© Siemens AG 2008

SIMATIC S7-400

5/2 Introduction 5/105 Communication


5/2 S7-400/S7-400H/S7-400F/FH 5/105 CP 440
5/106 CP 441-1, CP 441-2
5/4 Central processing units
5/108 CP 443-5 Basic
5/4 CPU 412
5/110 CP 443-5 Extended
5/10 CPU 414
5/112 CP 443-1
5/22 CPU 416
5/115 CP 443-1 Advanced
5/33 CPU 417
5/38 CPU 412H, CPU 414H, CPU 417H 5/120 Modules for SIMATIC S7-400H
5/48 CPU 416F 5/120 Y link for S7-400H
5/56 Sync module for coupling the
5/122 Modules for SIMATIC S7-400F/FH
CPU 41xH
5/122 IM 153-1/153-2
5/57 IF-964 DP PROFIBUS module
5/126 SIPLUS IM 153-1/153-2
5/58 SIPLUS central processing units 5/128 Isolation module
5/58 SIPLUS CPU 416, CPU 417 5/129 SIPLUS isolating module
5/59 SIPLUS CPU 414-4H, CPU 417-4H 5/129 Failsafe input/output modules

5/63 Digital modules 5/130 Connection methods


5/63 SM 421 digital input modules 5/130 Front connectors
5/66 SM 422 digital output modules 5/131 Fully modular connection
5/138 Flexible connection
5/69 SIPLUS digital modules
5/69 SIPLUS SM 421 digital input modules 5/139 Racks
5/69 SIPLUS SM 422 digital output modules 5/139 Racks
5/141 Fan subassembly
5/70 Analog modules
5/142 Expansion racks
5/70 SM 431 analog input modules
5/79 SM 432 analog output modules 5/143 Interface modules
5/143 IM 460-0
5/81 SIPLUS analog modules
5/144 IM 461-0
5/81 SIPLUS SM 431 analog input module
5/145 IM 460-1
SIPLUS SM 432 analog output module
5/146 IM 461-1
5/82 Function modules 5/147 IM 460-3
5/82 FM 450-1 counter module 5/148 IM 461-3
5/84 SIPLUS FM 450-1 counter module 5/149 IM 463-2
5/85 FM 451 positioning module
5/150 Power supplies
5/87 FM 452 cam controller
5/89 FM 453 positioning module 5/154 Accessories
5/91 FM 455 controller module 5/154 Labeling sheets
5/94 FM 458-1 DP application module 5/155 Spare parts
5/95 FM 458-1 DP basic module
5/97 EXM 438-1 input/output
expansion module
5/99 EXM 448 universal communication
expansion module
5/100 EXM 448-2 universal communication
expansion module
5/101 Accessories for FM 458-1 DP
5/104 SIPLUS DCF 77 radio clock module

Brochures
For brochures serving as selection
guides for SIMATIC products refer to:
http://www.siemens.com/simatic/
printmaterial

Siemens ST 70 · 2009
© Siemens AG 2008

SIMATIC S7-400
Introduction
S7-400/S7-400H/S7-400F/FH

■ Overview
S7-400H

5
• The power PLC for the mid to high-end performance ranges.
• The solution for even the most demanding tasks.
• Fault-tolerant automation system with redundant configuration
• With a comprehensive range of modules and performance-
• For applications with high failure safety requirements
graded CPUs for optimal adaptation to the automation task.
Processes with high restart costs, expensive downtimes, little
• Flexible in use through simple implementation of distributed supervision, and few maintenance options
structures; user-friendly connection methods.
• Redundant central functions
• Optimal communication and networking options.
• Increases availability of I/O: Switched-I/O configuration
• User-friendly handling and uncomplicated design without a
• Also possible to use standard-availability I/Os: Single-sided
fan.
configuration
• Can be expanded without problems when the tasks increase.
• Hot standby: Automatic reaction-free switching to the standby
• Multicomputing: unit in the event of a fault
Simultaneous operation of several CPUs in one S7-400 central
• Configuration with 2 separate or one divided central controller
rack.
The overall performance power of an S7-400 is spread by • Connection of switched I/O via redundant PROFIBUS DP
means of multicomputing. For example, complex tasks can be
broken down into technologies such open-loop control,
computing or communication, and assigned to different
CPUs. Each CPU can be assigned its own local I/O.
• Modularity:
The powerful backplane bus of the S7-400 and the communi-
cation interfaces that can be connected direct to the CPU
enable high-performance operation of many communication
lines. This makes it possible, for example, to have one
communication line for HMI and programming tasks, one for
high-performance and equidistant motion control compo-
nents, and one "normal" I/O fieldbus. Additionally required
connections to MES/ERP systems or the Internet can also be
implemented.
• Engineering and diagnostics:
The S7-400 is configured and programmed extremely
efficiently together with the SIMATIC Engineering Tools, partic-
ularly in the case of extensive automation solutions with a high
engineering component. There are high-level languages such
as SCL available for this purpose and graphical engineering
tools for sequential controls, state diagrams, and technology-
oriented diagrams.

5/2 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Introduction
S7-400/S7-400H/S7-400F/FH

■ Overview (continued) ■ Technical specifications


S7-400F/FH General technical specifications
Degree of protection IP20
Ambient temperature 0 … +60 °C
Relative humidity 5 … 95 %, no condensation
Atmospheric pressure 860 … 1080 hPa
Electromagnetic compatibility EU Directive 89/336/EWG;
• per EN 50082-2
(noise immunity), testing per :
IEC 61000-4-2, IEC 61000-4-4,
IEC 61000-4-3, IEC 61000-4-6,
IEC 61000-4-5;
Emitted interference to
EN 50081-2, limit values
according to EN 55011, Class A,

5
Group 1
Mechanical tolerance
• Vibration, tested per/with IEC 68, Part 2-6/10 to 58 Hz;
constant amplitude 0.075 mm;
58 to 150 Hz;
• Failsafe automation system for plant with high safety require-
ments constant acceleration 1 g;
• Complies with safety requirements up to SIL 3 to IEC 61508, Duration of vibrations:
AK6 to DIN V 19250 and Cat. 4 to EN 954-1 10 frequency cycles per axis in
the direction of each of the three
• If required, also fault tolerant through redundant configuration mutually normal axes
• Without additional wiring of the failsafe I/O: • Impact, tested per/with IEC 68, Part 2-27/semi-sinusoidal:
Failsafe communication via PROFIBUS DP with PROFISafe
profile. impact 15 g (peak value),
duration 11 ms
• Based on S7-400H and ET 200M, includes failsafe modules
• Standard modules for non-safety-related applications can
also be used in the automation system For brochures serving as selection guides for SIMATIC products
• Isolating module for common use of failsafe and standard refer to:
modules in safety operation on an ET 200M http://www.siemens.com/simatic/printmaterial

Siemens ST 70 · 2009 5/3


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 412

■ Overview
• The low-cost starter solution for the medium performance
range
• Can be used in small and medium-sized systems with require-
ments of the medium performance range

■ Technical specifications
6ES7 412-1XJ05- 6ES7 412-2XJ05- 6ES7 412-1XJ05- 6ES7 412-2XJ05-
0AB0 0AB0 0AB0 0AB0
Product status Backup
Hardware product status 1 • present Yes Yes
Firmware version V5.0 V5.0 • with battery Yes Yes
associated programming STEP7 V5.3 SP2 or STEP7 V5.3 SP2 or • without battery No No
package higher with HW- higher with HW-
update update CPU/blocks

Feeding of external buffer 5 to 15 V DC 5 to 15 V DC DB


voltage to CPU • Number, max. 1 500; Number 3 000; Number
Current consumption range: 1 to 16,000 range: 1 to 16,000

from backplane bus DC 5 V, 0.6 A 1.1 A • Size, max. 64 Kibyte 64 Kibyte


max. FB
from interface DC 5 V, max. 90 mA; At the DP 90 mA; At each DP • Number, max. 750; Number 1 500; Number
interface interface range: 0 to 7999 range: 0 to 7999
Current consumption/ • Size, max. 64 Kibyte 64 Kibyte
power loss
FC
Power loss, typ. 2.5 W 4W
• Number, max. 750; Number 1 500; Number
Backup battery range: 0 to 7,999 range: 0 to 7,999
• Buffer current, typ. 125 μA; 125 μA; • Size, max. 64 Kibyte 64 Kibyte
(up to 40 °C) Valid up to 40°C
OB
• Buffer current, max. 550 μA 550 μA; Dealt with
in the module data • Size, max. 64 Kibyte 64 Kibyte
manual with the Nesting depth
secondary conditi-
ons and the factors • per priority class 24 24
of influence
• additional within an 1 1
Memory error OB
Type of storage CPU/processing times
RAM for bit operations, min. 75 ns 75 ns
• integrated (for program) 144 Kibyte 256 Kibyte for word operations, min. 75 ns 75 ns
• integrated (for data) 144 Kibyte 256 Kibyte for fixed point arithmetic, 75 ns 75 ns
No No min.
• expandable
for floating point arithmetic, 225 ns 225 ns
Load memory min.
• expandable FEPROM Yes Yes

• expandable FEPROM, 64 MByte 64 MByte


max.
• integrated RAM, max. 512 Kibyte 512 Kibyte

• expandable RAM Yes Yes

• expandable RAM, max. 64 MByte 64 MByte

5/4 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 412

■ Technical specifications (continued)


6ES7 412-1XJ05- 6ES7 412-2XJ05- 6ES7 412-1XJ05- 6ES7 412-2XJ05-
0AB0 0AB0 0AB0 0AB0
Times/counters and their Process image
remanence
• Inputs, adjustable 4 Kibyte 4 Kibyte
S7 counter
• Outputs, adjustable 4 Kibyte 4 Kibyte
• Number 2 048 2 048
• Inputs, preset 128 byte 128 byte
• Remanence
• Outputs, preset 128 byte 128 byte
- adjustable Yes Yes
- lower limit 0 0 • consistent data, max. 244 byte 244 byte
- upper limit 2 047 2 047 • Access to consistent data Yes Yes
- preset Z 0 to Z 7 Z 0 to Z 7 in process image
• Counting range Subprocess images
- lower limit 0 0 • Number of subprocess 15 15
- upper limit 999 999 images, max.
IEC counter
• present Yes Yes
Digital channels
• Inputs 32 768 32 768
5
• Type SFB SFB • Outputs 32 768 32 768
S7 times • Inputs, of which central 32 768 32 768
• Number 2 048 2 048 • Outputs, of which central 32 768 32 768
• Remanence Analog channels
- adjustable Yes Yes • Inputs 2 048 2 048
- lower limit 0 0
- upper limit 2 047 2 047 • Outputs 2 048 2 048
- preset No times retentive • Inputs, of which central 2 048 2 048
• Time range • Outputs, of which central 2 048 2 048
- lower limit 10 ms 10 ms Hardware config.
- upper limit 9 990 s 9 990 s
connectable OPs 31 31
IEC timer
Central devices, max. 1 1
• present Yes Yes
Expansion devices, max. 21 21
• Type SFB SFB
Multicomputing Yes; Max. 4 CPUs Yes; Max. 4 CPUs
Data areas and their (with UR1 or UR2) (with UR1 or UR2)
remanence
IM
remanent data area, total Total working and Total working and
load memory load memory (with • Number of connectable 6 6
backup battery) IMs (total), max.
Flag • Number of connectable 6 6
IM 460s, max.
• Number, max. 4 Kibyte 4 Kibyte
• Number of connectable 4; IM 463-2 4; IM 463-2
• Remanence available Yes Yes IM 463s, max.
• Number of clock memories 8; 8; Number of DP masters
(in 1 memory byte) (in 1 memory byte)
• integrated 1 2
Address area
• via IM 467 4 4
I/O address area
• via CP 10; CP 443-5 10; CP 443-5
• Inputs 4 Kibyte 4 Kibyte Extended Extended
• Outputs 4 Kibyte 4 Kibyte • Mixed mode IM + CP No; IM 467 cannot No; IM 467 cannot
• of which, distributed permitted be used with be used with
CP 443-5 Ext.; CP 443-5 Ext.;
- MPI/DP interface, inputs 2 Kibyte 2 Kibyte IM 467 cannot be IM 467 cannot be
- MPI/DP interface, 2 Kibyte 2 Kibyte used with CP 443-1 used with CP 443-1
outputs EX40 in PN IO EX40 in PN IO
- DP interface, inputs 4 Kibyte mode mode
- DP interface, outputs 4 Kibyte • via interface module 0 0
• Number of pluggable 6 6
S5 modules (via adapter
capsule in central device),
max.

Siemens ST 70 · 2009 5/5


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 412

■ Technical specifications (continued)


6ES7 412-1XJ05- 6ES7 412-2XJ05- 6ES7 412-1XJ05- 6ES7 412-2XJ05-
0AB0 0AB0 0AB0 0AB0
Number of IO controllers Test commissioning
functions
• integrated 0
Status/control
• via CP 4; Via CP 443-1 EX 41
Via CP 443-1 EX 41 in PN mode; • Status/control variable Yes Yes
in PN mode; max. 4 max. 4 in central
in central controller controller Forcing

Number of operable FMs • Forcing Yes Yes


and CPs (recommended) Status block Yes Yes
• FM Limited due to Limited due to Single step Yes Yes
number of slots and number of slots and
number of connec- number of connec- Number of breakpoints 4 4
tions tions Diagnostic buffer
• CP, point-to-point Limited due to Limited due to • present Yes Yes
5 number of slots and
number of connec-
tions
number of slots and
number of connec-
tions
• Number of entries, max. 200 400
• adjustable Yes Yes
• PROFIBUS and Ethernet 14; Of which 10 14; Of which 10
• preset 120 120
CPs CPs max. or IMs as CP or IM max. as
DP master, 4 PN DP master and PN Communication functions
controller maximum controller
PG/OP communication Yes Yes
Time
Routing Yes Yes
Clock
Global data communication
• Hardware clock Yes Yes
(real-time clock) • supported Yes Yes

• buffered and synchroni- Yes Yes • Size of GD packets, max. 54 byte 54 byte
zable S7 basic communication
• Resolution 1 ms 1 ms • supported Yes Yes
Operating hours counter • Useful data per job, max. 76 byte 76 byte
• Number 8 8 S7 communication
Clock synchronization • supported Yes Yes
• supports Yes Yes • Useful data per job, max. 64 Kibyte 64 Kibyte
• to MPI, Master Yes Yes S5-compatible communi-
• to MPI, Slave Yes Yes cation

• to DP, Master Yes Yes • supported Yes; Via FC Yes; (via CP max.
AG_SEND and 10 and
• to DP, Slave Yes Yes AG_RECV, max. FC AG_SEND and
via 10 CP 443-1 or FC AG_RECV)
• in AS, Master Yes Yes
443-5
• in AS, Slave Yes Yes
• Useful data per job, max. 8 Kibyte 8 Kibyte
• on Ethernet via NTP No; Via CP No; Via CP
Standard communication
S7 message functions (FMS)
Number of login stations for 31; Max. 31 with 31; Max. 31 with • supported Yes; Via CP and Yes; Via CP and
message functions, max. alarm_S and alarm_S and loadable FB loadable FB
alarm_D (OP’s); alarm_D (OP’s);
Web server
max. 8 with alarm_8 max. 8 with alarm_8
and alarm_P (e.g. • Web server No; Via CP No; Via CP
WinCC)
• ISO-on-TCP (RFC1006) Via CP 443-1 Adv. Via CP 443-1 Adv.
Symbol-related messages Yes Yes and loadable FB and loadable FB
Number of messages - Number of connections, 30
max.
• overall, max. 512 512 - Data length, max. 1 452 byte 1452
Block related messages Yes Yes Number of connections
Alarm 8-blocks Yes Yes
• overall 32 32
Instrumentation & control Yes Yes
messages

5/6 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 412

■ Technical specifications (continued)


6ES7 412-1XJ05- 6ES7 412-2XJ05- 6ES7 412-1XJ05- 6ES7 412-2XJ05-
0AB0 0AB0 0AB0 0AB0
1st interface 2nd interface
Physics RS 485 / PROFIBUS RS 485 / PROFIBUS Physics RS 485 / PROFIBUS
isolated Yes Yes isolated Yes
Functionality Functionality
• MPI Yes Yes • DP master Yes
• DP master Yes Yes • DP slave Yes
• DP slave Yes Yes DP master
MPI • Number of connections, 16
max.
• Number of connections 32 32
• Services
• Services
- PG/OP communication Yes

5
- PG/OP communication Yes Yes
- Routing Yes
- Routing Yes Yes
- S7 basic communication Yes
- Global data communi- Yes Yes
cation - S7 communication Yes
- S7 basic communication Yes Yes - equidistance support Yes
- S7 communication Yes Yes - Activation/deactivation of Yes
DP slaves
• Transmission speeds, 12 MBit/s 12 MBit/s - direct data exchange Yes
max. (cross traffic)
DP master • Transmission speeds, 12 MBit/s
• Number of connections, 16 16 max.
max. • Number of DP slaves, max. 64
• Services • Address area
- PG/OP communication Yes Yes - Inputs, max. 4 Kibyte
- Routing Yes Yes - Outputs, max. 4 Kibyte
- S7 basic communication Yes Yes
• Useful data per DP slave
- S7 communication Yes Yes
- Inputs, max. 244 byte
- equidistance support Yes Yes
- Outputs, max. 244 byte
- Activation/deactivation of Yes Yes
DP slaves DP slave
- direct data exchange Yes Yes • Number of connections 16
(cross traffic)
• Services
• Transmission speeds, 12 MBit/s 12 MBit/s
max. - Routing Yes
- Programming Yes
• Number of DP slaves, max. 32; Max. 544 slots 32
• GSD file http://support.
• Address area automation.
- Inputs, max. 2 Kibyte 2 Kibyte siemens.com/WW/
- Outputs, max. 2 Kibyte 2 Kibyte view/en/113652
• Useful data per DP slave • Transmission speeds, 12 MBit/s
- Inputs, max. 244 byte 244 byte max.
- Outputs, max. 244 byte 244 byte • Transfer memory
DP slave - Inputs 244 byte
- Outputs 244 byte
• Number of connections 16 16
• Address area, max. 32
• Services
- PG/OP communication Yes Yes • Useful data per address 32 byte
area, max.
- Routing Yes Yes
• Useful data per address 32 byte
• Transmission speeds, 12 MBit/s 12 MBit/s area, of which consistent,
max. max.
• Transfer memory Isochronous mode
- Inputs 244 byte 244 byte
- Outputs 244 byte 244 byte Useful data per isoch- 244 byte 244 byte
ronous slave, max.
• Address area, max. 32; Virtual slots 32
equidistance Yes Yes
• Useful data per address 32 byte 32 byte
area, max. shortest clock pulse 1.5 ms; 1.5 ms;
0.5 ms without use 0.5 ms without use
• Useful data per address 32 byte 32 byte of SFC 126, 127 of SFC 126, 127
area, of which consistent,
max.

Siemens ST 70 · 2009 5/7


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 412

■ Technical specifications (continued)


6ES7 412-1XJ05- 6ES7 412-2XJ05- 6ES7 412-1XJ05- 6ES7 412-2XJ05-
0AB0 0AB0 0AB0 0AB0
CiR configuration in RUN Nesting levels 7 7
CiR synchronization time, 100 ms 100 ms User program protection/ Yes Yes
basic load password protection
CiR synchronization time, 200 μs 200 μs Dimensions
time per I/O slave
Required slots 1 1
CPU/programming
Dimensions
Configuration software
• Width 25 mm 25 mm
• STEP 7 Yes Yes
• Height 290 mm 290 mm
Programming language
• Depth 219 mm 219 mm
• LAD Yes Yes
Weights
• FUP Yes Yes
• Weight, approx. 720 g 720 g
5 • AWL
• SCL
Yes
Yes
Yes
Yes
• CFC Yes Yes
• GRAPH Yes Yes
• HiGraph Yes Yes

5/8 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 412

■ Ordering data Order No. Order No.


CPU 412-1 6ES7 412-1XJ05-0AB0 Manual "Communication for
SIMATIC S7-300/-400"
Main memory 288 KB,
power supply 24 V DC, German 6ES7 398-8EA00-8AA0
MPI/PROFIBUS DP master
interface, slot for memory card, English 6ES7 398-8EA00-8BA0
incl. slot number labels French 6ES7 398-8EA00-8CA0
CPU 412-2 6ES7 412-2XJ05-0AB0 Spanish 6ES7 398-8EA00-8DA0
Main memory 512 KB, Italian 6ES7 398-8EA00-8EA0
power supply 24 V DC,
MPI/PROFIBUS DP master SIMATIC Manual Collection B3 6ES7 998-8XC01-8YE0
interface, slot for memory card, Electronic manuals on DVD, five
incl. slot number labels languages: S7-200/300/400, C7,
Memory card RAM LOGO!, SIMATIC DP, PC, PG,
STEP 7, engineering software,
64 KB 6ES7 952-0AF00-0AA0 runtime software, PCS 7, SIMATIC
256 KB 6ES7 952-1AH00-0AA0 HMI, SIMATIC NET

1 MB 6ES7 952-1AK00-0AA0 SIMATIC Manual Collection


update service for 1 year
B3 6ES7 998-8XC01-8YE2
5
2 MB 6ES7 952-1AL00-0AA0
Current "Manual Collection" DVD
4 MB 6ES7 952-1AM00-0AA0 and the three subsequent
updates
8 MB 6ES7 952-1AP00-0AA0
Brochure "SIMATIC S7-400
16 MB 6ES7 952-1AS00-0AA0 automation system - Design
64 MB 6ES7 952-1AY00-0AA0 and application"
FEPROM memory card German 6ES7 498-8AA00-8AB0
64 KB 6ES7 952-0KF00-0AA0 English 6ES7 498-8AA00-8BB0
256 KB 6ES7 952-0KH00-0AA0 RS 485 bus connector with
90° cable outlet
1 MB 6ES7 952-1KK00-0AA0
Max. transfer rate 12 Mbit/s
2 MB 6ES7 952-1KL00-0AA0
Without PG interface 6ES7 972-0BA12-0XA0
4 MB 6ES7 952-1KM00-0AA0
With PG interface 6ES7 972-0BB12-0XA0
8 MB 6ES7 952-1KP00-0AA0
RS 485 bus connector with
16 MB 6ES7 952-1KS00-0AA0 angled cable outlet
32 MB 6ES7 952-1KT00-0AA0 Max. transfer rate 12 Mbit/s
64 MB 6ES7 952-1KY00-0AA0 Without PG interface 6ES7 972-0BA41-0XA0
MPI cable 6ES7 901-0BF00-0AA0 With PG interface 6ES7 972-0BB41-0XA0
For connecting SIMATIC S7 and RS 485 bus connector with 90°
the PG through MPI; 5 m in length cable outlet for Fast Connect
Slot number plates 6ES7 912-0AA00-0AA0 system

1 set (spare part) Max. transfer rate 12 Mbit/s

Manual "SIMATIC S7-400 Without PG interface 6ES7 972-0BA51-0XA0


automation system" With PG interface 6ES7 972-0BB51-0XA0
incl. instruction list RS 485 bus connector with
German 6ES7 498-8AA05-8AA0 axial cable outlet

English 6ES7 498-8AA05-8BA0 For SIMATIC OP, for connection to 6GK1 500-0EA02
PPI, MPI, PROFIBUS
French 6ES7 498-8AA05-8CA0
PROFIBUS FastConnect
Spanish 6ES7 498-8AA05-8DA0 bus cable
Italian 6ES7 498-8AA05-8EA0 Standard type with special design 6XV1 830-0EH10
for quick mounting, 2-core,
S7-400 instructions list
shielded, sold by the meter, max.
German 6ES7 498-8AA05-8AN0 delivery unit 1000 m, minimum
order quantity 20 m
English 6ES7 498-8AA05-8BN0
French 6ES7 498-8AA05-8CN0
Spanish 6ES7 498-8AA05-8DN0
Italian 6ES7 498-8AA05-8EN0
B3: Subject to export regulations: AL: N and ECCN: 5D992B1

Siemens ST 70 · 2009 5/9


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 414

■ Overview
• CPUs for high demands in the mid-level performance range
• Applicable for plants with additional demands on
programming scope and processing speed
• Integrated PROFINET functions in CPU 414-3 PN/DP

5
■ Technical specifications
6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM05-0AB0
Product status
Hardware product status 1
Firmware version V5.0 V5.0 V5.0
associated programming STEP7 V5.3 SP2 or higher with HW- STEP7 V5.3 SP2 or higher with HW- STEP7 V5.4 SP1 or higher
package update update
Feeding of external buffer 5 to 15 VDC 5 to 15 VDC 5 to 15 VDC
voltage to CPU
Current consumption
from backplane bus DC 5 V, 1.1 A 1.3 A 1.4 A
max.
from interface DC 5 V, max. 90 mA; At each DP interface 90 mA; At each DP interface 90 mA; At each DP interface
Current consumption/
power loss
Power loss, typ. 4W 4.5 W 5.5 W
Backup battery
• Buffer current, typ. 125 μA; Valid up to 40°C 125 μA; Valid up to 40°C 125 μA; Valid up to 40°C
• Buffer current, max. 550 μA 550 μA 550 μA
Memory
Type of storage
RAM
• integrated (for program) 0.5 MByte 1.4 MByte 1.4 MByte

• integrated (for data) 0.5 MByte 1.4 MByte 1.4 MByte

• expandable No No No

Load memory
• expandable FEPROM Yes Yes Yes

• expandable FEPROM, max. 64 MByte 64 MByte 64 MByte

• integrated RAM, max. 512 Kibyte 512 Kibyte 512 Kibyte

• expandable RAM Yes Yes Yes

• expandable RAM, max. 64 MByte 64 MByte 64 MByte

Backup
• present Yes Yes Yes
• with battery Yes Yes Yes; All data
• without battery No No No
CPU/blocks
DB
• Number, max. 6 000; Number range: 1 to 16,000 6 000; Number range: 1 to 16,000 6 000; Number range: 1 to 16,000
• Size, max. 64 Kibyte 64 Kibyte 64 Kibyte

5/10 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 414

■ Technical specifications (continued)


6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM05-0AB0
FB
• Number, max. 3 000; Number range: 0 to 7999 3 000; Number range: 0 to 7999 3 000; Number range: 0 to 7999
• Size, max. 64 Kibyte 64 Kibyte 64 Kibyte
FC
• Number, max. 3 000; Number range: 0 to 7,999 3 000; Number range: 0 to 7999 3 000; Number range: 0 to 7999
• Size, max. 64 Kibyte 64 Kibyte 64 Kibyte
OB
• Size, max. 64 Kibyte 64 Kibyte 64 Kibyte
Nesting depth
• per priority class 24 24 24
• additional within an error OB 1 1 1
CPU/processing times 5
for bit operations, min. 45 ns 45 ns 45 ns
for word operations, min. 45 ns 45 ns 45 ns
for fixed point arithmetic, min. 45 ns 45 ns 45 ns
for floating point arithmetic, min. 135 ns 135 ns 135 ns
Times/counters and their
remanence
S7 counter
• Number 2 048 2 048 2 048
• Remanence
- adjustable Yes Yes Yes
- lower limit 0 0 0
- upper limit 2 047 2 047 2 047
- preset From Z 0 to Z 7 From Z 0 to Z 7 From Z 0 to Z 7
• Counting range
- lower limit 0 0 0
- upper limit 999 999 999
IEC counter
• present Yes Yes Yes
• Type SFB SFB SFB
S7 times
• Number 2 048 2 048 2 048
• Remanence
- adjustable Yes Yes Yes
- lower limit 0 0 0
- upper limit 2 047 2 047 2 047
- preset No times retentive No times retentive
• Time range
- lower limit 10 ms 10 ms 10 ms
- upper limit 9 990 s 9 990 s 9 990 s
IEC timer
• present Yes Yes Yes
• Type SFB SFB SFB
Data areas and their
remanence
remanent data area, total Total working and load memory Total working and load memory Total working and load memory
(with backup battery) (with backup battery) (with backup battery)

Siemens ST 70 · 2009 5/11


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 414

■ Technical specifications (continued)


6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM05-0AB0
Flag
• Number, max. 8 Kibyte 8 Kibyte 8 Kibyte
• Remanence available Yes Yes Yes
• Number of clock memories 8; (in 1 memory byte) 8; (in 1 memory byte) 8; (in 1 memory byte)
Address area
I/O address area
• Inputs 8 Kibyte 8 Kibyte 8 Kibyte
• Outputs 8 Kibyte 8 Kibyte 8 Kibyte
• of which, distributed
- MPI/DPinterface, inputs 2 Kibyte 2 Kibyte 2 Kibyte
- MPI/DP interface, outputs 2 Kibyte 2 Kibyte 2 Kibyte
- DP interface, inputs 6 Kibyte 6 Kibyte 6 Kibyte
5 - DP interface, outputs
- PN interface, inputs
6 Kibyte 6 Kibyte 6 Kibyte
8 Kibyte
- PN interface, outputs 8 Kibyte
Process image
• Inputs, adjustable 8 Kibyte 8 Kibyte 8 Kibyte
• Outputs, adjustable 8 Kibyte 8 Kibyte 8 Kibyte
• Inputs, preset 256 byte 256 byte 256 byte
• Outputs, preset 256 byte 256 byte 256 byte
• consistent data, max. 244 byte 244 byte 244 byte
• Access to consistent data in Yes Yes Yes
process image
Subprocess images
• Number of subprocess 15 15 15
images, max.
Digital channels
• Inputs 65 536 65 536 65 536
• Outputs 65 536 65 536 65 536
• Inputs, of which central 65 536 65 536 65 536
• Outputs, of which central 65 536 65 536 65 536
Analog channels
• Inputs 4 096 4 096 4 096
• Outputs 4 096 4 096 4 096
• Inputs, of which central 4 096 4 096 4 096
• Outputs, of which central 4 096 4 096 4 096
Hardware config.
connectable OPs 31 31 31
Central devices, max. 1 1 1
Expansion devices, max. 21 21 21
Multicomputing Yes; Max. 4 CPUs (with UR1 or UR2) Yes; Max. 4 CPUs (with UR1 or UR2) Yes; Max. 4 CPUs (with UR1 or UR2)
IM
• Number of connectable IMs 6 6 6
(total), max.
• Number of connectable 6 6 6
IM 460s, max.
• Number of connectable 4; IM 463-2 4; IM 463-2 4; IM 463-2
IM 463s, max.

5/12 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 414

■ Technical specifications (continued)


6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM05-0AB0
Number of DP masters
• integrated 2 2 1
• via IM 467 4 4 4
• via CP 10; CP 443-5 Extended 10; CP 443-5 Extended 10; CP 443-5 Extended
• Mixed mode IM + CP permitted No; IM 467 cannot be used with No; IM 467 cannot be used with No; IM 467 cannot be used with
CP 443-5 Ext.; IM 467 cannot be CP 443-5 Ext.; IM 467 cannot be CP 443-5 Ext.; IM 467 cannot be
used with CP 443-1 EX40 in PN IO used with CP 443-1 EX40 in PN IO used with CP 443-1 EX40 in PN IO
mode mode mode
• via interface module 0 1 1; IF 964-DP
• Number of pluggable S5 6 6 6
modules (via adapter capsule
in central device), max.
Number of IO controllers
• integrated 1 5
• via CP 4; Via CP 443-1 EX 41 in PN mode; 4; Via CP 443-1 EX 41 in PN mode; 4; Via CP 443-1 EX 41 in PN mode;
max. 4 in central controller max. 4 in central controller max. 4 in central controller
Number of operable FMs and
CPs (recommended)
• FM Limited due to number of slots and Limited due to number of slots and Limited due to number of slots and
number of connections number of connections number of connections
• CP, point-to-point Limited due to number of slots and Limited due to number of slots and Limited due to number of slots and
number of connections number of connections number of connections
• PROFIBUS and Ethernet CPs 14; Of which 10 CP or IM max. as 14; Of which 10 CP or IM max. as 14; Of which 10 CP/IM max. as
DP master and PN controller DP master and PN controller DP master and PN controller
Time
Clock
• Hardware clock Yes Yes Yes
(real-time clock)
• buffered and synchronizable Yes Yes Yes
• Resolution 1 ms 1 ms 1 ms
Operating hours counter
• Number 8 8 8
Clock synchronization
• supports Yes Yes Yes
• to MPI, Master Yes Yes Yes
• to MPI, Slave Yes Yes Yes
• to DP, Master Yes Yes Yes
• to DP, Slave Yes Yes Yes
• in AS, Master Yes Yes Yes
• in AS, Slave Yes Yes Yes
• on Ethernet via NTP Yes; as client
• to IF 964 DP Yes Yes
S7 message functions
Number of login stations for 31; Max. 31 with alarm_S and 31; Max. 31 with alarm_S and 31; Max. 31 with alarm_S and
message functions, max. alarm_D (OP’s); max. 8 with alarm_8 alarm_D (OP’s); max. 8 with alarm_8 alarm_D (OP’s); max. 8 with alarm_8
and alarm_P (e.g. WinCC) and alarm_P (e.g. WinCC) and alarm_P (e.g. WinCC)
Symbol-related messages Yes Yes Yes
Number of messages
• overall, max. 512 512 512
Block related messages Yes Yes Yes
Alarm 8-blocks Yes Yes Yes
Instrumentation & control Yes Yes Yes
messages

Siemens ST 70 · 2009 5/13


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 414

■ Technical specifications (continued)


6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM05-0AB0
Test commissioning functions
Status/control
• Status/control variable Yes Yes Yes
Forcing
• Forcing Yes Yes Yes
Status block Yes Yes Yes
Single step Yes Yes Yes
Number of breakpoints 4 4 4
Diagnostic buffer
• present Yes Yes Yes
• Number of entries, max. 400 3 200 3 200

5 • adjustable Yes Yes Yes


• preset 120 120 120
Communication functions
PG/OP communication Yes Yes Yes
Routing Yes Yes Yes
Global data communication
• supported Yes Yes Yes
• Size of GD packets, max. 54 byte 54 byte 54 byte
S7 basic communication
• supported Yes Yes Yes
• Useful data per job, max. 76 byte 76 byte 76 byte
S7 communication
• supported Yes Yes Yes
• Useful data per job, max. 64 Kibyte 64 Kibyte 64 Kibyte
S5-compatible communication
• supported Yes; (via CP max. 10 and FC Yes; (via CP max. 10 and FC Yes; (via CP max. 10 and FC
AG_SEND and FC AG_RECV) AG_SEND and FC AG_RECV) AG_SEND and FC AG_RECV)
• Useful data per job, max. 8 Kibyte 8 Kibyte 8 Kibyte
Standard communication (FMS)
• supported Yes; Via CP and loadable FB Yes; Via CP and loadable FB Yes; Via CP and loadable FB
Web server
• Web server No; Via CP No; Via CP Yes
Open IE communication
• TCP/IP Yes
- Number of connections, max. 32
- Data length, max. 32 Kibyte
• ISO-on-TCP (RFC1006) Via CP 443-1 Adv. and loadable FB Via CP 443-1 Adv. and loadable FB Yes
- Number of connections, max. 32
- Data length, max. 1452 1452 32 Kibyte; 1452 bytes via
CP 443-1 Adv.
• UDP Yes
- Number of connections, max. 32
- Data length, max. 1 472 byte
Number of connections
• overall 32 32 32
PROFINET CBA (at set setpoint
communication load)
• Number of remote intercon- 32
nection partners
• Number of functions, 150
master/slave
• Total of all master/slave 4 500
connections

5/14 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 414

■ Technical specifications (continued)


6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM05-0AB0
PROFINET CBA (at set setpoint
communication load)
• Data length of all incoming 45 000 byte
connections master/slave,
max.
• Data length of all outgoing 45 000 byte
connections master/slave,
max.
• Number of device-internal and 1 000
PROFIBUS interconnections
• Data length of device-internal 16 000 byte
and PROFIBUS interconnec-
tions, max.
• Data length per connection, 2 000 byte
max.
• Remote interconnections with
5
acyclic transmission
- Sampling frequency: 200 ms; Depending on preset
sampling interval, min. communcation load, number of inter-
connections and data length used
- Number of incoming inter- 250
connections
- Number of outgoing intercon- 250
nections
- Data length of all incoming 8 000 byte
interconnections, max.
- Data length of all outgoing 8 000 byte
interconnections, max.
- Data length per connection, 2 000 byte
max.
• Remote interconnections with
cyclic transmission
- Transmission frequency: 1 ms; Depending on preset commu-
transmission interval, min. nication load, number of inter-
connections and data length used
- Number of incoming inter- 300
connections
- Number of outgoing intercon- 300
nections
- Data length of all incoming 4 800 byte
interconnections, max.
- Data length of all outgoing 4 800 byte
interconnections, max.
- Data length per connection, 250 byte
max.
• HMI variables via PROFINET
(acyclic)
- Number of log-in stations for 2x PN OPC / 1x iMap
HMI variables
(PN OPC/iMap)
- HMI variable updating 500 ms
- Number of HMI variables 1 000
- Data length of all HMI 32 000 byte
variables, max.
• PROFIBUS proxy functionality
- supported Yes; 32 PROFIBUS slaves max.
connectable
- Data length per connection, 240 byte; Slave-dependent
max.
1st interface
Physics RS 485 / PROFIBUS RS 485 / PROFIBUS RS 485 / PROFIBUS + MPI
isolated Yes Yes Yes

Siemens ST 70 · 2009 5/15


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 414

■ Technical specifications (continued)


6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM05-0AB0
Functionality
• MPI Yes Yes Yes
• DP master Yes Yes Yes
• DP slave Yes Yes Yes
MPI
• Number of connections 32 32 32; if a diagnostic repeater is used
on the line, the number of connection
resources on the line is reduced by 1
• Services
- PG/OP communication Yes Yes Yes
- Routing Yes Yes Yes
- Global data communication Yes Yes Yes
- S7 basic communication Yes Yes Yes
5 - S7 communication Yes Yes Yes
• Transmission speeds, max. 12 MBit/s 12 MBit/s 12 MBit/s
DP master
• Number of connections, max. 16 16 16
• Services
- PG/OP communication Yes Yes Yes
- Routing Yes Yes Yes
- Global data communication No No No
- S7 basic communication Yes Yes Yes
- S7 communication Yes Yes Yes
- equidistance support Yes Yes Yes
- Activation/deactivation of Yes Yes Yes
DP slaves
- direct data exchange Yes Yes Yes
(cross traffic)
• Transmission speeds, max. 12 MBit/s 12 MBit/s 12 MBit/s
• Number of DP slaves, max. 32 32 32
• Address area
- Inputs, max. 2 Kibyte 2 Kibyte 2 Kibyte
- Outputs, max. 2 Kibyte 2 Kibyte 2 Kibyte
• Useful data per DP slave
- Inputs, max. 244 byte 244 byte 244 byte
- Outputs, max. 244 byte 244 byte 244 byte
DP slave
• Number of connections 16 16 16
• Services
- PG/OP communication Yes Yes Yes
- Routing Yes Yes Yes
• Transmission speeds, max. 12 MBit/s 12 MBit/s 12 MBit/s
• Transfer memory
- Inputs 244 byte 244 byte 244 byte
- Outputs 244 byte 244 byte 244 byte
DP slave (continued)
• Address area, max. 32 32 32; Virtual slots
• Useful data per address area, 32 byte 32 byte 32 byte
max.
• Useful data per address area, 32 byte 32 byte 32 byte
of which consistent, max.
2nd interface
Physics RS 485 / PROFIBUS RS 485 / PROFIBUS Ethernet
isolated Yes Yes Yes

5/16 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 414

■ Technical specifications (continued)


6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM05-0AB0
Functionality
• DP master Yes Yes No
• DP slave Yes Yes No
• PROFINET IO controller Yes
• PROFINET CBA Yes
• Point-to-point coupling No
DP master
• Number of connections, max. 16 16
• Services
- PG/OP communication Yes Yes
- Routing Yes Yes
- S7 basic communication Yes Yes
- S7 communication
- equidistance support
Yes
Yes
Yes
Yes
5
- Activation/deactivation of Yes Yes
DP slaves
- direct data exchange Yes Yes
(cross traffic)
• Transmission speeds, max. 12 MBit/s 12 MBit/s
• Number of DP slaves, max. 96 96
• Address area
- Inputs, max. 6 Kibyte 6 Kibyte
- Outputs, max. 6 Kibyte 6 Kibyte
• Useful data per DP slave
- Inputs, max. 244 byte 244 byte
- Outputs, max. 244 byte 244 byte
DP slave
• Number of connections 16 16
• Services
- Routing Yes Yes
- Programming Yes Yes
• GSD file http://support.automation.siemens. http://support.automation.siemens.
com/WW/view/en/113652 com/WW/view/en/113652
• Transmission speeds, max. 12 MBit/s 12 MBit/s
• Transfer memory
- Inputs 244 byte 244 byte
- Outputs 244 byte 244 byte
• Address area, max. 32 32
• Useful data per address area, 32 byte 32 byte
max.
• Useful data per address area, 32 byte 32 byte
of which consistent, max.
PROFINET IO controller
• Services
- PG/OP communication Yes
- Routing Yes; Routing of PG functions
- S7 communication Yes
- open IE communication Yes
• Transmission rate, min. 10 MBit/s
• Transmission speed, max. 100 MBit/s
• Total number of connectable 256
IO Devices, max.
• Updating time 250 μs to 512 ms; minimum value
dependent on preset communication
share for PROFINET I/O, of number
of I/O devices and number of
configured user data

Siemens ST 70 · 2009 5/17


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 414

■ Technical specifications (continued)


6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM05-0AB0
PROFINET IO controller (cont.)
• Address area
- Inputs, max. 8 Kibyte
- Outputs, max. 8 Kibyte
- Useful data consistency, 255 byte;
max. incl. net data accompaniers
PROFINET CBA
• Acyclic transmission Yes
• cyclic transmission Yes
3rd interface
Type of interfaces Pluggable interface module (IF), Pluggable interface module (IF)
technical specifications as for 2nd
interface
5 pluggable interface module IF 964-DP IF 964-DP
(Order No.: 6ES7 964-2AA04-0AB0) (Order No.: 6ES7 964-2AA04-0AB0)
Physics RS 485 / PROFIBUS
isolated Yes
power supply to interface 150 mA; max. 150 mA
(15 to 30 V DC), max.
Number of connection resources 16
Functionality
• MPI No
• DP master Yes
• DP slave Yes
DP master
• Number of connections, max. 16
• Services
- PG/OP communication Yes
- Routing Yes
- Global data communication No
- S7 basic communication Yes
- S7 communication Yes
- Equidistance support Yes
- SYNC/FREEZE Yes
- Activation/deactivation of Yes
DP slaves
- Direct data exchange Yes
• Transmission rate, max. 12 MBit/s
• Number of DP slaves, max. 96
• Address area
- Inputs, max. 6 Kibyte
- Outputs, max. 6 Kibyte
• Useful data per DP slave
- Useful data per DP slave, 244 byte
max.
- Inputs, max. 244 byte
- Outputs, max. 244 byte
- Slots, max. 244
- per slot, max. 128 byte
DP slave
• Number of connections 16
• Services
- Routing Yes
- Status/control Yes

5/18 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 414

■ Technical specifications (continued)


6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM05-0AB0
DP slave (continued)
• GSD file http://support.automation.siemens.
com/WW/view/en/113652
• Transmission rate, max. 12 MBit/s
• Transfer memory
- Inputs 244 byte
- Outputs 244 byte
• Address range, max. 32
• Useful data per address area, 32 byte
max.
• Useful data per address area, 32 byte
of which consistent, max.

5
Isochronous mode
Useful data per isochronoous 244 byte 244 byte 244 byte
slave, max.
equidistance Yes Yes Yes
shortest clock pulse 1 ms; 0.5 ms without use of SFC 126, 1 ms; 0.5 ms without use of SFC 126, 1 ms; Without use of SFC 126 and
127 127 127 up to 0.5 ms
CiR configuration in RUN
CiR synchronization time, 100 ms 100 ms 100 ms
basic load
CiR synchronization time, 80 μs 80 μs 80 μs
time per I/O slave
CPU/programming
Configuration software
• STEP 7 Yes Yes Yes
Programming language
• STEP 7 Yes
• LAD Yes Yes Yes
• FUP Yes Yes Yes
• AWL Yes Yes Yes
• SCL Yes Yes Yes
• CFC Yes Yes Yes
• GRAPH Yes Yes Yes
• HiGraph Yes Yes Yes
Nesting levels 7 7 7
User program protection/ Yes Yes Yes
password protection
Dimensions
Required slots 1 2 2
Dimensions
Dimensions
• Width 25 mm 50 mm 50 mm
• Height 290 mm 290 mm 290 mm
• Depth 219 mm 219 mm 219 mm
Weights
• Weight, approx. 720 g 880 g 900 g

Siemens ST 70 · 2009 5/19


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 414

■ Ordering data Order No. Order No.


