0% found this document useful (0 votes)
381 views116 pages

RCS-924A - 080110 Stub Differential Relay Instruction Manual (EN - FZBH0106.0062.1101)

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
381 views116 pages

RCS-924A - 080110 Stub Differential Relay Instruction Manual (EN - FZBH0106.0062.1101)

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 116

RCS-924

Stub Differential Relay


Instruction Manual

Nanjing Nari-Relays Electric Co., Ltd.


RCS-924 Stub Differential Relay

Preface
Introduction
This guide and the relevant operating or service manual documentation for the equipment provide
full information on safe handling, commissioning and testing of this equipment.

Documentation for equipment ordered from NARI-RELAYS is dispatched separately from


manufactured goods and may not be received at the same time. Therefore, this guide is provided
to ensure that printed information normally present on equipment is fully understood by the
recipient.

Before carrying out any work on the equipment, the user should be familiar with the contents of
this manual, and read relevant chapter carefully.

This chapter describes the safety precautions recommended when using the equipment. Before
installing and using the equipment, this chapter must be thoroughly read and understood.

Health and safety


The information in this chapter of the equipment documentation is intended to ensure that
equipment is properly installed and handled in order to maintain it in a safe condition.

When electrical equipment is in operation, dangerous voltages will be present in certain parts of
the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger
personnel and equipment and cause personal injury or physical damage.

Before working in the terminal strip area, the equipment must be isolated.

Proper and safe operation of the equipment depends on appropriate shipping and handling,
proper storage, installation and commissioning, and on careful operation, maintenance and
servicing. For this reason, only qualified personnel may work on or operate the equipment.

Qualified personnel are individuals who:

l Are familiar with the installation, commissioning, and operation of the equipment and of the
system to which it is being connected;

l Are able to safely perform switching operations in accordance with accepted safety
engineering practices and are authorized to energize and de-energize equipment and to
isolate, ground, and label it;

l Are trained in the care and use of safety apparatus in accordance with safety engineering
practices;

l Are trained in emergency procedures (first aid).

Instructions and Warnings


The following indicators and standard definitions are used:

NANJING NARI-RELAYS ELECTRIC CO., LTD i


RCS-924 Stub Differential Relay

DANGER means that death, severe personal injury, or considerable equipment damage will
occur if safety precautions are disregarded.

WARNING means that death, severe personal, or considerable equipment damage could occur
if safety precautions are disregarded.

CAUTION means that light personal injury or equipment damage may occur if safety
precautions are disregarded. This particularly applies to damage to the device and to
resulting damage of the protected equipment.

WARNING!

The firmware may be upgraded to add new features or enhance/modify existing features, please
make sure that the version of this manual is compatible with the product in your hand.

WARNING!

During operation of electrical equipment, certain parts of these devices are under high voltage.
Severe personal injury or significant equipment damage could result from improper behavior.

Only qualified personnel should work on this equipment or in the vicinity of this equipment. These
personnel must be familiar with all warnings and service procedures described in this manual, as
well as safety regulations.

In particular, the general facility and safety regulations for work with high-voltage equipment must
be observed. Noncompliance may result in death, injury, or significant equipment damage.

DANGER!

Never allow the current transformer (CT) secondary circuit connected to this equipment to be
opened while the primary system is live. Opening the CT circuit will produce a dangerously high
voltage.

WARNING!

l Exposed terminals

Do not touch the exposed terminals of this equipment while the power is on, as the high voltage
generated is dangerous

l Residual voltage

Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. It
takes a few seconds for the voltage to discharge.

CAUTION!

l Earth

ii NANJING NARI-RELAYS ELECTRIC CO., LTD


RCS-924 Stub Differential Relay

The earthing terminal of the equipment must be securely earthed

l Operating environment

The equipment must only be used within the range of ambient environment detailed in the
specification and in an environment free of abnormal vibration.

l Ratings

Before applying AC voltage and current or the DC power supply to the equipment, check that they
conform to the equipment ratings.

l Printed circuit board

Do not attach and remove printed circuit boards when DC power to the equipment is on, as this
may cause the equipment to malfunction.

l External circuit

When connecting the output contacts of the equipment to an external circuit, carefully check the
supply voltage used in order to prevent the connected circuit from overheating.

l Connection cable

Carefully handle the connection cable without applying excessive force.

Copyright
Version: RCS-924 V2.00 T080010 NANJING NARI-RELAYS ELECTRIC CO., LTD.

Manual: V1.00 99 Shengtai Rd. Jiangning, Nanjing 211106, China

P/N: EN_FZBH0106.0062.1101 Tel: 86-25-87178185, Fax: 86-25-87178208

Copyright © NR 2007. All rights reserved Website: www.nari-relays.com

We reserve all rights to this document and to the information Email: [email protected]
contained herein. Improper use in particular reproduction and
dissemination to third parties is strictly forbidden except where
expressly authorized.

The information in this manual is carefully checked periodically,


and necessary corrections will be included in future editions. If
nevertheless any errors are detected, suggestions for correction or
improvement are greatly appreciated.

We reserve the rights to make technical improvements without


notice.

NANJING NARI-RELAYS ELECTRIC CO., LTD iii


RCS-924 Stub Differential Relay

Table of Contents
Preface.......................................................................................................................................... i

Introduction.............................................................................................................................. i

Health and safety ..................................................................................................................... i

Instructions and Warnings ..................................................................................................... i

Table of Contents ...................................................................................................................... iv


Chapter 1 Introduction............................................................................................................... 1

1.1 Application ........................................................................................................................ 1

1.2 Function............................................................................................................................. 1

1.3 Features ............................................................................................................................. 2

Chapter 2 Technical Data........................................................................................................... 3

2.1 Electrical Specifications .................................................................................................. 3

2.1.1 Analog input ratings .................................................................................................. 3

2.1.2 Power supply.............................................................................................................. 3

2.1.3 Binary input ................................................................................................................ 4

2.1.4 Binary output.............................................................................................................. 4

2.1.5 Power supply output for opto-coupler .................................................................... 4

2.2 Mechanical Specifications............................................................................................... 4

2.3 Ambient Temperature and Humidity Range................................................................... 5

2.4 Rear Communication Port ............................................................................................... 5

2.5 Type Tests.......................................................................................................................... 6

2.5.1 Environmental tests................................................................................................... 6

2.5.2 Mechanical tests ........................................................................................................ 7

2.5.3 Electrical tests............................................................................................................ 7

2.5.4 Electromagnetic compatibility.................................................................................. 7

2.6 Certifications..................................................................................................................... 8

2.7 Protective Functions ........................................................................................................ 8

2.7.1 Accurate operating scope......................................................................................... 8

2.7.2 General error of analog input metering................................................................... 8

iv NANJING NARI-RELAYS ELECTRIC CO., LTD


RCS-924 Stub Differential Relay

2.7.3 Differential protection................................................................................................ 8

2.7.4 End fault protection................................................................................................... 8

2.7.5 Overcurrent protection.............................................................................................. 9

Chapter 3 Protection Description............................................................................................11

3.1 General Description ........................................................................................................11

3.2 General Fault Detector element (GFD) ..........................................................................11

3.2.1 Differential current fault detector element.............................................................11

3.2.2 Phase overcurrent fault detector element............................................................. 12

3.3 Protective Fault Detection (PFD) .................................................................................. 12

3.4 Current Differential Protection...................................................................................... 12

3.4.1 3-terminal application.............................................................................................. 13

3.4.2 2-terminal application.............................................................................................. 14

3.5 End Fault Protection ...................................................................................................... 14

3.6 Overcurrent Protection .................................................................................................. 15

3.7 Scheme logic................................................................................................................... 15

Chapter 4 Automatic Supervision .......................................................................................... 19

4.1 General Description ....................................................................................................... 19

4.2 Relay Self-supervision ................................................................................................... 19

4.2.1 Relay hardware monitoring .................................................................................... 19

4.2.2 DC Supply monitoring............................................................................................. 19

