GENERAL CATALOGUE
HCAC-CA-CHILLER202201
Design and specifications are subject to change without notice. Pictures and diagrams are for reference only and are subject to change without notice.
All rights reserved by Qingdao Hisense HVAC Equipment Co., Ltd.
MANUFACTURING BASE
Qingdao Hisense HVAC Equipment Co., Ltd. is a wholly owned subsidiary of Qingdao Hisense
Hitachi Air-conditioning Systems Co., Ltd., who is a joint-venture of Hisense and Hitachi (changed to
Johnson Control Hitachi in 2015) and was established in 2003. It integrates technology development
for commercial and residential CAC, product manufacturing, marketing and service as a whole.
With solid technical innovation strength, Hisense VRF has participated in the formulation and revision
of 25 national standards, industry standards and association standards, and has 420 authorized
patents in the field of CAC and heat pump products. Since 2008, 58 technologies have reached the
advanced level through authorized certification. Now Hisense VRF has become a leading CAC
enterprise in China.
Note: The above data is valid before Dec. 31th, 2020.
266,000 m 2
40+ 6,000,000units/year 16,700 m /70+ 2
02
01
03
SINCE 1969
Hisense Group is a well-known large-scale electronic information industry group company.
Based on technology and focusing on innovation-oriented culture, its scientific and efficient
technological innovation system makes Hisense always be at the forefront of the counterparts.
Hisense brand family has continued to grow with Toshiba, Gorenje and ASKO. Multi-brand
operations will be defined according to Group's Strategy Management Department.
CONTENTS
CEILING
SUSPENDED AHU
FAN
AIR 87 COIL UNIT
HANDLING UNIT
AIR-COOLED WATER-COOLED 96
MODULAR CHILLER
AIR-COOLED
SCREW CHILLER
65
SCREW CHILLER
03 35 49
AIR-COOLED MODULAR CHILLER
HIGH QUALITY
Series Components strictly screened
AIR-COOLED MODULAR CHILLER
The new generation of air-cooled modular chiller Hi-Mod series has a Smart Dual System, Flexible Operation
series of products with full function and various specifications, including
The innovative dual-system V-shaped high efficiency fin-type heat exchangers are
standard type A series, low temperature and strong heating type E
applied in Hi-Mod series, and the two systems are independent, which could solve the
series and ultra-low temperature and strong heating type H series.
problems related to the dependency of two-system operation.
Modules of the same type can be connected freely, meeting the
customized demands.
High-accuracy Electronic Expansion Valve
High-accuracy electronic expansion valves are used for heating and cooling to
dynamically control the opening of the valve according to the changes of environment
and water temperature, minimizing the fluctuations of system pressure and
temperature and ensuring stable operation.
The system has dynamic over-heat control function to accurately control the flow of
refrigerant and ensures no remaining liquid refrigerant after evaporation.
Control accurately with 480-step control.
Water Outlet
Water Inlet
Refrigerant Outlet
04 09 11 17
High Quality High Flexibility Hi-Mod A Series Hi-Mod H Series
05 10 14 25 Refrigerant Inlet
05
03 04
AIR-COOLED MODULAR CHILLER
The control system can record the working condition and accumulated working time of each compressor, and balance the
allocation of the running time of each compressor intelligently. The compressor with short accumulated running time is firstly System On
System On
started when loading, while the compressor with long accumulated running time is firstly stopped when unloading, so as to
System Off System Off
extend the overall system's lifetime. 9.5 ℃ 9.5 ℃
7℃ 7℃
Intelligent Energy Regulation Conventional Energy Regulation
OFF ON OFF ON OFF ON OFF ON
Time
1001H Balance
1000H
Backup Operation
Independent refrigerant loops in each module can realize emergency standby operation.
Anti Liquid Slugging Technology
The modules in one multi-module unit can realize emergency standby operation.
There are electrical heating elements covering the crankcase of the compressor, which makes sure that the compressor is in
a good lubrication state when standby in winter. The liquid refrigerant can be evaporated fully, preventing liquid slugging to
the compressor on starting.
Compressor
Bottom Heating
Refrigerant separated from OFF ON
the lubrication oil fully ON
OFF
05 06
AIR-COOLED MODULAR CHILLER
The defrosting time is more accurate thanks to the innovative dual heat exchanger system.
Responding to Harsh Environment
The left and right coils of the heat exchanger are respectively equipped with temperature sensors, and the defrosting can
In case of heavy snow cover, thick frost layer formed due to
be accurately controlled according to the sensor values together with ambient temperature and running time.
high humidity in the environment or ice formed due to severe Heavy Frost and
Defrosting time can be automatically adjusted, avoiding ineffective defrosting and prolonging the defrosting interval. The Ice Covered Defrost
low temperature, the defrosting can be performed compulsively
efficiency under heating is largely improved. Compulsively
by human, ensuring the lasting and reliable heating operation.
Rotational defrosting can be achieved for module combination unit, fully guaranteeing the heating effect.
st
nt Defro
Intellige
System Temp Various protections for compressors, fan motor, water flow, high and low refrigerant pressure, water temp, power supply,
current and communicaition are fully considered and designed ahead.
Water flow switch is standard part, and there are multiple anti-freeze protections, protecting against freezing and setting
Running Time
off.
Anti-freezing function will be automatically conducted according to the ambient temperature and inlet and outlet water
Time/s …… temperature, to prevent the water system from freezing during standby state.
There is a minimum operation time for the compressor, to prevent the compressor from damage due to frequent starts
and stops.
Compressor
Overload Fan Motor
Protection Overheat
High/low Protection
Consecutive Heating Ensuring High Efficient Operation Pressure
Protection Power
The two systems of each unit are independent of each other. When one system defrosts, the other system can work Supply
normally, effectively reducing the fluctuation of water temperature and improving the users' comfort. Protection
Insufficient
When the module-combined units work, the control system will balance the defrosting time of each module, so as to prevent Water Flow
every module from entering defrosting at the same time. The modules without defrosting will continue to work normally, Protection
On/Off
ensuring a consecutive heating. Frequently
Protection
Automatic
Antifreezing
Protection
Low/high
Outlet Water
Temperature
External Protection
Linkage
Hot water Protection
Communication
Environment Protection
Heating Defrosting Heating Heating Temperature Overhigh
Limit of Cooling Exhaust
Over/Under Temperature
Current Protection
Protection
07 08
AIR-COOLED MODULAR CHILLER
Intelligent Controller
Module Design, More Convenient for Installation and Transportation
Comprehensive information display, easy to understand
The main and sub units are designed without difference, and any unit can be set as the main unit, which makes the
combination and installation more convenient.
Mode setting
Unit with different specifications of the same series can be connected freely to achieving large capacity output, and one
Inlet and outlet water temperature setting
controller can control up to 16 units, which is convenient to satisfy the various capacity cases.
Compressor, pump, heater and defrost state control
Malfunction information display
Time setting
Schedule setting
Central control
Phase II Max. 16 Units Dedicated Controller for Hi-Mod
Phase II
HSXE-FA01M
Max. 16 Units
Phase I
Phase I
Connected to BMS
RS-485 signal interface is built in the controller, through which the unit can be connected to BMS. The interconnection of
centralized control system realizes the networking group control and remote control.
* Hi-Mod A series has two base module, which can achieving capacity combination between 65kW and 2080kW.
Hi-Mod E series has two base module, which can achieving capacity combination between 65kW and 2080kW.
Hi-Mod H series has two base module, which can achieving heating capacity combination between 72kW and 2576kW.
The integral structure design effectively reduces the unit volume and occupied area, greatly saving space and cost of
installation.
The minimum occupied area is only 1.89m2, decreased by more than 42% compared with other traditional modules in the
industry.
5 5
Occupied Area: m2
Occupied Area: m2
09 10
AIR-COOLED MODULAR CHILLER
Hi-Mod A series adopts the high efficient hermetic scroll compressor, ensuring an
efficient, reliable and low noise operation. What's more, the scroll compressor has small
Standard type
Optimized design of scroll plate and seal ring One-way discharge valve is built in, avoiding the backflow
Hi-Mod A series can realize free combination guarantee small leakage and thereby greatly of refrigerant.
between 16 modules, and the maximum increasing the volume
combined capacity is 2080kW, which can be efficiency.
The bearing capacity of the drive bearing is enhanced to
applied in large space.
make operation more stable and reliable.
The bearing capacity of main bearing seat is
strengthened and the design is more stable and
High-efficiency motor makes compressor more efficient
reliable.
High Efficient Scroll Compressor and prolongs the compressor's lifetime.
Efficiency, reliability and strong capacity output
Environment-friendly Refrigerant R410A The bottom bearing plate with 4 screws makes Large oil tank can be precharged with more condensed
bearing more stable. oil to ensure that the compressor is lubricated reliably in
all working conditions.
50 50
40 45
11 12
AIR-COOLED MODULAR CHILLER
Heating Capacity kW 70 140 210 280 350 420 490 560 630 700 770 840 910 980 1050 1120
Water Flow m 3/h 11.2 22.4 33.6 44.8 56.0 67.2 78.4 89.6 100.8 112.0 123.2 134.4 145.6 156.8 168.0 179.2
Model HFRE-130W/A2F 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Cooling Capacity kW 130 260 390 520 650 780 910 1040 1170 1300 1430 1560 1690 1820 1950 2080
Heating Capacity kW 140 280 420 560 700 840 980 1120 1260 1400 1540 1680 1820 1960 2100 2240
EVI Compression Technology, Strong Heating Under Low Temperature
Water Flow m 3/h 22.4 44.8 67.2 89.6 112.0 134.4 156.8 179.2 201.6 224.0 246.4 268.8 291.2 313.6 336.0 358.4
Note:
EVI compression technology overcomes the shortcomings of traditional air source heat pump units under low ambient
1. Rated cooling capacity and heating capacity are tested in the following conditions: temperature, such as capacity decreasing and low efficiency, greatly enhancing the low temperature heating capacity and
Cooling conditions: outdoor ambient temperature is 35℃ DB, and water outlet temperature is 7℃ under the rated water flow. improving the capacity and efficiency of the whole system.
Heating conditions: outdoor ambient temperature is 7℃ DB/6℃ WB, and water outlet temperature is 45℃ under the rated water flow.
2. During the actual application, 6% loss of the capacity should be considered due to the pipeline, water pumps, various valves, dirt and so on.
3. Hi-Mod A series should not work at the temperature lower than 15℃ when cooling and lower than -15℃ when heating.
Heating capacity is increased by 7%~20%.
4. The specifications subject to change without notice in accordance with our policy of continuous product improvement. The highest outlet water temperature is 55℃.
5. The above noise values are measured in the anechoic chamber.
13 14
AIR-COOLED MODULAR CHILLER
The system has great performance under low ambient temperature. The Power Input of Heating (-12℃) kW 17.3 35.7
nominal heating efficiency can separately reach to 2.6 (HFRE-65W/E2F) and Cooling Capacity kW 65.0 130.0
2.52 (HFRE-130W/E2F). Meanwhile, it adopts environment-friendly Power Input of Cooling kW 19.0 38.1
refrigerant R410A, which is non-toxic to human and doesn't damage the COPc/COPh (-12℃) kW/kW 3.42/2.60 3.41/2.52
Noise dB(A) 68 78
Cooling operation temperature range 15~48℃, heating operation temperature range:-26~25℃.
Water Flow m 3/h 11.2 22.4
The cooled water outlet temperature is 5~15℃, while heated outlet temperature is 35~55℃. It greatly satisfies the various
Water Resistance kPa 50 50
requirements.
Water Inlet/Outlet Pipe Diameter DN DN65 Flange Connection DN65 Flange Connection
Max. Pressure Resistance of MPa 1.0 1.0
Water-side Heat Exchanger
Running Mode — Automatic Operation Controlled By Microcomputer Automatic Operation Controlled By Microcomputer
50 50
Compressor Type — Hermetic Scroll Compressor Hermetic Scroll Compressor
40 45
Quantity of Compressors PC 2 2
30 40 Type — Axial Flow with Low-noise Large Blades Axial Flow with Low-noise Large Blades
Cooling operation 35 Water temp Fan Air Volume m 3/h 26000 47000
20
30 35~55℃
temperature when cooling Quantity PC 2 2
10 15~48℃
25 Type — R410A R410A
0 Refrigerant
20 Precharged Amount kg 2×7.0 2×10.5
-10 Length mm 2200 2300
15
-20 Heating operation Water temp Dimensions Width mm 860 1100
10
-30 temperature when heating Height mm 1910 2200
-26~25℃ 5
5~15℃ Net Weight kg 665 1030
Weight
Running Weight kg 710 1130
Cooling Capacity kW 65 130 195 260 325 390 455 520 585 650 715 780 845 910 975 1040
60
Heating Capacity* kW 70 140 210 280 350 420 490 560 630 700 770 840 910 980 1050 1120
55
Outlet Water Temp/℃
Water Flow m /h
3 11.2 22.4 33.6 44.8 56.0 67.2 78.4 89.6 100.8 112.0 123.2 134.4 145.6 156.8 168.0 179.2
Working Range
50
Hi-Mod E Model HFRE-130W/E2F 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
45 Comparision between
Cooling Capacity kW 130 260 390 520 650 780 910 1040 1170 1300 1430 1560 1690 1820 1950 2080
Hi-Mod E and conventional Heating Capacity* 140 280 420 560 700 840 980 1120 1260 1400 1540 1680 1820 1960 2100 2240
kW
40
Conventional heat pump products Water Flow m3/h 22.4 44.8 67.2 89.6 112.0 134.4 156.8 179.2 201.6 224.0 246.4 268.8 291.2 313.6 336.0 358.4
35 Heat Pump
Note:
30 1. Rated cooling capacity and heating capacity are tested in the following conditions:
-30 -20 -10 0 10 20 30 Cooling conditions: outdoor ambient temperature is 35℃ DB, and water outlet temperature is 7℃ under the rated water flow.
Heating conditions (7℃): outdoor ambient temperature is 7℃ DB/6℃ WB, and water outlet temperature is 45℃ under the rated water flow.
Ambient Temp/℃ Heating conditions (-12℃): outdoor ambient temperature is -12℃ DB/-14℃ WB, and water outlet temperature is 41℃ under the rated water flow.
2. During the actual application, 6% loss of the capacity should be considered due to the pipeline, water pumps, various valves, dirt and so on.
3. Hi-Mod E series should not work at the temperature lower than 15℃ when cooling and lower than -26℃ when heating.
4. The specifications subject to change without notice in accordance with our policy of continuous product improvement.
5. The heat capacity noted with* is tested when outdoor ambient temperature is 7℃ DB/6℃ WB,
and water outlet temperature is 45℃ under the rated water flow.
15 16
AIR-COOLED MODULAR CHILLER
80
Heat Capacity/kW
70
Series 60 Up
50
15%
Ultra-low Temperature and Strong Heating Type 40
30
20
Low temp unit
10
Conventional
The highest outlet water temperature as high as 60℃, which 0 unit
better meets the water temp. demand of heat radiator. -30 -25 -20 -15 -10 -5 0 5 10
Heating operation temperature range: -26~25℃, cooling operation temperature range: 15~48℃.
Ultra low temperature and strong heating
The heated water outlet temperature is 35~60℃, and the cooled water outlet temperature is 5~15℃.
Strong capacity under extreme low ambient temperature
With wide range of water temperature, it covers hot water temperature needs of the old cast iron radiator, new
Outlet water temperature as high as 60℃
copper and aluminum composite radiator, fan coil, floor heating and other heating equipments.
EVI Compressor
Efficiency and reliable
50 50
40 45
30 40
Under the ambient temp -12℃, the heating capacity with 41℃ hot water outlet can reach more than 62.5% of the rated
heating capacity.
