High Performance

for a Wide Range of


Applications

SHP Series Actuators


for Butterfly Valves

Discover the advantages


www.belimo.us
Butterfly Valve Nomenclature

F6 50 -150SHP +PRB UP -MFT -T


Valve Valve Size Trim Material Actuator Type Power Supply Control
F6 = 2-way 50 = 2” -150SHP = ANSI Class 150, Non Fail-Safe -24 = 24 VAC/DC -3-X1 = On/Off, -S = B uilt-in -200 = 8”
F7 = 3-way 65 = 2½” Stainless Disc, Steel Body, GMB, GMX GR/ -110 = 110/120 VAC Floating Point Auxiliary Switch -250 = 10”
RPTFE Seat, 0% Leakage up GM... N4 -MFT or -MFT-X1 = N4 = NEMA 4/4X
80 = 3” to 285 psi
-120 = 120 VAC
100 = 4” PRB, PRX -230 = 230 VAC Multi-Function -T = Terminal
-300SHP = ANSI Class 300, SY Technology Block
125 = 5” Stainless Disc, Steel Body, Fail-Safe UP = 24-240 VAC
150 = 6” RPTFE Seat, 0% Leakage up Electronic or 24-125 VDC
200 = 8” to 600 psi
GKB, GKX
250 = 10” PKRX
300 = 12” Spring Return
350 = 14” AFB, AFX
AFRB, AFRX
400 = 16”
450 = 18”
500 = 20”
600 = 24”

Ordering Example

3 For MFT orders only - select programming code (consult factory)


1 Choose the valve actuator combination.

F650-150SHP+PRBUP-MFT-T NO Tagging (if needed)


4
2 Specify preference or configuration.
Does order
require
tagging?
2-way Configuration Set-Up 3-way Configuration
Set Up Required No Set Up Required
2 Pos.
2 Pos.

Field Logic Determines Normal Position Field Logic Determines Normal Position Tagging:
Specify Flow Pattern

Valves may be
Non Fail-Safe
Non Fail-Safe

(Normally Closed) Master (Actuated) Valve


NC
(Normally Closed)
tagged per customer
0.5 VDC/2 VDC/4mA = Closed NC
specification. ($12.00
Modulating
Modulating

0.5 VDC/2 VDC/4mA = Closed

Master (Actuated) Valve


per tag)
NO (Normally Open)
0.5 VDC/2 VDC/4mA = Open NO (Normally Open) Example:
0.5 VDC/2 VDC/4mA = Open Chiller 1
3rd Floor East
NO/FO (Normally Open/Fail Open) (Normally Open/Fail Open)
Field Logic Determines Normal Position NO/FO Field Logic Determines Normal Position
Master (Actuated) Valve Fails OPEN
Part number for
2 Pos.

Valve Fails OPEN


2 Pos.

(Normally Closed/Fail Closed) (Normally Closed/Fail Closed) tagging: 99981-00101


NC/FC
Field Logic Determines Normal Position NC/FC Field Logic Determines Normal Position
Valve Fails CLOSED Master (Actuated) Valve Fails CLOSED
Specify Flow Pattern

NO/FC (Normally Open/Fail Closed) (Normally Open/Fail Open)


0.5 VDC/2 VDC/4mA = Open NO/FO 0.5 VDC/2 VDC/4mA = Master Valve Open
Fail-Safe

Fail-Safe

Master (Actuated) Valve Fails OPEN


Valve Fails CLOSED
(Normally Closed/Fail Open) (Normally Open/Fail Closed)
5 Complete Ordering Example:
NC/FO
0.5 VDC/2 VDC/4mA = Closed NO/FC 0.5 VDC/2 VDC/4mA = Maser Valve Open F650-150SHP+PRBUP-MFT-T
Modulating

Modulating

Valve Fails OPEN Master (Actuated) Valve Fails CLOSED


(Normally Open/Fail Open) (Normally Closed/Fail Open) Configuration: NO
NO/FO 0.5 VDC/2 VDC/4mA = Master Valve Open NC/FO 0.5 VDC/2 VDC/4mA = Master Valve Closed
Master (Actuated) Valve Fails OPEN Master (Actuated) Valve Fails OPEN Programming: X10
(Normally Closed/Fail Closed) (Normally Closed/Fail Closed)
NC/FC 0.5 VDC/2 VDC/4mA = Master Valve Closed NC/FC 0.5 VDC/2 VDC/4mA = Master Valve Closed
Master (Actuated) Valve Fails CLOSED Master (Actuated) Valve Fails CLOSED
High Performance Butterfly Valve Product Range

2-way Valves Suitable Actuators

Valve Fail-Safe
Nominal Type Non Fail-Safe Spring
Size Electronic
Return
Cv Cv
Inches ANSI 150 2-way ANSI 300 2-way 150 300 150 300 150 300
90° 60°
102 56 2 F650-150SHP F650-300SHP

GM Series

GM Series

GK Series

GK Series
AF Series

AF Series
146 80 2½ F665-150SHP F665-300SHP

PR Series

PR Series
228 125 3 F680-150SHP F680-300SHP Mode of Operation
451 248 4 F6100-150SHP F6100-300SHP High performance butterfly valves are designed for
modulating and isolation service and feature a machined
714 392 5 F6125-150SHP F6125-300SHP

PKR

PKR
seat design and blow out proof solid shaft, providing better
1103 607 6 F6150-150SHP F6150-300SHP torque consistency, which offers longer actuator life and
2064 1135 8 F6200-150SHP F6200-300SHP reduced risk of leakage. Available for a variety of high

SY (2 Year Warranty)
SY Series (2 Year Warranty)
temperature and pressure ratings i.e., ASME/ANSI Class
3517 1934 10 F6250-150SHP F6250-300SHP 300 or 150. Valve sizes range from 2 to 24 inches, with
4837 2660 12 F6300-150SHP F6300-300SHP rangeabilities of 100:1, 0% leakage ratings, and a maximum
valve velocity of 32 FPS.
6857 3592 14* F6350-150SHP F6350-300SHP
9287 4865 16* F6400-150SHP F6400-300SHP Product Features
Unique body seat and double offset disc design ensures
11400 6270 18* F6450-150SHP positive valve sealing to help assure leak free performance
in water applications while maintaining low seating torque.
14420 7590 20* F6500-150SHP
22050 11550 24* F6600-150SHP Actuator Specifications
Note: Cv values listed for ANSI Class 150 Butterfly Valves. Please consult the technical documentation for ANSI Class 300 Cv values Control type on/off, floating point,
and configurations. modulating, 2-10 VDC,
*Call Customer Service at 1-800-543-9038 for product availability. Longer lead times may apply. multi-function technology
(MFT)
Manual override all models
Electrical connection 3 ft. [1 m] cable
terminal block (-T models)
Communication (PR) BACnet MS/TP, NFC,
listed by BTL, Modbus
3-way Valves Suitable Actuators
Tech.Doc - 04/19 - Subject to change. © Belimo Aircontrols (USA), Inc.

Valve Valve Specifications


Electronic Service chilled or hot water,
Nominal Type Non Fail-Safe
Fail-Safe 60% glycol, steam to 50 psi
Size
Flow characteristic F6 modified equal percentage,
Cv Cv unidirectional
Inches ANSI 150 3-way ANSI 300 3-way 150 300 150 300
90° 60° F7 modified linear,
unidirectional
102 56 2 F750-150SHP F750-300SHP
GM Series

GK Series

Sizes 2” to 24”
GM Series

GK Series
PR Series

PR Series

146 80 2½ F765-150SHP F765-300SHP End fitting ASME/ANSI Class 150 or 300


228 125 3 F780-150SHP F780-300SHP Materials
Body carbon steel full lug
PKR

451 248 4 F7100-150SHP F7100-300SHP Disc 316 stainless steel


Shaft 17-4 PH stainless
714 392 5 F7125-150SHP F7125-300SHP
Seat RTFE
1103 607 6 F7150-150SHP F7150-300SHP Gland seal TFE
(2 Year Warranty)

(2 Year Warranty)

Bearings glass backed PTFE


2064 1135 8 F7200-150SHP F7200-300SHP
SY Series

SY Series

Media temp. range -22°F to +400°F


3517 1934 10 F7250-150SHP F7250-300SHP [-30°C to +204°C]
Body pressure rating 150 SHP: ASME/ANSI Class 150
4837 2660 12 F7300-150SHP F7300-300SHP 300 SHP: ASME/ANSI Class 300
6857 3592 14* F7350-150SHP Close-off pressure 150: 285 psi, 300: 600 psi
Rangeability 100:1
9287 4865 16* F7400-150SHP
Maximum velocity 32 FPS
Note: Cv values listed for ANSI Class 150 Butterfly Valves. Please consult the technical documentation for ANSI Class 300 Cv values Leakage 0%
and configurations.
*Call Customer Service at 1-800-543-9038 for product availability. Longer lead times may apply. Double Dead End Service: Utilizes larger retainer ring set
screws to allow the valve to be placed at the end of the line
without a down stream flange in either flow direction while
still holding full pressure.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA


3
Features and Benefits
SHP… Series High Performance Butterfly Valves

Valve Design Features


• Unique seat and disc design provides Bi-Directional bubble tight shutoff at
Belimo SHP... Series Butterfly Valves rated pressure/temperatures
• The Soft Seat design creates a self-energized seal in vacuum-to-low
pressure applications
are designed for use in ANSI Class • Under high pressure conditions, the seat is also designed to permit, confine
and direct movement of the seat against the disc edge, up to the full ANSI
Class 150 or 300 Cold Working Pressures
150 and ANSI Class 300 piping • The Soft Seat is designed for high services with minimal wear and low torque
• Seat replacement is a simple operation, requiring no special tools

systems and are supplied in standard • Valve Body is Full Lug type cast in Carbon Steel
• Disc is cast in CF8M Stainless Steel
• Shaft is 17-4pH Stainless for superior strength
lug style body designs. • Soft Seat is RPTFE for increased wear resistance and low torque
• Top Mounted Gland Flange easily accessible without removing actuator or
mounting brackets
• Double Dead End Service: Utilizes larger retainer ring set screws to allow the valve
to be placed at the end of the line without a down stream flange in either flow
direction while still holding full pressure.
• Metal ID tag on valve neck

KEY BLOW OUT PROOF SHAFT


Square key valve-to-operator connection Solid shaft provides alignment and
provides an externally controlled failure point rigid support for disc.
upon over-torquing.
PACKING GLAND
GLAND FLANGE
Separate part from gland flange,
Applies load against packing gland to prevent
preventing uneven load distribution
external leakage. Fully adjustable.
against packing.
PACKING BEARINGS
Chevron design TFE prevents external leakage Both above and below the disc, bearings are of
out valve neck to full ANSI hydrostatic shell test composite design: PTFE bonded to epoxy-glass
pressures (150% of C.W.P.). filament wound ring. Used to align shaft, with high

Tech.Doc - 04/19 - Subject to change. © Belimo Aircontrols (USA), Inc.


capacity, low wear and low friction coefficient.
WEDGE RING DISC SPACERS
Stainless steel band wedged between valve Disc is centered by use of thrust spacers
body and retainer ring by set screws to lock around shaft in sizes 2” to 5”. Disc position
seat and retainer ring in position on valve sizes stops or thrust bolt arrangements are used for
2” through 30”. Socket head cap screws are larger valve sizes.
used on valve sizes 36”
and larger. WEDGE PINS
Provide positive mechanical
SET SCREWS attachment of disc to shaft.
Cone point screws force wedge BODY
ring outward to lock seat retainer in ANSI B16.34 design in either
position on valve sizes 2” through 30”. wafer or lug configuration.
Socket head cap screws are used on
valve sizes 36” and larger. DISC
360° uninterrupted spherical edge
OVERTRAVEL STOP for sealing. Profile is designed for
Prevents disc from rotating maximum flow and equal percentage
into wrong quadrant. control.