CPU 414-2 6ES7 414-2XK05-0AB0 Slot number plates 6ES7 912-0AA00-0AA0
Main memory 1 MB, 1 set (spare part)
power supply 24 V DC,
MPI/PROFIBUS DP master Manual "SIMATIC S7-400
interface, slot for memory card, automation system"
incl. slot number labels incl. instruction list
CPU 414-3 6ES7 414-3XM05-0AB0 German 6ES7 498-8AA05-8AA0
Main memory 2.8 MB, English 6ES7 498-8AA05-8BA0
power supply 24 V DC,
MPI/PROFIBUS DP master French 6ES7 498-8AA05-8CA0
interface, PROFIBUS DP master Spanish 6ES7 498-8AA05-8DA0
interface, slot for memory card,
module slots for 1 IF module, Italian 6ES7 498-8AA05-8EA0
incl. slot number labels
S7-400 instructions list
CPU 414-3 PN/DP 6ES7 414-3EM05-0AB0
German 6ES7 498-8AA05-8AN0
Main memory 2.8 MB,
5 power supply 24 V DC,
MPI/PROFIBUS DP master
English
French
6ES7 498-8AA05-8BN0
6ES7 498-8AA05-8CN0
interface, PROFINET interface,
slot for memory card, module slot Spanish 6ES7 498-8AA05-8DN0
for 1 IF module, incl. slot number Italian 6ES7 498-8AA05-8EN0
labels
Manual "Communication for
Memory card RAM SIMATIC S7-300/-400"
64 KB 6ES7 952-0AF00-0AA0 German 6ES7 398-8EA00-8AA0
256 KB 6ES7 952-1AH00-0AA0 English 6ES7 398-8EA00-8BA0
1 MB 6ES7 952-1AK00-0AA0 French 6ES7 398-8EA00-8CA0
2 MB 6ES7 952-1AL00-0AA0 Spanish 6ES7 398-8EA00-8DA0
4 MB 6ES7 952-1AM00-0AA0 Italian 6ES7 398-8EA00-8EA0
8 MB 6ES7 952-1AP00-0AA0 SIMATIC Manual Collection B3 6ES7 998-8XC01-8YE0
16 MB 6ES7 952-1AS00-0AA0 Electronic manuals on DVD, five
64 MB 6ES7 952-1AY00-0AA0 languages: S7-200/300/400, C7,
LOGO!, SIMATIC DP, PC, PG,
FEPROM memory card STEP 7, engineering software,
runtime software, PCS 7, SIMATIC
64 KB 6ES7 952-0KF00-0AA0
HMI, SIMATIC NET
256 KB 6ES7 952-0KH00-0AA0
SIMATIC Manual Collection B3 6ES7 998-8XC01-8YE2
1 MB 6ES7 952-1KK00-0AA0 update service for 1 year
2 MB 6ES7 952-1KL00-0AA0 Current "Manual Collection" DVD
and the three subsequent
4 MB 6ES7 952-1KM00-0AA0 updates
8 MB 6ES7 952-1KP00-0AA0 Brochure "SIMATIC S7-400
16 MB 6ES7 952-1KS00-0AA0 automation system - Design
and application"
32 MB 6ES7 952-1KT00-0AA0
German 6ES7 498-8AA00-8AB0
64 MB 6ES7 952-1KY00-0AA0
English 6ES7 498-8AA00-8BB0
MPI cable 6ES7 901-0BF00-0AA0
For connecting SIMATIC S7 and
the PG through MPI; 5 m in length
IF 964-DP interface module 6ES7 964-2AA04-0AB0
For connecting an additional
PROFIBUS subnet;
for CPU 414-3, CPU 414-3 PN/DP,
CPU 416-3, CPU 416-3 PN/DP,
CPU 417-4
B3: Subject to export regulations: AL: N and ECCN: 5D992B1

5/20 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 414

■ Ordering data Order No. Order No.


PROFIBUS bus components PROFINET bus components
RS 485 bus connector with IE FC TP Standard Cable GP 6XV1 840-2AH10
90° cable outlet 2x2
Max. transfer rate 12 Mbit/s 4-core, shielded TP installation
cable for connection to
Without PG interface 6ES7 972-0BA12-0XA0 IE FC Outlet RJ45/
With PG interface 6ES7 972-0BB12-0XA0 IE FC RJ45 Plug;
PROFINET-compatible;
RS 485 bus connector with with UL approval;
angled cable outlet sold by the meter
Max. transfer rate 12 Mbit/s FO Standard Cable GP (50/125) 6XV1 873-2A
Without PG interface 6ES7 972-0BA41-0XA0 Standard cable, splittable,
With PG interface 6ES7 972-0BB41-0XA0 UL approval, sold by the meter

RS 485 bus connector with SCALANCE X204-2 6GK5 204-2BB10-2AA3


90° cable outlet for Industrial Ethernet Switch

5
FastConnect system Industrial Ethernet Switches with
Max. transfer rate 12 Mbit/s integral SNMP access, web
diagnostics, copper cable
Without PG interface 6ES7 972-0BA51-0XA0 diagnostics and PROFINET
diagnostics for configuring line,
With PG interface 6ES7 972-0BB51-0XA0
star and ring topologies;
RS 485 bus connector with four 10/100 Mbit/s RJ45 ports and
axial cable outlet two FO ports
For SIMATIC OP, for connection to 6GK1 500-0EA02 IE FC RJ45 plugs
PPI, MPI, PROFIBUS
RJ45 plug connector for Industrial
PROFIBUS FastConnect bus Ethernet with a rugged metal
cable enclosure and integrated
insulation displacement contacts
Standard type with special design 6XV1 830-0EH10 for connecting Industrial Ethernet
for quick mounting, 2-core, FC installation cables
shielded, sold by the meter,
max. delivery unit 1000 m, IE FC RJ45 plug 180
minimum order quantity 20 m
180° cable outlet
RS 485 repeater for PROFIBUS 6ES7 972-0AA01-0XA0
1 unit 6GK1 901-1BB10-2AA0
Data transfer rate up to 12 Mbit/s;
10 units 6GK1 901-1BB10-2AB0
24 V DC; IP20 housing
50 units 6GK1 901-1BB10-2AE0
PROFIBUS/PROFINET see Catalogs IK PI, CA 01
bus components
For establishing
MPI/PROFIBUS/PROFINET
communication

Siemens ST 70 · 2009 5/21


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 416

■ Overview
• High-performance CPUs in the high-end performance range
• Applicable for plants with high requirements in the high-end
performance range
• Integrated PROFINET functions in CPU 416-3 PN/DP

5
■ Technical specifications
6ES7 416-2XN05-0AB0 6ES7 416-3XR05-0AB0 6ES7 416-3ER05-0AB0
Product status
Firmware version V5.0 V5.0 V5.0
associated programming STEP7 V5.3 SP2 or higher with STEP7 V5.3 SP2 or higher with STEP7 V5.4 SP1 or higher
package HW-update HW-update
Feeding of external buffer 5 to 15 V DC 5 to 15 V DC 5 to 15 V DC
voltage to CPU
Current consumption
from backplane bus DC 5 V, 1.1 A 1.3 A 1.4 A
max.
from interface DC 5 V, max. 90 mA; At each DP interface 90 mA; At each DP interface 90 mA; At each DP interface
Current consumption/
power loss
Power loss, typ. 4W 4.5 W 5.5 W
Backup battery
• Buffer current, typ. 125 μA; Valid up to 40°C 125 μA; Valid up to 40°C 125 μA; Valid up to 40°C
• Buffer current, max. 550 μA 550 μA 550 μA
Memory
Type of storage
RAM
• integrated (for program) 2.8 MByte 5.6 MByte 5.6 MByte
• integrated (for data) 2.8 MByte 5.6 MByte 5.6 MByte
• expandable No No No
Load memory
• expandable FEPROM Yes Yes Yes; with Memory Card (FLASH)
• expandable FEPROM, max. 64 MByte 64 MByte 64 MByte
• integrated RAM, max. 1 MByte 1 MByte 1 MByte
• expandable RAM Yes Yes Yes; With Memory Card (RAM)
• expandable RAM, max. 64 MByte 64 MByte 64 MByte
Backup
• present Yes Yes Yes
• with battery Yes Yes Yes
• without battery No No No
CPU/blocks
DB
• Number, max. 10 000; Number range: 1 to 16,000 10 000; Number range: 1 to 16,000 10 000; Number range: 1 to 16,000
• Size, max. 64 Kibyte 64 Kibyte 64 Kibyte

5/22 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 416

■ Technical specifications (continued)


6ES7 416-2XN05-0AB0 6ES7 416-3XR05-0AB0 6ES7 416-3ER05-0AB0
FB
• Number, max. 5 000; Number range: 0 to 7999 5 000; Number range: 0 to 7999 5 000; Number range: 0 to 7999
• Size, max. 64 Kibyte 64 Kibyte 64 Kibyte
FC
• Number, max. 5 000; Number range: 0 to 7999 5 000; Number range: 0 to 7999 5 000; Number range: 0 to 7,999
• Size, max. 64 Kibyte 64 Kibyte 64 Kibyte
OB
• Size, max. 64 Kibyte 64 Kibyte 64 Kibyte
Nesting depth
• per priority class 24 24 24
• additional within an error OB 2 2 2
CPU/processing times 5
for bit operations, min. 30 ns 30 ns 30 ns
for word operations, min. 30 ns 30 ns 30 ns
for fixed point arithmetic, min. 30 ns 30 ns 30 ns
for floating point arithmetic, min. 90 ns 90 ns 90 ns
Times/counters and their
remanence
S7 counter
• Number 2 048 2 048 2 048
• Remanence
- adjustable Yes Yes Yes
- lower limit 0 0 0
- upper limit 2 047 2 047 2 047
- preset From Z 0 to Z 7 From Z 0 to Z 7 From Z 0 to Z 7
• Counting range
- lower limit 0 0 0
- upper limit 999 999 999
IEC counter
• present Yes Yes Yes
• Type SFB SFB SFB
S7 times
• Number 2 048 2 048 2 048
• Remanence
- adjustable Yes Yes Yes
- lower limit 0 0 0
- upper limit 2 047 2 047 2 047
- preset No times retentive No times retentive No times retentive
• Time range
- lower limit 10 ms 10 ms 10 ms
- upper limit 9 990 s 9 990 s 9 990 s
IEC timer
• present Yes Yes Yes
• Type SFB SFB SFB
Data areas and their
remanence
remanent data area, total Total working and load memory Total working and load memory Total working and load memory
(with backup battery) (with backup battery) (with backup battery)

Siemens ST 70 · 2009 5/23


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 416

■ Technical specifications (continued)


6ES7 416-2XN05-0AB0 6ES7 416-3XR05-0AB0 6ES7 416-3ER05-0AB0
Flag
• Number, max. 16 Kibyte 16 Kibyte 16 Kibyte; Size of bit memory
address area
• Remanence available Yes Yes Yes
• Number of clock memories 8; (in 1 memory byte) 8; (in 1 memory byte) 8; (in 1 memory byte)
Address area
I/O address area
• Inputs 16 Kibyte 16 Kibyte 16 Kibyte
• Outputs 16 Kibyte 16 Kibyte 16 Kibyte
• of which, distributed
- MPI/DPinterface, inputs 2 Kibyte 2 Kibyte 2 Kibyte
- MPI/DP interface, outputs 2 Kibyte 2 Kibyte 2 Kibyte
5 - DP interface, inputs
- DP interface, outputs
8 Kibyte
8 Kibyte
8 Kibyte
8 Kibyte
8 Kibyte
8 Kibyte
- PN interface, inputs 8 Kibyte
- PN interface, outputs 8 Kibyte
Process image
• Inputs, adjustable 16 Kibyte 16 Kibyte 16 Kibyte
• Outputs, adjustable 16 Kibyte 16 Kibyte 16 Kibyte
• Inputs, preset 512 byte 512 byte 512 byte
• Outputs, preset 512 byte 512 byte 512 byte
• consistent data, max. 244 byte 244 byte 244 byte
• Access to consistent data in Yes Yes Yes
process image
Subprocess images
• Number of subprocess 15 15 15
images, max.
Digital channels
• Inputs 131 072 131 072 131 072
• Outputs 131 072 131 072 131 072
• Inputs, of which central 131 072 131 072 131 072
• Outputs, of which central 131 072 131 072 131 072
Analog channels
• Inputs 8 192 8 192 8 192
• Outputs 8 192 8 192 8 192
• Inputs, of which central 8 192 8 192 8 192
• Outputs, of which central 8 192 8 192 8 192
Hardware config.
connectable OPs 63 63 63
Central devices, max. 1 1 1
Expansion devices, max. 21 21 21
Multicomputing Yes; Max. 4 CPUs (with UR1 or UR2) Yes; Max. 4 CPUs (with UR1 or UR2) Yes; Max. 4 CPUs (with UR1 or UR2)
IM
• Number of connectable IMs 6 6 6
(total), max.
• Number of connectable 6 6 6
IM 460s, max.
• Number of connectable 4; IM 463-2 4; IM 463-2 4; IM 463-2
IM 463s, max.

5/24 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 416

■ Technical specifications (continued)


6ES7 416-2XN05-0AB0 6ES7 416-3XR05-0AB0 6ES7 416-3ER05-0AB0
Number of DP masters
• integrated 2 2 1
• via IM 467 4 4 4
• via CP 10; CP 443-5 Extended 10; CP 443-5 Extended 10; CP 443-5 Extended
• Mixed mode IM + CP permitted No; IM 467 cannot be used with No; IM 467 cannot be used with No; IM 467 cannot be used with
CP 443-5 Ext.; IM 467 cannot be CP 443-5 Ext.; IM 467 cannot be CP 443-5 Ext.; IM 467 cannot be
used with CP 443-1 EX40 in PN IO used with CP 443-1 EX40 in PN IO used with CP 443-1 EX40 in PN IO
mode mode mode
• via interface module 0 1 1; IF 964-DP
• Number of pluggable S5 6 6 6
modules (via adapter capsule
in central device), max.
Number of IO controllers
• integrated 1 5
• via CP 4; Via CP 443-1 EX 41 in PN mode; 4; Via CP 443-1 EX 41 in PN mode; 4; Via CP 443-1 EX 41 in PN mode;
max. 4 in central controller max. 4 in central controller max. 4 in central controller
Number of operable FMs and
CPs (recommended)
• FM Limited due to number of slots and Limited due to number of slots and Limited due to number of slots and
number of connections number of connections number of connections
• CP, point-to-point Limited due to number of slots and Limited due to number of slots and Limited due to number of slots and
number of connections number of connections number of connections
• PROFIBUS and Ethernet CPs 14; Of which 10 CP or IM max. as 14; Of which 10 CP or IM max. as 14; Of which 10 CP/IM max. as
DP master and PN controller DP master and PN controller DP master and PN controller
Time
Clock
• Hardware clock Yes Yes Yes
(real-time clock)
• buffered and synchronizable Yes Yes Yes
• Resolution 1 ms 1 ms 1 ms
Operating hours counter
• Number 8 8 8
Clock synchronization
• supports Yes Yes Yes
• to MPI, Master Yes Yes Yes
• to MPI, Slave Yes Yes Yes
• to DP, Master Yes Yes Yes
• to DP, Slave Yes Yes Yes
• in AS, Master Yes Yes Yes
• in AS, Slave Yes Yes Yes
• on Ethernet via NTP Via CP Via CP Yes; as client
• to IF 964 DP Yes Yes
S7 message functions
Number of login stations for 63; Max. 63 with ALARM_S and 63; Max. 63 with ALARM_S and 63; Max. 63 with ALARM_S and
message functions, max. ALARM_D (OPs); ALARM_D (OPs); ALARM_D (OPs);
max. 12 with ALARM_8 and max. 12 with ALARM_8 and max. 12 with ALARM_8 and
ALARM_P (e.g. WinCC) ALARM_P (e.g. WinCC) ALARM_P (e.g. WinCC)
Symbol-related messages Yes Yes Yes
Number of messages
• overall, max. 1 024 1 024 1 024
Block related messages Yes Yes Yes
Alarm 8-blocks Yes Yes Yes
Instrumentation & control Yes Yes Yes
messages

Siemens ST 70 · 2009 5/25


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 416

■ Technical specifications (continued)


6ES7 416-2XN05-0AB0 6ES7 416-3XR05-0AB0 6ES7 416-3ER05-0AB0
Test commissioning functions
Status/control
• Status/control variable Yes Yes Yes
Forcing
• Forcing Yes Yes Yes
Status block Yes Yes Yes
Single step Yes Yes Yes
Number of breakpoints 4 4 4
Diagnostic buffer
• present Yes Yes Yes
• Number of entries, max. 3 200 3 200 3 200

5 • adjustable Yes Yes Yes


• preset 120 120 120
Communication functions
PG/OP communication Yes Yes Yes
Routing Yes Yes Yes
Global data communication
• supported Yes Yes Yes
• Size of GD packets, max. 54 byte 54 byte 54 byte
S7 basic communication
• supported Yes Yes Yes
• Useful data per job, max. 76 byte 76 byte 76 byte
S7 communication
• supported Yes Yes Yes
• Useful data per job, max. 64 Kibyte 64 Kibyte 64 Kibyte
S5-compatible communication
• supported Yes; (via CP max. 10 and Yes; (via CP max. 10 and Yes; (via CP max. 10 and
FC AG_SEND and FC AG_RECV) FC AG_SEND and FC AG_RECV) FC AG_SEND and FC AG_RECV)
• Useful data per job, max. 8 Kibyte 8 Kibyte 8 Kibyte
Standard communication (FMS)
• supported Yes; Via CP and loadable FB Yes; Via CP and loadable FB Yes; Via CP and loadable FB
• Web server No; Via CP No; Via CP Yes; Read-only function
Open IE communication
• TCP/IP Yes
- Number of connections, max. 64
- Data length, max. 32 Kibyte
• ISO-on-TCP (RFC1006) Via CP 443-1 Adv. and loadable FB Via CP 443-1 Adv. and loadable FB Yes
- Number of connections, max. 64
- Data length, max. 1452 1452 32 Kibyte; 1452 bytes via
CP 443-1 Adv.
• UDP Yes
- Number of connections, max. 64
- Data length, max. 1 472 byte
Number of connections
• overall 64 64 64

5/26 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 416

■ Technical specifications (continued)


6ES7 416-2XN05-0AB0 6ES7 416-3XR05-0AB0 6ES7 416-3ER05-0AB0
PROFINET CBA (at set setpoint
communication load)
• Number of remote intercon- 32
nection partners
• Number of functions, 150
master/slave
• Total of all master/slave 6 000
connections
• Data length of all incoming 65 000 byte
connections master/slave,
max.
• Data length of all outgoing 65 000 byte
connections master/slave,
max.
• Number of device-internal and
PROFIBUS interconnections
1 000 5
• Data length of device-internal 16 000 byte
and PROFIBUS interconnec-
tions, max.
• Data length per connection, 2 000 byte
max.
• Remote interconnections with
acyclic transmission
- Sampling frequency: 200 ms; Depending on preset
sampling interval, min. communcation load, number of inter-
connections and data length used
- Number of incoming inter- 500
connections
- Number of outgoing intercon- 500
nections
- Data length of all incoming 16 000 byte
interconnections, max.
- Data length of all outgoing 16 000 byte
interconnections, max.
- Data length per connection, 2 000 byte
max.
• Remote interconnections with
cyclic transmission
- Transmission frequency: 1 ms; Depending on preset commu-
transmission interval, min. nication load, number of intercon-
nections and data length used
- Number of incoming inter- 300
connections
- Number of outgoing intercon- 300
nections
- Data length of all incoming 4 800 byte
interconnections, max.
- Data length of all outgoing 4 800 byte
interconnections, max.
- Data length per connection, 250 byte
max.
• HMI variables via PROFINET
(acyclic)
- Number of log-in stations for 2x PN OPC/1x iMap
HMI variables
(PN OPC/iMap)
- HMI variable updating 500 ms
- Number of HMI variables 1 500
- Data length of all HMI 48 000 byte
variables, max.

Siemens ST 70 · 2009 5/27


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 416

■ Technical specifications (continued)


6ES7 416-2XN05-0AB0 6ES7 416-3XR05-0AB0 6ES7 416-3ER05-0AB0
• PROFIBUS proxy functionality
- supported Yes; 32 PROFIBUS slaves max.
connectable
- Data length per connection, 240 byte; Slave-dependent
max.
1st interface
Physics RS 485 / PROFIBUS RS 485 / PROFIBUS RS 485 / PROFIBUS + MPI
isolated Yes Yes Yes
Functionality
• MPI Yes Yes Yes
• DP master Yes Yes Yes
• DP slave Yes Yes Yes

5 MPI
• Number of connections 44 44 44
• Services
- PG/OP communication Yes Yes Yes
- Routing Yes Yes Yes
- Global data communication Yes Yes Yes
- S7 basic communication Yes Yes Yes
- S7 communication Yes Yes Yes
• Transmission speeds, max. 12 MBit/s 12 MBit/s 12 MBit/s
DP master
• Number of connections, max. 32 32 32; if a diagnostic repeater is used
on the line, the number of connection
resources on the line is reduced by 1
• Services
- PG/OP communication Yes Yes Yes
- Routing Yes Yes Yes
- Global data communication No No No
- S7 basic communication Yes Yes Yes
- S7 communication Yes Yes Yes
- equidistance support Yes Yes Yes
- Activation/deactivation of Yes Yes Yes
DP slaves
- direct data exchange Yes Yes Yes
(cross traffic)
• Transmission speeds, max. 12 MBit/s 12 MBit/s 12 MBit/s
• Number of DP slaves, max. 32 32 32
• Address area
- Inputs, max. 2 Kibyte 2 Kibyte 2 Kibyte
- Outputs, max. 2 Kibyte 2 Kibyte 2 Kibyte
• Useful data per DP slave
- Inputs, max. 244 byte 244 byte 244 byte
- Outputs, max. 244 byte 244 byte 244 byte
DP slave
• Number of connections 32 32 32
• Services
- PG/OP communication Yes Yes Yes; with interface active
- Routing Yes Yes Yes; with interface active
• Transmission speeds, max. 12 MBit/s 12 MBit/s 12 MBit/s
• Transfer memory
- Inputs 244 byte 244 byte 244 byte
- Outputs 244 byte 244 byte 244 byte

5/28 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 416

■ Technical specifications (continued)


6ES7 416-2XN05-0AB0 6ES7 416-3XR05-0AB0 6ES7 416-3ER05-0AB0
DP slave (continued)
• Address area, max. 32 32 32; Virtual slots
• Useful data per address area, 32 byte 32 byte 32 byte
max.
• Useful data per address area, 32 byte 32 byte 32 byte
of which consistent, max.
2nd interface
Physics RS 485 / PROFIBUS RS 485 / PROFIBUS Ethernet
isolated Yes Yes Yes
Functionality
• DP master Yes Yes No
• DP slave Yes Yes No
• PROFINET IO controller Yes 5
• PROFINET CBA Yes
• Point-to-point coupling No
DP master
• Number of connections, max. 32 32
• Services
- PG/OP communication Yes Yes
- Routing Yes Yes
- S7 basic communication Yes Yes
- S7 communication Yes Yes
- equidistance support Yes Yes
- Activation/deactivation of Yes Yes
DP slaves
- direct data exchange Yes Yes
(cross traffic)
• Transmission speeds, max. 12 MBit/s 12 MBit/s
• Number of DP slaves, max. 125 125
• Address area
- Inputs, max. 8 Kibyte 8 Kibyte
- Outputs, max. 8 Kibyte 8 Kibyte
• Useful data per DP slave
- Inputs, max. 244 byte 244 byte
- Outputs, max. 244 byte 244 byte
DP slave
• Number of connections 32 32
• Services
- Routing Yes Yes
- Programming Yes Yes
• GSD file http://support.automation.siemens. http://support.automation.siemens.
com/WW/view/en/113652 com/WW/view/en/113652
• Transmission speeds, max. 12 MBit/s 12 MBit/s
• Transfer memory
- Inputs 244 byte 244 byte
- Outputs 244 byte 244 byte
• Address area, max. 32 32
• Useful data per address area, 32 byte 32 byte
max.
• Useful data per address area, 32 byte 32 byte
of which consistent, max.
PROFINET IO-Controller
• Services
- PG/OP communication Yes
- Routing Yes; Routing of PG functions
- S7 communication Yes
- open IE communication Yes

Siemens ST 70 · 2009 5/29


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 416

■ Technical specifications (continued)


6ES7 416-2XN05-0AB0 6ES7 416-3XR05-0AB0 6ES7 416-3ER05-0AB0
PROFINET IO-Controller (cont.)
• Transmission rate, min. 10 MBit/s
• Transmission speed, max. 100 MBit/s
• Total number of connectable IO 256
Devices, max.
• Updating time 250 μs to 512 ms; minimum value
dependent on preset communication
share for PROFINET I/O, of number
of I/O devices and number of
configured user data
• Address area
- Inputs, max. 8 Kibyte
- Outputs, max. 8 Kibyte

5
- Useful data consistency, 255 byte; incl. net data accompa-
max. niers
PROFINET CBA
• Acyclic transmission Yes
• cyclic transmission Yes
3rd interface
Type of interfaces Pluggable interface module (IF), Pluggable interface module (IF),
technical specifications as for 2nd technical specifications as for 2nd
interface interface
pluggable interface module IF 964-DP IF 964-DP
(Order No.: 6ES7 964-2AA04-0AB0) (Order No.: 6ES7 964-2AA04-0AB0)
Physics RS 485 / PROFIBUS
isolated Yes
power supply to interface 150 mA
(15 to 30 V DC), max.
Number of connection resources 32
Functionality
• MPI No
• DP master Yes
• DP slave Yes
DP master
• Number of connections, max. 32
• Services
- PG/OP communication Yes
- Routing Yes
- Global data communication No
- S7 basic communication Yes
- S7 communication Yes
- Equidistance support Yes
- SYNC/FREEZE Yes
- Activation/deactivation of Yes
DP slaves
- Direct data exchange Yes
• Transmission rate, max. 12 MBit/s
• Number of DP slaves, max. 125
• Address area
- Inputs, max. 8 Kibyte
- Outputs, max. 8 Kibyte
• Useful data per DP slave
- Useful data per DP slave, 244 byte
max.
- Inputs, max. 244 byte
- Outputs, max. 244 byte

5/30 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 416

■ Technical specifications (continued)


6ES7 416-2XN05-0AB0 6ES7 416-3XR05-0AB0 6ES7 416-3ER05-0AB0
• Useful data per DP slave
(cont.)
- Slots, max. 244
- per slot, max. 128 byte
DP slave
• Number of connections 32
• Services
- Routing Yes; When interface active
- Status/control Yes; When interface active
• GSD file http://support.automation.siemens.
com/WW/view/en/113652
• Transmission rate, max. 12 MBit/s
• Transfer memory
- Inputs
- Outputs
244 byte
244 byte
5
• Address range, max. 32
• Useful data per address area, 32 byte
max.
• Useful data per address area, 32 byte
of which consistent, max.
Isochronous mode
Useful data per isochronoous 244 byte 244 byte 244 byte
slave, max.
equidistance Yes Yes Yes
shortest clock pulse 1 ms; 1 ms; 1 ms; Without use of SFC 126 and
0.5 ms without use of SFC 126, 127 0.5 ms without use of SFC 126, 127 127 up to 0.5 ms
CiR configuration in RUN
CiR synchronization time, 100 ms 100 ms 100 ms
basic load
CiR synchronization time, 40 μs 40 μs 40 μs
time per I/O slave
CPU/programming
Configuration software
• STEP 7 Yes Yes Yes
Programming language
• STEP 7 Yes
• LAD Yes Yes Yes
• FUP Yes Yes Yes
• AWL Yes Yes Yes
• SCL Yes Yes Yes
• CFC Yes Yes Yes
• GRAPH Yes Yes Yes
• HiGraph Yes Yes Yes
Nesting levels 7 7 7
User program Yes Yes Yes
protection/password protection
Dimensions
Required slots 1 2 2
Dimensions
Dimensions
• Width 25 mm 50 mm 50 mm
• Height 290 mm 290 mm 290 mm
• Depth 219 mm 219 mm 219 mm
Weights
• Weight, approx. 720 g 880 g 900 g

Siemens ST 70 · 2009 5/31


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 416

■ Ordering data Order No. Order No.


CPU 416-2 6ES7 416-2XN05-0AB0 Slot number plates 6ES7 912-0AA00-0AA0
Main memory 5.6 MB, 1 set (spare part)
power supply 24 V DC,
MPI/PROFIBUS DP master Manual "SIMATIC S7-400
interface, PROFIBUS DP master automation system"
interface, slot for memory card, incl. instruction list
incl. slot number labels
German 6ES7 498-8AA05-8AA0
CPU 416-3 6ES7 416-3XR05-0AB0
English 6ES7 498-8AA05-8BA0
Main memory 11.2 MB,
power supply 24 V DC, French 6ES7 498-8AA05-8CA0
MPI/PROFIBUS DP master Spanish 6ES7 498-8AA05-8DA0
interface, PROFIBUS DP master
interface, module slot for 1 IF Italian 6ES7 498-8AA05-8EA0
module, slot for memory card,
S7-400 instructions list
incl. slot number labels
German 6ES7 498-8AA05-8AN0
CPU 416-3 PN/DP 6ES7 416-3ER05-0AB0

5 Main memory 11.2 MB,


power supply 24 V DC,
English
French
6ES7 498-8AA05-8BN0
6ES7 498-8AA05-8CN0
MPI/PROFIBUS DP master
interface, PROFINET interface, Spanish 6ES7 498-8AA05-8DN0
module slot for 1 IF submodule, Italian 6ES7 498-8AA05-8EN0
slot for memory card, incl. slot
number labels Manual "Communication for
SIMATIC S7-300/-400"
Memory card RAM
German 6ES7 398-8EA00-8AA0
64 KB 6ES7 952-0AF00-0AA0
English 6ES7 398-8EA00-8BA0
256 KB 6ES7 952-1AH00-0AA0
French 6ES7 398-8EA00-8CA0
1 MB 6ES7 952-1AK00-0AA0
Spanish 6ES7 398-8EA00-8DA0
2 MB 6ES7 952-1AL00-0AA0
Italian 6ES7 398-8EA00-8EA0
4 MB 6ES7 952-1AM00-0AA0
SIMATIC Manual Collection B3 6ES7 998-8XC01-8YE0
8 MB 6ES7 952-1AP00-0AA0
Electronic manuals on DVD, five
16 MB 6ES7 952-1AS00-0AA0 languages: S7-200/300/400, C7,
64 MB 6ES7 952-1AY00-0AA0 LOGO!, SIMATIC DP, PC, PG,
STEP 7, engineering software,
FEPROM memory card runtime software, PCS 7, SIMATIC
HMI, SIMATIC NET
64 KB 6ES7 952-0KF00-0AA0
SIMATIC Manual Collection B3 6ES7 998-8XC01-8YE2
256 KB 6ES7 952-0KH00-0AA0
update service for 1 year
1 MB 6ES7 952-1KK00-0AA0
Current "Manual Collection" DVD
2 MB 6ES7 952-1KL00-0AA0 and the three subsequent
updates
4 MB 6ES7 952-1KM00-0AA0
Brochure "SIMATIC S7-400
8 MB 6ES7 952-1KP00-0AA0 automation system - Design
16 MB 6ES7 952-1KS00-0AA0 and application"
32 MB 6ES7 952-1KT00-0AA0 German 6ES7 498-8AA00-8AB0
64 MB 6ES7 952-1KY00-0AA0 English 6ES7 498-8AA00-8BB0
MPI cable 6ES7 901-0BF00-0AA0 PROFIBUS bus components see CPU 414, page 5/21
For connecting SIMATIC S7 and PROFINET bus components see CPU 414, page 5/21
the PG through MPI; 5 m in length
IF 964-DP interface module 6ES7 964-2AA04-0AB0
For connecting an additional
PROFIBUS subnet;
for CPU 414-3, CPU 414-3 PN/DP,
CPU 416-3, CPU 416-3 PN/DP,
CPU 417-4
B3: Subject to export regulations: AL: N and ECCN: 5D992B1

5/32 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 417

■ Overview
• The most powerful SIMATIC S7-400 CPU
• Can be used in the most sophisticated installations in the
upper performance range
• With two slots for IF modules

5
■ Technical specifications
6ES7 417-4XT05-0AB0 6ES7 417-4XT05-0AB0
Product status FB
Firmware version V5.0 • Number, max. 8 000; Number range: 0 to 7999
associated programming STEP7 V5.3 SP2 or higher with • Size, max. 64 Kibyte
package HW-update
FC
Feeding of external buffer 5 to 15 V DC
voltage to CPU • Number, max. 8 000; Number range: 0 to 7,999

Current consumption • Size, max. 64 Kibyte

from backplane bus DC 5 V, 1.8 A OB


max. • Size, max. 64 Kibyte
Current consumption/ Nesting depth
power loss
• per priority class 24
Power loss, max. 6W
• additional within an error OB 2
Backup battery
CPU/processing times
• Buffer current, typ. 225 μA; Valid up to 40°C
for bit operations, min. 18 ns
• Buffer current, max. 750 μA
for word operations, min. 18 ns
Memory
for fixed point arithmetic, min. 18 ns
Type of storage
for floating point arithmetic, min. 54 ns
RAM
15 MByte Times/counters and their
• integrated (for program) remanence
• integrated (for data) 15 MByte
S7 counter
• expandable No
• Number 2 048
Load memory • Remanence
• expandable FEPROM Yes - adjustable Yes
64 MByte - lower limit 0
• expandable FEPROM, max.
- upper limit 2 047
• integrated RAM, max. 1 MByte
- preset From Z 0 to Z 7
• expandable RAM Yes
• Counting range
• expandable RAM, max. 64 MByte - lower limit 0
- upper limit 999
Backup
IEC counter
• present Yes
• present Yes
• with battery Yes
• Type SFB
• without battery No
CPU/blocks
DB
• Number, max. 16 000; Number range: 1 to 16,000
• Size, max. 64 Kibyte

Siemens ST 70 · 2009 5/33


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 417

■ Technical specifications (continued)


6ES7 417-4XT05-0AB0 6ES7 417-4XT05-0AB0
S7 times Hardware config.
• Number 2 048 connectable OPs 63
• Remanence Central devices, max. 1
- adjustable Yes Expansion devices, max. 21
- lower limit 0
- upper limit 2 047 Multicomputing Yes; Max. 4 CPUs (with UR1 or UR2)
- preset No times retentive IM
• Time range • Number of connectable IMs 6
- lower limit 10 ms (total), max.
- upper limit 9 990 s • Number of connectable 6
IM 460s, max.
IEC timer
• Number of connectable 4; IM 463-2
• present Yes
IM 463s, max.

5 • Type
Data areas and their
SFB
Number of DP masters
• integrated 2
remanence
• via IM 467 4
remanent data area, total Total working and load memory
(with backup battery) • via CP 10; CP 443-5 Extended
Flag • Mixed mode IM + CP permitted No; IM 467 cannot be used with
CP 443-5 Ext.; IM 467 cannot be
• Number, max. 16 Kibyte
used with CP 443-1 EX40 in PN IO
• Remanence available Yes mode
• Number of clock memories 8; (in 1 memory byte) • via interface module 2
Address area • Number of pluggable S5 6
modules (via adapter capsule
I/O address area in central device), max.
• Inputs 16 Kibyte Number of IO controllers
• Outputs 16 Kibyte • via CP 4; Via CP 443-1 EX 41 in PN mode;
• of which, distributed max. 4 in central controller
- MPI/DPinterface, inputs 2 Kibyte Number of operable FMs and
- MPI/DP interface, outputs 2 Kibyte CPs (recommended)
- DP interface, inputs 8 Kibyte • FM Limited due to number of slots and
- DP interface, outputs 8 Kibyte number of connections
Process image • CP, point-to-point Limited due to number of slots and
number of connections
• Inputs, adjustable 16 Kibyte
• PROFIBUS and Ethernet CPs 14; Of which 10 CP or IM max. as
• Outputs, adjustable 16 Kibyte
DP master and PN controller
• Inputs, preset 1 024 byte
Time
• Outputs, preset 1 024 byte
Clock
• consistent data, max. 244 byte
• Hardware clock Yes
• Access to consistent data in Yes (real-time clock)
process image
• buffered and synchronizable Yes
Subprocess images
• Resolution 1 ms
• Number of subprocess 15
Operating hours counter
images, max.
• Number 8
Digital channels
Clock synchronization
• Inputs 131 072
• supports Yes
• Outputs 131 072
• to MPI, Master Yes
• Inputs, of which central 131 072
• to MPI, Slave Yes
• Outputs, of which central 131 072
• to DP, Master Yes
Analog channels
• to DP, Slave Yes
• Inputs 8 192
• in AS, Master Yes
• Outputs 8 192
• in AS, Slave Yes
• Inputs, of which central 8 192
• on Ethernet via NTP Via CP
• Outputs, of which central 8 192
• to IF 964 DP Yes

5/34 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 417

■ Technical specifications (continued)


6ES7 417-4XT05-0AB0 6ES7 417-4XT05-0AB0
S7 message functions 1st interface
Number of login stations for 63; Max. 63 with ALARM_S and Physics RS 485 / PROFIBUS
message functions, max. ALARM_D (OPs);
max. 16 with ALARM_8 and isolated Yes
ALARM_P (e.g. WinCC) Functionality
Symbol-related messages Yes • MPI Yes
Number of messages • DP master Yes
• overall, max. 1 024 • DP slave Yes
Block related messages Yes MPI
Alarm 8-blocks Yes • Number of connections 44
Instrumentation & control Yes • Services
messages - PG/OP communication Yes

5
Test commissioning functions - Routing Yes
Status/control - Global data communication Yes
- S7 basic communication Yes
• Status/control variable Yes - S7 communication Yes
Forcing • Transmission speeds, max. 12 MBit/s
• Forcing Yes DP master
Status block Yes • Number of connections, max. 32
Single step Yes • Services
Number of breakpoints 4 - PG/OP communication Yes
Diagnostic buffer - Routing Yes
- Global data communication No
• present Yes
- S7 basic communication Yes
• Number of entries, max. 3 200 - S7 communication Yes
• adjustable Yes - equidistance support Yes
- Activation/deactivation of Yes
• preset 120 DP slaves
Communication functions - direct data exchange Yes
(cross traffic)
PG/OP communication Yes
• Transmission speeds, max. 12 MBit/s
Routing Yes
• Number of DP slaves, max. 32
Global data communication
• Address area
• supported Yes
- Inputs, max. 2 Kibyte
• Size of GD packets, max. 54 byte - Outputs, max. 2 Kibyte
S7 basic communication • Useful data per DP slave
• supported Yes - Inputs, max. 244 byte
• Useful data per job, max. 76 byte - Outputs, max. 244 byte
DP slave
S7 communication
• supported Yes • Number of connections 32

• Useful data per job, max. • Services


64 Kibyte
- PG/OP communication Yes
S5-compatible communication - Routing Yes
• supported Yes; (via CP max. 10 and • Transmission speeds, max. 12 MBit/s
FC AG_SEND and FC AG_RECV)
• Transfer memory
• Useful data per job, max. 8 Kibyte
- Inputs 244 byte
Standard communication (FMS) - Outputs 244 byte
• supported Yes; Via CP and loadable FB • Address area, max. 32
• Web server No; Via CP • Useful data per address area, 32 byte
• ISO-on-TCP (RFC1006) Via CP 443-1 Adv. and loadable FB max.
- Data length, max. 1452 • Useful data per address area, 32 byte
of which consistent, max.
Number of connections
• overall 64

Siemens ST 70 · 2009 5/35


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 417

■ Technical specifications (continued)


6ES7 417-4XT05-0AB0 6ES7 417-4XT05-0AB0
2nd interface 3rd interface
Physics RS 485 / PROFIBUS Type of interfaces Pluggable interface module (IF),
technical specifications as for 2nd
isolated Yes interface
Functionality pluggable interface module IF 964-DP
• DP master Yes (Order No.: 6ES7 964-2AA04-0AB0)
• DP slave Yes 4th interface
DP master Type of interface Pluggable interface module (IF),
technical specifications as for 2nd
• Number of connections, max. 32 interface
• Services pluggable interface modules IF 964-DP
- PG/OP communication Yes (Order No.: 6ES7 964-2AA04-0AB0)
- Routing Yes Isochronous mode
- S7 basic communication Yes
5 - S7 communication
- equidistance support
Yes
Yes
Useful data per isochronoous
slave, max.
244 byte

- Activation/deactivation of Yes equidistance Yes


DP slaves shortest clock pulse 1 ms;
- direct data exchange Yes 0.5 ms without use of SFC 126, 127
(cross traffic)
CiR configuration in RUN
• Transmission speeds, max. 12 MBit/s
CiR synchronization time, 100 ms
• Number of DP slaves, max. 125 basic load
• Address area CiR synchronization time, 40 μs
- Inputs, max. 8 Kibyte time per I/O slave
- Outputs, max. 8 Kibyte CPU/programming
• Useful data per DP slave Configuration software
- Inputs, max. 244 byte
• STEP 7 Yes
- Outputs, max. 244 byte
Programming language
DP slave
• LAD Yes
• Number of connections 32
• FUP Yes
• Services
- Routing Yes • AWL Yes
- Programming Yes • SCL Yes
• GSD file http://support.automation.siemens. • CFC Yes
com/WW/view/en/113652
• GRAPH Yes
• Transmission speeds, max. 12 MBit/s
• HiGraph Yes
• Transfer memory
- Inputs 244 byte Nesting levels 7
- Outputs 244 byte User program Yes
protection/password protection
• Address area, max. 32
Dimensions
• Useful data per address area, 32 byte
max. Required slots 2
• Useful data per address area, 32 byte Dimensions
of which consistent, max. Dimensions
• Width 50 mm
• Height 290 mm
• Depth 219 mm
Weights
• Weight, approx. 920 g

5/36 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 417

■ Ordering data Order No. Order No.


