Service Manual

ORDER NO: APIN1706005CE

Air Conditioner

Indoor Unit Outdoor Unit


CS-KC12SKY3 CU-KC12SKY3
CS-KC18SKY3M-1 CU-KC18SKY3M-1
CS-KC18SKY3R-1 CU-KC18SKY3R-1
CS-KC12SKY3E CU-KC12SKY3E
CS-KC12SKY3A CU-KC12SKY3A
CS-KC12SKY4A CU-KC12SKY4A
CS-KC18SKY4A CU-KC18SKY4A
CS-KC18SKY3PR CU-KC18SKY3PR
CS-KC18SKY3PM CU-KC18SKY3PM

(Manufactured in India)
Destination
India

This service information is designed for experienced repair technicians only and is not designed for
use by the general public.It does not contain warnings or cautions to advise non-technical individuals
of potential dangers in attempting to service a product. Products powered by electricity should be
serviced or repaired only by experienced professional technicians. Any attempt to service or repair the
products dealt with in this service information by anyone else could result in serious injury or death.

There are special components used in this equipment which are important for safety. These parts are
marked by--in the Schematic Diagrams, Circuit Board Diagrams, Exploded Views and Replacement
Parts List, It is essential that these critical parts should be replaced with manufacturer's specified parts
to prevent shock, fire or other hazards. Do not modify the original design without permission of manu-
facturer.

© Panasonic Corporation 2017.


Unauthorized Copying and distribution is a
violation of law.
TABLE OF CONTENTS
1. Safety Precautions ........................................................ 3
2. Specification ................................................................. 5
3. Location of Controls and Components ........................... 11
3.1 Indoor Unit .................................................................... 11
3.2 Outdoor Unit .................................................................. 11
3.3 Remote Control .............................................................. 12
4. Dimensions ................................................................... 13
4.1 CS-KC12SKY* Series...................................................... 13
4.2 CS-KC18SKY* Series...................................................... 14
4.3 CU-KC12SKY* Series,CU-KC18SKY* Series...................... 15
5. Refrigeration Cycle Diagram ........................................ 16
6. Block Diagram .............................................................. 17
7. Wiring Connection Diagram ......................................... 18
7.1 CS-KC12SKY3 ............................................................. 18
8. Electronic Circuit Diagram ........................................... 22
8.1 KC12SKY* Series,KC18SKY* Series..................................22
9. Printed Circuit Board ............................................... 23
9.1 Indoor Unit (Main PCB) ....KC12SKY3,KC12SKY*Series.......23
9.2.1 Indoor Unit (Main PCB) ....KC18SKY* Series................... 24
9.2.2 Indoor Unit (I&RPCB) ..KC12SKY*,KC18SKY*................. 25
10. Installation Instruction ............................................. 26
10.1 Select the Best Location ........................................... 26
10.2 Indoor Unit ................................................................ 27
10.3 Outdoor Unit ............................................................. 32
10.4 Front Grille ............................................................... 35
10.5 PM2.5/Catechin Filter ................................................ 36
11. Operation Control ..................................................... 37
11.1 Cooling Operation ...................................................... 37
11.2 Dry Operation ............................................................ 38
11.3 Automatic Operation ................................................... 39
11.4 Indoor Fan Speed Control ............................................ 39
11.5 Outdoor Fan Speed Control .......................................... 41
11.7 Vertical Airflow Direction Control ................................... 42
11.8 Horizontal Airflow Direction Control ............................... 42
11.9 Timer Control ............................................................. 42
11.10 Random Auto Restart Control ....................................... 43
11.11 Remote Control Signal Receiving Sound ..................... 43
12. Protection Control ..................................................... 44
12.1 Restart Control (Time Delay Safety Contr...................... 44
12.2 7 Minutes Time Save Control ...................................... 44
12.3 60 Seconds Forced Operation ..................................... 44
12.4 Starting Current Control ............................................... 44
12.5 Freeze Prevention Control ........................................... 44
12.6 Compressor Reverse Rotation Protection Control ........... 45
12.7 Dew Prevention Control ............................................... 45
13. Servicing Mode .......................................................... 46
13.1 Auto OFF/ON Button .................................................. 46
13.2 Remote Control Button ................................................ 47
14. Troubleshooting Guide .............................................. 48
14.1 Refrigeration cycle system........................................... 48
15. Disassembly and Assembly Instructions...................... 50
15.1 Indoor Electronic Controllers and Control ....................... 50
15.2 Outdoor disassembly ...KC12SKY*,KC18SKY*.............. 54
16. Technical Data .......................................................... 55
16.1 Operation Characteristics ........................................... 55
17. Exploded View and Replacement Parts List .............. 61
17.1 Indoor Unit ................................................................. 61
17.2 Outdoor Unit ............................................................... 66

2
1. Safety Precautions
# Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing.
# Electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating of the power plug and
main circuit for the model installed.
# The caution items stated here must be followed because these important contents are related to safety. The meaning of each
indication used is as below. Incorrect installation or servicing due to ignoring of the instruction will cause harm or damage,
and the seriousness is classified by the following indications.

WARNING This indication shows the possibility of causing death or serious injury.

CAUTION This indication shows the possibility of causing injury or damage to properties.

# The items to be followed are classified by the symbols:

This symbol denotes item that is PROHIBITED from doing.

# Carry out test run to confirm that no abnormality occurs after the servicing. Then, explain to user the operation,
care and maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future
reference.

WARNING

1. Do not modify the machine, part, material during repairing service.

2. If wiring unit is supplied as repairing part, do not repair or connect the wire even only partial wire break. Exchange the whole wiring unit.

3. Do not wrench the fasten terminal. Pull it out or insert it straightly.

4. Engage authorized dealer or specialist for installation and servicing. If installation of servicing done by the user is defective, it will cause water
leakage, electrical shock or fire.

5. Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electric shock or fire.

6. Use the attached accessories parts and specified parts for installation and servicing. Otherwise, it will cause the set to fall, water leakage, fire
or electrical shock.

7. Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly done,
the set will drop and cause injury.

8. For electrical work, follow the local national wiring standard, regulation and the installation instruction. An independent circuit and single outlet
must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire.

9. This equipment is strongly recommended to be installed with Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD).
Otherwise, it may cause electrical shock and fire in case equipment breakdown or insulation breakdown.

10. Do not use joint cable for indoor/outdoor connection cable. Use the specified indoor/outdoor connection cable, refer to installation instruction
CONNECT THE CABLE TO THE INDOOR UNIT and connect tightly for indoor/outdoor connection. Clamp the cable so that no external force
will be acted on the terminal. If connecting or fixing is not perfect, it will cause heat up or fire at the connection.

11. Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will cause
heat-up or fire at the connection point of terminal, fire or electrical shock.

12. When install or relocate air conditioner, do not let any substance other than the specified refrigerant, eg. air etc. mix into refrigeration cycle
(piping). (Mixing of air etc. will cause abnormal high pressure in refrigeration cycle and result in explosion, injury etc.).

13. Do not install outdoor unit near handrail of veranda. When installing air-conditioner unit at veranda of high rise building, child may
climb up to outdoor unit and cross over the handrail and causing accident.

14. This equipment must be properly earthed. Earth line must not be connected to gas pipe, water pipe, earth of lightning rod and
telephone. Otherwise, it may cause electrical shock in case equipment breakdown or insulation breakdown.

15. Keep away from small children, the thin film may cling to nose and mouth and prevent breathing.

16. Do not use unspecified cord, modified cord, joint cord or extension cord for power supply cord. Do not share the single outlet with
other electrical appliances. Poor contact, poor insulation or over current will cause electrical shock or fire.

3
17. Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the flare may
break and cause refrigerant gas leakage.
18. During pump down operation, stop the compressor before remove the refrigeration piping. (Removal of refrigeration piping while
compressor is operating and valves are opened condition will cause suck-in of air, abnormal high pressure in refrigeration cycle and
result in explosion, injury etc.).

19. During installation, install the refrigerant piping properly before run the compressor. (Operation of compressor without fixing refrigeration
piping and valves at opened condition will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury
etc.).

20. After completion of installation or service, confirm there is no leakage of refrigerant gas. It may generate toxic gas when the refrigerant
contacts with fire.

21. Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when the refrigerant contacts with fire.

22. Do not insert your fingers or other objects into the unit, high speed rotating fan may cause injury.

23. Must not use other parts except original parts describe in catalog and manual.

24. Using of refrigerant other than the specified type may cause product damage, burst and injury etc.

CAUTION
1. Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at surrounding of the
unit, it may cause fire.

2. Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage
the furniture.

3. Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the flare
may break and cause refrigerant gas leakage.

4. Do not touch outdoor unit air inlet and aluminium fin. It may cause injury.

5. Select an installation location which is easy for maintenance.

6. Pb free solder has a higher melting point than standard solder; typically the melting point is 50°F – 70°F (30°C – 40°C) higher. Please use
a high temperature solder iron. In case of the soldering iron with temperature control, please set it to 700 ± 20°F (370 ± 10°C).
Pb free solder will tend to splash when heated too high (about 1100°F / 600°C).
7. Power supply connection to the room air conditioner.
Use approved power supply cord 3 x 1.5 mm2 (1.5HP) or 3 x 2.5 mm2 (2.0 ~ 2.5HP) type designation IS 694 or 60245 IEC 57 or heavier cord.
Power supply point should be in easily accessible place for power disconnection in case of emergency.
In some countries, permanent connection of this air conditioner to the power supply is prohibited.
i. Power supply connection to the receptacle using power plug.
Use an approved 15/16A (1.0~1.5HP) or 16A (2.0HP) or 20A (2.5HP) power plug with earth pin for the connection to the socket.
ii. Power supply connection to a circuit breaker for the permanent connection.
Use an approved 16A (1.0 ~ 2.0HP) or 20A (2.5HP) circuit breaker for the permanent connection. It must be a double pole switch with a
minimum 3.0 mm contact gap.
8. Do not release refrigerant during piping work for installation, servicing, reinstallation and during repairing a refrigerant parts. Take
care of the liquid refrigerant, it may cause frostbite.

