PS48300-3B-2900 PS48600-3B-2900 User Manual V1.5 20130815
PS48300-3B-2900 PS48600-3B-2900 User Manual V1.5 20130815
Power System
User Manual
Version V1.5
Revisio n date August 15, 2013
BOM 31011772
Emerson Network Power provides customers with technical support. Users may contact the nearest
Emerson local sales office or service center.
Electrical Safety
I. Hazardous voltage
Danger
Some components of the power system carry hazardous voltage in operation. Direct contact or indirect contact through
moist objects with these components will result in fatal injury.
Observe safety rules in the industry when installing the power system. The installation personnel must be
licensed to operate high voltage and AC power.
In operation, the installation personnel are not allowed to wear conductive objects, such as watches, bracelets,
bangles and rings.
When you spot the cabinet with water or moisture, turn off the power immediately. In moist environment,
precautions must be taken to keep moisture out of the power system.
"Prohibit" warning label must be attached to the switches and buttons that are not permitted to operate during
installation.
Danger
High voltage operation may cause fire and electric shock. The connection and wiring of AC cables must be in compliance
with the local rule s and regulations. Only those who are licensed to operate high voltage and AC power can perform high
voltage operations.
II. Tools
Warning
III. Thunderstorm
Danger
Never operate on high voltage, AC, iron tower or mast in the thunderstorm.
In thunderstorms, a strong electromagnetic field will be generated in the air. Therefore the equipment should be
well earthed in time to avoid damage by lightning strikes.
IV. ESD
Note
The static electricity generated by the human body will damage the static sensitive elements on PCBs, such as large-scale
ICs. Before touching any plug-in board, PCB or IC chip, ESD wrist strap must be worn to prevent body static from
damaging the sensitive components. The other end of the ESD wrist str ap must be well earthed.
V. Short circuit
Danger
During operatio n, never short the positive and negative poles of the DC distribution unit of the power system or the
non-grounding pole and the earth. The power system is a co nstant- voltage DC power de vice, short circuit will result in
equipment burning and endanger human safety.
Check the polarity of the cable and c onnection terminal when performing DC live operations.
As the operation space in the DC distribution unit is very tight, please c arefully select the operation space.
Never wear a watch, bracelet, bangle, ring, or other conductive objects during operation.
Use insulated tools.
In live operation, keep the arm, wrist and hand tense, so that when the tool in operation s lips, the movement of
the human body and tool is reduced to a minimum.
Battery
Danger
Before any operation on battery, read carefully the safety prec autio ns for batte ry transportation and the correct batte ry
connection method.
Note
If the power system does not connect with m ains power for a long time, to prevent battery overdischarge, users should cut
batte ries off from the power system thoroughly, for example , pulling out battery fuses or switching off battery MCBs.
Before putting the power system into operation, insert all the battery fuses or switch on all the b attery MCBs.
Non-standard operation on the battery will cause danger. In operation, precautions should be taken to prevent
battery short circuit and overflow of electrolyte. The overflow of electrolyte will erode the metal objects and PCBs,
thus causing equipment damage and short circuit of PCBs.
Before any operation on battery, pay attention to the following points:
1. Remove the watch, bracelet, bangle, ring, and other metal objects on the wrist.
2. Use specialized insulated tools.
3. Use eye protection device, and take preventive measures.
4. Wear rubber gloves and apron to guard against electrolyte overflow.
5. In battery transportation, the electrode of the battery should always be kept facing upward. Never put the
battery upside down or slanted.
Note
The advantage of enabling BLVD is protecting the batteries from over-discharge when the batte ry voltage is low. The
disadvantage of enabling BLVD is that when the battery voltage drops down to a certain value, all the loads (including
non-priority loads and priority loads) will be cut off due to battery disconnection.
The advantage of software disabling BLVD is prolonging the power supply of priority loads. The disadvantage is that
software disabling cannot prevent unwanted power failure due to misoperation or power system failure.
The advantage of hardware disabling BLVD is pre venting unwante d power failure due to misoperation or power system
failure, and ensuring the continuity of vital loads’ power supply.
Others
I. Sharp object
Warning
When moving e quipment by hand, wear protective glo ves to avoid injury by sharp object.
Note
The signal cables should be routed at least 150mm away from power cables.
Note
Note
To preserve the environment, the busbar of the power system may use tinning technique or passivation technique. The
busbar may become dark due to long-term operation, which does not influence the performance or use of the power system.
Contents
Chapter 1 Overview ..............................................................................................................................................................1
Chapter 1 Overview
This chapter introduces model description, composition and configuration, and features of the power system.
The “power system” in this manual refers to the PS48600-3B/2900 (NetSure 701 C) (abbreviated as
“PS48600-3B/2900”) and PS48300-3B/2900 (NetSure 701 C) (abbreviated as “PS48300-3B/2900”) power system.
PS 48 600 - 3B / 2900 - X8
Type
Rated output power of the rectifier: 2900W
Version
Rated output current: 600A
Rated output voltage: -48V
Power supply system
NetSure 701 C
Region: China
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
2 Chapter 1 Overview
Composition
PS48600-3B/2900 power system has three models: PS48600-3B/2900-X8, PS48600-3B/2900-X9,
PS48600-3B/2900-X10 and PS48600-3B/2900-X11. Figure 1-2 illustrated structure of PS48600-3B/2900-X10 power
system. Compared with it, PS48600-3B/2900-X8 and PS48600-3B/2900-X9 power system has only one AC input
MCB, no AC output MCB; PS48600-3B/2900-X9 power system has only one AC input and output MCB. Other
components of the three power systems are the same. PS48600-3B/2900-X11 power system only one AC input MCB,
and the DC output configure is different.
Battery fuse
DC postitive busbar
Corntroller
AC input MCB
Rectifier
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Chapter 1 Overview 3
DC positive busbar
Controller
AC input MCB
Recrifier
Configuration
The configuration of the power system is in Table 1-1.
Table 1-1 Power system configuration
Configuration
Item
PS48300-3B/2900 PS48600-3B/2900
Model: R48-2900M0 Model: R48-2900M0
Rectifier Standard configuration: 5 pieces Standard configuration: 10 p ieces
Optional configuration: 2 pieces ~ 6 pieces Optional configuration: 2 pieces ~ 12 pieces
Model: M522S Model: M522S
Controller
Standard configuration: 1 piece Standard configuration: 1 piece
AC input:
AC input:
PS48600-3B/2900-X8: 1 × 100A/3P MCB
PS48300-3B/2900-X8: 1 × 63A/3P MCB
PS48600-3B/2900-X9: 1 × 100A/3P MCB
PS48300-3B/2900-X9: 1 × 63A/3P MCB
PS48600-3B/2900-X10: 2 × 100A/3P MCB
PS48300-3B/2900-X10: 2 × 63A/3P MCB
PS48600-3B/2900-X11: 1 × 100A/3P MCB
PS48300-3B/2900-X11: 1 × 63A/3P MCB
PS48600-3B/2900-XF: 1 × 100A/3P or 2 × 100A/3P
AC power PS48300-3B/2900-XF: 1 × 63A/3P or 2 × 63A/3P MCB
MCB
distribution
AC output: AC output:
PS48300-3B/2900-X8: 1 × 16A/3P, 1 × 16A/1P MCB PS48600-3B/2900-X8: 1 × 16A/3P, 1 × 16A/1P MCB
PS48300-3B/2900-X9: 1 × 16A/3P, 1 × 16A/1P MCB PS48600-3B/2900-X9: 1 × 16A/3P, 1 × 16A/1P MCB
PS48300-3B/2900-X10: 1 × 16A/3P, 1 × 16A/1P MCB PS48600-3B/2900-X10: 1 × 16A/3P, 1 × 16A/1P MCB
PS48300-3B/2900-X11: 1 × 16A/3P, 1 × 16A/1P MCB PS48600-3B/2900-X11: 1 × 16A/3P, 1 × 16A/1P MCB
PS48300-3B/2900-XF: optional PS48600-3B/2900-XF: optional
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
4 Chapter 1 Overview
Configuration
Item
PS48300-3B/2900 PS48600-3B/2900
Priority load output:
PS48300-3B/2900-X8: Priority load output:
2 × 32A/1P MCB, 2 × 10A/1P MCB 2 × 63A/1P MCB, 2 × 32A/1P, 2 × 10A/1P MCB
PS48300-3B/2900-X10: PS48600-3B/2900-11: 2 × 32A/1P MCB, 2 × 10A/1P
2 × 63A/1P MCB, 2 × 32A/1P MCB, 2 × 10A/1P MCB MCB
PS48300-3B/2900-11: 1 × 32A/1P MCB, 2 × 10A/1P MCB PS48600-3B/2900-XF: optional
PS48300-3B/2900-XF: optional
Non-prio rity load output:
Non-prio rity load output: PS48300-3B/2900-X8:
DC power PS48300-3B/2900-X8: 4 × 100A fuse, 6 × 63A/1P MCB, 3 × 32A/1P MCB,
distribution 2 × 100A fuse, 6 × 63A/1P MCB, 2 × 32A/1P MCB 2 × 16A/1P MCB
PS48300-3B/2900-X10: PS48300-3B/2900-X10:
5 × 100A fuse, 1 × 63A/1P MCB 3 × 160A fuse, 2 × 100A fuse, 2 × 63A/1P MCB, 3 ×
PS48300-3B/2900-11: 4 × 100A fuse, 4 ×63A fuse, 4× 32A/1P MCB, 2 × 10A/1P MCB
32A/1P MCB, 2 × 10A/1P MCB PS48600-3B/2900-11: 6 × 100A fuse, 6 ×63A fuse,
PS48300-3B/2900-XF: optional 2 × 16A/1P MCB, 2 × 10A/1P MCB
PS48600-3B/2900-XF: optional
Battery route:
Battery route:
2 × 250A fuse
2 × 500A fuse
PS48300-3B/2900-X11:2×300A fuse
Optional
Top cover, temperature sensor and modem
parts
1.3 Features
The rectifier uses the active Power Factor Co mpensation (PFC) technology, raising the power factor to 0.99
The power system has wide AC input voltage range of 90V ~ 290V
The rectifier uses soft s witching technology, raising the effic iency to 91%
The rectifier has high power density
The rectifier is hot pluggable. It takes less than 1min to replace a rectifier
The rectifier has two optional over-voltage protection methods: hardware protection and software protection. The
latter one also has two optional modes: lock-out at the first over-voltage and lock-out at the second
over-voltage
The controller has perfect battery management. The management functions include the LLVD, BLVD,
temperature compensation, auto voltage regulation, stepless current limiting, battery capacity calculation and
on-line battery test, etc
The controller can save up to 200 pieces of historical alarm records, and 10 sets of battery test data records
The power system has network design. Providing multiple communication ports (such as RS232, modem and
dry contacts), which enables flexible networking and remote monitoring
The power system has perfect lightning protection at both AC side and DC side
The power system has complete fault protection and fault alarm functions
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Chapter 1 Overview 5
Using centralized monitoring mode, the controller module manages the AC distribution unit and DC distribution unit. It
also receives the operating data of the rectifiers and controls them accordingly through CAN mode. The controller can
be connected to a local computer using the RS232 port. The power system can be connected to the monitoring
center through connecting a modem or other transmission resources (such as PSTN and so on) to achieve remote
monitoring.
