Spec No.

: XJ10078
Zhongtian Technology Submarine Cable Co., Ltd
中 天 科 技 海 缆 股 份 有 限 公 司
1. General
This listed specification covers the structure, test and packing information of Cables as manufactured
by Zhongtian Technology Submarine Cable Co., Ltd (ZTTSC). Matters not mentioned in this technical
specification shall be negotiated by purchaser & supplier. This document confirms the two parties’
agreement as technical agreement of contract unless otherwise in official written annexes.

2. Standards
The cable which ZTTSC offered shall be designed, manufactured and tested according to
international standards as follows:

ISO 9001:2015 Quality Management Systems


ISO 14001:2015 Environmental Management Systems
ISO 45001:2018 Occupational health and safety management system
IEC 60228:2004 Conductors of insulated cables
Power cables with extruded insulation and their accessories for rated
IEC 60502-2 voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 2: Cables
for rated voltages from 6 kV (Um = 7,2 kV) and up to 30 kV (Um = 36 kV)
Tests on electric cables under fire conditions – Part 1:Test on a single
IEC 60332-1
vertical insulated wire or cable
Measurement of smoke density of cables burning under defined
IEC 61034-2
conditions-Part 2: Test procedure and requirements
Note: ZTTSC shall comply with the latest vision standards.

www.zttcable.com All Rights Reserved Copyright © 2022 Page1


Zhongtian Technology Submarine Cable Co., Ltd
中 天 科 技 海 缆 股 份 有 限 公 司
Construction, parameters and characteristics

CU/TR-XLPE/CTS/PVC-8.7/15kV-1x240mm2
CU/TR-XLPE/CTS/PVC-8.7/15kV-1x500mm2

Cable construction

Note: The above drawing is only for reference.

Item Description Material Apply method


1 Conductor Bare copper wires Class2 circular stranding
2 Conductor screen Semi-conductive compound
3 Insulation TR-XLPE Triple extruding
4 Insulation screen Semi-conductive compound
5 Wrapper Semi-conductive water blocking tape Taping
6 Metallic Screen Copper tape Taping
7 Wrapper Non-conductive water blocking tape Taping
8 Outer sheath Low smoke, flame retardant, anti-UV, Extruding
anti-rodent PVC
Core identification Natural
Outer sheath color Black
Marking (laser marking or Ink jet printing): according to customer requirements

www.zttcable.com All Rights Reserved Copyright © 2022 Page2


Zhongtian Technology Submarine Cable Co., Ltd
中 天 科 技 海 缆 股 份 有 限 公 司

Dimension Data Ⅰ
Core No. x Cross Min. Conductor screen Nom./min. insulation Min. Insulation
section thick. thick. screen thick.
mm2 mm mm mm
1x240 0.50 4.5/3.95 0.30
1x500 0.50 4.5/3.95 0.30

Dimension Data Ⅱ
Core No. x Cross Nom. Nom. /Min. outer Approx. diam. over
section Copper tape thick. sheath thick. outer sheath
mm2 mm mm mm
1x240 0.12 2.0/1.40 37.7
1x500 0.12 2.3/1.64 46.9

Electrical Data Ⅰ
Core x Cross System Max. Continuous Max. Conductor Max. DC resistance
section frequency range conductor temp. temp. under short of conductor at 20 °C
(mm2) (Hz) (°C) circuit(°C) (Ω/km)
1x240 49-61 90 250 0.0754
1x500 49-61 90 250 0.0366

Usage characteristics
Lowest allowable temp.during installation (°C) 0
Min.bending radius during installation(mm) 20D
Design standard IEC 60502-2
Low smoke according to IEC 61034-2 Light transmittance ≥20%
Flame retardant IEC 60332-1

www.zttcable.com All Rights Reserved Copyright © 2022 Page3


Zhongtian Technology Submarine Cable Co., Ltd
中 天 科 技 海 缆 股 份 有 限 公 司
4 FAT Test requirements for cable
FAT test shall be in accordance with applicable standard of MV cable. The following test items shall
be carried out according to relevant standards. ZTTSC reserves the right to impose additional
charges for additional test as per request from customer or consultant(s).

No. Test item


Routine test
1 Measurement of electrical resistance of conductors
2 Voltage test
3 Partial discharge test
Sample test
1 Conductor examination
2 Measurement of thickness of insulation
3 Measurement of thickness of non-metallic sheath
4 Measurement of external diameter
5 Hot-set test for XLPE insulation

5 PACKING AND DRUM


ZTTSC cables are packed on wooden or iron wooden or iron drums. During transportation, right tools
should be used to avoid damaging the package and to handle with ease. Cables should be protected
from moisture; kept away from high temperature and fire sparks; protected from over bending and
crushing; protected from mechanical stress and damage.

The inner end of cable is then sealed with heat shrinkable end cap to prevent ingress of water and is
made available for testing. The outer end of cable is equipped with heat shrinkable end cap. Outer
sheath marking legend can be changed according to user’s requests.