0% found this document useful (0 votes)
185 views3 pages

General Notes: Vicinity Map

This document provides general notes for an electrical installation project. It specifies that all electrical works must comply with Philippine electrical codes and regulations. The power service for the proposed new connection will be 230 volts, 1-phase, 3-wire, and 60Hz. All panelboards and distribution panels must have a grounding bus for branch circuit and sub-feeder grounding, and the main grounding system shall be bonded to the nearest metal water pipe. Underground wiring in areas subject to vehicles must be buried 24 inches deep if using rigid metal conduit, intermediate metal conduit, or PVC with a concrete encasement and rebar reinforcement. All electrical works must be directly supervised by a registered electrical engineer.

Uploaded by

Kenneth Molina
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
185 views3 pages

General Notes: Vicinity Map

This document provides general notes for an electrical installation project. It specifies that all electrical works must comply with Philippine electrical codes and regulations. The power service for the proposed new connection will be 230 volts, 1-phase, 3-wire, and 60Hz. All panelboards and distribution panels must have a grounding bus for branch circuit and sub-feeder grounding, and the main grounding system shall be bonded to the nearest metal water pipe. Underground wiring in areas subject to vehicles must be buried 24 inches deep if using rigid metal conduit, intermediate metal conduit, or PVC with a concrete encasement and rebar reinforcement. All electrical works must be directly supervised by a registered electrical engineer.

Uploaded by

Kenneth Molina
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

GENERAL NOTES

All works shall comply with the latest provision of the


Philippine Electrical Code (PEC) with the rules and
regulation of the national and local authority concerned
in the enforcement of electrical laws and ordinance and
with rules regulation of utilities companies concerned.

1. Power service to the construction of Proposed New Power THIS SITE


Connection shall be 230 volts, 1Ø , 3 wire, 60Hertz.
2. All Panelboards, Distribution Panel, etc,. shall have grounding bus
for branch circuit and sub-feeder grounding system. Main grounding
system shall be bonded to the nearest metal water pipe in the system.

3. Underground wiring subject to vehicular passing shall be buried


24 inch deep if RMC, IMC or PVC with concrete encasement and
rebars.

4. All electrical works shall be under the direct supervision of


duly Registered Electrical Engineer.
3 VICINITY MAP
E 01 NOT TO SCALE

FUEL TANK AREA


FABRICATION AREA

3-Spool Insulator on Rack


(Heavy Duty Bolted)
50KVA, 13.8KV/230V
STEP DOWN TRANSFORMER
10" x 10" PP-EQUIP
1 Concrete Pedestal
LP
CIRCUIT HOMERUN
HAND HOLE

PANEL BOARD 150mm


Drip Loop (1.0m) 6
PP-E
CIRCUIT BREAKER Service Entrance
500 Cap

GROUNDING
60 60 RSC Clamp / Flat Bar
BURRIED 24 INCHES FROM
M METER TOP OF CONDUIT TO GROUND

ROOM 1
1X1200MM FLUORESCENT
LIGHT 80
Sab LIGHT SWITCH RSC Pipe

3-GANG CONVENIENCE 350


OUTLET ROOM 2

3-GANG WEATHER PROOF 4270mm


CONVENIENCE OUTLET HAND HOLE

ENCLOSED CIRCUIT 3660mm


BREAKER
500
AIR CONDITIONING
60

Meter Base
UNIT (ACU) OUTLET

Circuit Breaker
in NEMA 3R Enclosure

2 LEGENDS & SYMBOLS BURRIED 24 INCHES FROM


TOP OF CONDUIT TO GROUND
OFFICE AREA
E 01 NOT TO SCALE
1500mm
500
RSC Pipe

Ground Wire
CEILING
HAND HOLE HAND HOLE CONCEALED PP-OFFICE
N.G.L. & BUSBAR
60

PROPOSED CONCRETE
PEDESTAL AND METERING AREA
Ground Rod

4 HANDHOLE DETAILS
E 01 NOT TO SCALE
6 POWER DISTRIBUTION LAYOUT
E 01 NOT TO SCALE

5 PEDESTAL DETAILS
E 01 NOT TO SCALE

PROJECT TITLE PROJECT OWNER SHEET CONTENT DESIGNED BY KGMOLINA SHEET NO.

DRAWN BY KGMOLINA
PROFESSIONAL ELECTRICAL ENGINEER E-01
PROPOSED NEW POWER CONNECTION MR. MARVIN DEL PONSO AS SHOWN CHECKED BY
PRC NO.: VALIDTY: REV. NO.
APPROVED BY
PTR ISSUED ON:
LOCATION LAMPARA ST., HERMOSA, BATAAN DATE
ISSUED AT: TIN:
Designation : PP-EQUIP Mounting: SURFACE MOUNTED
System : 230V, 1Ø, 2WIRE + GROUND, 60Hz Enclosure: NEMA - 12
Location : FABRICATION AREA Feed: TOP

