NPI800R: Retrofitting Retrofitting Retrofitting Retrofitting

The document describes an NPI800R numerical relay that can be used to retrofit existing 700 and 7000 series overcurrent relays. It provides protection functions like overcurrent, earth fault, thermal overload, and negative phase sequence detection. It has inputs for current transformers, digital inputs, and output relays. Details are given on the protection functions, characteristics, and settings.

Uploaded by

MAJones89
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
95 views6 pages

NPI800R: Retrofitting Retrofitting Retrofitting Retrofitting

The document describes an NPI800R numerical relay that can be used to retrofit existing 700 and 7000 series overcurrent relays. It provides protection functions like overcurrent, earth fault, thermal overload, and negative phase sequence detection. It has inputs for current transformers, digital inputs, and output relays. Details are given on the protection functions, characteristics, and settings.

Uploaded by

MAJones89
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

RETROFITTING

Phase and Earth Fault


Overcurrent Relay

NPI800R (R2 case) is dedicated to the refurbishment of 700 and 7000 series
(R2 and R3 cases) of CEE phase and earth fault overcurrent relays providing
the detection of all type of short-circuits of medium and high voltage electrical
networks. This numerical and multi-function relay supervises in particular
phase to phase or phase to earth faults, negative sequence currents, thermal
state of the protected device, and the good operation of the circuit breaker
and its trip circuit.

NP800R relays provide monitoring, measurement and recording of the


electrical quantities of the network.
The relays can be set locally, using either the keypad and display or the RS232
port, or remotely using the RS485 port.

Two mountings are available, Flush Rear Connection (EDPAR) or Projecting


Rear Connection (SDPAR). A blank cover R1, provide in option, can improve
mechanical installation (replacement of CEE case R3 by a NPI800R).

Setting, reading, measurement and recording are all available locally or


remotely.

NPI800R Minimises retrofitting


man-hours

Maximises preservation of
existing installation

Simplifies and reduces re-


commissioning time

Minimises retrofitting costs

NPI800R - EDPAR

Protection functions
• Overcurrent with 3 thresholds [51-1] [51-2] [50]
• Earth fault with 2 thresholds [51N] [50N]
• Thermal overload for cable and transformer [49]
• Negative phase sequence overcurrent [46]
• Broken conductor with 2 thresholds [46BC]
• Load reclosing function
• Logical selectivity
Additional functions
• Latching of the output contacts [86]
• Trip circuit supervision of the breaker [74TC]
• Breaker failure [50BF][50N_BF]
• Load shedding – Load Restoration, remote control
CHARACTERISTICS NPI800R
Auxiliary Supply
• Auxiliary supply ranges 19 to 70 – 85 to 255 / Vdc or Vac 50 or 60 Hz
• Typical burden 6 W (DC), 6 VA (AC)
• Memory backup 72 hours
Analogue inputs
• Phase CT In 1 or 5 A
burden at In < 0.2 VA
Continuous rating 3 In, short duration withstand 80 In / 1s
CT setting: primary value from 1 A to 10 kA
measurement from 0.05 to 24 In
display of primary current from 0 to 65 kA
• Recommended CTs 5VA 5P20
• Earth current CT In0 1 or 5 A
burden at In0 < 0.5 VA
Continuous rating 1 In0, short duration withstand 40 In0 / 1s
measurement from 0.005 to 2.4 In0
display of primary current from 0 to 6.5 kA
• Earth current from Ring CT 100/1 measurement from 0.1 to 48 A primary
or Ring CT 1500/1 and BA800
• Frequency (50Hz or 60Hz) measurement: 45 to 55 Hz or 55 to 65 Hz
Digital inputs (4)
• Polarizing voltage 20 to 70 Vdc for 19 to 70 V auxiliary supply range
37 to 140 Vdc for 85 to 255 V auxiliary supply range
• Level 0 < 10Vdc range 19 to 70 V – < 33Vdc range 85 to 255 V
• Level 1 > 20Vdc range 19 to 70 V – > 37Vdc range 85 to 255 V
• Operating of the input by level 1 or 0 programmable
• Burden < 15 mA
Output Relays (3 + 1 WD)
• Relays A, B,: double contact NO, permanent current 8 A
(signalling, Shunt Opening Release) closing capacity 12 A / 4 s
short circuit current withstand 100 A / 30 ms
breaking capacity DC with L/R = 40 ms: 50W
breaking capacity AC with cos φ = 0.4: 1250 VA
• Relays C & WD: changeover contact, permanent current 10 A
(control, WD: Watchdog) closing capacity 15 A / 4 s
(C: programmable for CB Shunt short circuit current withstand 250 A / 30 ms
Opening Release or Under Voltage Release) breaking capacity DC with L/R = 40 ms: 50W
breaking capacity AC with cos φ = 0.4: 1250 VA
• Relays pulse, except WD adjustable from 100 to 500 ms
• Assignment of name to the output by the setting software
maximum of 16 characters capital letters or digits
Overcurrent function [51-1] [51-2] [50]
• Operating range I> - I>> - I>>> 0.3 to 24 In
• Thresholds accuracy 1% typical, 2% max from 0.5 to 4 In
3% typical, 5% max from 0.3 to 0.5 In and from 4 to 24 In
• Reset percentage on the operating level 95%
• Instantaneous operating time 60 ms including trip relay for I ≥ 2 Is
• Definite time delay 40 ms to 300 s: [51-1] I> - [51-2] I>> - [50] I>>>
• Accuracy of the time delays ± 2% or 20 ms
• Curves [51-1] I> - [51-2] I>> IEC 60255-3, ANSI IEEE
• Curves accuracy and type class 5 - Time Multiplier Setting: 0.03 to 3 s, type: see
functionalities
Earth fault function [51N] [50N]
• Operating range Io> - Io>> 0.03 to 2.4 In0 / CT - 0.6 to 48 A / ring CT
• Thresholds accuracy 1% typical, 2% max from 0.05 to 0.4 In0 / CT
3% typ., 5% max from 0.03 to 0.05 In0 and 0.4 to 2.4 In0 / CT
5% from 0.6 to 48 A / ring CT
• Reset percentage on the operating level 95%
• Instantaneous operating time 60 ms including trip for I ≥ 2 Is
• Definite time delay 40 ms to 300 s: [51N] Io> [50N] Io>>
• Accuracy of the time delays ± 2% or 20 ms
• Curves [51N] Io> IEC 60255-3, ANSI IEEE
• Curves accuracy and type class 5 - Time Multiplier Setting: 0.03 to 3 s, type: see
functionalities
CHARACTERISTICS NPI800R
Transformer thermal overload function [49]
• Tripping curves IEC 60255-8
• Heating-time constant CTE 4 to 180 min, class 5
• Cooling time constant 1 to 6.0 CTE, in step of 0.1
• Negative sequence factor 0 to 9
• Closing factor FD 50 to 100% CTE
• Thermal trip threshold Ib 40 to 130 % In, class 5
• Thermal alarm threshold 80 to 100 % θ thermal, class 5
• Reclosing thermal threshold inhibition 40 to 100 % θ thermal, class 5
Cable thermal overload function [49]
• Tripping curves IEC 60255-8
• Heating-time constant CTE 4 to 180 min, class 5
• Thermal alarm threshold 80 to 100 % θ thermal, class 5
• Thermal trip threshold Ib 40 to 130 % In, class 5
Negative phase sequence overcurrent function [46]
• Threshold Ineg: I2> 0.1 to 2.4 In, accuracy 5% for Iph > 0.3 In
• Instantaneous operating time 60 ms including trip relay for I ≥ 2 Is
• Definite time delay 40 ms to 300 s
• Accuracy of the time delay ± 2% or 20 ms
• Curves IEC 60255-3, ANSI IEEE
• Curves accuracy and type class 5 - Time Multiplier Setting: 0.03 to 3 s, type: see
functionalities
Broken conductor function [46BC]
• Threshold Ineg/Ipos: I2/I1> - I2/I1>> 10 to 250%
• Accuracy ±5%
• Definite time delay 40 ms to 300s
• Accuracy of the time delays ± 2% or 20 ms
Trip circuit supervision and breaker failure [74TC] [50BF] [50N_BF]
• Trip circuit supervision [74TC] requires one or two digital inputs (see application guide)
• Operating time (in faulty condition) 500 ms fixed for [74TC] function
• Failure threshold [50BF] 5% to 30 % In, step of 1 In
• Failure threshold [50N_BF] 0.5% to 3% In0, step of 0.1 In0
• Breaker failure time delay 60 to 1000 ms, step of 10 ms
Latching of the output contacts [86]
• Manual reset for output relays A, B, C (programmable assignment)
• Reset digital input, digital communication or local MMI
Load reclosing function
• Application threshold adjustment [50] [51] [50N] [51N] [46] [46BC]
• Operating principle function activation by digital input
• Ratio « K » of reclosing time 50 à 200%
• Accuracy ±5%
• Reclosing time 40 ms to 300s, ± 2% or 20 ms
Logical selectivity
• Application on radial network number of relays too important to allow the use of time
co-ordination
• Operating principle additional time added to the functions [50] [51] [50N] [51N]
• Additional time delay [51] [51N] 60 ms to 120s, ± 2% or 20 ms
• Additional time delay [50] [50N] 60 ms to 3s, ± 2% or 20 ms
• Operating mode of digital input negative or positive true-data mode
Digital inputs assignment
• By setting software
• Setting table selection set 1 – set 2
• Disturbance recording order
• Logical selectivity
• Interlock o/o
• Interlock c/o
• Control mode dedicated to remote control, local / remote
• Reclosing mode
• Reset [86] function acknowledgment of the selected output(s)
• Trip circuit supervision [74TC] function
• CB trip external order function [74TC] blocked if external trip order
CHARACTERISTICS NPI800R
User programmable functions (digital inputs – digital outputs)
• Status of the function in or out of service, by local MMI or by the setting software
• Tripping mode or report report: for time stamping and event recorder
• Operating and release time delays tripping mode: 40 ms to 300 s
• Assignment of name to the function, by the setting software
maximum of 14 characters
• Assignment of one or more output relays by local MMI or by the setting software
(alarm or trip) A, B, C
Counters
• Cumulative breaking current maximum 64.106 kA² (phase 1,2 and 3)
• Operation number of circuit breaker 0 to 10 000
Load shedding – Load Restoration, remote control
• Load shedding level 1 to 6
• Time delay before reclosing 1 to 120 s, ± 2%
• Reclosing pulse 100 to 500 ms (remote control)
• Output relays assigned programmable by local MMI or by setting software
A, B, C
Digital outputs assignment
• By local MMI or by setting software
Signalling LEDs assignment
• By setting software
Man Machine Interface
• Relay display 2 lines of 16 characters
Language French, English, Spanish, Italian
• Configuration and operating software Windows® 2000, XP, Vista and 7 compatible
Language French, English, Spanish, Italian
MODBUS® Communication
• Transmission asynchronous series, 2 wires
• Interface RS 485
• Transmission speed 300 to 115 200 bauds
Disturbance recording
• Number of recordings 4
• Total duration 52 periods per recording
• Pre fault time adjustable from 0 to 52 cycles
CHARACTERISTICS NPI800R
Presentation
• Height 4U
• Width case R2
• Brackets 19” rack mounting see diagram 9954 (7000 series rack definition table)
Case (see drawing D40037)
• EDPAR
H, W, D (case & base) 172 x 83 x 222 mm
H, W (front face dimensions) 217 x 98 mm
• SDPAR
H, W, D (case & base) 172 x 83 x 227 mm
H, W (front face dimensions) 172 x 83 mm
• Weight 3.5 kg
Connection - codification
• NPI800R See diagram S39962
• Ring CT See diagram 142941
• BA800 See diagram 38766
SMARTsoft
SMARTsoft, integrated software for the Industry, Railway and Transmission ranges, helps the User get the
best from NP800 series relays.

