Example Project Fire Sprinkler Reports

This document provides a summary of a fire sprinkler system design project for a test building owned by Amalgamated, Inc. located at 1234 Main Street in Harrisburg, PA. The project involved calculating sprinkler requirements for an ordinary hazard Group 1 occupancy with a 600 square foot design area and 5.65 K-factor sprinklers. Water supply data from a fire hydrant test indicated a static pressure of 20 psi and flow of 202 gpm. The calculation used an 8-node model of the sprinkler system piping network to determine flows and pressures would meet design requirements.

Uploaded by

magdy saleh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
42 views

Example Project Fire Sprinkler Reports

This document provides a summary of a fire sprinkler system design project for a test building owned by Amalgamated, Inc. located at 1234 Main Street in Harrisburg, PA. The project involved calculating sprinkler requirements for an ordinary hazard Group 1 occupancy with a 600 square foot design area and 5.65 K-factor sprinklers. Water supply data from a fire hydrant test indicated a static pressure of 20 psi and flow of 202 gpm. The calculation used an 8-node model of the sprinkler system piping network to determine flows and pressures would meet design requirements.

Uploaded by

magdy saleh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

EXAMPLE PROJECT

Fire Sprinkler Reports

for

Jones & Wilson, Architects

1234 First Street NW


Harrisburg, PA

Prepared By:

YOUR NAME
ABC Engineering, Inc.
4567 2nd St.
Harrisburg, PA
555-555-9876
November 20, 2000
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr EXAMPLE PROJECT
Hell Page 2

General Project Data Report

General Data
Project Title: EXAMPLE PROJECT Project File Name: Fire Pump Sample Before..fiw
Designed By: YOUR NAME Date: November 20, 2000
Code Reference: NFPA 13 Approving Agency: LOCAL JURISDICTION
Job number: 97594
Client Name: Jones & Wilson, Architects Phone: 555-555-1234
Address: 1234 First Street NW City, State Zip Code: Harrisburg, PA
Company Name: ABC Engineering, Inc. Representative: Mike Roberts
Company Address: 4567 2nd St. City And State: Harrisburg, PA
Phone: 555-555-9876
Job number: 97594
Building Name: Test Building Building Owner: Amalgamated, Inc.
Contact at Building: Jim Jones Phone at Building: 555-555-9876
Address Of Building: 1234 Main Street City, State Zip Code: Harrisburg, PA

Project Data
Description Of Hazard: Ordinary Group 1 Sprinkler System Type: Wet
Design Area Of Water Application: 600 ft² Maximum Area Per Sprinkler: 130 ft²
Default Sprinkler K-Factor: 5.65 K Default Pipe Material: SCHED 40 WET STEEL
Inside Hose Stream Allowance: 50.00 gpm Outside Hose Stream Allowance: 0.00 gpm
In Rack Sprinkler Allowance: 0.00 gpm

Sprinkler Specifications
Make: GLOBE Model: G
Size: 1 Temperature Rating: 160 F
NONE

Water Supply Test Data


Source Of Information: LOCAL FIRE MARSHAL
Test Hydrant ID: 3B Date Of Test: DECEMBER 15, 1992

Hydrant Elevation: 0 ft Static Pressure: 20.00 psi


Test Flow Rate: 202.00 gpm Test Residual Pressure: 12.00 psi
Calculated System Flow Rate: 110.00 gpm Calculated Inflow Residual Pressure: 22.02 psi
Available Residual Pressure At
17.4 psi
System Flow:

Calculation Project Data


Calculation Mode: Demand
HMD Minimum Residual Pressure: 7.00 psi Minimum Desired Flow Density: 0.00 gpm/ft²
Maximum Water Velocity: 20.00 ft/s Maximum Frictional Loss / 100 feet: 20.00 psi
Number Of Active Nodes: 8
Number Of Active Pipes: 8 Number Of Inactive Pipes: 0
Number Of Active Sprinklers: 4 Number Of Inactive Sprinklers: 0

C:\ ...\Fire Pump Sample Before.fiw Friday, November 4, 2022, 6:07 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr EXAMPLE PROJECT
Hell Page 3

Fire Sprinkler Input Data

Node Input Data


Sprinkler Pressure Node Elev (ft) Non-Sprinkler
Area Group
Node Node Description KFactor (K) Estimate (psi) Branch Non- Flow (gpm)
Branch Dia.
No. Branch Description Branch Len. Branch Stnd Stnd Fittings Branch Sprk
(in)
(ft) Fittings (ft) KFactor (K)

Sprinkler B 5.65 7.00 20.00 0.00


30
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler B 5.65 7.09 20.00 0.00


