0% found this document useful (0 votes)
101 views2 pages

Technical Specifications Eaton 9PX UPS Technical Specifications (

The document provides technical specifications for Eaton 9PX UPS models with 3 kVA power ratings, including dimensions, weight, input/output connections and receptacles, battery specifications, communications options, and environmental standards. Key details are the UPS models support input voltages of 176-276V and output power of 3000VA. They include internal sealed lead-acid batteries that provide backup times of 7-62 minutes depending on the load and additional optional extended battery modules can nearly double the backup time.

Uploaded by

Edison Gatto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
101 views2 pages

Technical Specifications Eaton 9PX UPS Technical Specifications (

The document provides technical specifications for Eaton 9PX UPS models with 3 kVA power ratings, including dimensions, weight, input/output connections and receptacles, battery specifications, communications options, and environmental standards. Key details are the UPS models support input voltages of 176-276V and output power of 3000VA. They include internal sealed lead-acid batteries that provide backup times of 7-62 minutes depending on the load and additional optional extended battery modules can nearly double the backup time.

Uploaded by

Edison Gatto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Technical

Specifications

Eaton 9PX UPS technical specifications (3 kVA 3U models*)


Model overview
Catalog Power rating Input Dimensions Weight
number (VA/watts) connection Output receptacles (HxWxD, in.)** (lb.)
208V output, 50/60 Hz bundles
(2) L6-30R, (2) L6-20R,
9PX3K3UN 3000/3000 L6-30P*** Hardwired 5.1 (3U) x 17.3 x 28.4 106
120/208V output, 50/60 Hz bundles
(1) L6-30R, (2) L6-20R,
9PX3K3UNTF5 3000/3000 L6-30P*** (18) 5-20R, Hardwired 10.2 (6U) x 17.3 x 28.4 201
(1) L14-30R, (1) L6-30R,
9PX3K3UNP11 3000/3000 L6-30P (6) 5-20R 10.2 (6U) x 17.3 x 28.4 203
9PX3K3UNP2 3000/3000 Hardwired Hardwired 10.2 (6U) x 17.3 x 28.4 201
*Due to continuing product improvement programs, specifications are subject to change without notice.
**Each module of every 9PX bundle ships with a 4-post rail kit.
***Terminal block with L6-30P cord.
1. Bundles with 9PXTFMR5 have output frequency of 60 Hz only

Additional specifications
General
Topology Double-conversion online
Configuration Rack/tower
Color Black and silver
Diagnostics Full system self-test at power up
Warranty 2 years
4-post rail kit and tower pedestals included; Optional 2-post rail kit available, part
Rail kit number: RK2PC
Remote emergency power off ROO and RPO: Rear deck emergency stop connectors (for remote on/off and
(REPO) power off)
UPS
Network-M2 Web/SNMP card
4-post rail kit
User manual
Quick start guide
Contents
Tower pedestals
(Ships with the following items)
Intelligent Power Software Suite CD
RS-232 serial cable
USB cable
Cable gland for hardwire connection
Phillips head screwdriver
Electrical input
Input voltage range Full load: 176-276V, Derating: 100-276V
Nominal voltage 200/208/220/230/240V
Default voltage 208V
Frequency 50/60 Hz
Frequency range 60 Hz: 50–70 Hz, 50 Hz: 40–60 Hz
Input power factor >.99
Input current distortion <5%
Circuit breakers (2) 20A for L6-20R

Eaton.com/9PX TD153014EN May 2021


Page 2 of 2

Electrical output
Power ratings 200/208/220/230/240V: 3000 VA/3000 watts
Nominal voltage 208V default (200/208/220/230/240V)
Output voltage regulation ±1% steady-state
Voltage THD <2% for linear loads
Power factor 0.9
Efficiency 92.5% with resistive load
Transfer time 0 ms
Battery
Optional extended battery
9PXEBM180RT
module (EBM)
Maximum number of EBMs Add up to 4 EBMs
Battery description Sealed, lead-acid; maintenance free
ABM technology; 3-stage charging extends battery service life by 50% and
Battery management
provides advance warning for battery replacement
Battery replacement Hot-swappable internal batteries and EBMs
Start on battery Cold-start enabled; first cold start is always forbidden
Communications
User interface Graphical display. UPS status in a single view.
LEDs 4 status-indicating LEDs
RS-232 (RJ45) ports; USB port as standard (HID). 6-foot RS-232 and USB cables
Communication ports included
Communications card slot Network Card-M2 included
Power management software Integrates with Eaton Intelligent Power Manager software
Environmental & standards
Energy Star Yes
RoHS compliance Yes
Surge protection IEEE ANSI C62.41 Cat B2
Heat dissipation (BTU/hr;
battery full charged, resistive 9PX3K: Online: 830. Battery: 1040
load)
Audible noise <45 dB at 1 meter
Operating temperature 0 to 40°C (32°F to 104°F)
Safety conformance CE / cULus / NOM
EMC markings IEC 62040-2:2006 Cat C2 / CISPR22 Class A / FCC part 15 Class A
Storage temperature 0 to 35°C (32°F to 95°F); without batteries: -15 to 60°C (5°F to 140°F)
Relative humidity 0 to 95% non-condensing
Altitude 3,000 meters at 40°C

Battery backup times (in minutes)****


Internal
Load (watts) +1 EBM +2 EBMs +3 EBMs +4 EBMs
batteries
3000 7.2 33 62 92 122
2500 9.4 42 78 109 147
2000 12.9 55 100 135 185
1500 19.1 75 133 184 258
1000 31.9 115 196 297 421
500 62.0 222 432 576 840
****Runtimes are shown at full load with maximum power factor, are approximate and may vary with equipment, configuration,
battery age, temperature, etc. View interactive runtime graphs at www.eaton.com/9PX.

Eaton.com/9PX TD153014EN May 2021

You might also like