0.4 - -- - --- 2 -
- -
- --- -1 5
- --- fault→
- -- -
0.2 X-line → ^ -^ ^ ^ ^ ---^ ^ 3 -- -
- -
- ^ ^ ^ ^ ^ ^ --^- ^ ^ -
- -- Z-line→ -- ^ -^ 0
-- --
- -- -- - 6
0 - -- - - -
- -
- -
- -
limit of -- - R
- -- relay lens → --- -
-- -
-0.2 reach - -- 110° ---- -
zone 1- - --- -
-- -
-
--- -
- --- --- -
-0.4 -- --- ------ --
-- ------ -
- - - - -
-0.6 SE - - -
0 → pre-fault Z(R, X)
this circle forms 3 → Z(R, X) under fault
-0.8 the right-hand side 5 → Z 20 ms after line out
edge of the lens 6 → pow er line reclosed
-1
-1 -0.5 0 0.5 1 1.5
Real part (R) of Z in Ohms → IEC10000111-1-en.vsd
IEC10000111 V1 EN-US
Figure 270: A stable case where the disturbance does not make the generator to go out-of-step
It shall be observed that for a stable case, as shown in Figure 270, where the disturbance does not
cause the generator to lose step, the complex impedance Z(R, X) exits the lens characteristic on the
same side (point 4) it entered it (point 2), and never re-enters the lens. In a stable case, where the
protected generator remains in synchronism, the complex impedance returns to quadrant 1, and,
after the oscillations fade, it returns to the initial normal load position (point 0), or near.
A precondition in order to be able to construct a suitable lens characteristic is that the power system
in which OOSPPAM is installed, is modeled as a two-machine equivalent system, or as a single
machine – infinite bus equivalent power system. Then the impedances from the position of
OOSPPAM in the direction of the normal load flow (that is from the measurement point to the remote
system) can be taken as forward. The lens characteristic, as shown in Figure268 and Figure270, is
obtained so that two equal in size but differently offset Mho characteristics are set to overlap. The
resultant lens characteristic is the loci of complex impedance Z(R, X) for which the rotor (power)
angle is constant, for example 110 degrees or 120 degrees; if the rotor (power) angle approaches
this value, then there is a high risk to have an out of step condition. The limit-of- reach circle is
constructed automatically by the algorithm; it is about 10% wider than the the circle that has the line
SE-RE as diameter (that is the out-of-step characteristic which corresponds to the rotor (power)
angle of 90 degrees). Figure 271 illustrates construction of the lens characteristic for a power system.
X
Position of the OOS
- - - RE- - -
0.6 - - --- - relay is the origin of
- - -- --- - the R - X plane
- -- - -- -
- --- Ze -- -
- Zone 2 -- -- -
0.4 X-line - - - -
--
Imaginary part (X) of Z in Ohms
--
- - - -
determined -- Zline
-
--
- - -
-- -
by the → ^ ^- ^ --- -- -
0.2 ^ ^ ^- ^ -
setting - - ^ ^ ^ ^ -
--- ^ ^ ^ --- ^
ReachZ1 - -- ^ ^ ^-
--- Ztr
- -- -- - R
0 - Zone 1 -- --
- -
-- relay -
- -- 120° -- Z(R,X) -
- -- --- -
-- ← Z-line -
-0.2 - -- Zgen -- -
- -- --- -
limit-of-reach → - -- -- -
-- -- ← Lens is- the locus
circle depends on -
- -- ---- of constant
- rotor (power)
-0.4 --
the position of the - -- --- - e.g. 120°.
- - --- - -- angle,-
points SE and RE - - - - - - - - -Lens' width determined
SE
-0.6 by the setting StartAngle
ReverseZ
ReverseZ(ReverseR, ReverseX)) ForwardZ(ForwardR, ForwardX)
SE RE
IEC10000113-2-en.vsd
IEC10000113 V2 EN-US
The out-of-step relay, as in Figure 272 looks into the system and the impedances in that direction are
forward impedances:
Resistances are much smaller than reactances, but in general can not be neglected. The ratio
(ForwardX + ReverseX) / (ForwardR + ReverseR) determines the inclination of the Z-line, connecting
the point SE (Sending End) and RE (Receiving End), and is typically approximately 85 degrees.
While the length of the Z-line depends on the values of ForwardX, ReverseX, ForwardR, and
ReverseR, the width of the lens is a function of the setting StartAngle .The lens is broader for smaller
values of the StartAngle , and becomes a circle for StartAngle = 90 degrees.
When the complex impedance Z(R, X) enters the lens, pole slipping is imminent, and a start signal is
issued. The angle recommended to form the lens is 110 or 120 degrees, because it is this rotor
(power) angle where problems with dynamic stability usually begin. Rotor (power) angle 120 degrees
is sometimes called “the angle of no return” because if this angle is reached under generator power
swings, the generator is most likely to lose step.
An out-of-step condition is characterized by periodic changes of the rotor angle, that leads to a wild
flow of the synchronizing power; so there are also periodic changes of rotational speed, currents and
voltages. When displayed in the complex impedance plane, these changes are characterized by a
cyclic change in the complex load impedance Z(R, X) as measured at the terminals of the generator,
or at the location of the instrument transformers of a power line connecting two power sub-systems.
This was shown in Figure 268. When a synchronous machine is out-of-step, pole-slips occur. To
recognize a pole-slip, the complex impedance Z(R,X) must traverse the lens from right to left in case
of a generator and in the opposite direction in case of a motor. Another requirement is that the travel
across the lens takes no less than a specific minimum traverse time, typically 40...60 milliseconds.
The above timing is used to discriminate a fault from an out-of-step condition. In Figure 268, some
important points on the trajectory of Z(R, X) are designated. Point 0: the pre-fault, normal load Z(R,
X). Point 1: impedance Z under a three-phase fault with low fault resistance: Z lies practically on, or
very near, the Z-line. Transition of the measured Z from point 0 to point 1 takes app. 20 ms, due to
Fourier filters. Point 2: Z immediately after the fault has been cleared. Transition of the measured Z
from point 1 to point 2 takes approximately 20 ms, due to Fourier filters. The complex impedance
then travels in the direction from the right to the left, and exits the lens on the opposite side. When
the complex impedance exits the lens on the side opposite to its entrance, the 1st pole-slip has
already occurred and more pole-slips can be expected if the generator is not disconnected. Figure
268 shows two pole-slips. Figures like Figure 268 and Figure 270 are always possible to draw by
means of the analog output data from the pole-slip function, and are of great help with eventual
investigations of the performance of the out-of-step function.
A pole-slip may be detected if it has a slip frequency lower than a maximum value fsMax. The
specific value of fsMax depends on the setting (parameter) StartAngle (which determines the width of
the lens characteristic). A parameter in this calculation routine is the value of the minimum traverse
time, traverseTimeMin. The minimum traverse time is the minimum time that the travel of the
complex impedance Z(R, X) through the lens, from one side to the other, must last in order to
recognize that a pole-slip has occurred. The value of the internal constant traverseTimeMin is a
function of the set StartAngle.For values of StartAngle <= 110°, traverseTimeMin = 50 ms. For values
StartAngle > 110°, traverseTimeMin = 40 ms. The expression which relates the maximum slip
frequency fsMax and the traverseTimeMin is as follows:
The minimum value of fsMax is 6.994 Hz. When StartAngle = 110 degrees, fsMax = 7.777 Hz. This
implies, that the default StartAngle = 110 degrees covers 90% of cases as, the typical final slip
frequency is between 2 - 5Hz. In practice, however, before the slip frequency, for example 7.777 Hz,
is reached, at least three pole-slips have occurred. In other words, if we consider a linear increase of
frequency from 50 Hz to 57.777 Hz, at least three pole-slips will occur (in fact: (57.777 - 50) / 2 =
3.889). The exact instantaneous slip-frequency expressed in Hz (corresponding to number of pole
slips per second) is difficult to calculate. The easiest and most exact method is to measure time
between two successive pole slips. This means that, the instantaneous slip-frequency is measured
only after the second pole-slip, if the protected machine is not already disconnected after the first
pole-slip. The measured value of slipsPerSecond (SLIPFREQ) is equal to the average slip-frequency
of the machine between the last two successive pole-slips.
Although out-of-step events are relatively rare, the out-of-step protection should take care of the
circuit breaker health. The electromechanical stress to which the breaker is exposed shall be
minimized. The maximum currents flowing under out-of-step conditions can be even greater that
those for a three-phase short circuit on generator terminals; see Figure 274. The currents flowing are
highest at rotor angle 180 degrees, and smallest at 0 degrees, where relatively small currents flow.
To open the circuit breaker at 180 degrees, when not only the currents are highest, but the two
internal (that is, induced) voltages at both ends are in opposition, could be fatal for the circuit breaker.
There are two methods available in order to minimize the stress; the second method is more
advanced than the first one.
Figure 274 for tBreaker = 0.060 s. The point in time when the breaker opening process must be
initiated is estimated by solving on-line the so called “synchronizer” differential equation. Note that if
tBreaker is left on the initial (default) value, which is zero (0), then the alternative setting TripAngle
decides when the trip command is given. If specified tBreaker > 0, for example tBreaker = 0.040
second, then automatically, the TripAngle is ignored and the second, more exact method applied.
X[Ohm]
0.6 trip RE - Receiving End (infinite bus)
region
loci of Z(R, X)
0.4 3
Imaginary part (X) of Z in Ohms →
no trip
region 1
here rotor here
0.2 2
angle rotor angle
is -90° no trip is +90°
rotor angle
region
= ±180°
0 no trip
relay
region R[Ohm]
inside ← Z - line connects
points SE & RE
-0.2 circle
← this circle
is loci of
outside the
the rotor
-0.4 circle is the trip
angle = 90°
region for
TripAngle <= 90° SE - Sending End (generator)
Figure 273: The imaginary offset Mho circle represents loci of the impedance Z(R, X) for which
the rotor angle is 90 degrees
35
very high currents due
Current in kA, trip command to CB, rotor angle in rad →
← rotor angle
0
angle towards 0°
-5
0 200 400 600 800 1000 1200
Time in milliseconds →
IEC10000115-1-en.vsd
IEC10000115 V1 EN-US
Figure 274: Trip initiation when the break-time of the circuit breaker is known
At every execution of the function the following is calculated: active power P, reactive power Q, rotor
angle ROTORANG, quantity UCOSPHI, the positive-sequence current CURRENT and voltage
VOLTAGE. All other quantities, that can as well be read as outputs, are only calculated if the Z(R, X)
enters the limit of reach zone, which is a circle in the complex (R – X) plane. When the complex
impedance Z(R, X) enters the limit-of-reach region, the algorithm:
• determines in which direction the impedance Z moves, that is, the direction the lens is traversed
• measures the time taken to traverse the lens from one side to the other one
If the traverse time is more than the limit 40 or 50 ms, a pole-slip is declared. If the complex
impedance Z(R, X) exits the lens on the same side it entered, then it is a stable case and the
protected machine is still in synchronism. If a pole-slip has been detected, then it is determined in
which zone the centre of oscillation is located. If the number of actual pole-slips exceeds the
maximum number of allowed pole-slips in either of the zones, a trip command is issued taking care of
the circuit breaker safety.
R R
UPSRE Calculation of X X
UPSIM R and X parts
of the complex Z(R,X)
UPSMAG
positive-
IPSRE
sequence Z(R,X) NO
IPSIM
impedance within limit of Return
Z(R, X) reach?
YES UCOSPHI
Z(R,X) ROTORANG
within lens NO
Function alert
characteristic?
SLIPFREQ
YES GENMODE
Z(R,X) MOTMODE
LEFT Z(R,X) RIGHT NO
exited lens
entered lens
on the left- hand
from?
Motor losing Generator losing side?
step ? step ?
YES
Was
traverse time NO
more than
Calculation of 50 ms?
P
positive- sequence YES (pole- slip!)
active power P, Q TRIP
>= 1
reactive power Q, Number
ZONE 2 NO
rotor angle UCOSPHI
of pole- slips
ROTORANG exceeded in TRIPZ1
a zone? Open
and
ROTORANG circuit
UCOSPHI ZONE 1 TRIPZ2
breaker
safely
IEC10000116-3-en.vsd
IEC10000116 V3 EN-US
8.18.2 Identification
SEMOD151937-2 v2
The Phase preference logic function PPLPHIZ is intended to be used in isolated or high impedance
earthed networks where there is a requirement to operate on only one of the faulty lines during a
cross-country fault. It can be used without preference to restrain operation for single earth faults with
a delayed zero-sequence current release.
For cross-country faults, the logic selects either the leading or lagging phase-earth loop for
measurement. It initiates operation on the preferred phase based on the selected phase preference
scheme. A number of different phase preference schemes are available.
PPLPHIZ provides an additional phase selection criteria, namely under voltage criteria, suitable for
phase selection during cross-country faults. In radial networks, where there is no fault current in the
phase with the external fault, current or impedance based phase selection methods become
ineffective. Hence, only voltage can be used for phase selection. The phase selection result will be
the same for all bays on a bus since the voltage is the same, which is an important condition for
operating with phase preference.
In meshed and stronger networks, it may be difficult to find appropriate under-voltage settings for
phase selection. Therefore an automatic phase selection logic is made available which works in
parallel with a set under-voltage criterion in order to detect the two faulty phases even for complex
networks. If for any reason the PPLPHIZ is unable to detect the two faulty phases, then after a short
time delay all three phase-to-earth loops of the distance protection will be released for operation. The
final result might be that both faulty feeders are disconnected. In other words, protection operation is
prioritized over strict adherence to preference.
PPLPHIZ
I3P* START
U3P* ZREL
BLOCK
RELL1N
RELL2N
RELL3N
STCND
IEC07000029-2-en.vsd
IEC07000029 V2 EN-US
PID-7504-INPUTSIGNALS v1
PID-7504-OUTPUTSIGNALS v1
PID-7504-SETTINGS v1
PPLPHIZ is connected between the Distance protection zones ZMQPDIS and ZMQAPDIS and
Phase selection FDPSPDIS, see Figure 277. Depending on the setting, the original phase selection
will be supplemented with an additional voltage based phase selection inside PPLPHIZ and then
filtered through the phase preference logic in order to release only the preferred phases of the
distance zones.
ZMQAPDIS
FDPSPDIS
W2_CT_B_I3P I3P* TRIP
I3P* TRIP
W2_VT_B_U3P U3P* TRL1
U3P* START FALSE BLOCK TRL2
BLOCK STFWL1 PHS_L1 W2_FSD1-BLKZ VTSZ TRL3
DIRCND STFWL2 PHS_L2 FALSE BLKTR START
STFWL3 PHS_L3 STCND STL1
STFWPE
DIRCND STL2
STRVL1
STL3
STRVL2
STND
STRVL3
STRVPE
STNDL1 ZMQPDIS
STNDL2 I3P* TRIP
W2_CT_B_I3P
STNDL3 U3P* TRL1
W2_VT_B_U3P
STNDPE FALSE BLOCK TRL2
STFW1PH VTSZ TRL3
W2_FSD1-BLKZ
STFW2PH BLKTR START
FALSE
STFW3PH
STCND STL1
STPE DIRCND STL2
STPP STL3
STCNDZ STND
STCNDLE
PPLPHIZ
W2_CT_B_I3P I3P* START
W2_VT_B_U3P U3P* ZREL
FALSE BLOCK
FALSE RELL1N
FALSE RELL2N
FALSE RELL3N
STCND
IEC06000552-3-en.vsd
IEC06000552 V3 EN-US
The fundamental start criterion for a cross-country fault is a continuous residual current (3I0) above
setting level IN>.
Transient residual currents associated with single phase fault inception are not allowed to release the
distance protection. This is taken care of by a time-on-delay tIN, which should be set longer than the
expected duration of the transient.
If a single phase fault remains for some time, it is possible to bypass the tIN time delay, since the
next fault event is expected to be a cross-country fault. The criterion for this bypass is that the
residual voltage is greater than setting level 3U0> for a time longer than setting tUN. The time-off-
delay tOffUN is used to make sure that the bypass is steady during the cross-country fault.
The time delay for residual current start is also bypassed as soon as two low voltages are detected
during the cross-country fault (startUPP). See Figure 278 for a simplified diagram showing the
residual current start logic.
startUPP
OR
tUN tOffUN
3U0 > 3U0> t t
(Non delayed IN start)
AND
tIN startIN
OR
3I0 > IN> t
IEC16000018-1-en.vsdx
IEC16000018 V2 EN-US
During a cross-country fault, the phase with an external fault typically does not carry any fault
current, which will make it difficult for a conventional phase selection function to detect the fault.
Therefore, PPLPHIZ function provides an additional phase selection based on voltage.
PPLPHIZ is designed to detect two-phase faults based on under-voltage in two phases or between
two phases.
AND startUL1L2
OR
AND startUL2L3
OR
startUL1
OR
AND startUL3L1
ULxLy < UPP< OR
startUL2
L1L2 OR
L2L3
startUL3
L3L1 OR
startIN
UL1
UL2 AND
UL3 Automatic
UL1L2 phase
AND
UL2L3 detection
UL3L1
AND
OpAutoDetect
IEC16000019-1-en.vsdx
IEC16000019 V2 EN-US
startUL1
AND
startUL2
AND OR
startUL3
AND
OperMode = No Filter
OR
AND
OperMode = NoPref
OR
RELL1N startL1
OR
OR
RELL2N startL2
OR
OR
RELL3N startL3
OR
OR
L1N
L2N
L3N
STCND Integer L1L2 zrelL1L2
to
Boolean L2L3 zrelL2L3
L3L1 zrelL3L1
IEC16000105-1-en.vsdx
IEC16000105 V2 EN-US
The different operating modes (selected with OperMode setting) determine how the internal status is
used to release the phases of the connected distance protection.
This setting shall be set in accordance with used phase preference scheme in the protected network.
It is of uttermost importance that all distance relays installed in this network has the same setting
value for this parameter.
No Filter mode is equivalent to connecting the phase selection directly to the distance protection.
startL1 zrelL1
startL2 zrelL2
startL3 zrelL3
IEC16000106-1-en.vsdx
IEC16000106 V1 EN-US
startL1
zrelL1
AND
startL2
zrelL2
AND
startL3
zrelL3
AND
startIN
IEC16000107-1-en.vsdx
IEC16000107 V1 EN-US
A logic is also included to handle the special case where only one start (startL1-3) is present.
The internal under-voltage phase selection always issues a release in at least two phases, but the
inputs RELL1-3N can be activated with some time apart. If no measures are taken, the phase
activated first will pass through the preference scheme and release the distance protection. Since it
could a be non-preferred phase, a time delay of 40 ms is provided to release if only one phase is
detected, in order to wait for the second phase to be activated. If no second phase is detected within
40 ms, the single phase is released without preference.
• All three phases are involved in the fault and a cyclic scheme is selected
• No faulty phase can be detected due to an insufficient voltage drop
In both cases, no release signals come from the phase preference scheme. For these cases, an
additional logic is provided that releases all three phase-to-earth loops if there is no output from the
preference scheme after 40 ms from the activation of the residual current start.
Hence, if there is a residual current start, it is guaranteed that the distance protection is released in at
least one phase. This is valid for all phase preference schemes.
Preference
OperMode Scheme
Scheme
startL1 prefL1
INL1 OUTL1
startL2 prefL2
INL2 OUTL2
startL3 prefL3
INL3 OUTL3
More than
one true stIN
AND
startIN
40 ms
stIN40ms
t
IEC16000023-1-en.vsdx
IEC16000023 V2 EN-US
prefL1
OR zrelL1
AND
prefL2
OR zrelL2
AND
prefL3
OR zrelL3
AND
30 ms
OR t
AND
stIN40ms
stIN OR
IEC16000024-1-en.vsdx
IEC16000024 V2 EN-US
Figure 284: Logic to release the preferred phase towards distance protection
Table 264 shows the preferred phase for each detected cross-country fault type and operating mode
(OperMode).
Table 264: Preferred phase for each cross-country fault type and operating mode
All loop releasing signals are gathered in the binary coded integer output ZREL. The value of ZREL
can be calculated according to Equation 137.
The BLOCK input will only block the enabling signals for phase-to-earth loops,
phase-to-phase loops are still released. The PPLPHIZ is designed not to have any
influence on the phase-to-phase loops of the distance protection.
startU
AND
zrelL1
AND
zrelL2
AND L1N
zrelL3 L2N
AND L3N
Bool to ZREL
zrelL1L2 L1L2 Integer
zrelL2L3 L2L3
BLOCK zrelL3L1 L3L1
IEC16000108-1-en.vsdx
IEC16000108 V1 EN-US
Independent time delay for residual (0.000 - 60.000) s ±0.2% or ±25 ms whichever is greater
voltage at 0.8 x Uset to 1.2 x Uset, tUN
Independent dropoff-delay for residual (0.000 - 60.000) s ±0.2% or ±25 ms whichever is greater
voltage at 1.2 x Uset to 0.8 x Uset,
tOffUN
Operating mode No Filter, NoPref
Cyclic: 1231c, 1321c
Acyclic: 123a, 132a, 213a, 231a,
312a, 321a
8.19.2 Identification
GUID-850E4134-E912-45EC-981E-E1A2C12A91A8 v1
The Phase preference logic function (PPL2PHIZ) is used with the high speed distance protection,
quad and mho characteristic (ZMFPDIS). It is intended to be used in isolated or high impedance
earthed networks where there is a requirement to operate on only one of the faulty lines during a
cross-country fault. It can be used without preference to restrain operation for single earth faults with
a delayed zero-sequence current release.
For cross-country faults, the logic selects either the leading or lagging phase-earth loop for
measurement. It initiates operation on the preferred phase based on the selected phase preference
scheme. A number of different phase preference schemes are available.
PPL2PHIZ provides an additional phase selection criteria, namely under voltage criteria, suitable for
phase selection during cross-country faults. In radial networks, where there is no fault current in the
phase with the external fault, current or impedance based phase selection methods become
ineffective. Hence, only voltage can be used for phase selection. The phase selection result will be
the same for all bays on a bus since the voltage is the same, which is an important condition for
operating with phase preference.
In meshed and stronger networks, it may be difficult to find appropriate under-voltage settings for
phase selection. Therefore an automatic phase selection logic is made available which works in
parallel with a set under-voltage criterion in order to detect the two faulty phases even for complex
networks. If for any reason the PPL2PHIZ is unable to detect the two faulty phases, then after a short
time delay all three phase-to-earth loops of the distance protection will be released for operation. The
final result might be that both faulty feeders are disconnected. In other words, protection operation is
prioritized over strict adherence to preference.
PPL2PHIZ
I3P* START
U3P* ZREL
BLOCK
RELL1N
RELL2N
RELL3N
IEC16000016-1-en.vsdx
IEC16000016 V2 EN-US
8.19.5 Signals
PID-7505-INPUTSIGNALS v1
PID-7505-OUTPUTSIGNALS v1
8.19.6 Settings
PID-7505-SETTINGS v1
The PPL2PHIZ function releases the phase selection inside the distance protection, see Figure 287.
The phase selection inside the distance protection has to detect the fault before an
operation from the distance zones can be achieved, even when the distance
protection is released by PPL2PHIZ.
PPL2PHIZ ZMFPDIS
Phase
Phase selection
preference
Zone1
L1N relcndphs TRZ1
L1N bitwise enable
L2N AND
L2N
L3N Zone2
L3N Bool to ZREL bitwise
TRUE L1L2 Integer AND
enable
RELCNDZ1
TRUE L2L3
Zone3
TRUE L3L1 RELCNDZ2 bitwise
enable
AND
RELCNDZ3
Zone4
RELCNDZ4 bitwise
enable
TRZ4
AND
RELCNDZ5 Zone5
bitwise
enable
TRZ5
RELCNDZRV AND
ZoneRV
bitwise
enable
TRZRV
AND
IEC16000017-1-en.vsdx
IEC16000017 V1 EN-US
The fundamental start criterion for a cross-country fault is a continuous residual current (3I0) above
setting level IN>.
Transient residual currents associated with single phase fault inception are not allowed to release the
distance protection. This is taken care of by a time-on-delay tIN, which should be set longer than the
expected duration of the transient.
If a single phase fault remains for some time, it is possible to bypass the tIN time delay, since the
next fault event is expected to be a cross-country fault. The criterion for this bypass is that the
residual voltage is greater than setting level 3U0> for a time longer than setting tUN. The time-off-
delay tOffUN is used to make sure that the bypass is steady during the cross-country fault.
The time delay for residual current start is also bypassed as soon as two low voltages are detected
during the cross-country fault (startUPP). See Figure 288 for a simplified diagram showing the
residual current start logic.
startUPP
OR
tUN tOffUN
3U0 > 3U0> t t
(Non delayed IN start)
AND
tIN startIN
OR
3I0 > IN> t
IEC16000018-1-en.vsdx
IEC16000018 V2 EN-US
During a cross-country fault, the phase with an external fault typically does not carry any fault
current, which will make it difficult for a conventional distance phase selection function to detect the
fault. Therefore, PPL2PHIZ function provides an additional phase selection based on voltage.
PPL2PHIZ is designed to detect two-phase faults based on under-voltage in two phases or between
two phases.
AND startUL1L2
OR
AND startUL2L3
OR
startUL1
OR
AND startUL3L1
ULxLy < UPP< OR
startUL2
L1L2 OR
L2L3
startUL3
L3L1 OR
startIN
UL1
UL2 AND
UL3 Automatic
UL1L2 phase
AND
UL2L3 detection
UL3L1
AND
OpAutoDetect
IEC16000019-1-en.vsdx
IEC16000019 V2 EN-US
startUL1
AND
startUL2
startUPP
AND OR
startUL3
AND
OperMode = No Filter
OR
OperMode = NoPref
startL1
RELL1N OR
startL2
RELL2N OR
startL3
RELL3N OR
IEC16000020-1-en.vsdx
IEC16000020 V1 EN-US
The different operating modes (selected with OperMode setting) determine how the internal status is
used to release the phases of the connected distance protection.
This setting shall be set in accordance with used phase preference scheme in the protected network.
It is of uttermost importance that all distance relays installed in this network has the same setting
value for this parameter.
TRUE zrelL1
TRUE zrelL2
TRUE zrelL3
IEC16000021-1-en.vsdx
IEC16000021 V1 EN-US
TRUE
zrelL1
AND
TRUE
zrelL2
AND
TRUE
zrelL3
AND
startIN
IEC16000022-1-en.vsdx
IEC16000022 V1 EN-US
A logic is also included to handle the special case where only one start (startL1-3) is present.
The internal under-voltage phase selection always issues a release in at least two phases, but the
inputs RELL1-3N can be activated with some time apart. If no measures are taken, the phase
activated first will pass through the preference scheme and release the distance protection. Since it
could a be non-preferred phase, a time delay of 40 ms is provided to release if only one phase is
detected, in order to wait for the second phase to be activated. If no second phase is detected within
40 ms, the single phase is released without preference.
• All three phases are involved in the fault and a cyclic scheme is selected
• No faulty phase can be detected due to an insufficient voltage drop
In both cases, no release signals come from the phase preference scheme. For these cases, an
additional logic is provided that releases all three phase-to-earth loops if there is no output from the
preference scheme after 40 ms from the activation of the residual current start.
Hence, if there is a residual current start, it is guaranteed that the distance protection is released in at
least one phase. This is valid for all phase preference schemes.
Preference
OperMode Scheme
Scheme
startL1 prefL1
INL1 OUTL1
startL2 prefL2
INL2 OUTL2
startL3 prefL3
INL3 OUTL3
More than
one true stIN
AND
startIN
40 ms
stIN40ms
t
IEC16000023-1-en.vsdx
IEC16000023 V2 EN-US
prefL1
OR zrelL1
AND
prefL2
OR zrelL2
AND
prefL3
OR zrelL3
AND
30 ms
OR t
AND
stIN40ms
stIN OR
IEC16000024-1-en.vsdx
IEC16000024 V2 EN-US
Figure 294: Logic to release the preferred phase towards distance protection
Table 270 shows the preferred phase for each detected cross-country fault type and operating mode
(OperMode).
Table 270: Preferred phase for each cross-country fault type and operating mode
All loop releasing signals are gathered in the binary coded integer output ZREL. The value of ZREL
can be calculated according to Equation 138.
The phase-to-phase loops are always released, that is, the value of ZREL will
always be at least 8+16+32=56. For example:
If only L1N is active, then the value is 1+56=57
If start L1N and L3N are active, then the value is 1+4+56=61
The BLOCK input will only block the enabling signals for phase-to-earth loops,
phase-to-phase loops are still released. The PPL2PHIZ is designed not to have any
influence on the phase-to-phase loops of the distance protection.
startU
AND
zrelL1
AND
zrelL2
AND L1N
zrelL3 L2N
AND L3N
Bool to ZREL
TRUE L1L2 Integer
TRUE L2L3
BLOCK TRUE L3L1
IEC16000025-1-en.vsdx
IEC16000025 V1 EN-US
Independent dropoff-delay for residual (0.000 - 60.000) s ±0.2% or ±25 ms whichever is greater
voltage at 1.2 to 0.8 x Uset, tOffUN
Z
S00346 V2 EN-US
The under impedance protection (ZGVPDIS) function is a three zone full scheme impedance
protection using offset mho characteristics for detecting faults in the generator, generator-transformer
and transmission system. The three zones have fully independent measuring loops and settings. The
functionality also comprises an under voltage seal-in feature to ensure issuing of a trip even if the
current transformer goes into saturation and, in addition, the positive-sequence-based load
encroachment feature for the second and the third impedance zone. Built-in compensation for the
unit step-up transformer vector group connection is available.
ZGVPDIS
I3P* TRIP
U3P* TRZ1
BLOCK TRZ2
BLKZ TRZ3
BLKUV TRUV
START
STZ1
STZ2
STZ3
STUV
IEC14000018-1-en.vsd
IEC14000018 V1 EN-US
8.20.4 Signals
PID-3587-INPUTSIGNALS v8
PID-3587-OUTPUTSIGNALS v8
8.20.5 Settings
PID-3587-SETTINGS v8
The full scheme backup distance element constitutes of three operating zones. Zone1 has only the
phase-to-phase loops enabled. Zone2 and zone3 can be selected for phase –to-phase or Enhanced
reach loop. Each measuring loop use the offset mho characteristic
UBase
ZBase =
3 IBase
IECEQUATION1400024 V1 EN-US (Equation 139)
Where,
ZBase is the base value of impedance
UBase is the line-to-line voltage rating at the generator terminal
IBase is the line current rating at the generator terminal
All the outputs will be blocked by activation of the BLOCK or BLKZ input.
jX
IEC11000294-2-en.vsd
IEC11000294 V2 EN-US
U3P STZ1
I3P ZONE 1 TRZ1
BLKZ OpModeZ1
Z1Fwd
BLOCK Z1Rev
tZ1 START
³1
ZONE 2 STZ2
OpModeZ2
Z2Fwd TRZ2
Z2Rev
tZ2
LoadEnchModZ2
OPERATE
³1
³1
STZ3
ZONE 3
OpModeZ3
Z3Fwd
Z3Rev
tZ3 TRZ3
LoadEnchModZ3
LoadEnch
RLd
ArgLd
UVSealIn TRUV
OpModeU< STUV
U<
tU<
BLCKUV
IEC11000295-3-en.vsd
IEC11000295 V2 EN-US
In general, the zone 1 must cover the generator winding, the cables or busbars and step up
transformer.
Under impedance functionality is provided as selective protection for the phase-to-phase faults in
zone 1. Hence the functionality of zone 1 includes only phase-to-phase measuring loops.
Zone 1 functionality can be set to PP Loops or Off using the setting OpModeZ1.
BLOCK
BLKZ
U3P Comparator
ZL1L2 <
I3P
OpModeZ1
Z1Fwd STZ1
Z1Rev
ImpedanceAng
tZ1
Comparator
³1 t TRZ1
ZL2L3 <
OPModeZ1
Z1Fwd
Z1Rev
ImpedanceAng
Comparator
ZL3L1 <
OpModeZ1
Z1Fwd
Z1Rev
ImpedanceAng
IEC11000297-3-en.vsd
IEC11000297 V3 EN-US
• Comparator to detect, if the operating impedance has entered inside zone 1 offset mho
characteristic.
• All three phase-to-phase loops are implemented separately.
• Forward and reverse reach values are provided in percentage of impedance base value at
generator.
• Operate time delay is provided.
Comparator characteristics
The comparator consists of offset mho characteristics. Three individual comparators are provided in
the three phase-to-phase loops. The offset mho characteristic is as shown in figure 300.
IL1L2 · jX
IL1L2 · Z 1Fwd
Ucomp1=UL1L2 - I L1L2 · Z1Fwd
IL1L2 · R
- IL1L2· Z1REV
IEC11000296-2-en.vsd
IEC11000296 V2 EN-US
Figure 300: Simplified offset mho characteristics for L1-L2 fault in zone 1
In the above characteristics, Z1Fwd and Z1Rev are the forward and reverse reach percentage values
and ImpedanceAng is the characteristic angle provided for the zone 1 operation region.
Operate time
The operate time delay for zone 1 can be provided using the setting tZ1.
Figure 301 shows the function block diagram describing the functionality of zone 2.
Zero
sequence
Voltage
Compensation
U3P
Measuring Loop
EnhancedReach
I3P
BLOCK OpModeZ2
Z2Fwd
Z2Rev
BLKZ ImpedanceAng
1
Measuring Loop
phase-to-phase STZ2
(ZL1L2<,ZL2L3<,ZL3L1<) &
OpModeZ2
tZ2
Z2Fwd
t TRZ2
Z2Rev
ImpedanceAng
LoadEnchModZ2
Load
Encroachment T
1 F
RLd
ArgLd
IEC11000298-3-en.vsd
IEC11000298 V3 EN-US
Zone 2 can be used to cover up to the HV side of the transformer and the HV bus bar. It also covers
to some degree, the stator winding. The time to trip is provided in order to coordinate with the zone 1
element on the shortest outgoing line from the bus.
Zone 2 coverage provides backup for the phase-to-phase and three-phase faults in generator. It also
protects LV winding of generator transformer and phase-to-earth, phase-to-phase and three-phase
faults in the HV side of transformer and the bus. A separate maximum current feature is provided in
phase-to-earth loop selection which gives correct reach measurement for phase-to-phase fault on HV
side. Zero sequence compensation for the phase voltages is given in phase-to-earth measuring
loops in order to prevent operation for the stator earth faults.
Zone 2 can be selected for different measuring loops using the setting OpModeZ2. The OpModeZ2
can be selected as Off or PP Loops or EnhancedReach. If the OpModeZ2 is selected as
EnhancedReach, the loop used for measurements is the phase-to-earth measuring loop (L1E, L2E
and L3E) which is with maximum phase current of all the three phase currents.
Figure 302 shows the logic to detect the phase to earth loop with maximum phase current.
A startPh1 &
i1Mag a
a==b
b
startPh2 & ³1 start
&
B
i2Mag a
a==b
b startPh3 &
&
³1
C
i3Mag a
a==b
b
MAX
IEC11000307_1_en.vsd
IEC11000307 V1 EN-US
Figure 302: Logic diagram for the selection of the maximum current loop
The phase-to-earth voltage is compensated with zero sequence voltage in order to avoid the function
operating for earth faults in zone 1, that is, complete generator stator winding and LV winding of the
power transformer.
The reach settings for zone 2 can be provided using the Z2Fwd, Z2Rev and ImpedanceAng settings.
The Z2Fwd is forward reach setting and Z2Rev is reverse reach setting. The offset mho
characteristic for phase-to-earth loop is shown in Figure 303. The offset mho characteristics for
phase-to-phase loop is shown in Figure 304.
IL1 jX
IL1 Z 2 Fwd
Ucomp1 UL1E U 0 IL1 Z 2 Fwd
IL1 R
IL1 Z 2 REV
IEC11000299-2-en.vsd
IEC11000299 V2 EN-US
Figure 303: Simplified offset mho characteristics for L1-to-E fault in zone 2
IL1L 2 jX
IL1L2 Z 2 Fwd
Ucomp1 UL1L2 IL1L2 Z 2 Fwd
IL1L 2 R
IL1L 2 Z 2 REV
IEC11000300-2-en.vsd
IEC11000300 V2 EN-US
Figure 304: Simplified offset mho characteristics for L1-to-L2 fault in zone 2
Operation occurs if 90° ≤ β ≤ 270°.
Impedance defined in the Figure 303 and 304 is described in equation 142.
Phase Phase:
Enhanced Reach:
IL21)
2 UL 2 E - U 0 IL2
3 IL31)
UL3 E - U 0 IL3
Operate time
The operate time delay for zone 2 can be provided using the setting tZ2.
Zone 2 is provided load encroachment detection feature based on positive sequence components
measurements.. This feature avoids the function from operating due to load encroachment. The load
encroachment feature for zone 2 can be set using LoadEnchModZ2 to On or Off.
Zone 3 is used to cover up to the HV side of the transformer, interconnecting bus network and
outgoing lines. The time to trip should be provided in order to coordinate with the transmission line
protection.
The zone 3 will provide protection from phase-to-earth, phase-phase and three-phase faults on the
HV side of the system. The zone 3 functionality is same as zone 2 hence the explanation of zone 2
applies except the zone 3 has separate reach (Z3Fwd, Z3Rev), operate timer (tZ3) and load
encroachment enable (LoadEnchModZ3) settings.
The load encroachment characteristics can be set for zone2 and zone3. Load encroachment can be
enabled for zone 2 by setting LoadEnchModZ2 to On. Similarly the load encroachment for zone 3
can be enabled by setting LoadEnchModZ3 to On.
The load encroachment characteristic is based on positive sequence quantities and can be set using
the settings RLd and ArgLd.
RLd is the positive sequence resistive reach value in percentage. ArgLd is angle in degrees from the
origin to the resistive axis as shown in Figure 305.
jX
ArgLd ArgLd
-RLd RLd R
ArgLd ArgLd
IEC11000304_1_en
IEC11000304 V1 EN-US
The under voltage seal-in logic ensures the trip under fault condition, where as under impedance
function will reset due to CT saturation. The start signal of zone 2 and zone 3 elements trigger the
under voltage seal-in. This can be selected using the setting OpModeU< . The setting OpModeU<
can be selected as Off or Z2Start or Z3Start. Select Z2Start to choose zone 2 for triggering the seal-
in logic. Similarly, select Z3Start to choose zone 3 for triggering the seal-in logic.
Under voltage seal-in is activated from the criterion based on line-to-line voltage magnitude. The
voltage criteria checks by comparing all three line-to-line voltage levels with the level given by the
setting parameter U<. If any loop detects lower voltage, the under voltage seal-in logic gets triggered,
provided the respective selected zone start is also high. Once the under voltage seal-in logic is
triggered, the pick-up signal STUV becomes high. If it is constantly high for a time longer than the
setting tU<, the tripping signal TRUV is issued as a pulse signal with a duration of one second.
Figure 306 shows the functionality of under voltage seal-in for zone 2 and zone 3.
- STUV
q1
BLOCK
BLKUV 1 tU<
TRUV
Zone 2 Start & t
tPulse = 1sec
&
OpModeU< =
10 ms -
0 = Off b0 1 q1
int 1 t
1 = Z2Start
2 = Z3Start b1
Drop-Off
& timer
Zone 3 Start
uP1P2 a
a<b
U< b
uP2P3 a
a<b 1
U< b
uP3P1 a
a< b
U< b
IEC11000306-3-en.vsd
IEC11000306 V3 EN-US
9.1.1 Identification
M14880-1 v5
SYMBOL-Z V1 EN-US
The instantaneous three phase overcurrent (PHPIOC) function has a low transient overreach and
short tripping time to allow use as a high set short-circuit protection function.
PHPIOC
I3P* TRIP
BLOCK TRL1
ENMULT TRL2
TRL3
IEC04000391-2-en.vsd
IEC04000391 V2 EN-US
PID-6914-INPUTSIGNALS v3
PID-6914-OUTPUTSIGNALS v3
PID-6914-SETTINGS v3
The sampled analogue phase currents are pre-processed in a discrete Fourier filter (DFT) block. The
RMS value of each phase current is derived from the fundamental frequency components, as well as
sampled values of each phase current. These phase current values are fed to the instantaneous
phase overcurrent protection 3-phase output function PHPIOC. In a comparator the RMS values are
compared to the set operation current value of the function (IP>>).
If a phase current is larger than the set operation current a signal from the comparator for this phase
is set to true. This signal will, without delay, activate the output signal TRLn (n=1,2,3) for this phase
and the TRIP signal that is common for all three phases.
There is an operation mode (OpMode) setting: 1 out of 3 or 2 out of 3. If the parameter is set to 1 out
of 3, any phase trip signal will be activated. If the parameter is set to 2 out of 3, at least two phase
signals must be activated for trip.
There is also a possibility to activate a preset change of the set operation current (StValMult) via a
binary input (ENMULT). In some applications the operation value needs to be changed, for example,
due to transformer inrush currents.
The operation current value IP>>, is limited to be between IP>>Max and IP>>Min. The default values
of the limits are the same as the setting limits for IP>>, and the limits can only be used for reducing
the allowed range of IP>>. This feature is used when remote setting of the operation current value is
allowed, making it possible to ensure that the operation value used is reasonable. If IP>> is set
outside IP>>Max and IP>>Min, the closest of the limits to IP>> is used by the function. If IP>>Max is
smaller then IP>>Min, the limits are swapped. The principle of the limitation is shown in Figure 308.
IP>>Max
MAX hi
u y
IP>>_used
IP>>
MIN lo
IP>>Min
IEC17000016-1-en.vsdx
IEC17000016 V1 EN-US
M12336-1 v14
9.2.2 Identification
M14885-1 v6
TOC-REVA V2 EN-US
Directional phase overcurrent protection, four steps (OC4PTOC) has an inverse or definite time delay
for each step.
All IEC and ANSI inverse time characteristics are available together with an optional user defined
time characteristic.
The directional function needs voltage as it is voltage polarized with memory. The function can be set
to be directional or non-directional independently for each of the steps.
A second harmonic blocking level can be set for the function and can be used to block each step
individually.
OC4PTOC
I3P* TRIP
U3P* TR1
BLOCK TR2
BLKTR TR3
BLKST1 TR4
BLKST2 TRL1
BLKST3 TRL2
BLKST4 TRL3
ENMULT1 TR1L1
ENMULT2 TR1L2
ENMULT3 TR1L3
ENMULT4 TR2L1
TR2L2
TR2L3
TR3L1
TR3L2
TR3L3
TR4L1
TR4L2
TR4L3
START
ST1
ST2
ST3
ST4
STL1
STL2
STL3
ST1L1
ST1L2
ST1L3
ST2L1
ST2L2
ST2L3
ST3L1
ST3L2
ST3L3
ST4L1
ST4L2
ST4L3
ST2NDHRM
DIRL1
DIRL2
DIRL3
STDI RCND
IEC06000187-4-en.vsdx
IEC06000187 V4 EN-US
9.2.5 Signals
PID-7873-INPUTSIGNALS v1
PID-7873-OUTPUTSIGNALS v1
9.2.6 Settings
PID-7873-SETTINGS v1
Directional phase overcurrent protection, four steps OC4PTOC is divided into four different sub-
functions. For each step x , where x is step 1, 2, 3 and 4, an operation mode is set by DirModex: Off/
Non-directional/Forward/Reverse.
If VT inputs are not available or not connected, setting parameter DirModex shall be
left to default value, Non-directional.
4 step overcurrent
Direction dirPh1Flt element faultState
faultState
Element One element for each
dirPh2Flt step
I3P dirPh3Flt START
U3P
TRIP
Harmonic harmRestrBlock
Restraint
Element
enableDir
Mode Selection
enableStep1-4
DirectionalMode1-4
IEC05000740-3-en.vsdx
IEC05000740 V3 EN-US
Using a parameter setting MeasType within the general settings for the function OC4PTOC, it is
possible to select the type of the measurement used for all overcurrent stages. Either discrete
Fourier filter (DFT) or true RMS filter (RMS) can be selected.
If the DFT option is selected, only the RMS value of the fundamental frequency component of each
phase current is derived. The influence of the DC current component and higher harmonic current
components are almost completely suppressed. If the RMS option is selected, then the true RMS
value is used. The true RMS value includes the contribution from the current DC component as well
as from the higher current harmonic in addition to the fundamental frequency component.
In a comparator, the DFT or RMS values are compared to the set operation current value of the
function (I1>, I2>, I3> or I4>) for each phase current. If a phase current is larger than the set
operation current, outputs START, STx, STL1, STL2 and STL3 are activated without delay. Output
signals STL1, STL2 and STL3 are common for all steps. This means that the lowest set step will
initiate the activation. The START signal is common for all three phases and all steps. It shall be
noted that the selection of measured value (DFT or RMS) do not influence the operation of
directional part of OC4PTOC.
Service values for individually measured phase currents are available on the local HMI for OC4PTOC
function, which simplifies testing, commissioning and in service operational checking of the function.
A harmonic restrain of the function can be chosen. A set 2nd harmonic current in relation to the
fundamental current is used.
The function can be directional. The direction of a fault is given as the current angle in relation to the
voltage angle. The fault current and fault voltage for the directional function are dependent on the
fault type. The selection of the measured value (DFT or RMS) does not influence the operation of the
directional part of OC4PTOC. To enable directional measurement at close-in faults, causing a low
measured voltage, the polarization voltage is a combination of the apparent voltage (85%) and a
memory voltage (15%). The following combinations are used.
U refL1L 2 = U L1 - U L 2 I dirL1L 2 = I L1 - I L 2
EQUATION1449 V1 EN-US (Equation 143)
U refL 2 L 3 = U L 2 - U L 3 I dirL 2 L 3 = I L 2 - I L 3
EQUATION1450 V1 EN-US (Equation 144)
U refL 3 L1 = U L 3 - U L1 I dirL 3 L1 = I L 3 - I L1
EQUATION1451 V1 EN-US (Equation 145)
U refL1 = U L1 I dirL1 = I L1
EQUATION1452 V1 EN-US (Equation 146)
U refL 2 = U L 2 I dirL 2 = I L 2
EQUATION1453 V1 EN-US (Equation 147)
U refL 3 = U L 3 I dirL 3 = I L 3
EQUATION1454 V1 EN-US (Equation 148)
The polarizing voltage is available as long as the positive-sequence voltage exceeds 5% of the set
base voltage UBase. So the directional element can be used for all unsymmetrical faults including
close-in faults.
For close-in three-phase faults, the U1L1M memory voltage, based on the same positive sequence
voltage, ensures correct directional discrimination.
The memory voltage is used for 100 ms or until the positive sequence voltage is restored.
• If the current is still above the set value of the minimum operating current (7% of the set terminal
rated current IBase), the condition seals in.
• If the fault has caused tripping, the trip endures.
• If the fault was detected in the reverse direction, the measuring element in the reverse
direction remains in operation.
• If the current decreases below the minimum operating value, the memory resets until the
positive sequence voltage exceeds 10% of its rated value.
The directional setting is given as a characteristic angle AngleRCA for the function and an angle
window ROADir.
Reverse
Uref
RCA
ROA
ROA Forward
Idir
en05000745.vsd
IEC05000745 V1 EN-US
A minimum current for the directional phase start current signal can be set. IMinOpPhSel is the start
level for the directional evaluation of IL1, IL2 and IL3. The directional signals release the overcurrent
measurement in the respective phases if their current amplitudes are higher than the start level
(IMinOpPhSel) and the direction of the current is according to the set direction of the step.
If no blocking signals are active, the start signal will start the timer of the steps. The time
characteristic for each step can be chosen as definite time delay or an inverse time delay
characteristic. A wide range of standardized inverse time delay characteristics is available. It is also
possible to create a tailor made time characteristic.
The possibilities for inverse time characteristics are described in section "Inverse characteristics".
HarmBlockx = Enabled
Freeze Timers
AND
2ndH_FreezeTimers_int
EMULTX
IMinx Characteristx=DefTime
X T b tx
F a>b
a t
TRx
AND AND
|IOP|
a OR
a>b
b
STx
IxMult AND
X T
F
Inverse
Ix>
AND
AND
Characteristx=Inverse
txmin
DirModex=Off t
OR STEPx_DIR_Int
DirModex=Non-directional
DirModex=Forward AND OR
FORWARD_Int
DirModex=Reverse
AND
REVERSE_Int
IEC12000008‐2‐en.vsdx
IEC12000008 V3 EN-US
I3P
DFWDLx
U3P DFWDLxx
DREVLx
Directional
Element
AngleRCA DREVLxx FORWARD_int
Directional
AngleROA Release REVERSE_int
Block
STLx
Greater
IMinOpPhSel Comparator
x‐ means three phases 1,2 and 3
xx – means phase to phase 12,23,31
IEC15000266-2-en.vsdx
IEC15000266 V2 EN-US
There is a possibility to activate a preset change (IxMult x= 1, 2, 3 or 4) of the set operation current
via a binary input ENMULTx (enable multiplier). In some applications the operation value needs to be
changed, for example due to changed network switching state.
The operation current value Ix>, is limited to be between Ix>Max and Ix>Min. The default values of
the limits are the same as the setting limits for Ix>, and the limits can only be used for reducing the
allowed range of Ix>. This feature is used when remote setting of the operation current value is
allowed, making it possible to ensure that the operation value used is reasonable. If Ix> is set outside
Ix>Max and Ix>Min, the closest of the limits to Ix> is used by the function. If Ix>Max is smaller then
Ix>Min, the limits are swapped. The principle of the limitation is shown in Figure 314.
Ix>Max
MAX hi
u y
Ix>_used
Ix>
MIN lo
Ix>Min
IEC17000018-1-en.vsdx
IEC17000018 V1 EN-US
The STDIRCND output provides an integer signal that depends on the start and directional
evaluation and is derived from a binary coded signal as described in Table 292.
STDIRCND Description
bit 0 (1) General start
bit 1 (2) Direction detected in forward
bit 2 (4) Direction detected in reverse
bit 3 (8) Start in phase L1
bit 4 (16) Forward direction detected in phase L1
bit 5 (32) Reverse direction detected in phase L1
bit 6 (64) Start in phase L2
bit 7 (128) Forward direction detected in phase L2
bit 8 (256) Reverse direction detected in phase L2
bit 9 (512) Start in phase L3
bit 10 (1024) Forward direction detected in phase L3
bit 11 (2048) Reverse direction detected in phase L3
All four steps in OC4PTOC can be blocked from the binary input BLOCK. The binary input BLKSTx
(x=1, 2, 3 or 4) blocks the operation of the respective step.
The start signals from the function can be blocked by the binary input BLKST. The trip signals from
the function can be blocked by the binary input BLKTR.
GUID-E3980B2D-EEDA-4BF1-A07D-E7B721130554 v7
A harmonic restrain of the directional phase overcurrent protection function OC4PTOC can be
chosen. If the ratio of the 2nd harmonic component in relation to the fundamental frequency
component in a phase current exceeds the preset level defined by the parameter 2ndHarmStab
setting, any of the four overcurrent stages can have their timers selectively frozen by the parameter
HarmBlockx setting. When the 2nd harmonic restraint feature is active, the OC4PTOC function
output signal ST2NDHRM will be set to the logical value one.
BLOCK
a
a>b
0.07*IBase b
a
a>b
b
Extract second AND
IOP
harmonic current a
a>b
component b
Extract 2ndH_FreezeTimers_Int
fundamental
current component
X
2ndHarmStab
IEC13000014-3-en.vsdx
IEC13000014 V3 EN-US
When enabled, the 2nd harmonic blocking function is used to freeze the Definite
and/or the Inverse Characteristics internal timers. When the function detects a 2nd
harmonic higher than the set threshold, the internal function timers are frozen but
START outputs continues to be active as long as the measured current is above the
set pickup level. Internal timers will again resume timing when harmonic content
becomes smaller than the set threshold and the measured current is higher than the
pickup value. If TRIP output is already active when harmonic blocking signal appears
the TRIP output will not be affected.
When DirModex is set to Forward/Reverse and Ix> is set at its minimum value, that
is, 5.0% of IBase, the operation from the respective overcurrent step takes place at
20.0% of IBase. This is done to avoid unintentional maloperations during unbalanced
loading conditions that might appear in power systems and the unbalanced loading
condition might lead to a neutral current in the range of 10.0% to 15.0% of IBase.
9.3.1 Identification
M14887-1 v4
IEF V1 EN-US
The Instantaneous residual overcurrent protection (EFPIOC) has a low transient overreach and short
tripping times to allow use for instantaneous earth-fault protection, with the reach limited to less than
typical eighty percent of the transformer impedance at minimum source impedance. EFPIOC can be
configured to measure the residual current from the three-phase current inputs or the current from a
separate current input.
EFPIOC
I3P* TRIP
BLOCK
BLKAR
ENMULT
IEC06000269-3-en.vsdx
IEC06000269 V3 EN-US
PID-6915-INPUTSIGNALS v4
PID-6915-OUTPUTSIGNALS v4
PID-6915-SETTINGS v4
The sampled analog residual currents are pre-processed in a discrete Fourier filter (DFT) block.
From the fundamental frequency components of the residual current, as well as from the sample
values the equivalent RMS value is derived. This current value is fed to the Instantaneous residual
overcurrent protection (EFPIOC). In a comparator the RMS value is compared to the set operation
current value of the function (IN>>).
If the residual current is larger than the set operation current a signal from the comparator is set to
true. This signal will, without delay, activate the output signal TRIP.
There is also a possibility to activate a preset change of the set operation current via a binary input
(enable multiplier ENMULT). In some applications the operation value needs to be changed, for
example, due to transformer inrush currents.
The operation current value IN>>, is limited to be between IN>>Max and IN>>Min. The default values
of the limits are the same as the setting limits for IN>>, and the limits can only be used for reducing
the allowed range of IN>>. This feature is used when remote setting of the operation current value is
allowed, making it possible to ensure that the operation value used is reasonable. If IN>> is set
outside IN>>Max and IN>>Min, the closest of the limits to IN>> is used by the function. If IN>>Max is
smaller then IN>>Min, the limits are swapped. The principle of the limitation is shown in Figure 317.
IN>>Max
MAX hi
u y
IN>>_used
IN>>
MIN lo
IN>>Min
IEC17000015-1-en.vsdx
IEC17000015 V1 EN-US
EFPIOC function can be blocked from the binary input BLOCK. The trip signals from the function can
be blocked from the binary input BLKAR, that can be activated during single pole trip and
autoreclosing sequences.
M12340-2 v10
9.4.2 Identification
M14881-1 v7
EF4PTOC has an inverse or definite time delay independent for each step.
All IEC and ANSI time-delayed characteristics are available together with an optional user-defined
characteristic.
IDir, UPol and IPol can be independently selected to be either zero sequence or negative sequence.
The residual current can be calculated by summing the three-phase currents or taking the input from
the neutral CT.
EF4PTOC also provides very fast and reliable faulty phase identification for phase selective tripping
and subsequent reclosing during earth fault.
EF4PTOC
I3P* TRIP
I3PDIR* TRIN1
I3PPOL* TRIN2
U3P* TRIN3
BLOCK TRIN4
BLKTR TRSOTF
BLKST1 START
BLKST2 STIN1
BLKST3 STIN2
BLKST4 STIN3
BLKPHSEL STIN4
ENMULT1 STSOTF
ENMULT2 STFW
ENMULT3 STRV
ENMULT4 PHSELL1
CBPOS PHSELL2
CLOSECB PHSELL3
OPENCB 2NDHARMD
IEC06000424-6-en.vsdx
IEC06000424 V6 EN-US
PID-7797-INPUTSIGNALS v1
PID-7797-OUTPUTSIGNALS v1
PID-7797-SETTINGS v1
M13941-51 v8
This function has the following four analog inputs on its function block in the configuration tool:
1. I3P, input used for the operating quantity. Supplies the zero-sequence magnitude measuring
functionality.
2. U3P, input used for the voltage polarizing quantity. Supplies either the zero or the negative
sequence voltage to the directional functionality
3. I3P and U3P also supply current and voltage samples for faulty phase selection functionality.
4. I3PPOL, input used for the current polarizing quantity. Provides polarizing current to the
directional functionality. This current is normally taken from the grounding of a power
transformer.
5. I3PDIR, input used for directional detection. Supplies either the zero or the negative sequence
current to the directional functionality.
These inputs are connected from the corresponding pre-processing function blocks in the
configuration tool in PCM600.
The function always uses residual current (3I0) for its operating quantity. The residual current can be:
1. Directly measured (when a dedicated CT input of the IED is connected in PCM600 to the fourth
analog input of the pre-processing block connected to EF4PTOC function input I3P). This
dedicated IED CT input can be, for example, connected to:
where:
IL1, IL2, and IL3 are fundamental frequency phasors of three individual phase currents.
The residual current is pre-processed by a discrete Fourier filter. Thus the phasor of the fundamental
frequency component of the residual current is derived. The phasor magnitude is used within the
EF4PTOC protection to compare it with the set operation current value of the four steps (IN1>, IN2>,
IN3>, or IN4>).
If the residual current is larger than the set operation current and the step is used in non-directional
mode a signal from the comparator for this step is set to true. This signal will, without delay, activate
the output signal STINx (x=step 1-4) for this step and a common START signal.
A polarizing quantity is used within the protection in order to determine the direction to the earth fault
(forward/reverse).
The function can be set to use voltage polarizing, current polarizing or dual polarizing.
Voltage polarizing
When voltage polarizing is selected, the protection will use the residual voltage -3U0 as the polarizing
quantity U3P.
1. Directly measured (when a dedicated VT input of the IED is connected in PCM600 to the fourth
analog input of the pre-processing block connected to EF4PTOC function input U3P). This
dedicated IED VT input shall be then connected to the open delta winding of a three-phase main
VT.
2. Calculated from three-phase voltage input within the IED (when the fourth analog input of the
pre-processing block, connected to EF4PTOC analog function input U3P, is NOT connected to a
dedicated VT input of the IED in PCM600). In such a case, the pre-processing block will
calculate -3U0 from the first three inputs into the pre-processing block by using the following
formula:
where:
UL1, UL2, and UL3 are fundamental frequency phasors of three individual phase voltages.
In order to use this, all three phase-to-earth voltages must be connected to three IED
VT inputs.
The residual voltage is pre-processed by a discrete Fourier filter. Thus, the phasor of the
fundamental frequency component of the residual voltage is derived.
This phasor is used together with the phasor of the operating directional current, in order to
determine the direction to the earth fault (Forward/Reverse). In order to enable voltage polarizing the
magnitude of polarizing voltage shall be bigger than a minimum level defined by setting parameter
UPolMin.
It shall be noted that residual voltage (-3U0) or negative sequence voltage (-3U2) is used to
determine the location of the earth fault. This ensures the required inversion of the polarizing voltage
within the earth-fault function.
Current polarizing
When current polarizing is selected, the function will use an external residual current (3I0) as the
polarizing quantity IPol. This current can be:
1. Directly measured (when a dedicated CT input of the IED is connected in PCM600 to the fourth
analog input of the pre-processing block, connected to EF4PTOC function input I3PPOL). This
dedicated IED CT input is then typically connected to one single current transformer located
between power system star point and earth (current transformer located in the star point of a
star connected transformer winding).
• For some special line protection applications, this dedicated IED CT input can be
connected to a parallel connection of current transformers in all three phases (Holm-
Green connection).
2. Calculated from three phase current input within the IED (when the fourth analog input into the
pre-processing block, connected to EF4PTOC function analog input I3PPOL, is NOT connected
to a dedicated CT input of the IED in PCM600). In such case, the pre-processing block will
calculate 3I0 from the first three inputs into the pre-processing block by using the following
formula:
where:
IL1, IL2, and IL3 are fundamental frequency phasors of three individual phase currents.
The residual current is pre-processed by a discrete fourier filter. Thus the phasor of the fundamental
frequency component of the polarizing current is derived. This phasor is then multiplied with the pre-
set equivalent zero-sequence source impedance in order to calculate the equivalent polarizing
voltage UIPol in accordance with the following formula:
which will be then used, together with the phasor of the operating current, in order to determine the
direction to the earth fault (forward/reverse).
In order to enable current polarizing, the magnitude of the polarizing current shall be bigger than a
minimum level defined by setting parameter IPolMin.
Dual polarizing
When dual polarizing is selected, the function will use the vectorial sum of the voltage based and
current based polarizing in accordance with the following formula:
UPol and IPol can be either zero sequence component or negative sequence component depending
upon the user selection.
Then the phasor of the total polarizing voltage UTotPol will be used, together with the phasor of the
operating current, to determine the direction of the earth fault (forward/reverse).
The individual steps within the protection can be set as non-directional. When this setting is selected,
it is possible via the function binary input BLKSTx to provide external directional control (that is,
torque control) by, for example, using one of the following functions if available in the IED:
Zero sequence components will be used for detecting directionality for the earth fault function. In
some cases, zero sequence quantities might detect directionality incorrectly. In such a scenario,
negative sequence quantities will be used. The user can select either zero sequence components or
negative sequence components for detecting directionality with the parameter SeqTypeIPol. I3PDIR
input is always connected to the same source as I3P input.
The base quantities are entered as global settings for all functions in the IED. Base current (IBase)
shall be entered as rated phase current of the protected object in primary amperes. Base voltage
(UBase) shall be entered as rated phase-to-phase voltage of the protected object in primary kV.
Each overcurrent step uses operating quantity Iop (residual current) as the measuring quantity. Each
of the four residual overcurrent steps has the following built-in facilities:
INx>Max
MAX hi
INx>_used
INx> u y
MIN lo
INx>Min
IEC17000017-2-en.vsdx
IEC17000017 V2 EN-US
Simplified logic diagram for one residual overcurrent step is shown in Figure 320.
HarmBlockx = Enabled
Freeze Timers
AND
2ndH_FreezeTimers_int
EMULTX
IMinx Characteristx=DefTime
X T b tx
F a>b
a t
TRINx
AND AND
|IOP|
a OR
a>b
b
STINx
INxMult AND
X T
F
Inverse
INx>
AND
AND
Characteristx=Inverse
txmin
DirModex=Off t
OR STEPx_DIR_Int
DirModex=Non-directional
DirModex=Forward AND OR
FORWARD_Int
DirModex=Reverse
AND
REVERSE_Int
IEC10000008-7-en.vsdx
IEC10000008 V7 EN-US
Figure 320: Simplified logic diagram for residual overcurrent step x, where x = step 1, 2, 3 or 4
The protection can be completely blocked from the binary input BLOCK. Output signals for respective
step, and STINx and TRINx, can be blocked from the binary input BLKSTx. The trip signals from the
function can be blocked from the binary input BLKTR.
At least one of the four residual overcurrent steps shall be set as directional in order
to enable execution of the directional supervision element and the integrated
directional comparison function.
The protection has an integrated directional feature. As the operating quantity current Iop is always
used, the polarizing method is determined by the parameter setting polMethod. The polarizing
quantity will be selected by the function in one of the following three ways:
The operating and polarizing quantity are then used inside the directional element, as shown in
Figure 321, in order to determine the direction of the earth fault.
Operating area
STRV
0.6 * IN>DIR
Characteristic for reverse
release of measuring steps
-RCA -85 deg
Characteristic
for STRV 40% of
IN>DIR RCA +85 deg
RCA
65° Upol = -3U 0
STFW
I op = 3I0
Operating area
Characteristic
for STFW IEC11000243-1-en.ai
IEC11000243 V1 EN-US
Figure 321: Operating characteristic for earth-fault directional element using the zero sequence
components
The relevant setting parameters for the directional supervision element are:
• The directional element will be internally enabled to operate as soon as Iop is bigger than 40%
of IN>Dir and the directional condition is fulfilled in the set direction.
• The relay characteristic angle AngleRCA, which defines the position of forward and reverse
areas in the operating characteristic.
1. STFW=1 when operating quantity magnitude Iop x cos(φ - AngleRCA) is bigger than setting
parameter IN>Dir and directional supervision element detects fault in forward direction.
2. STRV=1 when operating quantity magnitude Iop x cos(φ - AngleRCA) is bigger than 60% of
setting parameter IN>Dir and directional supervision element detects fault in reverse direction.
These signals shall be used for communication based earth-fault teleprotection communication
schemes (permissive or blocking).
Simplified logic diagram for directional supervision element with integrated directional comparison
step is shown in Figure 322:
| IopDir |
a
a>b STRV
b AND
REVERSE_Int
0.6
X
a
a>b STFW
IN>Dir b AND
FORWARD_Int
X
0.4
FWD
AND FORWARD_Int
AngleRCA
polMethod=Voltage
OR
UPolMin
Characteristic
Directional
polMethod=Dual IPolMin
UPol T
I3PDIR
0.0 F
polMethod=Current
OR
UTotPol
IPol AND REVERSE_Int
T RVS
F
UIPol
RNPol STAGE1_DIR_Int
X T
Complex 0.0 STAGE2_DIR_Int
Number 0.0 F OR
XNPol STAGE3_DIR_Int
STAGE4_DIR_Int
BLOCK AND
IEC07000067-7-en.vsdx
IEC07000067 V7 EN-US
Figure 322: Simplified logic diagram for directional supervision element with integrated directional comparison
step
A harmonic restrain can be chosen for each step by a parameter setting HarmBlockx. If the ratio of
the 2nd harmonic component in relation to the fundamental frequency component in the residual
current exceeds the preset level (defined by parameter 2ndHarmStab), output signal 2NDHARMD is
set to logical value one and the harmonic restraining feature to the function block will be applicable.
Blocking from the 2nd harmonic element activates if all of three criteria are satisfied:
In addition to the basic functionality explained above, the 2nd harmonic blocking can be set in such
way to seal-in until residual current disappears. This feature might be required to stabilize EF4PTOC
during switching of parallel transformers in the station. In case of parallel transformers there is a risk
of sympathetic inrush current. If one of the transformers is in operation, and the parallel transformer
is switched in, the asymmetric inrush current of the switched-in transformer will cause partial
saturation of the transformer already in service. This is called transferred saturation. The 2nd
harmonic of the inrush currents of the two transformers is in phase opposition. The summation of the
two currents thus gives a small 2nd harmonic current. The residual fundamental current is however
significant. The inrush current of the transformer in service before the parallel transformer energizing,
is a little delayed compared to the first transformer. Therefore, we have high 2nd harmonic current
component initially. After a short period this current is however small and the normal 2nd harmonic
blocking resets. If the BlkParTransf function is activated, the 2nd harmonic restrain signal is latched
as long as the residual current measured by the relay is larger than a selected step current level by
using setting UseStartValue.
This feature has been called Block for Parallel Transformers. This 2nd harmonic seal-in feature is
activated when all of the following three conditions are simultaneously fulfilled:
Once Block for Parallel Transformers is activated, the basic 2nd harmonic blocking signal is sealed-in
until the residual current magnitude falls below a value defined by parameter setting UseStartValue
(see condition 3 above).
Simplified logic diagram for 2nd harmonic blocking feature is shown in Figure 323.
BLOCK
a
a>b
0.07*IBase b
a
a>b
b
Extract second AND
IOP
harmonic current a
a>b
component b
Extract
fundamental
current component
X
2ndHarmStab
q-1
0-70ms OR 2ndH_FreezeTimers_int
AND OR
0
BlkParTransf=On
|IOP|
a
a>b
b
Use_PUValue
Pickup1>
Pickup2>
Pickup3>
Pickup4>
ANSI13000015-2-en.vsdx
ANSI13000015 V2 EN-US
Figure 323: Simplified logic diagram for 2nd harmonic blocking feature and Block for Parallel Transformers
feature
When enabled, the 2nd harmonic blocking function is used to freeze the Definite
and/or the Inverse Characteristics internal timers. When the function detects a 2nd
harmonic higher than the set threshold, the internal function timers are frozen but
START outputs continues to be active as long as the measured current is above the
set pickup level. Internal timers will again resume timing when harmonic content
becomes smaller than the set threshold and the measured current is higher than the
pickup value. If TRIP output is already active when harmonic blocking signal appears
the TRIP output will not be affected.
Integrated in the four step residual overcurrent protection are the switch on to fault logic (SOTF) and
the under-time logic. The setting parameter SOTF is set to activate SOTF, the under-time logic or
both. When the circuit breaker is closing there is a risk to close it onto a permanent fault, for example
during an autoreclosing sequence. The SOTF logic will enable fast fault clearance during such
situations. The time during which SOTF and under-time logics will be active after activation is defined
by the setting parameter t4U.