40
---- 0.000 0.0 ---- 0.0 0.00

Non-Sprinkler B N/A 7.54 20.00 50.00


50
---- 0.000 0.0 ---- 0.0 0.00

No Discharge C N/A 7.56 20.00 0.00


60
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler C 5.65 7.12 20.00 0.00


70
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler C 5.65 7.02 20.00 0.00


80
---- 0.000 0.0 ---- 0.0 0.00

No Discharge C N/A 7.86 20.00 0.00


90
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 22.02 20.00 0.00


100
---- 0.000 0.0 ---- 0.0 0.00

C:\ ...\Fire Pump Sample Before.fiw Friday, November 4, 2022, 6:07 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr EXAMPLE PROJECT
Hell Page 4

Fire Sprinkler Input Data

Pipe Input Data


Nominal Nominal Fitting Total CFactor
Beg. End. Type Fitting
Pipe Description Diameter Length Length Length (gpm/inch-
Node Node Group Data
(inch) (feet) (feet) (feet) psi)

30 40 SCHED 40 WET STEEL 1.500 2 10.00 0.00 10.00 120

40 50 SCHED 40 WET STEEL 1.500 2 T 5.00 8.00 13.00 120

50 90 SCHED 40 WET STEEL 2.500 1 15.00 0.00 15.00 120

60 90 SCHED 40 WET STEEL 2.500 1 ET 25.00 18.00 43.00 120

60 70 SCHED 40 WET STEEL 1.500 2 T 5.00 8.00 13.00 120

70 80 SCHED 40 WET STEEL 1.500 2 10.00 0.00 10.00 120

50 60 SCHED 40 WET STEEL 2.500 1 50.00 0.00 50.00 120

100 90 SCHED 40 WET STEEL 2.500 0 300.00 0.00 300.00 120

C:\ ...\Fire Pump Sample Before.fiw Friday, November 4, 2022, 6:07 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr EXAMPLE PROJECT
Hell Page 5

Fire Sprinkler Output Data

Overall Node Groupings Output Data


Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node Imbalance
Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg.
Node Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)

30 40 2 -14.95 14.95 0.00 0.00 7.00

40 30 2 14.95 15.05 0.00 0.00 7.09 0.01461


40 50 2 -29.99

50 40 2 29.99 0.00 50.00 0.00 7.54 0.01129


50 90 1 -71.22
50 60 1 -8.75

60 50 1 8.75 0.00 0.00 0.00 7.56 -0.00542


60 90 1 -38.78
60 70 2 30.03

70 60 2 -30.03 15.07 0.00 0.00 7.12 0.00491


70 80 2 14.96

80 70 2 -14.96 14.97 0.00 0.00 7.02 0.00857

90 50 1 71.22 0.00 0.00 0.00 7.86 0.00628


90 60 1 38.78
90 100 0 -110.00

100 90 0 110.00 0.00 0.00 -110.00 22.02

C:\ ...\Fire Pump Sample Before.fiw Friday, November 4, 2022, 6:07 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr EXAMPLE PROJECT
Hell Page 6

Fire Sprinkler Output Data

Overall Pipe Output Data


q (gpm) F. L./ft Pipe-Len.
Beg. Nodal Spk/Hose Residual Nom. Dia. PF-(psi)
Elevation Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure Inside Dia. PE-(psi)
(feet) Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) C-Value PT-(psi)
(fps) Type-Grp (ft)