Under the ambient temp -20℃, when the temp of hot water outlet is 45℃, the COP of the system can exceed 2.0.
Compared with the conventional R410A units on the market, Hi-Mod H series can increase the heat capacity as high as
15% at ultra low temperature.
Old Type Radiator New Type Radiator Fan Coil Floor Heating
(Hot water 50~65℃) (Hot water 45~55℃) (Hot water 40~50℃) (Hot water 35~45℃)
17 18
AIR-COOLED MODULAR CHILLER
Max. Power Consumption kW 30.0 66.0 11 1.337 0.799 1.269 0.884 1.201 0.956 1.133 1.020 1.042 1.102 0.952 1.170
Max. Current A 54.0 116.0 13 1.410 0.807 1.338 0.893 1.267 0.966 1.195 1.030 1.099 1.112 1.004 1.181
Single Unit Capacity Regulation — 0-50%-100% 0-50%-100% 15 1.475 0.815 1.400 0.901 1.325 0.975 1.250 1.040 1.150 1.123 1.050 1.193
Power Supply — AC 3Φ, 380V/50Hz AC 3Φ, 380V/50Hz
Note:The above correction factors are applied for these models:HFRE-65W/A2F, HFRE-130W/A2F, HFRE-65W/E2F, HFRE-130W/E2F, HFRE-70W/H1F,
Noise dB(A) 68 76 HFRE-150W/H1F.
Water Flow m 3/h 11.35 25.80
Fan Air Volume m 3/h 26000 60000 40 0.525 0.836 0.618 0.862 0.721 0.888 0.838 0.910 1.030 0.950 1.174 0.990 1.236 1.014
Quantity PC 2 4 45 0.510 0.900 0.600 0.919 0.700 0.938 0.814 0.960 1.000 1.000 1.140 1.043 1.200 1.074
Type — R410A R410A
Refrigerant 50 — — 0.582 0.983 0.679 1.003 0.790 1.025 0.970 1.055 1.106 1.105 1.164 1.134
Precharged Amount kg 2×8.5 2×16.0
Note:The above correction factors are applied for these models:HFRE-65W/A2F, HFRE-130W/A2F.
Length mm 2200 2200
40 0.464 0.851 0.524 0.859 0.595 0.867 0.646 0.871 0.771 0.894 0.861 0.907 1.030 0.939 1.163 0.966 1.260 0.989
Combined Capacity Parameter List
45 0.451 0.905 0.511 0.914 0.582 0.923 0.632 0.929 0.752 0.952 0.838 0.966 1.000 1.000 1.129 1.026 1.222 1.049
Model HFRE-70W/H1F 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
50 — — — — 0.563 1.001 0.611 1.008 0.726 1.025 0.809 1.034 0.965 1.060 1.089 1.086 1.179 1.108
Cooling Capacity kW 66 132 198 264 330 396 462 528 594 660 726 792 858 924 990 1056
Heating Capacity* kW 72 144 216 288 360 432 504 576 648 720 792 864 936 1008 1080 1152 55 — — — — — — — — 0.703 1.086 0.781 1.094 0.930 1.119 1.049 1.143 1.136 1.164
Water Flow m /h
3
11.36 22.72 34.08 45.44 56.80 68.16 79.52 90.88 102.24 113.60 124.96 136.32 147.68 159.04 170.40 181.76 Note:The above correction factors are applied for HFRE-65W/E2F.
19 20
AIR-COOLED MODULAR CHILLER
Environment Temperature℃
Water Outlet
-25 -20 -15 -12 -5 0 7 15 21
Temperature HFRE-130W/A2F
℃ Heating Power Heating Power Heating Power Heating Power Heating Power Heating Power Heating Power Heating Power Heating Power
Capacity Input Capacity Input Capacity Input Capacity Input Capacity Input Capacity Input Capacity Input Capacity Input Capacity Input HFRE-130W/E2F
35 0.466 0.788 0.536 0.798 0.605 0.809 0.647 0.815 0.783 0.841 0.886 0.860 1.060 0.886 1.219 0.924 1.325 0.953
2200
40 0.453 0.818 0.521 0.831 0.588 0.844 0.628 0.851 0.761 0.884 0.861 0.907 1.030 0.939 1.185 0.977 1.288 1.005
45 0.440 0.872 0.507 0.886 0.575 0.900 0.615 0.909 0.742 0.942 0.838 0.966 1.000 1.000 1.150 1.037 1.250 1.065 Connecting
Water-outlet Water-inlet Flange*
533.5
50 0.425 0.945 0.490 0.962 0.555 0.978 0.593 0.988 0.716 1.015 0.809 1.034 0.965 1.060 1.110 1.097 1.206 1.124
55 — — 0.474 1.029 0.538 1.043 0.577 1.052 0.693 1.076 0.781 1.094 0.930 1.119 1.070 1.154 1.163 1.180 4-φ18 1064 (Center Distance of
1400 450 Foundation Mounting Hole)
1500
60 — — — — 0.515 1.101 0.552 1.106 0.663 1.138 0.747 1.160 0.890 1.192 1.024 1.226 1.113 1.252 (Center Distance of Foundation Mounting Hole)
1100
Electric Control Box
1141
2300
Note:* The picture shows the connection flange position for E series, while for the A series, the connection flange
Environment Temperature℃ doesn't extend beyond the frame.
Water Outlet
-25 -20 -15 -12 -5 0 7 15 21
Temperature
℃ Heating Power Heating Power Heating Power Heating Power Heating Power Heating Power Heating Power Heating Power Heating Power
Capacity Input Capacity Input Capacity Input Capacity Input Capacity Input Capacity Input Capacity Input Capacity Input Capacity Input
35 0.472 0.831 0.528 0.837 0.612 0.855 0.667 0.869 0.793 0.876 0.886 0.885 1.060 0.893 1.197 0.919 1.297 0.943
40 0.460 0.862 0.514 0.870 0.595 0.892 0.649 0.910 0.771 0.919 0.861 0.927 1.030 0.939 1.163 0.972 1.260 0.995
HFRE-70W/H1F
45 0.446 0.917 0.501 0.926 0.582 0.950 0.635 0.968 0.752 0.978 0.838 0.987 1.000 1.000 1.129 1.032 1.222 1.055
50 — — 0.488 0.982 0.563 1.010 0.614 1.033 0.726 1.044 0.809 1.051 0.965 1.063 1.089 1.094 1.179 1.117
2010
55 — — — — 0.543 1.069 0.593 1.098 0.703 1.108 0.781 1.118 0.930 1.127 1.049 1.152 1.136 1.173
Connecting
60 — — — — — — — — 0.680 1.172 0.753 1.179 0.895 1.186 1.009 1.209 — — Water-outlet Water-inlet Flange
533.5
Note:The above correction factors are applied for HFRE-150W/H1F.
HFRE-65W/A2F HFRE-150W/H1F
HFRE-65W/E2F
1910
2100
Connecting
Flange
Connecting
Water-outlet Water-inlet Flange
Water-outlet Water-inlet
533.5
533.5
4-φ18 824 (Center Distance of
1400 400 Foundation Mounting Hole) 4-φ18
1450 1730 (Center Distance of Foundation Mounting Hole)
1500 860 1500 1760 Electric Control Box
(Center Distance of Foundation Mounting Hole) Electric Control Box
(Center Distance of Foundation Mounting Hole) 350
895
2200 2200
Front View Right View Isometric View Front View Right View Isometric View
21 22
AIR-COOLED MODULAR CHILLER
Installation Demand
Electric Control Box Electric Control Box Electric Control Box Electric Control Box Electric Control Box Electric Control Box
>2400
(2200+100)*a-100
>2400
(2200+100)*a-100
HFRE-130W/A2F, HFRE-130W/E2F
Note:The letter "a" means the quantity of modules.
(2300+500)*a-500
23 24
AIR-COOLED MODULAR CHILLER
V
Quality grade-500 PMV electronic pulse is adopted for precise adjustment, to realize the precise PID control of electronic
expansion valve, realtime dynamic matching, and higher precision of water temperature control.
Coil
Air-cooled Modular Chiller
Valve body
Hisense Hi-Mod V series air-cooled modular Needle valve
Liquid
chiller uses energy-efficient scroll compressors, refrigerant
R410A environmentally friendly refrigerants, inlet
Anti-snow function
The unit is featured with anti-snow function, so the unit can not be covered by the heavy snow when working.
Temperature sensor
linkage protection
Wide operation range -30℃ -20℃ -10℃ 0℃ 10℃ 20℃ 30℃ 40℃ 50℃ 60℃ Water pump linkage
control for anti-freezing
Hi-Mod V series has undergone a series of Anti-snow function
strict tests before launching, such as corrosion 5℃ ———— 48℃
resistance test, fatigue test, frequent start and
stop test and so on. After these rigorous
-15℃ ——— 30℃ Suspending heat exchanger and
long-term tests, the unit can operate stably in thermal radiation anti-frosting design
wide operation range, from 5℃ to 48℃ under
cooling, and from -15℃ to 30℃ under heating.
Centralized drainage
25 26
AIR-COOLED MODULAR CHILLER
The multiple systems in one single unit are independent of each other. When heating, the systems can realize intelligent Parameter setting function Defrosting function Memory function Master/slave integration
alternate defrost according to their own frosting conditions. When one system is defrosting, the rest can be heating normally Time setting Auto defrosting Memory function in case Any slave module can be used
to avoid large fluctuations of water temperature during defrosting. During the intelligent defrost mode, the total quantity of Timed ON/OFF for one week Manual defrosting of power off interchangeably as a master module
Cooling water inlet/outlet temp. Permanent storage for user Each system can be combined with 16
compressors under defrost is less than 50%,
so as to ensure stable heating requirements.
Heating water inlet/outlet temp. parameters modules
Anti-freezing temp. and defrost temp.
Convenient and intelligent control with multiple protections Parameter display function Other functions
Display of unit operating status Fault diagnosis function
The unit adopts microcomputer control system, and is standard with a touch LCD controller, easy to operate. Also, the Set water inlet and outlet temperature, actual water inlet Historical fault query
and outlet temperature Compressor average wear and module working time balance
optional RS485 interface and built-in Modbus protocol can realize centralized control.
Timed adjustment, anti-freezing temp Water system two-way valve control function
Anti-freezing temp in winter, defrosting temp Auxiliary electric heating control function
The unit has 13 built-in powerful protection functions, which provide comprehensive protections for the unit, including Remote ON/OFF control function within a maximum of 1 000 meters
compressor low/high pressure protection, power supply phase loss and reverse protection, frequent start protection, Start/stop control for chilled water pump
compressor overcurrent protection, compressor discharge temperature protection, unit overheating protection, sensor Pump protection feedback
failure protection, refrigeration anti-freeze protection, winter water system anti-freeze protection, insufficient water flow Terminal two-way valve interlock control
Power supply phase loss The V-shaped air-side heat exchanger of the unit conforms to the characteristics of airflow distribution, provides the largest
Compressor low/high and reverse protection windward area of the coil, and has the characteristics of good ventilation performance, large heat exchange area and strong
pressure protection corrosion resistance.
The heat exchanger adopts window-type hydrophilic aluminum fins and high-effciency internally threaded copper tubes to
enhance the heat exchange effect and improve the heat exchange efficiency.
Compressor overcurrent The new Venturi separator is used in the fin condenser, and the refrigerant is evenly distributed to reduce pressure loss,
Frequent start protection
protection reduce noise, and effectively improve heat exchange efficiency.
The surroundings are fixed by a reinforced metal frame to ensure higher firmness and higher stability and allow the entire unit
structure to have a larger maintenance and repair space and flexible layout by saving the floor space by 30%.
Compressor discharge
temperature protection Unit overheat protection
27 28
AIR-COOLED MODULAR CHILLER
Energy-efficient water-side heat exchanger Constant water temperature for enhanced comfort
The new shell-and-tube heat exchanger adopts a spiral heat exchange structure which has a spiral baffle with sealing The chilled water outlet temperature is controlled accurately to±1℃. And various sensors are built in the system to
edge inside, to reduce water resistance and enhance heat exchange capacity. accurately transmit the signal data to the controller, so as to ensure more reliable operation and optimal efficiency of the
The high-efficiency inner-threaded heat exchange tube effectively enhances the heat exchange effect. The refrigerant unit.
inlet area adopts inner-threaded heat exchange tube to realize better refrigerant distribution and heat exchange, with the
efficiency 10% higher than that of conventional shell-and-tube heat exchangers. The unit is equipped with standard outlet water temperature control, with constant water temperature, ensuring more
accurate end temperature regulation and the best user experience. Also the optional return water temperature control to
ensure the dynamic balance of the end users.
Compared with conventional air-cooled chillers, Hisense large temperature difference system can achieve cold water Less water temp.
fluctuation
temperature difference of 8 ~ 10 ℃. With the increase of cold water temperature difference, the cold water volume, water
pipe diameter and water pump capacity will be reduced, and the initial investment and operation cost will be reduced by 5% ~
10%.
Total energy saving(7%) 20% reduction in
start-up time
△=5℃
Intelligent control
Max. 16 units under control Easy access to operation parameters
Powerful historical operation data storage 4 timer-settings per day
Cooling capacity per unit volume: Alarm code display
take R22 as the relative value of 100%
29 30
AIR-COOLED MODULAR CHILLER
HFRWE-345TGF/AE
Capacity correction table
Capacity Cooling capacity
Cooling Power input
Running current
Capacity
Power Power Power Power Power Power Power Power
Heating Power input input input input input input input input input
Running current
Heating capacity
HFRWE-345TGF/AE
Note:
1. Working conditions for nominal cooling capacity: outlet water temperature 7℃; water flow 0.172m3/(h·kW); outdoor ambient temperature 35℃.
2. Working conditions for nominal heating capacity: outlet water temperature 45℃; water flow 0.172 m3/(h·kW); outdoor temperature 7℃ DB / 6℃ WB.
3. Water resistance excludes water pressure drop of the unit and the attached Y-shaped filter.
4. A maximum of 16 units can be connected to form a modular combination.
5. Specifications are subject to change due to design variations without further notice.
31 32
AIR-COOLED MODULAR CHILLER
Note:
1. The installation foundation must be a concrete floor, channel steel frame structure or spring isolator that can withstand the operating pressure of the unit;
2. N indicates the total number of installed modules;
3. Each unit is fixed with six M16 bolts;
4. Six 20-mm thick rubber isolators should be installed between the unit and the installation foundation;
5. The installation foundation must be equipped with drainage facilities to facilitate the drainage of condensate and defrosting water.
33 34
AIR-COOLED SCREW CHILLER
AIR-COOLED Features
The new generation HFC-134a high-efficiency double screw compressor uses the newly optimized 5:6 asymmetric
rotor profile made using the patented production process, ensuring the rotor processing precision and optimal fit
clearance of rotor.
The one-shot moulded screw rotor effectively avoids the stress damage of late cutting processing and ensures the
higher screw hardness and edge line velocity, shorter compression stroke and more efficient compression.
The double-layer pressure compensation shell made through precision casting of nodular cast iron undergoes
precision machining with the M/C machine tool, and a three-dimensional precision measurement instrument is used to
check the machining precision so as to ensure that the compressor gap and precision can meet the requirement for
efficient operation, and the double wall shell is rather stable and cannot be deformed even in a high pressure state. It
not only complies with the pressurization requirement, but also reduces noises.
The compressor housing adopts two stage casting and is divided into the compression side and oil separation side,
with better pressurization performance. Meanwhile, the built-in pressure reducing safety valve can connect the high
and low compression chambers for pressure relief, and the relative external safety valve avoids direct refrigerant
leakage in the air.
