GBU200 Leaflet 6660-2.2

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
80 views2 pages

GBU200 Leaflet 6660-2.2

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Multifunction HMI

- Standard LCD and touch type screens together with mimic option
- 24 configurable tri-state LEDs selectable red/green/yellow provided at the local
human-machine interface
- 7 programmable function keys and direct control buttons for open/close (O/I) and
control authority (43R/L)
- Standard local USB port and three signal monitoring terminals for testing purposes
- Multi-language display

Metering and Recording Bay Control IED


- Measurement of V, I, P, Q, S, f and THM%
- Alarms and events (each with 1,024) can be recorded with 1ms resolution.
- 8 most recent time-tagged fault records including pre-fault and fault values for
currents and voltages in text format
- Disturbance records provided using sampled data from all analog inputs and binary
signals selected, recorded in COMTRADE format

Extensive Hardware Options and Flexible Adaptation


- Comprehensive range of hardware components
- Main Processing/computing board with enhanced processor
- Wide variety of binary input & output combinations
- Plug-in communication module

©Copyright 2017 Toshiba Energy Systems & Solutions Corporation. All rights reserved.
- Flexible hardware combinations to meet specific applications

Function-wise Implementation
- Library of function blocks enables wide application for protection, control,
measurement and other functions
- Protection elements and schemes
- Control schemes
- Metering and recording functions
- Individual function blocks work independently
- Easy IED customisation to add/delete particular function blocks
- Flexible implementation of new functions and modification of specific functions

- The information provided in this catalog is subject to change without


notice.
- The information provided in this catalog is accurate as of 19 October
2017.
- The information provided in this catalog is presented only as a
guide for the application of TOSHIBA products. No responsibility is
assumed by TOSHIBA for any infringements of patents or other
TOSHIBA ENERGY SYSTEMS & SOLUTIONS CORPORATION rights of third parties which may result from its use. No license is
granted by implication or otherwise under any patent or patent rights
of TOSHIBA or others.
72-34, Horikawa-cho, Saiwai-ku Kawasaki-shi, Kanagawa 212-8585, Japan - TOSHIBA products should not be embedded within downstream
Tel +81-44-331-1462 Fax +81-44-548-9540 products production and sale of which are prohibited, under any law
and regulation.
http://www.toshiba-relays.com - Toshiba does not take any responsibility for incidental damage
(including loss of business profit, business interruption, loss of
business information and other pecuniary damage) arising out of the
use or misuse of TOSHIBA products.

Printed in Japan 6660 1710A0


Busbar

The GBU200, bay control unit is implemented on


Bay Control IED Toshiba’s next generation GR-200 series IED
52

CB Open Event
CB Close Recording 50/51 50SEF 67SEF 59

platform and has been designed to provide control, CB Status Fault


Recording 50N/51N 67/67N 27 USB2.0
(front)
CB Disturbance
37 46 59N
protection and monitoring applications for power
Condiotion Recording
Self
Monitoring A V f 49 32 47 RS485

network equipment in electrical substations. This 79/25 W Var pf 46 Cold load 81


Ethernet
74TC Fault
Locator
50BF 46BC ROCOF
powerful and user-friendly IED will provide you Control / Recording / Communication
Monitoring Indication Protection Interface
with the flexibility to meet your application and

engineering requirements in addition to offering

high performance, the highest quality and Features


- For control and monitoring of switchgear, transformers and other equipment or devices in EHV, HV, MV and LV substations
operational peace of mind. - Built-in feeder protection functions
- Suitable for single, double and one- and-a-half circuit breaker arrangements and for both GIS and AIS switchgear applications
- Various models and hardware options for flexible application depending on system requirements and controlled objects

Function / Function /
device number Description GBU200 device number Description GBU200
Control function 32 Directional power protection ○
Control Select-control ● 59 Positive sequence phase over-voltage protection (4 steps) ○
Interlock Interlock ● 59N Earth fault over-voltage protection (4 steps) ○
AutoSEQ Automatic sequential control ● 47 Negative sequence phase over-voltage protection (2 steps) ○
Monitoring Monitoring ● 27 Phase under-voltage protection (4 steps) ○
DCB Double command blocking ● 81 Frequency protection (6 steps) ○
TAP TAP control ● ROCOF Rate of change of frequency (df/dt) (6 steps) ○
DCAI DCAI measurement ○ 51V Voltage restricted overcurrent ○
DCAO DCAO control ○ 85-50N/ Command protection by OC/EF and DOC/DEF schemes ○
Synchrocheck between different network (e.g. between 51N/67N
SYNDIF ●
transmission line and generator plant) 50SOTF Switch on to fault protection ○
MNOVL Manual override ● 21FL Fault locator ○
LoadShed Load shedding ○ ICD Inrush current detection function ○
Protection CLP Cold load protection function ○
50/67, 51/67 Non-directional / directional phase overcurrent protection (4 steps) ○ 79 Autoreclosing function (upto 4 shots) ○
50HS /51HS High-speed overcurrent protection (1 step) ○ 25 Voltage check for autoreclosing ○
50N/67N, Common
Non-directional / directional earth fault overcurrent protection (4 steps) ○
51N/67N TCS Trip circuit supervision ●
50NHS/ VTF VTF detection function ●
High-speed earth fault overcurrent protection (1 step) ○
51NHS
CTF CTF detection function ●
50SEF/51SEF Non-directional / directional sensitive overcurrent protection (2 steps) ○
Event Event, alarm and statistics ●
Non-Directional / directional negative sequence phase over-
46/67 ○ Measurement Measurement ●
current protection (2 steps)
50BF Circuit breaker failure protection (2 stages) ○ PQRQTY Power quality monitoring ○
37 Phase under-current protection (2 steps) ○ Counter Counter ●
46BC Broken conductor protection ○ PLC Programmable logic controller ●
49 Thermal overload protection ○ ●: Standard, ○: Equipped depending on the hardware and model configuration