The SOTF logic uses the start signal from step 2 or step 3 for its operation, selected by setting
parameter StepForSOTF. The setting parameter ActivationSOTF can be set for activation of CB
position open change, CB position closed change or CB close command. In case of a residual
current start from step 2 or 3 (dependent on setting) the function will give a trip after a set delay
tSOTF. This delay is normally set to a short time (default 200 ms).
The under-time logic acts as a circuit breaker pole-discordance protection, but it is only active
immediately after breaker switching. The under-time logic can only be used in solidly or low
impedance grounded systems.
The under-time logic always uses the start signal from the step 4. The under-time logic will normally
be set to operate for a lower current level than the SOTF function. The under-time logic can also be
blocked by the 2nd harmonic restraint feature. This enables high sensitivity even if power transformer
inrush currents can occur at breaker closing. This logic is typically used to detect asymmetry of CB
poles immediately after switching of the circuit breaker. The under-time logic is activated either from
change in circuit breaker position or from circuit breaker close and open command pulses. This
selection is done by setting parameter ActUnderTime. In case of a start from step 4 this logic will give
a trip after a set delay tUnderTime. This delay is normally set to a relatively short time (default 300
ms).
SOTF
200 ms
Open
t
t4U
200 ms
Closed
t ActivationSOTF
Close command
tSOTF
AND t
AND
STIN2
StepForSOTF
STIN3
SOTF
BLOCK
OFF
SOTF
UNDERTIME
UnderTime TRIP
tUnderTime
SOTF or
AND
2nd Harmonic HarmResSOFT t UnderTime
OR
Open
Close OR
t4U
ActUnderTime
Close command AND
STIN4
IEC06000643-7-en.vsdx
IEC06000643 V7 EN-US
Figure 324: Simplified logic diagram for SOTF and under-time features
M13941-3 v6
Simplified logic diagram for the complete EF4PTOC function is shown in Figure 325:
harmRestrBlock
3I0 Harmonic
Restraint 1
Element TRIP
Blocking at parallel
transformers
SwitchOnToFault
TRSOTF
CB
DirMode pos
or cmd
enableDir
Mode
Selection enableStep1-4
DirectionalMode1-4
IEC06000376-4-en.vsdx
IEC06000376 V4 EN-US
The phase selection element provides very fast and reliable faulty phase identification for phase
selective tripping and subsequent reclosing during earth faults. The operation of the phase selection
element is based on both voltage phasor comparison and current change criteria. This measuring
principle successfully distinguishes the faulty phase with minimum influence from load current or
other disturbances, such as power swing. The phase selection feature can be enabled by setting
EnPhaseSel.
The faulty phases are primarily identified by a delta current criteria. Per-phase and phase-to-phase
delta currents are calculated and compared with different criteria to determine if there is a single
phase or phase-to-phase to earth fault. In case the fault cannot be identified by the delta current
criteria, a voltage phasor based method will be applied by comparing the angle between the voltage
phasor and the zero sequence current. The voltage phasor based method is applicable for forward
direction single phase to ground faults. If a three phase disturbance has been identified (for example,
during power swing), the voltage based method will be temporarily disabled until the disturbance
disappears.
The operation of the phase selection element is controlled by the measured zero sequence current.
When the measured zero sequence current is above the operate level (60% of IN>Dir), phase
selection is released. Once the faulty phase is selected, the selected phase will be latched until the
zero sequence current drops below the operate level.
Outputs PHSELL1, PHSELL2, and PHSELL3 are used to indicate the selected faulty phases. The
outputs are released when general START from EF4 function is TRUE.
The phase selection element will be blocked by the external input BLKPHSEL or when the circuit
breaker position is open. The CBPOS input will be high when the circuit breaker is closed and it will
be low when the circuit breaker is open. The CBPOS input provides the CB position to phase
selection element.
tON = 20ms
Phase selection by
U3P voltage and zero
AND 1s AND
sequence current
phasor
No 3 Phase Disturbance
STFW
IEC20000563-2-en.vsdx
IEC20000563 V2 EN-US
M15223-1 v18
Minimum operate time for inverse curves, (0.000 - 60.000) s ±0.2% or ±35 ms whichever is
step 1-4 greater
Inverse time characteristics, see Table 1294, 16 curve types See Table 1294, Table 1295 and
Table 1295 and Table 1296 Table 1296
Second harmonic blocking (5–100)% of fundamental ±2.0% of Ir
9.5.2 Identification
GUID-E1720ADA-7F80-4F2C-82A1-EF2C9EF6A4B4 v1
Four step directional negative phase sequence overcurrent protection (NS4PTOC) has an inverse or
definite time delay independent for each step separately.
All IEC and ANSI time delayed characteristics are available together with an optional user defined
characteristic.
NS4PTOC can be set directional or non-directional independently for each of the steps.
NS4PTOC
I3P* TRIP
I3PDIR* TR1
U3P* TR2
BLOCK TR3
BLKTR TR4
BLKST1 START
BLKST2 ST1
BLKST3 ST2
BLKST4 ST3
ENMULT1 ST4
ENMULT2 STFW
ENMULT3 STRV
ENMULT4
IEC10000054-2-en.vsd
IEC10000054 V2 EN-US
9.5.5 Signals
PID-7798-INPUTSIGNALS v1
PID-7798-OUTPUTSIGNALS v1
9.5.6 Settings
PID-7798-SETTINGS v1
Four step negative sequence overcurrent protection NS4PTOC function has the following three
“Analog Inputs” on its function block in the configuration tool:
These inputs are connected from the corresponding pre-processing function blocks in the
Configuration Tool within PCM600.
Four step negative sequence overcurrent protection NS4PTOC function always uses negative
sequence current (I2) for its operating quantity. The negative sequence current is calculated from
three-phase current input within the IED. The pre-processing block calculates I2 from the first three
inputs into the pre-processing block by using the following formula:
1
I2 = (
× IL1 + a × IL 2 + a × IL 3
2
)
3
EQUATION2266 V2 EN-US (Equation 156)
where:
IL1, IL2 and IL3 are fundamental frequency phasors of three individual phase currents.
a is so called operator which gives a phase shift of 120 deg, that is, a = 1∠120 deg
a2 similarly gives a phase shift of 240 deg, that is, a2 = 1∠240 deg
The phasor magnitude is used within the NS4PTOC protection to compare it with the set operation
current value of the four steps (I1>, I2>, I3> or I4>). If the negative sequence current is larger than
the set operation current and the step is used in non-directional mode a signal from the comparator
for this step is set to true. This signal, without delay, activates the output signal STx (x=1 - 4) for this
step and a common START signal.
A polarizing quantity is used within the protection to determine the direction to the fault (Forward/
Reverse).
Four step negative sequence overcurrent protection NS4PTOC function uses the voltage polarizing
method.
NS4PTOC uses the negative sequence voltage -U2 as polarizing quantity U3P. This voltage is
calculated from three phase voltage input within the IED. The pre-processing block calculates -U2
from the first three inputs into the pre-processing block by using the following formula:
1
UPol = -U 2 = - × (UL1 + a 2 × UL 2 + a × UL3 )
3
EQUATION2267 V2 EN-US
where:
UL1, UL2 and UL3 are fundamental frequency phasors of three individual phase voltages.
To use this all three phase-to-earth voltages must be connected to three IED VT inputs.
This phasor is used together with the phasor of the operating current, in order to determine the
direction to the fault (Forward/Reverse).To enable voltage polarizing the magnitude of polarizing
voltage must be bigger than a minimum level defined by setting UpolMin.
Note that –U2 is used to determine the location of the fault. This ensures the required inversion of the
polarizing voltage within the function.
The individual steps within the protection can be set as non-directional. When this setting is selected
it is then possible via function binary input BLKSTx (where x indicates the relevant step within the
protection) to provide external directional control (that is, torque control) by for example using one of
the following functions if available in the IED:
Each overcurrent stage uses Operating Quantity I2 (negative sequence current) as measuring
quantity. Every of the four overcurrent stage has the following built-in facilities:
• Operating mode (Off/ Non-directional /Forward / Reverse). By this parameter setting the
operating mode of the stage is selected. Note that the directional decision (Forward/Reverse) is
not made within the overcurrent stage itself. The direction of the fault is determined in common
“Directional Supervision Element” described in the next paragraph.
• Negative sequence current pickup value.
• Type of operating characteristic (Inverse or Definite Time). By this parameter setting it is
possible to select Inverse or definite time delay for negative sequence overcurrent function.
Most of the standard IEC and ANSI inverse characteristics are available. For the complete list of
available inverse curves, refer to Chapter "Inverse characteristics"
• Type of reset characteristic (Instantaneous / IEC Reset /ANSI reset).By this parameter setting it
is possible to select the reset characteristic of the stage. For the complete list of available reset
curves, refer to Chapter "Inverse characteristics"
• Time delay related settings. By these parameter settings the properties like definite time delay,
minimum operating time for inverse curves, reset time delay and parameters to define user
programmable inverse curve are defined.
• Multiplier for scaling of the set negative sequence current pickup value by external binary signal.
By this parameter setting it is possible to increase negative sequence current pickup value when
function binary input ENMULTx has logical value 1.
Simplified logic diagram for one negative sequence overcurrent stage is shown in the following
figure:
BLKTR
Characteristx=DefTime AND
TRx
|IOP| AND
tx
a OR
a>b
ENMULTx b
STx
IxMult AND
X T
Ix> F
txmin
BLKSTx AND
BLOCK
Inverse
Characteristx=Inverse
DirModex=Off OR STAGEx_DIR_Int
DirModex=Non-directional
DirModex=Forward
AND OR
FORWARD_Int
DirModex=Reverse
AND
REVERSE_Int
IEC09000683.vsd
IEC09000683 V3 EN-US
Figure 328: Simplified logic diagram for negative sequence overcurrent stage x , where x=1, 2, 3 or 4
NS4PTOC can be completely blocked from the binary input BLOCK. The start signals from
NS4PTOC for each stage can be blocked from the binary input BLKSTx. The trip signals from
NS4PTOC can be blocked from the binary input BLKTR.
At least one of the four negative sequence overcurrent steps must be set as
directional in order to enable execution of the directional supervision element and
the integrated directional comparison function.
The operating and polarizing quantity are then used inside the directional element, as shown in figure
329, to determine the direction of the fault.
Reverse
Area
AngleRCA Upol=-U2
Forward
Area
Iop = I2
IEC10000031-1-en.vsd
IEC10000031 V1 EN-US
• Directional element is internally enable to operate as soon as Iop is bigger than 40% of I>Dir
and the directional condition is fulfilled in set direction.
• Relay characteristic angle AngleRCA which defines the position of forward and reverse areas in
the operating characteristic.
Directional comparison step, built-in within directional supervision element, set NS4PTOC output
binary signals:
1. STFW=1 when tip of I2 phasor (operating quantity magnitude) is in forward area, see fig 329
(Operating quantity magnitude is bigger than setting I>Dir)
2. STRV=1 when tip of I2 phasor (operating quantity magnitude) is in the reverse area, see fig 329.
(Operating quantity magnitude is bigger than 60% of setting I>Dir)
These signals must be used for communication based fault teleprotection communication schemes
(permissive or blocking).
Simplified logic diagram for directional supervision element with integrated directional comparison
step is shown in figure 330:
|Iop|
a a>
STRV
b b REVERSE_Int
AND
0.6
X
a a>
STFW
I>Dir b b FORWARD_Int
AND
X
0.4
FWD
AND FORWARD_Int
AngleRCA
C h a r a c e ri s ti c
D i r e c ti o n a l
UPolMin
IPolMin
t
Iop
UPol
AND REVERSE_Int
RVS
STAGE1_DIR_Int
STAGE2_DIR_Int
STAGE3_DIR_Int OR
STAGE4_DIR_Int
BLOCK AND
IEC07000067-4.vsd
IEC07000067-4 V2 EN-US
Figure 330: Simplified logic diagram for directional supervision element with integrated directional comparison
step
GUID-E83AD807-8FE0-4244-A50E-86B9AF92469E v7
9.6.1 Identification
SEMOD172025-2 v4
In networks with high impedance earthing, the phase-to-earth fault current is significantly smaller
than the short circuit currents. Another difficulty for earth fault protection is that the magnitude of the
phase-to-earth fault current is almost independent of the fault location in the network.
Directional residual current can be used to detect and give selective trip of phase-to-earth faults in
high impedance earthed networks. The protection uses the residual current component 3I0 · cos φ,
where φ is the angle between the residual current and the residual voltage (-3U0), compensated with
a characteristic angle. Alternatively, the function can be set to strict 3I0 level with a check of angle φ.
Directional residual power can also be used to detect and give selective trip of phase-to-earth faults
in high impedance earthed networks. The protection uses the residual power component 3I0 · 3U0 ·
cos φ, where φ is the angle between the residual current and the reference residual voltage,
compensated with a characteristic angle.
A normal non-directional residual current function can also be used with definite or inverse time
delay.
A backup neutral point voltage function is also available for non-directional residual overvoltage
protection.
In an isolated network, that is, the network is only coupled to earth via the capacitances between the
phase conductors and earth, the residual current always has -90º phase shift compared to the
residual voltage (3U0). The characteristic angle is chosen to -90º in such a network.
In resistance earthed networks or in Petersen coil earthed, with a parallel resistor, the active residual
current component (in phase with the residual voltage) should be used for the earth fault detection. In
such networks, the characteristic angle is chosen to 0º.
As the amplitude of the residual current is independent of the fault location, the selectivity of the earth
fault protection is achieved by time selectivity.
When should the sensitive directional residual overcurrent protection be used and when should the
sensitive directional residual power protection be used? Consider the following:
• Sensitive directional residual overcurrent protection gives possibility for better sensitivity. The
setting possibilities of this function are down to 0.25 % of IBase, 1 A or 5 A. This sensitivity is in
most cases sufficient in high impedance network applications, if the measuring CT ratio is not
too high.
• Sensitive directional residual power protection gives possibility to use inverse time
characteristics. This is applicable in large high impedance earthed networks, with large
capacitive earth fault currents. In such networks, the active fault current would be small and by
using sensitive directional residual power protection, the operating quantity is elevated.
Therefore, better possibility to detect earth faults. In addition, in low impedance earthed
networks, the inverse time characteristic gives better time-selectivity in case of high zero-
resistive fault currents.
Phase
currents
IN
Phase-
Ground
voltages
UN
IEC13000013 V2 EN-US
Overcurrent functionality uses true 3I0, i.e. sum of GRPxL1, GRPxL2 and GRPxL3. For 3I0 to be
calculated, connection is needed to all three phase inputs.
Directional and power functionality uses IN and UN. If a connection is made to GRPxN this signal is
used, else if connection is made to all inputs GRPxL1, GRPxL2 and GRPxL3 the internally calculated
sum of these inputs (3I0 and 3U0) will be used.
SDEPSDE
I3P* TRIP
U3P* TRDIRIN
BLOCK TRNDIN
BLKTR TRUN
BLKTRDIR START
BLKNDN STDIRIN
BLKUN STNDIN
STUN
STFW
STRV
STDIR
UNREL
IEC07000032-2-en.vsd
IEC07000032 V2 EN-US
9.6.4 Signals
PID-3892-INPUTSIGNALS v7
PID-3892-OUTPUTSIGNALS v7
9.6.5 Settings
PID-3892-SETTINGS v7
The function is using phasors of the residual current and voltage. Group signals I3P and U3P
containing phasors of residual current and voltage which are taken from pre-processor blocks.
The sensitive directional earth fault protection has the following sub-functions included:
3I0
j = ang(3I0 ) - ang(3Uref )
-3U0 = Uref
3I0 × cosj
IEC06000648-4-en.vsd
IEC06000648 V4 EN-US
Uref
RCADir = −90 , ROADir = 90
3I0
3I0 ⋅ cos ϕ
−3U0
IEC06000649_3_en.vsd
IEC06000649 V3 EN-US
Trip from this function can be blocked from the binary input BLKTRDIR.
When the function picks up, binary output signals START and STDIRIN are activated. If the output
signals START and STDIRIN remain active for the set delay tDef the binary output signals TRIP and
TRDIRIN get activated. The trip from this sub-function has definite time delay.
ROADir is Relay Operating Angle. ROADir is identifying a window around the reference direction in
order to detect directionality. Figure 335 shows the restrictions made by the ROADir.
RCADir = 0o
3I0
Operate area
j
-3U0 = Uref
3I0 × cos j
ROADir
IEC06000650_2_en.vsd
IEC06000650 V2 EN-US
It is also possible to tilt the characteristic to compensate for current transformer angle error with a
setting RCAComp as shown in the Figure 336:
RCADir = 0º
Operate area
-3U0 =Uref
Instrument
transformer
angle error
RCAcomp
Characteristic after
angle compensation
IEC06000651-3-en.vsd
IEC06000651 V3 EN-US
φ is defined as the angle between the residual current 3I0 and the reference voltage (Uref = -3U0 e-
jRCA) compensated with the set characteristic angle RCADir (|φ=ang(3I )—ang(U )|). The function
0 ref
operates when 3I0 · 3U0 · cos φ gets larger than the set value SN>. Refer to the simplified logical
diagram in Figure 338.
For trip, the residual power 3I0 · 3U0 · cos φ, the residual current 3I0 and the release voltage 3U0,
shall be larger than the set levels (SN>, INRel> and UNRel>).
Trip from this function can be blocked from the binary input BLKTRDIR.
When the function picks up, binary output signals START and STDIRIN are activated. If the output
signals START and STDIRIN remain active for the set delay tDef or after the inverse time delay
(setting kSN) the binary output signals TRIP and TRDIRIN get activated.
The function shall indicate forward/reverse direction to the fault. Reverse direction is defined as 3I0 ·
3U0·cos (φ + 180°) ³ the set value.
This variant has the possibility of choice between definite time delay and inverse time delay.
RCADir = 0º
ROADir = 80º
Operate area
3I0
-3U0
IEC06000652-3-en.vsd
IEC06000652 V3 EN-US
Trip from this function can be blocked from the binary input BLKTRDIR.
When the function picks up, binary output signals START and STDIRIN are activated. If the output
signals START and STDIRIN remain active for the set delay tDef the binary output signals TRIP and
TRDIRIN get activated.
The function indicates forward/reverse direction to the fault. Reverse direction is defined as φ is
within the angle sector: RCADir + 180° ± ROADir
The non-directional function is using the calculated residual current, derived as sum of the phase
currents. This will give a better ability to detect cross-country faults with high residual current, also
when dedicated core balance CT for the sensitive earth fault protection will saturate.
This variant has the possibility of choice between definite time delay and inverse time delay
(TimeChar parameter). The inverse time delay shall be according to IEC 60255-3.
For trip, the residual current 3I0 shall be larger than the set level (INNonDir>).
Trip from this function can be blocked from the binary input BLKNDN.
When the function picks up, binary output signal STNDIN is activated. If the output signal STNDIN
remains active for the set delay tINNonDir or after the inverse time delay the binary output signals
TRIP and TRNDIN get activated.
In addition, there is also a separate non-directional residual over voltage protection, with its own
definite time delay tUN and set level UN>.
For trip, the residual voltage 3U0 shall be larger than the set level (UN>).
Trip from this function can be blocked from the binary input BLKUN.
When the function picks up, binary output signal STUN is activated. If the output signal STUN is
active for the set delay tUNNonDir, the binary output signals TRIP and TRUN get activated. A
simplified logical diagram of the total function is shown in Figure 338.
OpINNonDir> = On
STNDIN
&
INNonDir>
t
TRNDIN
TimeChar IN
OpUN> = On
STUN
&
UN>
tUN TRUN
t
OpMode = 3I0Cosfi
INRel>
tDef ³ TRDIRIN
t 1
OpMode = 3I03U0Cosfi
& &
SN>
t
³ S
1 N
STFW
RCADir Direction &
Detection
RCAComp Logic STRV
&
ROADir
DirMode = Forward
DirMode = Reverse
IEC06000653.vsd
IEC06000653 V4 EN-US
Figure 338: Simplified logical diagram of the sensitive earth fault current protection
SEMOD173350-2 v16
Independent time delay for non-directional (0.000 – 60.000) s ±0.2% or ± 75 ms whichever is greater
residual overcurrent at 0 to 2 x Iset
Independent time delay for directional (0.000 – 60.000) s ±0.2% or ± 170 ms whichever is
residual overcurrent at 0 to 2 x Iset greater
Inverse characteristics, see table 1297, 16 curve types See Table 1297, Table 1298 and Table
Table 1298 and Table 1299 1299
Relay characteristic angle (RCADir) (-179 to 180) degrees ±2.0 degrees
Relay operate angle (ROADir) (0 to 90) degrees ±2.0 degrees
9.7.1 Identification
M17106-1 v7
The increasing utilization of the power system closer to the thermal limits has generated a need of a
thermal overload protection for power lines.
A thermal overload will often not be detected by other protection functions and the introduction of the
thermal overload protection can allow the protected circuit to operate closer to the thermal limits.
The three-phase current measuring protection has an I2t characteristic with settable time constant
and a thermal memory. The temperature is displayed in either Celsius or Fahrenheit, depending on
whether the function used is Thermal overload protection (LCPTTR) (Celsius) or (LFPTTR)
(Fahrenheit).
An alarm level gives early warning to allow operators to take action well before the line is tripped.
Estimated time to trip before operation, and estimated time to reclose after operation are presented.
LCPTTR
I3P* TRIP
BLOCK START
BLKTR ALARM
ENMULT LOCKOUT
AMBTEMP
SENSFLT
RESET
IEC13000199-1-en.vsd
IEC13000199 V1 EN-US
LFPTTR
I3P* TRIP
BLOCK START
BLKTR ALARM
ENMULT LOCKOUT
AMBTEMP
SENSFLT
RESET
IEC13000301-1-en.vsd
IEC13000301 V1 EN-US
9.7.4 Signals
PID-3908-INPUTSIGNALS v7
PID-3909-INPUTSIGNALS v9
PID-3908-OUTPUTSIGNALS v7
PID-3909-OUTPUTSIGNALS v8
9.7.5 Settings
PID-3908-SETTINGS v7
PID-3909-SETTINGS v8
PID-3909-MONITOREDDATA v7
The sampled analog phase currents are pre-processed and for each phase current the RMS value is
derived. These phase current values are fed to the thermal overload protection, one time constant
LCPTTR/LFPTTR function. The temperature is displayed either in Celsius or Fahrenheit, depending
on whether LCPTTR/LFPTTR function is selected.
From the largest of the three-phase currents a final temperature is calculated according to the
expression:
2
æ I ö
Q final =ç ÷÷ × Tref
ç I ref
è ø
EQUATION1167 V1 EN-US (Equation 158)
where:
I is the largest phase current,
Iref is a given reference current and
The ambient temperature is added to the calculated final temperature. If this temperature is larger
than the set operate temperature level, TripTemp, a START output signal is activated.
æ Dt
ö
Qn = Qn -1 + ( Q final - Q n-1 ) × ç1 - e t ÷
-
è ø
EQUATION1168 V1 EN-US (Equation 159)
where:
Qn is the calculated present temperature,
The actual temperature of the protected component (line or cable) is calculated by adding the
ambient temperature to the calculated temperature, as shown above. The ambient temperature can
be taken from a separate sensor or can be given a constant value. The used ambient temperature is
available as a real figure signal, TEMPAMB. The calculated component temperature is available as a
real figure signal, TEMP. The temperature of the component compared to the setting TripTemp is also
available as a real figure signal, TERMLOAD which indicates the thermal status compared to the trip
level.
When the component temperature reaches the set alarm level AlarmTemp the output signal ALARM
is set. When the component temperature reaches the set trip level TripTemp the output signal TRIP is
set.
There is also a calculation of the present time to operate with the present current. This calculation is
only performed if the final temperature is calculated to be above the operation temperature:
æQ - Qoperate ö
toperate = -t × ln ç final
ç Q final - Q n ÷÷
è ø
EQUATION1169 V1 EN-US (Equation 160)
After a trip, caused by the thermal overload protection, there can be a lockout to reconnect the
tripped circuit. The output lockout signal LOCKOUT is activated when the device temperature is
above the set lockout release temperature setting ReclTemp.
The time to lockout release is calculated by the following cooling time calculation. The thermal
content of the function can be reset with input RESET.
æQ - Qlockout _ release ö
tlockout _ release = -t × ln ç final ÷÷
ç Q final - Q n
è ø
EQUATION1170 V1 EN-US (Equation 161)
In the above equation, the final temperature is equal to the set or measured ambient temperature.
The calculated time to reset of lockout is available as a real figure signal, TENRECL. This signal is
enabled when the LOCKOUT output is activated.
In some applications the measured current can involve a number of parallel lines. This is often used
where one bay connects several parallel cables. By setting the parameter IMult to the number of
parallel lines (cables) the actual current on one line is used in the protection algorithm by dividing the
measured current by the total number of cables. To activate this option the input ENMULT must be
activated.
The protection has a reset input: RESET. By activating this input the calculated temperature is reset
to its default initial value. This is useful during testing when secondary injected current has given a
calculated “false” temperature level.
START
Final Temp > Trip Temp
TEMP
Calculation of actual
temperature
AMBTEMP ALARM
Actual Temp > Alarm Temp
I3P
Calculation of final
temperature
ENMULT
TRIP
LOCKOUT
Lockout logic
TTRIP
Calculation of time to trip
BLKTR
TENRECL
Calculation of time to reset
of lockout
IEC09000637-2-en.vsd
IEC09000637 V2 EN-US
9.8.1 Identification
M14877-1 v2
SYMBOL-A V1 EN-US
If a power transformer reaches very high temperatures the equipment might be damaged. The
insulation within the transformer will experience forced ageing. As a consequence of this the risk of
internal phase-to-phase or phase-to-earth faults will increase.
The thermal overload protection (TRPTTR) estimates the internal heat content of the transformer
(temperature) continuously. This estimation is made by using a thermal model of the transformer with
two time constants, which is based on current measurement.
Two warning levels are available. This enables actions in the power system to be done before
dangerous temperatures are reached. If the temperature continues to increase to the trip value, the
protection initiates a trip of the protected transformer.
TRPTTR
I3P* TRIP
BLOCK START
COOLING ALARM1
ENMULT ALARM2
RESET LOCKOUT
WARNING
IEC06000272_2_en.vsd
IEC06000272 V2 EN-US
9.8.4 Signals
PID-4148-INPUTSIGNALS v4
PID-4148-OUTPUTSIGNALS v4
9.8.5 Settings
PID-6862-SETTINGS v1
The sampled analog phase currents are pre-processed and for each phase current the true RMS
value of each phase current is derived. These phase current values are fed to the protection function.
From the largest of the three phase currents a relative final temperature (heat content) is calculated
according to the expression:
2
æ I ö
Q final =ç ÷÷
ç I ref
è ø
EQUATION1171 V1 EN-US (Equation 163)
where:
I is the largest phase current
Iref is a given reference current
If this calculated relative temperature is larger than the relative temperature level corresponding to
the set operate (trip) current, then the start output signal START will be activated.
If Q final > Q n
EQUATION1172 V1 EN-US (Equation 164)
æ Dt
ö
Qn = Qn -1 + ( Q final - Q n-1 ) × ç1 - e t ÷
-
è ø
EQUATION1173 V1 EN-US (Equation 165)
If Q final < Qn
EQUATION1174 V1 EN-US (Equation 166)
Dt
Qn = Q final - ( Q final - Qn -1 ) × e
-
t
where:
Qn is the calculated present temperature
Q final is the calculated final (steady state) temperature with the actual current
Dt is the time step between calculation of the actual and final temperature
t is the thermal time constant of the protected circuit given in minutes. There are different time
constants depending on the cooling used. Please refer to manufacturer's manuals for details
The calculated transformer relative temperature can be monitored and it is exported from the function
as a real figure HEATCONT.
When the transformer temperature reaches any of the set alarm levels Alarm1 or Alarm2 the
corresponding output signal ALARM1 or ALARM2 is activated. When the temperature of the object
reaches the set trip level which corresponds to continuous current equal to ITrip the output signal
TRIP is activated.
There is also a calculation of the time to operation with the present current. This calculation is only
performed if the final temperature is calculated to be above the operation temperature:
æQ - Qoperate ö
toperate = -t × ln ç final
ç Q final - Q n ÷÷
è ø
EQUATION1176 V1 EN-US (Equation 168)
The calculated time to trip can be monitored and it is exported from the function as an integer output
TTRIP.
After a trip there can be a lockout to inhibit reconnecting the tripped circuit. The output lockout signal
LOCKOUT is activated when the temperature of the object is above the set lockout release
temperature setting ResLo.
The time to lockout release is calculated by the following cooling time calculation.
æQ - Qlockout _ release ö
tlockout _ release = -t × ln ç final ÷÷
ç Q final - Q n
è ø
EQUATION1177 V1 EN-US (Equation 169)
In the above equation, the final temperature is calculated according to equation 163. The calculated
component temperature can be monitored as it is exported from the function as a real figure,
TRESLO.
When the current is so high that it has given a start signal START, the estimated time to trip is
continuously calculated and given as analogue output TTRIP. If this calculated time get less than the
setting time Warning, set in minutes, the output WARNING is activated.
RESET HEATCONT
Calculation
of heat
content
I3P
Calculation
ENMULT of final
temperature
ALARM1
Actual Temp >
Alarm1,Alarm2
ALARM2
Temp
S LOCKOUT
Management of R
COOLING setting
parameters: Tau,
Actual Temp
IBase Tau used
< Recl
Temp
TTRIP
Calculation
of time to
WARNING
trip
Calculation
of time to TRESCAL
reset of
lockout
IEC05000833-2-en.vsd
IEC05000833 V2 EN-US
M13266-2 v9
Reset level temperature (10–95)% of heat content trip ±2.0% of heat content trip
9.9.2 Identification
M14878-1 v5
SYMBOL-U V1 EN-US
Breaker failure protection (CCRBRF) ensures a fast backup tripping of the surrounding breakers in
case the own breaker fails to open. CCRBRF measurement criterion can be current based, CB
position based or an adaptive combination of these two conditions.
A current based check with extremely short reset time is used as check criterion to achieve high
security against inadvertent operation.
CB position check criteria can be used where the fault current through the breaker is small.
CCRBRF provides three different options to select how t1 and t2 timers are run:
CCRBRF can be single- or three- phase initiated to allow its use with single phase tripping
applications. For the three-phase application of the CCRBRF the current criteria can be set to
operate only if “2 elements operates out of three phases and neutral” for example; two phases or one
phase plus the residual current start. This gives a higher security to the backup trip command.
The CCRBRF function can be programmed to give a single- or three- phase retrip to its own breaker
to avoid unnecessary tripping of surrounding breakers at an incorrect initiation due to mistakes during
testing.
CCRBRF
I3P* TRBU
BLOCK TRBU2
START TRRET
STL1 TRRETL1
STL2 TRRETL2
STL3 TRRETL3
CBCLDL1 CBALARM
CBCLDL2 STALARM
CBCLDL3
CBFLT
IEC18001006-1-en.vsd
IEC18001006 V1 EN-US
9.9.5 Signals
PID-7233-INPUTSIGNALS v1
PID-7233-OUTPUTSIGNALS v1
9.9.6 Settings
PID-7233-SETTINGS v1
Breaker failure protection CCRBRF is initiated from the protection trip command, either from
protection functions within the IED or from external protection devices.
To this function the three-phase current input and/or change to: the breaker normally open auxiliary
contact (i.e. "52a" or "closed") shall be connected. On OHL feeders where single pole auto-reclosing
is used, auxiliary contact from each CB pole shall be connected separately
The input START signal (i.e. initiate signal) can be phase selective or common (for all three phases).
Phase selective start signals enable single pole retrip functionality. This means that a second attempt
to open the same breaker can be done phase-selective. The retrip attempt is made after a set time
delay t1. For transmission lines, single pole trip and auto-reclosing is often used. The retrip function
can be phase selective if it is initiated from the phase selective line protection.
The retrip function can be done with or without FunctionMode check. With this check, the retrip is
only performed if the circuit breaker is still seen as closed when t1 timer has elapsed.
The START signal will also start the backup trip timer. The function detects the successful breaker
opening, either by detection of low current through RMS evaluation and a special adapted current
algorithm or by monitoring the circuit breaker status using normally open auxiliary contact from the
breaker. The special algorithm enables a very fast detection of successful breaker opening, which is,
fast resetting of the current measurement. If the function has not detected breaker opening before
the backup timer has run-out its time a backup trip is initiated.
• Three phase (i.e. common) start/initiation via input START or individual start/initiation per phase
by using phase segregated inputs STLx.
• The minimum length of the retrip pulse, the backup trip pulse and the second backup trip pulse
are settable. This pulse duration is defined by a parameter setting tPulse. The retrip pulse, the
backup trip pulse and the second backup trip pulse will however sustain as long as there is an
indication of closed breaker.
• If the current detection is used it is possible to use three different options: 1 out of 3 where it is
sufficient to detect failure to open (high current) in one pole, 1 out of 4 where it is sufficient to
detect failure to open (high current) in one pole or high residual current and 2 out of 4 where at
least two currents (phase current and/or residual current) shall be high for breaker failure
detection.
• The current detection level for the residual current can be set different from the setting of phase
current detection.
• It is possible to have different backup time delays for single-phase faults and for multi-phase
faults.
• It is possible to have instantaneous backup trip function if the circuit breaker is incapable to clear
faults, for example, at low gas pressure. This will happen when input signal CBFLT has logical
value one and timer tCBAlarm has expired. This situation will be indicated via output signal
CBALARM.
The selection of measurement criterion is done with setting parameter FunctionMode, to determine if
the breaker has opened or not:
• Option 1 - Current: Compares the measured phase current magnitude to setting IPh> (operate
phase current level in % of IBase), and the measured residual current magnitude to setting IN>
(Operate residual current level in % of IBase). Criterion is active (i.e. breaker did not open yet) if
the measured current magnitudes are higher than the set values.
• Option 2 - CB Pos: This criterion is active (i.e. breaker did not open yet in phase Lx) if the binary
input CBCLDLx has logical value one. Thus function simply follows the status of CB pole
normally open auxiliary contact (i.e. "52a" or "closed") which shall be connected to this input.
If TRBU has been given and CBCLDLx still has value one, TRBU and TRRET will internally be
reset intentionally after approximately 10 seconds. Another way of resetting TRBU and TRRET
is either to shortly activate BLOCK input or setting CCRBRF to blocked when the IED is in
TestMode.
• Option 3 - Current or CB Pos: It uses a combination of Current or CB Pos criteria. Note that
Current criterion will be then always used, while the CB Pos criterion will be only enabled and
used if current is smaller than set value I>BlkCBPos at the moment when external START signal
has been received. It is recommended to set value for I>BlkCBPos higher than the set value for
IPh>.
If TRBU has been given and CBCLDLx still has value one and if the CB Pos criterion is
used,TRBU and TRRET will internally be reset intentionally after approximately 10 seconds.
Another way of resetting TRBU and TRRET is either to shortly activate BLOCK input or setting
CCRBRF to blocked when the IED is in TestMode.
By the setting StartMode it is possible to select how t1 and t2 timers are run and consequently how
output commands are given from the function:
When one of the two “follow modes” is used, there is a settable timer tStartTimeout which will block
the external START input signal when it times-out. This will automatically also reset the t1 and t2
timers and consequently prevent any backup trip command. At the same time the STALARM output
from the function will have logical value one. To reset this signal external START signal shall be
removed. This is done in order to prevent unwanted operation of the breaker failure function for
cases where a permanent START signal is given by mistake (e.g. due to a fault in the station battery
system). Note that any backup trip command will inhibit running of tStartTimeout timer.
The BLOCK signal overrides any StartMode condition and resets START signal, running of t1 and t2
timers and all function outputs.
30ms t1 30ms
START OR TRRET
S Q t AND
t2 30ms
OR TRBU
t AND
Current Check
CB Position Check OR
150ms
AND
t
NOT
IEC18001002-1-en.vsdx
IEC18001002 V1 EN-US
t1
START OR TRRET
t AND
Current Check
CB Position Check OR
t2
TRBU
t AND
OR
IEC18001003-1-en.vsdx
IEC18001003 V1 EN-US
START t1 TRRET
AND t
Current Check
CB Position Check OR t2 TRBU
t
IEC18001004-1-en.vsdx
IEC18001004 V1 EN-US
Note that it is possible to set several timers for the backup trip as described below:
1. Timer t2 is used when function is started in one phase only (i.e. for single-phase to ground fault
on an OHL (Over Head Lines) when single-pole auto-reclosing is used).
2. Timer t2MPh is used when function is started in at least two phases. This will allow to have
shorter backup trip times for a multi-phase fault on an OHL Note that for a protected object
which are always tripped three-phase (e.g. transformers, generators, reactors, cables, etc.) this
timer shall always be set to the same value as t2 timer.
3. Timer t3 can be used to give a second backup trip command. It can be used in stations having
small DC battery which is not capable to trip all surrounding breakers at once. Note that t3 timer
will only start when t2 timer expires.
• Off: The retrip command to the own circuit breaker is permanently disabled.
• UseFunctionMode: Retrip command to the own circuit breaker is given only if measurement
criterion defined by setting parameter FunctionMode is still active when set timer t1 expires (e.g.
if FunctionMode=Current and current magnitude is higher than set value IPh> when t1 expires,
the retrip command will be issued).
• Always: Retrip command to the own circuit breaker is given always when set timer t1 expires
without any further checks.
The simplified logic for the function is given in the following figures.
StartMode
LatchedStart
FollowStart
1 FollowStart&Mode OR
START 30ms
int startL1
STL1 OR AND S Q
BLOCK
NOT
int reset
OR R
NOT
TRBU
NOT int startAlarmL1
tStartTimeout
AND t NOT
AND AND int startAlarmL2 STALARM
From other OR
phases int startAlarmL3
IEC18001005-1-en.vsdx
IEC18001005 V1 EN-US
Figure 347: Start logic for all three Function Modes of operation
IL1
a
a>b NOT
IPh> b
FunctionMode
Current
CB Pos OR AND int reset
OR
1
Current or CB Pos 150 ms
int startL1
t
OR AND
t1
t
t2
t OR
t2MPh
t
AND
CBCLDL1
NOT
IEC18001007-1-en.vsdx
IEC18001007 V1 EN-US
StartMode
LatchedStart
FollowStart
1 FollowStart&Mode OR AND
int retrip
currPh1Check
CB Position Check OR
AND t1 30ms
OR AND
int startL1 t OR
t1
t
BLOCK
RetripMode
Off tPulse
TRRETL1
UseFunctionMode AND OR AND
1
Always
TRRETL2 TRRET
TRRETL3
OR
tPulse
From other
AND phases
IEC18001008-2-en.vsdx
IEC18001008 V2 EN-US
StartMode
LatchedStart
1 FollowStart
FollowStart&Mode OR AND
currCheck
CB Position Check OR
backupTripL1
t2
AND t 30ms
OR AND
OR OR
int startL1
BLOCK
t3
t TRBU2
OR
AND
tPulse
IEC18001009 V2 EN-US
When the function Start mode is set to LatchedStart and the function mode is set CB Pos, Re-trip,
and Backup trip will internally operate and latch. To reset these two signals the breaker position has
to indicate that the CB is open.
To avoid continuous lockout of Re-trip and Back up trip signals, the signals are rested internally
under the following conditions:
1. When the function blocking input is activated breaker position input (CBCLDLxx) will internally
be forced to zero in all phases (that is simulating that CB is open), which will reset Re-
trip(TRRET) and back up trip (TRBU) output signals.
2. If TRBU is active for 10 seconds, then the activated breaker position input (CBCLDLxx) will
internally be forced to zero which will reset both RETRIP and TRBU.
3. When using FunctionMode=Current/CB pos, the same behavior is applicable only when the CB
pos part is active; that is, when the measured current is below the set value I>BlkCBPos.
M12353-1 v15
Additional time delay for a second backup trip at (0.000-60.000) s ±0.2% or ±20 ms whichever is
0 to 2 x Iset greater
Time delay for alarm for faulty circuit breaker (0.000-60.000) s ±0.2% or ±15 ms whichever is
greater
Minimum trip pulse duration (0.010-60.000) s ±0.2% or ±5 ms whichever is greater
* Valid for product version 2.2.3 or later
9.10.2 Identification
M17108-1 v2
3I>STUB
SYMBOL-T V1 EN-US
When a power line is taken out of service for maintenance and the line disconnector is opened in
multi-breaker arrangements the voltage transformers will mostly be outside on the disconnected part.
The primary line distance protection will thus not be able to operate and must be blocked.
The stub protection (STBPTOC) covers the zone between the current transformers and the open
disconnector. The three-phase instantaneous overcurrent function is released from a normally
closed, NC (b) auxiliary contact on the line disconnector.
STBPTOC
I3P* TRIP
BLOCK START
BLKTR
RELEASE
IEC05000678-2-en.vsd
IEC05000678 V2 EN-US
9.10.5 Signals
PID-7754-INPUTSIGNALS v1
PID-7754-OUTPUTSIGNALS v1
9.10.6 Settings
PID-7754-SETTINGS v1
The sampled analog phase currents are pre-processed in a discrete Fourier filter (DFT) block. From
the fundamental frequency components of each phase current the RMS value of each phase current
is derived. These phase current values are fed to a comparator in the stub protection function
STBPTOC. In a comparator the RMS values are compared to the set operating current value of the
function I>.
If a phase current is larger than the set operating current the signal from the comparator for this
phase is activated. This signal will, in combination with the release signal from either line
disconnector (RELEASE input) and ReleaseMode is set to Release or ReleaseMode is set to
Continuous activates START signal and timer tDelay. The output signal TRIP activates, if the fault
current remains during the set timer tDelay.
The function can be blocked by activation of the BLOCK input. Also, activation of BLKTR resets TRIP
output.
BLOCK
I3P* IL1
a
IL2 a>b
IL3 b
AND
START
1
a
a>b tDelay
b TRIP
AND t AND
a
a>b
I> b
AND
RELEASE
AND
ReleaseMode = Release 1
ReleaseMode = Continuous
BLKTR
IEC05000731 V2 EN-US
From the measured three-phase currents, various types of measurement modes such as DFT, Peak,
and Peak-to-peak can be selected for the BRPTOC operation.
Peak and Peak-to-Peak measurement mode allow this function to be used as instantaneous over-
current protection as well. If required by application, short time delay can also be applied.
BRPTOC can be used for different line and transformer protection applications. If required, it can also
be used to supervise on-load tap-changer operation.
9.11.5 Signals
PID-7755-INPUTSIGNALS v1
PID-7755-OUTPUTSIGNALS v1
9.11.6 Settings
PID-7755-SETTINGS v1
Using a parameter setting MeasType within the general settings for the function BRPTOC, it is
possible to select the type of the measurements such as DFT, Peak, and Peak-to-peak used for
overcurrent operation.
If the DFT option is selected, only the RMS value of the fundamental frequency component of each
phase current is derived. The influence of the DC current component and higher harmonic current
components are completely suppressed.
The peak-to-peak measurement efficiently suppers the DC current component from the measured
phase currents. On the contrary, when Peak measurement mode is selected, it allows the DC current
component into the measurement signal for the BRPTOC function.
If the Peak/Peak-to-peak option is selected, RMS equivalent phase currents are derived and
therefore, the set value of I> is remained intact irrespective of any type of the measurement mode.
These phase current values are fed to a comparator in the overcurrent protection with binary release
function BRPTOC. In a comparator, the RMS values are compared to the set operating current value
of the function I>.
If a phase current is larger than the set operating current, comparator output signal for this phase will
be high. This signal will, in combination with the release signal (RELEASE input), activate the timer
for the TRIP signal. If the current magnitude remains high during the timer tdelay, the TRIP output
signal is activated. The function can be blocked by activation of the BLOCK input.
I3P* IL1
a
IL2 a>b
IL3 b STL1
AND
a
a>b
b STL2
AND
a
a>b
I> b STL3
AND
RELEASE START
1
BLOCK
tDelay
TRIP
t AND
BLKTR
GUID-CAC3BE85-59F2-4264-A060-CA53DF9CA3E8 V1 EN-US
Figure 353: Simplified logic diagram for overcurrent protection with binary release
Peak to peak:
5 ms typically at 0 to 2 x Iset
Peak:
1 ms typically at 0 to 2 x Iset
9.12.1 Identification
M14888-1 v4
PD
SYMBOL-S V1 EN-US
An open phase can cause negative and zero sequence currents which cause thermal stress on
rotating machines and can cause unwanted operation of zero sequence or negative sequence
current functions.
Normally the own breaker is tripped to correct such a situation. If the situation persists the
surrounding breakers should be tripped to clear the unsymmetrical load situation.
The Pole discordance protection function (CCPDSC) operates based on information from auxiliary
contacts of the circuit breaker for the three phases with additional criteria from unsymmetrical phase
currents when required.
CCPDSC
I3P* TRIP
BLOCK START
BLKDBYAR
CLOSECMD
OPENCMD
EXTPDIND
POLE1OPN
POLE1CL
POLE2OPN
POLE2CL
POLE3OPN
POLE3CL
IEC13000305-1-en.vsd
IEC13000305 V1 EN-US
9.12.4 Signals
PID-3525-INPUTSIGNALS v8
PID-3525-OUTPUTSIGNALS v8
9.12.5 Settings
PID-3525-SETTINGS v8
circuit breaker
en05000287.vsd
IEC05000287 V2 EN-US
There is also a possibility to connect all phase selective auxiliary contacts (phase contact open and
phase contact closed) to binary inputs of the IED, see figure 356.
C.B.
+
poleOneOpened from C.B.
en05000288.vsd
IEC05000288 V1 EN-US
Pole discordance can also be detected by means of phase selective current measurement. The
sampled analog phase currents are pre-processed in a discrete Fourier filter (DFT) block. From the
fundamental frequency components of each phase current the RMS value of each phase current is
derived. The smallest and the largest phase current are derived. If the smallest phase current is
lower than the setting CurrUnsymLevel times the largest phase current the settable trip timer (tTrip) is
started. The tTrip timer gives a trip signal after the set delay. The TRIP signal is a pulse 150 ms long.
The current based pole discordance function can be set to be active either continuously or only
directly in connection to breaker open or close command.
The function also has a binary input that can be configured from the autoreclosing function, so that
the pole discordance function can be blocked during sequences with a single pole open if single pole
autoreclosing is used.
M13946-3 v7
The simplified block diagram of the current and contact based Pole discordance protection function
CCPDSC is shown in figure 357.
BLOCK
OR
BLKDBYAR
PolPosAuxCont
AND
POLE1OPN
POLE1CL
POLE2OPN
Discordance
POLE2CL
detection
POLE3OPN
POLE3CL t 150 ms
t TRIP
AND
OR
PD Signal from CB
AND
EXTPDIND
CLOSECMD t+200 ms
OR
OPENCMD
AND
Unsymmetry current
detection
en05000747.vsd
IEC05000747 V1 EN-US
Figure 357: Simplified block diagram of pole discordance function CCPDSC - contact and
current based
CCPDSC is blocked if:
• The IED is in TEST mode and CCPDSC has been blocked from the local HMI
• The input signal BLOCK is high
• The input signal BLKDBYAR is high
The BLOCK signal is a general purpose blocking signal of the pole discordance protection. It can be
connected to a binary input in the IED in order to receive a block command from external devices or
can be software connected to other internal functions in the IED itself in order to receive a block
command from internal functions. Through OR gate it can be connected to both binary inputs and
internal function outputs.
The BLKDBYAR signal blocks the pole discordance operation when a single phase autoreclosing
cycle is in progress. It can be connected to the output signal 1PT1 on SMBRRECfunction block. If the
autoreclosing function is an external device, then BLKDBYAR has to be connected to a binary input
in the IED and this binary input is connected to a signalization “1phase autoreclosing in progress”
from the external autoreclosing device.
If the pole discordance protection is enabled, then two different criteria can generate a trip signal
TRIP:
If one or two poles of the circuit breaker have failed to open or to close the pole discordance status,
then the function input EXTPDIND is activated from the pole discordance signal derived from the
circuit breaker auxiliary contacts (one NO contact for each phase connected in parallel, and in series
with one NC contact for each phase connected in parallel) and, after a settable time interval tTrip
(0-60 s), a 150 ms trip pulse command TRIP is generated by the Polediscordance function.
• any phase current is lower than CurrUnsymLevel of the highest current in the three phases.
• the highest phase current is greater than CurrRelLevel of IBase.
If these conditions are true, an unsymmetrical condition is detected and the internal signal INPS is
turned high. This detection is enabled to generate a trip after a set time delay tTrip if the detection
occurs in the next 200 ms after the circuit breaker has received a command to open trip or close and
if the unbalance persists. The 200 ms limitation is for avoiding unwanted operation during
unsymmetrical load conditions.
The pole discordance protection is informed that a trip or close command has been given to the
circuit breaker through the inputs CLOSECMD (for closing command information) and OPENCMD
(for opening command information). These inputs can be connected to terminal binary inputs if the
information are generated from the field (that is from auxiliary contacts of the close and open push
buttons) or may be software connected to the outputs of other integrated functions (that is close
command from a control function or a general trip from integrated protections).
9.13.1 Identification
SEMOD158941-2 v4
The task of a generator in a power plant is to convert mechanical energy available as a torque on a
rotating shaft to electric energy.
Sometimes, the mechanical power from a prime mover may decrease so much that it does not cover
bearing losses and ventilation losses. Then, the synchronous generator becomes a synchronous
motor and starts to take electric power from the rest of the power system. This operating state, where
individual synchronous machines operate as motors, implies no risk for the machine itself. If the
generator under consideration is very large and if it consumes lots of electric power, it may be
desirable to disconnect it to ease the task for the rest of the power system.
Often, the motoring condition may imply that the turbine is in a very dangerous state. The task of the
low forward power protection is to protect the turbine and not to protect the generator itself.
Figure 358 illustrates the low forward power and reverse power protection with underpower and
overpower functions respectively. The underpower IED gives a higher margin and should provide
better dependability. On the other hand, the risk for unwanted operation immediately after
synchronization may be higher. One should set the underpower IED to trip if the active power from
the generator is less than about 2%. One should set the overpower IED to trip if the power flow from
the network to the generator is higher than 1% depending on the type of turbine.
When IED with a metering class input CTs is used pickup can be set to more sensitive value
(e.g.0,5% or even to 0,2%).
Operate
Q Q
Operate
Line Line
Margin Margin
P P
IEC06000315-2-en.vsd
IEC06000315 V2 EN-US
GUPPDUP
I3P* TRIP
U3P* TRIP1
BLOCK TRIP2
BLOCK1 START
BLOCK2 START1
START2
P
PPERCENT
Q
QPERCENT
IEC07000027-2-en.vsd
IEC07000027 V2 EN-US
9.13.4 Signals
PID-3709-INPUTSIGNALS v6
PID-3709-OUTPUTSIGNALS v6
9.13.5 Settings
PID-3709-SETTINGS v6
Chosen current
phasors P
P = POWRE
Q = POWIM
IEC09000018-2-en.vsd
IEC09000018 V2 EN-US
The active and reactive power is available from the function and can be used for monitoring and fault
recording.
The component of the complex power S = P + jQ in the direction Angle1(2) is calculated. If this angle
is 0° the active power component P is calculated. If this angle is 90° the reactive power component Q
is calculated.
The calculated power component is compared to the power pick up setting Power1(2). For directional
underpower protection, a start signal START1(2) is activated if the calculated power component is
smaller than the pick up value. For directional overpower protection, a start signal START1(2) is
activated if the calculated power component is larger than the pick up value. After a set time delay
TripDelay1(2) a trip TRIP1(2) signal is activated if the start signal is still active. At activation of any of
the two stages a common signal START will be activated. At trip from any of the two stages also a
common signal TRIP will be activated.
To avoid instability there is a settable hysteresis in the power function. The absolute hysteresis of the
stage1(2) is Hysteresis1(2) = abs (Power1(2) + drop-power1(2)). For generator low forward power
protection the power setting is very low, normally down to 0.02 p.u. of rated generator power. The
hysteresis should therefore be set to a smaller value. The drop-power value of stage1 can be
calculated with the Power1(2), Hysteresis1(2): drop-power1(2) = Power1(2) + Hysteresis1(2)
For small power1 values the hysteresis1 may not be too big, because the drop-power1(2) would be
too small. In such cases, the hysteresis1 greater than (0.5 · Power1(2)) is corrected to the minimal
value.
If the measured power drops under the drop-power1(2) value, the function will reset after a set time
DropDelay1(2). The reset means that the start signal will drop out and that the timer of the stage will
reset.
In order to minimize the influence of the noise signal on the measurement it is possible to introduce a
recursive, low pass filtering of the measured values for S (P, Q). This will make slower measurement
response to the step changes in the measured quantity. Filtering is performed in according to the
following recursive formula:
S = k × SOld + (1 - k ) × SCalculated
EQUATION1959 V1 EN-US (Equation 180)
Where
S is a new measured value to be used for the protection function
Sold is the measured value given from the function in previous execution cycle
k is settable parameter by the end user which influence the filter properties
TD
Default value for parameter k is 0.00. With this value the new calculated value is immediately given
out without any filtering (that is without any additional delay). When k is set to value bigger than 0,
the filtering is enabled. A typical value for k=0.92 in case of slow operating functions.
Measured currents and voltages used in the Power function can be calibrated to get class 0.5
measuring accuracy. This is achieved by amplitude and angle compensation at 5, 30 and 100% of
rated current and voltage. The compensation below 5% and above 100% is constant and linear in
between, see example in figure 361.
IEC05000652 V2 EN-US
Analog outputs (Monitored data) from the function can be used for service values or in the
disturbance report. The active power is provided as MW value: P, or in percent of base power:
PPERCENT. The reactive power is provided as Mvar value: Q, or in percent of base power:
QPERCENT.
SEMOD175152-2 v11
S r = 1.732 × U r × I r
9.14.1 Identification
SEMOD176574-2 v4
The task of a generator in a power plant is to convert mechanical energy available as a torque on a
rotating shaft to electric energy.
Sometimes, the mechanical power from a prime mover may decrease so much that it does not cover
bearing losses and ventilation losses. Then, the synchronous generator becomes a synchronous
motor and starts to take electric power from the rest of the power system. This operating state, where
individual synchronous machines operate as motors, implies no risk for the machine itself. If the
generator under consideration is very large and if it consumes lots of electric power, it may be
desirable to disconnect it to ease the task for the rest of the power system.
Often, the motoring condition may imply that the turbine is in a very dangerous state. The task of the
reverse power protection is to protect the turbine and not to protect the generator itself.
Figure 362 illustrates the low forward power and reverse power protection with underpower and
overpower functions respectively. The underpower IED gives a higher margin and should provide
better dependability. On the other hand, the risk for unwanted operation immediately after
synchronization may be higher. One should set the underpower IED to trip if the active power from
the generator is less than about 2%. One should set the overpower IED to trip if the power flow from
the network to the generator is higher than 1%.
When IED with a metering class input CTs is used pickup can be set to more sensitive value
(e.g.0,5% or even to 0,2%).
Operate
Q Q
Operate
Line Line
Margin Margin
P P
IEC06000315-2-en.vsd
IEC06000315 V2 EN-US
Figure 362: Reverse power protection with underpower IED and overpower IED
GOPPDOP
I3P* TRIP
U3P* TRIP1
BLOCK TRIP2
BLOCK1 START
BLOCK2 START1
START2
P
PPERCENT
Q
QPERCENT
IEC07000028-2-en.vsd
IEC07000028 V2 EN-US
9.14.4 Signals
PID-3710-INPUTSIGNALS v7
PID-3710-OUTPUTSIGNALS v7
9.14.5 Settings
PID-3710-SETTINGS v7
Chosen current
phasors P
P = POWRE
Q = POWIM
IEC06000567-2-en.vsd
IEC06000567 V2 EN-US
The active and reactive power is available from the function and can be used for monitoring and fault
recording.
The component of the complex power S = P + jQ in the direction Angle1(2) is calculated. If this angle
is 0° the active power component P is calculated. If this angle is 90° the reactive power component Q
is calculated.
The calculated power component is compared to the power pick up setting Power1(2). A start signal
START1(2) is activated if the calculated power component is larger than the pick up value. After a set
time delay TripDelay1(2) a trip TRIP1(2) signal is activated if the start signal is still active. At
activation of any of the two stages a common signal START will be activated. At trip from any of the
two stages also a common signal TRIP will be activated.
To avoid instability there is a settable hysteresis in the power function. The absolute hysteresis of the
stage1(2) is Hysteresis1(2) = abs (Power1(2) – drop-power1(2)). For generator reverse power
protection the power setting is very low, normally down to 0.02 p.u. of rated generator power. The
hysteresis should therefore be set to a smaller value. The drop-power value of stage1 can be
calculated with the Power1(2), Hysteresis1(2): drop-power1(2) = Power1(2) – Hysteresis1(2)
For small power1 values the hysteresis1 may not be too big, because the drop-power1(2) would be
too small. In such cases, the hysteresis1 greater than (0.5 · Power1(2)) is corrected to the minimal
value.
If the measured power drops under the drop-power1(2) value the function will reset after a set time
DropDelay1(2). The reset means that the start signal will drop out ant that the timer of the stage will
reset.
In order to minimize the influence of the noise signal on the measurement it is possible to introduce
the recursive, low pass filtering of the measured values for S (P, Q). This will make slower
measurement response to the step changes in the measured quantity. Filtering is performed in
accordance with the following recursive formula:
S = k × SOld + (1 - k ) × SCalculated
EQUATION1959 V1 EN-US (Equation 190)
Where
S is a new measured value to be used for the protection function
Sold is the measured value given from the function in previous execution cycle
k is settable parameter by the end user which influence the filter properties
Default value for parameter k is 0.00. With this value the new calculated value is immediately given
out without any filtering (that is, without any additional delay). When k is set to value bigger than 0,
the filtering is enabled. A typical value for k = 0.92 in case of slow operating functions.
Measured currents and voltages used in the Power function can be calibrated to get class 0.5
measuring accuracy. This is achieved by amplitude and angle compensation at 5, 30 and 100% of
rated current and voltage. The compensation below 5% and above 100% is constant and linear in
between, see example in figure 365.
IEC05000652 V2 EN-US
Analog outputs from the function can be used for service values or in the disturbance report. The
active power is provided as MW value: P, or in percent of base power: PPERCENT. The reactive
power is provided as Mvar value: Q, or in percent of base power: QPERCENT.
SEMOD175159-2 v9
9.15.2 Identification
SEMOD172362-2 v2
Conventional protection functions cannot detect the broken conductor condition. Broken conductor
check BRCPTOC function, consisting of continuous phase selective current unsymmetrical check on
the line where the IED is connected, gives an alarm or trip at detecting broken conductors.
BRCPTOC
I3P* TRIP
BLOCK START
BLKTR
IEC07000034-2-en.vsd
IEC07000034 V2 EN-US
9.15.5 Signals
PID-3479-INPUTSIGNALS v6
PID-3479-OUTPUTSIGNALS v7
9.15.6 Settings
PID-3479-SETTINGS v7
Broken conductor check (BRCPTOC) detects a broken conductor condition by detecting the
asymmetry between currents in the three phases. The current-measuring elements continuously
measure the three-phase currents.
The current asymmetry signal output START is set on after 50.0 ms if:
• The difference in currents between the phase with the lowest current and the phase with the
highest current is greater than set percentage Iub> of the highest phase current
• The highest phase current is greater than the minimum setting value IP>.
• The lowest phase current is below 50% of the minimum setting value IP>
The third condition is included to avoid problems in systems involving parallel lines. If a conductor
breaks in one phase on one line, the parallel line will experience an increase in current in the same
phase. This might result in the first two conditions being satisfied. If the unsymmetrical detection lasts
for a period longer than the set time tOper, the TRIP output is activated.
The simplified logic diagram of the broken conductor check function is shown in Figure
• The IED is in TEST status and the function has been blocked from the local HMI test menu
(BlockBRC=Yes).
• The input signal BLOCK is high.
The BLOCK input can be connected to a binary input of the IED in order to receive a block command
from external devices, or can be software connected to other internal functions of the IED itself to
receive a block command from internal functions.
The output trip signal TRIP is a three-phase trip. It can be used to command a trip to the circuit
breaker or for alarm purpose only.
TEST
TEST-ACTIVE
AND
Block BRCPTOC=Yes
50 ms
START
t
Function Enable
BLOCK OR
tOper TRIP
AND
AND t
Unsymmetrical
Current Detection
STI
IL1<50%IP>
IL2<50%IP> OR
IL3<50%IP>
IEC09000158-4-en.vsd
IEC09000158 V4 EN-US
Figure 367: Simplified logic diagram for Broken conductor check BRCPTOC
SEMOD175200-2 v9
9.16.1 Identification
GUID-67FC8DBF-4391-4562-A630-3F244CBB4A33 v2
Shunt Capacitor Banks (SCB) are used in a power system to provide reactive power compensation
and power factor correction. They are as well used as integral parts of Static Var Compensators
(SVC) or Harmonic Filters installations. Capacitor bank protection (CBPGAPC) function is specially
designed to provide protection and supervision features for SCBs.
CBPGAPC
I3P* TRIP
BLOCK TROC
BLKTR TRUC
BLKOC TRQOL
BLKUC TRHOL
BLKUCCUT START
BLKQOL STOC
BLKHOL STUC
STQOL
STHOL
STOCL1
STOCL2
STOCL3
STUCL1
STUCL2
STUCL3
STQOLL1
STQOLL2
STQOLL3
STHDTL1
STHDTL2
STHDTL3
STHIDML1
STHIDML2
STHIDML3
RECNINH
IEC14000046-1-en.vsd
IEC08000500 V2 EN-US
9.16.4 Signals
PID-3580-INPUTSIGNALS v5
PID-3580-OUTPUTSIGNALS v5
9.16.5 Settings
PID-3580-SETTINGS v5
Capacitor bank protection (CBPGAPC) function measures the SCB three-phase current. CBPGAPC
has several built-in features:
• Overcurrent stage
• Undercurrent stage
• Reconnection inhibit
• Harmonic overload
• Reactive power overload
Three-phase input current from the SCB is connected via the preprocessing block to CBPGAPC
function. From this preprocessing block CBPGAPC function obtains the following quantities for every
phase:
• Current sample values with sampling rate of 1 kHz in 50 Hz power system and 1.2 kHz in 60 Hz
power system (that is, 20 samples in fundamental power system cycle). These samples
correspond to the instantaneous current waveform of the protected SCB and in further text will
be marked with symbol “i~”
• Equivalent RMS current value based on Peak Current measurement. This value is obtained as
maximum absolute current sample value over last power system cycle divided by √2 and in
further text will be marked with symbol “IpeakRMS”
• Equivalent true RMS current value based on the following formula:
åi 2
~m
I
TRMS = m =1
N
EQUATION2232 V1 EN-US (Equation 191)
where N is used number of samples in one power system cycle (that is, 20) and i~m are last N
samples of the current waveform. In further text this equivalent true rms current quantity will be
marked with symbol ITRMS.
Note that the measured IpeakRMS value is available as a service value in primary amperes for every
phase from the function.
From the measured SCB currents, voltage value across every SCB phase is calculated. This is done
by continuous integration of the measured current waveform by using the following principal
equation:
1
u (t ) = × i ( t ) × ¶t
ò
C
EQUATION2233 V1 EN-US (Equation 192)
Where:
u(t) is voltage waveform across capacitor
i(t) is capacitor current waveform
C is capacitance in Farads
By using this integration procedure and subsequent filtering the following quantities for every phase
are calculated within the function:
• Voltage sample values with rate of 1 kHz in 50 Hz power system and 1.2 kHz in 60 Hz power
system (that is, 20 samples in fundamental power system cycle). These samples correspond to
the instantaneous voltage waveform across the protected SCB and in further text will be marked
with symbol u~
• Equivalent rms voltage value based on Peak Voltage measurement. This value is obtained as
maximum absolute voltage sample value over last power system cycle divided by √2 and in
further text will be marked with symbol UpeakRMS
• Equivalent true RMS voltage value based on the following formula:
åu 2
~m
U TRMS = m =1
N
EQUATION2234 V1 EN-US (Equation 193)
Where:
N is used number of samples in one power system cycle (for example, 20)
u ~m are last N samples of the voltage waveform
In further text this equivalent true RMS voltage quantity will be marked with symbol UTRMS
Some additional filtering of the calculated voltage quantities is additionally performed within the
function in order to avoid equivalent RMS voltage values overshooting during capacitor switching.
In order to avoid dependence of the current integration on exact value of the protected capacitor
bank capacitance the whole integration process is done in per unit system. In order to convert
measured current in primary amperes into per unit value the base current for the protected capacitor
bank shall be known. This value is set as parameter IBase and it represents the rated SCB current in
primary amperes at fundamental frequency. This value is calculated for a three-phase SCB as
follows:
1000 × Q [ MVAr ]
IBase =
3 × U [ kV ]
EQUATION2235 V1 EN-US (Equation 194)
Where:
IBase is base current for the function in primary amperes
Q[MVAr] is shunt capacitor bank MVAr rating
U[kV] is shunt capacitor bank rated phase-to-phase voltage in kV
Once the base current is known the internal voltage calculations can be performed. Note that the
calculated UpeakRMS value is available as a service value in percent for every phase from the
function.
Generated reactive power (Q) by the capacitor bank is calculated within the function for every phase
as given by the following equation:
Q =U TRMS ×I TRMS
Where:
Q is generated reactive power in per-unit
U TRMS is capacitor equivalent true RMS voltage in per-unit
Additional filtering of the calculated Q quantity is performed within the function in order to avoid
overshooting during capacitor switching. Note that the calculated Q value is available as a service
value in percent for every phase from the function.
Simplified logic diagram about used analog quantities within one phase of the capacitor bank
protection function are shown in figure 369.
Undercurrent
I TRMS[A]
Reconnection Inhibit
IEC09000746-2-en.vsd
IEC09000746 V2 EN-US
Figure 369: Simplified logic diagram about used analog quantities within one phase
This feature determines that capacitor banks are disconnected from the power system and is used to
prevent reconnection of a charged capacitor bank to a live network. The IRMS values of the three
phase currents are compared with the IRecnInhibit< parameter in order to determine when the
capacitor bank is energized or disconnected. The simplified logic diagram is shown in fig 370.
currentRMS a 0.02 s
CapBank Energised
a>b t
b
IRecnInhibit<
CAPDISC
Phx
NOT
IEC08000345-1-en.vsd
IEC08000345 V1 EN-US
Figure 370: Capacitor bank energization check for one phase. Similar for all three phases
When SCB is disconnected in all three phases, the reconnection inhibit signal will be given. This
signal will be active until the preset time elapsed and is used to inhibit the reconnection of charged
capacitor bank to live network. The internal logic diagram for the inhibit feature is shown in figure
371.
CAPDISC
CAPDISC
_ Ph1
Z-2
en08000346.vsd
IEC08000346 V1 EN-US
The overcurrent protection feature protects the capacitor bank from excessive current conditions.
The sub function takes the current peakRMS value from the preprocessing block in the IED as input.
The peakRMS value of the current is compared with the setting of parameter IOC>. Whenever the
peakRMS value of the current crosses the set level the function sends a START signal as output.
The signal is passed through the definite timer for giving the TRIP signal. Each phase will have its
own START and TRIP signals for overcurrent. The internal logic for the overcurrent feature is shown
in fig 372.
IPeakRMS a
a>b tOC
IOC> b TROC
AND t AND
OperationOC=On
STOC
BLKTR
BLKOC
BLOCK OR
IEC08000350-1-en.vsd
IEC08000350 V1 EN-US
Undercurrent protection feature is used to disconnect the capacitor bank from the rest of the power
system when the voltage at the capacitor bank terminals is too low for too long period of time. This
sub function uses the current peakRMS value from the preprocessing block in the IED as input. The
peakRMS value of the current is compared to the set value of the parameter IUC<. Whenever the
peakRMS value of the current falls below the set undercurrent level, the function will send a START
signal as output. The function can be blocked when the current falls below the cut off level. The
capacitor bank disconnected signals are used for this blocking. This feature will help to prevent trip
operation when the capacitor bank is disconnected from the power system. The TRIP output signal is
delayed by a definite timer. Each phase will have its own START and TRIP signals for undercurrent.
The internal logic for the undercurrent feature is shown in fig 373.
IPeakRMS
a
b>a
IUC< b
tUC
AND t
AND TRUC
OperationUC=On
BLKUC
STUC
BLOCK
OR
CAPDISC
BLKTR
en08000351.vsd
IEC08000351 V1 EN-US
Harmonic overload protection feature will protect the capacitor from over load conditions caused by
harmonics. The sub-function protects the capacitor in two stages, first stage is Inverse time delay
(IDMT) based and a second stage is based on Definite Time (DT) delay.
