Product: GENERATOR SET
Model: 3406C GENERATOR SET 9ES
Configuration: 3406C Generator Set 9ES00001-UP
Testing and Adjusting
VR6 Voltage Regulator
Media Number -RENR2480-04 Publication Date -01/12/2007 Date Updated -17/12/2007
i02654206
Voltage Regulator - Test
SMCS - 4467-081-TB
Illustration 1 g01332879
Test Circuit
(1) Droop adjustment
(2) Factory voltage adjustment
(3) Voltage adjustment
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/s... 16/02/2009
PDF created with pdfFactory trial version www.pdffactory.com
3406C Generator Set 9ES00001-UP(SEBP2752 - 15) - Document Structure Página 2 de 3
(4) Knee frequency adjustment
(5) Stability adjustment
(6) 100 Watt light bulbs
(7) Switch (300 VAC and 15 Amperes)
(8) AGC10 fuse
(9) The AC power source (240 V ± 5% )
(10) 20 Ohm Resistor, 15 Watt Minimum 7D-5829 Resistor
Illustration 2 g01021519
The Cat VR6 presents an electrical shock/electrocution hazard. This
hazard will cause serious injury or death.
Service by trained personnel only.
The terminals and heat sinks are live at hazardous voltages when power
is applied and for up to 8 minutes after power is removed.
Perform the following procedure in order to determine whether the voltage regulator is providing
proper excitation.
1. Connect the voltage regulator according to Illustration 2.
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/s... 16/02/2009
PDF created with pdfFactory trial version www.pdffactory.com
3406C Generator Set 9ES00001-UP(SEBP2752 - 15) - Document Structure Página 3 de 3
2. Adjust stability (5) by turning adjustment in a fully clockwise direction.
3. Turn voltage adjustment (3) for five turns in a counterclockwise direction.
4. Close switch (7) in order to apply AC power. The AC power source is 240 V ± 5% for 60 Hz
applications. The AC power source is 200 V ± 5% for 50 Hz applications.
5. If the lights (6) turned on, turn the voltage adjustment (3) in a counterclockwise direction. The
lights should decrease in intensity. The lights should finally go out. Go to step 7.
If the lights (6) did not come on, go to step 6.
6. Turn the voltage adjustment in a clockwise direction. The lights should increase in intensity as
the voltage adjustment is turned CW. The regulator will shut off and the lights (6) will turn off
if one of the following conditions occurs:
¡ The voltage that is being applied to the lights (6) is above 90 V for 30 seconds.
¡ The voltage that is being applied to the lights (6) is above 125 V for 10 seconds.
7. Open switch (7) for at least 15 seconds. The lights (6) will flash momentarily.
8. Close switch (7) .
9. Slowly turn the voltage adjustment (3) CCW until the lights (6) come ON. Try to maintain a
low light intensity to medium light intensity by adjusting the voltage adjustment (3) .
Expected Result: The light bulbs (6) operate, as described above.
Results:
l "YES": The voltage regulator functions properly.
l "NO": The light bulbs (6) react differently. Replace the voltage regulator.
Note: Droop (1) should be adjusted during generator's operation.
Note: Knee frequency (4) should be adjusted during generator's operation.
Note: Stability (5) should be adjusted during generator's operation.
Copyright 1993 - 2009 Caterpillar Inc. Mon Feb 16 15:38:55 EST 2009