LR-W500 (C) : Instruction Manual
LR-W500 (C) : Instruction Manual
1-4 Specifications
LR-W500 LR-W500C
Model
2 m cable type 4-pin M12 connector type
Detectable distance 30 to 500 mm
Full-Spectrum Sensor Adjustable spot
Approx. 3.5 mm at 100 mm
Min. spot diameter
LR-W500(C)
Approx. 9 mm at 250 mm
Approx. 18 mm at 500 mm
*1
Response time 200 μs/1 ms/10 ms/100 ms/500 ms selectable
Light source White LED
*3
Tuning /Transmission OFF selectable,
I/O Short-circuit current: NPN: 1 mA or less, PNP: 2 mA or less,
The following symbols alert you to important messages. Be sure to read this section carefully.
For the applied voltage, see the wiring diagrams
External input
( page 2 in the instruction manual),
Indicates a hazardous situation which, if not avoided, could result in death For the input times, see the time charts
WARNING ( page 6 in the instruction manual)
or serious injury.
Protection against reverse power connection, power supply surge,
Indicates a situation which, if not avoided, could result in product damage Protection circuit
NOTICE output overcurrent, output surge, and reverse output connection
as well as property damage.
Enclosure
IP65/IP67 (IEC60529)
ratings
Environmental
resistance
Ambient
-20 to +50°C (no freezing)
temperature
1-1 Safety Precautions Ambient
35 to 85%RH (no condensation)
humidity
Shock 2
• This product is only intended to detect object(s). Do not use this product 1,000 m/s in X, Y, Z axis directions respectively 6 times
resistance
for the purpose of protecting a human body or a part of the human body. Vibration 10 to 55 Hz Double amplitude 1.5 mm in the X, Y, Z axis
• This product is not intended for use as an explosion-proof product. Do not resistance directions respectively, 2 hours
WARNING use this product in a hazardous location and/or potentially explosive Case: Zinc die cast (Nickel chrome plating)
atmosphere. Indicator cover: PPSU
• This product uses DC power. The product may explode or burn if an AC Buttons: PES
voltage is applied. Lens cover and display: PMMA (scratch-resistant coating)
Material Spot adjustment dial: Iron (black oxide finish)
• Do not wire this product along with power lines or high-tension lines. Doing Cable bushing (2 m cable type only): PBT
so may lead to product malfunctions or damage due to noise. Cable (2 m cable type only): PVC
NOTICE
• Do not use this product outdoors or in a place where extraneous light can Connector ring (4-pin M12 connector type only): PMP
enter the light-receiving element directly. Connector socket (4-pin M12 connector type only): PEI
Approx. 170 g
Weight Approx. 110 g
(including cable)
1-2 Precautions on Regulations and Standards *1 When you set an alternate frequency, the response time becomes approximately 20%
slower.
*2 195 mA or less (at 10 V, with load)
*3 IO-Link specification v.1.1/COM2 (38.4 kbps) is supported.
CSA Certificate You can download a setup file from the KEYENCE website (http://www.keyence.com). If you
This product complies with the following CSA and UL standards and has been certified by CSA. are using the product in an environment in which you cannot download files over the Internet,
Be sure to consider the following specifications when using this product as a CSA-certified contact your nearest KEYENCE office.
product.
• Applicable standards: CAN/CSA C22.2 No. 61010-1,
UL61010-1
• Use one of the following types of power supplies.
A CSA/UL certified power supply that provides Class 2 output as defined in the CEC (Canadian
Electrical Code) and NEC (National Electrical Code) or a CSA/UL certified power supply that 1-5 Part Functions
has been evaluated as a Limited Power Source as defined in CAN/CSA-C22.2 No.
60950-1/UL60950-1.
• Use this product at an altitude of 2000 m or less. Indicator [SET] button
• Overvoltage category: I Off: Output off The operation of this button varies depending
• Pollution degree: 3 Orange: Output on on the sensitivity adjustment method.
