660MW Emergency Operating Procedure
660MW Emergency Operating Procedure
Page 1 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
INDEX
A. Station/Unit Emergencies
Page 2 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
1 Station Blackout 12
2 Unit Tripping 14
1 19
FD Fan Tripping
2 20
ID Fan Trip
3 21
PA Fan Tripping
4 22
APH main motor Tripped and Auxiliary Motor not started
Page 3 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
32 Bunker Fire 47
Page 5 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
3 59
Deaerator Level High
4 Deaerator Level Low 59
6 TDBFP Tripped 61
11 67
Turbine Vibration High
12 Turbine Bearing Temperature High 69
16 High Eccentricity 73
27 83
LP Exhaust Temperature Shooting Up
28 Gland Steam Pressure Low 84
30 86
Gland Steam Pressure High
31 86
Gland Steam Temperature High
32 Control oil (EH oil) leakage 87
33 88
Control Oil (EH) Oil circulation Pump Failed
34 Seal Oil Pressure Going Low 89
39 Hydrogen Leakage 94
Page 7 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
40 95
Both Vacuum Pump Failed
41 Condenser Vacuum Low 96
42 Condenser Pressure Rise After Vacuum Loss (In Blackouts and Shut 97
Down Condition)
Page 8 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Page 9 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
6 110
DC fails of Motor Feeder
7 High Bus Transfer Blocked 110
17 117
Repeated tripping of rapping motor of ESP
Page 10 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
STATION/UNIT - EMERGENCIES
Page 11 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
1.Station Blackout
Turbine Side:
1. Close MS stop valves, Close HP-LP bypass valves, Close turbine drain MIVs.
2. Open vacuum breakers after isolating all steam lines/drains to condenser and close gland steam supply valves.
3. Close CW hot blow down valve.
4. Start Turbine Lube oil pump. Stop EOP.
5. Start AC seal oil pump (A / B). Stop DC pump.
6. Start AC JOP. Stop DC JOP.
7. Start MD BFP AOP.( Not essential if pump is not in service before blackout )
8. Ensure turbine barring came into service. Otherwise start manual barring.
9. Ensure TDBFPs EOP remains in service as No emergency power to LOP
10. Ensure DCDB and UPS come on AC supply from battery source.
Boiler Side:
1. Ensure running of DC scanner fan. ( No emergency supply for AC fan )
2. Open RH vent valve.
3. Start ID, FD, and PA fans lube oil pumps.
4. Start ID fans bearing cooling fan .( A / B )
5. Start mills lube oil pumps.
DC And UPS:
1. Check the healthiness of battery chargers.( Main plant )
2. Check the healthiness of UPS.( Main plant )
3. Check the healthiness of battery chargers.( switchyard )
4. Check the healthiness of UPS.( switchyard )
Page 12 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Note:
1. Note down the protections acted in Generator, Transformer, switchyard, Boiler, Turbine. Switchgear.
2. Check for TG vibration during coasting down and note down the coasting down time and max vibration
3. Remove all 6.6 KV from Stand-by mode and give one stop command pulse.
4. Ensure that all normally open tie breakers of 6.6/11 KV buses are open
5. Turbine, Boiler lifts will be available, don’t operate lifts and isolate the power supply after park at 0mtr with caution tag.
6. All MOVs, Motor operated dampers will be available on emergency power.
Normalization:
After blackout 11kv, 6.6 kV switchgear incomers, Motor feeders, PCC incomers will open on under voltage. MCC incomers
will remain close. CHP, CW 6.6 kV breakers will remain close. Operate all breakers from control room with local operator
clearance.
1. Co-ordinate with 220 KV/400 KV switchyard operators for power restoration.
2. Charge ST 5, 6 once power is available.
3. Charge Station switchgears , Unit switchgears.(11, 6.6 KV)
4. Charge Boiler PCC, Turbine PCC, ESP PCC.
5. Charge lighting PCC, Maintenance PCC.
6. Charge Water supply PCC , Chemical water PCC.( DM plant )
7. Normalize EPCC and stop DG.
8. Charge CMCTF PCCs ( CT )
9. Charge CHP PCC.
10. Start TD BFPs lube oil pumps. Stop DC pumps.( No emergency supply for AC pumps )
11. Start AC scanner fan. Stop DC fan. ( No emergency supply for AC fan )
12. Ensure DM plant, RO plant and CHP power restored.
13. Start service water pump.
14. Start air compressor and dryer.
15. Start circulating water pump as per SOP.
16. Start CTP.
17. Start ACW pump
18. Start CCCW pump.
19. Start control room air conditioning.
20. Stop diesel fire pumps.
21. Check the healthiness of battery chargers, UPS.
Page 13 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
2.Unit Tripping
Likely causes:
1. Tripping of air compressor.
2. Sudden increase in consumption.
3. Malfunction of air compressor.
4. Instrument air receiver air leak/Drain valve might be in opened condition.
5. Tripping of Station transformer.
6. Tripping of Service water pumps.
7. Tripping of compressor lube oil pumps due to power supply failure.
8. Instrument air piping failure at valve flange or pipe welding joints.
Plant Response:
1. TDBFP, MDBFP recirculation valve will open fully.
2. All extraction NRVs will close on air failure.
3. Ventilation valve will open fully.
4. BDV valve will open.
5. CEP recirculation will open fully.
6. Stator CW PCV,TCV will open fully.
7. All heaters emergency control valve will open fully.
8. All extraction line drains will open.
9. MSV,MSCV,HRH CV,CRH line drains will open.
10. Deaerator overflow valve will open .
Parameters of Concern:
1. Sudden drop in condenser vacuum.
2. Feedwater flow will decrease.
3. OHDR will rise suddenly.
4. Condensate flow will go down;
5. Unit load will rise.
6. SH,RH temperature will rise.
7. Mill HAGs will not operate.
8. Deaerator level will drop.
Page 15 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. Proper charging procedure not followed.(eg: Auxiliary steam header, Heaters charging)
2. Sudden entry of steam into water lines.
3. Sudden entry of steam into improperly drained pipelines.
4. Improper warm up during charging steam lines.
5. Faulty drain traps.
6. Sudden opening of high pressure valves.
7. Temperature difference between medians.
8. Improper venting of heaters on water side.
9. Sudden start/stop of high pressure pumps.
10. Not priming the lines before starting.
Plant Response:
1. Abnormal sound.
2. Damage to pipe lines.
3. Damage to hangers.
Parameters of Concern:
1. Thermal shock to piping system.
2. Pipe line failure.
3. Check hangers and supporting systems.
Page 16 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Page 17 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Page 18 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. ID fan Tripped & general interlock is in service.
2. Respective APH tripped.
3. FD fan bearing bush vibration > 7.1 mm/s.
4. Hydraulic oil supply pressure low & low low.
5. Fan bearing temperature high > 95°C.
6. Motor bearing temperature high > 95°C.
7. Motor winding temperature high > 120°C
8. Both hydraulic oil pumps tripped.
9. FD fan Running & O/L gate closed (Delay 20 sec).
10. Electrical protections.
11. Furnace pressure HH > 4 Kpa. (post purge trip).
12. Any Transmitter malfunction.
Plant Response:
1. Tripped fan blade pitch & discharge damper closes.
Parameters of Concern:
1. Blade pitch & disc damper closure for tripped fan.
2. Running fan current, Bearing and winding temperature, Vibration.
3. Fuel cut out to 50% to 60% TMCR.
4. Flue gas Oxygen %.
5. Fuel to Air ratio.
Page 19 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. APH trip.
2. Fan bearing temperature HH.
3. Fan bearing vibration HH.
4. Fan motor bearing temperature HH.
5. Fan motor winding temperature HH.
6. ID fan overloaded.
7. ID fan lube oil pressure LL or both lube oil pump trip.
8. Post purge trip.
9. Discharge damper closed
10. Motor protections acted.
Plant Response:
1. Particular FD fan trip(if general interlock put in service)
2. Furnace pressure goes to positive.
3. Oxygen rapidly decreases.
4. Total air flow decreases.
5. Wind box DP rapidly decreases.
6. Inter connection damper of FD fan open upon FD trip.
7. Furnace flame may disturb.
Page 20 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Parameters of Concern:
1. Oxygen in flue gas at APH inlet.
2. Furnace pressure.
3. Wind box DP.
4. Running ID and FD fan loading.
5. Power generation.
6. Main steam parameters
Likely causes:
1. Respective APH is tripped.
2. PA fan bearing temperature HH.
3. PA fan motor bearing or winding temperature HH.
4. PA fan bearing vibration HH.
5. PA fan lube oil pressure LL or both lube oil pump tripped.
6. Motor protection operated.
Plant Response:
1. PA header pressure drop rapidly.
2. Furnace pressure decrease.
3. Tripped fan outlet damper close.
Page 21 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Parameters of Concern:
1. Furnace pressure.
2. PA header pressure.
3. Mill inlet PA pressure and flow.
4. Running PA fan loading.
5. Power generation.
6. Main steam pressure & temperature and OHDR.
7. Flue gas oxygen.
Likely causes:
1. APH main motor tripped and the Auxiliary motor not in interlock
2. APH gear box problem
3. APH jamming and causing the overloading of Motors
4. Auxiliary motor is not ready from electrical(Module & VFD)
Plant Response:
1. APH trips and speed comes to Zero.
Page 22 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Parameters of Concern:
1. Power generation.
2. Furnace pressure.
3. O2 and Wind Box DP.
4. MS/RH temperature and pressure.
5. Running ID/FD/PA Fan’s loading.
6. Running Mills’ inlet flow and pressure.
Likely causes:
1. Both fan got overload/ electrical fault.
2. Standby DC fan fails to start after tripping of running AC fan trip.
3. Both fan running but still discharge pressure is LOW alarm persist by any reason of actual discharge filter choke or
malfunctioning of pressure transmitter.
Plant Response:
1. Boiler will trip on < 2.8 kpa scanner cooling air pressure low.
2. Scanner air fan tripped alarm
3. In adequate cooling of scanners may cause damage to scanner sensing element.
4. Flame cool fan pressure LOW alarm.
5. If flame cool fan suction filter is chocked discharge DP alarm switch act.
Parameters of Concern:
1. Cooling air to scanner.
Page 23 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
2. Unit tripping.
Likely causes:
1. Running seal air fan tripped and S/B has not picked up.
2. Mill Seal air line MOV or MIV closed / Malfunction.
3. Mill seal air fan suction manual valve closed.
4. Seal air fan Suction filter chocked and seal air discharge Header Pressure Low.
5. PA discharge pressure marinating low.
6. Seal Air leakage from seal air line.
7. Electrical protection operated.
Plant Response:
Alarm display on DCS of Low seal air Pr.
Mill thrust bearing damaged.
Coal dust enters to mill seal and damages.
Mill current.
