Wet and Dry Cooling Systems Optimization
Wet and Dry Cooling Systems Optimization
Applied Energy
journal homepage: www.elsevier.com/locate/apenergy
a r t i c l e i n f o a b s t r a c t
Article history: In Brescia, Italy, heat is delivered to 70% of 200.000 city inhabitants by means of a district heating system,
Received 9 January 2010 mainly supplied by a waste to energy plant, utilizing the non recyclable fraction of municipal and indus-
Received in revised form 1 August 2010 trial solid waste (800,000 tons/year, otherwise landfilled), thus saving annually over 150,000 tons of oil
Accepted 27 September 2010
equivalent and over 400,000 tons of CO2 emissions.
Available online 29 October 2010
This study shows how the performance of the waste-to-energy cogeneration plant can be improved by
optimising the condensation system, with particular focus on the combination of wet and dry cooling sys-
Keywords:
tems.
Wet and dry condenser
Cooling tower
The analysis has been carried out using two subsequent steps: in the first one a schematic model of the
Air condenser steam cycle was accomplished in order to acquire a knowledge base about the variables that would be
Off-design optimization most influential on the performance. In the second step the electric power output for different operating
conditions was predicted and optimized in a homemade program. In more details, a thermodynamic
analysis of the steam cycle, according to the design operating condition, was performed by means of a
commercial code (ThermoflexÓ) dedicated to power plant modelling. Then the off-design behaviour
was investigated by varying not only the ambient conditions but also several parameters connected to
the heat rejection rate, like the heat required from district heating and the auxiliaries load. Each of these
parameters has been addressed and considered in determining the overall performance of the thermal
cycle. After that, a complete prediction of the cycle behaviour was performed by simultaneously varying
different operating conditions. Finally, a MatlabÓ computer code was developed in order to optimize the
net electric power as a function of the way in which the condensation is operated. The result is an opti-
mum set of variables allowing the wet and dry cooling system to be regulated in such a way that the max-
imum power is achieved. The best strategy consists in using the maximum amount of heat rejection in
the wet cooling system to reduce the operational cost of the dry one.
Ó 2010 Elsevier Ltd. All rights reserved.
1. Introduction the latter, the cooling water taken from the condenser passes
through a wet mechanical draft tower (CT) and returns to the con-
The cooling system in a power plant rejects heat at approxi- denser. The obvious advantage of a closed-loop system is the
mately twice the rate at which electric power is generated [1]. It reduction in the water demand at the expense of larger operational
is important to underline that, since energy flows in power plants costs. Nevertheless environmental regulations and the increasing
are typically high, small improvements to the cooling system can scarcity of natural water supplies make both the AC and the CT
lead to large fuel savings and consequently efficiency enhancement convenient [3].
[2]. The effectiveness of a cooling system can be quantified through The way in which the heat rejection takes place in an AC does
the condensing steam pressure: the lower the pressure the greater not need to be deeply investigated: the critical element of the plant
the effects. is the CT. Although the basic parts of the tower can easily be de-
The present study was inspired by the operation of a waste-to- scribed and understood, heat and mass transfer processes are very
energy cogeneration plant placed in Brescia, Northern Italy (Fig. 1). complex. The temperature of the circulating water is reduced by
Attention was drawn to the condensing units because of the com- bringing it into direct contact with air: the cooling is attained
bined wet and dry cooling system (Fig. 2): it is composed of an air partly by the evaporation of a fraction of the water flow rate and
cooled condenser (AC) in parallel with a water cooled condenser. In partly by the transfer of sensible heat [4]. Each water particle is
surrounded by a film of saturated air which is considered to be
⇑ Corresponding author. Tel.: +39 035 2052346; fax: +39 035 2052077. at the same temperature as the water; the air is heated and be-
E-mail address: [email protected] (S. Ravelli). comes saturated with moisture as it passes through the tower. In
0306-2619/$ - see front matter Ó 2010 Elsevier Ltd. All rights reserved.
doi:10.1016/j.apenergy.2010.09.023
G. Barigozzi et al. / Applied Energy 88 (2011) 1366–1376 1367
Nomenclature
the heat transfer process more then two-thirds of the heat is trans- of differential equations [5–8], with the help of CFD modelling
ferred by evaporation with the rest being transferred by convec- [9,10], or by the NTU methods [11,12].
tion. In many works a great effort has been made to model the All cited papers think about the CT as a standalone component.
physical situation within a CT: since films and droplets of water According to different viewpoints it could be considered as a device
are in constantly changing configuration there is no theoretical which can minimize the environmental impact in the process
investigation capable of simulating such a complex phenomenon industry thanks to the recirculation of the cooling water [13,14]
without simplifying assumptions. It could be described by a set or increase the efficiency of a power plant [15].