For the detailed schematic diagram of the power system, see Appendix 5 Schematic Diagram.
1.5 Functions
Main functions of the power system include:
Lightning and surge protection.
LLVD and BLVD.
Fault alarm and protection.
AC and DC distribution.
Perfect earthing design.
The power system is equipped with lightning protection at both the AC side and the DC side. The lightning protection
system is shown in Figure 1-4.
Rectifier
unit
distribution
AC
unit
distribution
DC
5m ~ 10m
AC Input
input
Rectifier
- 48V output
DC
I/B II/C SPD
SPD SPD Rectifier
Battery
Battery
Monitoring string
Cotroller 1, 2
module 1,2
RS232
Note:
Note: Classes
Classes
Note: ClassesI,II,III
I, II,are
I,II,III are IEC
IECIEC
III are atandard,
standard,
standard,
classes B,C,D are RJ11
Note:
classes B,C,D are VDE
Classes VDE Geman
I, II, III are IEC
Geman standards.
standard,
standards. Modem PSTN
I:I: Lever classes B, C, D are VDE German standard.
standards.
Lever11(Class
Level classes
SPD B)B,
(Class SPD,
C,B),DIIII:
: Lever
are Lever
VDE22standard.
Level (Class
SPD C) SPD
(Class C)
DIN VDE0675- 6: 1989- 11(draft) RJ11 Remote host
SPD
The power system is equipped with a C lass C SPD. To achieve better lightning protection, it is recommended to
mount a Level 1 (Class B) SPD. The SPD installation is shown in Figure 1-5.
The Level 1 (Class B) SPD should be purchased and mounted by the user. If condition permits, it is recommended
that the c able length between the Level 1 (Class B) SPD and the input terminals of the AC distribution unit of the
power system range between 5m and 10m. And this section of cable should be routed indoors to avoid direct
lightning strike. When mounting the Level 1 (Class B) SPD, pay attention to the CSA and length of the cable
2
connecting the Level 1 (Class B) SPD: The CSA should not be less than 25mm , the cable should be advisably
shorter than 0.5m, and so should the earth cable of the Level 1 (Class B) SPD. The SPDs should be inspected
periodically to ensure their normal operations.
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
6 Chapter 1 Overview
Powersystem
Power supply
system
5m ~ 10m
A Lever
Level 2
Class
Class-C
(Class
B SPD C)
C SPD
SPD
N
SPD earth
PE --
System earth bar
-48Vdc
240Vdc
240Vdc
48Vdc
Lever
leverFirst
Lever
Level
1 SPD1 DC earth
Class-B
Class-B
(Class B) +
(Class
SPDB)
SPD +
SPD earth
DC earth cable
Protective earth
Protective earth cable
User earth bar
To prevent lightning strikes at the DC side from damaging the equipment, an effective lightning protection device is
provided, which can withstand simulated lightning surge currents of 10kA and 15kA at 8/20μs once respectively.
To prevent conductive lightning strike from damaging the modem port of the controller, the power system provides
lightning protection ( RJ11 SPD, optional) for the modem port. The RJ11 SPD can withstand a 5kA lightning surge
current at 8/20μs and a 4kV lightning surge voltage at 10/700s.
In case of mains failure, the rectifiers will stop working and the batteries will begin to discharge and power the load.
When the battery voltage falls to the low voltage alarm point 45.0V (adjustable), the system will give audible/visual
alarm. When the battery voltage continues to fall and reaches the LLVD point 44.0V (adjustable), the LLVD contactor
will open, cutting off the power supply for the non-priority loads connected to the LLVD output branches thus the
power supply to priority load can be prolonged. As the batteries discharge, the battery voltage continues to fall. When
it reaches the BLVD point 43.2V (adjustable), the BLVD contactor will open, and the battery discharge will come to an
end. Thus the power supply to all loads is stopped, protecting the battery from being damaged due to over-discharge.
When the mains recovers and the rectifier output resumes normal functioning, the LLVD and BLVD contactors will
automatically close, and the system will resume normal operation.
The power system provides perfect fault alarm and protection functions. The system operating data can be collected
and the states of the load MCBs, load fuses, battery fuses and Level 2 (class C) SPD can be detected by the
controller. The alarm level can be set and audible/visual alarms can be selected for the system alarms, such as AC
input over/under voltage, DC output over/under voltage, fuse alarm, rectifier fault and protection alarm. The alarm
type can be configured to correspond to dry contact relay output.
AC distribution
The functions of AC distribution are as follows:
The AC input uses 3-pole MCB, and has short circuit and over-current protection.
The AC input has overvoltage and undervoltage protection.
See Table 1-2 for the functions of the AC input and output interfaces of the power system.
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Chapter 1 Overview 7
DC distribution
The functions of DC distribution are as follows:
Output load branch has short circuit and over-current protections, and branch capacity can be adjusted
according to user requirements.
Battery input uses fuse which has functions like short circuit, over-current protection, alarm and fault status
detection.
Battery current detection.
DC output overvoltage, undervoltage alarm functions.
See Table 1-3 for the functions of the DC input and output interfaces of the power system.
The earthing system in the communication equipment room is generally designed on the principle of common earth,
that is, DC operation earth, SPD earth and protective earth sharing the same earth. The earth resistance should be in
accordance with the specifications listed in Table 1-4.
Table 1-4 Earth resistance requirements for communication station
Earth resistance Application range
Integrated building, inte rnational telecom bureau, tandem station, SPC switching office above 10000 lines,
<1Ω
toll office above 2000 lines
<3Ω SPC switching office above 2000 lines and below 10000 lines, toll office below 2000 routes
SPC switching office with less than 2000 lines, optical cable terminal station, carrier wave repeating station,
<5Ω
earth station, microwave junction center, mobile communication machine station
<10Ω Microwave relay station , optical cable rela y station, small-sized earth station
<20Ω Microwave passive rela y station
Suitable for those whose earth resistance rate is less than 100Ω·m , SPD earth in the inte rface between
<10Ω
electric cable and aerial electric line
Suitable for those whose earth resistance rate is 100-500Ω·m, SPD earth in the interface between electric
<15Ω
cable and aerial electric line
Suitable for those whose earth resistance rate is 501-1000Ω·m, SPD earth in the interface between electric
<20Ω
cable and aerial electric line
The basic method of common earth is to short the earth bar and DC earth of the power system to the user earth bar
in the equipment room. The SPD earth and protective earth of the power system shou ld be connected to the earth
bar of the power system in shortest route as shown in Figure 1-4.
When the AC neutral line is repeatedly earthed, the earth cable should be separately led out from the earth device. It
is strictly prohibited to connect it to the earth bar inside the cabinet of the power system or the earth point on the
cabinet. The protective earth cable of 3-phase 5-line system and single-phase 3-line system can be directly
connected to the earth bar of the power system.