Parameters of Concern:
1. Mill thrust bearing temp,
2. Mill vibration,
3. Mill current,
4. Mill bowl assembly will be damage.
Likely causes:
1. Mill outlet temperature maintaining high.
2. Foreign material in mill.
3. Coal quality (high CV).
Page 24 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Plant Response:
1. Mill outlet temperature shoots up.
2. Mill may trip on protection.
3. Surrounding may catch fire.
4. Mill gates and damper may not operated damage done by explosion.
5. Duct and bellow may damage.
6. Fluctuation in furnace pressure.
7. PA header pressure dropped rapidly.
8. Water coal ratio increase.
9. OHDR and main steam temperature decrease.
10. Power generation decrease.
Parameters of Concern:
1. Furnace pressure.
2. Water coal ratio and OHDR.
3. Main steam temp and PA header pressure.
4. Mill and duct surroundings.
5. Power generation.
Page 25 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. Coal chocking in bunkers.
2. Mill protections acted.
3. 6.6kv bus side electrical problem.
Plant Response:
1. Load reduces rapidly.
2. MS/RH Temperature goes down rapidly.
3. MS/RH pressure goes down rapidly.
4. OHDR decreases rapidly.
5. Separator level rises if OHDR becomes zero.
6. Total air flow decreases.
Parameters of Concern:
1. Power generation.
2. OHDR and hence MS/RH temperature and pressure.
3. MS Flow.
4. Separator level.
5. Air flow.
6. Furnace pressure.
7. Water Coal ratio.
Page 26 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. Poor water quality
2. Metal temperatures remains higher side for long time
3. Feed water flow is not adequate.
4. Any wall blower is in advanced position for long time and steam is charged.
5. Poor tube material and welding joints quality.
6. Furnace to wind box DP is not maintained.
7. Corrosion at fire side and water side of tubes.
8. Starved water walls.
9. Blocked tubes.
10. Bursting of tubes due to pressure fluctuations.
11. Improper setting of safety valves.
Plant Response:
1. Boiler make-up water consumption will increase.
2. Fluctuation in furnace pressure.
3. I.D.Fan will draw more current.
4. Water wall metal temperature will remain high around the leakage.
5. Abnormal sound comes from the boiler furnace.
6. Leakage detectors show high intensity.
7. O2 fluctuation at APH inlet.
8. Generation may vary.
Parameters of Concern:
1. D.M.Water make-up.
2. Furnace pressure.
3. I.D.Fan current.
4. Water wall metal temperatures.
5. Acoustics intensity.
6. O2 at APH inlet.
Page 27 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. Poor water quality
2. Feed water flow not maintained adequate.
3. Soot blowing steam pressure is very high.
4. Flue gas velocity is very high.
5. Poor metallurgy and weak welding joints.
6. Ash erosion.
Plant Response:
1. DM Water consumption will increase.
2. ID Fan current increase.
3. Flue gas temperature at economizer O/L drops.
4. Abnormal sound comes out from economizer.
5. Water coming out of economizer ash hoppers joints.
6. Trouble found in economizer deashing.
7. ASLD shows high intensity.
8. APH inlet O2 reading decreases.
9. Feed water flow will increase.
Parameters of Concern:
1. DM Water make-up.
2. Economiser outlet flue gas temperature.
3. ID Fan current.
4. Economiser deashing.
5. ASLD intensity.
6. O2 reading at APH inlet.
7. Flue gas temperatures at APH Inlet and Outlet.
Page 28 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. Main steam pressure very high.
2. Super heater safety valves fail to lift on very high pressure.
3. High super heater metal temp .
4. Poor water quality.
5. Erosion by ash due to high flue gas velocity.
6. Boiler running more than BMCR continues for long time.
7. LRSB operation for long time(not retracted).
8. Fire side corrosion.
9. Starvation.
Plant Response:
1. Fluctuation in furnace pressure.
2. Increase ID fans loading.
3. Leak detector shows high intensity in particular leakage area.
4. Increase DM water consumption.
5. SH tube metal temperature near to leakage may increase.
6. Drop in flue gas temperature at APH inlet.
7. Abnormal sound comes in boiler.
8. Increase difference between feed water and steam flow.
9. MS pressure and power generation will decrease.
10. Flue gas Oxygen reading may go down.
Parameters of Concern:
1. Furnace pressure.
2. ID fans current.
3. SH metal temp.
4. DM water consumption.
5. Furnace pressure.
6. Flue gas temp.
7. Main steam pressure.
8. Power generation.
Page 29 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. High reheater pressure due to IP turbine valve close and HRH safety valve fail to lift.
2. Poor water quality.
3. High Reheater metal temperature due to starvation.
4. Erosion of tube due to high flue gas velocity.
5. Boiler running more than BMCR continues for long time.
6. Advance any LRSB for long time.
7. Corrosion due to fly ash component.
Plant Response:
1. Fluctuation in furnace pressure.
2. Increase ID fans loading.
3. Increase metal temperature after particular tube leakage of reheater tube.
4. Drop of flue gas temperature at APH inlet.
5. Increase in DM water consumption.
6. Leak detector shows high intensity in particular leakage area.
7. Abnormal sound comes in boiler.
8. Power generation will decrease
9. Pressure drop across reheater coil will increase.
10. Flue gas Oxygen may go down.
Parameters of Concern:
1. ID fans current.
2. Reheater metal temp.
3. DM water consumption.
4. Furnace pressure.
5. Flue gas temperature.
6. Power generation.
Likely causes:
1. Tripping of one or more coal mills.
2. Fuel flow disturbance.
3. Malfunctioning of spray control valves.
4. Less air flow.
5. More spray.
6. Low feed water temperature.
7. Malfunctioning of gas biasing damper.
8. Inhering load set point fast.
9. Wall blowing may be in service.
10. Feed Water flow may be more.
11. Coal quality.
12. High excess air.
Plant Response:
1. Ms Temperature low alarm will appear.
2. Turbine expansion may become negative.
3. Axial shift.
4. Turbine shaft vibration.
5. Load will reduce.
6. Unit will trip <474 0C of MS temperature.
Parameters of Concern:
1. Main Steam Temperature,
2. Feed water flow,
3. Coal flow,
4. Flue gas O2,
5. Total air flow.
6. Transforming Parameters.
Page 31 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. Improper water and coal ratio.
2. Coal quality varying.
3. Feed water flow reduces.
4. Any BFP recirculation valve got open and feed water flow reduced.
5. SH spray valves malfunction
6. SH spray line leakage
7. Soot deposition on water wall
8. Improper air flow and SADC position.
9. Main stream flow reduces or pressure high due to HPSV, HPCV malfunction
10. Sudden increase in PA header pressure
11. Any mill got loaded suddenly
12. Any coal feeder feeding more coal than actual value.
13. Any oil gun admitted.
14. Sudden clear of soot during soot blowing.
Plant Response:
1. OHDR increases.
2. Metal temp high alarm will appear.
3. Spray control valves will go for further opening.
4. Load will rise for the same pressure.
5. Feed water flow increase in auto.
Parameters of Concern:
1. Metal temperature
2. Feed water flow
3. Total fuel flow
4. OHDR
5. Load
6. Air flow and Flue gas oxygen
7. SADC operation
8. Furnace to wind box DP
9. HP turbine casing and Differential expansion
Page 32 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. High air flow.
2. Tripping of one or more coal mills.
3. More spray.
4. Malfunctioning of spray control valves.
5. Malfunctioning of gas biasing dampers.
6. MS Temperature is low.
Plant Response:
1. ‘’Negative’’ Turbine expansion.
2. Turbine expansion may become negative.
3. Axial shift.
4. Turbine shaft vibration.
5. Load will reduce.
6. Axial shift.
Parameters of Concern:
1. RH temp,
2. Feed water flow,
3. Coal flow,
4. Flue gas O2,
5. Total air flow.
6. Transforming Parameters.
Likely causes:
1. Steam flow to reheater reduced suddenly.
2. RSV/CRV valves malfunction / close.
3. HP exhausts temperature high.
4. Inadequate spray due to mal function of spray valve or spray line leakage.
5. BFPs inter-stage spray MIVs in closed condition for running BFPs.
6. BFP tripped.
7. Excess air flow.
8. Ms Pressure & temperature are high.
9. Malfunctioning of RH gas damper(more opening)
10. SH gas damper closed due to link failure.
11. Furnace slagging
12. HP Heaters are out.
13. Reheater coil tube leakage.
Plant Response:
1. RH metal temp high alarm will appear.
2. Spray control valves will go for further opening.
3. Load will rise for the same pressure.
Parameters of Concern:
1. Reheater tube metal temperature
2. Wall blowing.
3. SADC operation.
4. IP turbine expansion.
5. Maintain oxygen %
6. Reduce lower elevation SADC.
7. Open SOFA dampers.
8. Inform maintenance department if any damper malfunction.
Likely causes:
1. Sudden drop in load.
2. Sudden Increase in fuel flow.
3. Any feeder malfunction.
4. MSV, TSV, HPCV malfunction.
5. Superheater spray valve malfunction.
6. PA header pressure increased.
7. Any HPHEATER extraction closed.
8. Pressure transmitter malfunction.
9. Any oil guns admitted.
10. Main steam temperature is high.
11. Soot blowing is in service.
Plant Response:
1. MS pressure will increase
2. Load variation.
3. HPBP will open if MS pressure crossed 24.8 MPa
4. ERV floats at 27.5 MPa.
5. MS safety valve floating if pressure more than 28.5 MPa.
Parameters of Concern:
1. Load.
2. Main steam pressure.
3. Main steam temperature.
4. OHDR.
5. Water To Coal ratio.
Page 35 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. One or more coal feeders tripped.
2. Coal flow from running feeder is not proper.
3. PA Header pressure drop.
4. Any mill air flow disturbed or MDV closed.
5. Sudden increase in load.
6. HP LP Bypass open or passing.
7. Boiler tube leakage.
8. Safety valve passing/lifted.
9. Pressure transmitter malfunction.
10. Change in Air flow.
Plant Response:
1. MS pressure will decrease.
2. Load reduces.
3. MS temperature reduces.
4. Coal feeding increase if mills are in auto.
Parameters of Concern:
1. Load.
2. Main steam pressure.
3. Main steam temperature.
4. OHDR.
5. Water to coal ratio.
Page 36 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. Main steam Pressure is very high
a. Coal quality improved.
b. Any coal feeder malfunction.
c. TSV/HPCV malfunction.
d. Turbine tripped and HPBP not operated.
e. MS stop valve malfunction.
f. Superheater spray valve malfunction.
g. SH spray increased in auto due to high MS temperature, OHDR.
Safety valve malfunction (Setting disturbed).
Safety valve passing/ simmering.
ERV floating due to Pressure switch malfunction.