CONNECTED LOAD OVERCURRENT CONDUCTORS


CKT. PROTECTION (CU. WIRE) RACEWAY QUANTITY
LOAD DESCRIPTION AMPERE
NO. VA
ɸAB AT AF P SIZE (MM2) TYPE SIZE TYPE CO LIGHT MOTOR
1 WELDING MACHINE 1 8000 34.8 50 100 2 2-8.0 + 1 - 5.5(G) THWN-2 20mmØ PVC
WIRING SCHEDULE PVC
2 WELDING MACHINE 2 8000 34.8 50 100 2 2-8.0 + 1 - 5.5(G) THWN-2 20mmØ

2 - 100 sq.mm THW + 3 WELDING MACHINE 3 8000 34.8 50 100 2 2-8.0 + 1 - 5.5(G) THWN-2 20mmØ PVC
x100
1 - 14 sq.mm THW 4 POWER TOOLS 3000 13.1 30 100 2 2-5.5 + 1 - 5.5(G) THWN 20mmØ PVC 6

5 POWER TOOLS 3000 13.1 30 100 2 2-5.5 + 1 - 5.5(G) THWN 20mmØ PVC 6
2 - 80 sq.mm THW +
x80 6 WATER PUMP 1.0HP 1840 8.0 20 100 2 2-3.5 + 1 - 3.5(G) THWN 20mmØ PVC 1
1 - 14 sq.mm THW
7 FUEL PUMP 1.5 HP 3450 15 30 100 2 2-5.5 + 1 - 5.5(G) THWN 20mmØ PVC 1
2 - 22 sq.mm THW +
x22 8 LIGHTING 500 2.2 20 100 2 2-3.5 THWN 20mmØ PVC 8
1 - 8.0 sq.mm THW
9 FUEL TANK LIGHTING 250 1.1 20 100 2 2-3.5 THWN 20mmØ PVC 6

2 - 8.0 sq.mm THWN-2 + 10 SPACE 1500 6.5 100 2


x8.0
1 - 5.5 sq.mm THWN-2 11 SPACE 1500 6.5 100 2
TOTAL 43290 169.9
2 - 5.5 sq.mm THHN +
x5.5
1 - 5.0 sq.mm THHN APPLICATION OF DEMAND FACTOR
IT DEMANDED LINE CURRENT: = (34428 VA / 230V ) + (15 x 25%)
FIRST TWO (2) WELDING MACHINES @ 100%DF : 16000 VA = 153 AMPS
2 - 3.5 sq.mm THHN +
x3.5 THIRD WELDING MACHINES @ 85%DF : 6800 VA
1 - 2.0 sq.mm THHN POWER TOOLS, LIGHTINGS, SPACE @ 65%DF : 6338 VA USE:
WATER PUMP @ 100%DF : 1840 VA PROTECTION: 175AT/225AF, 2P,600V, 60HZ, BOLT-ON, MCCB
SUB-FEEDER: 2 - 80MM2 THW + 1 - 14.0MM2 THW (G) IN 50MM DIA. CONDUIT
FUEL PUMP @ 1000%DF : 3450 VA
COMPUTED DEMAND LOAD : 34428 VA

Designation : PP-OFFICE Mounting: SURFACE MOUNTED


System : 230V, 1Ø, 2WIRE + GROUND, 60Hz Enclosure: NEMA - 12
Location : OFFICE Feed: TOP

CONNECTED LOAD OVERCURRENT CONDUCTORS


CKT. LOAD DESCRIPTION PROTECTION (CU. WIRE) RACEWAY QUANTITY
NO. AMPERE
VA
PROPOSED TRANSFORMER ɸAB AT AF P SIZE (MM2) TYPE SIZE TYPE CO LIGHT MOTOR

50KVA, 13.8KV/230V 1 ACU 1.5HP SPLIT TYPE 3450 15 30 100 2 2-5.5 + 1 - 5.5(G) THHN 20mmØ PVC 1
(VERIFY PRIMARY VOLTAGE OF UTILITY) 2 ACU 1.5HP SPLIT TYPE 3450 15 30 100 2 2-5.5 + 1 - 5.5(G) THHN 20mmØ PVC 1
x100 3 ACU 1.0 HP WINDOW TYPE 1840 8.0 20 100 2 2-3.5 + 1 - 3.5(G) THHN 20mmØ PVC 1
TAP TO NEAREST
UTILITY POLE 4 ACU 1.0 HP WINDOW TYPE 1840 8.0 20 100 2 2-3.5 + 1 - 3.5(G) THHN 20mmØ PVC 1