CPU 417-4 6ES7 417-4XT05-0AB0 Manual "Communication for
SIMATIC S7-300/-400"
Main memory 30 MB,
power supply 24 V DC, German 6ES7 398-8EA00-8AA0
MPI/PROFIBUS DP master
interface, PROFIBUS DP master English 6ES7 398-8EA00-8BA0
interface, module slots for max. French 6ES7 398-8EA00-8CA0
2 additional IF modules, slot for
memory card, incl. slot number Spanish 6ES7 398-8EA00-8DA0
labels Italian 6ES7 398-8EA00-8EA0
Memory card RAM SIMATIC Manual Collection B3 6ES7 998-8XC01-8YE0
64 KB 6ES7 952-0AF00-0AA0 Electronic manuals on DVD, five
256 KB 6ES7 952-1AH00-0AA0 languages: S7-200/300/400, C7,
LOGO!, SIMATIC DP, PC, PG,
1 MB 6ES7 952-1AK00-0AA0 STEP 7, engineering software,
2 MB 6ES7 952-1AL00-0AA0 runtime software, PCS 7, SIMATIC
HMI, SIMATIC NET

5
4 MB 6ES7 952-1AM00-0AA0
SIMATIC Manual Collection B3 6ES7 998-8XC01-8YE2
8 MB 6ES7 952-1AP00-0AA0 update service for 1 year
16 MB 6ES7 952-1AS00-0AA0 Current "Manual Collection" DVD
and the three subsequent
64 MB 6ES7 952-1AY00-0AA0 updates
FEPROM memory card Brochure "SIMATIC S7-400
64 KB 6ES7 952-0KF00-0AA0 automation system - Design
and application"
256 KB 6ES7 952-0KH00-0AA0
German 6ES7 498-8AA00-8AB0
1 MB 6ES7 952-1KK00-0AA0
English 6ES7 498-8AA00-8BB0
2 MB 6ES7 952-1KL00-0AA0
RS 485 bus connector with
4 MB 6ES7 952-1KM00-0AA0 90° cable outlet
8 MB 6ES7 952-1KP00-0AA0 Max. transfer rate 12 Mbit/s
16 MB 6ES7 952-1KS00-0AA0 Without PG interface 6ES7 972-0BA12-0XA0
32 MB 6ES7 952-1KT00-0AA0 With PG interface 6ES7 972-0BB12-0XA0
64 MB 6ES7 952-1KY00-0AA0 RS 485 bus connector with
MPI cable 6ES7 901-0BF00-0AA0 angled cable outlet

For connecting SIMATIC S7 and Max. transfer rate 12 Mbit/s


the PG through MPI; 5 m in length Without PG interface 6ES7 972-0BA41-0XA0
IF 964-DP interface module 6ES7 964-2AA04-0AB0 With PG interface 6ES7 972-0BB41-0XA0
To connect an additional DP line; RS 485 bus connector with
for CPU 414-3, CPU 414-3 PN/DP, 90° cable outlet for
CPU 416-3, CPU 416-3 PN/DP, FastConnect system
CPU 417-4
Max. transfer rate 12 Mbit/s
Slot number plates 6ES7 912-0AA00-0AA0
Without PG interface 6ES7 972-0BA51-0XA0
1 set (spare part)
With PG interface 6ES7 972-0BB51-0XA0
Manual "SIMATIC S7-400
automation system" RS 485 bus connector with
axial cable outlet
incl. instruction list
For SIMATIC OP, for connection to 6GK1 500-0EA02
German 6ES7 498-8AA05-8AA0 PPI, MPI, PROFIBUS
English 6ES7 498-8AA05-8BA0 PROFIBUS FastConnect
French 6ES7 498-8AA05-8CA0 bus cable

Spanish 6ES7 498-8AA05-8DA0 Standard type with special design 6XV1 830-0EH10
for quick mounting, 2-core,
Italian 6ES7 498-8AA05-8EA0 shielded, sold by the meter,
max. delivery unit 1000 m,
S7-400 instructions list
minimum order quantity 20 m
German 6ES7 498-8AA05-8AN0
English 6ES7 498-8AA05-8BN0
French 6ES7 498-8AA05-8CN0
Spanish 6ES7 498-8AA05-8DN0
Italian 6ES7 498-8AA05-8EN0
B3: Subject to export regulations: AL: N and ECCN: 5D992B1

Siemens ST 70 · 2009 5/37


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 412H, CPU 414H, CPU 417H

■ Overview CPU 412-3H ■ Overview CPU 417-4H

5
• CPU for the SIMATIC S7-400H and S7-400F/FH • CPU for SIMATIC S7-400H and S7-400F/FH
• Can be used in S7-400H fault-tolerant systems • Can be used in high availability S7-400H systems
• Can be used with F runtime license as F-enabled CPU in • Can be used with F-runtime license and F-compatible CPU in
S7-400F/FH safety-related systems failsafe S7-400F/FH systems
• With combined MPI/PROFIBUS DP master interface • With integrated PROFIBUS DP master interface
• With 2 connection slots for synchronization modules • With 2 slots for sync modules

■ Overview CPU 414-4H

• CPU for SIMATIC S7-400H and S7-400F/FH


• Can be used in high availability S7-400H systems
• Can be used with F-runtime license and F-compatible CPU in
failsafe S7-400F/FH systems
• With integrated PROFIBUS DP master interface
• With 2 slots for sync modules

5/38 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 412H, CPU 414H, CPU 417H

■ Technical specifications
6ES7 412-3HJ14-0AB0 6ES7 414-4HM14-0AB0 6ES7 417-4HT14-0AB0
Product status
Hardware product status 1 1 1
Firmware version V4.5 V4.5 V4.5
associated programming STEP7 V5.3 SP2 or higher with STEP7 V5.3 SP2 or higher with STEP7 V5.3 SP2 or higher with
package HW update HW update HW update
Supply voltages
Rated value
• DC 24 V No; Power supply via system power No; Power supply via system power No; Power supply via system power
supply supply supply
Feeding of external buffer 5 to 15 V DC 5 to 15 V DC 5 to 15 V DC
voltage to CPU
Current consumption
from backplane bus DC 5 V,
max.
1.5 A 1.7 A 1.8 A
5
from interface DC 5 V, max. 90 mA; At each DP interface 90 mA; At each DP interface 90 mA; At each DP interface
Current consumption/
power loss
Power loss, typ. 5.5 W 6W 6.5 W
Backup battery
• Buffer current, typ. 190 μA; Valid up to 40°C 190 μA; Valid up to 40°C 970 μA; Valid up to 40°C
• Buffer current, max. 660 μA 660 μA 1 980 μA
Memory
Type of storage
RAM
• integrated (for program) 512 Kibyte 1.4 MByte 15 MByte

• integrated (for data) 256 Kibyte 1.4 MByte 15 MByte

• expandable No No No

Load memory
• expandable FEPROM Yes Yes Yes

• expandable FEPROM, max. 64 MByte 64 MByte 64 MByte

• integrated RAM, max. 256 Kibyte 256 Kibyte 256 Kibyte

• expandable RAM Yes Yes Yes

• expandable RAM, max. 64 MByte 64 MByte 64 MByte

Backup
• present Yes Yes Yes
• with battery Yes; All data Yes; All data Yes; All data
• without battery No No No
CPU/blocks
DB
• Number, max. 4 095; Number range: 1 - 4095 4 095; Number range: 1 - 4095 8 191; Number range: 1 - 8191
• Size, max. 64 Kibyte 64 Kibyte 64 Kibyte
FB
• Number, max. 2 048; Number range: 0 - 2047 2 048; Number range: 0 - 2047 6 144; Number range: 0 - 6143
• Size, max. 64 Kibyte 64 Kibyte 64 Kibyte
FC
• Number, max. 2 048; Number range: 0 - 2047 2 048; Number range: 0 - 2047 6 144; Number range: 0 - 6143
• Size, max. 64 Kibyte 64 Kibyte 64 Kibyte
OB
• Size, max. 64 Kibyte 64 Kibyte 64 Kibyte
Nesting depth
• per priority class 24 24 24
• additional within an error OB 1 1 2

Siemens ST 70 · 2009 5/39


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 412H, CPU 414H, CPU 417H

■ Technical specifications (continued)


6ES7 412-3HJ14-0AB0 6ES7 414-4HM14-0AB0 6ES7 417-4HT14-0AB0
CPU/processing times
for bit operations, min. 0.075 μs 0.045 μs 0.018 μs
for word operations, min. 0.075 μs 0.045 μs 0.018 μs
for fixed point arithmetic, min. 0.075 μs 0.045 μs 0.018 μs
for floating point arithmetic, min. 0.225 μs 0.135 μs 0.054 μs
Times/counters and their
remanence
S7 counter
• Number 2 048 2 048 2 048
• Remanence
- adjustable Yes Yes Yes
- lower limit 0 0 0
5 - upper limit
- preset
2 047
From Z 0 to Z 7
2 047
From Z 0 to Z 7
2 047
From Z 0 to Z 7
• Counting range
- lower limit 0 0 0
- upper limit 999 999 999
IEC counter
• present Yes Yes Yes
• Type SFB SFB SFB
S7 times
• Number 2 048 2 048 2 048
• Remanence
- adjustable Yes Yes Yes
- lower limit 0 0 0
- upper limit 2 047 2 047 2 047
- preset No timers retentive No timers retentive No timers retentive
• Time range
- lower limit 10 ms 10 ms 10 ms
- upper limit 9 990 s 9 990 s 9 990 s
IEC timer
• present Yes Yes Yes
• Type SFB SFB SFB
Data areas and their
remanence
remanent data area, total Total working and load memory Total working and load memory Total working and load memory
(with backup battery) (with backup battery) (with backup battery)
Flag
• Number, max. 8 Kibyte 8 Kibyte 16 Kibyte
• Remanence available Yes Yes Yes
• Number of clock memories 8; (in 1 memory byte) 8; (in 1 memory byte) 8; (in 1 memory byte)
Address area
I/O address area
• Inputs 8 Kibyte 8 Kibyte 16 Kibyte
• Outputs 8 Kibyte 8 Kibyte 16 Kibyte
• of which, distributed
- MPI/DPinterface, inputs 2 Kibyte 2 Kibyte 2 Kibyte
- MPI/DP interface, outputs 2 Kibyte 2 Kibyte 2 Kibyte
- DP interface, inputs 6 Kibyte 8 Kibyte
- DP interface, outputs 6 Kibyte 8 Kibyte

5/40 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 412H, CPU 414H, CPU 417H

■ Technical specifications (continued)


6ES7 412-3HJ14-0AB0 6ES7 414-4HM14-0AB0 6ES7 417-4HT14-0AB0
Process image
• Inputs, adjustable 8 Kibyte 8 Kibyte 16 Kibyte
• Outputs, adjustable 8 Kibyte 8 Kibyte 16 Kibyte
• Inputs, preset 256 byte 256 byte 1 024 byte
• Outputs, preset 256 byte 256 byte 1 024 byte
• consistent data, max. 244 byte 244 byte 244 byte
• Access to consistent data in Yes Yes Yes
process image
Subprocess images
• Number of subprocess 15 15 15
images, max.
Digital channels
• Inputs 65 536 65 536 131 072 5
• Outputs 65 536 65 536 131 072
• Inputs, of which central 65 536 65 536 131 072
• Outputs, of which central 65 536 65 536 131 072
Analog channels
• Inputs 4 096 4 096 8 192
• Outputs 4 096 4 096 8 192
• Inputs, of which central 4 096 4 096 8 192
• Outputs, of which central 4 096 4 096 8 192
Hardware config.
connectable OPs 15 without message processing, 31 without message processing, 63 without message processing,
8 with message processing 8 with message processing 16 with message processing
Central devices, max. 1 1 1
Expansion devices, max. 21 21 21
Multicomputing No No No
IM
• Number of connectable IMs 6 6 6
(total), max.
• Number of connectable 6 6 6
IM 460s, max.
• Number of connectable 4; Single mode only 4; Single mode only 4; Single mode only
IM 463s, max.
Number of DP masters
• integrated 1 2 2
• via CP 10 10 10
• Mixed mode IM + CP permitted No No No
• via interface module 0
Number of operable FMs and
CPs (recommended)
• FM See manual Automation System See manual Automation System See manual Automation System
S7-400H fault-tolerant systems. S7-400H fault-tolerant systems. S7-400H fault-tolerant systems.
Limited due to number of slots and Limited due to number of slots and Limited due to number of slots and
number of connections number of connections number of connections
• CP, point-to-point See manual Automation System See manual Automation System See manual Automation System
S7-400H fault-tolerant systems. S7-400H fault-tolerant systems. S7-400H fault-tolerant systems.
Limited due to number of slots and Limited due to number of slots and Limited due to number of slots and
number of connections number of connections number of connections
• PROFIBUS and Ethernet CPs 14; 14; 14;
Of which max. 10 CP as DP master Of which max. 10 CP as DP master Of which max. 10 CP as DP master

Siemens ST 70 · 2009 5/41


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 412H, CPU 414H, CPU 417H

■ Technical specifications (continued)


6ES7 412-3HJ14-0AB0 6ES7 414-4HM14-0AB0 6ES7 417-4HT14-0AB0
Time
Clock
• Hardware clock Yes Yes Yes
(real-time clock)
• buffered and synchronizable Yes Yes Yes
• Resolution 1 ms 1 ms 1 ms
Operating hours counter
• Number 8 8 8
Clock synchronization
• supports Yes Yes Yes
• to MPI, Master Yes Yes Yes

5 • to MPI, Slave
• to DP, Master
Yes
Yes
Yes
Yes
Yes
Yes
• to DP, Slave Yes Yes Yes
• in AS, Master Yes Yes Yes
• in AS, Slave Yes Yes Yes
S7 message functions
Number of login stations for 8 8 16
message functions, max.
Symbol-related messages No No No
Block related messages Yes Yes Yes
Alarm 8-blocks Yes Yes Yes
Instrumentation & control Yes Yes Yes
messages
Test commissioning functions
Status/control
• Status/control variable Yes Yes Yes
Forcing
• Forcing Yes Yes Yes
Status block Yes Yes Yes
Single step Yes Yes Yes
Number of breakpoints 4 4 4
Diagnostic buffer
• present Yes Yes Yes
• Number of entries, max. 3 200 3 200 3 200
• adjustable Yes Yes Yes
• preset 120 120 120
Communication functions
PG/OP communication Yes Yes Yes
Routing Yes Yes Yes
Global data communication
• supported No No No
S7 basic communication
• supported No No No
S7 communication
• supported Yes Yes Yes
• as server Yes Yes Yes
• as client Yes Yes Yes
• Useful data per job, max. 64 Kibyte 64 Kibyte 64 Kibyte

5/42 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 412H, CPU 414H, CPU 417H

■ Technical specifications (continued)


6ES7 412-3HJ14-0AB0 6ES7 414-4HM14-0AB0 6ES7 417-4HT14-0AB0
S5-compatible communication
• supported Yes; (via CP -max. 10- and Yes; (via CP -max. 10- and Yes; (via CP -max. 10-
FC AG_SEND and FC AG_RECV) FC AG_SEND and FC AG_RECV) and FC AG_SEND and FC
AG_RECV)
• Useful data per job, max. 8 Kibyte 8 Kibyte 8 Kibyte
Standard communication (FMS)
• supported Yes; Via CP and loadable FB Yes; Via CP and loadable FB Yes; Via CP and loadable FB
Number of connections
• overall 16 32 64
1st interface
Physics RS 485 / PROFIBUS + MPI RS 485 / PROFIBUS + MPI RS 485 / PROFIBUS + MPI
isolated Yes Yes Yes
Functionality 5
• MPI Yes Yes Yes
• DP master Yes Yes Yes
• DP slave No No No
MPI
• Number of connections 16 32 44
• Services
- PG/OP communication Yes Yes Yes
- Routing Yes Yes Yes
- Global data communication No No No
- S7 basic communication No No No
- S7 communication Yes Yes Yes
• Transmission speeds, max. 12 MBit/s 12 MBit/s 12 MBit/s
DP master
• Number of connections, max. 16 16 32
• Services
- PG/OP communication Yes Yes Yes
- Routing Yes Yes Yes
- Global data communication No No No
- S7 basic communication No No No
- S7 communication Yes Yes Yes
- S7 communication, as client Yes
- S7 communication, as server Yes
- equidistance support No No No
- Activation/deactivation of No No No
DP slaves
- direct data exchange No No No
(cross traffic)
• Transmission speeds, max. 12 MBit/s 12 MBit/s 12 MBit/s
• Number of DP slaves, max. 32 32 32
• Address area
- Inputs, max. 2 Kibyte 2 Kibyte 2 Kibyte
- Outputs, max. 2 Kibyte 2 Kibyte 2 Kibyte
• Useful data per DP slave
- Inputs, max. 244 byte 244 byte 244 byte
- Outputs, max. 244 byte 244 byte 244 byte
DP slave
• Number of connections No configuration of CPU as DP slave

Siemens ST 70 · 2009 5/43


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 412H, CPU 414H, CPU 417H

■ Technical specifications (continued)


6ES7 412-3HJ14-0AB0 6ES7 414-4HM14-0AB0 6ES7 417-4HT14-0AB0
2nd interface
Physics RS 485 / PROFIBUS + MPI RS 485 / PROFIBUS + MPI
isolated Yes Yes
Functionality
• DP master Yes Yes
• DP slave No No
DP master
• Number of connections, max. 16 32
• Services
- PG/OP communication Yes Yes
- Routing Yes Yes
- S7 basic communication No No
5 - S7 communication
- equidistance support
Yes
No
Yes
No
- Activation/deactivation of No
DP slaves
- direct data exchange No No
(cross traffic)
• Transmission speeds, max. 12 MBit/s 12 MBit/s
• Number of DP slaves, max. 96 125
• Address area
- Inputs, max. 6 Kibyte 8 Kibyte
- Outputs, max. 6 Kibyte 8 Kibyte
• Useful data per DP slave
- Inputs, max. 244 byte 244 byte
- Outputs, max. 244 byte 244 byte
3rd interface
Type of interfaces Pluggable synchronization Pluggable synchronization Pluggable synchronization
submodule (FO) submodule (FO) submodule (FO)
pluggable interface module Synchronization submodule IF 960 Synchronization submodule IF 960 Synchronization submodule IF 960
6ES7 960-1AA04-0XA0 6ES7 960-1AA04-0XA0 or 6ES7 960-1AA04-0XA0 or
6ES7 960-1AB04-0XA0 6ES7 960-1AB04-0XA0
4th interface
Type of interface Pluggable synchronization Pluggable synchronization Pluggable synchronization
submodule (FO) submodule (FO) submodule (FO)
pluggable interface modules Synchronization submodule IF 960 Synchronization submodule IF 960 Synchronization submodule IF 960
6ES7 960-1AA04-0XA0 6ES7 960-1AA04-0XA0 or 6ES7 960-1AA04-0XA0 or
6ES7 960-1AB04-0XA0 6ES7 960-1AB04-0XA0
Isochronous mode
equidistance No
CiR configuration in RUN
CiR synchronization time, 150 ms 100 ms 60 ms
basic load
CiR synchronization time, 40 μs 25 μs 10 μs
time per I/O slave

5/44 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 412H, CPU 414H, CPU 417H

■ Technical specifications (continued)


6ES7 412-3HJ14-0AB0 6ES7 414-4HM14-0AB0 6ES7 417-4HT14-0AB0
CPU/programming
Configuration software
• STEP 7 Yes; With hardware update as of Yes; With hardware update as of Yes; With hardware update as of
STEP7 V5.3 SP2 STEP7 V5.3 SP2 STEP7 V5.3 SP2
Programming language
• STEP 7 Yes Yes Yes
• LAD Yes Yes Yes
• FUP Yes Yes Yes
• AWL Yes Yes Yes
• SCL Yes Yes Yes
• CFC Yes Yes Yes
• GRAPH
• HiGraph
Yes
Yes
Yes
Yes
Yes
Yes
5
Nesting levels 8 8 8
User program protection/ Yes Yes Yes
password protection
Dimensions
Required slots 2 2 2
Dimensions
Dimensions
• Width 50 mm 50 mm 50 mm
• Height 290 mm 290 mm 290 mm
• Depth 219 mm 219 mm 219 mm
Weights
• Weight, approx. 990 g 995 g 995 g

Siemens ST 70 · 2009 5/45


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 412H, CPU 414H, CPU 417H

■ Ordering data Order No. Order No.


CPU 412-3H 6ES7 412-3HJ14-0AB0 MPI cable 6ES7 901-0BF00-0AA0
For S7-400H and S7-400F/FH; For connecting SIMATIC S7 and
768 KB main memory, combined the PG through MPI; 5 m in length
MPI/PROFIBUS DP master
interface, 2 slots for sync Slot number plates 6ES7 912-0AA00-0AA0
modules, slot for memory card, 1 set (spare part)
incl. slot number labels
S7 F systems RT license 6ES7 833-1CC00-6YX0
CPU 412-3H system bundle
For processing safety-related
Not assembled, comprising: user programs, for one S7 400H-
UR2-H rack, 2 x PS 405/407 based system each with
power supply, 2 x CPU 412-3H, CPU 412-3H, CPU 414-4H or
2 x memory card RAM (1 MB), CPU 417-4H
4 x sync module (for max. 10 m),
2 x fiber-optic connecting cable S7 F systems V6.0 6ES7 833-1CC01-0YA5
for sync modules (1 m), Programming and configuration
4 x backup battery environment for creating and

5 412H system bundle, 1 MB, B7 6ES7 400-0HR00-4AB0 using safety-related STEP 7


120/230 V AC, 10 A programs for an S7 400H-based
target system, Floating License
412H system bundle, 1 MB, B7 6ES7 400-0HR50-4AB0 for 1 user, executes with Windows
24/48/60 V DC, 10 A XP Prof SP2, Windows 2000 SP4,
CPU 414-4H 6ES7 414-4HM14-0AB0 Windows Server 2003 SP1/SP2
2 languages (German, English)
For S7-400H and S7-400F/FH; Type of delivery:
2.8 MB main memory, Certificate of License as well as
MPI/PROFIBUS DP master software and electronic
interface, 2 slots for sync documentation on CD
modules, slot for memory card,
incl. slot number labels S7 F systems upgrade from 6ES7 833-1CC01-0YE5
V5.x to V6.0
CPU 417-4H 6ES7 417-4HT14-0AB0
2 languages (German, English),
For S7-400H and S7-400F/FH; Floating License for 1 user
30 MB main memory, Type of delivery:
MPI/PROFIBUS DP master Certificate of License as well as
interface, 2 slots for sync software and electronic
modules, slot for memory card, documentation on CD
incl. slot number plates
Manual "Communication for
Memory card RAM SIMATIC S7-300/-400"
1 MB 6ES7 952-1AK00-0AA0 German 6ES7 398-8EA00-8AA0
2 MB 6ES7 952-1AL00-0AA0 English 6ES7 398-8EA00-8BA0
4 MB 6ES7 952-1AM00-0AA0 French 6ES7 398-8EA00-8CA0
8 MB 6ES7 952-1AP00-0AA0 Spanish 6ES7 398-8EA00-8DA0
16 MB 6ES7 952-1AS00-0AA0 Italian 6ES7 398-8EA00-8EA0
64 MB 6ES7 952-1AY00-0AA0 SIMATIC Manual Collection B3 6ES7 998-8XC01-8YE0
FEPROM memory card Electronic manuals on DVD, five
languages: S7-200/300/400, C7,
1 MB 6ES7 952-1KK00-0AA0 LOGO!, SIMATIC DP, PC, PG,
2 MB 6ES7 952-1KL00-0AA0 STEP 7, engineering software,
runtime software, PCS 7, SIMATIC
4 MB 6ES7 952-1KM00-0AA0 HMI, SIMATIC NET
8 MB 6ES7 952-1KP00-0AA0 SIMATIC Manual Collection B3 6ES7 998-8XC01-8YE2
16 MB 6ES7 952-1KS00-0AA0 update service for 1 year

32 MB 6ES7 952-1KT00-0AA0 Current "Manual Collection" DVD


and the three subsequent
64 MB 6ES7 952-1KY00-0AA0 updates
B3: Subject to export regulations: AL: N and ECCN: 5D992B1
B7: Subject to export regulations: AL: N and ECCN: EAR99H

5/46 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 412H, CPU 414H, CPU 417H

■ Ordering data Order No. Order No.


Brochure "SIMATIC S7-400 RS 485 bus connector with
automation system - axial cable outlet
design and application"
For SIMATIC OP, for connecting to 6GK1 500-0EA02
German 6ES7 498-8AA00-8AB0 PPI, MPI, PROFIBUS
English 6ES7 498-8AA00-8BB0 PROFIBUS FastConnect
bus cable
RS 485 bus connector with
90° cable outlet Standard type with special design 6XV1 830-0EH10
for quick mounting, 2-core,
Max. transmission rate 12 Mbit/s shielded, sold by the meter,
Without programming device 6ES7 972-0BA12-0XA0 max. delivery unit 1000 m,
interface minimum ordering quantity 20 m
With programming device 6ES7 972-0BB12-0XA0
interface
RS 485 bus connector with
angular cable outlet
Max. transmission rate 12 Mbit/s
Without programming device 6ES7 972-0BA41-0XA0
5
interface
With programming device 6ES7 972-0BB41-0XA0
interface
Max. transmission rate 1.5 Mbit/s
Without programming device 6ES7 972-0BA30-0XA0
interface
RS 485 bus connector with
90° cable outlet for FastConnect
connection system
Max. transmission rate 12 Mbit/s
Without programming device 6ES7 972-0BA51-0XA0
interface
With programming device 6ES7 972-0BB51-0XA0
interface

Siemens ST 70 · 2009 5/47


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 416F

■ Overview
• For constructing a fail-safe automation system for plants with
increased safety requirements
• High-performance CPU in the top-end performance range
• Satisfies safety requirements up to SIL 3 acc. to IEC 61508
and Cat. 4 acc. to EN 954-1
• Standard and safety-related tasks can be performed with a
single CPU
• Multi-processor mode is possible
• Safety-related communication with distributed I/O devices
over PROFIBUS DP with the PROFIsafe profile
• Fail-safe I/O modules can be connected decentralized over
the integrated interfaces (DP and PN with CPU 416F-3 PN/DP)
and/or through communication modules (CP 443-5 Ext. and
CP 443-1 Adv.)

5 • Standard modules for non-safety-related applications can be


operated centrally and decentralized

■ Technical specifications
6ES7 416-2FN05- 6ES7 416-3FR05- 6ES7 416-2FN05- 6ES7 416-3FR05-
0AB0 0AB0 0AB0 0AB0
Product status CPU/blocks
Firmware version V5.0 V5.0 DB
associated programming STEP7 V5.3 SP2 or STEP7 V5.4 SP1 or • Number, max. 10 000; Number 10 000; Number
package higher with HW- higher range: 1 to 16,000 range: 1 to 16,000
update
• Size, max. 64 Kibyte 64 Kibyte
Feeding of external buffer 5 to 15 V DC 5 to 15 V DC
voltage to CPU FB

Current consumption • Number, max. 5 000; Number 5 000; Number


range: 0 to 7999 range: 0 to 7999
from backplane bus DC 5 V, 1.1 A 1.3 A
max. • Size, max. 64 Kibyte 64 Kibyte

from interface DC 5 V, max. 90 mA; At each 90 mA; At each FC


DP interface DP interface • Number, max. 5 000; Number 5 000; Number
Current consumption/ range: 0 to 7,999 range: 0 to 7,999
power loss • Size, max. 64 Kibyte 64 Kibyte
Power loss, typ. 4W 4.5 W OB
Backup battery • Size, max. 64 Kibyte 64 Kibyte
• Buffer current, typ. 125 μA; 125 μA; Nesting depth
Valid up to 40°C Valid up to 40°C
• per priority class 24 24
• Buffer current, max. 550 μA 550 μA
• additional within an error 2 2
Memory OB
Type of storage CPU/processing times
RAM for bit operations, min. 30 ns 30 ns
• integrated (for program) 2.8 MByte 5.6 MByte for word operations, min. 30 ns 30 ns
• integrated (for data) 2.8 MByte 5.6 MByte for fixed point arithmetic, 30 ns 30 ns
• expandable No No min.

Load memory for floating point arithmetic, 90 ns 90 ns


min.
• expandable FEPROM Yes Yes
Times/counters and their
• expandable FEPROM, 64 MByte 64 MByte remanence
max.
S7 counter
• integrated RAM, max. 1 MByte 1 MByte
• Number 2 048 2 048
• expandable RAM Yes Yes
• expandable RAM, max. 64 MByte 64 MByte
Backup
• present Yes Yes
• with battery Yes Yes
• without battery No No

5/48 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 416F

■ Technical specifications (continued)


6ES7 416-2FN05- 6ES7 416-3FR05- 6ES7 416-2FN05- 6ES7 416-3FR05-
0AB0 0AB0 0AB0 0AB0
S7 counter (continued) Subprocess images
• Remanence • Number of subprocess 15 15
- adjustable Yes Yes images, max.
- lower limit 0 0 Digital channels
- upper limit 2 047 2 047
• Inputs 131 072 131 072
- preset From Z 0 to Z 7 From Z 0 to Z 7
• Outputs 131 072 131 072
• Counting range
- lower limit 0 0 • Inputs, of which central 131 072 131 072
- upper limit 999 999 • Outputs, of which central 131 072 131 072
IEC counter Analog channels
• present Yes Yes • Inputs 8 192 8 192
• Type SFB SFB • Outputs 8 192 8 192
S7 times • Inputs, of which central 8 192 8 192 5
• Number 2 048 2 048 • Outputs, of which central 8 192 8 192
• Remanence Hardware config.
- adjustable Yes Yes connectable OPs 63 63
- lower limit 0 0
- upper limit 2 047 2 047 Central devices, max. 1 1
- preset No times retentive No times retentive Expansion devices, max. 21 21
• Time range Multicomputing Yes; Max. 4 CPUs Yes; Max. 4 CPUs
- lower limit 10 ms 10 ms (with UR1 or UR2) (with UR1 or UR2)
- upper limit 9 990 s 9 990 s IM
IEC timer • Number of connectable 6 6
• present Yes Yes IMs (total), max.

• Type SFB SFB • Number of connectable 6 6


IM 460s, max.
Data areas and their
remanence • Number of connectable 4; IM 463-2 4; IM 463-2
IM 463s, max.
remanent data area, total Total working and Total working and
load memory (with load memory (with Number of DP masters
backup battery) backup battery) • integrated 2 2
Flag • via IM 467 4 4
• Number, max. 16 Kibyte 16 Kibyte • via CP 10; CP 443-5 10; CP 443-5
• Remanence available Yes Yes Extended Extended

• Number of clock memories 8; (in 1 memory 8; (in 1 memory • Mixed mode IM + CP No; IM 467 cannot No; IM 467 cannot
byte) byte) permitted be used with be used with
CP 443-5 Ext.; CP 443-5 Ext.;
Address area IM 467 cannot be IM 467 cannot be
used with used with
I/O address area CP 443-1 EX40 in CP 443-1 EX40 in
• Inputs 16 Kibyte 16 Kibyte PN IO mode PN IO mode
• Outputs 16 Kibyte 16 Kibyte • via interface module 0 1
• of which, distributed • Number of pluggable 6 6
- MPI/DPinterface, inputs 2 Kibyte 2 Kibyte S5 modules (via adapter
capsule in central device),
- MPI/DP interface, 2 Kibyte 2 Kibyte max.
outputs
- DP interface, inputs 8 Kibyte 8 Kibyte Number of IO controllers
- DP interface, outputs 8 Kibyte 8 Kibyte • integrated
Process image • via CP 4; 4;
Via CP 443-1 EX 41 Via CP 443-1 EX 41
• Inputs, adjustable 16 Kibyte 16 Kibyte in PN mode; max. 4 in PN mode; max. 4
• Outputs, adjustable 16 Kibyte 16 Kibyte in central controller in central controller
• Inputs, preset 512 byte 512 byte Number of operable FMs
and CPs (recommended)
• Outputs, preset 512 byte 512 byte
• consistent data, max. 244 byte 244 byte • FM Limited due to Limited due to
number of slots and number of slots and
• Access to consistent data Yes Yes number of connec- number of connec-
in process image tions tions

Siemens ST 70 · 2009 5/49


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 416F

■ Technical specifications (continued)


6ES7 416-2FN05- 6ES7 416-3FR05- 6ES7 416-2FN05- 6ES7 416-3FR05-
0AB0 0AB0 0AB0 0AB0
Number of operable FMs Diagnostic buffer
and CPs (recommended)
(cont.) • present Yes Yes

• CP, point-to-point Limited due to Limited due to • Number of entries, max. 3 200 3 200
number of slots and number of slots and • adjustable Yes Yes
number of connec- number of connec-
tions tions • preset 120 120
• PROFIBUS and Ethernet 14; Of which 10 CP 14; Of which 10 Communication functions
CPs or IM max. as DP CP/IM max. as DP PG/OP communication Yes Yes
master and PN master and PN
controller controller Routing Yes Yes
Time Global data communication
Clock • supported Yes Yes

5 • Hardware clock
(real-time clock)
Yes Yes • Size of GD packets, max.
S7 basic communication
54 byte 54 byte

• buffered and synchroni- Yes Yes


• supported Yes Yes
zable
• Useful data per job, max. 76 byte 76 byte
• Resolution 1 ms 1 ms
S7 communication
Operating hours counter
• supported Yes Yes
• Number 8 8
• Useful data per job, max. 64 Kibyte 64 Kibyte
Clock synchronization
S5-compatible
• supports Yes Yes
communication
• to MPI, Master Yes Yes
• supported Yes; Yes;
• to MPI, Slave Yes Yes (via CP max. 10 (via CP max. 10
and FC AG_SEND and FC AG_SEND
• to DP, Master Yes Yes and FC AG_RECV) and FC AG_RECV)
• to DP, Slave Yes Yes • Useful data per job, max. 8 Kibyte 8 Kibyte
• in AS, Master Yes Yes Standard communication
• in AS, Slave Yes Yes (FMS)
• on Ethernet via NTP Via CP Via CP • supported Yes; Via CP and Yes; Via CP and
loadable FB loadable FB
• to IF 964 DP Yes
Web server
S7 message functions
• Web server No; Via CP Yes; Read-only
Number of login stations for 63; Max. 63 with 63; Max. 63 with function
message functions, max. ALARM_S and ALARM_S and
ALARM_D (OPs); ALARM_D (OPs); Open IE communication
max. 12 with max. 12 with • TCP/IP Yes
ALARM_8 and ALARM_8 and
- Number of connections, 64
ALARM_P ALARM_P
(e.g. WinCC) (e.g. WinCC) max.
- Data length, max. 32 Kibyte
Symbol-related messages Yes Yes
• ISO-on-TCP (RFC1006) Via CP 443-1 Adv. Yes
Number of messages
and loadable FB
• overall, max. 1 024 1 024 - Number of connections, 64
Block related messages Yes Yes max.
- Data length, max. 1452 32 Kibyte;
Alarm 8-blocks Yes Yes
1452 bytes via
Instrumentation & control Yes Yes CP 443-1 Adv.
messages
• UDP Yes
Test commissioning - Number of connections,
functions 64
max.
Status/control - Data length, max. 1 472 byte
• Status/control variable Yes Yes Number of connections
Forcing • overall 64 64
• Forcing Yes Yes
Status block Yes Yes
Single step Yes Yes
Number of breakpoints 4 4

5/50 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 416F

■ Technical specifications (continued)


6ES7 416-2FN05- 6ES7 416-3FR05- 6ES7 416-2FN05- 6ES7 416-3FR05-
0AB0 0AB0 0AB0 0AB0
PROFINET CBA (at set Functionality
setpoint communication
load) • MPI Yes Yes

• Number of remote inter- 32 • DP master Yes Yes


connection partners • DP slave Yes Yes
• Number of functions, 150 MPI
master/slave
• Number of connections 44 44
• Total of all master/slave 6 000
connections • Services
- PG/OP communication Yes Yes
• Data length of all incoming 65 000 byte
connections master/slave, - Routing Yes Yes
max. - Global data communi- Yes Yes
cation
• Data length of all outgoing 65 000 byte - S7 basic communication Yes Yes
connections master/slave,
max. - S7 communication Yes Yes 5
• Number of device-internal 1 000 • Transmission speeds, 12 MBit/s 12 MBit/s
and PROFIBUS intercon- max.
nections DP master
• Data length of device- 16 000 byte • Number of connections, 32 32; if a diagnostic
internal and PROFIBUS max. repeater is used on
interconnections, max. the line, the number
• Data length per 2 000 byte of connection
connection, max. resources on the
line is reduced by 1
• Remote interconnections
with acyclic transmission • Services
- Transmission frequency: - PG/OP communication Yes Yes
1 ms; Depending - Routing Yes Yes
transmission interval, on preset communi-
min. cation load, number - Global data communi- No No
of interconnections cation
and data length - S7 basic communication Yes Yes
used - S7 communication Yes Yes
- Number of incoming 300 - equidistance support Yes Yes
interconnections - Activation/deactivation of Yes Yes
- Number of outgoing 300 DP slaves
interconnections - direct data exchange Yes Yes
- Data length of all incoming 4 800 byte (cross traffic)
interconnections, max.
• Transmission speeds, 12 MBit/s 12 MBit/s
- Data length of all outgoing 4 800 byte max.
interconnections, max.
- Data length per • Number of DP slaves, max. 32 32
250 byte
connection, max. • Address area
• HMI variables via - Inputs, max. 2 Kibyte 2 Kibyte
PROFINET (acyclic) - Outputs, max. 2 Kibyte 2 Kibyte
- Number of log-in stations 2x PN OPC/1x iMap
for HMI variables • Useful data per DP slave
(PN OPC/iMap) - Inputs, max. 244 byte 244 byte
- HMI variable updating - Outputs, max. 244 byte 244 byte
500 ms
- Number of HMI variables DP slave
1 500
- Data length of all HMI • Number of connections 32 32
48 000 byte
variables, max. • Services
• PROFIBUS proxy - PG/OP communication Yes Yes; with interface
functionality active
- supported Yes; 32 PROFIBUS - Routing Yes Yes; with interface
slaves max. active
connectable • Transmission speeds, 12 MBit/s 12 MBit/s
- Data length per 240 byte; max.
connection, max. Slave-dependent • Transfer memory
1st interface - Inputs 244 byte 244 byte
- Outputs 244 byte 244 byte
Physics RS 485 / PROFIBUS RS 485 / PROFIBUS
+ MPI • Address area, max. 32 32; Virtual slots
isolated Yes Yes • Useful data per address 32 byte 32 byte
area, max.
• Useful data per address 32 byte 32 byte
area, of which consistent,
max.

Siemens ST 70 · 2009 5/51


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 416F

■ Technical specifications (continued)


6ES7 416-2FN05- 6ES7 416-3FR05- 6ES7 416-2FN05- 6ES7 416-3FR05-
0AB0 0AB0 0AB0 0AB0
2nd interface PROFINET IO controller
Physics RS 485 / PROFIBUS Ethernet • Services
isolated Yes Yes - PG/OP communication Yes
- Routing Yes; Routing of PG
Functionality functions
• DP master Yes No - S7 communication Yes
- open IE communication Yes
• DP slave Yes No
• Transmission rate, min. 10 MBit/s
• PROFINET IO controller Yes
• Transmission speed, max. 100 MBit/s
• PROFINET CBA Yes
• Total number of 256
• Point-to-point coupling No
connectable IO Devices,
DP master max.

5 • Number of connections,
max.
32 • Updating time 250 μs to 512 ms;
minimum value
dependent on
• Services preset communi-
- PG/OP communication Yes cation share for
- Routing Yes PROFINET I/O,
- S7 basic communication Yes of number of I/O
devices and
- S7 communication Yes
number of
- equidistance support Yes configured user
- Activation/deactivation of Yes data
DP slaves
• Address area
- direct data exchange Yes
(cross traffic) - Inputs, max. 8 Kibyte
- Outputs, max. 8 Kibyte
• Transmission speeds, 12 MBit/s
- Useful data consistency, 255 byte; incl. net
max.
max. data accompaniers
• Number of DP slaves, max. 125
PROFINET CBA
• Address area
• Acyclic transmission Yes
- Inputs, max. 8 Kibyte
- Outputs, max. 8 Kibyte • cyclic transmission Yes

• Useful data per DP slave 3rd interface


- Inputs, max. 244 byte Type of interfaces Pluggable interface
- Outputs, max. 244 byte module (IF),
technical specifica-
DP slave tions as for 2nd
• Number of connections 32 interface

• Services pluggable interface module IF 964-DP


(Order No.: 6ES7
- Routing Yes
964-2AA04-0AB0)
- Programming Yes
Physics RS 485 / PROFIBUS
• GSD file http://support.
automation. isolated Yes
siemens.com/WW/ power supply to interface 150 mA
view/en/113652 (15 to 30 V DC), max.
• Transmission speeds, 12 MBit/s Number of connection 32
max. resources
• Transfer memory Functionality
- Inputs 244 byte
- Outputs 244 byte • MPI No

• Address area, max. 32 • DP master Yes

• Useful data per address 32 byte • DP slave Yes


area, max.
• Useful data per address 32 byte
area, of which consistent,
max.

5/52 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 416F

■ Technical specifications (continued)


6ES7 416-2FN05- 6ES7 416-3FR05- 6ES7 416-2FN05- 6ES7 416-3FR05-
0AB0 0AB0 0AB0 0AB0
DP master Isochronous mode
• Number of connections, 32 Useful data per isoch- 244 byte 244 byte
max. ronous slave, max.
• Services equidistance Yes Yes
- PG/OP communication Yes shortest clock pulse 1 ms; 0.5 ms 1 ms; Without use
- Routing Yes without use of of SFC 126 and 127
- Global data communi- No SFC 126, 127 up to 0.5 ms
cation
CiR configuration in RUN
- S7 basic communication Yes
- S7 communication Yes CiR synchronization time, 100 ms 100 ms
basic load
- Equidistance support Yes
- SYNC/FREEZE Yes CiR synchronization time, 40 μs 40 μs
- Activation/deactivation of Yes time per I/O slave
DP slaves
- Direct data exchange Yes
CPU/programming
Configuration software
5
• Transmission rate, max. 12 MBit/s
• STEP 7 Yes Yes
• Number of DP slaves, max. 125
Programming language
• Address area
• STEP 7 Yes
- Inputs, max. 8 Kibyte
- Outputs, max. 8 Kibyte • LAD Yes Yes
• Useful data per DP slave • FUP Yes Yes
- Useful data per DP slave, 244 byte • AWL Yes Yes
max.
- Inputs, max. 244 byte • SCL Yes Yes
- Outputs, max. 244 byte • CFC Yes Yes
- Slots, max. 244 • GRAPH Yes Yes
- per slot, max. 128 byte
• HiGraph Yes Yes
DP slave
Nesting levels 7 7
• Number of connections 32
User program Yes Yes
• Services protection/password
- Routing Yes; When interface protection
active
Dimensions
- Status/control Yes; When interface
active Required slots 1 2
• GSD file http://support. Dimensions
automation. Dimensions
siemens.com/WW/
view/en/113652 • Width 25 mm 50 mm
• Transmission rate, max. 12 MBit/s • Height 290 mm 290 mm
• Transfer memory • Depth 219 mm 219 mm
- Inputs 244 byte Weights
- Outputs 244 byte
• Weight, approx. 720 g 900 g
• Address range, max. 32
• Useful data per address 32 byte
area, max.
• Useful data per address 32 byte
area, of which consistent,
max.

Siemens ST 70 · 2009 5/53


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 416F

■ Ordering data Order No. Order No.


CPU 416F-2 6ES7 416-2FN05-0AB0 MPI cable 6ES7 901-0BF00-0AA0
For configuring safety-related For connecting SIMATIC S7 and
automation systems; the PG through MPI; 5 m in length
main memory 5.6 MB, 24 V DC
power supply, MPI/PROFIBUS DP IF 964-DP interface module 6ES7 964-2AA04-0AB0
master interface, PROFIBUS DP For connecting an additional
master interface, slot for memory DP line
card, incl. slot number labels
Slot number plates 6ES7 912-0AA00-0AA0
CPU 416F-3 PN/DP 6ES7 416-3FR05-0AB0
1 set (spare part)
For configuring safety-related
automation systems; Manual "SIMATIC S7-400
main memory 11.2 MB, 24 V DC automation system"
power supply, MPI/PROFIBUS DP incl. instruction list
master interface, PROFINET
interface, PROFIBUS DP master German 6ES7 498-8AA05-8AA0
interface, receptacle for 1 IF
English 6ES7 498-8AA05-8BA0
submodule, slot for memory card,
5 incl. slot number labels
Option package S7 F
French
Spanish
6ES7 498-8AA05-8CA0
6ES7 498-8AA05-8DA0
Distributed Safety V5.4
Italian 6ES7 498-8AA05-8EA0
for generating fail-safe programs
for the S7-300F S7-400 instructions list

Floating License 6ES7 833-1FC02-0YA5 German 6ES7 498-8AA05-8AN0

Upgrade from V5.x to V5.4 6ES7 833-1FC02-0YE5 English 6ES7 498-8AA05-8BN0

Software Update Service 6ES7 833-1FC00-0YX2 French 6ES7 498-8AA05-8CN0

Memory card RAM Spanish 6ES7 498-8AA05-8DN0

64 KB 6ES7 952-0AF00-0AA0 Italian 6ES7 498-8AA05-8EN0

256 KB 6ES7 952-1AH00-0AA0 Manual "Communication for


SIMATIC S7-300/-400"
1 MB 6ES7 952-1AK00-0AA0
German 6ES7 398-8EA00-8AA0
2 MB 6ES7 952-1AL00-0AA0
English 6ES7 398-8EA00-8BA0
4 MB 6ES7 952-1AM00-0AA0
French 6ES7 398-8EA00-8CA0
8 MB 6ES7 952-1AP00-0AA0
Spanish 6ES7 398-8EA00-8DA0
16 MB 6ES7 952-1AS00-0AA0
Italian 6ES7 398-8EA00-8EA0
64 MB 6ES7 952-1AY00-0AA0
SIMATIC Manual Collection B3 6ES7 998-8XC01-8YE0
FEPROM memory card
Electronic manuals on DVD, five
64 KB 6ES7952-0KF00-0AA0 languages: S7-200/300/400, C7,
LOGO!, SIMATIC DP, PC, PG,
256 KB 6ES7952-0KH00-0AA0
STEP 7, engineering software,
1 MB 6ES7 952-1KK00-0AA0 runtime software, PCS 7, SIMATIC
HMI, SIMATIC NET
2 MB 6ES7 952-1KL00-0AA0
SIMATIC Manual Collection B3 6ES7 998-8XC01-8YE2
4 MB 6ES7 952-1KM00-0AA0 update service for 1 year
8 MB 6ES7 952-1KP00-0AA0 Current "Manual Collection" DVD
16 MB 6ES7 952-1KS00-0AA0 and the three subsequent
updates
32 MB 6ES7 952-1KT00-0AA0
Brochure "SIMATIC S7-400
64 MB 6ES7 952-1KY00-0AA0 automation system - Design
and application"
German 6ES7 498-8AA00-8AB0
English 6ES7 498-8AA00-8BB0
B3: Subject to export regulations: AL: N and ECCN: 5D992B1

5/54 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Central processing units
CPU 416F

■ Ordering data Order No. Order No.


PROFIBUS bus components PROFINET bus components
RS 485 bus connector with IE FC TP Standard Cable GP 6XV1 840-2AH10
90° cable outlet 2x2
Max. transfer rate 12 Mbit/s 4-core, shielded TP installation
cable for connection to IE
Without PG interface 6ES7 972-0BA12-0XA0 FC Outlet RJ45/ IE FC RJ45 Plug;
With PG interface 6ES7 972-0BB12-0XA0 PROFINET-compatible;
with UL approval;
RS 485 bus connector with sold by the meter
angled cable outlet
FO Standard Cable GP (50/125) 6XV1 873-2A
Max. transfer rate 12 Mbit/s
Standard cable, splittable,
Without PG interface 6ES7 972-0BA41-0XA0 UL approval, sold by the meter
With PG interface 6ES7 972-0BB41-0XA0 SCALANCE X204-2 6GK5 204-2BB10-2AA3
RS 485 bus connector with Industrial Ethernet Switch
90° cable outlet for FastConnect Industrial Ethernet Switches with

5
system integral SNMP access, web
Max. transfer rate 12 Mbit/s diagnostics, copper cable
diagnostics and PROFINET
Without PG interface 6ES7 972-0BA51-0XA0 diagnostics for configuring line,
star and ring topologies;
With PG interface 6ES7 972-0BB51-0XA0
four 10/100 Mbit/s RJ45 ports and
RS 485 bus connector with two FO ports
axial cable outlet
IE FC RJ45 plugs
For SIMATIC OP, for connection to 6GK1 500-0EA02
RJ45 plug connector for Industrial
PPI, MPI, PROFIBUS
Ethernet with a rugged metal
PROFIBUS FastConnect enclosure and integrated
bus cable insulation displacement contacts
for connecting Industrial Ethernet
Standard type with special design 6XV1 830-0EH10 FC installation cables
for quick mounting, 2-core,
shielded, sold by the meter, IE FC RJ45 plug 180
max. delivery unit 1000 m,
180° cable outlet
minimum order quantity 20 m
1 unit 6GK1 901-1BB10-2AA0
RS 485 repeater for PROFIBUS 6ES7 972-0AA01-0XA0
10 units 6GK1 901-1BB10-2AB0
Data transfer rate up to 12 Mbit/s;
24 V DC; IP20 housing 50 units 6GK1 901-1BB10-2AE0
PROFIBUS/PROFINET see Catalogs IK PI, CA 01
bus components
For establishing
MPI/PROFIBUS/PROFINET
communication

Siemens ST 70 · 2009 5/55


© Siemens AG 2008

SIMATIC S7-400
Central processing units
Sync module for coupling the CPU 41xH

■ Overview ■ Ordering data Order No.


for coupling the CPU 41xH for
S7-400H/F/FH;
2 modules required per CPU;
For 6ES7 412-3HJ14-0AB0, 6ES7 960-1AA04-0XA0
6ES7 414-4HM14-0AB0 and
6ES7 417-4HT14-0AB0;
for patch cable, can be used for
fiber-optic cables up to 10 m in
length
For 6ES7 414-4HM14-0AB0 and B7 6ES7 960-1AB04-0XA0
6ES7 417-4HT14-0AB0;
for patch and installation cables,
can be used for fiber-optic cables
up to 10 km in length
Fiber-optic connecting cable
For Sync module

5 6ES7 960-1Ax04-0XA0
•1m 6ES7 960-1AA04-5AA0
•2m 6ES7 960-1AA04-5BA0
• For coupling the two CPU 41xH in the S7-400H subunits.
• 10 m 6ES7 960-1AA04-5KA0
• Can be plugged direct into the CPU
For Sync module on request

■ Technical specifications
6ES7 960-1AB04-0XA0;
fiber-optic monomode
LC/LC duplex crossed 9/125 μ
6ES7 960-1AA04- 6ES7 960-1AB04- (max. 10 km)
0XA0 0XA0
Current consumption
from CPU, max. 210 mA 250 mA
Current consumption/
power loss
Power loss, typ. 1.1 mW 1.3 mW
Dimensions
Dimensions
• Width 25 mm 25 mm
• Height 53 mm 53 mm
• Depth 140 mm 140 mm
Weights
• Weight, approx. 65 g 65 g
B7: Subject to export regulations: AL: N and ECCN: EAR99H

5/56 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Central processing units
IF-964 DP PROFIBUS module

■ Overview 1st interface


Physics RS 485
isolated Yes
Functionality
• DP master Yes; Default setting
• DP slave Yes
DP master
• Services
- PG/OP communication Yes
- equidistance support Yes
- SYNC/FREEZE Yes
- direct data exchange Yes
(cross traffic)
• Transmission speeds, max. 12 MBit/s
• Transmission speeds, min. 9.6 kBit/s
• Number of DP slaves, max. 125; depending on the CPU used 5
• Address area
• To connect distributed I/Os over PROFIBUS DP - Inputs, max. device-dependent
• Max. transmission rate 12 Mbit/s - Outputs, max. device-dependent
• Electrically isolated RS 485 interface • Useful data per DP slave
• Connection via 9-pin sub-D connector - Inputs, max. 244 byte
- Outputs, max. 244 byte
• One or two PROFIBUS modules can be inserted per S7-400
CPU: Dimensions
- CPU 414-3/416-3: 1 module Dimensions
- CPU 417-4: 2 modules
• Width 26 mm
• Height 54 mm
Note:
• Depth 130 mm
Can only be used with CPUs 6ES7 414-3XM05-0AB0,
6ES7 414-3EM05-0AB0, 6ES7 416-3XR05-0AB0, Weights
6ES7 416-3ER05-0AB0 and 6ES7 417-4XT05-0AB0. • Weight, approx. 65 g

■ Technical specifications ■ Ordering data Order No.