Plant Response:
1. Main steam , separator pressures drop rapidly.
2. Stream flow will increase.
3. Load reduces.
4. Main steam temp reduce.
5. Heavy noise.
Parameters of Concern:
1. OHDR.
2. MS Temperature & Pressure.
3. Fuel flow.
4. Load.
5. Feed water flow.
6. Water consumption.
7. HPLP Bypass healthiness.
8. Metal temperature.
Page 37 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
5. Trip the unit if it not seating back ,with the Shift-Incharge clearance.
Likely causes:
1. HRH Pressure is very high
a. HP Heater 2 or 3 extraction cut
b. Any RSV or RCV closed
c. HPBP open and LPBP not operate
Plant Response:
1. Load reduces.
2. Heavy noise due to valve floating.
3. HRH steam temperature Drop.
4. HP HEATER #2 & # level may disturb.
5. Safety valve floating and simmering.
Parameters of Concern:
1. Load.
2. RSV RHCV operation.
3. Water consumption,
4. Condenser Vacuum if LPBP opened to reduce pressure.
Likely causes:
1. Sudden rise in feed water flow.
2. Sudden cut out in fuel.
3. Sudden rise in load.
Page 38 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Plant Response:
1. Water wall metal temperatures decrease.
2. SH Steam temperature decrease.
3. SH Steam pressure decrease.
4. Arch inlet temperature falls.
5. Water coal ratio increases.
Parameters of Concern:
1. OHDR.
2. Feed water flow.
3. Total fuel flow.
4. Water wall metal temperatures.
5. Total air flow.
6. Arch inlet temperature.
7. Water coal ratio.
Likely causes:
1. Sudden fall in feed water flow.
2. Sudden rise in fuel.
3. Sudden drop in load.
4. Air flow decreases.
5. Water coal ratio decreases.
6. Transmitter calculated saturation temperature may be faulty.
7. Sudden change in MS pressure.
8. Sudden change in coal quality.
9. Coal feeder fluctuation.
10. Feed water control comes to manual.
Page 39 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Plant Response:
1. Water wall metal temperatures increase.
2. SH Steam temperature rises.
3. SH Steam pressure rises.
4. Arch inlet temperature increases.
5. Water coal ratio drops.
Parameters of Concern:
1. OHDR.
2. Feed water flow.
3. Total fuel flow.
4. Water wall metal temperatures.
5. Total air flow.
6. Arch inlet temperature.
7. Water coal ratio.
Likely causes:
1. Feed water flow low.
2. Sudden fuel increase in boiler.
3. Improper Water coal ratio.
4. Any boiler feed water pump trip.
5. Water wall tube leakage.
6. Any leakage in feed water line.
7. Down comer line heavy leakage.
Page 40 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Plant Response:
1. Boiler may trip on arch inlet temperature high.
2. Over heat degree will rise fast
3. Boiler metal temperature will rise.
Parameters of Concern:
1. Arch inlet temperature.
2. Water wall metal temperature.
3. Main steam temperature & pressure.
4. Flue gas temperature.
5. Feed water flow.
6. Furnace pressure.
Likely causes:
1. Boiler bottom seal trough seal break
2. Slagging in furnace
3. Boiler Tube leakage
4. APH is tripped and respective ID fan not tripped
5. Flue gas side duct leakages
6. DP across APH is high due to blockage
7. APH leakages.
8. Sudden fuel increase in boiler.
9. FD fan getting loaded suddenly.
10. Other ID fan tripped and respective FD fan not tripped.
Plant Response:
1. Boiler furnace draught variation.
2. ID fan may trip due to overload.
3. Flame stability may disturb.
Page 41 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Parameters of Concern:
1. ID fan current /Blade pitch.
2. Furnace draught.
3. Flame intensity.
4. Flue gas O2.
5. Unit load.
6. Seal trough over flow.
7. Bottom ash system sump level.
8. Total airflow.
9. Furnace to wind box DP.
Likely causes:
1. Problem in SADC i.e., SADC is fluctuating very much.
2. Problem in blade pitch of FD Fan i.e., it is loading and unloading continuously.
3. Problem in air flow transmitter.
4. FD Fan stalling.
5. APH SA outlet damper closes due to link failure.
6. Malfunction of O2 analyzer (in Auto mode).
Plant Response:
1. Variation in O2 %.
2. Variation in flue gas temperature.
3. Variation in water wall temperature.
4. Variation in FD & ID Fan’s blade pitch.
5. Variation in furnace pressure.
Parameters of Concern:
1. Furnace pressure.
2. Wind Box DP.
Page 42 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. Any ID, FD or PA fan tripped.
2. Any one or more coal mills tripping suddenly.
3. Soot blowing may be in service.
4. Malfunctioning SH/RH gas dampers.
5. Any ID, FD or PA fan blade pitches malfunctioning.
6. Any ID, FD or PA fan suction damper close.
7. SOFA, SA, AUX dampers malfunctioning.
8. Tube leakage.
9. Bottom seal trough disturbed (Over flow not there or seal broken).
Plant Response:
1. Alarm display on DCS of furnace pressure variation.
2. Boiler will trip on heavy furnace fluctuation.
3. Chances of furnace flame disturb.
Parameters of Concern:
1. ID fan current,
2. Furnace to wind box DP,
3. Blade pitch position,
4. Seal trough O/F,
5. Bottom ash system.
Page 43 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. Any PA Fan trips.
2. Any PA Fan unloads suddenly i.e., its blade pitch decreases abnormally or current decreases abnormally.
3. Heavy leakage in hot PA Header or duct.
4. PA Fan Stalling.
Plant Response:
1. PA I/C damper will open in auto.
2. PA header pressure goes down.
3. Mill PA flow goes down.
4. Decrease in generation.
5. Variation in furnace pressure (towards negative side).
6. Decrease in total primary air.
7. SH/RH temperature will drop.
Parameters of Concern:
1. Current of running or Loaded PA Fan.
2. PA Flow in running mills.
3. PA Header Pressure.
4. Seal air discharge pressure.
5. Main Steam and HRH Temperature.
6. Flame stability due mills taken out.
Page 44 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. Oil leakage from APH bearing (due to oil seal damage).
2. Oil leakage from level gauge (due to damage).
Plant Response:
1. Bearing oil temperature shows high value (Guide and Support).
2. Oil leakage observed in local.
3. APH bearing temperature will rise.
Parameters of Concern:
1. Bearing oil temperature and hence the bearing itself.
Likely causes:
1. DM plant water silica may be high.
2. System taken into service after overhauling.
3. Condenser tube leakage.
4. Coliadal Silica in DM water
Page 45 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Plant Response:
1. As per DM plant report Silica will vary.
2. Turbine vibration may be high, duringlong time operation.
3. Axial shift may increase.
4. Turbine first stage pressure increase.
Parameters of Concern:
1. Silica concentration in separator steam.
2. Separator pressure.
3. Howell conductivity
Likely causes:
1. Make up water faulty.
2. Faulty analyzer.
3. Dosing line may be leaking or choked.
4. Ammonia NH 3 dosing concentration may be low / poor.
5. Dosing pump not developing pressure.
6. Tripping of dosing pump.
7. Condenser tube leakage or slippage.
Plant Response:
1. Boiler conductivity also comes down
2. Internal corrosion of boiler tubes increase and chance of tube failure if left for long duration.
3. Silica value variation.
4. Condenser tube leakage.
Parameters of Concern:
1. Boiler feed water pH,
2. pH of condensate water,
3. Entire water circuit PH will be drop gradually.
4. Main steam PH
Page 46 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. Metal temperature rate of rise may be quite high.
2. Not uniform heating in the boiler due to not rotating the oilguns.
3. Heavy soot deposition in the furnace.
4. In adequate individual oil flow through the Oil guns .
5. Improper fuel injection (Top gun / Top Mill)
6. Buck – stay mechanical jam or damaged.
7. Furnace DP not equally maintained.
8. Furnace part welded to boiler structure.
Plant Response:
1. Local expansion reading is uneven,
2. Buck-stay may damage.
3. Boiler structure loading may change.
Parameters of Concern:
1. Local reading.
Page 47 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
32.Bunker Fire
Likely causes:
1. High Volatile Matter coal stored in bunker and not in use since long time.
2. Any kind of ignition or fire caught by coal inside the bunker.
3. Higher surrounding temperatures.
4. Spontaneous ignition due to stagnate coal in bunker.
5. Air passing through the air cannon cylinder.
6. Hot coal fed by Coal Handling Plant.
Plant Response:
1. Smoke or fire comes out from the bunker.
2. Transfer conveyer may damage.
3. Coal feeder belt may damage.
4. Black spots may be observed at the outer wall of the coal bunker.
5. Coal feeder temperature will increase.
Parameters of Concern:
1. Bunker level.
2. Coal quality and Coal Handling Plant.
3. Coal feeder belt.
4. Bunker structure.
Page 48 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. OHDR decreases suddenly up to zero due to:
a. Sudden reduction in coal flow.
b. Sudden increase in feed water flow.
2. Separator to SH Spray control valve closed.
3. Sub cooling MOV got opened or passing.
4. Faulty feed water flow measurement
5. Faulty fuel flow measurement
6. Sudden cutout of oil guns at low loads
Plant Response:
1. Separator level increases.
2. Water carries over to Super heaters.
3. SH temperature goes down rapidly.
4. Sudden cooling of separator metal
Parameters of Concern:
1. Water coal ratio.
2. Water carryover.
3. Super heater metal temperature.
4. Main steam temperature.
Likely causes:
1. During unit start up with oil guns in service; oil spillage may be due to :
a. Improper smoothness in the nozzle.
b. Leakage in the oil gun pipe.
c. Improper combustion.
d. Igniters failure
e. Improper fuel air adjustment through SADC.
Page 49 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Plant Response:
1. No proper flame intensity.
2. Increase in oil flow than normal will be observed.
3. Oil tank level will go down.
Parameters of Concern:
1. Flame intensity.
2. Oil pressure.
3. Atomising steam pressure.
Likely causes:
1. Furnace Pressure very high.
2. Furnace Pressure very low.
3. Cooling Water Pump failure.
4. Seal trough makeup sump level low.
5. Any leakage in cooling water line.
6. Cooling water temp very high.
Plant Response:
1. Draught fluctuation.
2. ID fan may trip on over load.
3. Flame may disturb.
Parameters of Concern:
1. Furnace pressure.
Likely causes:
1. SSC motor overload
2. Hydraulic pump failure
3. Any leakage in hydraulic oil line.
4. SSC Chain broken.
5. Cooling water supply failure.
6. Heavy bottom ash.
7. Take-up device failure.
Plant Response:
1. More bottom ash collection in SSC.
Parameters of Concern:
1. SSC water temperature.
Page 51 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. Over flow pump failure.
2. Malfunction of overflow sump level switch.
3. HEC drain heavy passing.
4. Heavy leakage in over flow pumps discharge line.
5. Insufficient Make-up water.
Plant Response:
1. Cool and hot water pump may trip.
2. Seal trough water level will go down; concentrator water level will go down.
Parameters of Concern:
1. Cold water sump level.
2. Boiler water seal trough overflow.
Likely causes:
1. Mechanical jamming.
2. Motor tripped on overload
3. LRSB power cable failure.
4. Power supply failure.
Plant Response:
1. Soot blower may damage.
2. Damage super heater coil due to steam erosion.
Parameters of Concern:
1. Specific zone metal temperature.
Page 52 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. APH fire.
2. APH soot blowing not done for long time.
3. LRSB/SRSB not done for a long time.
4. High flue gas velocity.
5. High air flow.
6. Oil firing in service for long period.
7. Soot deposition on water wall, super heater and reheater tubes.
Plant Response:
1. Change in ∆P across APH.
2. Rise in metal temperature of SH/RH.
3. Increase in DM water consumption (in case of SH/RH tube leakage)
4. Difference between feed flow and steam flow increases(in case of SH/RH tube leakage)
5. MS temperature going down (in case of high air flow).
6. APH inlet temperature rise.
Parameters of Concern:
1. Furnace pressure.
2. SH/RH metal temperature
3. DM water consumption.
4. MS temperature
5. Feed and steam flow.
6. APH inlet temperature.
Page 53 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. De-ashing problems like:
a. No proper transport air pressure.
b. Failure to carry out ash evacuation.
c. No proper fluidization (due to problem in heater).
d. Problem in dome valve.
e. ESP field failure.
f. Evacuation line choking /moist ash / heater failure.