The present study complies with the last approach and wants to
show the effect of a wet and dry condensation system on the per-
formance of a cogenerative plant. At author’s knowledge, no works
concerning this field can be documented. This paper offers an ori-
ginal contribution not only for considering a split system for air
condenser and wet cooling tower but also for defining an optimiza-
tion procedure whose aim is to maximize the net electric power for
any operating condition. Consequently the power consumption of
all auxiliaries was accurately estimated. It is necessary to remem-
ber that a mechanical draft CT uses fans to provide the required
volume of airflow: their cost is an additional expense to be consid-
ered. With respect to a natural draft CT, where the circulation is en-
sured by the density difference existing between the heated, moist
air and the fresh air, the mechanical draft CT can be built with rel-
atively less expensive materials but requires higher operation and
maintenance costs. The major problems are associated with fog-
ging and recirculation. However the risk of recirculation is reduced
if the fan is located on the top of the tower, because of the high dis-
charge velocity. Furthermore, pumps with variable speed are re-
quired in order to guarantee the most favourable mass flow rate
of cooling water. Another issue dealing with the operation of a
Fig. 1. View of the waste-to-energy cogeneration plant placed in Brescia, Northern
CT is the plume formation: when the atmosphere is too cold and
Italy. humid to absorb the moisture in the exhaust air from the CT, it fol-
Fig. 2. Schematic of a split system for air condenser and wet cooling tower [16].
1368 G. Barigozzi et al. / Applied Energy 88 (2011) 1366–1376
lows that the excess moisture condenses and the water droplets Table 1
become visible. Nevertheless the plume is not a pollutant, many Reference cycle design parameters.
ways to avoid it are well documented in technical papers [16]. In Ambient temperature (°C) 15
spite of that, plume abatement is not widely applied since it is a Ambient pressure (bar) 1.01325
very expensive feature. Ambient R.H. (%) 60
HP turbine inlet pressure (bar) 72
HP turbine inlet temperature (°C) 450
HP turbine inlet steam flow rate (t/h) 345
2. Power plant and design operating conditions
DH heat load (MW) 22.8
AC fan load (%) 100
The present investigation refers to the thermal cycle of a waste- CT fan load (%) 100
to-energy 80 MWe cogeneration plant. The flue gas from the com- Water cooled condenser pumps load (%) 80
bustion of the municipal solid waste, downstream of materials Gross power output (MW) 81.5
Fig. 3. Thermal cycle layout with the Wet and dry cooling system.
G. Barigozzi et al. / Applied Energy 88 (2011) 1366–1376 1369
the combination of fans and pumps rotational speeds leading to Inlet pressure (bar) 1.118
the maximum net power output, whatever the operating condi- Inlet steam flow rate (t/h) 281.8
tions may be. Exit enthalpy before exhaust loss (kJ/kg) 2313.5
Dry exhaust loss (kJ/kg) 19.34
This optimization process was carried out by an in house devel- Exhaust volume flow (m3/s) 602
oped MatlabÓ code, taking the net power output P as the objective Annulus area (m2) 3.06
function. The user is first required to choose the plant configura-
tion (Dry or W&D), the ambient conditions (temperature T and rel-
ative humidity RH), and the heat demand from DH. The program
first makes use of these input data to correct the net power output
from the design (Pd) to the off design point (P) by means of a few
coefficients (k). The net power P is then further corrected using
polynomial functions, each one taking into account for the influ-
ence of the following parameters: the AC fan speed nAC, the CT
fan speed nCT and the cooling water pump speed nCWP.