6ES7 964-2AA04-0AB0 IF-964 DP interface module 6ES7 964-2AA04-0AB0
Current consumption Interface module with integral
PROFIBUS DP master interface
from CPU, max. 150 mA; Current consumption from
S7-400 bus: The module uses no
current at 24 V, it provides this
voltage only at the DP interface. Total
current consumption of the compo-
nents connected to the DP interface,
but maximum 150 mA. Current
carrying capacity of the isolated 5 V
(P5ext) maximum 90 mA, current
carrying capacity of the 24 V
maximum 150 mA.
Current consumption/
power loss
Power loss, typ. 1W
Communication functions
Number of connections
• overall device-dependent
PROFIBUS DP
Cable length, max. 1 200 m; at 9.6 Kbit/s: max. 1200 m;
at 12 Mbit/s: max. 100 m

Siemens ST 70 · 2009 5/57


© Siemens AG 2008

SIMATIC S7-400
SIPLUS central processing units
SIPLUS CPU 416, CPU 417

■ Overview SIPLUS CPU 416-3, CPU 416-3 PN/DP ■ Overview SIPLUS CPU 417-4

5
High-performance CPUs in the high-end performance range The most powerful SIMATIC S7-400 CPU
• Applicable for plants with high requirements in the high-end • Applicable for plants with maximum requirements in the high-
performance range end performance range
• Integrated PROFINET functions in CPU 416-3 PN/DP • With 2 plug-in slots for IF modules

SIPLUS CPU 416-3 SIPLUS CPU 417-4


Order No. 6AG1 416-3XR05- 6AG1 416-3ER05- Order No. 6AG1 417-4XT05-4AB0
4AB0 4AB0
Order No. based on 6ES7 417-4XT05-0AB0
Order No. based on 6ES7 416-3XR05- 6ES7 416-3ER05-
0AB0 0AB0 Environmental conditions Suited for exceptional medial exposure
(e. g. by chlorine sulfur atmosphere)
Environmental conditions Suited for exceptional medial exposure
(e. g. by chlorine sulfur atmosphere). Technical data The technical data are identical with
those of the based-on modules.
Technical data The technical data are identical with
those of the based-on modules.

For further technical documentation on SIPLUS, see: For further technical documentation on SIPLUS, see:
http://www.siemens.com/siplus-techdoku http://www.siemens.com/siplus-techdoku

■ Ordering data Order No. ■ Ordering data Order No.


CPU 416-3 B7 6AG1 416-3XR05-4AB0 SIPLUS CPU 417-4 B7 6AG1 417-4XT05-4AB0
(medium exposure) (medium exposure)
Main memory 11.2 MB, Main memory 30 MB,
power supply 24 V DC, power supply 24 V DC,
MPI/PROFIBUS DP master MPI/PROFIBUS DP master
interface, PROFIBUS DP master interface, PROFIBUS DP master
interface, module slot for 1 IF interface, module slots for max.
module, slot for memory card, 2 additional IF modules, slot for
incl. slot number labels memory card, incl. slot number
labels
CPU 416-3 PN/DP B7 6AG1 416-3ER05-4AB0
Accessories see CPU 417, page 5/37
(medium exposure)
Main memory 11.2 MB,
power supply 24 V DC,
MPI/PROFIBUS DP master
interface, PROFINET interface,
PROFIBUS DP master interface,
module slot for 1 IF submodule,
slot for memory card, incl. slot
number labels
Accessories see CPU 416, page 5/32
B7: Subject to export regulations: AL: N and ECCN: EAR99H B7: Subject to export regulations: AL: N and ECCN: EAR99H

5/58 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
SIPLUS central processing units
SIPLUS CPU 414-4H, CPU 417-4H

■ Overview SIPLUS CPU 414-4H ■ Overview SIPLUS CPU 417-4H

5
CPU for SIMATIC S7-400H and S7-400F/FH CPU for SIMATIC S7-400H and S7-400F/FH
• For use in S7-400H fault-tolerant systems • For use in S7-400H fault-tolerant systems
• Can be used with F-Runtime license as fail-safe CPU in safety- • Can be used with F-Runtime license as fail-safe CPU in safety-
related S7-400F/FH systems related S7-400F/FH systems
• With integral PROFIBUS DP master interface • With integral PROFIBUS DP master interface
• With 2 plug-in slots for sync modules • With 2 plug-in slots for sync modules

SIPLUS CPU 414-4H SIPLUS CPU 417-4H


Order No. 6AG1 414-4HJ04-4AB0 Order No. 6AG1 417-4HL04-4AB0
Order No. based on 6ES7 414-4HJ04-0AB0 Order No. based on 6ES7 417-4HL04-0AB0
Environmental conditions Suited for exceptional medial Environmental conditions Suited for exceptional medial
exposure (e. g. by chlorine sulfur exposure (e. g. by chlorine sulfur
atmosphere) atmosphere)
Technical data The technical data are identical Technical data The technical data are identical
with those of the based-on with those of the based-on
modules. modules.

For further technical documentation on SIPLUS, see: For further technical documentation on SIPLUS, see:
http://www.siemens.com/siplus-techdoku http://www.siemens.com/siplus-techdoku

■ Technical specifications
6AG1 414-4HJ04- 6AG1 417-4HL04- 6AG1 414-4HJ04- 6AG1 417-4HL04-
4AB0 4AB0 4AB0 4AB0
Supply voltages Memory
Rated value Type of storage
• DC 24 V Yes Yes RAM
Feeding of external buffer 5 to 15 V DC 5 to 15 V DC • integrated (for program) 700 Kibyte
voltage to CPU
• integrated (for data) 700 Kibyte
Current consumption
• expandable No No
from backplane bus DC 5 V, 2 A 1.7 A
max. Load memory

Current consumption/ • expandable FEPROM Yes; with Memory Yes; with Memory
power loss Card (FLASH) Card (FLASH)
Power loss, typ. 4.5 W 6W • expandable FEPROM, 64 MByte 64 MByte
max.
Backup battery
• integrated RAM, max. 256 Kibyte 256 Kibyte
• Buffer current, typ. 550 μA 600 μA
• expandable RAM Yes; With Memory Yes; With Memory
• Buffer current, max. 1 530 μA 1 810 μA Card (RAM) Card (RAM)
• expandable RAM, max. 16 MByte 16 MByte

Siemens ST 70 · 2009 5/59


© Siemens AG 2008

SIMATIC S7-400
SIPLUS central processing units
SIPLUS CPU 414-4H, CPU 417-4H

■ Technical specifications (continued)


6AG1 414-4HJ04- 6AG1 417-4HL04- 6AG1 414-4HJ04- 6AG1 417-4HL04-
4AB0 4AB0 4AB0 4AB0
Backup Data areas and their
remanence
• present Yes Yes
Flag
• with battery Yes; All data Yes; All data
• Number, max. 8 Kibyte 16 Kibyte
• without battery No No
• Remanence available Yes; Yes;
CPU/blocks MB 0 to MB 8191 MB 0 to MB 16383
DB Address area
• Number, max. 4 095; 8 192; I/O address area
DB 0 reserved DB 0 reserved
• Inputs 8 Kibyte 16 Kibyte
• Size, max. 64 Kibyte
• Outputs 8 Kibyte 16 Kibyte
FB
• of which, distributed
• Number, max. 2 048 6 144
5 • Size, max. 64 Kibyte 64 Kibyte
- MPI/DPinterface, inputs
- MPI/DP interface,
2 Kibyte
2 Kibyte
2 Kibyte
2 Kibyte
FC outputs
- DP interface, inputs 6 Kibyte 8 Kibyte
• Number, max. 2 048 6 144
- DP interface, outputs 6 Kibyte 8 Kibyte
• Size, max. 64 Kibyte 64 Kibyte
Process image
OB
• Inputs, adjustable 8 Kibyte 16 Kibyte
• Size, max. 64 Kibyte 64 Kibyte
• Outputs, adjustable 8 Kibyte 16 Kibyte
Nesting depth
• Inputs, preset 1 024 byte 1 024 byte
• per priority class 24 24
• Outputs, preset 1 024 byte 1 024 byte
• additional within an error 2
Subprocess images
OB
• Number of subprocess 8 8
CPU/processing times
images, max.
for bit operations, min. 0.06 μs 0.03 μs
Digital channels
for word operations, min. 0.06 μs 0.03 μs
• Inputs 65 536 131 072
for fixed point arithmetic, 0.06 μs 0.03 μs
• Outputs 65 536 131 072
min.
• Inputs, of which central 65 536 131 072
for floating point arithmetic, 0.18 μs 0.09 μs
min. • Outputs, of which central 65 536 131 072
Times/counters and their Analog channels
remanence
• Inputs 4 096 8 192
S7 counter
• Outputs 4 096 8 192
• Number 2 048 2 048
• Inputs, of which central 4 096 8 192
• Remanence
• Outputs, of which central 4 096 8 192
- adjustable Yes Yes
- lower limit 0 0 Hardware config.
- upper limit 2 047 2 047 Central devices, max. 1 1
- preset From Z 0 to Z 7 From Z 0 to Z 7
Expansion devices, max. 21 21
• Counting range
Multicomputing No No
- lower limit 0 1
- upper limit 999 999 IM
IEC counter • Number of connectable 6 6
IMs (total), max.
• present Yes Yes
• Number of connectable 6 6
• Type SFB SFB IM 460s, max.
S7 times • Number of connectable 6; IM 463-2 6; IM 463-2
• Number 2 048 2 048 IM 463s, max.

• Time range
- lower limit 10 ms 10 ms
- upper limit 9 990 s 9 990 s
IEC timer
• present Yes Yes
• Type SFB SFB

5/60 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
SIPLUS central processing units
SIPLUS CPU 414-4H, CPU 417-4H

■ Technical specifications (continued)


6AG1 414-4HJ04- 6AG1 417-4HL04- 6AG1 414-4HJ04- 6AG1 417-4HL04-
4AB0 4AB0 4AB0 4AB0
Number of DP masters S5-compatible communi-
cation
• integrated 2 2
• supported Yes; via CP and Yes; via CP and
• via IM 467 0 0 loadable FC loadable FC
• via CP 10 10 • Useful data per job, max. 8 Kibyte 8 Kibyte
• Mixed mode IM + CP No; IM 467 cannot No; IM 467 cannot Standard communication
permitted be used jointly with be used jointly with (FMS)
CP 443-5 Ext. CP 443-5 Ext.
• supported Yes; Via CP and Yes; Via CP and
• via interface module 0 0 loadable FB loadable FB
Number of operable FMs • Useful data per job, max. Dependent on CP Dependent on CP
and CPs (recommended)
Number of connections
• FM 32; Limited due to 64; Limited due to
number of slots and number of slots and • overall 32 64
number of connec-
tions
number of connec-
tions 1st interface 5
• CP, point-to-point 32; Limited due to 64; Limited due to Physics RS 485 / PROFIBUS RS 485 / PROFIBUS
number of slots and number of slots and isolated Yes Yes
number of connec- number of connec-
tions tions Functionality
• CP, LAN 32; limited due to 64; limited due to • MPI Yes; Default setting Yes; Default setting
number of slots and number of slots and • DP master Yes Yes
number of connec- number of connec-
tions tions • DP slave No No
Time MPI
Clock • Number of connections 32 44
• Hardware clock Yes Yes • Services
(real-time clock) - PG/OP communication Yes Yes
• buffered and synchroni- Yes Yes - Global data communi- No No
zable cation
- S7 basic communication No No
Operating hours counter
- S7 communication Yes Yes
• Number 8 8
• Transmission speeds, 12 MBit/s 12 MBit/s
Clock synchronization max.
• supports Yes Yes DP master
S7 message functions • Number of connections, 32 32
max.
Number of login stations for 8 16
message functions, max. • Services
Diagnostic buffer - PG/OP communication Yes Yes
- Global data communi- No No
• present Yes cation
• Number of entries, max. 3 200 - S7 basic communication No No
- S7 communication No No
• adjustable Yes
- S7 communication, as No No
• preset 120 client
Communication functions - S7 communication, as No No
server
PG/OP communication Yes Yes - equidistance support No No
Global data communication - Activation/deactivation of Yes No
DP slaves
• supported No No
- direct data exchange No No
S7 basic communication (cross traffic)
• supported No No • Transmission speeds, 12 MBit/s 12 MBit/s
max.
S7 communication
• Number of DP slaves, max. 32; Number of slots, 32; Number of slots,
• supported Yes Yes max. 512 max. 512
• as server Yes Yes
• as client Yes Yes
• Useful data per job, max. 64 Kibyte 64 Kibyte

Siemens ST 70 · 2009 5/61


© Siemens AG 2008

SIMATIC S7-400
SIPLUS central processing units
SIPLUS CPU 414-4H, CPU 417-4H

■ Technical specifications (continued)


6AG1 414-4HJ04- 6AG1 417-4HL04- 6AG1 414-4HJ04- 6AG1 417-4HL04-
4AB0 4AB0 4AB0 4AB0
DP master (continued) CPU/programming
• Address area Programming language
- Inputs, max. 2 Kibyte 2 Kibyte • STEP 7 Yes; V5.0 SP2 Yes; V5.0 SP2
- Outputs, max. 2 Kibyte 2 Kibyte
• LAD Yes Yes
• Useful data per DP slave
- Inputs, max. 244 byte 244 byte • FUP Yes Yes
- Outputs, max. 244 byte 244 byte • AWL Yes Yes
2nd interface • SCL Yes Yes
Physics RS 485 / PROFIBUS RS 485 / PROFIBUS • CFC Yes Yes
isolated Yes Yes • GRAPH Yes Yes
Functionality • HiGraph Yes Yes

5 • DP master
• DP slave
Yes; Default setting Yes
No No
User program
protection/password
protection
Yes Yes

• Point-to-point coupling No No Dimensions


DP master Required slots 2 2
• Number of connections, 16 32 Dimensions
max.
Dimensions
• Number of connections 1 for PG, 1 for OP 1 for PG, 1 for OP
(of which reserved), max. • Width 50 mm 50 mm
• Services • Height 290 mm 290 mm
- PG/OP communication Yes Yes • Depth 219 mm 219 mm
- S7 basic communication No No Weights
- S7 communication No No
- S7 communication, as No No • Weight, approx. 1 070 g 1 070 g
client
- S7 communication, as No No
server
- equidistance support No No
- Activation/deactivation of No No
DP slaves
- direct data exchange No No
(cross traffic)
• Transmission speeds, 12 MBit/s 12 MBit/s
max.
• Number of DP slaves, max. 96 125; Number of
slots, max. 2048
• Address area
- Inputs, max. 8 Kibyte 8 Kibyte
- Outputs, max. 8 Kibyte 8 Kibyte
• Useful data per DP slave
- Inputs, max. 244 byte 244 byte
- Outputs, max. 244 byte 244 byte

■ Ordering data Order No. Order No.


SIPLUS CPU 414-4H 6AG1 414-4HJ04-4AB0 SIPLUS CPU 417-4H 6AG1 417-4HL04-4AB0
(medium exposure) (medium exposure)
For S7-400H and S7-400F/FH; For S7-400H and S7-400F/FH;
main memory 1.4 MB, main memory 20 MB,
MPI/PROFIBUS DP master MPI/PROFIBUS DP master
interface, 2 slots for synchroni- interface, 2 slots for synchroni-
zation modules, slot for memory zation modules, slot for memory
card, incl. slot number plates card, incl. slot number plates
Accessories see CPU 41xH, page 5/46

5/62 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Digital modules
SM 421 digital input modules

■ Overview
• Digital inputs for the SIMATIC S7-400
• For connecting standard switches and two-wire proximity
switches (BERO)

5
■ Technical specifications
6ES7 421-7BH01- 6ES7 421-1BL01- 6ES7 421-1EL00- 6ES7 421-1FH20- 6ES7 421-7DH00-
0AB0 0AA0 0AA0 0AA0 0AB0
Supply voltages
Load voltage L+
• Rated value (DC) 24 V
• permissible range, 20.4 V
lower limit (DC)
• permissible range, 28.8 V
upper limit (DC)
Current consumption
from backplane bus DC 5 V, 130 mA 20 mA 200 mA 80 mA 150 mA
max.
from supply voltage L+, max. 120 mA
Current consumption/
power loss
Power loss, max. 5W 6W 16 W 12 W 8 W; 3.5 W (24 V DC);
6.5 W (48 V DC);
8.0 W (60 V DC)
Digital inputs
Number of digital inputs 16 32 32 16 16
Number of simultanneously
controllable inputs
- Number of simultaneously 16 32 32 16 16
controllable inputs,
up to 40 °C
- Number of simultaneously 16 32 32 16 16
controllable inputs,
up to 60 °C
Input voltage
• Rated value, DC 24 V 24 V
• Rated value, UC 120 V 230 V; 120/230 V UC 24 V; 24 to 60 V UC
• for signal "0" -30 to +5 V DC -30 to +5 V DC 0 to 20 V UC 0 to 40 V AC/ -6 to +6 V DC/
-40 to +40 V DC 0 to 5 V AC
• for signal "1" 11 to 30 V DC 13 to 30 V DC 79 to 132 V AC; 74 to 264 V AC; 15 to 72 V DC;
80 to 132 V DC 80 to 264 V DC, -15 to -72 V DC;
-80 to -264 V 15 to 60 V AC
• Frequency range 47 to 63 Hz 47 to 63 Hz 47 to 63 Hz AC / DC

Siemens ST 70 · 2009 5/63


© Siemens AG 2008

SIMATIC S7-400
Digital modules
SM 421 digital input modules

■ Technical specifications (continued)


6ES7 421-7BH01- 6ES7 421-1BL01- 6ES7 421-1EL00- 6ES7 421-1FH20- 6ES7 421-7DH00-
0AB0 0AA0 0AA0 0AA0 0AB0
Input current
• for signal "0", max. 1.3 mA 1 mA 6 mA;
(permissible quiescent current) AC: 6 mA; DC: 2 mA
• for signal "1", typ. 6 mA; 6 to 8 mA 7 mA 2 mA; 2 to 5 mA 10 mA; 4 mA; 4 to 10 mA
at 120 V: 10 mA AC,
1.8 mA DC;
at 230 V: 14 mA AC, 2
mA DC
Input delay (for rated value of
input voltage)
• for standard inputs
- programmable Yes Yes
- Rated value 0.5 ms; 0.5 / 3 / 10 /

5 Cable length
20 ms

• cable length, shielded, max. 1 000 m; 1 000 m 1 000 m 1 000 m 1 000 m


1000 m/3 ms;
70 m/0.5 ms;
30 m/0.1 ms;
30 m/0.05 ms
• Cable length unshielded, max. 600 m; 600 m 600 m 600 m 600 m;
600 m: 3 ms; 600 m: 3, 10, 20 ms;
50 m: 0.5 ms; 100 m: 0.5 ms
20 m: 0.1 ms;
20 m: 0.05 ms
Encoder
Connectable encoders
• 2-wire BEROS Yes Yes Yes Yes Yes
- permissible quiescent 3 mA 1.5 mA 1 mA 5 mA; 0.5 mA;
current (2-wire BEROS), max. AC: 5 mA 0.5 to 2 mA
Status information/alarms/
diagnostics
Alarms
• Diagnostic alarm Yes; parameterizable Yes; parameterizable
• Process alarm Yes; parameterizable Yes; parameterizable
Diagnoses
• Diagnostics Yes; Yes;
internal/ external fault internal/ external fault
Isolation
Isolation checked with 500 V DC 500 V DC 1500 V AC 1500 V AC 1500 V AC
Isolation
Galvanic isolation, digital inputs
• between the channels, in 8 32 8 4 1
groups of
• between the channels and the Yes Yes Yes Yes Yes
backplane bus
Dimensions
Dimensions
• Width 25 mm 25 mm 25 mm 25 mm 25 mm
• Height 290 mm 290 mm 290 mm 290 mm 290 mm
• Depth 210 mm 210 mm 210 mm 210 mm 210 mm
Weights
• Weight, approx. 600 g 500 g 600 g 650 g 600 g

5/64 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Digital modules
SM 421 digital input modules

■ Ordering data Order No. Order No.


SM 421 digital input modules Labeling sheets for machine
inscription
16 inputs, 24 V DC, with 6ES7 421-7BH01-0AB0
process/diagnostics interrupt DIN A4, for printing using laser
printer; pack of 10
32 inputs, 24 V DC 6ES7 421-1BL01-0AA0
petrol 6ES7 492-2AX00-0AA0
32 inputs, 120 V AC/DC 6ES7 421-1EL00-0AA0
light-beige 6ES7 492-2BX00-0AA0
16 inputs, 120/230 V AC/DC, 6ES7 421-1FH20-0AA0
inputs according to IEC 1131-2 yellow 6ES7 492-2CX00-0AA0
Type 2
red 6ES7 492-2DX00-0AA0
16 inputs, 24 to 60 V AC/DC, with 6ES7 421-7DH00-0AB0
process/diagnostics interrupt SIMATIC Manual Collection B3 6ES7 998-8XC01-8YE0

Front connectors Electronic manuals on DVD, five


languages: S7-200/300/400, C7,
48-pin LOGO!, SIMATIC DP, PC, PG,
STEP 7, engineering software,
• With screw-type contacts, B7 6ES7 492-1AL00-0AA0 runtime software, PCS 7, SIMATIC
1 unit
5
HMI, SIMATIC NET
• With screw-type contacts, B6 6ES7 492-1AL00-1AB0 SIMATIC Manual Collection B3 6ES7 998-8XC01-8YE2
84 units maintenance service for 1 year
• With spring-loaded contacts, 6ES7 492-1BL00-0AA0 Current "Manual Collection" DVD
1 unit and the three subsequent
• With crimp contacts, 1 unit B7 6ES7 492-1CL00-0AA0 updates
• With crimp contacts, 84 units 6ES7 492-1CL00-1AB0 Manual "SIMATIC S7-400
programmable controller"
SIMATIC TOP connect see page 5/131;
Information about which compo- incl. instruction list
nents can be used for the German 6ES7 498-8AA05-8AA0
respective module, see
DT&IAMall or Catalog KT 10.2 English 6ES7 498-8AA05-8BA0
Cover film for labeling strips 6ES7 492-2XX00-0AA0 French 6ES7 498-8AA05-8CA0
Spare part Spanish 6ES7 498-8AA05-8DA0
S7 SmartLabel V3.0 Italian 6ES7 498-8AA05-8EA0
Software for automatic labeling of
modules based on data of the
STEP 7 project
Single license B8 2XV9 450-1SL03-0YX0
Upgrade single license B8 2XV9 450-1SL03-0YX4
B3: Subject to export regulations: AL: N and ECCN: 5D992B1
B6: Subject to export regulations: AL: N and ECCN: EAR99
B7: Subject to export regulations: AL: N and ECCN: EAR99H
B8: Subject to export regulations: AL: N and ECCN: EAR99S

Siemens ST 70 · 2009 5/65


© Siemens AG 2008

SIMATIC S7-400
Digital modules
SM 422 digital output modules

■ Overview
• Digital outputs for the SIMATIC S7-400
• For connecting solenoid valves, contactors, low-power
motors, lamps and motor starters

5
■ Technical specifications
6ES7 422-1FH00- 6ES7 422-1HH00- 6ES7 422-1BH11- 6ES7 422-1BL00- 6ES7 422-7BL00-
0AA0 0AA0 0AA0 0AA0 0AB0
Supply voltages
Load voltage L+
• Rated value (DC) 60 V 24 V 24 V 24 V
• permissible range, lower limit 1V 20.4 V 20.4 V 20.4 V
(DC)
• permissible range, upper limit 60 V 28.8 V 28.8 V 28.8 V
(DC)
Load voltage L1
• Rated value (AC) 230 V; 120/230 V AC 230 V
• permissible range, lower limit 79 V 2V 20.4 V
(AC)
• permissible range, upper limit 264 V 264 V 28.8 V
(AC)
Current consumption
from load voltage L+ 1.5 mA 30 mA 30 mA 120 mA
(without load), max.
from load voltage L1 6 mA
(without load), max.
from backplane bus DC 5 V, 400 mA 1A 160 mA 200 mA 200 mA
max.
Current consumption/
power loss
Power loss, max. 16 W 25 W 7W 4W 8W
Digital outputs
Number of digital outputs 16 16; Relay 16 32 32
Short-circuit protection of the Yes; Fuse 8 A, 250 V; Yes; clocked Yes; clocked Yes; clocked
output per group electronically electronically electronically
Limitation of inductive shutdown -30 V -27 V L+ (-45 V)
voltage to
Lamp load, max. 50 W 60 W 10 W 5W 5W
Output voltage
• for signal "1", min. L1 (-18.1 V) L+ (-0.5 V) L+ (-0.3 V) L+ (-0.8 V)

5/66 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Digital modules
SM 422 digital output modules

■ Technical specifications (continued)


6ES7 422-1FH00- 6ES7 422-1HH00- 6ES7 422-1BH11- 6ES7 422-1BL00- 6ES7 422-7BL00-
0AA0 0AA0 0AA0 0AA0 0AB0
Output current
• for signal "1" rated value 2A 2A 0.5 A 0.5 A
• for signal "1" permissible range 10 mA 5 mA 5 mA 5 mA
for 0 to 60 °C, min.
• for signal "1" permissible range 2.4 A 0.6 A 0.6 A
for 0 to 60 °C, max.
• for signal "0" residual current, 2.6 mA 0.5 mA 0.3 mA 0.5 mA
max.
Switching frequency
• with resistive load, max. 10 Hz 10 Hz 100 Hz 100 Hz 100 Hz
• with inductive load, max. 0.5 Hz 0.1 Hz 0.5 Hz 2 Hz

5
Aggregate current of the outputs
(per group)
• up to 60 °C, max. 2 A; 5 A with fan 5 mA; 10 A with fan 2 A; 2 adjacent 2 A; 8 adjacent 2A
subassembly; per subassembly outputs each outputs each
4 adjacent outputs
• cable length, shielded, max. 1 000 m 1 000 m 1 000 m 1 000 m 1 000 m
• Cable length unshielded, max. 600 m 600 m 600 m 600 m 600 m
Relay outputs
Number of operating cycles 100 000; 100,000
(AC 15 / DC 13);
3,000,000
mechanical
Switching capacity of the
contacts
• with inductive load, max. 5 A; 5 A (30 V DC);
5 A (230 V AC)
• with resistive load, max. 5 A; 5 A (30 V DC);
5 A (230 V AC);
1.2 A (60 V DC);
0.2 A (125 V DC)
Status information/alarms/
diagnostics
Alarms
• Diagnostic alarm Yes; Parameterizable
Diagnoses
• Diagnostics Yes;
internal/ external fault
Isolation
Isolation checked with 1500 V AC 1500 V AC 500 V DC 500 V DC 500 V DC
Isolation
Isolation, digital outputs
• between the channels, in 4 2 8 32 8
groups of
• between the channels and the Yes Yes Yes Yes Yes
backplane bus
Dimensions
Dimensions
• Width 25 mm 25 mm 25 mm 25 mm 25 mm
• Height 290 mm 290 mm 290 mm 290 mm 290 mm
• Depth 210 mm 210 mm 210 mm 210 mm 210 mm
Weights
• Weight, approx. 800 g 700 g 600 g 600 g 600 g

Siemens ST 70 · 2009 5/67


© Siemens AG 2008

SIMATIC S7-400
Digital modules
SM 422 digital output modules

■ Ordering data Order No. Order No.


SM 422 Digital Output Modules Labeling sheets for machine
inscription
16 outputs, 24 V DC; 2 A 6ES7 422-1BH11-0AA0
DIN A4, for printing using laser
32 outputs, 24 V DC; 0.5 A 6ES7 422-1BL00-0AA0 printer; pack of 10
32 outputs, 24 V DC, 0.5 A; 6ES7 422-7BL00-0AB0 petrol 6ES7 492-2AX00-0AA0
with diagnostics
light-beige 6ES7 492-2BX00-0AA0
16 outputs, 120/230 V AC; 2 A 6ES7 422-1FH00-0AA0
yellow 6ES7 492-2CX00-0AA0
16 outputs, relay contacts 6ES7 422-1HH00-0AA0
red 6ES7 492-2DX00-0AA0
Front connectors
SIMATIC Manual Collection B3 6ES7 998-8XC01-8YE0
48-pin
Electronic manuals on DVD, five
• with screw contacts, 1 item B7 6ES7 492-1AL00-0AA0 languages: S7-200/300/400, C7,
• with screw contacts, 84 items B6 6ES7 492-1AL00-1AB0 LOGO!, SIMATIC DP, PC, PG,
STEP 7, engineering software,
• with spring-loaded terminals, 6ES7 492-1BL00-0AA0 runtime software, PCS 7, SIMATIC
1 item
5
HMI, SIMATIC NET
• with crimp contacts, 1 item B7 6ES7 492-1CL00-0AA0 SIMATIC Manual Collection B3 6ES7 998-8XC01-8YE2
• with crimp contacts, 84 items 6ES7 492-1CL00-1AB0 maintenance service for 1 year

SIMATIC TOP connect see page 5/131; Current "Manual Collection" DVD
Information about which compo- and the three subsequent
nents can be used for the updates
respective module, see Manual "SIMATIC S7-400
DT&IAMall or Catalog KT 10.2 programmable controller"
Cover film for labeling strips 6ES7 492-2XX00-0AA0 incl. instruction list
Spare part German 6ES7 498-8AA05-8AA0
S7 SmartLabel V3.0 English 6ES7 498-8AA05-8BA0
Software for automatic labeling of French 6ES7 498-8AA05-8CA0
modules direct from the STEP 7
project Spanish 6ES7 498-8AA05-8DA0
Single license B8 2XV9 450-1SL03-0YX0 Italian 6ES7 498-8AA05-8EA0
Upgrade single license B8 2XV9 450-1SL03-0YX4
B3: Subject to export regulations: AL: N and ECCN: 5D992B1
B6: Subject to export regulations: AL: N and ECCN: EAR99
B7: Subject to export regulations: AL: N and ECCN: EAR99H
B8: Subject to export regulations: AL: N and ECCN: EAR99S

5/68 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
SIPLUS digital modules
SIPLUS SM 421 digital input modules
SIPLUS SM 422 digital output modules

■ Overview SIPLUS SM 421 ■ Overview SIPLUS SM 422

5
• Digital inputs for SIMATIC S7-400 • Digital outputs for SIMATIC S7-400
• For connection of switches and 2-wire proximity switches • For connecting solenoid valves, contactors, small-power
(BEROs) motors, lamps and motor starters

Digital input module SIPLUS SM 421 Digital input module SIPLUS SM 422
Order No. 6AG1 421-1BL01-2AA0 Order No. 6AG1 422-1BL00-2AA0
Order No. based on 6ES7 421-1BL01-0AA0 Order No. based on 6ES7 422-1BL00-0AA0
Ambient temperature range -25 ... +60 °C Ambient temperature range -25 ... +60 °C
Environmental conditions Suited for exceptional medial Environmental conditions Suited for exceptional medial
exposure (e. g. by chlorine sulfur exposure (e. g. by chlorine sulfur
atmosphere). atmosphere).
Technical data The technical data are identical Technical data The technical data are identical
with those of the based-on with those of the based-on
modules. modules.

For further technical documentation on SIPLUS, see: For further technical documentation on SIPLUS, see:
http://www.siemens.com/siplus-techdoku http://www.siemens.com/siplus-techdoku

■ Ordering data Order No. ■ Ordering data Order No.


SIPLUS SM 421 SIPLUS SM 422
digital input module digital output module
(extended temperature range and (extended temperature range and
medium exposure) medium exposure)
32 inputs, 24 V DC 6AG1 421-1BL01-2AA0 32 outputs, 24 V DC; 0.5 A 6AG1 422-1BL00-2AA0
Accessories see S7-400 digital input modules Accessories see S7-400 digital output
SM 421, page 5/65 modules SM 422, page 5/68

Siemens ST 70 · 2009 5/69


© Siemens AG 2008

SIMATIC S7-400
Analog modules
SM 431 analog input modules

■ Overview
• Analog inputs for the SIMATIC S7-400
• For connection of voltage and current sensors,
thermocouples, resistors and resistance thermometers
• Resolution from 13 to 16 bit

5
■ Technical specifications
6ES7 431-0HH00-0AB0 6ES7 431-1KF20-0AB0 6ES7 431-1KF00-0AB0 6ES7 431-1KF10-0AB0
Supply voltages
Load voltage L+
• Rated value (DC) 24 V; only required for 24 V; only required for not necessary 24 V; only required for
supplying 2-wire trans- supplying 2-wire trans- supplying 2-wire trans-
mitters mitters mitters
• reverse polarity protection Yes Yes Yes
Current consumption
from load voltage L+ 400 mA; for 16 connected, 200 mA; for 8 connected, 200 mA
(without load), max. fully controlled 2-wire trans- fully controlled 2-wire trans-
mitters mitters
from backplane bus DC 5 V, 100 mA 1 000 mA 350 mA 600 mA
max.
Current consumption/
power loss
Power loss, typ. 2W 4.9 W 1.8 W 3.5 W
Analog inputs
Number of analog inputs 16 8 8 8
Number of analog inputs for 16 8 8 8
voltage/current measurement
Number of analog inputs for 4 4 4
resistance measurement
cable length, shielded, max. 200 m 200 m 200 m 200 m; 50 m with thermo-
couples and input ranges
<= 80 mV
Input ranges (rated values),
voltages
• 1 to 5 V Yes Yes Yes Yes
• -1 V to +1 V Yes Yes Yes Yes
• -10 V to +10 V Yes Yes Yes Yes
• -2.5 V to +2.5 V Yes
• -250 mV to +250 mV Yes
• -5 V to +5 V Yes
• -500 mV to +500 mV Yes
• -80 mV to +80 mV Yes

5/70 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Analog modules
SM 431 analog input modules

■ Technical specifications (continued)


6ES7 431-0HH00-0AB0 6ES7 431-1KF20-0AB0 6ES7 431-1KF00-0AB0 6ES7 431-1KF10-0AB0
Input ranges (rated values),
currents
• 0 to 20 mA Yes
• -20 to +20 mA Yes Yes Yes
• 4 to 20 mA Yes Yes Yes Yes
Input ranges (rated values),
thermoelements
• Type B Yes
• Type E Yes
• Type J Yes
• Type K Yes
• Type L Yes
• Type N Yes 5
• Type R Yes
• Type S Yes
• Type T Yes
• Type U Yes
Input ranges (rated values),
resistance thermometers
• Ni 100 Yes
• Ni 1000 Yes
• Pt 100 Yes
• Pt 1000 Yes
• Pt 10000 Yes
• Pt 200 Yes
• Pt 500 Yes
Input ranges (rated values),
resistors
• 0 to 150 Ohm Yes
• 0 to 300 Ohm Yes
• 0 to 48 Ohm Yes
• 0 to 600 Ohm Yes Yes Yes
• 0 to 6000 Ohm Yes; usable up to
5000 ohms
• permissible input frequency 20 V; 20 V continuous, 18 V; 18 V continuous, 50 V 18 V; 18 V continuous,
for voltage input (destruction 75 V for max. 1 s 75 V for 1 ms 75 V for 1 ms
limit), max. (mark to space ratio 1:20) (mark to space ratio 1:20) (mark to space ratio 1:20)
• permissible input current for 40 mA 40 mA; Permanent 50 mA; 40 mA continuous 40 mA; Permanent
current input (destruction limit),
max.
Characteristic curve linearization
• programmable Yes
- for thermoelements Type B, E, J, K, L, N, R, S,
T, U
- for thermoresistor Pt100, Pt200, Pt500,
Pt1000, Ni100, Ni1000
Temperature compensation
• internal temperature compen- Yes
sation
• external temperature compen- Yes
sation with compensations
socket
• external temperature compen- No
sation with Pt100
• dynamic reference temper- Yes
ature value

Siemens ST 70 · 2009 5/71


© Siemens AG 2008

SIMATIC S7-400
Analog modules
SM 431 analog input modules

■ Technical specifications (continued)


6ES7 431-0HH00-0AB0 6ES7 431-1KF20-0AB0 6ES7 431-1KF00-0AB0 6ES7 431-1KF10-0AB0
Analog value creation
Integration and conversion
time/resolution per channel
• Resolution with overload area 13 Bit 14 Bit; 14 / 14 / 14 13 Bit 14 Bit; with activated
(bit including sign), max. smoothing: 16 Bit
• Integration time, Yes Yes Yes Yes
parameterizable
• Basic conversion time, ms 50 / 60 ms 16.7 / 20 ms 16.7 / 20 ms
• Integration time, ms 55 / 65 ms 52 μs 23 / 25 ms 20.1 / 23.5 ms
• additional conversion time for 4.3 ms
wire break monitoring
• additional conversiontime for 5.5 ms
resistance measurement
5 • additional conversiontime for
wire break monitoring and
40.2 / 47 ms

resistance measurement
• Interference voltage 60 / 50 Hz none / 400 / 60 / 50 Hz 60 / 50 Hz 60 / 50 Hz
suppression for interference
frequency f1 in Hz
Encoder
Connection of signal encoders
• for current measurement as Yes Yes; with external trans- Yes
2-wire transducer mitter supply
• for current measurement as Yes Yes Yes Yes
4-wire transducer
• for resistance measurement Yes; Line resistances are Yes; Line resistances are Yes; Line resistances are
with 2-conductor connection also measured also measured also measured
• for resistance measurement Yes; Line resistances are Yes; Line resistances are Yes
with 3-conductor connection also measured also measured
• for resistance measurement Yes Yes Yes
with 4-conductor connection
Errors/accuracies
Operational limit in overall
temperature range
• Voltage, relative to input area +/- 0,65 %; +/- 0,7 %; +/- 1 %; +/- 0,38 %;
1.0% at 1 to 5 V; +/-0.7% at +/-1 V; +/-1.0% at +/-1 V; +/-0.38% at +/-80 mV;
0.65% at +/-1 V, +/-10 V +/-0.9% at +/-10 V, 1 to 5 V +/-0.6% at +/-10 V; +/-0.35% at +/-250 mV,
+/-0.7% at 1 to 5 V +/-500mV, +/-1 V, +/-2,5 V,
+/-5 V, 1 to 5 V, +/-10 V
• Current, relative to input area +/- 0.65 % +/- 0,8 %; +/- 1 %; +/- 0,35 %;
at +/-20 mA, 4 to 20 mA at +/-20 mA, 4 to 20 mA 0 to 20 mA, +/-20 mA,
4 to 20 mA
• Impedance, relative to input +/- 1 % +/- 1,25 %; 0 to 500 ohms +/- 0.5 %
area (4-conductor measurement,
in range of 600 ohms)
• Resistance-type thermometer, +/- 0.5 %
relative to input area
Basic error limit
(operational limit at 25 °C)
• Voltage, relative to input area +/- 0,25 %; +/- 0,6 %; +/- 0,7 %; +/- 0,15 %;
0.5% at 1 to 5 V; 0.6% at +/-1 V; 0.7% at +/-1 V; +/-0.15% (+/-250 mV,
0.25% at +/-1 V, +/-10 V 0.75% at +/-10 V, 1 to 5 V 0.4% at +/-10 V; +/-500 mV, +/-1 V, +/-2.5 V,
0.5% at 1 to 5 V +/-5 V, 1 to 5 V, +/- 10 V);
+/-0.17% (+/- 80 mV);
• Current, relative to input area +/- 0,25 %; +/- 0,7 %; +/- 0,7 %; +/- 0,15 %;
at +/-20 mA, 4 to 20 mA at +/- 20 mA, 4...20 mA at +/- 20 mA, 4...20 mA 0 to 20 mA, +/- 20 mA,
4 to 20 mA

5/72 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Analog modules
SM 431 analog input modules

■ Technical specifications (continued)


6ES7 431-0HH00-0AB0 6ES7 431-1KF20-0AB0 6ES7 431-1KF00-0AB0 6ES7 431-1KF10-0AB0
Basic error limit (operational limit
at 25 °C)
• Impedance, relative to input +/- 0,7 %; 0 to 600 ohms +/- 0,8 %; +/- 0,15 %;
area 0 to 500 ohms +/-0.15% at 0 to 48 ohms
(4-conductor measurement, (4-conductor
in range of 600 ohms) measurement),
0 to 150 ohms
(4-conductor
measurement),
0 to 300 ohms
(4-conductor
measurement),
0 to 600 ohms
(4-conductor
measurement),
0 to 5000 ohms

5
(4-conductor
measurement, in range of
6000 ohms);
+/-0.3% at 0 to 300 ohms
(3-conductor
measurement),
0 to 600 ohms
(3-conductor
measurement),
0 to 5000 ohms
(3-conductor
measurement, in range of
6000 ohms)
• Resistance-type thermometer, +/- 0.3 %
relative to input area
Isolation
Isolation checked with 500 V DC between bus and 2120 V DC between bus 2120 V DC between bus 2120 V DC between bus
local ground and analog part; and analog part; and L+/M;
500 V DC between bus and 500 V DC between bus and 2120 V D between bus and
local ground; local ground; analog part;
707 V DC between analog 2120 V DC between analog 500 V DC between bus and
part and L+/M; part and local ground local ground;
2120 V DC between analog 707 V DC between analog
part and local ground; part and L+/M;
2120 V DC between L+/M 2120 V DC between analog
and local ground part and local ground;
2120 V DC between L+/M
and local ground
Isolation
Isolation, analog inputs
• Isolation, analog inputs No Yes; internal/external Yes; internal/external Yes; internal/external
• between the channels No No No No
Permissible potential
difference
between the inputs (UCM) 2 V DC / 2 Vpp AC 8 V AC 30 V AC 120 V AC
Dimensions
Required slots 1 1 1 1
Dimensions
Dimensions
• Width 25 mm 25 mm 25 mm 25 mm
• Height 290 mm 290 mm 290 mm 290 mm
• Depth 210 mm 210 mm 210 mm 210 mm
Weights
• Weight, approx. 500 g 500 g 500 g 500 g

Siemens ST 70 · 2009 5/73


© Siemens AG 2008

SIMATIC S7-400
Analog modules
SM 431 analog input modules

■ Technical specifications (continued)


6ES7 431-7QH00-0AB0 6ES7 431-7KF00-0AB0 6ES7 431-7KF10-0AB0
Supply voltages
Load voltage L+
• Rated value (DC) 24 V; only required for supplying
2-wire transmitters
• reverse polarity protection Yes
Current consumption
from load voltage L+ (without 400 mA 400 mA 400 mA
load), max.
from backplane bus DC 5 V, 700 mA 1 200 mA 650 mA
max.
Current consumption/
power loss

5
Power loss, typ. 4.5 W 4.6 W 3.3 W
Analog inputs
Number of analog inputs 16 8 8
Number of analog inputs for 16 8
voltage/current measurement
Number of analog inputs for 8 8
resistance measurement
cable length, shielded, max. 200 m; 50 m with thermocouples and 200 m 200 m; 50 m with thermocouples and
input ranges <= 80 mV input ranges +/-80 mV
Input ranges (rated values),
voltages
• 1 to 5 V Yes Yes
• -1 V to +1 V Yes Yes
• -10 V to +10 V Yes Yes
• -100 mV to +100 mV Yes
• -2.5 V to +2.5 V Yes Yes
• -20 mV to +20 mV Yes
• -25 mV to +25 mV Yes
• -250 mV to +250 mV Yes Yes
• -5 V to +5 V Yes Yes
• -50 mV to +50 mV Yes Yes
• -500 mV to +500 mV Yes Yes
• -80 mV to +80 mV Yes Yes
Input ranges (rated values),
currents
• 0 to 20 mA Yes Yes
• -10 to +10 mA Yes Yes
• -20 to +20 mA Yes Yes
• -3.2 to +3.2 mA Yes
• 4 to 20 mA Yes Yes
• -5 to +5 mA Yes Yes
Input ranges (rated values),
thermoelements
• Type B Yes Yes
• Type E Yes Yes
• Type J Yes Yes
• Type K Yes Yes
• Type L Yes Yes
• Type N Yes Yes
• Type R Yes Yes
• Type S Yes Yes
• Type T Yes Yes
• Type U Yes Yes