Plant Response:
1. Ash build up in hopper may lead to tripping of CRM/ERM.
2. It will restrict the flue gas flow.
3. It may lead to field tripping.
4. Overloading on fields which are not tripped.
5. Build up of high tension emitting system, causing short circuit.
6. Dusts carry over through chimney.
7. High SPM.
Parameters of Concern:
1. Spark rate
2. ESP performance.
3. Environmental pollution.
Likely causes:
1. No proper circulation of HP cooling water inside BCP motor.
2. CCCW temperature is high.
Page 54 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Plant Response:
1. Temperature high indication will come on DCS.
2. If HP cooling water temperature becomes > 65 °C, BCP will trip and unit may trip on FW flow low -low.
Parameters of Concern:
1. BCP Motor’s winding temperature as higher temperature will lead to its damage.
2. Impurity level in the BCP filling water.
Likely causes:
1. UPS-1&2 failure.
2. Blackout with UPS failure.
3. UPS supply fails to control cabinets.
4. Any other C&I problem (software or hardware).
Plant Response:
1. No command will sent from DCS to equipments.
2. Parameter goes to bad quality.
3. DCS console’s power may off.
Parameters of Concern:
LOCAL OBSERVATION OF:
1. Turbine speed.
2. Mill status.
Page 55 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
Sudden Load through off.
1. One CEP tripped and second not started and make up maintain high.
2. Hotwell makeup control valve not operating properly.
3. Dearator level maintaining high due to wide opening of Heater normal drip CV.
4. HP and LP heater Emergency Drain opened to maximum suddenly.
5. Hotwell makeup bypass valve made 100% opened with CV in service.
6. Condenser Tube leakage.
7. Level Transmitter stands pipe leakage.
8. Dearator level faulty.
Plant Response:
1. Condenser vacuum start decreasing.
2. Load decreases because of vacuum drop.
Parameters of Concern:
1. Condenser Vacuum.
2. Hotwell Conductivity.
3. Dearator level.
4. Discharge pressure of CEP.
5. Healthiness of level transmitter.
6. Local level gauge reading.
7. Unit load.
Page 57 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. Standby CEP started in auto.
2. Hotwell makeup control valve not operating.
3. CST level low.
4. CEP discharge line leakage/drain opened condition.
5. Dearator level dropping.
6. Transmitter malfunctioning.
7. Feed Water line leakage.
8. Boiler tube leakage.
9. Dearator level gauge malfunctioning.
10. LPBP, exhaust hood, 3rd Stage Spray CV opened fully.
11. Unit Tripped.
Plant Response:
1. Condenser vacuum start decreasing
2. Dearator level drops fast.
3. CEP Discharge pressure drop.
4. CEP may trip on Hotwell level LL.
Parameters of Concern:
1. Condenser Vacuum.
2. Condensate Water Flow.
3. Dearator level.
4. Discharge pressure of CEP.
Page 58 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. Deaerator control CV abnormal operation.
2. HP heater 3 drip coming more.
3. Any BFP tripped.
4. Load reduced very fast.
5. HPH tube leakage.
6. FW demand low.
7. More no of CEP in service(3 CEPs ).
Plant Response:
1. Deaerator pressure may drop.
2. Deaerator temperature may drop.
3. Deaerator overflow valve open.
4. Hotwell level decreases.
5. Hotwel level variation.
Parameters of Concern:
1. Deaerator control CV position.
2. Hot well level.
3. BFP parameters like Recirculation valve positions and Suction flows.
4. CEP discharge Pressure.
5. Deaerator overflow valve position.
6. Hotwell level.
7. Deareator pressure and temperature
8. Extraction-4 MOV position.
9. All HP heater level.
Page 59 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. Any CEP tripped.
2. Deaerator control CV malfunctioning.
3. Sudden rise in feed water demand
4. HPH-3 normal drain suddenly closed and emergency drain control valve opened.
5. Extraction-4 cut out.
6. Deaerator drain MOV open/passing.
7. CEP recirculation suddenly opens.
8. HP heater tube leakage is heavy
Plant Response:
1. Deaerator level low alarm will come.
2. If deaerator level control valve in auto CEP outlet header pressure will drop & stand by CEP may pick up.
3. Hot well level may drop.
4. 2 BFP will tripped if level goes below -1500mm.
Parameters of Concern:
1. Deaerator level.
2. CEP parameters like discharge pressure and condensate flow.
3. Deaerator level control CV position.
4. HPH-3 levels and Drip control valve positions
5. Normal drain MOV position, emergency drain control valve position.
6. Deaerator drain MOV position.
Likely causes:
1. Hot well level low (200mm).
2. CEP tripped on any of the protection (check first out) and stand by pump not in interlock.
3. Standby pump tripped on overload.
4. Standby pump electrical protection acted.
5. Pump in interlock but all permissive are not healthy.
Plant Response:
1. D/A level decreases fast.
2. Overloading of other pump, running TDBFP or MDBFP booster pump sealing pressure reduces and other attemperation
pressure reduces.
3. If LP bypass system is in service its outlet temperature will rise.
4. CEP discharge header pressure decreases.
5. Hot well level increases.
6. LP gland steam spray disturbs
7. 3rd stage and LP exhaust spray disturbs
Parameters of Concern:
1. CEP outlet pressure,
2. Hot well level& Deareator level,
3. Deareator level control valve position,
4. Running CEP parameters,
5. Hot well level CV position,
6. Unit load,
7. Condenser vacuum,
8. Gland steam temperature.
Page 61 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
6.TDBFP Tripped
Likely causes:
1. TDBFP Booster pump Tripped due to any of the following reasons
Dearator level less than 1500mm.
TDBFBP suction pressure <1.5 Mpa for more than 3 seconds.
TDBFBP Suction MOV Closed.
TDBFBP booster pump bearing temperature high.
2. Lube oil pressure ≤ 0.07Mpa.
3. EH oil pressure is ≤7.8 Mpa.
4. Exhaust steam temperature ≥150°C.
5. Axial shift of turbine rotor is on trip value. (≥0.4mm or ≥-0.6mm).
6. Vacuum low.
7. Shaft bearing vibration ≥0.2mm.
8. TDBFP thrust bearing temperature ≥110°C and Bearing temperature ≥115°C.
9. Tripped on Over speed (≥6380 RPM).
10. Manual push button operated.
11. MEH trip Output.
12. Any Protection Malfunctioned.
13. Any Of the Instrument showing bad value.
Plant Response:
1. MDBFP picks in auto if is in interlock and scoop open by 30% in auto.
2. Second TDBFP comes to manual.
3. Feed water flow decreases.
4. Main steam flow decreases.
5. Water to Coal Ratio decreases.
6. OHDR increases.
7. Water Wall metal temperature increases.
8. Arch inlet temperature increases.
9. Main steam temperature Increases.
10. Separator Tank Pressure Decreases.
11. Unit Load decreases.
Parameters of Concern:
1. Unit Load.
2. Total coal flow, FW Flow, W/C ratio, MS flow, MS temperature, Arch inlet temperature, WW metal temperature, Separator
Tank pressure, total air flow.
3. MDBFP Started and scoop percentage.
Page 62 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. TDBFP Booster pump Tripped due to any of the following reasons
Dearator level less than 1500mm.
TDBFBP suction pressure <1.5 Mpa for more than 3 seconds.
TDBFBP Suction MOV Closed.
TDBFBP booster pump bearing temperature high.
2. Lube oil pressure ≤ 0.07Mpa.
3. EH oil pressure is ≤7.8 Mpa.
4. Exhaust steam temperature ≥150°C.
5. Axial shift of turbine rotor is on trip value. (≥0.4mm or ≥-0.6mm).
6. Vacuum low.
7. Shaft bearing vibration ≥0.2mm.
8. TDBFP thrust bearing temperature ≥110°C and Bearing temperature ≥115°C.
9. Tripped on Over speed (≥6380 RPM).
10. Manual push button operated.
11. MEH trip Output.
12. Any Protection Malfunctioned.
13. Any Of the Instrument showing bad value.
14. MDBFP not available as it is under PTW.
Plant Response:
1. Second TDBFP comes to manual.
2. Feed water flow decreases.
3. Main steam flow decreases.
4. Water to Coal Ratio decreases.
5. OHDR increases.
6. Water Wall metal temperature increases.
7. Arch inlet Main steam temperature increases.
8. Main steam temperature Increases.
Page 63 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Parameters of Concern:
1. Unit Load.
2. Total coal flow, FW Flow, W/C ratio, MS flow, MS temperature, Arch inlet temperature, WW metal temperature, Separator
Tank pressure, total air flow, OHDR.
3. Auxiliary steam header pressure and its availability (Interconnection opened from neighbour Unit).
Likely causes:
1. Pump discharge hydraulic control valve closed by 75°.
2. CW pump motor stator temperature reached to trip value.
3. CW pump bearing temperature reached to trip value.
4. Emergency Push button operated.
5. Hydraulic oil supply failure.
6. PLC, UPS failure resulted in Feed back loss to DCS.
7. Communication card Failure.
Plant Response:
1. Condenser Vacuum start decreasing very fast.
2. Unit Load Decreases.
3. Fall in CW Duct pressure.
4. CW sump may overflow.
Page 64 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Parameters of Concern:
1. Condenser Vacuum.
2. Unit load.
3. CW discharge Pressure, current and vibration of running pump.
4. Starting of 2nd vacuum pump.
5. ACW pumps healthiness.
6. Trip Pumps discharge valve fully closed and pump is not reverse rotating.
7. CW temperature.
8. Exhaust Hood Temperature.
Likely causes:
1. Pump discharge hydraulic control valve closed by 75°.
2. CW pump motor stator temperature reached to trip value.
3. CW pump bearing temperature reached to trip value.
4. Emergency Push button operated.
5. Hydraulic oil supply failure.
6. Standby CW pump not available due to maintenance work.
7. PLC, UPS failure resulted in Feedback loss to DCS.
8. Communication Card failure.
Plant Response:
1. Condenser Vacuum starts decreasing fast.
2. Unit Load Decreases.
3. Fall in CW Duct pressure.
4. CW sump may overflow.
Page 65 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Parameters of Concern:
1. Condenser Vacuum.
2. Unit load.
3. CW discharge Pressure, Current and vibration of running pump.
4. Starting of 2nd vacuum pump.
5. ACW pumps healthiness.
6. Effluent pit level.
7. Tripped pumps discharge valve is fully closed and pump is not reverse rotating.
8. Turbine Exhaust hood temperature and CW temperature.
Likely causes:
1. High feed water flow than rated or sudden increase in feed water flow.
2. Low feed water inlet temperature.
3. Auto failure of drip control valves.
4. Control valve stuck.
5. Drip interlock not working properly.
6. Dearator pressure higher than specified.
7. Inadequate extraction from turbine (ext NRV or MOV not fully open).
8. Adjacent heater got bypassed from feed water.
9. Heater tube leakage.
10. Level transmitter malfunction.
11. Level transmitters stand pipe leakage.
Plant Response:
1. Heater will be cut off and bypass if level rising than specified limit.
2. If heater is cut off vacuum may be effected.
Page 66 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Parameters of Concern:
1. Generation
2. Feed water temperature
3. Dearator pressure
4. Heater level
5. Condenser vacuum
6. Axial shift
7. MS pressure,MS temp,coal flow, feed water flow, feed water temp
8. Extraction pressure
9. Control valves position
10. Extraction pressure
11. Extraction temp
12. Feed water flow
3. Follow up maintenance department for the cause. If tube leakage not there, take the heater in service .
Likely causes:
1. Sudden change in steam parameters.
2. Sudden change in load, speed, frequency.
3. Heat soaking not done properly, cylinder expansion is not smooth.
4. Rotor eccentricity high.
5. Lube oil pressure and temperature abnormal.
6. Cold steam enters in to turbine.
7. Low condenser vacuum.
8. High temperature difference between HP & IP cylinder.
9. During start and stop, turbine speed is within critical running speed zone.
10. Turbine bearing damages.
11. Impeller blades damages.
12. Vibration due to generator due to sudden MVAR change.
13. Gland steam temperature low.
14. High axial shift.
15. Sudden Cutoff of Any HP Heater.
16. Turbine acceleration not maintained during rolling.
Plant Response:
1. Turbine vibration high alarm will come.
2. Turbine will trip if shaft vibration reaches to 250 microns.
3. Axial shift may increase.
4. Bearing metal temperature may rise.
Parameters of Concern:
1. Turbine vibration.
2. HP-IP differential expansion.
3. Turbine speed.
4. Rotor eccentricity.
5. Axial shift.
6. Lube oil pr. & temperature
7. Condenser vacuum.
8. Gland steam temperature
9. Main steam & Reheat steam parameters.
10. Bearing metal temperature Return oil temperature
11. Physical vibration.
Page 68 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
4. Check and ensure whether lube oil pr. and temperature at bearings are normal whether bearing metal temperature and
return oil temperature is normal . Otherwise take appropriate action.
5. During start-up do proper soaking of turbine .
6. Reduce load to suit the condition.
7. Wait for frequency change if it is high.
8. Try to maintain turbine steam parameters as per startup curve.
9. Avoid sudden change in steam temperatures & load.
10. Try to maintain axial shift, differential expansion, condenser vacuum, exhaust hood temp, eccentricity within limits.
Caution:
11. If the turbine vibration is very high, unit should be tipped immediately and fast coasting down to bring zero rpm.
Likely causes:
1. Lube oil pressure is low,
2. Lube oil cooler outlet temp high.
3. Poor oil flow rate, pressure.
4. Bearing is damaged.
5. Vibration high.
6. Overload.
7. High gland steam leakages.
8. Foreign material in oil (mechanical impurities and Moisture).
9. Turbine acceleration is high.
10. One HP turbine CV got closed.
11. Axial Shift may be high
Plant Response:
1. Bearing temperature high.
2. Bearing return oil temperature high
3. Friction noise at local.
4. Bearing vibration increases.
Parameters of Concern:
1. Bearing temperature.
2. Bearing return oil temperature.
3. Bearing vibration.
Page 69 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Caution:
1. If any oil leakage is heavy, immediately contact fire person to prevent fire.
Likely causes:
1. Abrupt change of load.
2. Sudden drop of steam temperature.
3. Sudden drop of vacuum.
4. Due Sudden cut off of HP Heaters (increase in too high flow in reheater).
5. Sudden closer of extraction NRV.
6. Lube oil failure of thrust bearing/lube oil pressure/temperature.
7. Too fast pick up of load.
8. Turbine overload.
9. Salting in turbine.
Plant Response:
1. Overloading of thrust pads and failure.
2. May contribute to turbine vibration.
3. Unusual sound from turbine.
4. May result in abnormal turbine differential expansion.
5. Increase eccentricity.
6. High vibrations.
7. Gradual increase in turbine first stage pressure.
Parameters of Concern:
1. Load rate.
2. Steam temperature.
Page 70 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
3. Condenser Vacuum.
4. Hp heaters status.
5. Extraction NRV position.
6. Lube oil temp/thrust bearing temperature.
7. Axial shift.
8. HP IP Differential Expansion and LP differential expansion.
9. Turbine vibrations.
10. Eccentricity.
Likely causes:
1. Too high steam temperature for rolling.
2. Too fast rolling or too fast pickup of load.
3. Inadequate soaking during rolling as well as during turbine loading.
4. Gland steam temperature high.
Plant Response:
1. Seal rubs can be expected at extreme values. Metallic sound from turbine when interference exist.
2. Possible increase in turbine vibrations, eccentricity.
3. Turbine will alarm on +10.3 incase of HP differential expansion and on +19.8 in case of LP differential expansion.
4. Turbine will trip on +11.6 incase of HP differential expansion and on +24.6 in case of LP differential expansion.
Parameters of Concern:
1. Main steam temp, turbine metal temp.
2. Acceleration rate
Page 71 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. During hot start ups, rolling or loading turbine too slowly.
2. Boiler steam temperature lower than turbine metal temp.
3. Low condenser vacuum.
4. Gland steam temperature low.
Plant Response:
1. Seal rubs can be expected at extreme values. metallic sound from turbine when interference exist.
2. Possible increase in turbine vibrations, eccentricity.
3. Turbine will alarm on -5.3 incase of HP differential expansion and on -4.6 in case of LP differential expansion.
4. Turbine will trip on -6.6 incase of HP differential expansion and on -8.0 in case of LP differential expansion.
Parameters of Concern:
1. Main steam temp, turbine metal temp.
2. Acceleration rate.
3. Heat soak time.
4. Gland steam temp.
5. Condenser vacuum.
6. DEH and DEL.
Page 72 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
7. Turbine vibrations.
8. Eccentricity.
Caution
1. When turbine differential expansion is in extreme negative and the turbine has already
rolled ,tripping is not ideal solution as it would worst the situation .Gland steam temp, boiler parameter correction, rapid
loading are better alternatives.
2. It is essential that we do not roll turbine with negative mismatch of steam parameters already when negative expansion is
there.
3. If turbine is tripped break vacuum immediately to reduce possible damages.
16.High Eccentricity
Likely causes:
1. Deflection of turbine rotor due to improper cooling after unit trip.
2. Improper draining of steam lines and turbine cylinders contributing water entry to turbine.
3. Abrupt drop of main steam temp due to water carryover from boiler.
4. Moister in gland steam.
5. Deformation of cylinders.
6. Disengaged barring gear etc.
7. Lube oil temperature, quality.
8. Spray CV is open in turbine rest condition.
9. Barring gear not engaged for long time after rest down to 0 RPM or during blackouts.
Plant Response:
1. Turbine vibration increases, unusual noise from turbine.
Page 73 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Parameters of Concern:
1. Eccentricity.
2. Acceleration rate.
3. Heat socking time.
4. MS Temperature.
5. Lube oil temperature.
6. Bearing temperature.
7. Gland steam temperature.
8. Vibrations.
9. Barring gear operation
Likely causes:
1. DEH control Failure.
2. Stop valve and CV close failure after unit goes out of synchronisms.
3. Turbine not coasting down due to stop valve and CV heavy passing.
4. Solenoid supply failure and Stop valves passing.
5. One or more control valves got closed.
6. Generator overload.
Plant Response:
1. Turbine Vibration goes to higher side if its maintaining in its 3rd critical speed range.
2. MOP discharge pressure decreases.
3. Unit goes out of synchronism with grid and trips @ 47.0Hz.
4. Rubbing sound may come from bearings.
5. HBT should occur in auto.
Page 74 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Parameters of Concern:
1. Turbine Vibrations.
2. Unit goes out of synchronism and Generator breaker opened.
3. Turbine bearings status.
4. DEH system healthiness.
5. Healthiness of Unit auxiliaries.
6. Availability of DG set.
7. DCDB and UPS healthiness.
8. HBT occurs in auto.
9. Excitation current.
Likely causes:
1. DEH control Failure.
2. OPC protection Failure.
3. Tripping Solenoid Failure.
4. Grid Disturbance.
5. Stop valves and CV close failure due to control failure.
Plant Response:
1. Turbine Vibration goes to higher side.
2. MOP discharge pressure Increases.
3. Unit load fluctuates.
4. Turbine should trip at 110% Electrical protection.
5. Generator current and Terminal voltage shoots up.
6. All plant auxiliaries over loaded.
Parameters of Concern:
1. Turbine Vibrations.
2. Unit load and Generator current and terminal voltage.
Page 75 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. Barring gear motor Power supply failure.
2. Engaging pneumatic solenoid air supply fails.
3. Engaging pneumatic solenoid malfunctioned.
4. Barring gear not meshing with gear on turbine rotor due to wear and tear.
Plant Response:
1. Turbine not comes on barring and after coasting down remains stand still.
2. Turbine rotor sagging.
3. TG eccentricity may increase.
4. Rotor may get damaged.
5. Hydrogen may escape generator.
Parameters of Concern:
1. Turbine metal temperature.
2. Rotors thermal state.
3. Bearing temperatures.
Page 76 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
4. JOP status.
5. Availability of manual barring spanner.
6. Generator H2 pressure.
7. Seal oil system parameters.
Likely causes:
1. Lube oil pressure low (pump inlet pressure).
1. Both JOP not in auto.
2. AC power failure & DC power supply off.
3. Supply fuses blown out.
4. Pump module problem.
5. Over load tripping of motor.
6. Pump mechanical damage.
7. No command from DCS, due to DCS fail
Plant Response:
1. Turbine speed less than 2000 rpm and JOP not in service alarm.
2. Barring motor will not start.
3. Bearing temperature and Bearing vibrations will increases
Parameters of Concern:
1. Turbine speed.
2. Turbine vibration.
3. Bearing temperature.
Page 77 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
4. Axial shift.
5. Eccentricity.
Likely causes:
1. Mechanical fault on CV/CRV.
2. CV/ CRV servo valve fail.
3. CV/ CRV servo valve card failure.
4. Heavy steam leakage near CV/CRV.
5. Tripping circuit fault.
6. Feedback problem.
Plant Response:
1. If stop valve is not closed properly turbine may over speed.
2. As HPT vent valve opens on Turbine trip, condenser vacuum may fall.
3. Turbine vibrations/axial shift may increase.
4. Turbine may not come to barring (if passing is minor).
5. Coasting down time will be greater than 60 minutes.
Parameters of Concern:
1. Turbine speed.
2. MSV/CV/RSV/CRV position.
3. Turbine vibration/axial shift.
4. Condenser vacuum.
Page 78 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. Mechanical fault on CV/CRV.
