C - Program Files (x86) - Cummins Power Suite - LoadsNSteps

This document provides a loads and steps detail report for a generator set project. It summarizes the calculated individual generator set load running and peak requirements, as well as the step load requirements over 4 steps. The largest load is in step 1, which has a starting kVA of 988.6 from a fire pump motor. Step 4 has the highest cumulative step kW and kVA of 516.0 and 1138.0 respectively, due to the addition of 3 jet fan motors.

Uploaded by

NATHAN
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
131 views4 pages

C - Program Files (x86) - Cummins Power Suite - LoadsNSteps

This document provides a loads and steps detail report for a generator set project. It summarizes the calculated individual generator set load running and peak requirements, as well as the step load requirements over 4 steps. The largest load is in step 1, which has a starting kVA of 988.6 from a fire pump motor. Step 4 has the highest cumulative step kW and kVA of 516.0 and 1138.0 respectively, due to the addition of 3 jet fan motors.

Uploaded by

NATHAN
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Loads and Steps Detail Report

for Project Montazah Complex block 2 3 generator

Project Parameters
Generator Sets Running in Parallel: 1 Fuel: Diesel
Max Allowable Starting Voltage Dip: 35 % Phase: 3
Max Allowable Peak Voltage Dip: 15 % Frequency, Hz: 60
Max Allowable Frequency Dip: 10 % Voltage: 277/480, Series Wye
Site Altitude, Ft. (M): 499 (152) Quiet Site: No
Site Ambient Temperature, oF (oC): 77 (25) Duty: Standby

Calculated Individual Generator Set Load Running and Peak Requirements


Running kW: 382.0 Max Step kW: 328.1 In Step 4 Cumulative Step kW: 516.0
Running kVA: 420.7 Max Step kVA: 988.6 In Step 1 Cumulative Step kVA: 1138.0
Running PF: 0.91 Peak kW: 258.2 Cumulative Peak kW: 501.2
Alternator kW: 386.0 Peak kVA: 923.5 Cumulative Peak kVA: 1191.3

Step 1
Calculated Individual Generator Set Step Load Requirements
Running kW: 137.9 Starting kW: 285.1 Cumulative Step kW: 285.1
Running kVA: 151.9 Starting kVA: 988.6 Cumulative Step kVA: 988.6
Running Amps: 183.0
Alternator kW: 137.9

Fire Pump Block-1 Three Phase Quantity: 1 In this Step


Category: Fire Pump
Running kW: 126.4 Starting kW: 245.6 Peak kW: 245.6
Running kVA: 138.9 Starting kVA: 909.5 Peak kVA: 909.5
Running PF: 0.91 Starting PF: 0.27 Cyclic: Yes
Running Amps: 193.4
Alternator kW: 126.4 Voltage: 415

Shaft HP: 154.16 Method: Across The Line


Shaft kW: 115.00
Efficiency: 0.91 LRkVA Factor: 5.9
Design: Standard NEMA Design B, C, or D LRkVA Code: G

Jokey Pump Three Phase Quantity: 1 In this Step


Category: Motor
Running kW: 11.5 Starting kW: 39.5 Peak kW: None
Running kVA: 13.1 Starting kVA: 79.1 Peak kVA: None
Running PF: 0.88 Starting PF: 0.50 Cyclic: No
Running Amps: 15.7
Alternator kW: 11.5 Voltage: 480

Shaft HP: 13.40 Method: Across The Line


Shaft kW: 10.00
Efficiency: 0.87 LRkVA Factor: 5.9
Design: Standard NEMA Design B, C, or D LRkVA Code: G

Step 2
Calculated Individual Generator Set Step Load Requirements
Running kW: 40.0 Starting kW: 40.0 Cumulative Step kW: 177.9
Running kVA: 42.1 Starting kVA: 42.1 Cumulative Step kVA: 194.0
Running Amps: 50.7
Alternator kW: 40.0

Light 1 Three Phase Quantity: 1 In this Step


Category: Light - Fluorescent
Running kW: 40.0 Starting kW: 40.0 Peak kW: None
Running kVA: 42.1 Starting kVA: 42.1 Peak kVA: None
Running PF: 0.95 Starting PF: 0.95 Cyclic: No
Running Amps: 50.7
Alternator kW: 40.0 Voltage: 480

Step 3
Calculated Individual Generator Set Step Load Requirements
Running kW: 10.0 Starting kW: 10.0 Cumulative Step kW: 187.9
Running kVA: 11.1 Starting kVA: 11.1 Cumulative Step kVA: 205.1
Running Amps: 13.4
Alternator kW: 14.0

Central Battery Three Phase Quantity: 1 In this Step


Category: Battery Charger
Running kW: 10.0 Starting kW: 10.0 Peak kW: None
Running kVA: 11.1 Starting kVA: 11.1 Peak kVA: None
Running PF: 0.90 Starting PF: 0.90 Cyclic: No
Running Amps: 13.4
Alternator kW: 14.0 Voltage: 480