9. Installation or servicing work: It may need two people to carry out the installation or servicing work.

10. Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.

11. Do not sit or step on the unit, you may fall down accidentally.

12. Do not touch the sharp aluminum fins or edges of metal parts.
If you are required to handle sharp parts during installation or servicing, please wear hand glove.
Sharp parts may cause injury.

4
2. Specification
Indoor CS-KC12SKY3 CS-KC12SKY3A CS-KC12SKY3E
MODEL
Outdoor CU-KC12SKY3 CU-KC12SKY3A CU-KC12SKY3E
Performance Test Condition Indian Standard Indian Standard Indian Standard
Power Supply Phase,Hz Single,50 Single,50 Single,50
V 230 230 230
kW 3.46 3.46 3.46
Capacity
BTU/h 11,805 11,805 11,805

Running Current A 4.9 4.9 4.9


Input Power W 1070 1070 1070
EER Class Star 3 3 3
W/W 3.23 3.23 3.23
EER
BTU/h 11.03 11.03 11.03

Power Factor % 98 98 98
Cooling

Power Level dB - - -
Indoor Noise
db-A High:48;Low:43 High:48;Low:43 High:48;Low:43

PowerLevel dB - - -
Outdoor Noise
db-A 54 54 54
Max Current (A)/Max Input Power (W) 8.1 A/ 1.76KW 8.1 A/ 1.76KW 8.1 A/ 1.76KW
Starting Current (A) 26.0 A / 1.06 K 26.0 A / 1.06 K 26.0 A / 1.06 K
Compressor Type Rotary Rotary Rotary
Motor Type Induction (2 Pole) Induction (2 Pole) Induction (2 Pole)
Output Power W 1055 1055 1055
FAN Type Cross Flow Fan Cross Flow Fan Cross Flow Fan
Material ASG30K1 ASG30K1 ASG30K1
MotorType DC (8 Pole) DC (8 Pole) DC (8 Pole)

Output Power W 30 30 30
Indoor

Lo rpm 1060 1060 1060


Speed Me rpm 1170 1170 1170
S Hi /Hi rpm 1280 1280 1380/1280
Type Propeller Fan Propeller Fan Propeller Fan
FAN
Material ABS ABS ABS
MotorType AC/Induction (6 Pole) AC/Induction (6 Pole) AC/Induction (6 Pole)
Outdoor

Power W 26 26 26
Speed Hi rpm 900 900 900
Moisture Removal L/h (Pt/h) 1.9 1.9 1.9
Cool 3 3
m /min.(ft /min.) 13.5(477) 13.5(477) 13.5(477)
Indoor Airflow
Heat m3/min.(ft3/min.) - - -

Outdoor Airflow Hi m3/min.(ft3/min.) 46.0 (1620) 46.0 (1620) 46.0 (1620)

Key in gas amount in W unit 1110 1110 1110


Control Device Capillary Tube Capillary Tube Capillary Tube
Refrigeration Cycle Refrigerant Oil cm3 4GSD(320ml) 4GSD(320ml) 4GSD(320ml)

RefrigerantType g(oz) R22 R22 R22

5
Model Indoor CS-KC12SKY3 CS-KC12SKY3A CS-KC12SKY3E
Outdoor CU-KC12SKY3 CU-KC12SKY3A CU-KC12SKY3E

Height(I/D / O/D) mm(inch) 290(11-7/16) / 619 290(11-7/16) / 619 290(11-7/16) / 619


Dimension
Length(I/D / O/D) mm(inch) 870(34-9/32)/824 870(34-9/32)/824 870(34-9/32)/824
Depth(I/D / O/D) mm(inch) 204(8-1/16)/299 204(8-1/16)/299 204(8-1/16)/299
Weight Net(I/D / O/D) kg(lb) 9(20)/30(66) 9(20)/30(66) 9(20)/30(66)

Pipe Diameter(liquid/gas) mm(inch) 6.35(1/4)/12.70(1/2) 6.35(1/4)/12.70(1/2) 6.35(1/4)/12.70(1/2)


Standard Length m(ft) Flare, 5.0 (16.4) Flare, 5.0 (16.4) Flare, 5.0 (16.4)

Piping Length Range(min-max) m(ft) 3-15 3-15 3-15


I/D & O/D Height different g/m(oz/ft) 5 (16.4) 5 (16.4) 5 (16.4)

Additional gas amount g/m(oz/ft) 10(0.1) 10(0.1) 10(0.1)

Length for Additional gas m(ft) 7.5 (24.6) 7.5 (24.6) 7.5 (24.6)
Inner Diameter mm 16.7 16.7 16.7
Drain Hose Length mm 650 650 650

Fin Material Aluminium(Pre Coat) Aluminium(Pre Coat) Aluminium(Pre Coat)

Indoor Heat Exchanger Fin Type Slit Fin Slit Fin Slit Fin
Row xStage xFPI 2 x 15 x 20 2 x 15 x 20
2 x 15 x 20
Size(W X H X L) mm 610 x 315 x 25.4 610 x 315 x 25.4 610 x 315 x 25.4
Fin Material Copper Copper Copper
Outdoor Heat Exchanger
Fin Type/PASS Slit Fin Slit Fin Slit Fin
Row xHair Pin xFPI 1 x 14 x 18 1 x 14 x 18 1 x 14 x 18
Size(W X H X L) 12.7 X 547 X 810 12.7 X 547 X 810 12.7 X 547 X 810
Material PP PP PP
Air Filter
Type One Touch One Touch One Touch
Power Supply Indoor Indoor Indoor
Power Supply Cord A 16 16 16
Protection Device Overload Protector
Dry Bulb Wet Bulb Dry Bulb Wet Bulb
Indoor Operation Range Maximum0C 35 35
24 24
0
Minimum C 16 11 16 11
Maximum0C 46 27 46 27
Outdoor Operation Range
0
Minimum C 16 11 16 11

Note:
1.Cooling capacities are based on indoor temperature of 270C Dry Bulb (80.60F Dry Bulb),19.00C Wet Bulb
(66.20F Wet Bulb)and outdoor air temperature of 350C Dry Bulb (950F Dry Bulb),240C Wet Bulb (75.20F Wet Bulb)

2. Specificaton are subjected to change without prior notice for further improvement.

6
2.1Specification
Indoor CS-KC18SKY3M-1 CS-KC18SKY3R-1 CS-KC12SKY4A
MODEL
Outdoor CU-KC18SKY3M-1 CU-KC18SKY3R-1 CU-KC12SKY4A
Performance Test Condition Indian Standard Indian Standard Indian Standard
Power Supply Phase,Hz Single,50 Single,50 Single,50
V 230 230 230
Capacity kW 4.99 5.10 3.46
BTU/h 17,025 17,401 11,805

Running Current A 7.1 7.4 4.7


Input Power W 1560 1020
1620
EER Class Star 3 3 4
W/W 3.20 3.15 3.39
EER 10.74 11.57
BTU/h 10.91

Power Factor % 98 98 98
Cooling

Power Level dB - - -
Indoor Noise
db-A High:48;Low:43 High:48;Low:43 High:48;Low:43

PowerLevel dB - - -
Outdoor Noise
db-A 58 58 54
Max Current (A)/Max Input Power (W) 10.5A / 2.14 KW 10.5A / 2.14 KW 6.4A / 1.25 KW
Starting Current (A) 41.0 A/ 1.37 K 41.0 A/ 1.37 K 23.3 A/ 1.02 K
Type Rotary Rotary Rotary
Compressor
Motor Type Induction (2 Pole) Induction (2 P) Induction (2 P)
Output Power W 1320/1365 1320/ 1365 845/ 865
FAN Type Cross Flow Fan Cross Flow Fan Cross Flow Fan
Material ASG30K1 ASG30K1 ASG30K1
MotorType DC (8 Pole) DC (8 Pole) DC (8 Pole)
Power
W 30 30 30
Indoor

Lo rpm 1150 1060 1060


Speed Me rpm 1310 1170 1170
Hi rpm 1570/1470 1280 1380/1280
Type Propeller Fan Propeller Fan Propeller Fan
FAN
Material ABS ABS ABS
MotorType AC/Induction(6 Pole) Induction(6 Pole) AC/Induction(6 Pole)
Outdoor

Power W 54 54 26

Speed Hi rpm 1140 1140 1140


Moisture Removal L/h (Pt/h) 2.9 2.9 2.2
Cool m3/min.(ft3/min.) 14.0(494) 14.0(494) 11.7(413)
Indoor Airflow
Heat m3/min.(ft3/min) - - -

Outdoor Airflow Hi m3/min.(ft3/min.) 46.0 (1620) 46.0 (1620) 36.0 (1270)