2. EH oil/ Trip oil line oil leakage on that particular CV/CRV.
3. EH oil to CV/ CRV filter chock on that particular CV/CRV.
4. CV/ CRV servo valve fail.
5. CV/ CRV servo valve card / Feed back failure.
6. Heavy steam leakage near CV/CRV.
Plant Response:
1. Unit Generation may reduce.
2. If CRV close CRH/HRH pressure will increase, increase reheated temperature.
3. In case of CV MS pressure will increase, MS temp increase.
4. If one CV closes, other CV opening may increase for same load.
5. Axial shift will increase.
6. Heaters levels may fluctuate.
7. Incase of heavy EH oil leakage EH oil tank level drop and EH oil pressure also.
Parameters of Concern:
1. Ms pressure/temperature.
2. CRH/HRH press/temperature.
3. Axial shift.
4. Turbine vibration.
5. CV/CRV position.
6. HPH/LPH levels.
7. EH oil press/Tank level.
8. CV/CRV EH oil DP alarm.
Page 79 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. Any CV/CRV is passing.
2. Any CV/CRV is open.
3. Wrong feedback of CV.
Plant Response:
1. If passing is heavy or CV/CRV is fully open turbine run fast and may over speed.
2. Turbine vibration/axial shift/DEH/DEL /eccentricity increase.
3. Due to passing acceleration rate may not be maintained.
4. Turbine rolling starts upon MSV/RSV opening.
5. Barring gear disengage.
Parameters of Concern:
1. Turbine CV/CRV position.
2. Turbine speed and acceleration.
3. Turbine vibration/axial shift/DEL/DEH/eccentricity.
Page 80 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. Drive coupling failure.
2. Bearing of MOP failure.
3. Suction of MOP failure due to turbo device failure or leakage.
4. MOP discharge line heavy leakage.
5. Low oil level in MOT.
6. Failure of NRV on MOP.
7. MSP not developing enough pressure or not started during start up.
Plant Response:
1. TOP start on auto, if it fails to start, EOP will start.
2. If Lube oil pressure drop up to .07mpa unit will trip.
Parameters of Concern:
1. MOP discharge pressure.
2. Lube oil pressure.
3. MOT level.
Likely causes:
1. Oil leakage from Turbine bearings view glasses and exciter end piping.
2. LP turbine bearings oil overflow.
3. Oil cooler leakages.
4. Oil leaks from oil purifier system.
5. Oil level in LLD is high.
6. MOT drain valve passing or open.
7. MOT level gauge leakage.
Page 81 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Plant Response:
1. MOT level decrease.
2. Oil pressure low alarm if oil leaks from oil supply line to bearing.
3. Turbine bearing temperatures may increase.
Parameters of Concern:
1. MOT level.
2. Lube oil pr. and temp.
3. VOT level.
4. Generator LLD.
5. Turbine bearing temperature
Caution:
1. If any oil leakage is heavy, immediately contact fire person to prevent fire.
Likely causes:
1. Insufficient steam flow from HP turbine during IP to HP transfer (HP bypass opened more than required & load set point is
not more).
2. MS temperature high.
Page 82 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Plant Response:
1. HP exhausts temp HIGH alarm display.
2. HP –IP diff expansion increases.
3. Turbine will trip on HP exhaust temperature>460deg.
4. CRH inlet temperature increases.
Parameters of Concern:
1. MS temperature.
2. HP exhausts pressure.
3. CRH pressure.
4. HP bypass valve position.
5. HPBP spray valve position.
6. CRH NRV position.
7. Unit load.
8. HP-IP differential expansion.
Likely causes:
1. HRH temp maintaining high in cold start up.
2. Low vacuum in condenser.
3. Tripping of any CW pump.
4. At low load exhaust hood spray valve is at closed position.
5. LP bypass spray valve is in closed condition during LP bypass operation.
6. CEP pr low for LP exhaust spray.
7. LP gland steam temp too high.
8. Keeping turbine speed 3000rpm for long time without synchronising.
Page 83 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Plant Response:
1. Vacuum decreases.
2. LP turbine differential expansion increases.
3. Turbine vibration increases.
4. LP bypass fast close on condenser vacuum low (78 kpa) OR LP exhaust temperature>80deg.
5. Turbine will trip on LP exhaust temperature>107deg.
6. There is chance of explosive diaphragm rupture.
Parameters of Concern:
1. RH temperature.
2. HP-LP bypass valve position.
3. HP-LP bypass spray valve position.
4. LP exhausts hood spray valve position.
5. Condenser vacuum.
6. LP Differential Expansion.
7. Turbine vibration.
Likely causes:
1. Gland steam pressure control valve failure.
2. Gland steam pressure transmitter reading wrong.
3. BDV opened.
4. Gland steam pressure over flow CV fully open.
5. Air leakage/air valve close of CVs.
6. Auxiliary steam header pressure low (CRH CV /MOV close, excess consumption, valves from other unit closed)
7. Load is low (for self sealing) and standby source disturbance
8. Gland steam piping leakage/drains open.
9. Gland steam temperature is low due to high spray or poor warm up.
Page 84 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Plant Response:
1. Condenser vacuum will fall.
2. LP turbines exhaust hood temperature increase.
3. Due to Low vacuum air will enter through the seals. This will cause negative expansion.
4. Turbine vibrations and other TSI parameters may affect.
Parameters of Concern:
1. Gland steam pressure/temperature.
2. Condenser vacuum.
3. LP exhausts temperature.
4. Aux header pressure.
5. DEH/DEL.
Likely causes:
1. Gland steam pressure control valve failure.
2. Gland steam pressure transmitter reading wrong.
3. Gland steam attemperation valve full open.
4. Condensation in gland steam line takes place.
5. Gland steam line drains closed at charging time.
6. LP attempt CV full open.
7. MS temperature/pressure low due to sudden variation if Gland Steam on self sealing.
8. Aux header pressure High and temperature is low.
Plant Response:
1. Gland steam line hammering may be observed.
2. Negative DEH/DEL.
Page 85 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Parameters of Concern:
1. Gland steam temperature.
2. DEH/DEL.
3. Vibration.
4. GSC level.
5. Vacuum.
6. Moisture in lube oil.
Likely causes:
1. Gland steam pressure control valve failure.
2. Gland steam pressure transmitter reading wrong.
3. Gland steam pressure over flow CV fully closed.
4. Air leakage/air valve CVs.
5. Auxiliary header pressure high (CRH full open, sudden loss of consumption).
Plant Response:
1. Gland steam out from seals at turbine shafts.
2. Seal damages.
3. Turbine vibrations increase.
Parameters of Concern:
1. Gland steam header pressure.
2. Turbine vibrations.
Page 86 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. Gland steam pressure control valve failure
2. Gland steam pressure/temperature transmitter reading wrong.
3. Gland steam attemperation valve not working.
4. Gland steam line drains full opened.
5. LP GS attempt CV full close.
6. LP GS attempt. Nozzle chock.
7. MS temp/press high due to sudden variation if GS on self sealing.
8. Aux header pressure and temperature is high.
9. Gland steam header attemperation line strainer in chocked condition.
Plant Response:
1. DEH/DEL increase.
2. Turbine vibration increase.
3. Damage of seals.
Parameters of Concern:
1. DEH/DEL
2. Vibration
3. Vacuum
4. GSC level
5. Gland steam temp
6. LP Gland steam attemperation CV Position.
7. If LP GS attempteration nozzle chock up is suspected then, trip the turbine and rectify it.
8. Gland steam header attemperation line strainer to be cleaned if it is in chocked condition.
Likely causes:
1. O rings at various hydraulic devices get damage.
2. Poor piping work.
3. Heavy material falling on pipe lines.
4. Air ingression in the system.
5. CCCW system fails and EH oil temperature got very high.
6. Heavy vibration in MSV/CV/RSV/CRV/TDBFP LSV, LCV.
Plant Response:
1. If leakage is heavy EH oil tank level, pressure fall and at <7.6 Mpa pressure Turbine will trip.
2. If leakage is heavy in specific MSV/CV/RSV/CRV/TDBFP LSV, LCV that valve will get close.
3. If leakage is heavy in common line turbine will trip.
4. If leakage is heavy in TDBFP or both TDBFP line they will trip.
Parameters of Concern:
1. MSV/CV/RSV/CRV position.
2. EH oil tank level.
3. EH oil pressure.
4. EH oil temperature.
5. Both TDBFP LSV/LCV position.
Page 88 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. Pump tripped on any electrical protection.
2. EH oil tank level low low.
Plant Response:
1. Standby pump pickup in auto.
2. Turbine will trip on EH oil outlet pressure<7.8MPA.
3. If tank level is low low both EH oil pump will trip.
4. TDBFP A & B will trip on low oil pressure.
Parameters of Concern:
1. EH oil tank level.
2. Outlet header pressure.
3. Oil temperature.
Likely causes:
1. VOT level dropping fast.
2. One seal oil pump tripped & standby pump not started.
3. Running seal oil pump PRV operated
4. Seal oil line leakages
5. DPR not operating properly.
6. Pump mechanical jamming.
7. Seal oil pump discharge recirculation valve open.
8. Seal oil filter DP high.
9. Motor protections operated
Plant Response:
1. Standby Pumpstarts on Seal oil header pressure low
Page 89 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Parameters of Concern:
1. Seal oil header pressure.
2. H2 pressure
3. Seal oil/H2 DP.
4. Generator stator winding temperatures.
5. VOT / FOT / MOT levels
6. Seal oil filter DP
7. H2 gas purity
8. Generation
Likely causes:
1. Trouble in lube oil supply.
2. Major oil leakage in seal oil system.
Page 90 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Plant Response:
1. Dc seal oil pump start if it is in interlock on -75 mm of VOT level.
2. Second A.C seal oil pump does not start because of not getting start permissive.
3. Recirculation pump trip on interlock.
4. If DC seal oil pump does not start or not developing sufficient pressure, seal oil to hydrogen differential pressure is low, then
hydrogen leakage may happen.
5. If DC seal oil pump start and seal oil to hydrogen differential pressure is high than oil may be enter in generator and
continuous LLD alarm may be persisting.