4.2.3 Fault detection monitoring ..................................................................................... 19

4.2.4 Check Output tripping circuit ................................................................................. 19

4.2.5 Check setting............................................................................................................ 19

4.3 AC Input Monitoring ....................................................................................................... 20

4.3.1 Voltage and current drift monitoring and auto adjusting .................................... 20

4.3.2 DSP sampling monitoring....................................................................................... 20

4.3.3 CPU sampling monitoring....................................................................................... 20

4.4 Secondary Circuit Monitoring ....................................................................................... 20

4.4.1 Opto-coupler power monitoring............................................................................. 20

4.4.2 Disconnector monitoring ........................................................................................ 20

NANJING NARI-RELAYS ELECTRIC CO., LTD v


RCS-924 Stub Differential Relay

4.4.3 CT circuit failure detection ..................................................................................... 20

Chapter 5 Metering and Recording ........................................................................................ 23

5.1 Metering Function........................................................................................................... 23

5.2 Recording Function........................................................................................................ 23

5.2.1 General description ................................................................................................. 23

5.2.2 Event recording........................................................................................................ 24

5.2.2.1 General description ...................................................................................... 24

5.2.2.2 Abnormal report information ......................................................................... 24

5.2.2.3 Change of binary input reports ..................................................................... 24

5.2.3 Fault recording......................................................................................................... 24

5.2.3.1 General description ...................................................................................... 24

5.2.3.2 Fault recording capacity and information ..................................................... 24

5.2.3.3 Fault waveform record capacity and information ......................................... 25

Chapter 6 Hardware Description ............................................................................................ 27

6.1 General............................................................................................................................. 27

6.2 Typical Wiring.................................................................................................................. 29

6.3 Plug-in Modules .............................................................................................................. 30

6.3.1 DC power supply module (#1 DC).......................................................................... 30

6.3.2 AC input module (#2 AC)......................................................................................... 30

6.3.3 Low-pass filter module (#3 LPF) ............................................................................ 31

6.3.4 Module CPU (#4 CPU).............................................................................................. 31

6.3.5 Communication interface module (#5 COM)......................................................... 32

6.3.6 Opto-coupler module (DC 24V) (#6 OPT) .............................................................. 33

6.3.7 Opto-coupler module (DC 220/110 Option) (#7 OPT 2) ........................................ 35

6.3.8 Signal relay module (#8 SIG) .................................................................................. 36

6.3.9 Output relay module (#9 OUT1).............................................................................. 36

6.3.10 Output relay module (#A OUT3) ........................................................................... 37

Chapter 7 Settings.................................................................................................................... 39

7.1 Equipment Setup ............................................................................................................ 39

7.2 Protection Settings......................................................................................................... 41

vi NANJING NARI-RELAYS ELECTRIC CO., LTD


RCS-924 Stub Differential Relay

7.3 Logic Settings ................................................................................................................. 43

7.4 Virtual Binary Input......................................................................................................... 44

7.5 IP ADDRESS .................................................................................................................... 44

Chapter 8 Human Machine Interface Operation.................................................................... 47

8.1 Human Machine Interface Overview............................................................................. 47

8.1.1 Design ....................................................................................................................... 47

8.1.2 Keypad operation..................................................................................................... 48

8.1.3 LED indications ........................................................................................................ 49

8.1.4 Communication port................................................................................................ 50

8.2 Understand The HMI Menu Tree.................................................................................... 50

8.2.1 Overview ................................................................................................................... 50

8.2.2 VALUES ..................................................................................................................... 51

8.2.3 REPORT .................................................................................................................... 53

8.2.4 PRINT ........................................................................................................................ 54

8.2.5 SETTINGS ................................................................................................................. 54

8.2.6 CLOCK ...................................................................................................................... 54

8.2.7 VERSION ................................................................................................................... 54

8.3 Understand the LCD Display ......................................................................................... 55

8.3.1 Main display under normal operation condition .................................................. 55

8.3.2 Display tripping report ............................................................................................ 55

8.3.3 Display abnormal report ......................................................................................... 56

8.3.4 Display status change of binary input................................................................... 57

8.3.5 View the settings...................................................................................................... 57

8.3.6 View Records............................................................................................................ 58

8.3.7 Printing reports and waveform............................................................................... 59

8.4 Input Operation Through Keypad ................................................................................. 60

8.4.1 Change the settings................................................................................................. 60

8.4.2 Copy settings ........................................................................................................... 60

8.4.3 Switch active setting group .................................................................................... 61

8.4.4 Delete fault records and event records ................................................................. 61

NANJING NARI-RELAYS ELECTRIC CO., LTD vii


RCS-924 Stub Differential Relay

8.4.5 Adjusting the clock .................................................................................................. 62

8.4.6 View software version ............................................................................................. 62

8.5 Understand the Alarms .................................................................................................. 63

Chapter 9 Communications .................................................................................................... 65

9.1 Communication with Substation Automation System ............................................... 65

9.2 Messages Description For IEC60870-5-103 Protocol ................................................. 65

9.2.1 Generic Service ........................................................................................................ 66

9.2.2 Function and Information ....................................................................................... 66

9.2.3 Disturbance ACC (Actual Channel)........................................................................ 67

9.2.4 Metering .................................................................................................................... 68

9.2.5 Blocking of monitoring direction ........................................................................... 68

9.2.6 Control Command.................................................................................................... 68

9.3 Messages Description For IEC61850 Protocol............................................................ 68

9.3.1 Overview ................................................................................................................... 68

9.3.2 Communication profiles.......................................................................................... 69

9.3.3 Server data organization ......................................................................................... 69

9.3.3.1 Digital status values...................................................................................... 70

9.3.3.2 Analog values ............................................................................................... 70

9.3.3.3 Protection logical nodes ............................................................................... 70

9.3.3.4 LLN0 and other logical nodes....................................................................... 71

9.3.4 Server features and configuration ......................................................................... 72

9.3.4.1 Buffered/unbuffered reporting ...................................................................... 72

9.3.4.2 File transfer................................................................................................... 72

9.3.4.3 Timestamps .................................................................................................. 72

9.3.4.4 Logical node name prefixes ......................................................................... 72

9.3.4.5 GOOSE services .......................................................................................... 73

9.3.5 ACSI conformance ................................................................................................... 74

9.3.5.1 ACSI basic conformance statement ............................................................. 74

9.3.5.2 ACSI models conformance statement.......................................................... 74

9.3.5.3 ACSI Services conformance statement........................................................ 76

viii NANJING NARI-RELAYS ELECTRIC CO., LTD


RCS-924 Stub Differential Relay

9.3.6 Logical nodes ........................................................................................................... 77

9.3.6.1 Logical nodes table....................................................................................... 77

9.4 Communication with printer.......................................................................................... 80

9.5 Communication with computer..................................................................................... 80

9.6 Communication with external clock ............................................................................. 80

Chapter 10 Installation And Commissioning......................................................................... 83

10.1 Introduction................................................................................................................... 83

10.2 Safety Information ........................................................................................................ 83

10.3 Overview ........................................................................................................................ 85

10.4 Unpacking And Checking The Protection Equipment.............................................. 85

10.5 Installing The Protection Equipment.......................................................................... 86

10.5.1 Overview ................................................................................................................. 86

10.5.2 Dimensions............................................................................................................. 86

10.5.3 Making the electrical connections ....................................................................... 87

10.6 Check The External Circuitry ...................................................................................... 89

10.7 Energizing the Protection Equipment ........................................................................ 90

10.8 Setting The Protection Equipment ............................................................................. 90

10.9 Establishing Connection And Verifying Communication......................................... 90

10.10 Verifying settings by secondary injection ............................................................... 91

10.10.1 AC measurement check ...................................................................................... 91

10.10.2 Percentage differential protection check .......................................................... 92

10.10.3 End fault protection check.................................................................................. 93

10.10.4 Overcurrent protection check ............................................................................ 93

10.10.5 Binary input check............................................................................................... 94