Key in gas amount in W unit 1025 1110 960


Control Device Capillary Tube Capillary Tube Capillary Tube
Refrigeration Cycle Refrigerant Oil cm3 4GSD(570ml) 4GSD(570ml) 4GSD(44ml)
RefrigerantType g(oz) R22 R22 R22
7
Indoor CS-KC18SKY3M-1 CS-KC18SKY3R-1 CS-KC12SKY4A
Model
Outdoor CU-KC18SKY3M-1 CU-KC18SKY3R-1 CU-KC12SKY4A

mm(inch) 290(11-7/16) /
Height(I/D / O/D) 290(11-7/16)/619 290(11-7/16)/619
Dimension 619
Length(I/D / O/D) mm(inch) 870(34-9/32)/824 1070(42-5/32)/
870(34-9/32)/824
824
Depth(I/D / O/D) mm(inch) 204(8-1/16)/299 235(9-1/4)/299 204(8-1/16)/299
Weight Net(I/D / O/D) kg(lb) 12(26)/43(95) 12(26)/45(99) 9(20)/34(75)
Pipe Diameter(liquid/gas) 6.35(1/4)/ 6.35(1/4)/ 6.35(1/4)/
mm(inch)
12.70(1/2) 12.70(1/2) 12.70(1/2)
Standard Length m(ft) Flare, 5.0 (16.4) Flare, 5.0 (16.4) Flare, 5.0 (16.4)

Piping Length Range(min-max) m(ft) 3-15 3-15 3-15


I/D & O/D Height different g/m(oz/ft) 5 (16.4) 5 (16.4) 5 (16.4)

Additional gas amount g/m(oz/ft) 30(0.3) 10(0.1) 10(0.1)


Length for Additional gas m(ft) 7.5 (24.6) 7.5 (24.6) 7.5 (24.6)
Inner Diameter mm 16.2 16.2 16.2
Drain Hose Length mm 650 650 650
Fin Material Al(PreCoat) Al(PreCoat) Al(PreCoat)

Indoor Heat Exchanger Fin Type Slit Fin Slit Fin Slit Fin
Row xStage xFPI 2 x 15 x 21 2 x 15 x 20
2 x 15 x 19
Size(W X H X L) mm 610 x 315 x 25.4 810 x 315 x 25.4 610 x 315 x 25.4
Fin Material Aluminium Copper Copper
Outdoor Heat Exchanger
Fin Type/PASS Slit Fin Slit Fin Slit Fin
Row xHair Pin xFPI 58 channel 2 x 23 x 17 1 x 23 x 14
Size(W X H X L) 16 x 579 x 796 12.7 X 595 X 606 12.7 X 595 X 795
Air Filter Material PP PP PP
Type One Touch One Touch One Touch
Power Supply Indoor Indoor Indoor
Power Supply Cord A 16 16 15
Protection Device Overload Protector
Dry Bulb Wet Bulb Dry Bulb Wet Bulb
Indoor Operation Range Maximum0C 35 24 35 24
Minimum0C 16 11 16 11
Maximum0C 46 27 46 27
Outdoor Operation Range
Minimum0C 16 11 16 11

Note:
1.Cooling capacities are based on indoor temperature of 270C Dry Bulb (80.60F Dry Bulb),19.00C Wet Bulb
(66.20F Wet Bulb)and outdoor air temperature of 350C Dry Bulb (950F Dry Bulb),240C Wet Bulb (75.20F Wet Bulb)

2. Specificaton are subjected to change without prior notice for further improvement.

8
2.2Specification
Indoor CS-KC18SKY4A CS-KC18SKY3PM CS-KC18SKY3PR
MODEL
Outdoor CU-KC18SKY4A CU-KC18SKY3PM CU-KC18SKY3PR
Performance Test Condition Indian Standard Indian Standard Indian Standard
Phase,Hz Single,50 Single,50 Single,50
Power Supply
V 230 230 230
Capacity kW 5.15 4.99 5.10
BTU/h 17,571 17,025 17,401

Running Current A 7.0 7.1 7.4


Input Power W 1530 1560 1620
EER Class Star 4 3 3
W/W 3.37 3.20 3.15
EER 10.91
BTU/h 11.48 10.74

Power Factor % 98 98 98
Cooling

Power Level dB
- -
Indoor Noise
High:48;Low:43 High:48;Low:43
db-A High:48;Low:43

PowerLevel dB - -
Outdoor Noise
db-A 58 58 58
Max Current (A)/Max Input Power (W) 10.5 A/ 2.14KW 10.5A / 2.14 KW 10.5A / 2.14 KW
Starting Current (A) 33.7 A/1.49K 41.0 A/1.37 K 41.0 A/1.37 K
Type Rotary Rotary Rotary
Compressor
Motor Type Induction (2 Pole) Induction (2 Pole) Induction (2 Pole)
Output Power W 1280 1320/1365 1320/1365
FAN Type Cross Flow Fan Cross Flow Fan Cross Flow Fan
Material ASG30K1 ASG30K1 ASG30K1
MotorType DC (8 Pole) DC (8 Pole) DC (8 Pole)

Power W 30 30 30
Indoor

Lo rpm 1060 1150 830


Speed Me rpm 1170 1310 1000

Hi rpm 1380/1280 1570/1470 1280/1180


Type Propeller Fan Propeller Fan Propeller Fan
FAN
Material ABS ABS ABS
MotorType AC/Induction(6 Pole) AC (6 Pole) AC (6 Pole)
Outdoor

Power W 60 60 60
Speed Hi rpm 1140 900 900
Moisture Removal L/h (Pt/h) 3.0 2.9 2.9
Cool m3/min.(ft3/min.) 16.0(565) 14.0(494) 14.0(494)
Indoor Airflow
Heat m3/min.(ft3/min.) - - -

Outdoor Airflow Hi m3/min.(ft3/min.) 1620 1620 1620

Key in gas amount in W unit 1260 1110 1110


Control Device Capillary Tube Capillary Tube Capillary Tube
Refrigeration Cycle Refrigerant Oil cm3 SUNISO4GSD(570ml) SUNISO4GSD(570ml) SUNISO4GSD(570ml)

RefrigerantType g(oz) R22 R22 R22


9
Model Indoor CS-KC18SKY4A CS-KC18SKY3PM CS-KC18SKY3PR
Outdoor CU-KC18SKY4A CU-KC18SKY3PM CU-KC18SKY3PR

Height(I/D / O/D) mm(inch) 290(11-7/16) /619 290(11-7/16) / 619 290(11-7/16) / 619


Dimension
Length(I/D / O/D) mm(inch) 1070(42-5/32)/824 870(34-9/32)/824 1070(42-5/32)/824
Depth(I/D / O/D) mm(inch) 235(9-1/4)/299 204(8-1/16)/299 235(9-1/4)/299
Weight Net(I/D / O/D) kg(lb) 12(26)/40(88) 9(20)/43(95) 12(26)/45(99)

Pipe Diameter(liquid/gas) mm(inch) 6.35(1/4)/12.70(1/2) 6.35(1/4)/12.70(1/2) 6.35(1/4)/12.70(1/2)


Standard Length m(ft) Flare, 5.0 (16.4) Flare, 5.0 (16.4) Flare, 5.0 (16.4)
Piping Length Range(min-max) m(ft) 3-15 3-15 3-15

I/D & O/D Height different g/m(oz/ft) 5 (16.4) 5 (16.4) 5 (16.4)

Additional gas amount g/m(oz/ft) 10(0.1) 10(0.1) 10(0.1)


Length for Additional gas m(ft) 7.5 (24.6) 7.5 (24.6) 7.5 (24.6)
Inner Diameter mm 16.2 16.2 16.2
Drain Hose Length mm 650 650 650
Fin Material Aluminium(PreCoat) Aluminium(PreCoat) Aluminium(PreCoat)

Indoor Heat Exchanger Fin Type Slit Fin Slit Fin Slit Fin
Row xStage xFPI 2 x 15 x 19 2 x 15 x 21
2 x 15 x 21
Size(W X H X L) mm 810 x 315 x 25.4 610 x 315 x 25.4 810 x 315 x 25.4
Fin Material Copper Aluminium Copper
Outdoor Heat Exchanger
Fin Type/PASS Slit Fin Slit Fin Slit Fin
Row xHair Pin xFPI 56 channel 52channel 2 x 20 x 20
Size(W X H X L) 16 x 539 x 510 16 x 520 x 755 25.4 x 507 x 766
Air Filter Material PP PP PP
Type One Touch One Touch One Touch
Power Supply Indoor Indoor Indoor
Power Supply Cord A 15 16 16
Protection Device Overload Protector
Dry Bulb Wet Bulb Dry Bulb Wet Bulb
0
Indoor Operation Range Maximum C 35 24 35 24
0
Minimum C 16 16 11
11
0
Maximum C 46 27 46 27
Outdoor Operation Range
Minimum0C 16 11 16 11

Note:
1.Cooling capacities are based on indoor temperature of 270C Dry Bulb (80.60F Dry Bulb),19.00C Wet Bulb
(66.20F Wet Bulb)and outdoor air temperature of 350C Dry Bulb (950F Dry Bulb),240C Wet Bulb (75.20F Wet Bulb)

2. Specificaton are subjected to change without prior notice for further improvement.

10
3. Location of Controls and Components

3.1 Indoor Unit

3.2 Outdoor Unit

HG Chassis

11
3.3 Remote Control

Model: KC12SKY3 Model: KC12SKY*Series/KC18SKY*Series

Model: KC-18SKY3R-1

12
4. Dimensions
4.1 Indoor Unit
CS-KC12SKY* Series

13
4.2 Dimensions
4.2.1 Indoor Unit
CS-KC18SKY*Series

14
4.3
Model: KC12SKY* Series / KC18SKY* Series

HG Chassis

15
5. Refrigeration Cycle Diagram

16
6. Block Diagram

17
7.1 Wiring Connection Diagram
7.1.1 CS-KC12SKY3 CU-KC12SKY3

Model CU-KC12SKY3 Model CU-KC12SKY3


Connection ACXB09-00320 Connection A951871
C-R 3.11 Blue - Yellow 324
C-S 4.12 Red- Yellow 324