RETAINER RING
Retains seat in valve. Standard surface finish
SOFT-SEAT
is 125 to 200 AARH and is compatible with
Patented bidirectional seat with encapsulated elas-
both standard gaskets and spiral wound
tomeric o-ring core for resiliency. Common seat
gasket designs. Outside diameter is recessed
materials include TFE, RTFE and UHMWPE.
within gasket sealing surface to prevent
external leakage.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

4
SHP Series Butterfly Valves

Average Assembly Weights

ACTUATOR
NON-SPRING RETURN SPRING RETURN ELECTRONIC FAIL-SAFE
Size Valve Max GPM COP GMB(X) 2*GMB(X) 2*AF GK 2*GK
2” F650-150SHP 313 150 24 lbs.
2” F650-150SHP 313 285 18 lbs. 19 lbs.
2½” F665-150SHP 490 150 24 lbs.
2½” F665-150SHP 490 285 18 lbs 19 lbs.
2-way

3” F680-150SHP 705 150 26 lbs.


ANSI 150

3” F680-150SHP 705 285 20 lbs. 21 lbs.


4” F6100-150SHP 1253 150 32 lbs. 33 lbs.
4” F6100-150SHP 1253 150 40 lbs. 42 lbs
2” F750-150SHP 313 285 67 lbs. 69 lbs.
2½” F765-150SHP 490 285 78 lbs. 80 lbs.
3-way

3” F780-150SHP 705 285 88 lbs. 90 lbs.


4” F7100-150SHP 1253 150 135 lbs. 139 lbs.

ACTUATOR
NON-SPRING RETURN SPRING RETURN ELECTRONIC FAIL-SAFE
Size Valve Max GPM COP GMB(X) 2*GMB(X) 2*AF GK 2*GK
2” F650-300SHP 313 150 24 lbs.
2” F650-300SHP 313 285 18 lbs. 19 lbs.
2½” F665-300SHP 490 150 24 lbs.
2½” F665-300SHP 490 285 18 lbs. 19 lbs.
2-way

3” F680-300SHP 705 150 30 lbs.


ANSI 300

3” F680-300SHP 705 285 24 lbs. 25 lbs.


4” F6100-300SHP 1253 150 31 lbs. 32 lbs.
4” F6100-300SHP 1253 285 39 lbs.
2” F750-300SHP 313 285 89 lbs. 94 lbs.
Tech.Doc - 04/19 - Subject to change. © Belimo Aircontrols (USA), Inc.

2½” F765-300SHP 490 285 109 lbs. 114 lbs.


3-way

3” F780-300SHP 705 285 132 lbs. 136 lbs.


4” F7100-300SHP 1253 150 185 lbs. 193 lbs.

Max GPM = Maximum US gallons of water (gpm) per minute, at room temperature, that will flow through the fully open valve without exceeding design velocity limits.

COP = Close-Off Pressure stated in psi. This is the maximum differential pressure the valve will close-off against while maintaining a bubble tight seal.

All SY and PR series actuators are NEMA 4X rated and include 2 auxiliary switches and a heater.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

5
SHP Series Butterfly Valves with Industrial Actuation

Average Assembly Weights

ACTUATOR
NON-SPRING RETURN
Max
Size Valve Model COP PR SY4-110 SY5-110 SY7-110 SY8-110 SY9-110 SY10-110 SY11-110 SY-12-110
GPM
2” F650-150SHP 313 285 30 lbs.
2½” F665-150SHP 490 285 30 lbs.
3” F680-150SHP 705 285 33 lbs.
4” F6100-150SHP 1253 285 45 lbs.
5” F6125-150SHP 1958 285 50 lbs.
6” F6150-150SHP 2820 285 55 lbs.
8” F6200-150SHP 5013 150 80 lbs
8” F6200-150SHP 5013 285 100 lbs.
10” F6250-150SHP 7834 285 146 lbs.
2-way

12” F6300-150SHP 11280 150 182 lbs.


12” F6300-150SHP 11280 285 182 lbs.
14” F6350-150SHP 15354 150 238 lbs.
14” F6350-150SHP 15354 285 269 lbs.
16” F6400-150SHP 20054 285 336 lbs.
18” F6450-150SHP 25381 150 391 lbs.
18” F6450-150SHP 25381 285 391 lbs.
20” F6500-150SHP 31334 150 500 lbs.
20” F6500-150SHP 31334 285 544 lbs.
ANSI 150

24” F6600-150SHP 45121 150 832 lbs.


30” F6750-150SHP 70502 100 1255 lbs.
2” F750-150SHP 313 285 74 lbs.
2½” F765-150SHP 490 285 85 lbs.
3” F780-150SHP 705 285 95 lbs.
4” F7100-150SHP 1253 285 154 lbs.
5” F7125-150SHP 1958 285 200 lbs
6” F7150-150SHP 2820 285 240 lbs
8” F7200-150SHP 5013 285 355 lbs.
10” F7250-150SHP 7834 150 585 lbs.
10” F7250-150SHP 7834 285 585 lbs.
3-way

12” F7300-150SHP 11280 150 785 lbs.


12” F7300-150SHP 11280 285 819 lbs.

Tech.Doc - 04/19 - Subject to change. © Belimo Aircontrols (USA), Inc.


14” F7350-150SHP 15354 285 1118 lbs.
16” F7400-150SHP 20054 150 1469 lbs. 1523 lbs.
18” F7450-150SHP 25381 150 1783 lbs.
18” F7450-150SHP 25381 285 1831 lbs.
20” F7500-150SHP 31334 150 2351 lbs.
20” F7500-150SHP 31334 285 2351 lbs.
24” F7600-150SHP 45121 150 3722 lbs.

Max GPM = Maximum US gallons of water (gpm) per minute, at room temperature, that will flow through the fully open valve without exceeding design velocity limits.

COP = Close-Off Pressure stated in psi. This is the maximum differential pressure the valve will close-off against while maintaining a bubble tight seal.

All SY ans PR series actuators are NEMA 4X rated and include 2 auxiliary switches and a heater.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

6
SHP Series Butterfly Valves with Industrial Actuation

Average Assembly Weights

ACTUATOR
NON-SPRING RETURN
Size Valve Model Max GPM COP PR SY4-110 SY5-110 SY7-110 SY8-110 SY9-110 SY10-110 SY11-110
2” F650-300SHP 313 600 30 lbs.
2½” F665-300SHP 490 600 30 lbs.
3” F680-300SHP 705 600 33 lbs.
4” F6100-300SHP 1253 600 45 lbs.
5” F6125-300SHP 1958 285 50 lbs. 60 lbs.
5” F6125-300SHP 1958 600 62 lbs.
6” F6150-300SHP 2820 285 77 lbs.
6” F6150-300SHP 2820 600 80 lbs.
8” F6200-300SHP 5013 150 110 lbs.
8” F6200-300SHP 5013 600 132 lbs.
8” F6200-300SHP 5013 285 170 lbs.
10” F6250-300SHP 7834 400 170 lbs.
10” F6250-300SHP 7834 600 201 lbs.
10” F6250-300SHP 7834 150 254 lbs.
ANSI 300
2-way

12” F6300-300SHP 11280 285 254 lbs.


12” F6300-300SHP 11280 600 285 lbs.
12” F6300-300SHP 11280 150 379 lbs.
14” F6350-300SHP 15354 400 410 lbs.
14” F6350-300SHP 15354 600 410 lbs.
14” F6350-300SHP 15354 150 487 lbs.
16” F6400-300SHP 20054 285 487 lbs.
16” F6400-300SHP 20054 400 531 lbs.
16” F6400-300SHP 20054 600 531 lbs.
16” F6400-300SHP 20054 150 603 lbs.
18” F6450-300SHP 25381 400 647 lbs.
18” F6450-300SHP 25381 600 647 lbs.
18” F6450-300SHP 25381 150 821 lbs.
20” F6500-300SHP 31334 285 865 lbs.
20” F6500-300SHP 31334 400 865 lbs.
24” F6600-300SHP 45121 150 1150 lbs.
Tech.Doc - 04/19 - Subject to change. © Belimo Aircontrols (USA), Inc.

Max GPM = Maximum US gallons of water (gpm) per minute, at room temperature, that will flow through the fully open valve without exceeding design velocity limits.

COP = Close-Off Pressure stated in psi. This is the maximum differential pressure the valve will close-off against while maintaining a bubble tight seal.

All SY and PR series actuators are NEMA 4X rated and include 2 auxiliary switches and a heater.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

7
SHP Series Butterfly Valves with Industrial Actuation

Average Assembly Weights

ACTUATOR
NON-SPRING RETURN
Max
Size Valve Model COP PR SY4-110 SY5-110 SY7-110 SY8-110 SY9-110 SY10-110 SY11-110 SY-12-110
GPM
2” F750-300SHP 313 400 104 lbs.
2” F750-300SHP 313 600 104 lbs.
2½” F765-300SHP 490 400 124 lbs.
2½” F765-300SHP 490 600 124 lbs.
3” F780-300SHP 705 400 147 lbs.
3” F780-300SHP 705 600 147 lbs.
4” F7100-300SHP 1253 285 222 lbs.
4” F7100-300SHP 1253 600 222 lbs.
5” F7125-300SHP 1958 285 275 lbs.
5” F7125-300SHP 1958 600 301 lbs.
6” F7150-300SHP 2820 285 366 lbs.
6” F7150-300SHP 2820 600 392 lbs.
8” F7200-300SHP 5013 400 579 lbs.
8” F7200-300SHP 5013 600 579 lbs.
8” F7200-300SHP 5013 150 897 lbs.
10” F7250-300SHP 7834 285 897 lbs.
ANSI 300
3-way

10” F7250-300SHP 7834 600 931 lbs.