IDMT curve has adjustable k factor and inverse time characteristic is shown in figure 374, where k =
1. The IDMT curve starts only when the equivalent RMS voltage value is higher than set value of
parameter HOLIDMTU> and stays active until the value falls below the reset value.
2.3
Voltage Peak RMS [pu]
2.1
1.9
1.7
1.5
1.3
1.1
0.1 1 10 100 1000 10000
Operate Time [s]
IEC08000352-1-en.vsd
IEC08000352 V1 EN-US
1. When parameter kHOLIDMT has different value from 1.0 operating time is proportionally
changed (for example, when kHOLIDMT =0.9 operating times will be 90% of the values shown
in above figure 374 and table 393)
2. Between the seven main points in table 393, the operate time is calculate by using linear
interpolation in the logarithmic scale
3. Integration process is used to calculate the operate time for varying voltage condition
4. By setting parameter tMinHOLIDMT =0.1s standard requirements for minimum operating time of
100ms for harmonic overload IDMT curve can be fluffed
5. By setting parameter tMaxHOLIDMT =2000s operation for small harmonics overload condition
when UpeakRMS is in-between 1.1pu and 1.2pu is assured
Harmonic overload definite time curve has settings facilities for independent pickup and time delay. It
can be used as separate tripping stage or as an alarm stage.
Both of these two harmonic overload stages are active during capacitor bank energizing and are
capable to properly measure and operate up to and including 9th harmonic.
The internal logic for harmonic overload feature is shown in figure 375:
STHDTLx
UPeakRMS [pu]
a
a>b
HOLDTU> b
tHOLDT
t
OperationHOL=On AND
OR TRHOL
AND
BLKHOL
BLOCK
OR OR STHOL
BLKTR
OperationHOL=On AND
TR
UPeakRMS [pu]
a
a>b kHOLIDMT IDMT
HOLIDMTU> b
tMaxHOLIDMT
STHIDMLx
tMinHOLIDMT ST
UPeakRMS [pu]
IEC09000752-1-en.vsd
IEC09000752 V1 EN-US
Reactive power overload protection feature will protect the capacitor bank from reactive power
overload conditions.
The sub-function will use the reactive power values as input. The reactive power input values are
calculated from the true RMS value of voltage and current. The reactive power value is compared
with the QOL> setting. When the reactive power value exceeds the QOL> setting the STQOL signal
will be activated. The start signal is delayed by the definite timer before activating the TRQOL signal.
The internal logic diagram for this feature is shown in figure 376.
Q [pu]
a
a>b
QOL> b
tQOL
t
OperationQOL=On AND
TRQOL
AND
BLKTR
BLKQOL
STQOL
BLOCK
OR
en08000353.vsd
IEC08000353 V1 EN-US
Negative-sequence time overcurrent protection for machines (NS2PTOC) is intended primarily for the
protection of generators against possible overheating of the rotor caused by negative sequence
current in the stator current.
The negative sequence currents in a generator may, among others, be caused by:
• Unbalanced loads
• Line to line faults
• Line to earth faults
• Broken conductors
• Malfunction of one or more poles of a circuit breaker or a disconnector
NS2PTOC can also be used as a backup protection, that is, to protect the generator in case line
protections or circuit breakers fail to clear unbalanced system faults.
To provide an effective protection for the generator for external unbalanced conditions, NS2PTOC is
able to directly measure the negative sequence current. NS2PTOC also has a time delay
2
characteristic which matches the heating characteristic of the generator I 2 t = K as defined in
standard IEEE C50.13.
where:
I2 is negative sequence current expressed in per unit of the rated generator
current
t is operating time in seconds
K is a constant which depends of the generators size and design
NS2PTOC has a wide range of K settings and the sensitivity and capability of detecting and tripping
for negative sequence currents down to the continuous capability of a generator.
In order to match the heating characteristics of the generator a reset time parameter can be set.
A separate definite time delayed output is available as an alarm feature to warn the operator of a
potentially dangerous situation.
NS2PTOC
I3P* TRIP
BLOCK TR1
BLKST1 TR2
BLKST2 START
BLKTR ST1
ST2
ALARM
NSCURR
IEC08000359.vsdx
IEC08000359-1-EN V3 EN-US
9.17.4 Signals
PID-7431-INPUTSIGNALS v1
PID-7431-OUTPUTSIGNALS v1
9.17.5 Settings
PID-7431-SETTINGS v1
To avoid oscillation in the output signals, a certain hysteresis has been included. For both steps, the
reset ratio is 0.97.
Step 1 of NS2PTOC can operate in the Definite Time (DT) or Inverse Time (IDMT) mode depending
on the selected value for the CurveType1 parameter. If CurveType1= Definite, NS2PTOC operates
with a Definite Time Delay characteristic and if CurveType1 = Inverse, NS2PTOC operates with an
Inverse Time Delay characteristic. Step 2 is operating in an analogous way as Step 1.
Definite time delay is not dependent on the magnitude of measured negative sequence current. Once
the measured negative sequence current exceeds the set level, the settable definite timer t1 or t2
respectively, starts to count and the corresponding trip signal gets activated after the pre-set definite
time delay has elapsed. Reset time in definite time mode is determined by the setting parameters
tResetDef1 or tResetDef2 respectively. If NS2PTOC has already started but not tripped and
measured negative sequence current drops below the start value, the start outputs remains active for
the time defined by the resetting parameters.
When the parameter CurveType1 is set to Inverse, an inverse curve is selected according to selected
value for parameter K1. The minimum trip time setting of parameter t1Min and reset time parameter
ResetMultip1 also influence step operation. However, to match the heating characteristics of the
generator, the reset time is depending on the setting of parameter K1, which must be set according
to the generators negative sequence current capacity.
K = I 2 2t
EQUATION2112 V1 EN-US
Where:
I2 is negative sequence current expressed in per unit of the rated generator current
Operate
time
t1Max
(Default= 1000 s)
t1Min
(Default= 5 s)
K1
Current I2-1>
IEC09000691-2-en.vsd
IEC09000691 V2 EN-US
ResetTime [ s ] = ResetMultip
⋅K
I 2
NS − 1
I Start
EQUATION2111 V4 EN-US (Equation 196)
Where
INS is the measured negative sequence current
ResetMultip is multiplier of the generator capability constant K equal to setting K1 and thus defines reset time
of inverse time characteristic
The trip start levels Current I2-1> and I2-2> of NS2PTOC are freely settable over a range of 3 to 500
% of rated generator current IBase. The wide range of start setting is required in order to be able to
protect generators of different types and sizes.
After start, a certain hysteresis is used before resetting start levels. For both steps the reset ratio is
0.97.
The alarm function is operated by START signal and used to warn the operator for an abnormal
situation, for example, when generator continuous negative sequence current capability is exceeded,
thereby allowing corrective action to be taken before removing the generator from service. A settable
time delay tAlarm is provided for the alarm function to avoid false alarms during short-time
unbalanced conditions.
CurveType1=Definite
AND t1 TR1
OR
Negative sequence current a
a>b
b Inverse
I2-1>
Operation=ON AND
t1Min AND
BLKST1
BLOCK
CurveType1=Inverse
t1Max
AND
ST1
IEC080004661-4-en.vsdx
IEC08000466-1-EN V4 EN-US
Figure 379: Simplified logic diagram for step 1 of Negative sequence time overcurrent
protection for machines (NS2PTOC)
Step 2 for Negative sequence time overcurrent protection for machines (NS2PTOC) is similar to step
1.
ST1
START
ST2 OR
tAlarm ALARM
TR1
TRIP
TR2 OR
IEC09000690-2-en.vsd
IEC09000690 V2 EN-US
Figure 380: Simplified logic diagram for the START, ALARM and TRIP signals for NS2PTOC
I 22t = K
Reset time, inverse characteristic, Reset Multiplier = 0.01-20.00 ±10.0% or ±40 ms whichever is greater
step 1 - 2
I 22t = K
Minimum operate time for inverse (0.000-60.000) s ±0.2% or ±35 ms whichever is greater
time characteristic, step 1 - 2
Maximum trip delay at 0.5 x Iset to 2 (0.00-6000.00) s ±0.2% or ±35 ms whichever is greater
x Iset, step 1 - 2
Independent time delay at 0.5 x Iset (0.00-6000.00) s ±0.2% or ±35 ms whichever is greater
to 2 x Iset, step 1 - 2
Independent time delay for Alarm at (0.00-6000.00) s ±0.2% or ±35 ms whichever is greater
0.5 x Iset to 2 x Iset
Voltage-restrained time overcurrent protection (VRPVOC) function can be used as generator backup
protection against short-circuits.
The overcurrent protection feature has a settable current level that can be used either with definite
time or inverse time characteristic. Additionally, it can be voltage controlled/restrained.
One undervoltage step with definite time characteristic is also available within the function in order to
provide functionality for overcurrent protection with undervoltage seal-in.
VRPVOC
I3P* TRIP
U3P* TROC
BLOCK TRUV
BLKOC START
BLKUV STOC
STUV
IEC12000184-1-en.vsd
IEC12000184 V1 EN-US
9.18.4 Signals
PID-7805-INPUTSIGNALS v1
PID-7805-OUTPUTSIGNALS v1
9.18.5 Settings
PID-7805-SETTINGS v1
The voltage-restrained time overcurrent protection VRPVOC function is always connected to three-
phase current and three-phase voltage input in the configuration tool (ACT), but it will always
measure the maximum of the three-phase currents and the minimum of the three phase-to-phase
voltages. If frequency tracking mode for preprocessing blocks is used, then the function operates
properly in wide frequency range (e.g. 10-90 Hz).
GlobalBaseSel defines the particular Global Base Values Group where the base quantities of the
function are set. In that Global Base Values Group:
IBase shall be entered as rated phase current of the protected object in primary amperes.
UBase shall be entered as rated phase-to-phase voltage of the protected object in primary kV.
The overcurrent step simply compares the magnitude of the measured current quantity with the set
start level. The overcurrent step starts if the magnitude of the measured current quantity is higher
than the set level.
• Voltage restrained overcurrent (when setting parameter VDepMode = Slope); the start level of
the overcurrent stage changes according to the Figure 382. The voltage restrained characteristic
is defined by the two points: (0.25*UBase ; VDepFact *StartCurr/100*IBase) and (UHighLimit/
100*UBase; StartCurr/100*IBase). In the first point the factor 0.25 that multiply UBase cannot be
changed.
StartCurr
VDepFact * StartCurr
0,25 UHighLimit
UBase
IEC10000123-2-en.vsd
IEC10000123 V2 EN-US
Figure 382: Example for start level of the current variation as function of measured voltage
magnitude in Slope mode of operation
• Voltage controlled overcurrent (when setting parameter VDepMode = Step); the start level of the
overcurrent stage changes according to the Figure 383.
StartCurr
VDepFact * StartCurr
UHighLimit UBase
IEC10000124-2-en.vsd
IEC10000124 V2 EN-US
Figure 383: Example for start level of the current variation as function of measured voltage
magnitude in Step mode of operation
DEF time
selected
TROC
OR
MaxPhCurr
a STOC
a>b
b
StartCurr
X Inverse
Inverse
Voltage time
control or selected
restraint
feature
MinPh-PhVoltage
IEC10000214-1-en.vsd
IEC10000214 V1 EN-US
DEF time
selected TRUV
MinPh-phVoltage a
b>a
b STUV
AND
StartVolt
Operation_UV=On
BLKUV
IEC10000213-1-en.vsd
IEC10000213 V1 EN-US
The undervoltage step simply compares the magnitude of the lowest measured phase-phase voltage
quantity with the set start level. The undervoltage step starts if the magnitude of the measured
voltage quantity is lower than the set level.
The start signal starts a definite time delay. If the value of the start signal is logical TRUE for longer
than the set time delay, the undervoltage step sets its trip signal to logical TRUE.
This undervoltage functionality together with additional ACT logic can be used to provide functionality
for overcurrent protection with undervoltage seal-in.
Inverse time characteristics, 13 curve types See tables 1294 and 1295
see tables 1294 and 1295
Minimum operate time for inverse time (0.00 - 60.00) s ±0.2% or ±35 ms whichever is
characteristics greater
Table continues on next page
Overcurrent: -
Critical impulse time 10 ms typically at 0 to 2 x Iset
Impulse margin time 15 ms typically
Undervoltage: -
Critical impulse time 10ms typically at 2 x Uset to 0
Impulse margin time 15 ms typically
Table 408:
Function description IEC 61850 identification IEC 60617 identification ANSI/IEEE C37.2 device
number
Average Power Transient APPTEF Io > → TEF 67NT
Earth Fault Protection
High impedance grounded power systems are characterized by a relatively high impedance which is
connected between the power system neutral point and ground. The most extreme example is an
isolated power system where this impedance is practically infinite. However, it is important to
understand that the natural distributed capacitances between the individual phase conductors and
ground are always present in any power network irrespective of the neutral point grounding. These
distributed capacitances are important to understand the power system behavior, during an Earth
Fault (EF) in a high impedance grounded power system.
The APPTEF (Average Power Transient Earth Fault Protection) function is a transient measuring
directional earth-fault protection. Determination of the earth fault direction is based on the short-term
built-up transient at the beginning of the earth fault. This transient is to a large extent independent of
the neutral point treatment. This means that the function can be used without any modification in all
types of high-impedance grounded, resonant grounded or isolated power systems.
For a resonant grounded system, the correct directional measurement is ensured regardless of how
many Petersen coils are used throughout the interconnected power network. The function is not
sensitive to the actual compensation degree of the coils. It will operate equally well in an under- or
over-compensated system. Parallel neutral resistor to the Petersen coil are not needed to correctly
determine earth fault direction. However, these neutral resistors can still be used if already installed
in the network.
APPTEF
I3P* TRIP
U3P* STFW
BLOCK STRV
BLKTR STUN
RESET STIEF
WRNFW
ALMCC
ALMCIRI
IFUNDRE
IFUNDIM
IHARMIM
IEC19000949-1-en.vsdx
GUID-62978D0E-DC7C-43E3-85FB-85A75D7672AD V1 EN-US
9.19.4 Signals
GUID-FA45F1A1-E73B-43D0-B074-07F1561CCB18 v1
GUID-5ACF7D05-F1F6-4977-A83E-B29B9956F2AD v1
9.19.5 Settings
GUID-080EE324-4997-4090-86D0-E96B5491E545 v1
The basic operating condition for the transient earth fault (EF) protection in a high impedance
grounded system is explained for a substation having a single incoming transformer which will be
feeding a LV side busbar having three outgoing feeders. The associated directional EF protection for
every feeder are also shown in Figure 387 as well as a grounding impedance connected to the
transformer LV winding star point.
HV Busbar
HV
CB
Power Δ
Transformer
Y Ground
Grounding
Impedance
Transformer
LV Bay
CB
Feeder 1 Feeder 2 Feeder 3
LV Busbar
VT
F1 F2 F3
CB CB CB
IEC19000933-1-en.vsdx
IEC19000933 V1 EN-US
Transformer
Feeder 1 Bay Feeder 2 Feeder 3
LV Busbar
VT
Uo
F1 LV F2 F3
CB CB CB CB
Io_F1
Io_F2
Io_F3
Io_Tr
Fault Point Power
HV Busbar
Transformer HV
Y Δ CB
Rf Grounding
Impedance
Ground
IEC19000934-1-en.vsdx
IEC19000934 V1 EN-US
1. The EF location is in Feeder 1. Consequently, its distributed capacitance is split into two parts,
one in-between the LV busbar and the fault point (that is C_F1’) and the second one behind the
fault point (that is C_F1”).
2. All feeders are just represented with a capacitance to ground. All series parameters of any
feeder are ignored because their impedance is much lower than this capacitive impedance and
consequently these series parameters can be ignored.
3. A resistance to ground (R_F3) is shown with dashed lines for Feeder 3, in practice these
resistances are extremely large and typically can be ignored. Consequently, these are not
shown for other feeders.
4. An inductance to ground ( L_F3) is also shown with dashed lines for Feeder 3, that in practice
may represent distributed coils along that feeder or remote coils located in the other substation
at the end of Feeder 3. In systems with multiple coils the above-mentioned resistance to ground
(R_F3) may also include the coil losses.
5. The grounding impedance at the transformer LV winding neutral point is represented as a
parallel connection of an inductor ( L) and a resistor ( R). This is the most practical
representation because it can then represent the most commonly used grounding principles (for
isolated system L= R=∞).
6. The location of all CTs and VTs are also given because these are used to determine the
measurement points for Io and respectively Uo signals in each feeder.
7. Note that Io and Uo are correct values for this equivalent circuit. In a real installation the IED will
actually measure 3Io and 3Uo, but the difference between them is just a fixed factor of 3. In
further writing only Io and Uo notation will be used, but whatever is written is applicable to 3Io
and 3Uo as well.
8. The reference direction for current measurement (towards the protected feeder) is also given
with associated directional EF protection ( 67NT-F1 for Feeder 1) in each outgoing feeder bay.
9. As per the superposition theorem, a single source in the zero-sequence system is located at the
fault point. Its magnitude is equal to the phase-to-ground voltage in the faulty phase just before
the fault, but its phase angle shall be turned-around for 180 degrees. If it is assumed that the
fault resistance (that is Rf) has approximately a value of zero ( a bolted fault), then the Uo
voltage will be equal to this source voltage. The Uo voltage will be approximately the same for
all IEDs throughout the system. That means that the differences in the measured Io currents in
the individual feeders are important to determine the faulty versus the healthy feeder.
When EF happens (that is when the switch at the fault point closes in Figure 388) the source located
at the fault point energizes all the distributed capacitances of all the feeders connected to the LV
busbar.
Note that these capacitors are not energized (that is the capacitors are empty or without any stored
energy) just before the earth fault.
Consequently, these are first charged to an energy level corresponding to the Uo voltage level (using
the formula 0.5*Uo2*C) before starting to exchange reactive power with either the source located at
the fault point or with the coil(s) which are possibly located at transformer neutral point(s). This active
power surge is quite short, but if it can be measured or detected by the IED, then it can be used to
detect the faulty feeder. Figure 389 displays the path for this active but transient power from the
source to the distributed capacitors.
Transformer
Feeder 1 Bay Feeder 2 Feeder 3
LV Busbar
VT
Uo
F1 LV F2 F3
CB CB CB CB
Io_F1
Io_F2
Io_F3
Io_Tr
67NT‐F1 67NT‐F2 67NT‐F3
Faulty Feeder
Fault Point Power
HV Busbar
Transformer HV
Y Δ CB
Rf Grounding
Impedance
Ground
IEC19000935-1-en.vsdx
IEC19000935 V1 EN-US
Figure 389: Flow of active power in the zero-sequence system at the moment when EF
happens
Note that the existence of any shunt resistance in the system (R or R_F3 in Figure 389) will increase
the active transient power flow and consequently make it easier for the active power measurement
principle to determine the EF position. The same is true if the fault resistance Rf is present in the
circuit. At the same time, the existence of any inductor in the circuit (L or L_F3) will not influence the
active power flow in any way.
The EF position can be determined because the flow of the active transient power will be in the
opposite direction through the CTs in the faulty feeder and the healthy feeders. In simple words this
active power will be negative in the faulty feeder and positive in a healthy feeder. Note that the
transient EF IED installed in a healthy feeder will measure the transient charging power of the own
distributed capacitance, while the IED installed in the faulty feeder will measure the active transient
charging power of all healthy feeders lumped together. Consequently, this transient charging power
signal magnitude will be the largest for the faulty feeder and the smallest for the shortest healthy
feeder.
It is quite a common protection practice to use -Uo voltage (that is Uo voltage phasor which is turned
around/rotated for 180 degrees) for all EF protection functions. This will only invert all power
directions previously explained. For example, in an actual IED implementation the measured power
will be essentially positive in the faulty feeder and negative in a healthy feeder. This can be simply
understood as a sign convention which is commonly used in protective relaying practice.
In a power system the active power can be only supplied by the fundamental frequency signals,
which means that this active power must be generated by one or more generation plant connected to
the networks. Consequently, only the fundamental frequency content of the Io and Uo signals shall
be used to measure this active transient power in every bay. To calculate active power based on
fundamental frequency phasors the formula given below is used. Note that Uo is taken with the
minus sign as explained previously.
P U 01 * I 01 *cos( 1)
The index one in this equation indicates that only the fundamental frequency component signals are
used for the active power calculation. As mentioned previously -Uo is a constant for all EF IEDs in
the galvanically interconnected system, and consequently only the active fundamental frequency
current component Io*cos(ɸ) can be used to determine the direction of the EF.
Figure 390 displays the method to derive the Io*cos(ɸ) component. Practically it is a part of Io
phasors which is in phase with -Uo phasor. This calculation is done at every execution of the
algorithm.
For fundamental frequency current phasor, only the Io*cos(ɸ) component has a useful physical
meaning. The Io*sin(ɸ) component is just a disturbing part of the input signal which can only cause
confusion and possible wrong operation of the transient EF IED if it is used. This is because when
multiple compensation coils are installed in the network, the flow of the reactive power in the zero-
sequence system is quite unpredictable.
‐Uo
Io
IEC19000936-1-en.vsdx
IEC19000936 V1 EN-US
Figure 390: Deriving Io*cos(ɸ) and Io*sin(ɸ) quantities from -Uo and Io phasors
Because the instantaneous Io*cos(ɸ) values will vary quite a lot during the transient an averaged
(that is integrated) value is used. This averaged power value will correspond to the actual energy
stored in the distributed capacitances. In the feeder where EF is located this averaged value will be
always positive, while in all healthy feeders this averaged value will be always negative. Thus, by
setting two simple current threshold levels (one positive and the second one negative) the direction
of the EF can be determined. The averaged Io*cos(ɸ) value is also given as a service value from the
APPTEF function in order to make easier testing and understanding of the function operation
principles (that is see signal IFUNDRE in Figure 395). This value can be recorded by the built in DR
and even be used to fine-tune the settings for the respective pickup levels.
An example how these signals may look like for an EF on a faulty feeder and on a healthy feeder are
given in Figure 391 and Figure 392 respectively.
IEC19000937 V1 EN-US
Figure 391: Example how waveforms and the active power signals may look like for a faulty
feeder
IEC19000938=IEC19000938=1=en-us=Original.vsdx
IEC19000938=IEC19000938=1=en-us=Original.vsdx
IEC19000938-1-en.vsdx
IEC19000938 V1 EN-US
Figure 392: Example how waveforms and the active power signals may look like for a healthy
feeder
Note that the presence of a grounding resistor is clearly visible in Figure 391b because the averaged
value of the Io*cos(ɸ) component do not drop to zero after the transient for a faulty feeder, but it
drops to zero for a healthy feeder as shown in Figure 392b.
The advantages of the averaged Io*cos(ɸ) method to detect the EF direction in high-impedance
grounded system are:
1. Simplicity, because only the active part of the fundamental frequency component of the Io
current phasor is used.
2. Use of the widely recognized protection principle Io*cos(ɸ).
3. Independence from the compensation degree, number of coils used and their physical location
in the protected network (Petersen coils do not consume active power).
4. Averaging (numerical integration) is performed continuously. No need to start/stop this
calculation process.
5. The Io*cos(ɸ) quantity will be approximately equal to zero during all operating conditions of the
protected network except during the transient charging process of the capacitors. Consequently,
it is relatively simple to determine when this quantity appears. As additional security measure it
can also be verified that this coincides with the jump of Uo voltage magnitude.
6. A low sampling rate is sufficient because only the fundamental frequency phasors of Uo and Io
are calculated from the input signal. A sampling rate of 20 samples per fundamental power
system cycle is enough for proper operation of the transient EF IED.
7. Raw samples of residual voltage and current are not at all directly used in the algorithm which
simplifies the overall design.
8. There are no angular accuracy issues because no angle-based criterion is used.
9. Separate operate levels for forward and reverse directions can be used.
The energizing of a shunt capacitor in a power system is typically followed by relatively large current
and voltage transients which contains a lot of harmonics. When an EF happens the same holds true
for the zero-sequence circuit.
As shown in Figure 391, some damped oscillation is clearly visible in the Io signal at the beginning of
this EF. The frequency of that oscillation is determined by network parameters (that is L, R and C)
and is almost never an exact multiple of the fundamental frequency signal. The frequency of the
oscillating signal may vary from 100Hz up to theoretically 5kHz. In modern numerical IEDs typically
full-cycle filters (that is 20ms long filtering window in 50Hz power system) will be used to extract the
fundamental frequency phasors but, also higher harmonic phasors. The filtering time is quite short
and the oscillation signal during an EF will pass through this filter making it visible in some of the Io
current harmonic phasors.
For resonant grounded systems the total inductance of all coils is tuned to the distributed
capacitance of the overall power system only at the fundamental (rated) frequency. For all higher
harmonic signals the coils have a h2 times higher impedance than the corresponding capacitive
reactance, where h is the harmonic number. Already for the second harmonic component (h=2) the
compensation coils will have a 4 times higher impedance than distributed capacitances. Therefore all
coils can be omitted from the zero-sequence equivalent circuit shown in Figure 388 for all harmonic
components. A simplification is that all harmonic components in any high-impedance grounded
systems behave as the fundamental frequency component in an isolated power system.
Subsequently the Io*sin(ɸ) principle which is typically used in an isolated power system can be now
applied to all the higher order harmonic components irrespective of the actual type of the grounding
used in the protected network.
Since the higher harmonics will primarily be present during the transient part of the EF, these
harmonic components will behave in a similar transient way as previously explained for the
fundamental frequency Io*cos(ɸ) component. Consequently, the same integration principle can be
used to measure this transient harmonic reactive power exchange between the capacitors and the
harmonic source located at the fault point.
To simplify the IED calculations, the following sum is formed first, where all reactive power
components from all current harmonics are lumped together:
K
IOh *sin( h )
h2
where K is the maximum harmonic component which can be measured by the relay. This summed
value is proportional to the total harmonic reactive power seen by the IED during an EF.
Since the summed instantaneous Io*sin(ɸ) harmonic values will vary quite a lot during a transient
period of the EF, the averaged (integrated) value is used. In the feeder where the EF is located this
averaged value will be positive, while in all feeders which see the EF in reverse, this averaged value
will be negative. By settings, two current threshold levels (one positive and the second negative), the
direction of the EF can be determined. Since everything is scaled back to current, even the same
pickup levels as for the active transient power part can be used.
The summed averaged Io*sin(ɸ) harmonic value is also given as a service value from the function
(see signal IHARMIM in Figure 395) to make testing and understanding of the function operation
principles easier. This value can be recorded by the built in disturbance recorder and even be used to
fine-tune the settings for the respective pickup levels.
Examples how these signals may look like for an EF on a faulty feeder and on a healthy feeder are
given in Figure 393 and Figure 394 respectively. Note that this is the same EF and feeders as shown
in Figure 391 and Figure 392.
IEC19000939=IEC19000939=1=en-us=Original.vsdx
IEC19000939-1-en.vsdx
IEC19000939-1-en.vsdx
IEC19000939 V1 EN-US
Figure 393: Example how waveforms and the summed harmonic reactive power signals may
look like for a faulty feeder
IEC19000940=IEC19000940=1=en-us=Original.vsdx
IEC19000939-1-en.vsdx
IEC19000940=IEC19000940=1=en-us=Original.vsdx
IEC19000940=IEC19000940=1=en-us=Original.vsdx
IEC19000940 V1 EN-US
Figure 394: Example how waveforms and the summed harmonic reactive power signals may
look like for a healthy feeder
Advantages of this harmonic based transient reactive power method to detect the EF direction in
high-impedance grounded system are:
1. Simplicity, because only the reactive part of the higher harmonic phasors of Io current is used.
2. Use of the widely recognized protection principle Io*sin(ɸ).
3. Independence from the compensation degree, number of coils used and their physical location
in the protected network (all coils are disregarded for harmonic calculations).
4. Averaging (that is numerical integration) is performed continuously. There is no need to start/
stop this calculation process.
5. The Ʃ(Ioh*sin(ɸh)) quantity will be approximately equal to zero during all operating conditions of
the protected network except during the transient period of the EF. Consequently, it is simple to
determine when this quantity appears. As an additional security measure, it can be verified that
this coincides with the jump of the fundamental frequency Uo voltage magnitude.
6. A low sampling rate is sufficient, because typically only up to and including the 5th harmonic is
required to be taken into calculation.
7. Raw samples of residual voltage and current are not at all directly used in the algorithm which
simplifies the overall design.
8. Separate operate levels for forward and reverse direction are possible.
As explained in the previous two sections this transient EF protection function is based on two
principles:
1. Distribution of the active transient power at fundamental frequency, which is supplied from the
fault point to initially charge all distributed capacitances to ground in the zero-sequence system
at the moment of an EF inception in a high-impedance grounded network.
2. Distribution of the reactive transient power for higher harmonic components at the moment of an
EF inception in a high-impedance grounded network.
These two principles will hold true for any type of EF in a high-impedance grounded network,
including low-ohmic, high-ohmic, intermittent and restriking earth-faults. Consequently, this function is
able to operate for all of them.
Note that the neutral voltage Uo is common for all relays installed in the galvanically interconnected
system and typically the voltage measurement does not pose any problem for the IED operation.
It is not trivial to properly measure the residual current signal Io and extract the useful parts from it.
Due to this, use of complete current phasors for either fundamental frequency or higher harmonics
can be a problem and can lead to incorrect operation of the relays which are using complete current
phasors for measurement.
For fundamental frequency current phasor only the Io*cos(ɸ) component has useful physical
meaning, while the Io*sin(ɸ) component is just a disturbing part of the signal.
For all higher harmonic current phasors the situation is exactly the opposite. Io*sin(ɸ) is a useful
component with physical meaning, while the Io*cos(ɸ) component shall be avoided.
To achieve a stable and reliable signal, only the useful components of the current signal are
integrated in time. This makes these integral values proportional to the respective energy. However,
these integral values are scaled back to the measured current magnitude by using the moving
average method. Only the sign of this integral (positive or negative) during an EF is used in this
design to determine the direction of the earth fault. Some minimum (settable) magnitude level of the
integrated signal shall be exceeded for security reasons and to avoid any possible issues with IED
hardware accuracy. Using two independent measurement principles, the best practical results in
respect to dependability and security for the transient earth-fault protection will be ensured.
Figure 395 displays the overall simplified logic diagram for the APPTEF function.
a uormshigh
a > b
UN> b
UNMAG *)
ioangle
ANGDIF *)
uoangle ‐
uofundamp
iofundamp
Continuous
Extract ‐Uo1 Integration IFUNDRE
|Io1|*cos(ɸ1)
Fundamental Derive current
(Averaging)
active and |Io1|*sin(ɸ1)
Extract Io1 reactive part Continuous IFUNDIM
Fundamental
Integration
Invert (Averaging)
Uo
Extract ‐Uo2 a activepowerhigh
3Uo |Io2|*cos(ɸ2) a > b
2nd Harmonic Derive current IMinForward b
VT input active and
Extract Io2 |Io2|*sin(ɸ2)
reactive part a activepowerlow
2nd Harmonic a < b
IMinReverse
‐1
x b
a reactivepowerlow
a < b
Extract ‐Uo5 b
|Io5|*cos(ɸ5)
5th Harmonic Derive current
active and |Io5|*sin(ɸ5) IHARMIM
Extract Io5 reactive part
5th Harmonic
INRMS *)
5 cycles
Io True RMS
a t iormshigh
Filter a > b
IN> b
*) shown only in PCM600 Monitoring Tool and LHMI
IEC19000941-1-en.vsdx
IEC19000941 V1 EN-US
Figure 395: Simplified logic for measurement part of the APPTEF function
Service values for 3Uo magnitude, 3Io magnitude and angle between them are only displayed in the
Monitoring Tool and LHMI, in order to facilitate function testing and commissioning.
The integrated value of the fundamental frequency Io*sin(ɸ) reactive part (IFUNDIM ) is not used in
the function but is provided as a service value. This enables the end user for easier understanding of
the flow of reactive power in the zero-sequence circuit during an EF in a complex sub-transmission
network configurations when several compensation coils are used which are geographically spread-
out throughout the system.
The output signals displayed in Figure 395 with small letters are only used in
simplified logic diagrams which are given below. These signals are not available
outside of the function.
After performing the measurement of the two averaged power components, the following Boolean
logics are used to derive required binary outputs from the transient EF protection function.
Residual over-voltage start logic and function overall reset logic GUID-C68D706F-BABC-48E2-B5E0-98A26121C09C v1
The residual over-voltage start signal is internally used in the APPTEF function to arm the function to
operate in case of an EF.
Note that this voltage signal defines when the function resets internally as well.
BLOCK block
stunwindow
2.5 cycles AND
STUN
AND
tStart
stun
t tStartOn
RESET 5ms
From LHMI reset
IEC61850 Command OR OR
almcc
IEC19000942-1-en.vsdx
IEC19000942 V1 EN-US
20ms
stfw Counter
AND Set CounterLimit
stun reset Reached STIEF
Reset block AND
UN>StartsNo CounterLimit
stief
IEC19000943-1-en.vsdx
IEC19000943 V1 EN-US
activepowerhigh
OR
reactivepowerhigh
stunwindow stfw
iormshigh AND
almcc S AND
reset RS
R STFW
tPulseMin OR
stief
tStartOn OR
tTrip
TRIP
t OR
AND
OperationMode = Start and Trip tPulseMin
BLKTR AND
IEC19000944-1-en.vsdx
IEC19000944 V1 EN-US
stunwindow
activepowerlow
reactivepowerlow OR
iormshigh AND
almcc
stfw
S
reset RS
R
stief
tStartOn OR AND STRV
OR
block tPulseMin
stun
IEC19000945-1-en.vsdx
IEC19000945 V1 EN-US
tCC
OperationCC = On 200ms
t
iofundamp AND t ALMCC
a reset AND AND
a > b block
CrossCntry_IN> b
almcc
IEC19000946-1-en.vsdx
IEC19000946 V1 EN-US
tCircIN
iofundamp 500ms block
a t
a > b reset t ALMCIRI
Circulate_IN> b AND AND
200ms
activepowerhigh
t
activepowerlow OR AND OR
stun
almciri
IEC19000947-1-en.vsdx
IEC19000947 V1 EN-US
Drop off time delay to de-activate cross Fixed 0.2 s ±0.2% or ±25 ms whichever is
country fault detection at 2 x Iset to 0 greater
Drop off time delay to de-activate circulating Fixed 0.5 s ±0.2% or ±25 ms whichever is
current detection at 2 x Iset to 0 greater
10.1.1 Identification
M16876-1 v7
3U<
V2 EN-US
SYMBOL-R-2U-GREATER-THAN
Undervoltages can occur in the power system during faults or abnormal conditions. The two-step
undervoltage protection function (UV2PTUV) can be used to open circuit breakers to prepare for
system restoration at power outages or as a long-time delayed back-up to the primary protection.
UV2PTUV has two voltage steps, each with inverse or definite time delay.
It has a high reset ratio to allow settings close to the system service voltage.
UV2PTUV
U3P* TRIP
BLOCK TR1
BLKTR1 TR1L1
BLKST1 TR1L2
BLKTR2 TR1L3
BLKST2 TR2
TR2L1
TR2L2
TR2L3
START
ST1
ST1L1
ST1L2
ST1L3
ST2
ST2L1
ST2L2
ST2L3
IEC06000276-2-en.vsd
IEC06000276 V2 EN-US
10.1.4 Signals
PID-3586-INPUTSIGNALS v7
PID-3586-OUTPUTSIGNALS v7
10.1.5 Settings
PID-3586-SETTINGS v7
Two-step undervoltage protection (UV2PTUV) is used to detect low power system voltage. If one,
two or three phase voltages decrease below the set value, a corresponding START signal is
generated. The parameters OpMode1 and OpMode2 influence the requirements to activate the
START outputs: the measured voltages 1 out of 3, 2 out of 3, or 3 out of 3 have to be lower than the
corresponding set point to issue the corresponding START signal.
UV2PTUV has two voltage-measuring steps with separate time delays. If the voltage remains below
the set value for the chosen time delay, the corresponding trip signal is issued. To avoid an unwanted
trip due to the disconnection of the related high-voltage equipment, a voltage-controlled blocking of
the function is available: if the voltage is lower than the set blocking level, the function is blocked and
no START or TRIP signal is generated. The time delay characteristic is individually chosen for each
step and can be either definite time delay or inverse time delay.
To avoid oscillations of the output START signal, a hysteresis has been included.
Depending on the value of the ConnType parameter, UV2PTUV can be set to measure phase-to-
earth fundamental value, phase-to-phase fundamental value, phase-to-earth true RMS value or
phase-to-phase true RMS value, and compares it against the set values, U1< and U2<. The voltage-
related settings are made in percentage of the base voltage which is set in kV phase-to-phase
voltage. This means operation for phase-to-earth voltage under:
UBase(kV )
U (%) ·
3
EQUATION1429 V3 EN-US (Equation 199)
The time delay for the two steps can be either definite time delay (DT) or inverse time delay (IDMT).
For the inverse time delay three different modes are available:
• inverse curve A
• inverse curve B
• customer programmable inverse curve
k
t=
æ Un < -U ö
ç ÷
è Un < ø
EQUATION1431 V2 EN-US (Equation 201)
where:
Un< Set value for step 1 and step 2
U Measured voltage
k × 480
t= 2.0
+ 0.055
æ Un < - U ö
ç 32 × - 0.5 ÷
è Un < ø
EQUATION1432 V2 EN-US (Equation 202)
é ù
ê ú
ê k×A ú
t=ê pú
+D
ê æ Un < - U ö ú
êçB × -C÷ ú
ëè Un < ø û
EQUATION1433 V2 EN-US (Equation 203)
When the denominator in the expression is equal to zero the time delay will be infinity. There will be
an undesired discontinuity. Therefore a tuning parameter CrvSatn is set to compensate for this
phenomenon. In the voltage interval Un< down to Un< · (1.0 – CrvSatn/100) the used voltage will be:
Un< · (1.0 – CrvSatn/100). If the programmable curve is used this parameter must be calculated so
that:
CrvSatn
B× -C > 0
100
EQUATION1435 V1 EN-US (Equation 204)
The lowest voltage is always used for the inverse time delay integration. The details of the different
inverse time characteristics are shown in section "Inverse characteristics".
Voltage
UL1
UL2
UL3
IDMT Voltage
Time
IEC12000186-1-en.vsd
IEC12000186 V1 EN-US
Figure 403: Voltage used for the inverse time characteristic integration
Trip signal issuing requires that the undervoltage condition continues for at least the user set time
delay. This time delay is set by the parameter t1 and t2 for definite time mode (DT) and by some
special voltage level dependent time curves for the inverse time mode (IDMT). If the start condition,
with respect to the measured voltage, ceases during the delay time, and is not fulfilled again within a
user-defined reset time (tReset1 and tReset2 for the definite time and tIReset1 and tIReset2 pickup
for the inverse time) the corresponding start output is reset. After leaving the hysteresis area, the
start condition must be fulfilled again and it is not sufficient for the signal to only return back to the
hysteresis area. For the undervoltage function the IDMT reset time is constant and does not depend
on the voltage fluctuations during the drop-off period. However, there are three ways to reset the
timer: the timer is reset instantaneously, the timer value is frozen during the reset time, or the timer
value is linearly decreased during the reset time. See figure 404 and figure 405.
tIReset1
Voltage Measured
START Voltage
HystAbs1
TRIP
U1<
Time
START
TRIP
Time
Integrator Frozen Timer
Time
Linearly
Instantaneous
decreased IEC05000010-5-en.vsdx
IEC05000010 V5 EN-US
Figure 404: Voltage profile not causing a reset of the START signal for step 1, and inverse time delay at
different reset types
tIReset1
Voltage
START
START
HystAbs1 Measured Voltage
TRIP
U1<
Time
START t
TRIP
Time
Integrator Frozen Timer
Time
Instantaneous Linearly decreased
IEC05000011-en-4.vsdx
IEC05000011 V4 EN-US
Figure 405: Voltage profile causing a reset of the START signal for step 1, and inverse time delay at different
reset types
Definite timer delay
When definite time delay is selected the function will operate as shown in figure 406. Detailed
information about individual stage reset/operation behavior is shown in figure 407 and figure 408
respectively. Note that by setting tResetn = 0.0s, instantaneous reset of the definite time delayed
stage is ensured.
ST1
U t1
a tReset1
TR1
t
a<b t
U1< R
b
AND
IEC09000785-3-en.vsd
IEC09000785 V3 EN-US
U1<
ST1
TR1
tReset1
t1
IEC10000039-3-en.vsd
IEC10000039 V3 EN-US
U1<
ST1
TR1
tReset1
t1
IEC10000040-3-en.vsd
IEC10000040 V3 EN-US
It is possible to block Two step undervoltage protection UV2PTUV partially or completely, by binary
input signals or by parameter settings, where:
If the measured voltage level decreases below the setting of IntBlkStVal1, either the trip output of
step 1, or both the trip and the START outputs of step 1, are blocked. The characteristic of the
blocking is set by the IntBlkSel1 parameter. This internal blocking can also be set to Off resulting in
no voltage based blocking. Corresponding settings and functionality are valid also for step 2.
In case of disconnection of the high voltage component the measured voltage will get very low. The
event will START both the under voltage function and the blocking function, as seen in figure 409.
The delay of the blocking function must be set less than the time delay of under voltage function.
U Disconnection
Normal voltage
U1<
U2<
tBlkUV1 <
t1,t1Min
IntBlkStVal1
tBlkUV2 <
t2,t2Min
IntBlkStVal2
Time
Block step 1
Block step 2
en05000466.vsd
IEC05000466 V1 EN-US
The voltage measuring elements continuously measure the three phase-to-neutral voltages or the
three phase-to-phase voltages. Recursive fourier filters or true RMS filters of input voltage signals
are used. The voltages are individually compared to the set value, and the lowest voltage is used for
the inverse time characteristic integration. A special logic is included to achieve the 1 out of 3, 2 out
of 3 and 3 out of 3 criteria to fulfill the START condition. The design of Two step undervoltage
protection UV2PTUV is schematically shown in Figure 410.
Step 1 TR1L2
Time integrator TRIP
MinVoltSelector tIReset1
ResetTypeCrv1 TR1L3
TR1
OR
Comparator ST2L1
UL1 < U2< Voltage Phase Phase 1
Selector
OpMode2 ST2L2
Comparator Phase 2
UL2 < U2< 1 out of 3
2 out of 3 Start t2 ST2L3
3 out of 3 Phase 3 t2Reset
Comparator IntBlkStVal2 &
UL3 < U2< Trip ST2
Output OR
Logic
START TR2L1
Step 2
TR2L2
Time integrator TRIP
MinVoltSelector tIReset2
ResetTypeCrv2 TR2L3
TR2
OR
START
OR
TRIP
OR
IEC05000834-2-en.vsd
IEC05000834 V2 EN-US
M13290-1 v16
10.2.1 Identification
M17002-1 v8
3U>
SYMBOL-C-2U-SMALLER-THAN V2 EN-US
Overvoltages may occur in the power system during abnormal conditions such as sudden power
loss, tap changer regulating failures, and open line ends on long lines.
Two step overvoltage protection (OV2PTOV) function can be used to detect open line ends, normally
then combined with a directional reactive over-power function to supervise the system voltage. When
triggered, the function will cause an alarm, switch in reactors, or switch out capacitor banks.
OV2PTOV has two voltage steps, each of them with inverse or definite time delayed.
OV2PTOV has a high reset ratio to allow settings close to system service voltage.
OV2PTOV
U3P* TRIP
BLOCK TR1
BLKTR1 TR1L1
BLKST1 TR1L2
BLKTR2 TR1L3
BLKST2 TR2
TR2L1
TR2L2
TR2L3
START
ST1
ST1L1
ST1L2
ST1L3
ST2
ST2L1
ST2L2
ST2L3
IEC06000277-2-en.vsd
IEC06000277 V2 EN-US
10.2.4 Signals
PID-3535-INPUTSIGNALS v7
PID-3535-OUTPUTSIGNALS v7
10.2.5 Settings
PID-3535-SETTINGS v7
Two step overvoltage protection OV2PTOV is used to detect high power system voltage. OV2PTOV
has two steps with separate time delays. If one-, two- or three-phase voltages increase above the set
value, a corresponding START signal is issued. OV2PTOV can be set to START/TRIP, based on 1
out of 3, 2 out of 3 or 3 out of 3 of the measured voltages, being above the set point. If the voltage
remains above the set value for a time period corresponding to the chosen time delay, the
corresponding trip signal is issued.
The time delay characteristic is individually chosen for the two steps, and can be either definite time
or inverse time delayed.
The voltage related settings are made in percent of the global set base voltage UBase, which is set
in kV, phase-to-phase.
The setting of the analog inputs are given as primary phase-to-earth or phase-to-phase voltage.
OV2PTOV will operate if the voltage gets higher than the set percentage of the set base voltage
UBase. This means operation for phase-to-earth voltage over:
All the three voltages are measured continuously, and compared with the set values, U1> for Step 1
and U2> for Step 2. The parameters OpMode1 and OpMode2 influence the requirements to activate
the START outputs. Either 1 out of 3, 2 out of 3 or 3 out of 3 measured voltages have to be higher
than the corresponding set point to issue the corresponding START signal.
The time delay for the two steps can be either definite time delay (DT) or inverse time delay (IDMT).
For the inverse time delay four different modes are available:
• inverse curve A
• inverse curve B
• inverse curve C
• customer programmable inverse curve
k
t=
æ U - Un > ö
ç ÷
è Un > ø
IECEQUATION2422 V1 EN-US (Equation 207)
where:
Un> Set value for step 1 and step 2
U Measured voltage
k 480
t 2.0
0.035
U Un
32 0.5
Un
k × 480
t= 3.0
+ 0.035
æ U - Un > ö
ç 32 × - 0.5 ÷
è Un > ø
IECEQUATION2425 V1 EN-US (Equation 209)
The customer programmable curve is defined by the below equation, where A, B, C, D, k and p are
settings:
k×A
t= p
+D
æ U -Un > ö
çB× -C÷
è Un > ø
EQUATION1439 V2 EN-US (Equation 210)
When the denominator in the expression is equal to zero the time delay will be infinity. There will be
an undesired discontinuity. Therefore, a tuning parameter CrvSatn is set to compensate for this
phenomenon. In the voltage interval Un> up to Un> · (1.0 + CrvSatn/100) the used voltage will be:
Un> · (1.0 + CrvSatn/100). If the programmable curve is used this parameter must be calculated so
that:
CrvSatn
B× -C > 0
100
EQUATION1435 V1 EN-US (Equation 211)
The highest phase (or phase-to-phase) voltage is always used for the inverse time delay integration,
see figure 412. The details of the different inverse time characteristics are shown in section "Inverse
characteristics".
Voltage
IDMT Voltage
UL1
UL2
UL3
Time
IEC05000016-2-en.vsd
IEC05000016 V2 EN-US
Figure 412: Voltage used for the inverse time characteristic integration
Operation of the trip signal requires that the overvoltage condition continues for at least the user set
time delay. This time delay is set by the parameter t1 and t2 for definite time mode (DT) and by
selected voltage level dependent time curves for the inverse time mode (IDMT). If the START
condition, with respect to the measured voltage ceases during the delay time, and is not fulfilled
again within a user defined reset time (tReset1 and tReset2 for the definite time and tIReset1 and
tIReset2 for the inverse time) the corresponding START output is reset, after that the defined reset
time has elapsed. Here it should be noted that after leaving the hysteresis area, the START condition
must be fulfilled again and it is not sufficient for the signal to only return back to the hysteresis area.
The hysteresis value for each step is settable HystAbsn (where n means either 1 or 2 respectively) to
allow a high and accurate reset of the function. For OV2PTOV the IDMT reset time is constant and
does not depend on the voltage fluctuations during the drop-off period. However, there are three
ways to reset the timer: either the timer is reset instantaneously, or the timer value is frozen during
the reset time, or the timer value is linearly decreased during the reset time.
tIReset1
Voltage
START
TRIP
U1>
HystAbs1 Measured
Voltage
Time
START t
TRIP
Time
Integrator Linearly decreased
Frozen Timer
t
Instantaneous Time
IEC09000055‐3‐en.vsdx
IEC09000055 V3 EN-US
Figure 413: Voltage profile not causing a reset of the START signal for step 1, and inverse time delay at
different reset types
tIReset1
Voltage
START TRIP
START HystAbs1
U1>
Measured
Voltage
Time
START t
TRIP
Time
Integrator Frozen Timer
Time
Linearly
Instantaneous decreased
IEC05000020‐4‐en.vsdx
IEC05000020 V4 EN-US
Figure 414: Voltage profile causing a reset of the START signal for step 1, and inverse time delay at different
reset types
Definite time delay
When definite time delay is selected, the function will operate as shown in figure 415. Detailed
information about individual stage reset/operation behavior is shown in figure 416 and figure 417
respectively. Note that by setting tResetn = 0.0s (where n means either 1 or 2 respectively),
instantaneous reset of the definite time delayed stage is ensured.
ST1
U tReset1 t1
a
a>b t t
TR1
U1>
b AND
OFF ON
Delay Delay
IEC10000100-2-en.vsd
IEC10000100 V2 EN-US
Figure 415: Logic diagram for step 1, definite time delay, DT operation
U1>
START
TRIP
tReset1
t1
IEC10000037-2-en.vsd
IEC10000037 V2 EN-US
Figure 416: Example for step 1, Definite Time Delay stage 1 reset
U1>
START
TRIP
tReset1
t1
IEC10000038-2-en.vsd
IEC10000038 V2 EN-US
It is possible to block Two step overvoltage protection OV2PTOV partially or completely, by binary
input signals where:
The voltage measuring elements continuously measure the three phase-to-earth voltages or the
three phase-to-phase voltages. Recursive Fourier filters or true RMS filters of input voltage signals
are used. The phase voltages are individually compared to the set value, and the highest voltage is
used for the inverse time characteristic integration. A special logic is included to achieve the 1 out of
3, 2 out of 3 or 3 out of 3 criteria to fulfill the START condition. The design of Two step overvoltage
protection (OV2PTOV) is schematically described in figure 418.
OR TR1
Comparator ST2L1
UL1 > U2> Phase 1
Voltage Phase
Selector ST2L2
Comparator OpMode2 Phase 2
UL2 > U2> 1 out of 3
Start ST2L3
2 out of 3
Phase 3 t2
3 out of 3
Comparator t2Reset
UL3 > U2> & ST2
OR
Trip
START Output TR2L1
Logic
TR2
OR
START
OR
TRIP
OR
IEC05000013-2-en.vsd
IEC05000013-WMF V2 EN-US
M13304-1 v15
10.3.2 Identification
SEMOD54295-2 v6
IEC15000108 V1 EN-US
Residual voltages may occur in the power system during earth faults.
Two step residual overvoltage protection (ROV2PTOV) function calculates the residual voltage from
the three-phase voltage input transformers or measures it from a single voltage input transformer fed
from an open delta or neutral point voltage transformer.
ROV2PTOV has two voltage steps, each with inverse or definite time delay.
ROV2PTOV
U3P* TRIP
BLOCK TR1
BLKTR1 TR2
BLKST1 START
BLKTR2 ST1
BLKST2 ST2
IEC06000278-2-en.vsd
IEC06000278 V2 EN-US
10.3.5 Signals
PID-7438-INPUTSIGNALS v1
PID-7438-OUTPUTSIGNALS v1
10.3.6 Settings
PID-7438-SETTINGS v1
Two step residual overvoltage protection ROV2PTOV is used to detect a high residual voltage. The
residual voltage can be measured directly from a voltage transformer in the neutral of a power
transformer or from a three-phase voltage transformer, where the secondary windings are connected
in an open delta. Another possibility is to measure the three phase-to-earth voltages, and calculate
the corresponding residual voltage internally in the IED. ROV2PTOV has two steps with separate
time delays. If the residual voltage remains above the set value for a time period corresponding to
the chosen time delay, the corresponding TRIP signal is issued.
The time delay characteristic is individually chosen for the two steps and can be either definite time
delay or inverse time delay.
The voltage-related settings are made in percent of the base voltage, which is set in kV, phase-
phase. The set UBase value is divided by sqrt(3) before the set value is calculated.
The residual voltage is measured continuously, and compared with the set values, U1> and U2>.
To avoid oscillations of the output START signal, a settable hysteresis has been included.
The time delay for the two steps can be either definite time delay (DT) or inverse time delay (IDMT).
For the inverse time delay four different modes are available:
• inverse curve A
• inverse curve B
• inverse curve C
• customer programmable inverse curve
k
t=
æ U - Un > ö
ç ÷
è Un > ø
IECEQUATION2422 V1 EN-US (Equation 212)
where:
Un> Set value for step 1 and step 2
U Measured voltage
k 480
t 2.0
0.035
U Un
32 0.5
Un
k × 480
t= 3.0
+ 0.035
æ U - Un > ö
ç 32 × - 0.5 ÷
è U > ø
IECEQUATION2421 V1 EN-US (Equation 214)
k×A
t= p
+D
æ U -Un > ö
çB× -C÷
è Un > ø
EQUATION1439 V2 EN-US (Equation 215)
When the denominator in the expression is equal to zero, the time delay will be infinite. There will be
an undesired discontinuity. Therefore a tuning parameter CrvSatn is set to compensate for this
phenomenon. In the voltage interval Un> up to Un> · (1.0 + CrvSatn/100) the used voltage will be:
Un> · (1.0 + CrvSatn/100). If the programmable curve is used this parameter must be calculated so
that:
CrvSatn
B× -C > 0
100
EQUATION1440 V1 EN-US (Equation 216)
The details of the different inverse time characteristics are shown in section "Inverse characteristics".
TRIP signal issuing requires that the residual overvoltage condition continues for at least the user set
time delay. This time delay is set by the parameter t1 and t2 for definite time mode (DT) and by some
special voltage level dependent time curves for the inverse time mode (IDMT).
If the START condition, with respect to the measured voltage ceases during the delay time, and is
not fulfilled again within a user defined reset time (tReset1 and tReset2 for the definite time and
tIReset1 and tIReset2 for the inverse time) the corresponding START output is reset, after the
defined reset time has elapsed.
Here it should be noted that after leaving the hysteresis area, the START condition must be fulfilled
again and it is not sufficient for the signal to only return back to the hysteresis area. Also, notice that
for the overvoltage function, IDMT reset time is constant and does not depend on the voltage
fluctuations during the drop-off period.
There are three ways to reset the timer: the timer is reset instantaneously, the timer value is frozen
during the reset time, or the timer value is linearly decreased during the reset time. See figure 420
and figure 421.
tIReset1
Voltage
START
TRIP
U1>
HystAbs1 Measured
Voltage
Time
START t
TRIP
Time
Integrator Linearly decreased
Frozen Timer
t
Instantaneous Time
IEC09000055‐3‐en.vsdx
IEC09000055 V3 EN-US
Figure 420: Voltage profile not causing a reset of the START signal for step 1, and inverse time delay
tIReset1
Voltage
START TRIP
START HystAbs1
U1>
Measured
Voltage
Time
START t
TRIP
Time
Integrator Frozen Timer
Time
Linearly
Instantaneous decreased
IEC05000020‐4‐en.vsdx
IEC05000020 V4 EN-US
Figure 421: Voltage profile causing a reset of the START signal for step 1, and inverse time delay
Definite time delay
When definite time delay is selected, the function will operate as shown in figure 422. Detailed
information about individual stage reset/operation behavior is shown in figure 423 and figure 424
respectively. Note that by setting tResetn = 0.0s, instantaneous reset of the definite time delayed
stage is ensured.
ST1
U tReset1 t1
a
a>b t t
TR1
U1>
b AND
OFF ON
Delay Delay
IEC10000100-2-en.vsd
IEC10000100 V2 EN-US
Figure 422: Logic diagram for step 1, Definite time delay, DT operation
U1<
ST1
TR1
tReset1
t1
IEC10000039-3-en.vsd
IEC10000039 V3 EN-US
U1<
ST1
TR1
tReset1
t1
IEC10000040-3-en.vsd
IEC10000040 V3 EN-US
It is possible to block two step residual overvoltage protection ROV2PTOV partially or completely by
binary input signals where:
The voltage measuring elements continuously measure the residual voltage. Recursive Fourier filters
filter the input voltage signal for the rated frequency. The residual voltage is compared to the set
value, and is also used for the inverse time characteristic integration. The design of the function is
schematically described in figure 425.
ST2
Comparator Phase 1
UN > U2> TR2
Start
t2
START tReset2
& START
Trip OR
Time integrator Output
TRIP Logic
tIReset2
ResetTypeCrv2 TRIP
Step 2 OR
IEC05000748_2_en.vsd
IEC05000748 V2 EN-US
Figure 425: Schematic design of Two step residual overvoltage protection ROV2PTOV
10.4.1 Identification
M14867-1 v3
U/f >
SYMBOL-Q V1 EN-US
When the laminated core of a power transformer or generator is subjected to a magnetic flux density
beyond its design limits, stray flux will flow into non-laminated components that are not designed to
carry flux. This will cause eddy currents to flow. These eddy currents can cause excessive heating
and severe damage to insulation and adjacent parts in a relatively short time. The function has
settable inverse operating curves and independent alarm stages.
OEXPVPH
I3P* TRIP
U3P* START
BLOCK ALARM
RESET
IEC05000329-2-en.vsd
IEC05000329 V3 EN-US
10.4.4 Signals
PID-3514-INPUTSIGNALS v6
PID-3514-OUTPUTSIGNALS v6
10.4.5 Settings
PID-3514-SETTINGS v6
Modern design transformers are more sensitive to overexcitation than earlier types. This is a result of
the more efficient designs and designs which rely on the improvement in the uniformity of the
excitation level of modern systems. If an emergency that causes overexcitation does occur,
transformers may be damaged unless corrective action is taken. Transformer manufacturers
recommend an overexcitation protection as a part of the transformer protection system.
Overexcitation results from excessive applied voltage, possibly in combination with below-normal
frequency. Such conditions may occur when a transformer unit is loaded, but are more likely to arise
when the transformer is unloaded, or when loss of load occurs. Transformers directly connected to
generators are in particular danger to experience an overexcitation conditions. It follows from the
fundamental transformer equation, see equation 217, that the peak flux density Bmax is directly
proportional to induced voltage E, and inversely proportional to frequency f and turns n.
E = 4.44 × f × n × Bmax× A
EQUATION898 V2 EN-US (Equation 217)
E f
M ( p.u.) =
( Ur ) ( fr )
IECEQUATION2296 V1 EN-US (Equation 218)
Disproportional variations in quantities E and f may give rise to core overfluxing. If the core flux
density Bmax increases to a point above saturation level (typically 1.9 Tesla), the flux will no longer
be contained within the core, but will extend into other (non-laminated) parts of the power transformer
and give rise to eddy current circulations.
Protection against overexcitation is based on calculation of the relative volt per hertz (V/Hz) ratio.
Protection initiates a reduction of excitation, and if this fails, or if this is not possible, the TRIP signal
will disconnect the transformer from the source after a delay ranging from seconds to minutes,
typically 5-10 seconds.
Overexcitation protection may be of particular concern on directly connected generator unit Step-up
Transformer. Directly connected generator-transformers are subjected to a wide range of frequencies
during the acceleration and deceleration of the turbine. In such cases, OEXPVPH (24) may trip the
field breaker during a start-up of a machine, by means of the overexcitation ALARM signal. If this is
not possible, the power transformer can be disconnected from the source, after a delay, by the TRIP
signal.
The IEC 60076 - 1 standard requires that transformers operate continuously at not more than 10%
above rated voltage at no load, and rated frequency. At no load, the ratio of the actual generator
terminal voltage to the actual frequency should not exceed 1.1 times the ratio of transformer rated
voltage to the rated frequency on a sustained basis, see equation 219.
E
---- £ 1.1 × Ur
------
f fr
EQUATION900 V1 EN-US (Equation 219)
E V Hz >
£
f fr
IECEQUATION2297 V2 EN-US (Equation 220)
where:
V/Hz> is the maximum continuously allowed voltage at no load, and rated frequency.
V/Hz> is a setting parameter. The setting range is 100% to 180%. If the user does not know exactly
what to set, then the default value for V/Hz> = 110 % given by the IEC 60076-1 standard shall be
used.
E f
M ( p.u.) =
Ur fr
IECEQUATION2299 V1 EN-US (Equation 221)
It is clear from the above formula that, for an unloaded power transformer, M = 1 for any E and f,
where the ratio E/f is equal to Ur/fr. A power transformer is not overexcited as long as the relative
excitation is M ≤ V/Hz>, V/Hz> expressed in % of Ur/fr.
The overexcitation protection algorithm is fed with an input voltage U which is in general not the
induced voltage E from the fundamental transformer equation. For no load condition, these two
voltages are the same, but for a loaded power transformer the internally induced voltage E may be
lower or higher than the voltage U which is measured and fed to OEXPVPH , depending on the
direction of the power flow through the power transformer, the power transformer side where
OEXPVPH is applied, and the power transformer leakage reactance of the winding. It is important to
specify in the application configuration on which side of the power transformer OEXPVPH is placed.
As an example, at a transformer with a 15% short circuit impedance Xsc, the full load, 0.8 power
factor, 105% voltage on the load side, the actual flux level in the transformer core, will not be
significantly different from that at the 110% voltage, no load, rated frequency, provided that the short
circuit impedance X can be equally divided between the primary and the secondary winding: Xleak =
Xleak1 = Xleak2 = Xsc / 2 = 0.075 pu.
OEXPVPH calculates the internal induced voltage E if Xleak (meaning the leakage reactance of the
winding where OEXPVPH is connected) is known to the user. The assumption taken for two-winding
power transformers that Xleak = Xsc / 2 is unfortunately most often not true. For a two-winding power
transformer the leakage reactances of the two windings depend on how the windings are located on
the core with respect to each other. In the case of three-winding power transformers the situation is
still more complex. If a user has the knowledge on the leakage reactance, then it should applied. If a
user has no idea about it, Xleak can be set to Xc/2. OEXPVPH protection will then take the given
measured voltage U, as the induced voltage E.
If one phase-to-phase voltage is available from the side where overexcitation protection is applied,
then Overexcitation protection OEXPVPH shall be set to measure this voltage, MeasuredU. The
particular voltage which is used determines the two currents that must be used. This must be chosen
with the setting MeasuredI.
It is extremely important that MeasuredU and MeasuredI are set to same value.
If, for example, voltage UL1L2 is fed to OEXPVPH, then currents IL1, and IL2 must be applied. From
these two input currents, current IL1L2 = IL1 - IL2 is calculated internally by the OEXPVPH algorithm.
The phase-to-phase magnitude and frequency of the voltage must be both higher than 20% of the
rated value, when any of the two quantities are below this threshold, otherwise the protection
algorithm exits without calculating the excitation. ERROR output is set to 1, and the displayed value
of relative excitation V/Hz shows 0.000.
If three phase-to-earth voltages are available from the side where overexcitation is connected, then
OEXPVPH shall be set to measure positive sequence voltage and current. In this case the positive
sequence voltage and the positive sequence current are used by OEXPVPH. A check is made if the
positive sequence magnitude and frequency are higher than 20% of the rated phase-to-earth voltage
and rated frequency respectively, when any of the two quantities are below this threshold, OEXPVPH
exits immediately, and no excitation is calculated. ERROR output is set to 1, and the displayed value
of relative excitation V/Hz shows 0.000.
• OEXPVPH can be connected to any power transformer side, independent from the power flow.
• The side with a possible load tap changer must not be used.
Basically there are two different delay laws available to choose between:
The so called IEEE law approximates a square law and has been chosen based on analysis of the
various transformers’ overexcitation capability characteristics. They can match the transformer core
capability well.
0.18 × k 0.18 × k
top = 2
= 2
æ M ö overexcitation
ç V Hz> - 1 ÷
è ø
IECEQUATION2298 V2 EN-US (Equation 222)
where:
M the relative excitation
V/Hz> is maximum continuously allowed voltage at no load, and rated frequency, in pu and
k is time multiplier for inverse time functions, see figure 428.
Parameter k (“time multiplier setting”) selects one delay curve from the family of curves.
æ Umeasured ö
ç ÷ Umeasured frated
=è
fmeasured ø
M = ×
æ UBase ö UBase fmeasured
ç ÷
è frated ø
IECEQUATION2404 V1 EN-US (Equation 223)
An analog overexcitation relay would have to evaluate the following integral expression, which
means to look for the instant of time t = top according to equation 224.
top
A digital, numerical relay will instead look for the lowest j (that is, j = n) where it becomes true that:
n
2
Dt × å ( M(j) – V/Hz> ) ³ 0.18 × k
j=k
EQUATION906 V1 EN-US (Equation 225)
where:
Dt is the time interval between two successive executions of OEXPVPH and
M(j) - V/Hz> is the relative excitation at (time j) in excess of the normal (rated) excitation which is given as Ur/fr.
As long as M > V/Hz> (that is, overexcitation condition), the above sum can only be larger with time,
and if the overexcitation persists, the protected transformer will be tripped at j = n.
Inverse delays as per figure 428, can be modified (limited) by two special definite delay settings,
namely tMax and tMin, see figure 427.
delay in s
tMax
overexcitation
tMin
0 Mmax - V/Hz> Overexcitation M-V/Hz>
99001067.vsd
IEC99001067 V1 EN-US
A definite minimum time, tMin, can be used to limit the operate time at high degrees of
overexcitation. In case the inverse delay is shorter than tMin, OEXPVPH function trips after tMin
seconds. The inverse delay law is not valid for values exceeding Mmax. The delay will be tMin,
irrespective of the overexcitation level, when values exceed Mmax (that is, M>V/Hz>).
1000
100
k = 60
k = 20
k = 10
10 k=9
k=8
k=7
k=6
k=5
k=4
k=3
k=2
k=1
1
1 2 3 4 5 10 20 30 40
OVEREXCITATION IN % (M-Emaxcont)*100)
en01000373.vsd
IEC01000373 V1 EN-US
(V Hz>> ) / f
M= = 1.40
Ur/fr
IECEQUATION2286 V1 EN-US (Equation 226)
The Tailor-Made law allows a user to design an arbitrary delay characteristic. In this case the interval
between M = V/Hz>, and M = Mmax is automatically divided into five equal subintervals, with six
delays. (settings t1, t2, t3, t4, t5 and t6) as shown in figure 429. These times should be set so that t1
=> t2 => t3 => t4 => t5 => t6.
The upper V/Hz limit for the Tailor-Made characteristic is always the greater value among the
following two values in %:
• 1.10 x V/Hz>
• V/Hz>>
The reason is to prevent the loss of accuracy of the Tailor-Made characteristic when small set value
for V/Hz>> is used.
delay in s
tMax
under- tMin
excitation Overexcitation M-Emaxcont
0 Mmax - Emaxcont Excitation M
Emaxcont Mmax
99001068.vsd
IEC99001068 V1 EN-US
Should it happen that tMax be lower than, for example, delays t1, and t2, the actual delay would be
tMax. Above Mmax, the delay can only be tMin.
A monitored data value, TMTOTRIP, is available on the local HMI and in PCM600. This value is an
estimation of the remaining time to trip (in seconds), if the overexcitation remained on the level it had
when the estimation was done. This information can be useful during small or moderate
overexcitation situations.
If the overexcitation is so low that the valid delay is tMax, then the estimation of the remaining time to
trip is done against tMax.
The relative excitation M, shown on the local HMI and in PCM600 has a monitored data value
VPERHZ and is calculated from the expression:
E f
M ( p.u.) =
Ur fr
IECEQUATION2299 V1 EN-US (Equation 227)
If VPERHZ value is less than setting V/Hz> (in %), the power transformer is underexcited. If
VPERHZ is equal to V/Hz> (in %), the excitation is exactly equal to the power transformer continuous
capability. If VPERHZ is higher than V/Hz>, the protected power transformer is overexcited. For
example, if VPERHZ = 1.100, while V/Hz> = 110 %, then the power transformer is exactly on its
maximum continuous excitation limit.
The monitored data value THERMSTA shows the thermal status of the protected power transformer
iron core. THERMSTA gives the thermal status in % of the trip value which corresponds to 100%.
THERMSTA should reach 100% at the same time, as TMTOTRIP reaches 0 seconds. If the
protected power transformer is then for some reason not switched off, THERMSTA shall go over
100%.