Bearing
The patented closed pressure-reducing bearing chamber works with the long life bearing, and the pressure relief
design of pressure bearing with double bearings is adopted in the axial direction to make the bearing solid and durable.
The bearing chamber is separated from the high pressure chamber to educe the bearing chamber pressure effectively
and ensure viscosity of the lubricating oil in the bearing cavity. The excellent lubricating oil path ully lubricates the
bearing, further increases the bearing service life and ensures safe operation of the unit.
35 36
AIR-COOLED SCREW CHILLER
ASME, PED and GB. The internal heat exchange tube adopts the efficient internal thread heat exchange copper tube
to strengthen heat transfer at the water side and refrigerant side, optimize the heat transfer efficiency, reduce the unit's High rate of dust accumulations, fast attenuation of heat
energy consumption, and cut the operating cost for the customer. Dust accmulation probability Small High
exchange efficiency, and low efficiency
The standard pipe connection mode provided by the heat exchanger is groove clamping connection (with short pipes)
which facilitates field installation, and each evaporator is configured with the discharge and drainage devices
separately.
It facilitates the compressor return oil design, simplifies air Cleaning probability Small High High rate of cleanings and considerable maintenance cost
return without requiring any oil pump and eradicates the
frost crack danger of heat exchange tube; the refrigerant
charge is only 1/3 of that of a common heat exchanger, Big wind resistance, improved fan energy efficiency,
without leakage, more reliable and environmentally Wind resistance Small High
and increased operating cost
friendly.
The anti-freeze electric heater and anti-freeze
temperature sensor are installed to implement anti-freeze Hard defrosting, easy secondary frosting, and reduced water
protection for the unit, and the large barrel type water filter Defrosting Easy Difficult
temperature of heating, not applicable to the heat pump condition
and water flow switch are configured for the water system
as additional accessories to implement multi-protection
for the waterway system.
37 38
AIR-COOLED SCREW CHILLER
First-stage Supercooling: The high performance double-screw compressor specially developed for the
The special secondary distribution technology of refrigerant is adopted to recollect the liquid refrigerant, which passes the HCF-134a heat pump, high grade bearing, lubricating oil path design without
recooling coil bottom and undergoes one time supercooling to improve the cooling energy efficiency and capacity effectively. oil pump, and suction spray and intermediate spray protection of the
compressor guarantee extremely safe operation of the compressor.
The three-level password protection prevents wrong operation of
non-professionals and ensures safe operation of the unit. The
multi-protection function ensures safe operation of the unit.
The unit (with standard configuration) adopts outlet water temperature control
Gas inlet
to ensure constancy of the outlet water temperature, make the terminal
temperature regulation more accurate and optimize the user experience;
Air inlet 35℃ return water temperature control can also be selected to achieve the best unit
efficiency under dynamic equilibrium of end user.
Liquid outlet The compressors start one by one to minimize the startup current and reduce
Refrigerant inlet the impact on the power grid.
of subcooling
Refrigerant outlet
of one stage
supercooling
Inverted "M" type heat exchanger of air side
S p e cial
s ti n g
fr o
he
de
at
ex
g
ha ol
in
c
ng co
er r
d e sig
n for s upe
Second-stage supercooling of the economizer
39 40
AIR-COOLED SCREW CHILLER
Wider Operation Range and Longer Service Life Environmentally Friendly Refrigerant R134a
The unit casing adopts the galvanized steel sheet (complying with the EU ROHS standard), undergoes electrostatic orange The environmentally friendly refrigerant R134a with excellent performance saves
pattern spraying with anticorrosive paint, and uses stainless steel screws to prevent corrosion effectively and adapts to power consumption and contains no chlorine element, so it does not damage the
various outdoor adverse conditions. atmospheric ozone layer and has no forbidden period.The refrigerant reduces CO2
The unit can cope with the outdoor wide temperature range of -10℃ to 50℃. emission effectively, alleviates the increasingly serious urban heat island effect
The unit supports air-to-air heat exchange that does not pollute the environment and meets environmental regulations. and constructs green life buildings.
The fan adopts aerofoil axial fan design, which looks like the bird's wings. It can
-10℃ 50℃
effectively decrease the noise from the air interference. Moreover, it adopts
large diameter aluminum blade to achiever higher airflow.
Through the optimized design of the front end of the curved impeller, the
generation of air vortex at the edge of the fan impeller is controlled, improving
the fan efficiency and lowering the fan noise.
The motor ensures zero idling and provides the thermal protection function, with
Operation on a wide temperature range
a longer service life.
The motor is directly driven to eliminate transmission loss effectively and reduce
vibration.
In addition, a high static pressure fan motor is optional, meeting all kinds of
scenarios with static pressure requirements.
Accurate and Stable EEV Control
The 0~3810 step electronic expansion valve control technology can realize fine adjustment in the range of 10% to 100%,
achieve best control on the superheat degree and ensure high performance operation of the unit. Convenient Installation and Simple Maintenance
The unit adopts the integral structure. One unit adopts the one inlet and one outlet system for the waterway to achieve
140% Effect of superheat changes simple installation. The user only needs to connect the power supply and water supply before operation, and does not
Performance need to rebuild an equipment room or purchase cooling tower and other auxiliary equipment, so the construction period
change ratio
Superheat control can be shortened effectively and the installation cost is cut down.
120%
Due to the integrated design of the electrical part and the main unit, the user does not need to set a special power
distribution cabinet, saving the complex power distribution work.
100%
Electrical layout adopts strong and weak current separation, switch design of power-on interlock and unique integrated
design of electric shock prevention. The strong current cabinet is equipped with an anti-shock insulating glass baffle, and
80% 20%
the standard main line configured for the electric control cabinet of unit is connected to the protection box to prevent
Compressor
Start superheat electric shock.
60% capacity
control when The intelligent control system automatically monitors and controls the operating status of the unit and displays the fault
compressor Heat exchange
cause in case of an exception to facilitate unit maintenance.
performance 40% capacity
is low 0
0 Superheat increase ℃
Note: Note:
Strong
Decreased or unstable superheat will reduce the performance of the The unit uniquely adopts the dual power supply current part
compressor, and even prevent the refrigerant from evaporating, resulting in design of electronic expansion valve to implement
Interlocking
liquid compression, resulting in compressor failure. Increased superheating power-off delay protection and prevent hidden
main switch
will reduce the performance of the water-side heat exchanger. danger of liquid hammer against the compressor
when the power supply of the unit fails Weak
current part
unexpectedly.
41 42
AIR-COOLED SCREW CHILLER
Capacity
Discharge adjusting piston
passage
Outer shell
Inner shell
Section sketch map of double layer casing Advanced aerofoil type spiral design
43 44
AIR-COOLED SCREW CHILLER
Specification
The displayed status information includes, but not limited to: ×104kcal/h 26.5 31.6 35.6 38.1 41.6 47.2 51.1 54.4 58.8 63.2
Unit status kW 292.1 346.8 393.7 419.5 457.3 520.3 562.2 602.2 648.0 693.6
Nominal
Unit capacity heating capacity USRT 83.0 98.6 111.9 119.3 130.0 147.9 159.8 171.2 184.2 197.2
Compressor, water pump and expansion valve status ×104kcal/h 25.1 29.8 33.9 36.1 39.3 44.7 48.3 51.8 55.7 59.6
Inlet and outlet water temperatures Cooling power input kW 104.9 123.7 138.2 148.6 162.5 183.7 200.4 209.5 230.6 248.6
Suction/discharge pressure/oil pressure of compressor Heating power input kW 98.0 115.8 129.1 135.4 149.0 166.9 190.7 197.7 214.0 232.4
Suction/discharge temperature/oil temperature of compressor, etc. 12.5%~100%
Control type - 25%~100% stepless regulation
stepless regulation
Alarm information includes, but not limited to: Startup type - Y-Δ
Power supply over/under-voltage and reverse phase/phase loss protection Power supply - AC 3Φ, 380V/50Hz
Compressor high/low voltage protection
Type - R134a
Compressor and fan overload protection
Refrigerant Circuits No. No. 1 1 1 1 1 1 1 1 2 2
Oil filter clogging protection
Control type - Electronic expansion valve
Discharge temperature high protection
Type - Semi-hermetic dual-screw type
Anti-freezing protection, cutoff protection and frequent start/stop protection Compressor
Qty No. 1 1 1 1 1 1 1 1 2 2
Feedback on various pressure/temperature sensor faults, etc.
Type - Spiral axial fan
Qty No. 6 8 8 10 10 12 12 14 14 16
Fan
Power input kW 9.6 12.8 12.8 16 16 19.2 19.2 22.4 22.4 25.6
Functions Unit Configuration
Air flow x104m3/h 12 16 16 20 20 24 24 28 28 32
Three level password protection of factory, service and user Standard unit accessories
Air-side Type - Fin tube type
Power-on self-test function Spring shock absorber heat
exchanger FPI Inch 16FPI
Weekly timed-on/off function Water filter
Type - Dry shell and tube type
Memory function in power failure Water flow switch
Water flow
Unit preheating m3/h 53.1 63.2 71.3 76.1 83.2 94.5 102.2 108.8 117.6 126.3
Clamp under cooling
Water-side
Outlet/return water temperature setting/control heat Water flow m3/h 50.2 59.6 67.7 72.1 78.7 89.5 96.7 103.6 111.4 119.3
exchanger under heating
Automatic/manual control of unit operation
Water
Balancing compressor operating time kPa 38 44 48 36 34 47 54 56 48 61
resistance
Delayed start control of compressor Diameter of Inch
connected pipe 8 5 5 6 6 6 6 6 6 6
Compressor start time setting
Compressor energy regulation control/setting Rated current A 209 240 258 279 303 339 353 371 449 480
Max. operating current A 275 303 338 345 385 434 505 512 578 606
A
Unit Options Max. startup current 414 649 710 710 882 882 1007 1007 689 952
Length mm 3750 4650 4650 5550 5550 6450 6450 7350 8000 8900
Low temperature cooling type/ Plateau type Ultra low noise type
annual heat pump type Unit
dimensions Width mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
"Hisense Cloud" remote monitoring Centralized controller Remote touch screen controller
Flange interface Anticorrosive fin Water side pressure bearing 1.6 Mpa Transportation kg 3528 4453 4463 5621 5881 5861 5961 6887 7588 8414
Unit weight
Built-in hydraulic module (some models are available) Operation kg 3728 4653 4713 5924 6184 6211 6311 7307 8008 8834
Note: For the above options, contact the local office. Notes:
1. Cooling design condition: outdoor dry bulb temperature 35℃, outlet water temperature 7℃ and water flow 0.172 m3/(h·kW).
2. Power distribution and wiring on the unit installation site are subject to the unit nameplates or installation instructions.
45 46
AIR-COOLED SCREW CHILLER
×104kcal/h 70.9 75.9 79.9 82.6 88.7 94.5 101.6 108.8 113.2 122.0 Water side maximum outlet water temperature(℃) 15 55
kW 781.2 837.5 878.1 908.7 975.9 1043.0 1107.6 1210.0 1250.2 1341.6 Water side maximum temperature difference (℃) 8 8
Nominal
heating capacity USRT 222.1 238.1 249.7 258.4 277.5 296.6 314.9 344.0 355.5 381.4
Water side minimum temperature difference (℃) 4 4
×104kcal/h 67.2 72.0 75.5 78.1 83.9 89.7 95.2 104.1 107.5 115.4
Notes:
Cooling power input kW 277.2 296.5 311.4 325.1 346.9 368.4 401.7 421.5 440.0 479.1 If the cooling at the ambient temperature -15℃ to 5℃ is required, contact the technical personnel at your local office of Hisense.
Heating power input kW 256.7 269.0 281.9 294.0 313.5 333.5 381.3 395.2 411.7 446.4
Type - R134a Altitude (m) 0 300 600 900 1200 1500 1800
Refrigerant Circuits No. No. 2 2 2 2 2 2 2 2 3 4
Atmospheric pressure (bar) 1.013 0.977 0.942 0.908 0.875 0.843 0.812
Control type - Electronic expansion valve
Cooling correction factor 1.000 0.993 0.986 0.979 0.973 0.967 0.960
Type - Semi-hermetic dual-screw type
Compressor
Qty Input power correction factor 1.000 1.005 1.009 1.015 1.021 1.026 1.031
No. 2 2 2 2 2 2 2 2 3 4
Qty No. 16 20 20 20 22 24 24 28 28 30
Fan
Power input kW 25.6 32 32 32 35.2 38.4 38.4 44.8 44.8 48.0
Correction factor for adding ethylene glycol
Air flow x104m3/h 32 40 40 40 44 48 48 56 56 60
Air-side Type - Fin tube type Ethylene glycol solution concentration (%) 10 20 30 40 50
heat
exchanger FPI Inch 16FPI
Cooling capacity correction factor 0.991 0.982 0.972 0.961 0.946
Type - Dry shell and tube type
Input power correction factorection factor 0.996 0.992 0.986 0.976 0.966
Water flow
m3/h 141.7 151.7 159.8 165.3 177.5 189.1 203.3 217.7 108.8+117.6 117.6+126.3
under cooling
Water flow correction factor 1.013 1.040 1.074 1.121 1.178
Water-side
Water flow
heat m3/h 134.4 144.1 151.0 156.3 167.9 179.4 190.5 208.1 103.6+111.4 111.4+119.3
under heating Water pressure drop correction factor 1.070 1.129 1.181 1.263 1.308
exchanger
Water
kPa 56 61 56 70 55 80 90 71 56/48 48/61
resistance
Diameter of
connected pipe Inch 6 6 8 8 8 8 8 8 6+6 6+6
Correction factor of operating performance at low temperature
Rated current A 514 556 582 606 642 677 706 743 820 929
Ethylene glycol chilled
water outlet temperature (℃) 2 0 -2 -4 -6 -8
Max. operating current A 676 690 730 770 819 868 1010 1024 512+578 578+606
Maximum outdoor ambient
40 39 38 37 36 35
temperature (℃)
Max. startup current A 1048 1055 1227 1267 1316 1316 1512 1519 1007+689 689+952
Cooling capacity correction factor
Compressor input 0.842 0.785 0.725 0.67 0.613 0.562
Length mm 8900 10700 10700 10700 11600 12500 12500 14300 15350 16900
power correction factor 0.95 0.94 0.92 0.89 0.87 0.84
Unit Minimum ethylene glycol
Width mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
dimensions solution concentration (%) 10 20 20 30 30 30
Height mm 2525 2525 2525 2525 2525 2525 2525 2525 2525 2525
Transportation kg 8447 8643 9685 9785 9769 10813 11123 11523 13742 14938
Unit weight
Operation kg 8867 9063 10165 10265 10269 10703 11623 12123 14542 15758
Notes:
1. Cooling design condition: outdoor dry bulb temperature 35℃, outlet water temperature 7℃ and water flow 0.172 m3/(h·kW).
2. The HFLGE-390T* and HFLGE-420F* units consist of the master unit and slave unit, which are transported to the site by segment for combination.
3. Power distribution and wiring on the unit installation site are subject to the unit nameplates or installation instructions.