18
7.2 Wiring Connection Diagram
7.2.1 CS-KC18SKY3M-1 CU-KC18SKY3M-1,CS-KC18SKY3R-1 CU-KC18SKY3R-1, CS-KC18SKY4A CU-KC18SKY4A,CS-
KC18SKY3PR CU-KC18SKY3PR, CS-KC18SKY3PM CU-KC18SKY3PM

Model CU-KC18SKY3M-1/3PM 3PR / 4A Model CU-KC18SKY3M-1 / 4A / 3PR / 3PM


Connection B092814 ACXB09-00270 Connection A921566
C-R 1.94 1.94 Blue - Black 125

C-S 1.79 1.79 Black- Red 66.6

19
7.3 Wiring Connection Diagram
7.3.1 CS-KC18SKY3R-1 CU-KC18SKY3R-1,CS-KC12SKY3E CU-KC12SKY3E, CS-KC12SKY3A CU-KC12SKY3A

Model CU-KC18SKY3R-1 CU-KC12SKY3E/12SKY3A Model CU-KC18SKY3R-1 Model 12SKY3E/3A


Connection B092814 ACXB09-00320 Connection A921566 Connection A951871
C-R 1.94 3.11 Blue - Black 125 Blue - Yellow 324
C-S 1.79 4.12 Black- Red 66.6 Red- Yellow 324

20
7.4 Wiring Connection Diagram
7.4.1 CS-KC12SKY4A CU-KC12SKY4A

Model CU-KC12SKY4A Model CU-KC12SKY4A


Connection ACXB09-00260 Connection A921566
C-R 2.63 Blue - Yellow 324
C-S 2.44 Red-Yellow 324

21
8. Electronic Circuit Diagram
8.1 CS-KC12SKY3,CS-KC18SKY3M-1,CS-KC18SKY3R-1,CS-KC12SKY3E,CS-KC12SKY3A,CS-KC12SKY4A,CS-
KC18SKY4A,CS-KC18SKY3PR,CS-KC18SKY3PM

22
9. Printed Circuit Board
9.1 Indoor Unit
9.1.1 Main Printed Circuit Board
CS-KC12SKY3,CS-KC12SKY* Series

AC303

RY-PWR

CN-FM

CN-TH

CN-STM1

CN-DISP

Service Code No.


Complete Code No.

23
9. Printed Circuit Board
9.2 Indoor Unit
9.2.1 Main Printed Circuit Board
CS-KC18SKY3* Series,CS-KC18SKY4* Series

AC310

RY-PWR

CN-FM

CN-STM1

Service Code No.


CN-TH

Complete Code No.

24
9.2.2 Indicator and Receiver Printed Circuit Board
CS-KC12* Series/CS-KC18* Series

25
10. Installation Instruction
10.1 Select the Best Location

10.1.1 Indoor Unit


Do not install the unit in excessive oil fume area
such as kitchen, workshop and etc.
There should not be any heat source or steam
near the unit.
There should not be any obstacles blocking the air
circulation.
A place where air circulation in the room is good.
A place where drainage can be easily done.
A place where noise prevention is taken into
consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the
wall, ceiling, fence or other obstacles.
Recommended installation height for indoor unit
shall be at least 2.5 m.

10.1.2 Outdoor Unit


If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from
the condenser is not obstructed.
There should not be any animal or plant which
could be affected by hot air discharged.
Keep the spaces indicated by arrows from wall,
ceiling, fence or other obstacles.
Do not place any obstacles which may cause a
short circuit of the discharged air.
If piping length is over the [piping length for
additional gas], additional refrigerant should be
added as shown in the table.

26
10.2 Indoor Unit
10.2.1 How to Fix Installation Plate

The center of installation plate should be at more than (1) at right and left of the wall.
The distance from installation plate edge to ceiling should more than (2)
From installation plate center to unit’s left side is (3)
From installation plate center to unit’s right side is (4)
For left side piping, piping connection for liquid should be about (5) from this line.
For left side piping, piping connection for gas should be about (6) from this line.
1) Mount the installation plate on the wall with 5 screws or more (at least 5 screws).
(If mounting the unit on the concrete wall, consider using anchor bolts.)
i) Always mount the installation plate horizontally by aligning the marking-off line with the thread and using a level gauge.
2) Drill the piping plate hole with ø70 mm hole-core drill.
i) Putting measuring tape at position as shown in the diagram above.
The hole center is obtained by measuring the distance namely 128 mm for left and right hole
respectively. Another method is intersection point of arrow mark extension.
The meeting point of the extension arrow mark is the hole center position.
ii) Drill the piping hole at either the right or the left and the hole should be slightly slanting to the outdoor
side. (refer to step 10.2.2)

10.2.2 To Drill a Hole in the Wall and


Install a Sleeve of Piping
1 Insert the piping sleeve to the hole.
2 Fix the bushing to the sleeve.
3 Cut the sleeve until it extrudes about 15 mm
from the wall.

CAUTION

When the wall is hollow, please be sure to use the


sleeve for tube assembly to prevent dangers
caused by mice biting the connection cable.

4 Finish by sealing the sleeve with putty or


caulking compound at the final stage.
27
10.2.3 Indoor Unit Installation
# Do not turn over the unit without it's shock absorber during pull out the piping. It may cause intake grill damage.
# Use shock absorber during pull out the piping to protect the intake grill from damage

10.2.3.1 For the right rear piping

10.2.3.2 For the right and right bottom piping

10.2.3.3 For the embedded piping

(This can be used for left rear piping and bottom


piping also.)
28
10.2.4 Connect the Cable to the Indoor Unit
The power supply cord, indoor and outdoor unit connection cable can be connected without removing the front grille.
1 Install the indoor unit on the installing holder that mounted on the wall,
2 Open the front panel and grille door by loosening the screw.
3 Cable connection to the power supply through Isolating Devices (Disconnecting means).
o Connect the approved PVC sheathed or polychloroprene sheathed power supply cord 3 x 1.5 mm2
(1.5HP) or 3 x 2.5 mm2 (2.0~2.5HP), type designation IS 694 or 60245 IEC 57 or heavier cord to the
terminal board, and connect the other end of the cable to Isolating Devices (Disconnecting means).
o Do not use joint power supply cord. Replace the wire if the existing wire (from concealed wiring, or
otherwise) is too short.
o In unavoidable case, joining of power supply cord between isolating devices and terminal board of air
conditioner shall be done by using approved socket and plug rated 15/16A (1.5HP) or 16A (2.0HP) or
20A (2.5HP). Wiring work to both socket and plug must follow to national wiring standard.
4 Bind all the power supply cord lead wire with tape and route the power supply cord via the left escapement.
5 Connection cable between indoor unit and outdoor unit shall be approved PVC sheathed or polychloroprene
sheathed 3 x 1.0 mm2 (1.5HP) or 3 x 1.5 mm2 (2.0HP ~2.5HP) flexible cord. Do not use joint connection
cable. Replace the wire if the existing wire (from concealed wiring, or otherwise) is too short.
6 Bind all the indoor and outdoor connection cable with tape and route the connection cable via the right
escapement.

29
7 Remove the tapes and connect the power supply cord and connection cable between indoor unit and outdoor
unit according to the diagram below.

8 Secure the power supply cord and connection cable onto the control board with the holder.
9 Close grille door by tighten with screw and close the front panel.

Note:
Isolating Devices (Disconnecting means) should have minimum 3.0 mm contact gap.
Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor’s respectively.
Earth wire shall be Yellow/Green (Y/G) in colour and longer than the other AC wires as shown in the figure for the
electrical safety in case of the slipping out of the cord from the anchorage.

30
10.2.5 Wire Stripping And Connecting Requirement

31
10.3 Outdoor Unit
10.3.1 Install the Outdoor Unit
After selecting the best location, start installation according to indoor/outdoor unit installation diagram.
1 Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10 mm).
2 When installing at roof, please consider strong wind and earthquake.
Please fasten the installation stand firmly with bolt or nails.

10.3.2 Connect the Piping

10.3.2.1 Connecting the piping to indoor


Please make flare after inserting flare nut (locate at joint portion
of tube assembly) onto the copper pipe.
(In case of using long piping)

Connect the piping


Align the center of piping and sufficiently tighten the flare nut with fingers.
Further tighten the flare nut with torque wrench in specified torque as stated in the table.

10.3.2.2 Connecting the piping to outdoor


Decide piping length and then cut by using pipe cutter. Remove burrs from cut edge.
Make flare after inserting the flare nut (locate at valve) onto the copper pipe.
Align center of piping to valves and then tighten with torque wrench to the specified torque as stated in the table.

Do not overtighten, overtightening may cause gas leakage

Piping size Torque


6.35 mm (1/4”) [18 N•m (1.8 kgf.m)]
9.52 mm (3/8”) [42 N•m (4.3 kgf.m)]
12.7 mm (1/2”) [55 N•m (5.6 kgf.m)]
15.88 mm (5/8”) [65 N•m (6.6 kgf.m)]
19.05 mm (3/4”) [100 N•m (10.2 kgf.m)]

32
FOR ENVIRONMENTAL PROTECTION, MANUFACTURER STRONGLY RECOMMENDS TO USE EVACUATION METHOD.

10.3.3 Evacuation of the Equipment

1 Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way
valve.
Be sure to connect the end of the charging hose with the push pin to the service port.
2 Connect the center hose of the charging set to a vacuum pump.
3 Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from
0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
4 Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the
gauge does not move after approximately five minutes.
Note: BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERENT GAS LEAKAGE.
5 Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6 Tighten the service port caps of the 3-way valve at a torque of 18 N•m with a torque wrench.
7 Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN”
using a hexagonal wrench (4 mm).
8 Mount valve caps onto the 2-way valve and the 3-way valve.
Be sure to check for gas leakage.

33
10.3.4 Air Purging of the Piping and Indoor
The remaining air in the Refrigerant cycle which contains moisture may cause malfunction on the compressor.
1 Remove the caps from the 2-way and 3-way valves.
2 Remove the service-port cap from the 3-way valves.
3 To open the valve, turn the valve stem of 2-way valve counter-clockwise approx. 90° and hold it there for ten
seconds, then close it.
4 Check gas-leakage of the connecting portion of the pipings.
For the left piping, refer to 4 (A).

10.3.5 Connect the cable to the Outdoor Unit


1. Remove the control board cover from the unit
by loosening the screw.
2. Connecting cable between indoor unit and
outdoor unit shall be approved type PVC
sheathed or polychloroprene sheathed 3 x
1.0 mm2 (1.5HP) or 3 x 1.5mm2 (2.0~2.5HP)
flexible cord, type designation 245 IEC 57 or
heavier cord. Do not use joint connection
cable. Replace the wire if the existing wire
(from concealed wiring, or otherwise) is too
short.

3. Secure the cable onto the control board with


the holder (clamper).
4. Attach the control board cover back to the
original position with the screw.
5. For wire stripping and connection requirement, Earth wire shall be Yellow/Green (Y/G) in colour
refer to instruction 10.2.5 of the indoor unit. 34 and longer than other AC wires for safety reason.
10.3.6 Piping Insulation
1 Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation
Diagram. Please wrap the insulated piping end to prevent water from going inside the piping.
2 If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by
using POLY-E-FOAM with thickness 6 mm or above.

10.3.6.1 Cutting and flaring the piping


1 Please cut using pipe cutter and then remove the burrs.
2 Remove the burrs by using reamer. If burrs are not removed, gas leakage may be caused.
Turn the piping end down to avoid the metal powder entering the pipe.
3 Please make flare after inserting the flare nut onto the copper pipes.

10.4 Front Grille

35
10.5 PM 2.5/ Catechin Filter

36
11. Operation Control

11.1 Cooling Operation


Cooling operation can be set using remote control.
This operation is applied to cool down the room temperature to the setting temperature set on the remote control.
The remote control setting temperature, which takes the reading of intake air temperature sensor, can be
adjusted from 16°C to 30°C.
During cooling operation, the compressor will stop and restart as shown in figure below:

11.1.1 Cooling Operation Time Diagram

37
11.2 Dry Operation
Dry operation can be set using remote control.
Dry operation is applied to dehumidify and to perform a gentle cooling to the room.
This operation starts when the intake air temperature sensor reaches -1.5°C from the setting temperature on the
remote control.
When operation begins,Dry will be switched “ON” for a maximum 10 minutes, then Dry operation will be
turned “OFF” for a minimum 6 minutes. After that, the Dry operation will be “ON” and “OFF” based on the
setting temperature as shown in figure below.
However after 3 minutes of compressor off, during Dry “OFF” (within 6 minutes Dry restart control), the
indoor unit will start to operate at normal Cooling mode if the intake temperature is higher than Cooling “ON” point.

11.2.1 Dry Operation Time Diagram

38
11.3 Automatic Operation
Automatic operation can be set using remote control.
This operation starts to operate with indoor fan at SLo speed for 20 seconds to judge the intake air temperature.
After judged the temperature, the operation mode is determined by referring to the below standard.

Then, the unit starts to operate at determined operation mode, until it is switched off using remote control, with
the setting temperature as shown in table below.

The setting temperature for all the operations can be changed one level up or one level down from the standard
temperature as shown in table below by pressing the temperature up or temperature down button at remote
control.

The operation mode judging temperature and standard setting temperature can be increased by 2°C
permanently, by open the circuit of JX03 at indoor unit’s printed circuit board.

11.4 Indoor Fan Speed Control


Indoor fan speed can be set using remote control

11.4.1 Fan Speed Rotation Chart

Speed Fan Speed (rpm)


CS-KC18SKY3R-1 CS-KC18SKY4A CS-KC18SKY3PM/M-1 CS-KC12SKY4A CS-KC18SKY3PR/R-1/KC12SKY3/3E/3A

S Hi/Hi 1280/1180 1380/1280 1570/1470 1330/1230 1380/1280

Me 1000 1170 1310 1030 1170

Lo 830 1060 1150 830 1060

Model: CS-KC12SKY3* CS-KC18SKY3M-1 CS-KC18SKY3R-1 CS-KC18SKY4A CS-KC18SKY3PR CS-KC12SKY4A CS-KC18SKY3PM

39
11.4.2 Automatic Fan Speed Control
When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table.
o Fan speed rotates in the range of Hi and Me.
o Deodorizing Control will be activated.

Auto Fan Speed during cooling operation:


1 Indoor fan will rotate alternately between off and on as shown in below diagram.
2 At the beginning of each compressor starts operation, indoor fan speed increases gradually for deodorizing
purpose.
3 For the first time the compressor operates, indoor fan will be switched to Hi fan speed from Lo- after
70 seconds from the start of compressor. This cause the room temperature to achieve the setting
temperature quickly.
4 During compressor stops, indoor fan will operate at Lo- for the beginning 3 minutes to prevent higher volume
of refrigerant in liquid form returning to the compressor.
5 After the compressor turned off for 3 minutes, indoor fan will start to operate at Lo- to circulate the air in the
room. This is to obtain the actual reading of the intake air temperature.
6 For the resume of compressor operation, indoor fan will operate at Me fan speed to provide comfort and
lesser noise environment, after 70 seconds from the restart of compressor.

40
Auto Fan Speed during Soft Dry operation:
1 Indoor fan will rotate alternately between off and Lo-.
2 At the beginning of each compressor starts operation, indoor fan will increase fan speed gradually for
deodorizing purpose.
3 When compressor turned off for 6 minutes, indoor fan will start at Lo- to circulate the air in the room. This is
to obtain the actual reading of intake air temperature.

11.4.3 Manual Fan Speed Control


Manual fan speed adjustment can be carried out by using the Fan Speed selection button at the remote control.
There are 3 types of fan speed settings: Lo, Me, Hi.

11.4.4 Indoor Fan Motor rpm Abnormal Control


Immediate after the fan motor is started, rpm abnormal control is performed every second.
During fan motor on, if fan motor feedback e” 2550 rpm or < 50 rpm continuously for 10 seconds, the fan motor
error counter increased; fan motor is then stopped and restarted. If the fan motor error counter increased to 7,
then air conditioner will stop operation.

11.5 Outdoor Fan Speed Control (KC12SKY**)


There is only one speed for outdoor fan motor.
When the air conditioner is turned on, the compressor and the outdoor fan will operate simultaneously.
Likewise, both compressor and outdoor fan will stop at the same time if the unit is turned off.

11.6 Outdoor Fan Speed Control (KC18SKY**)


Outdoor fan speed can be changes to Hi or Lo accordingly to outdoor temperature.
When the air conditioner is turned on, the compressor and the outdoor fan will operate simultaneously.
Likewise, both compressor and outdoor fan will stop at the same time if the unit is turned off.

11.6.1Outdoor
11.6.2 Fan Speed
FanRotation Chart
Motor rpm Abnormal Control
During fan motor ON, if fan motor feedback e” 2550 rpm or < 50 rpm continuously for 3 times, the fan motor will
stop operation.

CU-UC24RKY

41
11.7 Vertical Airflow Direction Control

11.7.1 Auto Control


When the vertical airflow direction is set to Auto using the remote control, the louver swings up and down as
shown in the diagram.
When stops operation using the remote control, the discharge vent is reset and stops at the closing position.
During Cooling operation or Soft Dry operation, indoor fan motor may stop to rotate at certain periods. At that
condition, the louver will stop swinging.

11.7.2 Manual Control


When the vertical airflow direction is set to Manual using the remote control, the automatic airflow is released and
the airflow direction louver move up and down in the range shown in the diagram.
The louver can be adjusted by pressing the button to the desired louver position.
When stop operation using the remote control, the discharge vent is reset, and stop at the closing position.

11.8 Horizontal Airflow Direction Control


The horizontal airflow direction louvers can be adjusted manually by hand.

11.9 Timer Control

11.9.1 ON Timer
When the ON Timer is set using the remote control, the unit will start to operate slightly before the set time, so
that the room will reach nearly to the set temperature by the set time.
For Cooling and Soft Dry operation, the operation will start 15 minutes before the set time.
For Automatic operation, the indoor fan will operate at SLo speed for 20 seconds, 15 minutes before the set time
to detect the intake air temperature to determine the operation mode. The Power indicator will blink at this time.

11.9.2 OFF Timer


When the OFF Timer is set by using the remote control, the unit will stop operate according to the desired setting.
Notes:
1 By pressing ON/OFF operation button, the ON Timer or OFF Timer setting will not be cancelled.
2 To cancel the previous timer setting, press CANCEL button.
3 To activate the previous timer setting, press SET button.
4 If main power supply is switched off, the Timer setting will be cancelled.