SMARTsoft

User friendly
Diagnosis
Fault analysis
Maintenance tools
Functionalities
• 2 ranges of auxiliary supply
• Storage of the lack and the restoration of the • Remote control by communication channel:
auxiliary voltage (time stamped events) tripping or closing, load shedding with priority
• Configuration and parameter setting by local MMI levels and load restoration
or off-line / on-line PC • Setting software compatible with Windows® 2000,
• Measurement of electrical quantities: XP, Vista and 7
Display expressed in primary values • User interface with access to all protection
Instantaneous, integrated and maximum values of functions
phase and earth currents • Time stamping of internals events with 10ms
• Instantaneous alarm threshold resolution
• Definite time tripping • Time stamping of digital inputs with 10ms
• Dependent time tripping according to inverse/very resolution
inverse/extremely inverse IEC 60255-3 curves • Event recording: 250 locally recorded events, 200
• Tripping according to RI curve (electromechanical) saved in case of loss of auxiliary supply
• Tripping according to moderately inverse/very • Recording of measurements and current setting
inverse/extremely inverse ANSI /IEEE curves group
• Logical selectivity on the three phase thresholds and • Local / remote events acknowledgment
the two earth thresholds • Disturbance recording according to Comtrade®
• Thermal image according to IEC 60255-8: format: storage of 4 recordings of 52 periods
• Cable (by phase) and transformer (3 phase) • Disturbance recording initiated by digital input,
• 2 setting groups, locally or remotely selectable setting software or communication channel
• CB Monitoring: interlocks discrepancy, local or • Closing function: adjustment of phase, earth,
remote control of closing / tripping negative sequence current thresholds by external
• Circuit breaker maintenance: input
• counters of operation number and cut-off ampers² • Remote setting and reading of measurements,
per phase, alarm and threshold counters, alarms and parameter settings
• Monitoring of breaker failure by checking • Remote reading of disturbance recording and event
the disappearance of current after opening log
• Self-diagnosis: Memories, output relays, A/D
converters, auxiliary supply, cycles of execution of
software, hardware failure
• Test of wiring, phase rotation and direction of the
currents

Related Equipement
• BA800 for ring CT 1500/1

Functional diagram

The specifications and drawings given are subject to change and are not binding unless confirmed by our specialists.