0% found this document useful (0 votes)
193 views4 pages

19165a Modulbeschreibung #30860 Steuermodul LEKS-ZR Englisch

The LEKS control module provides functions like lamp error analysis, shutter control, and temperature-based fan control. It has potentiometers to set the optimum exhaust air temperature and duration of lamp startup or fan after-run. It monitors inputs like shutter position and temperature and controls outputs like the shutter motor, fan, and status signals.

Uploaded by

Iulian
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
193 views4 pages

19165a Modulbeschreibung #30860 Steuermodul LEKS-ZR Englisch

The LEKS control module provides functions like lamp error analysis, shutter control, and temperature-based fan control. It has potentiometers to set the optimum exhaust air temperature and duration of lamp startup or fan after-run. It monitors inputs like shutter position and temperature and controls outputs like the shutter motor, fan, and status signals.

Uploaded by

Iulian
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

LEKS Control Module

Functions

The LEKS control module provides the following functions:

- Lamp error analysis


- Shutter status analysis
- Shutter control for electrically operated shutters
- Temperature-based fan control with optional fan after-run
- Potential-free contact for “Ready for production” status
(optional)

Settings

The optimum exhaust air temperature is set using potentiometer 1


(see figure) of the LEKS control module. The setting may only be
modified after consulting the service department at Dr. Hönle AG.

In modules with optional “Ready for production” status, the dura-


tion of the lamp start-up phase is set using potentiometer 2.

In modules with optional fan after-run, the duration of the fan after-
run is adjusted using potentiometer 3.

Figure
LEKS control module
left without options
right with options

Art.Nr. 19165a
LEKS Control Module

Display elements (optional)

Readiness for production is indicated by the green LED (see item


5 in figure). The yellow LED illuminates during fan after-run (item
4).

Signals

Connection Function

1 Supply 1: 24V DC (switched)

2 Supply 1: 0V, Reference potential

3 Input: Shutter closed

4 Input: Shutter open

5 (Optional) Supply 2: 24V DC (permanent)

6 (Optional) Supply 2: 0V, Reference potential

7 (Optional) Fan after-run: Input (connect to 20 externally)

8 (Optional) Fan after-run: Fan output

9 Output 24V: Power level

10 Input: Standby/production mode changeover

11 Shutter motor output

12 Shutter motor output

13, 14 Potential-free lamp error: open if error occurs

15, 16 Potential-free lamp error: closed if error occurs

17 Temperature sensor connection (reference poten-


tial)

18 Temperature sensor connection

19 Output : Fan (reference potential)

20 Output : Fan

21, 23 Potential-free UV ready: closed if ready for produc-


(Optional) tion

24 (Op- Input: UV on
tional)
LEKS Control Module

25, 26 Potential-free shutter: closed if shutter is open

27, 28 Potential-free shutter: closed if shutter is closed

29 Lamp voltage 0V AC input

31 Lamp voltage 230V AC input

32 Lamp voltage 400V AC input

22, 30 n.c.