47 48
WATER-COOLED SCREW CHILLER
SERIES
HISENSE WATER-COOLED SCREW CHILLER Compressor
Hisense water-cooled screw chiller (Hi-SC S Series) features superior overall energy efficiency factor,
efficient, stable and reliable unit design,
broad cooling capacity range and flexible configuration package,
can be widely used in large energy stations, data centers, rail transit, hospitals,
commercial complexes and other areas
Electric Cabinet
NOMENCLATURE
HS LG E - 210 S M H / A H
Evaporator type:
M - flooded type, J - falling film type, G - dry expansion type
Compressor quantity:
S- single-compressor, D- double-compressor,
T- triple-compressor
Compressor type:
LG - screw type, W - scroll type, LX - centrifugal type
50 51 61 62
Introduction Characteristics Technical Parameters Installation Product classification code:
HS - Hisense water-cooled unit
49 50
WATER-COOLED SCREW CHILLER
The high efficiency motor is R134a special rotor Double-layer cast Efficient three-stage
designed with an optimized profile and direct-drive Integral Cast Body, Reducing Leakage and Errors
body, less noise oil separation system
suction cooling channel for safe motor, more efficient
and efficient operation under all
The motor side and the screw side of the unit are cast
working conditions
in one piece, reducing the risky of leakage from flange
connections.
51 52
WATER-COOLED SCREW CHILLER
Stepless Compressor Load Adjustment and Stable Water Output High-efficiency direct-drive motor with optimized refrigerant cooling channel
The high-efficiency motor is designed with an optimized suction cooling channel for safe and efficient operation under all
ON-OFF switch of the solenoid valve Suction Gas CR1
working conditions.
controls the level of oil pressure in the
CR2
piston cavity, so as to push the
spring-pressed piston to drive the slide
CR3
valve to move sideways for continuous
stepless loading and unloading.
CR4
Reliable Bearing Operation Thanks to the Low Pressure Bearing Sealed Chamber High-efficiency motor
Low pressure bearing sealed chamber is introduced to ensure low bearing pressure, excellent lubrication and
cooling effect, gaining more reliable bearing operation.
A high-precision filter is built in. There is no need to replace it during the service life of the compressor
New High-efficiency Flooded Evaporator
The unique liquid homogenizing plate design and optimized heat exchange tube arrangement ensure uniform refrigerant
Three-stage Oil Return Technology distribution and sufficient heat exchange.
The high-efficiency internal and external ribbed copper tube tooth profile for flooded evaporator improves heat exchange
The three-stage oil return technology ensures sufficient oil supply for the compressor, while avoids excessive oil entering efficiency.
the system to lower the heat transfer efficiency, so as to ensure stable and efficient operation of the system. CFD simulation is applied to perform numerical simulation and analytical study of finite elements. Experimental results are
reliably analyzed to further optimize the gas channel, ensuring efficient heat transfer.
First-stage oil return The copper tube is immersed in the refrigerant, and a strong nucleate boiling is formed on the surface of the copper tube,
There is a built-in oil separator in the compressor. After giving high heat transfer efficiency.
Refrigeration Cycle & Lubricating Oil Cycle
compression, the mixture of oil and refrigerant can be The water flows inside the copper tube so that the heat exchanger is easy to clean.
Compressor
separated when going through the built-in oil separator. Only a
small amount of oil can be brought out of the compressor.
53 54
WATER-COOLED SCREW CHILLER
Sensitive and High-precision Magnetostrictive Liquid Level Sensor Differential Pressure Water Flow Switch for Easier Operation
Magnetostrictive liquid level detection technology is used to monitor liquid level in real time. Differential pressure water flow switch allows for more accurate flow disconnection and reset
High precision to micron level with small error. Factory-installed on the unit, no need for on-site hole cutting, installation and wiring by users.
Sensitive and quick response. Less space required for installation
Easy to install and use, no need for regular calibration or maintenance. No resistance loss produced to the water system.
No need for zero setting after power-down. Fewer moving parts contribute to lower possibility of fatigue damage.
Position magnet
The unit adopts dry filter with replaceable filter element, which is convenient for maintenance.
Strain pulse detector
The filter element adopts 100% 3A molecular sieve, which has super water absorption function.
Optimize the flow design for small pressure drop.
Aviation-grade oil filter with high filtration precision and large filtration area.
High-precision Electronic Expansion Valve
More precise control of evaporator liquid supply and smoother control of water temperature.
Advanced balanced flow port design allows for bi-directional liquid flow with effective bi-directional sealing.
Some models have built-in condenser sight glass to indicate the refrigerant water content, so that users can easily
check the refrigerant water content.
With the advanced algorithm“evaporator liquid level control as the primary and approach temperature difference
control as the supplement”
, the 6386-step electronic expansion valve can respond quickly and stably.
Filter element of filter-drier Inner core of oil filter Filter-drier cartridge
55 56
WATER-COOLED SCREW CHILLER
More Than 20% Energy-saving Compared with Conventional Units Intelligent Warning Technology
The Hi-SC S Series saves more than 20% energy than the conventional units, which can greatly reduce the energy The unit has multiple pre-detection functions to identify and correct the operating status by real-time monitoring and analysis
consumption caused by the HVAC. of the pressure, temperature, current and other parameters in time, so that the unit can work within the reliable operating
The COP can be up to 6.102. range and better cope with the harsh working conditions.
The capacity output of single compressor can achieve 25%-100% stepless adjustment, so that the capacity output can be The unit has multiple protection measures, such as water anti-freeze protection, water cut-off protection, high voltage & low
adjusted more accurately according to user needs. Thus, the operation is more energy-saving, and the outlet water voltage protection, over-current protection, power supply protection, discharge temperature protection, sensor fault reminder
temperature is more stable. and so on. So as to ensure the safe operation under the complex working conditions
100%
100
High Voltage &
90
Water Cut-off Low Voltage
80
70 Protection
60
50
40
30
25%
Discharge Temperature
Protection
Adaptive Control of Evaporator Liquid Level for Better Heat Exchange Water Anti-freeze
Protection
Intelligent adaptive control technology of evaporator liquid level is adopted to ensure that the evaporator plays
the highest heat transfer efficiency under variable working conditions and partial load condition.
Multiple Protections
Environmentally Friendly Refrigerant R134a Sensor Fault Reminder
Environmentally friendly R134a refrigerant is non-toxic with ODP=0 and will not
destruct the ozone layer.
New system design with less refrigerant charge.
Power Supply
Low energy consumption, reduced carbon emissions. Protection
57 58
WATER-COOLED SCREW CHILLER
Actual
7-inch high-resolution color touch screen displays the operation status and parameters in graphics dynamically.
X
H Screen saver is available to extend the life of the screen.
Target
Capacity
ON
Solenoid valve
OFF The detailed fault is displayed directly no need to check the alarm code, and the water temperature curve is displayed
intuitively, easy to check the operation load.
Stabilize product operation through optimal compressor start-stop control, minimum stop interval, and shortest running
Set password protection to prevent unauthorized personnel from operating.
time control.
The dual-compressor independent system design, with the two compressors as backup to each other, greatly improves
the reliability of the unit.
The rotation running time of the two compressors is intelligently balanced, effectively extending the service life.
The water inlets and outlets of the evaporator and condenser are arranged on the same side. It is convenient for users to
organize the machine room, facilitates the installation and saves the floor space. Capacity Adjustment Fault Protection
When the unit is unexpectedly powered off, the user's default settings and historical data can still be retained, and there is no Warning Control Timed On/Off
need to repeat settings.
59 60
WATER-COOLED SCREW CHILLER
Lifting is recommended for the transfer of Hi-SC S series, while forklift handling is
HSLGE-*MH/AH Unit 90S 100S 130S 150S 170S 190S 210S 230S 260D 300D 340D 390D 420D 470D strictly prohibited. Attention shall be paid to the followings.
Nominal cooling capacity kW 322.4 366.8 446.7 511.3 587.1 666.9 721.5 801.3 919.6 1053 1209 1373 1486 1650
Nominal cooling input power kW 55.4 63.1 77.0 86.6 97.5 110.3 125.1 138.0 153.0 175.1 198.9 225.0 253.0 279.1 The unit must be lifted from the designated lifting points.
COP / 5.819 5.813 5.801 5.904 6.022 6.046 5.767 5.807 6.010 6.014 6.078 6.102 5.874 5.912 Check the load-bearing capacity of the slings and hangers to make sure that
IPLV / 6.842 6.835 6.821 6.943 7.082 7.111 6.780 6.827 7.177 7.180 7.258 7.287 7.011 7.058 they are adequate to lift the unit and have sufficient margin.
Chilled water flow rate m3/h 55.5 63.1 76.8 87.9 101.0 114.7 124.1 137.8 158.2 181.1 207.9 236.2 255.5 283.8
Ensure that the unit is horizontal as much as possible during tranporting, and
Cooling water flow rate m3/h 69.3 78.9 96.0 109.9 126.2 143.4 155.1 172.3 197.7 226.3 259.9 295.2 319.4 354.7
Max. running current A 139.1 159.3 187.0 212.0 234.0 272.0 303.0 335.0 374.0 424.0 468.0 544.0 606.0 670.0 that the maximum height difference of the unit's feet from the ground does not Hanger
Power supply / AC 3Φ, 380V/50Hz exceed 25cm, so as to prevent the unit from overturning or reversing.
Capacity control / 25%-100% Stepless 12.5%-100% Stepless The handling of the unit should be carried out slowly, and the personnel should Sling
Type / Semi-hermetic screw compressor
keep a certain distance and take safety protections to prevent collisions with
Quantity pc 1 2
Compressor
Start mode / Y-Δ surrounding objects. Unit
Start current (Y) A 280.0 330.0 415.0 479.0 506.0 650.0 683.0 845.0 602.0 691.0 740.0 922.0 986.0 1180.0 During lifting, it is strictly forbidden to press the electric cabinet, pipeline or any
Type / High efficiency shell and tube type(flooded type ) valves by the cable, otherwise serious damage may be caused to the unit.
Water connection type / Clamp
The hoisting should be in place at once as much as possible to avoid accidents
Outer diameter of connection pipe mm 133 133 159 159 159 159 159 219 219 219 219 219 219 273
Evaporator
Standard pressure MPa 1.0 caused by repeated hoisting.
Water pressure drop kPa 50 49 49 48 48 49 49 49 88 87 87 86 87 87
Water dirt coefficient m2℃/kW 0.018
Type / High efficiency shell and tube type
Water connection type / Clamp
Outer diameter of connection pipe mm 133 133 159 159 159 159 219 219 219 219 219 273 273 273
Condenser
Standard pressure MPa 1.0 Unit Installation
Water pressure drop kPa 68 69 66 67 67 66 67 67 106 106 108 108 106 106
Water dirt coefficient m2℃/kW 0.044 Hi-SC S series must be installed on a fixed foundation (flat and firm, and treated as water-proof) with drainage ditches
Type / R134a
Refrigerant around. Please pay attention to the follows when construct the foundation.
Total charge amount kg 125 110 140 150 180 200 215 235 295 305 350 400 430 480
Length mm 3530 3530 3550 3550 3570 3570 3590 3590 4710 4710 4720 4750 4840 4840
Reinforced concrete foundation is recommended.
Dimensions Width mm 1240 1240 1320 1320 1430 1430 1520 1520 1570 1570 1660 1780 1780 1850 Unit foot
Height mm 1700 1700 1750 1750 1800 1800 1850 1850 1900 1900 1910 1960 1980 1980 It is recommended to reserve 4* 100×100 anchor bolt mounting holes. If M20 nut
Length mm 4000 4000 4000 4000 4000 4000 4000 4000 5100 5100 5100 5100 5100 5100 spring shock absorbers are used, no need to reserve mounting holes. φ20 gasket
Package size Damping pad
Width mm 1570 1570 1570 1570 1570 1570 1570 1570 1900 1900 1900 1900 1900 1900
(including base) The foundation shall be level and the maximum height difference shall be Steel sheet
Height mm 1860 1860 1910 1910 1960 1960 2010 2010 2080 2080 2090 2140 2160 2160
controlled within 1 mm/m. M20 anchor bolt
Shipping weight(without refrigerant) kg 2720 2780 3430 3510 3810 3870 4200 4330 6340 6510 6930 7480 7690 7920
Operation weight kg 2750 2820 3550 3650 4000 4090 4450 4620 6700 6900 7400 8080 8350 8620 Drainage ditch should be set, and there should be a certain slope to Reinforced concrete
foundation
facilitate drainage.
Notes:
You can refer to the following figure for the design and construction of the
1. Nominal cooling condition: chilled water outlet temperature 7℃, cooling water inlet temperature 30℃.
2. The standard pressure is 1.0 MPa. The 1.6 MPa or 2.0 MPa can be customized according to users’need. foundation. The dimension A, B, D, E and F should refer to the unit Installation of Damping pad
dimension.
Correction Coefficient for Refrigerating Capacity Correction Coefficient for Power input
Unit: mm
under Variable Working Conditions under Variable Working Conditions A Unit foot
A-A
300
Condenser Inlet Temperature (℃) Condenser Inlet Temperature (℃) Fastening bolt
Drainage 100*100 foundation
25 28 30 32 35 25 28 30 32 35 bolt hole
Reserved:4-100×100 ditch
5 1.01 0.98 0.95 0.92 0.89 5 0.86 0.93 0.99 1.04 1.12 anchor bolt holes
B+400
300
6 6
>400
1.04 1.01 0.97 0.95 0.91 0.86 0.93 1.00 1.05 1.12
7 1.07 1.03 1.00 0.98 0.94 7 0.87 0.93 1.00 1.05 1.12 D F+300
Evaporator Evaporator
8 1.11 1.07 1.03 1.02 0.98 8 0.87 0.93 1.00 1.05 1.12 E Adjusting bolt
Outlet Outlet A+600
9 1.15 1.12 1.08 1.06 1.02 9 0.87 0.93 1.00 1.05 1.13
Temperature Temperature
10 1.19 1.16 1.11 1.09 1.05 10 0.87 0.93 1.00 1.05 1.13 Foundation Base
A
11 1.24 1.20 1.16 1.14 1.10 11 0.87 0.93 1.00 1.05 1.13 Facing to electric cabinet
12 1.29 1.25 1.20 1.18 1.14 12 0.87 0.94 1.01 1.05 1.13 Installation of Shock Absorber
Foundation
61 62
WATER-COOLED SCREW CHILLER
1000
maintenance.
C
For the installation of multiple units, it should be noted that the distance between the 10
00
two units should be 1.5 times than the required distance of a single unit.
The unit must be installed indoors. Humid areas or areas with direct sunlight shall 0
80
be avoided;
The selection of the installation location should avoid the transmission of noise and 00
12 100
vibration from affecting the living and office areas. A- D 120 F E
50
The installation location of the unit shall be provided with appropriate safeguards to 0
A B
Model A B C D E F
The water pump shall be set at the water inlet side of the heat exchanger. HSLGE-230SMH/AH 3590 1520 1850 2852 1250 308
If the water system adopts a closed circuit, an expansion water tank should be provided. The expansion water tank
should be set at more than 1m higher than the highest point of the entire water system. The capacity of the water tank is Dimension of Double-compressor Unit
about 1/10 of the water capacity of the entire system.
A filter must be added at the water inlet pipeline and the filter mesh should be more than 16 meshes. The filter needs to
be cleaned regularly.
Vibration-proof soft connections should be added between the unit and the pipelines.
C
Minimum Water Capacity Requirements
Usually, an additional water tank needs to be added to expand the total water volume and the water tank is usually installed
Data Sheet of Double-compressor Unit (Unit: mm)
on the water inlet side. A baffle plate needs to be added in the water tank to avoid short circuit of the water flow. The form
Model A B C D E F
of the baffle plate can refer to the following forms:
HSLGE-260DMH/AH 4710 1570 1900 3922 1320 396
Unsatisfactory Recommended Unsatisfactory Recommended HSLGE-470DMH/AH 4840 1850 1980 3922 1600 396
63 64
AIR HANDLING UNIT
Hisense AHU can satisfy the customers' personalized demands thanks to its compact structure, excellent performance, multi-
ple static pressure, and wide air flow ranging from 2000 to 50000 m3/h. It adopts labyrinth internal and external frame structure
with low air leakage rate, high strength. There are five types of AHU for choice: Horizontal TypeⅠ, Horizontal TypeⅡ, Horizontal
TypeⅢ, Horizontal Type Ⅳ, Vertical TypeⅠ. Besides, according to the actual demand, hot water coils, wet-film humidifiers can
be configurated, and it is widely used in shopping malls, hotels, office buildings and other commercial buildings.