Output kVA: 10.00


Efficiency: 0.9 Pulse: 6

Step 4
Calculated Individual Generator Set Step Load Requirements
Running kW: 132.2 Starting kW: 328.1 Cumulative Step kW: 516.0
Running kVA: 146.5 Starting kVA: 932.9 Cumulative Step kVA: 1138.0
Running Amps: 176.5
Alternator kW: 132.2

Jet Fans Three Phase Quantity: 1 In this Step


Category: Motor
Running kW: 81.3 Starting kW: 179.5 Peak kW: None
Running kVA: 89.4 Starting kVA: 578.9 Peak kVA: None
Running PF: 0.91 Starting PF: 0.31 Cyclic: No
Running Amps: 107.6
Alternator kW: 81.3 Voltage: 480

Shaft HP: 98.12 Method: Across The Line


Shaft kW: 73.20
Efficiency: 0.9 LRkVA Factor: 5.9
Design: Standard NEMA Design B, C, or D LRkVA Code: G

Jet Fans 2 Three Phase Quantity: 1 In this Step


Category: Motor
Running kW: 25.4 Starting kW: 74.3 Peak kW: None
Running kVA: 28.6 Starting kVA: 177.0 Peak kVA: None
Running PF: 0.89 Starting PF: 0.42 Cyclic: No
Running Amps: 34.4
Alternator kW: 25.4 Voltage: 480

Shaft HP: 30.00 Method: Across The Line


Shaft kW: 22.38
Efficiency: 0.88 LRkVA Factor: 5.9
Design: Standard NEMA Design B, C, or D LRkVA Code: G

Jet Fans 3 Three Phase Quantity: 1 In this Step


Category: Motor
Running kW: 25.4 Starting kW: 74.3 Peak kW: None
Running kVA: 28.6 Starting kVA: 177.0 Peak kVA: None
Running PF: 0.89 Starting PF: 0.42 Cyclic: No
Running Amps: 34.4
Alternator kW: 25.4 Voltage: 480

Shaft HP: 30.00 Method: Across The Line


Shaft kW: 22.38
Efficiency: 0.88 LRkVA Factor: 5.9
Design: Standard NEMA Design B, C, or D LRkVA Code: G

Step 5
Calculated Individual Generator Set Step Load Requirements
Running kW: 14.2 Starting kW: 46.7 Cumulative Step kW: 366.8
Running kVA: 15.9 Starting kVA: 97.4 Cumulative Step kVA: 449.0
Running Amps: 19.1
Alternator kW: 14.2

Fire Lift Three Phase Quantity: 1 In this Step


Category: Motor
Running kW: 14.2 Starting kW: 46.7 Peak kW: None
Running kVA: 15.9 Starting kVA: 97.4 Peak kVA: None
Running PF: 0.89 Starting PF: 0.48 Cyclic: No
Running Amps: 19.1
Alternator kW: 14.2 Voltage: 480

Shaft HP: 16.50 Method: Across The Line


Shaft kW: 12.31
Efficiency: 0.87 LRkVA Factor: 5.9
Design: Standard NEMA Design B, C, or D LRkVA Code: G

Step 6
Calculated Individual Generator Set Step Load Requirements
Running kW: 12.6 Starting kW: 12.6 Cumulative Step kW: 346.8
Running kVA: 14.0 Starting kVA: 14.0 Cumulative Step kVA: 381.5
Running Amps: 16.9
Alternator kW: 12.6

Small power Three Phase Quantity: 1 In this Step


Category: Miscellaneous - Welding
Running kW: 12.6 Starting kW: 12.6 Peak kW: 12.6
Running kVA: 14.0 Starting kVA: 14.0 Peak kVA: 14.0
Running PF: 0.90 Starting PF: 0.90 Cyclic: Yes
Running Amps: 16.9
Alternator kW: 12.6 Voltage: 480

Step 7
Calculated Individual Generator Set Step Load Requirements
Running kW: 35.2 Starting kW: 96.6 Cumulative Step kW: 443.4
Running kVA: 39.1 Starting kVA: 247.8 Cumulative Step kVA: 629.3
Running Amps: 47.1
Alternator kW: 35.2

Sump Pumps Three Phase Quantity: 1 In this Step


Category: Motor
Running kW: 35.2 Starting kW: 96.6 Peak kW: None
Running kVA: 39.1 Starting kVA: 247.8 Peak kVA: None
Running PF: 0.90 Starting PF: 0.39 Cyclic: No
Running Amps: 47.1
Alternator kW: 35.2 Voltage: 480

Shaft HP: 42.00 Method: Across The Line


Shaft kW: 31.33
Efficiency: 0.89 LRkVA Factor: 5.9
Design: Standard NEMA Design B, C, or D LRkVA Code: G