Data sheet 6ES7155-6BA01-0CN0
SIMATIC ET 200SP, PROFIBUS bundle IM, IM 155-6DP HF, max. 32 I/O
modules and 16 ET 200AL modules, Multi-hotswap, bundle consists of:
Interface module (6ES7155-6BU01-0CN0), Server module (6ES7193-
6PA00-0AA0), PROFIBUS connector (6ES7972-0BB70-0XA0)
General information
Product type designation IM 155-6 DP HF
HW functional status From FS02
Firmware version V4.2
Product function
● I&M data Yes; I&M0 to I&M3
● Module swapping during operation (hot swapping) Yes; Multi-hot swapping
● Isochronous mode No
Engineering with
● STEP 7 TIA Portal configurable/integrated from V15 SP1
version
● STEP 7 configurable/integrated from version As of V5.5 SP4, only up to FW V3.1
● PROFIBUS from GSD version/GSD revision One GSD file each, Revision 3 and 5 and higher
Configuration control
via dataset Yes
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Mains buffering
● Mains/voltage failure stored energy time 10 ms
Input current
Current consumption, max. 335 mA
Inrush current, max. 1.6 A
I²t 0.038 A²·s
Power loss
Power loss, typ. 1.5 W
Address area
Address space per module
● Address space per module, max. 32 byte; per input / output
Address space per station
● Address space per station, max. 244 byte; per input / output
Hardware configuration
Rack
● Quantity of operable ET 200SP modules, max. 32
● Quantity of operable ET 200AL modules, max. 16
6ES71556BA010CN0 Subject to change without notice
7.21.2021
Page 1/3 © Copyright Siemens
Interfaces
Number of PROFIBUS interfaces 1
1. Interface
Interface types
● RS 485 Yes
● Output current of the interface, max. 90 mA
Protocols
● PROFIBUS DP slave Yes
Interface types
RS 485
● Transmission rate, max. 12 Mbit/s
Protocols
Open IE communication
● TCP/IP No
PROFIBUS DP
Services
— SYNC capability Yes
— FREEZE capability Yes
— DPV0 Yes
— DPV1 Yes
Interrupts/diagnostics/status information
Status indicator Yes
Alarms Yes
Diagnostics function Yes
Diagnostics indication LED
● RUN LED Yes; green LED
● ERROR LED Yes; red LED
● MAINT LED Yes; Yellow LED
● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
● Connection display DP Yes; green DP LED
Potential separation
between backplane bus and electronics No
between PROFIBUS DP and all other circuit components Yes
between supply and all other circuits No
Permissible potential difference
between different circuits Safety extra low voltage SELV
Isolation
Isolation tested with 707 V DC (type test)
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -25 °C
● horizontal installation, max. 60 °C
● vertical installation, min. -25 °C
● vertical installation, max. 50 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Connection method
ET-Connection
● via BU/BA Send Yes; + 16 ET 200AL modules
Dimensions
Width 50 mm
Height 117 mm
Depth 74 mm
Weights
Weight, approx. 150 g