The implemented procedure attempts to find a constrained
minimum of a scalar function (P) of several variables (nAC, nCT
and nCWP), each one depending on ambient and DH conditions,
starting at an initial estimate (P0). The minimum is thus subjected
to the linear inequalities Ax 6 b. The resulting problem to be solved
consisted in
min funðPÞ ¼ kT amp kRH kDH Pd P3i¼1 ðAi n3i þ Bi n2i þ C i ni þ Di Þ ð1Þ
Cooling tower approach to wet bulb temperature (°C) 6.2 The model was first run at the plant design condition, consid-
Air wet bulb temperature rise in wet section (°C) 12.2 ered as a reference, and also under different ambient conditions
Number of cells 3
and DH requirements, in order to evaluate its prediction capability.
Cooling water mass flow rate (t/h) 12,000
Air mass flow rate (t/h) 7695 Table 7 compares computed and measured data for three different
Fan power consumption (kW) 560.8 operating conditions of the W&D configuration. All the reported
cases refer to a full condensing asset, corresponding to the mini-
mum steam extraction for DH.
plant lay-out schemes (Table 6). The combination of wet and dry Table 8 compares the model results against the cycle perfor-
cooling systems implies that a portion of the exhaust steam may mance data provided by the turbine manufacturer, for the Dry con-
condense by the water condenser and another portion may con- figuration. The reported cases show three values of the steam flow
dense by air in the AC. A balancing splitter was chosen to govern rate entering the HP turbine and different DH requirements. In par-
the exhaust steam allocation so as to balance the turbine exit pres- ticular, case 1 refers to a steam extraction for DH of about 60% of
sure: the basic idea is that both the condensers, except of the pip- the HP turbine inlet flow, corresponding to an heat demand of
ing connections pressure drops, work at the same pressure level. about 55 MWt while, in case 2 and case 3, the steam extraction
for DH is relatively low (about 20% of HP turbine inlet flow), corre-
sponding to an heat demand of about 20 MWt. The model predic-
5. Results and discussion tion capability was verified by comparing computed and measured
LP turbine exhaust steam temperature values as well as AC, cooling
As a first step of this investigation, the power cycle model was water condenser and CT inlet and outlet temperature values. The
validated against operational data. Then a parametric analysis was net power production cannot be directly compared, due to the fact
that the HP turbine steam extractions were not simulated in a de-
Table 6 tailed way, leading to an overestimation of the computed HP tur-
Pressure drops in pipes (with reference to Fig. 2). bine power. Few other cases were considered to validate the
Pipes Pressure drop (dP/P) W&D model but they were not included in the paper. For all the
cases, a good agreement was found between model results and
(a) 0.08
(b) 0.07
measurements: the maximum difference is lower than ±8%, as
(c) 0.001 shown in Tables 7 and 8.
(d) + (e) 0.5 + 0.5 In the W&D case, the simulation provides also the steam shar-
ing between the two condensers: approximately 54% of the steam
Table 7
Comparison between model results (M.) and experimental data (Exp.) – W&D.
Table 8
Comparison between model results and cycle data provided by the turbine manufacturer – dry.
flow rate goes to the air cooled condenser in the tested operating
conditions (i.e. with minimum steam extraction for DH). Unfortu-
nately, this information is not made available by DCS.
Fig. 6. AC fan load and Tamb influence on (a) normalized net power output, (b) auxiliary power consumption, (c) exhaust steam pressure and (d) AC steam fraction – W&D.
The amount of heat exchanged in the water condenser can be creases. The steam distribution at constant temperature and var-
regulated also by varying the cooling water flow rate through a iable DH heat requirement instead depends on the ambient
change in pumps rotational speed (Fig. 8). The plant behaviour temperature level: at the lowest temperature of 10 °C the AC
for variable pump load is not different than before, as the effect steam fraction increases with rising DH heat load. The opposite
on exhaust pressure is almost unchanged. Fig. 8a shows that the occurs at the highest temperature of 35 °C. This behaviour is con-
choice of cooling water flow rate exceeding the design point (cor- sistent with the water cooled condenser better performances with
responding to an 80% pump load) produces an increase in the net rising air temperature.
power only for high temperature (35 °C). At low ambient temper-
ature the circulation pumps should be run at partial speed to re- 5.2.2. Dry configuration
duce the power consumption: a pump load lower than 33% is In the coldest period of the year (5–15 °C) the AC receives the
enough for a temperature range between 10 °C and 20 °C. whole exhaust steam flow rate. Thus the investigation has been re-
The influence of the DH heat demand on cycle performance in stricted to ambient temperature, to the AC fan load and to the heat
shown in Fig. 9. P/Pd linearly reduces with an increase in the heat demand from DH.