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
8 Chapter 2 Installation Instruction
This chapter introduces installation and cable connection. Before installation, please read through safety regulations,
and then follow this instruction to carry out the installation step by step.
2.2 Preparation
Unpacking inspection
The equipment should be unpacked and inspected after it arrives at the installation site. The inspection shall be done
by representatives of both the user and Emerson Network Power Co., Ltd.
To inspect the equipment, you should open the packing case, take out the packing lis t and check against the packing
list that the equipment is correct and complete. Make sure that the equipment is delivered intact.
Cables
The cable should be selected in acc ordance with relevant industry standards.
It is recommended to use the RVVZ cables as AC cables. The cable should reach at least 70°C temperature durability.
Select the AC cable CSA according to Table 2-1.
The CSA of DC cable depends on the current flowing through the cable, the allowable voltage drop and load peak
current. The recommended load peak current is 1/2 to 2/3 of MCB or fuse capacity.
Select the battery cable CSA according to Table 2-1. Select the load cable CSA according to Table 2-2.
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Chapter 2 Installation Instruction 9
The CSA of the system grounding cable should be the same as that of the largest power dis tribution cable and not
less than 35mm2. The grounding terminal of the grounding busbar is M10 bolt.
The power cabinet must be installed directly onto the cement floor, and kept a sufficient distance away from
combustible materials.
1. Mark the specific installation position of the cabinet
Determine the installation position of the power cabinet in the equipment room according to Figure 2-1.
≥800mm
≥800mm ≥800mm
400mm
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
10 Chapter 2 Installation Instruction
18 436
400 300
600
Note
1. In the non-full-configuration, install dummy plates at empty slots.
2. When installing the rectifier, hold the handle and push the rectifier to the slot gently, otherwise the slot may be damaged.
R48-2900U Handle
2. Put the rectifier onto the guide rail. Push the rectifier completely into the cabinet. Push the handle into the front
panel to pop out the positioning pin and lock the rectifier to the cabinet.
Danger
1. Switch off all MCBs and pull out all fuses before the electrical connection.
2. Only the qualified personnel shall do the power cable connection.
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Chapter 2 Installation Instruction 11
Grounding terminal
Neutral busbar
Connecting AC cables
1. Connect the AC input phase cables to the AC input MCB, as shown in Figure 2-5.
Priority load MCB Non-priority load fuse
Battery fuse
DC positive busbar
AC input MCB
AC output MCB
2. If the power system is configured with AC output MCB, connect the AC out cables to the AC output MCB and
neutral busbar, as shown in Figure 2-4 and Figure 2-5.
Note
The total capacity of the priority loads should not exceed 100A.
Connect the negative load cable to the upper terminal of the load MCB or load fuse. Connect the positive load cable
to the DC positive busbar, as shown in Figure 2-5.
Note
1. The batterie s may have dangerous current. Before connecting battery cables, make sure that the battery fuses at the system side
and the battery MCBs at the battery side are switched off. If there are no battery MCBs at the battery side, users should
disconnect any one of the connectors between battery cells to avoid live state of the power system after installation.
2. Be careful not to reversely connect the battery. Otherwise, both the battery and the power system will be damaged!
3. When the load capacity exceeds 200A, it is recommended to connect two routes of batteries.
1. Connect one end of the negative battery cable to the upper terminal of the battery fuse. Connect one end of the
positive battery cable to the DC positive busbar. The positions of the connection terminals are shown in Figure 2-5.
2. Connect OT lugs to the other end of the two battery cables. Wrap all the bare parts with insulating tape, and put
them beside the battery. Do not connect the cables to the battery until the DC distribution unit is to be tested.
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
12 Chapter 2 Installation Instruction
All the signal cables are connected to controller. The position of the controller is shown in Figure 1-2 and Figure 1-3.
The interfaces of the controller are shown in Figure 2-6. The functions of the interfaces are listed in Table 2-4.
RS232 Temp
9 6
5 1
J1 J2 J3 J4 J5 J6 J7 J8
J9
M522S
J10
J11 J12
Installing modem
Modem is an optional accessory, suitable for those who have purchased the modem remote monitoring system.
The following is an introduction to the specific modem installation position and connection, taking e-TEK TD-5648DCII
modem for example.
1. Fastening the modem
Put the cable ties through the fixing holes at the top of the cabinet. Use the cable ties to fix the modem to the top of
the cabinet, as shown in Figure 2-7.
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Chapter 2 Installation Instruction 13
Cable tie
Modem
Power
Note
During system testing, set the parameter ‘MODEM’ of the controller to ‘Y’.
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
14 Chapter 3 Installation Testing
This chapter introduces procedures of installation testing. The corresponding safety rules shall be adhered to in the
test.
Installation check
Check ite m OK Comments
Check all the MCBs, fuses and cables. Are their models correct?
Check the busbar connections, input and output cable connection, and connection between the power
system and the system grounding
Check if the number and connections of the batteries are correct. Check the polarity of the battery string
with a voltmeter
Make sure all the comm unication cables and alarm cables are connected to the controller. Check that the
tem perature sensor, if any, has been installed
Startup preparations
Check ite m OK Comments
Ma ke sure that all the MCBs are switched off and all the fuses are removed
Measure the AC input voltage. Ma ke sure the input voltage is within the allowable range Umin=___V
Check that the battery string circ uit is not closed
Connect the disconnected batteries to the battery string circ uit
Measure with a voltm eter across the connection points of each battery and make sure that the polarity is Umin=___V
right. For a lead-acid battery with 24 cells, the voltmeter should read 2.0V ~ 2.1V/cell o r 48V ~
51V/battery. If the voltage of certain cell is lower than 2.0 V, that cell must be replaced
Check with an ohmm eter that there is no short circuit between the positive & negative distribution
busbars, or between the positive & negative battery po les
(Note : Pull out all the rectifiers before the check and restore them after the check)
Startup
Check ite m OK Comments
Switch on the AC input MCB. Switch on one rectifier MCB. The green LED on the rectifier will be on and
the fan will start running after a certain dela y. The controller will show that the power supply voltage is
53.5V
Check the voltage and busbar polarity with a voltmeter. The voltage difference between the m easured
value and displa yed value should be less than ± 0.3V
Start and stop each rectifier of the power system by switching on and switching off the rectifier MCBs.
Check their ou tput vo ltages
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Chapter 3 Installation Testing 15
Select the main menu Settings (password: 1) Battery Settings Batt. Selection submenu. Set the ‘Mode’
parameter to ‘Manual’. Return to the Settings menu to set the parameters in relative submenus. For detailed
controller parameter setting method, see 4.7 Setting System Parameters.
Che ck item OK Comments
The system model has been set correctly in factory before delivery, check that the setting agrees with
the actual system (PS48300-3B/2900: 48V/300; PS48600-3B/2900: 48V/500)
The battery string number set at the controller should be the same as the number actually connected.
(By de fault: 2 )
Set the battery capacity according to the total capacity of all the battery connected to the power
system (By default: 300Ah)
Configure the tem perature coefficient according to the battery manufacturer’s requirement. Setting
range: 0 ~ 500mV/°C. By default: 72mV/°C. (if no temperature sensor is installed, do not set this
parameter)
Set the charge current limit according to your needs. Setting range: 0.1C10 ~ 0.25C 10. (By default:
0.1C10)
Set the controller according to the voltage suggested by the battery supplier.
Floating Charge (FC) voltage range: 42V ~ Boost Charge (BC) voltage. Default: 53.5V.
BC voltage range: FC vo ltage ~ 58V. By default: 56.4V.
For batteries that do not need BC, set the BC voltage to FC voltage plus 0.1V
Measure the battery voltage with a multimeter and record it. Enter Main menu Main tenance
(password: 1) RectTrim submenu. Set the output voltage of the rectifier to the value o f the battery
voltage. Insert the battery fuse. Set the output voltage of the rectifier to 53.5V
Enter the Batt. Selection submenu. Set the ‘Mode’ parameter to ‘Auto’
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
16 Chapter 3 Installation Testing
If any defect is found in this equipment, inform the personnel responsible for the contract.
If repairing is needed, please fill in the FAILURE REPORT and send the report together with the defective unit to the
repairing center for fault analysis.
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Chapter 4 Use Of The Controller 17
This chapter introduces the front panel and functional keys briefly, and expounds screen contents, access method,
system controlling, information querying and parameter setting.
After the controller is powered on, the language selection screen will pop up, and the controller is initialized. The
default language is Chinese. After the initialization, the first system information page will appear.
LCD
The controller uses a 128 × 64 LCD, and a keypad with six keys (listed in Table 4-2). The interface language is
Chinese/English optional. Description of the c ontroller keypad is listed in Table 4-2.