Nomenclature
Air flow direction
HZK A - 02 W1 120 H Z 4 1 F 0 A
Serial No.: A, B, C
Type: W1- Horizontal TypeⅠ W3- Horizontal TypeⅢ L1- Vertical TypeⅠ
W2- Horizontal TypeⅡ W4- Horizontal Type Ⅳ
65 66
AIR HANDLING UNIT
Specification
Labyrinth Seal Structure Design Firm Structure Design
Low Air Leakage Rate
The air handling unit is composed with an outer
Classification
aluminum alloy frame and a concealed inner
It is designed with labyrinth seal structure. The aluminum profile
metal frame. The outer aluminum alloy frame is
with concave and convex grooves is adopted at the junction of
fastened by the tenon structure, bolts and nuts to
housing and further fastened by bolts and nuts, forming a
form a torsion-resistant rigid body, while the
labyrinth sealing structure. The max. air leakage rate is only
inner concealed metal frame greatly increases W1- Horizontal TypeⅠ
0.27%, far lower than the internationally allowed air leakage L1- Vertical TypeⅠ
the strength of the unit. Nylon Filter+(Plate Primary Filter)+
rate. Nylon Filter+(Plate Primary Filter)+ Coil+(Wet-film Humidifier)+Fan
Coil+(Wet-flim Humidifier)+Fan
All metals inside the labyrinth body are isolated from the outside by means of polyurethane foam and specially designed
seals, avoiding the sticking of insulation strips everywhere inside the housing as the common AHU and it simply eliminates
the cold bridge problem. All panels are inlaid with aluminum profile frame on all edges so that the corners and edges of sheet
metal are totally isolated from air and moisture, thereby preventing rust spot on panels. Hisense
Air Handling Unit
The AHU adopts the integrated water tray which is possessed by the advanced German-made spraying equipment and W2- Horizontal TypeⅡ
then pasted with the integral insulation material. It is installed on the bottom of the AHU on the full size, so that there will be W4- Horizontal Type Ⅳ Mixing Section+Plate Primary Filter+
no water leakage worry during operation. Mixing Section+Plate Primary Filter+ Coil+(Wet-film Humidifier)+Fan
Electrostatic Precipitator+Coil+Fan
Upper Front UF Upper Front UF Upper Rear UR Front Top FT Front Bottom FB
67 68
AIR HANDLING UNIT
02 2000 27.4 30.7 1.6 31.8 40 25 33.7 34.2 1.6 66.5 40 25 55.0
02 2000 11.0 22.8 0.5 7.5 32 25 14.8 27.6 0.7 44.8 32 25 55.0
03 3000 40.5 44.3 1.9 44.0 40 25 47.9 48.9 2.3 89.6 40 25 58.0
03 3000 17.2 35.1 0.8 13.8 32 25 22.7 41.9 1.1 71.6 32 25 58.0
04 4000 54.7 58.8 2.6 62.5 50 25 63.8 67.0 3.0 55.8 50 25 59.0
04 4000 23.4 47.1 1.1 20.7 32 25 29.6 54.6 1.4 34.8 32 25 59.0
05 5000 68.4 73.8 3.3 64.3 50 25 79.8 83.9 3.8 53.5 50 25 61.0
05 5000 28.2 57.0 1.3 19.9 32 25 34.5 64.5 1.6 30.3 32 25 61.0
06 6000 81.0 85.0 3.9 78.3 50 25 97.9 100.5 4.7 74.9 50 25 62.0
06 6000 35.1 69.1 1.7 27.0 40 25 42.4 78.2 2.0 40.3 40 25 62.0
07 7000 89.6 95.0 4.3 40.5 65 25 115.4 116.7 5.5 31.4 65 25 64.0
07 7000 41.0 80.7 2.0 31.9 50 25 48.8 92.5 2.3 50.0 50 25 64.0
08 8000 101.7 108.6 4.9 57.7 65 25 127.7 134.5 6.1 42.8 65 25 64.0
08 8000 48.2 93.7 2.3 46.9 50 25 57.2 106.7 2.7 74.7 50 25 64.0
09 9000 116.8 123.5 5.6 58.5 65 25 140.5 146.7 6.7 40.7 65 25 65.0
09 9000 52.3 102.6 2.5 42.4 50 25 65.1 120.6 3.1 75.7 50 25 65.0
10 10500 132.8 154.9 7.0 78.6 65 25 162.1 167.3 7.7 60.0 65 25 66.0
10 10500 59.7 115.7 2.8 60.0 50 25 74.2 138.1 3.5 48.8 50 25 66.0
12 12000 157.9 175.3 7.5 82.7 65 25 193.6 196.5 9.2 89.0 65 25 67.0
12 12000 69.8 136.8 3.3 46.0 50 25 89.9 165.3 4.3 75.6 50 25 67.0
13 13500 79.1 158.1 3.8 20.8 65 32 104.1 187.7 5.0 39.0 65 32 68.0 13 13500 172.8 195.2 8.2 27.2 80 32 222.6 223.1 10.6 61.5 80 32 68.0
15 15000 90.4 172.7 4.3 61.5 65 32 115.0 207.6 5.5 38.1 65 32 68.0 15 15000 194.7 221.3 9.3 27.8 80 32 252.6 252.3 12.0 62.8 80 32 68.0
18 18000 107.0 210.8 5.1 31.8 65 32 136.4 247.2 6.5 51.2 65 32 69.0 18 18000 230.5 257.6 11.0 37.5 80 32 293.6 296.1 13.1 74.4 80 32 69.0
21 21000 126.6 247.3 6.0 36.3 65 32 157.4 289.4 7.5 26.4 65 32 70.0 21 21000 276.3 303.6 13.2 28.1 80 32 331.5 336.1 13.9 78.3 80 32 70.0
24 24000 148.8 285.6 7.1 53.4 65 32 181.9 332.2 8.7 37.7 65 32 71.0 24 24000 319.9 348.8 15.2 39.6 80 32 *366.2 *380.6 *12.5 *70.7 80 32 71.0
27 27000 167.5 321.3 8.0 55.1 65 32 204.7 372.0 9.8 39.0 65 32 72.0 27 27000 359.9 389.7 17.1 42.6 80 32 *409.6 *428.2 *13.9 *72.4 80 32 72.0
30 30000 186.1 357.0 8.9 56.8 65 32 226.1 413.4 10.8 39.8 65 32 73.0 30 30000 384.1 420.5 18.3 43.2 80 32 *455.2 *473.6 *15.5 *75.0 80 32 73.0
33 33000 204.7 392.7 9.8 72.3 80 32 253.0 456.8 12.1 52.2 80 32 73.0 33 33000 445.7 482.0 21.2 59.8 80 32 *503.6 *523.3 *17.1 *96.3 80 32 73.0
35 35000 220.1 416.5 10.5 85.6 80 32 271.3 486.9 12.9 61.6 80 32 73.5 35 35000 454.3 490.5 21.6 63.7 80 32 *552.5 *578.3 *15.5 *83.6 80 32 73.5
40 40000 230.8 451.0 11.0 69.2 80 32 299.8 546.1 14.3 52.5 80 32 73.5 40 40000 477.1 525.2 22.7 40.3 80 32 *589.3 *622.5 *18.7 *83.5 80 32 73.5
45 45000 248.1 484.8 11.8 71.5 80 32 341.1 617.2 16.3 59.8 80 32 74.0 45 45000 536.7 594.2 25.6 45.3 80 32 *647.2 *679.6 *19.3 *79.8 80 32 74.0
50 50000 275.6 538.5 13.1 79.1 80 32 379.0 685.9 18.1 65.9 80 32 74.0 50 50000 605.1 663.9 28.8 51.6 80 32 *727.9 *774.6 *21.7 *89.9 80 32 74.0
Note: Note:
1. Standard cooling conditions: chilled water inlet/outlet at 7/12℃; air inlet at 27℃ DB/19.5℃ WB. 1. Standard cooling conditions: chilled water inlet/outlet at 7/12℃; air inlet at 35℃DB/28℃WB.
2. Standard heating conditions: hot water inlet at 60℃; air inlet at 15℃ DB. 2. Standard heating conditions: hot water inlet at 60℃; air inlet at 7℃DB.
3. Specifications are subject to change without prior notice. 3. The value noted with * indicates that the temperature difference between inlet and outlet water is more than 5℃ to control the pressure drop of refrigerant pipeline.
4. The noise in the table is tested based on the vertical type unit, and the value will change due to different ESP. 4. Specifications are subject to change without prior notice.
5. The noise in the table is tested based on the vertical type unit, and the value will change due to different ESP.
69 70
AIR HANDLING UNIT
Standard Condition (Four-Pipe, Additional Heat Coil)--Optional Fresh Air Condition (Four-Pipe, Additional Heat Coil)--Optional
HZK*-* m 3/h kW l/s kPa DN kW l/s kPa DN HZK*-* m 3/h kW l/s kPa DN kW l/s kPa DN
02 2000 6.7 0.2 0.2 32 13.6 0.3 1.2 32 02 2000 9.0 0.2 0.3 32 16.6 0.4 1.7 32
03 3000 10.2 0.3 0.3 32 20.0 0.5 2.0 32 03 3000 13.5 0.3 0.5 32 25.7 0.6 3.1 32
04 4000 13.8 0.3 0.5 32 27.2 0.7 3.0 32 04 4000 18.6 0.5 0.8 32 33.2 0.8 4.2 32
05 5000 18.5 0.5 0.5 32 35.8 0.9 3.3 32 05 5000 23.2 0.6 0.8 32 43.6 1.1 4.6 32
06 6000 23.2 0.6 0.7 32 43.7 1.1 4.3 32 06 6000 28.7 0.7 1.0 32 50.6 1.2 5.5 32
07 7000 27.6 0.7 0.9 32 50.9 1.2 5.1 32 07 7000 33.9 0.8 1.3 32 63.0 1.5 7.2 32
08 8000 32.5 0.8 1.3 32 56.8 1.4 6.4 32 08 8000 39.9 1.0 1.9 32 73.1 1.8 10.5 32
09 9000 37.0 0.9 1.3 32 64.4 1.6 6.5 32 09 9000 45.5 1.1 1.8 32 78.4 1.9 9.1 32
10 10500 42.0 1.0 1.8 32 77.7 1.9 10.3 32 10 10500 51.6 1.3 2.5 32 92.9 2.3 14.0 32
12 12000 48.7 1.2 2.5 32 88.8 2.2 14.2 32 12 12000 59.0 1.4 3.5 32 106.2 2.6 19.2 32
13 13500 56.4 1.4 3.7 40 101.5 2.5 20.4 40 13 13500 69.2 1.7 5.3 40 123.3 3.0 28.4 40
15 15000 61.7 1.5 3.9 40 111.0 2.7 21.1 40 15 15000 75.9 1.9 5.5 40 134.9 3.3 29.5 40
18 18000 75.2 1.8 5.4 40 135.3 3.3 29.2 40 18 18000 92.3 2.3 7.6 40 161.9 3.9 39.7 40
21 21000 88.9 2.2 7.0 40 157.8 3.9 37.5 40 21 21000 109.2 2.7 10.0 40 182.9 4.5 7.4 40
24 24000 103.1 2.5 10.2 40 174.7 4.3 7.7 40 24 24000 124.8 3.0 14.1 40 212.4 5.2 10.7 40
27 27000 116.0 2.8 10.3 40 196.5 4.8 7.8 40 27 27000 140.4 3.4 14.3 40 237.1 5.8 10.7 40
30 30000 128.8 3.1 10.4 40 216.5 5.3 7.7 40 30 30000 156.0 3.8 14.4 40 261.3 6.4 10.7 40
33 33000 141.7 3.5 13.4 40 240.1 5.9 10.1 40 33 33000 173.9 4.2 19.0 40 292.1 7.1 14.1 40
35 35000 150.3 3.7 15.6 40 254.7 6.2 11.7 40 35 35000 184.4 4.5 22.1 40 309.8 7.6 16.4 40
40 40000 167.0 4.1 13.9 40 281.5 6.9 10.4 40 40 40000 202.3 4.9 19.2 40 342.8 8.4 14.5 40
45 45000 187.9 4.6 15.3 40 322.1 7.9 11.8 40 45 45000 227.6 5.6 21.2 40 385.7 9.4 16.0 40
50 50000 208.8 5.1 16.7 40 357.9 8.7 12.8 40 50 50000 256.1 6.2 23.6 40 423.6 10.3 17.1 40
Note: Note:
1. Standard heating conditions: hot water inlet/outlet at 60/50℃; air inlet at 15℃ DB. 1. Standard heating conditions: hot water inlet/outlet at 60/50℃; air inlet at 7℃ DB.
2. Specifications are subject to change without prior notice. 2. Specifications are subject to change without prior notice.
71 72
AIR HANDLING UNIT
E G×H G×H
K×L
D
C
C
D
D
C
C
K×L
A B B
A B B Dimension(mm) Weight(kg)
Model HZK
A B C D E G H K L 4 Rows 6 Rows
02W1 1060 853 690 570 1000 232 262 793 510 129 138
Dimension(mm) Weight(kg) 03W1 1160 953 720 600 1100 298 262 893 540 148 155
Model HZK
A B C D E G H K L 4 Rows 6 Rows 04W1 1160 1053 790 670 1100 331 289 993 610 167 175
02L1 640 900 1120 1000 580 232 262 840 390 137 143
05W1 1160 1053 920 800 1100 309 341 993 740 186 197
03L1 640 1000 1220 1100 580 298 262 940 490 153 160
06W1 1160 1153 990 870 1100 395 341 1093 810 211 223
04L1 640 1100 1320 1200 580 331 289 1040 550 175 183
07W1 1260 1203 1070 950 1200 373 404 1143 890 242 257
05L1 720 1100 1520 1400 660 309 341 1040 700 206 216
08W1 1260 1353 1070 950 1200 373 404 1293 890 256 282
06L1 720 1200 1620 1500 660 395 341 1140 750 231 244
09W1 1410 1353 1170 1050 1350 430 478 1293 990 299 318
07L1 800 1200 1720 1600 740 373 404 1140 800 257 272
08L1 800 1400 1720 1600 740 373 404 1340 800 272 289 10W1 1410 1553 1170 1050 1350 430 478 1493 990 325 342
09L1 930 1400 1920 1800 870 430 478 1340 900 326 344 12W1 1460 1703 1170 1050 1400 557 478 1643 990 350 376
10L1 930 1600 1920 1800 870 430 478 1540 900 360 376 13W1 1360 1953 1170 1050 1300 1040 404 1893 990 442 459
12L1 930 1700 1920 1800 870 557 478 1640 900 367 394 15W1 1360 1953 1270 1150 1300 1040 404 1893 1090 447 470
13L1 930 2000 1920 1800 870 1040 404 1940 900 481 518
18W1 1510 2153 1320 1200 1450 1203 478 2093 1140 539 580
15L1 930 2000 2020 1900 870 1040 404 1940 1000 491 520
21W1 1510 2353 1370 1250 1450 1203 478 2293 1190 584 626
18L1 960 2200 2120 2000 900 1203 478 2140 1050 570 611
24W1 1510 2653 1390 1250 1450 1572 478 2593 1190 644 692
21L1 960 2500 2120 2000 900 1203 478 2440 1050 631 673
27W1 1510 2653 1520 1380 1450 1572 478 2593 1320 728 781
24L1 960 2800 2220 2100 900 1572 478 2740 1150 682 730
30W1 1560 2653 1640 1500 1500 1572 478 2593 1440 761 813
27L1 960 2800 2320 2200 900 1572 478 2740 1200 735 789
30L1 960 2800 2420 2300 900 1572 478 2740 1350 786 845 33W1 1610 2903 1640 1500 1550 1588 569 2843 1440 882 947
33L1 1060 3100 2420 2300 1100 1588 569 3040 1300 952 1018 35W1 1710 3053 1640 1500 1650 1776 638 2993 1440 953 1022
35L1 1160 3200 2520 2400 1100 1776 638 3140 1300 1020 1089 40W1 1760 3053 1893 1753 1700 1776 638 2993 1693 986 1099
40L1 1160 3400 2620 2500 1100 1776 638 3340 1400 1067 1181 45W1 1760 3053 2020 1880 1700 1776 638 2993 1820 1070 1187
45L1 1160 3600 2720 2600 1100 1776 638 3540 1500 1112 1129
50W1 1760 3153 2150 2010 1700 1776 638 3093 1950 1097 1231
50L1 1160 3800 2720 2600 1100 1776 638 3740 1500 1194 1330
Note:
Note: 1. If the plate primary filter is adopted, the size of A need to be increased by 40mm.