5/74 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Analog modules
SM 431 analog input modules

■ Technical specifications (continued)


6ES7 431-7QH00-0AB0 6ES7 431-7KF00-0AB0 6ES7 431-7KF10-0AB0
Input ranges (rated values),
resistance thermometers
• Ni 100 Yes Yes
• Ni 1000 Yes Yes; Different characteristics
selectable: Europe/U.S
• Pt 100 Yes Yes
• Pt 1000 Yes Yes
• Pt 200 Yes Yes
• Pt 500 Yes Yes
Input ranges (rated values),
resistors
• 0 to 150 Ohm Yes
• 0 to 300 Ohm
• 0 to 48 Ohm
Yes
Yes
5
• 0 to 600 Ohm Yes
• 0 to 6000 Ohm Yes; usable up to 5000 ohms
• permissible input frequency for 18 V; 18 V continuous, 35 V; 35 V continuous, 35 V; 35 V continuous,
voltage input (destruction 75 V for 1 ms 75 V for max. 1 s 75 V for max. 1 s
limit), max. (mark to space ratio 1:20) (mark to space ratio 1:20) (mark to space ratio 1:20)
• permissible input current for 40 mA 32 mA
current input (destruction limit),
max.
Characteristic curve linearization
• programmable Yes Yes Yes
- for thermoelements Type B, E, J, K, L, N, R, S, T, U Type B, E, J, K, L, N, R, S, T, U
- for thermoresistor Pt100, Pt200, Pt500, Pt1000, Ni100, Pt100, Pt200, Pt500, Pt1000, Ni100,
Ni1000 Ni1000; different characteristics
selectable (Europe/U.S.)
Temperature compensation
• internal temperature compen- Yes Yes
sation
• external temperature compen- Yes
sation with compensations
socket
• external temperature compen- Yes
sation with Pt100
• dynamic reference temper- Yes Yes
ature value
Analog value creation
Integration and conversion
time/resolution per channel
• Resolution with overload area 16 Bit; 16 / 16 / 16 16 Bit 16 Bit
(bit including sign), max.
• Integration time, parameter- Yes Yes Yes
izable
• Basic conversion time, ms 2.5 / 16.7 / 20 ms 2.5 / 16.7 / 20 / 100 8 / 23 / 25 ms

Siemens ST 70 · 2009 5/75


© Siemens AG 2008

SIMATIC S7-400
Analog modules
SM 431 analog input modules

■ Technical specifications (continued)


6ES7 431-7QH00-0AB0 6ES7 431-7KF00-0AB0 6ES7 431-7KF10-0AB0
Analog value creation (cont.)
• Integration time, ms 2.5 / 16.7 / 20 ms 2.5 / 16.7 / 20 / 100 ms 20 ms at 50 Hz (entire module incl.
wire break)
• additional conversion time for 4.3 / 4.3 / 4.3 ms 110 ms / 4 ms
wire break monitoring
• additional conversion time for 12 / 40.2 / 47 ms
resistance measurement
• additional conversiontime for 5.5 ms 1 ms (module) none
wire break monitoring and
resistance measurement
• Interference voltage 400 / 60 / 50 Hz 400 / 60 / 50 / 10 Hz none/ 60 / 50 Hz
suppression for interference
frequency f1 in Hz

5
Encoder
Connection of signal encoders
• for current measurement as Yes
2-wire transducer
• for current measurement as Yes Yes
4-wire transducer
• for resistance measurement Yes; Line resistances are also
with 2-conductor connection measured
• for resistance measurement Yes Yes
with 3-conductor connection
• for resistance measurement Yes Yes Yes
with 4-conductor connection
Errors/accuracies
Operational limit in overall
temperature range
• Voltage, relative to input area +/- 0,3 %; +/-0.3% at +/-250 mV, +/- 0.3 %
+/-500 mV, +/-1 V, +/-2.5 V, +/-5 V,
1 to 5 V, +/- 10 V;
+/-0.31% at +/-80 mV;
+/-0.32% at +/-50 mV;
+/-0.35% at +/-25 mV;
• Current, relative to input area +/- 0,3 %; at 0 to 20 mA, +/-5 mA, +/- 0.5 %
+/-10 mA, +/- 20 mA, 4 to 20 mA
• Impedance, relative to input +/- 0,3 %; +/-0.3% at 0 to 48 ohms
area (4-conductor measurement),
0 to 150 ohms (4-conductor
measurement),
0 to 300 ohms (4-conductor
measurement),
0 to 600 ohms (4-conductor
measurement),
0 to 5000 ohms (4-conductor
measurement, in range of
6000 ohms);
+/-0.4% at 0 to300 ohms (3-
conductor measurement),
0 to 600 ohms (3-conductor
measurement),
0 to 5000 ohms (3-conductor
measurement, in range of
6000 ohms);
• Resistance-type thermometer, +/- 0.4 % +/-1 °C
relative to input area
Basic error limit (operational limit
at 25 °C)
• Voltage, relative to input area +/- 0,15 %; +/-0.15% at +/-250 mV, +/- 0.1 %
+/-500 mV, +/-1 V, +/-2.5 V, +/-5 V,
1 to 5 V, +/-10 V;
+/-0.17% at +/-80 mV;
+/-0.19% at +/-50 mV;
+/-0.23% at +/-25 mV;
• Current, relative to input area +/- 0,15 %; at 0 to 20 mA, +/-5 mA, +/- 0.17 %
+/-10 mA, +/- 20 mA, 4 to 20 mA

5/76 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Analog modules
SM 431 analog input modules

■ Technical specifications (continued)


6ES7 431-7QH00-0AB0 6ES7 431-7KF00-0AB0 6ES7 431-7KF10-0AB0
Basic error limit (operational limit
at 25 °C)
• Impedance, relative to input +/- 0,15 %; +/-0.15% at 0 to 48 ohms
area (4-conductor measurement),
0 to 150 ohms (4-conductor
measurement),
0 to 300 ohms (4-conductor
measurement),
0 to 5000 ohms (4-conductor
measurement, in range of
6000 ohms);
+/-0.3% at 0 to 300 ohms
(3-conductor measurement),
0 to 600 ohms (3-conductor
measurement),
0 to 5000 ohms (3-conductor

5
measurement, in range of
6000 ohms)
• Resistance-type thermometer, +/- 0.3 % +/-0.2 °C
relative to input area
Status information/alarms/
diagnostics
Alarms
• Diagnostic alarm Yes; Parameterizable Yes; Parameterizable Yes; Parameterizable
• Limit value alarm Yes; Parameterizable Yes Yes
Diagnoses
• Diagnostics Yes; Parameterizable Yes Yes
Isolation
Isolation checked with 2120 V DC between bus and L+/M; 1500 V DC 1500 V DC
2120 V D between bus and analog
part;
500 V DC between bus and local
ground;
707 V DC between analog part and
L+/M;
2120 V DC between analog part and
local ground;
2120 V DC between L+/M and local
ground
Isolation
Isolation, analog inputs
• Isolation, analog inputs Yes; internal/external Yes; internal/external Yes; internal/external
• between the channels No Yes No
Permissible potential
difference
between the inputs (UCM) 120 V AC 120 V AC none
Dimensions
Required slots 1 1 1
Dimensions
Dimensions
• Width 25 mm 25 mm 25 mm
• Height 290 mm 290 mm 290 mm
• Depth 210 mm 210 mm 210 mm
Weights
• Weight, approx. 500 g 650 g 650 g

Siemens ST 70 · 2009 5/77


© Siemens AG 2008

SIMATIC S7-400
Analog modules
SM 431 analog input modules

■ Ordering data Order No. Order No.


SM 431 analog output module S7 SmartLabel V3.0
16 inputs, non-floating, 13 bit 6ES7 431-0HH00-0AB0 Software for automatic labeling of
modules direct from the STEP 7
8 inputs, floating, 13 bit 6ES7 431-1KF00-0AB0 project
8 inputs, floating, 14 bit, with 6ES7 431-1KF10-0AB0 Single license B8 2XV9 450-1SL03-0YX0
linearization
Upgrade single license B8 2XV9 450-1SL03-0YX4
8 inputs, floating, 14 bit 6ES7 431-1KF20-0AB0
Labeling sheets for machine
16 inputs, floating, 16 bit, process 6ES7 431-7QH00-0AB0 inscription
interrupt capability
DIN A4, for printing using laser
8 inputs, floating, 16 bit, process 6ES7 431-7KF00-0AB0 printer; pack of 10
interrupt capability, for thermo-
couples (I, U) petrol 6ES7 492-2AX00-0AA0
8 inputs, floating, 16 bit, process 6ES7 431-7KF10-0AB0 light-beige 6ES7 492-2BX00-0AA0
interrupt capability, for temper-
ature sensors yellow 6ES7 492-2CX00-0AA0

5 Front connectors red 6ES7 492-2DX00-0AA0

48-pin SIMATIC Manual Collection B3 6ES7 998-8XC01-8YE0

• with screw contacts, 1 item B7 6ES7 492-1AL00-0AA0 Electronic manuals on DVD, five
languages: S7-200/300/400, C7,
• with screw contacts, 84 items B6 6ES7 492-1AL00-1AB0 LOGO!, SIMATIC DP, PC, PG,
STEP 7, engineering software,
• with spring-loaded terminals, 6ES7 492-1BL00-0AA0 runtime software, PCS 7, SIMATIC
1 item HMI, SIMATIC NET
• with crimp contacts, 1 item B7 6ES7 492-1CL00-0AA0 SIMATIC Manual Collection B3 6ES7 998-8XC01-8YE2
• with crimp contacts, 84 items 6ES7 492-1CL00-1AB0 maintenance service for 1 year
1 unit; for 6ES7 431-7KF00-0AB0; 6ES7431-7KF00-6AA0 Current "Manual Collection" DVD
spare part, included in scope of and the three subsequent
delivery updates
SIMATIC TOP connect see page 5/131; Manual "SIMATIC S7-400
Information about which compo- programmable controller"
nents can be used for the incl. instruction list
respective module, see
DT&IAMall or Catalog KT 10.2 German 6ES7 498-8AA05-8AA0
Measuring range module for 6ES7 974-0AA00-0AA0 English 6ES7 498-8AA05-8BA0
analog inputs
French 6ES7 498-8AA05-8CA0
1 module for 2 inputs (spare part)
Spanish 6ES7 498-8AA05-8DA0
Cover film for labeling strips 6ES7 492-2XX00-0AA0
Italian 6ES7 498-8AA05-8EA0
Spare part

B3: Subject to export regulations: AL: N and ECCN: 5D992B1


B6: Subject to export regulations: AL: N and ECCN: EAR99
B7: Subject to export regulations: AL: N and ECCN: EAR99H
B8: Subject to export regulations: AL: N and ECCN: EAR99S

5/78 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Analog modules
SM 432 analog output modules

■ Overview
• Analog outputs for the SIMATIC S7-400
• For the connection of analog actuators

5
■ Technical specifications
6ES7 432-1HF00-0AB0 6ES7 432-1HF00-0AB0
Supply voltages Analog value creation
Load voltage L+ Integration and conversion
time/resolution per channel
• Rated value (DC) 24 V
• Resolution with overload area 13 Bit
Current consumption (bit including sign), max.
from backplane bus DC 5 V, 150 mA • Conversion time (per channel) 420 μs; 420 μs in the ranges 1 to 5 V
max. and 4 to 20 mA; 300 μs in all ranges
from supply voltage L+, max. 400 mA Settling time
Current consumption/ • for resistive load 0.1 ms
power loss
• for capacitive load 3.5 ms
Power loss, max. 9W
• for inductive load 0.5 ms
Analog outputs
Errors/accuracies
Number of analg outputs 8
Operational limit in overall
cable length, shielded, max. 200 m temperature range
Voltage output, Short-circuit Yes • Voltage, relative to output area +/- 0,5 %; +/-10 V, 0 to 10 V, 1 to 5 V
protection
• Current, relative to output area +/- 1 %; +/-20 mA, 4 to 20 mV
Voltage output, short-circuit 30 mA
current, max.. Basic error limit (operational limit
at 25 °C)
Current output, no-load voltage, 19 V
max. • Voltage, relative to output area +/- 0,5 %; +/- 10 V, 0 to 10 V, 1 to 5 V
Output ranges, voltage • Current, relative to output area +/- 0,5 %; +/-20 mA, 0 to 20 mA
• 0 to 10 V Yes Status information/alarms/
diagnostics
• 1 to 5 V Yes
Substitute values connectable No
• -10 to +10 V Yes
Isolation
Output ranges, current
Isolation checked with 2120 V DC between bus and L+/M;
• 0 to 20 mA Yes 2120 V D between bus and analog
• -20 to +20 mA Yes part;
500 V DC between bus and local
• 4 to 20 mA Yes ground;
Load impedance 707 V DC between analog part and
(in rated range of output) L+/M;
2120 V DC between analog part and
• with voltage outputs, min. 1 kΩ local ground;
2120 V DC between L+/M and local
• with voltage outputs, 1 μF
ground
capacitive load, max.
• with current outputs, max. 500 Ω; 600 ohms if common-mode-
voltage reduced to <1 V

Siemens ST 70 · 2009 5/79


© Siemens AG 2008

SIMATIC S7-400
Analog modules
SM 432 analog output modules

■ Technical specifications (continued) ■ Ordering data Order No.


6ES7 432-1HF00-0AB0 SM 432 analog output module 6ES7 432-1HF00-0AB0
Isolation 8 outputs, floating, 13 bit
Isolation, analog outputs Front connectors
• between the channels and the Yes 48-pin
backplane bus
• with screw contacts, 1 item B7 6ES7 492-1AL00-0AA0
Dimensions
• with screw contacts, 84 items B6 6ES7 492-1AL00-1AB0
Required slots 1
• with spring-loaded terminals, 6ES7 492-1BL00-0AA0
Dimensions 1 item
Dimensions • with crimp contacts, 1 item B7 6ES7 492-1CL00-0AA0
• Width 25 mm • with crimp contacts, 84 items 6ES7 492-1CL00-1AB0
• Height 290 mm SIMATIC TOP connect see page 5/131;
Information about which compo-
• Depth 210 mm nents can be used for the

5 Weights respective module, see A&D


Mall or Catalog KT 10.2
• Weight, approx. 650 g
Cover film for labeling strips 6ES7 492-2XX00-0AA0
Spare part
S7 SmartLabel V3.0
Software for automatic labeling of
modules direct from the STEP 7
project
Single license B8 2XV9 450-1SL03-0YX0
Upgrade single license B8 2XV9 450-1SL03-0YX4
Labeling sheets for machine
inscription
DIN A4, for printing using laser
printer; pack of 10
petrol 6ES7 492-2AX00-0AA0
light-beige 6ES7 492-2BX00-0AA0
yellow 6ES7 492-2CX00-0AA0
red 6ES7 492-2DX00-0AA0
SIMATIC Manual Collection B3 6ES7 998-8XC01-8YE0
Electronic manuals on DVD, five
languages: S7-200/300/400, C7,
LOGO!, SIMATIC DP, PC, PG,
STEP 7, engineering software,
runtime software, PCS 7, SIMATIC
HMI, SIMATIC NET
SIMATIC Manual Collection B3 6ES7 998-8XC01-8YE2
maintenance service for 1 year
Current "Manual Collection" DVD
and the three subsequent
updates
Manual "SIMATIC S7-400
programmable controller"
incl. instruction list
German 6ES7 498-8AA05-8AA0
English 6ES7 498-8AA05-8BA0
French 6ES7 498-8AA05-8CA0
Spanish 6ES7 498-8AA05-8DA0
Italian 6ES7 498-8AA05-8EA0
B3: Subject to export regulations: AL: N and ECCN: 5D992B1
B6: Subject to export regulations: AL: N and ECCN: EAR99
B7: Subject to export regulations: AL: N and ECCN: EAR99H
B8: Subject to export regulations: AL: N and ECCN: EAR99S

5/80 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
SIPLUS analog modules
SIPLUS SM 431 analog input module
SIPLUS SM 432 analog output module

■ Overview SIPLUS SM 431 ■ Overview SIPLUS SM 432

5
• Analog inputs for SIMATIC S7-400 • Analog outputs for SIMATIC S7-400
• Connecting voltage sensors and current sensors, • For connection of analog actuators
thermo elements, resistors and resistance thermometers
• Resolution 13 to 16 bit

Analog input module SIPLUS SM 431 Analog output module SIPLUS SM 432
Order No. 6AG1 431-0HH00-4AB0 Order No. 6AG1 432-1HF00-4AB0
Order No. based on 6ES7 431-0HH00-0AB0 Order No. based on 6ES7 432-0HF00-0AB0
Ambient conditions Suited for exceptional medial Ambient conditions Suited for exceptional medial
exposure (e. g. by chlorine sulfur exposure (e. g. by chlorine sulfur
atmosphere). atmosphere).
Technical data The technical data are identical Technical data The technical data are identical with
with those of the based-on those of the based-on
modules. modules.

For further technical documentation on SIPLUS, see: For further technical documentation on SIPLUS, see:
http://www.siemens.com/siplus-techdoku http://www.siemens.com/siplus-techdoku

■ Ordering data Order No. ■ Ordering data Order No.


SIPLUS SM 431 6AG1 431-0HH00-4AB0 SIPLUS SM 432 6AG1 432-1HF00-4AB0
analog input module analog output module
(medial exposure) (medium exposure)
16 inputs, non-floating, 13 bit 8 outputs, floating, 13 bit
Accessories see S7-400 analog input Accessories see S7-400 analog output
modules SM 431, page 5/78 modules SM 432, page 5/80

Siemens ST 70 · 2009 5/81


© Siemens AG 2008

SIMATIC S7-400
Function modules
FM 450-1 counter module

■ Overview
• Two-channel intelligent counter module for simple counting
tasks
• For direct connection of incremental encoders
• Comparison function with 2 specifiable comparison values
• Integrated digital outputs for outputting the response when the
comparison values are reached
Note
SIMODRIVE Sensor/Motion Connect 500 feature incremental
encoders and preassembled connecting cables for counting
and positioning functions.
http://www.siemens.com/simatic-technology

5
■ Technical specifications
6ES7 450-1AP00-0AE0 6ES7 450-1AP00-0AE0
Supply voltages Input delay (for rated value of
input voltage)
Aux. voltage 1L+,
load voltage 2 L+ • Input frequency (with 0.1 ms 200 kHz
delay), max.
• Rated value (DC) 24 V
• for standard inputs
• permissible range, lower limit 20.4 V; dynamic 18.5 V
(DC) - programmable Yes
- at "0" to "1", max. 2.5 μs; >= 2.5 μs (200 kHz);
• permissible range, upper limit 28.8 V; dynamic 30.2 V <= 25 μs (20 kHz)
(DC)
Digital outputs
• non-periodic skip
- Duration 500 ms Number of digital outputs 6
- Recovery time 50 s Short-circuit protection of the Yes; clocked electronically
- Value 35 V output
Load voltage 1L+ Limitation of inductive shutdown 2L+ (-39 V)
voltage to
• Reverse polarity protection Yes
Output voltage
Load voltage 2L+
• for signal "0" (DC), max. 3V
• Reverse polarity protection Yes
• for signal "1", min. 2L+ (-1.5 V)
Current consumption
Output current
from load voltage 1L+ (without 40 mA
load), max. • for signal "1" rated value 0.5 A
from backplane bus DC 5 V, 450 mA • for signal "1" permissible range 5 mA
max. for 0 to 60 °C, min.
Current consumption/ • for signal "1" permissible range 0.6 A
power loss for 0 to 60 °C, max.
Power loss, typ. 9W Output delay with resistive load
Connection point • "0" to "1", max. 300 μs
required front connectors 1x 48-polig Encoder supply
Digital inputs 5 V encoder supply
Number of digital inputs 6 •5V Yes; 5.2 V +/-2 %
Functions 1 for gate start, 1 for gate stop, • Short-circuit protection Yes
1 for setting the counter • Output current, max. 300 mA
Input voltage 24 V encoder supply
• for signal "0" -28.8 to +5 V • 24 V Yes; 1L+ (-3 V)
• for signal "1" +11 to +28.8 V • Short-circuit protection Yes
Input current • Output current, max. 300 mA
• for signal "1", typ. 9 mA

5/82 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Function modules
FM 450-1 counter module

■ Technical specifications (continued) ■ Ordering data Order No.


6ES7 450-1AP00-0AE0 FM 450-1 counter module 6ES7 450-1AP00-0AE0
Encoder with 2 channels, max. 500 kHz;
for incremental encoder
Connectable encoders
Front connectors
• Incremental encoder Yes; with 2 pulse strings offset by 90°
(symmetrical) 48-pin
• Incremental encoder Yes • with screw contacts, 1 item B7 6ES7 492-1AL00-0AA0
(asymmetrical)
• with screw contacts, 84 items B6 6ES7 492-1AL00-1AB0
• 24 V initiator Yes
• with spring-loaded terminals, 6ES7 492-1BL00-0AA0
• 24 V directional element Yes; 1 pulse train, 1 direction level 1 item
Counters • with crimp contacts, 1 item B7 6ES7 492-1CL00-0AA0
Number of counter inputs 2; 32 bit or +/-31 bit • with crimp contacts, 84 items 6ES7 492-1CL00-1AB0
Counter input 5 V Front covers for CPU and 6ES7 492-1XL00-0AA0
function modules
• Type RS 422
• Terminating resistor 220 Ω
Spare part
5
• Differential input voltage min. 0.5 V B6: Subject to export regulations: AL: N and ECCN: EAR99
B7: Subject to export regulations: AL: N and ECCN: EAR99H
• Counter frequency, max. 500 kHz
Counter input 24 V
• Input voltage, for signal "0" -30 to +5 V
• Input voltage, for signal "1" +11 to +30 V
• Input current, for signal "1", typ. 9 mA
• Counter frequency, max. 200 kHz
• Minimum pulse width >= 2.5 μs (200 kHz);
<= 25 μs (20 kHz) (parameterizable)
Parameter
Remark Assigned binary addresses:
64 bytes/64 bytes
Isolation
Isolation checked with 500 V
Isolation
Galvanic isolation, digital inputs
• between the channels and the Yes; Optocoupler
backplane bus
Isolation, digital outputs
• between the channels and the Yes; Optocoupler
backplane bus
Isolation counter
• between the channels and the Yes; Optocoupler
backplane bus
Permissible potential
difference
between different circuits 75 V DC / 60 V AC
Dimensions
Dimensions
• Width 25 mm
• Height 290 mm
• Depth 210 mm
Weights
• Weight, approx. 650 g

Siemens ST 70 · 2009 5/83


© Siemens AG 2008

SIMATIC S7-400
Function modules
SIPLUS FM 450-1 counter module

■ Overview ■ Ordering data Order No.


• Two-channel, intelligent counter module for simple counting FM 450-1 counter module 6AG1 450-1AP00-4AE0
tasks
(medium exposure)
• For direct connection of incremental sensors
with 2 channels, max. 500 kHz;
• Comparison functions with two definable comparison values for incremental encoder
• Integrated digital outputs for the output of the reaction on Accessories see FM 450-1, page 5/83
reaching the comparison values

SIPLUS FM 450-1 counter module


Order No. 6AG1 450-1AP00-4AE0
Order No. based on 6ES7 450-1AP00-0AE0
Ambient conditions Suited for exceptional medial
exposure (e. g. by chlorine sulfur
atmosphere)

5 Technical data The technical data are identical


to that of the based-on modules.

For further technical documentation on SIPLUS, see:


http://www.siemens.com/siplus-techdoku

Note:
We offer incremental sensors and preassembled connecting
cables for counting and positioning functions under SIMODRIVE
Sensor or Motion Connect 500.
http://www.siemens.com/simatic-technology

5/84 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Function modules
FM 451 positioning module

■ Overview
• Three-channel positioning module for rapid traverse/creep
speed drives
• 4 digital outputs per channel for motor control
• Incremental or synchro-serial position decoding
Note
SIMODRIVE Sensor/Motion Connect 500 feature position-
measuring systems and preassembled connecting cables for
counting and positioning functions.
http://www.siemens.com/simatic-technology

5
■ Technical specifications
6ES7 451-3AL00-0AE0 6ES7 451-3AL00-0AE0
Supply voltages Encoder supply
Rated value 5 V encoder supply
• DC 24 V Yes •5V Yes
Current consumption • Output current, max. 210 mA
Current consumption, max. 550 mA • Cable length, max. 35 m; at max. 210 mA
Connection point 24 V encoder supply
required front connectors 1x 48-pin • 24 V Yes
Digital inputs • Output current, max. 300 mA
Number of digital inputs 12; 4 per axis • Cable length, max. 100 m; at max. 300 mA
Functions Reference cams, reversing cams, Absolute encoder (SSI) encoder
flying actual value setting, start/stop supply
positioning
• Absolute encoder (SSI) Yes
Input voltage
• Output voltage 24 V DC
• Rated value, DC 24 V
• Output current, max. 300 mA
• for signal "0" -3 to +5 V
• Cable length, max. 300 m; at max.156 kbit/s
• for signal "1" 11 to 30 V
Encoder
Input current
Connectable encoders
• for signal "1", typ. 6 mA
• Incremental encoder Yes
• for 2-wire BERO (symmetrical)
- for signal "1", typ. 30 mA • Incremental encoder Yes
Digital outputs (asymmetrical)
Number of digital outputs 12; 4 per axis • Absolute encoder (SSI) Yes
Functions Rapid traverse, creep, run right, run Encoder signals, incremental
left encoder (symmetrical)
Short-circuit protection of the Yes • Trace mark signals A, notA, B, notB
output • Zero mark signal N, notN
Output voltage • Input signal 5 V difference signal (phys. RS 422)
• for signal "1", min. UP - 3 V • Input frequency, max. 1 MHz
Output current Encoder signals, incremental
• for signal "1" permissible range 600 mA; with UPmax encoder (asymmetrical)
for 0 to 55 °C, max. • Trace mark signals A. B
• for signal "0" residual current, 0.5 mA • Zero mark signal N
max.
• Input voltage 24 V
• Input frequency, max. 50 kHz; for 25 m cable length,
25 kHz for 100 m cable length
• cable length, shielded, max. 100 m

Siemens ST 70 · 2009 5/85


© Siemens AG 2008

SIMATIC S7-400
Function modules
FM 451 positioning module

■ Technical specifications (continued) ■ Ordering data Order No.


6ES7 451-3AL00-0AE0 FM 451 positioning module 6ES7 451-3AL00-0AE0
Encoder signals, absolute for rapid traverse and creep
encoder (SSI) speed drives
• Input signal 5 V difference signal (phys. RS 422) Front connector
• Data signal DATA. notDATA 48-pin
• Clock signal CL. notCL • with screw contacts, 1 item B7 6ES7 492-1AL00-0AA0
• Telegram length 13 or 25 bit serial • with screw contacts, 84 items B6 6ES7 492-1AL00-1AB0
• Clock frequency, max. 1.25 MHz • with spring-loaded terminals, 6ES7 492-1BL00-0AA0
1 item
• Gray code 1
• with crimp contacts, 1 item B7 6ES7 492-1CL00-0AA0
• cable length, shielded, max. 300 m; at max. 156 kBit/s
• with crimp contacts, 84 items 6ES7 492-1CL00-1AB0
Isolation
Front covers for CPU and 6ES7 492-1XL00-0AA0
Galvanic isolation, digital inputs function modules

5 • galvanic isolation, digital inputs Yes


Isolation, digital outputs
Spare part
Signal cable
• Galvanic isolation, digital Yes Pre-assembled for HTL encoder, 6FX5 0 7 2-2AL00- 7 7 7 7
outputs UL/DESINA
Environmental requirements Pre-assembled for SSI absolute 6FX5 0 7 2-2CC11- 7 7 7 7
Operating termperature encoder, UL/DESINA
• min. 0 °C Pre-assembled for TTL encoder 6FX5 0 7 2-2CD01- 7 7 7 7
6FX2001-1, UL/DESINA
• max. 55 °C
Pre-assembled for TTL encoder 6FX5 0 7 2-2CD24- 7 7 7 7
Storage/transport temperature 24 V, UL/DESINA
• min. -40 °C
Not crimped 0
• max. 70 °C
Module end crimped, connector 1
Relative humidity case supplied
• Humidity class F Yes Motor end crimped, connector 4
Degree of protection case supplied
IP 20 Yes 0m 1
100 m 2
Dimensions
200 m 3
Dimensions
0m A
• Width 50 mm 10 m B
• Height 290 mm 20 m C
30 m D
• Depth 210 mm
40 m E
Weights 50 m F
• Weight, approx. 1 300 g 60 m G
70 m H
80 m J
90 m K
0m A
1m B
2m C
3m D
4m E
5m F
6m G
7m H
8m J
0m K
0.0 m 0
0.1 m 1
0.2 m 2
0.3 m 3
0.4 m 4
0.5 m 5
0.6 m 6
0.7 m 7
0.8 m 8
B6: Subject to export regulations: AL: N and ECCN: EAR99
B7: Subject to export regulations: AL: N and ECCN: EAR99H

5/86 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Function modules
FM 452 cam controller

■ Overview
• Extremely high-speed electronic cam controller
• Low-cost alternative to mechanical cam controllers
• 32 cam tracks, 16 onboard digital outputs for direct output of
actions
• Incremental or synchro-serial position decoding
Note:
SIMODRIVE Sensor/Motion Connect 500 feature position-
measuring systems and preassembled connecting cables for
counting and positioning functions.
http://www.siemens.com/simatic-technology

5
■ Technical specifications
6ES7 452-1AH00-0AE0 6ES7 452-1AH00-0AE0
Supply voltages Encoder supply
Rated value 5 V encoder supply
• DC 24 V Yes •5V Yes
Current consumption • Output current, max. 300 mA
Current consumption, max. 500 mA • Cable length, max. 32 m
Connection point 24 V encoder supply
required front connectors 1x 48-pin • 24 V Yes
Digital inputs • Output current, max. 300 mA
Number of digital inputs 11 • Cable length, max. 100 m
Functions Reference point switch, flying actual Encoder
value setting/length measurement,
brake release, enable track output Connectable encoders
no. 3 to 10 • Incremental encoder Yes
Input voltage (symmetrical)

• Rated value, DC 24 V • Incremental encoder Yes


(asymmetrical)
• for signal "0" -28.8 to +5 V
• Absolute encoder (SSI) Yes
• for signal "1" 11 to 28.8 V
• 2-wire BEROS Yes
Input current
Encoder signals, incremental
• for signal "0", max. (permissible 2 mA encoder (symmetrical)
quiescent current)
• Trace mark signals A. notA. B. notB
• for 2-wire BERO
• Zero mark signal N. notN
- for signal "1", typ. 9 mA
• Input signal 5 V difference signal (phys. RS 422)
Digital outputs
• Input frequency, max. 1 MHz
Number of digital outputs 16
Encoder signals, incremental
Functions Cam tracks encoder (asymmetrical)
Short-circuit protection of the Yes • Trace mark signals A. B
output
• Zero mark signal N
Output voltage
• Input voltage 24 V
• Rated value (DC) 24 V
• Input frequency, max. 50 kHz; 50 kHz for 25 m cable
• for signal "1", min. UP - 0.8 V length; 25 kHz for 100 m cable
Output current length
• for signal "1" permissible range 600 mA; with UPmax
for 0 to 55 °C, max.
• for signal "0" residual current, 0.5 mA
max.

Siemens ST 70 · 2009 5/87


© Siemens AG 2008

SIMATIC S7-400
Function modules
FM 452 cam controller

■ Technical specifications (continued) ■ Ordering data Order No.


6ES7 452-1AH00-0AE0 FM 452 6ES7 452-1AH00-0AE0
electronic cam controller
Encoder signals, absolute
encoder (SSI) Front covers for CPU and 6ES7 492-1XL00-0AA0
function modules
• Input signal 5 V difference signal (phys. RS 422)
Spare part
• Data signal DATA. notDATA
Front connector
• Clock signal CL. notCL
48-pin
• Telegram length 13 or 25 bit serial
• with screw contacts, 1 item B7 6ES7 492-1AL00-0AA0
• Clock frequency, max. 1 MHz
• with screw contacts, 84 items B6 6ES7 492-1AL00-1AB0
• Gray code 1
• with spring-loaded terminals, 6ES7 492-1BL00-0AA0
• cable length, shielded, max. 300 m; at max. 125 kHz 1 item
Isolation • with crimp contacts, 1 item B7 6ES7 492-1CL00-0AA0
Galvanic isolation, digital inputs • with crimp contacts, 84 items 6ES7 492-1CL00-1AB0

5 • galvanic isolation, digital inputs No


Isolation, digital outputs
Signal cable
Pre-assembled for HTL and TTL 6FX5 002-2CA12- 7777
• Galvanic isolation, digital No encoder, without Sub-D
outputs connector, UL/DESINA
Environmental requirements Pre-assembled for SSI absolute 6FX5 002-2CC12- 7777
encoder 6FX2001-5, without
Operating termperature Sub-D connector, UL/DESINA
• min. 0 °C
• max. 55 °C Length code see FM 451, page 5/86
Storage/transport temperature
• min. -40 °C
• max. 70 °C
Relative humidity
• Humidity class F Yes
Degree of protection
IP 20 Yes
Dimensions
Dimensions
• Width 25 mm
• Height 290 mm
• Depth 210 mm
Weights
• Weight, approx. 650 g
B6: Subject to export regulations: AL: N and ECCN: EAR99
B7: Subject to export regulations: AL: N and ECCN: EAR99H

5/88 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Function modules
FM 453 positioning module

■ Overview
• Positioning module for servo and/or stepper motors in
machines with high clock pulse rates
• Can be used for point-to-point positioning tasks and for
complex traversing patterns
• Up to 3 independent motors can be controlled
Note:
SIMODRIVE Sensor/Motion Connect 500 feature position-
measuring systems and preassembled connecting cables for
counting and positioning functions.
http://www.siemens.com/simatic-technology

5
■ Technical specifications
6ES7 453-3AH00-0AE0 6ES7 453-3AH00-0AE0
Supply voltages Output voltage
Aux. voltage 1L+ to 4L+ • Rated value (DC) 24 V
• Rated value (DC) 24 V • for signal "1", min. UP - 0.3 V
• dynamic range 18.5 to 30.2 V Output current
• static area 20.4 to 28.8 V • for signal "1" rated value 0.5 A; at 40 °C; 0.1 A at 60 °C
Current consumption • for signal "1" permissible range 5 mA
for 0 to 40 °C, min.
from load voltage1L+, max. 1 A; with 24 V position encoder;
1 A for 5 V position encoder • for signal "1" permissible range 0.6 A
for 0 to 40 °C, max.
from load voltage 2L+ to 4L+, 2 A; per channel
max. • for signal "1" permissible range 5 mA
for 40 to 60 °C, min.
from backplane bus DC 5 V, 1.6 A; Rated current
max. • for signal "1" permissible range 0.12 A
for 40 to 60 °C, max.
Current consumption/
power loss • for signal "0" residual current, 2 mA
max.
Power loss, max. 8W
Switching frequency
Connection point
• with resistive load, max. 100 Hz
required front connectors 1x 48-pin
• with inductive load, max. 0.25 Hz
Digital inputs
Encoder supply
Number of digital inputs 6; for each channel/axis
5 V encoder supply
Functions configurable
•5V Yes
Input voltage
• Output current, max. 300 mA
• Rated value, DC 24 V
• Cable length, max. 35 m; at max. 210 mA;
• for signal "0" -3 to +5 V (max. 3 mA) 25 m at max. 300 mA
• for signal "1" 11 to 30 V (max. 7 mA) 24 V encoder supply
Input delay (for rated value of • 24 V Yes
input voltage)
• Cable length, max. 100 m; at max. 300 mA
• for standard inputs
- at "0" to "1", max. 15 μs; via input voltage range, Encoder
8 μs at DC 24 V Connectable encoders
- at "1" to "0", max. 45 μs; via input voltage range
• Incremental encoder Yes
Digital outputs (symmetrical)
Number of digital outputs 4; for each channel/axis • Absolute encoder (SSI) Yes
Functions configurable Encoder signals, incremental
Short-circuit protection of the Yes encoder (symmetrical)
output • Input signal 5 V difference signal (phys. RS 422)
• Input frequency, max. 1 MHz; for 10 m cable length;
0.5 MHz for 35 m cable length

Siemens ST 70 · 2009 5/89


© Siemens AG 2008

SIMATIC S7-400
Function modules
FM 453 positioning module

■ Technical specifications (continued)


6ES7 453-3AH00-0AE0 6ES7 453-3AH00-0AE0
Encoder signals, absolute Isolation
encoder (SSI)
Galvanic isolation, digital inputs
• Input signal 5 V difference signal (phys. RS 422)
• galvanic isolation, digital inputs Yes; Optocoupler
• Clock frequency, max. 1.25 Mbit/s at 10 cable length
(2.5 Mbit/s available soon) Isolation, digital outputs

• cable length, shielded, max. 250 m; at max. 156 kBit/s • Galvanic isolation, Yes; Optocoupler
digital outputs
Drive interface
Environmental requirements
Signal input I
Operating termperature
• Type Drive interface step, signal input
"READY 1" • min. 0 °C

• Function "Power section ready" where • max. 55 °C


Ui < 1 V, Ii = 2mA Storage/transport temperature

5
Signal output I • min. -40 °C
• Type 5 V (phys. RS 422) • max. 70 °C
• Function Clock pulse, direction, enable, Relative humidity
current control
• Humidity class F No
• Differential output voltage, min. 2 V; RL = 100 Ohm
Degree of protection
• Differential output voltage for 1.1 V; Io = 30 mA
signal "0", max. IP 20 Yes
• Differential output voltage, 3.7 V; Io = -30 mA Dimensions
for signal "1", min. Dimensions
• Load impedance 55 Ω • Width 50 mm
• Pulse frequency 200 kHz; 500 kHz available soon • Height 290 mm
• Cable length, max. 35 m; 35 m with symm. transmission; • Depth 210 mm
10 m with asymm. transmission
Weights
Signal output II
• Weight, approx. 1 620 g
• Type Contact relay
• Function Drive disconnection for operation
• Load 1 A/50 V/30 VA DC
Signal output III
• Type Analog output
• Function Drive interface Servo:
Setpoint output for drive
• Output voltage -10 to +10 V
• Output current 3 to +3 mA
• Cable length, max. 30 m

■ Ordering data Order No. Order No.


FM 453 positioning module 6ES7 453-3AH00-0AE0 Front connector
with 3 channels/axes 48-pin
Setpoint connecting cable • with screw contacts, 1 item B7 6ES7 492-1AL00-0AA0
for 3 servo motors 6FX2 002-3AD01- 7777 • with screw contacts, 84 items B6 6ES7 492-1AL00-1AB0
for 3 stepper motors 6FX2 002-3AB04- 7777 • with spring-loaded terminals, 6ES7 492-1BL00-0AA0
1 item
for 2 servo motors / 1 stepper 6FX2 002-3AB02- 7777
motor • with crimp contacts, 1 item B7 6ES7 492-1CL00-0AA0
for 1 servo motor / 2 stepper 6FX2 002-3AB03- 7777 • with crimp contacts, 84 items 6ES7 492-1CL00-1AB0
motors
Signal cable
Length code see FM 451. page 5/86
Pre-assembled for SSI absolute 6FX5 0 7 2-2CC11- 7777
Front covers for CPU and 6ES7 492-1XL00-0AA0 encoder, UL/DESINA
function modules
Pre-assembled for TTL encoder 6FX5 0 7 2-2CD01- 7777
Spare part 6FX2001-1, UL/DESINA
Pre-assembled for TTL encoder 6FX5 0 7 2-2CD24- 7777
24 V, UL/DESINA
B6: Subject to export regulations: AL: N and ECCN: EAR99
Length code see FM 451, page 5/86
B7: Subject to export regulations: AL: N and ECCN: EAR99H

5/90 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Function modules
FM 455 controller module

■ Overview
• 16-channel closed-loop control module for universal closed-
loop control tasks
• Suitable for temperature, pressure, and flow control systems
• User-friendly online self-optimization for temperature controls
• Preprogrammed controller structures
• 2 control algorithms
• 2 versions:
- FM 455 C as continuous-action controller
- FM 455 S as step controller or pulse controller
• With 16 analog outputs (FM 455 C) or 32 digital outputs
(FM 455 S) for actuators

5
■ Technical specifications
6ES7 455-0VS00- 6ES7 455-1VS00- 6ES7 455-0VS00- 6ES7 455-1VS00-
0AE0 0AE0 0AE0 0AE0
Supply voltages Limitation of inductive L+ (-1.5 V)
shutdown voltage to
Load voltage L+
Lamp load, max. 5W
• Rated value (DC) 24 V 24 V
Controlling a digital input Yes
• permissible range, lower 20.4 V 20.4 V
limit (DC) Output voltage
• permissible range, upper 28.8 V 28.8 V • for signal "1", min. L+ (-2.5 V)
limit (DC)
Output current
Current consumption
• for signal "1" rated value 0.1 A
from load voltage L+ 440 mA; 400 mA;
(without load), max. typ. 370 mA typ. 330 mA • for signal "1" permissible 5 mA
range for 0 to 60 °C, min.
Current consumption/
power loss • for signal "1" permissible 150 mA
range for 0 to 60 °C, max.
Power loss, max. 17.3 W 16.2 W
• for signal "0" residual 0.5 mA
Power loss, typ. 12 W 10.7 W current, max.
Connection point Parallel switching of
2 outputs
required front connectors 2x 48-pin 2x 48-pin
• for logic links Yes
Digital inputs
Switching frequency
Number of digital inputs 16 16
• with resistive load, max. 100 Hz
Input characteristic curve to Yes Yes
IEC 1131, Type 2 • with inductive load, max. 0.5 Hz
Input voltage • on lamp load, max. 100 Hz
• Rated value, DC 24 V 24 V Load impedance range
• for signal "0" -3 to +5 V -3 to +5 V • lower limit 240 Ω
• for signal "1" 13 to 30 V 13 to 30 V • upper limit 4 kΩ
Input current • cable length, shielded, 1 000 m
max.
• for signal "1", typ. 7 mA 7 mA
• Cable length unshielded, 600 m
Cable length max.
• cable length, shielded, 1 000 m 1 000 m Analog inputs
max.
Number of analog inputs 16; 16;
• Cable length unshielded, 600 m 600 m with thermo- with thermo-
max. couples or 2-wire couples or 2-wire
Digital outputs connection; connection;
8 with Pt 100 or 8 with Pt 100 or
Number of digital outputs 32 4-wire connection 4-wire connection
Short-circuit protection of Yes; Electronic
the output

Siemens ST 70 · 2009 5/91


© Siemens AG 2008

SIMATIC S7-400
Function modules
FM 455 controller module

■ Technical specifications (continued)


6ES7 455-0VS00- 6ES7 455-1VS00- 6ES7 455-0VS00- 6ES7 455-1VS00-
0AE0 0AE0 0AE0 0AE0
cable length, shielded, max. 200 m; 200 m; Output ranges, voltage
50 m at 80 mV and 50 m at 80 mV and
thermocouples thermocouples • 0 to 10 V Yes

Input ranges (rated values), • -10 to +10 V Yes


voltages Output ranges, current
• 0 to +10 V Yes Yes • 0 to 20 mA Yes
• -1.75 to +11.75 V Yes Yes • -20 to +20 mA Yes
• -80 mV to +80 mV Yes Yes • 4 to 20 mA Yes
Input ranges (rated values), Connection of actuators
currents
• for voltage output Yes
• 0 to 20 mA Yes Yes 2-conductor connection
• 0 to 23.5 mA Yes Yes • for current output Yes
5 • -3.5 to +23.5 mA Yes Yes 2-conductor connection
Load impedance (in rated
• 4 to 20 mA Yes Yes
range of output)
Input ranges (rated values),
thermoelements • with voltage outputs, min. 1 kΩ

• Type B Yes Yes • with voltage outputs, 1 μF


capacitive load, max.
• Type J Yes Yes
• with current outputs, max. 500 Ω
• Type K Yes Yes
• with current outputs, 1 mH
• Type R Yes Yes inductive load, max.
• Type S Yes Yes Analog value creation
Input ranges (rated values), Measurement principle integrating integrating
resistance thermometers
Integration and conversion
• Pt 100 Yes Yes time/resolution per channel
• permissible input 20 V 20 V • Resolution with overload 14 Bit; 12 or 14 bit, 14 Bit; 12 or 14 bit,
frequency for voltage input area (bit including sign), parameterizable parameterizable
(destruction limit), max. max.
• permissible input current 40 mA 40 mA • Conversion time (per 16.67 ms; 16.67 ms;
for current input channel) at 12 bits: 16 2/3 ms at 12 bits: 16 2/3 ms
(destruction limit), max. at 60 Hz, at 60 Hz,
20 ms at 50 Hz; 20 ms at 50 Hz;
Characteristic curve linear- at 14 bits: 100 ms at at 14 bits: 100 ms at
ization 50 and 60 Hz 50 and 60 Hz
• programmable Yes Yes Settling time
- for thermoelements Typ B. J. K. R. S Typ B. J. K. R. S
- for thermoresistor Pt100 (Standard) Pt100 (Standard) • for resistive load 0.2 ms 0.1 ms

Temperature compensation • for capacitive load 3.3 ms 3.3 ms

• internal temperature Yes; parametrizable Yes; parametrizable • for inductive load 0.5 ms 0.5 ms
compensation Encoder
• external temperature Yes; parametrizable Yes; parametrizable Connection of signal
compensation with Pt100 encoders
Analog outputs • for voltage measurement Yes Yes
Number of analg outputs 16 • for current measurement Yes Yes
cable length, shielded, max. 200 m; as 4-wire transducer
50m at 80 mV and Connectable encoders
thermocouples
• 2-wire BEROS Yes Yes
Voltage output, Short-circuit Yes - permissible quiescent 1.5 mA 1.5 mA
protection current (2-wire BEROS),
Voltage output, short-circuit 25 mA max.
current, max.. Errors/accuracies
Current output, no-load 18 V Linearity error (relative to +/- 0.05 % +/- 0.05 %
voltage, max. input area)

5/92 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Function modules
FM 455 controller module

■ Technical specifications (continued)


6ES7 455-0VS00- 6ES7 455-1VS00- 6ES7 455-0VS00- 6ES7 455-1VS00-
0AE0 0AE0 0AE0 0AE0
Temperature error (relative +/- 0.005 %/K +/- 0.005 %/K Interference voltage
to input areas) suppression for
f = n x (fl +/- 1 %),
Linearity error (relative to +/- 0.05 % fl = interference frequency
output area)
• Series mode interference 40 dB 40 dB
Temperature error (relative +/- 0.02 %/K (peak value of interference
to output area) < rated value of input
Operational limit in overall range), min.
temperature range • common mode voltage 70 dB 70 dB
• Voltage, relative to input +/-0.6 to +/-1% +/-0.6 to +/-1% (USS < 2.5 V) , min.
area Control technology
• Current, relative to input +/-0.6 to +/-1% +/-0.6 to +/-1% Number of closed loop 16; with thermo- 16; with thermo-
area controllers couples or 2-wire couples or 2-wire
connection; connection;
5
• Resistance-type +/-0.6 to +/-1% +/-0.6 to +/-1%
thermometer, relative to 8 with Pt 100 or 8 with Pt 100 or
input area 4-wire connection 4-wire connection
• Voltage, relative to output +/- 0.5 % Status information/alarms/
area diagnostics
• Current, relative to output +/- 0.6 % Substitute values Yes; Yes;
area connectable Parameterizable Parameterizable
Basic error limit (operational Isolation
limit at 25 °C) Isolation checked with 500 V DC 500 V DC
• Voltage, relative to input +/-0.4 to +/-0.6% +/-0.4 to +/-0.6% Isolation
area
Isolation, controller
• Current, relative to input +/-0.4 to +/-0.6% +/-0.4 to +/-0.6%
area • between the channels No No
• Resistance-type +/-0.4 to +/-0.6% +/-0.4 to +/-0.6% • between the channels and Yes; Optocoupler Yes; Optocoupler
thermometer, relative to the backplane bus
input area
Permissible potential
• Voltage, relative to output +/- 0.4 % difference
area
between inputs and MANA 2.5 V DC 2.5 V DC
• Current, relative to output +/- 0.5 % (UCM)
area
between M internally and 75 V DC / 60 V AC 75 V DC / 60 V AC
the inputs
Dimensions
Dimensions
• Width 50 mm 50 mm
• Height 290 mm 290 mm
• Depth 210 mm 210 mm
Weights
• Weight, approx. 1 400 g 1 400 g

■ Ordering data Order No. Order No.