Table 4-2 Description of controller keypad
Screenprint Name Function
Return to the upper level m enu. When the audible alarm tone is generated, p ress ESC to cancel the
ESC Return ke y
alert
Enter the m ain menu or confirm the menu operation. When changing or inputting pa rameters, press
ENT Enter key
ENT to get in to ed iting state. After any change is made, press ENT to va lidate the change
▲ Up key Shift among parallel menus. For a character string, these two keys can be used to shift among
▼ Down key diffe rent options
Left key Change values at a va lue setting interface. For a character string, thes e two ke ys can move the
Right key cursor left or right
When the controller is powered on, the language selection page will appear and the controller will be initialized. The
default language is English. After initialization, the first page of system information will appear.
The system information page shows the main information which is displayed on five pages. You can press ▲ or ▼
repeatedly to select different system information pages. The first system information page is shown in Figure 4-2. At
this page, you may press ◄ and ► to adjust the LCD contrast (7-level).
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
18 Chapter 4 Use Of The Controller
2009-3-23
Float
53.5V 125A
Auto Normal
Figure 4-2 First system information page
During the operation, the power system will prompt y ou to enter password, as shown in Figure 4-3. Only the correct
password will allow you to enter the page you need.
Login:
Password:
1. To input the password, use ▲ or ▼ to modify numbers, and use ◄ or ► to move the c ursor. After the input, press
ENT to confirm.
2. If the password is incorrect, the power system will prompt ‘Password incorrect’.
3. Press ESC to return to MAINMENU page.
4. The power system has three different password levels: user level (default: 1), engineer level (default: 2) and
administrator level (default: 640275).
Once you enter the correct password, you never need to enter the password again during the operation. While the
interval time for adjacent operation is more than four minutes, the power system will prompt you to input the
password again. If you want to enter senior setting pages, you need to wait four minutes and cannot do any operation
during waiting, and then the power system will enter the senior setting pages after you input the higher level
password. If the two level passwords are the same, the power system will display the senior menus after you enter
the password.
MAINMENU page is the highest-level menu. At the sub-menus of this page, you can query the settings, controls,
rectifier information and alarm information of the power system, as shown in Figure 4-4.
1. At any system information page, press ENT to enter the MAINMENU page.
2. At any sub-menu of the MAINMENU page, press ESC repeatedly to return to the higher- level menu, and ultimately
to the MAINMENU page.
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Chapter 4 Use Of The Controller 19
The STATUS page is a sub-menu of the Main Menu. It contains three sub-menus, including Rectifiers, Active Alarm
and History Alarm, as shown in Figure 4-5.
STATUS
Rectifiers
Active Alarm
History Alarm
Displayed in two pages, the Settings page is a sub-menu of the MAINMENU. It is used to set all the parameters of
the power system. Input the correct password to enter the Settings page, as shown in Figure 4-6.
Settings DC Settings
Alarm Setting Rect Settings
Bat. Settings Sys Settings
AC Settings Comm Settings
Figure 4-6 Settings page
1. At the MAINMENU page, press ▲ or ▼ to select the Settings menu, and press ENT to confirm. System will then
prompt you to input the password.
2. Input the correct password and press ENT to enter the Settings page. Press ▲ or ▼ to scroll to the operation page
you need.
Users with different password level have different authorities. See Table 4-3.
Once you enter the correct password, y ou never need to enter the password again during the operation. While the
interval time for adjacent operation is more than four minutes, the power system will prompt you to input the
password again. If you want to enter senior setting pages, y ou need to wait four minutes and cannot do any operation
during waiting, and then the power system will enter the senior setting pages after you input the higher level
password. If the two level passwords are the same, the power system will display the senior menus after you enter
the password.
Displayed in two pages, the Maintenance page is a sub-menu of the MAINME NU. It is used to control the power
system in real time. You can enter the Maintenance page after you input the correct password. For this menu, the
user, engineer and administrator password, all users have the same authorities. The Maintenance page is shown in
Figure 4-7.
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
20 Chapter 4 Use Of The Controller
Maintenance
RectTrim: 53.5V
Start: FC
RectLimit: 121%
Batt: ReConnect
Load: DisConn
Figure 4-7 Maintenance page
1. At the MAINMENU page, press ▲ or ▼ to select the Maintenance menu, and press ENT to confirm. The power
system will prompt you to input the password when the battery management mode is set to Manual (see 4.7.2
Battery Settings).
2. Input the correct password and press ENT to enter the Maintenance page. Press ▲ or ▼ to scroll to the operation
page you need.
The Energy Saving page is a sub-menu of the MAINMENU, as shown in Figure 4-8. It is used to energy relevant
parameters.
Save Enable: N
Cyc Period: 168h
Rect Work: 80%
Rect Limit: 1
1. At the MAINMENU page, press ▲ or ▼ to select Energy Sa ving, and press ENT to confirm. The power system will
prompt you to input the password.
2. Input the correct password and press ENT to enter the Energy Saving page. Press ▲ or ▼ to select the
parameters you need.
The Fast Settings page is a sub-menu of the MAINMENU, as shown in Figure 4-9. It is used to set system type and
battery capacity.
System Type:
48V/SET
Capacity: 600Ah
1. At the MAINMENU page, press ▲ or ▼ to select Fast Settings, and press ENT to confirm. The power system will
prompt you to input the password.
2. Input the correct password and press ENT to enter the Fast Settings page. Press ▲ or ▼ to select the parameters
you need.
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Chapter 4 Use Of The Controller 21
2009-3-23
Float
53.5V 125A
Auto Normal
Figure 4-10 First system information page
The date and time are displayed at the interval of 2s. System operation state contains No Alarm and A larm. Battery
management mode includes Auto and Manual. Battery state includes Float charge, Temp Comp, Boost charge, Cyclic
Boost, Batt. Test, ShortTest and TimeTest.
Save Stat: Y
Sys Used: 80.0%
Cyc BC After:
2400h
Figure 4-11 Sys Used and Cyc BC After information page
The first line displays the save state. The second line displays the percentage between the output power and rated
power of the rectifier. The lower line displays the BC prompt information, they will be different for different states of
the power system, including:
1. Prompt the time of the next Cyclic BC according to the battery state.
2. If BC is going on or prohibited, ‘---’ will be prompted.
Battery information
At the first system information page, press ▼ to query the battery information, as shown in Figure 4-12.
Batt1: 0A
Remain: 100%
Batt2: 0A
Remain: 100%
Figure 4-12 Battery information page
Batt1 and Batt2 in the preceding page represent respectively the currents of the batteries that battery shunt 1 and
shunt 2 are connected to. If the Shunt Coeff of battery group is set to No, the battery information page will display
‘Not connected’ and no actual c apacity will be displayed.
The remaining battery capacity can be displayed in the mode of percentage, remaining Ah or remaining time. The
default is the percentage.
AC information
At the battery information page, press ▼ to display AC information page, as shown in the following page. The power
system will display AC voltage of the A, B and C phases, as shown in Figure 4-13.
AC 1 Volt AC 2 Volt
Phase A: 0V Phase A: 0V
Phase B: 0V Phase B: 0V
Phase C: 0V Phase C: 0V
Figure 4-13 AC information page
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
22 Chapter 4 Use Of The Controller
Bat.Temp:
25℃
Figure 4-14 Bat. Temp page
If the temperature sensor is not connected or is faulty, the power system will prompt ‘---’. Meanwhile, alarm
information page will display Temperature sensor not connected or Temperature sensor failures. If the controller bans
BC and no temperature sensor is configured, this page will not be displayed.
Note
If the controller has not detected rectifiers, you cannot query the rectifier information.
The rectifier information includes the rectifier serial No., voltage, current, current limit, AC input voltage, mains
situation, rectifier power limit and temperature power limit.
At the STATUS page (see Figure 4-5), press ▲ or ▼ to select the Rectifiers sub-menu, as shown in Figure 4-15.
Press ENT to confirm.
The information of every rectifier is displayed in three pages. Press ► to scroll to the next page, or ◄ to return to the
last. Press ◄ and ► to shift between rectifiers.
At most 24 pieces of rectifier information can be displayed. When selecting one rectifier, the green indicator of the
corresponding rectifier will blink. If the rectifier communic ation is interrupted, the information will be displayed in high
light.
When a new alarm is raised, and there is no operation on controller keypad within two minutes, the LCD of the
controller will prompt the active alarm automatically.
If there are multiple alarms in the current system, you can query alarms through the following steps.
At the STATUS page (see Figure 4-5), press ▲ or ▼ to select Active Alarm menu. Press ENT to confirm.
1. If there is no active alarm, ‘Active alarm: None’ will be displayed.
2. If there is any alarm, the display will be like the page shown in Figure 4-16.
Alarm 1/5
Manual Mode
Observation
071213 14:27:50
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Chapter 4 Use Of The Controller 23
The preceding page includes alarm serial No./ total alarm No., alarm name, alarm level and time. The alarm raising
time determines the sequence it is displayed, with the latest alarm displayed first. Use ▲ or ▼ to view all active
alarms.
When querying rectifier alarms, press ► to view rectifier ID. The green indicator of the rectifier will blink.
