Power System Protection (Distance)
Power System Protection (Distance)
Consider an impedance relay for breaker B12 in Figure 10.27, for which Z = V1 / I12
Two ways to include directional capability with an impedance relay are shown in Figure 10.29.
o In Figure 10.29 a), an impedance relay with directional restraint is obtained by including a
directional relay in series with an impedance relay
o In Figure 10.29 b), a modified impedance relay is obtained by offsetting the centre of the
impedance circle from the origin. This modified impedance relay is called a Mho relay.
o If either of these relays is used at B12 in Figure 10.27, a fault at P1 will result in a trip
decision, but a fault at P3 will result in a block decision.
a) Impedance relay with directional restraint b) Modified impedance relay (mho relay)
Figure 10.29: Impedance relay with directional capability
It is common practice to use three directional impedance relays per phase, with increasing
reaches and longer time delays.
For example, Figure 10.27 shows three protection zones for B12.
o Zone 1 relay is typically set for an 80% reach and instantaneous operation, in order to
provide primary protection for line 1-2.
o Zone 2 relay is set for about 120% reach, extending beyond bus 2, with a typical time delay
of 0.2 to 0.3 seconds.
o Zone 2 relay provides backup protection for faults on line 1-2 as well as remote backup for
faults on line 2-3 or 2-4 in zone 2.
o Reach for the zone 3 B12 relay is typically set to extend beyond buses 3 and 4 in order to
provide remote backup for neighbouring lines.
o Therefore, zone 3 reach is set for 100% of line 1-2 plus 120% of either line 2-3 or 2-4
whichever is longer, with an even larger time delay, typically one second
Typical block and trip regions are shown in Figure 10.30 for both types of three-zone,
directional impedance relays.
a) Impedance relay with directional restraint b) Modified impedance relay (mho relay)
Figure 10.30: Three-zone, directional relay
Relay connections for a three-zone impedance relay with directional restraint are shown in
Figure 10.31.
Figure 10.31: Relay connections for a three zone directional impedance relay
a) Denoting V LN as the line to neutral voltage at bus 1 and IL as the line current through B12,
the primary impedance Z viewed at B12 is
V LN
Z
IL
Using the CT and VT ratios given in Table 10.8, the secondary impedance viewed by the
B12 impedance relays is
3000
VLN
Z ' 1 Z
1500 10
IL
5
We set the B12 zone 1 relay for 80% reach, that is, 80% of the line 1-2 (secondary)
impedance:
From Table 10.8, line 2-3 has larger impedance than line 2-4. Therefore, we set the B12
zone 3 relay for 100% reach of line 1-2 plus 120% reach of line 2-4.
199.2 10 3
Z ' Z 10 10 13.2818.19 Secondary
1500 18.19
Since this impedance exceeds the zone 3 setting of 9.0780.9ºΩ, the impedance during
emergency loading lies outside the trip regions of the three zone, directional impedance
relay.