USD Analysis in Beams (New Way)
USD Analysis in Beams (New Way)
Page 48
Example 2.8
Determine Mn , the nominal or theoretical ultimate moment strength of the beam section shown
in Figure 2.12, if fy = 60,000 psi and fc = 3000 psi.
SOLUTION
T = C for equilibrium
180 k = 35.7a
a = 5.04 in.
0.85fc′
a C
d = 21 in. d− a
24 in. 2
3 #9 bars
(As = 3.00 in.2)
T
3 in.
b = 14 in.
In Example 2.9, the nominal moment capacity of another beam is determined much as
it was in Example 2.8. The only difference is that the cross section of the compression area
(Ac ) stressed at 0.85fc is not rectangular. As a result, once this area is determined, we need to
locate its center of gravity. The c.g. for the beam of Figure 2.13 is shown as being a distance
y from the top of the beam in Figure 2.14. The lever arm from C to T is equal to d − y (which
corresponds to d − a/2 in Example 2.8) and Mn equals As fy (d − y).
With this very simple procedure, values of Mn can be computed for tensilely reinforced
beams of any cross section.
McCormac c02.tex V2 - January 10, 2013 9:16 P.M. Page 50
18 in.
18 in.
F I G U R E 2.13 Beam cross section for
Example 2.9.
F I G U R E 2.14 Area under compression stress
block for Example 2.9.
Example 2.9
Calculate the nominal or theoretical ultimate moment strength of the beam section shown in
Figure 2.13, if fy = 60,000 psi and fc = 3000 psi. The 6-in.-wide ledges on top are needed for
the support of precast concrete slabs.
SOLUTION
2.5 SI Example 51
2.5 SI Example
In Example 2.10, the nominal moment strength of a beam is computed using SI units.
Appendix B, Tables B.1 to B.9 provide information concerning various concrete and steel
grades, as well as bar diameters, areas, and so on, all given in SI units.
Example 2.10
Determine the nominal moment strength of the beam shown in Figure 2.15 if fc = 28 MPa
and fy = 420 MPa.
SOLUTION
T=C
As fy = 0.85fc ab
As fy (1530 mm2 ) (420 MPa)
a= = = 90 mm
0.85fc b
(0.85) (28 MPa) (300 mm)
a a a
Mn = T d − =C d− = As fy d −
2 2 2
90 mm
= (1530 mm2 ) (420 MPa) 430 mm −
2
430 mm
500 mm
3 #25 bars
70 mm
300 mm
F I G U R E 2.15 Beam cross section for
(As = 1530 mm2 from Appendix B, Table B.4) Example 2.10.
McCormac c02.tex V2 - January 10, 2013 6:34 P.M. Page 52
Example 2.11
SOLUTION
Open the Chapter 2 spreadsheet and select the worksheet called Cracking Moment. Input only
the cells highlighted in yellow (only in the Excel spreadsheets, not in the printed example), the
first six values below.
The last five values are the same as calculated in Example 2.1.
Example 2.12
SOLUTION
Open the Chapter 2 spreadsheet and select the worksheet called Elastic Stresses. Input only the
cells highlighted in yellow, the first seven values below.
b = 12 in.
d = 17 in.
n = 9
As = 3 in.2
McCormac c02.tex V2 - January 10, 2013 6:34 P.M. Page 53
M = 70 ft-k
fc = 3000 psi
γc = 145 pcf
Ec = 3,155,924 psi
n = 9.19
nρ = 0.132
x = 6.78 in.
Icr = 4067 in.4
fc = Mx/I = 1401 psi
fs = nM(d − x)/I = 18,996 psi
The last four values are the same (within a small roundoff) as calculated in Example 2.2.
Example 2.13
SOLUTION
Open the Chapter 2 spreadsheet, and select the worksheet called Nominal Moment Strength.
Input only the cells highlighted in yellow, the first five values below.
The third worksheet, called Nominal Moment Strength, can be used to easily work Example
2.8. In this case, enter the first five values, and the results are the same as in the example.
The process can be reversed if ‘‘goal seek’’ is used. Suppose that you would like to
know how much reinforcing steel, As , is needed to resist a moment, Mn , of 320 ft-k
for the beam shown in Example 2.8. Highlight the
cell where Mn is calculated in ft-k (cell C11), then
go to ‘‘Data’’ at the top of the Excel window and
select ‘‘What-If Analysis’’ and ‘‘Goal seek . . . ’’ The
Goal Seek window shown will open. In ‘‘Set cell,’’
C11 appears because it was highlighted when
you selected ‘‘Goal seek . . . ’’. In ‘‘To value,’’ type
320 because that is the moment you are seeking.
Finally, for ‘‘By changing cell,’’ insert C7 because
the area of reinforcing steel is what you want to
McCormac c02.tex V2 - January 10, 2013 6:34 P.M. Page 54
vary to produce a moment of 320 ft-k. Click OK, and the value of As will change to 3.55. This
means that a steel area of 3.55 in.2 is required to produce a moment capacity Mn of 320 ft-k.
The Goal Seek feature can be used in a similar manner for most of the spreadsheets provided in
this text.
PROBLEMS
Cracking Moments
20 in.
18 in.
21 in. 26 in.
4 #9 4 #8 3 in.
3 in. 3 in.
12 in. 18 in.
9 in.
18 in.
21 in.
2 #9 9 in. 27 in.
3 in.
3 #10
9 in.
14 in. 3 in.
6 in. 6 in. 6 in.
Problem 2.3 (Ans. 31.6 ft-k)
18 in.
30 in.
4 in.
17 in. 24 in.
1 #11
3 in.
6 in.