In the case of battery test alarm or maintenance time alarm, press ► to display the prompt information, then press
ENT to confirm that the alarm is cleared. The active alarms in the controller are given in Table 4-4.
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
24 Chapter 4 Use Of The Controller
1. At the S TATUS page (see Figure 4-5), press ▲ or ▼ to select History Alarm menu. Press ENT to confirm.
1) If there is no history alarm, the power system cannot enter the lower level menu.
2) If there is history alarm, the display will be like the page shown in Figure 4-17.
199 ID2067000584
Rect1 Fault
071213 14:27:50
071213 17:30:05
If the alarm is a rectifier related alarm, the first line in Figure 4-17 will display the latter 10 number of the rectifier ID.
The history alarms of the controller are stored in cyclic order. Up to 200 alarms will be recorded. Above that, the
earliest alarm will be cleared automatically.
2. Use ▲ or ▼ to view other history alarms.
3. At any History Alarm page, press ESC repeatedly to return to the first system information page.
4.6 Maintenance
Note
Be careful! BLVD operations may result in power interruption.
1. At the battery basic parameter setting page (see Figure 4-24), change the battery management mode from Auto to
Manual. Press ENT to confirm. For the detailed procedures, see Basic parameters in 4.7.2 Battery Settings.
2. At the MAINMENU page, press ▲ or ▼ to select the Maintenance menu. Press ENT and the power system will
prompt you to enter the password.
3. Input the password and press E NT to enter the Maintenance page, as shown in Figure 4-18.
Maintenance Rect 1: DC On
Start: FC Rect 1: AC On
RectTrim: 53.5V Rect 1: Reset
RectLimit: 121%
Figure 4-18 Maintenance page
4. Use ◄ or ► to select the needed action. After the input, press E NT to confirm or ESC to cancel.
1) Start: The options include FC, BC and Test. Press ◄ or ► to select the needed action. If there is AC power off
alarm, or the busbar voltage is too low, the BC and battery test control will not be executed by the power system. No
battery test control can be conducted when the rectifier c ommunication is interrupted. Finally, after the battery test,
the battery management mode will be changed from Manual to Auto automatically.
2) RectTrim: Range: 42V ~ 58V. If the value of this parameter cannot exceed the over-voltage alarm point, otherwise,
the parameter will be invalid.
3) RectLimit: Range: 10% ~ 121%.
4) Rect N: The maintenance operations over a single rectifier include: DC ON/OFF, AC ON/OFF and Reset.
The Operation method:
1) Use ▲ or ▼ to select the rectifier parameter, and ◄ or ► to change the rectifier serial No. Then press E NT to
confirm. The bottom line of the page displays the rectifier ID.
2) Use ▲ or ▼ to move the cursor to the maintenance operation area (that is DC On in Figure 4-18), and ◄ or ► to
select the value.
If the rectifier voltage is too high, you can select Reset to restore the output voltage of that rectifier to normal.
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Chapter 4 Use Of The Controller 25
5. Press ESC to return to the MAINMENU page and change the battery management mode from Manual to Auto. And
then press ESC to return to the system information page.
At the Settings page, press ▲ or ▼ to select Alarm Settings menu. Then press ENT to enter the A larm Settings page,
as shown in Figure 4-19.
Alarm Settings
Alarm Level
Alarm Control
DI Settings
Alarm Type:
Load Fuse Alarm
Level: OB
Out Relay: NO
Press ▲ or ▼ to move the cursor to the needed option. Press ◄ or ► to select the corresponding content and press
ENT to confirm.
The controller alarms are classified in to four types: critical alarm, major alarm, observation and no alarm. Critical
alarm, major alarm: These two types of alarms have strong impacts on the system performance. Whenever these
alarms are generated, you are supposed to handle them immediately. The alarm indic ators will be on and audible
indication will be given.
Observation: When this type of alarm is raised, the power system maintains normal output for a while. If the alarm
occurs during watch time, it should be handled immediately. If the alarm occurs during non- watch- time, handle it
during watch time. The alarm indicators will be on when observation alarm occurs.
No alarm: The power system will not generate a visible or audib le indication.
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
26 Chapter 4 Use Of The Controller
DC Volt Under DC output vo ltage lower than the setting of ‘DC output Under- vo ltage
8 No ala rm None
under- voltage alarm point’ alarm
Over Tem p
9 Batt Ove r Temp Battery tem perature higher than the setting of Temp Critical None
alarm point
Batt Temp High High Temp
10 Battery tem perature higher than the setting of Temp Observation None
Alarm alarm point
Batt Temp Low Low Temp
11 Battery tem perature lower than the setting of Temp Observation None
Alarm alarm point
Ambient Tem p High Temp
12 Ambient temperature higher than the setting of Temp Observation None
High Alarm alarm point
Ambient Tem p Low Temp
13 Ambient temperature lower than the setting o f Temp Observation None
Low Alarm alarm point
14 T No Probe Configured with temperature sensor but not connected Ma jor None -
Tem perature sensor measures unreasonable
15 Sensor Fault Ma jor None -
temperature
16 LVD 1 Load low voltage disconnects Ma jor 5 LLVD enabled
17 LVD 2 Battery low voltage disconnects Ma jor 4 BLVD enabled
Load Fuse Alarm Load failure caused by ove rload, short circuit, manual
18 Ma jor None -
1~6 disconnect, and alarm circuit failure
19 Aux Load Fails The last load fuse fa ilure Ma jor None -
Batt Fuse Alarm Battery failure caused by ove rload, short circuit, m anual
20 Ma jor None -
1~2 disconnect, and alarm circuit failure
Charging current of ba ttery string 1 higher than the Over (o ve r
21 Batt 1 Curr High Observation None
setting of ‘Over’ (Charging over current limit) current point)
Charging current of ba ttery string 2 higher than the Over (o ve r
22 Batt 2 Curr High Observation None
setting of ‘Over’ (Charging over current limit) current point)
AC input voltage of this rectifier lower than low- voltage
23 Rect AC Fail Critical 3 -
alarm point
24 Rect Over Temp The internal temperature of the rectifie r is higher than 90° Observation 3 -
25 Rect Failure The rectifier voltage is higher than upper limit voltage Ma jor 3 -
26 Rect Protect Rectifier performs self- protection and has no output Observation 3 -
27 Rect Fan Fails Rectifier fan fails Critical 3 -
28 Rect Derated Rectifier limits its output power Observation 3 -
29 Rect Not Respond Rectifier does not communicate with the controller Critical 3 -
30 HVSD Rectifier shut down under high voltage 3 -
31 Multi-Rect Alarm More than two rectifiers alarm Ma jor None -
32 Self-detect Err Hardware Self-detect Error No ala rm None -
33 Manual Mode Battery management is in manual control mode No ala rm None -
34 Non Float Status Battery is not under float status No ala rm None -
35 Batt Discharge Battery is discharging Observation None -
In the power system with load current shunt, the sampled
36 Load share Alarm load current plus batte ry current d iffers greatly from No ala rm 3 -
rectifier current
37 Batt Test Fail Battery d ischarging tim e shorter than expected Observation None -
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Chapter 4 Use Of The Controller 27
Related
No. Alarm Description Alarm level Related relay
parameter
In short test, battery discharging capacity is bigger than
38 Short Test Fail Observation None -
setting value
Actual output voltage is different from both the m easured
39 Volt Discrepancy DC bus voltage and different from the voltage reported by Observation None -
the rectifier to controller. The error is bigger than 1V
40 Ma intain Alarm Time to maintain system Observation None -
The controller has detected a reduction in the number of
41 Rectifier Lost Major None -
running rectifiers
42 Save Power The power system is running under energy saving status No alarm None -
Alarm Control
Voice Sign: Open
Clear: Hist Alarm
Voice Sign option: open/ off/ 3min/ 10 min/ 1h/ 4h. You can set according to you requirement.
‘Clear: His Alarm’ option: His Alarm, Rect Lost, TestFail, ShortTest, ESaveFail and Maintain. Press ENT to clear the
saved alarm information in the controller.
DI settings
At the Alarm Settings page, press ▲ or ▼ to select DI Settings menu. Then press ENT to enter the DI Settings page,
as shown in Figure 4-22.
DI Settings
DI NO: 1
SPD Alarm
Active: High
Press ▲ or ▼ to select the needed option. Press ◄ or ► to select the parameter value and press E NT to confirm.
Press ▲ or ▼ to modify the number and letter of DI name on the third line after pressing the ENT to confirm, press ◄
or ► to move the cursor left or right and input ‘#’ to end. Finally, press ENT to confirm.
Use ▲ or ▼ to change the number, and ◄ or ► to move the cursor left or right. Press ENT to confirm.
The value description of the parameter is listed in Table 4-6.
Table 4-6 Alarm setting parameter description
Parameter Range Factory setting Value description
The eighth corresponding connecting term inals, queued up in the
DI No. 1~8 1
order that the hardware switches are put
Figures or letters, When there are DI alarms , this param eter shows the alarm name you
DI Name SPD
10 at most have actually defined.