FM 455 C controller module 6ES7 455-0VS00-0AE0 Front connectors
with 16 analog outputs for 48-pin
16 continuous controllers
• with screw contacts, 1 item B7 6ES7 492-1AL00-0AA0
FM 455 S controller module 6ES7 455-1VS00-0AE0
• with screw contacts, 84 items B6 6ES7 492-1AL00-1AB0
with 32 digital outputs for 16 step
or pulse controllers • with spring-loaded terminals, 6ES7 492-1BL00-0AA0
1 item
• with crimp contacts, 1 item B7 6ES7 492-1CL00-0AA0
• with crimp contacts, 84 items 6ES7 492-1CL00-1AB0
B6: Subject to export regulations: AL: N and ECCN: EAR99
B7: Subject to export regulations: AL: N and ECCN: EAR99H

Siemens ST 70 · 2009 5/93


© Siemens AG 2008

SIMATIC S7-400
Function modules
FM 458-1 DP application module

■ Overview
SIMATIC FM 458-1 DP integrated into SIMATIC S7-400
• Designed for high-performance and freely-configurable
control tasks in the SIMATIC S7-400
• Can be adapted as required to individual requirements, e.g.:
open-loop control, closed-loop control, computing and motion
control. Therefore highly flexible for many different applica-
tions.
• Extensive library with approx. 300 function blocks:
These include simple functions such as AND, ADD and OR up
to complex GMC (General Motion Control) blocks such as
virtual master or gearbox functions.
• User-friendly graphic configuring with the SIMATIC
engineering tool CFC (Continuous Function Chart):
Optimum code generation by compiler, therefore SCL is not
required.
5 • PROFIBUS DP interface onboard
SIMATIC FM 458-1 DP is based on more than 15 years
experience with high-performance control systems, and
combines this know-how with the advantages of SIMATIC – the
global leader in automation systems for decades already. In
contrast to other function modules with static struc-
tures/functions, the FM 458-1 DP application module can be
flexibly configured according to individual requirements.

5/94 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Function modules
FM 458-1 DP basic module

■ Overview
• Basic module for handling computing, open-loop control and
closed-loop control tasks
• PROFIBUS DP interface for linking of distributed I/O and drive
engineering
• Modular configuration with expansion modules for I/O and
communication

5
■ Technical specifications
6DD1 607-0AA2 6DD1 607-0AA2
Supply voltages Digital inputs
Rated value Number of digital inputs 8; Connectors x2
• DC 5 V Yes Input voltage
• DC 24 V Yes • Rated value, DC 24 V
• Permissible range (ripple 4.8 V • for signal "0" -1 to +6 V
included), lower limit (DC)
• for signal "1" 13.5 to 33 V
• permissible range (ripple 5.25 V
included), upper limit (DC) Input current

Current consumption • for signal "0", max. (permissible 0 mA


quiescent current)
Current consumption, typ. 3A
• for signal "1", typ. 3 mA; at 24 V
Current consumption, max. 1.5 A
Input delay (for rated value of
Backup battery input voltage)
Battery op. Yes • for standard inputs
• Buffer current, max. 15 μA - at "0" to "1", max. 5 μs

Memory Status information/alarms/


diagnostics
Backup
Alarms
• present Yes; SRAM
• Alarms Yes
Time
Isolation
Clock
Galvanic isolation, digital inputs
• Hardware clock Yes
(real-time clock) • galvanic isolation, digital inputs No; only via optional interface
modules
• Resolution 500 ms
Dimensions
PROFIBUS DP
Required slots 1
equidistance Yes; with connection to interrupt
tasks Dimensions

direct data exchange Yes Weights 1 000 g


(cross traffic)

Siemens ST 70 · 2009 5/95


© Siemens AG 2008

SIMATIC S7-400
Function modules
FM 458-1 DP basic module

■ Ordering data Order No. Order No.


FM 458-1 DP application 6DD1 607-0AA2 RS 485 bus connector with
module 90° cable outlet
Basic module for computing, Max. transfer rate 12 Mbit/s
closed-loop control and open-
loop control tasks; with Without PG interface 6ES7 972-0BA12-0XA0
PROFIBUS DP interface With PG interface 6ES7 972-0BB12-0XA0
Micro Memory Card RS 485 bus connector with
for FM 458-1 DP basic module angled cable outlet

2 MB 6ES7 953-8LL20-0AA0 Max. transfer rate 12 Mbit/s

4 MB 6ES7 953-8LM20-0AA0 Without PG interface 6ES7 972-0BA41-0XA0

FM 458-1 DP Know-How-Protect 6DD1 607-0GA0 With PG interface 6ES7 972-0BB41-0XA0

for protection of technological RS 485 bus connector with


application modules against 90° cable outlet for FastConnect
unauthorized copying system

5 SC 64 interface cable 6DD1 684-0GE0 Max. transfer rate 12 Mbit/s

To connect FM 458-1 to the serial Without PG interface 6ES7 972-0BA51-0XA0


interface of a programming With PG interface 6ES7 972-0BB51-0XA0
device/ PC
PROFIBUS FastConnect
SB10 interface module 6DD1 681-0AE2 bus cable
To connect 8 binary I/Os to Standard type with special design 6XV1 830-0EH10
FM 458-1 DP for quick mounting, 2-core,
SB61 interface module 6DD1 681-0EB3 shielded, sold by the meter,
max. delivery unit 1000 m,
To connect 8 binary I/Os to minimum order quantity 20 m
FM 458-1 DP, input voltage:
24/48 V DC Preferred lengths:

SU12 interface module 6DD1 681-0AJ1 20 m 6XV1 830-0EN20

To connect 10 signals to 50 m 6XV1 830-0EN50


FM 458-1 DP 100 m 6XV1 830-0ET10

5/96 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Function modules
EXM 438-1 input/output expansion module

■ Overview Output voltage


• for signal "0" (DC), max. 3V
• for signal "1" (DC), max. Supply voltage -2.5 V
Output current
• for signal "1" rated value 50 mA
• for signal "1" permissible range 100 mA
for 0 to 40 °C, min.
• for signal "0" residual current, 20 μA
max.
• Total switching current 80% at 50 °C all outputs 50 mA
Output delay with resistive load
• "0" to "1", max. 15 μs
Analog inputs
Number of analog inputs 5; Differential inputs
Input ranges (rated values),
voltages 5
• -10 V to +10 V Yes; -10 V: +/-4 LSB;
• Optional plug-in expansion module for the FM 458-1 DP basic to +10 V: +/-4 LSB
module (1 LSB = 4.88 mV)
• For input and output of time-critical signals • Input resistance 470 kΩ
• With digital and analog inputs/outputs (-10 V to +10 V)

• Incremental and absolute value encoders can be connected Analog outputs


• 4 high-resolution analog outputs Number of analg outputs 8; 4 outputs 16 bit; 4 outputs12 bit
• Fan-free operation up to 40°C Voltage output, Short-circuit Yes; relative to frame
protection
■ Technical specifications Voltage output, short-circuit
current, max..
16 bits: 27 mA; 12 bits: 100 mA

6DD1 607-0CA1
Output ranges, voltage
Supply voltages
• -10 to +10 V Yes
Rated value
Analog value creation
• DC 5 V Yes
Integration and conversion
• DC 24 V Yes; to be set up externally time/resolution per channel
Current consumption • Resolution with overload area 4 AO: 16 bits,
(bit including sign), max. 4 AO: 12 bits,
Current consumption, typ. 1.5 A 5 AI: 12 bits
Digital inputs • Conversion time (per channel) 4 AO (16 bits): 2 μs;
Number of digital inputs 16 4 AO (12 bits): 4 μs;
5 AI: 45 μs
Input voltage
Encoder supply
• Rated value, DC 24 V
Output voltage about 14 V (non-isolated)
• for signal "0" -1 to +6 V or input open
Output current, rated value 100 mA
• for signal "1" +13 to +33 V
Short-circuit protection Yes; electronic
Input current
Encoder
• for signal "0", max. (permissible 0 mA
quiescent current) Number of connectable 12;
encoders, max. 8 incremental encoders
• for signal "1", typ. 3 mA (synchronizable),
Input delay (for rated value of 4 absolute encoders
input voltage) Connectable encoders
• for standard inputs • Incremental encoder Yes
- at "0" to "1", max. 200 μs (symmetrical)

Digital outputs • Incremental encoder Yes


(asymmetrical)
Number of digital outputs 8
• Absolute encoder (SSI) Yes; Single- or multiturn-encoder
Short-circuit protection of the Yes; electronic/thermal with SSI (synchronous serial) or
output EnDat interface+
• Response threshold, typ. 250 mA
Limitation of inductive shutdown Supply voltage +1 V
voltage to

Siemens ST 70 · 2009 5/97


© Siemens AG 2008

SIMATIC S7-400
Function modules
EXM 438-1 input/output expansion module

■ Technical specifications ■ Ordering data Order No.


6DD1 607-0CA1 EXM 438-1 6DD1 607-0CA1
input/output expansion
Encoder signals, incremental
encoder (symmetrical) for direct exchange of digital and
analog signals between
• Trace mark signals 1) for tracks A and B (90° out of FM 458-1 DP and the plant
phase), poss. with zero pulse N;
2) for separate forward and SB10 interface module 6DD1 681-0AE2
backward track
To connect 8 binary inputs or
• Input signal with 0 signal: -5 to 0 V; outputs to FM 458-1 DP
with 1 signal: +3 to +5 V;
permissible input voltage range: SB61 interface module 6DD1 681-0EB3
differential voltage -5 to +5 V; To connect 8 binary inputs to
max. input current: 15 mA FM 458-1 DP, input voltage:
(important: not limited on module 24/48 V DC
side!)
SB71 interface module 6DD1 681-0DH1
• Input frequency, max. 2.5 MHz
To connect 8 binary outputs to
Encoder signals, incremental
5
FM 458-1 DP, output voltage:
encoder (asymmetrical) 24/48 V DC
• Trace mark signals Track A and B (phase-shifted by 90 SU12 interface module 6DD1 681-0AJ1
degrees), possibly with zero pulse N
To connect 10 signals to
• Input voltage with 0 signal: -30 to +4 V FM 458-1 DP
(at 15 mA load);
with 1 signal: +8 to 30 V SU13 interface module 6DD1 681-0GK0
(at 15 mA load); To connect 50 signals to
permissible input voltage range: FM 458-1 DP
differential voltage -30 to +30 V
SC 62 interface cable 6DD1 684-0GC0
• Input frequency, max. 1 MHz; Track frequency
To connect EXM 438-1 with up to
Encoder signals, absolute 5 SBxx or SU12
encoder (SSI)
SC 63 interface cable 6DD1 684-0GD0
• Input signal 5 V to RS 422
To connect EXM 438-1 with an
• Data signal Dual-, Gray-, Gray-Excess-Code SU13
• Clock frequency, max. 2 MHz; 100 kHz to 2 MHz
(depending on cable length)
Errors/accuracies
Linearity error (relative to (+/- 1 LSB )
output area)
Isolation
Galvanic isolation, digital inputs
• galvanic isolation, digital inputs No
Isolation, digital outputs
• Galvanic isolation, digital No
outputs
Isolation, analog inputs
• Isolation, analog inputs No
Isolation, analog outputs
• Galvanic isolation, analog No
outputs
Dimensions
Required slots 1
Dimensions
Weights 1 kg

5/98 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Function modules
EXM 448
universal communication expansion module

■ Overview ■ Technical specifications


6DD1 607-0EA0
Supply voltages
Rated value
• DC 5 V Yes
Current consumption
Current consumption, typ. 0.8 A
Dimensions
Required slots 1
Dimensions
Weights 0.8 kg

■ Ordering data Order No.


5
EXM 448 6DD1 607-0EA0
universal communications
• Optional expansion module for the FM 458-1 DP basic expansion module
module
For fast communication, for
• For fast communication over PROFIBUS DP or SIMOLINK example, with drives; with free
• EXM 448: With vacant slot for a MASTERDRIVES option slot for MASTERDRIVES option
module module

Siemens ST 70 · 2009 5/99


© Siemens AG 2008

SIMATIC S7-400
Function modules
EXM 448-2
universal communication expansion module

■ Overview ■ Technical specifications


6DD1 607-0EA2
Supply voltages
Rated value
• DC 5 V Yes
Current consumption
Current consumption, typ. 0.6 A
Dimensions
Required slots 1
Dimensions
Weights 0.9 kg

5 ■ Ordering data Order No.


EXM 448-2 6DD1 607-0EA2
universal communications
• Optional plug-in expansion module for the FM 458-1 DP basic expansion module
module
For fast communication with
• For high-speed communication over up to 2 SIMOLINK inter- drives;
faces for constructing two SIMOLINK
• For coupling several FM 458-1 DP application modules in fiber-optic connections
synchronism with the sampling time FM 458-1 DP User Manual B7 6DD1 904-0AE1
English/German
B7: Subject to export regulations: AL: N and ECCN: EAR99H

5/100 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Function modules
Accessories for FM 458-1 DP

■ Overview SC64 interface cable ■ Overview SC63 interface cable

5
• For connecting the FM 458-1 DP to an SBxx or SU12 interface This cable is used to connect the SIMATIC TDC SM500
module peripheral (I/O) module or the SIMATIC S7-400 EXM 438-1
• To use the digital inputs of the FM 458-1 DP with interrupt expansion module to a SU13 interface module.
capability

■ Overview SC62 interface cable ■ Overview SB10 interface module

This cable is used to connect the SIMATIC TDC SM500 The interface module is used to connect 8 digital inputs or
peripheral module (I/O) or the SIMATIC S7-400 EXM 438-1 outputs.
expansion module to up to 5 interface modules SB10, SB60,
SB70, SB61 SB71 and/ or SU12.

Siemens ST 70 · 2009 5/101


© Siemens AG 2008

SIMATIC S7-400
Function modules
Accessories for FM 458-1 DP

■ Overview SB61 interface module ■ Overview SU12 interface module

5
It is used to connect 8 digital inputs with conversion from The interface module is used to connect 10 signals;
24/48 V DC to 24 V DC. there is no electronic conversion.

■ Overview SB71 interface module ■ Overview SU13 interface module

The interface module is used to connect 8 digital outputs with This interface module can be used to connect 50 signals;
conversion of the 24 V DC voltage on the module side to a max. there is no electronic conversion.
of 24/48 V DC/AC on the plant side using transistors.

5/102 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Function modules
Accessories for FM 458-1 DP

■ Technical specifications ■ Ordering data Order No.


Technical specifications SB10 interface module SC 64 interface cable 6DD1 684-0GE0
Number of digital inputs or outputs 8 for connection of FM 458-1 to the
serial port of a PG/PC
Electrical isolation No
SC62 interface cable 6DD1 684-0GC0
Max. cable cross-section 1.5 mm²
between the SM500 or EXM 438-1
Dimensions (W x H x D) in mm 45 x 130 x 156 module and a max. of 5 interface
Weight 0.3 kg moduls SB10, SB60, SB70, SB61,
SB71 and/or SU12, 2 m long
Technical specifications SB61 interface module
SC63 interface cable 6DD1 684-0GD0
Number of digital inputs for 8
between an SM500 or EXM 438-1
• Input voltage DC 24/48 V module and SU13 interface
Electrical isolation Yes, via optocoupler module, 2 m long

Max. cable cross-section 1.5 mm² SB10 interface module 6DD1 681-0AE2

Dimensions (W x H x D) in mm 45 x 130 x 156 8 digital inputs/outputs, 24 V DC

Weight 0.32 kg SB61 interface module


8 digital inputs, 24/48 V DC
6DD1 681-0EB3
5
Technical specifications SB71 interface module
Number of digital outputs 8 SB71 interface module 6DD1 681-0DH1

• Output voltage, max 24/48 V DC 8 digital outputs with transistors,


24/48 V DC
Output current, max. 40 mA, short-circuit proof
SU12 interface module 6DD1 681-0AJ1
Electrical isolation Yes, via optocoupler
with plug-in terminal, 10-pin
Max. cable cross-section 1.5 mm²
SU13 interface module 6DD1 681-0GK0
Dimensions (W x H x D) in mm 45 x 130 x 156
with screw-plug-in terminal
Weight 0.32 kg
Technical specifications SU12 interface module
Number of signal cables which can 10
be connected
Signal amplitude per signal, max. 60 V. 0.5 A
Electrical isolation No
Max. cable cross-section 1.5 mm²
Dimensions (W x H x D) in mm 45 x 130 x 156
Weight 0.28 kg
Technical specifications SU13 interface module
Number of signal cables which can 50
be connected
Signal amplitude per signal, max. 60 V, 0.5 A
Electrical isolation No
Max. cable cross-section 1.5 mm²
Dimensions (W x H x D) in mm 45 x 130 x 156
Weight 0.3 kg

Siemens ST 70 · 2009 5/103


© Siemens AG 2008

SIMATIC S7-400
Function modules
SIPLUS DCF 77 radio clock module

■ Overview ■ Technical specifications


Radio clock module SIPLUS
DCF 77
Radio frequency 77.5 Hz
Power supply DC 24 V (DC 20.4 ... 28. 8)
Power consumption, typ. 50 mA
Dimensions (W x H x D) 75 x 125 1) x 75
1) Additionally 25 mm (0.98 in) for heavy duty threaded joint and bending
radius for cables

■ Ordering data Order No.


SIPLUS DCF 77 radio clock B7 6AG1 057-1AA03-0AA0
module
For synchronizing SIMATIC

5
S7-200, S7-300 and S7-400 with
the official time of the DCF 77 time
signal transmitter of the
Physikalisch-Technische Bunde-
This module can be used to synchronize the real-time clock of sanstalt Braunschweig
the SIMATIC S7-200, S7-300 and S7-400 automation systems
with the official time of the DCF 77 time signal transmitter of the B7: Subject to export regulations: AL: N and ECCN: EAR99H
Physikalisch-Technische Bundesanstalt Braunschweig.
The time is received by means of a DCF receiver (antenna with
electronics) which is connected via two digital inputs on the
SIMATIC and SIPLUS together with a software driver included in
the scope of delivery (function block FB). The function blocks
are available on the Internet for downloading.
http://www.siemens.com/siplus – Support – Tools and
Downloads!

5/104 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Communication
CP 440

■ Overview ■ Technical specifications


6ES7 440-1CS00-0YE0
Supply voltages
Rated value
• DC 5 V Yes
• DC 24 V Yes
Current consumption
from backplane bus DC 5 V, 360 mA
max.
Current consumption/
power loss
Power loss, typ. 1.7 W
Memory
Type of storage
Memory requirements per
interface in CompactFlash Card
1 to 5 Kbytes for parameters 5
of S7-CPU
• For high-performance transmission of messages via point-to-
interfaces
point connections (high message rate)
• Physical interface: RS 422/RS 485 (X.27) Number of interfaces 1

• Up to 32 nodes interface physics, Yes


RS 422/RS 485 (X.27)
• Protocol implemented: ASCII, 3964 (R)
RS 422/485, cable length, 1 200 m
• Simple parameterization via a parameterization tool integrated shielded, max.
into STEP 7
Point-to-point
Integrated protocol driver
• 3964 (R) Yes
• ASCII Yes
Transmission speed, RS 422/485
• with 3964 (R) protocol, max. 115.2 kBit/s
• with ASCII protocol, max. 115.2 kBit/s
CPU/programming
Configuration software
• STEP 7 Yes; own parameter assignment
forms
Dimensions
Dimensions
• Width 25 mm
• Height 290 mm
• Depth 210 mm
Weights
• Weight, approx. 600 g

■ Ordering data Order No.


CP 440 communications 6ES7 440-1CS00-0YE0
processor
with one RS 422/485 (X.27)
interface
RS 422/485 connecting cable
for linking to SIMATIC S7
5m 6ES7 902-3AB00-0AA0
10 m 6ES7 902-3AC00-0AA0
50 m 6ES7 902-3AG00-0AA0

Siemens ST 70 · 2009 5/105


© Siemens AG 2008

SIMATIC S7-400
Communication
CP 441-1, CP 441-2

■ Overview
• For powerful, high-speed serial communication via point-to-
point connections
• 2 versions:
- CP 441-1 with 1 variable interface for simple point-to-point
connection
- CP 441-2 with 2 variable interfaces for powerful point-to-
point connection
• Plug-in interface modules for different transmission interfaces:
RS 232C (V.24) , 20 mA (TTY) or RS 422/RS 485 (X.27)
• Implemented protocols: ASCII, 3964 (R), printer drivers;
CP 441-2 additionally has RK 512 and customized protocols
(retrofittable)
• Simple parameterization via a parameterization tool integrated
into STEP 7

5
■ Technical specifications
6ES7 441-1AA04- 6ES7 441-2AA04- 6ES7 441-1AA04- 6ES7 441-2AA04-
0AE0 0AE0 0AE0 0AE0
Supply voltages Point-to-point
Rated value supported printers HP-Deskjet, HP-Deskjet,
HP-Laserjet, HP-Laserjet,
• DC 5 V Yes Yes IBM-Proprinter, IBM-Proprinter,
• DC 24 V Yes Yes user-defined user-defined
Current consumption Transmission speed, max. 38.4 kBit/s 115.2 kBit/s;
distributed on both
from backplane bus DC 5 V, 600 mA; without 600 mA; without interfaces
max. interface module interface module
Integrated protocol driver
Current consumption/
power loss • 3964 (R) Yes Yes
Power loss, typ. 0.3 W 0.3 W • ASCII Yes Yes
Memory • Printer Yes Yes
Type of storage • customer-specific drivers No Yes
reloadable
Memory requirements per 1 to 5 KB for param- 1 to 5 KB for param-
interface in CompactFlash eters; eters; • RK512 No Yes
Card of S7-CPU 0 to 55 KB for 0 to 55 KB for
message texts message texts; Transmission speed,
0 to 64 KB for 20 mA (TTY)
loadable drivers • with 3964 (R) protocol, 19.2 kBit/s 19.2 kBit/s
interfaces max.

Number of interfaces 1; variable 2; variable • with ASCII protocol, max. 19.2 kBit/s 19.2 kBit/s

Physical interface, Yes Yes • with printer driver, max., 19.2 kBit/s 19.2 kBit/s
20mA (TTY) • with RK 512 protocol, max. 19.2 kBit/s
interface physics, Yes Yes Transmission speed,
RS 232C (V.24) RS 422/485
interface physics, Yes Yes • with 3964 (R) protocol, 38.4 kBit/s 115.2 kBit/s
RS 422/RS 485 (X.27) max.
20mA (TTY), cable length, 1 000 m 1 000 m • with ASCII protocol, max. 38.4 kBit/s 115.2 kBit/s
shielded, max.
• with printer driver, max. 38.4 kBit/s 115.2 kBit/s
RS 232, cable length, 10 m 10 m
shielded, max. • with RK 512 protocol, max. 115.2 kBit/s
RS 422/485, cable length, 1 200 m 1 200 m Transmission speed, RS232
shielded, max. • with 3964 (R) protocol, 38.4 kBit/s 115.2 kBit/s
interface module max.
• 20 mA (TTY), 100 mA; 100 mA 300 mA at 5 V; • with ASCII protocol, max. 38.4 kBit/s 115.2 kBit/s
power consumption from from 5 V; 45 mA at 24 V • with printer driver, max., 38.4 kBit/s 115.2 kBit/s
5 V/24 V, max. 45 mA from 24 V
• with RK 512 protocol, max. 115.2 kBit/s
• RS 422/485 (X.27), 250 mA; from 5 V 300 mA
power consumption from
5 V, max.
• RS 232C (V.24), 100 mA; from 5V 300 mA
power consumption from
5 V, max.

5/106 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Communication
CP 441-1, CP 441-2

■ Technical specifications (continued)


6ES7 441-1AA04- 6ES7 441-2AA04- 6ES7 441-1AA04- 6ES7 441-2AA04-
0AE0 0AE0 0AE0 0AE0
CPU/programming Dimensions
Configuration software Dimensions
• STEP 7 Yes; own parameter Yes; own parameter • Width 25 mm 25 mm
assignment forms assignment forms
• Height 290 mm 290 mm
• Depth 210 mm 210 mm
Weights
• Weight, approx. 800 g; 720 g;
Interface module: Interface module:
100 g 100 g

■ Ordering data Order No. Order No.


5
CP 441-1 6ES7 441-1AA04-0AE0 RS 422/485 connecting cable
communications processor
5m 6ES7 902-3AB00-0AA0
With 1 variable interface for
interface submodules; including 10 m 6ES7 902-3AC00-0AA0
configuration package on CD 50 m 6ES7 902-3AG00-0AA0
CP 441-2 6ES7 441-2AA04-0AE0 Loadable drivers for CP 441-2
communications processor
MODBUS master (RTU format)
With 2 variable interfaces for
interface submodules; including • Single license 6ES7 870-1AA01-0YA0
configuration package on CD • Single license, without software 6ES7 870-1AA01-0YA1
Interface submodules or documentation
RS 232C (V.24) 6ES7 963-1AA00-0AA0 MODBUS slave (RTU format)
20 mA (TTY) 6ES7 963-2AA00-0AA0 • Single license 6ES7 870-1AB01-0YA0
RS 422/485 (X.27) 6ES7 963-3AA00-0AA0 • Single license, without software 6ES7 870-1AB01-0YA1
or documentation
RS 232 connecting cable
Data highway (DF1 protocol)
5m 6ES7 902-1AB00-0AA0
• Single license 6ES7 870-1AE00-0YA0
10 m 6ES7 902-1AC00-0AA0
• Single license, without software 6ES7 870-1AE00-0YA1
TTY connecting cable or documentation
5m 6ES7 902-2AB00-0AA0
10 m 6ES7 902-2AC00-0AA0
50 m 6ES7 902-2AG00-0AA0

Siemens ST 70 · 2009 5/107


© Siemens AG 2008

SIMATIC S7-400
Communication
CP 443-5 Basic

■ Overview
• Connection of the S7-400 to PROFIBUS
• Communication services:
- PG/OP communication
- S7 communication
- Open communication (SEND/RECEIVE)
- PROFIBUS FMS
• Time synchronization
• Easy programming and configuration over PROFIBUS
• Cross-network programming device communication through
S7 routing
• Can be easily integrated into the SIMATIC S7-400 system
• Modules can be replaced without the need for a PG
• SIMATIC H system operation for redundant S7 communication

5
'30 '36 )06 3*23 66
*B,.B;;B

■ Technical specifications
Order No. 6GK7 443-5FX02-0XE0 Order No. 6GK7 443-5FX02-0XE0
Product type description CP 443-5 BASIC Product type description CP 443-5 BASIC
Transfer rate Design, dimensions and weight
Transmission rate at Interface 1 Module format S7-400 compact module,
single width
• Minimum 9.6 kbit/s
• Width 25 mm
• Maximum 12 Mbit/s
• Height 290 mm
Interfaces
• Depth 210 mm
Version of electrical connection of 9-pin Sub-D socket (RS 485)
the PROFIBUS interface Net weight 700 g
Supply voltage Performance data
Type of supply voltage DC FMS function
Supply voltage 5V Number of possible connections in 48
the case of FMS connection, max.
Relative symmetrical tolerance at 5%
5 V DC Data volume of the variables
Current consumption • for READ job, max. 237 byte
Current consumed from backplane 1.2 A • for WRITE job, max. 233 byte
bus at 5 V DC, typical
Number of variables
Effective power loss
• Configurable from server to 512
Effective power loss 6.5 W FMS partner
Permitted ambient conditions • Loadable from server to 2640
FMS partner
Ambient temperature
S7 communication
• during operation 0 … +60 °C
Number of possible connections for 48
• during storage -40 … +70 °C S7 communication, max. 1)
• during transport -40 … +70 °C
Maximum relative humidity at 95%
25 °C during operation
1) depending on the CPU type

5/108 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Communication
CP 443-5 Basic

■ Technical specifications (continued)


Order No. 6GK7 443-5FX02-0XE0 Order No. 6GK7 443-5FX02-0XE0
Product type description CP 443-5 BASIC Product type description CP 443-5 BASIC
Open communication Multi-protocol operation
Number of possible connections for 32 Number of possible connections, 59
open communication by means of of which 2 reserved for PG/OP
SEND/RECEIVE blocks, max. 2) communication in the case of
multi-protocol operation, max.
Data volume as useful data for open 240 bytes
communication (SEND/RECEIVE)
per connection, max.
2)
also S5-compatible communication

■ Ordering data Order No. Order No.


CP 443-5 6GK7 443-5FX02-0XE0 PROFIBUS FastConnect
communications processor bus connector RS485
Communications processor for
connection of S7-400 to
With 90° cable outlet; insulation
displacement technology, max.
5
PROFIBUS, FMS, open communi- transmission rate 12 Mbit/s
cation, PG/OP and S7 communi-
cation; with electronic manual on • without PG interface 6ES7 972-0BA51-0XA0
CD-ROM • with PG interface 6ES7 972-0BB51-0XA0
STEP 7 Version 5.4 PROFIBUS bus connector IP20
Target system: With connection to
SIMATIC S7-300/-400, PPI, MPI, PROFIBUS
SIMATIC C7, SIMATIC WinAC
Requirement: • without PG interface 6ES7 972-0BA12-0XA0
Windows 2000 Prof./XP Prof. • with PG interface 6ES7 972-0BB12-0XA0
Delivery package:
German, English, French, PROFIBUS bus terminal 12M 6GK1 500-0AA10
Spanish, Italian; incl. 3.5" authori-
Bus terminal for connection
zation diskette, without documen-
of PROFIBUS stations up to
tation
12 Mbit/s with plug-in cable
• Floating license on CD 6ES7 810-4CC08-0YA5
• Rental license for 50 hours 6ES7 810-4CC08-0YA6
• Software Update Service 6ES7 810-4BC01-0YX2
on CD (requires current software
version)
• Upgrade Floating License 6ES7 810-4CC08-0YE5
3.x/4.x/5.x to V5.4; on CD
• Trial License STEP 7 V5.4; 6ES7 810-4CC08-0YA7
on CD, runs for 14 days

Siemens ST 70 · 2009 5/109


© Siemens AG 2008

SIMATIC S7-400
Communication
CP 443-5 Extended

■ Overview
• DP-V1 master connection of the S7-400 to PROFIBUS
• For setting up additional PROFIBUS DP lines
• Communication services:
- PROFIBUS DP
- PG/OP communication
- S7 communication
- Open communication (SEND/RECEIVE)
• Time synchronization
• Easy programming and configuration over PROFIBUS
• Cross-network programming device communication through
S7 routing
• Can be easily integrated into the SIMATIC S7-400 system
• Module replacement without PG
• SIMATIC H system operation for redundant S7 communication
5 or DP-Master communication
• Data record routing (PROFIBUS DP)
• Adding or modifying distributed I/O during operation
'30 '36 )06 3*23 66
*B,.B;;B

■ Technical specifications
Order No. 6GK7 443-5DX04-0XE0 Order No. 6GK7 443-5DX04-0XE0
Product type description CP 443-5 Extended Product type description CP 443-5 Extended
Transfer rate Design, dimensions and weight
Transmission rate at Interface 1 Module format S7-400 compact module,
• Minimum 9.6 kbit/s single width
• Maximum 12 Mbit/s • Width 25 mm
Interfaces • Height 290 mm
• Depth 210 mm
Version of electrical connection of 9-pin Sub-D socket (RS 485)
the PROFIBUS interface Net weight 700 g
Supply voltage Max. number of modules per CPU 14
Type of supply voltage DC Number of external DP lines per 10
central rack, max.
Supply voltage 5V
Performance data
Relative symmetrical tolerance 5%
at 5 V DC PROFIBUS DP
Current consumption Service as DP-Master DPV1 Yes
Current consumed from backplane 1.3 A Number of DP-Slaves 125
bus at 5 V DC, typical operable on DP-Master
Effective power loss Data volume
Effective power loss 6.5 W • of the address area of the inputs 4 Kibyte
as DP-Master overall
Permitted ambient conditions
• of the address area of the outputs 4 Kibyte
Ambient temperature as DP-Master overall
• during operation 0 … +60 °C • of the address area of the inputs 244 bytes
• during storage -40 … +70 °C per DP-Slave
• during transport -40 … +70 °C • of the address area of the outputs 244 bytes
per DP-Slave
Maximum relative humidity at 95%
25 °C during operation

5/110 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Communication
CP 443-5 Extended

■ Technical specifications (continued)


Order No. 6GK7 443-5DX04-0XE0 Order No. 6GK7 443-5DX04-0XE0
Product type description CP 443-5 Extended Product type description CP 443-5 Extended
S7 communication Multi-protocol operation
Number of possible connections 48 1) Number of active connections in
for S7 communication, max. multi-protocol operation
Open communication • without DP, max. 59
Number of possible connections for 32 • with DP, max. 55
open communication by means of
SEND/RECEIVE blocks, max. 2)
Data volume as useful data 240 bytes
for open communication (SEND/
RECEIVE) per connection, max.
1)
depending on the CPU type
2)
also S5-compatible communication

■ Ordering data Order No. Order No.


5
CP 443-5 Extended 6GK7 443-5DX04-0XE0 PROFIBUS FastConnect
communications processor bus connector RS485
for connection of the With 90° cable outlet; insulation
SIMATIC S7-400 to PROFIBUS, displacement technology, max.
Extended version for transmission rate 12 Mbit/s
PROFIBUS DP; with electronic
manual on CD-ROM • without PG interface 6ES7 972-0BA51-0XA0

STEP 7 Version 5.4 • with PG interface 6ES7 972-0BB51-0XA0

Target system: PROFIBUS bus connector IP20


SIMATIC S7-300/-400, With connection to PPI, MPI,
SIMATIC C7, SIMATIC WinAC PROFIBUS
Requirement:
Windows 2000 Prof./XP Prof. • without PG interface 6ES7 972-0BA12-0XA0
Delivery package: • with PG interface 6ES7 972-0BB12-0XA0
German, English, French,
Spanish, Italian; incl. 3.5" authori- PROFIBUS bus terminal 12M 6GK1 500-0AA10
zation diskette, without documen-
Bus terminal for connection
tation
of PROFIBUS nodes at up to
• Floating license on CD 6ES7 810-4CC08-0YA5 12 Mbit/s with connecting cable
• Rental license for 50 hours 6ES7 810-4CC08-0YA6
• Software Update Service 6ES7 810-4BC01-0YX2
on CD (requires current software
version)
• Upgrade Floating License 6ES7 810-4CC08-0YE5
3.x/4.x/5.x to V5.4; on CD
• Trial License STEP 7 V5.4; 6ES7 810-4CC08-0YA7
on CD, runs for 14 days

Siemens ST 70 · 2009 5/111


© Siemens AG 2008

SIMATIC S7-400
Communication
CP 443-1

■ Overview
• Connection of SIMATIC S7-400 to Industrial Ethernet
- 2 x RJ45 interface for 10/100 Mbit/s full/half duplex
connection with autosensing/autonegotiation and
autocrossover function
- Integrated real-time switch ERTEC with two ports
- Multi-protocol operation for ISO, TCP/IP, UDP and PROFINET
IO protocols
- Adjustable Keep Alive function
• Communication services:
- Open communication (ISO, TCP/IP and UDP)
- PROFINET IO Controller with real-time properties RT and IRT
- PG/OP communication: Across networks by means of S7
routing
- S7 communication
• Multicast for UDP

5
• Access protection by means of configurable access list
• Support for fail-safe programmable controllers in combination
with SIMATIC S7-400 CPU 416F-3 PN/DP
,62 7&3 31 053 ,7 ,35 3*23 66
• Module replacement without PG
8'3 • SIMATIC H system operation for redundant S7 communication
*B,.B;;B

• Configuration with STEP 7


• Diagnostic possibilities in STEP 7 and with web browser
• Automatic setting of the CPU clock by means of Industrial
Ethernet with NTP or SIMATIC procedure
• Integration of network management systems via SNMP
(MIB II diagnostic information)

5/112 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Communication
CP 443-1

■ Technical specifications
Order No. 6GK7 443-1EX20-0XE0 Order No. 6GK7 443-1EX20-0XE0
Product type description CP 443-1 Product type description CP 443-1
Transfer rate Performance data
Transmission rate at Interface 1 Open communication
• Minimum 10 Mbit/s Number of possible connections 64 2)
for open communication by means
• Maximum 100 Mbit/s of SEND/RECEIVE blocks, max. 3)
Interfaces Data volume as useful data for
Version of electrical connection to 2 x RJ45 (TP) open communication by means of
the Industrial Ethernet interface 1 SEND/RECEIVE blocks
Supply voltage • per ISO connection, max. 8 KB
Type of supply voltage DC • per ISO on TCP connection, max. 8 KB
Supply voltage 5V • per TCP connection, max. 8 KB

5
Relative symmetrical tolerance 5% • per UDP connection, max. 2 KB
at 5 V DC Number of possible connections 64
Current consumption for open communication by means
T blocks, max.
Current consumed from backplane 1.4 A
bus at 5 V DC, typical Data volume as useful data for
open communication by means
Effective power loss T-blocks
Effective power loss 8.6 W • per ISO on TCP connection, max. 1 452 bytes
Permitted ambient conditions S7 communication
Ambient temperature Number of possible connections
• during operation 0 … +60 °C for S7 communication

• during storage -40 … +70 °C • Maximum 128 1)

• during transport -40 … +70 °C • for PG connections, maximum 2

Maximum relative humidity 95% • for OP connections, maximum 30


at 25 °C during operation Multi-protocol operation
Design, dimensions and weight Number of active connections in 128
Module format S7-400 compact module, multi-protocol operation
single width Performance data,
• Width 25 mm PROFINET communication
as PN IO controller
• Height 290 mm
Number of PN IO devices operable 128
• Depth 210 mm on PROFINET IO controller
Net weight 700 g Number of external PN IO lines 4
with PROFINET per subrack
of which, PN IO IRT devices 32
Data volume
• as useful data for input variables 4 KB
as PROFINET IO controller
• as useful data for output variables 4 KB
as PROFINET IO controller
• as useful data for input variables 240 bytes
per PN IO device as PROFINET IO
controller
• as useful data for output variables 240 bytes
per PN IO device as PROFINET IO
controller
Configuration
Configuration software Yes
for full functional scope
STEP 7 V5.4 SP4 or higher
1) when using several CPUs
2)
depending on the CPU type
3)
also S5-compatible communication

Siemens ST 70 · 2009 5/113


© Siemens AG 2008

SIMATIC S7-400
Communication
CP 443-1

■ Ordering data Order No. Order No.


