V-Sense Modbus: User Manual

The document provides installation and troubleshooting instructions for the V-Sense Modbus device. It outlines the minimum system requirements, wiring instructions, and how to configure the V-Sense expansion board for Modbus RTU communication. The status LED colors and potential issues are described for troubleshooting communication problems. Register maps with the Modbus holding register and coil addresses and parameters are also included.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
102 views11 pages

V-Sense Modbus: User Manual

The document provides installation and troubleshooting instructions for the V-Sense Modbus device. It outlines the minimum system requirements, wiring instructions, and how to configure the V-Sense expansion board for Modbus RTU communication. The status LED colors and potential issues are described for troubleshooting communication problems. Register maps with the Modbus holding register and coil addresses and parameters are also included.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

V-Sense Modbus

USER MANUAL
January 2020 Version 1.3
Contents

Installation Guidelines 1
Minimum System Requirements 2
Wiring Instructions 2
V-Sense Configuration 3

Troubleshooting 2
Status LED 4
No communication to V-Sense (Blue, White, Red) 4
No communication to Modbus Master (Red, Yellow) 4
RS485 activity, but no comms to Modbus Master (Purple, White) 4
Status LED Green, but incorrect data read by Modbus Master 4

Register Maps 3
Minimum System Requirements 5
Function 01 - Read Coils 5
Function 03 - Read Holding Registers 9

1
Installation Guidelines 1

Minimum system requirements


There are several minimum requirements that should be established;
• V-Sense release 3 2018 Firmware Version or greater
• Modbus adapter ACB_13_08
• Modbus RTU over RS485 master device supporting:
Baud rate: 9600, 19200 or 38400 bps
Data bits: 8
Parity: none
Stop bits: 1
• 3 core shielded cable connecting adapter to Modbus Master

Wiring
Turn the V-Sense off when connecting cables or removing boards.
Connect the RS485+ to the RS485+ input, RS485- to the RS485- input
and GND to the GND input. Ensure the ribbon cable is connected
between the expansion board and the header in the bottom right
corner of the motherboard.

2
Installation Guidelines 1
Expansion Board dialog
From the main screen, press “System” to access the System Settings
Page.

From the System Settings Page, press “Expansion Board” button to


access the Expansion board dialog.

In the Expansion Board dialog, you can see three settings.


Expansion Board = {None, 4-20, Modbus RTU, Corrosion}
Slave Address = {1-240}
Baud Rate = {9600,19200,38400}

Choose Modbus RTU, your desired slave address and baud rate to
configure the V-Sense.

3
Troubleshooting 2
Status LED
Green – Valid communications to V-Sense, valid Modbus requests in last 10

secondsPurple - Valid communications to V-Sense, activity on RS485 in last 10

seconds Yellow- Valid communications to V-Sense, no activity on RS485 in last 10

seconds Blue - No communications to V-Sense, valid Modbus requests in last 10

seconds White – No communications to V-Sense, activity on RS485 in last 10

seconds

Red – No communications to V-Sense and no activity on RS485 in last 10 seconds

No communication to V-Sense (Blue, White, Red)


Check expansion board on V-Sense is set to Modbus RTU.
Check cable is seated properly

No communication to Modbus Master (Red, Yellow)


Check cable is securely connected to master and slave
Check cable is shielded, and shield is connected at Modbus master
Check a supported function is requested, see Modbus Register Map

RS485 activity, but no comms to Modbus Master (Purple, White)


Check slave address on V-Sense Expansion board screen matches slave
addressModbus master is requesting.
Check a supported function is requested, see Modbus Register Map
Check cable is securely connected to master and slave
Check cable is shielded, and shield is connected at Modbus master

Status LED Green, but incorrect data read by Modbus Master


Master may use an offset or address starting with 0. Try instead of 10001 using
address 0 function 01; or instead of using 40001 using address 0 function 03
Check the data type in the register map.
Compare the value on the V-Sense screen to the value being
readCheck the conversion formula used by the Master.

4
Register Maps 3
Function 01 - Coils
Address Parameter
10001 Output1 active?
10002 Output2 active?
10003 Output3 active?
10004 Output4 active?
10005 Output5 active?
10006 Output6 active?
10007 Output7 active?
10008 Output8 active?
10009 Output9 active?
10010 Output10 active?
10011 Output11 active?
10012 Output12 active?
10013 Output13 active?
10014 Output14 active?
10015 Output8 open=dose?
10016 Output9 open=dose?
10017 Output10 open=dose?
10018 Output11 open=dose?
10019 Output12 open=dose?
10020 Output13 open=dose?
10021 Output14 open=dose?
10022 Generic1 / LevelSensor1 output on?
10023 Generic1 / LevelSensor1 alarm?
10024 Generic1 / LevelSensor1 lockout?
10025 Generic2 / LevelSensor2 output on?
10026 Generic2 / LevelSensor2 alarm?
10027 Generic2 / LevelSensor2 lockout?
10028 Generic3 / LevelSensor3 output on?
10029 Generic3 / LevelSensor3 alarm?
10030 Generic3 / LevelSensor3 lockout?
10031 Generic4 / LevelSensor4 output on?
10032 Generic4 / LevelSensor4 alarm?
10033 Generic4 / LevelSensor4 lockout?
10034 Generic5 / LevelSensor5 output on?
10035 Generic5 / LevelSensor5 alarm?
10036 Generic5 / LevelSensor5 lockout?
10037 Generic6 output on?
10038 Generic6 alarm?

5
Register Maps 3
Address Parameter
10039 Generic6 lockout?
10040 Temperature enabled?
10041 Temperature output on?
10042 Temperature alarm?
10043 pH enabled?
10044 pH output on?
10045 pH alarm?
10046 pH lockout?
10047 pHB enabled?
10048 pHB output on?
10049 pHB alarm?
10050 pHB lockout?
10051 ORP enabled?
10052 ORP output on?
10053 ORP alarm?
10054 ORP lockout?
10055 ORPB enabled?
10056 ORPB output on?
10057 ORPB alarm?
10058 ORPB lockout?
10059 Conductivity enabled?
10060 Conductivity output on?
10061 Conductivity alarm?
10062 Conductivity TDS/nCond
10063 ConductivityB enabled?
10064 ConductivityB output on?
10065 ConductivityB alarm?
10066 ConductivityB TDS/nCond
10067 FacCtrl enabled?
10068 FacCtrl output on?
10069 FacCtrl alarm?
10070 FacCtrl lockout?
10071 FacCtrlB enabled?
10072 FacCtrlB output on?
10073 FacCtrlB alarm?
10074 FacCtrlB lockout?
10075 PreTreat enabled?
10076 PreTreat active?
10077 Dispersant enabled?
10078 Dispersant active?
10079 Timer1 enabled?
10080 Timer1 active?
10081 acc1 active

6
Register Maps 3
Address Parameter
10082 acc2 active
10083 acc3 active
10084 acc4 active
10085 Timer2 enabled?
10086 Timer2 active?
10087 acc1 active
10088 acc2 active
10089 acc3 active
10090 acc4 active
10091 Timer3 enabled?
10092 Timer3 active?
10093 acc1 active
10094 acc2 active
10095 acc3 active
10096 acc4 active
10097 Timer4 enabled?
10098 Timer4 active?
10099 acc1 active
10100 acc2 active
10101 acc3 active
10102 acc4 active
10103 Timer5 enabled?
10104 Timer5 active?
10105 acc1 active
10106 acc2 active
10107 acc3 active
10108 acc4 active
10109 Timer6 enabled?
10110 Timer6 active?
10111 acc1 active
10112 acc2 active
10113 acc3 active
10114 acc4 active
10115 Flow output on?
10116 Flow?
10117 Common Alarm on?
10118 Common Alarm outputOn?
10119 Common Alarm flowAlarmDisabled
10120 Common Alarm alarmRelayDelay
10121 Corrosion 1 Value Alarm on?
10122 Corrosion 1 Pitting Alarm on?
10123 Corrosion 2 Value Alarm on?
10124 Corrosion 2 Pitting Alarm on?

7
Register Maps 3

Function 03 - Holding Registers


Address Type Parameter Unit Scaling
40001 uint16 serialNumber-600000 - 1
40002 uint16 mapVersion - 1
40003 uint16 Generic1 / LevelSensor1 value - 1000
40004 uint16 Generic1 / LevelSensor1 voltage mV 1
40005 uint16 Generic1 / LevelSensor1 setpoint - 1000
40006 uint16 Generic2 / LevelSensor2 value - 1000
40007 uint16 Generic2 / LevelSensor2 voltage mV 1
40008 uint16 Generic2 / LevelSensor2 setpoint - 1000
40009 uint16 Generic3 / LevelSensor3 value - 1000
40010 uint16 Generic3 / LevelSensor3 voltage mV 1
40011 uint16 Generic3 / LevelSensor3 setpoint - 1000
40012 uint16 Generic4 / LevelSensor4 value - 1000
40013 uint16 Generic4 / LevelSensor4 voltage mV 1
40014 uint16 Generic4 / LevelSensor4 setpoint - 1000
40015 uint16 Generic5 / LevelSensor5 value - 1000
40016 uint16 Generic5 / LevelSensor5 voltage mV 1
40017 uint16 Generic5 / LevelSensor5 setpoint - 1000
40018 uint16 Generic6 value - 1000
40019 uint16 Generic6 voltage mV 1
40020 uint16 Generic6 setpoint - 1000
40021 uint16 Temperature value degC 10
40022 uint16 Temperature setpoint degC 10
40023 uint16 pH value - 1000
40024 uint16 pH setpoint - 1000
40025 uint16 pH fuzzy - 1000
40026 uint16 pHB value - 1000
40027 uint16 pHB setpoint - 1000
40028 uint16 pHB fuzzy - 1000
40029 uint16 ORP value mV 1
40030 uint16 ORP setpoint mV 1
40031 uint16 ORP fuzzy mV 1
40032 uint16 ORPB value mV 1
40033 uint16 ORPB setpoint mV 1
40034 uint16 ORPB fuzzy mV 1
40035 uint16 Conductivity value uS/cm or ppm 1
40036 uint16 Conductivity setpoint uS/cm or ppm 1
40037 uint16 Conductivity CF us/cm per ppm 1000
40038 uint16 ConductivityB value uS/cm or ppm 1
40039 uint16 ConductivityB setpoint uS/cm or ppm 1

8
Register Maps 3
Address Type Parameter Unit Scaling
40040 uint16 ConductivityB CF us/cm per ppm 1000
40041 uint16 LSI value 100
40042 uint16 FacCtrl value ppm 10
40043 uint16 FacCtrl voltage mV 1
40044 uint16 FacCtrl setpoint ppm 10
40045 uint16 FacCtrl fuzzy ppm 1000
40046 uint16 FacCtrlB value ppm 10
40047 uint16 FacCtrlB voltage mV 1
40048 uint16 FacCtrlB setpoint ppm 10
40049 uint16 FacCtrlB fuzzy ppm 1000
40050 uint16 WaterMeter1 MTD LitrePerPulse L/pulse 1000
40051 uint32 WaterMeter1 MTD value kL 1000
40053 uint32 WaterMeter1 YTD value kL 1000
40055 uint16 PreTreat pumpSize L/hour 1000
40056 uint16 PreTreat doseRate L/hour 1000
40057 uint16 PreTreat ppm ppm 1
40058 uint16 PreTreat concentration % 1
40059 uint16 PreTreat period minutes 1
40060 uint16 Dispersant pumpSize L/hour 1000
40061 uint16 Dispersant doseRate L/hour 1000
40062 uint16 Dispersant period minutes 1
40063 uint16 Corrosion 1 Value mil per year 10
40064 uint16 Corrosion 1 Pitting mil per year 10
40065 uint16 Corrosion 2 Value mil per year 10
40066 uint16 Corrosion 2 Pitting mil per year 10
40067 uint16 Flow Velocity Value m/s 10
40068 uint16 Flow Velocity Diameter mm 1