Alarm Mode High, Low Low High: alarm upon h igh level; Low: ala rm upon low level
Battery parameters are very important, for they are related to the life of battery.
At the Settings page, press ▲ or ▼ to select Bat. Settings menu. Then press ENT to enter the BAT Settings page, as
shown in Figure 4-23.
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
28 Chapter 4 Use Of The Controller
The battery parameters are divided into 5 kinds: basic, LVD, charging management, battery test and temperature
coefficient parameters.
Basic parameters
1. At the BAT Settings page, press ▲ or ▼ to select Basic Setting menu. Then press E NT to enter the battery basic
parameter setting page, as shown in Figure 4-24.
2. Press ▲ or ▼ to select one page or one of the parameters, and ◄ or ► to select the parameter value. Then press
ENT to confirm and save.
The value description of the basic battery parameters is listed in Table 4-7.
LVD parameters
At the BAT Settings page, press ▲ or ▼ to select LVD Setting menu. Then press E NT to enter LVD settings page, as
shown in Figure 4-25.
LVD1 Enable: Y
LVD2 Enable: Y
LVD1 Volt: 44.0V
LVD2 Volt: 43.2V
Figure 4-25 LVD settings page
Press ▲ or ▼ to select the parameter, and ◄ or ► to select the parameter value. Then press ENT to confirm.
LVD1 means the c ontroller opens the LLVD contactor, so that the non-priority load will be powered off. In this way, the
battery remaining capacity can sustain the priority load longer.
LVD2 means the c ontroller opens the BLVD contactor. In this way, the battery will stop powering the load, preventing
over-discharge.
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Chapter 4 Use Of The Controller 29
Cyc Boost:
Boost Limit Time:
-Enable: Yes
-Period: 2400h 1080min
-Time: 720min
Figure 4-26 Charge m anagement settings page
Press ▲ or ▼ to select the parameter, and ◄ or ► to select the parameter value. Then press E NT to confirm.
The charging management parameter value description is listed in Table 4-9.
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
30 Chapter 4 Use Of The Controller
Charge current
Constant BC smaller than
time-up 'Constant BC
Constant
BC Curr'
2. Press ▲ or ▼ to select one page or one of the parameters, and ◄ or ► to select the parameter value. Then press
ENT to confirm and save.
The controller can do battery test, and record 10 sets of test data (accessible only through the host). The battery test
has to be started manually, then the controller will control the rectifier output voltage, make it lower than the battery
voltage, and the battery discharge will begin. The controller will stop the test if the battery voltage reaches the Battery
Test Voltage, or the discharge time reaches Battery Test Time, or the battery capacity reaches Test End Cap.
Afterwards, it will restore the rectifier output voltage to the normal FC voltage, begin the battery charge and switch the
power system to battery auto-management.
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Chapter 4 Use Of The Controller 31
Meanwhile the test start time/voltage and end time/voltage and battery remaining capacity will be recorded. The
records can be queried through the host. During the battery test, if abnormalities occur, the controller will stop the
battery test automatically.
The value description of the parameters is listed in Table 4-10.
Table 4-10 Battery test parameters description
Parameter Range Factory setting Value description
End Test Volt 43.1V ~ 57.9 V 45.2V
5min ~ The controller will stop the test and change to FC if the battery voltage
End Test Time 300min
1440min reaches the Battery Test Voltage, or the discharge tim e reaches Battery
0.01C 10 ~ Test Tim e, or the battery capacity reaches Test End Cap
End Test Cap 0.7C10
0.95C 10
Select ‘Y’ to enable this function
Cyc Test En Y, N Y
Select ‘N’ to disable this function
01-01-00:00
Month, da y, 04-01-00:00 When the parameter Cyc Test En is set to Y, the controller will test the
Cyc Test Time
time 07-01-00:00 battery according to the 4 sets of test time
10-01-00:00
Short Test Enable Y, N Y Whether using Short Test function
Short Test Ala rm 1A ~ 100A 10A If the battery is not dis charged within the ShortTest Cycle, the controller
Short Test Period 24h ~ 8760h 720h will start a short test, whose operation time is set by the parameter
ShortTest Duration. By the end of the test, if the d ifference in the
discharge currents of batteries is bigger than the Alarm Current, the
Short Test Time 1min ~ 60min 5min
battery discharge imbalance alarm will be raised. This alarm will
automatically end after 5min of dela y. Also you can end it by confirming it
Stable Test Enable Y, N Y The stable test is conducted with constant battery current, whose value
is set through the parameter StableTest Current. If the parameter
Stable Test Current 0 ~ 9999A 9999A StableTest Enable is set to Y, and the test will be started onc e the
battery satisfies the test condition
Temperature coefficient
1. At the BAT Settings page, press ▲ or ▼ to select Temp. Comp menu. Then press ENT to confirm.
There are two pages, as shown in Figure 4-30.
2. Press ▲ or ▼ to select the parameter, and ◄ or ► to select the parameter value. Then press ENT to confirm and
save.
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
32 Chapter 4 Use Of The Controller
4.7.3 AC Settings
At the Settings page, press ▲ or ▼ to select AC Settings menu. Then press ENT to enter the AC Settings page, as
shown in Figure 4-31.
Press ▲ or ▼ to select the parameter, and ◄ or ► to select the parameter value. Then press ENT to confirm.
The value description of the parameters is listed in Table 4-12.
4.7.4 DC Settings
At the Settings page, press ▲ or ▼ to select DC Settings menu. Then press ENT to enter the DC Settings page, as
shown in Figure 4-32.
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Chapter 4 Use Of The Controller 33
Press ▲ or ▼ to select the parameter, and ◄ or ► to select the parameter value. Then press E NT to confirm.
The value description of the parameters is listed in Table 4-13.
At the Settings page, press ▲ or ▼ to select Rect Settings menu. Then press ENT to confirm.
There are three pages, as shown in Figure 4-33.
Press ▲ or ▼ to select the parameter, and ◄ or ► to select the parameter value. Then press E NT to confirm.
The value description of the parameters is listed in Table 4-14.
Table 4-14 Rectifie r parameter description
Parameter Range Factory setting Value description
‘Y’: The controller will prompt you to set rectifier position befo re the rectifier
Position En Y, N Y and controller a re powered on.
‘N’: You need not to set rectifier position
R-Posi: represented in two digits. The first digit represents the rectifier
num ber, and the last digit rep resents position number. Press ENT to select
R-Posi 1 ~ 30 - the rectifier, press ◄ or ► to change position number. When the controller
communicates with the rectifier, the green indicator on the corresponding
rectifier will blink
The rectifier over-vo ltage a larm will be ra ised when the rectifier output voltage
HVSD 56V ~ 59V 59V
is higher than the HVSD vo ltage
Default output voltage when communication interrupted. Must be lower than
Default V 48V ~ 58V 53.5V
the HVSD voltage
Walk-in On Y, N N The output soft start func tion means the rectifier voltage will rise from 0V to
Walk-in 8s ~ 128s 8s the Default Volt after the Walk-in tim e
The controller can set the DCDC Interval Start of the rec tifiers.
Interval T 0s ~ 10s 0s
Start time = rectifier address × interval time
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
34 Chapter 4 Use Of The Controller
At the Settings page, press ▲ or ▼ to select Sys Settings menu, then press ENT to confirm.
After inputting the user level password (by default: 1), three pages as shown in Figure 4-34 are displayed.
If the ‘Rest Para’ is set to ‘Y’, press ENT and prompt a page shown in Figure 4-35.
Notice:
ENT Continue
ESC Quit
Press ESC to cancel the resetting, or ENT to confirm. All the parameters will resume the default value. It is
recommended to power off or reset to perform system resetting when the c ontroller cannot work normally.
Press ▲ or ▼ to select the parameter, and ◄ or ► to select the parameter value. Then press ENT to confirm.
The value description of the parameters is listed in Table 4-15.
Table 4-15 System setting parameter description
Param eter Range Factory setting Value description
Lang Chinese, English Chinese Set according to your need
Tzone - - Set according to actual instance
Set the time according to the current actual time, regardless of
Date 2000 ~ 2099 -
whether it is a leap year or not
24V/100
24V/300 The system type of the controller has been set according to the
24V/500 actual instance before the controller is delivered with power
24V/1000 PS48300-3B/2900: system. You need not to change the value except that the
24V/SET 48V/300 controller is replaced with a new one.
System Type
48V/100 PS48600-3B/2900: After changing the type, the controller will restart and the other
48V/300 48V/500 parameters will resume the default. You need to reset and
48V/500 change some parameters according to the battery and
48V/1000 equipment configured with system
48V/SET
ComDownLoad Y, N N -
Reset PWD Y, N N Whether resetting the password to the default
Reset Para - N Whether resetting the parameters to the defaults
Op1 PWD - - The password can be 6 digits long at m ost. If it is shorter than 6
Op2 PWD - - digits, end it with a #. Use ▲ or ▼ to change the number, and ◄
or ► to m ove the cursor left or right. Press ENT to confirm. You
Adm PWD - -
should input the same number twice to complete the setting
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Chapter 4 Use Of The Controller 35
At the Settings page, press ▲ or ▼ to select Comm Settings menu. Then press ENT to enter the Communication
Settings page, as shown in Figure 4-36.
