Fire and Gas Monitoring Panel: ST7-HV

The ST7-HV system is a programmable PLC suitable for safety and security installations. It covers fire and gas detection as well as CCTV and security systems. The ST7-HV system has been designed to meet reliability and availability requirements for companies operating in energy production and transformation. It can communicate with other panels and supervisory systems using Ethernet TCP/IP and Modbus protocols. The ST7-HV system is commonly used for automatic fire extinguishing control systems, integrated safety and security systems, and gas detection systems. It can be configured to achieve Safety Integrity Levels 2 and 3 as required by applicable regulations.

Uploaded by

peerless
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
88 views10 pages

Fire and Gas Monitoring Panel: ST7-HV

The ST7-HV system is a programmable PLC suitable for safety and security installations. It covers fire and gas detection as well as CCTV and security systems. The ST7-HV system has been designed to meet reliability and availability requirements for companies operating in energy production and transformation. It can communicate with other panels and supervisory systems using Ethernet TCP/IP and Modbus protocols. The ST7-HV system is commonly used for automatic fire extinguishing control systems, integrated safety and security systems, and gas detection systems. It can be configured to achieve Safety Integrity Levels 2 and 3 as required by applicable regulations.

Uploaded by

peerless
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

Fire and Gas Monitoring Panel

ST7-HV
ST7-HV

I NTRODUCTI ON TO THE ST7- HV SYSTEM

The ST7- HV syst em is a program m able PLC suit able for


safet y and securit y inst allat ions wit h a high t echnological
and econom ic cont ent t o ensure safety of people and
prot ect ion of asset s wit hin com m ercial and indust rial
environm ent s. This syst em is ideal for process plant s,
refineries, energy product ion fact ories, governm ent al and
public buildings, m ilit ary, naval inst allat ions and m any
m ore.

The ST7- HV syst em has st at e of t he art t echnology t hat


covers fire & gas det ect ion as well as CCTV and securit y
syst em s.

The ST7- HV syst em has been designed to m eet a variet y of


funct ions, reliabilit y and availabilit y requirem ent s which is
ideal for com panies t hat operat e in t he field of energy
product ion and t ransform at ion. The ST7- HV has excellent
resist ance t o elect rom agnet ic dist urbances and is capable of
cont inuous operat ion in difficult environm ent al condit ions.
I t s capacit y is set to t he com pliance wit h t he requirem ent s
of fault t olerance set by t he I nt ernat ional St andards I EC
61508. Due t o it s com pliance, it has obt ained t he level SI L3
( Safet y I nt egrit y Level 3) cert ified by a t hird party agency.

The ST7- HV syst em is cert ified t o perform m any prot ect ion funct ions. I t is in com pliance wit h t he applicable
regulat ions list ed in t he st andards for t he construct ion product s ( CPD & CPR) and in UL laborat ories t o m eet
t he corresponding US st andards.

Ext ernally, t he panel ST7- HV is sim ilar to a safet y PLC; it is com posed by elect ronic cards m echanically
com pat ible, which are insert ed in 19” racks. The panel ST7- HV can have from 1 t o 10 racks, each rack has 13
card slot s.

About 20 different cards can be used, each dedicat ed t o different funct ions such as firefight ing, gas det ect ion,
int ruder alarm , t echnologic cont rol and com m unicat ion wit h ot her syst em s and/ or panels. The ST7- HV panel
has a dedicat ed rack for t he operator’s int erface and it is const it ut ed by a big alphanum eric display, by a
keyboard and led indicat ions to show t he syst em st at us. Each panel ST7- HV has it s own m odular feeder and
bat t ery charger which allows the panel to work even wit hout an ext ernal power supply.

The ST7- HV syst em can com m unicat e wit h ot her panels of t he sam e t ype and wit h supervisory and SCADA
syst em s. This can be done using bot h propriet ary and st andard prot ocols, such as Et hernet TCP/ I P and
Modbus.

Special feat ures


• Hot backup redundant CPU’s
• Hot swap of all cards, including CPU’s, wit h aut om at ic reconfigurat ion
• Redundant and looped com m unicat ion bus bet ween cards and CPU’s
• Periodical aut om at ic t est ing of card input s and out put s
• Self- diagnost ics and signaling of card and CPU fault
• Aut om at ic safet y disabling of m alfunct ioning cards

Page 1 of 9
ST7-HV

APPLI CATI ONS OF THE ST7- HV SYSTEM


The ST7- HV syst em is com m only used for :
• Aut om at ic fire ext inguishing cont rol system s and in t he case of com plex firefight ing inst allat ion sect ioning.
This is in conform it y wit h t he Const ruct ion Product s Direct ive ( CPD) ;
• I nt egrat ed syst em s, including fire, int ruder/ burglar alarm , CCTV and t echnologic cont rol funct ions;
• Safet y & Securit y syst em s, where panels operat e as m ast er or slave unit s. Panels com m unicat e t hrough
net works ( of a fiber opt ic and fault t olerant t ype t oo) and are connect ed t o DCS or SCADA t hrough Modbus
prot ocol Et hernet and OPC Server;
• Fire prot ect ion wit h special logics t hat are in accordance wit h t he recom m endat ions of t he NFPA st andard;
• Gas det ect ion and m easurem ent syst em s. I t is ATEX- cert ifiable and capable of int erfacing wit h 4 & 20 m A
out put t oxic or explosive gas det ect ors.
All of t hese funct ions can coexist or be configured t o m eet specific cust om er requirem ent s.

SI L syst em s
The ST7- HV panel can be used t o produce syst em s cert ifiable t o SI L2 and SI L3. This is wit h t he requirem ent s
of t he applicable regulat ions that refer t o t he I EC 61508 and deriving st andards.
I n t hese applicat ions, t he ST7- HV plays t he role of logic solver so it represent s t he core of t he syst em and it
can obt ain t he SI L2 or SI L3 level depending on t he cards select ed to be used wit h it .
Clearly, to reach t he expect ed safet y level, t he field devices ( input s and out put s) m ust also be cert ified
accordingly, in addit ion t o t he panel.

Page 2 of 9
ST7-HV

According t o t he st andards, t he ST7- HV panel ( or syst em ) , can be considered a PES ( Program m able Electronic
Safet y-relat ed syst em ) and can be configured t o perform t he following safet y funct ions:
• Monit or digit al input s from field devices ( convent ional det ectors, pressure swit ches, release pushbut t ons,
select or swit ches, et c.)
• Monit or analogue 4- 20m A input s from field devices ( explosive gas, toxic gas, oxygen and heat det ect ors,
et c.)
• Elaborat ion of logics as a funct ion of input st at us ( including fire ext inguishing cont rol t o EN12094- 1)
• Cont rol act uat ors ( solenoids, relays, et c.) .

I n t he past , cert ified safet y funct ions were lim it ed only to processed applicat ions and gas det ect ion due to t he
sm all availabilit y of sensor and act uat ors on t he m arket t hat were SI L cert ified; now addressable flam e
det ect ors wit h t his cert ificat ion are highly available and aut om at ic fire ext inguishing com m and devices such as
solenoids for cylinders, deluge valves and fire m onit ors.

Page 3 of 9
ST7-HV

PARTI CULAR NOTES FOR SAFETY APPLI CATI ONS


There will always be t wo CPU’s.
A SI L- cert ified ST7- HV panel can cont ain different cards and perform different funct ions from t hose t hat m ust
be cert ified to SI L.
For whole syst em configurat ion, refer t o ST7- HV panel Safety Manual.
Should you have any doubt s, please cont act Silver- Tec t echnical service.

SI L 2 Configurat ion ( SI NGLE/ MONO) SI L 3 Configurat ion (REDUNDANT/ DUPLEX)


The I / O cards do not need t o be duplicat ed. I n case of aut om at ic fire ext inguishing cont rol,
sensors m ust be inst alled on two different det ect ion
The I / O cards not relat ing t o SI L2- cert ified safet y lines.
funct ions do not need t o be duplicat ed. The I / O cards concerning SI L3- cert ified safet y
funct ions m ust be duplicat ed in different racks.
Consequent ly, also t he racks are duplicat ed.
The redundant I / O cards m ust be evenly spread in
t he redundant racks.

Page 4 of 9
ST7-HV

ST7LAR&C- M ST7LAR&C- D
Det ect ion, alarm and cont rol from analogue input s Det ect ion, alarm and cont rol from analogue input s
( t ypical of gas det ect ors) ( t ypical of gas det ect ion)

ST7LDR&C- M ST7LDR&C- D
Det ect ion, alarm and cont rol from analogue input s Det ect ion, alarm and cont rol from analogue input s
( t ypical of fire det ect ors) ( t ypical of fire det ect ors)

ST7LDR&C- M ST7LDR&C- D
Det ect ion and aut om at ic ext inguishing cont rol Det ect ion and aut om at ic ext inguishing cont rol
according t o t he st andard EN 12094- 1. according t o t he st andard EN 12094- 1.

Page 5 of 9
ST7-HV

Com m unicat ion net work


ST7- HV is suit able for use in syst em s where several panels fully int eract on a network. They m ust ent irely
m aint ain t heir aut onom y in respect ive area cont rol.

