0% found this document useful (0 votes)
103 views2 pages

SX25 Process Controller: Description

Uploaded by

Mohammad Hossein
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
103 views2 pages

SX25 Process Controller: Description

Uploaded by

Mohammad Hossein
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

TI-P323-24

CH Issue 3

Cert. No. LRQ 0963008


ISO 9001
SX25
Process Controller
Description
The SX25 controllers are 1 /16 DIN panel mounted, suitable for
constant set point applications and for use with the Spirax Sarco
range of pneumatic (PN) and electric (EL) control valves
and sensors.

Available types
There are two SX25 models available which both have 100 Vac
to 240 Vac mains:
One linear control output (mA)
SX25 mA
Auxiliary power supplier for loop powered sensors
SX25 VMD VMD (Valve Motor Drive) control output

SX25 general technical data


Mounting arrangement Panel mounted 1 /16 DIN
Control action
100 to 240 Vac, 50 / 60 Hz
Power supply Proportional band 0.5 to 999.9%
(-15 to +10% of the nominal value)
Electrical connections Screw connection terminal block Integral time 0.1 to 100.0 minutes or off
Power consumption 1.6 VA maximum Control parameters Derivative time 0.01 to 10.00 minutes or off
Protection IP65 front protection Error band 0.1 to 10%
Operating temperature 0 to +50°C, 5 to 90% RH One shot tune, or natural frequency tune.
The controller will automatically select
RTD Pt100 2 or 3 wire connection Auto tuning the best method according to the
4 - 20 mA, 0 - 20 mA, using external process conditions.
Universal Linear mA shunt resistor 2.5 W, Ri10 MW A self-learning, non-intrusive analysis of the
inputs Adaptive process to continuously calculate the
Voltage 0 / 10 to 50 mV, Ri 10 MW tuning PID parameters.
Thermocouples L, J, T, K, S, custom On-Off control Hysteresis from 0.1 to 10%
Sampling time 500 ms Overshoot To minimise overshoot on
RTD Pt100 / protection critical processes.
0.25% ±1 digit @ 25°C ambient
thermocouples Actuator response time from 15 to 600 secs.
Accuracy Valve motor
Linear mA 1.25% ±1 digit @ 25°C ambient drive control Minimum correction step 0.1 to 5.0%
Linear voltage 0.10% ±1 digit @ 25°C ambient of the valve travel
Number of set points 1 Auto / manual modes Selectable from keyboard.

Functions available
SX25 mA version technical data
Resistance thermometers,
0 / 4 - 20 mA 750 W maximum Universal input thermocouples, mA and volt
(15 V maximum)
mA control output (OP4) Auxiliary power For external sensors requiring loop power
Resolution 12 bit (0.025%) supply (SX25 mA only)
Accuracy 0.1% Auto / manual Indication of manual mode
* Relay (OP1) SPST relay N.O. 2 A / 250 Vac selection and power output %
Two independent ramps (ramp up and
SPST relay N.O. 2 A / 250 Vac or Ramps
* Relay / SSR (OP2) ramp down) for set point change
SSR 5 V ±10%, 30 mA maximum
Two programmable relay outputs for
* Relay (OP3) SPST relay N.O. 2 A / 250 Vac Event alarm deviation, band and process alarms
Supply for a two wire 4 - 20 mA with latch and block feature
Auxiliary power supply or three wire, +18 V ±20%,
30 mA maximum for transmitters Approvals
These instruments are marked. Therefore they conform to the
* Only two of the outputs can be used from relays OP1, OP2 or OP3. council directive 93 / 68 / EEC and the regulations on the essential
protection requirements in electrical apparatus EN 61010-1
SX25 VMD version technical data (IEC 1010 -1) : 90 +A1:92 + A2:95
Regulations on Electromagnetic Compatibility according to the
2 x SPST relay N.O. 2 A / 250 Vac European Community directive 89 / 336 / EEC, amended by the
Valve travel time: 15 - 600 seconds European Community directive 92 / 31 / EEC and the following
VMD (OP1, OP3) regulations:
Valve minimum step:
0.1 to 5.0% of travel EN 50081 - 1 residential environments
RF emissions
EN 50081 - 2 industrial environments
SPST relay N.O. 2A / 250 Vac or
Relay / SSR (OP2) SSR 5V ±10%, 30 mA maximum RF immunity EN 50082 - 2 industrial environments

Local regulations may restrict the use of this product to below the conditions quoted.
In the interests of development and improvement of the product, we reserve the right to change the specification. © Copyright 2004
Wiring diagram

Dimensions and weight


(approximate) in millimetres and grammes

48 mm 120 mm

48 mm
Weight
130 g (approximately)

Panel cut-out
(approximate) in mm
65 mm 20 mm maximum
minimum

65 mm minimum

45 +0.6 mm

45 +0.6 mm

How to order
Example: 1 off SX25 mA, with mA output or 1 off SX25 VMD, with valve motor drive output.

SX25 Process Controller TI-P323-24 CH Issue 3