1. If the plate primary filter is adopted, the size of A need to be increased by 40mm. 2. If the air flow of the unit is horizontal, the size of C should be reduced by 40mm.
2. The dimensions in the above table is for the units of HZKA series whose skin thickness is 25mm. And for the units of HZKB series whose skin thickness is 50mm, 3. The dimensions in the above table is for the units of HZKA series whose skin thickness is 25mm. And for the units of HZKB series whose skin thickness is 50mm,
the extra dimension of 25mm should be added accordingly. the extra dimension of 25mm should be added accordingly.
73 74
AIR HANDLING UNIT
Mixing Section+Plate Primary Filter+Coil+(Wet-film Humidifier)+Fan Mixing Section+Plate Primary Filter+Medium Efficiency Filter+Coil+Fan
E E
G×H G×H K×L G×H G×H
K×L
K×L
K×L
D
C
C
D
D
C
C
A B B
A B B
02W2 1540 853 690 570 1500 232 262 600 160 158 164 02W3 1990 853 690 570 1950 232 262 600 160 176 181
03W2 1640 953 720 600 1600 298 262 600 300 177 184 03W3 2040 953 720 600 2000 298 262 600 300 197 201
04W2 1640 1053 790 670 1600 331 289 700 300 201 208 04W3 2090 1053 790 670 2050 331 289 700 300 224 232
05W2 1640 1053 920 800 1600 309 341 800 300 230 240 05W3 2090 1053 920 800 2050 309 341 800 300 249 259
06W2 1640 1153 990 870 1600 395 341 900 300 261 274 06W3 2090 1153 990 870 2050 395 341 900 300 282 295
07W2 1740 1203 1070 950 1700 373 404 1000 300 288 303 07W3 2190 1203 1070 950 2150 373 404 1000 300 310 324
08W2 1740 1353 1070 950 1700 373 404 1100 300 319 335 08W3 2190 1353 1070 950 2150 373 404 1100 300 345 362
09W2 1990 1353 1170 1050 1950 430 478 1000 440 343 362 09W3 2440 1353 1170 1050 2400 430 478 1000 440 394 412
10W2 1990 1553 1170 1050 1950 430 478 1100 440 392 408 10W3 2440 1553 1170 1050 2400 430 478 1100 440 433 450
12W2 2040 1703 1170 1050 2000 557 478 1200 440 426 452 12W3 2490 1703 1170 1050 2450 557 478 1200 440 471 494
13W2 1940 1953 1170 1050 1900 1040 404 1300 440 525 554 13W3 2390 1953 1170 1050 2350 1040 404 1300 440 574 598
15W2 1940 1953 1270 1150 1900 1040 404 1500 440 569 597 15W3 2390 1953 1270 1150 2350 1040 404 1500 440 622 645
18W2 2090 2153 1320 1200 2050 1203 478 1700 440 652 693 18W3 2540 2153 1320 1200 2500 1203 478 1700 440 727 759
21W2 2090 2353 1370 1250 2050 1203 478 1900 440 707 750 21W3 2540 2353 1370 1250 2500 1203 478 1900 440 809 842
24W2 2090 2653 1390 1250 2050 1572 478 2200 440 780 829 24W3 2540 2653 1390 1250 2500 1572 478 2200 440 885 922
27W2 2290 2653 1520 1380 2250 1572 478 2200 580 912 965 27W3 2740 2653 1520 1380 2700 1572 478 2200 580 978 1022
30W2 2340 2653 1640 1500 2300 1572 478 2300 580 958 1017 30W3 2790 2653 1640 1500 2750 1572 478 2300 580 1033 1092
33W2 2390 2903 1640 1500 2350 1588 569 2400 580 1084 1149 33W3 2840 2903 1640 1500 2800 1588 569 2400 580 1185 1250
35W2 2490 3053 1640 1500 2450 1776 638 2400 580 1170 1239 35W3 2940 3053 1640 1500 2900 1776 638 2400 580 1246 1316
40W2 2540 3053 1893 1753 2500 1776 638 2600 580 1202 1315 40W3 2940 3053 1893 1753 2900 1776 638 2600 580 1306 1400
45W2 2540 3053 2020 1880 2500 1776 638 2800 580 1285 1403 45W3 2940 3053 2020 1880 2900 1776 638 2800 580 1421 1539
50W2 2640 3153 2150 2010 2600 1776 638 2800 630 1324 1459 50W3 3040 3153 2150 2010 3000 1776 638 2800 630 1462 1597
Note: Note:
1. The dimensions in the above table is for the units of HZKA series whose skin thickness is 25mm. And for the units of HZKB series whose skin thickness is 50mm, 1. The dimensions in the above table is for the units of HZKA series whose skin thickness is 25mm. And for the units of HZKB series whose skin thickness is 50mm,
the extra dimension of 25mm should be added accordingly. the extra dimension of 25mm should be added accordingly.
2. The units with air flow more than or equal to 4000m 3/h has two surface air coolers. 2. The units with air flow more than or equal to 4000m3/h has two surface air coolers.
75 76
AIR HANDLING UNIT
Air Flow Rows of Power Input (kW) Under Certain ESP (Pa)
E ModelHZK Heat
K×L (m3/h) Exchanger 120 170 220 270 320 370 420 470 520 570 620
G×H G×H
4 0.55 0.55 0.55 0.55 0.55
02L1 2000
6 0.55 0.55 0.55 0.55 0.75
K×L
D
C
C
4 1.1 1.1 1.1 1.1 1.1 1.5
04L1 4000
6 1.1 1.1 1.1 1.1 1.5 1.5
4 1.1 1.1 1.1 1.5 1.5 1.5
05L1 5000
6 1.1 1.1 1.5 1.5 1.5 1.5
B B 4 1.5 1.5 1.5 2.2 2.2 2.2
A 06L1 6000
6 1.5 1.5 2.2 2.2 2.2 2.2
4 1.5 1.5 1.5 2.2 2.2 2.2 2.2
07L1 7000
6 1.5 1.5 2.2 2.2 2.2 2.2 2.2
4 2.2 2.2 2.2 2.2 2.2 3.0 3.0
08L1 8000
Dimension(mm) Weight(kg) 6 2.2 2.2 2.2 2.2 3.0 3.0 3.0
Model HZK 2.2 2.2
4 2.2 2.2 3.0 3.0 3.0
A B C D E G H K L 4 Rows 6 Rows 09L1 9000
6 2.2 2.2 2.2 3.0 3.0 3.0 3.0
02W4 1990 853 720 600 1950 232 262 600 160 188 193
4 2.2 3.0 3.0 3.0 3.0 3.0 4.0
10L1 10500
03W4 2040 953 790 670 2000 298 262 600 300 215 219 6 3.0 3.0 3.0 3.0 3.0 4.0 4.0
04W4 2090 1113 289 300 254 262 4 2.2 3.0 3.0 3.0 3.0 4.0 4.0 4.0 4.0
790 670 2050 331 700
12L1 12000
6 3.0 3.0 3.0 3.0 4.0 4.0 4.0 4.0 5.5
05W4 2090 111 3 920 800 2050 309 341 800 300 279 289
4 3.0 3.0 3.0 4.0 4.0 4.0 4.0 5.5 5.5
06W4 2090 1153 870 2050 395 341 900 300 312 325 13L1 13500
990 6 3.0 3.0 4.0 4.0 4.0 4.0 5.5 5.5 5.5
07W4 2190 1203 1170 1050 2150 373 404 1000 300 352 366 4 3.0 4.0 4.0 4.0 5.5 5.5 5.5 5.5 5.5
15L1 15000
6 4.0 4.0 4.0 5.5 5.5 5.5 5.5 5.5 7.5
08W4 21 90 1353 1170 1050 2150 373 404 1100 300 387 404
4 5.5 5.5 5.5 5.5 7.5 7.5 7.5
09W4 2440 1453 1170 1050 2400 430 478 1000 440 442 460 18L1 18000
6 5.5 5.5 5.5 7.5 7.5 7.5 7.5
10W4 2440 1553 1170 1050 2400 430 478 1100 440 493 510 4 5.5 7.5 7.5 7.5 7.5 11.0 11.0
21L1 21000
12W4 2490 1703 1170 1050 2450 557 478 1200 440 531 554 6 7.5 7.5 7.5 7.5 11.0 11.0 11.0
4 5.5 7.5 7.5 7.5 11.0 11.0 11.0 11.0
13W4 2390 1953 1170 1050 2350 1040 404 1300 440 646 670 24L1 24000
6 7.5 7.5 7.5 11.0 11.0 11.0 11.0 11.0
15W4 2390 2103 1270 1150 2350 1040 404 1500 440 712 735 7.5 7.5 11.0 11.0 11.0
4 11.0 11.0 11.0 15.0
27L1 27000
18W4 2540 2153 1320 1200 2500 1203 478 1700 440 817 849 6 7.5 11.0 11.0 11.0 11.0 11.0 11.0 15.0 15.0
4 11.0 11.0 11.0 11.0 11.0 15.0 15.0 15.0 15.0
21W4 2540 2353 1420 1300 2500 1203 478 1900 440 917 950 30L1 30000
6 11.0 11.0 11.0 11.0 15.0 15.0 15.0 15.0
24W4 2540 2653 1440 1300 2500 1572 478 2200 440 1005 1042
4 11.0 11.0 11.0 11.0 15.0 15.0 15.0 15.0 15.0
33L1 33000
27W4 2740 2653 1520 1380 2700 1572 478 2200 580 1110 1154 6 11.0 11.0 11.0 15.0 15.0 15.0 15.0 15.0 15.0
30W4 2790 2803 1640 1500 2750 1572 478 2300 580 1177 1236 4 11.0 11.0 15.0 11.0 11.0 15.0 15.0 15.0 15.0
35L1 35000
6 11.0 11.0 11.0 11.0 15.0 15.0 15.0 15.0 15.0
33W4 2840 2903 1640 1500 2800 1588 569 2400 580 1329 1394
4 11.0 15.0 15.0 15.0 15.0 15.0 18.5 18.5
35W4 2940 3153 1640 1500 2900 1776 638 2400 580 1414 1484 40L1 40000
6 15.0 15.0 15.0 15.0 15.0 18.5 18.5 18.5
40W4 2940 3053 1893 1753 2900 1776 638 2600 580 1498 1592 4 15.0 15.0 15.0 18.5 18.5 18.5 18.5 22.0
45L1 45000
45W4 2940 3053 1755 6 15.0 15.0 18.5 18.5 18.5 18.5 22.0 22.0
2043 1903 2900 1776 638 2800 580 1637
4 18.5 18.5 18.5 22.0 22.0 22.0
50W4 3040 3153 2150 2010 3000 1776 638 2800 680 1714 1849 50L1 50000
6 18.5 18.5 22.0 22.0 22.0
Note:
1. The dimensions in the above table is for the units of HZKA series whose skin thickness is 25mm. And for the units of HZKB series whose skin thickness is 50mm,
the extra dimension of 25mm should be added accordingly.