If the delay as per IEEE law, or Tailor-made Law, is limited by tMax, and/or tMin, then the Thermal
status will generally not reach 100% at the same time, when tTRIP reaches 0 seconds. For example,
if, at low degrees of overexcitation, the very long delay is limited by tMax, then the OEXPVPH TRIP
output signal will be set to 1 before the Thermal status reaches 100%.
A separate step, AlarmLevel, is provided for alarming purpose. It is normally set 2% lower than (V/
Hz>) and has a definite time delay, tAlarm. This will give the operator an early warning.
BLOCK
AlarmLevel
tAlarm ALARM
&
t
M>V/Hz>
TRIP
&
V/Hz>
U3P Calculation
Ei k
M
of internal M=
I3P induced (Ei / f) IEEE law &
voltage Ei (Ur / fr) tMax ³1
M t
Tailor-made law
M>V/Hz>>
tMin
Xleak
t
V/Hz>>
Curve type IEEE or customer defined ±5.0 % or ±45 ms, whichever is greater
(0.18 × k )
IEEE : t =
( M - 1) 2
where M = (E/f)/(Ur/fr)
Minimum time delay for inverse (0.000–60.000) s ±1.0% or ±45 ms, whichever is greater
function
Maximum time delay for inverse (0.00–9000.00) s ±1.0% or ±45 ms, whichever is greater
function
Alarm time delay (0.00–9000.00) ±1.0% or ±45 ms, whichever is greater
The healthy condition close to the rated values (that is, V/Hz below the set pickup
value) must be applied first when the operate time of a function is tested. Otherwise,
an additional delay of up to 50 ms should be added to stated operate times.
10.5.2 Identification
SEMOD167723-2 v2
A voltage differential monitoring function is available. It compares the voltages from two three phase
sets of voltage transformers and has one sensitive alarm step and one trip step.
VDCPTOV
U3P1* TRIP
U3P2* START
BLOCK ALARM
U1LOW
U2LOW
UL1DIFF
UL2DIFF
UL3DIFF
IEC06000528-2-en.vsd
IEC06000528 V2 EN-US
10.5.5 Signals
PID-7421-INPUTSIGNALS v1
PID-7421-OUTPUTSIGNALS v1
10.5.6 Settings
PID-7421-SETTINGS v1
The Voltage differential protection function VDCPTOV (60) is based on comparison of the amplitudes
of the two voltages connected in each phase. Possible differences between the ratios of the two
Voltage/Capacitive voltage transformers can be compensated for with a ratio correction factors RFLx.
The voltage difference is evaluated and if it exceeds the alarm level UDAlarm or trip level UDATrip
signals for alarm (ALARM output) or trip (TRIP output) is given after definite time delay tAlarm
respectively tTrip. The two three phase voltage supplies are also supervised with undervoltage
settings U1Low and U2Low. The outputs for loss of voltage U1LOW resp U2LOW will be activated.
The U1 voltage is supervised for loss of individual phases whereas the U2 voltage is supervised for
loss of all three phases.
Loss of all U1 or all U2 voltages will block the differential measurement. This blocking can be
switched off with setting BlkDiffAtULow = No.
VDCPTOV function can be blocked from an external condition with the binary BLOCK input. It can,
for example, be activated from Fuse failure supervision function FUFSPVC.
To allow easy commissioning the measured differential voltage is available as service value. This
allows simple setting of the ratio correction factor to achieve full balance in normal service.
UDTripL1>
AND
UDTripL3>
AND
AND START
UDAlarmL1>
AND
UDAlarmL2> O tAlarm
AND
R t AND ALARM
UDAlarmL3>
AND
U1<L1
tAlarm
U1<L2 AND t U1LOW
AND
U1<L3 AND
OR
BlkDiffAtULow
U2<L1
t1
U2<L2 AND t U2LOW
AND
U2<L3
BLOCK
en06000382-2.vsd
IEC06000382 V3 EN-US
10.6.1 Identification
SEMOD171954-2 v2
Loss of voltage check (LOVPTUV ) is suitable for use in networks with an automatic system
restoration function. LOVPTUV issues a three-pole trip command to the circuit breaker, if all three
phase voltages fall below the set value for a time longer than the set time and the circuit breaker
remains closed.
LOVPTUV
U3P* TRIP
BLOCK START
CBOPEN
VTSU
IEC07000039-2-en.vsd
IEC07000039 V2 EN-US
10.6.4 Signals
PID-3519-INPUTSIGNALS v6
PID-3519-OUTPUTSIGNALS v6
10.6.5 Settings
PID-3519-SETTINGS v6
The operation of Loss of voltage check LOVPTUV is based on line voltage measurement. LOVPTUV
is provided with a logic, which automatically recognizes if the line was restored for at least tRestore
before starting the tTrip timer. All three phases are required to be low before the output TRIP is
activated. The START output signal indicates start.
Additionally, LOVPTUV is automatically blocked if only one or two phase voltages have been
detected low for more than tBlock.
LOVPTUV operates again only if the line has been restored to full voltage for at least tRestore.
Operation of the function is also inhibited by fuse failure and open circuit breaker information signals,
by their connection to dedicated inputs of the function block.
Due to undervoltage conditions being continuous the trip pulse is limited to a length set by setting
tPulse.
The operation of LOVPTUV is supervised by the fuse-failure function (BLKU input) and the
information about the open position (CBOPEN) of the associated circuit breaker.
The BLOCK input can be connected to a binary input of the IED in order to receive a block command
from external devices or can be software connected to other internal functions of the IED itself in
order to receive a block command from internal functions. LOVPTUV is also blocked when the IED is
in TEST status and the function has been blocked from the HMI test menu. (Blocked=Yes).
TEST
TEST-ACTIVE
&
Blocked = Yes
START
BLOCK >1
Function Enable tTrip tPulse TRIP
STUL1N & t
STUL2N &
only 1 or 2 phases are low for
Latched at least 10 s (not three)
STUL3N Enable
&
tBlock
>1 t
IEC07000089_2_en.vsd
IEC07000089 V2 EN-US
Pulse timer when disconnecting all three (0.050–60.000) s ±0.2% or ±15 ms whichever is
phases greater
Time delay for enabling the functions after (0.000–60.000) s ±0.2% or ±35 ms whichever is
restoration greater
Operate time delay when disconnecting all (0.000–60.000) s ±0.2% or ±35 ms whichever is
three phases greater
Time delay to block when all three phase (0.000–60.000) s ±0.2% or ±35 ms whichever is
voltages are not low greater
Cascading failures are series faults in shunt capacitor banks involving more than one capacitor unit
(or even more than one rack) as shown in Figure 435. Cascading failures are characterized by the
presence of an unbalanced shunt capacitor bank (SCB) current. However, as the connected power
system is much stronger than the SCB rating, any unbalance voltage due to cascading faults inside
the capacitor bank is typically not present in the system.
The SCCFPVOC function provides protection against cascading faults and has the following
protection modes to detect the unbalances.
At any time only one mode can be selected for the operation. The zero sequence mode shall only be
selected if the capacitor is solidly earthed.
The zero sequence based function can also be used as a turn to turn fault protection for a shunt
reactor with a earthed neutral point.
Bus
VT
670 IED
CT
Cascading failure
SCCFPVOC
I3P* TRIP
U3P* TR1
BLOCK TR2
BLKST1 START
BLKST2 ST1
ST2
IMEAS
UMEAS
IEC19000102-1-en.vsdx
IEC19000102 V1 EN-US
11.1.5 Signals
PID-7804-INPUTSIGNALS v1
PID-7804-OUTPUTSIGNALS v1
11.1.6 Settings
PID-7804-SETTINGS v1
The negative or the zero sequence voltage restrained over-current principle is used to detect a
cascading failure within the shunt capacitor bank (SCB). Table 462 summarizes the current/voltage
pairs which are used for the voltage restrained principle.
The choice between the negative or the zero sequence quantity depends on whether the star point is
earthed or not. The restrained characteristics for this application is set in accordance with Figure 437.
Measured Current
(%IBase)
VDepFact × Current
start level (I> or I>>)
IEC19000103-1-en.vsdx
IEC19000103 V1 EN-US
Figure 437: General voltage restrained characteristic for SCB cascading protection (Stage 1
and stage 2)
The SCCFPVOC function has two stages of definite time voltage restrained over-current functionality.
In both the stages, voltage restrained over-current feature will follow the characteristics shown in
Figure 437. In the characteristics, the over-current set values I > and I >> are modified according to
the measured voltage as follows:
é æ U öù
ê 120 - ç ´100 ÷ ú
Stage1Current set level = ê VDepFact1 ´ è UBase øú ´ I >
ê 117 ú
êë úû
é æ U öù
ê 120 - ç ´ 100 ÷ ú
Stage2Current set level = êVDepFact 2 ´ è UBase ø ú ´ I >>
ê 117 ú
êë úû
IECEQUATION19001 V1 EN-US (Equation 231)
Since the capacitor impedance is linearly dependent with respect to voltage across the capacitor, the
two steps of SCCFPVOC should work as parallel characteristics (see Figure 438) to achieve the
combination of security and speed. This parallel characteristics of two steps are achieved by setting
VDepFactx as follows:
æ 117 ö
For Stage1: VDepFact1 = 1 - ç ÷
èI>ø
æ 117 ö
For Stage2 : VDepFact 2 = 1 - ç ÷
è I >> ø
IECEQUATION19009 V1 EN-US (Equation 232)
Once the VDepFact1 and VDepFact2 are set as per the above equations, the current pick up level
for the linear part of Figure 437 (between 3% - 120% of the measured voltage) is calculated as
follows:
éæ UBase ö ù
Stage1 Current pickup level = I > - êç 120 ´ ÷ -Uú
ëè 3 ø û
éæ UBase ö ù
Stage2 Current pickup level = I >> - êç 120 ´ ÷ -Uú
ëè 3 ø û
IECEQUATION190010 V1 EN-US (Equation 233)
Set IBase and UBase according to the capacitor bank rating. That is,
The above rated settings are required for the restrained characteristic to follow the
capacitor impedance properly.
%IBase
I>>:130
I>:125
120
100
Characteristic for
external faults
defined by XSCB
13.0(VDepFact2: 0.100)
8 (VDepFact1: 0.064)
IEC19000106-1-en.vsdx
IEC19000106 V1 EN-US
Figure 438: General voltage restrained characteristic for SCB cascading failure protection
(Stage 1 and Stage 2)
Based on the current input and the voltage input selection, Equation 229, Equation 230, and
Equation 231 uses either the negative or the zero sequence quantities.
The simplified logic diagram of the function is shown in Figure 439. Start of each stage will release
the trip signal respectively after a definite time delay.
This function has an additional zero sequence 2nd harmonic restrained feature which can be
switched On/Off by setting HarmRestrx (x = 1, 2). If this setting is set to On, then the respective
stage will be blocked, if:
This second harmonic restrained feature shall only be enabled if the zero sequence mode of
operation is selected.
When enabled, the 2nd harmonic blocking function is used to freeze the Definite
and/or the Inverse Characteristics internal timers. When the function detects a 2nd
harmonic higher than the set threshold, the internal function timers are frozen but
START outputs continues to be active as long as the measured current is above the
set pickup level. Internal timers will again resume timing when harmonic content
becomes smaller than the set threshold and the measured current is higher than the
pickup value. If TRIP output is already active when harmonic blocking signal appears
the TRIP output will not be affected.
Freeze
HarmRestr1=On/Off Timer
AND
ST1
tDef1
I3P a
Voltage / Current I> a>b t TR1
X b AND
input selection
U3P
(Zero Sequence /
currentInput = NegSeq/3.ZeroSeq Negative Sequence)
1
voltageInput = NegSeq/3.ZeroSeq K
START
BLOCK 1
TRIP
VDepFact1 1
a
a>b tDef2
Zero sequence 2nd harmonic and I>> X b TR2
AND t
fundamental current extraction from
phase current
ST2
1
K
VDepFact2
Freeze
HarmRestr2 = On/Off AND Timer
I_2ndHarm/I_fund
I_2nd/I_fund Comparison
IEC19000104 V2 EN-US
Function description IEC 61850 identification IEC 60617 identification ANSI/IEEE C37.2 device
number
Current unbalance SCUCPTOC dI>C 60N
protection of SCB
Shunt capacitor banks (SCB) are used in transmission and distribution substations for the benefit of
reactive power support and filtering. Any internal fault in the capacitor bank leads to unbalance in the
SCB and severe damage to the entire bank, which can result in an explosion or fire. Generally
internal faults in the shunt capacitor bank are due to the open or short-circuit of the capacitor units or
elements.
An internal fault will typically lead to an unbalance of currents between the two legs of the SCB. To
measure the unbalance current, several configurations are possible:
• Place a CT between the two neutral point connections of a double WYE configuration as shown
in Figure 440.
• Place a CT between the two strings of the same phase of a single WYE configuration as shown
in Figure 441.
• Place a CT between the two legs of the same phase of a H-bridge configuration as shown in
Figure 442.
For unbalance current calculation, the SCUCPTOC function uses measured phase current (I3P) and
measured unbalance current (I3UNB). Based on the measured unbalance current deviation from the
stored reference current value, the function identifies the severity of the internal fault in the SCB.
L1
IL1
L2
IL2
L3
IL3
C C C C C C
C C C C C C
C C C C C C
C C C C C C
IUNB1
Grounded
IUNB1 Ungrounded
IEC19000181-1-en.vsdx
IEC19000181 V1 EN-US
L1
IL1
L2
IL2
L3
IL3
C C C C C C
C C C C C C
C C C C C C
Grounded/Ungrounded
IEC19000182-1-en-us. vsdx
IEC19000182 V1 EN-US
Figure 441: Typical earthed/unearthed single WYE connected SCB with strings in each phase
L1
IL1
L2
IL2
L3
IL3
C C C C C C
C C C C C C
Grounded/Ungrounded
IEC19000183-1-en-us.vsdx
IEC19000183 V1 EN-US
SCUCPTOC
I3P* TRIP
I3UNB* TRL1
BLOCK TRL2
BLKTR TRL3
BLKALM START
BLKWRN STL1
INHIBIT STL2
TRIGCOMP STL3
RESETCOMP ALARM
ALML1
ALML2
ALML3
WARNING
WRN L1
WRN L2
WRN L3
BLKDL1
BLKDL2
BLKDL3
COMP EX ED
IUNBCLCL1
IUNBCLCL2
IUNBCLCL3
IEC19000184-1-en-us.vsdx
IEC19000184 V1 EN-US
11.2.4 Signals
PID-7215-INPUTSIGNALS v1
PID-7215-OUTPUTSIGNALS v2
11.2.5 Settings
PID-7215-SETTINGS v1
In case of single WYE or H-bridge capacitor bank configurations the three-phase unbalance currents
are used for the protection. For double WYE configuration, only the neutral unbalance current is used
for the protection. The internal unbalance in the capacitor bank due to capacitor units or elements
failure is measured by the SCUCPTOC function and warning, alarm, start and trip signals are issued
when the unbalance current exceeds preset levels. The terminologies of different currents used in
the document are mentioned in the following table:
Quantity Description
ĪLy Measured phase current
(where y = 1, 2, and 3)
ĪUnbLy Measured unbalance current
Īx Reference current
IBase1 and IBase2 corresponds to the primary phase currents and primary
unbalance currents, respectively.
The unbalance current in a phase or in the neutral is either due to natural differences in the capacitor
bank impedances or due to faults within the capacitor bank.
The natural unbalance current in the capacitor bank (ĪMemUnbLy) is present because of the following
factors:
To avoid operation of the SCUCPTOC function during healthy conditions of the capacitor bank, the
natural unbalance current (ĪMemUnbLy) is measured during a healthy situation and stored for future
reference. The actively measured unbalance current (ĪUnbLy) is then compensated by subtracting the
stored natural unbalance current (ĪMemUnbLy) and the resulting current is referred to as the calculated
unbalance current (ĪUnbClcLy ). By doing this, the sensitivity of the protection function improves and
can be maintained as the capacitor bank changes its natural unbalance current over its lifetime.
Storing of the natural unbalance current is achieved through an active trigger input (TRIGCOMP).
This TRIGCOMP input can be activated by using either a binary input, MMS input or through an
LHMI command.
The unbalance current flowing through the capacitor bank is directly proportional to the respective
phase current in the shunt capacitor bank and is expressed through the following equation:
I UNBLy = k ´ I X
IECEQUATION19016 V1 EN-US (Equation 235)
If any external disturbances occur, the phase currents of the SCB will be affected, which in turn
changes the unbalance current as per Equation 235. Since the natural unbalance current (ĪMemUnbLy)
is stored under the healthy condition of the system, it is scaled to the present phase current (Īx) in
order to compare correctly with the present unbalance current. This scaled natural unbalance current
is considered as the reference unbalance current which is compensated from the measured (present)
unbalance current.
For double WYE connected capacitor banks, the positive sequence component of the three-phase
current is selected as the reference current (Īx). Whereas for single WYE or H-bridge connected
capacitor banks, individual phase currents are considered as the reference current (Īx) to the
respective phase unbalance currents.
The measured unbalance current (ĪUnbLy) is referred with respect to its reference
current (Īx).
The stored natural unbalance current (ĪMemUnbLy) is scaled with the present phase current, which is
considered as the reference unbalance current (ĪRefUnbLy).
I
X
I = ×I
RefUnbLy MemUnbLy
I
MemLy
The outputs IMEMUNBLy (where y = 1, 2, and 3) and IMEMLy shows the magnitude of the recorded
value of natural unbalance current (ĪMemUnbLy) and reference current (ĪMemLy), respectively. The
output IREFUNBLy shows the magnitude of the reference unbalance current (ĪRefUnbLy).
When there is no stored current, such as when the function is first turned on, the
stored reference and stored natural unbalance current are considered as zero.
I
UnbClcLy (
= I
UnbLy
-I
Re fUnbLy )
IECEQUATION19022 V1 EN-US (Equation 237)
IX
IMemLy = IX
IMemLy
IRefUnbLy
IMemUnbLy = IUnbLy IUnbLy
IMemUnbLy
IUnbClcLy -IRefUnbLy
IEC19000188-1-en-us.vsdx
IEC19000188 V1 EN-US
If the magnitude of the calculated unbalance current (ĪUnbClcLy) is higher than the set value, an
internal fault is declared in the shunt capacitor bank.
The output IUNBCLCLy (where y = 1, 2, and 3) shows the magnitude of the calculated unbalance
current (ĪUnbClcLy).
• The measured unbalance current and reference current are considered as stored natural
unbalance current (ĪMemUnbLy) and stored reference current (ĪMemLy) respectively, and these two
currents are used for further calculation of unbalance current.
• The output COMPEXED is pulsed for a duration of 100 ms. This indicates that the function is
ready for the reference unbalance current calculation.
• The output LASTCOMP displays the date and time of the latest successfully performed trigger
event.
100 ms
COMPEXED
Z -1
Ix
T IMemLy
Z -1
IEC19000187-1-en.vsdx
IEC19000187 V1 EN-US
Ensure that IED date and time values are set or synchronized properly before the
compensation process.
All the stored current values can be reset to zero by activating RESETCOMP input. When
RESETCOMP is activated by using either a binary input or through an LHMI command, the stored
natural unbalance current (ĪMemUnbLy) and the stored reference current (ĪMemLy) resets to zero. By
returning the stored natural unbalance current value to zero, the SCUCPTOC function behaves as an
over-current protection and will respond directly to the measured unbalance current.
If SCBConf is selected as 3 unbalance curr and if any of the phase current magnitude goes below
the set minimum current level, the corresponding phase operation is blocked and the respective
output BLKDLy (where y = 1, 2, and 3) rises. The corresponding analog output IUNBCLCLy will show
a zero value.
ScbConf
IL2
Reference current BLKDLy
IL3 selection
IMin
<
IEC19000186-1-en-us.vsdx
IEC19000186 V1 EN-US
The warning level pickup signal is passed through a definite timer before giving the output WRNLy
(where y = 1, 2, and 3). The definite time delay for the warning signal can be set by using the setting
tDefWrn. The general warning output WARNING is activated when any one of the outputs among
WRNLy becomes active.
Similar to the warning logic, for the alarm output the set alarm limit IUnbalAlm> is checked. Once the
alarm level is crossed, the ALMLy output raises after the security time delay. The definite time delay
for the alarm signal can be set by using the setting tDefAlm. The general alarm output ALARM is
activated when any one of the outputs among ALMLy becomes active.
The STLy output is activated if the magnitude of the calculated unbalance current (ĪUnbClcLy) is above
the set trip level which is set by using the setting IUnbal>. The stability is checked by adding a
security time delay of approximately 20 ms.
The TRLy output is issued after a time delay, which is based on the setting CurveType.
If the setting CurveType is selected as Definite time, then definite time delay is selected for the trip
operation and the output is activated after a time delay given by the setting tDefTrip.
If the setting CurveType is selected as Programmable, then programmable curve is selected for the
trip operation and the output is activated after a time delay given by the following equation:
ì ææ A ö öü
top = max ítMin, ç ç P + B ÷ ´ k + tDef ÷ý
î èè I - C ø øþ
Where,
A, B, C, and P are the numerical coefficients which can be set by using the settings tACrv, tBCrv,
tCCrv, and tPCrv respectively.
k is the time multiplier setting value which can be set by using the setting ‘k’
tMin is the setting which provides the minimum operating time for the programmable curve
tDef is the definite time delay which can be set by using the setting tDefTrip
I is the ratio between the magnitude of calculated unbalance current (ĪUnbClcLy) and the setting
IUnbal>
The general start output START is activated when any one of the outputs among STLy becomes
active. Similarly, the general trip output TRIP is activated when any one of the outputs among TRLy
becomes active.
Once the magnitude of the calculated unbalance current (ĪUnbClcLy) goes below the set warning level,
the warning output resets after the set time delay tReset. Similarly, the alarm and trip outputs reset
after the set tReset time delay and when the magnitude of the calculated unbalance current
(ĪUnbClcLy) goes below the corresponding set levels. To avoid oscillations at the boundary conditions,
hysteresis is added to the calculated unbalance current for comparison with the set value.
The setting BlockTrip can be used to avoid tripping of the function during energization or de-
energization of SCB or while commissioning the IED. To block the TRLy and TRIP signals, select the
setting as Trip disabled.
BLKDL1
tOn 20 ms
IUnbClcL1 a tOn = tDefWrn
ABS From other WRNL3
a >b t tOff = tReset WARNING
phases WRNL2 OR
IUnbalWrn> b t
t WRNL1
tDefWrn AND
BLKWRN
tOn 20 ms
a tOn = tDefAlm
From other ALML3
a >b t tOff = tReset phases
ALARM
t ALML2 OR
IUnbalAlm> b
t ALML1
AND
tDefAlm
STL3
BLKALM From other START
phases
STL2 OR
BlockTrip STL1
AND
tOn 20 ms
a
a >b t AND tOn = tDefTrip
IUnbal> b
t
CurveType
tDefTrip From other TRL3
Definite Time tOff = tReset phases TRIP
TRL2 OR
k
t TRL1
tPCrv AND
t
tACrv
INHIBIT
OR
BLOCK
BLKTR
IEC19000179-1-en.vsdx
IEC19000179 V1 EN-US
If any programmable curve is selected as IEC curve, then tDef should be set to 0.
When SCBConf is selected as 1 unbalance curr, then all the outputs corresponding
to one unbalance current are referred to phase L1 and the remaining phases (L2 and
L3) outputs show zero.
2.8
2.6
Unbalance current (I) in (pu)
2.4
2.2
2.0
1.8
1.6
1.4
1.2
1
0 500 1000 1500
Operate time (sec)
IEC19000192-1-en.vsdx
IEC19000192 V1 EN-US
Name Value
tMin 0.0
k 1
tPCrv 2.0
tACrv 28.2
tBCrv 0.1217
tCCrv 1.0
tDef 5.00
tMin 0.00
Blocking logic
• When the BLOCK input is activated, the binary outputs of the function will be reset.
• The warning, alarm, and trip outputs can be blocked individually by using BLKWRN, BLKALM,
and BLKTR inputs respectively.
• The INHIBIT input can be used in case of any problems during switching On/Off of a capacitor
bank and also it can be used to freeze all the calculations and to block binary outputs.
Table 471 summarizes the INHIBIT and BLOCK behavior in the function.
Activated ILy and IMEMLy and IUNBCLCLy TIMER operation TRIGCOMP RESETCOMP
input signal IUNBLy IMEMUNBLy
INHIBIT - Freeze Freeze Reset Not allowed Allowed
BLOCK - - - Reset Allowed Allowed
– No impact due to the respective input activation
The reporting of reference unbalance current is performed in 1 minute interval over IEC 61850. If the
reference unbalance current changes from the last reported value, and if the change is larger than
the pre-defined limit of 2% of IBase2, then the measuring channel reports the new value irrespective
of the cyclic trigger as shown in Figure 449. Similarly the calculated unbalance current is also
reported.
Value
Value
Reported
Y5 Y6
+ΔY
-ΔY
Y”
Y’
Y1 Y2 Y7
Y4
Y3
Δt Δt Δt Δt Δt Δt
Time
IEC16000109-2-en.vsdx
IEC16000109 V2 EN-US
Reset time delay at to 2 x Iset to 0 (0.00 - 60.00) s ±0.2% or ±45 ms, whichever is
greater
Inverse time characteristics Programmable ±5.0% or ±65 ms, whichever is
greater
Minimum operate time for inverse (0.00 - 60.00) s ±0.2% or ±65 ms, whichever is
curve greater
Operate time, START at 0 to 2 x Iset Min = 30 ms -
Max = 60 ms
Reset time, START at 2 x Iset to 0 Min = 20 ms -
Max = 35 ms
Critical impulse time 10 ms typically at 0 to 10 x Iset -
11.3.1 Identification
GUID-9E095985-CC54-4BDE-8108-B10BBB5EE3EE v1
Function description IEC 61850 IEC 60617 identification ANSI/IEEE C37.2 device number
identification
Phase voltage differential SCPDPTOV Ud> 87V
based capacitor bank
unbalanced protection
Shunt capacitor banks (SCB) are used in transmission and distribution substations for the benefit of
reactive power support and filtering. Any internal fault in the capacitor bank leads to unbalance in the
SCB and severe damage to the entire bank, which can result in an explosion or fire. In the shunt
capacitor bank, the internal faults are due to open-circuit or short circuit of the capacitor units or
elements. The phase voltage differential protection function (SCPDPTOV) can detect the voltage
unbalance in the capacitor bank.
The SCPDPTOV function can be applied to grounded and ungrounded capacitor bank
configurations, where the three-phase bus and tap voltage measurements are available. The function
has the option of connecting an ungrounded capacitor bank configuration with or without neutral
voltage measurement. If a neutral VT is not available, then the zero sequence component of the bus
voltage is used as the neutral voltage (UN).The tapped voltage can be measured in percentage of the
total series capacitor groups in the bank from the ground or across a low-voltage capacitor in each
phase. The typical shunt capacitor bank configuration with VT connections is shown in Figure 450.
Bus
ULx
UTapLx
SCB
UN
Grounded/Ungrounded
IEC19000639-1-en.vsdx
IEC19000639 V1 EN-US
Figure 450: Single line diagram of the typical single WYE shunt capacitor bank configuration
SCPDPTOV
U3P* TRIP
U3PTAP* TRL1
U3NEUT TRL2
BLOCK TRL3
BLKTR START
BLKALM STL1
BLKWRN STL2
INHIBIT STL3
TRIGCOMP ALARM
RESETCOMP ALML1
ALML2
ALML3
WARNING
WRNL1
WRNL2
WRNL3
BLKDL1
BLKDL2
BLKDL3
DIFURATL1
DIFURATL2
DIFURATL3
COMPEXED
PUDIFL1
PUDIFL2
PUDIFL3
USEDURATL1
USEDURATL2
USEDURATL3
URATIOL1
URATIOL2
URATIOL3
IEC19000716-1-en.vsdx
IEC19000716 V1 EN-US
11.3.4 Signals
PID-7276-INPUTSIGNALS v1
PID-7276-OUTPUTSIGNALS v1
11.3.5 Settings
PID-7276-SETTINGS v1
The SCPDPTOV function is based on the voltage division principle across the capacitor bank. It uses
the measured bus and tap voltages to calculate the differential voltage in the shunt capacitor bank
which is caused by the internal faults. The differential voltage is either due to the difference in the
capacitor bank impedances or due to the faults within the capacitor bank. The phase voltage
differential protection is intended to operate for the capacitor elements or the units failure within the
capacitor bank.
The measured tap voltages are multiplied by the voltage ratio and subtracted from the bus voltages
to give the differential voltage (UDIFLx, where Lx = Phase L1, L2 and L3).
1
UDIFLx U Lx U TapLx
m
Where,
As per the tap position, the measured bus voltage and the tap voltage have a constant voltage ratio.
This voltage ratio can be calculated based on the tap position and set in the function (VoltRatioLx).
The function continuously calculates the voltage ratio using the measured bus voltage and tap
voltage. This calculated voltage ratio can be stored and used in the function by activating a trigger
input (TRIGCOMP). The trigger input can be activated by using either a binary input, MMS input or
through an LHMI command.
The stored voltage ratio helps to remove the differential voltage due to mismatch between real
capacitor unit values and ideal manufacturing data, variation in temperature and aging of capacitors.
In the case of ungrounded shunt capacitor bank configuration, measured neutral voltage or zero
sequence component of the bus voltage is used to calculate the voltage ratio and differential voltage.
The Shunt capacitor bank grounding type can be selected by using the parameter setting
SCBGndType.
• If the parameter setting SCBGndType is selected as Grounded, then the function uses grounded
capacitor bank configuration.
• If the parameter setting SCBGndType is selected as Ungrounded, then the function uses
ungrounded capacitor bank configuration.
The internal fault caused by open circuiting or short circuiting of the capacitor elements or the units in
the bank results in a differential voltage. Based on the magnitude of a differential voltage, the
function identifies the severity of the internal fault in the SCB.
The voltage ratio is calculated using bus, tap, and neutral voltage as follows:
U TapLx U N
U RatClcLx
U Lx U N
IECEQUATION19372 V1 EN-US (Equation 240)
Where URatClcLx is an internal signal which represents the calculated voltage ratio for phase Lx (Lx =
Phase L1, L2 and L3).
The URatClcLx is checked against plausibility limit (0.000 ≤ URatClcLx ≤ 1.000). If URatClcLx passes the
plausibility check, the output URATIOLx shows the calculated voltage ratio (URatClcLx). Otherwise, the
output URATIOLx shows 9999.999 to indicate that the calculated voltage ratio is invalid.
If URATIOLx is valid, its percentage variation from the set value (VoltRatioLx) is monitored as shown
in Equation 241. If the monitored percentage value goes above the set percentage limit
(URatioVar>), the binary output DIFURATLx is raised.
The voltage ratio URATIOLx can be stored and used for the calculation of differential voltage by
activating a trigger input (TRIGCOMP). The output USEDURATLx shows the stored voltage ratio.
• The calculated voltage ratio (URATIOLx) is saved as the stored voltage ratio (USEDURATLx)
and used for further calculation of the differential voltage.
• The output COMPEXED is pulsed for a duration of 100 ms. This indicates that the calculated
voltage ratio (URATIOLx) is ready to use for differential voltage calculation.
• The output LASTCOMP displays the date and time of the latest successfully performed trigger
event.
• The URatClcLx variation is more than ± 25% of set VoltRatioLx at the time of trigger.
• The trip signal exists.
• Bus voltage or tap voltage of any phase has disturbances at the time of trigger.
When there is no stored voltage ratio, such as when the function is first turned ON,
the set voltage ratio (VoltRatioLx) is considered as stored voltage ratio
(USEDURATLx).
When RESETCOMP is activated by using either a binary input, MMS input or through a LHMI
command, the setting value of voltage ratio (VoltRatioLx) is considered as the stored voltage ratio
(USEDURATLx) and it is used for the differential voltage calculation.
Irrespective of any other inputs (INHIBIT and BLOCK) and minimum voltage
condition, RESETCOMP input activation resets the stored voltage ratios
(USEDURATLx) to set values (VoltRatioLx).
For a grounded single WYE capacitor bank, the phase wise differential voltage is calculated using
the measured bus voltage (ULx, where Lx = Phase L1, L2 and L3), the tap voltage (UTapLx) and the
stored voltage ratio USEDURATLx. The typical grounded single WYE capacitor bank is shown in
Figure 452.
L1
L2
L3
C C C
C C C
Tap
UL1
C C C
UTapL1
C C C
IEC19000644-1-en.vsdx
IEC19000644 V1 EN-US
1
UDIFLx | U Lx U TapLx |
USEDURATLx
IECEQUATION19374 V1 EN-US (Equation 242)
Where,
UDIFLx is the differential voltage of phase Lx (Lx = Phase L1, L2 and L3)
ULx is the voltage of phase Lx at the bus. These voltages (UL1, UL2 and UL3) are derived from the
U3P input.
UTapLx is the tap voltage of the phase Lx. These voltages (UTapL1, UTapL2 and UTapL3) are derived from
the U3PTAP input.
USEDURATLx is the stored voltage ratio used for the differential voltage calculation for the phase Lx
(Lx = Phase L1, L2 and L3).
For an ungrounded single WYE capacitor bank, the phase wise differential voltage is calculated
using the measured bus voltage (ULx, where Lx = Phase L1, L2 and L3), the tap voltage (UTapLx), the
capacitor bank neutral voltage (UN) and the stored voltage ratio USEDURATLx. A typical ungrounded
single WYE capacitor bank is shown in Figure 453.
If the neutral VT is not available, the differential voltage is calculated by using the zero-sequence
component of the bus voltage. The selection of the shunt capacitor bank neutral VT availability can
be done using the parameter setting NeutVoltMeas.
• If the parameter setting NeutVoltMeas is selected as Available, then the measured neutral
voltage from the capacitor bank is used for calculation of the differential voltage.
• If the parameter setting NeutVoltMeas is selected as Not available, then the zero sequence
component of the bus voltage is used for the differential voltage calculation. In this case, the
neutral voltage is calculated as follows.
U L1 U L 2 U L3
U N U 0
3
L1
L2
L3
C C C
C C C
Tap
UL1
C C C UTapL1
C C
C
UN
IEC19000645-1-en.vsdx
IEC19000645 V1 EN-US
1
UDIFLx | U Lx U N U TapLx U N |
USEDURATLx
IECEQUATION19375 V1 EN-US (Equation 244)
Where,
UN is either the measured neutral voltage or the zero sequence component of the bus voltage
The differential voltages are expressed in percentage of base voltage UBase as follows:
UDIFLx
PUDIFLx = ´ 100
UBase 3
Where,
PUDIFLx is the percentage differential voltage of the phase Lx (Lx = Phase L1, L2 and L3).
A minimum voltage check is performed on both the bus voltages and their equivalent tap voltages.
The equivalent tap voltage is calculated by dividing the tap voltage with the stored voltage ratio
(UEDURATLx).
The output BLKDLx (Lx = Phase L1, L2 and L3) is raised if the corresponding phase bus voltage or
all three phase equivalent tap voltage goes below the set minimum voltage level. To avoid
oscillations of the BLKDLx output, a hysteresis is added for comparison with the set value.
When the function is blocked due to a minimum voltage violation, the output URATIOLx shows
9999.99 and outputs UDIFLx and PUDIFLx show a zero value.
The setting UMin> is used to set the minimum bus voltage or equivalent tap voltage level.
The phase voltage differential function has warning, alarm, and trip signals based on the magnitude
of the differential voltage. The operation levels for the warning, alarm, and trip can be independently
set. If the magnitude of the differential voltage (UDIFLx) is above the set warning level UdifWrn>, a
security time delay of approximately 20 ms is considered to check the stability of the warning pickup
level. This security time avoids incorrect operation due to de-energization and energization of the
SCB.
The warning level pickup signal is passed through a definite timer before providing the output
WRNLx (Where, x = 1, 2, and 3). The definite time delay for the warning can be set by using the
setting tDefWrn. The general warning output WARNING is raised when any of the outputs among
WRNLx becomes active.
Similar to the warning logic, the set alarm limit UdifAlm> will be checked for the alarm level. Once the
alarm level is crossed, the ALMLx output raises after a security time delay and a definite time delay.
The definite time delay can be set by using the setting tDefAlm. The general alarm output ALARM
will be raised when any of the outputs among ALMLx becomes active.
The SCPDPTOV function raises the STLx output if the magnitude of the differential voltage (UDIFLx)
is above the set trip level which is set by using the setting Udif>, after the stability is checked by
adding a security time delay of approximately 20 ms. The TRLx output activates from the output
STLx after a time delay which is based on the setting CurveType.
If the setting CurveType is selected as Definite time, the definite time delay is selected for the trip
operation and the output is activated after a time delay given by the setting tDefTrip.
If the setting CurveType is selected as Programmable, the programmable curve is selected for the
trip operation and the output is activated after a time delay set by the setting tMin or the time delay
calculated by the equation 246, whichever is greater:
k . A
t op max tMin, p
D
U U
B. C
U
Where,
A, B, C, D, and P are the numerical coefficients which can be set using the settings tACrv, tBCrv,
tCCrv, tDCrv, and tPCrv respectively.
k is the time multiplier setting which can be set using the setting k
U> is the settable trip level in % UBase which can be set using the setting Udif>
tMin is the settable minimum operating time for programmable curve which can be set using the
setting tMin
When the denominator in the expression is equal to zero, the time delay is infinity and there is an
undesired discontinuity. Therefore, a tuning parameter CrvSat is set to compensate for this
phenomenon.
In the voltage interval U> up to U>×(1.0 + CrvSat/100) the used voltage is: U>× (1.0 + CrvSat /100).
If the programmable curve is used, then this parameter can be calculated as mentioned below:
CrvSat
B´ -C = 0
100
GUID-5B25EED3-C433-4B55-B545-71205E1E6E79 V1 EN-US (Equation 247)
The general start output START is activated when any one of the outputs among STLx becomes
active. Similarly, the general trip output TRIP is activated when any one of the outputs among TRLx
becomes active.
Once the magnitude of the differential voltage (UDIFLx) drops below the set warning level, the
warning output resets after the set time delay tReset. Similarly, alarm and trip outputs reset after the
set tReset time delay and once the magnitude of the differential voltage (UDIFLx) drops below the
corresponding set levels. To avoid oscillations at boundary conditions, a hysteresis is added to the
calculated differential voltage for comparison with the set value.
The setting BlockTrip can be used to avoid tripping of the function so that the function can be used
for alarming only. To block the TRLx and TRIP signals, select the setting as Trip disabled.
BLKDL1
tOn = 20 ms
UDIFL1 a tOn = tDefWrn
ABS From other WRNL3
a>b t tOff = tReset WARNING
phases WRNL2 OR
UdifWrn> b t
t WRNL1
AND
tDefWrn
BLKWRN
tOn = 20 ms
a tOn = tDefAlm
From other ALML3
a>b t tOff = tReset phases
ALARM
ALML2 OR
UdifAlm> t
b
t ALML1
AND
tDefAlm
STL3
BLKALM From other START
phases STL2 OR
BlockTrip STL1
AND
tOn = 20 ms
a
a>b t AND tOn = tDefTrip
Udif> b
t
CurveType
TRL3
tDefTrip Definite Time tOff = tReset From other TRIP
phases TRL2 OR
k
t TRL1
AND
tPCrv
tACrv t
tBCrv
tCCrv
Programmable
tDCrv Curve
CrvSat
tMin
tReset
INHIBIT
OR
BLOCK
BLKTR
IEC19000650-1-en.vsdx
IEC19000650 V1 EN-US
Name Value
tMin 0.10
k 0.05
tPCrv 1.000
tACrv 1.000
tBCrv 1.00
tCCrv 0.0
tDCrv 0.000
CrvSat 0
2.5
1.5
1
0 tMin 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5
Operate time (sec)
IEC19000649-1-en.vsdx
IEC19000649 V1 EN-US
• When the BLOCK input is activated, the binary outputs of the function will reset and will be
suppressed as long as the BLOCK signal is active.
• The warning, alarm and trip outputs can be blocked individually using BLKWRN, BLKALM, and
BLKTR inputs respectively.
• The INHIBIT input can be used in case of any problems during switching On/Off of a capacitor
bank. Also, it can be used to freeze all the calculations and to block binary outputs.
Table 480 summarizes the INHIBIT and BLOCK behavior in the function.
The SCPDPTOV Function has below service values reported over IEC 61850:
The cyclic reporting of the calculated voltage ratio (URATIOLx) and stored voltage ratio
(USEDURATLx) is performed over IEC61850 in a reporting interval of 30 seconds. The measuring
channel reports the value independent of amplitude change as shown in Figure 456.
Y
Value Reported Value Reported
Value Reported Value Reported
(1st)
Y3 Value Reported
Y4
Y2
Y1 Y5
∆t ∆t ∆t ∆t
t
Value 1
Value 2
Value 3
Value 4
Value 5
IEC19000016‐1‐en.vsdx
IEC19000016 V1 EN-US
Figure 456: Cyclic reporting of calculated and stored voltage ratios over IEC 61850
The reporting of differential voltage over IEC 61850 is performed in a reporting interval of 1 minute.
Additionally, if the value has changed from the last reported value, and the change is larger than the
predefined limit of 1% of UBase, then the measuring channel reports the new value to a higher level
immediately irrespective of cyclic trigger as shown in Figure 457.
Value
Value
Reported
Y5 Y6
+ΔY
-ΔY
Y”
Y’
Y1 Y2 Y7
Y4
Y3
Δt Δt Δt Δt Δt Δt
Time
IEC16000109-2-en.vsdx
IEC16000109 V2 EN-US
Table 481: Phase voltage differential based capacitor bank unbalanced protection SCPDPTOV
The unbalance protection function provides the protection against faults within the shunt capacitor
bank (SCB). The protection scheme is decided based on the following:
• Fusing method
• Size of the capacitor bank
• Method of grounding
• Available CT or VT installation
The SCUVPTOV function uses the neutral voltage measurement of an ungrounded single or double
WYE configuration of SCB.
The protection arrangements are based on the terminal voltage limit and the current limit of the
capacitor units.
The natural unbalance, which exists on all the capacitor bank installations, is due to the system
voltage unbalance and the capacitor manufacturing tolerances. In addition to these natural
unbalances, there are secondary unbalance errors that are introduced by the measurement device
tolerances and variations, and by the relative changes in the capacitance due to the difference in the
capacitor unit temperatures in the capacitor bank.
The use of fuses for protecting the capacitor units and its location has influence in the design of the
capacitor bank unbalance protection. Removal of a failed element or unit by its fuse, results in an
increase in the voltage across the remaining elements or units, causing unbalance in the capacitor
bank. Unbalance protection senses these changes associated with the failure of a capacitor element
or unit.
The SCUVPTOV function considers both the bus voltage and the capacitor bank neutral voltage
which is measured between the capacitor bank neutral and ground of the system. It uses the system
bus voltages to remove the system unbalance from the measured neutral voltage. If any internal fault
occurs in the capacitor elements, then there is an unbalance in the capacitor bank and that
unbalance voltage appears across the neutral. The protection decision is taken based on the
magnitude of the neutral voltage.
SCUVPTOV
U3P* TRIP
U3NEUT* START
BLOCK ALARM
BLKTR WARNING
BLKALM BLKD
BLKWRN COMP EX ED
INHIBIT PUNU NBAL
TRIGCOMP
RESETCOMP
IEC19000110-1-en.vsdx
IEC19000110 V1 EN-US
11.4.4 Signals
PID-7329-INPUTSIGNALS v1
PID-7329-OUTPUTSIGNALS v1
11.4.5 Settings
PID-7329-SETTINGS v1
The SCUVPTOV function is used to protect an ungrounded shunt capacitor bank, which has a
neutral voltage transformer. The measured neutral voltage is used to calculate the unbalance neutral
voltage due to the capacitor failure. The function uses the bus voltage to avoid any system
unbalance effect.
The function can compensate the natural unbalance in the capacitor bank from the measured
unbalance voltage. A zero-sequence component of the three phase bus voltage is used to
compensate the system unbalance from the calculated neutral unbalance voltage. If there is any
neutral unbalance voltage after compensating for the natural and the system unbalances, then it is
because of the unit or elements failure in the capacitor bank.
As the unbalance voltage value is very small, for security reasons the warning and alarm signals
have a settable definite time delay and the trip signal has a definite time delay or a programmable
curve-based time delay.
Figure 459 shows the simplified block diagram of a neutral voltage unbalance protection function.
BLKD
Minimum COMPEXED
U3P*
voltage check LASTCOMP
K1MON
SCB
K2MON
disconnection
detection Calculation of K1USED
compensation K2USED
factors
U3NEUT*
TRIGCOMP PUNUNBAL
RESETCOMP Calculation of
INHIBIT neutral
unbalance
voltage UNUNBAL
Warning,
alarm, and
trip logic
START
WARNING
BLOCK Blocking logic ALARM
BLKWRN
TRIP
BLKALM
BLKTR
IEC19000307-1-en.vsdx
IEC19000307 V1 EN-US
Figure 460 shows the connection between SMAI and the function block of a typical ungrounded
single WYE capacitor bank.
L3
L2
L1
VL1
VL2
VL3
C C C
VL1N
C C C
V L1G C C C
C C C
N
VNG UN
IEC19000308-1-en.vsdx
IEC19000308 V1 EN-US
3V0 = VL1G + VL 2G + VL 3G
IECEQUATION19321 V1 EN-US (Equation 248)
Where,
VL1G, VL2G, and VL3G are the phase-to-ground bus voltages of phases L1, L2, and L3, respectively.
Where,
VL1N, VL2N, and VL3N are the bus voltages with respect to the neutral of phases L1, L2, and L3,
respectively.
and,
Where,
ZL1, ZL2, and ZL3 are the impedances of SCB of phases L1, L2, and L3, respectively.
I L1 + I L 2 + I L 3 = 0
IECEQUATION19324 V1 EN-US (Equation 251)
I L1 = - ( I L 2 + I L 3 )
IECEQUATION19325 V1 EN-US (Equation 252)
3 (VNG - VO ) = ( Z L1 - Z L 2 ) I L 2 + ( Z L1 - Z L 3 ) I L 3
IECEQUATION19326 V1 EN-US (Equation 253)
æ Z - Z L1 ö æ Z L 3 - Z L1 ö
VNG = V0 + ç L 2 ÷ (VNG - VL 2G ) + ç ÷ (VNG - VL 3G )
è 3 Z L2 ø è 3Z L 3 ø
IECEQUATION19327 V1 EN-US (Equation 254)
The voltage appearing at the capacitor bank neutral due to the system unbalance is the zero-
sequence component. An equivalent zero-sequence component can be derived utilizing three-phase
bus voltages. The voltage difference between the neutral unbalance voltage due to the system
unbalance and the zero-sequence voltage is adjusted to zero. Once this adjustment is made, the
effect of the system voltage unbalance is compensated for all conditions of the system unbalance.
In Equation 254, assume that all the impedances at different phases are equal (ZL1 = ZL2 = ZL3), then
Equation 254 can be written as,
VNG = V0
IECEQUATION19328 V1 EN-US (Equation 255)
VNU = VNG - V0
IECEQUATION19329 V1 EN-US (Equation 256)
However, the effects of manufacturer’s capacitor tolerances are not considered in the calculation of
VNU in Equation 256. An impedance ratio compensates for the remaining error appearing at the
neutral due to the manufacturer’s capacitor tolerance. When this error is subtracted from the
measured neutral-to-ground voltage, the remaining quantity represents the true unbalance resulting
from an element or a unit failure within the bank.
Note that K1 and K2 factors are scalar quantities whose values are ideally zero if the bank is
completely balanced.
The calculated neutral unbalance voltage is presented at the output PUNUNBAL in terms of % of
UBase and the actual value UNUNBAL is communicated through IEC 61850.
The magnitude of the compensated neutral unbalance voltage (VNU), indicates the presence of faulty
elements in the capacitor bank.
and
After solving Equation 258 and Equation 259, the factors are,
K1 =
( ( ( R (V
e ) - Re (V0 ) ) ´ ( I m (VNG ) - I m (VL 3G ) ) ) - ( ( I m (VNG ) - I m (V0 ) ) ´ ( Re (VNG ) - Re (VL 3G ) ) ) )
NG
and
K2 =
( ( ( R (V
e ) - Re (V0 ) ) ´ ( I m (VNG ) - I m (VL 2G ) ) ) - ( ( I m (VNG ) - I m (V0 ) ) ´ ( Re (VNG ) - Re (VL 2G ) ) ) )
NG
The compensation factors are automatically calculated based on the available voltage
measurements. However, it is assumed that the capacitor bank is in an acceptably balanced state
and neutral unbalance voltage is zero, for the calculation of compensation factors. The calculated
compensation factors can be stored in the IED and used for further calculation of neutral unbalance
voltage by activating the trigger input TRIGCOMP. This TRIGCOMP input can be activated by using
either a binary input, MMS input or through an LHMI command. After the successful operation of the
compensation factor update, a binary output COMPEXED is pulsed for a period of 100 ms. Also, the
function output LASTCOMP indicates the date and time of the latest successfully performed trigger
event.
Ensure that IED date and time values are set or synchronized properly before the
compensation process.
The compensation for the natural unbalance with factors K1 and K2 can be either enabled or disabled
based on the setting CompEnable. If the setting CompEnable is enabled, then the calculated
compensation factors can be stored in the IED for compensation by activating TRIGCOMP input. If
the setting CompEnable is disabled, then the compensation factors are considered as zero. The
calculated compensation factors are shown at the outputs K1MON and K2MON. When there is no
stored compensation factors, such as when the function is first turned on, the stored compensation
factors are considered as zero. The used compensation factor values are shown at outputs K1USED
and K2USED. The used compensation factor values can be reset to zero by activating the
RESETCOMP input. The RESETCOMP input can be activated either through binary input or the
LHMI command.
The calculated compensation factors are checked for stability before using them for unbalance
voltage calculation. This check will be performed once the TRIGCOMP input is received. The stability
is checked by observing the deviation in the last five K1 and K2 calculated values. If the difference is
within 2% of the present value, then the compensation factor is updated and COMPEXED is set. If
the calculated compensation factors fail during stability check or if the TRIP output exists in the
SCUVPTOV function, the present TRIGCOMP input is discarded and the COMPEXED output is not
raised.
The minimum voltage level can be set using the setting UMin>.
To avoid oscillations of the BLKD output at the boundary conditions, a hysteresis is added with the
bus voltage for comparison with the set value.
If the magnitude of the neutral unbalance voltage (UNUNBAL) is above the set warning level
UNUnbalWrn>, then a security time delay of approximately 20 ms is considered to check the stability
of the warning pickup level. This security time prevents maloperation due to de-energization,
energization, and asymmetrical switching of the SCB.
The warning level pickup signal is passed through a definite timer before giving the output
WARNING. The definite time delay for the warning signal can be set by using the setting tDefWrn.
Similar to the warning logic, the set alarm limit UNUnbalAlm> is checked for the alarm output. Once
the alarm level is crossed, the ALARM output is activated after the security time delay and the set
definite time delay (tDefAlm).
The function gives START output, if the magnitude of the neutral unbalance voltage (UNUNBAL) is
above the trip level set by the setting UNUnbal>. The stability is checked by adding a security time
delay. The TRIP output is activated from the START after a time delay based on the setting
CurveType.
ì ü
ï ï
ï k´A ï
top = max ítMin, + D ý
UNUNBAL - UNUnbal >
P
ï æ ö ï
ç B ´ - C ÷
ïî è UNUnbal > ø ïþ
Where,
A, B, C, D, and P are the numerical coefficients provided by the settings tACrv, tBCrv, tCCrv, tDCrv,
and tPCrv, respectively.
The time delay is infinity when the denominator in Equation 262 is equal to zero. There will be an
undesired discontinuity. Therefore, a tuning parameter CrvSat is set to compensate for this
phenomenon. In the unbalance voltage interval UNUnbal> up to UNUnbal> × (1.0 + CrvSat/100), the
used voltage will be: UNUnbal> × (1.0 + CrvSat/100). If the programmable curve is used, the
parameter must be calculated so that:
Once the magnitude of the neutral unbalance voltage is below the set warning level, the warning
output is reset after the set time delay tReset. Similarly, the alarm and the trip outputs are reset after
the set tReset time delay once the magnitude of the neutral unbalance voltage is less than the
corresponding set levels. But the START output resets immediately once the magnitude of the
neutral unbalance voltage is less than the set trip level. To avoid oscillations at the boundary
conditions, a hysteresis is added with the neutral unbalance voltage for comparison with the set
value.
Blocking logic
The function can be blocked by activating the BLOCK input. When the BLOCK input is activated,
• - The function will be blocked from operating binary outputs, the function will reset and will be
suppressed as long as the BLOCK signal is active.
• All the ongoing timers will reset.
• If the TRIGCOMP input is received, the calculated compensation factors can be stored in the
IED.
• The COMPEXED pulse output will be active, if the trigger command is received and valid
compensation factors are calculated and stored.
In each individual level of the warning, the alarm and the trip can be blocked through separate binary
inputs BLKWRN, BLKALM, and BLKTR respectively.
The INHIBIT input can be used in case of any problems during switching On/Off of a capacitor bank.
When the INHIBIT input is activated,
• Binary outputs from the function will reset and will be suppressed as long as the INHIBIT signal
is active.
• All the ongoing timers will reset.
• Processed values (K1MON, K2MON, K1USED, K2USED, PUNUNBAL, and UNUNBAL) are
frozen with the previous valid (plausibility checked) values.
• The function is not allowed to store the compensation factors in the IED.
The INHIBIT input can be connected from the output RECNINH of the CBPGAPC function or an
operation of any bay protection function. Figure 461 shows the logic diagram for the warning, alarm,
and trip logic.
Irrespective of INHIBIT and BLOCK inputs and minimum voltage condition, RESETCOMP input
activation resets the stored compensation factors to zero.
BLKD
tOn » 20 ms
UNUNBAL a tOn = tDefWrn
ABS
a>b t tOff = tReset
b t
UNUnbalWrn> t
WARNING
tDefWrn AND
BLKWRN
tOn » 20 ms
a tOn = tDefAlm
t
a>b tOff = tReset
UNUnbalAlm> b t
t
AND
ALARM
tDefAlm
BLKALM
BlockTrip START
AND
tOn » 20 ms
a
t AND tOn = tDefTrip
a>b
UNUnbal> b
t
CurveType
tDefTrip Definite Time tOff = tReset
k t
AND
TRIP
tPCrv
tACrv t
tBCrv
tCCrv IDMT Curve
tDCrv
tMin
CrvSat
tReset
INHIBIT
BLOCK OR
BLKTR
IEC19000309-1-en.vsdx
IEC19000309 V1 EN-US
Value
Value
Reported
Y5 Y6
+ΔY
-ΔY
Y”
Y’
Y1 Y2 Y7
Y4
Y3
Δt Δt Δt Δt Δt Δt
Time
IEC16000109-2-en.vsdx
IEC16000109 V2 EN-US
12.1.1 Identification
M14865-1 v5
f<
SYMBOL-P V1 EN-US
Underfrequency protection (SAPTUF) measures frequency with high accuracy, and is used for load
shedding systems, remedial action schemes, gas turbine startup and so on. Separate definite time
delays are provided for operate and restore.
The operation is based on positive sequence voltage measurement and requires two phase-phase or
three phase-neutral voltages to be connected. For information about how to connect analog inputs,
refer to Application manual /IED application /Analog inputs /Setting guidelines .
SAPTUF
U3P* TRIP
BLOCK START
BLKTRIP RESTORE
BLKREST BLKDMAGN
FREQ
IEC06000279_2_en.vsd
IEC06000279 V2 EN-US
12.1.4 Signals
PID-6752-INPUTSIGNALS v2
PID-6752-OUTPUTSIGNALS v2
12.1.5 Settings
PID-6752-SETTINGS v2
Underfrequency protection SAPTUF is used to detect low power system frequency. SAPTUF can
either have a definite time delay or a voltage magnitude dependent time delay. If the voltage
magnitude dependent time delay is applied, the time delay will be longer if the voltage is higher, and
the delay will be shorter if the voltage is lower. If the frequency remains below the set value for a time
period corresponding to the chosen time delay, the corresponding trip signal is issued. To avoid an
unwanted trip due to uncertain frequency measurement at low voltage magnitude, a voltage
controlled blocking of the function is available, that is, if the voltage is lower than the set blocking
voltage IntBlockLevel, the function is blocked and no START or TRIP signal is issued.
The fundamental frequency of the measured input voltage is measured continuously, and compared
with the set value, StartFrequency. The frequency function is dependent on the voltage magnitude. If
the voltage magnitude decreases below the setting IntBlockLevel, SAPTUF gets blocked, and the
output BLKDMAGN is issued. All voltage settings are made in percent of the setting UBase, which
should be set as a phase-phase voltage in kV.
To avoid oscillations of the output START signal, a hysteresis has been included.
The time delay for underfrequency protection SAPTUF can be either a settable definite time delay or
a voltage magnitude dependent time delay, where the time delay depends on the voltage level; a
high voltage level gives a longer time delay and a low voltage level causes a short time delay. For the
definite time delay, the setting tDelay sets the time delay.
For the voltage dependent time delay the measured voltage level and the settings UNom, UMin,
Exponent, tMax and tMin set the time delay according to Figure 464 and Equation 264. The setting
TimerMode is used to decide what type of time delay to apply.
Trip signal issuing requires that the underfrequency condition continues for at least the user set time
delay tDelay. If the START condition, with respect to the measured frequency ceases during this user
set delay time, and is not fulfilled again within a user defined reset time, tReset, the START output is
reset, after that the defined reset time has elapsed. Here it should be noted that after leaving the
hysteresis area, the START condition must be fulfilled again and it is not sufficient for the signal to
only return back to the hysteresis area.
The total time delay consists of the set value for time delay plus the minimum
operate time of the start function (80-90 ms).
On the RESTORE output of SAPTUF a 100ms pulse is issued, after a time delay corresponding to
the setting of tRestore, when the measured frequency returns to the level corresponding to the
setting RestoreFreq, after an issue of the TRIP output signal. If tRestore is se to 0.000 s the restore
functionality is disabled, and no output will be given.
Since the fundamental frequency in a power system is the same all over the system, except some
deviations during power oscillations, another criterion is needed to decide, where to take actions,
based on low frequency. In many applications the voltage level is very suitable, and in most cases is
load shedding preferable in areas with low voltage. Therefore, a voltage dependent time delay has
been introduced, to make sure that load shedding, or other actions, take place at the right location. At
constant voltage, U, the voltage dependent time delay is calculated according to Equation 264
undervoltage and overvoltage functions.
Exponent
é U - UMin ù
t=ê × ( tMax - tMin) + tMin
ëUNom - UMin úû
U = U measured
where:
t is the voltage dependent time delay (at constant voltage),
U is the measured voltage
Exponent is a setting,
UMin, UNom are voltage settings corresponding to
tMax, tMin are time settings.
UMin = 90%
UNom = 100%
tMax = 1.0 s
tMin = 0.0 s
Exponent = 0, 1, 2, 3, and 4
1
0
1
Exponenent
TimeDlyOperate [s]
2
3
0.5 4
0
90 95 100
U [% of UBase]
en05000075.vsd
IEC05000075 V1 EN-US
Figure 464: Voltage dependent inverse time characteristics for underfrequency protection
SAPTUF. The time delay to operate is plotted as a function of the measured
voltage, for the Exponent = 0, 1, 2, 3, 4 respectively.
If the measured voltage level decreases below the setting of IntBlockLevel, both the START and the
TRIP outputs are blocked.
The frequency measuring element continuously measures the frequency of the positive sequence
voltage and compares it to the setting StartFrequency. The frequency signal is filtered to avoid
transients due to switchings and faults. The time integrator can operate either due to a definite delay
time or to the special voltage dependent delay time. When the frequency has returned back to the
setting of RestoreFreq, the RESTORE output is issued after the time delay tRestore. The design of
underfrequency protection SAPTUF is schematically described in figure 465.
BLKDMAGN
BLOCK
block START
OR
U < IntBlockLevel
Start
&
start Trip
Voltage
output
Definite timer
logic TRIP
or
Voltage based timer
Frequency
f < StartFrequency
tReset trip
tDelay RESTORE
AND
BLKTRIP
IEC16000041-1-en.vsdx
IEC16000041 V1 EN-US
Exponent
é U - UMin ù
t=ê × ( tMax - tMin) + tMin
ëUNom - UMin úû
U = U measured
EQUATION1182 V2 EN-US
Note: The stated accuracy is valid for the voltage range 50 V – 250 V secondary.
1) The settings and test conditions are in accordance with IEC 60255-181 standard (section 6.2 – 6.7).
12.2.1 Identification
M14866-1 v4
f>
SYMBOL-O V1 EN-US
Overfrequency protection function (SAPTOF) is applicable in all situations, where reliable detection
of high fundamental power system frequency is needed.
Overfrequency occurs because of sudden load drops or shunt faults in the power network. Close to
the generating plant, generator governor problems can also cause over frequency.
SAPTOF measures frequency with high accuracy, and is used mainly for generation shedding and
remedial action schemes. It is also used as a frequency stage initiating load restoring. A definite time
delay is provided for operate.
The operation is based on positive sequence voltage measurement and requires two phase-phase or
three phase-neutral voltages to be connected. For information about how to connect analog inputs,
refer to Application manual /IED application /Analog inputs /Setting guidelines .
SAPTOF
U3P* TRIP
BLOCK START
BLKTRIP BLKDMAGN
FREQ
IEC06000280_2_en.vsd
IEC06000280 V2 EN-US
12.2.4 Signals
PID-6751-INPUTSIGNALS v2
PID-6751-OUTPUTSIGNALS v2
12.2.5 Settings
PID-6751-SETTINGS v2
Overfrequency protection SAPTOF is used to detect high power system frequency. SAPTOF has a
settable definite time delay. If the frequency remains above the set value for a time period
corresponding to the chosen time delay, the corresponding TRIP signal is issued. To avoid an
unwanted TRIP due to uncertain frequency measurement at low voltage magnitude, a voltage
controlled blocking of the function is available, that is, if the voltage is lower than the set blocking
voltage IntBlockLevel, the function is blocked and no START or TRIP signal is issued.
The fundamental frequency of the positive sequence voltage is measured continuously, and
compared with the set value, StartFrequency. Overfrequency protection SAPTOF is dependent on
the voltage magnitude. If the voltage magnitude decreases below the setting IntBlockLevel, SAPTOF
is blocked and the output BLKDMAGN is issued. All voltage settings are made in percent of the
UBase, which should be set as a phase-phase voltage in kV. To avoid oscillations of the output
START signal, a hysteresis has been included.
The time delay for Overfrequency protection SAPTOF is a settable definite time delay, specified by
the setting tDelay.
TRIP signal issuing requires that the overfrequency condition continues for at least the user set time
delay, tDelay. If the START condition, with respect to the measured frequency ceases during this
user set delay time, and is not fulfilled again within a user defined reset time, tReset, the START
output is reset, after that the defined reset time has elapsed. It is to be noted that after leaving the
hysteresis area, the START condition must be fulfilled again and it is not sufficient for the signal to
only return back to the hysteresis area.
The total time delay consists of the set value for time delay plus minimum operate
time of the start function (80 - 90 ms).
If the measured voltage level decreases below the setting of IntBlockLevel, both the START and the
TRIP outputs are blocked.
The frequency measuring element continuously measures the frequency of the positive sequence
voltage and compares it to the setting StartFrequency. The frequency signal is filtered to avoid
transients due to switchings and faults in the power system. The time integrator operates due to a
definite delay time. The design of overfrequency protection SAPTOF is schematically described in
figure 467.
BLKDMAGN
BLOCK
block START
OR
U < IntBlockLevel
Start
&
start Trip
Voltage
output
logic TRIP
Definite timer
Frequency
f > StartFrequency tReset
trip
tDelay
AND
BLKTRIP
IEC16000042-1-en.vsdx
IEC16000042 V1 EN-US
1) The settings and test conditions are in accordance with IEC 60255-181 standard (section 6.2 – 6.7).
12.3.1 Identification
M14868-1 v4
df/dt >
<
SYMBOL-N V1 EN-US
The rate-of-change of frequency protection function (SAPFRC) gives an early indication of a main
disturbance in the system. SAPFRC measures frequency with high accuracy, and can be used for
generation shedding, load shedding and remedial action schemes. SAPFRC can discriminate
between a positive or negative change of frequency. A definite time delay is provided for operate.
SAPFRC is provided with an undervoltage blocking. The operation is based on positive sequence
voltage measurement and requires two phase-phase or three phase-neutral voltages to be
connected. For information about how to connect analog inputs, refer to Application manual/IED
application/Analog inputs/Setting guidelines .
SAPFRC
U3P* TRIP
BLOCK START
BLKTRIP RESTORE
BLKREST BLKDMAGN
IEC06000281-2-en.vsd
IEC06000281 V2 EN-US
12.3.4 Signals
PID-6754-INPUTSIGNALS v2
PID-6754-OUTPUTSIGNALS v2
12.3.5 Settings
PID-6754-SETTINGS v2
Rate-of-change frequency protection SAPFRC is used to detect fast power system frequency
changes at an early stage. SAPFRC has a settable definite time delay. If the rate-of-change of
frequency remains below the set value, for negative rate-of-change, for a time period equal to the
chosen time delay, the TRIP signal is issued. If the rate-of-change of frequency remains above the
set value, for positive rate-of-change, for a time period equal to the chosen time delay, the TRIP
signal is issued. To avoid an unwanted trip due to uncertain frequency measurement at low voltage
magnitude a voltage controlled blocking of the function is available, that is, if the voltage is lower than
the set blocking voltage IntBlockLevel the function is blocked and no START or TRIP signal is issued.
If the frequency recovers, after a frequency decrease, a restore signal is issued.
The rate-of-change of the fundamental frequency of the selected voltage is measured continuously,
and compared with the set value, StartFreqGrad. Rate-of-change frequency protection SAPFRC is
also dependent on the voltage magnitude. If the voltage magnitude decreases below the setting
IntBlockLevel , SAPFRC is blocked, and the output BLKDMAGN is issued. The sign of the setting
StartFreqGrad, controls if SAPFRC reacts on a positive or on a negative change in frequency. If
SAPFRC is used for decreasing frequency that is, the setting StartFreqGrad has been given a
negative value, and a trip signal has been issued, then a 100 ms pulse is issued on the RESTORE
output, when the frequency recovers to a value higher than the setting RestoreFreq. A positive
setting of StartFreqGrad, sets SAPFRC to START and TRIP for frequency increases.
To avoid oscillations of the output START signal, a hysteresis has been included.
Rate-of-change frequency protection SAPFRC has a settable definite time delay, tDelay.
Trip signal issuing requires that the rate-of-change of frequency condition continues for at least the
user set time delay, tDelay. If the START condition, with respect to the measured frequency ceases
during the delay time, and is not fulfilled again within a user defined reset time, tReset, the START
output is reset, after that the defined reset time has elapsed. Here it should be noted that after
leaving the hysteresis area, the START condition must be fulfilled again and it is not sufficient for the
signal to only return back into the hysteresis area.
The RESTORE output of SAPFRC is set, after a time delay equal to the setting of tDelay, when the
measured frequency has returned to the level corresponding to RestoreFreq, after an issue of the
TRIP output signal. If tRestore is set to 0.000 s the restore functionality is disabled, and no output will
be given. The restore functionality is only active for lowering frequency conditions and the restore
sequence is disabled if a new negative frequency gradient is detected during the restore period,
defined by the settings RestoreFreq and tRestore.
Rate-of-change frequency protection (SAPFRC) can be partially or totally blocked, by binary input
signals or by parameter settings, where:
If the measured voltage level decreases below the setting of IntBlockLevel, both the START and the
TRIP outputs are blocked.
BLKDMAGN
BLOCK
block
OR
Voltage
U < IntBlockLevel
START
Start
Rate-of-change
&
of Frequency start
If Trip
[StartFreqGrad<0 output
AND logic
Definite timer
df/dt < StartFreqGrad]
start TRIP
OR
tReset
[StartFreqGrad>0
AND
tDelay
df/dt > StartFreqGrad]
Then
START trip
AND
BLKTRIP
RESTORE
Frequency restore
f > RestoreFreq
> tRestore
AND
BLKREST
IEC16000040-1-en.vsdx
IEC16000040 V1 EN-US
13.1.2 Identification
M14886-2 v3
13.1.3 Functionality
M13083-3 v6
The protection module is recommended as a general backup protection with many possible
application areas due to its flexible measuring and setting facilities.