10.10.6 Output contact check .......................................................................................... 94

10.10.7 Print fault report................................................................................................... 94

10.11 Final Check.................................................................................................................. 94

Chapter 11 Maintenance .......................................................................................................... 95

11.1 Appearance Check........................................................................................................ 95

11.2 Failure Tracing And Repair .......................................................................................... 95

NANJING NARI-RELAYS ELECTRIC CO., LTD ix


RCS-924 Stub Differential Relay

11.3 Replace Failed Modules ............................................................................................... 96

11.4 Replace Button Battery ................................................................................................ 97

11.5 Cleaning ......................................................................................................................... 97

11.6 Storage........................................................................................................................... 97

Chapter 12 Software RCSPC................................................................................................... 99

12.1 General Description ..................................................................................................... 99

12.2 Connection Between RCS-924 And Computer.......................................................... 99

12.3 Parameter Configuration ........................................................................................... 100

12.3.1 Equipment configuration .................................................................................... 100

12.3.2 Software configuration........................................................................................ 100

12.4 Usage Instruction For RCSPC................................................................................... 102

12.4.1 Description for tool bar ....................................................................................... 102

12.4.2 Device settings..................................................................................................... 102

12.4.3 Show device status.............................................................................................. 103

12.4.4 Show device report.............................................................................................. 103

12.4.5 Signal reset........................................................................................................... 104

x NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 1 Introduction

Chapter 1 Introduction
1.1 Application
The RCS-924 is a digital stub differential relay, which mainly is designed for “T” zone in one and a
half busbar arrangement.

The protection function of RCS-924 comprises of percentage differential protection, end fault
protection and overcurrent protection. It is suitable for fast 3-terminal percentage differential
protection, and implements 3-pole tripping. In addition, 2-terminal percentage differential
protection is enabled automatically when line isolator is open, in the same time, two stages end
fault protection are also enabled.

Figure 1.1-1 Functional diagram of RCS-924

Where:

87: Percentage differential protection

51P: Definite-time phase overcurrent protection

51EF: End fault protection

1.2 Function
PERCENTAGE DIFFERENTIAL PROTECTION

n Percentage differential protection (87)

NANJING NARI-RELAYS ELECTRIC CO., LTD 1


Chapter 1 Introduction

BACKUP PROTECTION

n Two-stage end fault protection (51EF)

n Phase overcurrent protection (51P)

ADDITIONAL PROTECTION

n Self diagnostic test

n Fault Recorder including 128 tripping reports, 128 binary input change reports, 128
self-supervision reports and 128 miscellaneous reports, and 24 oscillograms (The format of
event report is compatible with international COMTRADE file.)

n GPS clock synchronization - second pulse, minute pulse, RS-485 difference level and IRIG-B
synchronization

n CT circuit failure detection logic

COMMUNICATIONS

n 2 RS-485 communication rear ports conform to IEC 60870-5-103 protocol

n 1 RS-485 communication rear ports for clock synchronization

n 1 RS-232 communication rear ports or RS-485 for printer

n 1 RS-232 communication faceplate port for testing and setting

n 2 optional Ethernet ports, IEC 61850

1.3 Features
n High speed and accuracy calculation because of DSP and microprocessor parallel computing.

n Plug connectors from the relay rear panel to the terminal blocks on the rack or cabinet, which
makes the on-site commissioning and replacement much easier than what you do the
commissioning using the traditional screw terminals on the rear panel.

n Two independent data acquisition paths, one for fault detector element and another for
protections and logic functions, to prevent any undesired trip.

n The CT ratio of 3-terminal could be different. Different ratio of various CT on each terminal
could be regulated by configurable coefficients in software.

n Friendly HMI interface with LCD and 9 button keypad on the front panel.

n 24 samples per cycle, all tasks including data measurement, protection calculation, logic
discrimination, event recording and protection logic calculation could be done within one
sampling period.

2 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 2 Technical Data

Chapter 2 Technical Data


2.1 Electrical Specifications
2.1.1 Analog input ratings
1. Analog current

Phase rotation: A, B and C


Nominal frequency: 50, 60Hz, ±10%
Rated Current 1A 5A
Linear to 30A 150A
(non-offset AC current) (non-offset AC current)
Thermal withstand
-continuously 3In 3In
-for 10s 30In 30In
-for 1s 100In 100In
-for half a cycle 250In 250In
Burden < 0.2VA/phase @ In < 0.5VA/phase @ In

2. Analog voltage

Per IEC 60255-6, IEC 60288


Rated Voltage 100V/ 3 , 110V/ 3 100V, 110V 200V
Linear to 100V 173V 230V
Thermal withstand
-continuously 120V 120V 200V
-10s 200V 200V 350V
-1s 250V 250V 400V
Burden at rated <0.2VA/phase @ Un < 0.5VA/phase@ Un < 2.5VA/phase @ Un

2.1.2 Power supply


Rated Voltage 24Vdc, 110Vdc, 125Vdc, 220Vdc, 250Vdc
Variation 80%-120%
Ripple in the DC Max 15% of the DC value. Per IEC 60255-11
auxiliary voltage
Voltage short Per IEC 61000-4-11, IEC 60255-11:1979
interruptions 20ms for interruption without de-energizing
Voltage dips Per IEC 61000-4-11, IEC 60255-11:1979
Up to 100ms for dips 60% of Un without reset
Quiescent
<10W
condition
Burden
Operating
<15W
condition

NANJING NARI-RELAYS ELECTRIC CO., LTD 3


Chapter 2 Technical Data

Backup battery type ML2032, 3V, 65mAh

2.1.3 Binary input


Rated Voltage 110VDC 125VDC 220VDC 250VDC
Pickup voltage 77VDC 87.5VDC 154VDC 175VDC
Dropout voltage 60.5VDC 68.8VDC 121VDC 137.5VDC
Maximum permitted 150V 150V 300V 300V
voltage
Withstand 2000Vac
Resolving time for 1ms
logic input

2.1.4 Binary output


Item Tripping contact Other contacts
Output mode Potential free contact
Continuous carry 8A 5A
Making capacity >1000W at L/R=40ms
Max system voltage 250VAC/DC
Test voltage across 1000Vrms
open contact, 1min
Short duration current 50A for 200ms
Pickup time 5/10ms 10/15ms
(Typical/Max)
Bounce time 1ms 1ms
Breaking capacity 0.4A resistance 0.2A resistance
(250Vdc) 0.2A inductive(L/R=40ms) 0.05A inductive (L/R=40ms)
Loaded
10,000 operations minimum 10,000 operations minimum
contact
Durability
Unloaded
100,000 operations minimum 100,000 operations minimum
contact

2.1.5 Power supply output for opto-coupler


Rated Voltage 24V
Rated Current 200mA
Max current 500mA

2.2 Mechanical Specifications


Enclosure dimensions 482.6×177×291 (unit: mm)
(W×H×D)
Mounting Way Flush mounted
Trepanning 450×179, M6 screw
dimensions (W×H)
Housing color Silver grey
Weight per device Approx. 15kg

4 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 2 Technical Data

Local control panel Small control module: 4 LED indicator a 9-key keypad and a 128×64
dot LCD
Display language English
Housing material Aluminum
Location of terminala Rear panel of the device
Protection class
Standard Per IEC60529:1989
Front side IP51 (Flush mounted)
Other sides IP30
Rear side, connection IP20
terminals