2. The units with air flow more than or equal to 4000m 3/h has two surface air coolers.
77 78
AIR HANDLING UNIT
Model Air Flow Rows of Power Input (kW) Under Certain ESP (Pa) Model Air Flow Rows of Power Input (kW) Under Certain ESP (Pa)
HZK (m 3/h) Heat Exchanger HZK (m3/h) Heat Exchanger
170 220 270 320 370 420 470 520 570 170 220 270 320 370 420 470 520 570
4 0.55 0.55 0.55 0.55 0.75 4 0.55 0.55 0.75 0.75 0.75
02W1 2000 02W2 2000
6 0.55 0.55 0.55 0.75 0.75 6 0.55 0.75 0.75 0.75 0.75
4 0.75 0.75 0.75 1.1 1.1 4 0.75 0.75 1.1 1.1 1.1
03W1 3000 03W2 3000
6 0.75 0.75 1.1 1.1 1.1 6 0.75 1.1 1.1 1.1 1.1
4 1.1 1.1 1.1 1.1 1.5 4 1.1 1.1 1.1 1.5 1.5
04W1 4000 04W2 4000
6 1.1 1.1 1.1 1.5 1.5 6 1.1 1.1 1.5 1.5 1.5
4 1.1 1.5 1.5 1.5 1.5 2.2 4 1.1 1.5 1.5 1.5 1.5
05W1 5000 05W2 5000
6 1.5 1.5 1.5 1.5 2.2 2.2 6 1.5 1.5 1.5 1.5 2.2
4 1.5 2.2 2.2 2.2 2.2 2.2 4 1.5 2.2 2.2 2.2 2.2 2.2
06W1 6000 06W2 6000
6 2.2 2.2 2.2 2.2 2.2 3.0 6 2.2 2.2 2.2 2.2 2.2 3.0
4 1.5 2.2 2.2 2.2 2.2 2.2 4 1.5 2.2 2.2 2.2 2.2 2.2
07W1 7000 07W2 7000
6 2.2 2.2 2.2 2.2 2.2 3.0 6 2.2 2.2 2.2 2.2 2.2 3.0
4 2.2 2.2 2.2 3.0 3.0 3.0 4 2.2 2.2 3.0 3.0 3.0 3.0
08W1 8000 08W2 8000
6 2.2 2.2 3.0 3.0 3.0 3.0 6 2.2 3.0 3.0 3.0 3.0 3.0
4 2.2 2.2 3.0 3.0 3.0 3.0 4 2.2 3.0 3.0 3.0 3.0 4.0
09W1 9000 09W2 9000
6 2.2 3.0 3.0 3.0 3.0 4.0 6 3.0 3.0 3.0 3.0 4.0 4.0
4 3.0 3.0 3.0 3.0 4.0 4.0 4 3.0 3.0 4.0 4.0 4.0 4.0
10W1 10500 10W2 10500
6 3.0 3.0 3.0 4.0 4.0 4.0 6 3.0 4.0 4.0 4.0 4.0 4.0
4 3.0 3.0 3.0 4.0 4.0 4.0 4 3.0 3.0 4.0 4.0 4.0 5.5
12W1 12000 12W2 12000
6 3.0 3.0 4.0 4.0 4.0 4.0 6 3.0 4.0 4.0 4.0 5.5 5.5
4 3.0 4.0 4.0 4.0 4.0 5.5 4 4.0 4.0 4.0 4.0 5.5 5.5
13W1 13500 13W2 13500
6 4.0 4.0 4.0 4.0 5.5 5.5 6 4.0 4.0 4.0 5.5 5.5 5.5
4 4.0 4.0 5.5 5.5 5.5 5.5 5.5 4 5.5 5.5 5.5 5.5 5.5 7.5
15W1 15000 15W2 15000
6 4.0 5.5 5.5 5.5 5.5 5.5 7.5 6 5.5 5.5 5.5 5.5 7.5 7.5
4 5.5 5.5 5.5 5.5 7.5 7.5 7.5 4 5.5 5.5 7.5 7.5 7.5 7.5
18W1 18000 18W2 18000
6 5.5 5.5 5.5 7.5 7.5 7.5 7.5 6 5.5 7.5 7.5 7.5 7.5 7.5
4 5.5 7.5 7.5 7.5 7.5 11.0 11.0 4 7.5 7.5 7.5 11.0 11.0 11.0
21W1 21000 21W2 21000
6 7.5 7.5 7.5 7.5 11.0 11.0 11.0 6 7.5 7.5 11.0 11.0 11.0 11.0
4 5.5 7.5 7.5 7.5 11.0 11.0 11.0 4 7.5 11.0 11.0 11.0 11.0
24W1 24000 24W2 24000
6 7.5 7.5 7.5 11.0 11.0 11.0 11.0 6 11.0 11.0 11.0 11.0 11.0
4 7.5 7.5 11.0 11.0 11.0 11.0 11.0 11.0 4 11.0 11.0 11.0 11.0 11.0
27W1 27000 27W2 27000
6 7.5 11.0 11.0 11.0 11.0 11.0 11.0 15.0 6 11.0 11.0 11.0 11.0 15.0
4 11.0 11.0 11.0 11.0 11.0 15.0 15.0 15.0 4 11.0 11.0 15.0 15.0 15.0
30W1 30000 30W2 30000
6 11.0 11.0 11.0 11.0 15.0 15.0 15.0 15.0 6 11.0 15.0 15.0 15.0 15.0
4 11.0 11.0 15.0 15.0 15.0 4 11.0 15.0 15.0 15.0 15.0 15.0
33W1 33000 33W2 33000
6 11.0 15.0 15.0 15.0 15.0 6 15.0 15.0 15.0 15.0 15.0 15.0
4 11.0 11.0 11.0 15.0 15.0 4 11.0 15.0 15.0 15.0 15.0 15.0
35W1 35000 35W2 35000
6 11.0 11.0 15.0 15.0 15.0 6 15.0 15.0 15.0 15.0 15.0 15.0
4 15.0 15.0 15.0 15.0 15.0 4 15.0 15.0 15.0 18.5 18.5
40W1 40000 40W2 40000
6 15.0 15.0 15.0 15.0 18.5 6 15.0 15.0 18.5 18.5 18.5
4 15.0 15.0 18.5 18.5 18.5 4 18.5 18.5 18.5 18.5 22.0
45W1 45000 45W2 45000
6 15.0 18.5 18.5 18.5 18.5 6 18.5 18.5 18.5 22.0 22.0
79 80
AIR HANDLING UNIT
Model Air Flow Rows of Power Input (kW) Under Certain ESP (Pa) Model Air Flow Rows of Power Input (kW) Under Certain ESP (Pa)
HZK (m 3/h) Heat Exchanger HZK (m 3/h) Heat Exchanger
120 170 220 270 320 370 420 470 520 140 190 240 290 340 390 440 490 540
4 0.55 0.75 0.75 0.75 0.75 1.1 1.1 1.1 4 0.55 0.55 0.75 0.75 0.75
02W3 2000 02W4 2000
6 0.75 0.75 0.75 0.75 1.1 1.1 1.1 1.1 6 0.55 0.75 0.75 0.75 0.75
4 0.75 1.1 1.1 1.1 1.1 1.1 1.5 1.5 4 0.75 0.75 1.1 1.1 1.1
03W3 3000 03W4 3000
6 1.1 1.1 1.1 1.1 1.1 1.5 1.5 6 0.75 1.1 1.1 1.1 1.1
4 1.1 1.1 1.5 1.5 1.5 2.2 2.2 2.2 4 1.1 1.1 1.1 1.5 1.5
04W3 4000 04W4 4000
6 1.1 1.5 1.5 1.5 2.2 2.2 2.2 2.2 6 1.1 1.1 1.5 1.5 1.5
4 1.5 1.5 1.5 1.5 2.2 2.2 2.2 2.2 4 1.1 1.5 1.5 1.5 1.5
05W3 5000 05W4 5000
6 1.5 1.5 1.5 2.2 2.2 2.2 2.2 2.2 6 1.5 1.5 1.5 1.5 2.2
4 2.2 2.2 2.2 2.2 2.2 3.0 3.0 3.0 4 1.5 2.2 2.2 2.2 2.2 2.2
06W3 6000 06W4 6000
6 2.2 2.2 2.2 2.2 3.0 3.0 3.0 6 2.2 2.2 2.2 2.2 2.2 3.0
4 2.2 2.2 2.2 2.2 3.0 3.0 3.0 4 1.5 2.2 2.2 2.2 2.2 2.2
07W3 7000 07W4 7000
6 2.2 2.2 2.2 3.0 3.0 3.0 3.0 6 2.2 2.2 2.2 2.2 2.2 3.0
4 2.2 3.0 3.0 3.0 3.0 3.0 4.0 4 2.2 2.2 3.0 3.0 3.0 3.0
08W3 8000 08W4 8000
6 3.0 3.0 3.0 3.0 3.0 4.0 4.0 6 2.2 3.0 3.0 3.0 3.0 3.0
4 3.0 3.0 4.0 4.0 4.0 4 2.2 3.0 3.0 3.0 3.0 4.0
09W3 9000 09W4 9000
6 3.0 4.0 4.0 4.0 4.0 6 3.0 3.0 3.0 3.0 4.0 4.0
4 4.0 4.0 4.0 4.0 5.5 4 3.0 3.0 4.0 4.0 4.0 4.0
10W3 10500 10W4 10500
6 4.0 4.0 4.0 5.5 5.5 6 3.0 4.0 4.0 4.0 4.0 4.0
4 4.0 4.0 5.5 5.5 5.5 4 3.0 3.0 4.0 4.0 4.0 5.5
12W3 12000 12W4 12000
6 4.0 5.5 5.5 5.5 5.5 6 3.0 4.0 4.0 4.0 5.5 5.5
4 4.0 5.5 5.5 5.5 5.5 4 4.0 4.0 4.0 4.0 5.5 5.5
13W3 13500 13W4 13500
6 5.5 5.5 5.5 5.5 7.5 6 4.0 4.0 4.0 5.5 5.5 5.5
4 5.5 5.5 5.5 7.5 7.5 4 5.5 5.5 5.5 5.5 5.5 7.5
15W3 15000 15W4 15000
6 5.5 5.5 7.5 7.5 7.5 6 5.5 5.5 5.5 5.5 7.5 7.5
4 7.5 7.5 7.5 7.5 7.5 4 5.5 5.5 7.5 7.5 7.5 7.5
18W3 18000 18W4 18000
6 7.5 7.5 7.5 7.5 11.0 6 5.5 7.5 7.5 7.5 7.5 7.5
4 7.5 11.0 11.0 11.0 11.0 4 7.5 7.5 7.5 11.0 11.0 11.0
21W3 21000 21W4 21000
6 11.0 11.0 11.0 11.0 11.0 6 7.5 7.5 11.0 11.0 11.0 11.0
4 11.0 11.0 11.0 11.0 11.0 4 7.5 11.0 11.0 11.0 11.0
24W3 24000 24W4 24000
6 11.0 11.0 11.0 11.0 6 11.0 11.0 11.0 11.0 11.0
4 11.0 11.0 11.0 11.0 15.0 4 11.0 11.0 11.0 11.0 11.0
27W3 27000 27W4 27000
6 11.0 11.0 11.0 15.0 15.0 6 11.0 11.0 11.0 11.0 15.0
4 11.0 15.0 15.0 15.0 15.0 4 11.0 11.0 15.0 15.0 15.0
30W3 30000 30W4 30000
6 15.0 15.0 15.0 15.0 6 11.0 15.0 15.0 15.0 15.0
4 15.0 15.0 15.0 15.0 15.0 15.0 4 11.0 15.0 15.0 15.0 15.0 15.0
33W3 33000 33W4 33000
6 15.0 15.0 15.0 15.0 15.0 18.5 6 15.0 15.0 15.0 15.0 15.0 18.5
4 15.0 15.0 15.0 15.0 15.0 15.0 4 11.0 15.0 15.0 15.0 15.0 15.0
35W3 35000 35W4 35000
6 15.0 15.0 15.0 15.0 15.0 18.5 6 15.0 15.0 15.0 15.0 15.0 18.5
4 15.0 15.0 15.0 18.5 18.5 18.5 4 15.0 15.0 15.0 18.5 18.5
40W3 40000 40W4 40000
6 15.0 15.0 18.5 18.5 18.5 18.5 6 15.0 15.0 18.5 18.5 18.5
4 18.5 18.5 18.5 18.5 22.0 22.0 4 18.5 18.5 18.5 18.5 22.0
45W3 45000 45W4 45000
6 18.5 18.5 18.5 22.0 22.0 6 18.5 18.5 18.5 22.0 22.0
81 82
AIR HANDLING UNIT
Specification of Humidifier
Control System
08
there is a switch-type water valve connected, the water valve can be
8000 7 14 19 38 15 31
09 9000 8 16 22 43 17 36
switched off when the indoor temperature reaches the setting value,
10 10500 9 18 25 51 20 42
achieving energy saving.
12 12000 10 20 28 57 23 47
13 13500 12 24 33 66 26 54
15 15000 13 25 35 70 28 58
Features
18 18000 15 30 42 83 33 69
21 21000 18 35 49 97 39 80
Control Cabinet
24 24000 20 40 55 111 44 92
27 27000 22 44 62 123 49 102 Professional design, integrated control, reasonable wiring and various protections;
30 30000 24 49 68 136 54 112 Standardized design for convenient installation;
33 33000 27 54 75 150 60 124 Various external interlocks, reserved control signals for fire valve, fresh air valve (stop or start together with the fan motor)
35 35000 28 57 79 158 63 130 and water valve;
40 40000 31 62 86 172 69 142 Control cabinet can be installed before shipment, simplifying the installation progress on site.
45 45000 35 69 96 193 77 159
Temperature Controller
Wet-film Humidifier Grand and elegant appearance, large size LCD, one-button booting;
Multiple states display;
The wet-film humidifier is made of hydrophilic materials, which can evenly distribute the water absorbed on the surface of the
Built-in temperature sensor to display the indoor temperature;
material to form a vaporized layer of water. When the air flows through the surface of the material, the water in the vaporized
Equipped with high reliability microcontroller.
layer is evaporated and absorbed by the air flow. The thickness of the wet film can be 50mm or 100mm according to the amount
of humidification, and the water supply is 3 times of the amount of humidification. Note: The control cabinet and the temperature controller are optional.
83 84
AIR HANDLING UNIT
Drainage Ditch
Foundation
Temperature Controller
High Mid Low
L=Unit L
Floor Drain- on the same side of W=Unit
A
sondensate pipe
Live On H=Foun
A
sondensate pipe
85 86
CEILING SUSPENDED AHU
Ceiling suspended air handling unit is mainly composed of filter, coil and fan,
etc. and can meet various static pressure needs. Because of its compact struc-
ture, light weight, excellent cooling performance, and the optional components
of electric heater, wet-film humidifier or electrical controller, the ceiling type air
handling unit can be widely used in the places with centralized air handing
demands such as shopping malls, hotels, office buildings and so on. The units
with air flow of less than 2500m3/h is direct-driven type and units with air flow of
more than 3000m3/h is belt-driven type. 2000~15000m3/h
*If the unit is planned to be installed near the coast or in the chemical-corrosion environment,
please firstly consult with our local engineer.
Facing the air flow, if water piping at left side indicates left type. Otherwise, right
type.
Air flow direction
Nomenclature
Air flow direction
HKGE - 02 D A / S D C 300 H Z BN # d D
Design Code: C
87 88
CEILING SUSPENDED AHU
HKGE-02DA 2000 11.5 21.2 0.55 59.2 32 14.9 25.3 0.71 84.9 32 25 BVDB
Prevention Of Cold Bridge and Rust HKGE-03DA 3000 17.5 32.0 0.83 63.8 32 22.0 37.3 1.05 76.2 32 25
All metals inside the labyrinth body are isolated from the outside by means of polyurethane foam
and specially designed seals, avoiding the sticking of insulation strips everywhere inside the hous- HKGE-04DA 23.4 41.5 1.13 89.7 32 1.43 87.1 32
4000 30.1 49.1 25
ing as the common AHU and it simply eliminates the cold bridge problem (cold bridge factor of unit Conven�onal
Conventional
AHU AHU
is up to 0.88, TB1 grade by reference to European Standard EN1886-2007). All panels are inlaid
with aluminum profile frame on all edges so that the corners and edges of sheet metal are totally HKGE-05DA 5000 28.3 51.4 1.37 76.2 32 35.2 61.8 1.68 47.3 40 25
isolated from air and moisture, thereby prevent-ing rust spot on panels
HKGE-06DA 6000 34.5 61.7 1.64 86.4 32 43.7 73.9 2.08 76.0 40 25
AC 3Φ,
Belt
380V/
Integrated Seamless Water Tray with No Water Leakage Integral stamping and
driven
seamless water tray HKGE-07DA 7000 40.3 71.3 1.92 81.0 32 49.4 85.3 2.35 70.6 40 25 50Hz
The AHU adopts the integrated water tray which is possessed by the advanced German-made
spraying equipment and then pasted with the integral insulation material. It is installed on the
bottom of the AHU on the full size, so that there will be no water leakage worry during operation. HKGE-08DA 8000 46.2 83.1 2.20 81.2 32 57.6 98.3 2.74 89.9 40 25
Integral Insulation
HKGE-10DA 10000 59.9 108.1 2.85 88.9 40 75.1 135.3 3.58 55.8 50 25
Mechatronics Control HKGE-12DA 12000 69.3 131.7 3.30 89.8 40 85.8 161.1 4.09 76.9 50 25
Adopt the large LCD controller, which can realized one-button booting and automatic operation,
various working conditions display. High reliability microcontroller is configured with high anti-in-
HKGE-15DA 15000 85.3 162.8 4.06 89.8 50 108.5 189.7 5.17 77.5 50 32
terference. The main components are supplied by international famous brands for reliable and
guaranteed quality. Various external interlocks are adopted. Control signals for fire valve, fresh air
valve and water valve are reserved.
Note:
1. Standard cooling conditions: chilled water inlet/outlet at 7/12℃; air inlet at 27℃DB/19.5℃WB.
2. Standard heating conditions: hot water inlet/outlet at 60/50℃; air inlet at 15℃DB.
4. The water flow in the above table is the chilled water flow rate, and the heated water flow rate is smaller than the chilled water flow rate.
So the model selection of the pump shall refer to the chilled water flow.