When the Comm Mode is ‘MODEM’, the CallbackTime and Phone Number should be set. Use ◄ or ► to change the
Phone Number or move the cursor left or right. And then press ENT to confirm. The communication parameter
settings list is given in Table 4-16.
Save Enable: N
Cyc Period: 168h
Rect Work: 80%
Rect Limit: 1
If you want the power system to operate under energy saving mode, set ‘Save Enable’ to ‘Y’, otherwise, set it to ‘N’.
Set ‘Cyc Period’ according to actual instance. The saving operating theory of the power system is described as
follows:
1. Operating theory
Under energy saving mode, the controller will switch off some rectifiers, the power-on rectifiers will be charged with all
loads. Each power-on rectifier works on the best efficiency to improve utilization ratio of the rectifier and save energy
consumption. After certain time (that is ‘Cyc Period’ in Figure 4-37), the power-off rectifiers will work, meanwhile the
power-on rectifiers will stop work. Two states circulate, so as to make sure that the working hours of the rectifiers in
the power system approach. If the battery c urrent and load current change, the controller will switch off some
power-on rectifiers or switch on some power-off rectifiers. In any case, the power system guarantees at least one
rectifier to work.
2. Prerequisite
If the battery is configured and load current without instantly shocks, the power system will operate under energy
saving mode, that is, ‘Save Enable’ is set to ‘Y’.
3. Advantage
Working on the best efficiency to save energy.
Balancing working hours of the rectifiers to prolong the lifetime of the rectifier.
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
36 Chapter 4 Use Of The Controller
In shutdown state, preventing rectifiers from damaged about AC inrush to reduce lightning fault.
4. Abnormal situation treatment
Switch off all the rectifiers when busbar voltage fails (DC over- voltage or low- voltage).
Switch on all the rectifiers when a rectifier alarm ( Rect Not Respond) is generated.
Switch on all the rectifiers when an AC alarm (Mains Failure) is generated.
Switch on all the rectifiers automatically when the power system has no controller or the communication is
interrupted between the rectifier and controller.
Delay implementation when the rectifier receives shutdown command, immediately execute when the rectifier
receives startup order.
The parameters of the energy saving are listed in Table 4-17.
Table 4-17 Energy saving parameters
Parameter Range Factory setting Value description
Save It can be set to ‘Y’ when the battery is configured and load current without
Y, N N
Enable instantly shocks
Cyc Tim e of rectifier under power-on state and power-o ff state, it can be set
1h ~ 8760h 48h
Period* according to actual requirement
Output capacity percentage. More rectifiers will startup to work when larger than
Rect Work 30% ~ 90% 80%
this setting percentage
Rect Limit 1 ~ 30 1 Minim um number of the rectifier
Note*: Cyc Period, Rect Work and Rect Limit are a va ilable when ‘Save Enable’ is set to ‘Y’
System Type:
48V/SET
Capacity: 600Ah
At the Fast Settings page, you can set the system type and battery capacity, as listed in Table 4-18.
Table 4-18 List of fast settings
Parameter Range Factory setting Value description
24V/100
24V/300 The system type of the controller has been set according to the actual
24V/500 instance before the controller is delivered with power system. You need
24V/1000 PS48300-3B/2900: not to change the value except that the controller is replaced with a new
System 24V/SET 48V/300 one.
Type 48V/100 PS48600-3B/2900: After changing the type, the controller will restart and the other
48V/300 48V/500 parameters will resume the default. You need to reset and change some
48V/500 parameters according to the battery and equipment configured with
48V/1000 system
48V/SET
The capacity of the total battery strings. You should set this parameter
Capacity 50Ah ~ 5000Ah 300Ah
according to the actual battery configuration
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Chapter 5 Alarm Handling 37
This chapter describes the handling of alarms, as well as the preventive maintenance of the power system during
system daily operation.
The maintenance personnel must have adequate knowledge about the power system.
Note
1. The maintenance must be conducted under the guidance of related safety regulations.
2. Only the trained personnel with adequate knowledge about the power system can maintain the inner part of the cabinet.
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
38 Chapter 5 A larm Handling
Fault estimation
The symptoms of usual rectifier faults include: green indicator (run indicator) off, yellow indicator (protection indicator)
on, yellow indicator blink, red indicator (fault indicator) on and red indicator blink.
The indicators are shown in Figure 5-1 and the indicator descriptions are given in Table 5-2.
Run indicator
Protection indicator
R48-2900U
Fault indicator
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Chapter 5 Alarm Handling 39
Fan
Front panel
Right fixing hole
2. Unplug the power cable of the fan and remove the fan.
3. Install a new fan.
4. Plug the fan power cable.
5. Put the front panel back and fasten it with the 3 screws.
Replacing rectifier
Except replacing the fan, it is recommended not to repair any other parts of the rectifier. When faulty, the rectifier
should be returned to the manufacturer and replaced, not repaired. See the following procedures to replace the
rectifier:
1. Take a new rectifier and check it for any damage from transport.
2. Pull out the faulty rectifier from the rack by grabbing its handle.
Be careful with the rectifier just pulled out from the power system, as it could be very hot due to long-term operation.
Do not let it slip away and get damaged.
3. By holding the rectifier handle, push the new rectifier into the slot just vacated and make sure the connection is
good.
After a brief delay, the green indicator of the rectifier will turn on and the fan will start running.
4. Check whether the new rectifier works normally.
You should make sure that:
1) The controller recognizes the new rectifier.
2) The new rectifier shares current with other rectifiers.
3) When this new rectifier is pulled out, there is a corresponding alarm and the controller displays the alarm.
If the new rectifier passes all the above tests, the replacement is a success.
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
40 Chapter 5 A larm Handling
5. Push the handle back into the front panel to fix the rectifier with the positioning pin.
Fault estimation
The fault phenomena of the controller are LCD failure or displayed contents incorrect. You should take the following
procedures to estimate fault causes:
1. Loosen the three fixing screws on the controller to remove the cover plate, as shown in Figure 5-3.
LCD
2. Estimate fault causes according to the indicator status of the PCB board, as listed in Table 5-3.
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Chapter 5 Alarm Handling 41
The indic ators and terminals of the PCB board are shown in Figure 5-4.
RS232 Temp
9 6
5 1
J1 J2 J3 J4 J5 J6 J7 J8
J9
J10
Replacement
Note
Care should be taken when replacing components of the controller. Unplugging terminals optionally may result in system shut
down. Carry out the replacement sequentially according to the following procedures.
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
42 Appendix 1 Technic al Data
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Appendix 1 Technical Data 43
Parameter
Parameter Description
category
The rectifiers can work in parallel and share the current. The
Load sharing unbalance is better than ± 5% rated output current. Test current range:
10% ~ 100% rated current
The rectifier can output max. power of 2900W with input voltage of
Derate by input (a t 45°C) 176Vac ~ 290Vac.
Rectifiers output 20% power with input voltage of 85Vac
The rectifier provides over-voltage hardware and software protection.
The hardware protection point is 59.5V ± 0 .5V, and it requires manual
resetting to restore operation. The software protection point is between
56V and 59V (0.5V above output voltage, 59 V by default), and can be
set through the controller
There are two software protection modes, which can be selected
through the software at the host:
1. Lock out at the first over-voltage
Once the output voltage reaches protection point, the rectifier will shut
Over-voltage protection off and hold that state. it requires manual resetting to restore the
Rectifier operation
2. Lock out at the second over-voltage
When the output voltage reaches the software protection point, the
rectifier will shutdown, and restart automatically after 5 seconds. If the
over-voltage happens again within a set time (default: 5min.
Configurable through controller), the rectifier will shut off and hold tha t
state. It requires manual resetting to restore the operation
Manual resetting: Resetting can be done manually through the
controller, or by removing the rectifier from system
Output voltage can rise slowly upon rectifier start up. The rise time is
Output dela y
configurable
Fan speed adjustable Rectifier fan speed can be set to half or full speed
Temperature below 40°C, outputs full power: 2900W
Temperature above 40°C, there will be linear derating, that is:
Temperature derating At 45°C, output power is 2610W
At 55°C, output power is 1450W
At 60°C, output power is 0W
Conducted emission
Class A EN55022
Radiated emission
Immunity to EFT Level 4 EN61000-4-4
EMC Immunity to ESD Level 3 EN61000-4-2
Immunity to Surges Level 4 EN61000-4-5
Immunity to radiation Level 2 EN61000-4-3
Immunity to conduction Level 2 EN61000-4-6
The AC input side can withstand five times of sim ulated lightning
voltage of 5kV at 10/700µs, for the positive and negative polarities
respectively. It can withstand five times of simulated lightning surge
At AC side current of 20 kA at 8/20µs, fo r the positive and negative polarities
Lightning
respectively. The test interval is not smaller than 1 minute. It can also
protection features
withstand one event of sim ulated lightning surge current o f 40kA at
8/20µs
The DC side can withstand one event of simulated lightning current of
At DC side
10kA at 8/20µs
Acoustic noise ≤ 55dB (A) (When the ambient temperature is lower than25℃)
At temperature of 15°C ~ 35°C and relative humidity not b igger than
Others 90%RH, apply a test voltage of 500Vdc. The insulation res istances
Insulation resistance
between AC circuit and earth, DC circuit and earth, and AC and DC
circuits are all not less than 10MΩ
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
44 Appendix 1 Technic al Data
Param eter
Parameter Description
category
(Remove the SPD, controller and rec tifiers from the power system
before the test.)