6. If H2 press drops hot/cold gas temp may increase.
7. Generator winding temperatures may increase.
Parameters of Concern:
1. DC seal oil pumps current/discharge pressure.
2. VOT level/pressure.
3. H2 pressure.
4. Seal oil DP.
5. LLD alarms.
6. Lube oil pressure.
7. Hot /cold gas temperature.
8. Generator winding temperature.
Likely causes:
1. Float oil tank float not working/stuck up.
2. Float oil tank inlet MIV closed.
3. Float tank bypass MIV open.
4. Float oil tank drain MIV open .
5. Seal oil DP low (DPR malfunctions).
6. Enlargement section tank drain MIV open.
7. Lube oil system trouble and air deterring section/float oil tank is supplying oil to seal oil system.
8. LLD alarm.
Plant Response:
1. H2 pressure decreases.
2. LLD in enlargement section observed.
Parameters of Concern:
1. FOT level.
2. H2 pressure.
3. Seal oil DP.
4. Seal oil pump discharge pressure.
5. MOT level.
6. Lube oil pressure.
7. Hot/cold gas temperature.
8. Generator temperature.
9. FOT bypass valve position
Page 92 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Likely causes:
1. FOT float may not working/stuck.
2. H2 pressure low.
3. Seal oil DP high (DPR malfunctions).
4. Seal oil ring damaged.
5. H2 line MIV at FOT closed.
6. FOT outlet MIV closed.
Plant Response:
1. If float tank level is full and still rising the oil may enter in generator.
2. If oil enters in generator insulation value may go down and earth fault may result.
3. LLD in enlargement section and turbine and generator end found continuously.
4. H2 purity drop.
Parameters of Concern:
1. Float oil tank level.
2. H 2 purity.
3. LLD alarms.
4. Seal oil DP.
Likely causes:
1. Contamination of hydrogen by oil vapors.
2. H2 cylinder lacking in specified purity.
3. Oil/water in generator.
4. H2 dew point is not maintaining.
Page 93 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Plant Response:
1. Purity of hydrogen less then 97% is not desire as heat transfer will not proper.
2. If purity lower further and if oxygen in the mixture exceeds 1.2explosion risk is there.
3. Alarm will appear at 97%.
4. Not safe to run the Unit at <95% H2 purity.
Parameters of Concern:
1. Hydrogen purity.
2. LLDS.
3. Hot/cold gas temperature.
4. Generator temperature.
39.Hydrogen Leakage
Likely causes:
1. Seal oil DP low.
2. Seal oil pump trip due to low VOT level and DC pick up and its R/C valve is in open condition.
3. DPR malfunction.
4. Leakage from generator H2 pipe connections,H2 cooler flanges, near generator bushings etc.
5. Stator bar leakage.
6. LLD drain may be in open condition.
7. H2 leakage from its flange joint, valves, H2 coolers, sampling and filling lines, valves.
8. Float oil tank level is low
9. H2 system purging vent valve is passing
10. H2 driers drain valves are passing
11. H2 feeding line NRVis not holding
Plant Response:
1. High H2 pressure drop rate.
2. H2 leakage alarm will come.
3. Hot-cold gas temperature high alarm will come.
Page 94 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Parameters of Concern:
1. H2 pressure in generator.
2. Seal oil/H2 DP.
3. H2 leakage alarm.
4. Hot-cold gas temperature.
5. Generator winding temperature.
6. H2 dew point.
7. Generation
Likely causes:
1. One pump tripped & standby fails to start.
2. Both pump running & tripped on electrical protections.
3. Power supply failure.
4. Pump mechanical failure.
5. Pump operation at high vacuum.
Page 95 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Plant Response:
1. Vacuum drops fast.
2. Unit load decreases.
3. Turbine exhaust hood temperature increases.
4. Howell temp starts increasing.
5. Axial shift may rise.
Parameters of Concern:
1. Condenser vacuum.
2. Unit load.
3. Exhaust hood temperature.
4. Hot well temperature.
5. Axial shift.
Likely causes:
1. Any CW pump trips,
2. CW outlet valve closed (partially or fully).
3. Condenser CW inlet or outlet valve closed and CW flow decrease.
4. Sudden increase in load.
5. High condenser Inlet & outlet cooling water temperature.
6. Vacuum pump trips or poor performance of PHE.
7. Vacuum pump air jet valve malfunction.
8. Vacuum breaking valve not fully closed or improper water sealing of vacuum breaking valve.
9. Gland sealing pressure drops, GSC siphon level low.
10. Leakages, ingress of air in to vacuum system through any drain line going to condenser or from loose flanges, instrument
tapping points.
11. Hot well level very high.
12. TDBFP vacuum system leaks (When it is in stopped condition).
13. Condenser tube choking (Condenser inlet-outlet DP high) so CW flow low.
14. VV valve open condition due to instrument air failure.
15. CT fans trip.
16. CT fan riser valve closed.
17. Condenser poor performance due to tube scaling /fouling
Page 96 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Plant Response:
1. Condenser vacuum low alarm.
2. LP exhaust steam temp increase.
3. Hot well temperature increases.
4. Load reduces.
5. Fuel flow increases if unit is in CCS mode.
6. Turbine vibration may increase.
7. Unit trip at 74Kpa vacuum.
8. Standby vacuum pump will pick up.
Parameters of Concern:
1. LP exhaust steam temperature
2. Hot well water temperature & level.
3. CW inlet/outlet water temperature.
4. Drain manifold temp. Coming to HP-LP flash tank.
5. Condenser pressure.
6. CW flow.
7. Cooling tower range / No fans in service.
Page 97 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
42.Condenser Pressure Rise After Vacuum Loss (In Blackouts and Shut Down Condition)
Likely causes:
1. Vacuum Breaker closed condition.
2. Lack of condensation in condenser as CW pumps tripped.
3. Gland steam supply not cut off.
4. HP-LP flash tank attemperation not available as CEP not running.
5. MS, CRH, HRH, extraction line drains, TDBFP steam line drains, HP-LP bypass line, HP heaters and LP heater drains CV
open due to Instrument air pressure low and high temperature steam coming to flash tank(Any drain to condenser open).
6. LP exhaust hood spray not available.
7. HP-LP bypass open/passing.
8. MS stop valve open (Boiler side)/passing.
Plant Response:
1. Condenser vacuum low alarm.
2. LP exhaust temperature increases.
3. LP turbine rupture disc may damage.
Parameters of Concern:
1. Condenser pr. and temp.
2. LP exhaust temperature.
Likely causes:
1. Sudden steam loading to the condenser.
2. Sudden opening of HP/LP bypass valves.
3. Repeated blackouts.
4. Both CW pumps trips and ARV’s close condition.
Page 98 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
5. Manufacturing defect.
6. High COC.
7. High cooling water temperature.
8. CW pressure surges during CW pumps start / stop due to improper air venting.
9. High Vacuum
10. Sudden opening of high pressure drains like HPT VV and BDV.
Plant Response:
1. Cation conductivity increases in CLD, CEP outlet and CPU outlet.
2. CEP outlet Na+ Increases.
3. Condensate & feed water pH value decreases.
4. MS conductivity & Na+ increases.
5. If run for prolonged period chances of boiler tube failure and LP/HP heaters tube leakages, Turbine blade cracking
6.
Parameters of Concern:
1. Cation Conductivity in CLD & CEP outlet, value of pH ,specific Conductivity, Na+ in feed water, MS & condensate.
Likely causes:
1. Overloading of generator.
2. High MVAR loading.
3. Stator cooling water flow low.
4. CCCW flow to hydrogen cooler low.
5. Hydrogen cooler not lined up or air locked.
Page 99 of 117
EMERGENCY OPERATING APL- (PH 3 & 4) REV NO
PROCEDURE 5 x 660 MW 0.0
Plant Response:
1. Generator winding temperature rising.
2. H2 consumption may increase
Parameters of Concern:
1. Generator winding temperature high alarm.
2. Generator hot and cold gas temperature high.
3. Stator cooling water flow and temperature.
4. H2 pressure.
5. H2 Purity.
6. Unit load
7. Stator water tank level and Makeup frequency.
Likely causes:
1. Hydrogen cooler leakage.
2. DPR malfunctioning and maintaining high DP.
3. Defective seal component and oil entering generator casing.
Plant Response:
1. Liquid in generator casing alarm.
2. Liquid traces in Local LLD gauges
Parameters of Concern:
1. LLD level
2. MOT level.
3. Seal oil pressure at generator end.
4. Hydrogen gas pressure and purity.
5. Seal oil/H2 DP.
Likely causes:
1. CT fan Gearbox oil temperature Exceeded >80°C.
2. CT fan Vibration Switch Actuated.
3. Protection malfunctioning.
4. CT fan Gearbox oil level low due to which fan tripped on protection.
5. Gearbox oil temperature measuring RTD Showing wrong temperature.
6. Emergency Push button actuated.
7. CMCTF Power supply failure and tie not closed.
Plant Response:
1. Condenser Inlet water temperature increases.
2. If more than 2 fans tripped than condenser inlet water temperature increases fast and so vacuum drops.
Parameters of Concern:
1. Condenser inlet water temperature.
2. Condenser vacuum.
3. Unit load.
4. Check physical status of tripped fan and position of emergency push button.
5. Reset the vibration switch with coordination of I&C team and start the fan if vibration switch had malfunctioned.
6. If CMCTF trips, close tie after checking the reason.
Likely causes:
1. All running sea intake pumps got tripped.
2. CW Trash Screen in Chocked Condition.
3. Blow Down valve opened to full suddenly.
4. Trash Screen in Damaged condition.
5. CW makeup valve closes to 0%.
6. Sea water intake pumps trash cleaner chocked.
7. Level Transmitter faulty.
8. Clarifier Inlet valve or Fore bay Makeup Valve close.
9. Any other Unit make up valve in full open condition.
10. Any seawater discharge line problem.
Plant Response:
1. CW duct pressure may drop if fore bay level go to lower limit.
2. CW pumps vibration will increase.
3. CW pump motor Current reduces.
Parameters of Concern:
1. Condenser Vacuum.
2. Sea Intake pumps status.
3. CW makeup valve status.
4. CW Duct Pressure.
Likely causes:
1. Station Blackout.
2. PLC failure
3. Pump tripped on any protection.
4. Both pump discharge valve closed, pump tripped in interlock.
5. Both pump cooling water supply failure.
6. Loss of suction head due to suction pool level low or trash cleaner choking.
7. All sea water pumps discharge valves supply from Sea water MCC , which is feeding from CMCTF-5B and CMCTF-6B.
Plant Response:
1. CW forebay level drops fast.
2. CL2 system makeup water loss
3. 20MLD plant makeup loss
Parameters of Concern:
1. CW temperature.
2. CW forebay level.
3. Hot blow down/ Cold blow down valve opening status
4. Chlorination system
5. 20 MLD plant
ELECTRICAL SYSTEM -
EMERGENCIES
Likely causes:
1. Boiler transformer tripping and DG/Stand by DG set not Started on auto.
2. Bus fault on boiler PCC and DG/Stand by DG set not Started on auto
3. Emergency PCC bus fault.
4. Fault on any outgoing feeder which extended up to main incomer of emergency PCC.
Plant Response:
1.If power supply fails on EMPCC-A then incomer to EMPCC-A will open.
2.Power supply to turbine EMCC-A, boiler EMCC-A, UPS supply-A, 220v DCDB supply-A, switchyard DCDB-A, boiler valves
MCC supply will interrupt.(important auxiliaries on boiler EMCC-A section are ID/FD/PA fan # A lube oil supply power,
coal mill a/b/c lube oil supply power,TDBFP a MEH panel power, Aph-A Standby power. Important auxiliaries on turbine
EMCC-A section are TDBFP-A barring gear, EH oil pump-A, seal oil pump-A, Ac Jop , turbine lift, generator duct
pressurization compressor., switchyard UPS-A power supply.)
3.If power supply fails on EMPCC-B then incomer to EMPCC b will open.
4.Power supply to turbine EMCC-B, boiler EMCC-B, UPS supply-B , 220v DCDB supply-B, turbine valve MCC supply will
interrupt.(important auxiliaries on boiler EMCC-B section are ID/FD/PA fan # B lube oil supply power, coal mill d/e/f lube
oil supply power,TDBFP-B MEH panel power, APH-B b Standby power and boiler lift power. Important auxiliaries on
turbine EMCC-B section are TDBFP-B barring gear, turbine barring gear,EH oil pump-B ,seal oil pump b ,top, MDBFP
AOP)
5.Turbine valve MCC supply will interrupt.