89 90
CEILING SUSPENDED AHU
m3/h kW kW I/s kPa DN kW kW I/s kPa DN DN 3 0.32 0.37 0.37 0.45 0.45
0.32
HKGE-02DA 2000
5 0.32 0.37 0.37 0.45 0.45 0.55
HKGE-02DA 2000 27.0 27.5 1.29 84.8 32 31.2 31.3 1.49 64.6 32 25 BVDB
HKGE-03DA 3000
HKGE-03DA 3000 39.9 40.9 1.90 87.0 32 45.8 45.1 2.18 80.5 32 25 5 0.75 0.75 0.75 0.75 1.1 1.1 1.1
HKGE-04DA 4000
HKGE-04DA 4000 49.7 51.1 2.37 79.9 32 63.8 61.8 3.04 66.3 40 25
5 1.1 1.1 1.1 1.1 1.1 1.5 1.5
HKGE-05DA 5000 64.5 64.0 3.07 84.0 32 75.4 70.3 3.59 81.6 40 25 HKGE-05DA 5000
5 1.1 1.1 1.1 1.5 1.5 1.5 1.5
HKGE-08DA 8000 99.0 101.7 4.71 87.7 50 120.7 119.7 5.75 85.7 50 25 3 2.2 2.2 2.2 2.2 2.2 3.0 3.0
HKGE-08DA 8000
5 2.2 2.2 2.2 2.2 3.0 3.0 3.0
HKGE-10DA 10000 133.1 133.3 6.34 50.6 65 160.2 157.9 7.63 60.2 65 25
3 2.2 3.0 3.0 3.0 3.0 3.0 3.0
HKGE-10DA 10000
5 3.0 3.0 3.0 3.0 3.0 3.0 4.0
HKGE-12DA 12000 149.4 155.1 7.12 69.1 65 185.2 180.4 8.20 82.1 65 25
3 3.0 3.0 3.0 4.0 4.0 4.0
HKGE-12DA 12000
5 3.0 3.0 4.0 4.0 4.0 4.0
HKGE-15DA 15000 184.2 200.2 8.77 69.1 65 244.7 237.1 10.65 82.1 65 32
HKGE-15DA 15000
5 4.0 5.5 5.5 5.5
Note:
1. Standard cooling conditions: chilled water inlet/outlet at 7/12℃; air inlet at 35℃DB/28℃WB.
2. Standard heating conditions: hot water inlet/outlet at 60/50℃; air inlet at 7℃DB.
4. The water flow in the above table is the chilled water flow rate, and the heated water flow rate is smaller than the chilled water flow rate.
So the model selection of the pump shall refer to the chilled water flow.
91 92
CEILING SUSPENDED AHU
Waterinlet Pipe The onboard control system of HKGE is adopted to control the fan and the water valve of 220V. The control system is mainly
Junction Suspending Hole composed of low-voltage electrical components and temperature controllers of well-known brands. When the temperature
Box
controller with the communication function is configured, it can be easily connected with the third-party control system such as
BMS to achieve remote and networked monitoring. Besides, the control cabinet is equipped with multiple protections of short
Condensate Pipe
circuit, power loss and overload, etc. to ensure the reliable operation. If there is a switch-type water valve connected, the water
valve can be switched off when the indoor temperature reaches the setting value, achieving energy saving.
Flange of Flange of
M N Return Air
A B C D E F Air Outlet J K L P Q R Weight(kg)
Model L×W(mm) (L×W)(mm)
(mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) 3 rows 5 rows 3 rows 5 rows (mm) (mm) (mm)
G H S T 3 rows 5 rows
HKGE-
1007 545 900 843 505 800 302 275 122 277 385 108 86 64 108 150 413 90 783 445 71 81
02DA
HKGE-
03DA
1167 625 950 1003 585 850 302 262 184 226 385 108 86 64 108 150 514 90 943 525 90 121 Features
HKGE-
04DA 1387 625 950 1223 585 850 331 289 146 356 385 108 86 64 108 150 514 90 1163 525 99 129
Control Cabinet
HKGE-
05DA 1567 635 950 1403 585 850 331 289 156 446 385 108 86 64 108 150 514 90 1343 525 128 158
Professional design, integrated control, reasonable wiring and various protections;
Standardized design for convenient installation;
Various external interlocks, reserved control signals for fire valve, fresh air valve (stop or start together with the fan motor)
Wateroutlet Pipe and water valve;
Control cabinet can be installed before shipment, simplifying the installation progress on site.
Waterinlet Pipe
Junction Suspending Hole
Box
Temperature Controller
Condensate Pipe
HKGE-
12DA 2477 790 1050 2313 740 950 1114 341 214.5 437 385 108 86 64 108 108 155 667 90 2253 680 287 311
HKGE-
15DA 2477 940 1150 2313 890 1050 1040 404 214.5 557 385 108 86 94 108 108 155 819 90 2253 830 372 414
Note:
1. The above size of the units does not include the size of heating coil. If heating coil needs to be added, the value of F needs to be increased by 100m.
2. The size and weight of control cabinet are not included in the above table.
3. 25(20) is the distance between the lifting hole and the outer edge of the bottom frame. 20 is for the unit HKGE-02*-HKGE-04*, and 25 is for the other.
93 94
CEILING SUSPENDED AHU
380V/3N/50Hz
N PE
OF
T1
R1 S1 T1 FR
4 5 6
KW
KM
R1 S1 T1 2
Live
Line
Earth 3
Valve
U V W U1 V1 W1 Line
Solenoid Valve
FAN FAN
N
Blower Exhaust Fan (if any)
7 KM 8
Fresh Air Valve
97 98 99
Nomenclature Ceiling Concealed Fan Coil Unit Cassette Fan Coil Unit
100 104
Specification Dimensions
95 96
FAN COIL UNIT
HFPE- 34 W A/ S D F 12 Y 03# X
Return air box type: X-Return air box at the bottom, Default- Without return air box
Design code: F
Air volume code: Specifications×10m3/h The unit is designed with compact body and excellent ap- The fan motor with new design
pearance. The height of the unit is as thin as 230mm, is high efficiency and con-
Name code: fan coil unit which can fit into the narrowest ceiling spaces, saving sumes less electricity. Besides,
ceiling spaces for higher room height without compromis- the motor protection class is
ing users' comfort and satisfaction; Besides, ceiling con- IP44, which reduces the risk of
cealed design can match with various interior decorations. use and ensures the long-term
reliable operation.
Multiple Static Pressure Choices
Users can freely choose the products with static pressure High-quality Condensate Water Pan
of 12Pa, 30Pa and 50Pa according to their needs, to meet
the requirements of air supply distance in different occa- The condensate water pan is
sions. made from one-piece stretched
metal without solder joints or
3 Fan Speed welds. Also the design of dou-
Three fan speeds are available to satisfy the various ble-sided plastic spray ensures
97 98
FAN COIL UNIT
H 340 510 680 850 1020 1190 1360 1700 2040 2380
Airflow rate(m3/h)
M 255 383 510 638 765 893 1020 1275 1530 1785
(ESP 12Pa,30Pa,50Pa)
L 170 255 340 425 510 595 680 850 1020 1190
Total H 2250 3350 4300 5100 5770 6650 8250 9350 11200 13100
Cooling
capacity(W) Sensible H 1598 2379 3053 3621 4097 4722 5858 6639 7952 9301
Heating capacity(45 ℃ water inflow)(W) H 2250 3350 4300 5100 5770 6650 8250 9350 11200 13100
Heating capacity(60 ℃ water inflow)(W) H 3550 5400 6850 8450 9530 11200 13600 15850 18400 21550
360°Surround Air Flow for Comfort Standard with High Head Drain Pump L 35 46 56 70 91 105 119 171 198 246
H 35.0 36.5 40.5 43.0 45.0 46.0 45.0 48.0 49.0 51.0
4-way cassette fan coil units could achieve 360 °surround The drain pump with high head of 750mm is built in the
air delivery to obtain a more uniform air temperature unit, so the condensate water piping can be more flexibly. 12Pa M 28.5 31.0 33.0 36.3 39.5 40.3 40.0 42.0 44.3 44.0
distribution. What's more, the float switch is also equipped, which can
L 22.0 23.0 24.0 26.0 30.0 34.0 30.0 36.0 33.4 34.5
alarm warning due to the malfunction of draining, thus
H 38.0 39.0 42.0 42.0 46.0 45.0 45.0 49.5 48.0 50.0
avoiding leakage of drain water.
Sound pressrue
30Pa M 30.0 31.0 35.0 37.0 39.0 41.0 41.0 44.9 44.0 45.0
dB(A)
Gradient(1/100,1/50) L 24.5 25.5 26.0 27.3 28.0 34.0 32.0 37.0 34.7 41.0
H 40.0 43.0 44.5 46.0 48.0 47.0 49.0 49.5 50.0 51.0
750mm
Connection Hose 50Pa M 32.0 38.0 38.0 40.0 42.0 43.0 43.5 46.0 47.0 47.0
≤300m
Ceiling L 25.5 30.0 31.5 31.0 35.0 37.3 33.0 42.0 44.0 44.5
Water flow rate(m3/h) 0.39 0.58 0.74 0.88 0.99 1.14 1.42 1.61 1.93 2.25
High Efficiency and Low Noise Thanks to the
Cooling 22 27 25 30 25 34 27 38 35 41
Turbo Fan Water pressure drop kPa
Heating 16 24 20 22 21 30 21 30 31 31
The new type of turbo fan uses aviation level 3D spiral
Type Louver aluminum fin mechanically inserted by red copper pipes
blades, which effectively reduces airflow resistance and
Elegant Appearance Coil
expands the heat dissipation area, so that the airflow is Operating pressure 1.6MPa
The 4-way cassette fan coil has beautiful appearance balanced and stable. What’s more, it eliminates vibration Type Front curved multi-wing galvanized steel plate centrifugal fan with double-suction impeller
which could easily match with different interior decoration and noise, and together with low-noise motors, supplying Fan
Quantity 1 2 2 2 2 2 3 4 4 4
styles, offering a pleasant environment. comfortable and quiet environment.
99 100
FAN COIL UNIT
Ceiling Concealed Fan Coil Unit Correction Coefficient of Cooling Capacity under Variable Working Conditions
Quantity 1 1 1 1 1 1 2 2 2 2 WB/℃ Total heat Sensible heat Total heat Sensible heat Total heat Sensible heat Total heat Sensible heat Total heat Sensible heat Total heat Sensible heat
Water inlet/outlet connection pipe Rc 3/4 Taper pipe internal thread 18.0 0.87 0.94 0.87 0.99
Condensate connection pipe R 3/4 Taper pipe external thread
19.0 0.95 0.97 0.99 1.04
Without return air box kg 11 14.5 15 16.5 18 19.5 26 28 31 32.5
With return air box kg 13.8 17.8 18.8 20 22 24 31.5 33.5 37 39 19.5 1 1
W mm 677 817 892 972 1062 1217 1447 1497 1697 1847
Dimensions 20.0 1.03 0.98 1.04 1.06
D mm 469
(Without return air box)
H mm 230 21.0 1.12 1.01
W mm 677 817 892 972 1062 1217 1447 1497 1697 1847
Dimensions
D mm 505
(With return air box)
H mm 249
Heating operation conditions: indoor air inlet temperature: 21℃ DB, Inlet water temperature: 60℃/45℃,The water flow is the same as the cooling condition. Inlet water temperature
2. Rated air volume is tested based on following conditions: standard air condition, dry coil condition(20℃ DB). Model Water flow(m3/h)
35 40 45 50 55 60
3. The sound pressure level is tested in a semi-anechoic room using the unit without return air box and filter.The actual sound value may be different from the data in the above
table due to the influence of environmental noise and other reasons. The sound pressure level of the unit that adopts the bottom return air will be higher than that of the rear HFPE-34WA 0.39 0.34 0.47 0.64 0.77 0.88 1.00
return air.
HFPE-51WA 0.58 0.34 0.47 0.63 0.77 0.88 1.00
4. H, M and L in the table represent high, medium and low fan speeds.
5. The ESP in the table is the value of ESP of air outlet. HFPE-68WA 0.74 0.34 0.47 0.63 0.77 0.88 1.00
6.The performance parameters in the table were measured under the power supply 220V/50Hz.
HFPE-85WA 0.88 0.34 0.47 0.61 0.77 0.88 1.00
7.The indoor unit can change the left / right connection on site. After changing the direction of the connecting pipe, the cooling capacity / heating capacity of the indoor unit
HFPE-102WA 0.99 0.34 0.47 0.62 0.77 0.88 1.00
needs to be corrected with the factor 0.86-0.92.
8.The air volume, cooling capacity and heating capacity in the above table are all measured under the condition of without return air box and filter; For the indoor unit with return HFPE-119WA 1.14 0.34 0.47 0.62 0.77 0.88 1.00
air box at the bottom, the data should be corrected with the factor 0.93~0.96 correspondingly.
HFPE-136WA 1.42 0.34 0.47 0.61 0.77 0.88 1.00
101 102
FAN COIL UNIT
130 32
Inlet-water pipe Rc 3/4"
Cooling Capacity Hole size
M W 2160 2880 3600 4320 5040 5760 7200 8640 10080
Outlet-water pipe Rc 3/4"
R8.5
469
L W 1620 2160 2700 3240 3780 4320 5400 6480 7560 Condensate pipe R 3/4 "
27.5
25 160
154 11
H W 4050 5400 6750 8100 9450 10800 13500 16200 18900
Heating Capacity R5
230
M W 3240 4320 5400 6480 7560 8640 10800 12960 15120
60℃Inlet Water C 10
B
L W 2340 3240 4050 4860 5670 6480 8100 9720 11340 A 29
469
H W 2700 3600 4500 5400 6300 7200 9000 10800 12600
Heating Capacity
45℃Inlet Water M W 2160 2880 3600 4320 5040 5760 7200 8640 10080 Model HFPE-34 HFPE-51 HFPE-68 HFPE-85 HFPE-102 HFPE-119 HFPE-136 HFPE-170 HFPE-204 HFPE-238
A 647 787 862 942 1032 1187 1417 1467 1667 1817
L W 1620 2160 2700 3240 3780 4320 5400 6480 7560
B 470 610 685 765 855 1010 1240 1290 1490 1640
Noise dB(A) 39 41 43 45 46 46 48 50 52
C 444 584 659 739 829 984 1214 1264 1464 1614
D
Current A 0.23 0.27 0.34 0.42 0.51 0.59 0.67 0.83 1
Water Flow m3/h 0.5 0.61 0.78 0.94 1.1 1.2 1.65 1.85 2.15 Hole size The hole size for hook
12
242
R8.5
Water Resistance kPa 30 30 30 40 40 40 40 40 50
506
27.5
Inlet Pipe in ZG3/4"
32
12
160
Pipe Diameter
Outlet Pipe mm φ26 R6
C 10 R5 25
25
Unit mm 660*660*190 660*660*290 760*760*290 860*860*290 B
Dimensions
A 29
(L×D×H)
Panel mm 750*750*45 850*850*45 950*950*45
11
506
32
Inlet-water pipe Rc 3/4"
154
130
230
Condensate pipe R 3/4 "
Notes:
E 190 20
1. Cooling capacity is tested under the condition: inlet air temp. 27℃ DB/19.5℃ WB; inlet water temp. 7℃; outlet water temp. 12℃.
2. Heating capacity(inlet water temp. 60℃) is tested under the condition: inlet air temp. 21℃ DB; inlet water temp. 60℃.
(Tested under the same water flow conditions as the cooling conditions)
Model HFPE-34 HFPE-51 HFPE-68 HFPE-85 HFPE-102 HFPE-119 HFPE-136 HFPE-170 HFPE-204 HFPE-238
3. Heating capacity(inlet water temp. 45℃) is tested under the condition: inlet air temp. 21℃ DB; inlet water temp. 45℃.
A 647 787 862 942 1032 1187 1417 1467 1667 1817
(Tested under the same water flow conditions as the cooling conditions)
B 470 610 685 765 855 1010 1240 1290 1490 1640
4. The sound pressure in the table is measured in the semi-anechoic room (according to GB/T 19232-2019).
C 444 584 659 739 829 984 1214 1264 1464 1614
5. The data in the table are all tested under 220V~/50Hz power supply.
D 545 685 761 841 931 1085 1315 1365 1565 1715
E 451 591 666 746 836 991 1221 1271 1471 1621
103 104