• Indoor use only. Red (flashing): Error ( pages 3 to 4)
Green: Master
calibration reference
CE Marking registered
Function Indicators
KEYENCE Corporation has confirmed, on the basis of the following specifications, that this STB: Illuminates green when receiving stable light
product complies with the essential requirements of the applicable EU Directive. Be sure to C: Illuminates green when using C/C+I mode
consider the following specifications when using this product in a member state of the I: Illuminates green when using C+I/Super I mode
European Union.
STB C I
EMC Directive NO/NC
-1-
2. Installation and Wiring 3. Initial Settings (NPN/PNP Selection)
When the power is turned on for the first time after purchase, or initialization is
2-1 Installation performed, the initial setting (NPN/PNP selection) is required as shown below.
• Tightening torque for the mounting holes: 0.63 N·m (M3 screw)
• If the workpiece contains a glossy surface that could interfere with stable
detection, tilt the sensor approx. 15° to 20°. If tilting the sensor does not
improve detection, please attach the reflection canceling attachment P2P 2P2
(LR-WA1). NPN PNP
15 to 20°
3 s or more
RUN
SET
FOCUS
FOCUS Detection mode Explanation
Auto When adjusting the sensitivity, the optimal mode
(default) is automatically selected between C+I or C.
NOTICE Dial turning torque: 0.2 N · m or less
Detection is performed according to the color
C+I mode components (R, G, B) and illumination (the
• Turn the dial to the right to decrease the focal distance. received light intensity).
Detection is performed according to the color
C mode
components (R, G, B) only.
Detection is performed according to the
Super I mode
The focal point moves illumination (the received light intensity) only.
closer to the sensor.
-2-
5. Sensitivity Adjustment < Precautions for master calibration>
• Continue calibration until the green light that indicates reference addition
does not turn on any more.
5-1 Auto/C+I/C Mode • If the master calibration is performed again, the registered contents from the
first master calibration will be overwritten. To add an allowable range after
About the display value the master calibration, perform the master addition calibration.
• Conformity • If the registration status is saturated and "---" is displayed. Perform the
The level of conformity of the current detected workpiece to the registered master calibration again after lowering the "7-8 Master Calibration Set
reference workpiece. Value " (page 6).
Display range: 0 to 999 (The more the workpiece conform to reference workpiece, • Changing the master calibration set value after a master calibration has
the higher the value.) been performed, does not affect the current setting value, only subsequent
calibrations.
• Setting value
The threshold of conformity at which a workpiece is judged to be the same as the Permitting color variations between different
registered workpiece. workpieces
To check or manually make fine adjustments to the setting value, Master addition calibration (when adding workpieces to be permitted)
see "Checking and adjusting the setting value" (page 3). Position a workpiece which is to be judged the same as the current
* The blinking numeric value that appears after calibration is the setting value. registered color. Then press and hold the [SET] button and the [] button.
When the added registration is successful, the "setting value" flashes three
Setting the sensitivity (apply one of the following times, and the sensor returns to the normal screen (the setting value is not
three methods) changed at this point in time).
1-point calibration (use to detect 1 specific color) In this case, references are added to permit colors between "the current
Register the color of the workpiece to be detected. registered color" and "the additional registered color".
(When Auto mode is used, this function operates in C+I.)
1
Press and
1 hold the [SET]
FOCUS
Press and and []
SET
FOCUS
FOCUS
[SET] [SET]
SET
SET
button (for button When the In contrast, when the setting value is reduced, a wider detection tolerance is
1 second again (for difference is enabled. The [] and [] buttons can be used to increase or decrease the
or less). 1 second too small. setting value.
or less).
workpiece)
Press the [SET] button to register the reference color. Then, press and hold
Setting value (flashes)
the [SET] button to perform sampling. During sampling, references are
added and are set to be judged as the same color. When a reference is
added, the indicator flashes (once) in green.
...