CP 443-1 A8 6GK7 443-1EX20-0XE0 SOFTNET-S7 Lean Edition 2007
communications processor for Industrial Ethernet
For connecting SIMATIC S7-400 up to 8 connections
to Industrial Ethernet through
TCP/IP, ISO and UDP; PROFINET • Single license for 1 installation B3 6GK1 704-1LW70-3AA0
IO Controller, integrated real-time • Software Update Service 6GK1 704-1LW00-3AL0
switch ERTEC with two ports; for 1 year,
2 x RJ45 interface; S7 communi- with automatic extension;
cation, open communication requirement: Current software
(SEND/RECEIVE) with FETCH/ version
WRITE, with and without
RFC 1006, DHCP, SNMP V2, • Upgrade from V6.4 B3 6GK1 704-1LW00-3AE0
diagnostics, multicast, access to 2007 Edition
protection over IP access list,
initialization over • Upgrade from V6.0, V6.1, V6.2 B3 6GK1 704-1LW00-3AE1
LAN 10/100 Mbit/s with electronic or V6.3 to 2007 Edition
manual on DVD S7-1613 Edition 2007
IE FC TP Standard Cable GP 2x2 6XV1 840-2AH10
5
Software for S7 and open commu-
4-core, shielded TP installation nication, incl. PG/OP communi-
cable for connection to IE cation, OPC server and NCM PC;
FC Outlet RJ45/ IE FC RJ45 Plug; up to 120 connections, runtime
PROFINET-compatible; with UL software, software and electronic
approval; sold by the meter manual on CD-ROM, license key
on USB stick, Class A, for 32-bit
FO Standard Cable GP (50/125) 6XV1 873-2A Windows XP Professional SP1, 2;
Standard cable, splittable, Windows 2003 Server SP1, R2,
UL approval, sold by the meter SP2, Windows Vista Business/
Ultimate; for
SCALANCE X204-2 6GK5 204-2BB10-2AA3 CP 1613/CP 1613 A2/CP 1623;
Industrial Ethernet switch German/English
Industrial Ethernet switches with
integral SNMP access, online • Single license for 1 installation B3 6GK1 716-1CB70-3AA0
diagnostics, copper cable • Software Update Service 6GK1 716-1CB00-3AL0
diagnostics and PROFINET for 1 year,
diagnostics for configuring line, with automatic extension;
star and ring topologies; requirement: Current software
four 10/100 Mbit/s RJ45 ports version
and two FO ports
• Upgrade S7-1613 from V6.4 B3 6GK1 716-1CB00-3AE0
IE FC RJ45 Plug 180 to 2007 Edition
RJ45 plug connector for Industrial B3 6GK1 716-1CB00-3AE1
• Upgrade S7-1613 from V6.0,
Ethernet with a rugged metal
V6.1, V6.2 or V6.3 to S7-1613
housing and integrated insulation
Edition 2007
displacement contacts for
connecting Industrial Ethernet FC STEP 7 Version 5.4
installation cables; with 180°
cable outlet; for network compo- Target system:
nents and CPs/CPUs with SIMATIC S7-300/-400,
Industrial Ethernet interface SIMATIC C7, SIMATIC WinAC
Requirement:
• 1 pack = 1 unit 6GK1 901-1BB10-2AA0 Windows 2000 Prof./XP Prof.
• 1 pack = 10 units 6GK1 901-1BB10-2AB0 Delivery package:
German, English, French,
• 1 pack = 50 units 6GK1 901-1BB10-2AE0 Spanish, Italian;
SOFTNET Edition 2007 incl. 3.5" authorization diskette,
for Industrial Ethernet without documentation
Software for S7 and open commu- • Floating license on CD 6ES7 810-4CC08-0YA5
nication, incl. OPC server, PG/OP
communication and NCM PC, • Rental license for 50 hours 6ES7 810-4CC08-0YA6
runtime software, software and • Software Update Service on CD 6ES7 810-4BC01-0YX2
electronic manual on CD-ROM, (requires current software
license key on USB stick, Class A, version)
for 32-bit Windows XP Profes-
sional SP1, 2, Windows 2003 • Upgrade Floating License 6ES7 810-4CC08-0YE5
Server SP1, R2, SP2, Windows 3.x/4.x/5.x to V5.4; on CD
Vista Business/Ultimate; • Trial License STEP 7 V5.4; 6ES7 810-4CC08-0YA7
German/English on CD, runs for 14 days
SOFTNET-S7 Edition 2007
for Industrial Ethernet
up to 64 connections
• Single license for 1 installation B3 6GK1 704-1CW70-3AA0
• Software Update Service 6GK1 704-1CW00-3AL0
for 1 year, with automatic
extension; requirement: Current
software version
• Upgrade from V6.4 B3 6GK1 704-1CW00-3AE0
to 2007 edition
• Upgrade from V6.0, V6.1, V6.2 B3 6GK1 704-1CW00-3AE1 A8: Subject to export regulations: AL: N and ECCN: 5A991X
or V6.3 to 2007 Edition B3: Subject to export regulations: AL: N and ECCN: 5D992B1

5/114 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Communication
CP 443-1 Advanced

■ Overview
• Connection of SIMATIC S7-400 to Industrial Ethernet
- Multi-protocol operation for ISO, TCP/IP, UDP and PROFINET
IO protocols
- Adjustable Keep Alive function
• Two separate interfaces (integrated network separation):
- Gigabit interface with an RJ45 connection with
10/100/1000 Mbit/s full/half duplex with auto-sensing
functionality
- PROFINET interface with four RJ45 connections with
10/100 Mbit/s full/half duplex with auto-sensing and auto-
crossover functionality via integrated 4-port switch
• Communication services via both interfaces
- Open communication (ISO, TCP/IP and UDP), Multicast with
UDP, incl. routing between two interfaces
- PG/OP communication:
Cross-network by means of S7 routing
- S7 communication (client, server, multiplexing) incl. routing
between both interfaces
5
- IT communication:
HTTP communication allows access to process data via own
,62 7&3 31 053 ,7 ,35 3*23 66
8'3 web sites;
e-mail client function, sending of e-mails with authentication
*B,.B;;B

directly from the user program;


FTP communication allows program-controlled FTP client
communication;
access to data blocks via FTP servers
• Communication services via PROFINET interface
- PROFINET IO Controller with real-time properties (RT and IRT)
- PROFINET CBA
- IP address assignment via DHCP, simple PC tool or via the
user program (e.g. HMI)
- Support of prioritized start-ups of PROFINET IO Devices
• Configuration with STEP 7
• Access protection by means of a configurable IP access list
• Module replacement without PG;
all information is stored on the C-PLUG (also file system for IT
functions)
• Extensive diagnostic functions for all modules in the rack
• Integration into network management systems through the
support of SNMP V1 MIB-II
• Operation in SIMATIC H system for redundant S7 communi-
cation
• Operation in fail-safe applications (PROFIsafe) together with
SIMATIC S7-400 CPU 416F

Siemens ST 70 · 2009 5/115


© Siemens AG 2008

SIMATIC S7-400
Communication
CP 443-1 Advanced

■ Technical specifications
Order No. 6GK7 443-1GX20-0XE0 Order No. 6GK7 443-1GX20-0XE0
Product type description CP 443-1 Advanced Product type description CP 443-1 Advanced
Transfer rate Data volume as useful data for
open communication by means of
Transmission rate at Interface 1 SEND/RECEIVE blocks
• Minimum 10 Mbit/s • per ISO connection, max. 8 KB
• Maximum 1000 Mbit/s • per ISO on TCP connection, max. 8 KB
Transmission rate at Interface 2 • per TCP connection, max. 8 KB
• Minimum 10 Mbit/s • per UDP connection, max. 2 KB
• Maximum 100 Mbit/s • for each e-mail connection, max. 2 KB
Interfaces Number of possible connections 64 2)
Electrical connection version for open communication by means
of T blocks, max.
• at Industrial Ethernet interface 1 1 x RJ45 (TP)

5
Data volume as useful data for
• at Industrial Ethernet interface 2 4 x RJ45 (TP) open comm. by means of T-blocks
Slot version of the swap medium C-PLUG • per ISO on TCP connection, max. 1 452 bytes
Supply voltage S7 communication
Type of supply voltage DC Number of possible connections
Supply voltage 5V for S7 communication

Relative symmetrical tolerance 5% • Maximum 128


at 5 V DC • for PG connections, maximum 2
Current consumption • for OP connections, maximum 30
Current consumed from backplane 1.34 A Multi-protocol operation
bus at 5 V DC, typical
Number of active connections in 128
Effective power loss multi-protocol operation
Effective power loss 7.25 W IT functions
Permitted ambient conditions Number of possible connections
Ambient temperature • as client by means of FTP, max. 20
• during operation 0 … +60 °C • as server
• during storage -40 … +70 °C - by means of FTP, max. 10
• during transport -40 … +70 °C - by means of HTTP, max. 4
Maximum relative humidity 95% Memory capacity of the user
at 25 °C during operation memory
Design, dimensions and weight • as Flash memory file system 30 MB
Module format S7-400 compact module, • as RAM 16 MB
single width • additionally buffered as RAM 512 KB
• Width 25 mm via central backup battery
• Height 290 mm Performance data,
• Depth 217 mm PROFINET communication
as PN IO controller
Net weight 750 g
Number of PN IO devices operable 128
Performance data on PROFINET IO controller
Open communication • of which, PN IO IRT devices 32
Number of possible connections 64 2) Number of external PN IO lines 4
for open communication by means with PROFINET per subrack
of SEND/RECEIVE blocks, max. 1)
Data volume
• as useful data for input variables 4 KB
as PROFINET IO controller
• as useful data for output variables 4 KB
as PROFINET IO controller
1) also S5-compatible communication
2)
depending on the CPU type

5/116 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Communication
CP 443-1 Advanced

■ Technical specifications (continued)


Order No. 6GK7 443-1GX20-0XE0 Order No. 6GK7 443-1GX20-0XE0
Product type description CP 443-1 Advanced Product type description CP 443-1 Advanced
Data volume (continued) Number of remote
interconnections
• as useful data for input variables 240 bytes
per PN IO device as • with input variables 250
PROFINET IO controller in case of cyclic transmission
with PROFINET CBA, max.
• as useful data for output variables 240 bytes
• with output variables 250
per PN IO device as PROFINET IO
in case of cyclic transmission
controller
with PROFINET CBA, max.
Performance data
Data volume
PROFINET CBA
• as useful data for remote inter- 2 000 bytes
Number of remote interconnection 64 connections with input variables
partners in the case of PROFINET in the case of cyclic transmission
CBA with PROFINET CBA, max.

5
Total number of interconnections in 600 • as useful data for remote inter- 2 000 bytes
the case of PROFINET CBA connections with output variables
in the case of cyclic transmission
Data volume with PROFINET CBA, max.
• as useful data for digital inputs in 8 192 bytes Performance data
the case of PROFINET CBA, max. PROFINET CBA, HMI variables via
• as useful data for digital outputs in 8 192 bytes PROFINET (acyclic)
the case of PROFINET CBA, max. Number of HMI stations with login 3
• as useful data for arrays and data capability for HMI variables in the
types case of acyclic transmission with
PROFINET CBA
- in case of acyclic transmission 8 192 bytes
with PROFINET CBA, max. Send cycle of the HMI variables in 500 ms
the case of acyclic transmission
- in case of cyclic transmission 250 bytes
with PROFINET CBA
with PROFINET CBA, max.
- in case of local interconnection 2 400 bytes Send cycle of the HMI variables in 200
with PROFINET CBA, max. the case of acyclic transmission
with PROFINET CBA max.
Performance data PROFINET
Data volume as useful data for 8 192 bytes
CBA, remote interconnections
HMI variables in the case of
with acyclic transmission
acyclic transmission with
Send cycle of the remote intercon- 100 ms PROFINET CBA max.
nections in the case of acyclic
Performance data
transmission with PROFINET CBA
PROFINET CBA, device-internal
Number of remote interconnections
interconnections Number of interconnections in the 300
• with input variables 150 case of PROFINET CBA, max
in case of acyclic transmission Data volume of internal inter- 2 400 bytes
with PROFINET CBA, max. connections in the case of
• with output variables 150 PROFINET CBA, max
in case of acyclic transmission Performance data
with PROFINET CBA, max. PROFINET CBA, interconnections
Data volume with constants

• as useful data for remote inter- 81 92 bytes Number of interconnections 500


connections with input variables with constants in the case of
in the case of acyclic transmission PROFINET CBA, max
with PROFINET CBA Data volume as useful data 4 000 bytes
for interconnections with constants
• as useful data for remote inter- 8 192 bytes in the case of PROFINET CBA, max
connections with output variables
in the case of acyclic transmission Performance data
with PROFINET CBA PROFINET CBA, PROFIBUS proxy
functionality
Performance data PROFINET
CBA, remote interconnections Product function in the case of No
with cyclic transmission PROFINET CBA, PROFIBUS proxy
Send cycle of the remote inter- functionality
10 ms
connections in the case of cyclic Number of accesses to 32
transmission with PROFINET CBA S7-extended variables in case of
PROFINET CBA max.
Configuration
Configuration software for full Yes
functional scope STEP 7 V5.4 SP4
or higher

Siemens ST 70 · 2009 5/117


© Siemens AG 2008

SIMATIC S7-400
Communication
CP 443-1 Advanced

■ Ordering data Order No. Order No.


CP 443-1 Advanced SOFTNET-S7 Lean Edition 2007
communications processor for Industrial Ethernet
For the connection of SIMATIC up to 8 connections
S7-400 to Industrial Ethernet;
PROFINET IO Controller with RT • Single License for 1 installation B3 6GK1 704-1LW70-3AA0
and IRT, MRP, PROFINET CBA; • Software Update Service 6GK1 704-1LW00-3AL0
TCP/IP, ISO and UDP; for 1 year,
S7 communication, with automatic extension;
open communication requirement:
(SEND/RECEIVE) with Current software version
FETCH/WRITE, with and without
RFC 1006, diagnostic expan- • Upgrade from V6.4 6GK1 704-1LW00-3AE0
sions, multicast, clock synchroni- to 2007 edition
zation by means of SIMATIC • Upgrade from V6.0, V6.1, V6.2 B3 6GK1 704-1LW00-3AE1
procedure or NTP, access or V6.3 to 2007 Edition
protection by means of IP access
list, FTP client/server, HTTP S7-1613 2007 Edition
server, HTML diagnostics, SNMP,
5
Software for S7 and open commu-
DHCP, e-mail, data storage on
nication, incl. PG/OP communi-
C-PLUG;
cation, OPC server and NCM PC;
PROFINET connection: 4 x RJ45
up to 120 connections, runtime
(10/100 Mbit/s) via switch;
software, software and electronic
Gigabit connection:
manual on CD-ROM, license key
1 x RJ45 (10/100/1000 Mbit/s);
on USB stick, Class A, for 32-bit
with electronic manual on DVD
Windows XP Professional SP1, 2;
• For use with SIMATIC S7-400 A8 6GK7 443-1GX20-0XE0 Windows 2003 Server SP1, R2,
CPU, V5.2 or higher; SP2, Windows Vista Business/
Ultimate; for
C-PLUG 6GK1 900-0AB00 CP 1613/CP 1613 A2/CP 1623;
Swap medium for simple German/English
replacement of devices in the • Single License for 1 installation B3 6GK1 716-1CB70-3AA0
event of a fault; for storing config-
uration or engineering and appli- • Software Update Service 6GK1 716-1CB00-3AL0
cation data; can be used for for 1 year,
SIMATIC NET products with with automatic extension;
C-PLUG slot requirement:
Current software version
SOFTNET Edition 2007
for Industrial Ethernet • Upgrade S7-1613 from V6.4 B3 6GK1 716-1CB00-3AE0
to S7-1613 2007 Edition
Software for S7 and open commu-
nication, incl. OPC server, PG/OP • Upgrade S7-1613 from V6.0, B3 6GK1 716-1CB00-3AE1
communication and NCM PC, V6.1, V6.2 or V6.3 to S7-1613
runtime software, software and 2007 Edition
electronic manual on
IE FC RJ45 Plug 180
CD-ROM, license key on USB
stick, Class A, for 32-bit RJ45 plug connector for Indus-
Windows XP Professional SP1, 2, trial Ethernet with a rugged metal
Windows 2003 Server SP1, R2, housing and integrated insulation
SP2; Windows Vista displacement contacts for
Business/Ultimate; connecting Industrial Ethernet FC
German/English installation cables; with 180°
cable outlet; for network compo-
SOFTNET-S7 Edition 2007
nents and CPs/CPUs with
for Industrial Ethernet
Industrial Ethernet interface
up to 64 connections
• 1 pack = 1 unit 6GK1 901-1BB10-2AA0
• Single License for 1 installation B3 6GK1 704-1CW70-3AA0
• 1 pack = 10 units 6GK1 901-1BB10-2AB0
• Software Update Service 6GK1 704-1CW00-3AL0
• 1 pack = 50 units 6GK1 901-1BB10-2AE0
for 1 year,
with automatic extension;
requirement: Current software
version
• Upgrade from V6.4 6GK1 704-1CW00-3AE0
to 2007 edition
• Upgrade from V6.0, V6.1, V6.2 B3 6GK1 704-1CW00-3AE1
or V6.3 to 2007 Edition

A8: Subject to export regulations: AL: N and ECCN: 5A991X


B3: Subject to export regulations: AL: N and ECCN: 5D992B1

5/118 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Communication
CP 443-1 Advanced

■ Ordering data (continued) Order No. Order No.


IE FC RJ45 Plug 4 x 2 STEP 7 Version 5.4
RJ45 plug connector for Indus- Target system:
trial Ethernet (10/100/1000 Mbit/s) SIMATIC S7-300/-400,
with a rugged metal housing and SIMATIC C7, SIMATIC WinAC
integrated insulation Requirement:
displacement contacts for Windows 2000 Prof./XP Prof.
connecting Industrial Ethernet FC Delivery package:
installation cables; 180° cable German, English, French,
outlet; for network components Spanish, Italian;
and CPs/CPUs with Industrial incl. 3.5" authorization diskette,
Ethernet interface without documentation
• 1 pack = 1 unit 6GK1 901-1BB11-2AA0 • Floating license on CD 6ES7 810-4CC08-0YA5
• 1 pack = 10 units 6GK1 901-1BB11-2AB0 • Rental license for 50 hours 6ES7 810-4CC08-0YA6
• 1 pack = 50 units 6GK1 901-1BB11-2AE0 • Software Update Service on CD 6ES7 810-4BC01-0YX2
(requires current software
SCALANCE X204-2 6GK5 204-2BB10-2AA3 version)
Industrial Ethernet switch
with four 10/100 Mbit/s RJ45 ports
and two fiber-optic ports
• Upgrade Floating License
3.x/4.x/5.x to V5.4; on CD
6ES7 810-4CC08-0YE5
5
• Trial License STEP 7 V5.4; 6ES7 810-4CC08-0YA7
Industrial Ethernet Switch 6GK5 308-2FL00-2AA3 on CD, runs for 14 days
SCALANCE X308-2
SIMATIC iMap V3.0
2 x 1000 Mbit/s multimode fiber-
optic ports (SC sockets), for configuring
1 x 10/100/1000 Mbit/s RJ45 port, PROFINET CBA,
7 x 10/100 Mbit/s RJ45 ports;
for glass fiber-optic cables Requirement:
(multimode) up to a max. 750 m. Windows 2000 Prof.
with Service Pack 4 or later or
Windows XP Prof. with
Service Pack 1 or later or
Windows 2003 Server
with Service Pack 1 or later;
on PG or PC with Pentium
processor, min. 1 GHz;
STEP 7 V5.3 or later with
Service Pack 3,
PN OPC Server V6.3 or later
Type of supply:
German, English,
with electronic documentation
• Single License B3 6ES7 820-0CC04-0YA5
• Software Update Service B3 6ES7 820-0CC01-0YX2
• Upgrade to V3.0, B3 6ES7 820-0CC04-0YE5
Single License

B3: Subject to export regulations: AL: N and ECCN: 5D992B1

Siemens ST 70 · 2009 5/119


© Siemens AG 2008

SIMATIC S7-400
Modules for SIMATIC S7-400H
Y link for S7-400H

■ Overview
• Transceiver for the transition from a redundant PROFIBUS DP
master system to a single-channel PROFIBUS DP master
system
• To connect devices with a single PROFIBUS DP interface to
the redundant PROFIBUS DP master system of the SIMATIC
S7-400H

5
■ Technical specifications
6ES7 153-2BA02-0XB0 6ES7 153-2BA02-0XB0
Supply voltages 1st interface
Rated value DP slave
• Permissible range (ripple 20.4 V • GSD file SI04801.GSG
included), lower limit (DC)
CPU/programming
• permissible range (ripple 28.8 V
included), upper limit (DC) Configuration software

Power supply and voltage • STEP 7 Yes; STEP 7 / COM PROFIBUS /


jumpering non-Siemens tools via GSD file

• Mains/voltage failure 20 ms Time stamping


jumpering Accuracy 1 ms; 1ms at up to 8 modules;
Voltages and currents 10ms at up to 12 modules

external protection for supply 2.5 A Number of stampable digital 128; Max. 128 signals / station;
cables (recommendation) inputs, max. max. 32 signals / slot

Current consumption Time format RFC 1119

Inrush current, typ. 3A Time resolution 0.466 ns

I²t 0.1 A²s Time stamp on signal change Yes

Current consumption, max. 600 mA Environmental requirements

Power loss, typ. 5.5 W Operating termperature

Address area • min. 0 °C

Adressing volume • max. 60 °C

• Outputs 244 byte Air pressure

• Inputs 244 byte • Operating height above sea 3.000 m


level, max.
Hardware config.
Degree and class of protection
Number of modules per DP 12
slave interface, max. • IP 20 Yes

interfaces General information

PROFIBUS DP, Output current, 70 mA Vendor identification (VendorID) 801E


max. Dimensions
interface physics, RS 485 Yes Dimensions
PROFIBUS DP Width 40 mm
Transmission procedure RS 485 Height 125 mm
Transmission speed, max. 12 MBit/s Depth 117 mm
Node addresses 1...125 Weights
SYNC capability Yes Weight, approx. 360 g
FREECE capability Yes
direct data exchange Yes; Sender
(cross traffic)

5/120 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Modules for SIMATIC S7-400H
Y link for S7-400H

■ Technical specifications (continued) ■ Ordering data Order No.


6ES7 197-1LB00-0XA0 For use with STEP 7 from V5.4 or
PCS 7 from V7.0:
System
Y link B7 6ES7 197-1LA04-0XA0
Demands on DP master system
For connecting single-channel DP
• Length of parameter 244 byte slaves to SIMATIC S7-400H;
assignment message consisting of
Supply voltages Two IM 153 interface modules
(6ES7 153-2BA02-0XB0),
Description via bus module One Y coupler
Protocols (6ES7 197-1LB00-0XA0),
One BM IM/IM bus module
PROFIBUS DP protocol Yes (6ES7 195-7HD80-0XA0),
One BM Y coupler bus module
PROFIBUS DP
(6ES7 654-7HY00-0XA0)
Properties of the lower level DP
For use with PCS 7 V6.1 SP1
master systems
Y link B7 6ES7 197-1LA11-0XA0
• Transmission speed, max. 12 MBit/s; 45.45 Kbit/s to 12 Mbit/s
• Termination of lower-level
DP master system
Active terminating resistor
(Bus Terminator)
For connecting single-channel DP
slaves to SIMATIC S7-400H;
5
consisting of
• Use of OLM/OBT Yes Two IM 153 interface modules
(6ES7 153-2BA82-0XB0),
• Use of RS 485 repeaters, max. 9 One Y coupler
• Number of DP slaves, max. 31; 64 when using RS 485 repeaters (6ES7 197-1LB00-0XA0),
or OLM/OBT One BM IM/IM bus module
(6ES7 195-7HD80-0XA0),
Status information/alarms/ One BM Y coupler bus module
diagnostics (6ES7 654-7HY00-0XA0)
Status indicator No Accessories
Alarms Mounting rail
• Alarms No For assembling the Y link with
Diagnoses active bus modules

• Diagnostic functions Yes • Length 483 mm 6ES7 195-1GA00-0XA0

Isolation • Length 530 mm 6ES7 195-1GF30-0XA0

to lower-level DP master system Yes


Dimensions
Dimensions
• Width 40 mm
• Height 125 mm
• Depth 130 mm
Weights
• Weight, approx. 200 g
B7: Subject to export regulations: AL: N and ECCN: EAR99H

Siemens ST 70 · 2009 5/121


© Siemens AG 2008

SIMATIC S7-400
Modules for SIMATIC S7-400F/FH
IM 153-1/153-2

■ Overview
IM 153-1 Standard
The IM 153-1 is one reasonably priced version that is best suited
for most applications in the manufacturing environment. It
permits the use of up to eight S7-300 I/O modules.
IM 153-2 High Feature
For higher requirements in manufacturing technology, such as
the use of F-technology or the highest performance in
conjunction with clock synchronization, the IM 153-2 High
Feature is available. This IM is also designed for use with the
PCS 7 in the field of manufacturing applications. This IM can be
redundantly used and supports typical functions as they are
required in the control field. These include, for example, clock
synchronization or time stamping with an accuracy of up to
1 ms.

5 IM 153-2 High Feature FO


The High Feature version (with reduced scope of services) is
also available as an FO version. This permits fiber optic cables
The ET 200M system with various interface modules is available
to be connected in the POF or the PCF, and is therefore particu-
for the decentralized use of S7-300 I/O modules. Depending on
larly well suited for use in the heavily EMC-charged areas.
the application purpose, the best suited IM in terms of costs and
functions can be selected:

■ Technical specifications
6ES7 153-1AA03-0XB0 6ES7 153-2BA02-0XB0 6ES7 153-2BA82-0XB0 6ES7 153-2BB00-0XB0
Power supply
Input current
• Rated value at DC 24 V 625 mA
Output voltage
• Rated value, DC 5 V Yes Yes Yes
Output current
• for backplane bus (DC 5 V), 1A 1.5 A 1A
max.
Supply voltages
Rated value
• DC 24 V Yes Yes Yes
• Permissible range (ripple 20.4 V 20.4 V 20.4 V 20.4 V
included), lower limit (DC)
• permissible range (ripple 28.8 V 28.8 V 28.8 V 28.8 V
included), upper limit (DC)
external protection for supply not necessary 2.5A 2.5A not necessary
cables (recommendation)
Power supply and voltage
jumpering
• Mains/voltage failure 5 ms 20 ms 20 ms
jumpering
Current consumption
Current consumption, max. 350 mA; At 24 V DC 600 mA 600 mA 500 mA; At 24 V DC
Inrush current, typ. 2.5 A 3A 3A 3.5 A
I²t 0.1 A²s 0.1 A²s 0.1 A²s 0.1 A²s
Current consumption/
power loss
Power loss, typ. 3W 5.5 W 5.5 W 4.5 W

5/122 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Modules for SIMATIC S7-400F/FH
IM 153-1/153-2

■ Technical specifications (continued)


6ES7 153-1AA03-0XB0 6ES7 153-2BA02-0XB0 6ES7 153-2BA82-0XB0 6ES7 153-2BB00-0XB0
Address area
Adressing volume
• Outputs 128 byte 244 byte 244 byte 128 byte
• Inputs 128 byte 244 byte 244 byte 128 byte
Hardware config.
Number of modules per DP 8 12 12 8
slave interface, max.
Communication functions
Bus protocol/ PROFIBUS DP to EN 50170 PROFIBUS DP to EN 50170 PROFIBUS DP PROFIBUS DP to EN 50170
transmission protocol
interfaces
PROFIBUS DP, Output current, 90 mA 70 mA 70 mA Not applicable
max.
interface physics, RS 485 Yes Yes Yes No
5
interface physics, LWL No No No Yes
Connection point
PROFIBUS DP 9-pin sub D socket 9-pin SUB-D 9-pin SUB-D optical, 2 x duplex sockets
PROFIBUS DP
Transmission procedure RS 485 RS 485 RS 485 LWL, wavelength 660 nm
Transmission speed, max. 12 MBit/s 12 MBit/s 12 MBit/s 12 MBit/s; 9.6 / 19.2 /
45.45 / 93.75 / 187.5 /
500 Kbit/s; 1.5 / 12 Mbit/s
Node addresses 1 to 125 permitted 1 to 125 permitted 1.125 1 to 125 permitted
automatic detection of Yes Yes Yes 1 to 125 permitted
transmission speed
SYNC capability Yes Yes Yes Yes
FREECE capability Yes Yes Yes Yes
direct data exchange Yes; Sender Yes; Sender Yes Yes; Sender
(cross traffic)
1st interface
DP slave
• GSD file (for DPV1) SIEM801D.GSD; SI04801.GSG SI0480E.GSG (for DPV1) SIEM8071.GSD;
SI01801D.GSG SI018071.GSG
(for IM 153-2AB0x);
SI028071.GSG
(for IM 153-2BB0x)
• automatic baud rate search Yes Yes Yes Yes
CPU/programming
Configuration software
• STEP 7 STEP 7 / COM PROFIBUS / Yes; STEP 7 / Yes Yes; STEP 7 /
non-Siemens tools via GSD COM PROFIBUS / non- COM PROFIBUS / non-
file Siemens tools via GSD file Siemens tools via GSD file
Time stamping
Accuracy 1 ms; 1ms at up to 1 ms; 1ms at up to 10 ms; 10 ms / 3 ms
8 modules; 10ms at up to 8 modules; 10ms at up to
12 modules 12 modules
Number of message buffers 15
Messages per message buffer 20
Number of stampable digital 128; Max. 128 signals / 128; 128 signals / station; 128
inputs, max. station; max. 32 signals / max. 32 signals / slot
slot
Time format RFC 1119 RFC 1119 Internet (ISP)

Siemens ST 70 · 2009 5/123


© Siemens AG 2008

SIMATIC S7-400
Modules for SIMATIC S7-400F/FH
IM 153-1/153-2

■ Technical specifications (continued)


6ES7 153-1AA03-0XB0 6ES7 153-2BA02-0XB0 6ES7 153-2BA82-0XB0 6ES7 153-2BB00-0XB0
Time resolution 0.466 ns 0.466 ns 1 ms
Time interval for transmitting the 1 000 ms
message buffer if a message is
present
Time stamp on signal change rising / falling edge as Yes rising / falling edge as
signal entering or exiting signal entering or exiting
Isolation
Isolation checked with Isolation voltage 500 V Isolation voltage 500 V 500 V DC Isolation voltage 500 V
Environmental requirements
Operating termperature
• min. 0 °C 0 °C -25 °C 0 °C
• max. 60 °C 60 °C 60 °C 60 °C

5 Air pressure
• Operating height above sea 3 000 m 3 000 m 3 000 m 3 000 m
level, max.
Degree of protection
IP 20 Yes Yes Yes Yes
General information
Vendor identification (VendorID) 801Dh 801E 801E 8071h
Dimensions
Dimensions
• Width 40 mm 40 mm 40 mm 40 mm
• Height 125 mm 125 mm 125 mm 125 mm
• Depth 117 mm 117 mm 117 mm 117 mm
Weights
• Weight, approx. 360 g 360 g 360 g 360 g

6ES7 195-7HD10-0XA0 6ES7 195-7HA00-0XA0 6ES7 195-7HB00-0XA0 6ES7 195-7HC00-0XA0


Accessories
belongs to product ET 200M
Dimensions
Weights
• Weight, approx. 133 g 111 g 140 g 127 g

5/124 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Modules for SIMATIC S7-400F/FH
IM 153-1/153-2

■ Ordering data Order No. Order No.


IM 153-1 interface module Accessories
Slave interface for connecting an PROFIBUS bus connector
ET 200M to PROFIBUS DP
• 90° outgoing cable, terminating 6ES7 972-0BA51-0XA0
• Standard temperature range 6ES7 153-1AA03-0XB0 resistor with disconnecting
function, without PG connection
IM 153-2 interface module socket, up to 12 Mbit/s,
Slave interface for connecting an FastConnect
ET 200M to PROFIBUS DP; also • 90° outgoing cable, terminating 6ES7 972-0BB51-0XA0
for use in redundant systems resistor with disconnecting
• High Feature 6ES7 153-2BA02-0XB0 function, with PG connection
socket, up to 12 Mbit/s,
• High Feature with extended 6ES7 153-2BA82-0XB0 FastConnect
temperature range
SIMATIC DP DIN rail for
• Fiber optic 6ES7 153-2BB00-0XB0 ET 200M
Active IM 153 /IM 153 6ES7 195-7HD10-0XA0 For insertion of up to 5 bus
bus module modules for
For two IM 153-2 High Feature
modules for designing redundant
• Length: 483 mm (19“) 6ES7 195-1GA00-0XA0 5
systems • Length: 530 mm 6ES7 195-1GF30-0XA0
Bus module for ET 200M SIMATIC S7-300 DIN rail
• To accommodate a power 6ES7 195-7HA00-0XA0 • Length: 160 mm 6ES7 390-1AB60-0AA0
supply and an IM 153 module for • Length: 480 mm (19“) 6ES7 390-1AE80-0AA0
the hot-swapping function
during RUN time including bus • Length: 530 mm 6ES7 390-1AF30-0AA0
module cover
• Length: 830 mm 6ES7 390-1AJ30-0AA0
• To accommodate two 40-mm 6ES7 195-7HB00-0XA0
wide I/O modules for the hot- • Length: 2,000 mm 6ES7 390-1BC00-0AA0
swapping function S7 Manual Collection B3 6ES7 998-8XC01-8YE0
• To accommodate one 80-mm 6ES7 195-7HC00-0XA0 Electronic manuals on DVD,
wide I/O module for the hot- multi-language:
swapping function S7-200, TD 200, S7-300, C7,
ET 200M redundancy bundle 6ES7153-2AR03-0XA0 S7-400, STEP 7, Engineering
Tools, Runtime Software, SIMATIC
Comprising two IM 153-2 DP (Distributed I/O), SIMATIC
High Feature modules and one HMI (Human Machine Interface),
IM 153/IM 153 bus module SIMATIC NET (Industrial Commu-
nication)
S7 Manual Collection update B3 6ES7 998-8XC01-8YE2
service for 1 year
Scope of delivery:
Current DVD "S7 Manual
Collection" and the three subse-
quent updates
B3: Subject to export regulations: AL: N and ECCN: 5D992B1

Siemens ST 70 · 2009 5/125


© Siemens AG 2008

SIMATIC S7-400
Modules for SIMATIC S7-400F/FH
SIPLUS IM 153-1/153-2

■ Overview
• For connecting ET 200M as a slave to PROFIBUS DP (via
copper conductors)
• IM 153-2 also for use in redundant PROFIBUS DP systems
with S7-400H, software redundancy and S5-155H
• With time stamp functionality and time synchronization
• Suitable for isochronous mode

5
SIPLUS IM 153-1 SIPLUS IM 153-2
Order No. 6AG1 153-1AA03-2XB0 6AG1 153-2BA02-7XB0
Order No. based on 6ES7 153-1AA03-0XB0 6ES7 153-2BA02-0XB0
Ambient temperature range -25 ... +60 °C -25 ... +70 °C
Condensation permissible -25 ... +60 °C (for applications with cUL approval),
condensation permissible
Environmental conditions Suited for exceptional medial exposure (e.g. by chlorine sulfur atmosphere)
Approvals CE. UL haz. Loc. CE
Conforms with standard for Yes No
electronic equipment used on
rolling stock (EN 50155,
temperature T1, category 1).
Technical data The technical data are identical with those of the based-on modules.

SIPLUS bus module for accommodating an for accommodating two for accommodating a PS For accommodating two
80 mm module IM 153-2 and an IM 153 40 mm wide I/O modules
Order No. 6AG1 195-7HC00-2XA0 6AG1 195-7HD10-2XA0 6AG1 195-7HA00-2XA0 6AG1 195-7HB00-7XA0
Order No. based on 6ES7 195-7HC00-0XA0 6ES7 195-7HD10-0XA0 6ES7 195-7HA00-0XA0 6ES7 195-7HB00-0XA0
Ambient temperature range -25 ... +60 °C
Condensation permissible
Environmental conditions Suited for exceptional medial exposure (e.g. by chlorine sulfur atmosphere)
Approvals CE, cUL (available soon) CE, UL haz. Loc. CE. UL haz. Loc.
Conforms with standard for No No No No
electronic equipment used on
rolling stock (EN 50155,
temperature T1, category 1).
Technical data The technical data are identical with those of the based-on modules.

For further technical documentation on SIPLUS, see:


http://www.siemens.com/siplus-techdoku

5/126 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Modules for SIMATIC S7-400F/FH
SIPLUS IM 153-1/153-2

■ Ordering data Order No. Order No.


IM 153-1 interface module Bus module for ET 200M
Slave interface for connecting an • To accommodate a power 6AG1 195-7HA00-2XA0
ET 200M to PROFIBUS DP supply and an IM 153 for the hot-
swapping function during RUN,
• Standard temperature range 6AG1 153-1AA03-2XB0 incl. bus module cover
IM 153-2 interface module • To accommodate two 40 mm 6AG1 195-7HB00-7XA0
Slave interface for connecting an wide I/O modules for the hot-
ET 200M to PROFIBUS DP; also swapping function
for use in redundant systems • To accommodate one 80 mm 6AG1 195-7HC00-2XA0
• High Feature B7 6AG1 153-2BA02-7XB0 wide I/O module for the hot
swapping function
Active IM 153/IM 153 6AG1 195-7HD10-2XA0
bus module Accessories see IM 153-1/IM 153-2,
page 5/125
For two IM 153-2 High Feature
modules for designing redundant
systems
B7: Subject to export regulations: AL: N and ECCN: EAR99H
5

Siemens ST 70 · 2009 5/127


© Siemens AG 2008

SIMATIC S7-400
Modules for SIMATIC S7-400F/FH
Isolation module

■ Overview ■ Technical specifications


6ES7 195-7KF00-0XA0
Dimensions
Weights
• Weight, approx. 10 g

■ Ordering data Order No.


Isolation module 6ES7 195-7KF00-0XA0
for simultaneous operation of fail-
safe and standard modules in an
ET 200M
Isolation bus module 6ES7 195-7HG00-0XA0
for accommodating the isolating
5 module in an ET 200M

• Supports mixed operation of fail-safe signal modules in safety


mode and S7-300 standard modules in an ET 200M when
Cat. 4 or SIL 3 has to be achieved
• The isolation module is not required if the safety class or safety
category to be achieved is less than SIL 3 or Cat. 4, respec-
tively
When Cat. 4/SIL 3 is required, the isolation module must be
implemented in the following situations:

Application Isolation module must be used


Central use after CPU 31xF-2 DP
or CPU 31xF-2 PN/DP
• Only fail-safe modules in the tier Yes, behind the CPU
• Standard and fail-safe modules in Yes, after the last standard
the tier module and before the first fail-
safe module
Central use after CPU 31xF-2 DP
or CPU 31xF-2 PN/DP in an
expansion rack
• Only fail-safe modules in the tier Yes, after the IM 36x
• Standard and fail-safe modules in Yes, after the last standard
the tier module and before the first fail-
safe module
Distributed behind the IM 153-2
with copper connection
• Only fail-safe modules in the Yes, after the IM 153-2
station
• Standard and fail-safe modules in Yes, after the last standard
the station module and before the first fail-
safe module
Distributed behind the IM 153-2
with fiber-optic connection
• Only fail-safe modules in the No
station
• Standard and fail-safe modules in Yes, after the last standard
the station module and before the first fail-
safe module

5/128 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Modules for SIMATIC S7-400F/FH
SIPLUS isolating module

■ Overview SIPLUS S7-300 isolation module


Order No. 6AG1 195-7KF00-2XA0
Order No. based on 6ES7 195-7KF00-0XA0
Ambient temperature range - 25 ... + 60 °C, condensation
permitted
Environmental conditions Suited for exceptional medial
exposure (e.g. by chlorine sulfur
atmosphere).
Conforms with standard for Yes
electronic equipment used on
rolling stock (EN 50155,
temperature T1, category 1).
Technical data The technical data are identical with
those of the based-on modules.

Information about safety class and safety category see isolating


module, page 5/128.
5
• Permits combined operation of fail-safe signal modules in
safety mode and standard S7-300 modules in the same ■ Ordering data Order No.
ET 200M system. Isolating module 6AG1 195-7KF00-2XA0
• Design of PROFIBUS DP lines using copper bus cables. It is (medial exposure)
not necessary to use fiber-optic cables.
for simultaneous operation of fail-
• Every IM 153-x can be used safe and standard modules in an
The isolation module is not required if safety class SIL 2 is to be ET 200M
achieved. Accessories see Isolation module,
page 5/128

Failsafe input/output modules

■ Overview
• Failsafe input/output modules for use with the SIMATIC
S7-400F/FH
• With integrated safety functions
• Can only be plugged into the ET 200M
• Achievable safety classes in safety operation: SIL 2, SIL 3 to
IEC 61508, AK 4, AK 6 to DIN V 19250, Category 3, 4 to
EN 954-1
• Use in standard mode with high diagnostics requirements
• Also suitable for redundant operation
For further information see section 4, page 111.

Siemens ST 70 · 2009 5/129


© Siemens AG 2008

SIMATIC S7-400
Connection methods
Front connectors

■ Overview ■ Ordering data Order No.


Front connectors
48-pin for signal modules,
function modules; 1 unit
• With screw contacts B7 6ES7 492-1AL00-0AA0
• With spring-loaded terminals 6ES7 492-1BL00-0AA0
• With crimp contacts B7 6ES7 492-1CL00-0AA0
48-pin for signal modules,
function modules; 84 units per
pack
• With screw contacts B6 6ES7 492-1AL00-1AB0
• With crimp contacts 6ES7 492-1CL00-1AB0
for 6ES7 431-7KF00-0AB0; 6ES7 431-7KF00-6AA0
spare part, included in scope of
delivery ; 1 piece
5 Crimp contacts 6XX3 070
250 units
• For simple and user-friendly connection of sensors and Crimping tool 6XX3 071
actuators
for crimping the contacts
• For retaining the wiring when replacing modules
Front cover for front connector B7 6ES7 492-2XL00-0AA0
• With coding to avoid mistakes when replacing modules
6 units
Connection terminal for 6ES7 490-1BA00-0AA0
modules
6 units
Manual "SIMATIC S7-400
automation system"
incl. instruction list
German 6ES7 498-8AA05-8AA0
English 6ES7 498-8AA05-8BA0
French 6ES7 498-8AA05-8CA0
Spanish 6ES7 498-8AA05-8DA0
Italian 6ES7 498-8AA05-8EA0
SIMATIC Manual Collection B3 6ES7 998-8XC01-8YE0
Electronic manuals on DVD, five
languages: S7-200/300/400, C7,
LOGO!, SIMATIC DP, PC, PG,
STEP 7, engineering software,
runtime software, PCS 7, SIMATIC
HMI, SIMATIC NET
SIMATIC Manual Collection B3 6ES7 998-8XC01-8YE2
update service for 1 year
Current "Manual Collection" DVD
and the three subsequent
updates
B3: Subject to export regulations: AL: N and ECCN: 5D992B1
B6: Subject to export regulations: AL: N and ECCN: EAR99
B7: Subject to export regulations: AL: N and ECCN: EAR99H

5/130 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Connection methods
Fully modular connection

■ Overview
Basic modules

5
The fully modular connection is the standard connection for the
SIMATIC S7-300/400. The fully modular connection facilitates
convenient, fast, and correct connection of the I/O to the In the case of the basic module, the connection modules are
SIMATIC S7-300/400. used with basic functionality. Here, the I/O signal is connected
quickly and simply from the field to the module or from the
• Easy plugging in of front connector module, connecting cable module to the field.
and connection module
The connection terminals for the I/O signals are designed as
• Fast and low-cost wiring screw terminals or spring terminals. The connection modules are
• Supply voltage connectable to front connector module or available for digital and analog signals.
connection module for digital and analog signals
Signal modules
• Reduction in wiring errors, clear control cabinet wiring
• Distribution of digital signals by byte or by double-byte
• Each component can be replaced individually.
• Every cable length can be configured without cutting, or
pre-assembled cables can be used
Connecting cables

In the case of the signal module, the digital connection modules


with LED are used. The yellow LEDs indicate the "active high"
signal of the individual channels. This makes commissioning
easier for you, and you always have an overview of the signal
states of your I/O. At the same time, a green LED indicates when
the 24 V DC is applied.
The connection terminals for the I/O signals are designed as
The connection cable is the linking element between the front screw terminals or spring terminals. The connection modules are
connector module and the connection module. It transmits available for digital signals.
8 signals and the supply voltage. The maximum bridgeable
distance is 30 m. The connecting cable is available in two
different versions:
• The pre-assembled round cable
• The round-sheath ribbon cable assembled by the user

Siemens ST 70 · 2009 5/131


© Siemens AG 2008

SIMATIC S7-400
Connection methods
Fully modular connection

■ Overview (continued) Wiring rules for the front connector modules


Front connector module
Function modules SIMATIC TOP connect,
connection for potential supply
Screw connection
Modules up to 4 connections
Connectable cable cross-sections
• solid cables No
• flexible cables with/without 0.25 to 1.5 mm2
wire end ferrule
Number of cables per 1 or a combination of 2 conductors up to
connection 1.5 mm2 (total) in a common wire end
ferrule
Max. diameter of the cable 3.1 mm
insulation
Stripping length of the cables
5 • without insulating collar 6 mm
• with insulating collar -
Wire-end ferrules to DIN 46228
Function modules are implemented with digital connection • without insulating collar Form A; 5 to 7 mm long
modules fitted with relays or optocouplers.
• with insulating collar -
If other voltage or power levels are required in the field, the 0.25 to 1.0 mm2
connection module for output signals TPRo is used. This • with insulating collar -
converts the 24 V DC output signal simply and reliably to another 1.5 mm2
voltage or power level. If 230 V AC input signals have to be trans-
mitted to the controller in the field, a connection module with Blade width of the screw- 3.5 mm (cylindrical shape)
driver
relay TPRi is available that converts the 230 V AC signal simply
to 24 V DC. This means you always have the same voltage level Tightening torque for 0.4 to 0.7 Nm
on the module side. connecting the cables

■ Technical specifications front connector modules Front connector module


SIMATIC TOP connect,
Technical data of front connector module connection for potential supply
Rated operating voltage 24 V DC Screw connection
Max. permissible operating voltage 60 V DC Modules up to 6 connections
Max. permissible continuous Connectable cable cross-sections
current 1A • solid cables No
• per connector pin
• flexible cables with/without 0.25 bis 0.75 mm2
Max. permissible summation 4 A/byte (power supply) wire end ferrule
current
Number of cables per 1 or a combination of 2 conductors up to
Permissible ambient temperature 0 to + 60 °C connection 1.5 mm2 (total) in a common wire end
ferrule
Test voltage 0.5 kV, 50 Hz, 60 s
Max. diameter of the cable 2.0 mm
Air gaps and creepage distances IEC 664 (1980), insulation
IEC 664 A (1981),
in accordance with DIN VDE 0110 Stripping length of the wires
(01.89),
overvoltage class II, pollution • without insulating collar 6 mm
degree 2 • with insulating collar -
Wire-end ferrules to DIN 46228
• without insulating collar Form A; 5 to 7 mm long
• with insulating collar -
0.25 to 1.0 mm2
• with insulating collar -
1.5 mm2
Blade width of the screw- 3.5 mm (cylindrical shape)
driver
Tightening torque for 0.4 to 0.7 Nm
connecting the cables

5/132 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Connection methods
Fully modular connection

■ Technical specifications connecting cables Connection module TPA

Technical data of connecting cable from SIMATIC S7 to connection Max. operating voltage 60 V DC
module Continuous current signal 1A
Operating voltage 60 V DC conductor

Continuous current per signal 1A Operating temperature 0 to + 60°C


conductor Mounting position Any
Max. summation current 4 A/byte Air gaps and creepage distances IEC Report 664, IEC 664 A,
Operating temperature 0 to +60°C IEC 1131 T2,
CSA C22.2 No 142 UL 508,
Outer diameter of pre-assembled Approx. 6.5/7.0 VDE 0160 (12.90),
round cable in mm, overvoltage category II, pollution
unshielded/shielded degree 3
Outer diameter of round-sheath Approx. 9.5/11.5 Dimensions (W x H x D) in mm
ribbon cable in mm ,
16-pole/2 x 16-pole • for 2 analog modules Approx. 68 x 43.2 x 80
6ES7 924-0CC10-0A_0

■ Technical specifications basic modules


Connection module TP1, TP3 and TPK Wiring rules for connection modules 5
Max. operating voltage 60 V DC Connection module TPA, TP1, TP2,
TP3, TPK
Continuous current per signal 1A
Spring connection Screw connection
Max. summation current 4 A/byte
(voltage infeed) Connectable cable cross-sections
Operating temperature 0 to + 60°C • solid cables No
Mounting position Any • flexible cables without wire 0.5 to 2.5 mm2
end ferrule
Air gaps and creepage distances IEC Report 664, IEC 664 A,
IEC 1131 T2, • flexible cables with wire 0.5 to 1.5 mm2 0.5 to 2.5 mm2
CSA C22.2 No 142 UL 508, end ferrule in accordance (2.5 mm2 with a
VDE 0160 (12.90), overvoltage with DIN 46228/1 crimp in accor-
category II, pollution degree 3 dance with
EN 60947-1
Dimensions (W x H x D) in mm
• flexible cables with wire 0.5 to 1.5 mm2
• 1-wire connection Approx. 55 x 43.2 x 63 end ferrule and plastic
6ES7 924-0AA10-0A_0 collar in accordance with
• for 3-wire initiators Approx. 68 x 43.2 x 80 DIN 46228/4
6ES7 924-0CA10-0A_0 Number of cables per 1 or a combination of 2 cables up to the
• for 2 x 8 signals Approx. 100 x 43.2 x 80 connection cross-sections specified above(total) in a
6ES7 924-1AA10-0A_0 shared wire end ferrule
Blade width of the screw- 3.5 mm (cylindrical shape)
driver
Connection module TP2 Tightening torque for - 0.4 to 0.7 Nm
Max. operating voltage 60 V DC connecting the cables