AC circuit to earth: 50Hz, 2500Vac
DC c ircuit to earth: 50Hz, 1000Vac
Insulation strength Assistant circuit (not directly connected to the host circuit): 50Hz,
Others
500Vac
AC to DC circuits: 50Hz, 3000Vac
For all the three tests above, there should be no breakdown or
flashover within 1min, with lea kage current not bigger than 10mA
MTBF 200000hr
600 (W) × 400 (D) × 1600 (H)
Dimensions Cabinet
or 600 (W) × 400 (D) × 2000 (H, with heightening base)
(mm)
Rectifier 132.5 (H) × 88 (W) × 287 (D)
Mechanical
Cabinet (including PS48300-3B/2900 ≤ 95
Weight (kg) rectifiers) PS48600-3B/2900 ≤ 105
Rectifier ≤ 3.5
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Appendix 2 Engineering Diagram 45
600
99 146 159
173 160
434 464
1600
600
99 146
173 160
433 464
1600
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
46 Appendix 2 Engineering Diagram
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Appendix 3 Parameter Setting Of The Controller 47
This chapter gives the description of the controller parameter setting. The detailed information of parameter setting
and operating method are given in Chapter 4 Use Of The Controller. See 4.7.1 Alarm Settings for alarm setting
method.
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
48 Appendix 3 Parameter Setting Of The Controller
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Appendix 3 Parameter Setting Of The Controller 49
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
50 Appendix 3 Parameter Setting Of The Controller
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Appendix 4 Menu Structure Of The Controller 51
Main Menu
Note: Position En Y
R-Posi
1. 'Status' information can be queried only. Refer to
Figure 4 for system information. HVSD 59V
Operator level authority is compatible with user level Rectifier Default V 53.5V
2.
authority. Administrator level authority is compatible Settings Walk-in On N
with operator level authority. Walk-in 8s
3. Parameters on the right side are default values set Interval T 0s
before delivery. AC OverV On N
ACCurrLim 30A
Lang Chinese
Tzone
Date
PS48300-3B/2900: 48V/300
System System Type PS48600-3B/2900: 48V/500
Settings ComDownLoad N
Reset PWD N
Reset Para N
Change Password
Address 1
Comm Mode RS232
Comm unication BaudRate 9600bps
Settings IP/Subnet/Gate
CallbackTime
Phone Number
Save Enable N
Cyc Period 48h
Energy Saving
Rect Work 80%
Rect Limit 1
Capacity 300Ah
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
52 Appendix 4 Menu Structure Of The Controller
Center Temp 25 ℃
Coeff 72mv/ ℃
Temp Temp None
Comp Batt T H2 50 ℃
Batt T H1 50 ℃
Batt T L1 0℃
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Appendix 5 Schematic Diagram 53
V1 FUD1
mains input Ⅰ PE FUD2
W1
FUD3
QFA2
U2
V2 FC FUDn NPL
PA1
mains input Ⅱ Monitor Module
W2 M522S QFD1
N1、 2
QFDn
QFA5 can
H1
QFA1
U H2
V
QFDn+1
mains input
W H3
QFDn+2
N KMD2
PL
LLVD Contactor
QFDn+m
KMD1
H1 2
BLVD Contactor
RB1
Rectifer
RB1 FUB1 Battery 1
SPD
FUB2 Battery 2
AC Output SPD 11D RB2
QFA4
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Appendix 5 Schematic Diagram 54
V1 FUD1
mains inputⅠ PE FUD2
W1
FUD3
QFA2
U2
V2 FC FUDn NPL
Monitor Module PA1
mains inputⅡ
W2
M522S Q FD1
N
Q FDn
QFA5
can
H1
QFA1
U
H2
V
QFDn+1
mains input
W
QFDn+2
H2
N KM D2
PL
LLVD Contactor
H2 QFDn+m
H8 KMD1
H9
BLVD Contactor
Rectifer
QFA3 Battery 1
Option RB1 FUB1
SP D
AC Ou tput FUB2 Bat tery 2
SPD11D RB2
QFA4
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Appendix 6 Wiring Diagram 55
DC unit
4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
QFD1 QFD2 QFD3 QFD4 QFD5 QFD6 F UD1 FUD2 FUD3 FUD4 FUD5 QFD1 QFD2 QFD3 QFD4 QFD5 QFD6 QFD7
6 6
24-J11-10
24-J11-11
24-J12-10
24-J12-11
24-J12-12
24-J11-12
24-J11-7
24-J11-8
24-J11-9
24-J12-1
24-J12-3
24-J12-4
24-J12-5
24-J12-2
24-J11-5 24-J11-6
24-J12-6
24-J12-7
24-J12-8
24-J12-9
W10 W10
Battery 1 Battery 2
1 1
1 2
FUB1 FUB2 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1
2 2
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
W10 24-J11-1 24-J11-3
1 1
3 50
RB1 RB2 WC4C5Z Configuration
24-J11-2 2 24-J11-4 2 24-J10-3 24-J10-2
W08 24-J10-4 1 22 W08 2 23
2 KMD1 W08 24-J10-1 1 KMD2
26
DC-
1 W07
To BUS-
24-J8-1
28
BUS+
24-J8-2
Casing W06_3 1 2
3
W07
25-OV
25
SPD
SPD11D W25
Controller PE 0V -48V
W07 W07W07
27
28-2
27-2
28-1
26-1
27-1 BUS-
RS232
T emp
W25 Rectifier output negative
busbar(t op view )
9 6
J1 J2 J3 J4 J5 5 1 J7 J8 Optional
2
47-12
47-11
J6 25--48v W25
29-9
29-6
W09 W09
24-J8-3 W07
1
J9
J11 J12
31 1
32 2
50-1
50-2
14-1
10-1
11-1
12-1
13-1
15-1
L CD
16-1
17-1
18-1
19-1
20-1
21-1
WC4C5Z
3-1
3-2
1-1
2-1
9-1
4-1
5-1
6-1
7-1
8-1
Configuratin
液晶
10
W10 W11
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Appendix 6 Wiring Diagram 56
AC unit
42 43 44 45 46 W01
46-2/45-2
46-4/45-4
46-6/45-6
80 81 82 83 84 85 86 87 88 89 90 91 QF4 QF3 QF2 QF1 QF0
86-1
87-1
88-1
48-3
QF16 QF15 QF14 QF13 QF12 QF11 QF10 QF9 QF8 QF7 QF6 QF5
AC output MCB
Main s 2 input Mains 1 input Mains 1 input
U2 V2 W2 U1 V1 W1 U1 V1 W1 L1 L2 L3 PE
47-L1
47-L2
47-L3
1 3 5 1 3 5 1 3 5
47
1 1 1 1 1 1 1 1 1 1 1 1 1 3 5 1 SPD
2 4 6 2 4 6 2 4 6 N
11 12
47-L1
47-L2
47-L3
47-L1
47-L2
47-L3
2 2 2 2 2 2 2 2 2 2 2 2 2 4 6 2
44-2
44-4
44-6
29-2/34-2
35-2/40-2
45-2
45-4
45-6
24-J9-6
24-J9-5
41-4
34-L
33-L
32-L
31-L
30-L
35-L
36-L
37-L
38-L
39-L
40-L
29-L
1 1 1 1 1 1 1
29 30 31 32 33 34 48 41
H1 H2 H3 H4 H5 H6 PE N
24-J9-1
W09 6 6 6 6 6 6
24-J9-2
9 9 9 9 9 9 W06_1 Door
10 10 10 10 10 10 1 2
1 3
Zero line 4
2
W04 W04 W04 W04 W04 W04 47-PE(16mm^2)
Cabinet
P PE P PE P PE P PE P PE P PE
47-N
47-N W03 3
N N N N N N W02
W05 W05 W05 W05 W05 W05 (6mm^2)
L 80-2 L 81-2 L 82-2 L 83-2 L 84-2 L 85-2 W02
W05 AC i nstallation boar d
50A Rectifier
subrack2
1 1 1 1 1 1
35 36 37 38 39 40
H7 H8 H9 H10 H11 H12
6 6 6 6 6 6
9 9 9 9 9 9
10 10 10 10 10 10
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual
Appendix 7 Glossary 57
Appendix 7 Glossary
PS48300-3B/2900-X8 ~ X11, PS48600-3B/2900-X8 ~ X11 Series Power Supply System User Manual