10” F7250-300SHP 7834 150 1301 lbs.
12” F7300-300SHP 11280 400 1335 lbs.
12” F7300-300SHP 11280 600 1335 lbs.
12” F7300-300SHP 11280 150 1927 lbs.
14” F7350-300SHP 15354 400 1927 lbs.
14” F7350-300SHP 15354 600 1975 lbs.
14” F7350-300SHP 15354 150 2461 lbs.
16” F7400-300SHP 20054 285 2510 lbs.
16” F7400-300SHP 20054 400 2510 lbs.
16” F7400-300SHP 20054 600 2510 lbs.
16” F7400-300SHP 20054 150 3063 lbs.
18” F7450-300SHP 25381 285 3111 lbs.
18” F7450-300SHP 25381 400 3111 lbs.
18” F7450-300SHP 25381 150 4096 lbs.
20” F7500-300SHP 31334 285 4096 lbs.

Tech.Doc - 04/19 - Subject to change. © Belimo Aircontrols (USA), Inc.


24” F7600-300SHP 45121 150 6049 lbs.

Max GPM = Maximum US gallons of water (gpm) per minute, at room temperature, that will flow through the fully open valve without exceeding design velocity limits.

COP = Close-Off Pressure stated in psi. This is the maximum differential pressure the valve will close-off against while maintaining a bubble tight seal.

All SY and PR series actuators are NEMA 4X rated and include 2 auxiliary switches and a heater.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

8
Butterfly Valve Selection-Velocity Chart

150 SHP/300 SHP Series Valves – SHP Series Valves are Flow Direction Specific

MASTER

MASTER
COMMON
MASTER

COMMON

SLAVE
FLOW FLOW FLOW

MASTER

MASTER
COMMON
MASTER

COMMON

SLAVE
FLOW FLOW FLOW
MIXING
MIXING

COMMON
SLAVE SLAVE COMMON
SLAVE SLAVE

COMMON
COMMON
MASTER

MASTER

SLAVE

MASTER
DIVERTING

FLOW FLOW FLOW

COMMON
COMMON
MASTER

MASTER

SLAVE

MASTER
DIVERTING

FLOW FLOW FLOW

COMMON

SLAVE SLAVE COMMON

SLAVE SLAVE

ON/OFF OR ON/OFF OR ON/OFF OR


MOD@2VDC MASTER MOD@2VDC MASTER MOD@2VDC MASTER
CONFIG ON/OFF
MASTEROR VALVE CONFIG ON/OFF
MASTEROR VALVE CONFIG ON/OFF
MASTEROR VALVE
CODE MOD@2VDC
VALVE IS MASTER
@ FAIL CODE MOD@2VDC
VALVE IS MASTER
@ FAIL CODE MOD@2VDC
VALVE IS MASTER
@ FAIL
CONFIG MASTER VALVE CONFIG MASTER VALVE CONFIG MASTER VALVE
M(D)10
CODE OPENIS
VALVE FAIL@INFAIL
PLACE M(D)20
CODE OPENIS
VALVE FAIL@INFAIL
PLACE M(D)30
CODE OPENIS
VALVE FAIL@INFAIL
PLACE
M(D)11
M(D)10 OPEN
OPEN FAILOPEN
IN PLACE M(D)21
M(D)20 OPEN
OPEN FAILOPEN
IN PLACE M(D)31
M(D)30 OPEN
OPEN FAILOPEN
IN PLACE
M(D)12
M(D)11 OPEN
OPEN CLOSED
OPEN M(D)22
M(D)21 OPEN
OPEN CLOSED
OPEN M(D)32
M(D)31 OPEN
OPEN CLOSED
OPEN
M(D)13
M(D)12 CLOSED
OPEN FAIL IN PLACE
CLOSED M(D)23
M(D)22 CLOSED
OPEN FAIL IN PLACE
CLOSED M(D)33
M(D)32 CLOSED
OPEN FAIL IN PLACE
CLOSED
M(D)14
M(D)13 CLOSED
CLOSED FAILOPEN
IN PLACE M(D)24
M(D)23 CLOSED
CLOSED FAILOPEN
IN PLACE M(D)34
M(D)33 CLOSED
CLOSED OPEN
FAIL IN PLACE
M(D)15
M(D)14 CLOSED
CLOSED CLOSED
OPEN M(D)25
M(D)24 CLOSED
CLOSED CLOSED
OPEN M(D)35
M(D)34 CLOSED
CLOSED CLOSED
OPEN
Tech.Doc - 04/19 - Subject to change. © Belimo Aircontrols (USA), Inc.

M(D)15 MIXING,
M Specifies CLOSED CLOSED
D Specifies DIVERTING M(D)25 CLOSED CLOSED M(D)35 CLOSED CLOSED
M Specifies MIXING, D Specifies DIVERTING
Notes:
1. Slave Valve operates inversely of the Master Valve.
Notes:
2. The Master Valve is always located on the run.
1. Slave Valve operates inversely of the Master Valve.
3. The Slave Valve may also have an actuator if required (Direct Coupled).
2. The Master Valve is always located on the run.
4. On/Off actuator normal position is a function of field logic.
3. The Slave Valve may also have an actuator if required (Direct Coupled).
5. Modulating actuator normal position (i.e., fully CW or fully CCW) is set by the direction control switch or field programming via NFC app.
4. On/Off actuator normal position is a function of field logic.
6. All 3-way assemblies are designed for 90 degree actuator rotation.
5. Modulating actuator normal position (i.e., fully CW or fully CCW) is set by the direction control switch or field programming via NFC app.
7. Actuators installed default over Master Valve.
6. All 3-way assemblies are designed for 90 degree actuator rotation.
7. Actuators installed default over Master Valve.
Flow in Std Weight Pipe (Fluid Velocity in GPM). Use with SHP Series BF Valves.
SIZE 4 FPS 8 FPS 12 FPS 16 FPS 20 FPS 24 FPS 28 FPS 32 FPS 36 FPS✕
2” 39 78 118 157 196 235 274 313 353
2½” 61 122 184 245 306 367 428 490 551
3” 88 176 264 353 441 529 617 705 793
4” 157 313 470 627 783 940 1097 1253 1410
5” 245 490 734 979 1224 1469 1714 1958 2203
6” 352 705 1058 1410 1763 2115 2468 2820 3173
8” 627 1253 1880 2507 3133 3760 4387 5013 5640
10” 979 1958 2938 3917 4896 5875 6854 7834 8813
12” 1410 2820 4230 5640 7050 8460 9870 11280 12690
14” 1919 3838 5738 7677 9596 11515 13435 15354 17273
16” 2507 5013 7520 10027 12534 15040 17547 20054 22561
18” 3173 6345 9518 12690 15863 19036 22208 25381 28553
20” 3917 7834 11750 15667 19584 23501 27418 31334 35251
24” 5640 11280 16921 22561 28201 33841 39481 45121 50762
30” 8813 17625 26438 35251 44064 52877 61689 70502 79315
It is not recommended to exceed 32 feet per second through high performance butterfly valves.
Velocities greater than 32 fps may damage the valve.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

9
SY... Series Non-Spring Return Actuator
Dimensions

SY-2~6..
. SY-1..
.

B A
C

C
A
C

D B
SY-9~12..

SY-7~8..
.
B
C
A

Tech.Doc - 04/19 - Subject to change. © Belimo Aircontrols (USA), Inc.


A

Add to Dim A for


MODEL DIM A (MAX) cover removal DIM B DIM C (MAX) DIM D
Inches [mm] Inches [mm] Inches [mm] Inches [mm] Inches [mm]
SY4~6 12.40 [315] 8.86 [225] 9.21 [234] 14.96 [380] 11.81 [300]
SY7~8 16.54 [420] 8.86 [225] 9.21 [234] 17.72 [450] 13.39 [340]
SY9~12 23.23 [590] 8.86 [225] 10.24 [260] 18.50 [470] 13.78 [350]
Note: ~ indicates range of actuator i.e., SY4~6 = SY-4 and SY-6

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

10
Tech.Doc - 04/19 - Subject to change. © Belimo Aircontrols (USA), Inc.

SY1 SY2 SY3 SY4 SY5


[A] [A] [A] [A] [A]
current 1.6 3.4 3.1 9.4 8.9
wire gauge MAX distance between actuator and supply [feet]
18 97 45 50
16 153 72 79 26 28

24 VAC
14 244 115 126 42 44

800-543-9038 USA
12 387 182 200 66 70
10 616 290 318 105 111
8 980 461 506 167 176

SY1 SY2 SY3 SY4 SY5 SY6 SY7 SY8 SY9 SY10 SY11 SY12
[A] [A] [A] [A] [A] [A] [A] [A] [A] [A] [A] [A]
current 0.7 1.2 1.2 2.1 2 2.4 4.2 4.2 3 3.2 3.6 3.8
wire gauge MAX distance between actuator and supply [feet]
18 1,103 644 644 368 386 322 184 184 257 241 215 203
16 1,750 1,021 1,021 583 613 510 292 292 408 383 340 322

120 VAC
14 2,788 1,626 1,626 929 976 813 465 465 651 610 542 514
12 4,428 2,583 2,583 1,476 1,550 1,292 738 738 1,033 969 861 816

866-805-7089 CANADA
10 7,044 4,109 4,109 2,348 2,465 2,054 1,174 1,174 1,644 1,541 1,370 1,298
8 11,204 6,536 6,536 3,735 3,922 3,268 1,867 1,867 2,614 2,451 2,179 2,064

SY1 SY2 SY3 SY4 SY5 SY6 SY7 SY8 SY9 SY10 SY11 SY12
[A] [A] [A] [A] [A] [A] [A] [A] [A] [A] [A] [A]
current 0.4 0.6 0.6 1.1 1 1.1 2 2 2.5 2.6 2.7 2.5
wire gauge MAX distance between actuator and supply [feet]
18 3,701 2,467 2,467 1,346 1,480 1,346 740 740 592 569 548 592
16 5,871 3,914 3,914 2,135 2,348 2,135 1,174 1,174 939 903 870 939

230 VAC
14 9,352 6,234 6,234 3,401 3,741 3,401 1,870 1,870 1,496 1,439 1,385 1,496
12 14,854 9,903 9,903 5,401 5,942 5,401 2,971 2,971 2,377 2,285 2,201 2,377
10 23,626 15,751 15,751 8,591 9,450 8,591 4,725 4,725 3,780 3,635 3,500 3,780
8 37,581 25,054 25,054 13,666 15,033 13,666 7,516 7,516 6,013 5,782 5,568 6,013

203-791-8396 LATIN AMERICA / CARIBBEAN


The NEC mandates that 24 VAC over 100 VA power requires CLASS 1 wiring conduit. Local codes may vary. Do NOT mix CLASS 1 & CLASS 2 circuits in the same conduit. Gener-
ally, 24 VAC actuators over 100 VA should be changed to 120 VAC models.

11
On/Off
Wire Size vs. Length of Run for SY Series Actuators
12
SY1 SY2 SY3 SY4 SY5
[A] [A] [A] [A] [A]
current 2.8 3.4 3.1 9.4 8.9
wire gauge
Modulating

MAX distance between actuator and supply [feet]


18 55 45 50
16 88 72 79 26 28

24 VAC
14 139 115 126 42 44

800-543-9038 USA
12 221 182 200 66 70
10 352 290 318 105 111
8 560 461 506 167 176

SY1 SY2 SY3 SY4 SY5 SY6 SY7 SY8 SY9 SY10 SY11 SY12
[A] [A] [A] [A] [A] [A] [A] [A] [A] [A] [A] [A]
current 0.6 0.8 0.7 2.1 1.9 2 2 2.8 2.7 3 4.3 4.5
wire gauge MAX distance between actuator and supply [feet]
18 1,287 966 1,103 368 407 386 386 276 286 257 180 172
16 2,042 1,531 1,750 583 645 613 613 438 454 408 285 272

120 VAC
14 3,253 2,440 2,788 929 1,027 976 976 697 723 651 454 434
12 5,167 3,875 4,428 1,476 1,632 1,550 1,550 1,107 1,148 1,033 721 689
Wire Size vs. Length of Run for SY Series Actuators

866-805-7089 CANADA
10 8,218 6,163 7,044 2,348 2,595 2,465 2,465 1,761 1,826 1,644 1,147 1,096
8 13,072 9,804 11,204 3,735 4,128 3,922 3,922 2,801 2,905 2,614 1,824 1,743

SY1 SY2 SY3 SY4 SY5 SY6 SY7 SY8 SY9 SY10 SY11 SY12
[A] [A] [A] [A] [A] [A] [A] [A] [A] [A] [A] [A]
current 0.4 0.4 0.4 1.1 1 1 1.2 1.6 1.1 1.4 2.2 2.5
wire gauge MAX distance between actuator and supply [feet]
18 3,701 3,701 3,701 1,346 1,480 1,480 1,234 925 1,346 1,057 673 592
16 5,871 5,871 5,871 2,135 2,348 2,348 1,957 1,468 2,135 1,677 1,067 939

230 VAC
14 9,352 9,352 9,352 3,401 3,741 3,741 3,117 2,338 3,401 2,672 1,700 1,496
12 14,854 14,854 14,854 5,401 5,942 5,942 4,951 3,713 5,401 4,244 2,701 2,377
10 23,626 23,626 23,626 8,591 9,450 9,450 7,875 5,906 8,591 6,750 4,296 3,780
8 37,581 37,581 37,581 13,666 15,033 15,033 12,527 9,395 13,666 10,738 6,833 6,013

203-791-8396 LATIN AMERICA / CARIBBEAN


The NEC mandates that 24 VAC over 100 VA power requires CLASS 1 wiring conduit. Local codes may vary. Do NOT mix CLASS 1 & CLASS 2 circuits in the same conduit. Gener-
ally, 24 VAC actuators over 100 VA should be changed to 120 VAC models.

Tech.Doc - 04/19 - Subject to change. © Belimo Aircontrols (USA), Inc.


Butterfly Valve Actuators

Power Supply 24 VAC/VDC Single Phase


Speed Current Draw VA
Model # Torque Override Weight
50 Hz/60 Hz (60 Hz) (60 Hz)
PRBUP-3-T* 1400 in-lbs/ 160 Nm 35 seconds 0.8 A 20 Manual override crank 5.8 kg/12.8 lbs.
PRXUP-3-T* 1400 in-lbs/ 160 Nm 35, 30-120 seconds 0.8 A 20 Manual override crank 5.8 kg/12.8 lbs.
SY4-24 3540 in-lbs/ 400 Nm 16 seconds 9.5 A 228 Hand wheel 22 kg/48.5 lbs.
SY5-24 4430 in-lbs/ 500 Nm 35 seconds 9.4 A 227 Hand wheel 22 kg/48.5 lbs.

Power Supply 120 VAC Single Phase


Current Draw VA
Model # Torque Speed 60 Hz Override Weight
(60 Hz) (60 Hz)
PRBUP-3-T* 1400 in-lbs/ 160 Nm 35 seconds 0.2 A 23 Manual override crank 5.8 kg/12.8 lbs.
PRXUP-3-T* 1400 in-lbs/ 160 Nm 35, 30-120 seconds 0.2 A 23 Manual override crank 5.8 kg/12.8 lbs.
SY4-110 3540 in-lbs/ 400 Nm 18 seconds 1.8 A 216 Hand wheel 22 kg/48.5 lbs.
SY5-110 4430 in-lbs/ 500 Nm 25 seconds 1.8 A 216 Hand wheel 22 kg/48.5 lbs.
SY6-110 5750 in-lbs/ 650 Nm 32 seconds 1.8 A 216 Hand wheel 22 kg/48.5 lbs.
SY7-110 8850 in-lbs/ 1000 Nm 49 seconds 3.5 A 420 Hand wheel 36 kg/79.5 lbs.
SY8-110 13280 in-lbs/ 1500 Nm 50 seconds 4.8 A 576 Hand wheel 36 kg/79.5 lbs.
SY9-110 17700 in-lbs/ 2000 Nm 57 seconds 2.8 A 336 Hand wheel 72 kg/176.4 lbs.
SY10-110 22130 in-lbs/ 2500 Nm 62 seconds 2.9 A 348 Hand wheel 72 kg/176.4 lbs.
SY11-110 26550 in-lbs/ 3000 Nm 69 seconds 3.6 A 432 Hand wheel 72 kg/176.4 lbs.
SY12-110 30980 in-lbs/ 3500 Nm 60 seconds 3.8 A 456 Hand wheel 72 kg/176.4 lbs.
Tech.Doc - 04/19 - Subject to change. © Belimo Aircontrols (USA), Inc.

Power Supply 230 VAC Single Phase


Current Draw VA
Model # Torque Speed 60 Hz Override Weight
(60 Hz) (60 Hz)
PRBUP-3-T* 1400 in-lbs/ 160 Nm 35 sec. 0.2 A 52 Manual override crank 5.8 kg/12.8 lbs.
PRXUP-3-T* 1400 in-lbs/ 160 Nm 35, 30-120 sec. 0.2 A 52 Manual override crank 5.8 kg/12.8 lbs.
SY4-220 3540 in-lbs/ 400 Nm 18 seconds 0.9 A 207 Hand wheel 22 kg/48.5 lbs.
SY5-220 4430 in-lbs/ 500 Nm 25 seconds 0.9 A 207 Hand wheel 22 kg/48.5 lbs.
SY6-220 5750 in-lbs/ 650 Nm 31 seconds 0.9 A 207 Hand wheel 22 kg/48.5 lbs.

*-200 and -250 versions have the same ratings.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

13
Butterfly Valve Actuators

Power Supply 24 VAC/VDC Single Phase


Speed Current Draw VA
Model # Torque Override Weight
50 Hz/60 Hz (60 Hz) (60 Hz)
PRBUP-MFT-T* 1400 in-lbs/160 Nm 30-120 sec. 0.9 A 20 Manual override crank 5.8 kg/12.8 lbs.
PRXUP-MFT-T* 1400 in-lbs/160 Nm 30-120 sec. 0.9 A 20 Manual override crank 5.8 kg/12.8 lbs.
PKRXUP-MFT-T* 1400 in-lbs/160 Nm 30-120 sec. 2.2 A 55 Manual override crank 6.4 kg/14.1 lbs.
SY4-24MFT 3540 in-lbs/ 400 Nm 16 seconds 11.0 A 264 Hand wheel 22 kg/48.5 lbs.
SY5-24MFT 4430 in-lbs/ 500 Nm 30 seconds 10.2 A 245 Hand wheel 22 kg/48.5 lbs.

Power Supply 120 VAC Single Phase


Speed Current Draw VA
Model # Torque Override Weight
60 Hz (60 Hz) (60 Hz)
PRBUP-MFT-T* 1400 in-lbs/160 Nm 30-120 sec. 0.2 A 23 Manual override crank 5.8 kg/12.8 lbs.
PRXUP-MFT-T* 1400 in-lbs/160 Nm 30-120 sec. 0.2 A 23 Manual override crank 5.8 kg/12.8 lbs.
PKRXUP-MFT-T* 1400 in-lbs/160 Nm 30-120 sec. 0.3 A 43 Manual override crank 6.4 kg/14.1 lbs.
SY4-120MFT 3540 in-lbs/ 400 Nm 17 seconds 2.4 A 288 Hand wheel 22 kg/48.5 lbs.
SY5-120MFT 4430 in-lbs/ 500 Nm 21 seconds 2.3 A 276 Hand wheel 22 kg/48.5 lbs.
SY6-120MFT 5750 in-lbs/ 650 Nm 29 seconds 2.2 A 264 Hand wheel 22 kg/48.5 lbs.
SY7-120MFT 8850 in-lbs/ 1000 Nm 44 seconds 1.7 A 204 Hand wheel 36 kg/79.5 lbs.
SY8-120MFT 13280 in-lbs/ 1500 Nm 48 seconds 2.6 A 312 Hand wheel 36 kg/79.5 lbs.
SY9-120MFT 17700 in-lbs/ 2000 Nm 47 seconds 3.4 A 408 Hand wheel 72 kg/176.4 lbs.
SY10-120MFT 22130 in-lbs/ 2500 Nm 51 seconds 4.0 A 480 Hand wheel 72 kg/176.4 lbs.
SY11-120MFT 26550 in-lbs/ 3000 Nm 56 seconds 3.0 A 360 Hand wheel 72 kg/176.4 lbs.
SY12-120MFT 30980 in-lbs/ 3500 Nm 62 seconds 3.4 A 408 Hand wheel 72 kg/176.4 lbs.

Tech.Doc - 04/19 - Subject to change. © Belimo Aircontrols (USA), Inc.


Power Supply 230 VAC Single Phase
Speed Current Draw VA
Model # Torque Override Weight
60 Hz (60 Hz) (60 Hz)
PRBUP-MFT-T* 1400 in-lbs/160 Nm 30-120 sec. 0.1 A 52 Manual override crank 5.8 kg/12.8 lbs.
PRXUP-MFT-T* 1400 in-lbs/160 Nm 30-120 sec. 0.1 A 52 Manual override crank 5.8 kg/12.8 lbs.
PKRXUP-MFT-T* 1400 in-lbs/160 Nm 30-120 sec. 0.2 A 68 Manual override crank 6.4 kg/14.1 lbs.
SY4-230MFT 3540 in-lbs/ 400 Nm 17 seconds 1.1 A 253 Hand wheel 22 kg/48.5 lbs.
SY5-230MFT 4430 in-lbs/ 500 Nm 22 seconds 1.0 A 230 Hand wheel 22 kg/48.5 lbs.
SY6-230MFT 5750 in-lbs/ 650 Nm 32 seconds 1.1 A 253 Hand wheel 22 kg/48.5 lbs.
SY7-230MFT 8850 in-lbs/ 1000 Nm 44 seconds 0.8 A 184 Hand wheel 36 kg/79.5 lbs.
SY8-230MFT 13280 in-lbs/ 1500 Nm 57 seconds 1.4 A 322 Hand wheel 36 kg/79.5 lbs.
SY9-230MFT 17700 in-lbs/ 2000 Nm 61 seconds 1.1 A 253 Hand wheel 72 kg/176.4 lbs.
SY10-230MFT 22130 in-lbs/ 2500 Nm 70 seconds 1.4 A 322 Hand wheel 72 kg/176.4 lbs.
SY11-230MFT 26550 in-lbs/ 3000 Nm 48 seconds 1.9 A 437 Hand wheel 72 kg/176.4 lbs.
SY12-230MFT 30980 in-lbs/ 3500 Nm 51 seconds 2.0 A 460 Hand wheel 72 kg/176.4 lbs.

*-200 and -250 versions have the same ratings.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

14
WAR NING Interface Wiring Detail
SYx-MFT, 24V, 120/230V

Actuators: SYx-MFT
CAUTION
WAR NING INSTALLATION NOTES

Notes:
INSTALLATION NOTES 1. Motor CAMS have been factory calibrated and should not be moved.
2. An adaption must be performed if any limit switch is adjusted. This will
calibrate the beginning and end stopping points. Press the adaption
CAUTION button for 3 seconds and release.
3. New SY actuators must have an adaption performed before operation.
PC Tool Service Jack Connection

C
APPLICATION NOTES
APPLICATION NOTES

C C
C Power Supply Com -
Control Signal +
Control Signal -
C
C Power Supply Hot +

FDBK +
FDBK -
C
Adaption
C
C

Direction of Rotation 24V


Tech.Doc - 04/19 - Subject to change. © Belimo Aircontrols (USA), Inc.

N - Power Supply Common


H - Power Supply Hot
C
C

WAR NING
Control Signal +
C
C INSTALLATION NOTES
Control Signal -
FDBK +
FDBK -
C
C C PC Tool Service Jack

CAUTION
C Adaption
C

APPLICATION NOTES
Direction of Rotation
120/230V

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

15
SY… SeriesWNon-Spring
AR NING Actuators

C AU TION
Electrical Travel Adjustment Factory pre-set see chart below. Field adjustable if required

SY4-12 LS4
Auxiliary Switch for Closed Indication
INSTALLATION NOTES LS3
Auxiliary Switch for Opened Indication
LS4
LS3
Factory pre-set and calibrated. Do not adjust without consulting factory. This will
LS2
void the warranty
LS1

APP LIC ATION NOTES LS2 Clockwise Decrease Closed Angle


“CLOSE”
Counter-clockwise Increase Closed Angle

W AR NING
W AR NING LS1 Clockwise Increase Opening Angle
“OPEN”
Counter-clockwise Decrease Opening Angle

F
W AR NING Switches at left are shown with actuator fully open.
W AR NING E
0° 5° 85° 90°
W AR NING D LS4
LS3 A - B A-C
C
C AU TION B 0° 5° 85° 90°
C AU TION
A LS4 D - F D-E
LS3
W AR NING
Notes:
1. An adaption must be performed when the limit switches are adjusted. For the SYx-MFT

Tech.Doc - 04/19 - Subject to change. © Belimo Aircontrols (USA), Inc.


INSTALLATION NOTES actuators. This will calibrate the beginning and end stopping points. Press the adaption
INSTALLATION NOTES
button for 3 seconds and release.
C AU TION 2. Contact Technical Support if travel adjustment is required.

APP LIC ATION NOTES


INSTALLATION INSTALLATION NOTES
W AR NINGAPP LIC ATION NOTES

APP LIC ATION NOTES


U TION

APP LIC ATION NOTES

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

16
Wiring
On/Off, 24V, 120/230V

Actuators: SY4...12-110 SY4...12-220


SY Actuator Wiring Diagram, SY1…5-24 – On/Off
SY1…12-110 (220) On/Off

W546
Hazard Identification
INSTALLATION NOTES
Warnings and Cautions appear at appropriate sections throughout
this manual. Read these carefully.
Observe class 1 and class 2 wiring restrictions.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, Transformer sizing = SY actuator draw X 1.25 (safety margin)
may result in minor or moderate injury. It may also be used to (Ex. SY2-24 requires 3.0A x 1.25 = 3.75A,
alert against unsafe practices. 3.75A X 24 VAC = 90VA Transformer).
Indicates an action or condition that may cause irreversible
damage to the actuator(s) or associated equipment.
Equipment damage! NOTES SY4...12-110 (220)
SY1…12-110 (220)
Power consumption and input impedance must be observed.
• Caution: Power Supply Voltage
• Isolation relays must be used in parallel connection of multiple actuators
NOTES SY4...5-24
SY1…5-24 using a common control signal input.
• "H" (L2) cannot be connected to terminal #3 and #4 simultaneously.
Each actuator should be powered by a single, isolated • Required: Terminal #7 needs to be field wired to enable heater circuit.
33 control transformer.

• Isolation relays must be used in parallel connection of multiple actuators


using a common control signal input.
• "H" cannot be connected to terminal #3 and #4 simultaneously.
• Required: Terminal #7 needs to be field wired to enable heater circuit.

33 24 VAC Transformer G G Ground 120 and 230 VAC


G G Ground

1 Common N L1 1 Common
Line Open Open
Volts
3 Open H L2 3 Open
Tech.Doc - 04/19 - Subject to change. © Belimo Aircontrols (USA), Inc.

4 Closed Close
4 Closed
Close
5 Connect to #1 for fully
open indication
5 Connect to #1 for fully
open indication

6 Connect to #1 for fully


closed indication
6 Connect to #1 for fully
closed indication

7 HTR 7 HTR

A A
LS3 LS3
B B
A-C (Open Indication) A-C (Open Indication)
C C
D D
LS4 LS4
E E
D-F (Closed Indication) D-F (Closed Indication)
F F
Contact Rating: 5A 250 VAC Max. Contact Rating: 5A 250 VAC Max.

SY2…5-24
SY4...5-24 SY4...12-110
SY2…12-110 (220)

A LS3 A LS3

B B
A-B (Open Indication) A-B (Open Indication)
C Contact Rating: 5A 125 VAC Max.
C Contact Rating: 5A 125 VAC Max.
3A 250 VAC Max. 3A 250 VAC Max.
E LS4
E LS4

F A-E (Closed Indication)


F A-E (Closed Indication)

SY1-24 SY1-110 (220)


SY1 Contact Arrangements

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

W546 17
Wiring for Multiple SY
On/Off, 24V, 120/230V
Wiring for Multiple SY
On/Off, 24V, 120/230V
Actuators: SY4...5-24 SY4...12-110 SY4...12-220

Actuators: SY4...5-24 SY4...12-110 SY4...12-220

Hazard Identification INSTALLATION NOTES


Warnings and Cautions appear at appropriate sections throughout this
manual. Read these carefully. Observe class 1 and class 2 wiring restrictions.
Transformer sizing = SY actuator draw X 1.25 (safety margin)
CAUTION
(Ex. SY2-24 requires 3.0A x 1.25 = 3.75A,
Indicates a potentially hazardous situation which, if not avoided, may result in 3.75A X 24 VAC = 90VA Transformer).
minor or moderate injury. It may also be used to alert against unsafe practices.

Indicates an action or condition that may cause irreversible damage to the


actuator(s) or associated equipment. NOTES
Equipment damage! • Caution: Power Supply Voltage.
Power consumption and input impedance must be observed. • Isolation relays must be used in parallel connection of multiple actuators
using a common control signal input.
• "H" (L2) cannot be connected to terminal #3 and #4 simultaneously.
• Required: Terminal #7 needs to be field wired to enable heater circuit.

24 VAC Transformer G Actuator B


G Actuator B
G Ground 120 and 230 VAC G Ground

Line 1 Common N L1 1 Common


Volts Open K1 Open K1
3 Open 3 Open
H L2
4 Closed 4 Closed
Close K1-B Close K1-B
5 5
6 6
7 HTR 7 HTR

A A
LS3 LS3
B B
A-C (Open Indication) A-C (Open Indication)
C C
D D
LS4 LS4
E E

71150-00001.D 01/17 - Subject to change. © Belimo Aircontrols (USA), Inc.


D-F (Closed Indication) D-F (Closed Indication)
F F
Contact Rating: 5A 250 VAC Max. Contact Rating: 5A 250 VAC Max.

SY4…5-24 SY4…12-110 (220)

Tech.Doc - 04/19 - Subject to change. © Belimo Aircontrols (USA), Inc.


G Actuator A G Actuator A
G Ground G Ground

1 Common 1 Common
3 Open 3 Open
4 Closed 4 Closed
K1-A K1-A
5 5
6 6
7 HTR 7 HTR

A LS3 A LS3
B B
A-C (Open Indication) A-C (Open Indication)
C C
D D
LS4 LS4
E E
D-F (Closed Indication) D-F (Closed Indication)
F F
Contact Rating: 5A 250 VAC Max. Contact Rating: 5A 250 VAC Max.

SY4…5-24 SY4…12-110 (220)

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA


800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
12
18
Wiring
Proportional, 24V, 120/230V
W547_2
Actuator: SY2…5-24MFT SY2...12-120MFT SY2...12-230MFT
W547_2 Actuator: SY2…5-24MFT SY2...12-120MFT SY2...12-230MFT
Actuators: SY4...5-24MFT SY4...12-120MFT SY4...12-230MFT
Hazard Identification INSTALLATION NOTES
Hazard Identification

W547-2
Warnings and Cautions appear at appropriate sections throughout INSTALLATION NOTES
thisWarnings
manual. Read these carefully.
and Cautions appear at appropriate sections throughout Observe Class 1 and Class 2 wiring restrictions.
this
CAUTION manual. Read these carefully. Observe Class
Transformer sizing1=and
SY Class 2 wiring
actuator draw restrictions.
X 1.25 (safety margin)
CAUTION
Indicates a potentially hazardous situation which, if not avoided, (Ex.Transformer
SY2-24 requires 3.0A x 1.25 = 3.75A,
sizing = SY actuator draw X3.75A
1.25 X(safety
24 VAC = 90VA Transformer)
margin)
mayIndicates
result inaminor or moderate
potentially injury.
hazardous It maywhich,
situation also beif used to
not avoided, (Ex. SY2-24 requires 3.0A x 1.25 = 3.75A, 3.75A X 24 VAC = 90VA Transformer)
alertmay
against
resultunsafe practices.
in minor or moderate injury. It may also be used to
alert against
Indicates unsafe
an action practices. that may cause irreversible
or condition APPLICATION NOTES
damage to the
Indicates anactuator(s) or associated
action or condition equipment.
that may cause irreversible APPLICATION NOTES
Ground shielded wire at control panel chassis.
damagedamage!
Equipment to the actuator(s) or associated equipment. 34 Tape back ground
Ground at wire
shielded actuator.
at control panel chassis.
Power consumption and input impedance must be observed.
Equipment damage! 34
36 UseTape back ground
of feedback at actuator.
is optional.
Power consumption and input impedance must be observed.
36 Use of feedback is optional.

NOTES SY2...5-24MFT NOTES SY2...12-120MFT (230MFT)


Each NOTES SY4...5-24MFT
SY2...5-24MFT
actuator should be powered by a single, isolated NOTES SY4...12-120 (230MFT)
SY2...12-120MFT (230MFT)
33 • Caution: Power supply voltage.
control
Eachtransformer.
actuator should be powered by a single, isolated
33 • Caution: Power supply voltage.
• Power control transformer. and Control Signal "–" wiring to a common is
supply Com/Neutral
prohibited.
• Power supply Com/Neutral and Control Signal "–" wiring to a common is
prohibited.

A Internal Use Only

B A Internal
Internal UseUse
OnlyOnly
PC Tool Internal
1 B Internal UseUse
OnlyOnly
Service Jack
PC Tool 1 Internal Use Only
Service Jack
2 Internal Use Only

3 2 Internal
Internal UseUse
OnlyOnly

Control Signal (+) Y ┴ /- 3 Internal


Power SupplyUse Only
Com
Control Signal 24VAC
Control
Control Signal
Signal (-) (+) Y ~/+ ┴ /- Power
Power Supply
Supply Hot Com
┴1
Control Signal 24VAC
Address ~/+ Power Supply Hot
Feedback Signal
Control (+) (-)
Signal U5 ┴ 1
Feedback 33
Address
Feedback Signal (+) U5
Feedback Feedback Signal (-) ┴2 8 Internal Use Only 33
Adaption
36 34 Feedback Signal
Not Used - (-) C1 ┴ 2 9 8 Internal
Internal UseUse
OnlyOnly
Adaption
36 34 Not Not
UsedUsed
- - C2 C1 10 9 Internal
Internal UseUse
OnlyOnly
Y2 Y1 SYx-24MFT
Tech.Doc - 04/19 - Subject to change. © Belimo Aircontrols (USA), Inc.

Not Used - C2 10 Internal Use Only


Y2 Y1 SYx-24MFT

G PE

G PE

Power Supply Com – 120v (N) / 230v (L1)


Power
Power Supply
Supply HotCom – 120v
– 120v (H) /(N) / 230v
230v (L2) (L1)
Power Supply Hot – 120v (H) / 230v (L2)

A Internal Use Only


N L
B A Internal
Internal Use Use
OnlyOnly
PC Tool N L
Control Signal (+) Y Service Jack 1 B Internal
Internal Use Use
OnlyOnly
Control Signal PC Tool
Control
Control Signal
Signal (-) (+) ┴1 Y Service Jack 2 1 Internal
Internal Use Use
OnlyOnly
Control Signal
Control
Feedback Signal
Signal (+) (-) U5 ┴1 3 2 Internal
Internal Use Use
OnlyOnly
Feedback
Feedback
Feedback Signal
Signal (-) (+) ┴ 2 U5 3 Internal Use Only
36Feedback
Feedback Signal
Not Used - (-) C1 ┴2
34
36
Not Used
Not Used - - C2 C1
34 Adaption Address
Not Used - C2
Adaption Address
8 Internal Use Only
A LS3
Y1
9 8 Internal
Internal Use Use
OnlyOnly
B A LS3
SYx-120MFT
Y2
Y1
10 9 Internal
Internal Use Use
OnlyOnly
C B
A-B (Open Indication) SYx-230MFT Y2
SYx-120MFT
Contact Rating: 5A 125 VAC Max. 10 Internal Use Only
A-B (Open Indication)
3A 250 VAC Max. SYx-230MFT
E C
G PE
Contact Rating: 5A 125 VAC Max.
LS4
3A 250 VAC Max. G PE
F E LS4
A-E (Closed Indication)

FSY4...5-24MFT
SY2...5-24MFT
A-E (Closed Indication)

SY2...5-24MFT
SY4...12-120
SY2...12-120MFT
(230MFT)
(230MFT)
SY2...12-120MFT
(230MFT)
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

19
Wiring
Proportional, Multiple Wiring, 24V

Actuators: SY4...5-24MFT
W550_2

Actuators: SY2...5-24MFT

W550-2
Hazard Identification
INSTALLATION NOTES
Warnings and Cautions appear at appropriate
sections throughout this manual. Read these carefully.
Observe class 1 and class 2 wiring restrictions.

CAUTION Transformer sizing = SY actuator draw X 1.25 (safety margin)


Indicates a potentially hazardous situation which, if (Ex. SY2-24 requires 3.0A x 1.25 = 3.75A,
not avoided, may result in minor or moderate injury. 3.75A X 24 VAC = 90VA Transformer).
It may also be used to alert against unsafe practices.

NOTES SY4...5-24MFT
SY2...5-24MFT
Indicates an action or condition that may cause
irreversible damage to the actuator(s) or Each actuator should be powered by a single, isolated
33 control transformer.
associated equipment.

Equipment damage!
Power consumption and input impedance
must be observed. APPLICATION NOTES
Recommended twisted shielded pair for control wiring.
35 Ground shielded wire at control panel chassis.
Tape back ground at actuator.

36 Use of feedback is optional.

Actuator A
A Internal Use Only

B Internal Use Only


PC Tool 1 Internal Use Only
Service Jack

2 Internal Use Only

3 Internal Use Only

Control Signal (+) Y ┴ /- Power Supply Com


24VAC
Control Signal (-) ┴1 ~/+ Power Supply Hot

Feedback Signal (+) U5 Address 33


Feedback

Tech.Doc - 04/19 - Subject to change. © Belimo Aircontrols (USA), Inc.


Feedback Signal (-) ┴2 8 Internal Use Only
36
35 Adaption
Not Used - C1 9 Internal Use Only

Not Used - C2 10 Internal Use Only


Y1 Y2
SYx-24MFT

G PE

Actuator B
A Internal Use Only

B Internal Use Only


PC Tool 1 Internal Use Only
Service Jack

2 Internal Use Only

3 Internal Use Only

Control Signal (+) Y ┴ /- Power Supply Com


Control Signal 24VAC
Control Signal (-) ~/+ Power Supply Hot
┴1

Feedback Signal (+) U5 Address 33


Feedback

A 36
Feedback Signal (-) ┴2
Adaption
8 Internal Use Only
LS3 35 Not Used - C1 9 Internal Use Only
B Not Used - C2 10 Internal Use Only
A-C (Open Indication) Y1 Y2
SYx-24MFT

C
D
LS4 G PE

E
D-F (Closed Indication)
F
Contact Rating: 5A 250 VAC Max.

SY4...5-24MFT
SY2…5-24MFT

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

20
Wiring for Multiple SY
Proportional, Multiple Wiring, 120/230V

Actuators: SY4...12-120MFT SY4...12-230MFT


W552_2
W552-2

Actuators: SY2...12-120MFT SY2...12-230MFT

Hazard Identification INSTALLATION NOTES


Warnings and Cautions appear at appropriate
sections throughout this manual. Read these carefully.
Observe class 1 and class 2 wiring restrictions.

CAUTION
Indicates a potentially hazardous situation which, if
not avoided, may result in minor or moderate injury. APPLICATION NOTES
It may also be used to alert against unsafe practices.
Recommended twisted shielded pair for control wiring.
35
Indicates an action or condition that may cause Ground shielded wire at control panel chassis.
irreversible damage to the actuator(s) or Tape back ground at actuator.
associated equipment. 36 Use of feedback is optional.

Equipment damage!
Power consumption and input impedance
must be observed. NOTES SY4...12-120 (230MFT)
SY2...12-120MFT (230MFT)
• Caution: Power supply voltage.

Power Supply Com – 120V (N) / 230V (L1)


Power Supply Hot – 120V (H) / 230V (L2)

A Internal Use Only


N L
B Internal Use Only
PC Tool
Control Signal (+) Y Service Jack 1 Internal Use Only

Control Signal (-) ┴1 2 Internal Use Only

Feedback Signal (+) U5 3 Internal Use Only


Feedback
Feedback Signal (-) ┴2
36
Not Used - C1
35
Not Used - C2
Adaption Address
Tech.Doc - 04/19 - Subject to change. © Belimo Aircontrols (USA), Inc.