demand from DH up to 85 MW. This is mainly due to the reduc- Fig. 11 reports some of the parametric analysis results for the
tion in the power produced by the LP turbine, as a result of a Dry configuration. The effects of air temperature on net power out-
decreasing steam flow going into it, even if the LP turbine exhaust put are not reported as they are very similar to those given for the
pressure progressively decreases (Fig. 9b). Increasing the DH heat W&D layout, even though the influence is less marked, as a result
load further, P quickly decreases. This is due to the crossover of more favourable ambient conditions. On the contrary, the effect
valve closing strategy, resulting in a constant HP turbine exhaust of the AC fan load on net power output greatly differs from the
pressure, as reported in Fig. 10. Concerning the way in which the W&D behaviour: in fact, if Tamb varies between 5 °C and 15 °C,
exhaust steam is shared into the two condensers, Fig. 9c shows, the AC fan should be operated according to the maximum load to
as expected, that an increasing steam mass flow rate goes get the highest power production. The regulation of fans speed,
through the water cooling system as the ambient temperature in- so as to reduce the auxiliary power consumption, is convenient
G. Barigozzi et al. / Applied Energy 88 (2011) 1366–1376 1373
Fig. 7. CT fan load and Tamb influence on (a) normalized net power output, (b) auxiliary power consumption, (c) exhaust steam pressure and (d) AC steam fraction – W&D.
in hard weather conditions. As far as the DH is concerned, no sig- of the AC fan load and the DH heat load or RH on the optimum net
nificant matters deserve notation; in fact the Dry layout reacts in power output.
the same way as the W&D layout to variation in the heat demand From the optimized AC and CT fans behaviour (Fig. 12) it can be
from DH. deduced that, if Tamb < 15 °C, the condensation heat is more effi-
ciently dissipated in the AC: in fact, in this condition, the optimized
AC fan load (60–70%) is higher than the CT fan load (45.7–47.5%).
5.3. Optimization of the cycle performance
On the contrary, if Tamb is hotter, the water cooling system ensures
the greatest results in terms of power production: the optimized
The performed parametric analysis demonstrated that the
CT fan load (86.8–100%) is now higher than the AC fan load (40–
superposition rules do not apply either to the W&D or to Dry con-
80%).
figuration. Nevertheless, this analysis provided a detailed data base
The optimization of the W&D layout led to the following major
for plant performance evaluation at different operating conditions.
suggestions:
This data base was then included in an optimization procedure
whose final target was the selection of a set of fans and pumps
– The pumps rotational speed should gradually increase with
loads to operate the condensing system in such a way that the
Tamb, passing from about 33% at 10 °C to 100% at 35 °C.
maximum power is achieved at different ambient conditions and
– Similarly, the CT fan rotational speed should be raised from 45%
DH heat demands.
to 87% while Tamb increasing up to 20 °C and maintained at the
highest level (100%) if Tamb exceeds 25 °C.
5.3.1. W&D configuration – Concerning the AC fan rotational speed, the range between 40%
Figs. 12 and 13 report the results of the condensing system opti- and 80% is confirmed to provide the best performance.
mization procedure for the W&D configuration. In particular,
Fig. 12 shows the optimum load of CT fan, AC fan and pumps by In the warmest conditions the plant should be regulated accord-
varying air temperature, while Fig. 13 shows the combining effects ing to the following logic: heat rejection has to be performed as
1374 G. Barigozzi et al. / Applied Energy 88 (2011) 1366–1376
Fig. 8. Cooling water condenser pumps load and Tamb influence on (a) normalized
net power output, (b) exhaust steam pressure – W&D.
Fig. 10. DH heat load and Tamb influence on HP turbine exhaust pressure (W&D).
Fig. 13. Optimized normalized net power output: influence of (a) DH heat load and
(b) RH – W&D.
Fig. 11. AC fan load and Tamb influence on normalized net power output – dry.
Fig. 12. Optimized cooling water flow pumps load and CT and AC fans load for
different Tamb – W&D. Fig. 14. Optimized AC fan load for different Tamb – dry.
1376 G. Barigozzi et al. / Applied Energy 88 (2011) 1366–1376
6. Conclusions ing variable steam conditions and their effect on cycle power
output.