2.3 Ambient Temperature and Humidity Range


Standard IEC60255-6:1988
Operating temperature -25°C to +55°C

Transport and storage -40°C to +70°C


temperature range
Permissible humidity 5%-95%, condensation not permissible

2.4 Rear Communication Port


Interface for communicating with RTU/SCADA
Port number 2
Baud rate 4800~38400bps
Transmission distance <1000m@4800bps
Electrical Maximal capacity 32
Twisted pair Screened twisted pair cable
Protocol IEC 60870-5-103: 1997
Safety level Isolation to ELV level
Port number 2
RS-485
Connector type ST
(EIA)
Baud rate 4800~38400bps
Transmission standard 100Base-FX
Optical Transmission distance <1500m
(Optional) Optical fibre type Multi-mode fibre
Wave length 850/820nm
Fibre size 62.5/125μm (core DIA/cladding DIA)
Protocol IEC 60870-5-103: 1997
Safety level Isolation to ELV level
Port number 2
Connector type RJ-45
Transmission rate 100Mbits/s
Transmission standard 100Base-TX

NANJING NARI-RELAYS ELECTRIC CO., LTD 5


Chapter 2 Technical Data

Electrical Transmission distance <100m


Protocol IEC 60870-5-103: 1997 or IEC 61850
Ethernet Safety level Isolation to ELV level
Port number 2
Connector type SC
Transmission rate 100Mbits
Transmission standard 100Base-TX
Transmission distance <1500m
Optical
Optical fibre type Multi-mode or single-mode
(Optional)
Wave length 853/1310nm for multi-mode
1310/1550nm for single-mode
Fibre size 62.5/125μm (core DIA/cladding DIA)
Protocol IEC 60870-5-103: 1997 or IEC 61850
Safety level Isolation to ELV level
Rear interface for local HMI with personal computer via RCSPC software
Port number 1
Application Local HMI communication
Download protection program
RS-232 (EIA)
Baud rate 4800~9600bps
Connector type 9 pin D-type female connector
Safefy level Isolation to ELV level
Interface for communicating with printer
Prot number 1
Baud Rate 4800bps or 9600bps
RS-232 (EIA)
Printer type EPSON® 300K printer
Safety level Isolation to ELV level
Interface for clock synchronization
Port number 1
Transmission distance <500m
RS-485 (EIA) Maximal capacity 32
Timing standard PPS, IRIG-B
Safety level Isolation to ELV level

2.5 Type Tests


2.5.1 Environmental tests

Dry cold test


Per IEC60068-2-1:1990
Test Ad for 16 h at -10°C
Dry heat test
Per IEC60068-2-2:1974
Test Bd for 16 h at +55°C
Damp heat test, cyclic
Per IEC60068-2-30:1980

6 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 2 Technical Data

Test Db Two (12+12) hour cycles 95%RH, low temperature +25°C, high temperature +55°C

2.5.2 Mechanical tests

Vibration Class I IEC 60255-21-1:1988


Shock and bump Class I IEC 60255-21-2:1988

2.5.3 Electrical tests

Dielectric tests
Per IEC 60255-5:2000
Test voltage 2kV, 50Hz, 1min
Impulse voltage tests
Per IEC60255-5:2000
Test voltage 5kV, unipolar impulses waveform 1.2/50μs,source energy 0.5J
Insulation resistance measurements
Per IEC 60255-5:2000
Isolation resistance >100MΩ, 500Vdc

2.5.4 Electromagnetic compatibility


1MHz burst disturbance test
Per IEC 60255-22-1 (idt IEC61000-4-12)
Common mode class III 2.5KV
Differential mode class III 1.0KV
Electrostatic discharge test
Per IEC60255-22-2 class IV
For contact discharge 8kV
For air discharge 15kV
Radio frequency interference tests
Per IEC 60255-22-3 class III
Frequency sweep
Radiated amplitude-modulated

10V/m (rms), f=80…1000MHz

Spot frequency
Radiated amplitude-modulated

10V/m (rms), f=80MHz/160MHz/450MHz/900MHz

Radiated pulse-modulated

10V/m (rms), f=900MHz


Fast transient disturbance tests
Per IEC 60255-22-4
Power supply, I/O, Class IV, 4kV, 2.5 kHz, 5/50ns
Earth
Communication Class IV, 2kV, 5 kHz, 5/50ns
terminals

NANJING NARI-RELAYS ELECTRIC CO., LTD 7


Chapter 2 Technical Data

Surge immunity test


Per IEC 60255-22-5, 1.2/50us class III
Power supply, AC 2kV, line to earth; 1kV line to line
input, I/O port
Conducted RF Electromagnetic Disturbance
Per IEC 60255-22-6
Power supply, AC, I/O, Comm. Terminal Class III, 10Vrms, 150 kHz~80MHz
Power Frequency Magnetic Field Immunity
Per IEC 61000-4-8:1993
Class 5: 100A/m for 1min, 1000A/m for 3s
Pulse Magnetic Field Immunity
Per IEC 61000-4-9:1993
Class 5: 6.4/16μs, 1000A/m for 3s
Damped oscillatory magnetic field immunity
IEC 61000-4-10:1993
Class 5: 100kHz & 1MHz–100A/m

2.6 Certifications
l ISO9001: 2000

l ISO14001:2004

l OHSAS18001: 1999

l CMMI L2

l EMC:89/336/EEC, EN50263:2000

l Products safety(PS): 73/23/EEC, EN61010-1: 2001, EN60950:2002

2.7 Protective Functions


2.7.1 Accurate operating scope
Current : 0.1In~20In

2.7.2 General error of analog input metering


Current: ≤Max (0.02In, 5%)

Accuracy of GPS synchronization : ≤1ms

Resolution of SOE : ≤1ms

2.7.3 Differential protection


Setting range : 0.1In~20In

Tolerance: < Max(0.02In, 5%Setting)

2.7.4 End fault protection


Setting range : 0.1In~20In

8 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 2 Technical Data

Tolerance: < Max(0.02In, 5%Setting)

Time delay of stage 1 and stage 2: 0s~10s

Tolerance: ≤1%Setting+ 40ms (including operating time of contact)

2.7.5 Overcurrent protection


Setting range : 0.1In~20In

Tolerance: < Max(0.02In, 5%Setting)

Time delay : 0s~10s

Tolerance: ≤1%Setting+ 40ms (including operating time of contact)

NANJING NARI-RELAYS ELECTRIC CO., LTD 9


Chapter 2 Technical Data

10 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 3 Protection Description

Chapter 3 Protection Description


3.1 General Description
Main program accepts sampling interruption request, and then enters sampling program with
regular sampling period. The program flow will go to the regular program if no protective fault
detector element (PFD) operates, otherwise it will go to fault calculation program.

During the regular program flow, corresponding alarm will be issued to indicate there are some
errors in the protective device. if any failure is detected during the check. There are two kinds of
alarms: abnormal alarm and failure blocking alarm. In case of abnormal alarm, the protective
device could be still in service but the operator is warned to solve the problem. In case of failure
blocking alarm, the protective device will be blocked and the all protection functions will be
disabled.

Once any of protective fault detector elements operates, the program flow will go to the fault
calculation program. During the fault calculation program, various protection algorithms are
calculated, and then corresponding tripping logic is selected and sends tripping command. Finally,
event recorders, fault reports and fault waveform are formatted.

3.2 General Fault Detector element (GFD)


Main part of GFD is steady-state overcurrent fault detector element that reflects differential current
of 3-terminal and phase overcurrent fault detector element that reflects total current on both sides
of circuit is taken as supplementary.

The GFD comprise of the following elements:

n Differential current fault detector element

n Phase overcurrent fault detector element

If any of the above fault detector elements operates, the GFD will operate to provide DC power
supply to the output relays to switch on the output circuit.

3.2.1 Differential current fault detector element


The criterion:

ISCDΦmax>[I_Pkp_PcntDiff] Equation 3.2-1

Where:

ISCDΦmax=Max( I&A1 + I&A 2 + I&A3 , I&B1 + I&B 2 + I&B 3 , I&C1 + I&C 2 + I&C 3 ), the maximum among differential

current of phase A, differential current of phase B and differential current of phase C

[I_Pkp_PcntDiff]: Pick-up setting of current differential protection

If the differential current fault detector element operates, DC power supply will be provided to
output relay for 7 seconds.