The built-in overcurrent protection feature has two settable current levels. Both of them can be used
either with definite time or inverse time characteristic. The overcurrent protection steps can be made
directional with selectable voltage polarizing quantity. Additionally they can be voltage and/or current
controlled/restrained. 2nd harmonic restraining facility is available as well. At too low polarizing
voltage the overcurrent feature can be either blocked, made non directional or ordered to use voltage
memory in accordance with a parameter setting.
Additionally two overvoltage and two undervoltage steps, either with definite time or inverse time
characteristic, are available within each function.
The general function suits applications with underimpedance and voltage controlled overcurrent
solutions. The general function can also be utilized for generator transformer protection applications
where positive, negative or zero sequence components of current and voltage quantities are typically
required.
CVGAPC
I3P* TRIP
U3P* TROC1
BLOCK TROC2
BLKOC1 TRUC1
BLKOC1TR TRUC2
ENMLTOC1 TROV1
BLKOC2 TROV2
BLKOC2TR TRUV1
ENMLTOC2 TRUV2
BLKUC1 START
BLKUC1TR STOC1
BLKUC2 STOC2
BLKUC2TR STUC1
BLKOV1 STUC2
BLKOV1TR STOV1
BLKOV2 STOV2
BLKOV2TR STUV1
BLKUV1 STUV2
BLKUV1TR BLK2ND
BLKUV2 DIROC1
BLKUV2TR DIROC2
UDIRLOW
CURRENT
ICOSFI
VOLTAGE
UIANGLE
IEC05000372-2-en.vsd
IEC05000372 V2 EN-US
13.1.5 Signals
PID-7803-INPUTSIGNALS v1
PID-7803-OUTPUTSIGNALS v1
13.1.6 Settings
PID-7803-SETTINGS v1
General current and voltage protection (CVGAPC) function is always connected to three-phase
current and three-phase voltage input in the configuration tool, but it will always measure only one
current and one voltage quantity selected by the end user in the setting tool.
The user can select a current input, by a setting parameter CurrentInput, to measure one of the
current quantities shown in table 510.
11 Phase2-Phase3 CVGAPC function will measure the current phasor internally calculated as the vector
difference between the phase L2 current phasor and phase L3 current phasor (IL2-IL3)
12 Phase3-Phase1 CVGAPC function will measure the current phasor internally calculated as the vector
difference between the phase L3 current phasor and phase L1 current phasor ( IL3-IL1)
13 MaxPh-Ph CVGAPC function will measure ph-ph current phasor with the maximum magnitude
14 MinPh-Ph CVGAPC function will measure ph-ph current phasor with the minimum magnitude
15 UnbalancePh-Ph CVGAPC function will measure magnitude of unbalance current, which is internally
calculated as the algebraic magnitude difference between the ph-ph current phasor
with maximum magnitude and ph-ph current phasor with minimum magnitude. Phase
angle will be set to 0° all the time
The user can select a voltage input, by a setting parameter VoltageInput, to measure one of the
voltage quantities shown in table 511:
11 Phase2-Phase3 CVGAPC function will measure the voltage phasor internally calculated as the vector
difference between the phase L2 voltage phasor and phase L3 voltage phasor (UL2-
UL3)
12 Phase3-Phase1 CVGAPC function will measure the voltage phasor internally calculated as the vector
difference between the phase L3 voltage phasor and phase L1 voltage phasor ( UL3-
UL1)
13 MaxPh-Ph CVGAPC function will measure ph-ph voltage phasor with the maximum magnitude
14 MinPh-Ph CVGAPC function will measure ph-ph voltage phasor with the minimum magnitude
15 UnbalancePh-Ph CVGAPC function will measure magnitude of unbalance voltage, which is internally
calculated as the algebraic magnitude difference between the ph-ph voltage phasor
with maximum magnitude and ph-ph voltage phasor with minimum magnitude. Phase
angle will be set to 0° all the time
Note that the voltage selection from table 511 is always applicable regardless the actual external VT
connections. The three-phase VT inputs can be connected to IED as either three phase-to-earth
voltages, UL1, UL2 and UL3, , and or three phase-to-phase voltages UL1L2, UL2L3 and UL3L1, , and .
This information about actual VT connection is entered as a setting parameter for the pre-processing
block, which will then be taken care automatically.
The user can select one of the current quantities shown in table 512 for built-in current restraint
feature:
The parameter settings for the base quantities, which represent the base (100%) for pickup levels of
all measuring stages shall be entered as setting parameters for every CVGAPC function.
1. rated phase current of the protected object in primary amperes, when the measured Current
Quantity is selected from 1 to 9, as shown in table "".
2. rated phase current of the protected object in primary amperes multiplied by √3 (1.732 x
Iphase), when the measured Current Quantity is selected from 10 to 15, as shown in table "".
1. rated phase-to-earth voltage of the protected object in primary kV, when the measured Voltage
Quantity is selected from 1 to 9, as shown in table "".
2. rated phase-to-phase voltage of the protected object in primary kV, when the measured Voltage
Quantity is selected from 10 to 15, as shown in table "".
Two overcurrent protection steps are available. They are absolutely identical and therefore only one
will be explained here.
Overcurrent step simply compares the magnitude of the measured current quantity (see table 510)
with the set pickup level. Non-directional overcurrent step will pickup if the magnitude of the
measured current quantity is bigger than this set level. However depending on other enabled built-in
features this overcurrent pickup might not cause the overcurrent step start signal. Start signal will
only come if all of the enabled built-in features in the overcurrent step are fulfilled at the same time.
This feature will prevent overcurrent step start if the second-to-first harmonic ratio in the measured
current exceeds the set level.
Table 513 gives an overview of the typical choices (but not the only possible ones) for these two
quantities from traditional directional relays.
Table 513: Typical current and voltage choices for directional feature
Unbalance current or voltage measurement shall not be used when the directional feature is enabled.
Two types of directional measurement principles are available, I & U and IcosPhi&U. The first
principle, referred to as "I & U" in the parameter setting tool, checks that:
• the magnitude of the measured current is bigger than the set pick-up level
• the phasor of the measured current is within the operating region (defined by the relay operate
angle, ROADir parameter setting; see figure 471).
U=-3U0
RCADir
Operate region
MTA line
IEC05000252-2-en.vsd
IEC05000252 V2 EN-US
where:
RCADir is 75°
ROADir is 50°
The second principle, referred to as "IcosPhi&U" in the parameter setting tool, checks that:
• that the product I·cos(Φ) is bigger than the set pick-up level, where Φ is angle between the
current phasor and the mta line
• that the phasor of the measured current is within the operating region (defined by the I·cos(Φ)
straight line and the relay operate angle, ROADir parameter setting; see figure 471).
U=-3U0
Operate region
MTA line
IEC05000253-2-en.vsdx
IEC05000253 V2 EN-US
where:
RCADir is 75°
ROADir is 50°
Note that it is possible to decide by a parameter setting how the directional feature shall behave
when the magnitude of the measured voltage phasor falls below the pre-set value. User can select
one of the following three options:
It shall also be noted that the memory duration is limited in the algorithm to 100 ms. After that time
the current direction will be locked to the one determined during memory time and it will re-set only if
the current fails below set pickup level or voltage goes above set voltage memory limit.
StartCurr_OC1
VDepFact_OC1 * StartCurr_OC1
ULowLimit_OC1 UHighLimit_OC1
Selected Voltage
Magnitude
en05000324.vsd
IEC05000324 V1 EN-US
Figure 473: Example for OC1 step current pickup level variation as function of measured
voltage magnitude in Slope mode of operation
StartCurr_OC1
VDepFact_OC1 * StartCurr_OC1
en05000323.vsd
IEC05000323 V1 EN-US
Figure 474: Example for OC1 step current pickup level variation as function of measured
voltage magnitude in Step mode of operation
This feature will simply change the set overcurrent pickup level in accordance with magnitude
variations of the measured voltage. It shall be noted that this feature will as well affect the pickup
current value for calculation of operate times for IDMT curves (overcurrent with IDMT curve will
operate faster during low voltage conditions).
Imeasured
StartCurr_OC2
StartCurr_OC1
Atan(RestrCoeff)
Restraint
IEC05000255 V2 EN-US
When set, the start signal will start definite time delay or inverse (IDMT) time delay in accordance
with the end user setting. If the start signal has value one for longer time than the set time delay, the
overcurrent step will set its trip signal to one. Reset of the start and trip signal can be instantaneous
or time delay in accordance with the end user setting.
Two undercurrent protection steps are available. They are absolutely identical and therefore only one
will be explained here. Undercurrent step simply compares the magnitude of the measured current
quantity (see table 510) with the set pickup level. The undercurrent step will pickup and set its start
signal to one if the magnitude of the measured current quantity is smaller than this set level. The start
signal will start definite time delay with set time delay. If the start signal has value one for longer time
than the set time delay the undercurrent step will set its trip signal to one. Reset of the start and trip
signal can be instantaneous or time delay in accordance with the setting.
Two overvoltage protection steps are available. They are absolutely identical and therefore only one
will be explained here.
Overvoltage step simply compares the magnitude of the measured voltage quantity (see table 511)
with the set pickup level. The overvoltage step will pickup if the magnitude of the measured voltage
quantity is bigger than this set level.
The start signal will start definite time delay or inverse (IDMT) time delay in accordance with the end
user setting. If the start signal has value one for longer time than the set time delay, the overvoltage
step will set its trip signal to one. Reset of the start and trip signal can be instantaneous or time delay
in accordance with the end user setting.
Two undervoltage protection steps are available. They are absolutely identical and therefore only one
will be explained here.
Undervoltage step simply compares the magnitude of the measured voltage quantity (see table 511)
with the set pickup level. The undervoltage step will pickup if the magnitude of the measured voltage
quantity is smaller than this set level.
The start signal will start definite time delay or inverse (IDMT) time delay in accordance with the end
user setting. If the start signal has value one for longer time than the set time delay, the undervoltage
step will set its trip signal to one. Reset of the start and trip signal can be instantaneous or time delay
in accordance with the end user setting.
The simplified internal logics, for CVGAPC function are shown in the following figures.
The following currents and voltages are inputs to the multipurpose protection function. They must all
be expressed in true power system (primary) Amperes and kilovolts.
1. Instantaneous values (samples) of currents & voltages from one three-phase current and one
three-phase voltage input.
2. Fundamental frequency phasors from one three-phase current and one three-phase voltage
input calculated by the pre-processing modules.
3. Sequence currents & voltages from one three-phase current and one three-phase voltage input
calculated by the pre-processing modules.
1. Selects one current from the three-phase input system (see table 510) for internally measured
current.
2. Selects one voltage from the three-phase input system (see table 511) for internally measured
voltage.
3. Selects one current from the three-phase input system (see table 512) for internally measured
restraint current.
CURRENT
UC1
TRUC1
2nd Harmonic
Selected current restraint
STUC2
UC2
nd
TRUC2
2 Harmonic
restraint
STOC1
OC1 TROC1
STOC2
OC2 TROC2
2nd Harmonic
restraint
Current restraint ³1
UDIRLOW
Directionality DIROC2
Voltage control /
restraint
STOV1
OV1 TROV1
STOV2
OV2 TROV2
STUV1
Selected voltage
UV1 TRUV1
STUV2
UV2 TRUV2
VOLTAGE
en05000170.vsd
IEC05000170 V1 EN-US
Figure 476: CVGAPC function main logic diagram for built-in protection elements
Logic in figure 476 can be summarized as follows:
1. The selected currents and voltage are given to built-in protection elements. Each protection
element and step makes independent decision about status of its START and TRIP output
signals.
2. More detailed internal logic for every protection element is given in the following four figures.
3. Common START and TRIP signals from all built-in protection elements & steps (internal OR
logic) are available from multipurpose function as well.
a Freeze Timers
a>b AND
BlkLevel2nd b
Enable DEF time
second Second harmonic selected
harmonic check DEF BLKTROC1 TROC1
AND
OR
a
a>b
b
OC1=On STOC1
AND
StartCurr_OC1 BLKOC1
X
Inverse
Voltage
control or Directionality DIR_OK Inverse
time
restraint check selected
feature
Selected voltage Current
Restraint
Feature
Selected restrain current Imeasured > k Irestraint
IEC05000831‐2‐en.vsdx
IEC05000831 V3 EN-US
Figure 477: Simplified internal logic diagram for built-in first overcurrent step that is, OC1 (step OC2 has the
same internal logic)
BLKUC1TR
a Freeze Timer
a>b AND
BlkLevel2nd b
Enable
second Second harmonic
harmonic check
a TRUC1
b>a
DEF AND
b
StartCurr_UC1
AND
Operation_UC1=On
STUC1
BLKUC1
IEC05000750‐2‐en.vsdx
IEC05000750 V2 EN-US
Figure 478: Simplified internal logic diagram for built-in first undercurrent step that is, UC1 (step UC2 has the
same internal logic)
Inverse
Operation_OV1=On
Inverse time
BLKOV1 selected
en05000751.vsd
IEC05000751 V1 EN-US
Figure 479: Simplified internal logic diagram for built-in first overvoltage step OV1 (step OV2 has the same
internal logic)
Inverse
Operation_UV1=On
Inverse time
BLKUV1 selected
en05000752.vsd
IEC05000752 V1 EN-US
Figure 480: Simplified internal logic diagram for built-in first undervoltage step UV1 (step UV2 has the same
internal logic)
When enabled, the 2nd harmonic blocking function applied in UC1, UC2, OC1 and
OC2 is used to freeze the Definite and/or the Inverse Characteristics internal timers.
When the function detects a 2nd harmonic higher than the set threshold, the internal
function timers are frozen but START outputs continues to be active as long as the
measured current is above the set pickup level. Internal timers will again resume
timing when harmonic content becomes smaller than the set threshold and the
measured current is higher than the pickup value. If TRIP output is already active
when harmonic blocking signal appears the TRIP output will not be affected.
Overcurrent (non-directional):
Start time at 0 to 2 x Iset Min. = 15 ms -
Max. = 30 ms
Reset time at 2 x Iset to 0 Min. = 15 ms -
Max. = 30 ms
Start time at 0 to 10 x Iset Min. = 5 ms -
Max. = 20 ms
Reset time at 10 x Iset to 0 Min. = 20 ms -
Max. = 35 ms
Undercurrent:
Start time at 2 x Iset to 0 Min. = 15 ms -
Max. = 30 ms
Reset time at 0 to 2 x Iset Min. = 15 ms -
Max. = 30 ms
Overcurrent:
Inverse time characteristics, see table 16 curve types See table 1294, 1295 and table
1294, 1295 and table 1296 1296
Overcurrent:
Minimum operate time for inverse (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is
curves, step 1 - 2 greater
Voltage level where voltage memory (0.0 - 5.0)% of UBase ±0.5% of Ur
takes over
Start overvoltage, step 1 - 2 (2.0 - 200.0)% of UBase ±0.5% of Ur at U ≤ Ur
±0.5% of U at U > Ur
Overvoltage:
Start time at 0.8 x Uset to 1.2 x Uset Min. = 15 ms -
Max. = 30 ms
Reset time at 1.2 x Uset to 0.8 x Uset Min. = 15 ms -
Max. = 30 ms
Undervoltage:
Start time at 1.2 x Uset to 0.8 x Uset Min. = 15 ms -
Max. = 30 ms
Reset time at 1.2 x Uset to 0.8 x Uset Min. = 15 ms -
Max. = 30 ms
Overvoltage:
Inverse time characteristics, see table 4 curve types See table 1302
1302
Undervoltage:
Inverse time characteristics, see table 3 curve types See table 1303
1303
High and low voltage limit, voltage (1.0 - 200.0)% of UBase ±1.0% of Ur at U ≤ Ur
dependent operation, step 1 - 2 ±1.0% of U at U > Ur
The multi-purpose filter function block (SMAIHPAC) is arranged as a three-phase filter. It has very
much the same user interface (e.g. inputs and outputs) as the standard pre-processing function block
SMAI. However the main difference is that it can be used to extract any frequency component from
the input signal. Thus it can, for example, be used to build sub-synchronous resonance protection for
synchronous generator.
SMAIHPAC
BLOCK AI3P
G3P* AI1
AI2
AI3
AI4
IEC13000180-1-en.vsd
IEC13000180 V1 EN-US
PID-6733-INPUTSIGNALS v1
PID-6733-OUTPUTSIGNALS v1
PID-6733-SETTINGS v1
For all four analogue input signals into this filter (i.e. three phases and the residual quantity) the input
samples from the TRM module which are coming at rate of 20 samples per fundamental system
cycle are first stored. When enough samples are available in the internal memory, the phasor values
at set frequency defined by the setting parameter SetFrequency are calculated. The following values
are internally available for each of the calculated phasors:
• Magnitude
• Phase angle
• Exact frequency of the extracted signal
Note that the special filtering algorithm is used to extract these phasors. This algorithm is different
from the standard one-cycle Digital Fourier Filter typically used by the numerical IEDs. This filter
provides extremely good accuracy of measurement and excellent noise rejection, but at the same
time it has much slower response time. It is capable to extract phasor (i.e. magnitude, phase angle
and actual frequency) of any signal (e.g. 37,2Hz) present in the waveforms of the connected CTs
and/or VTs. The magnitude and the phase angle of this phasor are calculated with very high
precision. For example the magnitude and phase angle of the phasor can be estimated even if it has
magnitude of one per mille (i.e. 1‰ ) in comparison to the dominating signal (e.g. the fundamental
frequency component). Several instances of this function block are provided. These instances are
fully synchronized between each-other in respect of phase angle calculation. Thus if two multi-
purpose filters are used for some application, one for current and the second one for the voltage
signals, the power values (i.e. P & Q) at the set frequency can be calculated from them by the over-/
under-power function or CVMMXN measurement function block.
In addition to these phasors the following quantities are internally calculated as well:
In order to properly calculate phase-to-phase phasors from the individual phase phasors or vice
versa, the setting parameters ConnectionType is provided. It defines what quantities (i.e. individual
phases or phase-to-phase quantities) are physically connected to the IED analogue inputs by wiring.
Then the IED knows which one of them are the measured quantities and the other one is then
internally calculated. This setting is only important for the VT inputs, because the CTs are typically
star connected all the time.
Thus when this filter is used in conjunction with multi-purpose protection function or overcurrent
function or over-voltage function or over-power function many different protection applications can be
arranged. For example the following protection, monitoring or measurement features can be realized:
The filter output can also be connected to the measurement function blocks such as CVMMXN
(Measurements), CMMXU (Phase current measurement), VMMXU (Phase-phase voltage
measurement), etc.
The filter has as well additional capability to report the exact frequency of the extracted signal. Thus
the user can check the actual frequency of some phenomenon in the power system (e.g. frequency
of the sub-synchronous currents) and compare it with expected value obtained previously by either
calculation or simulation. For the whole three-phase filter group the frequency of the signal
connected to the first input (i.e. phase L1) is reported. This value can be then used either by over-/
under-frequency protections or reported to the built-in HMI or any other external client via the
measurement blocks such is the CVMMXN.
How many samples in the memory are used for the phasor calculation depends on the setting
parameter FilterLength. Table 518 gives overview of the used number of samples for phasor
calculation by the filter. Note that the used number of samples is always a power of number two.
Value for parameter Used No of samples for Corresponding length of Corresponding length of
FilterLength calculation (fixed, the input waveform in the input waveform in
independent from rated miliseconds for 50Hz miliseconds for 60Hz
frequency) power system power system
0.1 s 128 = 27 128 ms 107 ms
Note that the selected value for the parameter FilterLength automatically defines certain filter
properties as described below:
First in order to secure proper filter operation the selected length of the filter shall always be longer
than three complete periods of the signal which shall be extracted. Actually the best results are
obtained if at least five complete periods are available within the filtering window. Thus, this filter
feature will limit which filter lengths can be used to extract low frequency signals. For example if 16,7
Hz signal shall be extracted the minimum filter length in milliseconds shall be:
1000
3× = 180ms
16.7
EQUATION000028 V1 EN-US (Equation 265)
Thus based on the data from Table 518 the minimum acceptable value for this parameter would be
“FilterLength = 0.2 s” but more accurate results will be obtained by using “FilterLength = 0.5 s”
Second feature which is determined by the selected value for parameter FilterLength is the capability
of the filter to separate the desired signal from the other disturbing signals which may have similar
frequency value. Note that the filter output will be the phasor with the highest magnitude within
certain “pass frequency band” around the SetFrequency. Table 519 defines the natural size of this
pass frequency band for the filter, depending on the selected value for parameter FilterLength.
Value for parameter FilterLength For 50Hz power system For 60Hz power system
0.1 s ±22.5 Hz ±27.0 Hz
0.2 s ±11.5 Hz ±14.0 Hz
0.5 s ±6.0 Hz ±7.2 Hz
1.0 s ±3.0 Hz ±3.6 Hz
2.0 s ±1.5 Hz ±1.8 Hz
4.0 s ±0.8 Hz ±1.0 Hz
Thus the longer length of the filter the better capability it has to reject the disturbing signals close to
the required frequency component and any other noise present in the input signal waveform. For
example if 46 Hz signal wants to be extracted in 50Hz power system, then from Table 519 it can be
concluded that “FilterLength=1,0 s” shall be selected as a minimum value. However if frequency
deviation of the fundamental frequency signal in the power system are taken into account it may be
advisable to select “FilterLength=2,0 s” for such application.
Note that in case when no clear magnitude peak exist in the set pass frequency band the filter will
return zero values for the phasor magnitude and angle while the signal frequency will have value
minus one. Finally the set value for parameter FilterLength also defines the response time of the filter
after a step change of the measured signal. The filter will correctly estimate the new signal
magnitude once 75% of the filter length has been filed with the new signal value (i.e. after the
change).
If for any reason this natural frequency band shall be extended (e.g. to get accurate but wider filter) it
is possible to increase the pass band by entering the value different from zero for parameter
FreqBandWidth. In such case the total filter pass band can be defined as:
Example if in 60Hz system the selected values are “FilterLength =1.0 s” and “FreqBandWidth = 5.0”
the total filter pass band will be ±(3.6+5.0/2)= ± 6.1 Hz.
It shall be noted that the phasor calculation is relatively computation demanding (required certain
amount of the CPU processing time). In order to control the CPU usage for this filter, the setting
parameter OverLap is used. This setting parameter defines how often the new phasor value is
calculated during time period defined by the set value for the parameter FilterLength (see Table 518).
The following list gives some examples how this parameter influence the calculation rate for the
extracted phasor:
• when OverLap=0% the new phasor value is calculated only once per FilterLength
• when OverLap=50% the new phasor value is calculated two times per FilterLength
• when OverLap=75% the new phasor value is calculated four times per FilterLength
• when OverLap=90% the new phasor value is calculated ten times per FilterLength
Filterlength of SMAIHPAC shall be properly coordinated with the operate times of the
functions that are consuming SMAIHPAC data, in order to prevent inadvertent
operation.
In the following Figure an example from an installation of this filter on a large, 50 Hz turbo generator
with a rating in excess of 1000 MVA is presented. In this installation filter is used to measure the
stator sub-synchronous resonance currents. For this particular installation the following settings were
used for the filter:
• SetFrequency= 31.0 Hz
• FilterLength= 1.0 s
• OverLap = 75%
• FreqBandWidth= 0.0 Hz
IEC13000178-2-en.vsd
IEC13000178 V3 EN-US
b) RMS value of the sub-synchronous resonance current extracted by the filter in primary amperes.
c) Frequency of the extracted sub-synchronous resonance current provided by the filter in Hz.
Note the very narrow scale on the y-axle for b) and c). Such small scale as well indicates with which
precision and consistency the filter calculates the phasor magnitude and frequency of the extracted
stator sub-synchronous current component.
With above given settings the sub-synchronous current magnitude and frequency are calculated
approximately four times per second (that is, correct value is four times per 1024 ms).
15.1.1 Identification
M14870-1 v5
Open or short circuited current transformer cores can cause unwanted operation of many protection
functions such as differential, earth-fault current and negative-sequence current functions.
Current circuit supervision (CCSSPVC) compares the residual current from a three phase set of
current transformer cores with the neutral point current on a separate input taken from another set of
cores on the current transformer.
A detection of a difference indicates a fault in the circuit and is used as alarm or to block protection
functions expected to give inadvertent tripping.
CCSSPVC
I3P* FAIL
IREF* ALARM
BLOCK
IEC13000304-1-en.vsd
IEC13000304 V1 EN-US
15.1.4 Signals
PID-6806-INPUTSIGNALS v2
PID-6806-OUTPUTSIGNALS v2
15.1.5 Settings
PID-6806-SETTINGS v2
Current circuit supervision CCSSPVC compares the absolute value of the vectorial sum of the three
phase currents |ΣIphase| and the absolute value of the residual current |Iref| from another current
transformer set, see figure 483.
The FAIL output will be set to high when the following criteria are fulfilled:
• The numerical value of the difference |ΣIphase| – |Iref| is higher than 80% of the numerical value
of the sum |ΣIphase| + |Iref|.
• The numerical value of the current |ΣIphase| – |Iref| is equal to or higher than the set operate
value IMinOp.
• No phase current has exceeded Ip>Block during the last 10 ms.
• CCSSPVC is enabled by setting Operation = On.
The FAIL output remains activated 100 ms after the AND-gate resets when being activated for more
than 20 ms. If the FAIL lasts for more than 150 ms an ALARM will be issued. In this case the FAIL
and ALARM will remain activated 1 s after the AND-gate resets. This prevents unwanted resetting of
the blocking function when phase current supervision element(s) operate, for example, during a fault.
40 ms 100 ms
IEC05000463-3-en.vsd
IEC05000463 V3 EN-US
Figure 483: Simplified logic diagram for Current circuit supervision CCSSPVC
The operate characteristic is percentage restrained, which is shown in Figure 484.
| åI phase | - | I ref |
Slope = 1
Operation
Slope = 0.8
area
I MinOp
| åI phase | + | I ref |
99000068.vsd
IEC99000068 V1 EN-US
Due to the formulas for the axis compared, |SIphase | - |I ref | and |S I phase | + | I ref
| respectively, the slope can not be above 1.
15.2.1 Identification
M14869-1 v4
The aim of the fuse failure supervision function (FUFSPVC) is to block voltage measuring functions
at failures in the secondary circuits between the voltage transformer and the IED in order to avoid
inadvertent operations that otherwise might occur.
The fuse failure supervision function basically has three different detection methods, negative
sequence and zero sequence based detection and an additional delta voltage and delta current
detection.
The negative sequence detection algorithm is recommended for IEDs used in isolated or high-
impedance earthed networks. It is based on the negative-sequence quantities.
The zero sequence detection is recommended for IEDs used in directly or low impedance earthed
networks. It is based on the zero sequence measuring quantities.
The selection of different operation modes is possible by a setting parameter in order to take into
account the particular earthing of the network.
A criterion based on delta current and delta voltage measurements can be added to the fuse failure
supervision function in order to detect a three phase fuse failure, which in practice is more associated
with voltage transformer switching during station operations.
FUFSPVC
I3P* BLKZ
U3P* BLKU
BLOCK 3PH
CBCLOSED DLD1PH
MCBOP DLD3PH
DISCPOS STDI
BLKTRIP STDIL1
STDIL2
STDIL3
STDU
STDUL1
STDUL2
STDUL3
IEC14000065-1-en.vsd
IEC14000065 V1 EN-US
15.2.4 Signals
PID-3492-INPUTSIGNALS v9
PID-3492-OUTPUTSIGNALS v9
15.2.5 Settings
PID-3492-SETTINGS v9
The zero and negative sequence function continuously measures the currents and voltages in all
three phases and calculates, see figure 486:
The measured signals are compared with their respective set values 3U0> and 3I0<, 3U2> and 3I2<.
The function enable the internal signal FuseFailDetZeroSeq if the measured zero-sequence voltage
is higher than the set value 3U0> and the measured zero-sequence current is below the set value
3I0<.
The function enable the internal signal FuseFailDetNegSeq if the measured negative sequence
voltage is higher than the set value 3U2> and the measured negative sequence current is below the
set value 3I2<.
A drop out delay of 100 ms for the measured zero-sequence and negative sequence current will
prevent a false fuse failure detection at un-equal breaker opening at the two line ends.
Sequence Detection
3I0< CurrZeroSeq
IL1
Zero 3I0
sequence
filter 100 ms CurrNegSeq
a
IL2 a>b t
b
Negative 3I2
sequence
IL3 filter FuseFailDetZeroSeq
AND
100 ms
a
a>b t
3I2< b
FuseFailDetNegSeq
AND
3U0>
VoltZeroSeq
UL1
Zero
sequence a 3U0
a>b
b
filter
UL2 VoltNegSeq
Negative
sequence a 3U2
a>b
UL3 filter b
3U2>
IEC10000036-2-en.vsd
IEC10000036 V2 EN-US
The input BLOCK signal is a general purpose blocking signal of the fuse failure supervision function.
It can be connected to a binary input of the IED in order to receive a block command from external
devices or can be software connected to other internal functions of the IED itself in order to receive a
block command from internal functions. Through OR gate it can be connected to both binary inputs
and internal function outputs.
The input BLKTRIP is intended to be connected to the trip output from any of the protection functions
included in the IED. When activated for more than 20 ms, the operation of the fuse failure is blocked;
a fixed drop-out timer prolongs the block for 100 ms. The aim is to increase the security against
unwanted operations during the opening of the breaker, which might cause unbalance conditions for
which the fuse failure might operate.
The output signal BLKZ will also be blocked if the internal dead line detection is activated. The dead
line detection signal has a 200 ms drop-out time delay.
The input signal MCBOP is supposed to be connected via a terminal binary input to the N.C. auxiliary
contact of the miniature circuit breaker protecting the VT secondary circuit. The MCBOP signal sets
the output signals BLKU and BLKZ in order to block all the voltage related functions when the MCB is
open independent of the setting of OpMode selector. The additional drop-out timer of 150 ms
prolongs the presence of MCBOP signal to prevent the unwanted operation of voltage dependent
function due to non simultaneous closing of the main contacts of the miniature circuit breaker.
The input signal DISCPOS is supposed to be connected via a terminal binary input to the N.C.
auxiliary contact of the line disconnector. The DISCPOS signal sets the output signal BLKU in order
to block the voltage related functions when the line disconnector is open. The impedance protection
function is not affected by the position of the line disconnector since there will be no line currents that
can cause malfunction of the distance protection. If DISCPOS=0 it signifies that the line is connected
to the system and when the DISCPOS=1 it signifies that the line is disconnected from the system
and the block signal BLKU is generated.
The output BLKU can be used for blocking the voltage related measuring functions (undervoltage
protection, energizing check and so on) except for the impedance protection.
The function output BLKZ shall be used for blocking the impedance protection function.
A simplified diagram for the functionality is found in figure 487. The calculation of the changes of
currents and voltages is based on a sample analysis algorithm. The calculated delta quantities are
compared with their respective set values DI< and DU>. The algorithm detects a fuse failure if a
sufficient change in voltage without a sufficient change in current is detected in each phase
separately. The following quantities are calculated in all three phases:
The internal FuseFailDetDUDI signal is activated if the following conditions are fulfilled:
• The magnitude of the phase-ground voltage has been above UPh> for more than 1.5 cycles (i.e.
30 ms in a 50 Hz system)
• The magnitudes of DU in three phases are higher than the corresponding setting DU>
• The magnitudes of DI in three phases are below the setting DI<
• The magnitude of voltages drop in all three phases
• The zero sequence voltage is smaller than 3U0>
In addition to the above conditions, at least one of the following conditions shall be fulfilled in order to
activate the internal FuseFailDetDUDI signal:
• The magnitude of the phase currents in three phases are higher than the setting IPh>
• The circuit breaker is closed (CBCLOSED = True)
The first criterion means that detection of failure in three phases together with high current for the
three phases will set the output. The measured phase current is used to reduce the risk of false fuse
failure detection. If the current on the protected line is low, a voltage drop in the system (not caused
by fuse failure) may be followed by current change lower than the setting DI<, and therefore a false
fuse failure might occur.
The second criterion requires that the delta condition shall be fulfilled at the same time as circuit
breaker is closed. If CBCLOSED input is connected to FALSE , then only the first criterion can enable
the delta function. If the DUDI detections of three phases set the internal signal FuseFailDetDUDI at
the level high, then the signal FuseFailDetDUDI will remain high as long as the voltages of three
phases are lower then the setting Uph>.
In addition to fuse failure detection, two internal signals DeltaU and DeltaI are also generated by the
delta current and delta voltage DUDI detection algorithm. The internal signals DelatU and DeltaI are
activated when a sudden change of voltage, or respectively current, is detected. The detection of the
sudden change is based on a sample analysis algorithm. In particular DelatU is activated if at least
three consecutive voltage samples are higher then the setting DU>. In a similar way DelatI is
activated if at least three consecutive current samples are higher then the setting DI<. When DeltaU
or DeltaI are active, the output signals STDUL1, STDUL2, STDUL3 and respectively STDIL1,
STDIL2, STDIL3, based on a sudden change of voltage or current detection, are activated with a 20
ms time off delay. The common start output signals STDU or STDI are activated with a 60 ms time off
delay, if any sudden change of voltage or current is detected.
The delta function (except the sudden change of voltage and current detection) is
deactivated by setting the parameter OpDUDI to Off.
DUDI Detection
DUDI detection Phase 1
DeltaIL1
IL1
IL2
IL3 DI detection based on sample analysis OR
DI<
UL1
IL1 DeltaIL2
IL2 DUDI detection Phase 2
DeltaUL2
IL3
UL2 Same logic as for phase 1
IL1 DeltaIL3
DUDI detection Phase 3
IL2
DeltaUL3
IL3
UL3 Same logic as for phase 1
UL1
a
a<b
b
IL1
a
a>b
IPh> b AND
OR AND
CBCLOSED AND OR
UL2
a
a<b
b
IL2
a
a>b
b AND
OR AND
AND OR
UL3
a
a<b
b
IL3
a
a>b
b AND
OR AND
AND OR FuseFailDetDUDI
AND
IEC12000166-3-en.vsd
IEC12000166 V3 EN-US
Figure 487: Simplified logic diagram for the DU/DI detection part
intBlock
STDI
AND
20 ms
DeltaIL1 STDIL1
t AND
OR
20 ms
DeltaIL2
t STDIL2
AND
20 ms
DeltaIL3
t
STDIL3
AND
STDU
AND
20 ms
DeltaUL1 STDUL1
t AND
OR
20 ms
DeltaUL2
t STDUL2
AND
20 ms
DeltaUL3
t
STDUL3
AND
IEC12000165-1-en.vsd
IEC12000165 V1 EN-US
Figure 488: Internal signals DeltaU or DeltaI and the corresponding output signals
A simplified diagram for the functionality is found in figure 489. A dead phase condition is indicated if
both the voltage and the current in one phase is below their respective setting values UDLD< and
IDLD<. If at least one phase is considered to be dead the output DLD1PH and the internal signal
DeadLineDet1Ph is activated. If all three phases are considered to be dead the output DLD3PH is
activated
IL3
a
a<b
b
IDLD<
DeadLineDet1Ph
UL1
a AND
a<b
b OR DLD1PH
AND
UL2
a AND
a<b
b
AND DLD3PH
UL3 AND
a AND
a<b
b
UDLD<
intBlock
IEC10000035-1-en.vsd
IEC10000035 V2 EN-US
Figure 489: Simplified logic diagram for Dead Line detection part
A simplified diagram for the functionality is found in figure 490. The fuse failure supervision function
(FUFSPVC) can be switched on or off by the setting parameter Operation to On or Off.
For increased flexibility and adaptation to system requirements an operation mode selector, OpMode,
has been introduced to make it possible to select different operating modes for the negative and zero
sequence based algorithms. The different operation modes are:
The delta function can be activated by setting the parameter OpDUDI to On. When selected it
operates in parallel with the sequence based algorithms.
If the fuse failure situation is present for more than 5 seconds and the setting parameter SealIn is set
to On it will be sealed in as long as at least one phase voltages is below the set value USealIn<. This
will keep the BLKU and BLKZ signals activated as long as any phase voltage is below the set value
USealIn<. If all three phase voltages drop below the set value USealIn< and the setting parameter
SealIn is set to On the output signal 3PH will also be activated. The signals 3PH, BLKU and BLKZ
will now be active as long as any phase voltage is below the set value USealIn<.
If SealIn is set to On the fuse failure condition lasting more then 5 seconds is stored in the non-
volatile memory in the IED. At start-up of the IED (due to auxiliary power interruption or re-start due
to configuration change) it uses the stored value in its non-volatile memory and re-establishes the
conditions that were present before the shut down. All phase voltages must be restored above
USealIn< before fuse failure is de-activated and resets the signals BLKU, BLKZ and 3PH.
The output signal BLKU will also be active if all phase voltages have been above the setting
USealIn< for more than 60 seconds, the zero or negative sequence voltage has been above the set
value 3U0> and 3U2> for more than 5 seconds, all phase currents are below the setting IDLD<
(criteria for open phase detection) and the circuit breaker is closed (input CBCLOSED is activated).
If a MCB is used then the input signal MCBOP is to be connected via a binary input to the N.C.
auxiliary contact of the miniature circuit breaker protecting the VT secondary circuit. The MCBOP
signal sets the output signals BLKU and BLKZ in order to block all the voltage related functions when
the MCB is open independent of the setting of OpMode or OpDUDI. An additional drop-out timer of
150 ms prolongs the presence of MCBOP signal to prevent the unwanted operation of voltage
dependent function due to non simultaneous closing of the main contacts of the miniature circuit
breaker.
The input signal DISCPOS is supposed to be connected via a terminal binary input to the N.C.
auxiliary contact of the line disconnector. The DISCPOS signal sets the output signal BLKU in order
to block the voltage related functions when the line disconnector is open. The impedance protection
function does not have to be affected since there will be no line currents that can cause malfunction
of the distance protection.
TEST ACTIVE
AND
BlocFuse = Yes
BLOCK intBlock
OR
BLKTRIP 20 ms 100 ms
AND t t
FusefailStarted
AND
Any UL < UsealIn<
FuseFailDetDUDI
AND 5s
OpDUDI = On
OR t
FuseFailDetZeroSeq
AND
AND
FuseFailDetNegSeq
AND
UNsINs OR
UZsIZs OR
UZsIZs OR UNsINs
OpMode
UZsIZs AND UNsINs
OptimZsNs
OR
CurrZeroSeq
a AND
CurrNegSeq a>b
b
AND
DeadLineDet1Ph 200 ms
AND BLKZ
t OR AND
150 ms
MCBOP t
AND BLKU
60 s
t OR OR
All UL > UsealIn<
AND
VoltZeroSeq 5s
VoltNegSeq OR t
AllCurrLow
CBCLOSED
DISCPOS IEC10000033-2-en.vsd
IEC10000033 V2 EN-US
Figure 490: Simplified logic diagram for fuse failure supervision function, Main logic
Different protection functions within the protection IED operates on the basis of measured voltage at
the relay point. Some example of protection functions are:
These functions can operate unintentionally, if a fault occurs in the secondary circuits between
voltage instrument transformers and the IED. These unintentional operations can be prevented by
fuse failure supervision (VDSPVC).
VDSPVC is designed to detect fuse failures or faults in voltage measurement circuit, based on phase
wise comparison of voltages of main and pilot fused circuits. VDSPVC blocking output can be
configured to block functions that need to be blocked in case of faults in the voltage circuit.
VDSPVC
U3P1* MAINFUF
U3P2* PILOTFUF
BLOCK U1L1FAIL
U1L2FAIL
U1L3FAIL
U2L1FAIL
U2L2FAIL
U2L3FAIL
IEC14000048-1-en.vsd
IEC12000142 V2 EN-US
15.3.4 Signals
PID-3485-INPUTSIGNALS v8
PID-3485-OUTPUTSIGNALS v8
15.3.5 Settings
PID-3485-SETTINGS v8
VDSPVC requires six voltage inputs, which are the three phase voltages on main and pilot fuse
groups. The initial voltage difference between the two groups is theoretical zero in the healthy
condition. Any subsequent voltage difference will be due to a fuse failure.
If the main fuse voltage becomes smaller than the pilot fuse voltage (vMainL1 < vPilotL1 or vMainL2
< vPilotL2 or vMainL3 < vPilotL3) and the voltage difference exceeds the operation level
(Ud>MainBlock), a blocking signal will be initiated to indicate the main fuse failure and block the
voltage-dependent functions. In addition, the function also indicates the phase in which the voltage
reduction has occurred.
If the pilot fuse voltage becomes smaller than the main fuse voltage (vPilotL1 < vMainL1 or vPilotL2
< vMainL2 or vPilotL3 < vMainL3) and the voltage difference exceeds the operation level
(Ud>PilotAlarm), an alarm signal will be initiated to indicate the pilot fuse failure and also the faulty
phase where the voltage reduction occurred.
When SealIn is set to On and the fuse failure has last for more than 5 seconds, the blocked
protection functions will remain blocked until normal voltage conditions are restored above the
USealIn setting. Fuse failure outputs are deactivated when normal voltage conditions are restored.
5s
a
a<b AND OR t
USealIn b
SealIn=0
vPilotL1
+
vMainL1 -
å MAX a U1L1FAIL
OR
a>b AND
Ud>MainBlock b MAINFAIL
OR
0
MIN ABS a
a>b AND U2L1FAIL
Ud> PilotAlarm b
BLOCK
OR PILOTFAIL
vPilotL2 U1L2FAIL
vMainL2 Phase L2, same as Phase L1 U2L2FAIL
vPilotL3 U1L3FAIL
vMainL3 Phase L3, same as Phase L1 U2L3FAIL
IEC12000144-1-en.vsd
IEC12000144 V1 EN-US
15.4.1 Identification
GUID-C7108931-DECA-4397-BCAF-8BFF3B57B4EF v2
Delta supervision function is used to quickly detect (sudden) changes in the network. This can, for
example, be used to detect faults in the power system networks and islanding in grid networks.
Voltage based delta supervision (DELVSPVC) is needed at the grid interconnection point.
DELVSPVC
U3P* START
BLOCK STARTL1
STARTL2
STARTL3
STRISE
STRISEL1
STRISEL2
STRISEL3
STLOW
STLOWL1
STLOWL2
STLOWL3
DELMAGL1
DELMAGL2
DELMAGL3
IEC18000007‐1‐en.vsdx
IEC18000007 V1 EN-US
15.4.4 Signals
PID-7097-INPUTSIGNALS v1
PID-7097-OUTPUTSIGNALS v1
15.4.5 Settings
PID-7097-SETTINGS v1
The delta supervision function DELVSPVC is a phase segregated function with the following
features.
Signal pre‐processing
fundamental DFT
opMode= RMS/DFTMag
harmonic extraction
Magnitude based STARTMAG
delta calculation DELMAGLx
MinValueCheck AND
BLOCK
IEC18000008-1-en.vsdx
IEC18000008 V1 EN-US
Figure 494: Simplified logic diagram for voltage based delta supervision DELVSPVC
The setting Umin is used to check and release the signals for the delta supervision. The delta
detection is blocked for 2 cycles by Umin comparator for angle shift mode.
• Instantaneous 1 cycle
• Instantaneous 2 cycle
• True RMS
• DFT mag
• Vector Shift
This method uses the instantaneous samples for delta detection. The logic of this scheme is shown
in Figure 495. The instantaneous difference between the present sample and the one cycle (or two
cycle) old sample is used for the delta detection. The change (delta) is verified for three continuous
samples in order to release the start signal. Once the start signal is set, any subsequent change in
sample values within 60 ms will not be detected. The DELU> setting will be set in % of UB. The
sample based delta is selectable for one cycle/two cycle operation, based on the OpMode setting.
Old value buffer
Voltage sample input
1 cycle /
2 cycle
‐ Abs
60ms
>
StartSampleDelta
AND t
DelU>
q‐1
q‐1
IEC17000199-2-en.vsdx
IEC17000199 V2 EN-US
Figure 495: Simplified logic diagram for sample based delta detection
This mode uses the RMS or DFT magnitude value of the voltage signal for the delta detection. The
logic of this scheme is given in Figure 496. Difference between the present value and the old value is
used for the delta detection. The old value is chosen based on the setting DeltaT, which is defined as
the number of old power cycles.
The function has an execution cycle time of 3 ms. For a DeltaT setting of 3, the old
value is 60 ms. Therefore, accuracy of the old cycle data depends upon the
execution cycle.
The output of the comarator is ascertained for half a cycle before releasing a STARTMAG signal. In
DELVSPVC, the DelU> setting is set in % of UB. RMS based delta will have poor accuracy if the
signal contains harmonics and other frequency components. DFT Mag based delta will operate better
in these conditions.
Additional information for the STARTRISE and STARTLOW outputs of the delta are also available in
this mode. The STARTRISE and STARTLOW outputs will be sealed by the start signal. These
outputs explains the reason for the STARTMAG signal.
Seal‐in STARTLOW
logic
0.1
>
IEC17000200-2-en.vdsx
IEC17000200 V2 EN-US
Figure 496: Simplified logic diagram for RMS/DFT based delta detection
The Vector shift selection in the OpMode setting is used to set the DELVSPVC function to operate. A
change in magnitude will not have any impact on this supervision. Angle shift is measured based on
the half cycle time (HCTime) as shown in Figure 497. The figure shows a waveform shift of 40
degree in the voltage waveform. There are two half cycle times which are affected by this angle shift
namely, HCTime(k-1) and HCTime(k). A cumulative difference of two HCTime difference is calculated
to get an accurate estimate of the angle shift. This angle shift is compared with DelUang> setting to
release the STARTANGLE signal.
The logic for this mode is given in Figure 498. The DelUAng> setting will be set in absolute degrees.
Voltage
Angle shift= [{Hctime(k) ‐ Hctime(k‐2)} + {Hctime(k‐1) ‐ Hctime(k‐3)}]
Angle shift
IEC17000210-1-en.vsdx
IEC17000210 V1 EN-US
ULx Angle shift
calculation
0.5 cycle
Abs Delta Angle
> t
DelUang> STARTANGLE
Frequency difference of last 2 cycles AND
> AND
0.2 Hz
IEC18000902-1-en.vsdx
IEC18000902 V1 EN-US
Figure 498: Simplified logic diagram for angle based delta detection
15.5.1 Identification
GUID-0B735A27-6A7D-40E1-B981-91B689608495 v1
Delta supervision function is used to quickly detect (sudden) changes in the network. This can, for
example, be used to detect disturbances in the power system network. Current based delta
supervision (DELISPVC) provides selectivity between load change and the fault.
Present power system has many power electronic devices or FACTS devices, which injects a large
number of harmonics into the system. The function has additional features of 2nd harmonic blocking
and 3rd harmonic start level adaption. The 2nd harmonic blocking secures the operation during the
transformer charging, when high inrush currents are supplied into the system.
DELISPVC
I3P* START
BLOCK STARTL1
STARTL2
STARTL3
STRISE
STRISEL1
STRISEL2
STRISEL3
STLOW
STLOWL1
STLOWL2
STLOWL3
ADAPTVAL
HARM2BLK
DELMAGL1
DELMAGL2
DELMAGL3
IEC18000005-1-en.vsdx
IEC18000005 V1 EN-US
15.5.4 Signals
PID-7098-INPUTSIGNALS v1
PID-7098-OUTPUTSIGNALS v1
15.5.5 Settings
PID-7098-SETTINGS v1
The delta supervision function is a phase segregated function. Following are the features of
DELISPVC:
Signal pre‐processing
fundamental DFT
opMode= RMS/DFTMag
harmonic extraction
Magnitude based STARTMAG
delta calculation DELMAGLx
DFTMagToComp
rd
3 harmonic based
ADAPTVAL
adaption nd HARM2BLK
2 harmonic
blocking
AND
MinValueCheck
BLOCK
IEC18000006-1-en.vsdx
IEC18000006 V1 EN-US
Figure 500: Simplified logic diagram for current based delta supervision DELISPVC
The setting Imin is used to check and release the signals for the delta supervision. This setting can
be used to obtain selectivity between load current and fault current.
• Instantaneous 1 cycle
• Instantaneous 2 cycle
• True RMS
• DFT mag
This method uses the buffer of instantaneous sample for delta detection. The logic of this scheme is
given in Figure 501. The instantaneous difference between the present sample and the one cycle (or
two cycle) old sample is used for the delta detection. The change (vectorial delta) is verified for three
continuous samples in order to release the start signal. This delta calculation is affected by angle or
magnitude or both changes in the signal in the last one cycle/two cycle. It is also known as vectorial
delta scheme. Once the start signal is set, any subsequent change in sample values within 60 ms will
not be detected. The DelI> setting will be set in % of IB. The sample based delta is selectable for one
cycle/two cycle operation, based on the OpMode setting.
Old value buffer
Current Samples 1 cycle /
2 cycle
‐
60ms
Abs
> AND
StartSampleDelta
t
DelI>
q‐1
q‐1
IEC17000191-2-en.vsdx
IEC17000191 V2 EN-US
Figure 501: Simplified logic diagram for sample based delta detection
This mode uses the RMS or DFT magnitude value of the current signal for the delta detection. The
logic of this scheme is given in Figure 502. Difference between the present value and the old value is
used for the delta detection. The old value is chosen based on the setting DeltaT, which is defined as
the number of old power cycles.
The function has an execution cycle of 3 ms. For a DeltaT setting of 3, the old value
is 60 ms. Therefore, accuracy of the old cycle data depends upon the execution
cycle.
The output of the comparator is ascertained for half a cycle before releasing a STARTMAG signal. In
DELISPVC, the DelI> setting is set in % of IB.
Additional information for the STARTRISE and STARTLOW outputs of the delta are also available in
this mode. The STARTRISE and STARTLOW outputs will be sealed by the start signal. These
outputs explains the reason for the STARTMAG signal.
Seal‐in STARTLOW
logic
0.1
>
Seal‐in STARTRISE
> logic
RMS Input Delay defined by ‐0.1
DeltaT
0. 5 cycle
‐ Abs STARTMAG
> t
DelI>
IEC17000192-2-en.vsdx
IEC17000192 V2 EN-US
Figure 502: Simplified logic diagram for RMS based delta detection
Presence of the harmonics is another reason for maloperation of the delta based protection. The 2nd
harmonic blocking is an additional security feature in this function. It can be enabled by the
EnaHarm2Blk setting. If the ratio of 2nd harmonic frequency signal magnitude to the fundamental
frequency magnitude is greater than the set level harmBlkLev, then this feature will block the start
signal of the delta protection. The logic for this functionality is shown in Figure 503. The tON of 1.25
cycle is added to ensure a reliable harmonic blocking. The tOFF of 2 cycles is added to block the
operation during any sudden increase in the current load.
EnaHarm2Blk
2 cycles
t HARM2BLK
DFTInput‐2ndHarm AND
< 1.25 cycle
t
DFTInput ‐ fundamental
X
HarmBlkLev
IEC17000194-2-en.vsdx
IEC17000194 V2 EN-US
Figure 503: Simplified logic diagram for 2nd harmonic blocking logic
Present days power system network has high amount of the 3rd harmonics presence due to heavy
power electronic devices. In such case, many networks modify the settings based on the 3rd
harmonic present in the system. Delta supervision can be adapted based on the 3rd harmonic
present in the signal. When OpMode is set to DFTMag and EnStValAdap is set to is Enable, then the
setting DelI> will change based on the StValGrad setting if the third harmonic is greater than the set
level defined by the Harm3Level setting. The logic for this functionality is shown in Figure 504.
DeltaMode = DFTMag
EnStValAdap = Enable/Disable
2 cycle
t ADAPTSTLEV
rd
DFTInput ‐ 3 Harmonics AND
< 1.25 cycle
DFTInput ‐ fundamental t
X
Harm3Lev
StValGrad X T DeltaMagToComp
F
DelI>
IEC17000195-2-en.vsdx
IEC17000195 V2 EN-US
Figure 504: Simplified logic diagram for 3rd harmonic restrain of MagStVal setting
Since this mode is adaptably changing the setting, the tOFF time is mandatory to ensure the reliable
operation during any sudden change.
15.6.1 Identification
GUID-66CFBA71-B3A4-489F-B7F4-F1909B75E1DD v1
Delta supervision functions are used to quickly detect (sudden) changes in the power system. Real
input delta supervision (DELSPVC) function is a general delta function. It is used to detect the
change measured qualities over a settable time period, such as:
• Power
• Reactive power
• Temperature
• Frequency
• Power factor
DELSPVC
BLOCK START
INPUT STRISE
STLOW
DELREAL
IEC17000202-1-en.vsdx
IEC17000202 V1 EN-US
15.6.4 Signals
PID-7096-INPUTSIGNALS v1
PID-7096-OUTPUTSIGNALS v1
15.6.5 Settings
PID-7096-SETTINGS v1
Delta supervision of real input DELSPVC is a general delta function with the following features:
Seal‐in STARTLOW
Logic
>
0.1
Seal‐in STARTRISE
Logic
REALIN Delay defined by >
‐0.1
DeltaT
0. 5 cycle
‐ Abs
> t
DelStLevel
tHold
& t
>
MinStVal
IEC17000203-1-en.vsdx
IEC17000203 V1 EN-US
The outputs STARTRISE and STARTLOW are released based on the difference (respectively above
and below) from the old value at the instant when the START signal is released.
Section 16 Control
16.1 Synchrocheck, energizing check, and synchronizing
SESRSYN IP14558-1 v4
16.1.1 Identification
M14889-1 v4
SYMBOL-M V1 EN-US
The Synchronizing function allows closing of asynchronous networks at the correct moment including
the breaker closing time, which improves the network stability.
Synchrocheck, energizing check, and synchronizing (SESRSYN) function checks that the voltages
on both sides of the circuit breaker are in synchronism, or with at least one side dead to ensure that
closing can be done safely.
SESRSYN function includes a built-in voltage selection scheme for double bus and 1½ breaker or
ring busbar arrangements.
Manual closing as well as automatic reclosing can be checked by the function and can have different
settings.
For systems, which can run asynchronously, a synchronizing feature is also provided. The main
purpose of the synchronizing feature is to provide controlled closing of circuit breakers when two
asynchronous systems are in phase and can be connected. The synchronizing feature evaluates
voltage difference, phase angle difference, slip frequency and frequency rate of change before
issuing a controlled closing of the circuit breaker. Breaker closing time is a setting.
SESRSYN
U3PBB1* SYNOK
U3PBB2* AUTOSYOK
U3PLN1* AUTOENOK
U3PLN2* MANSYOK
BLOCK MANENOK
BLKSYNCH TSTSYNOK
BLKSC TSTAUTSY
BLKENERG TSTMANSY
B1QOPEN TSTENOK
B1QCLD USELFAIL
B2QOPEN B1SEL
B2QCLD B2SEL
LN1QOPEN LN1SEL
LN1QCLD LN2SEL
LN2QOPEN SYNPROGR
LN2QCLD SYNFAIL
UB1OK UOKSYN
UB1FF UDIFFSYN
UB2OK FRDIFSYN
UB2FF FRDIFFOK
ULN1OK FRDERIVA
ULN1FF UOKSC
ULN2OK UDIFFSC
ULN2FF FRDIFFA
STARTSYN PHDIFFA
TSTSYNCH FRDIFFM
TSTSC PHDIFFM
TSTENERG INADVCLS
AENMODE UDIFFME
MENMODE FRDIFFME
PHDIFFME
UBUS
ULINE
MODEAEN
MODEMEN
IEC10000046-1-en.vsd
IEC10000046 V1 EN-US
16.1.4 Signals
PID-6724-INPUTSIGNALS v1
PID-6724-OUTPUTSIGNALS v1
16.1.5 Settings
PID-6724-SETTINGS v2
The synchrocheck feature measures the conditions across the circuit breaker and compares them to
set limits. The output for closing operation is given when all measured quantities are simultaneously
within their set limits.
The energizing check feature measures the bus and line voltages and compares them to both high
and low threshold detectors. The output is given only when the actual measured quantities match the
set conditions.
The synchronizing feature measures the conditions across the circuit breaker, and also determines
the angle change occurring during the closing delay of the circuit breaker, from the measured slip
frequency. The output is given only when all measured conditions are simultaneously within their set
limits. The closing of the output is timed to give closure at the optimal time including the time needed
for the circuit breaker and the closing circuit operation.
The voltage difference, frequency difference and phase angle difference values are measured in the
IED centrally and are available for the SESRSYN function for evaluation. By setting the phases used
for SESRSYN, with the settings SelPhaseBus1, SelPhaseBus2, SelPhaseLine1 and SelPhaseLine2,
a compensation is made automatically for the voltage amplitude difference and the phase angle
difference caused if different setting values are selected for both sides of the breaker. If needed, an
additional phase angle adjustment can be done for selected line voltage with the PhaseShift setting.
Some restrictions when using CBConfig selections 1½ bus CB, 1½ bus alt.CB and
Tie CB are described in Table 561 Such restriction are applicable only when a power
transformer is connected in the diameter and VT used for synchrocheck function is
located on the other side of the transformer.
For double bus single circuit breaker and 1½ circuit breaker arrangements, the SESRSYN function
blocks have the capability to make the necessary voltage selection. For double bus single circuit
breaker arrangements, selection of the correct voltage is made using auxiliary contacts of the bus
disconnectors. For 1½ circuit breaker arrangements, correct voltage selection is made using auxiliary
contacts of the bus disconnectors as well as the circuit breakers.
The internal logic for each function block as well as, the input and outputs, and the setting
parameters with default setting and setting ranges is described in this document. For application
related information, please refer to the application manual.
M14833-3 v5
The logic diagrams that follow illustrate the main principles of the SESRSYN function components
such as Synchrocheck, Synchronizing, Energizing check and Voltage selection, and are intended to
simplify the understanding of the function.
The function will compare the bus and line voltage values with the set values for UHighBusSC and
UHighLineSC.
If both sides are higher than the set values, the measured values are compared with the set values
for acceptable frequency, phase angle and voltage difference: FreqDiffA, FreqDiffM, PhaseDiffA,
PhaseDiffM and U DiffSC. If additional phase angle adjustment is done with the PhaseShift setting,
the adjustment factor is deducted from the line voltage before the comparison of the phase angle
values.
The frequency on both sides of the circuit breaker is also measured. The frequencies must not
deviate from the rated frequency more than ±5Hz. The frequency difference between the bus
frequency and the line frequency is measured and may not exceed the set value FreqDiff.
Two sets of settings for frequency difference and phase angle difference are available and used for
the manual closing and autoreclose functions respectively, as required.
The inputs BLOCK and BLKSC are available for total block of the complete SESRSYN function and
selective block of the Synchrocheck function respectively. Input TSTSC will allow testing of the
function where the fulfilled conditions are connected to a separate test output.
The outputs MANSYOK and AUTOSYOK are activated when the actual measured conditions match
the set conditions for the respective output. The output signal can be delayed independently for
MANSYOK and AUTOSYOK conditions.
A number of outputs are available as information about fulfilled checking conditions. UOKSC shows
that the voltages are high, UDIFFSC, FRDIFFA, FRDIFFM, PHDIFFA, PHDIFFM shows when the
voltage difference, frequency difference and phase angle difference are out of limits.
Output INADVCLS, inadvertent circuit breaker closing, indicates that the circuit breaker has been
closed at wrong phase angle by mistake. The output is activated, if the voltage conditions are fulfilled
at the same time the phase angle difference between bus and line is suddenly changed from being
larger than 60 degrees to smaller than 5 degrees.
OperationSC = On
AND TSTAUTSY
AND
invalidSelection AND
OR AUTOSYOK
AND
0-60 s
AND t
tSCA
UDiffSC 50 ms
AND t
UHighBusSC
UOKSC
AND
UHighLineSC
UDIFFSC
1
1
FRDIFFA
FreqDiffA
1
PHDIFFA
PhaseDiffA
UDIFFME
voltageDifferenceValue
FRDIFFME
frequencyDifferenceValue
PHDIFFME
phaseAngleDifferenceValue
32 ms 100 ms
AND t INADVCLS
PhDiff > 60° AND
PhDiff < 5°
IEC07000114-6-en.vsdx
IEC07000114 V6 EN-US
Figure 508: Simplified logic diagram for the auto synchrocheck function
The function will compare the values for the bus and line voltage with the set values for
UHighBusSynch and UHighLineSynch, which is a supervision that the voltages are both live. Also the
voltage difference is checked to be smaller than the set value for UDiffSynch, which is a p.u value of
set voltage base values. If both sides are higher than the set values and the voltage difference
between bus and line is acceptable, the measured values are compared with the set values for
acceptable frequency FreqDiffMax and FreqDiffMin, rate of change of frequency FreqRateChange
and phase angle CloseAngleMax.
The measured frequencies between the settings for the maximum and minimum frequency will
initiate the measuring and the evaluation of the angle change to allow operation to be sent at the
right moment including the set tBreaker time. The calculation of the operation pulse sent in advance
is using the measured SlipFrequency and the set tBreaker time. To prevent incorrect closing pulses,
a maximum closing angle between bus and line is set with CloseAngleMax. Table 560 below shows
the maximum settable value for tBreaker when CloseAngleMax is set to 15 or 30 degrees, at different
allowed slip frequencies for synchronizing. To minimize the moment stress when synchronizing near
a power station, a narrower limit for CloseAngleMax needs to be used.
Table 560: Dependencies between tBreaker and SlipFrequency with different CloseAngleMax values
tBreaker [s] (max settable value) with tBreaker [s] (max settable value) with SlipFrequency [Hz]
CloseAngleMax = 15 degrees [default CloseAngleMax = 30 degrees [max (BusFrequency -
value] value] LineFrequency)
0.040 0.080 1.000
0.050 0.100 0.800
0.080 0.160 0.500
0.200 0.400 0.200
0.400 0.810 0.100
1.000 0.080
0.800 0.050
1.000 0.040
At operation the SYNOK output will be activated with a pulse tClosePulse and the function resets.
The function will also reset if the synchronizing conditions are not fulfilled within the set tMaxSynch
time. This prevents that the function is, by mistake, maintained in operation for a long time, waiting
for conditions to be fulfilled.
The inputs BLOCK and BLKSYNCH are available for total block of the complete SESRSYN function
and block of the Synchronizing function respectively. TSTSYNCH will allow testing of the function
where the fulfilled conditions are connected to a separate output.
OperationSynch=On
TSTSYNCH
STARTSYN
invalidSelection
SYNPROGR
AND
BLOCK AND
S
BLKSYNCH OR
R
UDiffSynch
50 ms SYNOK
AND
UHighBusSynch AND t
UHighLineSynch OR
FreqDiffMax TSTSYNOK
AND
FreqDiffMin
tClosePulse
FreqRateChange
AND
fBus&fLine ± 5Hz
tMaxSynch
CloseAngleMax AND
SYNFAIL
FreqDiff
Close pulse
in advance
tBreaker
=IEC06000636=5=en=Original.vsd
IEC06000636 V5 EN-US
The function measures voltages on the busbar and the line to verify whether they are live or dead.
This is done by comparing with the set values UHighBusEnerg and ULowBusEnerg for bus
energizing and UHighLineEnerg and ULowLineEnerg for line energizing.
The frequency on both sides of the circuit breaker is also measured. The frequencies must not
deviate from the rated frequency more than +/-5Hz.
The Energizing direction can be selected individually for the Manual and the Automatic functions
respectively. When the conditions are met the outputs AUTOENOK and MANENOK respectively will
be activated if the fuse supervision conditions are fulfilled. The output signal can be delayed
independently for MANENOK and AUTOENOK conditions. The Energizing direction can also be
selected by an integer input AENMODE respective MENMODE, which for example, can be
connected to a Binary to Integer function block (B16I). Integers supplied shall be 1=Off, 2=DLLB,
3=DBLL and 4= Both. Not connected input will mean that the setting is done from Parameter Setting
tool. The active position can be read on outputs MODEAEN resp MODEMEN. The modes are
0=OFF, 1=DLLB, 2=DBLL and 3=Both.
The inputs BLOCK and BLKENERG are available for total block of the complete SESRSYN function
respective block of the Energizing check function. TSTENERG will allow testing of the function where
the fulfilled conditions are connected to a separate test output.
manEnergOpenBays
MANENOK
OR
TSTENERG
BLKENERG
OR
BLOCK
selectedFuseOK
UHighBusEnerg
DLLB 50ms tManEnerg
AND
OR t t
AND
OR
ULowLineEnerg AND
ManEnerg BOTH
ULowBusEnerg
DBLL
AND
UHighLineEnerg
TSTENOK
ManEnergDBDL AND AND
UMaxEnerg
fBus and fLine ±5 Hz
IEC14000031-2-en.vsdx
IEC14000031 V2 EN-US
TSTENERG
BLKENERG
OR
BLOCK
selectedFuseOK
UHighBusEnerg
DLLB 50ms tAutoEnerg
AND
OR t t
AND OR
AUTOENOK
ULowLineEnerg AND
BOTH
AutoEnerg
ULowBusEnerg
DBLL
AND
UHighLineEnerg
TSTENOK
UMaxEnerg AND
IEC14000030-2-en.vsdx
IEC14000030 V2 EN-US
BLKENERG
BLOCK OR manEnergOpenBays
AND
ManEnerg
1½ bus CB
CBConfig AND
B1QOPEN
LN1QOPEN AND
OR
B1QCLD
B2QOPEN
AND
LN2QOPEN
B2QCLD
AND
Tie CB
AND
AND
OR
AND
IEC14000032-1-en.vsd
IEC14000032 V1 EN-US
The UB1OK/UB2OK and UB1FF/UB2FF inputs are related to the busbar voltage and the ULN1OK/
ULN2OK and ULN1FF/ULN2FF inputs are related to the line voltage. Configure them to the binary
input or function outputs that indicate the status of the external fuse failure of the busbar and line
voltages. In the event of a fuse failure, the energizing check function is blocked. The synchronizing
and the synchrocheck function requires full voltage on both sides, thus no blocking at fuse failure is
needed.
The voltage selection type to be used is set with the parameter CBConfig.
If No voltage sel. is set the voltages used will be U-Line1 and U-Bus1. This setting is also used in the
case when external voltage selection is provided. Fuse failure supervision for the used inputs must
also be connected.
The voltage selection function, selected voltages, and fuse conditions are used for the
Synchronizing, Synchrocheck and Energizing check inputs.
For the disconnector positions it is advisable to use (NO) a and (NC) b type contacts to supply
Disconnector Open and Closed positions but, it is also possible to use an inverter for one of the
positions.
If breaker or disconnector positions not are available for deciding if energizing is allowed, it is
considered to be allowed to manually energize. This is only allowed for manual energizing in 1½
breaker and Tie breaker arrangements. Manual energization of a completely open diameter in 1 1/2
CB switchgear is allowed by internal logic.
Voltage selection for a single circuit breaker with double busbars M14838-3 v10
The setting CBConfig selected for Double Bus activates the voltage selection for single CB and
double busbars. This function uses the binary input from the disconnectors auxiliary contacts
B1QOPEN-B1QCLD for Bus 1, and B2QOPEN-B2QCLD for Bus 2 to select between bus 1 and bus
2 voltages. If the disconnector connected to bus 1 is closed and the disconnector connected to bus 2
is opened the bus 1 voltage is used. All other combinations use the bus 2 voltage. The outputs
B1SEL and B2SEL respectively indicate the selected Bus voltage.
The function checks the fuse failure signals for bus 1, bus 2 and line voltage transformers. Inputs
UB1OK-UB1FF supervise the MCB for Bus 1 and UB2OK-UB2FF supervises the MCB for Bus 2.
ULN1OK and ULN1FF supervises the MCB for the Line voltage transformer. The inputs fail (FF) or
healthy (OK) can alternatively be used dependent on the available signal. If a VT failure is detected
in the selected voltage source an output signal USELFAIL is set. This output signal is true if the
selected bus or line voltages have a VT failure. This output as well as the function can be blocked
with the input signal BLOCK. The function logic diagram is shown in figure 513.
B1QOPEN
B1SEL
B1QCLD AND
B2QOPEN B2SEL
AND
1
B2QCLD
invalidSelection
AND
bus1Voltage busVoltage
bus2Voltage
UB1OK AND
UB1FF OR
OR selectedFuseOK
AND
UB2OK AND
UB2FF OR USELFAIL
AND
ULN1OK
ULN1FF OR
BLOCK
en05000779-2.vsd
IEC05000779 V2 EN-US
Figure 513: Logic diagram for the voltage selection function of a single circuit breaker with double busbars
With the setting parameter CBConfig the selection of actual CB location in the 1½ circuit breaker
switchgear is done. The settings are: 1½ bus CB, 1½ alt. bus CB or Tie CB.