Panels can com m unicat e wit h supervisory syst em s on an Ethernet LAN, and wit h ext ernal elem ent s ( e.g.
DCS, PLC, SCADA syst em s) via MODBUS RTU.

Com m unicat ion on a net work enables t he int egrat ion of different - vector syst em s, also including fault -
t olerant loop archit ect ures.

Page 6 of 9
ST7-HV

Sum m a r y of ST7 - H V syst e m


Charact erist ics of device m anagem ent & addressing
Mult iple input rack cards for collect ive lines; alarm t hreshold current values can be
Convent ional det ectors
adapt ed t o m ost det ect ors.
Addressable det ect ors and Loop rack cards, up to 127 addresses per loop; up t o 130 cards in panel version ST7-
devices HV/ 10R.
Support ed prot ocols and On t he sam e panel, cards wit h addressable loops belonging t o different brands and
addressable devices prot ocols can be used at t he sam e t im e
Rack cards for digit al I / O’s and analogue addressable I / O m odules on field bus; SSP
Technologic and I / O devices
propriet ary, up to 127 addresses per bus.
Rack cards, wit h one/ t wo 4-20 m A input s, for direct det ector connect ion and analogue
4- 20m A det ect ors
addressable m odules on field bus.
Gas det ect ors Rack cards wit h individual display and addressable m odules on bus.
Special rack cards ( ECD) * , cert ified for t his funct ion, wit h no logic and cont rol
Fire ext inguishing cont rol lim it at ion.
* = elect ric aut om at ic cont rol and delay device to EN 12094- 1
Special rack cards ( ECD) * , cert ified for t his funct ion, wit h no logic and cont rol
Fire ext inguishing cont rol
lim it at ion.
( direct ional valves)
Cert ified for 64 ext inguishing zones (ST7- HV/ 10R) .
Repeat er panels Addressable, on SSP serial bus, LCD display, 255 event - relat ed m essages.
Rem ot e cont rol PC wit h SI LVER- VI EW soft ware
Graphic m aps Silver- View int eract ive program , wit h different access levels and funct ions
St andard MODBUS RTU prot ocol; propriet ary prot ocol on Ethernet available upon
I nt erfacing wit h SCADA syst em
request .
Panel configurat ion Local and rem ot e, by m eans of PC and ProST7 program .
Com m unicat ion net work TCP/ I P on Et hernet , wit h com m unicat ion and consist ency cont rol.
Connect ion to ot her equipm ent Cards and MODBUS RTU protocol
Mult i- panel archit ect ure Et hernet and Modbus, copper of opt ic fibre.

Power supply

Several kind of feeder from 4 t o 20A are available and usable in parallel; all of t hem
are cert ified EN 54-4 and are in accordance wit h CPD / CPR
Feeder
Wit h fault indicat ion in case of m ains supply failure, bat t ery charger or bat t ery fault ,
overheat ing.

Can be coupled wit h feeder.


Bat t ery charge and aging st at us m onit oring, t hrough m icrocont roller-processed
Bat t ery charger
algorit hm ; t herm al com pensation during bat t ery charging; test ing but t on; bat t ery
capacit y < = 110 Ah.

Page 7 of 9
ST7-HV

Mechanic m odularit y and const ruct ion charact erist ics of t he panel

Cabinet wit h front door and swivel chassis for st andard 19” racks
• ST7- HV/ 1R for wall m ount ing L= 600 H= 700 P= 400m m
St ruct ure • ST7- HV/ 2R for wall m ount ing L= 600 H= 1100 P= 400m m
• ST7- HV/ 10R self- st anding L= 800 H= 2100 P= 400m m
Non- st andard panels can be produced, upon request , using different size cabinet s.

Front Acrylic glass door, lockable, wit h alarm swit ch.

By addit ion of 13- card slot racks; m axim um 10 ( + 1 base) racks, for m axim um 130
Expansion and rack cards.
Racks can be wired t o t erm inal blocks via flat cable, or cable wit h plug connect or.

There can be of t wo t ypes of t erm inal blocks:


t abbed t erm inal for DI N rail t erm inals and elect ronics ( cables up t o 4 m m 2) connect ed
Term inal blocks
t o rack cards using wired ribbon cable, or via t he t erm inals wit h elect ro- m echanical
cable assem blies and push- in connect or on t he rack.

Card inst allat ion Front plug- in, wit h locking screws.

Just change! ( no need t o eit her swit ch t he panel off or m ake changes to t he
Card & CPU replacem ent
connect ions and wiring) .

Card int erconnect ion Serial on rack backplane, and looped redundant bus, m anaged by FPGA.

