LiFePO4 Battery 48V 100Ah for Telecom/Solar/Backup System
Cylindrical Lithium Iron Phosphate Battery
OPT48100
Brief Introduction
OptimumNano always develop and produce
32650 cells to or assemble battery packs to Diameter: 32.2±0.5mm
satisfy the requirements of high performance Height: 70.0±0.5mm
and operational reliability of our customers. We
also have the 14500/18650/22650/26650 cells
Electrical Charateristics
to meet all your requirements.
Nominal Voltage 48V
Nominal Capacity 100Ah
Characteristics of ESS
Impedance
哦发 ≤55mΩ
Cells and Battery Voltage Detection: (Max. at1000Hz)
protection and alarming for over charge, over More than 2000 cycles, with 1C
Expected Cycle Life
discharge charge and discharge rate, at 25 ℃
Cells and Battery Ambient Temperature
Detection: protection and alarming for high Mechanical Characteristics
temperature and low temperature 482±2mm
Width
(442mm without food mounting)
Battery Charge and Discharge Current Dimensions
Detection: protection and alarming for (4U steel rack) Depth 510±2mm
charge current and discharge current, also for Height 176±2mm
short circuit protection Weight ~65Kg
Battery SOC and Cycles Detection: show
the real-time SOC and recycle times Operation Conditions
With 6 LED indicators: to show the SOC, Charge Method CC-CV
operation mode, alarming and protection
Max. Charge Voltage 54.75V
status
Continuous Charge Current Max. 100A
Bottom for Start-up, Shutdown and Reset
Charge Temperature 0℃~45℃
RS232 and RS485 Communication
Interface: the PC can do the battery Data Continuous Discharge Current Max. 100A
Monitoring, Operation Controlling and Peak Instant Discharge
110A
Parameter Setting through the remote order Current (10 Seconds)
History Data Record Storing and Reading Discharge Cut-off Voltage 37.5V
Battery Parameter Setting: to cells and Discharge Temperature -20℃~60℃
battery over discharge, over charge, over Storage Temperature -20℃~55℃
current, short circuit, high temperature, low
Self Discharge
temperature, number of serials, battery <= 3%/month
(Stored at 50% SOC)
capacity
This document is the enterprise standard of our company, without authorization, any pirate or circulation is not allowed.
Charge and discharge curve
充电曲线图
charge curve
25℃±5℃
57.0
55.5
54.0
52.5
51.0
Voltage(V)
电压(V)
49.5 0.2C
48.0
46.5
45.0
43.5
42.0
40.5
39.0
37.5
36.0
0 10 20 30 40 50 60 70 80 90 100 110
容量(Ah)
Capacity(Ah)
放电曲线图
Diploid discharge curve
25℃±5℃
57.0
55.5
54.0
52.5
51.0
Voltage(V)
电压(V)
49.5
48.0
46.5
45.0
1C
43.5
42.0
40.5
39.0
37.5
36.0
0 10 20 30 40 50 60 70 80 90 100 110
容量(Ah)
Capacity(Ah)
This document is the enterprise standard of our company, without authorization, any pirate or circulation is not allowed.
1. Instructions
Overview
Display Display Buttons
Positive Negative
RST
D Power
I Indicator
P
2. Description for the buttons
Setting
Page up
Page down
Return
3. Display instructions
Picture 1:
This is what the BMS show when awakening, and to get to
XXXXXX normal parameters. Then it will automatically jump to the
Welcome
Picture 2.
2014-12-30 16:55
At this moment, all the buttons do not work.
Picture 2:
To show the battery voltage, current, SOC and status.
Bat_Volt:51. 16V
Bat_Curt:0.00A
Press “setting”, turn to Interface 2nd to set all the parameters;
Rem_Capt: 70.71Ah
Sys_Stat: Standby The “return” do not work;
Press “page down”, turn to Interface 3rd;
Press “page up”, turn to Interface 7th
This document is the enterprise standard of our company, without authorization, any pirate or circulation is not allowed.
Picture 3:
To show the battery used capacity, ambient temperature,
Cycles : 35Ah
power temperature and the BMS alarming status.
Amb_TemP: 19.3℃
Pow_Temp: 26.7℃
Press “setting”, turn to Interface 8th to set all the parameters;
AlarStat: None
The “return” do not work;
Press “page down”, turn to Interface 4th;;
Press “page up”, turn to Interface 2nd
Picture 4:
To show the voltage from B1-B8.
Cel_Volt mV 01~08
3342 3343 3345
3343 3344 3343 Press “setting”, turn to Interface 8th to set all the parameters;
3345 3346 The “return” do not work;
Press “page down”, turn to Interface 5th;;
Press “page up”, turn to Interface 3rd
Picture 5:
To show the voltage from B9-B15.