* After master calibration or master addition calibration has been executed, the
1 2
setting value cannot be increased.
FOCUS
FOCUS
SET
-3-
5-2 Super I Mode When the received light intensity is saturated or
insufficient
When using the product with the (200 μs) or 1 ms response time selected,
About the display value stable operation may be reduced. In this situation, it may be possible to increase
• Received light intensity
stability by adjusting the light intensity to the optimal value using the steps below.
The current received light intensity is displayed.
Display range: 0 to 999 (The greater the received light intensity, the higher the
value.) 1 Press the
[SET] and
FOCUS
• Setting value []
SET
The threshold at which the received light intensity is judged to indicate that a buttons at
the same OK CFL
workpiece is present.
time (for 1
To check or manually make fine adjustments to the value, see "Checking second or
and adjusting the setting value" (page 4). less.)
* The blinking numeric value that appears after calibration is the setting value.
FOCUS
SET
NG
(3sec)
MODE Press and hold the [] button and []
button at the same time for 3 s or more.
1
Press and
FOCUS
hold the
.QE WP.
SET
[SET]
button for OK
3 seconds
or more. Keys locked Key lock released
FOCUS
hold the
SET
SET
[SET] Press 5x
button for OK STB C I
NO/NC
RUN
3 seconds
or more. (3sec)
MODE While pressing the [] button,
press the [] button five times.
When "" flashes, continue After passing the
holding the [SET] button and workpiece in front of Hold
pass the workpiece in front of the sensor, release the
TV PQ [GU
the sensor. [SET] button.
STB C I RUN
NO/NC YES
(3sec)
Press the [] button NO
MODE
(for 1 second or less).
P2P
RUN
Return to the initial settings screen.
-4-
7. Settings
NO/NC RUN
(3sec) (Press and hold the button to enter the settings menu.)
MODE (On the parameter selection screen, press the button while holding the button to return to the
previous screen.)
>3s
7-3 Timer
( page 6) F.[ Q(( QPF Q(F 5JV
OFF ON delay OFF delay One-shot
The most significant digit can be changed. 1, 2, …9, 10, 20, …90, 100, 200, …900.
7-8 Master Calibration While holding the [] button, press the
Set Value ( page 6)
* Only when Auto, C+I, or VJT [] button to decrease the value.
GP
GPF
RUN
-5-
7-1 Detection Mode 7-5 Display Selection
Select the desired detection mode. The display can be turned off by selecting .
See "4-2 Detection Mode" (page 2).
OFF
With a higher setting value, there is a higher possibility of saturation or "---"
ON occurring after Master calibration. If Master calibration results in "---", perform
N.C.
OFF Master calibration again after lowering this value.
ON
N.O.
ON delay
OFF
7-9 Password
ON
N.C. An optional password can be set to further prohibit unauthorized releasing of the
OFF
"6-1 Key Lock" (page 4). Select a value from 1 to 999 for this setting. If "0" is
ON selected, the password will not be required.
N.O.
OFF delay
OFF
ON
N.C.
OFF
ON
N.O.
One-shot
OFF
ON
N.C.
OFF
Timer duration
ON
Input
OFF
> 60 ms > 60 ms
ON
Input
OFF
< 10 ms < 10 ms
-6-
8. Troubleshooting 8-4 Other Precautions
• When using the luster canceling attachment (LR-WA1)
8-1 Error Display With some glossy targets (ex. stretched films), stable detection may not be
achievable at certain angles. In such cases, rotate the sensor +/-45°, as shown in
Display Cause Solution the diagram below, to determine the most appropriate angle for stable detection.
Excessiv e current • Check if the output wires are
(ov ercurrent) is f lowing connected correctly and are
through the output wire. not in contact with other wires.
• Check if the load is within the
FOCUS
rated range f or the output.
SET
SET
The memory has reached its Perf orm initialization. If the 45°
end of lif e, or the sensor is problem persists, contact
malf unctioning. KEY ENCE.