This voltage selection function uses the binary inputs from the disconnectors and circuit breakers
auxiliary contacts to select the right voltage for the SESRSYN function. For the bus circuit breaker
one side of the circuit breaker is connected to the busbar and the other side is connected either to
line 1, line 2 or the other busbar depending on the selection of voltage circuit.
The tie circuit breaker is connected either to bus 1 or line 1 voltage on one side and the other side is
connected either to bus 2 or line 2 voltage. Four different output combinations are possible, bus to
bus, bus to line, line to bus and line to line.
Some restrictions when using CBConfig selections 1½ bus CB, 1½ bus alt.CB and
Tie CB are described in Table 561. Such restriction are applicable only when a
power transformer is connected in the diameter and VT used for synchrocheck
function is located on the other side of the transformer.
Table 561: Limitations for VT selection regarding selected value for CBConfig
CBConfig setting Possible closing Used GblBaseSel settings PhaseShift setting Conclusion
between has impact on
1½ bus CB Bus1 - Line1 GblBaseSelBus => Bus1 Line1
GblBaseSelLine => Line1
Bus1 - Line2 GblBaseSelBus => Bus1 Line2
GblBaseSelLine => Line2
Bus1 - Bus2 GblBaseSelBus => Bus1 No impact Bus1 and Bus2 must have
GblBaseSelBus => Bus2 same base voltage.
GblBaseSelLine has no impact PhaseShift setting has no
impact.
1½ bus alt.CB Bus2 - Line2 GblBaseSelBus => Bus2 Line2
GblBaseSelLine => Line2
Bus2 - Line1 GblBaseSelBus => Bus2 Line1
GblBaseSelLine => Line1
Bus2 - Bus1 GblBaseSelBus => Bus2 No impact Bus2 and Bus1 must have
GblBaseSelBus => Bus1 same base voltage.
GblBaseSelLine has no impact PhaseShift setting has no
impact.
Table continues on next page
CBConfig setting Possible closing Used GblBaseSel settings PhaseShift setting Conclusion
between has impact on
Tie CB Bus1 - Line2 GblBaseSelBus => Bus1 Line2
GblBaseSelLine => Line2
Bus1 - Bus2 GblBaseSelBus => Bus1 No impact Bus1 and Bus2 must have
GblBaseSelBus => Bus2 same base voltage.
GblBaseSelLine has no impact PhaseShift setting has no
impact.
Bus2 - Line1 GblBaseSelBus => Bus2 Line1
GblBaseSelLine => Line1
Line1 - Line2 GblBaseSelLine => Line1 Line2 Line1 and Line2 must
GblBaseSelLine => Line2 have same base voltage.
GblBaseSelBus has no affect
The function also checks the fuse failure signals for bus 1, bus 2, line 1 and line 2. If a VT failure is
detected in the selected voltage an output signal USELFAIL is set. This output signal is true if the
selected bus or line voltages have a MCB trip. This output as well as the function can be blocked with
the input signal BLOCK. The function block diagram for the voltage selection of a bus circuit breaker
is shown in figure 514 and for the tie circuit breaker in figure 515.
LN1QOPEN
AND
LN1SEL
LN1QCLD
B1QOPEN
LN2SEL
B1QCLD AND AND
B2SEL
OR
LN2QOPEN
AND invalidSelection
LN2QCLD AND
AND
B2QOPEN
B2QCLD AND
line1Voltage lineVoltage
line2Voltage
bus2Voltage
UB1OK
UB1FF OR
OR selectedFuseOK
UB2OK AND
AND
UB2FF OR
USELFAIL
ULN1OK AND
AND
ULN1FF OR
ULN2OK
AND
ULN2FF OR
BLOCK
en05000780-2.vsd
IEC05000780 V2 EN-US
Figure 514: Simplified logic diagram for the voltage selection function for a bus circuit breaker in a 1 1/2
breaker arrangement
LN1QOPEN
AND
LN1SEL
LN1QCLD
B1SEL
1
B1QOPEN AND
AND
B1QCLD AND
line1Voltage busVoltage
bus1Voltage
LN2QOPEN
LN2SEL
LN2QCLD AND
B2SEL
1
invalidSelection
OR
B2QOPEN AND
AND
B2QCLD AND
line2Voltage lineVoltage
bus2Voltage
UB1OK AND
UB1FF OR
OR selectedFuseOK
UB2OK AND
AND
UB2FF OR
USELFAIL
ULN1OK AND
AND
ULN1FF OR
ULN2OK
AND
ULN2FF OR
BLOCK
en05000781-2.vsd
IEC05000781 V2 EN-US
Figure 515: Simplified logic diagram for the voltage selection function for the tie circuit breaker in 1 1/2 breaker
arrangement.
Time delay for energizing check when (0.000-60.000) s ±0.2% or ±100 ms whichever is
voltage jumps from 0 to 90% of Urated greater
Operate time for synchrocheck function when Min. = 15 ms –
angle difference between bus and line jumps Max. = 30 ms
from “PhaseDiff” + 2 degrees to “PhaseDiff” -
2 degrees
Operate time for energizing function when Min. = 70 ms –
voltage jumps from 0 to 90% of Urated Max. = 90 ms
16.2.1 Identification
M14890-1 v7
Up to five reclosing shots can be performed. The first shot can be single-, two-, and /or three-phase
depending on the type of the fault and the selected auto reclosing mode.
Several auto reclosing functions can be provided for multi-breaker arrangements. A priority circuit
allows one circuit breaker to reclose first and the second will only close if the fault proved to be
transient.
Each auto reclosing function can be configured to co-operate with the synchrocheck function.
SMBRREC
ON BLOCKED
OFF SETON
BLKON READY
BLKOFF ACTIVE
RESET SUCCL
INHIBIT UNSUCCL
START INPROGR
STARTHS 1PT1
TRSOTF 2PT1
SKIPHS 3PT1
ZONESTEP 3PT2
TR2P 3PT3
TR3P 3PT4
THOLHOLD 3PT5
CBREADY PERMIT1P
CBCLOSED PREP3P
PLCLOST CLOSECB
SYNC WFMASTER
WAIT COUNT1P
RSTCOUNT COUNT2P
MODEINT COUNT3P1
COUNT3P2
COUNT3P3
COUNT3P4
COUNT3P5
COUNTAR
MODE
ABORTED
SYNCFAIL
INHIBOUT
IEC06000189-3-en.vsd
IEC06000189 V3 EN-US
16.2.4 Signals
PID-6796-INPUTSIGNALS v2
PID-6796-OUTPUTSIGNALS v2
16.2.5 Settings
PID-6797-SETTINGS v2
Before describing the auto reclosing function it is first necessary to define the following terminology:
The auto reclosing function can be in one of the following five statuses:
“Inactive” GUID-BF80C969-FCBE-4CAB-BF71-9590A2DB433C v1
The auto recloser is in “inactive” status when the following conditions are fulfilled:
The function will not react on any start from protection trips while in “inactive” status and no
automatic reclosing is possible.
“Ready” GUID-04F154EC-E236-40A4-A3E0-7624A2F6B132 v1
The function is in “ready” status when the following conditions are fulfilled:
Start can be initiated by either protection trip command or circuit breaker position change. The
second starting alternative is only possible when enabled by a setting.
In “in progress” status the dead time starts and the status ceases when the dead time expires. Then
circuit breaker close command is given and the function changes its state into the "reclaim time"
status.
A new start signal during “reclaim time” status forces the function to proceed to next shot and change
state into “in progress” status, as long as the last shot is not reached.
“Blocked” GUID-9C38B1BE-3772-49AE-B4B3-391CE15D5CD2 v1
The function is in “blocked” status when an external blocking signal exists. No auto reclosing is
possible in “blocked” status. Only an external signal for cancellation of the blocking can cancel this
status.
From Table 567 below it is possible to see which status transitions are possible. When the auto
recloser is for instance in “inactive” status only two transition are possible:
• transition to “ready” status when the circuit breaker is ready and closed
• transition to “blocked” status by external blocking
The empty cells in the table indicate that no such transition is possible.
To comprehend this chapter better it is essential to first read chapters “Status descriptions“ and
“Description of the status transition” carefully.
The logic for most of the explained inputs, outputs, settings and internal signals, described in this
chapter, is shown in Figure 522. Other figures mentioned are in some way connected or cooperate
with Figure 522.
Before going into details in the following chapters, the short functional/feature summary is given
below.
The auto reclosing function is multi-shot capable and suitable for both high-speed and delayed auto
reclosing. The function can be set to perform a single-shot, two-shot, three-shot, four-shot or five-
shot reclosing sequence. Dead times for all shots can be set independently.
• protection operation
• circuit breaker operation (when enabled by setting StartByCBOpen=On)
At the end of the dead time, provided that other conditions are fulfilled, a circuit breaker close
command signal is given. The other conditions to be fulfilled are:
• input signal SYNC is true, which typically indicates that power systems on the two sides of the
circuit breaker are in synchronism
• and that input signal CBREADY is true, typically indicating that circuit breaker springs are
charged.
If a circuit breaker close command is given successfully at the end of the dead time, a reclaim time
starts. If the circuit breaker does not trip again within reclaim time, the auto recloser indicates a
successful reclosing and resets into "ready" status. If the protection trips again during the reclaim
time, the sequence advances to the next shot. If all reclosing attempts have been made and the
circuit breaker does not remain closed, the auto recloser indicates an unsuccessful reclosing. Each
time a breaker close command is given, a shot counter is incremented by one.
If the input conditions CBCLOSED and CBREADY, from the circuit breaker, are not fulfilled while
switching the auto recloser on, the auto recloser changes into “inactive” status and the output
SETON is activated (high). The auto recloser is not ready for auto reclosing. If, however, the circuit
breaker is closed and ready when switching the auto recloser on, the output READY is activated and
the function is prepared to start the auto reclosing cycle. The circuit breaker must have been closed
for at least the set value for setting tCBClosedMin before a start is accepted. The logic for Off or On
operation is shown in Figure 517.
Operation
AND OR S SETON
ExternalCtrl
R
ON AND
OR
OFF AND
StartByCBOpen
START AND
STARTHS AND
100ms OR
AND OR initiate
100ms
AND
TRSOTF
startThermal AND
CBReady
120ms
CBREADY OR S
t AND start
AND
AND
tCBClosedMin R
CBCLOSED
t
cbClosed AND
count0 AND READY
inhibit
OR
INHIBIT
IEC16000153-1-en.vsdx
IEC16000153 V1 EN-US
When a valid integer is connected to the input MODEINT the selected setting ARMode will be invalid
and the MODEINT input value will be used instead. The selected mode is reported as an integer on
the MODE output.
Please note that tripping mode of the IED is defined in Trip Logic function block SMPPTRC. For
example for two-phase faults either 2ph or 3ph tripping and consequent auto reclosing can be
selected
Table 568: Type of reclosing shots at different settings of “ARMode” or integer inputs to "MODEINT"
MODEINT (Integer) ARMode Type of fault 1st shot 2nd - 5th shot
1ph 3ph 3ph
1 3ph 2ph 3ph 3ph
3ph 3ph 3ph
1ph 1ph 3ph
2 1/2/3ph 2ph 2ph 3ph
3ph 3ph 3ph
1ph 1ph 3ph
3 1/2ph 2ph 2ph 3ph
3ph - -
1ph 1ph 3ph
4 1ph+1x2ph 2ph 2ph -
3ph - -
1ph 1ph 3ph
5 1/2ph+1x3ph 2ph 2ph 3ph
3ph 3ph –
1ph 1ph 3ph
6 1ph+1x2/3ph 2ph 2ph -
3ph 3ph -
The first shot differs from the other shots by the possibility to extend its dead time and to utilize up to
four different time settings for it.
For the first shot, there are separate settings for single-, two- and three-phase dead times, t1 1Ph, t1
2Ph and t1 3Ph. If only the START input signal is applied, and an auto-reclosing program with single-
phase reclosing is selected, the auto reclosing dead time t1 1Ph will be used. If one of the TR2P or
TR3P inputs is activated in in parallel with the START input, the auto reclosing dead time for either
two-phase or three-phase auto reclosing is used.
There is also a separate time setting facility for three-phase high-speed auto reclosing, t1 3PhHS.
This high-speed auto reclosing is activated by the STARTHS input and is used when auto reclosing
is done without the requirement of synchrocheck conditions to be fulfilled. The high-speed dead time
shall be set shorter than normal first shot three-phase dead time. Note that if high-speed three-phase
shot is not successful the auto reclosing sequence will continue with shot two.
A time extension delay, tExtended t1, can be added to the dead time delay for the first shot. It is
intended to come into use if the communication channel for permissive line protection is lost. In a
case like this there can be a significant time difference in fault clearance at the two line ends, where
a longer auto reclosing dead time can be useful. This time extension is controlled by the setting
Extended t1 and the PLCLOST input. The logic for control of extended dead time is shown in
Figure518 and Figure 522. Time extension delay is not possible to add to the three-phase high-
speed auto reclosing dead time, t1 3PhHS.
Extended t1
AND extendTime
PLCLOST
OR
initiate AND
AND
start
IEC16000155-1-en.vsdx
IEC16000155 V1 EN-US
The usual way to start a reclosing sequence, is to start it when a selective line protection tripping has
occurred, by applying a signal to the START input. If the auto reclosing mode with only three-phase
reclosing is selected, activation of the START input will start the three-phase dead timer. When
alternatively the START input signal is applied, and an auto reclosing mode with single-phase
reclosing is selected, the auto reclosing dead time for single-phase is used. However if one of the
TR2P or TR3P inputs is activated in connection with the START input, the auto reclosing dead time
for two-phase or three-phase auto reclosing is used. The STARTHS input (start high-speed
reclosing) can also be used to start a separate, high-speed three-phase dead time in which case the
synchrocheck condition will be bypassed.
To start a new auto reclosing cycle, a number of conditions of input signals need to be fulfilled. The
inputs are:
• CBREADY: circuit breaker is ready for a reclosing cycle, for example, charged operating gear.
• CBCLOSED: to ensure that the circuit breaker was closed when the line fault occurred and start
was applied. The CBCLOSED condition must be present for more that the settable time
tCBClosedMin.
• no BLKON or INHIBIT signal is present.
When the start has been accepted, the internal signals “start” and “initiate” are set. The internal
signal “start” is latched and the internal signal “initiate” follows the length of the signal on the START
input. The latched signal “start” can be interrupted by a signal to the INHIBIT input.
The auto recloser is normally started by selective tripping. It is either a zone 1 or communication
aided trip, or a general trip. If the general trip is used the auto recloser must be blocked, via the
INHIBIT input, from all back-up tripping. The breaker failure function must always be connected to
inhibit the auto recloser. START makes a first shot with synchrocheck conditions to be fulfilled,
STARTHS makes its first shot without any fulfilled synchrocheck conditions. The TRSOTF “trip by
switch onto fault” input starts shots 2 to 5. It may be connected to the “switch onto fault” output of line
protection if multi-shot auto reclosing is used.
In normal circumstances, the auto recloser is started with a protection trip command which resets
quickly due to fault clearing. In case the start signal lasts for a too long time, the user can set a
maximum start pulse duration tLongStartInh. This start pulse duration time is controlled by setting
LongStartInhib. When the start pulse duration signal is longer than the set maximum start pulse
duration, the auto reclosing sequence will be interrupted in the same way as if the INHIBIT input was
set to true. The logic for the control of long start pulse duration is shown in Figure 519.
LongStartInhib
start
AND
tLongStartInh
initiate
t
longStartInhibit
OR
Extended t1 AND
t13PhExtTimeout
IEC16000154-1-en.vsdx
IEC16000154 V1 EN-US
The function can also be set to proceed to the next reclosing shot (if selected) even if the external
start signal is not received but the breaker is still not closed. The user can set a required time delay
for the auto recloser to proceed without a new start with setting tAutoContWait. Also the
synchrocheck conditions not fulfilled will also make the auto recloser to proceed to next shot. This
automatic proceeding of shots is controlled by setting AutoContinue and is shown in figure 520.
tAutoContWait
t
AND
commandCloseCB
AND S
R
OR
AND
OR
cbClosed AND autoInitiate
synchroCheckOK
AutoContinue
IEC16000156-1-en.vsdx
IEC16000156 V1 EN-US
The RESET input is used to reset the auto recloser to its initial conditions. When initial starting
conditions are fulfilled again, after a reset, the auto recloser is ready for a new reclosing sequence.
If the INHIBIT input is activated it is reported on the INHIBOUT output. To ensure reliable interruption
and temporary blocking of the auto recloser a reset time delay tInhibit is used. The auto recloser will
be blocked the time set in tInhibit after the deactivation of the INHIBIT input. The following internal
inhibit signals are also affected by the setting tInhibit:
• inhibitWaitForMaster: after expiration of the tWaitForMaster time for the WAIT input to reset, the
reclosing cycle of the slave is inhibited.
• longStartInhibit: if start pulse duration is longer than the tLongStartInh time, the reclosing cycle
is inhibited.
The ABORTED output indicates that the auto recloser is inhibited while it was in one of following
internal states:
The SYNCFAIL output indicates that the auto recloser is inhibited because the synchrocheck or
energizing check condition has not been fulfilled within the set time interval, tSync. The ABORTED
output will also be activated.
The behavior of the functionality described above is described in Table 569 and Table 570 below.
Table 569: BLKON, BLKOFF, RESET, INHIBIT and SYNC behavior when the function is in "ready" status
Table 570: BLKON, BLKOFF, RESET, INHIBIT and SYNC behavior when the function is in "in progress" status
reclosing started by STARTHS input, synchronization is not checked either, and the state of the
SYNC input is disregarded. The SYNC input shall be true within a set time interval, tSync. If it is not,
the auto reclosing is interrupted and the SYNCFAIL and ABORTED outputs are activated.
By choosing CBReadyType = CO (circuit breaker ready for a Close-Open sequence) the readiness of
the circuit breaker is also checked before issuing the circuit breaker closing command. If the circuit
breaker has a readiness contact of type CBReadyType = OCO (circuit breaker ready for an Open-
Close-Open sequence) this condition may not be fulfilled during the dead time and at the moment of
auto reclosure. The Open-Close-Open condition was however checked at the start of the auto
reclosing cycle and it is then likely that the circuit breaker is prepared for a Close-Open sequence.
The reclaim timer, tReclaim, is started each time a circuit breaker closing command is given. If no
start occurs within this time, the auto recloser will reset. A new start received in “reclaim time” status
will move the auto recloser to “in progress” status and next shot as long as the final shot is not
reached. The auto recloser will reset and enter “inactive” status if a new start is given during the final
reclaim time. This will also happen if the circuit breaker has not been closed within set time interval
tUnsucCl after each circuit breaker close command. The latter case is controlled by setting
UnsucClByCBChk. The auto reclosing sequence is considered unsuccessful for both above cases
and the UNSUCCL output is activated.
If the circuit breaker closing command is given and the circuit breaker is closed within the set time
interval tUnsucCl, the SUCCL output is activated after the set time interval tSuccessful. The logic for
successful and unsuccessful reclosing indication is shown in Figure 521.
initiate
reclaimTimeStarted AND
OR
AND UNSUCCL
OR tUnsucCl S
AND t unsuccessful
cbClosed
AND
UnsucClByCBChk
count0
OR R
tUnsucCl tSuccessful
AND SUCCL
commandCloseCB t AND S t
R
OR
IEC16000157-1-en.vsdx
IEC16000157 V1 EN-US
IEC16000158 V1 EN-US
TR2P and INPROGR
TR3P NoOfShots 1PT1
startThermal OR 2PT1
Technical manual
selection 3PT1
Dead time
reclaimTimeStarted 3PT2
tExtended t1 tExtended t1 is 3PT3
extendTime added to t1 1Ph inhibitThermalStart
1MRK 504 164-UEN Rev. N
t 3PT4
or t1 2ph or t1 3Ph 3PT5
SKIPHS Skips high-speed shot (t1 3PhHS) and PREP3P
continues with delayed shot (t1 3Ph) AND tReclaim PERMIT1P
AND t 1
t1 1Ph OR
tSync
SYNC AND t SYNCFAIL
inProgress AND
reclaimTimeStarted OR
CBReadyType wait AND ABORTED
CB OR
AND
readiness
AND inhibitWaitForMaster tInhibit
CBReady check t
OR
longStartInhibit count0
OR Counter COUNT1P
inhibitThermalStart COUNT2P
CutPulse inProgress COUNT3P1
AND Set COUNT3P2
OR COUNT3P3
OR COUNT3P4
AND
AND COUNT3P5
Reset COUNTAR
tPulse
Follow CB CLOSECB
OR
AND AND
cbClosed
RSTCOUNT
RESET
BLKON
BLKOFF
INHIBIT INHIBOUT
IEC16000158-1-en.vsdx
A number of outputs from the function keeps track of the actual state in the auto reclosing sequence.
891
Control
Section 16
Section 16 1MRK 504 164-UEN Rev. N
Control
The possible statuses are described in Table 571 below. Their mapping to output signals and their
corresponding IEC 61850 integer value is also given in the table. Mapping from IEC 61850 Ed2
standard is also shown for the AutoRecSt data object.
Table 571: Auto reclosing status reported by IEC 61850 in priority order
Data object AutoRecSt Description for mapped Mapped output signals / Description in IEC61850
value signals Comments Ed2
1 Ready READY Ready
2 In Progress INPROGR In Progress
3 Successful SUCCL Successful
4 Waiting for trip
5 Trip issued by protection
6 Fault disappeared
7 Wait to complete CLOSECB Wait to complete
8 Circuit breaker closed
9 Cycle unsuccessful UNSUCCL
10
-1 Aborted by synchrocheck SYNCFAIL
fail
11 Aborted ABORTED Aborted
-2 Set On, Not Ready SETON = 1, READY = 0,
ACTIVE = 0, SUCCL = 0,
UNSUCC = 0, INPROG =
0
-3 Set Off, Not Ready SETON = 0
-99 Others Means that auto recloser is
in transitional state, that
should not be visible in
steady state situation
There are several counters within the function. One for each shot and type of fault and one overall
counter for total number of circuit breaker closing commands. All counters can be reset to zero using
either the HMI command or the RSTCOUNT input or by an IEC 61850 command.
The circuit breaker closing command, CLOSECB output is a pulse with settable duration by setting
tPulse. For circuit breakers without anti-pumping function, close pulse cutting can be used. This is
controlled by the setting CutPulse. In case of a new auto recloser start pulse, the breaker closing
command pulse is cut (interrupted). The minimum duration of the closing pulse is always 50ms.
The prepare three-phase trip, PREP3P output is usually connected to the trip function SMPPTRC to
force the coming trip to be three-phase. If the auto recloser cannot make a single-phase or two-
phase reclosing, the start from the trip function should be three-phase.
The permit single-phase trip, PERMIT1P output is the inverse of the PREP3P output. It can be
connected to a binary output relay for connection to external protection or trip relays. In case of a
total loss of auxiliary power, the output relay drops and does not allow single-phase trip.
The setting Follow CB can be used to prevent close command to be issued when dead time has
expired and circuit breaker is already closed (e.g. by manual close command). If a new start is
received after the dead time expiration the auto recloser will advance to next shot.
If input SKIPHS is activated, and simultaneously STARTHS input is initiated then actually normal
three-phase shot one with dead time "t1 3Ph" will be started.
The ZONESTEP input is used when coordination between local auto reclosers and down stream
auto reclosers is needed. If function is in "ready" status and this input is activated the auto recloser
increases its actual shot number by one and enters directly the “reclaim time” status for shot one. If a
start is received during the reclaim time, the function will proceed with the next shot (e.g. starting
dead time for shot two). Every new pulse on the ZONESTEP input will further increase the shot
number. Note that ZONESTEP input will have such effect only if local start signal was not activated,
as shown in Figure 522. The setting NoOfShots limits of course the maximum number of available
shots. This functionality is controlled by the setting ZoneSeqCoord.
By activating the THOLHOLD input the auto recloser is set on hold. It can be connected to a thermal
overload protection trip signal which resets only when the thermal content has fallen to an acceptable
level, for example, 70%. As long as the signal is high, indicating that the line is hot, the auto reclosing
is halted. When the signal resets, a reclosing cycle will continue. This may cause a considerable
delay between start of the auto recloser and the breaker closing command. An external logic limiting
this time and activating the INHIBIT input can be used. The THOLHOLD input can also be used to
set the auto recloser on hold, for longer or shorter time periods, for other purposes if for some reason
the auto recloser needs to be halted. The logic for thermal protection hold is shown in Figure 523.
start inhibitThermalStart
THOLHOLD AND AND S
q-1 20ms
startThermal
AND
inhibit OR
IEC16000159-1-en.vsdx
IEC16000159 V1 EN-US
When activating the WAIT input, in the auto recloser set as slave, every dead timer is changed to the
value of setting tSlaveDeadTime and holds back the auto reclosing operation. When the WAIT input
is reset at the time of a successful reclosing of the first circuit breaker, the slave is released to
continue the reclosing sequence after the set tSlaveDeadTime. The reason for shortening the time,
for the normal dead timers with the value of tSlaveDeadTime, is to give the slave permission to react
almost immediately when the WAIT input resets. The mimimum settable time for tSlaveDeadTime is
0.1sec because both master and slave should not send the breaker closing command at the same
time. The slave should take the duration of the breaker closing time of the master into consideration
before sending the breaker closing command. A setting tWaitForMaster sets a maximum wait time
for the WAIT input to reset. If the wait time expires, the reclosing cycle of the slave is inhibited. The
maximum wait time, tWaitForMaster for the second circuit breaker is set longer than the auto
reclosing dead time plus a margin for synchrocheck conditions to be fulfilled for the first circuit
breaker. Typical setting is 2sec. In single circuit breaker applications, the setting Priority is set to
None. The logic for master-slave is shown in Figure 524.
Master:
High (Master)
Priority
WFMASTER
inProgress AND
unsuccessful OR
Slave:
Low (Slave)
Priority
inhibitWaitForMaster
AND
start tWaitForMaster
AND t
WAIT
wait
AND slaveDeadTime
AND S
inhibit
commandCloseCB R
OR
reclaimTimeStarted
IEC16000160-1-en.vsdx
IEC16000160 V1 EN-US
Some examples of the timing of internal and external signals at typical transient and permanent faults
are shown below in Figure 525 to 528.
Fault
CBCLOSED
Closed Open Closed
CBREADY
START
SYNC
tReclaim
READY
INPROGR
1PT1
ACTIVE
PREP3P
SUCCL
Time
IEC04000196-4-en.vsd
IEC04000196 V4 EN-US
Fault
CBCLOSED Open
Closed Open C C
CBREADY
START
TR3P
SYNC
READY
INPROGR
3PT1 t1 3Ph
3PT2 t2 3Ph
ACTIVE tReclaim
PREP3P
UNSUCCL
Time
IEC04000197-3-en.vsd
IEC04000197 V3 EN-US
Fault
CBCLOSED
CBREADY
START
TR3P
SYNC
READY
INPROGR
1PT1
3PT1
3PT2
CLOSECB t1 1Ph
PREP3P
UNSUCCL tReclaim
IEC04000198-3-en.vsd
IEC04000198 V3 EN-US
Fault
CBCLOSED
CBREADY
START
TR3P
SYNC
READY
INPROGR
1PT1
3PT1
3PT2
t2 3Ph
CLOSECB t1 1Ph
PREP3P
UNSUCCL tReclaim
IEC04000199-3-en.vsd
IEC04000199 V3 EN-US
Figure 528: Permanent single-phase fault, single-phase trip, two-shot reclosing, ARMode=1ph
+ 1*2ph
The interlocking functionality blocks the possibility to operate high-voltage switching devices, for
instance when a disconnector is under load, in order to prevent material damage and/or accidental
human injury.
Each control IED has interlocking functions for different switchyard arrangements, each handling the
interlocking of one bay. The interlocking functionality in each IED is not dependent on any central
function. For the station-wide interlocking, the IEDs communicate via the station bus or by using hard
wired binary inputs/outputs.
The interlocking conditions depend on the circuit configuration and status of the system at any given
time.
The interlocking function consists of software modules located in each control IED. The function is
distributed and not dependent on any central function. Communication between modules in different
bays is performed via the station bus.
The reservation function (see section "Functionality") is used to ensure that HV apparatuses that
might affect the interlock are blocked during the time gap, which arises between position updates.
This can be done by means of the communication system, reserving all HV apparatuses that might
influence the interlocking condition of the intended operation. The reservation is maintained until the
operation is performed.
After the selection and reservation of an apparatus, the function has complete data on the status of
all apparatuses in the switchyard that are affected by the selection. Other operators cannot interfere
with the reserved apparatus or the status of switching devices that may affect it.
The open or closed positions of the HV apparatuses are inputs to software modules distributed in the
control IEDs. Each module contains the interlocking logic for a bay. The interlocking logic in a module
is different, depending on the bay function and the switchyard arrangements, that is, double-breaker
or 1 1/2 breaker bays have different modules. Specific interlocking conditions and connections
between standard interlocking modules are performed with an engineering tool. Bay-level interlocking
signals can include the following kind of information:
The interlocking module is connected to the surrounding functions within a bay as shown in figure
529.
Apparatus control
Interlocking
modules
modules in
SCILO SCSWI
other bays SXSWI
Apparatus control
modules
Interlocking SCILO SCSWI SXCBR
module
Apparatus control
modules
en04000526.vsd SCILO SCSWI SXSWI
IEC04000526 V1 EN-US
• Unearthed busbars
• Busbars connected together
• Other bays connected to a busbar
• Received data from other bays is valid
Station bus
Disc QB1 and QB2 closed Disc QB1 and QB2 closed WA1 unearthed
WA1 unearthed
WA1 and WA2 interconn
...
WA1 not earthed WA1 not earthed
WA2 not earthed WA2 not earthed WA1 and WA2 interconn
WA1 and WA2 interconn WA1 and WA2 interconn in other bay
..
WA1
WA2
QB1 QB2 QB1 QB2 QB1 QB2 QC1 QC2
QB9 QB9
en05000494.vsd
IEC05000494 V1 EN-US
On the local HMI an override function exists, which can be used to bypass the interlocking function in
cases where not all the data required for the condition is valid.
• The interlocking conditions for opening or closing of disconnectors and earthing switches are
always identical.
• Earthing switches on the line feeder end, for example, rapid earthing switches, are normally
interlocked only with reference to the conditions in the bay where they are located, not with
reference to switches on the other side of the line. So a line voltage indication may be included
into line interlocking modules. If there is no line voltage supervision within the bay, then the
appropriate inputs must be set to no voltage, and the operator must consider this when
operating.
• Earthing switches can only be operated on isolated sections for example, without load/voltage.
Circuit breaker contacts cannot be used to isolate a section, that is, the status of the circuit
breaker is irrelevant as far as the earthing switch operation is concerned.
• Disconnectors cannot break power current or connect different voltage systems. Disconnectors
in series with a circuit breaker can only be operated if the circuit breaker is open, or if the
disconnectors operate in parallel with other closed connections. Other disconnectors can be
operated if one side is completely isolated, or if the disconnectors operate in parallel to other
closed connections, or if they are earthed on both sides.
• Circuit breaker closing is only interlocked against running disconnectors in its bay or additionally
in a transformer bay against the disconnectors and earthing switch on the other side of the
transformer, if there is no disconnector between CB and transformer.
• Circuit breaker opening is only interlocked in a bus-coupler bay, if a bus bar transfer is in
progress.
To make the implementation of the interlocking function easier, a number of standardized and tested
software interlocking modules containing logic for the interlocking conditions are available:
The interlocking conditions can be altered, to meet the customer specific requirements, by adding
configurable logic by means of the graphical configuration tool PCM600. The inputs Qx_EXy on the
interlocking modules are used to add these specific conditions.
The input signals EXDU_xx shall be set to true if there is no transmission error at the transfer of
information from other bays. Required signals with designations ending in TR are intended for
transfer to other bays.
16.3.3.1 Identification
GUID-3EC5D7F1-FDA0-4F0E-9391-08D357689E0C v3
The Logical node for interlocking SCILO function is used to enable a switching operation if the
interlocking conditions permit. SCILO function itself does not provide any interlocking functionality.
The interlocking conditions are generated in separate function blocks containing the interlocking
logic.
SCILO
POSOPEN EN_OPEN
POSCLOSE EN_CLOSE
OPEN_EN
CLOSE_EN
IEC05000359-2-en.vsd
IEC05000359 V2 EN-US
16.3.3.4 Signals
PID-3487-INPUTSIGNALS v7
PID-3487-OUTPUTSIGNALS v7
The function contains logic to enable the open and close commands respectively if the interlocking
conditions are fulfilled. That means also, if the switch has a defined end position for example, open,
then the appropriate enable signal (in this case EN_OPEN) is false. The enable signals EN_OPEN
and EN_CLOSE can be true at the same time only in the intermediate and bad position state and if
they are enabled by the interlocking function. The position inputs come from the logical nodes Circuit
breaker/Circuit switch (SXCBR/SXSWI) and the enable signals come from the interlocking logic. The
outputs are connected to the logical node Switch controller (SCSWI). One instance per switching
device is needed.
POSOPEN SCILO
POSCLOSE =1 1
EN_OPEN
&
>1
&
OPEN_EN
CLOSE_EN & EN_CLOSE
>1
&
en04000525.vsd
IEC04000525 V1 EN-US
16.3.4.1 Identification
GUID-F3CBAFDC-3723-429F-9183-45229A6F0A12 v3
The interlocking for busbar earthing switch (BB_ES) function is used for one busbar earthing switch
on any busbar parts according to figure 533.
QC
en04000504.vsd
IEC04000504 V1 EN-US
BB_ES
QC_OP QCREL
QC_CL QCITL
BB_DC_OP BBESOPTR
VP_BB_DC BBESCLTR
EXDU_BB
IEC05000347-2-en.vsd
IEC05000347 V2 EN-US
BB_ES
VP_BB_DC QCREL
BB_DC_OP QCITL
EXDU_BB & 1
QC_OP BBESOPTR
QC_CL BBESCLTR
en04000546.vsd
IEC04000546 V1 EN-US
16.3.4.5 Signals
PID-3494-INPUTSIGNALS v10
PID-3494-OUTPUTSIGNALS v10
16.3.5.1 Identification
GUID-29EF1F25-E10A-4C82-A6B7-FA246D9C6CD2 v3
The interlocking for bus-section breaker (A1A2_BS) function is used for one bus-section circuit
breaker between section 1 and 2 according to figure 535. The function can be used for different
busbars, which includes a bus-section circuit breaker.
QA1
QC3 QC4
en04000516.vsd
A1A2_BS
IEC04000516 V1 EN-US
A1A2_BS
QA1_OP QA1OPREL
QA1_CL QA1OPITL
QB1_OP QA1CLREL
QB1_CL QA1CLITL
QB2_OP QB1REL
QB2_CL QB1ITL
QC3_OP QB2REL
QC3_CL QB2ITL
QC4_OP QC3REL
QC4_CL QC3ITL
S1QC1_OP QC4REL
S1QC1_CL QC4ITL
S2QC2_OP S1S2OPTR
S2QC2_CL S1S2CLTR
BBTR_OP QB1OPTR
VP_BBTR QB1CLTR
EXDU_12 QB2OPTR
EXDU_ES QB2CLTR
QA1O_EX1 VPS1S2TR
QA1O_EX2 VPQB1TR
QA1O_EX3 VPQB2TR
QB1_EX1
QB1_EX2
QB2_EX1
QB2_EX2
IEC05000348-2-en.vsd
IEC05000348 V2 EN-US
A1A2_BS
QA1_OP
QA1_CL =1 VPQA1
QB1_OP
QB1_CL =1 VPQB1
QB2_OP
QB2_CL =1 VPQB2
QC3_OP
QC3_CL =1 VPQC3
QC4_OP
QC4_CL =1 VPQC4
S1QC1_OP
S1QC1_CL =1 VPS1QC1
S2QC2_OP
S2QC2_CL =1 VPS2QC2
VPQB1
QB1_OP QA1OPREL
& >1
QA1O_EX1 QA1OPITL
1
VPQB2
QB2_OP
&
QA1O_EX2
VP_BBTR
BBTR_OP
&
EXDU_12
QA1O_EX3
VPQB1 QA1CLREL
VPQB2 & QA1CLITL
1
VPQA1
VPQC3 QB1REL
& >1
VPQC4 QB1ITL
1
VPS1QC1
QA1_OP
QC3_OP
QC4_OP
S1QC1_OP
EXDU_ES
QB1_EX1
VPQC3
VPS1QC1
&
QC3_CL
S1QC1_CL
EXDU_ES
QB1_EX2
en04000542.vsd
IEC04000542 V1 EN-US
VPQA1
VPQC3 QB2REL
VPQC4 & >1
QB2ITL
VPS2QC2 1
QA1_OP
QC3_OP
QC4_OP
S2QC2_OP
EXDU_ES
QB2_EX1
VPQC4
VPS2QC2
&
QC4_CL
S2QC2_CL
EXDU_ES
QB2_EX2
VPQB1 QC3REL
VPQB2 QC3ITL
QB1_OP & 1
QC4REL
QB2_OP
QC4ITL
1
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
QB1_OP S1S2OPTR
QB2_OP >1 S1S2CLTR
QA1_OP 1
VPQB1
VPS1S2TR
VPQB2 &
VPQA1
en04000543.vsd
IEC04000543 V1 EN-US
16.3.5.5 Signals
PID-3498-INPUTSIGNALS v9
PID-3498-OUTPUTSIGNALS v9
16.3.6.1 Identification
GUID-0A0229EB-5ECD-405C-B706-6A54CBBDB49D v3
The interlocking for bus-section disconnector (A1A2_DC) function is used for one bus-section
disconnector between section 1 and 2 according to figure 537. A1A2_DC function can be used for
different busbars, which includes a bus-section disconnector.
QB
WA1 (A1) WA2 (A2)
QC1 QC2
A1A2_DC en04000492.vsd
IEC04000492 V1 EN-US
A1A2_DC
QB_OP QBOPREL
QB_CL QBOPITL
S1QC1_OP QBCLREL
S1QC1_CL QBCLITL
S2QC2_OP DCOPTR
S2QC2_CL DCCLTR
S1DC_OP VPDCTR
S2DC_OP
VPS1_DC
VPS2_DC
EXDU_ES
EXDU_BB
QBCL_EX1
QBCL_EX2
QBOP_EX1
QBOP_EX2
QBOP_EX3
IEC05000349-2-en.vsd
IEC05000349 V2 EN-US
A1A2_DC
QB_OP
VPQB VPDCTR
QB_CL =1
DCOPTR
DCCLTR
S1QC1_OP
VPS1QC1
S1QC1_CL =1
S2QC2_OP
VPS2QC2
S2QC2_CL =1
VPS1QC1
VPS2QC2
VPS1_DC & >1 QBOPREL
S1QC1_OP QBOPITL
1
S2QC2_OP
S1DC_OP
EXDU_ES
EXDU_BB
QBOP_EX1
VPS1QC1
VPS2QC2
VPS2_DC &
S1QC1_OP
S2QC2_OP
S2DC_OP
EXDU_ES
EXDU_BB
QBOP_EX2
VPS1QC1
VPS2QC2
S1QC1_CL &
S2QC2_CL
EXDU_ES
QBOP_EX3
en04000544.vsd
IEC04000544 V1 EN-US
IEC04000545 V1 EN-US
16.3.6.5 Signals
PID-3499-INPUTSIGNALS v10
PID-3499-OUTPUTSIGNALS v10
16.3.7.1 Identification
GUID-8149EE0A-E2A4-431C-9D07-D1A0BD296743 v3
The interlocking for bus-coupler bay (ABC_BC) function is used for a bus-coupler bay connected to a
double busbar arrangement according to figure 539. The function can also be used for a single
busbar arrangement with transfer busbar or double busbar arrangement without transfer busbar.
WA1 (A)
WA2 (B)
WA7 (C)
QB1 QB2 QB20 QB7
QC1
QA1
QC2
en04000514.vsd
IEC04000514 V1 EN-US
ABC_BC
QA1_OP QA1OPREL
QA1_CL QA1OPITL
QB1_OP QA1CLREL
QB1_CL QA1CLITL
QB2_OP QB1REL
QB2_CL QB1ITL
QB7_OP QB2REL
QB7_CL QB2ITL
QB20_OP QB7REL
QB20_CL QB7ITL
QC1_OP QB20REL
QC1_CL QB20ITL
QC2_OP QC1REL
QC2_CL QC1ITL
QC11_OP QC2REL
QC11_CL QC2ITL
QC21_OP QB1OPTR
QC21_CL QB1CLTR
QC71_OP QB220OTR
QC71_CL QB220CTR
BBTR_OP QB7OPTR
BC_12_CL QB7CLTR
VP_BBTR QB12OPTR
VP_BC_12 QB12CLTR
EXDU_ES BC12OPTR
EXDU_12 BC12CLTR
EXDU_BC BC17OPTR
QA1O_EX1 BC17CLTR
QA1O_EX2 BC27OPTR
QA1O_EX3 BC27CLTR
QB1_EX1 VPQB1TR
QB1_EX2 VQB220TR
QB1_EX3 VPQB7TR
QB2_EX1 VPQB12TR
QB2_EX2 VPBC12TR
QB2_EX3 VPBC17TR
QB20_EX1 VPBC27TR
QB20_EX2
QB7_EX1
QB7_EX2
IEC05000350-2-en.vsd
IEC05000350 V2 EN-US
ABC_BC
QA1_OP
QA1_CL =1 VPQA1
QB1_OP
QB1_CL =1 VPQB1
QB20_OP
QB20_CL =1 VPQB20
QB7_OP
QB7_CL =1 VPQB7
QB2_OP
QB2_CL =1 VPQB2
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QC11_OP
QC11_CL =1 VPQC11
QC21_OP
QC21_CL =1 VPQC21
QC71_OP
QC71_CL =1 VPQC71
VPQB1
QB1_OP QA1OPREL
& >1 QA1OPITL
QA1O_EX1 1
VPQB20
QB20_OP &
QA1O_EX2
VP_BBTR
BBTR_OP &
EXDU_12
QA1O_EX3
VPQB1 QA1CLREL
VPQB2 QA1CLITL
VPQB7 & 1
VPQB20
en04000533.vsd
IEC04000533 V1 EN-US
VPQA1
VPQB2 QB1REL
& >1
VPQC1 QB1ITL
VPQC2 1
VPQC11
QA1_OP
QB2_OP
QC1_OP
QC2_OP
QC11_OP
EXDU_ES
QB1_EX1
VPQB2
VP_BC_12
&
QB2_CL
BC_12_CL
EXDU_BC
QB1_EX2
VPQC1
VPQC11
&
QC1_CL
QC11_CL
EXDU_ES
QB1_EX3
en04000534.vsd
IEC04000534 V1 EN-US
VPQA1
VPQB1 QB2REL
& >1
VPQC1 QB2ITL
VPQC2 1
VPQC21
QA1_OP
QB1_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQB1
VP_BC_12
&
QB1_CL
BC_12_CL
EXDU_BC
QB2_EX2
VPQC1
VPQC21
&
QC1_CL
QC21_CL
EXDU_ES
QB2_EX3
en04000535.vsd
IEC04000535 V1 EN-US
VPQA1
VPQB20 QB7REL
& >1
VPQC1 QB7ITL
VPQC2 1
VPQC71
QA1_OP
QB20_OP
QC1_OP
QC2_OP
QC71_OP
EXDU_ES
QB7_EX1
VPQC2
VPQC71
&
QC2_CL
QC71_CL
EXDU_ES
QB7_EX2
VPQA1
VPQB7 QB20REL
& >1
VPQC1 QB20ITL
VPQC2 1
VPQC21
QA1_OP
QB7_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES
QB20_EX1
VPQC2
VPQC21
&
QC2_CL
QC21_CL
EXDU_ES
QB20_EX2
en04000536.vsd
IEC04000536 V1 EN-US
VPQB1 QC1REL
VPQB20 QC1ITL
& 1
VPQB7
QC2REL
VPQB2
QB1_OP QC2ITL
1
QB20_OP
QB7_OP
QB2_OP
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
QB20_OP QB220OTR
QB2_OP & QB220CTR
VPQB20 1
VQB220TR
VPQB2 &
QB7_OP QB7OPTR
QB7_CL QB7CLTR
VPQB7 VPQB7TR
QB1_OP QB12OPTR
QB2_OP >1 QB12CLTR
VPQB1 1
VPQB12TR
VPQB2 &
QA1_OP BC12OPTR
QB1_OP >1 BC12CLTR
QB20_OP 1
VPQA1
VPBC12TR
VPQB1 &
VPQB20
QA1_OP BC17OPTR
QB1_OP >1 BC17CLTR
QB7_OP 1
VPQA1
VPBC17TR
VPQB1 &
VPQB7
QA1_OP BC27OPTR
QB2_OP >1 BC27CLTR
QB7_OP 1
VPQA1
VPBC27TR
VPQB2 &
VPQB7
en04000537.vsd
IEC04000537 V1 EN-US
16.3.7.5 Signals
PID-3500-INPUTSIGNALS v9
PID-3500-OUTPUTSIGNALS v9
16.3.8.1 Identification
GUID-03F1A3BB-4A1E-49E8-88C6-10B3876F64DA v4
The interlocking for 1 1/2 breaker diameter (BH_CONN, BH_LINE_A, BH_LINE_B) functions are
used for lines connected to a 1 1/2 breaker diameter according to figure 541.
WA1 (A)
WA2 (B)
QB1 QB2
QC1 QC1
QA1 QA1
QC2 QC2
QB6 QB6
QC3 QC3
BH_LINE_A BH_LINE_B
QB9 QB9
QC1 QC2
QC9 QC9
BH_CONN
en04000513.vsd
IEC04000513 V1 EN-US
M13574-3 v6
BH_LINE_A
QA1_OP QA1CLREL
QA1_CL QA1CLITL
QB6_OP QB6REL
QB6_CL QB6ITL
QB1_OP QB1REL
QB1_CL QB1ITL
QC1_OP QC1REL
QC1_CL QC1ITL
QC2_OP QC2REL
QC2_CL QC2ITL
QC3_OP QC3REL
QC3_CL QC3ITL
QB9_OP QB9REL
QB9_CL QB9ITL
QC9_OP QC9REL
QC9_CL QC9ITL
CQA1_OP QB1OPTR
CQA1_CL QB1CLTR
CQB61_OP VPQB1TR
CQB61_CL
CQC1_OP
CQC1_CL
CQC2_OP
CQC2_CL
QC11_OP
QC11_CL
VOLT_OFF
VOLT_ON
EXDU_ES
QB6_EX1
QB6_EX2
QB1_EX1
QB1_EX2
QB9_EX1
QB9_EX2
QB9_EX3
QB9_EX4
QB9_EX5
QB9_EX6
QB9_EX7
IEC05000352-2-en.vsd
IEC05000352 V2 EN-US
M13578-3 v6
BH_LINE_B
QA1_OP QA1CLREL
QA1_CL QA1CLITL
QB6_OP QB6REL
QB6_CL QB6ITL
QB2_OP QB2REL
QB2_CL QB2ITL
QC1_OP QC1REL
QC1_CL QC1ITL
QC2_OP QC2REL
QC2_CL QC2ITL
QC3_OP QC3REL
QC3_CL QC3ITL
QB9_OP QB9REL
QB9_CL QB9ITL
QC9_OP QC9REL
QC9_CL QC9ITL
CQA1_OP QB2OPTR
CQA1_CL QB2CLTR
CQB62_OP VPQB2TR
CQB62_CL
CQC1_OP
CQC1_CL
CQC2_OP
CQC2_CL
QC21_OP
QC21_CL
VOLT_OFF
VOLT_ON
EXDU_ES
QB6_EX1
QB6_EX2
QB2_EX1
QB2_EX2
QB9_EX1
QB9_EX2
QB9_EX3
QB9_EX4
QB9_EX5
QB9_EX6
QB9_EX7
IEC05000353-2-en.vsd
IEC05000353 V2 EN-US
BH_CONN
QA1_OP QA1CLREL
QA1_CL QA1CLITL
QB61_OP QB61REL
QB61_CL QB61ITL
QB62_OP QB62REL
QB62_CL QB62ITL
QC1_OP QC1REL
QC1_CL QC1ITL
QC2_OP QC2REL
QC2_CL QC2ITL
1QC3_OP
1QC3_CL
2QC3_OP
2QC3_CL
QB61_EX1
QB61_EX2
QB62_EX1
QB62_EX2
IEC05000351-2-en.vsd
IEC05000351 V2 EN-US
M13577-1 v5
BH_CONN
QA1_OP
QA1_CL =1 VPQA1
QB61_OP
QB61_CL =1 VPQB61
QB62_OP
QB62_CL =1 VPQB62
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
1QC3_OP
1QC3_CL =1 VP1QC3
2QC3_OP
2QC3_CL =1 VP2QC3
VPQB61 QA1CLREL
VPQB62 & QA1CLITL
1
VPQA1
VPQC1 QB61REL
& >1
VPQC2 QB61ITL
1
VP1QC3
QA1_OP
QC1_OP
QC2_OP
1QC3_OP
QB61_EX1
VPQC1
VP1QC3
&
QC1_CL
1QC3_CL
QB61_EX2
VPQA1
VPQC1 QB62REL
& >1
VPQC2 QB62ITL
1
VP2QC3
QA1_OP
QC1_OP
QC2_OP
2QC3_OP
QB62_EX1
VPQC2
VP2QC3
&
QC2_CL
2QC3_CL
QB62_EX2
VPQB61 QC1REL
VPQB62 QC1ITL
& 1
QB61_OP QC2REL
QB62_OP QC2ITL
1
en04000560.vsd
IEC04000560 V1 EN-US
BH_LINE_A
QA1_OP
QA1_CL =1 VPQA1
QB1_OP
QB1_CL =1 VPQB1
QB6_OP
QB6_CL =1 VPQB6
QC9_OP
QC9_CL =1 VPQC9
QB9_OP
QB9_CL =1 VPQB9
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QC3_OP
QC3_CL =1 VPQC3
CQA1_OP
CQA1_CL =1 VPCQA1
CQC1_OP
CQC1_CL =1 VPCQC1
CQC2_OP
CQC2_CL =1 VPCQC2
CQB61_OP
CQB61_CL =1 VPCQB61
QC11_OP
QC11_CL =1 VPQC11
VOLT_OFF
VOLT_ON =1 VPVOLT
VPQB1 QA1CLREL
VPQB6 QA1CLITL
& 1
VPQB9
VPQA1
VPQC1 QB6REL
VPQC2 & >1
QB6ITL
1
VPQC3
QA1_OP
QC1_OP
QC2_OP
QC3_OP
QB6_EX1
VPQC2
VPQC3
&
QC2_CL
QC3_CL
QB6_EX2
en04000554.vsd
IEC04000554 V1 EN-US
VPQA1
VPQC1 QB1REL
VPQC2 & >1
QB1ITL
1
VPQC11
QA1_OP
QC1_OP
QC2_OP
QC11_OP
EXDU_ES
QB1_EX1
VPQC1
VPQC11
&
QC1_CL
QC11_CL
EXDU_ES
QB1_EX2
VPQB1 QC1REL
VPQB6 QC1ITL
QB1_OP & 1
QC2REL
QB6_OP QC2ITL
VPQB6 1
VPQB9 QC3REL
VPCQB61 &
QC3ITL
1
QB6_OP
QB9_OP
CQB61_OP
VPQA1 QB9REL
VPQB6 QB9ITL
VPQC9 & >1 1
VPQC1
VPQC2
VPQC3
VPCQA1
VPCQB61
VPCQC1
VPCQC2
QB9_EX1
QB6_OP
QB9_EX2
>1
QA1_OP
QC1_OP
QC2_OP &
QB9_EX3
en04000555.vsd
IEC04000555 V1 EN-US
CQB61_OP
QB9_EX4
>1 & >1
CQA1_OP
CQC1_OP
CQC2_OP &
QB9_EX5
QC9_OP
QC3_OP
QB9_EX6
VPQC9
VPQC3
&
QC9_CL
QC3_CL
QB9_EX7
VPQB9 QC9REL
VPVOLT QC9ITL
QB9_OP & 1
VOLT_OFF
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
en04000556.vsd
IEC04000556 V1 EN-US
BH_LINE_B
QA1_OP
QA1_CL =1 VPQA1
QB2_OP
QB2_CL =1 VPQB2
QB6_OP
QB6_CL =1 VPQB6
QC9_OP
QC9_CL =1 VPQC9
QB9_OP
QB9_CL =1 VPQB9
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QC3_OP
QC3_CL =1 VPQC3
CQA1_OP
CQA1_CL =1 VPCQA1
CQC1_OP
CQC1_CL =1 VPCQC1
CQC2_OP
CQC2_CL =1 VPCQC2
CQB62_OP
CQB62_CL =1 VPCQB62
QC21_OP
QC21_CL =1 VPQC21
VOLT_OFF
VOLT_ON =1 VPVOLT
VPQB2 QA1CLREL
VPQB6 QA1CLITL
& 1
VPQB9
VPQA1
VPQC1 QB6REL
VPQC2 & >1
QB6ITL
1
VPQC3
QA1_OP
QC1_OP
QC2_OP
QC3_OP
QB6_EX1
VPQC2
VPQC3
&
QC2_CL
QC3_CL
QB6_EX2
en04000557.vsd
IEC04000557 V1 EN-US
VPQA1
VPQC1 QB2REL
VPQC2 & >1
QB2ITL
1
VPQC21
QA1_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQC1
VPQC21
&
QC1_CL
QC21_CL
EXDU_ES
QB2_EX2
VPQB2 QC1REL
VPQB6 QC1ITL
QB2_OP & 1
QC2REL
QB6_OP QC2ITL
VPQB6 1
VPQB9 QC3REL
VPCQB62 &
QC3ITL
1
QB6_OP
QB9_OP
CQB62_OP
VPQA1 QB9REL
VPQB6 QB9ITL
VPQC9 & >1 1
VPQC1
VPQC2
VPQC3
VPCQA1
VPCQB62
VPCQC1
VPCQC2
QB9_EX1
QB6_OP
QB9_EX2
>1
QA1_OP
QC1_OP
QC2_OP &
QB9_EX3
en04000558.vsd
IEC04000558 V1 EN-US
CQB62_OP
QB9_EX4
>1 & >1
CQA1_OP
CQC1_OP
CQC2_OP &
QB9_EX5
QC9_OP
QC3_OP
QB9_EX6
VPQC9
VPQC3
&
QC9_CL
QC3_CL
QB9_EX7
VPQB9 QC9REL
VPVOLT QC9ITL
QB9_OP & 1
VOLT_OFF
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
en04000559.vsd
IEC04000559 V1 EN-US
16.3.8.5 Signals
PID-3593-INPUTSIGNALS v9
PID-3593-OUTPUTSIGNALS v9
PID-3594-INPUTSIGNALS v9
PID-3594-OUTPUTSIGNALS v9
PID-3501-INPUTSIGNALS v9
PID-3501-OUTPUTSIGNALS v9
16.3.9.1 Identification
GUID-D6D10255-2818-44E4-A44E-DF623161C486 v3
The interlocking for a double busbar double circuit breaker bay including DB_BUS_A, DB_BUS_B
and DB_LINE functions are used for a line connected to a double busbar arrangement according to
figure 545.
WA1 (A)
WA2 (B)
QB1 QB2
QC1 QC4
QA1 QA2
DB_BUS_A DB_BUS_B
QC2 QC5
QB61 QB62
QC3
QB9
DB_LINE
QC9
en04000518.vsd
IEC04000518 V1 EN-US
M15105-1 v4
DB_BUS_A
QA1_OP
QA1_CL =1 VPQA1
QB61_OP
QB61_CL =1 VPQB61
QB1_OP
QB1_CL =1 VPQB1
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QC3_OP
QC3_CL =1 VPQC3
QC11_OP
QC11_CL =1 VPQC11
VPQB61 QA1CLREL
VPQB1 & QA1CLITL
1
VPQA1
VPQC1 QB61REL
& >1
VPQC2 QB61ITL
1
VPQC3
QA1_OP
QC1_OP
QC2_OP
QC3_OP
QB61_EX1
VPQC2
VPQC3
&
QC2_CL
QC3_CL
QB61_EX2
VPQA1
VPQC1 QB1REL
& >1
VPQC2 QB1ITL
1
VPQC11
QA1_OP
QC1_OP
QC2_OP
QC11_OP
EXDU_ES
QB1_EX1
VPQC1
VPQC11
&
QC1_CL
QC11_CL
EXDU_ES
QB1_EX2
en04000547.vsd
IEC04000547 V1 EN-US
VPQB61 QC1REL
VPQB1 QC1ITL
& 1
QB61_OP QC2REL
QB1_OP QC2ITL
1
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
en04000548.vsd
IEC04000548 V1 EN-US
DB_BUS_B
QA2_OP
QA2_CL =1 VPQA2
QB62_OP
QB62_CL =1 VPQB62
QB2_OP
QB2_CL =1 VPQB2
QC4_OP
QC4_CL =1 VPQC4
QC5_OP
QC5_CL =1 VPQC5
QC3_OP
QC3_CL =1 VPQC3
QC21_OP
QC21_CL =1 VPQC21
VPQB62 QA2CLREL
VPQB2 & QA2CLITL
1
VPQA2
VPQC4 QB62REL
& >1
VPQC5 QB62ITL
1
VPQC3
QA2_OP
QC4_OP
QC5_OP
QC3_OP
QB62_EX1
VPQC5
VPQC3
&
QC5_CL
QC3_CL
QB62_EX2
VPQA2
VPQC4 QB2REL
& >1
VPQC5 QB2ITL
1
VPQC21
QA2_OP
QC4_OP
QC5_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQC4
VPQC21
&
QC4_CL
QC21_CL
EXDU_ES
QB2_EX2
en04000552.vsd
IEC04000552 V1 EN-US
VPQB62 QC4REL
VPQB2 QC4ITL
& 1
QB62_OP QC5REL
QB2_OP QC5ITL
1
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
en04000553.vsd
IEC04000553 V1 EN-US
DB_LINE
QA1_OP
QA1_CL =1 VPQA1
QA2_OP
QA2_CL =1 VPQA2
QB61_OP
QB61_CL =1 VPQB61
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QB62_OP
QB62_CL =1 VPQB62
QC4_OP
QC4_CL =1 VPQC4
QC5_OP
QC5_CL =1 VPQC5
QB9_OP
QB9_CL =1 VPQB9
QC3_OP
QC3_CL =1 VPQC3
QC9_OP
QC9_CL =1 VPQC9
VOLT_OFF
VOLT_ON =1 VPVOLT
VPQA1
VPQA2 QB9REL
VPQC1 & >1
QB9ITL
1
VPQC2
VPQC3
VPQC4
VPQC5
VPQC9
QA1_OP
QA2_OP
QC1_OP
QC2_OP
QC3_OP
QC4_OP
QC5_OP
QC9_OP
QB9_EX1
& en04000549.vsd
IEC04000549 V1 EN-US
VPQA1
VPQC1
VPQC2 & >1
VPQC3
VPQC9
VPQB62
QA1_OP
QC1_OP
QC2_OP
QC3_OP
QC9_OP
QB62_OP
QB9_EX2
VPQA2
VPQB61
&
VPQC3
VPQC4
VPQC5
VPQC9
QA2_OP
QB61_OP
QC3_OP
QC4_OP
QC5_OP
QC9_OP
QB9_EX3
VPQC3
VPQC9
&
VPQB61
VPQB62
QC3_OP
QC9_OP
QB61_OP
QB62_OP
QB9_EX4
VPQC3
VPQC9
&
QC3_CL
QC9_CL
QB9_EX5
en04000550.vsd
IEC04000550 V1 EN-US
VPQB61
VPQB62 QC3REL
VPQB9 &
QC3ITL
1
QB61_OP
QB62_OP
QB9_OP
VPQB9
VPVOLT QC9REL
QB9_OP &
QC9ITL
1
VOLT_OFF
en04000551.vsd
IEC04000551 V1 EN-US
M13591-3 v6
DB_BUS_A
QA1_OP QA1CLREL
QA1_CL QA1CLITL
QB1_OP QB61REL
QB1_CL QB61ITL
QB61_OP QB1REL
QB61_CL QB1ITL
QC1_OP QC1REL
QC1_CL QC1ITL
QC2_OP QC2REL
QC2_CL QC2ITL
QC3_OP QB1OPTR
QC3_CL QB1CLTR
QC11_OP VPQB1TR
QC11_CL
EXDU_ES
QB61_EX1
QB61_EX2
QB1_EX1
QB1_EX2
IEC05000354-2-en.vsd
IEC05000354 V2 EN-US
DB_LINE
QA1_OP QB9REL
QA1_CL QB9ITL
QA2_OP QC3REL
QA2_CL QC3ITL
QB61_OP QC9REL
QB61_CL QC9ITL
QC1_OP
QC1_CL
QC2_OP
QC2_CL
QB62_OP
QB62_CL
QC4_OP
QC4_CL
QC5_OP
QC5_CL
QB9_OP
QB9_CL
QC3_OP
QC3_CL
QC9_OP
QC9_CL
VOLT_OFF
VOLT_ON
QB9_EX1
QB9_EX2
QB9_EX3
QB9_EX4
QB9_EX5
IEC05000356-2-en.vsd
IEC05000356 V2 EN-US
M13596-3 v6
DB_BUS_B
QA2_OP QA2CLREL
QA2_CL QA2CLITL
QB2_OP QB62REL
QB2_CL QB62ITL
QB62_OP QB2REL
QB62_CL QB2ITL
QC4_OP QC4REL
QC4_CL QC4ITL
QC5_OP QC5REL
QC5_CL QC5ITL
QC3_OP QB2OPTR
QC3_CL QB2CLTR
QC21_OP VPQB2TR
QC21_CL
EXDU_ES
QB62_EX1
QB62_EX2
QB2_EX1
QB2_EX2
IEC05000355-2-en.vsd
IEC05000355 V2 EN-US
16.3.9.5 Signals
PID-3598-INPUTSIGNALS v9
PID-3598-OUTPUTSIGNALS v9
PID-3601-INPUTSIGNALS v9
PID-3601-OUTPUTSIGNALS v9
PID-3508-INPUTSIGNALS v10
PID-3508-OUTPUTSIGNALS v10
16.3.10.1 Identification
GUID-BEA26EA4-F402-4385-9238-1361E862D987 v3
The interlocking for line bay (ABC_LINE) function is used for a line connected to a double busbar
arrangement with a transfer busbar according to figure 549. The function can also be used for a
double busbar arrangement without transfer busbar or a single busbar arrangement with/without
transfer busbar.
WA1 (A)
WA2 (B)
WA7 (C)
QB1 QB2 QB7
QC1
QA1
QC2
QB9
QC9
en04000478.vsd
IEC04000478 V1 EN-US
ABC_LINE
QA1_OP QA1CLREL
QA1_CL QA1CLITL
QB9_OP QB9REL
QB9_CL QB9ITL
QB1_OP QB1REL
QB1_CL QB1ITL
QB2_OP QB2REL
QB2_CL QB2ITL
QB7_OP QB7REL
QB7_CL QB7ITL
QC1_OP QC1REL
QC1_CL QC1ITL
QC2_OP QC2REL
QC2_CL QC2ITL
QC9_OP QC9REL
QC9_CL QC9ITL
QC11_OP QB1OPTR
QC11_CL QB1CLTR
QC21_OP QB2OPTR
QC21_CL QB2CLTR
QC71_OP QB7OPTR
QC71_CL QB7CLTR
BB7_D_OP QB12OPTR
BC_12_CL QB12CLTR
BC_17_OP VPQB1TR
BC_17_CL VPQB2TR
BC_27_OP VPQB7TR
BC_27_CL VPQB12TR
VOLT_OFF
VOLT_ON
VP_BB7_D
VP_BC_12
VP_BC_17
VP_BC_27
EXDU_ES
EXDU_BPB
EXDU_BC
QB9_EX1
QB9_EX2
QB1_EX1
QB1_EX2
QB1_EX3
QB2_EX1
QB2_EX2
QB2_EX3
QB7_EX1
QB7_EX2
QB7_EX3
QB7_EX4
IEC05000357-2-en.vsd
IEC05000357 V2 EN-US
ABC_LINE
QA1_OP
QA1_CL =1 VPQA1
QB9_OP
QB9_CL =1 VPQB9
QA1CLREL
QB1_OP
QB1_CL =1 VPQB1 QA1CLITL
& 1
QB2_OP
QB2_CL =1 VPQB2
QB7_OP
QB7_CL =1 VPQB7
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QC9_OP
QC9_CL =1 VPQC9
QC11_OP
QC11_CL =1 VPQC11
QC21_OP
QC21_CL =1 VPQC21
QC71_OP
QC71_CL =1 VPQC71
VOLT_OFF
VOLT_ON =1 VPVOLT
VPQA1
VPQC1 QB9REL
VPQC2 & >1
QB9ITL
1
VPQC9
QA1_OP
QC1_OP
QC2_OP
QC9_OP
QB9_EX1
VPQC2
VPQC9
&
QC2_CL
QC9_CL
QB9_EX2
en04000527.vsd
IEC04000527 V1 EN-US
VPQA1 QB1REL
& ³1
VPQB2
VPQC1 1 QB1ITL
VPQC2
VPQC11
QA1_OP
QB2_OP
QC1_OP
QC2_OP
QC11_OP
EXDU_ES
QB1_EX1
VPQB2 &
VP_BC_12
QB2_CL
BC_12_CL
EXDU_BC
QB1_EX2
VPQC1 &
VPQC11
QC1_CL
QC11_CL
EXDU_ES
QB1EX3
en04000528.vsd
IEC04000528 V1 EN-US
VPQA1 QB2REL
& ³1
VPQB1
VPQC1 1 QB2ITL
VPQC2
VPQC21
QA1_OP
QB1_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQB1 &
VP_BC_12
QB1_CL
BC_12_CL
EXDU_BC
QB2_EX2
VPQC1 &
VPQC21
QC1_CL
QC21_CL
EXDU_ES
QB2_EX3
en04000529.vsd
IEC04000529 V1 EN-US
VPQC9 QB7REL
& >1
VPQC71
VP_BB7_D 1 QB7ITL
VP_BC_17
VP_BC_27
QC9_OP
QC71_OP
EXDU_ES
BB7_D_OP
EXDU_BPB
BC_17_OP
BC_27_OP
EXDU_BC
QB7_EX1
VPQA1
VPQB1
VPQC9
&
VPQB9
VPQC71
VP_BB7_D
VP_BC_17
QA1_CL
QB1_CL
QC9_OP
QB9_CL
QC71_OP
EXDU_ES
BB7_D_OP
EXDU_BPB
BC_17_CL
EXDU_BC
QB7_EX2
IEC04000530 V1 EN-US
VPQA1
VPQB2
& >1
VPQC9
VPQB9
VPQC71
VP_BB7_D
VP_BC_27
QA1_CL
QB2_CL
QC9_OP
QB9_CL
QC71_OP
EXDU_ES
BB7_D_OP
EXDU_BPB
BC_27_CL
EXDU_BC
QB7_EX3
VPQC9
VPQC71
&
QC9_CL
QC71_CL
EXDU_ES
QB7_EX4
VPQB1 QC1REL
VPQB2 QC1ITL
VPQB9 & 1
QC2REL
QB1_OP
QB2_OP QC2ITL
1
QB9_OP
VPQB7
VPQB9 QC9REL
VPVOLT &
QC9ITL
QB7_OP 1
QB9_OP
VOLT_OFF
en04000531.vsd
IEC04000531 V1 EN-US
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
QB7_OP QB7OPTR
QB7_CL QB7CLTR
VPQB7 VPQB7TR
QB1_OP QB12OPTR
QB2_OP >1 QB12CLTR
VPQB1 1
VPQB12TR
VPQB2 &
en04000532.vsd
IEC04000532 V1 EN-US
16.3.10.5 Signals
PID-3509-INPUTSIGNALS v10
PID-3509-OUTPUTSIGNALS v10
16.3.11.1 Identification
GUID-AD839CAA-531B-43BC-B508-39AED3D0A97D v3
The interlocking for transformer bay (AB_TRAFO) function is used for a transformer bay connected
to a double busbar arrangement according to figure 551. The function is used when there is no
disconnector between circuit breaker and transformer. Otherwise, the interlocking for line bay
(ABC_LINE) function can be used. This function can also be used in single busbar arrangements.
