Current Transformer Sizing
Current Transformer Sizing
Introduction:
Current transformers are predominantly utilised in areas where it is impossible to
measure current directly. They are different types of transformers with a defined degree of
precision (class), which translates the primary current into a (usually) smaller, standardised
secondary current inputs to protection relays and metering equipment and galvanically
separates primary and secondary circuits from each other. The physical saturation (especially
with monitoring CTs) of the core material additionally guarantees protection of the secondary
circuit from higher currents.
The protection CTs are separated by standards the CTs are used for different applications like
backup protection, line protection, transformer protection, differential protection, distance
protection, bus bar protection etc. the current transformer differs construction-wise. One
primary winding and n-numbers of the secondary windings are placed in the CT for both
protection and metering purposes in the same CT and some special protection also. The
HARIKRISHNAN.R
difference between the normal CT and the special CT is remanence flux has to be lowered
than 10% of the saturation flux. The residual magnetism is known as remanence.
Points To Be Consider:
CT Ratio:
Calculate the system full load amps and fix the ratio of CT nearest value available
in the market. Select the secondary 1 or 5 amps depending upon the distance and cost of
the CT.
Burden:
The external load is connected to the secondary CT expressed in VA. The connected
load burden should not be higher than the rated burden. Lead resistance to considered
2.5sqmm and 4sqmm. The connected burden should not be less than 25% of the rated
burden.
Knee point voltage:
This is the significance of the saturation level of a CT core mainly used for protection
purposes. The sinusoidal voltage of rated frequency applied to the secondary terminals of
current transformer, with other winding being open circuit, which when increased by 10%
cause the exiting current to increase 50%.
Accuracy:
The accuracy depends upon the loading of CT it should be not less than 10% of its
rated value. The accuracy is guaranteed only 25% to 100% of the rated burden. Below the
25%, the CT could not able to induse the emf in the secondary winding.
Safety factor:
The ratio of rated instrument limits primary current to rated primary rated
current. The connected burden should be equal to or lesser than the rated burden If it is high
the CT will be damaged thermally.
ALF – Accuracy limit factor
ISF – instrument safety factor
Working Operation of Current Transformer:
The current Transformer (CT) functions to replicate the primary current waveform at
a smaller magnitude in proportion to the turn’s ratio so that protection relays do not expose
to high fault current thus simplifying the design of the IED. The current transformer has two
sets of winding around the magnetic core. When alternating current (Ip) flows in the primary,
the alternating field is generated and the magnetic flux flows in the core. The magnetic flux
gets linked to the secondary of the CT and produces a voltage (Vs) in the secondary.
HARIKRISHNAN.R
If the secondary of the current transformer is not connected to a burden, the secondary
current will be zero. In the absence of the secondary current (Is), the net magnetic flux in the
core will be equal to the flux created by the primary current. The higher flux density in the
core will saturate the core and the dangerously high voltage is produced across the secondary
under this condition that is why the secondary of the current transformer must not be kept
open circuit. The flux in the core is produced by excitation current. We have a non-linear
relationship between excitation current and magnetizing flux. After a certain value of
excitation current, the flux will not further increase so rapidly with an increase in excitation
current. This non-linear relation curve is also called the B – H curve. The secondary voltage of
a current transformer is directly proportional to the flux. Hence one typical curve can be
drawn from this relation between secondary voltage and excitation current as shown below.
It is clear from the curve that, a linear relation between V and Ie is maintained from point A
and K. The point ′A′ is known as the ′ankle point′ and point ′K′ is known as the ′Knee Point.
Once the relation between the V and Ie has increased the point K the CT get into the pre-
saturation and then to the saturation region and CT is not capable of excitation current in the
secondary. Just below the knee point voltage, all the magnets are aligned in the same
direction as the magnetic field and the maximum rated flux density of the core has reached.
If the primary current is further increased after attaining the maximum flux density in the
core, the core can’t handle this increased magnetic field and CT is said to be saturated. For
better accuracy, a typical rule of thumb is to select a current transformer which is rated
approximately 20% above the expected maximum load current. If not the level of accuracy of
the CT is not guaranteed. Because the CT could not able to induce emf in secondary less than
1% table below shows the % error at % rated current of CT to the accuracy class. A typical rule
of thumb is to select a current transformer which is rated approximately 20% above the
expected maximum load current.
HARIKRISHNAN.R
1A 5A
The knee point will be low The knee point will be high
It can be used If the distance between the It can be used If the distance between the
CT and connected equipment is long CT and connected equipment is short
Calculation:
To calculate the lead burden = I2 * 2RL
I- secondary current.
R- Resistance of the connected wire between CT to equipment.
L- Length of the cable
secondary current = 1A
Cable used = 2.5 Sqmm
Cable resistance = 8.87Ω/kM
length = 50m
lead burden = 12 ∗ 2(0.00887*50) =0.887VA
If the I2=5
The lead burden will increase to 4.435 VA this will affect the CT burden at the fault condition.
When the fault current increases the burden also will increases.
Measuring CT Protection CT
1000/1A,5VA,500V, to below 5 or 10 ISF 1000/1A,5VA,500V,150 ISF
HARIKRISHNAN.R
Conclusion:
The current transformer essentially lowers (steps down) a high current to a lower,
safer level that you can manage properly. It steps down the current to be measured so that
you can measure it with an average range ammeter. Providing the current for the coil of
measuring device and protective relaying. The resistance of the instruments current coil with
which the current transformer secondary winding is connected is small. The current
transformer operates under state close to the short circuit under normal condition.
Reference:
IEC 61869 standard general requirements of current transformer