FD & DFD 150X Models: Installation, Operation and Maintenance Instructions
FD & DFD 150X Models: Installation, Operation and Maintenance Instructions
.)!
3 4!4
BOCA National Building Codes Curtain Fire Wall Dampers
3 4!4
or Floor
,
&)
!,
2%
Upon receiving dampers, check for both obvious and hidden damage. If damage is found, record all necessary information
on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including
accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly recommended.
Do not store at temperatures in excess of 100°F.
Duct
Vertical Mount Damper Duct
Retaining Angles
(See Section 3)
1/4 in. minimum Type B
total clearance Type A
Wall or Floor
Wall or Floor
Maximum Maximum
6 in. 6 in.
Duct Damper
Duct
Duct
Damper
Retaining Angles Type C, CO, CR, & R
(See Section 3) Type B
Type A
Wall or Floor
Wall or Floor
Horizontal Mount
On types R & CR factory
Damper furnished duct collar
Duct
qualifies as breakaway
Retaining Angles
(See Section 4) connection. Retaining Angles
(See Section 4)
Sleeve
Sleeve
Sleeve
(see sections 2 & 3) On types R & CR factory
(see sections 2 & 3)
See Section 2 furnished duct collar qualifies
See Section 2 Damper Duct Damper
as breakaway connection, see
Section 5
Duct
Duct
Type B
Duct Damper Type C, CO, CR, & R
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job
is complete.
Duct Damper
Safety WARNING: Warranty
Improper installation, adjustment, alteration, service Greenheck warrants this equipment to be free from
or maintenance can cause property damage, injury defects in material and workmanship for a period of one
or death. Read the installation, operating, and year from the purchase date. Any units or parts which
maintenance instructions thoroughly before installing prove to be defective during the warranty period will be
or servicing this equipment. repaired or replaced at our option. Greenheck shall not
be liable for damages resulting from misapplication or
misuse of its products. Greenheck will not be responsible
for any installation or removal costs. Greenheck will not be
responsible for any service work or backcharges without
prior written authorization.
Table of Contents
Pre-Installation Guidelines............................................................................................................2
Installation................................................................................................................................. 3-4
Breakaway Connections...............................................................................................................5
Damper Maintenance....................................................................................................................6
Damper Troubleshooting...............................................................................................................6
Installation for Steel Stud Connection Option......................................................................... 6-7
Pre-Installation Guidelines
The basic intent of a proper installation is to secure the fire damper in, not to, the opening in such a manner
as to prevent distortion and disruption of damper operation. This is accomplished by allowing the fire damper
in rated separation openings to expand and for the connecting duct to separate in the event of the collapse of
the hanging system. The following items will aid in completing the damper installation in a timely and effective
manner.
1. Check the schedules for proper damper locations within the building. Visually inspect the damper for damage
and verify that the fusible link is in place or has not separated. If fusible link is not present or has separated,
replace link. Never install a fire damper without the proper UL approved fusible link in place. (Fusible link is
standard control option. An electric link may have been provided.)
2. Lift or handle damper using sleeve or frame.
3. Install damper accordingly to comply with manufacturer’s appropriate UL procedure file number.
4. Damper must be installed into duct or opening square and free of twist or other misalignment. Damper must
not be squeezed or stretched into duct or opening.
5. Damper must be kept clean and protected from dirt, dust and other foreign materials prior to and after
installation. Examples of such foreign materials include, but are not limited to:
a. Mortar dust
b. Drywall dust
c. Firesafing materials
d. Wall texture
e. Paint overspray
6. Damper should be sufficiently covered as to prevent overspray of spray-on insulating, wall texturing, or spray
painting when performed within 5 feet of the damper. Excessive dirt or foreign material deposits can cause
damper to bind and not operate properly.
7. Caulking is not necessary, nor is it allowed, between the damper sleeve and the wall or floor opening (annular
space). However, caulking may be applied to the retaining angles.
8. ACCESS: Suitable access (such that fusible links can be changed) must be provided for damper inspection
and servicing. Where it is not possible to achieve sufficient size access, it will be necessary to install a
removable section of duct. (Refer to NFPA 90A).
9. The Code Authority Having Jurisdiction (AHJ) must evaluate and provide approval of final installation where
variations to these instructions are necessary.