NANJING NARI-RELAYS ELECTRIC CO., LTD 11


Chapter 3 Protection Description

3.2.2 Phase overcurrent fault detector element


The criterion:

Max( I&Φ1 + I&Φ 2 )>[I_OC] Equation 3.2-2

where:

Φ= A, B or C

I&Φ1 : Secondary phase current of CT1

I&Φ 2 : Secondary phase current of CT2

[I_OC]: Current setting of overcurrent protection

If the phase overcurrent fault detector element operates, DC power supply will be provided to
output relay for 7 seconds.

Note!

It is valid only if overcurrent protection is enabled. (Energizing binary input [EBI_OC] and
Setting virtual binary input [VEBI_OC] as “1”)

3.3 Protective Fault Detection (PFD)


The protective fault detection element is the same as the general fault detection element.

3.4 Current Differential Protection


RCS-924 can be used to either 3-terminal differential or 2-terminal differential in applications like
below. It is often used to 3-terminal differential, however, 2-terminal differential is enabled
automatically only if line isolator is open.

12 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 3 Protection Description

3.4.1 3-terminal application

Figure 3.4-1 3-Terminal application

3-terminal differential protection consists of percentage differential protection. When percentage


differential protection is enabled, 3-terminal differential protection is valid if auxiliary contact of line
isolator is open (line isolator is closed).

The criterion :

Icd>[I_Pkp_PcntDiff] Equation 3.4-1

Icd>[Slop_PcntDiff]×Ir Equation 3.4-2

Where:

Icd: Differential current ( I cd = I&Φ1 + I&Φ 2 + I&Φ 3 )

Ir: Restraint current ( I r =


2
(
1 &
)
I Φ1 + I&Φ 2 + I&Φ 3 )

[I_Pkp_PcntDiff]: Pick-up setting of current differential protection

[Slop_PcntDiff]: Percentage restraint coefficient

When Icd>1.3IN, percentage differential protection operates and outputs tripping command without
time delay.

When Icd<1.3IN, percentage differential protection operates and outputs tripping command after
20ms

Both local circuit breakers are tripped and transfer trip is initiated after 3-terminal differential
protection operates.

NANJING NARI-RELAYS ELECTRIC CO., LTD 13


Chapter 3 Protection Description

3.4.2 2-terminal application


2-terminal differential protection consists of percentage differential protection. When current
differential protection is enabled, 2-terminal differential protection is valid if auxiliary contact of line
isolator is closed (line isolator is open).

The criterion :

Icd>[I_Pkp_PcntDiff] Equation 3.4-3

Icd>[Slop_PcntDiff]×Ir Equation 3.4-4

Where:

Icd: Differential current ( I cd = I&Φ1 + I&Φ 2 )

Ir: Restraint current ( I r =


2
(
1 &
)
I Φ1 + I&Φ 2 )

[I_Pkp_PcntDiff]: Pick-up setting of current differential protection

[Slop_PcntDiff]: Percentage restraint coefficient

When Icd>1.3IN, percentage differential protection operates and outputs tripping command without
time delay.

When Icd<1.3IN, percentage differential protection operates and outputs tripping command after
20ms.

Both local circuit breakers are tripped but transfer trip is not initiated after 2-terminal differential
protection operates.

I&Φ1 , I&Φ 2 and I&Φ 3 are secondary phase current of CT1, CT2 and CT3 respectively. Φ= A, B or C

3.5 End Fault Protection


End fault protection consists of two stages end fault protection. When end fault protection is
enabled, end fault protection is valid if auxiliary contact of line isolator is closed (line isolator is
open).

The criterion:

IΦ3max>Iglzd Equation 3.5-1

Iscdmax>[I_Pkp_PcntDiff] Equation 3.5-2

Where:

IΦ3max=Max(IA, IB, IC), IA, IB and IC are secondary phase current of CT3

Iglzd: Current setting of overcurrent protection [I_EFP1] or [I_EFP2]

Iscdmax=Max( I&A1 + I&A 2 + I&A3 , I&B1 + I&B 2 + I&B 3 , I&C1 + I&C 2 + I&C 3 ), the maximum among differential

14 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 3 Protection Description

current of phase A, differential current of phase B and differential current of phase C

[I_Pkp_PcntDiff]: Pick-up setting of current differential protection

In order to prevent protective device undesired operation resulting from error in auxiliary contact of
isolator, end fault protection is blocked by differential current fault detector element.

When IΦ3max>[I_EFP1], stage 1 of end fault protection will operate after time delay [t_EFP1] and
transfer trip will be initiated.

When IΦ3max>[I_EFP2], stage 2 of end fault protection will operate after time delay [t_EFP2] and
transfer trip will be initiated.

3.6 Overcurrent Protection


Overcurrent protection can be enabled or disabled by binary input [EBI_OC], virtual binary input
[VEBI_OC] and logic setting [En_OC]. Based on calculating total current of CT1 and CT2,

The criterion:

Max( I&Φ1 + I&Φ 2 )>Ichzd Equation 3.6-1

I&Φ1 : secondary phase current of CT1

I&Φ 2 : secondary phase current of CT2

Φ= A, B or C

Ichzd: current setting of overcurrent protection for SOTF [I_OC]

Both local circuit breakers will be tripped if overcurrent protection operates.

3.7 Scheme logic


Ilcda: Differential current of phase A for 2-terminal differential element

Ilcdb: Differential current of phase B for 2-terminal differential element

Ilcdc: Differential current of phase C for 2-terminal differential element

Iscda: Differential current of phase A for 3-terminal differential element

Iscdb: Differential current of phase B for 3-terminal differential element

Iscdc: Differential current of phase C for 3-terminal differential element

Ilra: Restraint current of phase A for 2-terminal differential element

Ilrb: Restraint current of phase B for 2-terminal differential element

Ilrc: Restraint current of phase C for 2-terminal differential element

Isra: Restraint current of phase A for 3-terminal differential element

NANJING NARI-RELAYS ELECTRIC CO., LTD 15


Chapter 3 Protection Description

Isrb: Restraint current of phase B for 3-terminal differential element

Isrc: Restraint current of phase C for 3-terminal differential element

Flag_En_OC
&
. .
Max(IIΦ1+IΦ2I)>[I_OC] [t_OC]

Ilcda>=[I_Pkp_PcntDiff]
&

Ilcda>=Kbl×Ilra &

Ilcda>=1.3×IN ≥1

≥1 ≥1 Tripping

Flag_CTS
& 20ms 0
Fiag_DS

Flag_2T_Diff_PhB

Flag_2T_Diff_PhC
&

Flag_En_Diff

Iscdmax>=[I_Pkp_PcntDiff]
& &

Iscda>=Kbl×Isra &

Iscda>=1.3×IN ≥1

≥1

& 20ms 0

Flag_3T_Diff_PhB
Flag_3T_Diff_PhC

& [t_EFP1]

& Initiating transfer


IΦ3max>=[I_EFP1] ≥1
trip
≥1

& [t_EFP2]

IΦ3max>=[I_EFP2] &

Iscdmax>=[I_Pkp_PcntDiff]

Flag_En_EFP

Figure 3.7-1 Scheme logic diagram of RCS-924

Please refer to Chapter 7 about the description of corresponding settings.

1. Flag_En_Diff: The flage of enabling percentage differential protection

n [En_PcntDiff]=1, [EBI_PcntDiff]=1 and [VEBI_PcntDiff]=1

2. Flag_En_OC: The flag of enabling overcurrent protection

n [En_OC]=1, [EBI_OC]=1 and [VEBI_OC]=1

3. Flag_En_EFP: The flag of enabling end fault protection

n stage 1: [En_EFP1]=1, [EBI_EFP]=1 and [VEBI_EFP]=1

n stage 2: [En_EFP2]=2, [EBI_EFP]=1 and [VEBI_EFP]=1

4. Flag_CTS: The flag of CT circuit failure

16 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 3 Protection Description

5. Flag_DS: The flag of disconnector position. Normally closed auxiliary contact of line
disconnector is connected to the protective device. When line disconnector is open, auxiliary
contact is closed and the logic input [Flag_DS] is “1”. When line disconnector is closed,
auxiliary contact is open and the logic input [Flag_DS] is “0”.