6.DCDB and ups battery backup charged of respective section.
7.Switch yard DCDB and ups battery backup charged of respective section.
8.Control room emergency lighting will changeover on battery source.
Parameters of Concern:
1. EMPCC bus voltage.
2. 220v DCDB voltage and battery voltage of respective section.
3. Ups battery voltage of respective section.
4. Switchyard DCDB voltage and battery voltage of respective section.
5. Switchyard UPS battery voltage of respective section.
Likely causes:
1. DG in manual mode.
2. Emergency push button operated at DG AMF panel or DG relay.
3. Diesel level is not sufficient.
4. Diesel tank outlet valve or DG inlet/outlet valve are in closed condition.
5. DG control supply failed (From DCDB BUS-B).
6. Low battery voltage.
7. DG set governor operation is sluggish or jam.
8. DG set protection is already in acted condition.
Plant Response:
1. DG fails to start alarm on DCS (EALM12-DG three trials fail).
2. After three crank cycle of main DG command will go to Start Standby DG set.
3. EPCC charge through Standby DG set running.
4. If Standby DG set also fails to start , no power at Emergency PCC.
5. No power at Turbine Emergency MCC and Boiler Emergency MCC.
6. DCDB and UPS will switch over to Battery source.
7. DC drives will run.
8. Check Tie Breakers of EPCC-A and EPCC-B will be in closed condition.
Parameters of Concern:
1. Ensure DC emergency drives of Turbine and Boiler are running .
2. Monitor bus voltage of DCDB.
3. Monitor bus voltage of UPS-1 and UPS-2.
4. Ready to run manually turbine Barring Gear and APH auxiliary motor.
Likely causes:
1. Tripping of 220 kV bus.
2. Tripping of transformer due to internal fault.
3. Tripping of transformer due to fault on 6.6kv/11kv bus.
Plant RESPONSE:
1. 220kv bus side breaker , 11 kv bus incomer , 6.6kv bus incomer will open ( in case of under voltage or blackout all
breaker remains close ) .
2. Under voltage occurs on respective OA and OB bus.
3. Respective PCC incomer at common PCC, water supply PCC , lighting PCC, maintenance PCC and chemical water
PCC will open.
4. Coal handling plant incomer will open.
5. Bus coupler at above mentioned PCC will close.
6. Auxiliaries running on above PCC will trip.
7. Auxiliaries running on downstream side MCC of above mentioned PCC like Service water pump, Dm transfer pump,
control room AHU, switch yard AHU, circulation water pump and cooling water pump of VAM/ chiller plant, cooling
tower fan and pump of VAM system , hot water pump and cooling tower fan of HEC, switchgear room AHU, CPU r/c pump,
chemical dozing pump , CHP belt conveyor , EOT crane, normal lighting, TG area exhaust fan will trip.
8. Compressors B, C and D, MDBFP will trip if they are running condition.
9. Switch yard control room normal lighting, power supply for operation of isolator,breaker,earth switch will interrupt.
10. Switchyard UPS reserve supply will interrupt.
Parameters of Concern:
1. Station 11kv/6.6kv/415 v PCC/415v MCC bus voltage.
2. Service water header pressure.
3. Instrument air and service air header pressure.
4. Coal bunker level.
5. CST level.
6. If MDBFP is in service then feed water flow.
4.UPS Failure
Likely causes:
8. UPS source failure.
9. Rectifier failure and Reserve supply not available or Reserve switch OFF condition also Battery switch is in OFF condition.
10. Inverter trips and Reserve supply not available or Reserve switch OFF condition.
11. Frequency variation between UPS frequency and Reserve supply Frequency.
12. UPS protection acted condition.
Plant Response:
1. Unit may trip.
2. UPS power to DCS protection not available.
3. Plant parameter readings will go bad.
4. DCS computers may fail.
Parameters of Concern:
1. UPS bus voltage, Battery current, healthiness of incoming source supply and alarm on UPS panel
5.DCDB Failure
Likely causes:
1. Incomer at EMPCC trips and battery backup source fails
2. Battery backup source is in service and its voltage becomes low .
3. Electrical fault on DC bus.
4. Electrical fault on outgoing feeder which extended up to bus/ incomer .
Plant response:
1. Incomer at EMPCC will trip if fault occurs on bus.
2. Remote operation of electrical drives will not possible.
3. Unavailability of DC emergency drives.
4. Protection relay of generator/GT/UAT/ST/11kv bus/6.6kv bus/415v PCC will not act.
Parameters of Concern:
1. DC bus voltage.
2. Battery set voltage.
Likely causes:
1. DCDB fails.
2. Switchgear Main DC MCB is in OFF condition (Breaker of Incomer Line PT).
3. DC MCB of Motor feeder is OFF condition.
Plant Response:
1. Bad feedback comes on DCS of Motor.
2. Motor ON/OFF command not possible from DCS.
3. Motor ON/OFF command possible only through Breaker.
4. Motor Electric protection bypass.
Parameters of Concern:
1. Flow/Pressure/Vibration/Temperature of Motor.
2. Bus voltage.
Likely causes:
1. HBT relay will not in service.
2. HBT will in block condition due to following reasons,
Protection will be acted in GRP panel.
Bus PT of Station switchgear is in racked out condition/fuse not healthy.
Bus PT of Unit switchgear is in racked out condition/fuse not healthy.
Line PT of Unit switchgear Incomer is in racked out condition/fuse not healthy.
Unit switchgear Incomer breaker/ Unit switchgear Tie breaker (Tie to Station switchgear)/Station switchgear Tie breaker
(Tie to Unit switchgear) DC OFF.
Unit switchgear Incomer breaker/ Unit switchgear Tie breaker (Tie to Station switchgear)/Station switchgear Tie breaker (Tie
to Unit switchgear) is in TEST MODE.
Unit switchgear Incomer breaker/ Unit switchgear Tie breaker (Tie to Station switchgear)/Station switchgear Tie breaker (Tie
to Unit switchgear) is in LOCAL MODE.
Unit switchgear Incomer breaker/ Unit switchgear Tie breaker (Tie to Station switchgear)/Station switchgear Tie breaker (Tie
to Unit switchgear) LOCKOUT RELAY OPERATED in Breaker.
Station switchgear Tie breaker (Tie to Unit switchgear) is Open condition.
3. HBT relay control supply OFF condition (DCDB BUS-A).
4. HBT relay is in MANUAL MODE.
5. Voltage difference between Station and Unit switchgear bus.
6. Difference in Phase angle between Station and Unit switchgear bus.
Plant Response:
1. No permissive for Bus Transfer in 6.6KV Unit switchgear DCS screen.
2. Transfer Blocked in HBT Relay.
3. Bus Transfer not possible (Unit to Station/Station to Unit).
Parameters of Concern:
1. 6.6KV Bus voltage of Unit switchgear.
2. 6.6KV Bus voltage of Station switchgear.
3. Unit Blackout.
8.Flash over
Likely causes:
1. Flash over due to loose contacts at joint’s or clamps of bus bar, isolator, breaker, CT, PT or CVT.
2. Due to heavy wind or stormy condition.
3. Due to accumulation of dust and moisture particle at string and support insulator.
4. Due to misalignment of isolator moving contact.
5. Due to breakdown of live conductor which falls on another live part.
6. Over loading.
7. Due to high oil temperature in case of oil immersed CB/CT/PT/CVT used.
8. CT failure due to opening of secondary coil or mfg. Defects.
Plant RESPONSE:
1. Tripping of concern section/line/unit/bus bar.
2. Damage occurred to Men and Equipment due to flashover
Parameters of Concern:
1. Bus voltage.
2. Line loading.
Likely causes:
1. Gasket of circuit breaker is damaged.
Plant RESPONSE:
1. At 0.55mpa gas pressure Low alarm will come
2. At 0.50mpa gas pressure Breaker will lockout.
Parameters of Concern:
1. Breaker operating gas pressure
Likely causes:
1. External fire spreading into cable gallery.
2. Overheating or insulation failure of any cable which results into flashover.
3. Fire due to any hot job work in cable gallery
4. Due to high temperature steam/fluid leakage around cable gallery.
Plant Response:
1. Many auxiliaries will trip if fire is severe.
2. Fire inert gas system charged on auto.
Parameters of Concern:
1. Parameter of affected system.
2. 11kv/6.6kv/415v bus voltage.
11.Hot spot
Likely causes:
1. Loose contacts at joints or clamps of bus bar, isolator, breaker, CT, PT or CVT.
2. Overloading of bus bar, line, isolator or breaker.
Plant RESPONSE:
1. Temperature remains high at hot spot. Winding temp.
Parameters of Concern:
1. Temperature at hot spot. It should less than 70 deg. C
2. Loading of respective line/bus bar/auxiliary. .
Likely causes:
1. Low oil level in conservator tank.
2. Short circuit or inter turn fault of winding.
3. High atmospheric temperature.
4. Malfunction of temperature detector switch.
Plant RESPONSE:
1. Winding temperature High alarm at 100 deg c and tripping at 110 deg c.
2. Oil temperature High alarm at 90 deg c and tripping at 100 deg c.
Parameters of Concern:
3. Bus voltage.
3. Line voltage.
3. Isolate the reactor according to condition if temperature Continues remains on higher side for further investigation.
Likely causes:
1. Gasket of circuit breaker is damaged.
2. Damage to equipment due to improper handling.
Plant RESPONSE:
1. Reactor winding and oil temperature remains high if oil level goes low.
2. Overheating of CT / PT /reactor core and winding.
Parameters of Concern:
1. Reactor oil temperature High alarm will comes at 90 deg c. and tripping at 100 deg c.
2. Reactor winding temperature high alarm will comes at 100 deg c. and tripping at 110 deg c
3. Feedback from ct/pt/ will interrupt or goes bad in case of winding damage.
Likely causes:
1. Tripping due to bus bar fault.
2. Tripping due to reactor electrical protection operated.
3. Tripping due to high winding temperature.
4. Tripping due to high oil temperature.
5. Tripping due to buchollz relay operation.
6. Malfunction of any of above relay.
Plant RESPONSE:
1. Bus voltage will increase.
Parameters of Concern:
1. Bus voltage.
2. Line voltage.
3. Generator MVAR.
Likely causes:
1. Ups failure
2. Software/hardware side problem at engineering Station.
Plant RESPONSE:
1. Process status will not available.
2. Remote operation will not possible.
3. Switch yard status will not updated in main control room DCS also.
Parameters of Concern:
1. Plant running parameter feedback will not update.
2. CB/isolator/earth switch status will not update.
Likely causes:
1. Electrical fault of rapping motor.
2. Overloading of rapping motor.
3. Misalignment or poor coupling between motor and rapping shaft which results into motor overloading.
4. High ash level in respective hopper.
Plant RESPONSE:
1. Field loading will increase.
2. Spark rate will rise in respective field
3. Field may got tripped due to high spark rate
Parameters of Concern:
1. Loading of field.
2. Spark rate of field.
3. Dust percentage at chimney outlet.