2
Installation - Failure to follow these instructions will void all warranties.
These instructions apply to 1 1⁄2 hour rated fire dampers mounted in masonry, block or stud walls and concrete floors.
Specific requirements in these instructions are mandatory. These instructions meet the requirements of UL 555.
Installation shall comply with the requirements of NFPA 90A Standard for the Installation of Air Conditioning and
Ventilating Systems. U.L. listing R13317, California State Fire Marshal listings 3225-981:102, and New York City
BSA/MEA listing 260-91-M as they apply to these dampers.
1. NO ADDITIONAL SLEEVES ARE REQUIRED
The fire damper extended frame is an approved sleeve and can be properly installed without the need for a
supplemental field installed sleeve. Damper frame shall extend a maximum of 6 in. beyond the wall or floor
opening on each side.
Example: A 12 in. x 12 in. damper would require a minimum clearance of 1/4 in.
A 48 in. x 12 in. damper would require a minimum clearance of 1/2 in. on width and 1/4 in. on height.
3. SECURING THE FIRE DAMPER TO WALL AND
FLOOR OPENINGS
Fire damper assemblies must be installed in wall and
floor openings using retaining angles on each side of the
wall or floor as described below:
• Retaining angles must be a minimum of 16 gauge
steel and have a minimum of 1 1⁄2 in. x 1 1⁄2 in. legs.
2ETAINING
• #10 sheetmetal screws !NGLE
!NGLE
• 1/4 in. bolts and nuts 3LEEVE
• 3/16 in. steel pop rivets
Attachments must be spaced a maximum of 6 in. on
$UCT
center and a maximum of 2 in. from corners. The angles IN
-
AX
must be attached to all 4 sides of the sleeve with butt
joints at each corner. A minimum of two attachments are IN
-
AX $AMPER
required on each side, top and bottom. The angles need
not be attached to each other at the corners. IN
-
AX
.BYJNVN
NFUBMTUVET
JO NN
1BOIFBE
4DSFXT
JO NN
JOPD JOPD
Damper Maximum Sizes Max Overall Size .BYJNVN .BYJNVN
XPPETUVET
XPPETUVET
$AMPER
)N METAL STUD CONSTRUCTION
$AMPER
3LEEVE
)N METAL STUD CONSTRUCTION
EXPOSED STEEL SURFACES NEED
3LEEVE EXPOSED STEEL SURFACES NEED
NOT BE COVERFEXJUIHZQTVN
Recommended Preparation of NOT BE COVERFEXJUIHZQTVN
WALLBOARD
WALLBOARD
Openings in Wood and Metal Stud Figure 4: Detail of retaining angles and gypsum board
Walls application for metal and wooden stud construction.
7OODEN 3TUD #ONSTRUCTION
7OODEN 3TUD #ONSTRUCTION
• Frame wall openings as shown in Figure 3.
'YPSUM 7A LLBOARD
• Double vertical studs are not required for openings 36 'YPSUM 7A LLBOARD
Figure 4).
• All construction and fasteners must meet the 2ETAINING
2ETAINING
!NGL E
requirements of the appropriate wall design. (See UL Fire !NGL E
$AMPER )N WOOD STUD CONSTRUCTION
$AMPER
3LEEVE )N WOOD STUD CONSTRUCTION
GYPSUM WALLBOARD MUST COVER
3LEEVE GYPSUM WALLBOARD MUST COVER
ALL WOOD STUD SURFACES
4 ALL WOOD STUD SURFACES
Breakaway Connections
Traditional Breakaway Style Transverse Joints
Neoprene gasket
between all angles
Duct
TDC and TDF systems are approved as breakaway connections when installed as described in the SMACNA Duct
Construction Standards. Standard 6 in. metal clips may be used with spacing (see Figure 7). Three-eighth in. metal bolts and
nuts may be used to fasten together corner pieces (see Figure 8).
#LIP 3PACING 3TD #LIP $UCT %ND
,ENGTH &LANGE
IN
IN IN IN
IN $UCT #ORNER 0IECE
2EQD
IN IN
IN $UCT
2EQD
IN IN
3LEEVE $UCT IN $UCT IN BOLT
2EQD OPTIONAL
IN IN
IN $UCT
2EQD
4YPICAL 4$#4$&