NANJING NARI-RELAYS ELECTRIC CO., LTD 17


Chapter 3 Protection Description

18 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 4 Automatic Supervision

Chapter 4 Automatic Supervision


4.1 General Description
Though the protection system is in non-operating state under normal conditions, it is waiting for a
power system fault to occur at any time and must operate for the fault without fail. When
equipment is in energizing process before the LED “HEALTHY” is on, the equipment need to be
checked to ensure no errors. Therefore, the automatic supervision function, which checks the
health of the protection system when startup and during normal operation, plays an important role.

The numerical relay based on the microprocessor operations is suitable for implementing this
automatic supervision function of the protection system.

In case a fault is detected during initialization when DC power supply is provided to the equipment,
the equipment will be blocked out, which means relay is out of service. Therefore you must
re-energize the relays or reset CPU module by restarting equipment to make relay back into
service.

When a failure is detected by the automatic supervision, it is followed with an LCD message, LED
indication and alarm contact outputs. At the same time event recording will record the failure alarm
which can be viewed in event recording report and be printed.

4.2 Relay Self-supervision


4.2.1 Relay hardware monitoring
The DSP, RAM, ROM chips on CPU module are monitored to ensure whether they are damaged
or have errors. If any one of them is detected damaged or having error, equipment will be blocked
and issue alarm [Alm_RAM] and [Alm_ROM].

4.2.2 DC Supply monitoring


The secondary voltage level of the built-in DC/DC converter is monitored and checked whether the
DC voltage is within a prescribed range.

If a failure is detected in the DC power supply circuit, [Alm_Pwr_DC] alarm will be issued and the
relay will be blocked.

4.2.3 Fault detection monitoring


When any general fault detector picks up for longer than 10s, an alarm will be issued
[Alm_PersistFD] without equipment blocked.

4.2.4 Check Output tripping circuit


Chips controlling the output relays in the output circuit are continually monitored. If any error or
damage is detected in these chips, alarm [Alm_TripOut] will be given and the relay will be blocked.

4.2.5 Check setting


RCS-924 series has 30 setting groups, while only one is active at the same time. The settings of
active setting group are checked to ensure they are reasonable. If the settings are checked to be

NANJING NARI-RELAYS ELECTRIC CO., LTD 19


Chapter 4 Automatic Supervision

invalid, an alarm [Alm_Setting] will be issued. Equipment is blocked. At the same time. if there is
any summation error of all setting groups, an alarm [Alm_EEPROM] will be issued, equipment is
also blocked.

If these 30 setting groups are not all set, when the equipment is provided DC power supply first, an
alarm [Alm_InvalidGrp] will be issued. If the secondary rated current of CT (I2n) in equipment
settings is changed and the protection settings is not confirmed or some settings in protection
settings exceed setting range, an alarm [Alm_InvalidGrp] will be issued.

4.3 AC Input Monitoring


4.3.1 Voltage and current drift monitoring and auto adjusting
Zero point of voltage and current may drift influenced by variation of temperature or other
environment factors. The equipment continually automatically traces the drift and adjusts it to
normal value.

4.3.2 DSP sampling monitoring


AC sampling of DSP chip is monitored and if the samples are detected to be wrong, an alarm
[Alm_Smpl_DSP] will be issued and the relay will be blocked.

4.3.3 CPU sampling monitoring


The relay compares the CPU sampling and DSP sampling. In normal condition, the sampling
should be the same for a certain AC input. If a sampling in CPU is detected to be different largely
with that in DSP, an alarm [Alm_Smpl_CPU] will be issued and the relay will be blocked.

4.4 Secondary Circuit Monitoring


4.4.1 Opto-coupler power monitoring
Positive power supply of opto-coupler is continually monitored. If an error or damage has occurred,
an alarm [Alm_Pwr_Opto] will be issued.

4.4.2 Disconnector monitoring


If line disconnector is open, i.e. normally closed auxiliary contact is closed, and there is current
flowing through the line, an alarm [Alm_BI_DS] will be issued after 10 seconds.

4.4.3 CT circuit failure detection


The main purpose of the current transformer (CT) circuit failure supervision function is to detect
faults in the secondary circuits of CT and avoid influence on the operation of corresponding
protection functions.

CTS with time delay is executed in the sampling program. If the operating time of differential
current fault detector element is longer than 10 seconds, an alarm [Alm_CTS] will be issued after
time delay. CTS with time delay can also finish self-checking for sampling circuit.

CTS without time delay is executed in the fault measurement program, CTS without time delay will
be disabled if any of the following conditions is met.

1. Maximum phase current is less than 0.2In before fault detector element operates.

20 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 4 Automatic Supervision

2. Maximum phase current is greater than 1.2In after fault detector element operates.

3. Phase current after fault detector element operating comparing with that before fault detector
element operating increases more than 0.1In.

When the following conditions for any side are both met, an alarm [Alm_CTS] will be issued
immediately.

1. Any phase current is less than 0.1In.

2. The other two phase currents after fault detector element operating are equal to those before
fault detector element operating(the difference is smaller than 0.1In).

NANJING NARI-RELAYS ELECTRIC CO., LTD 21


Chapter 4 Automatic Supervision

22 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 5 Metering and Recording

Chapter 5 Metering and Recording


5.1 Metering Function
RCS-924 performs continuous measurement of the analogue input quantities. The relay samples
24 points per cycle and calculates the RMS value in each interval and updated the LCD display in
every 0.5 second. The measurement data can be displayed on the LCD of the relay front panel or
on the local via software RCCSPC or remote PC. Navigate the menu to view the sampling value
through LCD screen. Access path in menu is:

Figure 5.1-1 Access path in menu tree for VALUES

Measured directly

n Magnitude of phase current of CT1 (Ia1, Ib1, Ic1)

n Magnitude of phase current of CT2 (Ia2, Ib2, Ic2)

n Magnitude of phase current of CT3 (Ia3, Ib3, Ic3)

n Phase angle of (Ia1-Ib1), (Ib1-Ic1), (Ic1-Ia1)

n Phase angle of (Ia2-Ib2), (Ib2-Ic2), (Ic2-Ia2)

n Phase angle of (Ia3-Ib3),(Ib3-Ic3), (Ic3-Ia3)

n Phase angle of (Ia1-Ia2), (Ib1-Ib2), (Ic1-Ic2)

n Phase angle of (Ia1-Ia3), (Ib1-Ib3), (Ic1-Ic3)

n Phase angle of (Ia2-Ia3), (Ib2-Ib3), (Ic2-Ic3)

Calculated by DSP

n Differential current (Id_a, Id_b, Id_c)

5.2 Recording Function


5.2.1 General description
The RCS-924 series provides the following recording functions:

n Event recording

NANJING NARI-RELAYS ELECTRIC CO., LTD 23


Chapter 5 Metering and Recording

n Fault recording

These records are displayed on the LCD of the relay front panel or on the local or remote PC.
Navigate the menu to view the report through LCD screen. Access path in menu is:

MENU
1: VALUES
2: REPORT REPORT
3: PRINT
1: TRP REPORT
4: SETTINGS
2: ALM REPORT
5: CLOCK
3: BI CHG REPORT
6: VERSION
4: MISC REPORT
0: EXIT
0: EXIT

Figure 5.2-1 Access path in menu tree for REPORT

5.2.2 Event recording


5.2.2.1 General description

Event recording includes abnormal report or change of binary input reports. The equipment can
store 128 records of each kind in non-volatile memory.

5.2.2.2 Abnormal report information

n Failure alarms of automatic supervision

All failure alarms of automatic supervision will be logged in event recording.

n Setting Changes

Changes to any setting within the relay are logged as an event.

5.2.2.3 Change of binary input reports

If one or more of the binary inputs has changed state from “0” to “1” or from “1” to “0”, it will be
logged as an event.

