Generator set data sheet
Model: C2250 D5
Frequency: 50 Hz
Fuel type: Diesel
Spec sheet: SS17-CPGK
Noise data sheet: ND50-OSHHP
Airflow data sheet: AF50-HHP
Derate data sheet: DD50-OSHHP
Transient data sheet: RTF
Standby Prime
Fuel consumption kVA (kW) kVA (kW)
Ratings 2250 (1800) 2000 (1600)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
US gph 36.5 60.5 86.6 115.3 30.1 52.7 76.9 103.9
L/hr 138 229 328 437 114 200 291 394
Engine Standby rating Prime rating
Engine manufacturer Cummins
Engine model QSK60-G4
Configuration Cast iron, 60º V16 cylinder
Aspiration Turbocharged and low temperature after-cooled
Gross engine power output, kWm 1915 1730
BMEP at set rated load, kPa 2544 2296
Bore, mm 159
Stroke, mm 190
Rated speed, rpm 1500
Piston speed, m/s 9.5
Compression ratio 14.5:1
Lube oil capacity, L 378
Overspeed limit, rpm 1725 ±50
Regenerative power, kW 146
Governor type Electronic
Starting voltage 24 Volts DC
Fuel flow
Maximum fuel flow, L/hr 1893
Maximum fuel inlet restriction, mm Hg 203
Maximum fuel inlet temperature, °C 70
power.cummins.com
©2018 Cummins Inc. | DS52-CPGK (09/18)
Air Standby rating Prime rating
Combustion air, m3/min 144 136
Maximum air cleaner restriction, kPa 6.2
Exhaust
Exhaust gas flow at set rated load, m3/min 337 311
Exhaust gas temperature, °C 450 430
Maximum exhaust back pressure, kPa 6.7
Standard set-mounted radiator cooling
Ambient design, °C 40
Fan load, kW m 33
Coolant capacity (with radiator), L 456
Cooling system air flow, m3/sec @ 12.7 mm H2O 26.4
Total heat rejection, Btu/min 54030 48080
Maximum cooling air flow static restriction mm H2O 12.7
Weights* Open Enclosed
Unit dry weight kgs 15095
Unit wet weight kgs 16160
* Weights represent a set with standard features. See outline drawing for weights of other configurations.
Dimensions Length Width Height
Standard open set dimensions mm 6175 2286 2537
Enclosed set standard dimensions mm
Genset outline
Open set
Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.
power.cummins.com
©2018 Cummins Inc. | DS52-CPGK (09/18)
Alternator data
Connection Temp rise ºC Duty Alternator Voltage
Wye, 3-phase 150/125 S/P PI734G 400 – 440 V
Wye, 3-phase 105* P PI734G 400 – 440 V
Wye, 3-phase 150/125 S/P MVSI804R 3300 V
Wye, 3-phase 125/105 S/P HVSI804R 6300 – 6600 V
Wye, 3-phase 105/80 S/P HVSI804R,S 10500 – 11000 V
*Option available only through ETO (Engineering to Order)
Ratings definitions
Emergency Standby Limited-Time Running Prime Power (PRP): Base Load (Continuous)
Power (ESP): Power (LTP): Power (COP):
Applicable for supplying Applicable for supplying Applicable for supplying Applicable for supplying
power to varying electrical power to a constant power to varying electrical power continuously to a
load for the duration of electrical load for limited load for unlimited hours. constant electrical load for
power interruption of a hours. Limited Time Prime Power (PRP) is in unlimited hours. Continuous
reliable utility source. Running Power (LTP) is in accordance with ISO 8528. Power (COP) is in
Emergency Standby Power accordance with ISO 8528. Ten percent overload accordance with ISO 8528,
(ESP) is in accordance with capability is available in ISO 3046, AS 2789,
ISO 8528. Fuel stop power accordance with ISO 3046, DIN 6271 and BS 5514.
in accordance with AS 2789, DIN 6271 and
ISO 3046, AS 2789, DIN BS 5514.
6271 and BS 5514.
Formulas for calculating full load currents:
Three phase output Single phase output
kW x 1000 kW x SinglePhaseFactor x 1000
Voltage x 1.73 x 0.8 Voltage
For more information contact your local Cummins distributor
or visit power.cummins.com
©2018 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of
Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
DS52-CPGK (09/18)