Technical Data Features: Ratings

The document describes the MK201A Earth Fault Relay, a microprocessor-based numerical relay for protection of electrical circuits. It has low-set and high-set definite time and instantaneous overload protection functions. The relay operates on auxiliary supply voltages of 198-265V AC or 94-127V AC at 50Hz, has contact ratings of 5A/250V, and complies with IEC 60255-26 standards. It has indicators for power, pickup, and trip states, with front panel access and adjustable settings.

Uploaded by

Minh Chung
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
33 views

Technical Data Features: Ratings

The document describes the MK201A Earth Fault Relay, a microprocessor-based numerical relay for protection of electrical circuits. It has low-set and high-set definite time and instantaneous overload protection functions. The relay operates on auxiliary supply voltages of 198-265V AC or 94-127V AC at 50Hz, has contact ratings of 5A/250V, and complies with IEC 60255-26 standards. It has indicators for power, pickup, and trip states, with front panel access and adjustable settings.

Uploaded by

Minh Chung
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

MK201A

Features Technical Data


• Microprocessor based numerical relay RATINGS
Rated current ( In ) : 5 A
• Current measurement based on
Rated frequency : 50 Hz
fundamental frequency
Burden : < 0.3 VA at In
• Low-set definite time relay Thermal withstand : 4 x In continuous

• High-set instantaneous relay AUXILIARY SUPPLY


Model MK201A-240A : 198 ~ 265 V AC
• Separate low-set and high-set
Model MK201A-110A : 94 ~ 127 V AC
indicators
Supply frequency : 50 Hz

MK201A Earth Fault Relay


• Option to disable the high-set relay VA rating : 3 VA typical

• Front panel access to the test function SETTING RANGES


• Complies with IEC 60255-26 standard Low-set ( I > ) : 0.1 A to 2.0 A
: 2% to 40%
Low-set delay time(DELAY): 0.05 sec to 1.0 sec
High-set ( I >> ) : I > to 10 x I > or
disable
PERFORMANCE High-set delay time ( t >> ) : Instantaneous
Adjustable accuracy : Less than ±5%
Repeatability : Less than 0.5% of CONTACTS
full scale Trip contact (R1) : Manual reset type
Contact Arrangement : Change-over
MECHANICAL Contact rating : 5 A, 250 V AC ( cosϕ = 1 )
Mounting : Panel mounting Contact material : Silver alloy
Front panel : Standard DIN Expected electrical life: 100,000 operations at
96 mm x 96 mm rated current
Approximate weight : 0.6 kg Expected mechanical life: 5 x 106 operations

ENVIRONMENTAL CONDITIONS INDICATORS


Temperature : -5˚C to +55˚C Auxiliary supply : Green indicator
Humidity : 56 days at 93% RH and Pick-up : Red indicator
40˚C non-condensing Trip : Red indicator
MK201A Earth Fault Relay

TYPICAL APPLICATION DIAGRAM COMBINED OVERCURRENT & EARTH FAULT RELAYS

Aux AUX AUX


L N MK 201A L N MK 204A L N MK 201A
NO NC COM NO NC COM NO NC COM
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8

R1 R1 R1
9 10 11 12 13 14 15 16 9 10 11 12 13 14 15 16 9 10 11 12 13 14 15 16

L1
L2 L1
L3 L2
N L3
N

CASE DIMENSIONS
90 mm
96 mm 70 mm 91.0 ± 0.5 mm
91.0 ± 0.5 mm
96 mm

Front Side Panel Cutout

Ordering Information

MODEL DESCRIPTION
MK201A - 240A For 50 Hz system, auxiliary voltage 198 ~ 265 V AC
MK201A - 110A For 50 Hz system, auxiliary voltage 94 ~ 127 V AC