5.2.3 Fault recording


5.2.3.1 General description

Disturbance recording is consisted of fault operation report recording and fault waveform recording.
Disturbance recording is initiated by fault detection element.

There are two types of disturbance recording initiation: with and without pickup of protective
elements.

5.2.3.2 Fault recording capacity and information

The equipment can store 128 records of operation report in non-volatile memory. If a new fault
occurs when 128 faults have been stored, the oldest fault report is overwritten by the latest one.

This equipment captures current and voltage waveforms and can store up to 24 oscillography

24 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 5 Metering and Recording

wave form data with COMTRADE format.

For each trip report, the following items are included:

n Sequence number

Each operation will be recorded with a sequence number in the report and displayed on LCD
screen.

n Date and time of fault occurrence

The time resolution is 1ms using the relay internal clock synchronized via GPS if connected.
Initiating time is the moment when a protective fault detector operates.

n Operating time

An operating time (not including the operating time of output relays) is recorded in the report.

n Protective elements

For the details of designation of each protective element, please refer to 8.3.2 Display tripping
report

5.2.3.3 Fault waveform record capacity and information

The equipment can save 24 pieces of fault waveform oscillogram. If a new fault occurs when 24
fault waveform records have been stored, the latest waveform record overwrites the oldest one.
The equipment stores actual samples that are taken at a rate of 24 samples per cycle.

The recording time before fault detection initiation is fixed at 2 cycles (40 ms at 50Hz). The
recording time after fault detector initiation is fixed at 6 cycles (120 ms at 50Hz) without protection
operation or with protection operation within 6 cycles. If any protection element operates after 6
cycles, then the recording time will be prolonged to another 8 cycles (160ms at 50Hz) in order to
show continuous 8 cycle waveform after the protection element operates.

NANJING NARI-RELAYS ELECTRIC CO., LTD 25


Chapter 5 Metering and Recording

26 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 6 Hardware Description

Chapter 6 Hardware Description


6.1 General
RCS-924 is made of a 4U height 19” chassis for panel flush mounting. Components mounted on
its front include a 128×64 dot matrix LCD, a 9 button keypad, 8 LED indicators, a signal reset
button, a 9 pin connector for communication with PC and a 15 pin connector for analog quantity
inputs by HELP-90A during commissioning. A monolithic micro controller is installed in the
equipment for these functions. Shown as Figure 6.1-1 front view of RCS-924.

GRP
ESC

Figure 6.1-1 Front view of RCS-924

The 4 LED indicators are, from top to bottom, operation (HEALTHY), line is out of service (LINE
OUT), protection operates (TRIP), initiating transfer trip (TRFR TRIP). A button of target reset is
below these indicators.

As to buttons of the keypad, ENT is “enter”, GRP is “group number” and ESC is “escape”.

Figure 6.1-2 Rear view of RCS-924

RCS-924 comprises following 9 plug-in modules. Figure 6.1-2 is rear view of the equipment and
shows disposition of these modules.

NANJING NARI-RELAYS ELECTRIC CO., LTD 27


Chapter 6 Hardware Description

Table 6.1-1 Hardware configuration

Item Description
DC DC power supply
AC AC current and voltage input
LPF low-pass filter
CPU control nucleus of the equipment
COM communication interface
OPT1 binary input opto-coupler module (DC 24V)
OPT2 binary input opto-coupler module (DC 220/110V)
SIG signal module
OUT1 output module 1
OUT3 output module 3 (Optional)

28 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 6 Hardware Description

6.2 Typical Wiring

Figure 6.2-1 RCS-924 integral structure diagram

NANJING NARI-RELAYS ELECTRIC CO., LTD 29


Chapter 6 Hardware Description

6.3 Plug-in Modules


6.3.1 DC power supply module (#1 DC)
DC power supply (250V/220V/125V/110 V) shall be connected to terminals 101 (+) and 102 (-).
Through interference filter and power switch on the rear, DC/DC converter converts the DC power
supply to three voltage class +5V, ±12V and +24V to supply to other modules of the equipment.
Terminal 104 (+) and terminal 105 (-) output ±24V as power supply of OPT. Terminal 106 is surge
ground. Figure 6.3-1 shows rear view and connections of DC power supply module.

Interference filter

Figure 6.3-1 Rear view and connections of DC module

Note!

When ordering, please mark the input voltage class of DC power supply.

6.3.2 AC input module (#2 AC)


I1A, I1B and I1C are three-phase current of CT1. I2A, I2B and I2C are three-phase current of CT2. I3A,
I3B and I3C are three-phase current of CT3. They are input into AC module separately with rating 5A
or 1A. Please declare which kind of AC module is needed before ordering. Terminal 201, 203 and
205 are polarity marks of CT1. Terminal 207, 209 and 211 are polarity marks of CT2. Terminal 213,
215 and 217 are polarity marks of CT3. Terminal 219 is ground point. It shall be connected to
ground bus. Figure 6.3-2 shows rear view and typical connection of AC input module.

30 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 6 Hardware Description

CURRENT 1
CURRENT 2

Isolator
CURRENT 3

To LPF
To LPF

To LPF
Figure 6.3-2 Rear view and typical connections of AC module

6.3.3 Low-pass filter module (#3 LPF)


This module is used to filter high frequency disturbance from the AC module, regulate the input
level and used as an interface between the equipment and dedicated test instrument HELP-90A
developed by NARI-RELAYS.

Figure 6.3-3 Block diagram of module LFP module

6.3.4 Module CPU (#4 CPU)


Module CPU, control nucleus of the equipment, comprises monolithic micro controller CPU and
digital signal processor DSP. CPU finishes the following functions:

n General fault detection

n Event recorder, fault oscillograph recorder (could be printed via serial port)

n Print and communication with HMI

n Communication with the host of SCADA system of the substation

DSP finishes the following functions:

n Algorithm and logic of protection

NANJING NARI-RELAYS ELECTRIC CO., LTD 31


Chapter 6 Hardware Description

Sampling rate of the equipment is 24 points per cycle. Parallel real time data is calculated for
algorithm and logic of protection at every sampling point. Hence, very high inherent reliability and
security are ensured.

6.3.5 Communication interface module (#5 COM)


Module COM performs connection between the equipment and the SCADA system or RTU. Three
types are available.

RS485 ports provided by type 5A and type 5B can communicate with SAS and RTU and support
IEC60870-5-103 protocol, moreover, Ethernet port in COM modules of type 5C also supports
IEC61850. From Figure 6.3-4 to Figure 6.3-6 shows rear view of these types and their external
connections.

All type are equipped with a RS-485 port for receiving second pulse signal (PPS-pulse per second)
from GPS and a port for printer. Printer port could be configured as RS-232 or RS-485 by setting
corresponding jumpers on the PCB (RS-232 default). If logic setting [En_Net_Print] is set to “1” ,
printer port must be set as RS-485. Transmission rate of printer port can be set by the setting
[Printer_Baud] and should be the same with baud rate of the printer.

Figure 6.3-4 Rear view of type A and external connections of COM module

Figure 6.3-5 Rear view of type B and external connections of COM module

32 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 6 Hardware Description

Figure 6.3-6 Rear view of type C and external connections of COM module

There are three options to finish time synchronization:

1. Receiving PPS (pulse per second) and PPM (pulse per minute) via external contact

2. Receiving IRIG-B signal via RS-485

3. Receiving time synchronization message from substation automatic system

Note!

For the port used to printer or controller, it can be configured as RS-485 or RS-232 by
setting corresponding jumper of module COM. The port is configured as RS-232 by
shorting PIN 1 and PIN 2 and as RS-485 by shorting PIN 2 and PIN 3. As shown in Figure
6.3-7

Figure 6.3-7 Print Port Configuration

6.3.6 Opto-coupler module (DC 24V) (#6 OPT)


1. Terminal 601

It is used to receive clock synchronism signal from GPS or other equipment used clock
synchronism, the binary input [BI_Pulse_GPS] will change from “0” to “1” one time per second or
per minute depended on the setting [GPS_Pulse]. When setting [GPS_Pulse] is set to “1”, the
equipment receives PPM (pulse per minute), otherwise, receives PPS (pulse per second). Clock
synchronism via RS-485 bus is recommended. Only one of them can be selected.