A detailed simulation of a wet and dry condensing system in-
stalled in a steam power cycle for district heating was developed. References
A parametric analysis was carried out in order to check the influ-
[1] Conradie AE, Kroger DG. Performance evaluation of dry-cooling systems for
ence of ambient conditions, DH heat demand and condensation
power plant applications. Appl Therm Eng 1996;16:219–32.
heat transfer (i.e. AC, water cooled condenser and CT fans and [2] Smrekar J, Oman J, Sirok B. Improving the efficiency of natural draft cooling
pumps rotational speeds) on plant thermodynamic performances, towers. Energy Convers Manage 2006;47:1086–100.
and particularly, on net power output. No superposition rules [3] El-Wakil MM. Powerplant technology. NewYork: McGraw-Hill; 1984.
[4] Mohiuddin AKM, Kant K. Knowledge base for the systematic design of wet
could be applied, but several parameters simultaneously influences cooling towers. Part I: Selection and tower characteristics. Int J Refrig
in a combined way the net power output. For example, the way the 1996;1:43–51.
CT fan load influences the net power output depends on the ambi- [5] Fisenko SP, Petruchik AI. Toward to the control system of mechanical draft
cooling tower of film type. Int J Heat Mass Transfer 2005;48:31–5.
ent temperature as well as on the AC fan load. Thus, a wide data [6] Brin AA, Petruchik AI, Fisenko SP. Mathematical modeling of evaporative
base of cycle thermodynamic performances was carried out, cover- cooling of water in a mechanical-draft tower. J Eng Phys Thermophys
ing all the possible operating conditions. This data base was in- 2002;75:1332–8.
[7] Fisenko SP, Brin AA, Petruchik AI. Evaporative cooling of water in a mechanical
cluded in an in house developed optimization code providing the draft cooling tower. Int J Heat Mass Transfer 2004;47:165–77.
condensing system control strategy giving the maximum net [8] Fisenko SP, Brin AA. Simulation of a cross-flow cooling tower performance. Int J
power output for each ambient condition and DH requirement. Heat Mass Transfer 2007;50:3216–23.
[9] Rafat AW, Masud B. CFD simulation of wet cooling towers. Appl Therm Eng
The air cooled condenser resulted the best way to reject heat if 2006;26:382–95.
the ambient temperature is lower than 15 °C. At higher ambient [10] Milosavljevic N, Heikkila P. A comprehensive approach to cooling tower
temperature, the condensation should exploit the cooling capacity design. Appl Therm Eng 2001;21:899–915.
[11] Soylemez MS. On the optimum performance of forced draft counter flow
of the tower as much as possible while discarding the remaining
cooling towers. Energy Convers Manage 2004;45:2335–41.
heat in the air cooled condenser. This strategy uses the maximum [12] Qureshi BA, Zubair SM. A complete model of wet cooling towers with fouling
available amount of heat rejection in the cooling tower to reduce in fills. Appl Therm Eng 2006;26:1982–9.
the cost of the air condenser. Another result is about the cooling [13] Bloemkolk JW, Van der Schaaf RJ. Design alternatives for the use of cooling
water in the process industry: minimization of the environmental impact from
water pumps rotational speed: it would be simultaneously in- cooling systems. J Cleaner Prod 1996;1:21–7.
creased with ambient temperature. The AC fan load providing the [14] Harte R, Kratzig WB. Large-scale cooling towers as part of an efficient
best performance in terms of net power came out to be between and cleaner energy generating technology. Thin-Walled Struct 2002;40:
651–664.
40% and 80%. The increase in both heat demand from DH and in [15] Ganan J, Rahman Al-Kassir A, Gonzales JF, Macias A, Diaz MA. Influence of the
ambient RH was found to scale downwards the power production cooling circulation water on the efficiency of a thermonuclear plant. Appl
without having an effect on the optimum condition. Therm Eng 2005;25:485–94.
[16] Lindahl PA, Jameson RW. Plume abatement and water conservation with the
The prediction and the optimization of the thermal cycle per- wet/dry cooling tower. In: Proceedings of the Cooling Tower Institute annual
formance have been achieved by fixing flow rate, temperature meeting; 2003.
and pressure of the steam entering the high pressure turbine.
An interesting hint on how to improve the model lies in consider-