0% found this document useful (0 votes)
109 views1 page

F605 Error

The document discusses fault management parameters for output phase loss detection. It explains that output phase loss detection can be disabled, set to check only at startup, or set continuously during operation. It describes the dangers of not detecting output phase loss and provides explanations of the number settings for the parameter F605 that controls output phase loss detection mode.

Uploaded by

Muhammad Maulana
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
109 views1 page

F605 Error

The document discusses fault management parameters for output phase loss detection. It explains that output phase loss detection can be disabled, set to check only at startup, or set continuously during operation. It describes the dangers of not detecting output phase loss and provides explanations of the number settings for the parameter F605 that controls output phase loss detection mode.

Uploaded by

Muhammad Maulana
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Detected Fault Management Parameters

Code Name / Description Factory setting

F605 [Output phase loss] Output phase loss detection Mode 3

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
z If F605 = 0, loss of cable is not detected
z If F605 =1 or 2, loss of cable is only detected at the startup of the motor
z Check this action will not endanger personnel or equipment in any way
Failure to follow these instructions will result in death or serious injury.

If output phase loss detection is enabled and an output phase loss persists for more than 1 second, the drive will trip and display
the EPH0 code.

0 [Disabled]
If parameter F605 is set to 0, output phase loss detection is disabled.
1 [First start]: At the first start-up.
If parameter F605 is set to 1, an output phase loss check is made only during the first motor start-up after power is applied to
the drive.
2 [Each start]: At every start-up.
If parameter F605 is set to 2, an output phase loss check is made every time the motor is started.
3 [During run]: During operation.
If parameter F605 is set to 3, continuous output phase loss monitoring is performed while the motor is running.
4 [Permanent]: At start-up and during operation.
If parameter F605 is set to 4, monitoring for an output phase loss is performed at motor start-up and continuously during op-
eration.
5 [Output contactor]: Load side disconnect mode.
Setting 5 for parameter F605 is for applications with a load side disconnect. The drive will automatically restart the motor if the
following are true:
- An all-phase loss has been detected (an output contactor or a load side disconnect has opened)
- The drive detects that a 3-phase connection has been reestablished (the output contactor or load side disconnect has
closed). It is necessary to wait 1 s between disconnection and connection. See following scheme to have an example of
loss of output contactor.
Speed

t
Ouput contactor t1 t2

1
0 t

t1: deceleration without ramp (freewheel)


t2: acceleration with ramp

- A valid run command exists.


An output phase loss detection sweep is made as part of the auto-tuning process, regardless of the setting of parameter F605.
High-speed motors and other special motors may cause nuisance output phase losss.