30 5.65 20.00 14.95 7.00 1.50 14.95 0.00944 10.00 0.094


40 5.65 20.00 15.05 7.09 1.610 14.95 ----- 0.00 0.000
SCHED 40 WET STEEL 120 2.36 2 10.00 0.094

40 5.65 20.00 15.05 7.09 1.50 15.05 0.03419 5.00 0.444


50 0.00 20.00 50.00 7.54 1.610 29.99 T 8.00 0.000
SCHED 40 WET STEEL 120 4.73 2 13.00 0.444

50 0.00 20.00 50.00 7.54 2.50 8.75 0.00044 50.00 0.022


60 0.00 20.00 0.00 7.56 2.469 8.75 ----- 0.00 0.000
SCHED 40 WET STEEL 120 0.59 1 50.00 0.022

60 0.00 20.00 0.00 7.56 1.50 15.07 0.03428 5.00 0.446


70 5.65 20.00 15.07 7.12 1.610 30.03 T 8.00 0.000
SCHED 40 WET STEEL 120 4.73 2 13.00 0.446

70 5.65 20.00 15.07 7.12 1.50 14.97 0.00945 10.00 0.094


80 5.65 20.00 14.97 7.02 1.610 14.96 ----- 0.00 0.000
SCHED 40 WET STEEL 120 2.36 2 10.00 0.094

50 0.00 20.00 50.00 7.54 2.50 71.22 0.02112 15.00 0.317


90 0.00 20.00 0.00 7.86 2.469 71.22 ----- 0.00 0.000
SCHED 40 WET STEEL 120 4.77 1 15.00 0.317

60 0.00 20.00 0.00 7.56 2.50 0.00 0.00686 25.00 0.295


90 0.00 20.00 0.00 7.86 2.469 38.78 ET 18.00 0.000
SCHED 40 WET STEEL 120 2.60 1 43.00 0.295

100 0.00 20.00 0.00 22.02 2.50 0.00 0.04720 300.00 14.160
90 0.00 20.00 0.00 7.86 2.469 110.00 ----- 0.00 0.000
SCHED 40 WET STEEL 120 7.37 0 300.00 14.160

C:\ ...\Fire Pump Sample Before.fiw Friday, November 4, 2022, 6:07 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr EXAMPLE PROJECT
Hell Page 7

Fire Sprinkler Output Data

Overall Sprinkler Output Data


Flowing Sprinkler Residual Flowing Sprinkler
Area Group Sprinkler Flowing Area
Sprinkler Elevation Pressure Density Discharge
Code KFactor (K) (ft²)
Node No. (feet) (psi) (gpm/ft²) (gpm)

30 B 5.65 20.00 7.00 130.00 0.115 14.95


40 B 5.65 20.00 7.09 130.00 0.116 15.05
Sub Totals For Group B 260.00 0.115 30.00

70 C 5.65 20.00 7.12 130.00 0.116 15.07


80 C 5.65 20.00 7.02 130.00 0.115 14.97
Sub Totals For Group C 260.00 0.116 30.04

Totals For All Groups 520.00 0.115 60.04

C:\ ...\Fire Pump Sample Before.fiw Friday, November 4, 2022, 6:07 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr EXAMPLE PROJECT
Hell Page 8

Fire Sprinkler Output Summary

Hydraulically Most Demanding Sprinkler Node


HMD Sprinkler Node Number: 30
HMD Actual Residual Pressure: 7.00 psi
HMD Actual Flow: 14.95 gpm

Sprinkler Summary
Sprinkler System Type: Wet
Specified Area Of Application: 600.00 ft²
Minimum Desired Density: 0.000 gpm/ft²
Application Average Density: 0.100 gpm/ft²
Application Average Area Per Sprinkler: 150.00 ft²
Sprinkler Flow: 60.04 gpm
Average Sprinkler Flow: 15.01 gpm

Flow Velocity And Imbalance Summary


Maximum Flow Velocity ( In Pipe 90 - 100 ) 7.37 ft/sec
Maximum Velocity Pressure ( In Pipe 90 - 100 ) 0.37 psi

Allowable Maximum Nodal Pressure Imbalance: 0.0100 psi


Actual Maximum Nodal Pressure Imbalance: 0.0093 psi
Actual Average Nodal Pressure Imbalance: 0.0013 psi
Actual Maximum Nodal Flow Imbalance: 0.0146 gpm
Actual Average Nodal Flow Imbalance: 0.0064 gpm

Overall Network Summary


Number Of Unique Pipe Sections: 8
Number Of Flowing Sprinklers: 4

Pipe System Water Volume: 100.17 gal

Sprinkler Flow: 60.04 gpm


Non-Sprinkler Flow: 50.00 gpm

Minimum Required Residual Pressure At System Inflow


22.02 psi
Node:
Demand Flow At System Inflow Node: 110.00 gpm

C:\ ...\Fire Pump Sample Before.fiw Friday, November 4, 2022, 6:07 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr EXAMPLE PROJECT
Hell Page 9

Fire Sprinkler Output Data

Hydraulic Supply/Demand Graph

50

45

40

35
Pressure psi

30

25

20
20

15
12

10

0
0
1 2 3 4 5 6 7 8 9 10
Flowrate(x100) gpm

Supply Curve Data


Static Pressure: 20 psi
Test Residual Pressure: 12 psi
Test Flow Rate: 202 gpm

Demand Curve Data


Calculated Residual Pressure: 22.02 psi
Calculated Flow Rate: 110.00 gpm
Excess Available Residual Pressure At Calculated Flow: -4.61 psi
Pressure Required For First Sprinkler Downstream From Inflow Node To Flow: 0.00 psi

C:\ ...\Fire Pump Sample Before.fiw Friday, November 4, 2022, 6:07 PM