5 CONVENIENCE OUTLET 1440 6.3 20 100 2 2-3.5 + 1 - 3.5(G) THHN 20mmØ PVC 8

6 CONVENIENCE OUTLET 1440 6.3 20 100 2 2-3.5 + 1 - 3.5(G) THHN 20mmØ PVC 8

PVC
M 7 LIGHTING OUTLET 250 1.1 30 100 2 2-3.5 THHN 20mmØ 12
PP-OFFICE PP-EQUIP 8 LIGHTING OUTLET 250 1.1 30 100 2 2-3.5 THHN 20mmØ PVC 12
PROPOSED 70AT, 2P 175AT, 2P
BUSBAR 9 SPACE 1500 6.5 100 2
CONCRETE PEDESTAL 10 SPACE 1500 6.5 100 2
200AT, 2P TOTAL 16960 73.8
MDP
IT DEMANDED LINE CURRENT: = (73.8 X 70% ) + (15 x 25%) USE:
= 55.4 AMPS PROTECTION: 70AT/100AF, 2P,600V, 60HZ, BOLT-ON, MCCB
SUB-FEEDER: 2 - 22MM2 THW + 1 - 8.0MM2 THW (G) IN 32MM DIA. CONDUIT

Designation : MDP Mounting: SURFACE MOUNTED


System : 230V, 1Ø, 2WIRE + GROUND, 60Hz Enclosure: NEMA 3R
Location : SERVICE PEDESTAL Feed: TOP

CONNECTED LOAD OVERCURRENT CONDUCTORS


x100 x22 CKT. PROTECTION (CU. WIRE) RACEWAY QUANTITY
LOAD DESCRIPTION AMPERE
NO. VA
ɸAB AT AF P SIZE (MM2) TYPE SIZE TYPE CO LIGHT MOTOR
x80
PP-EQUIP 43290 169.9 175 225 2 2-80 + 1 - 14(G) THW 50mmØ PVC

PP-OFFICE 16960 73.8 70 100 2 2-22 + 1 - 8.0(G) THW 32mmØ PVC

2 SINGLE LINE/RISER DIAGRAM TOTAL 60250 243.7


E 02 NOT TO SCALE
IT DEMANDED LINE CURRENT: = (243.7 A X 70%DF) + (25% X 15) TRANSFORMER SIZING:
= 174.4 AMPS CAPACITY(KVA) = (174.4A x 230V) / 1000
USE: CAPACITY (KVA) = 40.01 KVA
MAIN PROTECTION: 200AT/225AF, 2P,600V, 60HZ, BOLT-ON, MCCB
USE:
MAIN FEEDER: 2 - 100MM2 THW + 1 - 14MM2 THW (G) IN 65MM DIA. RSC CONDUIT
1 - 50KVA POLE MTD. TRANSFORMER,
13.8KV PRIMARY, 230V SECONDARY, 60HZ, OIL-IMMERSED
(VERIFY PRIMARY VOLTAGE OF UTILITY)

3 LOAD SCHEDULE AND COMPUTATION


E 02 NOT TO SCALE

PROJECT TITLE PROJECT OWNER SHEET CONTENT DESIGNED BY KGMOLINA SHEET NO.

DRAWN BY KGMOLINA
PROFESSIONAL ELECTRICAL ENGINEER E-02
PROPOSED NEW POWER CONNECTION MR. MARVIN DEL PONSO AS SHOWN CHECKED BY
PRC NO.: VALIDTY: REV. NO.
APPROVED BY
PTR ISSUED ON:
LOCATION LAMPARA ST., HERMOSA, BATAAN DATE
ISSUED AT: TIN:
6
3 PP-O
PP-O a b

Sab ROOM 1
ROOM 1

a b

p q
4 d c
PP-O

ROOM 2 Scd
ROOM 2 FUEL TANK AREA

d c p q

9
PP-E Spq
OPEN AREA m m e f
p q

OFFICE 1 OPEN AREA OFFICE 1


1 Sef
PP-O

7
PP-O
l l e f FUEL TANK AREA
Sklm
5 LIGHTING LAYOUT
E 03 NOT TO SCALE

g h
KITCHEN k KITCHEN k
OFFICE 2
Sgh

OFFICE 2
2
PP-O Sij 8
PP-O
g h
5
CR PP-O i j
PP-OFFICE PP-OFFICE
CR

OFFICE OFFICE
1 POWER LAYOUT 3 LIGHTING LAYOUT
E 03 NOT TO SCALE E 03 NOT TO SCALE

Sno FUEL TANK AREA


7
PP-E

8
PP-E
n n o o

FABRICATION AREA FABRICATION AREA

5 4
PP-E PP-E n n o o
1 2 3
PP-E PP-E PP-E
PP-EQUIP PP-EQUIP FABRICATION AREA
6 POWER LAYOUT
E 03 NOT TO SCALE
FABRICATION AREA FABRICATION AREA
2 POWER LAYOUT 4 LIGHTING LAYOUT
E 03 NOT TO SCALE E 03 NOT TO SCALE

PROJECT TITLE PROJECT OWNER SHEET CONTENT DESIGNED BY KGMOLINA SHEET NO.

DRAWN BY KGMOLINA
PROFESSIONAL ELECTRICAL ENGINEER E-03
PROPOSED NEW POWER CONNECTION MR. MARVIN DEL PONSO AS SHOWN CHECKED BY
PRC NO.: VALIDTY: REV. NO.
APPROVED BY
PTR ISSUED ON:
LOCATION LAMPARA ST., HERMOSA, BATAAN DATE
ISSUED AT: TIN: