R4850N1 Rectifier
Introduction
The R4850N1 is a digital rectifier that converts the 85~300VAC to 53.5 VDC
and possesses the characters of high efficiency, high power density, walk-in
start, hot-plug, complete protection, and low noise. The rectifier adopts the
latest power monitoring technology, implements the function of monitoring the
states of loads and the rectifier status in real time. The output voltage of the
rectifier can be adjusted through the host.
Electrical Specifications Specification
Rectifier Input
Features Input voltage 85~300VAC
High efficiency: ≥92% 220VAC single phase
Input voltage mode
(or 110VAC dual live lines)
Input voltage range: 85~300VAC 45~65Hz
Frequency
Rated: 50Hz/60Hz
Operating temperature range: -40℃~75℃
Maximum input current ≤19.5A
Total harmonic distortion(THD): ≤5%
Power factor ≥0.99
Hot-plug
Digital control THD ≤5%
Intelligent electric meter Output
Communication over RS485 42~58VDC
Output voltage
Default value: 53.5VDC
Adjustment of voltage and current
Output power 2900W(176~300VAC)
Meet RoHS requirements
Others
Passing the TUV,CE,CB,UL certifications
Dimension 88.9(H)×103(W)×243(D)mm
Weight ≤2.8kg
Cooling Forced air cooling
Environmental Specifications
Efficiency(%)
Operating temperature -40℃~+75℃(non-derating under 50℃)
Storage temperature -40℃~+70℃
Relative humidity 5%~95%(non-condensing)
≤4000m(If the altitude is within the range of
Load(%) 3000m to 4000m, the maximum operating
Altitude range
temperature decreases by 1℃ as the
Efficiency curve altitude increases by 200m.)
www.huawei.com
R4850N1 Rectifier
Protection
Input overvoltage protection Protection point: >300VAC
Input undervoltage protection Protection point: <85VAC
Output overvoltage protection 58.5~60.5VDC(can be set by PMU)
Output short circuit protection A long term short circuit is allowed.
Rectifier
Over-temperature protection Protection point: ≥75℃(167℉)
Reliability
MTBF >500,000hours
Output voltage(V)
Audible Noise
Specification ≤50dB
Safety/EMC/Lightening Protection
Passes TUV, CE, UL certifications
Catch the CB certificate
Output current(A)
Complies with
Output voltage V.S Output current Safety
UL60950-1
Certification
IEC60950-1
EN60950-1
CAN/CSA C22.2 No. 60950 -1
EN55022 Class B
EN55024
Power(w)
EN61000-3-2
EMC EN61000-3-3
ETSI EN300 386
ETSI EN301489
ITU-T K.20
Temp.(℃)
Lightning protection YD 5098-2005 5KA
Power derating curve
The information in this document may contain predictive statements including, without limitation, Huawei Industrial Base
statements regarding the future financial and operating results, future product portfolio, new Bantian, Longgang
technology, etc. There are a number of factors that could cause actual results and developments
Shenzhen 518129, P.R.China
to differ materially from those expressed or implied in the predictive statements. Therefore, such
Tel: +86-755-28780808
information is provided for reference purpose only and constitutes neither an offer nor an
www.huawei.com
acceptance. Huawei may change the information at any time without notice.