8 Internal Use Only


Y1
9 Internal Use Only
Y2
G PE SYx-120MFT
Actuator A 10 Internal Use Only
SYx-230MFT

Power Supply Com – 120V (N) / 230V (L1)


Power Supply Hot – 120V (H) / 230V (L2)

A Internal Use Only


N L
B Internal Use Only
PC Tool
Control Signal (+) Y Service Jack 1 Internal Use Only
Control Signal
Control Signal (-) ┴1 2 Internal Use Only

Feedback Signal (+) U5 3 Internal Use Only


Feedback
Feedback Signal (-) ┴2
36
Not Used - C1
35
A Not Used - C2
Adaption Address
LS3
B 8 Internal Use Only
A-C (Open Indication)
C 9 Internal Use Only
Y1
Y2
SYx-120MFT
G PE Actuator B 10 Internal Use Only
SYx-230MFT
D
LS4
E
D-F (Closed Indication)
F
Contact Rating: 5A 250 VAC Max.

SY4...12-120MFT
SY2...12-120MFT
SY4...12-230MFT
SY2...12-230MFT

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

21
Installation Recommendations
SHP Series Butterfly Valves

Valve Design Pipe Schedule Compatibility


1. The SHP Series High Performance Butterfly Valve features a double The SHP valve is designed to allow the disc edge to rotate into the open
offset (or, double eccentric) shaft design to minimize seat abrasion position without interference with the pipeline I.D. in the following pipe
and lower torque. This double offset design allows the disc to lift off schedules:
and “cam” away from the seat as it rotates open. SIZE ANSI 150 ANSI 300
2. The SHP valve always rotates clockwise to close (when viewed from 2” - 12” SCH 80 SCH 80
above) and counterclockwise to open. 14” - 24” SCH 40 SCH 80
3. The valve body has an Overtravel Stop which prevents 30” SCH 30 SCH 80
36” - 42” STD WT
the disc from over rotating into the wrong quadrant. This stop is not
48” XS
to be used as a disc position stop; if the disc contacts the Overtravel
Stop, this means it has rotated beyond the seat.
4. The SHP valve is bidirectional, but the preferred installation position Product Identification
is with the seat in the upstream position (SUS). Note the arrow on
the metal tag attached to the valve body. 1. Every SHP valve has a metal identification tag attached to the valve
body. Information includes the Figure Number, the Size and Pressure
Class, the Materials of Construction, and the Operating Pressures and
Safety Precautions Temperatures.
1. Be sure the line is depressurized and drained. 2. Every SHP valve is hydrostatically tested before it is shipped. The
2. Be sure of the pipeline media. Proper care should be taken for metal tag also includes a Serial Number; this number, unique for
protection against toxic and/or flammable fluids. each valve, is recorded by the Belimo Quality Control Department
along with the test results and material certification data, for
3. Never install the valve without an Operator (Manual or Automatic)
individual traceability and verification of every valve produced.
already attached to the valve shaft.
4. Never remove the Operator from the valve while the valve is in the

PreferredFlowrate
pipeline under pressure.
5. Always be sure that the disc is in the full-closed position before SHP series
installing the valve. valves have a
preferred flow
6. Take care in handling the valve. Treat this valve as a piece of
direction.
machinery.

Flange Compatibility
The SHP valve is designed to fit between flanges as follows: UNPACKING AND STORAGE INSTRUCTIONS

ANSI Class 150 2” to 24” 1. Check the packing list against the valve received to verify that the
quantities, sizes and materials are correct.

Tech.Doc - 04/19 - Subject to change. © Belimo Aircontrols (USA), Inc.


MSS SP-44 Class 150 30” to 48”
ANSI B16.47 Class 150 A Flanges 2. Check to make sure that the valve and operator were not damaged
ANSI Class 300 2” to 24” during shipment.
MSS SP-44 Class 300 30” 3. If the valve is to be stored before being installed, it should be
protected from harsh environmental conditions.
ANSI B16.47 Class 200 A Flanges
4. Store the valve with the disc in the closed position to protect the
sealing edge and the seat.
Gasket Compatibility 5. Keep the valve in a clean location, away from dirt, debris and
corrosive materials.
The SHP valve is designed to accommodate the use of standard fiber
gaskets (such as non-asbestos, flexible graphite, asbestos or equivalent 6. Keep the valve in a dry area with the flange protectors attached.
gasket materials) of 1/16” or less, meeting the dimensional 7. Keep the valve in a cool location if possible, out of direct sunlight.
requirements of ANSI B16.21-1978. Thick elastomeric gaskets are not 8. If not in use, exercise the butterfly valve (full open and close) at least
recommended. Metallic wound (Flexitallic) gaskets may also be used. once a month.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

22
Installation Recommendations
SHP Series Butterfly Valves

SHP Series Butterfly Valves

Storage of Butterfly Valve Assemblies Installation using Welded Flanges


l Assemblies must be stored indoors, protected from the elements. l Mount flanges on both sides of valve body and install bolts to
l Materials received on job sites that have long installation lead times properly align valve body and both flanges.
should receive extra protection from construction damage. l Make sure the valve I.D. and flange internal diameters are in
l Valve faces must be protected from abrasion, cutting and nicking, as alignment.
this will damage the face and may cause flange area leaks. l Take valve body / flange pair assembly and align with piping ends.
l Electric actuators cannot be stored in wet, damp or caustic areas. l TACK weld the flanges to the piping in several places.
l Do not store construction material on top of valve assemblies. Do NOT seam weld at this time!
l Remove the lug bolts and carefully remove the valve body from the
Installation Practices flanges.
l Seam weld the entire flange / piping connection for both flanges.
l SHP series butterfly valves are designed to be installed between
l Let the piping components cool completely before re-inserting the
ANSI 125/150 flat-faced or raised face, slip-on weld neck flanges.
valve body.
l Valve should be installed a minimum of 6 pipe diameters from
l WARNING! Seam welding with the valve body installed between the
upstream or downstream elbows, strainers, pumps, etc.
flanges can damage the valve seats due to heat migration through
l For chilled water, condenser water or hot water applications, the
the flange to the valve body.
valve should be installed with the stem in a vertical orientation, with
the actuator mounted above the valve.
l For applications in which there is a possibility of sediment in the
flow, the valve should be installed with the stem in a horizontal
position and the bottom of the disc should close FROM the
Butterfly Sizing and Selection
downstream side, rather than from the upstream side.
l Flange gaskets must be used on SHP series BF valves. CONSULT CHART ON PAGE 9
l Make sure the flange faces are clean and free of rust, scale and (Flow in Standard Weight Pipe-Fluid Velocity in GPM).
debris to prevent damage to the flange gasket. For SHP Series Butterfly Valves, the 32 ft/second column is applied.
l Follow the recommended flange bolting sequence found in the
For example: Application requires a 2-way, 600 GPM Butterfly
“Installation Recommendations” section of this guide.
valve, a valve of 3” minimum would be selected. The 3” valve at
32 ft/second would be able to withstand a capacity of 705 GPM,
without damage to the seat.
Notes
1. Most Butterflies are line size and piping geometry is not
Tech.Doc - 04/19 - Subject to change. © Belimo Aircontrols (USA), Inc.

considered. If valve size must be reduced, a recommendation is


to select a valve only one size less than the pipe. (Do not exceed
velocity limit)
2. For a modulating Butterfly valve, the Cv rating is determined at
60° open. For a 2-position Butterfly valve, the Cv is determined
at 90° open.
Consult Belimo Technical Support for applications involving
steam, high velocity requirements, etc.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

23
Installation Recommendations
SHP Series Butterfly Valves

Pre-Installation Procedure NOTE


Actuator must be mounted at
1. Remove the protective face covers from the valve.
or above pipe center line for
2. Inspect the valve to be certain the waterway is free from dirt and all actuator types.
foreign matter. Be certain the adjoining pipeline is free from any
foreign material such as rust and pipe scale or welding slag that
Fig. 6
could damage the seat and disc sealing surfaces.
3. Actuators should be mounted on the valve prior to installation to 90° 90°
facilitate proper alignment of the disc in the valve seat.
4. The valve should be in the closed position. Make sure the open and
closed positions of the actuator correspond to the counter-clockwise
to open direction of rotation of the valve.
5. Cycle the valve to the fully open position, then back to the fully closed
position, checking the actuator travel stop settings for proper disc
alignment.
6. Check the valve identification tag for valve class, materials, and
operating pressure to be sure they are correct for the application.
WARNING! Personal injury or property damage may result if the
valve is installed where service conditions could exceed the valve
ratings.
7. Check the flange bolts or studs for proper size, threading, and length.
REMEMBER: Install the valve with the disc in the full-closed position
using the appropriate flange gaskets on BOTH valve flange faces.

Valve Installation Procedure


The SHP High Performance Butterfly Valve can be installed in the
pipeline with the shaft in the vertical, horizontal, or other intermediate 1Fig. 8
position. Based on applications experience, however, in media
with concentrations of solid or abrasive particles or media subject
to solidification buildup, valve performance and service life will be
enhanced by mounting the valve with the shaft in the horizontal position.
All SHP valves are bidirectional and can be mounted in the pipeline in
either flow direction; however, the preferred flow direction for all seat

Tech.Doc - 04/19 - Subject to change. © Belimo Aircontrols (USA), Inc.


styles and materials is with the seat retainer ring located upstream (sus) 1 3
to provide maximum seat protection.
For SHP Series valves
a. Noting the flow direction arrow on the tag, place the valve between 4 2
the flanges, making sure the arrow on the tag points in the 1 5
direction of the flow.
b. Install the lower flange bolts loosely, leaving space for the flange 8 3
gaskets.
4 7 1 13
c. After inserting the flange gaskets, install the remaining bolts. 1 5 15 5
3. Using the sequence shown to the right, tighten the flange bolts evenly 6 2 12 9 8 9
to assure uniform gasket compression.
8 3 12 3
CAUTION: The SHP valve should be centered between the flanges and
4 7 4 11
gaskets to prevent damage to the disc edge and shaft as a result of
the disc striking the flange, gasket, or pipe. 10 11 10 7
4. Electricity should be connected to the unit as specified by the actuator 6 2 6 16
14 2
manufacturer.
5. The valve is now ready for operation.