42
11.10 Random Auto Restart Control
If there is a power failure during operation, the air conditioner will automatically restart after 3 to 4 minutes when
the power is resumed.
It will start with previous operation mode and airflow direction.
If there are more than one air conditioner unit in operation and power failure occur, restart time for each unit to
operate will be decided randomly using 4 parameters: intake air temperature, setting temperature, fan speed and
air swing louver position.
This random Auto Restart Control is not available when Timer is set.
This control can be omitted by open the circuit of JX02 (refer printed circuit board indoor unit).

11.11 Remote Control Signal Receiving Sound


Short beep sound will be heard when turn ON the air conditioner or enabling other operations.
Long beep sound will be heard when turn OFF the air conditioner or disabling other operations.

43
12. Protection Control

12.1 Restart Control (Time Delay Safety Control)


When the thermo-off temperature (temperature which compressor stops to operate) is reached during:
o Cooling operation – the compressor stops for 3 minutes (minimum) before resume operation.
o Dry operation – the compressor stops for 6 minutes (minimum) before resume operation.
If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the
moment operation stop, although the unit is turn on again within the period.
This phenomenon is to balance the pressure inside the refrigerant cycle.

12.2 7 Minutes Time Save Control


The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls
between the compressor ON (A) temperature and compressor OFF temperature (B) during the period.
This phenomenon is to reduce the built up humidity inside a room.

12.3 60 Seconds Forced Operation


Once the air conditioner is turned on, the compressor will not stop within 60 seconds in a normal operation
although the intake air temperature has reached the thermo-off temperature. However, force stop by pressing the
OFF/ON button at the remote control is permitted.
The reason for the compressor to force operation for minimum 60 seconds is to allow the refrigerant oil run in a
full cycle and return back to the outdoor unit.

12.4 Starting Current Control


When the compressor, outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor
will start to operate 1.6 second later.
The reason of the difference is to reduce the starting current flow.

12.5 Freeze Prevention Control


If the temperature of the indoor heat exchanger falls below 2°C continuously for 4 minutes or more, the
compressor turns off. The fan speed setting remains the same.
This phenomenon is to protect the indoor heat exchanger from freezing and to prevent higher volume of
refrigerant in liquid form returning to the compressor.
Compressor will restart again when the indoor heat exchanger temperature rises to 10°C (Recovery).
Restart control (Time Delay Safety Control) will be applied in this Control if the recovery time is too short.

44
12.6 Compressor Reverse Rotation Protection Control
If the compressor is operating continuously for 5 minutes or longer and the temperature difference between
intake air and indoor heat exchanger is 2.5°C or less for continuously 2 minutes, compressor will stop and restart
automatically.
Time Delay Safety Control is activated before the compressor restart.

Compressor starts for ≥ 5 minutes Compressor Compressor


restart
5T ≤ 2.5°C for 2 minutes OFF

5T = Intake air temperature – Indoor heat exchanger temperature


This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
If this condition happens continuously for 5 times within 50 minutes, unit will turns OFF with TIMER indicator
blinks.
The 5 Times counter can be reset when either one of the following condition happen:
o Unit is OFF by remote control or AUTO OFF/ON button.
o Indoor intake temperature – Indoor piping temperature > 5°C for 1 minute or more.
o Operation mode change.
The unit could be ON by pressing OFF/ON button at remote control but the TIMER LED will continue blinking.
TIMER LED blinking will be reset if:
o Indoor intake temperature – Indoor piping temperature > 5°C for 1 minute or more.
o Power supply reset.

12.7 Dew Prevention Control


To prevent dew formation at indoor unit discharge area.
This control will be activated if:
o Cooling mode.
o Remote Control setting temperature is less than 25°C.
o Fan speed is at CLo.
o Room temperature is constant (±1°C) for 30 minutes.
o Compressor is continuously running.
Fan speed will be adjusted accordingly in this control.
o Fan speed will be increased slowly if the unit is in quiet mode but no change in normal cooling mode.
Dew prevention stop condition
o Remote control setting temperature is more than 25°C.
o Fan speed is not set to CLo.

45
13. Servicing Mode

13.1 Auto OFF/ON Button

1 AUTO OPERATION MODE


The Auto Operation will be activated immediately once the Auto OFF/ON button is pressed. This operation
can be used to operate air conditioner with limited function if remote control is misplaced or malfunction.
2 TEST RUN OPERATION (FOR PUMP DOWN/SERVICING PURPOSE)
The Test Run Operation will be activated if the Auto OFF/ON button is pressed continuously for more than 5
seconds. A “beep” sound will be heard at the fifth second, in order to identify the starting of this operation.
3 VARIOUS SETTING MODE
The Various Setting Mode will be activated if (within 20 seconds of Test Run Operation) the Auto OFF/ON
button is pressed for more than 5 seconds. 2 “beep” sounds will be heard to identify the starting of this
operation.
Under Various Setting Mode, user could perform the following operation:
i. Press Auto OFF/ON button to toggle remote control receiving sound.
- Short “beep”: Turn ON remote control receiving sound.
- Long “beep”: Turn OFF remote control receiving sound.
After Auto OFF/ON button is pressed, the 20 seconds counter for Remote Control Receiving Sound OFF/ON
Mode is restarted.
ii. Remote Control Number Switch.
- There are 4 types of remote control transmission code could be selected and stored in EEPROM of
indoor unit. The indoor unit will only operate when received signal with same transmission code from
remote control. This could prevent signal interference when there are 2 or more indoor units installed
nearby together.
- To change remote control transmission code, short or open jumpers at the remote control printed circuit board.

- During Various Setting Mode, press any button at remote control to transmit and store the desired
transmission code to the EEPROM.
- After signal is received, the Various Setting Mode is cancelled and return to normal operation.
- If there is no code is transmitted of Auto OFF/ON button is not pressed within 20 seconds, the
Various Setting Mode will be cancelled.

46
13.2 Remote Control Button

13.2.1 SET Button

To check current remote control transmission code and store the transmission code to EEPROM:
o Press “Set” button for more than 10 seconds
o Press “Timer Set” button until a “beep” sound is heard as confirmation of transmission code change

13.2.2 RESET

To clear and restore the remote control setting to factory default.


o Press once to clear the memory

13.2.3 TIMER

To change indoor unit indicators’ intensity:


o Press continuously for 5 seconds

13.2.4 TIMER

To change remote control display from Degree Celsius (°C) to Degree Fahrenheit (°F)
o Press continuously for 10 seconds

47
14. Troubleshooting Guide
14.1 Refrigeration cycle system
In order to diagnose malfunctions, ensure the air conditioner is free
from electrical problems before inspecting the refrigeration cycle.
Such problems include insufficient insulation, problem with the
power source, malfunction of a compressor and a fan. The normal
outlet air temperature and pressure of the refrigeration cycle
depends on various conditions, the standard values for them are
shown in the table to the right.

48
14.1.1 Relationship between the condition of the air conditioner and pressure and
electric current

49
15. Disassembly and Assembly Instructions
WARNING
High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with
repair work. Failure to heed this caution may result in electric shocks.

15.1 Indoor Electronic Controllers and Control Board Removal Procedures

15.1.1 To remove Front Grille Badge on Intake


1
Grille

3
Front Grille

15.1.2 To remove Power Electronic Controller

50
15.1.3 To remove Discharge Grille

51
15.1.4 To remove Control Board

15.1.5 To remove Cross Flow Fan and Indoor Fan Motor

52
53
15.2 Disassembly and Assembly Instructions
WARNING
High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with
repair work. Failure to heed this caution may result in electric shocks.

15.2 Outdoor Unit Removal Procedures

15.2.1 To remove the Front Panel:

Model: KC12SKY3, KC18SKY3M-1 ,KC18SKY3R-1 ,KC15SKY3R,KC12SKY3E,KC12SKY3A,KC12SKY4A,KC18SKY4A

HG Chassis

54
16. Technical Data

16.1 Operation Characteristics


CS-KC12SKY* Series, CU-KC12SKY* Series

55
Gas Side
Piping
Pressure
(MPa)

56
Gas Side
Piping
Pressure
(MPa)

57
16.2 Operation Characteristics
Model : CS-KC18SKY Series, CU-KC18SKY Series

58
Gas Side
Piping
Pressure
(MPa)

59
Gas Side
Piping
Pressure
(MPa)

60
17. Exploded View and Replacement Parts List
17.1 Indoor Unit CS-KC12SKY3 CS-KC18SKY3M-1 CS-KC12SKY3E CS-KC12SKY3A
CS-KC12SKY4A CS-KC18SKY3PM

37

3 36

4
38

2
1

7 5 10
8 6 9

33

34

30 17

35

12 19
25 13
11 14
16
22 31

15
23 32

29
20
26

24

27

21

39 28
18

Note:
• The above exploded view is for the purpose of parts disassembly and replacement.
• The non-numbered parts are not kept as standard service parts.