Logic configurat ion of t he panel

Windows- com pat ible user- friendly program Silver- Pro enables t he configurat ion of:
• I / O st at us variat ions, expressed in AND/ OR logic gat es.
• Tim e and t im e period- based associat ions.
• Associat ions relat ing t o any input / out put int ernal t o t he panel.
• Associat ions and event s, or stat uses, relat ing to ot her panels on t he
net work.
Logics
• Dist inct logics for event s relat ing t o fire- fight ing, int ruder alarm and
t echnological cont rol funct ions.
• Special logics relat ing t o fire ext inguishing funct ions ( including direct ional
valve cont rol) .
• Vot ing logics 1oo2, 2oo2, or alike, conform ing to int ernat ional specificat ions
( ARAMCO and sim ilar) .

300 zones for area 1 ( fire) + 300 zones for area 2 ( int ruder and t echnologic cont rol
Zones alarm ) ; each zone can be at t ribut ed 99 input s, 99 out put s and 99 dist inct logic
associat ions.

Logics can be configured for int eract ion of panels on a net work, t he num ber of
Panel int eract ion
int erconnect ed panels being 99.

Once t he panel has been configured, a prot ect ion funct ion can be enabled, so t hat
m odificat ions can be m ade only by people in possession of a USB-port hardware key
and a com pat ible code.
This funct ion, whose enabling is at Custom er’s discret ion, prevent s unaut horized
Prot ect ion m odificat ions aft er t est ing.

Page 8 of 9
ST7-HV

Elect ronic m odularit y

LCD, LED ret ro- illum inat ed, graphic t ype, wit h t hirt y 52- charact er lines; can display
Display
event s concerning ot her panels on t he net work.

- ST7- CP1101- N CPU Rj 45


Main or secondary CPU ( Hit achi, 32 bit s, wit h int ernal operat ing syst em ; int egrat ed wat chdog; 4 MByt e Dat a
Mem ory SRAM + 2 MByt e Program Mem ory on Flash Eprom , 2 RS 232 port s + 1 port
Et hernet 10/ 100 base TX per CPU) .

- Display + keyboard ST7- ST7- DU1001- N


- Default input s/ out put s ST7-FT3001
Cards in base rack
- Default repet it ion FT3201- N ( t erm inals) or FT3101- N (relays)
- Back Plane BP1301- N

- BP1401- N Rack backplane ( flat cable)


- BP1402- N Rack backplane (plug cable)
Cards in each addit ional rack
- RC1201- N Rack cont roller
- BL0000- N Blank card ( em pt y slot s)

- FT3201- NTerm inal block m odule, 16 t erm inals


- FT3104- N - 1Term inal block m odule, 8 t erm inals
- PC2001- S Plug cable, 16 wires
- PC2001- R Double plug cable, 16 wires, for redundant applicat ions
- PC2101- S Plug cable, 2 wires
- PC2101- R Double plug cable, 4 wires, for redundant applicat ions
- PC2201- S Plug cable, 8 wires
- PC2201- R Double plug cable, 8 wires, for redundant applicat ions
Card t erm inat ion
- PC2301- S Plug cable, 4 wires
- PC2301- R Double plug cable, 4 wires, for redundant applicat ions
- PC2401- S Plug cable, 6 wires
- PC2501- S Plug cable, 4 wires
- PC2501- R Double plug cable, 4 wires, for redundant applicat ions
- FT3103- N Term inal block card, 8 volt age- free relays
- FT3102- N Term inal block card, 16 volt age-free relays
- FT3104- N Term inal block card, 4x2A out put s, polarit y reversing, for OC6201- S

- ST7-I C4001 Eight input s, convent ional det ect ion


- ST7-I C5001 One 4- 20 m A analogue input
- ST7-I C5002 Two analogue input s
- ST7-I C5003 Eight analogue input s
- ST7- OC6001 Eight 500 m A m onit ored out put s
- ST7- OC6101 Sixt een open collect or out put s
- ST7- OC6201 Eight polarit y reversal- m onit ored out put s
- ST7- OC6002 Four m onit ored out put s
Cards in expansion racks
- ST7- EX9001 Fire ext inguishing cont rol ( EDC) , cert ified to EN12094- 1
- ST7- LS9002 Special logic cont rol
- ST7- AL7001- S Addressable analogic loop cont rol DCP ( UL)
- ST7- AL7002- S Analogue addressable loop cont rol, ESP prot ocol
- ST7- AL7003- S Analogue addressable loop cont rol, SSP prot ocol
- ST7- AL7004- S Analogue addressable loop cont rol, Apollo prot ocol
- ST7- MD8001- N MODBUS RTU card
- ST7- AL7005- S Addressable bus cont rol, Syst em Sensor prot ocol