S-TERM-F
TP/FT-10 Network Terminator
DESCRIPTION
Free Topology Transceiver (FTT)/ Linked Power Transceiver (LPT) networks require termination to provide reliable and robust network communication. Depending on the network topology, one or more S-TERM-F Network Terminators may be required, see Figures 1 5. The S-TERM-F has been designed to be a high performance and low cost TP/FT-10 (FTT/LPT) network terminator that can accommodate the most rigorous installation challenges. A shrink tube protests the termination circuitry from environmental conditions allowing installation any where throughout a network. The S-TERM-F has pre-spliced wires that can be directly connected for easy and fast single and double termination. The quickest method to attach an S-TERM-F is at the network terminals of a controller as shown in Figure 7 and 8. Materials and components have been selected that are rated for UL 94-V0. The S-TERM-F is manufactured with no leaded materials and is CE Mark compliant.
FEATURES
For use on ALL Free Topology TP/FT-10 channels (FTT/LPT) Single and Double Termination capability in one package Small size for limited enclosure space High performance components at low cost Pre-spliced flying leads for fast installation CE Mark
NETWORK TERMINATIONS
TERMINATION
TERMINATION
Figure 1 Single Terminated Bus Topology
TERMINATION
Figure 4 Single Terminated Loop Topology
TERMINATION
Figure 2 Single Terminated Star Topology
TERMINATION
TERMINATION
Figure 5 Double Terminated Bus Topology (Used for very long and to maximumize cable distance)
Figure 3 Single Terminated Mixed Topology
SPECIFICATIONS CONTACT
SMART CONTROLS
Office: 10000 St. Clair Avenue Fairview Heights, IL 62208 U.S.A. Phone: 618-394-0300 Fax: 618-394-1575 E-mail: [email protected] Web site: www.smartcontrols.com
Smart Controls is a trademark of Smart Controls, LLC. SMART CONTROLS, LLC reserves the right to make changes without further notice to this product for improvements in design and reliability. SMART CONTROLS, LLC does not assume any liability arising out of the application or use of this product; neither does it convey any license under its patent rights of others.
1.8" (45.7mm) Smart Controls BR SINGLE S-TERM-F YE TP/FT-10 DOUBLE Network OR Terminator Made in U.S.A. 0.5" (12.7mm)
General Termination for Transceiver Types: TP/FT-10 (FTT/LPT Networks) Connections: Flying leads Packaging and Wiring: Components rated for UL94-V0 Power Operating Power: None Maximum Applied Voltage: 63 WVDC Environmental Operating Temperature: -40 C to +85 C, -40 F to 185 F Storage Temperature: -40 C to +85 C, -40 F to 185 F Relative Humidity: 5 to 95% (non-condensing, 25C) Warranty Period: 2 Years (Limited)
DIMENSIONS
3.0" (76.2mm) BROWN YELLOW ORANGE
(20.3mm) 0.8"
Document Number: 37-0246, ver. 1.0.0
Figure 6 S-TERM-F Dimensions and Wire Color
Wire spliced from end and insulation has not been removed
WIRING Single Terminated Network
Use BROWN and YELLOW leads on S-TERM-F for Single Termination.
To other controllers and devices on TP/FT-10 Network.
Install
NET A NET B +20V UI1 UI2 UI3 GND UI4 NET A NET B
Power/Service 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
GND PWR GND PWR GND UO1 GND UO2 GND UO3 UO4 GND UO5 UO6 DO1 DO2 DO3 DO4 DO5 DO6
1 2 3 4 5 6 7 8
SMART C ONTROLS
+20V UI1 UI2 UI3 GND UI4 Universal Inputs UI5 UI6 GND UI7 UI8 UI9 GND UI10 UI11 UI12
GND UO1 GND Universal Outputs UO2 GND UO3 UO4 GND UO5 UO6 DO1 Digitial Outputs DO2 DO3 DO4 DO5 DO6
Smart Controls BR SINGLE S-TERM-F YE TP/FT-10 DOUBLE Network OR Terminator Made in U.S.A.
UI5 UI6 GND UI7 UI8 UI9 GND UI10 UI11 UI12
9 10 11 12 13 14 15 16 17 18
Muiltifunctional I/O Module with RTC
EC240
Place a wire nut on unused ORANGE lead.
(wire nut not provided with S-TERM-F)
Figure 7 S-TERM-F Single Termination Wiring
Double Terminated Network
Use BROWN and ORANGE leads on S-TERM-F for Double Termination.
Install
NET A NET B +20V UI1 UI2 UI3 GND UI4 NET A NET B
First and last controller or device on TP/FT-10 Bus Network.
Power/Service 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
GND PWR GND PWR GND UO1 GND UO2 GND NET A NET B +20V UI1 UI2 UI3 GND UI4
Install
NET A NET B
Power/Service 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
GND PWR GND PWR GND UO1 GND UO2 GND UO3 UO4 GND UO5 UO6 DO1 DO2 DO3 DO4 DO5 DO6
1 2 3 4 5 6 7 8
1 2
SMART C ONTROLS
SMART C ONTROLS
+20V UI1 UI2 UI3 GND UI4 Universal Inputs UI5 UI6 GND UI7 UI8 UI9 GND UI10 UI11 UI12
GND UO1 GND Universal Outputs UO2 GND UO3 UO4 GND
+20V UI1 UI2 UI3 GND UI4 Universal Inputs UI5 UI6 GND UI7 UI8 UI9 GND UI10 UI11 UI12
GND UO1 GND Universal Outputs UO2 GND UO3 UO4 GND
3 4 5 6 7 8
Smart Controls BR SINGLE S-TERM-F YE TP/FT-10 DOUBLE Network OR Terminator Made in U.S.A.
UI5 UI6 GND UI7 UI8 UI9 GND UI10 UI11 UI12
Smart Controls BR SINGLE S-TERM-F YE TP/FT-10 DOUBLE Network OR Terminator Made in U.S.A.
UO3 UO4 GND UO5 UO6 DO1 DO2 DO3 DO4 DO5 DO6
UI5 UI6 GND UI7 UI8 UI9 GND UI10 UI11 UI12
9 10 11 12 13 14 15 16 17 18
9 10 11 12 13 14 15 16 17 18
Muiltifunctional I/O Module with RTC
Muiltifunctional I/O Module with RTC
UO5 UO6 DO1 Digitial Outputs DO2 DO3 DO4 DO5 DO6
UO5 UO6 DO1 Digitial Outputs DO2 DO3 DO4 DO5 DO6
Place a wire nut on unused YELLOW lead.
(wire nut not provided with S-TERM-F)
Figure 8 S-TERM-F Double Termination Wiring
EC240
EC240