WA1 (A)
WA2 (B)
QB1 QB2
QC1
QA1
AB_TRAFO
QC2
QC3
QA2
QA2 and QC4 are not
QC4 used in this interlocking
QB3 QB4
en04000515.vsd
IEC04000515 V1 EN-US
AB_TRAFO
QA1_OP QA1CLREL
QA1_CL QA1CLITL
QB1_OP QB1REL
QB1_CL QB1ITL
QB2_OP QB2REL
QB2_CL QB2ITL
QC1_OP QC1REL
QC1_CL QC1ITL
QC2_OP QC2REL
QC2_CL QC2ITL
QB3_OP QB1OPTR
QB3_CL QB1CLTR
QB4_OP QB2OPTR
QB4_CL QB2CLTR
QC3_OP QB12OPTR
QC3_CL QB12CLTR
QC11_OP VPQB1TR
QC11_CL VPQB2TR
QC21_OP VPQB12TR
QC21_CL
BC_12_CL
VP_BC_12
EXDU_ES
EXDU_BC
QA1_EX1
QA1_EX2
QA1_EX3
QB1_EX1
QB1_EX2
QB1_EX3
QB2_EX1
QB2_EX2
QB2_EX3
IEC05000358-2-en.vsd
IEC05000358 V2 EN-US
AB_TRAFO
QA1_OP
QA1_CL =1 VPQA1
QB1_OP
QB1_CL =1 VPQB1
QB2_OP
QB2_CL =1 VPQB2
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QB3_OP
QB3_CL =1 VPQB3
QB4_OP
QB4_CL =1 VPQB4
QC3_OP
QC3_CL =1 VPQC3
QC11_OP
QC11_CL =1 VPQC11
QC21_OP
QC21_CL =1 VPQC21
VPQB1 QA1CLREL
VPQB2 QA1CLITL
VPQC1 & 1
VPQC2
VPQB3
VPQB4
VPQC3
QA1_EX2
QC3_OP
QA1_EX3
QC1_CL >1
QC2_CL
QC3_CL &
QA1_EX1
en04000538.vsd
IEC04000538 V1 EN-US
VPQA1
VPQB2 QB1REL
& >1
VPQC1 QB1ITL
VPQC2 1
VPQC3
VPQC11
QA1_OP
QB2_OP
QC1_OP
QC2_OP
QC3_OP
QC11_OP
EXDU_ES
QB1_EX1
VPQB2
VPQC3
&
VP_BC_12
QB2_CL
QC3_OP
BC_12_CL
EXDU_BC
QB1_EX2
VPQC1
VPQC2
&
VPQC3
VPQC11
QC1_CL
QC2_CL
QC3_CL
QC11_CL
EXDU_ES
QB1_EX3
en04000539.vsd
IEC04000539 V1 EN-US
VPQA1
VPQB1 QB2REL
& >1
VPQC1 QB2ITL
VPQC2 1
VPQC3
VPQC21
QA1_OP
QB1_OP
QC1_OP
QC2_OP
QC3_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQB1
VPQC3
&
VP_BC_12
QB1_CL
QC3_OP
BC_12_CL
EXDU_BC
QB2_EX2
VPQC1
VPQC2
&
VPQC3
VPQC21
QC1_CL
QC2_CL
QC3_CL
QC21_CL
EXDU_ES
QB2_EX3
en04000540.vsd
IEC04000540 V1 EN-US
VPQB1 QC1REL
VPQB2 QC1ITL
& 1
VPQB3
QC2REL
VPQB4
QB1_OP QC2ITL
1
QB2_OP
QB3_OP
QB4_OP
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
QB1_OP QB12OPTR
QB2_OP >1 QB12CLTR
VPQB1 1
VPQB12TR
VPQB2 &
en04000541.vsd
IEC04000541 V1 EN-US
16.3.11.5 Signals
PID-3510-INPUTSIGNALS v10
PID-3510-OUTPUTSIGNALS v10
16.3.12.1 Identification
GUID-3C4B9379-C861-406C-9295-0309014D548E v2
Position evaluation (POS_EVAL) function converts the input position data signal POSITION,
consisting of value, time and signal status, to binary signals OPENPOS or CLOSEPOS.
The output signals are used by other functions in the interlocking scheme.
POS_EVAL
POSITION OPENPOS
CLOSEPOS
IEC09000079_1_en.vsd
IEC09000079 V1 EN-US
POS_EVAL
Position including quality POSITION OPENPOS
Open/close position of
CLOSEPOS switch device
IEC08000469-1-en.vsd
IEC08000469-1-EN V1 EN-US
Only the value, open/close, and status is used in this function. Time information is not used.
16.3.12.5 Signals
PID-3555-INPUTSIGNALS v6
PID-3555-OUTPUTSIGNALS v6
The apparatus control functions are used for control and supervision of circuit breakers,
disconnectors and earthing switches within a bay. Permission to operate is given after evaluation of
conditions from other functions such as interlocking, synchrocheck, operator place selection and
external or internal blockings.
Normal security means that only the command is evaluated and the resulting position is not
supervised. Enhanced security means that the command is evaluated with an additional supervision
of the status value of the control object. The command sequence with enhanced security is always
terminated by a CommandTermination service primitive and an AddCause telling if the command was
successful or if something went wrong.
Control operation can be performed from the local HMI with authority control if so defined.
A bay can handle, for example a power line, a transformer, a reactor, or a capacitor bank. The
different primary apparatuses within the bay can be controlled via the apparatus control functions
directly by the operator or indirectly by automatic sequences.
Because a primary apparatus can be allocated to many functions within a Substation Automation
system, the object-oriented approach with a function block that handles the interaction and status of
each process object ensures consistency in the process information used by higher-level control
functions.
Primary apparatuses such as breakers and disconnectors are controlled and supervised by one
function block (SCSWI) each. Because the number and type of signals used for the control of a
breaker or a disconnector are almost the same, the same function block type is used to handle these
two types of apparatuses.
The SCSWI function block is connected either to an SXCBR function block (for circuit breakers) or to
an SXSWI function block (for disconnectors and earthing switches). The physical process in the
switchyard is connected to these two function blocks via binary inputs and outputs.
Four types of function blocks are available to cover most of the control and supervision within the
bay. These function blocks are interconnected to form a control function reflecting the switchyard
configuration. The total number used depends on the switchyard configuration. These types are:
The functions Local Remote (LOCREM) and Local Remote Control (LOCREMCTRL), to handle the
local/remote switch. The functions Bay reserve (QCRSV) and Reservation input (RESIN), for the
reservation function, also belong to the apparatus control function.
The principles of operation, function blocks, input and output signals and setting parameters for all
these functions are described below.
Depending on the error that occurs during the command sequence the error signal will be set with a
value. Table 601 describes the cause values given on local HMI. The translation to AddCause
values specified in IEC 61850-8-1 is shown in Table 602. For IEC 61850-8-1 edition 2 only
addcauses defined in the standard are used, for edition 1 also a number of vendor specific causes
are used. The values are available in the command response to commands from IE C61850-8-1
clients. An output L_CAUSE on the function block for Switch controller (SCSWI), Circuit breaker
(SXCBR) and Circuit switch (SXSWI) indicates the value of the cause during the latest command if
the function specific command evaluation has been started. The causes that are not always reflected
on the output L_CAUSE, with description of the typical reason are listed in table 603.
Table 602: Translation of cause values for IEC 61850 edition 2 and edition 1
The Bay control (QCBAY) function is used together with Local remote and local remote control
functions to handle the selection of the operator place per bay. QCBAY also provides blocking
functions that can be distributed to different apparatuses within the bay.
QCBAY
LR_OFF PSTO
LR_LOC UPD_BLKD
LR_REM CMD_BLKD
LR_VALID LOC
BL_UPD STA
BL_CMD REM
IEC10000048-3-en.vsdx
IEC10000048 V3 EN-US
16.4.5.3 Signals
PID-4086-INPUTSIGNALS v8
PID-4086-OUTPUTSIGNALS v8
16.4.5.4 Settings
PID-4086-SETTINGS v8
functionality is not described by the LLN0 node or any other node, therefore the Bay control function
is represented as a vendor specific node in edition 1.
When the local panel switch (or LHMI selection, depending on the set source to select this) is in Off
position, all commands from remote and local level will be ignored. If the position for the local/remote
switch is not valid the PSTO output will always be set to faulty state (3), which means no possibility to
operate.
To adapt the signals from the local HMI or from an external local/remote switch, the function blocks
LOCREM and LOCREMCTRL are needed and connected to QCBAY.
When the external switch is in Off position, or invalid position, the output always shows the actual
state of the switch (0 for Off and 3 for Invalid). In these cases, it is not possible to control anything,
and the setting AllPSTOValid has no effect on the PSTO output.
If the setting AllPSTOValid is set to No Priority and the LR-switch position is in Local or Remote
state, the PSTO output is set to 5 (all), that is, it is permitted to operate from local, station and remote
level without any priority.
If the setting RemoteIncStation is set to Yes and the LR-switch position is in Remote state, the PSTO
output is set to 2 (Station or Remote), that is, it is permitted to operate from both station and remote
level without any priority.
If the LR-switch position is in Remote state, and AllPSTOValid is set to Priority and RemoteIncStation
is set to No, the switching between station and remote level control is done through the command
LocSta. The command is accessible only through the IEC 61850 Edition 2 protocol.
Table 607: PSTO values for different Local panel switch positions
Blockings M13446-50 v6
The blocking states for position indications and commands are intended to provide the possibility for
the user to make common blockings for the functions configured within a complete bay.
The blocking facilities provided by the bay control function are the following:
• Blocking of position indications, BL_UPD. This input will block all inputs related to apparatus
positions for all configured functions within the bay.
• Blocking of commands, BL_CMD. This input will block all commands for all configured functions
within the bay.
The switching of the Local/Remote switch requires at least system operator level. The password will
be requested at an attempt to operate if authority levels have been defined in the IED, otherwise the
default authority level can handle the control without LogOn. The users and passwords are defined
with the IED Users tool in PCM600.
M17086-3 v11
The signals from the local HMI or from an external local/remote switch are connected via the function
blocks local remote (LOCREM) and local remote control (LOCREMCTRL) to the Bay control
(QCBAY) function block. The parameter ControlMode in function block LOCREM is set to choose if
the switch signals are coming from the local HMI or from an external hardware switch connected via
binary inputs.
LOCREM
CTRLOFF OFF
LOCCTRL LOCAL
REMCTRL REMOTE
LHMICTRL VALID
IEC05000360-3-en.vsdx
IEC05000360 V3 EN-US
LOCREMCTRL
^PSTO1 HMICTR1
^PSTO2 HMICTR2
^PSTO3 HMICTR3
^PSTO4 HMICTR4
^PSTO5 HMICTR5
^PSTO6 HMICTR6
^PSTO7 HMICTR7
^PSTO8 HMICTR8
^PSTO9 HMICTR9
^PSTO10 HMICTR10
^PSTO11 HMICTR11
^PSTO12 HMICTR12
IEC05000361-3-en.vsdx
IEC05000361 V3 EN-US
16.4.6.2 Signals
PID-3944-INPUTSIGNALS v7
PID-3944-OUTPUTSIGNALS v7
PID-3943-INPUTSIGNALS v6
PID-3943-OUTPUTSIGNALS v6
16.4.6.3 Settings
PID-3944-SETTINGS v7
PID-3943-SETTINGS v2
The function block Local remote (LOCREM) handles the signals coming from the local/remote switch.
The connections are seen in Figure 557, where the inputs on function block LOCREM are connected
to binary inputs if an external switch is used. When the local HMI is used, the inputs are not used.
The switching between external and local HMI source is done through the parameter ControlMode.
The outputs from the LOCREM function block control the output PSTO (Permitted Source To
Operate) on Bay control (QCBAY).
LOCREM QCBAY
CTRLOFF OFF LR_ OFF PSTO
LOCCTRL LOCAL LR_ LOC UPD_ BLKD
REMCTRL REMOTE LR_ REM CMD_ BLKD
LHMICTRL VALID LR_ VALID LOC
BL_ UPD STA
BL_ CMD REM
LOCREM QCBAY
CTRLOFF OFF LR_ OFF PSTO
LOCCTRL LOCAL LR_ LOC UPD_ BLKD
REMCTRL REMOTE LR_ REM CMD_ BLKD
LHMICTRL VALID LR_ VALID LOC
BL_ UPD STA
BL_ CMD REM
LOCREMCTRL
PSTO1 HMICTR1
PSTO2 HMICTR2
PSTO3 HMICTR3
PSTO4 HMICTR4
PSTO5 HMICTR5
PSTO6 HMICTR6
PSTO7 HMICTR7
PSTO8 HMICTR8
PSTO9 HMICTR9
PSTO 10 HMICTR 10
PSTO 11 HMICTR 11
PSTO 12 HMICTR 12
IEC10000052-1-en.vsd
IEC10000052 V2 EN-US
Figure 557: Configuration for the local/remote handling for a local HMI with two bays and two
screen pages
If the IED contains control functions for several bays, the local/remote position can be different for the
included bays. When the local HMI is used the position of the local/remote switch can be different
depending on which single line diagram screen page that is presented on the local HMI. The function
block Local remote control (LOCREMCTRL) controls the presentation of the LEDs for the local/
remote position to applicable bay and screen page.
The switching of the local/remote switch requires at least system operator level. The password will be
requested at an attempt to operate if authority levels have been defined in the IED. Otherwise the
default authority level, SuperUser, can handle the control without LogOn. The users and passwords
are defined with the IED Users tool in PCM600.
The Switch controller (SCSWI) initializes and supervises all functions to properly select and operate
switching primary apparatuses. The Switch controller may handle and operate on one multi-phase
device or up to three one-phase devices.
SCSWI
BLOCK EXE_OP
PSTO EXE_CL
L_SEL SEL_OP
L_OPEN SEL_CL
L_CLOSE SELECTED
AU_OPEN RES_RQ
AU_CLOSE START_SY
BL_CMD CANC_SY
RES_GRT POSITION
RES_EXT OPENP OS
SY_INPRO CLOSEPOS
SYNC_OK POLEDISC
EN_OPEN CMD_BLK
EN_CLOSE L_CAUSE
XPOSL1* POS_INTR
XPOSL2* XEXINF
XPOSL3*
IEC05000337-6-en.vsdx
IEC05000337 V6 EN-US
16.4.7.3 Signals
PID-7574-INPUTSIGNALS v2
PID-7574-OUTPUTSIGNALS v1
GUID-7DABB496-EABE-48A4-8078-7ED5D6D4FE14 v3
AU_OPEN and AU_CLOSE are used to issue automated commands. They work
without regard to how the operator place selector, PSTO, is set. In order to have
effect on the outputs EXE_OP and EXE_CL, the corresponding enable input,
EN_OPEN respectively EN_CLOSE must be set, and that no interlocking is active.
L_SEL, L_OPEN and L_CLOSE are used for local command sequence connected to
binary inputs. In order to have effect, the operator place selector, PSTO, must be set
to local or to remote with no priority. If the control model used is Select before
operate, Also the corresponding enable input must be set, and no interlocking is
active. The L_SEL input must be set before L_OPEN or L_CLOSE is operated, if the
control model is Select before operate.
If one multi-phase XCBR/XSWI or two single-phase XCBR/XSWI are used for a two-
or three-phase system, two or more of the inputs XPOSL1, XPOSL2 and XPOSL3
are connected to the same source.
16.4.7.4 Settings
PID-7574-SETTINGS v1
Reservation SXCBR /
Client SCSWI
logic SXSWI
select
SEL_CL = TRUE
RES_RQ = TRUE
tReservation
Response
tSelect
RES_GRT = TRUE
SELECTED = TRUE
selectAck/AddCause = 0
requestedPosition = 10
opRcvd = TRUE
EXE_CL
RES_RQ = FALSE
RES_GRT = FALSE
IEC15000416-2-EN.vsdx
IEC15000416 V2 EN-US
Figure 559: Example of command sequence for a successful close command when the control
model SBO with enhanced security is used
requestedPosition = 10
opRcvd = TRUE
RES_RQ
tReservation
Response
RES_GRT = TRUE
EXE_CL
operateAck/AddCause = 0 operateAck/AddCause = 0
RES_RQ = FALSE
RES_GRT = FALSE
IEC15000417-1-en.vsdx
IEC15000417 V1 EN-US
Figure 560: Example of command sequence for a successful close command when the control
model direct with normal security is used
Normal security means that only the command is evaluated and the resulting position is not
supervised. Enhanced security means that the command sequence is supervised in three steps, the
selection, command evaluation and the supervision of position. Each step ends up with a pulsed
signal to indicate that the respective step in the command sequence is finished. If an error occurs in
one of the steps in the command sequence, the sequence is terminated. The last error (L_CAUSE)
can be read from the function block and used for example at commissioning.
Before an execution command, an evaluation of the position is done. If the parameter PosDependent
is set to Not perm 00/11 or Not perm cPos/00/11, and the position is in intermediate state or in bad
state, the command is rejected with the cause Invalid-position. If the parameter is set to Not perm
cPos or Not perm cPos/00/11 and the command is to move to the current position, the command is
rejected with the cause Position-reached. If the parameter is set to Always permitted the execution
command is sent independent of the position value.
In the case when there are two or more one-phase switches connected to the switch control function,
the switch control will "merge" the position of the switches to the resulting multi-phase position. In the
case when the position differ between the one-phase switches, following principles will be applied:
The time stamp of the output multi-phase position from switch control will have the time stamp of the
last changed phase when it reaches the end position. When it goes to intermediate position or bad
state, it will get the time stamp of the first changed phase.
In addition, there is also the possibility that one of the one-phase switches will change position at any
time due to a trip. Such situation is here called pole discordance and is supervised by this function. In
case of a pole discordance situation, that is, the positions of the one-phase switches are not equal for
a time longer than the setting tPoleDiscord, an error signal POLEDISC will be set.
In the supervision phase, the switch controller function evaluates the "cause" values from the switch
modules circuit breaker (SXCBR)/circuit switch (SXSWI). At error the "cause" value with highest
priority is shown.
The different block conditions will only affect the operation of this function, that is, no
blocking signals will be "forwarded" to other functions. The above blocking outputs
are stored in a non-volatile memory.
When there is no positive confirmation from the synchrocheck function, SCSWI will send a start
signal START_SY to the synchronizing function, which will send the closing command to SXCBR
when the synchronizing conditions are fulfilled, see Figure 561. If no synchronizing function is
included, the timer for supervision of the "synchronizing in progress signal" is set to 0, which means
no start of the synchronizing function. SCSWI will then set the attribute "blocked-by-synchrocheck" in
the "cause" signal. See also the time diagram in Figure 565.
SCSWI SXCBR
EXE_CL
OR CLOSE
SYNC_OK
START_SY
CANC_SY
SY_INPRO
SESRSYN
CLOSECB
Synchro Synchronizing
check function
IEC09000209-2-en.vsd
IEC09000209 V2 EN-US
The timer tSelect is used for supervising the time between the select and the execute command
signal, that is, the time the operator has to perform the command execution after the selection of the
object to operate.
select
execute command
tSelect
timer t1 t1>tSelect, then long-
operation-time in 'cause'
is set
en05000092.vsd
IEC05000092 V1 EN-US
The Long-operation-time cause (-30) is only given on the output L_CAUSE. It is not
sent on protocols since the selection has already received a positive response, and
no operation has been issued. If an operation is issued after the time out, the
negative response is Object-not-selected.
The parameter tResResponse is used to set the maximum allowed time to make the reservation, that
is, the time between reservation request and the feedback reservation granted from all bays involved
in the reservation function.
select
execute command
position L1 open
close
position L2 open
close
position L3 open
close
cmd termination L1
cmd termination L2
cmd termination L3
cmd termination *
position open
close
t1>tExecutionFB, then
tExecutionFB timer long-operation-time in
t1 'cause' is set
The parameter tSynchronizing is used to define the maximum allowed time between the start signal
for synchronizing and the confirmation that synchronizing is in progress.
execute command
SYNC_OK
tSynchrocheck
t1
START_SY
SY_INPRO
en05000095.vsd
IEC05000095 V1 EN-US
The purpose of Circuit breaker (SXCBR) is to provide the actual status of positions and to perform
the control operations, that is, pass all the commands to primary apparatuses in the form of circuit
breakers via binary output boards and to supervise the switching operation and position.
SXCBR
BLOCK XPOS
LR_SWI EXE_OP
OPEN EXE_CL
CLOSE SUBSTED
BL_OPEN OP_BLKD
BL_CLOSE CL_BLKD
BL_UPD UPD_BLKD
POSOP EN POSITION
POSCLOSE OPENP OS
CBOPCAP CLOSEPOS
TR_OPEN TR_POS
TR_CLOSE CNT_VAL
RS_CNT L_CAUSE
EEH_WARN EEHEALTH
EEH_ALM CBOPCAP
XIN
IEC05000338-6-en.vsdx
IEC05000338 V6 EN-US
16.4.8.3 Signals
PID-6799-INPUTSIGNALS v3
PID-6799-OUTPUTSIGNALS v3
16.4.8.4 Settings
PID-6799-SETTINGS v3
SXCBR has an operation counter for closing and opening commands. The counter value can be read
remotely from the operator place. The value is reset from local HMI, a binary input or remotely from
the operator place by configuring a signal from the Single Point Generic Control 8 signals
(SPC8GAPC) for example. The health of the external equipment, the switch, can be monitored
according to IEC 61850-8-1. The operation counter functionality and the external equipment health
supervision are independent sub-functions of the circuit breaker function.
Local= Operation at
UE switch yard level
TR
en05000096.vsd
IEC05000096 V1 EN-US
• Block/deblock for open command. It is used to block operation for the open command.
• Block/deblock for close command. It is used to block operation for the close command.
• Update block/deblock of positions. It is used to block the updating of position values. Other
signals related to the position will be reset.
• Blocking of function, BLOCK. If BLOCK signal is set, it means that the function is active, but no
outputs are generated, no reporting, control commands are rejected and functional and
configuration data is visible.
Substitution M13487-22 v5
The substitution part in SXCBR is used for manual set of the position and quality of the switch. The
typical use of substitution is that an operator enters a manual value because that the real process
value is erroneous for some reason. SXCBR will then use the manually entered value instead of the
value for positions determined by the process.
When the position of the SXCBR is substituted, its IEC 61850-8-1 data object is
marked as “substituted", in addition to the substituted quality, but the position quality
of the connected SCSWI is not dependent on the substitution indication in the
quality, so it does not show that it is derived from a substituted value.
OPENPOS
CLOSEPOS
en05000097.vsd
IEC05000097 V1 EN-US
OPENPOS
CLOSEPOS
AdaptivePulse=FALSE
EXE_CL
tClosePulse
AdaptivePulse=TRUE
EXE_CL
tClosePulse
en05000098.vsd
IEC05000098 V1 EN-US
The execute output pulses are reset when the activating input is reset and either of the following
happens:
• the new expected final position is reached and the configuration parameter AdaptivePulse is set
to true
• the timer tOpenPulse or tClosePulse has elapsed
• an error occurs due to the switch not start moving, that is tStartMove has elapsed for normal
commands, or tIntermediate has elapsed starting from intermediate position, and the position
indications are valid.
If either of the position inputs are invalid or unconnected, the combined position is considered as
invalid. Then the execute output pulse resets at earliest when time tOpenPulse or tClosePulse has
elapsed.
If the breaker reaches the final position before the execution pulse time has elapsed,
and AdaptivePulse is not true, then the function waits for the end of the execution
pulse before indicating the activating function that the command is complete.
If the activating input remains active when the breaker has reached its final position
and the execution pulse time has elapsed, then the function waits for the reset of the
activating input before indicating that the command is complete.
There is one exception to the first item above: if the primary device is in open position and an open
command is executed or if the primary device is in closed position and a close command is executed.
In these cases, with the additional condition that the configuration parameter AdaptivePulse is true,
the execute output pulse is always activated and resets when tStartMove has elapsed. If the
configuration parameter AdaptivePulse is set to false, the execution output remains active until the
pulse duration timer has elapsed.
If the start position indicates bad state (OPENPOS=1 and CLOSEPOS=1) when a
command is executed, the execute output pulse resets at earliest when timer
tOpenPulse or tClosePulse has elapsed.
An example of when a primary device is open and an open command is executed is shown in
Figure 570 .
OPENPOS
CLOSEPOS
EXE_OP AdaptivePulse=FALSE
tOpenPulse
EXE_OP AdaptivePulse=TRUE
tOpenPulse
tStartMove timer
en05000099.vsd
IEC05000099 V1 EN-US
The purpose of Circuit switch (SXSWI) function is to provide the actual status of positions and to
perform the control operations, that is, pass all the commands to primary apparatuses in the form of
disconnectors or earthing switches via binary output boards and to supervise the switching operation
and position.
SXSWI
BLOCK XPOS
LR_SWI EXE_OP
OPEN EXE_CL
CLOSE SUBSTED
BL_OPEN OP_BLKD
BL_CLOSE CL_BLKD
BL_UPD UPD_BLKD
POSOP EN POSITION
POSCLOSE OPENP OS
SWOPCAP CLOSEPOS
RS_CNT CNT_VAL
EEH_WARN L_CAUSE
EEH_ALM EEHEALTH
XIN SWOPCAP
IEC05000339-5-en.vsdx
IEC05000339 V5 EN-US
16.4.9.3 Signals
PID-6800-INPUTSIGNALS v4
PID-6800-OUTPUTSIGNALS v4
16.4.9.4 Settings
PID-6800-SETTINGS v4
SXSWI has an operation counter for closing and opening commands. The counter value can be read
remotely from the operator place. The value is reset from a binary input or remotely from the operator
place by configuring a signal from the Single Point Generic Control 8 signals (SPC8GAPC), for
example.
Also, the health of the external equipment, the switch, can be monitored according to IEC 61850-8-1.
Local= Operation at
UE switch yard level
TR
en05000096.vsd
IEC05000096 V1 EN-US
• Block/deblock for open command. It is used to block operation for open command.
• Block/deblock for close command. It is used to block operation for close command.
• Update block/deblock of positions. It is used to block the updating of position values. Other
signals related to the position will be reset.
• Blocking of function, BLOCK. If BLOCK signal is set, it means that the function is active, but no
outputs are generated, no reporting, control commands are rejected and functional and
configuration data is visible.
Substitution M16494-21 v7
The substitution part in SXSWI is used for manual set of the position and quality of the switch. The
typical use of substitution is that an operator enters a manual value because the real process value is
erroneous of some reason. SXSWI will then use the manually entered value instead of the value for
positions determined by the process.
When the position of the SXSWI is substituted, its IEC 61850-8-1 data object is
marked as “substituted", in addition to the substituted quality, but the position quality
of the connected SCSWI is not dependent on the substitution indication in the
quality, so it does not show that it is derived from a substituted value.
OPENPOS
CLOSEPOS
en05000097.vsd
IEC05000097 V1 EN-US
OPENPOS
CLOSEPOS
AdaptivePulse=FALSE
EXE_CL
tClosePulse
AdaptivePulse=TRUE
EXE_CL
tClosePulse
en05000098.vsd
IEC05000098 V1 EN-US
For the SXSWI the activating inputs should be pulsed, however, the functionality of following them is
the same as for SXCBR.
The execute output pulses are reset when the activating input is reset and either of the following
happens:
• the new expected final position is reached and the configuration parameter AdaptivePulse is set
to true
• the timer tOpenPulse or tClosePulse has elapsed
• an error occurs due to the switch not start moving, that is tStartMove has elapsed for normal
commands, or tIntermediate has elapsed starting from intermediate position, and the position
indications are valid.
If either of the position inputs are invalid or unconnected, the combined position is considered as
invalid. Then the execute output pulse resets at earliest when time tOpenPulse or tClosePulse has
elapsed.
If the controlled primary device reaches the final position before the execution pulse
time has elapsed, and AdaptivePulse is not true, the function waits for the end of the
execution pulse before indicating the activating function that the command is
completed.
If the activating input remains active when the switch has reached its final position
and the execution pulse time has elapsed, the function waits for the reset of the
activating input before indicating that the command is completed.
There is one exception from the first item above. If the primary device is in open position and an
open command is executed or if the primary device is in close position and a close command is
executed. In these cases, with the additional condition that the configuration parameter
AdaptivePulse is true, the execute output pulse is always activated and resets when tStartMove has
elapsed. If the configuration parameter AdaptivePulse is set to false the execution output remains
active until the pulse duration timer has elapsed.
If the start position indicates bad state (OPENPOS=1 and CLOSEPOS =1) when a
command is executed the execute output pulse resets only when timer tOpenPulse
or tClosePulse has elapsed.
An example when a primary device is open and an open command is executed is shown in
Figure 575.
OPENPOS
CLOSEPOS
EXE_OP AdaptivePulse=FALSE
tOpenPulse
EXE_OP AdaptivePulse=TRUE
tOpenPulse
tStartMove timer
en05000099.vsd
IEC05000099 V1 EN-US
16.4.10 Proxy for signals from switching device via GOOSE XLNPROXY
The proxy for signals from switching device via GOOSE (XLNPROXY) gives an internal
representation of the position status and control response for a switch modelled in a breaker IED.
This representation is identical to that of an SXCBR or SXSWI function.
XLNPROXY
BEH* XPOS
BEH_VALID* SELECTED
LOC* OP_BLKD
LOC_VALID* CL_BLKD
BLKOPN* OPENPOS
BLKOPN_V* CLOSEPOS
BLKCLS* CNT_VAL
BLKCLS_V* L_CAUSE
POSVAL* EEHEALTH
POSVAL_V* OPCAP
OPCNT*
OP_CNT_V*
BLK
BLK_VAL
STSELD
STSELD_V
OPRCVD
OPRCVD_V
OPOK
OPOK_VAL
EEHEALTH
EEH_VAL
OPCAP
OPCAP_V
COMMVALID
XIN
IEC16000043-1-en.vsdx
IEC16000043 V1 EN-US
16.4.10.3 Signals
PID-6712-INPUTSIGNALS v3
PID-6712-OUTPUTSIGNALS v3
16.4.10.4 Settings
PID-6712-SETTINGS v3
GUID-A4CCC681-D4D8-4534-905D-1D8AD40E923B v1
The default values of the inputs BEH, OPCNT, EEHEALTH and OPCAP are set to -1
to denote that they are not connected.
The proxy for signals from switching device via GOOSE (XLNPROXY) is intended to be used when
the switch (XCBR/XSWI) is modelled and controlled in a breaker IED or similar unit on the process
bus. XLNPROXY packages the signals from the GOOSE receive function, normally
GOOSEXLNRCV, into the same format as used from SXCBR and SXSWI to SCSWI. It makes a
similar evaluation of the command response as SXCBR and SXSWI when a command is issued from
the connected SCSWI.
XLNPROXY has two outputs for position indication: OPENPOS and CLOSEPOS. Position is a
double point indication and the OPENPOS and CLOSEPOS are binary outputs intended to be used
for condition logics to protection and control functions
Normally, the position outputs, OPENPOS and CLOSEPOS, follow the value of the input POSVAL.
However, if the POSVAL_V input is FALSE, the communication is lost (COMMVALID = FALSE), or
the quality of the position received is bad, the OPENPOS and CLOSEPOS are both set to FALSE.
The command evaluation is triggered through the group input XIN that is connected to the SCSWI
function controlling the switch.
If an operation is initiated by the SCSWI, the XLNPROXY function checks if the switch is blocked for
the operation direction and that the position moves to the desired position within the two time limits
tStartMove and tIntermediate. The default values for tStartMove and tIntermediate are for a breaker.
The typical values for a disconnector are:
• tStartMove = 3s
• tIntermediate = 15s
In most cases, tStartMove and tIntermediate can be set to the same values as in the
source XCBR or XSWI function. However, if the time limits are set very close to the
actual movement times of the apparatus, compensation may be needed for the
communication delays and differences in cycle time of the XLNPROXY function and
the source function. The compensation should be in the range of 0 - 5ms.
When the switch has started moving, it issues a response to the SCSWI function that the operation
has started. If it does not start moving within tStartMove, the command is deemed as failed, and a
cause is raised on the L_CAUSE output and sent to the SCSWI. The different causes it can identify
are listed in order of priority in table 1. The detection of the different ways of blocking is done while
waiting for movement of the switch, but the cause is not given until the tStartMove has elapsed.
The L_CAUSE output keeps its output value until a new command sequence has been started.
If the quality of the position or the communication becomes bad, the command evaluation replaces
the uncertain position value with intermediate position. Thus, as long as the quality is bad, all
commands will result in the cause Persistant-intermediate-state, -32.
If the switch in the merging unit has the behaviour set to Test or Test blocked, when the IED has the
behaviour On or Blocked, all data from the switch is regarded as invalid. Thus, any command will fail
with the cause PersistantiIntermediate-state, -32, and if selection is used for the switch, all attempts
to select the connected SCSWI will fail with the cause Select-failed, 3, from the SCSWI.
It is possible to speed up the command response for when the command has been started by the
switch in the breaker IED by connecting the inputs OPOK and OPOK_VAL. Then the blocking check
is only done until OPOK is activated and confirmation of that the command has been started is given
to the SCSWI function.
If the inputs STSELD and STSELD_V are connected, the switch in the breaker IED is assumed to
use selection. Then the SCSWI will wait for a selected indication, STSELD input of XLNPROXY,
before accepting selection, this information is transferred to the SCSWI function from the
XLNPROXY through the group connection XPOS. If STSELD is not activated within tSelect of the
SCSWI function, the selection is deemed failed and it gives a negative selection acknowledgement to
the command issuer with the cause Select-failed. Further, if the communication is lost, or the data
received is deemed invalid, the selection will also fail with cause Select-failed from the SCSWI.
The purpose of the reservation (QCRSV) function is primarily to transfer interlocking information
between IEDs in a safe way and to prevent double operation in a bay, switchyard part, or complete
substation.
QCRSV
EXCH_IN RES_GRT1
RES_RQ1 RES_GRT2
RES_RQ2 RES_GRT3
RES_RQ3 RES_GRT4
RES_RQ4 RES_GRT5
RES_RQ5 RES_GRT6
RES_RQ6 RES_GRT7
RES_RQ7 RES_GRT8
RES_RQ8 RES_BAYS
BLOCK ACK_TO_B
OVERRIDE RESERVED
RES_DATA EXCH_OUT
IEC05000340-3-en.vsdx
IEC05000340 V3 EN-US
16.4.11.3 Signals
PID-3561-INPUTSIGNALS v7
PID-3561-OUTPUTSIGNALS v7
16.4.11.4 Settings
PID-3561-SETTINGS v7
The parameters ParamRequestx (x=1-8) are chosen at reservation of the own bay only (TRUE) or
other bays (FALSE). To reserve the own bay only means that no reservation request RES_BAYS is
created.
If the RESERVED output is not set, the selection is made with the output RES_GRTx (where x=1-8 is
the number of the requesting apparatus), which is connected to switch controller SCSWI. If the bay
already is reserved the command sequence will be reset and the SCSWI will set the attribute "1-of-n-
control" in the "cause" signal.
When it receives acknowledge from the bays via the input RES_DATA, it sets the output RES_GRTx
(where x=1-8 is the number of the requesting apparatus). If not acknowledgement from all bays is
received within a certain time defined in SCSWI (tResResponse), the SCSWI will reset the
reservation and set the attribute "1-of-n-control" in the "cause" signal.
The reservation function can also be overridden in the own bay with the OVERRIDE input signal, that
is, reserving the own bay without waiting for the external acknowledge.
If there are more than eight apparatuses in the bay, there has to be one additional QCRSV. The two
QCRSV functions have to communicate and this is done through the input EXCH_IN and
EXCH_OUT according to Figure 578. If more than one QCRSV are used, the execution order is very
important. The execution order must be in the way that the first QCRSV has a lower number than the
next one.
QCRSV
EXCH_IN RES_GRT1
RES_RQ1 RES_GRT2
RES_RQ2 RES_GRT3
RES_RQ3 RES_GRT4
RES_RQ4 RES_GRT5
RES_RQ5 RES_GRT6
RES_RQ6 RES_GRT7
RES_RQ7 RES_GRT8
RES_RQ8 RES_BAYS
BLOCK ACK_TO_B
OVERRIDE RESERVED
RES_DATA EXCH_OUT
QCRSV
EXCH_IN RES_GRT1
RES_RQ1 RES_GRT2
RES_BAYS
RES_RQ2 RES_GRT3 1
RES_RQ3 RES_GRT4
RES_RQ4 RES_GRT5
RES_RQ5 RES_GRT6 ACK_TO_B
RES_RQ6 RES_GRT7 1
RES_RQ7 RES_GRT8
RES_RQ8 RES_BAYS
1
BLOCK ACK_TO_B RESERVED
OVERRIDE RESERVED
RES_DATA EXCH_OUT
IEC05000088-3-en.vsdx
IEC05000088 V3 EN-US
The Reservation input (RESIN) function receives the reservation information from other bays. The
number of instances is the same as the number of involved bays (up to 60 instances are available).
RESIN1
BAY_ACK ACK_F_B
BAY_VAL ANY_ACK
BAY_RES VALID_TX
RE_RQ_B
V_RE_RQ
EXCH_OUT
IEC05000341-2-en.vsd
IEC05000341 V2 EN-US
RESIN2
EXCH_IN ACK_F_B
BAY_ACK ANY_ACK
BAY_VAL VALID_TX
BAY_RES RE_RQ_B
V_RE_RQ
EXCH_OUT
IEC09000807_1_en.vsd
IEC09000807 V1 EN-US
16.4.12.3 Signals
PID-3629-INPUTSIGNALS v7
PID-3629-OUTPUTSIGNALS v7
PID-3630-INPUTSIGNALS v7
PID-3630-OUTPUTSIGNALS v7
16.4.12.4 Settings
PID-3629-SETTINGS v7
PID-3630-SETTINGS v7
The reservation input (RESIN) function is based purely on Boolean logic conditions. The logic
diagram in Figure 581 shows how the output signals are created. The inputs of the function block are
connected to a receive function block representing signals transferred over the station bus from
another bay.
EXCH_IN INT
BIN
ACK_F_B
&
FutureUse
³1
ANY_ACK
BAY_ACK ³1
VALID_TX
&
BAY_VAL ³1
RE_RQ_B
³1
BAY_RES &
V _RE_RQ
³1
BIN
EXCH_OUT
INT
en05000089.vsd
IEC05000089 V1 EN-US
RESIN
BAY_ACK ACK_F_B
Bay 1 BAY_VAL ANY_ACK
BAY_RES VALID_TX
RE_RQ_B
V_RE_RQ
EXCH_OUT
RESIN
EXCH_IN ACK_F_B
BAY_ACK ANY_ACK
Bay 2 BAY_VAL VALID_TX
BAY_RES RE_RQ_B
V_RE_RQ
EXCH_OUT
RESIN
EXCH_IN ACK_F_B
BAY_ACK ANY_ACK
Bay n BAY_VAL VALID_TX
BAY_RES RE_RQ_B QCRSV
V_RE_RQ
EXCH_OUT RES_DATA
en05000090.vsd
IEC05000090 V2 EN-US
16.5.1 Identification
SEMOD173054-2 v6
IEC10000165 V1 EN-US
IEC10000166 V1 EN-US
IEC10000165000 V1 EN-US
IEC10000165000 V1 EN-US
Automatic voltage control for tap changer, single control (TR1ATCC), Automatic voltage control for
tap changer, parallel control (TR8ATCC), Tap changer control and supervision, 6 binary inputs
(TCMYLTC) and Tap changer control and supervision, 32 binary inputs (TCLYLTC) are used for
control of power transformers with an on-load tap changer. The functions provide automatic
regulation of the voltage on the secondary side of transformers or alternatively on a load point further
out in the network.
Voltage control includes many extra features such as the possibility to avoid simultaneous tapping of
parallel transformers, hot stand by regulation of a transformer in a group which regulates it to a
correct tap position even though the LV CB is open, compensation for a possible capacitor bank on
the LV side bay of a transformer, extensive tap changer monitoring including contact wear and
hunting detection, monitoring of the power flow in the transformer so that, for example, the voltage
control can be blocked if the power reverses, etc.
SEMOD158823-5 v6
The Automatic voltage control for tap changer TR1ATCC for single control and TR8ATCC for parallel
control function controls the voltage on the LV side of a transformer either automatically or manually.
The automatic control can be either for a single transformer, or for a group of parallel transformers.
In addition, all three-phase currents from the HV-winding (usually the winding where the tap changer
is situated) are used by the Automatic voltage control for tap changer TR1ATCC for single control
and TR8ATCC for parallel control function for over current blocking.
The analog input signals are normally common for other functions in the IED for example, protection
functions.
The LV-busbar voltage is designated UB, load current IL and for load point voltage UL
will be used in the text to follow.
Automatic voltage control for tap changer, single control TR1ATCC SEMOD158887-4 v6
Automatic voltage control for tap changer, single control TR1ATCC measures the magnitude of the
busbar voltage UB. If no other additional features are enabled (line voltage drop compensation), this
voltage is further used for voltage regulation.
TR1ATCC then compares this voltage with the set voltage, USet and decides which action should be
taken. To avoid unnecessary switching around the setpoint, a deadband (degree of insensitivity) is
introduced. The deadband is symmetrical around USet, see figure 583, and it is arranged in such a
way that there is an outer and an inner deadband. Measured voltages outside the outer deadband
start the timer to initiate tap commands, whilst the sequence resets when the measured voltage is
once again back inside the inner deadband. One half of the outer deadband is denoted ΔU. The
setting of ΔU, setting Udeadband should be set to a value near to the power transformer’s tap
changer voltage step (typically 75–125% of the tap changer step).
Security Range
*) *) *)
Raise Cmd DU DU Lower Cmd
DUin DUin
IEC06000489_2_en.vsd
IEC06000489 V2 EN-US
This way of working is used by TR1ATCC while the busbar voltage is within the security range
defined by settings Umin and Umax
A situation where UB falls outside this range will be regarded as an abnormal situation.
Instead of controlling the voltage at the LV busbar in the same substation as the transformer itself, it
is possible to control the voltage at a load point out in the network, downstream from the transformer.
The Line Voltage Drop Compensation (LDC) can be selected by a setting parameter, and it works
such that the voltage drop from the transformer location to the load point is calculated based on the
measured load current and the known line impedance.
In order to prevent unnecessary load tap changer operations caused by temporary voltage
fluctuations and to coordinate load tap changer operations in radial networks, a time delay is used for
the tapping command to the load tap changer. The time delay can be either definite time or inverse
time and two time settings are used, the first (t1) for the initial delay of a tap command, and the
second (t2) for consecutive tap commands.
Three alternative methods can be used for parallel control with Automatic control for tap changer,
parallel control TR8ATCC:
• master-follower method
• reverse reactance method
• circulating current method.
The followers can act in one of two alternative ways selected by a setting parameter:
1. Raise and lower commands (URAISE and ULOWER) generated by the master, initiates the
corresponding command in all follower TR8ATCCs simultaneously, and consequently they will
blindly follow the master commands irrespective of their individual tap positions.
2. The followers read the tap position of the master and adapt to the same tap position or to a tap
position with an offset relative to the master. In this mode, the followers can also be time
delayed relative to the master.
When the voltage at a load point is controlled by using LDC, the line impedance from the transformer
to the load point is defined by the setting Xline. If a negative reactance is entered instead of the
normal positive line reactance, parallel transformers will act in such a way that the transformer with a
higher tap position will be the first to tap down when the busbar voltage increases, and the
transformer with a lower tap position will be the first to tap up when the busbar voltage decreases.
The overall performance will then be that a runaway tap situation will be avoided and that the
circulating current will be minimized.
If the functions are located in different IEDs they must communicate via GOOSE interbay
communication on the IEC 61850 communication protocol. Complete exchange of TR8ATCC data,
analog as well as binary, via GOOSE is made cyclically every 300 ms.
The main objectives of the circulating current method for parallel voltage control are:
The busbar voltage UB is measured individually for each transformer in the parallel group by its
associated TR8ATCC function. These measured values will then be exchanged between the
transformers, and in each TR8ATCC block, the mean value of all UB values will be calculated. The
resulting value UBmean will then be used in each IED instead of UB for the voltage regulation, thus
assuring that the same value is used by all TR8ATCC functions, and thereby avoiding that one
erroneous measurement in one transformer could upset the voltage regulation. At the same time,
supervision of the VT mismatch is also performed.
Figure 584 shows an example with two transformers connected in parallel. If transformer T1 has
higher no load voltage it will drive a circulating current which adds to the load current in T1 and
subtracts from the load current in T2.
IT1 IT2
UB
IL IL
UL Load UL Load
IEC06000484_3_en.vsd
IEC06000484 V3 EN-US
UT1 - UT 2
I cc _ T 1 = I cc _ T 2 =
ZT 1 + ZT 2
EQUATION1866 V1 EN-US (Equation 266)
Because the transformer impedance is dominantly inductive, it is possible to use just the transformer
reactances in the above formula. At the same time this means that T1 circulating current lags the
busbar voltage by almost 90°, while T2 circulating current leads the busbar voltage by almost 90°.
UT1 CT1*ICC_T1*ZT1
UB
CT2*ICC_T2*ZT2
UT2
IL
IT2 IT1
2*Udeadband
ICC_T2 ICC_T1
T2 Receives Cir_Curr T1 Produces Cir_Curr
IL = IT1+ IT2
Icc_T1 = Imag {IT1- (ZT2/(ZT1+ZT2)) * IL}
Icc_T2 = Imag {IT2- (ZT1/(ZT1+ZT2)) * IL}
en06000525.vsd
IEC06000525 V1 EN-US
Figure 585: Vector diagram for two power transformers working in parallel
Thus, by minimizing the circulating current flow through transformers, the total reactive power flow is
optimized as well. In the same time, at this optimum state the apparent power flow is distributed
among the transformers in the group in proportion to their rated power.
In order to calculate the circulating current, measured current values for the individual transformers
must be communicated between the participating TR8ATCC functions. It should be noted that the
Fourier filters in different IEDs run asynchronously, which means that current and voltage phasors
cannot be exchanged and used for calculation directly between the IEDs. In order to “synchronize”
measurements within all IEDs in the parallel group, a common reference must be chosen. The most
suitable reference quantity for all transformers, belonging to the same parallel group, is the busbar
voltage. This means that the measured busbar voltage is used as a reference phasor in all IEDs, and
the position of the current phasors in a complex plane is calculated in respect to this reference. This
is a simple and effective solution, which eliminates any additional need for synchronization between
the IEDs regarding TR8ATCC function.
At each transformer bay, the real and imaginary parts of the current on the secondary side of the
transformer are calculated from measured values, and distributed to the TR8ATCC functions
belonging to the same parallel group.
As mentioned before, only the imaginary part (reactive current component) of the individual
transformer current is needed for the circulating current calculations. The real part of the current will,
however, be used to calculate the total through load current and will be used for the line voltage drop
compensation.
The total load current is defined as the sum of all individual transformer currents:
k
I L = å Ii
i =1
where the subscript i signifies the transformer bay number and k the number of parallel transformers
in the group (k≤ 8). Next step is to extract the circulating current Icc_i that flows in bay i. It is possible
to identify a term in the bay current which represents the circulating current. The magnitude of the
circulating current in bay i, Icc_i , can be calculated as:
I cc _ i = - Im( I i - K i ´ I L )
EQUATION1868 V1 EN-US (Equation 268)
where Im signifies the imaginary part of the expression in brackets and Ki is a constant which
depends on the number of transformers in the parallel group and their short-circuit reactances. The
TR8ATCC function automatically calculates this constant based on the transformer reactances which
are setting parameters, and shall be given in primary ohms calculated from each transformer rating
plate. The minus sign is added in the above equation in order to get a positive value of the circulating
current for the transformer that generates it.
In this way each TR8ATCC function calculates the circulating current of its own bay.
A plus sign means that the transformer produces circulating current while, a minus sign means that
the transformer receives circulating current.
As a next step, it is necessary to estimate the value of the no-load voltage in each transformer. To do
that the magnitude of the circulating current in each bay is first converted to a voltage deviation, Udi,
with the following formula:
U di = Ci ´ I cc _ i ´ X i
EQUATION1869 V1 EN-US (Equation 269)
where Xi is the short-circuit reactance for transformer i and Ci, is a setting parameter named Comp
which serves the purpose of alternatively increasing or decreasing the impact of the circulating
current in the TR8ATCC control calculations. It should be noted that Udi will have positive values for
transformers that produce circulating current and negative values for transformers that receive
circulating current.
Now the magnitude of the no-load voltage for each transformer can be approximated with:
U i = U Bmean + U di
EQUATION1870 V1 EN-US (Equation 270)
Generally speaking, this value for the no-load voltage can then be put into the voltage control
function in a similar way as for the single transformer described previously. Ui would then be
regarded similarly to the single transformer measured busbar voltage, and further control actions
taken.
For the transformer producing/receiving the circulating current, the calculated no-load voltage will be
greater/smaller than the measured voltage UBmean. The calculated no-load voltage will thereafter be
compared with the set voltage USet . A steady deviation which is outside the outer deadband will
result in ULOWER or URAISE being initiated alternatively. In this way the overall control action will
always be correct since the position of a tap changer is directly related to the transformer no-load
voltage. The sequence resets when UBmean is inside the inner deadband at the same time as the
calculated no-load voltages for all transformers in the parallel group are inside the outer deadband.
The example in figure 586,is a fabricated case and not very realistic, but it illustrates some details on
how the described regulation works.
T1 T2 T3 T4
UBmean
T1 No-load voltage
DB1
DB2
USet
DB2
DB1
IEC06000526_2_en.vsd
IEC06000526 V2 EN-US
In the TR8ATCC function for T1 and T4, the calculated no-load voltage for T1 and T4 respectively, is
above the upper limit of DB1 and thus outside the deadband.
In the TR8ATCC function for T2, the calculated no-load voltage for T2, viewed from the upper DB1, is
not outside (above) the deadband, but as viewed from the lower DB1 it is outside (below) the
deadband. However, there is a restriction in a situation like this, when the measured busbar voltage,
UBmean, is on the opposite side of the USet line (in figure 586), then UBmean must be inside DB1 if the
calculated no-load voltage for that transformer shall qualify as a candidate for tapping. Thus in the
example above, the calculated no-load voltage for T2, although below DB1, would not be considered
for tapping in this case.
In the TR8ATCC function for T3, the calculated no-load voltage for T3, is above the upper limit of
DB1 and thus outside the deadband. However, viewed from the upper limit DB1, transformers with
negative voltage deviation, Udi, are disregarded and similarly, viewed from the lower limit DB1,
transformers with positive voltage deviation, Udi, are disregarded. Thus in the example above, the
calculated no-load voltage for T3, although above DB1, would not be considered in this case. Thus in
the example above, the calculated no-load voltage for T3, although above DB1, would not be
considered for tapping in this case.
It is possible to avoid simultaneous tapping, and to distribute tapping actions evenly among the
parallel transformers in a busbar group. This is a selected by a setting parameter, and the algorithm
in the TR8ATCC function will then select the transformer with the greatest voltage deviation Udi to tap
first that is, after time delay t1. Thereafter, the transformer with the then greatest value of Udi
amongst the remaining transformers in the group will tap after a further time delay t2, and so on. This
is made possible as the calculation of Icc is updated every time the measured values are exchanged
on the horizontal communication (every 300 ms). If two transformers have equal magnitude of Udi,
then there is a predetermined order governing which one is going to tap first.
AUTO
UL a
a<b
< &
U1 INNER DB b &
a
a>b
>
U2 INNER DB b &
a
a<b
>1 URAISE
<
U1 DB b
a
a>b
>1
> >1 ULOWER
U2 DB b
UB a
a>b
>
U MAX b &
FSD &
en06000509.vsd
IEC06000509 V1 EN-US
Figure 587: Simplified logic for automatic control in single mode operation
AUTO
PARALLEL START
&
OPERSIMTAP
UL a
a<b
< &
U1 INNER DB b &
&
a
a>b
>
U2 INNER DB b &
U CIRCCOMP
&
MIN a
a<b
>1 URAISE
<
U1 DB b >1
U CIRCCOMP
MAX a
a>b
>1
> >1 ULOWER
U2 DB b >1
UB a
a>b
>
U MAX b &
FSD &
en06000511.vsd
IEC06000511 V1 EN-US
Figure 588: Simplified logic for parallel control in the circulating current mode
UCCT4 a
a=b
b &
T4PG &
T4
UCCT3 a 1
a=b & ³1
b & & &
T3PG T3 SIMLOWER
³1
UCCT2 a
a=b
1 &
b & &
T2
T2PG
UCCT1 a &
a=b
1 &
& T1
b
MAX
T1PG
a
a=b
b &
&
T1
a 1
a=b & ³1
b & & &
T2PG T2 SIMRAISE
³1
a
a=b
1 &
b & &
T3
T3PG
a &
a=b
1 &
T4
b &
T4PG
MIN
ADAPT
a
³1
a=b
ActualUser S b
³1 1
³1
Udeadband S a
a=b
b
LoadVoltage
HOMING
OperSimTap
1
en06000521.vsd
IEC06000521 V1 EN-US
relativePosition a
a<b
<
raiseVoltageOut
b &
&
lowerVoltageOut
a
a>b
> =
b & URAISE
& 1
Follow Tap
&
& =
ULOWER
1 1
YLTCOUT ® ATCCIN
tapPosition &
&
tapInHighVoltPos
tapInLowVoltPos
en06000510.vsd
IEC06000510 V1 EN-US
SEMOD171466-5 v7
The Tap changer control and supervision, 6 binary inputs TCMYLTC and 32 binary inputs TCLYLTC
gives the tap commands to the tap changer, and supervises that commands are carried through
correctly. It has built-in extensive possibilities for tap changer position measurement, as well as
supervisory and monitoring features. This is used in the voltage control and can also give information
about tap position to the transformer differential protection.
1. Via binary input signals, one per tap position (max. 6 or 32 positions).
2. Via coded binary (Binary), binary coded decimal (BCD) signals, or Gray coded binary signals.
3. Via a mA input signal.
Via coded binary (Binary), binary coded decimal (BCD) signals or Gray coded binary signals SEMOD159170-24 v4
The Tap changer control and supervision, (TCMYLTC or TCLYLTC) decodes binary data from up to
six binary inputs to an integer value. The input pattern may be decoded either as BIN, BCD or GRAY
format depending on the setting of the parameter CodeType.
It is also possible to use even parity check of the input binary signal. Whether the parity check shall
be used or not is set with the setting parameter UseParity.
The input BIERR on (TCMYLTC or TCLYLTC) can be used as supervisory input for indication of any
external error ( Binary Input Module) in the system for reading of tap changer position. Likewise, the
input OUTERR can be used as a supervisory of the Binary Input Module.
The truth table (see table 635) shows the conversion for Binary, Binary Coded Decimal, and Gray
coded signals.
IEC06000522 V1 EN-US
The Gray code conversion above is not complete and therefore the conversion from decimal
numbers to Gray code is given below.
IEC06000523 V1 EN-US
The measurement of the tap changer position via MIM module is based on the principle that the
specified mA input signal range (usually 4-20 mA) is divided into N intervals corresponding to the
number of positions available on the tap changer. All mA values within one interval are then
associated with one tap changer position value.
The number of available tap changer positions N is defined by the setting parameters LowVoltTap
and HighVoltTap, which define the tap position for lowest voltage and highest voltage respectively.
The two function blocks Automatic voltage control for tap changer, single control TR1ATCC and
parallel control TR8ATCC and Tap changer control and supervision, 6 binary inputs TCMYLTC and
32 binary inputs TCLYLTC are connected to each other according to figure 591 below.
(Rmk. In case of
parallel control,
this signal shall
TR8ATCC TCLYLTC also be connected
I3P1 ATCCOUT YLTCIN URAISE to HORIZx input of
I3P2 MAN TCINPROG ULOWER the parallel
U3P2 AUTO INERR HIPOSAL transformer
BLOCK IBLK RESETERR LOPOSAL TR8ATCC function
MANCTRL PGTFWD OUTERR POSERRAL
block)
AUTOCTRL PLTREV RS_CLCNT CMDERRAL
PSTO QGTFWD RS_OPCNT TCERRAL
RAISEV QLTREV PARITY POSOUT
LOWERV REVACBLK BIERR CONVERR
EAUTOBLK UHIGH B1 NEWPOS
DEBLKAUT ULOW B2 HIDIFPOS
LVA1 UBLK B3 INVALPOS
LVA2 HOURHUNT B4 YLTCOUT
LVA3 DAYHUNT B5
LVA4 HUNTING B6
LVARESET SINGLE B7
RSTERR PARALLEL B8
DISC HOMING B9
Q1ON ADAPT B10
Q2ON TOTBLK B11
Q3ON AUTOBLK B12
SNGLMODE MASTER B13
T1INCLD FOLLOWER B14
T2INCLD MFERR B15
T3INCLD OUTOFPOS B16
T4INCLD COMMERR B17
T5INCLD ICIRC B18
T6INCLD TRFDISC B19
T7INCLD VTALARM B20
T8INCLD T1PG B21
FORCMAST T2PG B22
RSTMAST T3PG B23
ATCCIN T4PG B24
HORIZ1 T5PG B25
HORIZ2 T6PG B26
HORIZ3 T7PG B27
HORIZ4 T8PG B28
HORIZ5 B29
HORIZ6 B30
HORIZ7 B31
HORIZ8 B32
MA
IEC06000507_2_en.vsd
IEC06000507 V2 EN-US
Signal Description
raiseVolt Order to TCMYLTC or TCLYLTC to make a raise command
lowerVolt Order to TCMYLTC or TCLYLTC to make a lower command
automaticCtrl The regulation is in automatic control
extRaiseBlock Block raise commands
extLowerBlock Block lower commands
Signal Description
CircCurrBl Alarm/Block tap changer operation because of high circulating current
CmdErrBl Alarm/Block tap changer operation because of command error
OCBl Alarm/Block tap changer operation because of over current
MFPosDiffBl Alarm/Block tap changer operation because the tap difference between a follower and the
master is greater than the set value
OVPartBl Alarm/Block raise commands because the busbar voltage is above Umax
RevActPartBl Alarm/Block raise commands because reverse action is activated
TapChgBl Alarm/Block tap changer operation because of tap changer error
TapPosBl Alarm/Block commands in one direction because the tap changer has reached an end
position, or Alarm/Block tap changer operation because of tap changer error
UVBl Alarm/Block tap changer operation because the busbar voltage is below Ublock
UVPartBl Alarm/Block lower commands because the busbar voltage is between Umin and Ublock
Signal Description
currAver Value of current in the phase with the highest current value
In case of parallel control of transformers, the data set sent from output signal ATCCOUT to other
TR8ATCC blocks input HORIZx contains one "word" containing 10 binary signals and 6 analog
signals:
Signal Description
TimerOn This signal is activated by the transformer that has started its timer and is going to tap when
the set time has expired.
automaticCTRL Activated when the transformer is set in automatic control
mutualBlock Activated when the automatic control is blocked
disc Activated when the transformer is disconnected from the busbar
receiveStat Signal used for the horizontal communication
TermIsForcedMaster Activated when the transformer is selected Master in the master-follower parallel control
mode
TermIsMaster Activated for the transformer that is master in the master-follower parallel control mode
termReadyForMSF Activated when the transformer is ready for master-follower parallel control mode
raiseVoltageOut Order from the master to the followers to tap up
lowerVoltageOut Order from the master to the followers to tap down
Signal Description
voltageBusbar Measured busbar voltage for this transformer
ownLoad Currim Measured load current imaginary part for this transformer
ownLoadCurrre Measured load current real part for this transformer
reacSec Transformer reactance in primary ohms referred to the LV side
relativePosition The transformer's actual tap position
voltage Setpoint The transformer's set voltage (USet) for automatic control
The TCMYLTC or TCLYLTC function blocks have an output YLTCOUT. As shown in figure 591, this
output shall be connected to the input ATCCIN and it contains 10 binary signals and 4 integer
signals:
Signal Description
tapInOperation Tap changer in operation, changing tap position
direction Direction, raise or lower, for the most recent tap changer operation
tapInHighVoltPos Tap changer in high end position
tapInLowVoltPos Tap changer in low end position
tapPositionError Error in reading of tap position ( tap position out of range, more than one step change, BCD
code error (unaccepted combination), parity fault, mA out of range, hardware fault for
example, BIM etc.)
tapChgError This is set high when the tap changer has not carried through a raise/lower command within
the expected max. time, or if the tap changer starts tapping without a given command.
cmdError This is set high if a given raise/lower command is not followed by a tap position change
within the expected max. time
raiseVoltageFb Feedback to TR1ATCC or TR8ATCC that a raise command shall be executed
lowerVoltageFb Feedback to TR1ATCC or TR8ATCC that a lower command shall be executed
timeOutTC Setting value of tTCTimeout that tTCTimeout has timed out.
Signal Description
tapPosition Actual tap position as reported from the load tap changer
numberOfOperations Accumulated number of tap changer operations
tapPositionMaxVolt Tap position for highest voltage
tapPositionMinVolt Tap position for lowest voltage
SEMOD173000-4 v4
TR1ATCC
I3P1* ATCCOUT
I3P2* MAN
U3P2* AUTO
BLOCK IBLK
MANCTRL PGTFWD
AUTOCTRL PLTREV
PSTO QGTFWD
RAISEV QLTREV
LOWERV REVACBLK
EAUTOBLK UHIGH
DEBLKAUT ULOW
LVA1 UBLK
LVA2 HOURHUNT
LVA3 DAYHUNT
LVA4 HUNTING
LVARESET TIMERON
RSTERR TOTBLK
ATCCIN AUTOBLK
UGTUPPDB
ULTLOWDB
IEC07000041_2_en.vsd
IEC07000041 V2 EN-US
TR8ATCC
I3P1* ATCCOUT
I3P2* MAN
U3P2* AUTO
BLOCK IBLK
MANCTRL PGTFWD
AUTOCTRL PLTREV
PSTO QGTFWD
RAISEV QLTREV
LOWERV REVACBLK
EAUTOBLK UHIGH
DEBLKAUT ULOW
LVA1 UBLK
LVA2 HOURHUNT
LVA3 DAYHUNT
LVA4 HUNTING
LVARESET SINGLE
RSTERR PARALLEL
DISC TIMERON
Q1ON HOMING
Q2ON ADAPT
Q3ON TOTBLK
SNGLMODE AUTOBLK
T1INCLD MASTER
T2INCLD FOLLOWER
T3INCLD MFERR
T4INCLD OUTOFPOS
T5INCLD UGTUPPDB
T6INCLD ULTLOWDB
T7INCLD COMMERR
T8INCLD ICIRC
FORCMAST TRFDISC
RSTMAST VTALARM
ATCCIN T1PG
HORIZ1 T2PG
HORIZ2 T3PG
HORIZ3 T4PG
HORIZ4 T5PG
HORIZ5 T6PG
HORIZ6 T7PG
HORIZ7 T8PG
HORIZ8
IEC07000040_2_en.vsd
IEC07000040 V2 EN-US
SEMOD173008-4 v4
TCMYLTC
YLTCIN* URAISE
TCINPROG ULOWER
INERR HIPOSAL
RESETERR LOPOSAL
OUTERR POSERRAL
RS_CLCNT CMDERRAL
RS_OPCNT TCERRAL
PARITY POSOU T
BIERR CONVERR
B1 NEWPOS
B2 HIDIFPOS
B3 INVALPOS
B4 TCPOS
B5 YLTCOUT
B6
MA
IEC07000038-4-en.vsdx
IEC07000038 V4 EN-US
TCLYLTC
YLTCIN* URAISE
TCINPROG ULOWER
INERR HIPOSAL
RESETERR LOPOSAL
OUTERR POSERRAL
RS_CLCNT CMDERRAL
RS_OPCNT TCERRAL
PARITY POSOUT
BIERR CONVERR
B1 NEWPOS
B2 HIDIFPOS
B3 INVALPOS
B4 TCPOS
B5 YLTCOUT
B6
B7
B8
B9
B10
B11
B12
B13
B14
B15
B16
B17
B18
B19
B20
B21
B22
B23
B24
B25
B26
B27
B28
B29
B30
B31
B32
MA
IEC07000037_2_en.vsd
IEC07000037 V2 EN-US
VCTRRCV
BLOCK VCTR_REC
COMVALID
DATVALID
IEC07000045-2-en.vsd
IEC07000045 V2 EN-US
16.5.7 Signals
PID-6562-INPUTSIGNALS v3
PID-6562-OUTPUTSIGNALS v3
PID-6559-INPUTSIGNALS v3
PID-6559-OUTPUTSIGNALS v3
PID-6506-INPUTSIGNALS v6
PID-6506-OUTPUTSIGNALS v6
PID-3668-INPUTSIGNALS v6
PID-3668-OUTPUTSIGNALS v7
PID-923-INPUTSIGNALS v6
PID-923-OUTPUTSIGNALS v6
16.5.8 Settings
PID-6562-SETTINGS v3
PID-6559-SETTINGS v3
PID-6506-SETTINGS v5
PID-3668-SETTINGS v6
PID-6559-MONITOREDDATA v3
PID-6506-MONITOREDDATA v5
PID-3669-MONITOREDDATA v2
PID-3668-MONITOREDDATA v6
The voltage control function is built up by two function blocks. Both are logical nodes in IEC
61850-8-1.
TR1ATCC and TR8ATCC are designed to automatically maintain the voltage at the LV-side side of a
power transformer within given limits around a set target voltage. A raise or lower command is
generated whenever the measured voltage, for a given period of time, deviates from the set target
value by more than the preset deadband value that is, degree of insensitivity. A time-delay (inverse
or definite time) is set to avoid unnecessary operation during shorter voltage deviations from the
target value, and in order to coordinate with other automatic voltage controllers in the system.
TCMYLTC and TCLYLTC are an interface between TR1ATCC and TR8ATCC and the transformer
load tap changer. More specifically this means that it receives information from TR1ATCC or
TR8ATCC and based on this it gives command-pulses to a power transformer motor driven on-load
tap changer and also receives information from the load tap changer regarding tap position, progress
of given commands, and so on.
TCMYLTC and TCLYLTC also serve the purpose of giving information about tap position to the
transformer differential protection T2WPDIF and T3WPDIF.
16.6.1 Identification
SEMOD167845-2 v3
The logic rotating switch for function selection and LHMI presentation (SLGAPC) (or the selector
switch function block) is used to get an enhanced selector switch functionality compared to the one
provided by a hardware selector switch. Hardware selector switches are used extensively by utilities,
in order to have different functions operating on pre-set values. Hardware switches are however
sources for maintenance issues, lower system reliability and an extended purchase portfolio. The
selector switch function eliminates all these problems.
SLGAPC
BLOCK ^P01
PSTO ^P02
UP ^P03
DOWN ^P04
^P05
^P06
^P07
^P08
^P09
^P10
^P11
^P12
^P13
^P14
^P15
^P16
^P17
^P18
^P19
^P20
^P21
^P22
^P23
^P24
^P25
^P26
^P27
^P28
^P29
^P30
^P31
^P32
SWPOSN
IEC14000005-1-en.vsd
IEC14000005 V1 EN-US
16.6.4 Signals
PID-6641-INPUTSIGNALS v3
PID-6641-OUTPUTSIGNALS v3
16.6.5 Settings
PID-6641-SETTINGS v3
Besides the inputs visible in the application configuration in the Application Configuration Tool, there
are other possibilities that will allow an user to set the desired position directly (without activating the
intermediate positions), either locally or remotely, using a “select before execute” dialog. One can
block the function operation, by activating the BLOCK input. In this case, the present position will be
kept and further operation will be blocked. The operator place (local or remote) is specified through
the PSTO input. If any operation is allowed the signal INTONE from the Fixed signal function block
can be connected. SLGAPC function block has also an integer value output, that generates the
actual position number. The positions and the block names are fully settable by the user. These
names will appear in the menu, so the user can see the position names instead of a number.
• if it is used just for the monitoring, the switches will be listed with their actual position names, as
defined by the user (max. 13 characters).
• if it is used for control, the switches will be listed with their actual positions, but only the first
three letters of the name will be used.
In both cases, the switch full name will be shown, but the user has to redefine it when building the
Graphical Display Editor, under the "Caption". If used for the control, the following sequence of
commands will ensure:
Control
Control Sing le Line Diagram
Measurements Comma nds
Events
Disturb ance r eco rds
Settings
Diagno stics
Test
Chang e to the "Switche s" pag e Reset
of the SLD by left-righ t arrows. Authori zation
Sele ct switch by up-down Lan guage
arro ws
../Control/SLD/Switch
O I ../Control/SLD/Switch
Damage control
P: Disc N: Disc Fe
DAL
The pos will not b e mod ified
(outputs will not b e activa ted) unt il OK Cancel
you press the Enter button for O.K.