Cel_Volt mV 09~16
3345 3345 3346
3346 3345 3345 Press “setting”, turn to Interface 8th to set all the parameters;
3345 The “return” do not work;
Press “page down”, turn to Interface 6th;;
Press “page up”, turn to Interface 4th
Picture 6:
To show the temperate from 1 to 4
Cel_TemP℃ 01~04
17.6 17.2
Press “setting”, turn to Interface 8th to set all the parameters;
17.6 17.6
The “return” do not work;
Press “page down”, turn to Interface 7th;;
Press “page up”, turn to Interface 5th.
4. DP number: It is used for battery parallel with binary system and the four bottoms represent 1, 2, 4,8
If you use one battery only, pls keep all the bottoms down, like this
if you want to connect the battery in parallel, then you should change the the DP number(stated in the BMS
sepecification)
After change the DP number, pls "RST"
This document is the enterprise standard of our company, without authorization, any pirate or circulation is not allowed.
Function of PCM/BMS (Battery Management System)
Item Content Criterion
To show the battery voltage, temperature, SOC,
Communication RS485 or RS232
faults and so on
Over charge detection voltage 3900±20 mV ( can be set)
Over charge
Over charge release voltage 3800±20 mV ( can be set)
Protection
Release condition The single voltage is up to the release voltage
Over discharge detection voltage 2000±50 mV (can be set)
Over discharge detection delay time 5 ±1S (can be set)
Over discharge
protection Over discharge release voltage 2300±50 mV(can be set)
Detect the effective charge current and the single voltage
Release condition
is higher than the release voltage
Over charge current detection current 100±1A (can be set, 3A~100A )
Over charge detection delay time 5±1S (can be set, 1S~600S )
Over current
Over discharge current detection current -100±1A (can be set, 3A~100A )
protection
Over discharge detection delay time 5±1S (can be set, 1S~600S )
Release condition Connect with charger or reset
Balancing voltage 3370 mV(can be set, 3000mV-4500mV)
Cells balancing Balancing voltage different 50mV(can be set, 50mV-100mV)
Balancing end voltage 30mV(can be set, 10mV-30mV)
Temperature Low temperature alarm -10±3℃(can be set, -20-60℃)
Protection High temperature alarm 60±3℃(can be set, -20-60℃)
Storage and Transportation
1. Based on the character of cell, proper environment for transportation of LiFePO4 battery pack need to be created to
protect the battery.
2. During transportation, 50% SOC must be kept to ensure that short circuit, appearance of liquid in the battery or
immersion of battery in liquid never occur.
3. Battery should be kept at -20℃~45℃ in warehouse where it’s dry, clean and well-ventilated.
4. During loading of battery, attention must be paid against dropping, turning over and serious stacking.
This document is the enterprise standard of our company, without authorization, any pirate or circulation is not allowed.
Warnings and Tips
In order to prevent the battery leaking, getting hot and exploding, please pay attention to preventing measure as
following:
send to hospital. Otherwise it will hurt eyes.
Warning!
If battery emit peculiar smell, heating, distortion or
Never throw the battery into water, keep it under
appear any unconventionality during using, storage
dry, shady and cool circumstance when not use. or charging process, please take it out from device
Never upside down the positive and negative. or charge and stop using.
Never connect the positive and negative of battery Never cut the battery in socket directly; please use
with metal. the stated charger when charging.
Never ship or store the battery together with metal
Check the voltage of battery and relevant
Never knock, throw or trample the battery.
connectors before using the battery. It can’t be used
Never cut through the battery with nail or other edge
tool. until everything turns out to be normal.
Prior to charging, fully check the insulativity,
Tips!
Never use or keep the battery under the high physical condition and ageing status, since
temperature. Otherwise it will cause battery heat, breakage and ageing are never allowed; the pack
get into fire or lose some function and reduce the life.
voltage must not be less than the cutoff voltage, if
The proposed temperature for long-term storage is
not, it’s abnormal and that battery needs to be
10-45℃.
labeled. The user should contact our Customer
Never throw the battery into fire or heating machine
to avoid fire, explosion and environment pollution; Service Dept and it can’t be charged until repaired
scrap battery should be returned to the supplier and by our staff.
handled by the recycle station. The battery should be stored in 50% SOC. It needs
Never use the battery under strong static and strong
to be charged once if out of use for as long as half a
magnetic field, otherwise it will destroy the
year.
protecting device.
Clean the dirty electrode, if any, with a clean dry
If battery leaked, the electrolyte get into eyes,
please don’t knead, please wash eyes by water and cloth, or poor contact or operation failure may occur.
Contact Us
OptimumNano Energy Co., Ltd
Address: No. 68, Lanjing North Road, Pingshan New District, Shenzhen, China 518118
Tel: +86-755-87640787 Fax: +86-755-84630785
E-mail:
[email protected] Web: www.optimumnanoenergy.com
This document is the enterprise standard of our company, without authorization, any pirate or circulation is not allowed.