Continuous current signal 2A


conductor
Operating temperature 0 to + 60°C
Mounting position Any
Air gaps and creepage distances IEC Report 664, IEC 664 A,
IEC 1131 T2,
CSA C22.2 No 142 UL 508,
VDE 0160 (12.90), overvoltage
category II, pollution degree 3
Dimensions (W x H x D) in mm
• for 2 ampere modules Approx. 68 x 43.2 x 80
6ES7 924-0BB10-0A_0

Siemens ST 70 · 2009 5/133


© Siemens AG 2008

SIMATIC S7-400
Connection methods
Fully modular connection

■ Technical specifications signal modules ■ Technical specifications function modules


Connection module TP1, TP3 and TPK with LED Connection module with relay for outputs (TPRo)
Max. operating voltage 24 V DC Energizing side
Continuous current per signal 1A Operating voltage for coil 24 V DC
Max. summation current 4 A/byte Input circuit Reverse polarity protection and
(voltage infeed) freewheeling diodes
Operating temperature 0 to + 60 °C Contact side
Mounting position Any Number of relay outputs 8 (NO contacts)
Air gaps and creepage distances IEC Report 664, IEC 664 A, Contact design Single contact, 1 NO contact
IEC 1131 T2,
CSA C22.2 No 142 UL 508, Switching capacity (resistive load) max. 4 A/250 V AC,
VDE 0160 (12.90), overvoltage max. 3 A/30 V DC
category II, pollution degree 3 max. 0.6 A/48 V DC
max. 0.4 A/60 V DC
Dimensions (W x H x D) in mm recommended minimum load
≥10 mA
• 1-wire connection with LED Approx. 55 x 43.2 x 63
5 6ES7 924-0AA10-0B_0
• for 3-wire initiators with LED Approx. 68 x 43.2 x 80
Switching frequency
Service life
20 cycles/minute

6ES7 924-0CA10-0B_0
• mechanical 5 x 106 operating cycles
• for 2 x 8 signals with LED Approx. 100 x 43.2 x 80
6ES7 924-1AA10-0B_0 • electrical 3 x 104 operating cycles at 230 V
AC/2 A/ cos ϕ = 1
Operating temperature 0 to +60 °C
Connection module TP2 with LED Mounting position Any
Max. operating voltage 24 V DC Air gaps and creepage distances Basic standard IEC 60664-1;
Continuous current per signal 2A UL 508; Cul
conductor (Reference CSA C22.2 No. 142)
overvoltage category III
Operating temperature 0 to + 60 °C pollution degree 2
Mounting position Any Dimensions (W x H x D) in mm
Air gaps and creepage distances EC Report 664, IEC 664 A, 6ES7 924-0BD10-0B_0 Approx. 100 x 45 x 80
IEC 1131 T2,
CSA C22.2 No 142 UL 508,
VDE 0160 (12.90), overvoltage
category II, pollution degree 3 Connection module with relay for inputs (TPRi)

Dimensions (W x H x D) in mm Energizing side

• for 2-ampere modules with LED Approx. 68 x 43.2 x 80 Operating voltage for coil 230 VAC
6ES7 924-0BB10-0B_0 from 207 – 280 V AC
Input circuit Varistors

Wiring rules for connection modules Contact side


Number of relay outputs 8 (NO contacts)
Connection module TP1 LED, TPK LED, TP2 LED, TP3 LED
Contact design Single contact, 1 NO contact
Spring connection Screw connection
Switching capacity (resistive load) max. 50 mA/24 V AC,
Connectable cable cross-sections max. 50 mA/48 V DC
• solid cables No max. 50 mA/60 V DC
recommended minimum load
• flexible cables without wire 0.5 to 2.5 mm2 ≥5 mA
end ferrule
Switching frequency 200 cycles/minute
• flexible cables with wire 0.5 to 1.5 mm2 0.5 to 2.5 mm2
end ferrule in accordance (2.5 mm2 with a Service life
with DIN 46228/1 crimp in accor- • mechanical 10 x 106 operating cycles
dance with
EN 60947-1) • electrical 3 x 106 operating cycles at
2 230 V AC/50 mA/ cos ϕ = 1
• flexible cables with wire 0.5 to 1.5 mm
end ferrule and plastic Operating temperature 0 to +60 °C
collar in accordance with
DIN 46228/4 Mounting position Any

Number of wires per 1 or a combination of 2 conductors up to Air gaps and creepage distances Basic standard IEC 60664-1;
connection the cross-sections specified above (total) UL 508; Cul
in a shared wire end ferrule (Reference CSA C22.2 No. 142)
overvoltage category III
Blade width of the screw- 3.5 mm (cylindrical shape) pollution degree 2
driver
Dimensions (W x H x D) in mm
Tightening torque for - 0.4 to 0.7 Nm
connecting the cables 6ES7 924-0BE10-0B_0 Approx. 120 x 45 x 80

5/134 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Connection methods
Fully modular connection

■ Technical specifications function modules (continued) ■ Ordering data


front connector modules Order No.
Wiring rules for the connection modules
Front connector module
Connection modules TPRo and TPRi (digital 4 x 8 I/O)
Spring connection Screw connection Voltage infeed via
Connectable cable cross-sections • Screw terminals 6ES7 921-4AB00-0AA0
• Solid cables No Front connector module
• flexible cables without wire 0.5 to 2.5 mm2 (2 x 8 outputs) for 2 ampere
end ferrule digital outputs
• flexible cables with wire 0.5 to 1.5 mm2 0.5 to 2.5 mm2 Voltage infeed via
end ferrule in accordance (2.5 mm2 with a • Screw terminals 6ES7 921-4AD00-0AA0
with DIN 46228/1 crimp in accor-
dance with Front connector module
EN 60947-1) (analog)
• flexible cables with wire 0.5 to 1.5 mm2 Voltage infeed via
end ferrule and plastic
• Screw terminals 6ES7 921-4AG00-0AA0
collar in accordance with
DIN 46228/4 5
Number of wires per 1 or a combination of 2 conductors up to ■ Ordering data connect. cables Order No.
connection the cross-sections specified above (total)
in a shared wire end ferrule Pre-assembled round cable

Blade width of the screw- 3.5 mm (cylindrical shape) 16-pole, 0.14 mm 2


driver unshielded
Tightening torque for - 0.4 to 0.7 Nm 0.5 m 6ES7 923-0BA50-0CB0
connecting the cables
1.0 m 6ES7 923-0BB00-0CB0
1.5 m 6ES7 923-0BB50-0CB0
2.0 m 6ES7 923-0BC00-0CB0
2.5 m 6ES7 923-0BC50-0CB0
3.0 m 6ES7 923-0BD00-0CB0
4.0 6ES7 923-0BE00-0CB0
5.0 m 6ES7 923-0BF00-0CB0
shielded
1.0 m 6ES7 923-0BB00-0DB0
2.0 m 6ES7 923-0BC00-0DB0
2.5 m 6ES7 923-0BC50-0DB0
3.0 m 6ES7 923-0BD00-0DB0
4.0 m 6ES7 923-0BE00-0DB0
5.0 m 6ES7 923-0BF00-0DB0
Round-sheath ribbon cable
16-pole, 0.14 mm 2
unshielded
30 m 6ES7 923-0CD00-0AA0
60 m B7 6ES7 923-0CG00-0AA0
shielded
30 m 6ES7 923-0CD00-0BA0
60 m 6ES7 923-0CG00-0BA0
Round-sheath ribbon cable
2 x 16-pole, 0.14 mm 2
unshielded
30 m 6ES7 923-2CD00-0AA0
60 m 6ES7 923-2CG00-0AA0
8 connectors (16-pole)
Insulation displacement system 6ES7 921-3BE10-0AA0
with 8 cable grips
Accessories
Crimping tool 6ES7 928-0AA00-0AA0
For processing the connectors
(female ribbon cable connector)
B7: Subject to export regulations: AL: N and ECCN: EAR99H

Siemens ST 70 · 2009 5/135


© Siemens AG 2008

SIMATIC S7-400
Connection methods
Fully modular connection

■ Ordering data basic modules Order No. ■ Ordering data signal modules Order No.
Connection module TP1 Connection module TP1 with
LED
for 1-wire initiators
for 1-wire initiators
Packaging unit (1 unit)
Packaging unit (1 unit)
• Spring terminals 6ES7 924-0AA10-0AB0
• Spring terminals 6ES7 924-0AA10-0BB0
• Screw terminals 6ES7 924-0AA10-0AA0
• Screw terminals 6ES7 924-0AA10-0BA0
Connection module TP3
Connection module TP3 with
for 3-wire initiators LED
Packaging unit (1 unit) for 3-wire initiators
• Spring terminals 6ES7 924-0CA10-0AB0 Packaging unit (1 unit)
• Screw terminals 6ES7 924-0CA10-0AA0 • Spring terminals 6ES7 924-0CA10-0BB0
Connection module TPK • Screw terminals 6ES7 924-0CA10-0BA0
for 2 x 8 signals Connection module TPK with
5 Packaging unit (1 unit) LED
for 2 x 8 signals
• Spring terminals 6ES7 924-1AA10-0AB0
• Screw terminals 6ES7 924-1AA10-0AA0 Packaging unit (1 unit)
Connection module TP2 • Spring terminals 6ES7 924-1AA10-0BB0
for 2 A modules • Screw terminals 6ES7 924-1AA10-0BA0
for 2-wire initiators Connection module TP2 with
LED
Packaging unit (1 unit)
for 2 A modules
• Spring terminals 6ES7 924-0BB10-0AB0
for 2-wire initiators
• Screw terminals 6ES7 924-0BB10-0AA0
Packaging unit (1 unit)
Connection module TPA
• Spring terminals 6ES7 924-0BB10-0BB0
for analog signals
• Screw terminals 6ES7 924-0BB10-0BA0
Packaging unit (1 unit)
Accessories
• Spring terminals 6ES7 924-0CC10-0AB0
Labeling plates for connection
• Screw terminals 6ES7 924-0CC10-0AA0
modules
Insertable labeling plate 6ES7 928-2AB00-0AA0
Accessories PU = 200 units
Labeling plates Self-adhesive labeling plate 6ES7 928-2BB00-0AA0
for connection modules PU = 200 units
Insertable labeling plate 6ES7 928-2AB00-0AA0
PU = 200 units
Self-adhesive labeling plate 6ES7 928-2BB00-0AA0
PU = 200 units
Shield plate 6ES7 928-1BA00-0AA0
for analog connection module
(4 units)
Shield connection terminal
for shield plate, 2 units, with cable
diameter
• 2 to 6 mm (2 cables) 6ES7 390-5AB00-0AA0
• 3 to 8 mm 6ES7 390-5BA00-0AA0
• 4 to 13 mm 6ES7 390-5CA00-0AA0

5/136 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Connection methods
Fully modular connection

■ Ordering data
function modules Order No. Order No.
Connection module TPRo for Accessories
output signals
Labeling plates for connection
for 2-wire connection modules
Packaging unit (1 unit) Insertable labeling plate 6ES7 928-2AB00-0AA0
PU = 200 units
• Spring terminals 6ES7 924-0BD10-0BB0
Self-adhesive labeling plate 6ES7 928-2BB00-0AA0
• Screw terminals 6ES7 924-0BD10-0BA0 PU = 200 units
Connection module TPRi for Replacement relay for relay
input signals connection module
for 2-wire connection PU = 4 units
Packaging unit (1 unit) Replacement relay for TPRi 6ES7 928-3BA00-4AA0
• Spring terminals 6ES7 924-0BE10-0BB0 Replacement relay for TPRo 6ES7 928-3AA00-4AA0
• Screw terminals 6ES7 924-0BE10-0BA0 Optocoupler DC alternative 6ES7 928-3DA00-4AA0
for relay in the case of TPRo
PU = 4 units 5
Optocoupler AC alternative 6ES7 928-3CA00-4AA0
for relay in the case of TPRo
PU = 4 units

Siemens ST 70 · 2009 5/137


© Siemens AG 2008

SIMATIC S7-400
Connection methods
Flexible connection

■ Overview ■ Ordering data Order No.


Front connector with single
cores
for 32-channel digital modules
SIMATIC S7-400, 46 x 0.5 mm2
Core type H05V-K
Screw version
Packaging unit (1 unit)
Length:
• 2.5 m 6ES7 922-4BC50-0AD0
• 3.2 m 6ES7 922-4BD20-0AD0
•5m 6ES7 922-4BF00-0AD0
• Special lengths on request
Packaging unit (5 units)
Length:
5 • 2.5 m 6ES7 922-4BC50-5AD0
• 3.2 m 6ES7 922-4BD20-5AD0
The flexible connection guarantees a fast and direct connection •5m 6ES7 922-4BF00-5AD0
from the input/output modules of the SIMATIC S7-300/400 to the
individual elements in the cabinet. Crimp version
Packaging unit (1 unit)
Already attached single cores reduce the wiring effort. Length:
The core cross-sections of 0,5 mm2 also allow higher currents. • 2.5 m 6ES7 922-4BC50-0AE0
• 3.2 m 6ES7 922-4BD20-0AE0
•5m 6ES7 922-4BF00-0AE0
■ Technical specifications • Special lengths on request
Front connector with single cores Packaging unit (5 units)
Rated operating voltage 24 V DC • 2.5 m 6ES7 922-4BC50-5AE0
Max. permissible continuous 1.0 A • 3.2 m 6ES7 922-4BD20-5AE0
current with simultaneous load on
all cores •5m 6ES7 922-4BF00-5AE0
Permissible ambient temperature 0 to +60 °C Core type UL/CSA-certified
Core type H05V-K or with Screw version
UL style 1007/1569 CSA TR64 Packaging unit (1 unit)
Number of cores 46 Length:
Core cross-section 0.5 mm2, Cu • 3.2 m 6ES7 922-4BD20-0UD0
Bundle diameter in mm Approx. 17 •5m 6ES7 922-4BF00-0UD0
Color of core Blue, RAL 5010 • Special lengths on request
Designation of cores Numbered from 3 to 48
(adapter contact = core number)
Fabrication Screw or crimp contacts

5/138 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Racks
Racks

■ Overview
CR2 (Central Rack)
• For setting up central controllers
• For holding up to 18 modules
• Segmented rack:
For operating two mutually independent S7-400 CPUs without
S7-400 Multicomputing, but with communication between the
CPUs over the backplane bus (C bus). Both CPUs can
address their own local I/O modules (segmented P bus).
CR3 (Central Rack)
• For configuring central racks
• Optimized for distributed automation solutions due to holding
up to 4 modules
UR2-H
• For configuring a complete S7-400H system in one subrack
• Also suitable for S7-400:
5
Operation of 2 separate CPUs with their own I/O (separate
• The basic mechanical framework of the SIMATIC S7-400/ P and C buses)
S7-400H • Can also be used as an expansion unit
• For accommodating the modules, supplying them with • For holding up to 18 modules
operating voltage and connecting them via the backplane bus
• Also available as aluminum rack
• Several versions for configuring central controllers and
expansion racks ER1 (Extension Rack)
UR1 (Universal Rack) • For setting up expansion units economically
• For setting up central controllers and expansion units • For holding up to 18 modules with restricted functionality
• For holding up to 18 modules • Also suitable for S7-400H
• Also suitable for S7-400H • Also available as aluminum rack
• Also available as aluminum rack ER2 (Extension Rack)
UR2 (Universal Rack) • For setting up expansion units economically
• For setting up central controllers and expansion units • For holding up to 9 modules with restricted functionality
• For holding up to 9 modules • Also suitable for S7-400H
• Also suitable for S7-400H • Also available as aluminum rack
• Also available as aluminum rack

■ Technical specifications
6ES7 400-1TA01- 6ES7 400-1TA11- 6ES7 400- 6ES7 400- 6ES7 401-2TA01- 6ES7 401-
0AA0 0AA0 1JA01-0AA0 1JA11-0AA0 0AA0 1DA01-0AA0
Hardware config.
Number of single-width slots, 18 18 9 9 18; 2 segments 4
max. with 8 or 10 slots
Rack
• K bus Yes Yes Yes Yes Yes Yes
• P bus Yes Yes Yes Yes Yes Yes
Dimensions
Dimensions
• Width 482.5 mm 482.5 mm 257.5 mm 257.5 mm 482.5 mm 130 mm
• Height 290 mm 290 mm 290 mm 290 mm 290 mm 290 mm
• Depth 27.5 mm 27.5 mm 27.5 mm 27.5 mm 27.5 mm 27.5 mm
Weights
• Weight, approx. 4 200 g 3 000 g 2 200 g 1 500 g 4 200 g 750 g

Siemens ST 70 · 2009 5/139


© Siemens AG 2008

SIMATIC S7-400
Racks
Racks

■ Technical specifications (continued)


6ES7 400- 6ES7 400- 6ES7 403-1TA01- 6ES7 403-1TA11- 6ES7 403- 6ES7 403-
2JA00-0AA0 2JA10-0AA0 0AA0 0AA0 1JA01-0AA0 1JA11-0AA0
Hardware config.
Number of single-width slots, 18 18 18 18 9 9
max.
Rack
• K bus Yes Yes
• P bus Yes Yes Yes Yes Yes Yes
Dimensions
Dimensions
• Width 482.5 mm 482.5 mm 482.5 mm 482.5 mm 257.5 mm 257.5 mm
• Height 290 mm 290 mm 290 mm 290 mm 290 mm 290 mm
• Depth 27.5 mm 27.5 mm 27.5 mm 27.5 mm 27.5 mm 27.5 mm
5 Weights
• Weight, approx. 4 200 g 3 000 g 4 200 g 2 500 g 2 200 g 1 250 g

■ Ordering data Order No. Order No.


UR1 rack 6ES7 400-1TA01-0AA0 UR2-H rack 6ES7 400-2JA00-0AA0
for central controllers and for split CCs, 18 slots
expansion units, 18 slots
UR2-H aluminum rack 6ES7 400-2JA10-0AA0
UR1 aluminum rack 6ES7 400-1TA11-0AA0
for split CCs, 18 slots
for central controllers and
expansion units, 18 slots ER1 rack 6ES7 403-1TA01-0AA0

UR2 rack 6ES7 400-1JA01-0AA0 for expansion units, P bus only, 18


slots
for central controllers and
expansion units, 9 slots ER1 aluminum rack 6ES7 403-1TA11-0AA0

UR2 aluminum rack 6ES7 400-1JA11-0AA0 for expansion units, P bus only, 18
slots
for central controllers and
expansion units, 9 slots ER2 rack 6ES7 403-1JA01-0AA0

CR2 rack 6ES7 401-2TA01-0AA0 for expansion units, P bus only,


9 slots
for segmented central controllers,
18 slots, 2 local segments ER2 aluminum rack 6ES7 403-1JA11-0AA0

CR3 rack 6ES7 401-1DA01-0AA0 for expansion units, P bus only,


9 slots
for central controllers and
expansion units, 4 slots; Slot cover 6ES7 490-1AA00-0AA0
optimized for distributed 10 units (spare part)
automation solutions

5/140 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Racks
Fan subassembly

■ Overview ■ Technical specifications


6ES7 408-1TA01- 6ES7 408-1TB00-
0XA0 0XA0
Supply voltages
Rated value
• DC 24 V Yes
• permissible range, lower 19.2 V
limit (DC)
• permissible range, upper 30 V
limit (DC)
• AC 120 V Yes
• AC 230 V Yes
• permissible range, lower 85/170 V AC
limit (AC)

5
• permissible range, upper 132 V AC or
limit (AC) 264 V AC
• permissible frequency 47 Hz
• Fans for the SIMATIC S7-400 range, lower limit
• Necessary when using modules that generate an extremely • permissible frequency 63 Hz
large amount of heat range, upper limit
Current consumption
Inrush current, typ. 0.9 A; at 24 V 0.6 A at rated
voltage 230 V AC:
1.15 A: at rated
voltage 120 V AC
Current consumption/
power loss
Power loss, max. 11 W 20 W
Relay outputs
Rated input voltage of relay 24 V 24 V
L+ (DC)
Switching capacity of the
contacts
• with resistive load, max. 200 mA 200 mA
Dimensions
Dimensions
• Width 482.5 mm 482.5 mm
• Height 109.5 mm 109.5 mm
• Depth 235 mm 235 mm
Weights
• Weight, approx. 1.6 kg 2 kg

■ Ordering data Order No.


Fan subassembly
for all racks; Supply voltage
24 V DC 6ES7 408-1TA01-0XA0
120 / 230 V AC 6ES7 408-1TB00-0XA0
Dust filter 6ES7 408-1TA00-7AA0
10 pieces
Replacement fan 6ES7 408-1TA00-6AA0
Spare part
Cable duct 6ES7 408-0TA00-0AA0
Same design as fan subas-
sembly, but without fans or
electronic units

Siemens ST 70 · 2009 5/141


© Siemens AG 2008

SIMATIC S7-400
Racks
Expansion racks

■ Overview
• SIMATIC S5 expansion racks for distributed expansion of the The following requirements must be met for expansion:
SIMATIC S7-400 • IM 463-2 interface module plugged into the SIMATIC S7-400
• For connection to existing SIMATIC S5 systems central controller
The following components can be connected to the SIMATIC • IM 314 interface module plugged into SIMATIC S5 expansion
S7-400: racks
• Expansion racks ER 701-2 and ER 701-3 from the • Maximum configuration:
SIMATIC S5-115U series • Up to 32 SIMATIC S5 expansion racks can be connected to
• Expansion racks EG 183U and EG 185U from the one S7-400 central controller
SIMATIC S5-135U/-155U series • Transmission distance:
The maximum permissible distance between the central
controller and the last expansion rack on a line is 600 m

Suitable SIMATIC S5 modules


Expansion rack ER 701-2, ER 701-3 EG 183U, Expansion rack ER 701-2, ER 701-3 EG 183U,
EG 185 U EG 185 U
5 Digital input modules 6ES5 420-7LA11 6ES5 420-4UA14 Analog input modules 6ES5 460-7LA13 6ES5 460-4UA13
6ES5 430-7LA12 6ES5 430-4UA14 6ES5 463-4UA12 6ES5 463-4UA13
6ES5 431-7LA11 6ES5 431-4UA12 6ES5 463-4UB12 6ES5 465-4UA13
6ES5 432-7LA11 6ES5 432-4UA12 6ES5 465-7LA13 6ES5 466-4UA11
6ES5 434-4UA12 6ES5 434-4UA12 6ES5 466-4UA11
6ES5 434-7LA12 6ES5 436-4UA12 Analog output modules 6ES5 470-7LA13 6ES5 470-4UA13
6ES5 435-7LA11 6ES5 470-7LB13 6ES5 470-4UB13
6ES5 435-7LB11 6ES5 470-7LC13 6ES5 470-4UC13
6ES5 435-7LC11 Interface modules 6ES5 306-7LA11 6ES5 300-3AB11
6ES5 436-7LA11 6ES5 314-3UA11 6ES5 300-5CA11
6ES5 436-7LB11
6ES5 436-7LC11
Digital output modules 6ES5 441-7LA13 6ES5 441-4UA14
6ES5 451-7LA21 6ES5 451-4UA14
6ES5 453-7LA11 6ES5 453-4UA12
6ES5 454-7LA12 6ES5 454-4UA14
6ES5 454-7LB11 6ES5 455-4UA12
6ES5 455-7LA11 6ES5 456-4UA12
6ES5 456-7LA11 6ES5 457-4UA12
6ES5 456-7LB11 6ES5 458-4UA13
6ES5 457-7LA11 6ES5 458-4UC11
6ES5 458-7LA11
6ES5 458-7LB11
6ES5 458-7LC11
Digital input/output 6ES5 482-7LA11 6ES5 482-4UA20
modules
6ES5 482-7LF11
6ES5 482-7LF21
6ES5 482-7LF31

5/142 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Interface modules
IM 460-0

■ Overview ■ Technical specifications


6ES7 460-0AA01-0AB0
Current consumption
from backplane bus DC 5 V, 140 mA
max.
Current consumption/
power loss
Power loss, max. 700 mW
Hardware config.
Cable length between first and 5m
last interface module, max.
Dimensions
Dimensions
• Width 25 mm
• Height
• Depth
290 mm
217 mm
5
• Send interface module for central expansion to 5 m Weights

• Transmission of P and K bus • Weight, approx. 600 g


• Can be plugged into the central controller
• Up to 8 expansion racks can be connected (up to 4 per
interface) ■ Ordering data Order No.
• Can be used exclusively with IM 461-0 IM 460-0 interface module 6ES7 460-0AA01-0AB0
Send interface module for central
connection up to 5 m;
with C bus transmission
468-1 connecting cable
between IM 460-0 and IM 461-0;
IM 460-3 and IM 461-3
0.75 m 6ES7 468-1AH50-0AA0
1.5 m 6ES7 468-1BB50-0AA0
5m 6ES7 468-1BF00-0AA0

Siemens ST 70 · 2009 5/143


© Siemens AG 2008

SIMATIC S7-400
Interface modules
IM 461-0

■ Overview ■ Technical specifications


6ES7 461-0AA01-0AA0
Current consumption
from backplane bus DC 5 V, 290 mA
max.
Current consumption/
power loss
Power loss, max. 1 450 mW
Hardware config.
Cable length between first and 5m
last interface module, max.
Dimensions
Dimensions
• Width 25 mm

5 • Height
• Depth
290 mm
217 mm

• Receive interface for centralized expansion up to 5 m Weights

• Transmission of P and K bus • Weight, approx. 610 g


• Can be plugged into expansion rack
• To be used exclusively with IM 460-0
■ Ordering data Order No.
IM 461-0 interface module 6ES7 461-0AA01-0AA0
Receive interface module for
central connection up to 5 m;
with C bus transmission
468-1 connecting cable
between IM 460-0 and IM 461-0;
IM 460-3 and IM 461-3
0.75 m 6ES7 468-1AH50-0AA0
1.5 m 6ES7 468-1BB50-0AA0
5m 6ES7 468-1BF00-0AA0
Terminating connector 6ES7 461-0AA00-7AA0
for IM 461-0

5/144 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Interface modules
IM 460-1

■ Overview ■ Technical specifications


6ES7 460-1BA01-0AB0
Current consumption
from backplane bus DC 5 V, 85 mA
max.
Current consumption/
power loss
Power loss, max. 425 mW
Hardware config.
Cable length between first and 1.5 m
last interface module, max.
Dimensions
Dimensions
• Width 25 mm
• Height
• Depth
290 mm
217 mm
5
• Send interface module for central expansion to 1.5 m Weights

• Transmission of P bus • Weight, approx. 600 g


• With voltage supply for expansion units
• Can be plugged into the central controller
• Up to 2 expansion racks can be connected (up to 1 per ■ Ordering data Order No.
interface) IM 460-1 interface module 6ES7 460-1BA01-0AB0
• Can be used exclusively with IM 461-1
Send interface module for central
connection up to 1.5 m; with 5 V
power supply, without C bus
transmission
468-3 connecting cable
between IM 460-1 and IM 461-1;
0.75 m 6ES7 468-3AH50-0AA0
1.5 m 6ES7 468-3BB50-0AA0

Siemens ST 70 · 2009 5/145


© Siemens AG 2008

SIMATIC S7-400
Interface modules
IM 461-1

■ Overview ■ Technical specifications


6ES7 461-1BA01-0AA0
Current consumption
from backplane bus DC 5 V, 120 mA
max.
Current consumption/
power loss
Power loss, max. 600 mW
Hardware config.
Cable length between first and 1.5 m
last interface module, max.
Dimensions
Dimensions
• Width 25 mm

5 • Height
• Depth
290 mm
217 mm

• Receive interface for central expansion up to 1.5 m Weights

• Transmission of P bus • Weight, approx. 610 g


• With voltage supply for expansion racks
• Can be plugged into expansion rack
• Can be used exclusively with IM 460-1 ■ Ordering data Order No.
IM 461-1 interface module 6ES7 461-1BA01-0AA0
Receive IM for central coupling
up to max. 1.5 m; without C bus
transfer
468-3 connecting cable
For connecting IM 460-1 and
IM 461-1
0.75 m 6ES7 468-3AH50-0AA0
1.5 m 6ES7 468-3BB50-0AA0

5/146 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Interface modules
IM 460-3

■ Overview ■ Technical specifications


6ES7 460-3AA01-0AB0
Current consumption
from backplane bus DC 5 V, 1 550 mA
max.
Current consumption/
powerloss
Power loss, max. 7 750 mW
Hardware config.
Cable length between first and 102 m
last interface module, max.
Dimensions
Dimensions
• Width 25 mm
• Height
• Depth
290 mm
217 mm
5
• Send interface module for distributed expansion to 102 m Weights

• Transmission of K and P bus • Weight, approx. 630 g


• Can be plugged into the central controller
• Up to 8 expansion racks can be connected (up to 4 per
interface) ■ Ordering data Order No.
• Can be used exclusively with IM 461-3 IM 460-3 interface module 6ES7 460-3AA01-0AB0
Send interface module for
distributed connection up to
102 m; with C bus transmission
468-1 connecting cable
between IM 460-3 and IM 461-3
0.75 m 6ES7 468-1AH50-0AA0
1.5 m 6ES7 468-1BB50-0AA0
5m 6ES7 468-1BF00-0AA0
10 m 6ES7 468-1CB00-0AA0
25 m 6ES7 468-1CC50-0AA0
50 m 6ES7 468-1CF00-0AA0
100 m 6ES7 468-1DB00-0AA0

Siemens ST 70 · 2009 5/147


© Siemens AG 2008

SIMATIC S7-400
Interface modules
IM 461-3

■ Overview ■ Technical specifications


6ES7 461-3AA01-0AA0
Current consumption
from backplane bus DC 5 V, 620 mA
max.
Current consumption/
power loss
Power loss, max. 3 100 mW
Hardware config.
Cable length between first and 102 m
last interface module, max.
Dimensions
Dimensions
• Width 25 mm

5 • Height
• Depth
290 mm
217 mm

• Receive interface for distributed expansion up to 102 m Weights

• Transmission of data from the P-bus and C-bus • Weight, approx. 620 g
• Can be plugged into expansion rack
• To be used exclusively with IM 460-3
■ Ordering data Order No.
IM 461-3 interface module 6ES7 461-3AA01-0AA0
Receive interface module for
distributed connection up to
102 m; with C bus transmission
468-1 connecting cable
between IM 460-3 and IM 461-3
0.75 m 6ES7 468-1AH50-0AA0
1.5 m 6ES7 468-1BB50-0AA0
5m 6ES7 468-1BF00-0AA0
10 m 6ES7 468-1CB00-0AA0
25 m 6ES7 468-1CC50-0AA0
50 m 6ES7 468-1CF00-0AA0
100 m 6ES7 468-1DB00-0AA0
Terminating connector 6ES7 461-3AA00-7AA0
for IM 461-3

5/148 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Interface modules
IM 463-2

■ Overview ■ Technical specifications


6ES7 463-2AA00-0AA0
Current consumption
from backplane bus DC 5 V, 1 320 mA
max.
Current consumption/
power loss
Power loss, max. 6 600 mW
Hardware config.
Cable length between first and 600 m
last interface module, max.
Dimensions
Dimensions
• Width 25 mm
• Height 290 mm 5
• Depth 217 mm
• Send interface for distributed expansion with SIMATIC S5 Weights
expansion racks up to 600 m • Weight, approx. 360 g
• Can be plugged into the central controller
• Up to 8 SIMATIC S5 expansion racks can be connected (up to
4 per interface)
• Can be used exclusively with IM 314
■ Ordering data Order No.
IM 463-2 interface module 6ES7 463-2AA00-0AA0
Receiving IM for distributed
coupling of SIMATIC S5-EUs
up to max. 600 m

Siemens ST 70 · 2009 5/149


© Siemens AG 2008

SIMATIC S7-400
Power supplies
PS 405/407 power supply

■ Overview
• Power supplies for SIMATIC S7-400
• For conversion of AC or DC line voltages to the 5 V DC and
24 V DC operating voltages required
• 4 A, 10 A and 20 A output currents
• In addition:
- SIPLUS power supply 6AG1 405-0KA02-2AA0 for temper-
ature range of -25 to +60 °C and use under medium load
(e.g. chlorine/sulfur atmosphere). Technical specifications
similar to 6ES7 405-0KA02-0AA0
- SIPLUS power supply 6AG1 407-0KA02-4AA0 for use under
medium load (e.g. chlorine/sulfur atmosphere). Technical
specifications similar to 6ES7 407-0KA02-0AA0
- SIPLUS power supply 6AG1 407-0KR02-4AA0 for use under
medium load (e.g. chlorine/sulfur atmosphere). Technical
specifications similar to 6ES7 407-0KR02-0AA0

5
■ Technical specifications
6ES7 405-0DA02-0AA0 6ES7 405-0KA02-0AA0 6ES7 405-0KR02-0AA0 6ES7 405-0RA02-0AA0
Power supply
Input voltage
• Rated value, DC 24 V Yes Yes Yes Yes
• Rated value, DC 48 V Yes Yes Yes Yes
• Rated value, DC 60 V Yes Yes Yes Yes
• permissible range, lower limit 19.2 V; dynamic 18.5 V Static 19.2 V, 19.2 V; dynamic 18.5 V static 19.2 V,
(DC) dynamic 18.5 V dynamic 18.5 V
• permissible range, upper limit 72 V; dynamic 75.5 V static 72 V, 72 V; dynamic 75.5 V static: 72 V
(DC) dynamic 75.5 V dynamic 75.5 V
Input current
• Rated value at DC 24 V 2A 4A 4A 7A
• Rated value at DC 48 V 1 000 mA 2A 2A 3.2 A
• Rated value at DC 60 V 800 mA 1.6 A 1.6 A 2.5 A
• Inrush current, max. 18 A; Full width at half 18 A; Full width at half 18 A; Full width at half 56 A; Full width at half
maximum 20 ms maximum 20 ms maximum 20 ms maximum 1.5 ms
Output voltage
• Rated value, DC 5 V Yes Yes Yes Yes
• Rated value, DC 24 V Yes Yes Yes Yes
Output current
• for backplane bus (DC 5 V), 4A 10 A; no base load 10 A; no base load 20 A; no base load
max. required required required
• for backplane bus (DC 24 V), 0.5 A 1 A; idling-proof 1 A; idling-proof 1 A; idling-proof
max.
• Short-circuit protection Yes Yes Yes Yes
Supply voltages
Power supply and voltage
jumpering
• Mains/voltage failure 20 ms 20 ms 20 ms 20 ms
jumpering
• Mains/power failure jumper to Yes Yes Yes Yes
NAMUR recommendation
Current consumption/
power loss
Power consumption
• Power consumption, typ. 48 W 95 W 95 W 168 W

5/150 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Power supplies
PS 405/407 power supply

■ Technical specifications (continued)


6ES7 405-0DA02-0AA0 6ES7 405-0KA02-0AA0 6ES7 405-0KR02-0AA0 6ES7 405-0RA02-0AA0
Current consumption/
power loss
Power loss, typ. 16 W 20 W 20 W 44 W
Backup battery
• Backup battery (optional) Yes; 1 x lithium AA; Yes; 2 x lithium AA; Yes; 2 x lithium AA; Yes; 2 x lithium AA;
3.6 V/2.3 Ah 3.6 V/1.9 Ah 3.6 V/2.3 Ah 3.6 V/2.3 Ah
Connection point
Connecting cables/ 3x 1.5 mm2, solid or 3x 1.5 mm2, solid or 3x 1.5 mm2, solid or 3 x 1.5 mm2, solid or
cross sections stranded wire with end stranded wire with end stranded wire with end stranded wire with end
sleeve, external diameter sleeve, external diameter sleeve, external diameter sleeve, external diameter
3 to 9 mm 3 to 9 mm 3 to 9 mm 3 to 9 mm
Isolation
primary/secondary Yes Yes Yes Yes
EMC 5
• Observance of line harmonic Yes Yes
distortion to IEC 61000-3-2,
IEC 61000-3-3
Degree of protection
Class of protection 1; with protective 1; with protective 1; with protective 1; with protective
conductor conductor conductor conductor
Standards, approvals,
certificates
FM approval Yes; Ta: 0 to 60 °C T4 Yes; Up to 60 °C: T4 Yes; Ta: 0 to 60 °C T4 Yes; Up to 60°C: T4
Dimensions
Required slots 1 2 2 2
Dimensions
Dimensions
• Width 25 mm 50 mm 50 mm 50 mm
• Height 290 mm 290 mm 290 mm 290 mm
• Depth 217 mm 217 mm 217 mm 217 mm
Weights
• Weight, approx. 760 g 1 200 g 1 200 g 1 300 g

6ES7 407-0DA02-0AA0 6ES7 407-0KA02-0AA0 6ES7 407-0KR02-0AA0 6ES7 407-0RA02-0AA0


Power supply
Input voltage
• Rated value, DC 24 V Yes
• Rated value, DC 110 V Yes; Rated value 120 V DC Yes; Rated value 120 V DC Yes; Rated value 120 V DC Yes; Rated value 120 V DC
• Rated value, DC 230 V Yes Yes Yes Yes
• permissible range, lower limit 88 V 88 V 88 V 88 V
(DC)
• permissible range, upper limit 300 V 300 V 300 V 300 V
(DC)
• Rated value, AC 120 V Yes Yes Yes Yes
• Rated value, AC 230 V Yes Yes Yes Yes
• permissible range, lower limit 85 V 85 V 85 V 85 V
(AC)
• permissible range, upper limit 264 V 264 V 264 V 264 V
(AC)

Siemens ST 70 · 2009 5/151


© Siemens AG 2008

SIMATIC S7-400
Power supplies
PS 405/407 power supply

■ Technical specifications (continued)


6ES7 407-0DA02-0AA0 6ES7 407-0KA02-0AA0 6ES7 407-0KR02-0AA0 6ES7 407-0RA02-0AA0
Power supply
Input voltage
• Mains frequency
- Rated value 50 Hz Yes Yes Yes Yes
- Rated value 60 Hz Yes Yes Yes Yes
- permissible range, lower limit 47 Hz 47 Hz 47 Hz 47 Hz
- permissible range, upper 63 Hz 63 Hz 63 Hz 63 Hz
limit
Input current
• Rated value at DC 110 V 350 mA; at 120 V DC 1 A; at 120 V DC 1 A; at 120 V DC 1.4 A
• Rated value at DC 230 V 190 mA 0.5 A 0.5 A 0.7 A

5
• Rated value at AC 120 V 0.42 A 0.9 A 0.9 A 1.4 A
• Rated value at AC 230 V 0.22 A 0.5 A 0.5 A 0.7 A
• Inrush current, max. 8.25 A; Full width at half 63 A; Full width at half 63 A; Full width at half 88 A; Full width at half
maximum 5 ms maximum 1 ms maximum 1 ms maximum 1.1 ms
Output voltage
• Rated value, DC 5 V Yes Yes
• Rated value, DC 24 V Yes Yes
Output current
• for backplane bus (DC 5 V), 4 A; no base load required 10 A; no base load 10 A; no base load 20 A; no base load
max. required required required
• for backplane bus (DC 24 V), 0.5 A 1 A; idling-proof 1 A; idling-proof 1 A; idling-proof
max.
• Short-circuit protection Yes Yes Yes Yes
Supply voltages
Power supply and voltage
jumpering
• Mains/voltage failure 20 ms 20 ms 20 ms 20 ms
jumpering
• Mains/power failure jumper to Yes Yes Yes Yes
NAMUR recommendation
Current consumption/
power loss
Power consumption
• Power consumption, typ. 52 W 95 W 95 W
Power loss, typ. 20 W 20 W 20 W 35 W
Backup battery
• Backup battery (optional) Yes; 1 x lithium AA; Yes; 2 x lithium AA; Yes; 2 x lithium AA; Yes; 2 x lithium AA;
3.6 V/2.3 Ah 3.6 V/2.3 Ah 3.6 V/2.3 Ah 3.6 V/2.3 Ah
Connection point
Connecting cables/cross 3x 1.5 mm2, solid or 3x 1.5 mm2, solid or 3x 1.5 mm2, solid or 3x 1.5 mm2, solid or
sections stranded wire with end stranded wire with end stranded wire with end stranded wire with end
sleeve, external diameter sleeve, external diameter sleeve, external diameter sleeve, external diameter
3 to 9 mm 3 to 9 mm 3 to 9 mm 3 to 9 mm
Isolation
primary/secondary Yes Yes Yes Yes
EMC
• Observance of line harmonic Yes Yes Yes Yes
distortion to IEC 61000-3-2,
IEC 61000-3-3

5/152 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Power supplies
PS 405/407 power supply

■ Technical specifications (continued)


6ES7 407-0DA02-0AA0 6ES7 407-0KA02-0AA0 6ES7 407-0KR02-0AA0 6ES7 407-0RA02-0AA0
Degree of protection
Class of protection 1; with protective 1; with protective 1; with protective 1; with protective
conductor conductor conductor conductor
Standards, approvals,
certificates
FM approval Yes; Ta: 0 to 60 °C T4 Yes; Ta: 0 to 60 °C T4 Yes; Ta: 0 to 60 °C T4 Yes; Ta: 0 to 60 °C T4
Dimensions
Required slots 1 2 2 2
Dimensions
Dimensions
• Width 25 mm 50 mm 50 mm 50 mm
• Height 290 mm 290 mm 290 mm 290 mm
• Depth 217 mm 217 mm 217 mm 217 mm 5
Weights
• Weight, approx. 760 g 1 200 g 1 200 g 1 300 g

■ Ordering data Order No. Order No.


PS 405 power supply modules PS 407 power supply modules
24 V DC; 5 V DC, 24 V DC 120/230 V AC; 5 V DC, 24 V DC
4A 6ES7 405-0DA02-0AA0 4A 6ES7 407-0DA02-0AA0
10 A, wide range 6ES7 405-0KA02-0AA0 10 A 6ES7 407-0KA02-0AA0
10 A, redundant, wide range 6ES7 405-0KR02-0AA0 10 A, redundant 6ES7 407-0KR02-0AA0
20 A, wide range 6ES7 405-0RA02-0AA0 20 A 6ES7 407-0RA02-0AA0
SIPLUS PS 405 SIPLUS PS 407
power supply modules power supply modules
(extended temperature range and (extended temperature range and
medium load) medium load)
24 V DC; 5 V DC, 24 V DC 120/230 V AC; 5 V DC, 24 V DC
10 A, wide range 6AG1 405-0KA02-2AA0 10 A 6AG1 407-0KA02-4AA0
Power plug for PS 405 6ES7 490-0AA00-0AA0 10 A, redundant B7 6AG1 407-0KR02-4AA0
Spare part Power plug for PS 407 6ES7 490-0AB00-0AA0
Backup battery 6ES7 971-0BA00 Spare part
Type AA, 1.9 Ah Backup battery 6ES7 971-0BA00
Type AA, 1.9 Ah
B7: Subject to export regulations: AL: N and ECCN: EAR99H

Siemens ST 70 · 2009 5/153


© Siemens AG 2008

SIMATIC S7-400
Accessories
Labeling sheets

■ Overview
Labeling sheets Label cover
• Film sheets for application-specific labeling of SIMATIC • Film to cover and hold user-made labeling strips on normal
S7-400 I/O modules with commercial laser printers paper
• Single-color films, tear-resistant, dirt-resistant • Accessories, 10 pieces
• Easy handling:
- Pre-perforated labeling sheets in DIN A4 format to allow
easy separation of the labeling strips
- The separated strips can be inserted directly into the I/O
modules
• Different colors for distinction between module types or
preferred areas of application:
The labeling sheets are available in the colors teal, light beige,
red and yellow. Yellow is reserved for failsafe systems.

5 ■ Technical specifications
6ES7 492-2AX00- 6ES7 492-2BX00- 6ES7 492-2CX00- 6ES7 492-2DX00- 6ES7 492-2XX00-
0AA0 0AA0 0AA0 0AA0 0AA0
Dimensions
Weights
• Weight, approx. 2g 2g 2g 2g 72 g

■ Ordering data Order No. Order No.


Labeling sheets Cover film for labeling strips 6ES7 492-2XX00-0AA0
DIN A4, for printing using laser 10 pieces (spare part)
printer; 10 pieces
Petrol 6ES7 492-2AX00-0AA0
Light beige 6ES7 492-2BX00-0AA0
Yellow 6ES7 492-2CX00-0AA0
Red 6ES7 492-2DX00-0AA0

5/154 Siemens ST 70 · 2009


© Siemens AG 2008

SIMATIC S7-400
Accessories
Spare parts

■ Overview ■ Ordering data Order No.

Cover film for labeling strips Cover foil for labeling strip 6ES7 492-2XX00-0AA0
• Teal-colored film for covering and fixing user-created labeling 10 units (spare part)
strips Range card for analog input 6ES7 974-0AA00-0AA0
• On standard paper modules
• Spare part 1 card for 2 inputs; 2 units (spare
part)
Measuring range module for analog input modules
Slot covers 6ES7 490-1AA00-0AA0
• Plug-in module for selecting the input ranges for analog
modules for racks; 10 units (spare part)

• 1 module for 2 inputs Power plug for PS 405 6ES7 490-0AA00-0AA0


• Spare part Spare part
Power plug for PS 407 6ES7 490-0AB00-0AA0
Module slot cover
Spare part
• Cover plates for unassigned slots in module mounting racks
Replacement fan 6ES7 408-1TA00-6AA0
5
• Spare part, 10 items
Spare part
Power plug
• Plug for connecting the PS 405 and PS 407 power supply
modules to the line supply
• Spare part
Exchangeable fan
• Fan unit for installation in the fan subassembly
• Spare part
Exchangeable monitoring unit
• Electronic monitoring unit for the fan subassembly
• Spare part
Exchangeable power supply unit
• Power supply unit for installation in the fan subassembly
• Spare part

Siemens ST 70 · 2009 5/155


© Siemens AG 2008

SIMATIC S7-400

5/156 Siemens ST 70 · 2009

You might also like