61
REF.
SAFETY PART NAME & DESCRIPTION QTY. CS-KC12SKY3 CS-KC12SKY3E CS-KC12SKY3A CS-KC12SKY4A IGP
NO.

1 CHASSIS-COMPLETE 1 CWD50C1769-AN ← ← ←
DC MOTORS (BRUSHLESS GENERAL
2 1 ACRL6CBYYYL0172 ← ← ← o
USE)
3 CROSS-FLOW FAN-COMPLETE 1 CWH02C1171-AN ← ← ACRH02K1052 o

4 BEARING ASS'Y 1 CWH64K1011 ← ← ------

5 BOX SHAPED PLATE 1 ACRD661267 ← ← ←

6 FIN & TUBE EVAPORATER-COMPLETE 1 CWB30C5030-AN ← ← ← o

7 UNION NUT 1 CWT251026 ← ← ← o

8 UNION NUT 1 CWT251062 ← ← ← o

9 PARTICULAR PIECE 1 CWD933739 ← ← ←

10 PARTICULAR PIECE 1 CWD933740 ← ← ←

11 HOLDER-SENSOR 1 CWH321110 ← ← ←

12 TERMINAL BOARD-COMPLETE 1 CWA28C2620-AN ← ← ← o

13 ELECTRONIC CONTROLLER-MAIN 1 CWA73C8302-AN# CWA73C9138-AN# ← CWA73C9132-AN# o

14 CONTROL BOARD COVER 1 CWH131611 ← ← ←

15 ELECTRONIC CONTROLLER-DISPLAY 1 ACRA747154-A CWA748192-W ← CWA748184-W o

16 CONTROL BOARD-COMPLETE 1 ACRH10C11100-1A ACRH16C1729-2-1AN ← CWH16C1727-1-AN o

17 SENSOR-COMPLETE 1 CWA50C2782 ← ← ← o

18 DISCHARGE GRILLE-COMPLETE 1 CWE20C3412-AN ← ← ← o

19 CONTROL BOARD COVER 1 CWH131612 ← ← ←

20 VANE-COMPLETE 1 CWE24C1458-AN ← ← ←

21 VANE-COMPLETE 1 CWE24C1459-AN ← ← ←

22 CAP 2 CWH521194 ← ← ←

23 INDICATOR-COMPLETE 1 CWE39C1235-AN ← ← ←

24 FULCRUM 1 CWH621102 ← ← ←

25 PARTICULAR PIECE 1 CWD934027 ← ← ←

26 FLEXIBLE PIPE 1 CWH851173 ← ← ←

27 FAN MOTOR (P.PH.V.) 1 CWA981264 ← ← ← o

28 VANE-COMPLETE 1 CWE24C1479-AN ← ← ←

29 CAP 1 CWH521259 ← ← ←

30 PARTICULAR PIECE 1 CWD933741 ← ← ←

31 PARTICULAR PIECE 1 CWD933762 ← ← ←

32 REMOTE CONTROL SWITCH-COMPLETE 1 CWA75C4289 CWA75C4621 ← ACRA75C03930

33 FRONT GRILLE-COMPLETE 1 ACRE10C02860-AN ACRE10C02920-AN ← ACRE10C03210-AN o

34 INTAKE GRILLE-COMPLETE 1 ACRE22C00840-AN ACRE22C00900-AN ← ACRE22C01060-AN

35 CONTROL BOARD COVER-COMPLETE 1 CWH13C1303-AN ← ← ←

36 INSTALLING HOLDER 1 CWH361134-A ← ← ←

37 AIR FILTER 2 ACRD00-00420 ← ← ←

38 AIR FILTER-COMPLETE 2 CWD00C1293 ← ← ←

39 C.C.CASE 1 ACRG50-16360 ← ← ←

NOTE:
• All parts are supplied from APIN, India (Vendor Code: 00026071).
• "O" marked parts are recommended to be kept in stock.

62
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-KC18SKY3M-1 CS-KC18SKY3PM IGP

1 CHASSIS-COMPLETE 1 CWD50C1769-AN ←

2 DC MOTORS (BRUSHLESS GENERAL USE) 1 ACRL6CBYYYL0172 ← o

3 CROSS-FLOW FAN-COMPLETE 1 CWH02C1171-AN ← o

4 BEARING ASS'Y 1 CWH64K1011 ←

5 BOX SHAPED PLATE 1 ACRD661267 ←

6 FIN & TUBE EVAPORATER-COMPLETE 1 CWB30C5030-AN CWB30C5046-AN o

7 UNION NUT 1 CWT251026 ← o

8 UNION NUT 1 CWT251062 ← o

9 PARTICULAR PIECE 1 CWD933739 ←

10 PARTICULAR PIECE 1 CWD933740 ←

11 HOLDER-SENSOR 1 CWH321110 ←

12 TERMINAL BOARD-COMPLETE 1 CWA28C2620-AN ACRA28C2783-1-AN o

13 ELECTRONIC CONTROLLER-MAIN 1 CWA73C8302-AN# CWA73C9131-AN# o

14 CONTROL BOARD COVER 1 CWH131611 ←

15 ELECTRONIC CONTROLLER-DISPLAY 1 ACRA747154-A CWA748192-W o

16 CONTROL BOARD-COMPLETE 1 ACRH10C11100-1A ACRH10C08490-1A o

17 SENSOR-COMPLETE 1 CWA50C2782 ← o

18 DISCHARGE GRILLE-COMPLETE 1 CWE20C3412-AN ← o

19 CONTROL BOARD COVER 1 CWH131612 ←

20 VANE-COMPLETE 1 CWE24C1458-AN ←

21 VANE-COMPLETE 1 CWE24C1459-AN ←

22 CAP 2 CWH521194 ←

23 INDICATOR-COMPLETE 1 CWE39C1235-AN CWE39C1224-AN

24 FULCRUM 1 CWH621102 ←

25 PARTICULAR PIECE 1 CWD934027 ←

26 FLEXIBLE PIPE 1 CWH851173 ←

27 FAN MOTOR (P.PH.V.) 1 CWA981264 ← o

28 VANE-COMPLETE 1 CWE24C1479-AN ←

29 CAP 1 CWH521259 ←

30 PARTICULAR PIECE 1 CWD933741 ←

31 PARTICULAR PIECE 1 CWD933762 ←

32 REMOTE CONTROL SWITCH-COMPLETE 1 CWA75C4289 CWA75C4621

33 FRONT GRILLE-COMPLETE 1 ACRE10C02860-AN ACRE10C02910-AN o

34 INTAKE GRILLE-COMPLETE 1 ACRE22C00840-AN ACRE22C00890-AN

35 CONTROL BOARD COVER-COMPLETE 1 CWH13C1303-AN ←

36 INSTALLING HOLDER 1 CWH361134-A ←

37 AIR FILTER 2 ACRD00-00420 ←

38 AIR FILTER-COMPLETE 2 CWD00C1293 ←

39 C.C.CASE 1 ACRG50-16360 ←

NOTE:
• All parts are supplied from APIN, India (Vendor Code: 00026071).
• "O" marked parts are recommended to be kept in stock.

63
17.1.2 CS-KC18SKY3R-1 CS-KC18SKY4A CS-KC18SKY3PR

37

3
36

4
28
2

7 5
6 1 10
8 9

33

34

30
17

35

12 19
13
25 11 14
22 16
31

15
23
20 29

18
26

24

27 32

21

38

Note:
• The above exploded view is for the purpose of parts disassembly and replacement.
• The non-numbered parts are not kept as standard service parts.

64
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-KC18SKY3R-1 CS-KC18SKY4A CS-KC18SKY3PR IGP

1 CHASSIS-COMPLETE 1 ACRCWD50C1778-AN ← ←

2 DC MOTORS (BRUSHLESS GENERAL USE) 1 ACRL6CBYYYL0172 ← ← o


3 CROSS-FLOW FAN-COMPLETE 1 CWH02C1077 ← CWH02C1146-AN# o

4 BEARING ASS'Y 1 CWH64K1011 ← ←


5 BOX SHAPED PLATE 1 ACRD661267 ← ←

6 FIN & TUBE EVAPORATER-COMPLETE 1 CWB30C4847-AN ← ← o


7 UNION NUT 1 CWT251026 ← ← o

8 UNION NUT 1 CWT251062 ← ← o


9 PARTICULAR PIECE 1 ACRD933450 ← CWD933739

10 PARTICULAR PIECE 1 CWD933753 ← ←


11 HOLDER-SENSOR 1 CWH321110 ← ←

12 TERMINAL BOARD-COMPLETE 1 ACRA28C2783-1-AN ← ← o

13 ELECTRONIC CONTROLLER-MAIN 1 CWA73C9133-AN# ← CWA73C9130-AN# o


14 CONTROL BOARD COVER 1 CWH131611 ← ←

15 ELECTRONIC CONTROLLER-DISPLAY 1 CWA748189-W ← CWA748193-W o


16 CONTROL BOARD-COMPLETE 1 CWH16C1728-1-AN ← CWH16C1730-1-AN o

17 SENSOR-COMPLETE 1 CWA50C2782 ← ← o
18 DISCHARGE GRILLE-COMPLETE 1 CWE20C3394-AN ← ← o

19 CONTROL BOARD COVER 1 CWH131612 ← ←


20 VANE-COMPLETE 1 CWE24C1477-AN ← ←

21 VANE-COMPLETE 1 CWE24C1469-AN ← ←
22 CAP 3 CWH521194 ← ←
23 INDICATOR-COMPLETE 1 CWE39C1225-AN ← ←

24 FULCRUM 2 CWH621160 ← ←

25 PARTICULAR PIECE 1 CWD934027 ← ←

26 FLEXIBLE PIPE 1 CWH851173 ← ←

27 FAN MOTOR (P.PH.V.) 1 CWA981241 ← ← o

28 AIR FILTER-COMPLETE 2 CWD00C1293 ← ←

29 CAP 1 CWH521259 ← ←

30 PARTICULAR PIECE 1 CWD933741 ← ←

31 PARTICULAR PIECE 1 CWD933762 ← ←

32 REMOTE CONTROL SWITCH-COMPLETE 1 ACRA75C03930 ← CWA75C4621


33 FRONT GRILLE-COMPLETE 1 ACRE10C03250-AN ACRE10C03300-AN ACRE10C03180-AN o

34 INTAKE GRILLE-COMPLETE 1 ACRE22C01070-AN ACRE22C01080-AN ACRE22C01020-AN


35 CONTROL BOARD COVER-COMPLETE 1 CWH13C1303-AN ← ←

36 INSTALLING HOLDER 1 CWH361141 ← ←


37 AIR FILTER 2 ACRD00-00430 ← ←

38 C.C.CASE 1 ACRG50-16370 ← ←

NOTE:
• All parts are supplied from APIN, India (Vendor Code: 00026071).
• "O" marked parts are recommended to be kept in stock.