Safety Notes
WARNING: This product can expose you to lead which is known to the State of
California to cause cancer and reproductive harm. For more information go to
www.P65Warnings.ca.gov

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

24
Installation Recommendations
SHP Series Butterfly Valves

FLANGE BOLTING RECOMMENDATIONS


Lug Valves, 2”– 30”, ANSI 125/150 Bolt Pattern
STUDS & NUTS MACHINE BOLTS
Valve Size Thread Size C QTY LENGTH D QTY LENGTH F QTY LENGTH G QTY LENGTH
2” 5/8-11 4 2.50 4 2.50 4 1.63 4 1.63
2-1/2” 5/8-11 4 2.75 4 2.75 4 1.85 4 1.85
3” 5/8-11 4 3.25 4 2.50 4 2.25 4 1.63
4” 5/8-11 8 3.00 8 2.75 8 2.12 8 1.88
5” 3/4-10 8 3.00 8 3.00 8 2.00 8 2.00
6” 3/4-10 8 3.50 8 3.00 8 2.50 8 1.88
8” 3/4-10 8 3.75 8 3.25 8 2.70 8 2.13
10” 7/8-9 12 4.25 12 3.50 12 3.00 12 2.25
12” 7/8-9 12 4.75 12 3.50 12 3.45 12 2.35
14” 1-8 12 5.00 12 4.00 12 3.75 12 2.70
16” 1-8 16 5.50 16 4.25 16 4.12 16 2.75
18” 1-1/8-8 16 5.75 16 4.75 16 4.38 16 3.25
1-1/8-8 16 6.75 16 4.75 16 5.12 16 3.25
20”
1-1/8-8 4** 5.50 4** 4.75 4* 4.12 4** 3.25
24” 1-1/4-8 20 7.25 20 5.75 20 5.63 20 4.25
1-1/4-8 24 7.75 24 7.75 24 6.25 24 6.25
30”
1-1/4-8 4** 6.50 4** 6.25 4* 5.00 4** 4.63

Bolting and torque recommendations are made without warranty, and apply only
LUG BODY LUG BODY
HEX HEAD MACHINE BOLTS STUDS and NUTS to steel weld-neck or slip-on flanges.
The use of lock washers and/or lubrication with the bolting will affect stated
torque values.
Length of machine bolts based on:
1. Gasket thickness of 0.06 inches.
2. Minimum flange thickness of weld-neck flanges per ANSI B16.5 and
B16.47 Series A.
* Variation to specified bolting length may result in improper installation.

FLANGE BOLTING RECOMMENDATIONS


Flange Detail for ANSI 150 B16.5 Pipe Flanges 150 SHP Series Butterfly Valves
Tech.Doc - 04/19 - Subject to change. © Belimo Aircontrols (USA), Inc.

FLANGES DRILLING BOLTING


Nominal
Pipe Size A Flange Diameter B Flange Thickness C Diameter of
Bolt Circle D Diameter of
Bolt Holes
Number
of Bolts
Diameter
of Bolts
2” 6” 3/4” 4-3/4” 3/4” 4 5/8”
2-1/2” 7” 7/8” 5-1/2” 3/4” 4 5/8”
3” 7-1/2” 15/16” 6” 3/4” 4 5/8”
4” 9” 15/16” 7-1/2” 3/4” 8 5/8”
5” 10” 15/16” 8-1/2” 7/8” 8 3/4”
6” 11” 1” 9-1/2” 7/8” 8 3/4”
8” 13-1/2” 1-1/8” 11-3/4” 7/8” 8 3/4”
10” 16” 1-3/16” 14-1/4” 1” 12 7/8”
12” 19” 1-1/4” 17” 1” 12 7/8”
14” 21” 1-3/8” 18-3/4” 1-1/8” 12 1”
16” 23-1/2” 1-7/16” 21-1/4” 1-1/8” 16 1”
18” 25” 1-5/8” 22-3/4” 1-1/4” 16 1-1/8”
20” 27-1/2” 1-11/16” 25” 1-1/4” 20 1-1/8”
24” 32” 1-7/8 29-1/2” 1-3/8” 20 1-1/4”

Every effort is made to provide accurate information, but no liability for claims
arising from erroneous data will be accepted by Belimo.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

25
Installation Recommendations
SHP Series Butterfly Valves

FLANGE BOLTING RECOMMENDATIONS


Lug Valves, 2”-24”, ANSI 250/300 Bolt Pattern
BOLT ENGAGEMENT IN VALVE* STUDS & NUTS MACHINE BOLTS
Valve Size Thread Size A QTY LENGTH B QTY LENGTH C QTY LENGTH D QTY LENGTH F QTY LENGTH G QTY LENGTH
2” 5/8-11 8 .94 8 .57 8 2.25 8 2.62 8 1.50 8 2.00
2-1/2” 5/8-11 8 .97 8 .67 8 2.75 8 3.00 8 1.75 8 2.00
3” 3/4-10 8 1.03 8 .82 8 3.00 8 3.00 8 2.12 8 2.00
4” 3/4-10 8 1.19 8 .87 8 3.50 8 3.25 8 2.50 8 2.00
5” 3/4-10 8 1.22 8 .79 8 5.25 8 3.62 8 2.25 8 2.75
6” 3/4-10 12 1.30 12 .92 12 3.75 12 3.50 12 2.75 12 2.25
8” 7/8-9 12 1.70 12 1.12 12 4.50 12 4.00 12 3.25 12 2.75
10” 1-8 16 1.86 16 1.30 16 5.00 16 4.50 16 3.25 16 3.12
12” 1-1/8-8 16 2.05 16 1.47 16 5.50 16 5.00 16 4.00 16 3.38
1-1/8-8 16 2.44 16 2.11 16 6.00 16 5.75 16 4.62 16 4.25
14”
1-1/8-8 4** 1.60 4** 1.26 4** 5.25 4** 4.75 4** 3.75 4** 3.44
1-1/4-8 16 2.56 16 2.62 16 6.50 16 6.50 16 4.88 16 4.88
16”
1-1/4-8 4** 1.53 4** 1.58 4** 5.25 4** 5.25 4** 3.88 4** 4.25
1-1/4-8 20 2.87 20 2.89 20 7.00 20 7.00 20 5.25 20 5.25
18”
1-1/4-8 4** 1.65 4** 1.43 4** 5.50 4** 5.50 4** 4.00 4** 3.88
1-1/4-8 20 3.18 20 3.00 20 7.50 20 7.25 20 5.69 20 5.69
20”
1-1/4-8 4** 1.68 4** 1.75 4** 5.75 4** 5.50 4** 4.19 4** 4.00
1-1/2-8 20 3.56 20 3.51 20 8.25 20 8.25 20 6.31 20 6.25
24”
1-1/2-8 4** 1.80 4** 1.75 4** 6.25 4** 6.25 4** 4.56 4** 4.50

LUG BODY LUG BODY * Bolt lengths “A” & “B” are from face of valve body to minimum depth
HEX HEAD MACHINE BOLTS STUDS and NUTS in lug. Flange & gasket thickness must be added to calculate mini-
mum bolt length.
**Special length required for tapped blind holes on either side of the
valve shaft at the top and bottom ends of the valve body.

FLANGE BOLTING RECOMMENDATIONS

Tech.Doc - 04/19 - Subject to change. © Belimo Aircontrols (USA), Inc.


Flange Detail for ANSI 300 B16.5 Pipe Flanges 300 SHP Series Butterfly Valves
FLANGES DRILLING BOLTING
Nominal
Pipe Size A Flange Diameter B Flange Thickness C Diameter of
Bolt Circle D Diameter of
Bolt Holes
Number
of Bolts
Diameter
of Bolts
2” 6.50 .88 5.00 .75 8 5/8”
2-1/2” 7.50 1.00 5.88 .88 8 3/4”
3” 8.25 1.12 6.63 .88 8 3/4”
4” 10.00 1.25 7.88 .88 8 3/4”
5” 11.00 1.38 9.25 .88 8 3/4”
6” 12.50 1.44 10.63 .88 12 3/4”
8” 15.00 1.62 13.00 1.00 12 7/8”
10” 17.50 1.88 15.25 1.12 16 1”
12” 20.50 2.00 17.75 1.25 16 1-1/8”
14” 23.00 2.12 20.25 1.25 20 1-1/8”
16” 25.50 2.25 22.50 1.37 20 1-1/4”
18” 28.00 2.38 24.75 1.37 24 1-1/4”
20” 30.50 2.50 27.00 1.37 24 1-1/4”
24” 36.00 2.75 32.00 1.62 24 1-1/2”

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

26
SY MFT Actuators
Quick Troubleshooting Guide

Verify that Control Signal and Power are present at the actuator. If the actuator adapts correctly:
• Measure between Control Signal + and – and power + and – on 1. Verify correct wiring of control signal (confirm correct polarity of field
control board. (See photo of control boards below for locations). wiring and meter). Must have “Control +” and “Control –” and not
• Check fuses on both boards. If fuses are blown, replace before share the “Control –” with the 24V common, or 120V Neutral (4 wires
proceeding. are required, 2 for power and 2 for Control Signal).
2. Provide a DC control signal other than minimum or maximum
Verify that the green LED is lit on the control board – this indicates power
(suggest 6 VDC or 50% command).
is present.
3. Measure with DC voltmeter on “Control +” and “Control –” at actuator
If yes: and verify that a voltage other than 0(2) or 10V is present on those
• Push the button labelled “Adaption”, hold for 3-5 seconds then terminals. If actuator does not drive to approximately the mid position
release. (see left photo for 24V, right photo for 120V) and voltage is present, the actuator most likely will need to be
• The LED next to green LED should light up (amber in color) replaced.
• Actuator should click. Drive fully in one direction. It will stop there for
The following information is helpful to determine warranty coverage and
5-10 seconds. Click and drive fully in the opposite direction.
additional steps that might need to be taken:
• The amber light should go out.
1. PO# or Belimo SO# or ID# (ID is located on actuator cover under the
If the sequence does not happen as above, please have the tech make a model #).
note of what does happen. 2. Is this a retrofit or was it factory assembled to a valve?
Possibilities include 3. Has this actuator ever worked on this site (brand new install that did
• Amber light goes on, actuator clicks but does not move at all. not work, or has been working correctly for a certain period of time).
• Amber light goes on, actuator clicks and drives in one direction, and 4. Proper transformer sizing (see PGPL for current VA requirements).
clicks but does not drive in the other direction. 5. Confirm correct wire size vs. length or run for SY actuators.
• Amber light does not light, and the actuator does nothing at all.
If something else occurs, please make a note and communicate to a
Belimo Technical Support Representative as the actuator most likely will
need to be replaced.
PC Tool Service Jack Connection

Control Signal + Power Supply Com -


Power Supply Hot +
Tech.Doc - 04/19 - Subject to change. © Belimo Aircontrols (USA), Inc.

Control Signal -
FDBK +
FDBK -

Adaption

24V
LED Location Direction of Rotation

N - Power Supply Common


H - Power Supply Hot

Control Signal +
Control Signal -
FDBK +
FDBK - PC Tool Service Jack

LED Location Adaption

120/230V
Direction of Rotation

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

27
Belimo Americas
USA, Latin America, and the Caribbean: www.belimo.us
Canada: www.belimo.ca, Brazil: www.belimo.com.br
Belimo Worldwide: www.belimo.com