../Control/SLD/Switch
SMBRREC control
WFM
Pilo t se tup
OFF
Damage control
DFW
IEC06000421-3-en.vsdx
IEC06000421 V3 EN-US
Figure 598: Example 2 on handling the switch from the local HMI.
From the single line diagram on local HMI.
16.7.1 Identification
SEMOD167850-2 v4
The Selector mini switch (VSGAPC) function block is a multipurpose function used for a variety of
applications, as a general purpose switch.
VSGAPC can be controlled from the menu, from a symbol on the single line diagram (SLD) on the
local HMI or from Binary inputs.
VSGAPC
BLOCK BLOCKED
PSTO POSITION
IPOS1 POS1
IPOS2 POS2
CMDPOS12
CMDPOS21
IEC14000066-1-en.vsd
IEC14000066 V1 EN-US
16.7.4 Signals
PID-7478-INPUTSIGNALS v1
PID-7478-OUTPUTSIGNALS v1
16.7.5 Settings
PID-7478-SETTINGS v1
Selector mini switch (VSGAPC) function can be used for double purpose, in the same way as switch
controller (SCSWI) functions are used:
• for indication on the single line diagram (SLD). Position is received through the IPOS1 and
IPOS2 inputs and distributed in the configuration through the POS1 and POS2 outputs, or to
IEC 61850 through reporting, or GOOSE.
• for commands that are received via the local HMI or IEC 61850 and distributed in the
configuration through outputs CMDPOS12 and CMDPOS21.
The output CMDPOS12 is set when the function receives a CLOSE command from the local
HMI when the SLD is displayed and the object is chosen.
The output CMDPOS21 is set when the function receives an OPEN command from the local
HMI when the SLD is displayed and the object is chosen.
It is important for indication in the SLD that a symbol is associated with a controllable
object, otherwise the symbol won't be displayed on the screen. A symbol is created
and configured in GDE tool in PCM600.
The PSTO input is connected to the Local remote switch to have a selection of operators place,
operation from local HMI (Local) or through IEC 61850 (Remote). An INTONE connection from Fixed
signal function block (FXDSIGN) will allow operation from local HMI.
As it can be seen, both indications and commands are done in double-bit representation, where a
combination of signals on both inputs/outputs generate the desired result.
The following table shows the relationship between IPOS1/IPOS2 inputs and the name of the string
that is shown on the SLD. The value of the strings are set in PST.
16.8.1 Identification
GUID-E16EA78F-6DF9-4B37-A92D-5C09827E2297 v3
Generic communication function for Double Point indication (DPGAPC) function block is used to
send double point position indications to other systems, equipment or functions in the substation
through IEC 61850-8-1 or other communication protocols. It is especially intended to be used in the
interlocking station-wide logics.
IEC13000081 V1 EN-US
PID-4139-INPUTSIGNALS v12
PID-4139-OUTPUTSIGNALS v11
The function does not have any parameters available in the local HMI or PCM600.
When receiving the input signals, DPGAPC sends the signals over IEC 61850-8-1 to the systems,
equipment or functions that requests and thus subscribes on these signals. To be able to get the
signals into other systems, equipment or functions, one must use other tools, described in the
Engineering manual, and define which function block in which systems, equipment or functions
should receive this information.
More specifically, DPGAPC function reports a combined double point position indication output
POSITION, by evaluating the value and the timestamp attributes of the inputs OPEN and CLOSE,
together with the logical input signal VALID.
When the input signal VALID is active, the values of the OPEN and CLOSE inputs determine the two-
bit integer value of the output POSITION. The timestamp of the output POSITION will have the latest
updated timestamp of the inputs OPEN and CLOSE.
When the input signal VALID is inactive, DPGAPC function forces the position to intermediated state.
When the value of the input signal VALID changes, the timestamp of the output POSITION will be
updated as the time when DPGAPC function detects the change.
Refer to Table 679 for the description of the input-output relationship in terms of the value and the
quality attributes.
POSITION
VALID OPEN CLOSE
Value Description
0 - - 0 Intermediate
1 0 0 0 Intermediate
1 1 0 1 Open
1 0 1 2 Closed
1 1 1 3 Bad State
16.9.1 Identification
SEMOD176456-2 v3
The Single point generic control 8 signals (SPC8GAPC) function block is a collection of 8 single point
commands that can be used for direct commands for example reset of LEDs or putting IED in
"ChangeLock" state from remote. In this way, simple commands can be sent directly to the IED
outputs, without confirmation. Confirmation (status) of the result of the commands is supposed to be
achieved by other means, such as binary inputs and SPGAPC function blocks. The commands can
be pulsed or steady with a settable pulse time.
SPC8GAPC
BLOCK ^OUT1
PSTO ^OUT2
^OUT3
^OUT4
^OUT5
^OUT6
^OUT7
^OUT8
IEC07000143-3-en.vsd
IEC07000143 V3 EN-US
16.9.4 Signals
PID-3575-INPUTSIGNALS v8
PID-3575-OUTPUTSIGNALS v8
16.9.5 Settings
PID-3575-SETTINGS v8
The PSTO input selects the operator place (LOCAL, REMOTE or ALL). One of the eight outputs is
activated based on the command sent from the operator place selected. The settings Latchedx and
tPulsex (where x is the respective output) will determine if the signal will be pulsed (and how long the
pulse is) or latched (steady). BLOCK will block the operation of the function – in case a command is
sent, no output will be activated.
PSTO is the universal operator place selector for all control functions. Although,
PSTO can be configured to use LOCAL or ALL operator places, only REMOTE
operator place is used in SPC8GAPC function.
16.10.1 Identification
GUID-C3BB63F5-F0E7-4B00-AF0F-917ECF87B016 v4
Automation bits function for DNP3 (AUTOBITS) is used within PCM600 to get into the configuration
of the commands coming through the DNP3 protocol. The AUTOBITS function plays the same role
as functions GOOSEBINRCV (for IEC 61850) and MULTICMDRCV (for LON).
AUTOBITS
BLOCK ^CMDBIT1
PSTO ^CMDBIT2
^CMDBIT3
^CMDBIT4
^CMDBIT5
^CMDBIT6
^CMDBIT7
^CMDBIT8
^CMDBIT9
^CMDBIT10
^CMDBIT11
^CMDBIT12
^CMDBIT13
^CMDBIT14
^CMDBIT15
^CMDBIT16
^CMDBIT17
^CMDBIT18
^CMDBIT19
^CMDBIT20
^CMDBIT21
^CMDBIT22
^CMDBIT23
^CMDBIT24
^CMDBIT25
^CMDBIT26
^CMDBIT27
^CMDBIT28
^CMDBIT29
^CMDBIT30
^CMDBIT31
^CMDBIT32
IEC09000925-1-en.vsd
IEC09000925 V1 EN-US
16.10.4 Signals
PID-3776-INPUTSIGNALS v6
PID-3776-OUTPUTSIGNALS v6
16.10.5 Settings
PID-3776-SETTINGS v6
AutomationBits function (AUTOBITS) has 32 individual outputs which each can be mapped as a
Binary Output point in DNP3. The output is operated by a "Object 12" in DNP3. This object contains
parameters for control-code, count, on-time and off-time. To operate an AUTOBITS output point,
send a control-code of latch-On, latch-Off, pulse-On, pulse-Off, Trip or Close. The remaining
parameters will be regarded were appropriate. ex: pulse-On, on-time=100, off-time=300, count=5
would give 5 positive 100 ms pulses, 300 ms apart.
There is a BLOCK input signal, which will disable the operation of the function, in the same way the
setting Operation: On/Off does. That means that, upon activation of the BLOCK input, all 32
CMDBITxx outputs will be set to 0. The BLOCK acts like an overriding, the function still receives data
from the DNP3 master. Upon deactivation of BLOCK, all the 32 CMDBITxx outputs will be set by the
DNP3 master again, momentarily. For AUTOBITS , the PSTO input determines the operator place.
The command can be written to the block while in “Remote”. If PSTO is in “Local” then no change is
applied to the outputs.
16.11.1 Identification
GUID-2217CCC2-5581-407F-A4BC-266CD6808984 v1
The IEDs can receive commands either from a substation automation system or from the local HMI.
The command function block has outputs that can be used, for example, to control high voltage
apparatuses or for other user defined functionality.
SINGLECMD
BLOCK ^OUT1
^OUT2
^OUT3
^OUT4
^OUT5
^OUT6
^OUT7
^OUT8
^OUT9
^OUT10
^OUT11
^OUT12
^OUT13
^OUT14
^OUT15
^OUT16
IEC05000698-2-en.vsd
IEC05000698 V3 EN-US
16.11.4 Signals
PID-6189-INPUTSIGNALS v7
PID-6189-OUTPUTSIGNALS v7
16.11.5 Settings
PID-6189-SETTINGS v7
Single command, 16 signals (SINGLECMD) function has 16 binary output signals. The outputs can
be individually controlled from a substation automation system or from the local HMI. Each output
signal can be given a name with a maximum of 13 characters in PCM600.
The output signals can be of the types Off, Steady, or Pulse. This configuration setting is done via the
local HMI or PCM600 and is common for the whole function block. The length of the output pulses
are 100 ms. In steady mode, SINGLECMD function has a memory to remember the output values at
power interruption of the IED. Also a BLOCK input is available used to block the updating of the
outputs.
The output signals, OUT1 to OUT16, are available for configuration to built-in functions or via the
configuration logic circuits to the binary outputs of the IED.
17.1.2 Identification
M14854-1 v4
To achieve instantaneous fault clearance for all line faults, scheme communication logic is provided.
All types of communication schemes for permissive underreaching, permissive overreaching,
blocking, delta based blocking, unblocking and intertrip are available.
The built-in communication module (LDCM) can be used for scheme communication signaling when
included.
ZCPSCH
I3P* TRIP
U3P* CS
BLOCK CHSTOP
BLKTR CRL
BLKCS LCG
CSBLK
CACC
CSOR
CSUR
CR
CRG
CBOPEN
IEC09000004
IEC09000004 V4 EN-US
17.1.5 Signals
PID-3766-INPUTSIGNALS v7
PID-3766-OUTPUTSIGNALS v5
17.1.6 Settings
PID-3766-SETTINGS v7
A permissive scheme is inherently faster and has better security against false tripping than a blocking
scheme. On the other hand, a permissive scheme depends on a received signal for a fast trip, so its
dependability is lower than that of a blocking scheme.
The principle of operation for a blocking scheme is that an overreaching zone is allowed to trip
instantaneously after the settable co-ordination time tCoord has elapsed, when no signal is received
from the remote IED.
The received signal, which shall be connected to CR, is used to block the zone to be accelerated to
clear the fault instantaneously (after time tCoord). The forward overreaching zone to be accelerated
is connected to the input CACC, see figure 605.
In case of external faults, the blocking signal (CR) must be received before the settable timer tCoord
elapses to prevent a false trip, see figure 605.
The function can be totally blocked by activating the input BLOCK. Tripping can be blocked by
activating the input BLKTR. Signal send can be blocked by activating the input BLKCS.
tCoord
CACC
t TRIP
CR AND
en05000512.vsd
IEC05000512 V1 EN-US
In order to avoid delays due to carrier coordination times, the initiation of sending of blocking signal
to remote end is done by a fault inception detection element based on delta quantities of currents
and voltages. The delta based fault detection is very fast and if the channel is fast there is no need
for delaying the operation of the remote distance element. The received blocking signal arrives well
before the distance element has started. If the fault is in forward direction the sending is immediately
stopped by a forward directed distance, directional current or directional earth fault element.
The fault inception detection element detects instantaneous changes in any phase currents or zero
sequence current in combination with a change in the corresponding phase voltage or zero sequence
voltage. The criterion for the fault inception detection is if the change of any phase voltage and
current exceeds the settings DeltaU and DeltaI respectively, or if the change of zero sequence
voltage and zero sequence current exceeds the settings Delta3U0,Delta3I0 respectively. The
schemeType is selected as DeltaBlocking.
If the fault inception function has detected a system fault, a block signal CS will be issued and sent to
remote end in order to block the overreaching zones. Different criteria has to be fulfilled for sending
the CS signal:
1. The breaker has to be in closed condition, that is, the input signal CBOPEN is deactivated.
2. A fault inception should have been detected while the carrier send signal is not blocked, that is,
the input signal BLKCS is not activated.
If it is later detected that it was an internal fault that made the function issue the CS signal, the
function will issue a CHSTOP signal to unblock the remote end.
The received signal, which is connected to the CR input, is not used to accelerate the release of the
overreaching zone to clear the fault instantaneously. The overreaching zone to be accelerated is
connected to the input CACC, see Figure 606.
In case of external faults, the blocking signal (CR) must be received before the settable timer tCoord
elapses, to prevent a false trip, see Figure 606.
The function can be totally blocked by activating the input BLOCK, block of trip by activating the input
BLKTR, block of carrier send by activating the input BLKCS.
tCoord
CACC
t TRIP
CR AND
en05000512.vsd
IEC05000512 V1 EN-US
Figure 606: Basic logic for trip signal in delta blocking scheme
Channels for communication in each direction must be available.
The logic for trip signal in permissive scheme is shown in figure 607.
tCoord
CACC
t TRIP
CR AND
en05000513.vsd
IEC05000513 V1 EN-US
The logic for trip signal in permissive scheme is shown in figure 607.
tCoord
CACC
t TRIP
CR AND
en05000513.vsd
IEC05000513 V1 EN-US
In unblocking scheme, the lower dependability of a permissive scheme is overcome by using the loss
of guard signal from the communication equipment to locally create a receive signal. It is common or
suitable to use the function when older, less reliable power-line carrier (PLC) communication is used.
The unblocking function uses a guard signal CRG, which must always be present, even when no CR
signal is received. The absence of the CRG signal for a time longer than the setting tSecurity time is
used as a CR signal, see figure 609. This enables a permissive scheme to operate when the line
fault blocks the signal transmission. The CRG signal is only used in unblocking schemes.
The received signal created by the unblocking function is reset 150 ms after the security timer has
elapsed. When that occurs an output signal LCG is activated for signalling purpose. The unblocking
function is reset 200 ms after that the guard signal is present again.
CR
tSecurity CRL
t OR
CRG
200 ms 150 ms
t OR t AND
AND
LCG
IEC05000746-2-en.vsd
IEC05000746 V2 EN-US
Figure 609: Guard signal logic with unblocking scheme and with setting Unblock = Restart
CR
CRL
tSecurity OR
CRG t
IEC11000253-2-en.vsd
IEC11000253 V2 EN-US
Figure 610: Guard signal logic with unblocking scheme and with setting Unblock = NoRestart
The unblocking function can be set in three operation modes (setting Unblock):
In the direct intertrip scheme, the send signal CS is sent from an underreaching zone that is tripping
the line.
The received signal CR is directly transferred to a trip for tripping without local criteria. The signal is
further processed in the tripping logic.
The simplified logic diagram for the complete logic is shown in figure 611.
Unblock =Off
CR
Unblock =
OR CRL
NoRestart AND
CRL
Unblock =
tSecurit
Restart
y
CRG 1 t AND
SchemeType =
Intertrip
CSUR
tSendMi
n AND
OR
BLOCK AND
CSBLK OR
CRL
Schemetype =
Permissive UR AND CS
OR
tCoord
AND 25 ms
OR
t TRIP
CACC t
Schemetype =
Permissive OR
CSOR OR AND
AND
tSendMin
OR
AND
SchemeType =
Blocking
BLKCS
AND
IEC05000515-3-en.vsdx
IEC05000515 V3 EN-US
Figure 611: Scheme communication logic for distance or overcurrent protection, simplified logic
diagram
17.2.2 Identification
SEMOD141699-2 v3
Communication between line ends is used to achieve fault clearance for all faults on a power line. All
possible types of communication schemes for example, permissive underreach, permissive
overreach and blocking schemes are available. To manage problems with simultaneous faults on
parallel power lines phase segregated communication is needed. This will then replace the standard
Scheme communication logic for distance or Overcurrent protection (ZCPSCH) on important lines
where three communication channels (in each subsystem) are available for the distance protection
communication.
The main purpose of the Phase segregated scheme communication logic for distance protection
(ZPCPSCH) function is to supplement the distance protection function such that:
• fast clearance of faults is also achieved at the line end for which the faults are on the part of the
line not covered by its underreaching zone.
• correct phase selection can be maintained to support single-pole tripping for faults occurring
anywhere on the entire length of a double circuit line.
To accomplish this, three separate communication channels, that is, one per phase, each capable of
transmitting a signal in each direction is required.
ZPCPSCH can be completed with the current reversal and WEI logic for phase segregated
communication, when found necessary in Blocking and Permissive overreaching schemes.
ZPCPSCH
BLOCK TRIP
BLKTR TRL1
BLKTRL1 TRL2
BLKTRL2 TRL3
BLKTRL3 CSL1
CACCL1 CSL2
CACCL2 CSL3
CACCL3 CSMPH
CSURL1 CRLL1
CSURL2 CRLL2
CSURL3 CRLL3
CSORL1
CSORL2
CSORL3
CSBLKL1
CSBLKL2
CSBLKL3
BLKCSL1
BLKCSL2
BLKCSL3
CRL1
CRL2
CRL3
CRMPH
IEC06000427 V3 EN-US
17.2.5 Signals
PID-7669-INPUTSIGNALS v1
PID-7669-OUTPUTSIGNALS v1
17.2.6 Settings
PID-7669-SETTINGS v1
A permissive scheme is inherently faster and has better security against false tripping than a blocking
scheme. On the other hand, a permissive scheme depends on a received signal for a fast trip, so its
dependability is lower than that of a blocking scheme.
The Phase segregated scheme communication logic for distance protection (ZPCPSCH) function is a
logical function built-up from logical elements. It is a supplementary function to the distance
protection, requiring for its operation inputs from the distance protection and the communication
equipment.
The type of communication-aided scheme to be used can be selected by way of the settings.
The ability to select which distance protection zone is assigned to which input of ZPCPSCH makes
this logic able to support practically any scheme communication requirements regardless of their
basic operating principle. The outputs to initiate tripping and sending of the teleprotection signal are
given in accordance with the type of communication-aided scheme selected and the zone(s) and
phase(s) of the distance protection which have operated.
When power line carrier communication channels are used for permissive schemes communication,
unblocking logic which uses the loss of guard signal as a receive criteria is provided. This logic
compensates for the lack of dependability due to the transmission of the command signal over the
faulted line.
The principle of operation for a blocking scheme is that an overreaching zone is allowed to trip
instantaneously after the settable co-ordination time tCoord has elapsed, when no signal is received
from the remote IED. The received signal (sent by a reverse looking element in the remote IED),
which shall be connected to CRLx, is used to not release the zone to be accelerated to clear the fault
instantaneously (after time tCoord). The overreaching zone to be accelerated is connected to the
input CACCLx, see figure 613. In case of external faults, the blocking signal (CRLx) must be received
before the settable timer tCoord elapses, to prevent an unneccesary trip, see figure 613.
ZPCPSCH can be totally blocked by activating the input BLOCK, block of trip is achieved by
activating the input BLKTRLx, Block of carrier send is done by activating the input BLKCSLx.
tCoord 25 ms
CACCLx
t t TRLx
CRLx AND
IEC06000310_2_en.vsd
IEC06000310 V2 EN-US
Figure 613: Basic logic for trip carrier in one phase of a blocking scheme
tCoord 25 ms
CACCLx t t TRLx
CRLx AND
IEC07000088_2_en.vsd
IEC07000088 V2 EN-US
Figure 614: Basic logic for trip carrier in one phase of a permissive underreach scheme
The permissive overreach scheme has the same blocking possibilities as mentioned for blocking
scheme above. The blocking inputs are activated from the current reversal logic when this function is
included.
In an unblocking scheme, the lower dependability in permissive scheme is overcome by using the
loss of guard signal from the communication equipment to locally create a carrier receive signal. It is
common or suitable to use the function when older, less reliable, power-line carrier (PLC)
communication is used. As phase segregated communication schemes uses phases individually and
the PLC is typically connected single-phase or phase-to-phase it is not possible to evaluate which of
the phases to release and the unblocking scheme has thus not been supported.
In the direct intertrip scheme, the carrier send signal CS is sent from an underreaching zone that is
tripping the line.
The received signal per phase is directly transferred to the trip function block for tripping without local
criteria. The signal is not further processed in the phase segregated communication logic. In case of
single-pole tripping the phase selection and logic for tripping the three phases is performed in the trip
function block.
The simplified logic diagram for one phase is shown in figure 615.
SchemeType =
Intertrip
CSURLx
tSendMin AND
OR
BLOCK
AND
CSBLKLx OR
CRLx
Scheme Type =
Permissive UR AND CSLx
OR
tCoord
25 ms
AND t TRLx
OR t
CACCLx
Scheme Type =
Permissive OR
CSORLx OR AND
AND
tSendMin
OR
AND
Scheme Type =
Blocking
BLKCSx
AND
CSL1
CSL2 AND
CSL2
OR CSMPH
CSL3 AND
CSL3
CSL1 AND
CSL1
CSL2 GENERAL
OR
CSL3
IEC06000311_2_en.vsd
IEC06000311 V2 EN-US
17.3.2 Identification
M15073-1 v5
The ZCRWPSCH function provides the current reversal and weak end infeed logic functions that
supplement the standard scheme communication logic. It is not suitable for standalone use as it
requires inputs from the distance protection functions and the scheme communications function
included within the terminal.
On detection of a current reversal, the current reversal logic provides an output to block the sending
of the teleprotection signal to the remote end, and to block the permissive tripping at the local end.
This blocking condition is maintained long enough to ensure that no unwanted operation will occur as
a result of the current reversal.
On verification of a weak end infeed condition, the weak end infeed logic provides an output for
sending the received teleprotection signal back to the remote sending end and other output(s) for
local tripping. For terminals equipped for single- and two-pole tripping, outputs for the faulted
phase(s) are provided. Undervoltage detectors are used to detect the faulted phase(s).
ZCRWPSCH
U3P* IRVL
BLOCK TRWEI
IRVBLK TRWEIL1
IRV TRWEIL2
WEIBLK1 TRWEIL3
WEIBLK2 ECHO
VTSZ
CBOPEN
CRL
IEC06000287-2-en.vsd
IEC06000287 V2 EN-US
17.3.5 Signals
PID-3521-INPUTSIGNALS v8
PID-3521-OUTPUTSIGNALS v8
17.3.6 Settings
PID-3521-SETTINGS v8
The current reversal logic can be enabled by setting the parameter CurrRev = On. The current
reversal logic uses a reverse zone connected to the input IRV to recognize the fault on the parallel
line in any of the phases.When the reverse zone has been activated (even if only for a short time), it
prevents sending of a communication signal and tripping through the scheme communication logic
after a settable time tPickUpRev. The prevention will last for tPickUpRev + 10 ms + tDelayRev after
the IREV reset. This makes it possible for the receive signal to reset before the carrier-aided trip
signal is activated due to the current reversal by the forward directed zone. The logic diagram for
current reversal is shown in Figure 617.
BLOCK
IRVBLK
tDelayRev
tPickUpRev 10 ms tPickUpRev IRVL
IRV AND t
t t t
CurrRev = On
IEC05000122-4-en.vsd
IEC05000122 V4 EN-US
The function has an internal 10 ms drop-off timer which will secure that the current reversal logic will
be activated for short input signals even if the pick-up timer is set to zero.
The weak-end infeed logic (WEI) function sends back (echoes) the received signal under the
condition that no fault has been detected on the weak-end by different fault detection elements
(distance protection in forward or reverse direction).
The WEI function returns the received signal, shown in Figure 618, when:
• The setting parameter WEI is set to either Echo or Echo & Trip.
• No active signal is present on the input BLOCK.
• The functional input CRL is active for a time longer than the tPickUpWei setting. This input is
usually connected to the CRL output on the scheme communication logic ZCPSCH.
• The WEI function is not blocked by the active signal connected to the WEIBLK1 functional input
or to the VTSZ functional input. The later is usually configured to the VTSZ functional output of
the fuse-failure function.
• No active signal has been present for at least 200 ms on the WEIBLK2 functional input. An OR
combination of all fault detection functions (not undervoltage) as present within the IED is
usually used for this purpose.
• The weak-end infeed logic also echoes the received permissive signal when local breaker
opens.
BLOCK
VTSZ
WEIBLK1 OR
tPickUpWEI
CRL AND 50 ms 200 ms
t AND
OR t t
ECHO
200 ms AND
WEIBLK2
t
AND
OR
1500 ms
CBOPEN
t
WEI = Echo
IEC05000123-3-en.vsd
IEC05000123 V3 EN-US
Figure 618: Simplified logic diagram for weak-end infeed logic — Echo
When an echo function is used in both IEDs (should generally be avoided), a spurious signal can be
looped round by the echo logics. To avoid a continuous lock-up of the system, the duration of the
echoed signal is limited to 200 ms.
An undervoltage criteria is used as an additional tripping criteria, when the tripping of the local
breaker is selected, setting WEI = Echo&Trip. With this setting the Echo and Trip are working in
parallel as in logic shown in Figure 619.
BLOCK
VTSZ
WEIBLK1 OR
tPickUpWEI
CRL AND 50 ms 200 ms
t AND ECHO
OR t t AND
200 ms
WEIBLK2
t
AND
1500 ms
OR
CBOPEN
t
AND
U3P*
UL1<UPN<
UL2 < UPN<
UL3 < UPN<
UPN< 100 ms
OR
AND t
TRWEI
OR
15 ms
TRWEIL1
U3P*
AND t
UL1L2 <UPP< OR
UL2L3 < UPP<
UL3L1 < UPP<
15 ms
UPP< TRWEIL2
AND t
OR
15 ms
OR TRWEIL3
AND t
Figure 619: Simplified logic diagram for weak-end infeed logic — Echo&Trip
17.4.2 Identification
SEMOD156467-2 v3
Current reversal and weak-end infeed logic for phase segregated communication (ZPCWPSCH)
function is used to prevent unwanted operations due to current reversal when using permissive
overreach protection schemes in application with parallel lines where the overreach from the two
ends overlaps on the parallel line.
The weak-end infeed logic is used in cases where the apparent power behind the protection can be
too low to activate the distance protection function. When activated, received carrier signal together
with local undervoltage criteria and no reverse zone operation gives an instantaneous trip. The
received signal is also echoed back to accelerate the sending end.
ZPCWPSCH
U3P* TRPWEI
BLOCK TRPWEIL1
BLKZ TRPWEIL2
CBOPEN TRPWEIL3
CR IRVOP
CRL1 IRVOPL1
CRL2 IRVOPL2
CRL3 IRVOPL3
IRVL1 ECHO
IRVL2 ECHOL1
IRVL3 ECHOL2
IRVBLKL1 ECHOL3
IRVBLKL2
IRVBLKL3
WEIBLK
WEIBLKL1
WEIBLKL2
WEIBLKL3
WEIBLKOP
WEIBLKO1
WEIBLKO2
WEIBLKO3
IEC06000477 V3 EN-US
17.4.5 Signals
PID-7876-INPUTSIGNALS v1
PID-7876-OUTPUTSIGNALS v1
17.4.6 Settings
PID-7876-SETTINGS v1
The current reversal logic can be enabled by setting the parameter OperCurrRev = On. The current
reversal logic uses a reverse zone connected to the input IRVLx to recognize the fault on the parallel
line in any of the phases. When the reverse zone has been activated (even if only for a short time), it
prevents sending of a communication signal and tripping through the scheme communication logic
after a settable time tPickUpRev. The prevention will last for tPickUpRev + 10 ms + tDelayRev after
the IRVLx reset. This makes it possible for the receive signal to reset before the trip signal is
activated due to the current reversal by the forward directed zone. The logic diagram for current
reversal is shown in Figure 621.
BLOCK
IRVBLKLx
tDelayRev
tPickUpRev 10 ms tPickUpRev IRVOPLx
IRVLx & t
t t t
operCurrRev=On
IEC06000474-3-en.vsd
IEC06000474 V3 EN-US
The Current reversal and weak-end infeed logic for phase segregated communication (ZPCWPSCH)
function has an internal 10 ms drop-off timer which secure that the current reversal logic will be
activated for short input signals even if the pickup timer is set to zero.
The WEI function sends back (echoes) the received carrier signal under the condition that no fault
has been detected at the weak end by different fault detection elements (distance protection in
forward and reverse direction).
BLOCK
BLKZ
WEIBLKLx 1 ECHOLx-contd
&
tPickUpWEI
CRLx & 50 ms 200 ms
t &
1 t t
ECHOLx
200 ms &
WEIBLKOx
t
&
1
1500 ms
CBOPEN
t
OperationWEI=Echo
IEC07000085-3-en.vsd
IEC07000085 V3 EN-US
When an echo function is used in both the IEDs on the protected line (should generally be avoided),
a spurious signal can be looped round by the echo logics. To avoid a continuous lock-up of the
system, the duration of the echoed signal is limited to 200 ms.
An undervoltage criteria is used as an additional tripping criteria when the tripping of the local
breaker is selected. Setting OperationWEI = Echo &Trip together with the WEI function and ECHOLx,
trip signal TRPWEIx has been issued by the echo and trip logic which is described in Figure 623.
ECHOLx- contd
CBOPEN
U3P*
100 ms
=1
& t
Undervoltage TRPWEI
detection =1
UPE<
15 ms
UPP< TRPWEI1
& t
15 ms
TRPWEI2
& t
15 ms
TRPWEI3
& t
IEC13000278-1-en.vsd
IEC13000278 V1 EN-US
Figure 623: Simplified logic diagram for weak-end infeed logic – Echo & Trip
Start signals can be connected to WEIBLKLx and WEIBLKOx via OR gate to achieve the blocking of
echo signal in case if the faults are detected by local protection functions and thereby, avoiding the
operation from the remote end. By this, 3-pole operation can be accomplished in addition to 1-pole
and 2-pole operations by ZPCWPSCH function. Also, if a 3-pole operation needs to be achieved by a
separate protection function, current reversal and weak-end infeed logic for distance protection 3-
phase ZCRWPSCH function can be used. Figure 624 and Figure 625 shows the connection of start
signals from ZMFCPDIS function to WEIBLKLx and WEIBLKOx in ACT configuration to block echo
signal.
ZMFCPDIS(21;Z<)
I3P I3P TRIP
U3P U3P TRZ1
INP TRL1Z1
BLOCK TRL2Z1
VTSZ TRL3Z1
BLKZ1 TRZ2
BLKZ2 TRL1Z2
BLKZ3 TRL2Z2
BLKZ4 TRL3Z2
BLKZ5 TRZ3
BLKZRV TRZ4
BLKZBU TRZ5 ZPCWPSCH(85)
BLKTRZ1 TRZRV
BLKTRZ2 TRZBU U3P U3P TRPWEI
BLKTRZ3 START ZMFCPDIS_START BLOCK TRPWEIL1
BLKTRZ4 STZ1 OR BLKZ TRPWEIL2
BLKTRZ5 STNDZ1 CBOPEN TRPWEIL3
BLKTRZRV STZ2 ZMFCPDIS_START INPUT1 OUT CR IRVOP
BLKTRZBU STL1Z2 ZMFCPDIS_STFWL1 INPUT2 NOUT CRL1 IRVOPL1
BLKTD STL2Z2 O:2403|T:3|I:26 CRL2 IRVOPL2
EXTNST STL3Z2 CRL3 IRVOPL3
ORCND STNDZ2 IRVL1 ECHO ZPCWPSCH_ECHO
RELCNDZ1 STZ3 IRVL2 ECHOL1 ZPCWPSCH_ECHOL1
RELCNDZ2 STNDZ3 IRVL3 ECHOL2 ZPCWPSCH_ECHOL2
RELCNDZ3 STZ4 IRVBLKL1 ECHOL3 ZPCWPSCH_ECHOL3
RELCNDZ4 STNDZ4 IRVBLKL2
RELCNDZ5 STZ5 IRVBLKL3
RELCNDZRV STNDZ5 OR WEIBLK
RELCNDZBU STZRV WEIBLKL1
STL1ZRV ZMFCPDIS_START INPUT1 OUT WEIBLKL2
STL2ZRV ZMFCPDIS_STFWL2 INPUT2 NOUT WEIBLKL3
STL3ZRV O:2400|T:3|I:25 WEIBLKOP
STNDZRV WEIBLKO1
STZBU WEIBLKO2
STNDZBU WEIBLKO3
STND O:3815|T:3|I:1
STNDL1
STNDL2
STNDL3 OR
STNDPE
STFWL1 ZMFCPDIS_STFWL1 ZMFCPDIS_START INPUT1 OUT
STFWL2 ZMFCPDIS_STFWL2 ZMFCPDIS_STFWL3 INPUT2 NOUT
STFWL3 ZMFCPDIS_STFWL3 O:2406|T:3|I:27
STFWPE
STRVL1
STRVL2
STRVL3
STRVPE
STFW1PH
STFW2PH
STFW3PH
STPE
STPP
STTDFWL1
STTDFWL2
STTDFWL3
STTDRVL1
STTDRVL2
STTDRVL3
O:2095|T:3|I:1
IEC18000012 V2 EN-US
ZMFCPDIS(21;Z<)
I3P I3P TRIP
U3P U3P TRZ1
INP TRL1Z1
BLOCK TRL2Z1
VTSZ TRL3Z1
BLKZ1 TRZ2
BLKZ2 TRL1Z2
BLKZ3 TRL2Z2
BLKZ4 TRL3Z2
BLKZ5 TRZ3
BLKZRV TRZ4 ZPCWPSCH(85)
BLKZBU TRZ5
BLKTRZ1 TRZRV U3P U3P TRPWEI
BLKTRZ2 TRZBU BLOCK TRPWEIL1
BLKTRZ3 START ZMFCPDIS_START BLKZ TRPWEIL2
BLKTRZ4 STZ1 CBOPEN TRPWEIL3
BLKTRZ5 STNDZ1 CR IRVOP
BLKTRZRV STZ2 CRL1 IRVOPL1
BLKTRZBU STL1Z2 CRL2 IRVOPL2
BLKTD STL2Z2 OR CRL3 IRVOPL3
EXTNST STL3Z2 IRVL1 ECHO ZPCWPSCH_ECHO
ORCND STNDZ2 ZMFCPDIS_START INPUT1 OUT IRVL2 ECHOL1 ZPCWPSCH_ECHOL1
RELCNDZ1 STZ3 ZMFCPDIS_STFWL1 INPUT2 NOUT IRVL3 ECHOL2 ZPCWPSCH_ECHOL2
RELCNDZ2 STNDZ3 O:3000|T:3|I:29 IRVBLKL1 ECHOL3 ZPCWPSCH_ECHOL3
RELCNDZ3 STZ4 IRVBLKL2
RELCNDZ4 STNDZ4 IRVBLKL3
RELCNDZ5 STZ5 WEIBLK
RELCNDZRV STNDZ5 WEIBLKL1
RELCNDZBU STZRV WEIBLKL2
STL1ZRV WEIBLKL3
STL2ZRV OR WEIBLKOP
STL3ZRV WEIBLKO1
STNDZRV ZMFCPDIS_START INPUT1 OUT WEIBLKO2
STZBU ZMFCPDIS_STFWL2 INPUT2 NOUT WEIBLKO3
STNDZBU O:3003|T:3|I:30 O:3816|T:3|I:2
STND
STNDL1
STNDL2
STNDL3
STNDPE
STFWL1 ZMFCPDIS_STFWL1
STFWL2 ZMFCPDIS_STFWL2 OR
STFWL3 ZMFCPDIS_STFWL3
STFWPE ZMFCPDIS_START INPUT1 OUT
STRVL1 ZMFCPDIS_STFWL3 INPUT2 NOUT
STRVL2 O:3006|T:3|I:31
STRVL3
STRVPE
STFW1PH
STFW2PH
STFW3PH
STPE
STPP
STTDFWL1
STTDFWL2
STTDFWL3
STTDRVL1
STTDRVL2
STTDRVL3
O:2095|T:3|I:1
IEC18000013 V2 EN-US
17.5.2 Identification
M14882-1 v2
To achieve fast fault clearance of earth faults on the part of the line not covered by the instantaneous
step of the residual overcurrent protection, the directional residual overcurrent protection can be
supported with a logic that uses communication channels.
In the directional scheme, information of the fault current direction must be transmitted to the other
line end. With directional comparison, a short operate time of the protection including a channel
transmission time, can be achieved. This short operate time enables rapid autoreclosing function
after the fault clearance.
The communication logic module for directional residual current protection enables blocking as well
as permissive under/overreaching, and unblocking schemes. The logic can also be supported by
additional logic for weak-end infeed and current reversal, included in Current reversal and weak-end
infeed logic for residual overcurrent protection (ECRWPSCH) function.
ECPSCH
BLOCK TRIP
BLKTR CS
BLKCS CRL
CSBLK LCG
CACC
CSOR
CSUR
CR
CRG
IEC06000288-2-en.vsd
IEC06000288 V2 EN-US
17.5.5 Signals
PID-3581-INPUTSIGNALS v7
PID-3581-OUTPUTSIGNALS v6
17.5.6 Settings
PID-3581-SETTINGS v6
• Input signal CACC is used for tripping of the communication scheme, normally the start signal of
a forward overreaching step of STFW.
• Input signal CSBLK is used for sending block signal in the blocking communication scheme,
normally the start signal of a reverse overreaching step of STRV.
• Input signal CSUR is used for sending permissive signal in the underreaching permissive
communication scheme, normally the start signal of a forward underreaching step of STINn,
where n corresponds to the underreaching step.
• Input signal CSOR is used for sending permissive signal in the overreaching permissive
communication scheme, normally the start signal of a forward overreaching step of STINn,
where n corresponds to the overreaching step.
In addition to this a signal from the autoreclosing function should be configured to the BLKCS input
for blocking of the function at a single phase reclosing cycle.
In the blocking scheme a signal is sent to the other line end if the directional element detects an
earth fault in the reverse direction. When the forward directional element operates, it trips after a
short time delay if no blocking signal is received from the opposite line end. The time delay, normally
30 – 40 ms, depends on the communication transmission time and a chosen safety margin.
One advantage of the blocking scheme is that only one channel (carrier frequency) is needed if the
ratio of source impedances at both end is approximately equal for zero and positive sequence source
impedances, the channel can be shared with the impedance measuring system, if that system also
works in the blocking mode. The communication signal is transmitted on a healthy line and no signal
attenuation will occur due to the fault.
Blocking schemes are particular favorable for three-terminal applications if there is no zero-sequence
outfeed from the tapping. The blocking scheme is immune to current reversals because the received
signal is maintained long enough to avoid unwanted operation due to current reversal. There is never
any need for weak-end infeed logic, because the strong end trips for an internal fault when no
blocking signal is received from the weak end. The fault clearing time is however generally longer for
a blocking scheme than for a permissive scheme.
If the fault is on the line, the forward direction measuring element operates. If no blocking signal
comes from the other line end via the CR binary input (received signal) the TRIP output is activated
after the tCoord set time delay.
IEC05000448 V1 EN-US
In the permissive scheme the forward directed earth-fault measuring element sends a permissive
signal to the other end, if an earth fault is detected in the forward direction. The directional element at
the other line end must wait for a permissive signal before activating a trip signal. Independent
channels must be available for the communication in each direction.
An impedance measuring IED, which works in the same type of permissive mode, with one channel
in each direction, can share the channels with the communication scheme for residual overcurrent
protection. If the impedance measuring IED works in the permissive overreaching mode, common
channels can be used in single line applications. In case of double lines connected to a common bus
at both ends, use common channels only if the ratio Z1S/Z0S (positive through zero-sequence source
impedance) is about equal at both ends. If the ratio is different, the impedance measuring and the
directional earth-fault current system of the healthy line may detect a fault in different directions,
which could result in unwanted tripping.
Common channels cannot be used when the weak-end infeed function is used in the distance or
earth-fault protection.
In case of an internal earth-fault, the forward directed measuring element operates and sends a
permissive signal to the remote end via the CS output (sent signal). Local tripping is permitted when
the forward direction measuring element operates and a permissive signal is received via the CR
binary input (received signal).
The permissive scheme can be of either underreaching or overreaching type. In the underreaching
alternative, an underreaching directional residual overcurrent measurement element will be used as
sending criterion of the permissive input signal CSUR.
BLOCK
CRL
CR AND
25 ms
t TRIP
0 - 60 s
AND
BLKCS OR CS
AND
Overreach
CSOR AND 25 ms
CSUR OR t
IEC05000280.vsd
IEC05000280 V4 EN-US
In unblocking scheme, the lower dependability in permissive scheme is overcome by using the loss
of guard signal from the communication equipment to locally create a receive signal. It is common or
suitable to use the function when older, less reliable, power line carrier (PLC) communication is used.
The unblocking function uses a guard signal CRG, which must always be present, even when no CR
signal is received. The absence of the CRG signal for a time longer than the setting tSecurity time is
used as a CR signal, see figure 628. This also enables a permissive scheme to operate when the
line fault blocks the signal transmission.
The received signal created by the unblocking function is reset 150 ms after the security timer has
elapsed. When that occurs an output signal LCG is activated for signaling purpose. The unblocking
function is reset 200 ms after that the guard signal is present again.
CR
tSecurity CRL
t OR
CRG
200 ms 150 ms
t OR t AND
AND
LCG
IEC05000746-2-en.vsd
IEC05000746 V2 EN-US
17.6.1 Identification
M14883-1 v2
17.6.2 Functionality
M13928-3 v8
The Current reversal and weak-end infeed logic for residual overcurrent protection (ECRWPSCH) is
a supplement to Scheme communication logic for residual overcurrent protection ECPSCH.
To achieve fast fault clearing for all earth faults on the line, the directional earth fault protection
function can be supported with logic that uses tele-protection channels.
This is why the IEDs have available additions to the scheme communication logic.
M13928-6 v2
If parallel lines are connected to common busbars at both terminals, overreaching permissive
communication schemes can trip unselectively due to fault current reversal. This unwanted tripping
affects the healthy line when a fault is cleared on the other line. This lack of security can result in a
total loss of interconnection between the two buses. To avoid this type of disturbance, a fault current
reversal logic (transient blocking logic) can be used.
M13928-8 v5
Permissive communication schemes for residual overcurrent protection can basically operate only
when the protection in the remote IED can detect the fault. The detection requires a sufficient
minimum residual fault current, out from this IED. The fault current can be too low due to an opened
breaker or high-positive and/or zero-sequence source impedance behind this IED. To overcome
these conditions, weak-end infeed (WEI) echo logic is used. The weak-end infeed echo is limited to
200 ms to avoid channel lockup.
ECRWPSCH
U3P* IRVL
BLOCK TRWEI
IRVBLK ECHO
IRV
WEIBLK1
WEIBLK2
VTSZ
CBOPEN
CRL
IEC06000289-3-en.vsd
IEC06000289 V3 EN-US
17.6.4 Signals
PID-3522-INPUTSIGNALS v9
PID-3522-OUTPUTSIGNALS v8
17.6.5 Settings
PID-3522-SETTINGS v9
The directional comparison function contains logic for blocking overreaching and permissive
overreaching schemes.
The circuits for the permissive overreaching scheme contain logic for current reversal and weak-end
infeed functions. These functions are not required for the blocking overreaching scheme.
Use the independent or inverse time functions in the directional earth fault protection module to get
backup tripping in case the communication equipment malfunctions and prevents operation of the
directional comparison logic.
Connect the necessary signal from the autorecloser for blocking of the directional comparison
scheme, during a single-phase autoreclosing cycle, to the BLOCK input of the directional comparison
module.
The fault current reversal logic uses a reverse directed element, connected to the input signal IRV,
which recognizes that the fault is in reverse direction. When the reverse direction element is
activated the output signal IRVL is activated which is shown in Figure 630. The logic is now ready to
handle a current reversal without tripping. The output signal IRVL will be connected to the block input
on the permissive overreaching scheme.
When the fault current is reversed on the healthy line, IRV is deactivated and IRVBLK is activated.
The tDelayRev timer delays the reset of the output signal. The signal blocks operation of the
overreach permissive scheme for residual current and thus prevents unwanted operation caused by
fault current reversal.
BLOCK
IRVBLK
tDelayRev
tPickUpRev 10 ms tPickUpRev AND t
IRVL
IRV
t t t
CurrRev = On
IEC09000031-4-en.vsd
IEC09000031 V4 EN-US
The weak-end infeed function can be set to send only an echo signal (WEI=Echo) or an echo signal
and a trip signal (WEI=Echo & Trip). The corresponding logic diagrams are depicted in Figure 631
and Figure 632.
The weak-end infeed logic uses normally a reverse and a forward direction element, connected to
WEIBLK2 via an OR-gate. If neither the forward nor the reverse directional measuring element is
activated during the last 200 ms, the weak-end infeed logic echoes back the received permissive
signal as shown in Figure 631 and Figure 632. The weak-end infeed logic also echoes the received
permissive signal when CBOPEN is high (local breaker opens) prior to faults appeared at the end of
line.
If the forward or the reverse directional measuring element is activated during the last 200 ms, the
fault current is sufficient for the IED to detect the fault with the earth fault function that is in operation.
CR
BLOCK AND
VTSZ
OR
tPickUpWEI
WEIBLK1
t AND 50 ms 200 ms
AND
OR t t ECHO
200 ms AND
CRL t
WEIBLK2
AND
1500 ms
CBOPEN OR
t
WEI = Echo
IEC09000032-6-en.vsd
IEC09000032 V6 EN-US
Figure 631: Simplified logic diagram for weak-end infeed logic - Echo
With the WEI= Echo & Trip setting, the logic sends an echo according to the diagram above. Further,
it activates the TRWEI signal to trip the breaker if the echo conditions are fulfilled and the neutral
point voltage is above the set operate value for 3U0> .
The voltage signal that is used to calculate the zero sequence voltage is set in the earth fault function
which is in operation.
BLOCK
VTSZ
OR
tPickUpWEI
WEIBLK1 t AND 50 ms 200 ms
AND
OR t t ECHO
200 ms AND
t
CRL
AND
WEIBLK2 1500 ms
OR
t
CBOPEN
AND
ST3U0
15 ms TRWEI
a>b AND
3U0> t
WEI = Echo&Trip
IEC09000020-6-en.vsd
IEC09000020 V6 EN-US
Figure 632: Simplified logic diagram for weak-end infeed logic - Echo & Trip
The weak-end infeed echo sent to the strong line end has a maximum duration of 200 ms. When this
time period has elapsed, the conditions that enable the echo signal to be sent are set to zero for a
time period of 50 ms. This avoids ringing action if the weak-end echo is selected for both line ends.
Operate time for current reversal (0.000-60.000) s ±0.2% or ±30 ms whichever is greater
logic
Delay time for current reversal (0.000-60.000) s ±0.2% or ±30 ms whichever is greater
Coordination time for weak-end (0.000–60.000) s ±0.2% or ±30 ms whichever is greater
infeed logic
Section 18 Logic
18.1 Tripping logic SMPPTRC IP14576-1 v4
18.1.2 Identification
SEMOD56226-2 v7
A function block for protection tripping and general start indication is always provided as a basic
function for each circuit breaker. It provides a settable pulse prolongation time to ensure a trip pulse
of sufficient length, as well as all functionality necessary for correct co-operation with autoreclosing
functions.
The trip function block includes a settable latch function for the trip signal and circuit breaker lockout.
The trip function can collect start and directional signals from different application functions. The
aggregated start and directional signals are mapped to the IEC 61850 logical node data model.
SMPPTRC
BLOCK TRIP
BLKLKOUT TRL1
TRINALL TRL2
TRINL1 TRL3
TRINL2 TRN
TRINL3 TR1P
TRINN TR2P
PSL1 TR3P
PSL2 CLLKOUT
PSL3 START
1PTRZ STL1
1PTREF STL2
P3PTR STL3
SETLKOUT STN
RSTLKOUT FW
STDIR REV
IEC05000707-5-en.vsdx
IEC05000707 V5 EN-US
18.1.5 Signals
PID-7434-INPUTSIGNALS v1
PID-7434-OUTPUTSIGNALS v1
18.1.6 Settings
PID-7434-SETTINGS v1
There is a single input (TRINALL) through which all trip output signals from the protection functions
within the IED or from external protection functions via one or more of the IEDs' binary inputs are
routed. It has a three-phase trip output (TRIP) to connect to one or more of the IEDs' binary outputs,
as well as to other functions within the IED requiring this signal.
P3PTR
TRINN
SETLKOUT
RSTLKOUT
P3PTR
TRINN
SETLKOUT
RSTLKOUT
IEC10000266-3-en.vsdx
IEC10000266 V3 EN-US
The input TRINN can be activated from functions which provide data for trip in the neutral.
The inputs 1PTRZ and 1PTREF enable single- phase and two-phase tripping for those functions
which do not have their own phase selection capability (that is, which have just a single trip output).
An example of such a protection function is the residual overcurrent protection. The SMPPTRC
function has two inputs for these functions, one for impedance tripping (1PTRZ used for carrier-aided
tripping commands from the scheme communication logic), and one for earth fault tripping (1PTREF
used for tripping from a residual overcurrent protection). External phase selection for these two trip
signals shall be provided via inputs PSL1, PSL2, and PSL3.
A timer tWaitForPHS, secures a three-phase trip command for these two trip signals in the absence
of the external phase selection signals.
The SMPPTRC function has three trip outputs TRL1, TRL2, TRL3 (besides the three-phase trip
output TRIP), one per phase, to connect to one or more of the IEDs’ binary outputs, as well as to
other functions within the IED requiring these signals. These three output signals shall be used as
trip signals for individual circuit breaker poles. These signals are important for cooperation with the
autorecloser SMBRREC function.
The outputs TRN and TRIP are activated when the input TRINN is activated.
The SMPPTRC function is equipped with logic which secures correct operation for evolving faults as
well as for reclosing on to persistent faults. A binary input P3PTR is provided which will force all
tripping to be three-phase. This input is required in order to cooperate with the SMBRREC function.
In multi-breaker arrangements, one SMPPTRC function block is used for each circuit breaker.
If external conditions are required to initiate a circuit breaker lockout, it can be achieved by activating
input SETLKOUT. The settingAutoLock = Off means that the internal three-phase trip will not activate
lockout so only initiation of the input SETLKOUT will result in lockout. This is normally the case for
overhead line protection where most faults are transient. Unsuccessful autoreclosing and back-up
zone tripping can in such cases be connected to initiate lockout by activating the input SETLKOUT.
If CLLKOUT is set by an external trip signal from another protection function, that is by activating
SETLKOUT input, or internally by a three-phase trip, that is with the setting AutoLock = On and the
setting TripLockout = On, then also all trip outputs are set latched.
The lockout can manually be reset after checking the primary fault by activating the reset lockout
input RSTLKOUT.
The BLKLKOUT input blocks the circuit breaker lockout output CLLKOUT.
The following three sequences in the following table shows the interaction between the inputs
BLOCK, BLKLKOUT, SETLKOUT, RSTLKOUT and the output CLLKOUT.
Inputs Output
BLOCK BLKLKOUT SETLKOUT RSTLKOUT CLLKOUT
Active - - - False
Active - Active - False
- - - - False
- - Active - True
Active - - - True
Active - - Activated True
- - - - True
- Active - - False
Table continues on next page
Inputs Output
BLOCK BLKLKOUT SETLKOUT RSTLKOUT CLLKOUT
- Active Active - False
- - - - True
- - - Activated False
Directional data
Merged directional data from application functions can be provided to the trip function (SMPPTRC)
via the start matrix function (SMAGAPC) connected to the STDIR input.
The directional input signal STDIR is a coded integer signal which contains 15 individual Boolean
signals, see Figure 639:
STDIRX=[b0, b1, b2, b3, b4, b5, b6, b7, b8, b9, b10, b11, b12, b13, b14]
b0= START (start)
b1= FW (forward)
b2= REV (reverse)
b3= STL1 (start L1)
b4= FWL1 (forward L1)
b5= REVL1 (reverse L1)
b6= STL2 (start L2)
b7= FWL2 (forward L2)
b8= REVL2 (reverse L2)
b9= STL3 (start L3)
b10= FWL3 (forward L3)
b11= REVL3 (reverse L3)
b12= STN (start N)
b13= FWN (forward N)
b14= REVN (reverse N)
The indications for general start START and phase-wise starts STL1, STL2 and STL3, and neutral
STN and general directional forward FW and reverse REV are all available as outputs on the trip
function.
All start and directional outputs are mapped to the IEC 61850 logical node data model of the trip
function. The time stamping is updated each time an operate or start signal is changed:
dirGeneral
0 unknown
1 forward
2 backward (reverse)
3 both
• The phase wise directional outputs (DIRL1, DIRL2, DIRL3, and DIRN) are mapped as:
tTripMin
BLOCK TRIPALL
OR
AND t
TRINL1
TRINL2
TRINL3
TRINALL OR
1PTREF
1PTRZ
IEC05000517-5-en.vsdx
IEC05000517 V5 EN-US
TRINALL
TRINL1 L1TRIP
OR
PSL1
AND
TRINL2
L2TRIP
OR
PSL2
AND
TRINL3
L3TRIP
OR
PSL3
AND
-LOOP
OR OR
OR
AND AND
OR
tWaitForPHS
-LOOP
t
OR
1PTREF AND
AND
1PTRZ OR
IEC10000056-5-en.vsdx
IEC10000056 V5 EN-US
tTripMin
BLOCK
OR TR
L1TRIP AND t OR
tEvolvingFault
t AND
L2TRIP
L3TRIP
OR
P3PTR
IEC170
IEC17000065 V2 EN-US
Figure 637: Simplified additional logic per phase, Program = 1ph/3ph or 1ph/2ph/3ph
TRIPL1
OR TRL1
OR
TRIPL2
OR TRL2
OR
TRIPL3
OR TRL3
OR
TRIPN TRN
OR OR TRIP
OR
TRIPALL
OR -LOOP
OR
-LOOP AND
AND TR3P
OR
AND OR
AND
10 ms To ensure that the
fault is single phase TR1P
AND t
AND
AND OR AND
OR
-LOOP
AND
TripLockout
AND AND
AutoLock -LOOP
SETLKOUT OR
OR AND CLLKOUT
AND AND
RSTLKOUT
AND
AND
BLOCK
BLKLKOUT
IEC17000066-3-en.vsdx
IEC17000066 V3 EN-US
Directional logic
IntToBits
STDIR START START
in b0
FW STL1
b1
REV STL2
b2
STL1 STL3
b3
FWL1 STN
b4
REVL1
b5
STL2
b6
FWL2 FW
b7
REVL2 BitsToInt
b8 dirGeneral (61850 Standard)
STL3
b9 0 = unknown
FWL3 b0 out
b10 DIR 1 = forward
REVL3 b1 2 = backward (reverse)
b11
STN 3 = both
b12
FWN REV
b13
REVN
b14
b15
AND
XOR
AND
XOR
AND
IEC16000179-2-en.vsdx
IEC16000179 V2 EN-US
The Start Matrix (SMAGAPC) merges start and directional output signals from different application
functions and creates a common start and directional output signal (STDIR) to be connected to the
Trip function, see Figure 640.
The purpose of this functionality is to provide general start and directional information for the IEC
61850 trip logic data model SMPPTRC.
SMAGAPC
BLOCK STDIR
STDIR1
STDIR2
STDIR3
STDIR4
STDIR5
STDIR6
STDIR7
STDIR8
STDIR9
STDIR10
STDIR11
STDIR12
STDIR13
STDIR14
STDIR15
STDIR16
IEC16000165-1-en.vsdx
IEC16000165 V1 EN-US
18.2.4 Signals
PID-6906-INPUTSIGNALS v2
PID-6906-OUTPUTSIGNALS v2
18.2.5 Settings
PID-6906-SETTINGS v2
Start matrix
The Start Matrix function requires that a protection function delivers the directional output signals in a
fixed order to Start Matrix.
A directional input signal STDIRX of the Start Matrix is of type word. Each input contains 14
individual Boolean signals, which are positioned as, see Figure 642.
STDIRX=[b0, b1, b2, b3, b4, b5, b6, b7, b8, b9, b10, b11, b12, b13, b14]
b0= START (start)
b1= FW (forward)
b2= REV (reverse)
b3= STL1 (startL1)
b4= FWL1 (forwardL1)
b5= REVL1 (reverseL1)
b6= STL2 (startL2)
b7= FWL2 (forwardL2)
b8= REVL2 (reverseL2)
b9= STL3 (startL3)
b10= FWL3 (forwardL3)
b11= REVL3 (reverseL3)
Table continues on next page
The StartMatrix function contains two function: the START criteria and the DIRECTION criteria, see
Figure 641.
The START criteria is to ensure that a forward and reverse signal shall come together with a start
signal to pass through the block. This is done individually for each protection function connected to
the StartMatrix via the STDIRX inputs, see Figure 642.
All STDIROUT signals are then connected via an OR gate, see Figure 641.
The DIRECTION criteria allow either forward or reverse (phase-wise forward FWLx or forward
neutral FWN or phase-wise reverse REVLx or reverse neutral REVN) to pass through to the general
STDIR output. If both forward and reverse are active phase-wise (e.g. REVLx=FWLx = True) or at
neutral (e.g. FWN = REVN = True) at the same time, none will be shown, see Figure 643.
SMAGAPC
(StartMatrix)
START Criteria
STDIR1
STDIRX STDIROUT
START Criteria
STDIR2
STDIRX STDIROUT
START Criteria
STDIR3
STDIRX STDIROUT
DIRECTION Criteria
STDIR
≥1 STDIRIN STDIR
START Criteria
STDIR4
STDIRX STDIROUT
START Criteria
STDIR5
STDIRX STDIROUT
START Criteria
STDIR6
STDIRX STDIROUT
START Criteria
STDIR7
STDIRX STDIROUT
START Criteria
STDIR8
STDIRX STDIROUT
START Criteria
STDIR9
STDIRX STDIROUT
START Criteria
STDIR10
STDIRX STDIROUT
START Criteria
STDIR11
STDIRX STDIROUT
START Criteria
STDIR12
STDIRX STDIROUT
START Criteria
STDIR13
STDIRX STDIROUT
START Criteria
STDIR14
STDIRX STDIROUT
START Criteria
STDIR15
STDIRX STDIROUT
START Criteria
STDIR16
STDIRX STDIROUT
IEC16000161-2-en.vsdx
IEC16000161 V2 EN-US
START Criteria
START (in)
STL1 (in)
STL2 (in) ≥1 START (out)
STL3 (in)
IntToBits STN (in) BitsToint
STDIRX STDIROUT
in b0 START (in) STL1 (out) START (out) b0 out
b1 FW (in) STL2 (out) FW (out) b1
b2 REV (in) STL3 (out) REV (out) b2
b3 STL1 (in) STN (out) STL1 (out) b3
b4 FWL1 (in) FWL1 (out) b4
b5 REVL1 (in) REVL1 (out) b5
&
b6 STL2 (in) FW (in) STL2 (out) b6
b7 FWL2 (in) FWL2 (out) b7
≥1 FW (out)
b8 REVL2 (in) REVL2 (out) b8
b9 STL3 (in) STL3 (out) b9
b10 FWL3 (in) FWL3 (out) b10
b11 REVL3 (in) & REVL3 (out) b11
REV (in)
b12 STN (in) STN (out) b12
b13 FWN (in) ≥1 REV (out) FWN (out) b13
b14 REVN (in) REVN (out) b14
b15 N/A FALSE b15
IEC16000162-2-en.vsdx
IEC16000162 V2 EN-US
DIRECTION Criteria
FWL1 (in)
=1
REVL1 (in)
FWL2 (in)
=1
REVL2 (in)
FWL3 (in)
=1
REVL3 (in)
FWN (in)
=1
REVN (in)
IEC16000163-2-en.vsdx
IEC16000163 V2 EN-US
STARTCOMB
To make it possible to provide the directional information from a protection function, a STARTCOMB
block is used in between the application function and the Start Matrix function.
The STARTCOMB function has one block input and 14 Boolean inputs that convert the 14 Boolean
inputs into a WORD output STDIR, see Figure 644.
STDIRX=[b0, b1, b2, b3, b4, b5, b6, b7, b8, b9, b10, b11, b12, b13, b14]
b0= START (start)
b1= FW (forward)
b2= REV (reverse)
b3= STL1 (startL1)
b4= FWL1 (forwardL1)
b5= REVL1 (reverseL1)
b6= STL2 (startL2)
b7= FWL2 (forwardL2)
b8= REVL2 (reverseL2)
b9= STL3 (startL3)
b10= FWL3 (forwardL3)
b11= REVL3 (reverseL3)
b12= STN (startN)
b13= FWN (forwardN)
b14= REVN (reverseN)
STARTCOMB
BLOCK STDI R
START
FW
REV
STL1
FWL1
REVL1
STL2
FWL2
REVL2
STL3
FWL3
REVL3
STN
FWN
REVN
IEC16000166-2-en.vsdx
IEC16000166 V2 EN-US
Protection functions
Some protection functions are provided with start and directional outputs, for example:
Connection example
In Figure 645 below is an example how to connect start and directional signals from protection
functions via STARTCOMB and SMAGAPC to SMPPTRC.
SMAGAPC
STARTCOMB BLOCK STDIR
PROTECTION 1 BLOCK STDIR STDIR1
START START STDIR2
FW FW STDIR3
REV REV STDIR4
STL1 STDIR5
FWL1 STDIR6 SMPPTRC
REVL1 STDIR7 BLOCK TRIP
STL2 STDIR8 BLKLKOUT TRL1
FWL2 STDIR9 TRIN TRL2
REVL2 STDIR10 TRINL1 TRL3
STL3 STDIR11 TRINL2 TR1P
FWL3 STDIR12 TRINL3 TR2P
REVL3 STDIR13 PSL1 TR3P
STN STDIR14 PSL2 CLLKOUT
FWN STDIR15 PSL3 START
REVN STDIR16 1PTRZ STL1
1PTREF STL2
P3PTR STL3
STARTCOMB SETLKOUT STN
BLOCK STDIR RSTLKOUT FW
START STDIR REV
FW
PROTECTION 2 REV
STL1 STL1
FWL1 FWL1
REVL1 REVL1
STL2 STL2
FWL2 FWL2
REVL2 REVL2
STL3 STL3
FWL3 FWL3
REVL3 REVL3
STN
FWN
REVN
STARTCOMB
BLOCK STDIR
START
FW
REV
STL1
FWL1
REVL1
STL2
FWL2
REVL2
STL3
PROTECTION 4
FWL3
-
PROTECTION 3 REVL3
STDIR
STN STN
-
FWN FWN
-
REVN REVN
IEC16000164-2-en.vsdx
IEC16000164 V2 EN-US
18.3.1 Identification
SEMOD167882-2 v3
The trip matrix logic (TMAGAPC) function is used to route trip signals and other logical output signals
to different output contacts on the IED.
The trip matrix logic function has 3 output signals and these outputs can be connected to physical
tripping outputs according to the specific application needs for settable pulse or steady output.
TMAGAPC
BLOCK OUTPUT1
BLK1 OUTPUT2
BLK2 OUTPUT3
BLK3
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16
INPUT17
INPUT18
INPUT19
INPUT20
INPUT21
INPUT22
INPUT23
INPUT24
INPUT25
INPUT26
INPUT27
INPUT28
INPUT29
INPUT30
INPUT31
INPUT32
IEC13000197-1-en.vsd
IEC13000197 V1 EN-US
18.3.4 Signals
PID-6513-INPUTSIGNALS v4
PID-6513-OUTPUTSIGNALS v4
18.3.5 Settings
PID-6513-SETTINGS v4
The trip matrix logic (TMAGAPC) block is provided with 32 input signals and 3 output signals. The
function block incorporates internal logic OR gates in order to provide grouping of connected input
signals to the three output signals from the function block.
Internal built-in OR logic is made in accordance with the following three rules:
1. when any one of first 16 inputs signals (INPUT1 to INPUT16) has logical value 1 the first output
signal (OUTPUT1) will get logical value 1.
2. when any one of second 16 inputs signals (INPUT17 to INPUT32) has logical value 1 the
second output signal (OUTPUT2) will get logical value 1.
3. when any one of all 32 input signals (INPUT1 to INPUT32) has logical value 1 the third output
signal (OUTPUT3) will get logical value 1.
PulseTime
t
&
ModeOutput1=Pulsed
INPUT 1
OUTPUT 1
Ondelay Offdelay
&
³1
³1 t t
INPUT 16
PulseTime
t
&
ModeOutput2=Pulsed
INPUT 17
OUTPUT 2
Ondelay Offdelay
&
³1
³1 t t
INPUT 32
PulseTime
t
&
ModeOutput3=Pulsed
OUTPUT 3
Ondelay Offdelay
&
³1
³1 t t
IEC09000612-3-en.vsd
IEC09000612 V3 EN-US
The group alarm logic function (ALMCALH) is used to route several alarm signals to a common
indication, LED and/or contact, in the IED.
ALMCALH
BLOCK ALARM
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16
IEC13000181-1-en.vsd
IEC13000181 V1 EN-US
18.4.4 Signals
PID-6510-INPUTSIGNALS v5
PID-6510-OUTPUTSIGNALS v5
18.4.5 Settings
PID-6510-SETTINGS v5
The logic for group alarm ALMCALH block is provided with 16 input signals and one ALARM output
signal. The function block incorporates internal logic OR gate in order to provide grouping of
connected input signals to the output ALARM signal from the function block.
When any one of 16 input signals (INPUT1 to INPUT16) has logical value 1, the ALARM output
signal will get logical value 1.
The function has a drop-off delay of 200 ms when all inputs are reset to provide a steady signal.
Input 1
200 ms
ALARM
³1 t
Input 16
IEC13000191-1-en.vsd
IEC13000191 V1 EN-US
The group warning logic function (WRNCALH) is used to route several warning signals to a common
indication, LED and/or contact, in the IED.
WRNCALH
BLOCK WARNING
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16
IEC13000182-1-en.vsd
IEC13000182 V1 EN-US
18.5.4 Signals
PID-4127-INPUTSIGNALS v3
PID-4127-OUTPUTSIGNALS v3
18.5.5 Settings
PID-4127-SETTINGS v3
The logic for group warning WRNCALH block is provided with 16 input signals and 1 WARNING
output signal. The function block incorporates internal logic OR gate in order to provide grouping of
connected input signals to the output WARNING signal from the function block.
When any one of 16 input signals (INPUT1 to INPUT16) has logical value 1, the WARNING output
signal will get logical value 1.
The function has a drop-off delay of 200 ms when all inputs are reset to provide a steady signal.
INPUT1
200 ms
WARNING
³1 t
INPUT16
IEC13000192-1-en.vsd
IEC13000192 V1 EN-US
The group indication logic function (INDCALH) is used to route several indication signals to a
common indication, LED and/or contact, in the IED.
INDCALH
BLOCK IND
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16
IEC13000183-1-en.vsd
IEC13000183 V1 EN-US
18.6.4 Signals
PID-4128-INPUTSIGNALS v4
PID-4128-OUTPUTSIGNALS v4
18.6.5 Settings
PID-4128-SETTINGS v4
The logic for group indication INDCALH block is provided with 16 input signals and 1 IND output
signal. The function block incorporates internal logic OR gate in order to provide grouping of
connected input signals to the output IND signal from the function block.
When any one of 16 input signals (INPUT1 to INPUT16) has logical value 1, the IND output signal
will get logical value 1.
The function has a drop-off delay of 200 ms when all inputs are reset to provide a steady signal.
INPUT1
200 ms
IND
³1 t
INPUT16
IEC13000193-1-en.vsd
IEC13000193 V1 EN-US
The basic configurable logic blocks do not propagate the time stamp and quality of signals (have no
suffix QT at the end of their function name). A number of logic blocks and timers are always available
as basic for the user to adapt the configuration to the specific application needs. The list below
shows a summary of the function blocks and their features.
The logic blocks are available as a part of an extension logic package. The list below is a summary of
the function blocks and their features.
• AND function block. The AND function is used to form general combinatory expressions with
boolean variables. The AND function block has up to four inputs and two outputs. One of the
outputs is inverted.
• GATE function block is used for whether or not a signal should be able to pass from the input to
the output.
• INVERTER function block that inverts the input signal to the output.
• LLD function block. Loop delay used to delay the output signal one execution cycle.
• OR function block. The OR function is used to form general combinatory expressions with
boolean variables. The OR function block has up to six inputs and two outputs. One of the
outputs is inverted.
• PULSETIMER function block can be used, for example, for pulse extensions or limiting of
operation of o