(The bar pulses Normal operation Normal operation
across the display .)
-7-
8-5 WARRANTIES AND DISCLAIMERS
(1) KEYENCE warrants the Products to be free of defects in materials and
workmanship for a period of one (1) year from the date of shipment. If any
models or samples were shown to Buyer, such models or samples were used
merely to illustrate the general type and quality of the Products and not to
represent that the Products would necessarily conform to said models or
samples. Any Products found to be defective must be shipped to KEYENCE
with all shipping costs paid by Buyer or offered to KEYENCE for inspection
and examination. Upon examination by KEYENCE, KEYENCE, at its sole
option, will refund the purchase price of, or repair or replace at no charge any
Products found to be defective. This warranty does not apply to any defects
resulting from any action of Buyer, including but not limited to improper
installation, improper interfacing, improper repair, unauthorized modification,
misapplication and mishandling, such as exposure to excessive current, heat,
coldness, moisture, vibration or outdoors air. Components which wear are not
warranted.
(2) KEYENCE is pleased to offer suggestions on the use of its various Products.
They are only suggestions, and it is Buyer's responsibility to ascertain the
fitness of the Products for Buyer's intended use. KEYENCE will not be
responsible for any damages that may result from the use of the Products.
(3) The Products and any samples ("Products/Samples") supplied to Buyer are
not to be used internally in humans, for human transportation, as safety
devices or fail-safe systems, unless their written specifications state otherwise.
Should any Products/Samples be used in such a manner or misused in any
way, KEYENCE assumes no responsibility, and additionally Buyer will
indemnify KEYENCE and hold KEYENCE harmless from any liability or
damage whatsoever arising out of any misuse of the Products/Samples.
(4) OTHER THAN AS STATED HEREIN, THE PRODUCTS/SAMPLES ARE
PROVIDED WITH NO OTHER WARRANTIES WHATSOEVER. ALL
EXPRESS, IMPLIED, AND STATUTORY WARRANTIES, INCLUDING,
WITHOUT LIMITATION, THE WARRANTIES OF MERCHANTABILITY,
FITNESS FOR A PARTICULAR PURPOSE, AND NON-INFRINGEMENT OF
PROPRIETARY RIGHTS, ARE EXPRESSLY DISCLAIMED.
IN NO EVENT SHALL KEYENCE AND ITS AFFILIATED ENTITIES BE
LIABLE TO ANY PERSON OR ENTITY FOR ANY DIRECT, INDIRECT,
INCIDENTAL, PUNITIVE, SPECIAL OR CONSEQUENTIAL DAMAGES
(INCLUDING, WITHOUT LIMITATION, ANY DAMAGES RESULTING FROM
LOSS OF USE, BUSINESS INTERRUPTION, LOSS OF INFORMATION,
LOSS OR INACCURACY OF DATA, LOSS OF PROFITS, LOSS OF
SAVINGS, THE COST OF PROCUREMENT OF SUBSTITUTED GOODS,
SERVICES OR TECHNOLOGIES, OR FOR ANY MATTER ARISING OUT
OF OR IN CONNECTION WITH THE USE OR INABILITY TO USE THE
PRODUCTS, EVEN IF KEYENCE OR ONE OF ITS AFFILIATED ENTITIES
WAS ADVISED OF A POSSIBLE THIRD PARTY'S CLAIM FOR DAMAGES
OR ANY OTHER CLAIM AGAINST BUYER. In some jurisdictions, some of
the foregoing warranty disclaimers or damage limitations may not apply.
BUYER'S TRANSFER OBLIGATIONS:
If the Products/Samples purchased by Buyer are to be resold or delivered to a
third party, Buyer must provide such third party with a copy of this document,
all specifications, manuals, catalogs, leaflets and written information provided
to Buyer pertaining to the Products/Samples.
E 1101-3
2015
13761E 1086-1a 96M13761
-8-