65
17.2 Outdoor Unit

11
R

13

30

25

29
21

12

3 27
4
6 20

26

5 22 18
7
23

9
19

17

10

28
14 15
16
24
1

Note:
• The above exploded view is for the purpose of parts disassembly and replacement.
• The non-numbered parts are not kept as standard service parts.
66
SAF REF. QT
PART NAME & DESCRIPTION CU-KC12SKY3 CU-KC12SKY3E CU-KC12SKY3A CU-KC12SKY4A IGP
ETY NO. Y.
1 BASE PAN ASSY 1 ACRD52K00180-AN ← ← ← o
2 FAN MOTOR BRACKET 1 CWD541219-AN ← ← ←
3 STRAINER 1 CWB11025 ← ← ←
4 FAN MOTOR (6P 1PH V) 1 CWA951871 ← ← ← o
5 SCREW 4 CWH55406J ← ← ←
6 FAN ASSY 1 CWH03K1087 ← ← ← o
7 NUT 1 CWH56053J ← ← ← o
8 COMPRESSOR 1 HSM185S2UFT ← ← PH190M2A-4FTL1-0 o
9 LEAD WIRE-COMPLETE 1 ACRA68C1675 ← ← ←
10 NUT 3 CWH561049 ← ← ←
11 FIN & TUBE CONDENSER COMPLETE 1 CWB32C4180-AN ← ← ←
12 CAPILLARY TUBE ASSY 1 ACXB15K00380-AN ← ← ← o
13 CABINET TOP PLATE 1 CWE031182-AN ← ← ←
14 HOLDER-COUPLING 1 CWH351249 ← ← ←
15 2-WAYS VALVE 1 CWB021077 ← ← ← o
16 3-WAYS VALVE 1 CWB011105 ← ← ← o

17 CONTROL BOARD COVER-COMPLETE 1 CWH13C1293-AN ← ← ←

18 CONTROL BOARD COVER 1 CWH131593-AN ← ← ←


19 CABINET FRONT PLATE 1 ACRE061328-AN ← ← ←
20 SOUND-PROOF BOARD 1 CWH151362-AN ← ← ←
21 PARTICULAR PLATE 1 CWD912408 ← ← ←
CAPACITOR NETWORKS CAPACITOR
22 1 ACRF5A32356A012 ← ← ←
ARRAY
23 HOLDER-CAPACITOR 1 CWH30060 ← ← ←
24 SCREW 4 ACRH551342 ← ← ←
25 CABINET SIDE PLATE- L 1 CWE041691-AN ← ← ←
26 TERMINAL BOARD-COMPLETE 1 CWA28C2567-AN ← ← ← o
27 CABINET SIDE PLATE-COMPLETE - R 1 CWE04C1540-AN ← ← ←
28 DISCHARGE GRILLE 1 ACRE201309 ← ← ←
29 BASE BOARD-COMPLETE 1 CWG62C1200 ← ← ←
30 C.C.CASE 1 ACRG50-16340 ← ← ←

NOTE:
• All parts are supplied from APIN, India (Vendor Code: 00026071).
• "O" marked parts are recommended to be kept in stock.

67
REF.
SAFETY PART NAME & DESCRIPTION QTY. CU-KC18SKY3M-1 CU-KC18SKY3R-1 CU-KC12SKY4A IGP
NO.
1 BASE PAN ASSY 1 ACRD52K00180-AN ← ← o
2 FAN MOTOR BRACKET 1 CWD541219-AN ← ←
3 ACCESSORY-COMPLETE 1 CWH82C2001-AN ← CWH82C2002-AN
4 FAN MOTOR (6P 1PH V) 1 CWA921566 ← CWA951871 o
5 SCREW 4 CWH55406J ← ←
6 FAN ASSY 1 CWH03K1087 ← ← o
7 NUT 1 CWH56053J ← ← o
8 COMPRESSOR 1 PH300G2C-4KUL1 ← PH190M2A-4FTL1-0 o
9 LEAD WIRE-COMPLETE 1 CWA68C0730 ← ACRA68C1675
10 NUT 3 CWH561049 ← ←
11 FIN & TUBE CONDENSER COMPLETE 1 CWB32C4050-AN ACRB32C00820-AN CWB32C4180-AN
12 CAPILLARY TUBE ASSY 1 ACRB15K00200-AN ACXB15K00360-AN ACXB15K00680-AN o
13 CABINET TOP PLATE 1 CWE031182-AN ← ←
14 HOLDER-COUPLING 1 CWH351249 ← ←
15 2-WAYS VALVE 1 CWB021077 ← ← o
16 3-WAYS VALVE 1 CWB011105 ← ← o

17 CONTROL BOARD COVER-COMPLETE 1 CWH13C1293-AN ← ←

18 CONTROL BOARD COVER 1 CWH131593-AN ← ←


19 CABINET FRONT PLATE 1 ACRE061328-AN ← ←
20 SOUND-PROOF BOARD 1 CWH151362-AN ← ←
21 PARTICULAR PLATE 1 CWD912409 CWD912405 CWD912408
CAPACITOR NETWORKS CAPACITOR
22 1 CWF5A32556A001 ← ACRF5A32356A012
ARRAY
23 HOLDER-CAPACITOR 1 CWH301057 ← CWH30060
24 SCREW 4 ACRH551342 ← ←
25 CABINET SIDE PLATE- L 1 CWE041691-AN ACRE04-00350-AN CWE041691-AN
26 TERMINAL BOARD-COMPLETE 1 CWA28C2510-AN CWA28C2510-AN CWA28C2567-AN o
27 CABINET SIDE PLATE-COMPLETE - R 1 ACRE04C00380-AN ← CWE04C1541-AN
28 DISCHARGE GRILLE 1 ACRE201309 ← ←
29 STRAINER 1 CWB11025 ← ←
30 BASE BOARD-COMPLETE 1 CWG62C1200 ← ←
31 C.C.CASE 1 ACRG50-16340 ← ←

NOTE:
• All parts are supplied from APIN, India (Vendor Code: 00026071).
• "O" marked parts are recommended to be kept in stock.

68
17. Exploded View and Replacement Parts List
17.2.1 Outdoor Unit CU-KC18SKY3PR CU-KC18SKY3PM

38

39

Note:
• The above exploded view is for the purpose of parts disassembly and replacement.
• The non-numbered parts are not kept as standard service parts.

69
REF.
SAFETY PART NAME & DESCRIPTION QTY. CU-KC18SKY3PR CU-KC18SKY3PM IGP
NO.
1 BASE PAN ASSEMBLY 1 ACA20SM02005 ACA20SM02005
2 CONDENSER ASSY 1 ACRACA20HE02701 ACRACA20CO01002 o
3 VALVE PLATE 1 ACA20SM02301 ACA20SM02301
5 SERVICE VALVE 1/2 1 ACA20CU06701 ACA20CU06701 o
6 VALVE 1/4 1 ACA20CU01301 ACA20CU01301
7 COMPRESSOR 1 PH290G2C-7KUL1 PH300G2C-4KUL1
11 TUBE CONNECTOR 1 ACA20CU01101 ACA20CU01101 o
12 CAPILLARY 1 ACA20CU06801 ACW1CU01204 o
13 MOUNT MOTOR 1 ACA20SM02401 ACA20SM02401 o
14 ODU MOTOR 1 ACA20MOT00301 ACRACA20MOT00401
15 FAN 1 ACA20PL00101 ACA20PL00101 o
17 FRONT PANEL 1 ACRACA20SM04201 ACRACA20SM04201
18 FAN GUARD 1 ACA18PL00201 ACA18PL00201 o
20 CONTROL PLATE 1 ACRACA20SM06801 ACRACA20SM06801
21 DUAL CAPACITOR 1 ACW2EL00301EXT10 ACW2EL00301EXT10 o
23 TERMINAL BLOCK 1 CWA22CON004933 CWA22CON004933
26 SIDE PANEL-R 1 ACA20SM04301 ACA20SM04301 o
28 SIDE COULMN-L 1 ACA20SM04401 ACA20SM04401
29 COMPRESSOR WIRE 1 ACA18WI00401EXT-02 ACA18WI00401EXT-02
31 TOP COVER 1 ACA20SM04501 ACA20SM04501
32 CONTROL COVER PLASTIC 1 ACA22PL00101 ACA22PL00101
33 SCREW 4 ACW3HA01101EXT02 ACW3HA01101EXT02
34 BASE BOARD COMPLETE 1 ACRACA20PA01401 ACRACA20PA01401 o
36 INSTALLATION KIT ASSY 1 CWH82C2001-AN CWH82C2001-AN
37 C.C. CASE 1 ACA20PA01101 ACA20PA01101
38 CAPACITOR WIRE 1 ACA18WI00301EXT-02 ACA18WI00301EXT-02
39 WASHER 3 ACA20HA00601EXT-02 ACA20HA00601EXT-02

NOTE:
• All parts are supplied from APIN, India (Vendor Code: 00026071).