2. Terminal 602

It is the manual input [BI_Print] to trigger printing latest report when the equipment is configured as

NANJING NARI-RELAYS ELECTRIC CO., LTD 33


Chapter 6 Hardware Description

manual printing mode by logic setting [En_Auto_Print]=0. The printer button is located on the
panel usually. If the equipment is configured as automatic printing mode ([En_Auto_Print]=1),
report will be printed automatically as soon as it is formed.

3. Terminal 603

It is maintenance status input [BI_BlkComm] to block monitoring direction communication. A


isolator link located on the panel is used for that. When the equipment is in maintenance or
commissioning status, this link should be closed. All of the reports will not be sent via
communication port then, but local displaying and printing are still working. This link should be
open during normal operation condition.

4. Terminal 604

It is input for reset of latching signal relay and LCD displaying [BI_RstTarg]. The reset is done by
pressing a button on the panel or by remote command via communication channel.

5. Terminal 605

It is percentage differential protection enabling input [EBI_PcntDiff].

6. Terminal 606

It is end fault protection enabling input [EBI_EFP].

7. Terminal 607

It is overcurrent protection enabling input [EBI_OC].

8. Terminal 622

It is input of normally closed auxiliary contact of disconnector. [BI_DS_Line]

When line disconnector is open, binary input [BI_DS_Line] is energized.

Figure 6.3-8 shows rear view and external connections of OPT module.

34 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 6 Hardware Description

Figure 6.3-8 Rear view and external connections of OPT1 module

6.3.7 Opto-coupler module (DC 220/110 Option) (#7 OPT 2)


If normally closed auxiliary contact of line disconnector is connected to the protective device
directly, DC 24V opto-coupler module is not suitable becase of the heavy disturbance and DC
220V/110V opto-coupler module is designed for this case. Figure 6.3-9 shows rear view and
external connections of OPT2 module.

Terminal 701 and terminal 717 are the positive pole of DC 220V/110V power supply and terminal
711 and terminal 727 is the negative pole of DC 220V/110V power supply.

1. Terminal 703

It is input of normally closed auxiliary contact of disconnector. [BI_DS_Line]

When line disconnector is open, binary input [BI_DS_Line] is energized.

Terminal 701 does not connects with terminal 717 and terminal 711 does not connects with
terminal 727 internally, hence, when one group of power supply for opto-coupler is used, the other
group must be connected with DC power supply. Otherwise, an alarm [Alm_Pwr_Opto] will be
issued.

NANJING NARI-RELAYS ELECTRIC CO., LTD 35


Chapter 6 Hardware Description

Binary input common DC+


OPT 701 Positive polarity of DC220V/110V OPTO

703 BI_DS_Line

705 RESERVE
701
703
707 RESERVE
705
707
709 RESERVE
709
711
Binary input common DC- 711 Negative polarity of DC220V/110V OPTO

717
Binary input common DC+
719 717 Positive polarity of DC220V/110V OPTO
721
723 719 RESERVE

725
727 721 RESERVE

723 RESERVE

725 RESERVE

Binary input common DC- 727 Negative polarity of DC220V/110V OPTO

Figure 6.3-9 Rear view and external connections of OPT2 module

6.3.8 Signal relay module (#8 SIG)


There are no connections in the SIG module, which is used to convert 5V signal to 24V signal via
triode to drive relay. Under normal operation condition, all output of triodes should be checked,
moreover, an alarm [Alm_TrpOut] will be issued and protective device will be blocked if any error is
detected.

There is general fault detector element in the SIG module. General fault detector element will
operates and DC power supply is provided if pick-up condition is met in CPU.

6.3.9 Output relay module (#9 OUT1)


Figure 6.3-10 shows output contacts and corresponding terminals provided by this module.

} }
} }
Figure 6.3-10 Output contacts and terminals of OUT1 module

1. BO_Alm_Fail is an equipment failure alarm relay.

36 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 6 Hardware Description

Its normally closed contacts, BO_Alm_Fail1-2 and BO_Alm_Fail2-2, will be closed if DC power
supply of the equipment is lost or internal failure occurs.

2. BO_Alm_Abnor is an abnormality alarm relay.

Its normally open contacts, BO_Alm_Abnor-1 and BO_Alm_Abnor-2, will be closed and alarm
signal will be sent when protective device is in abnormal condition but still in service, such as CT
circuit failure, etc..

3. BO_Trp is magnetic latching target relay for tripping.

When the protective device operates, BO_Trp will operate and be latched until pressing signal
reset button on the faceplate, or pressing signal reset button on the panel to energize binary input
[BI_RstTarg] or remote reset signal being received via communication channel.

4. BO_InitTT is magnetic latching target relay for initiating transfer trip.

When the protective device operates to initiate transfer trip, BO_InitTT will operate and be latched
until pressing signal reset button on the faceplate, or pressing signal reset button on the panel to
energize binary input [BI_RstTarg] or remote reset signal being received via communication
channel.

5. BO_Trp1, BO_Trp2 and BO_Trp3 are tripping relays

They are non-latching relay. They operates when protective device operates and drops off when
protective element drops off,

6. BO_InitTT1 and BO_InitTT2 are relays for initiating transfer trip

They operates when protective device operates to initiate transfer trip.

6.3.10 Output relay module (#A OUT3)


When these contacts in the OUT1 module are not enough to used, OUT3 module can be use as a
expansion. Additional four sets of trip contacts can be gained. Figure 6.3-11shows output contacts
and corresponding terminals provided by this module.

Figure 6.3-11 Output contacts and terminals of OUT3 module

NANJING NARI-RELAYS ELECTRIC CO., LTD 37


Chapter 6 Hardware Description

38 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 7 Settings

Chapter 7 Settings
The equipment has 30 setting groups for protection to coordinate with the mode of power system
operation, one of which is assigned to be active. However, equipment parameters are common for
all protection setting groups.

Note!

All current settings in this chapter are secondary current converted from primary current by
CT ratio.

7.1 Equipment Setup


Table 7.1-1 Equipment setup

No. Item Range


1 Active_Grp 0~29
2 Comm_Addr 0~254
3 COM1_Baud 4800/9600/19200/38400 bit/s
4 COM2_Baud 4800/9600/19200/38400 bit/s
5 Printer_Baud 4800/9600/19200/38400 bit/s
6 Debug_Baud 4800/9600 bit/s
7 fn 50Hz/60Hz
8 U1n 127 Kv~655 Kv
9 U2n 57.73 V
10 I1n 0.1 KA~65.535 KA
11 I2n 1 A or 5 A
12 Equip_ID
13 En_Net_Print 0/1
14 En_Auto_Print 0/1
15 Protocol 0/1
16 GPS_Pulse 0/1
17 En_Remote_Cfg 0/1

² Settings description

1. Active_Grp

Current active group of setting;

Thirty setting groups are provided for selecting, group number from 0 to 29. Equipment setup is
shared for 30 setting groups and only protection settings are independent.

2. Comm_Addr

Communication address between the equipment with the SCADA or RTU via RS-485;

NANJING NARI-RELAYS ELECTRIC CO., LTD 39


Chapter 7 Settings

3. COM1_Baud

Baud rate of rear RS-485 communication port 1;

4. COM2_Baud

Baud rate of rear RS-485 communication port 2;

5. Printer_Baud

Baud rate of printer port;

6. Debug_Baud

Baud rate of front communication port for setting and testing via the software RCSPC;

7. fn

System nominal frequency;

8. U1n

Primary rated voltage of VT;

9. U2n

Secondary rated voltage of VT;

10. I1n

Primary rated current of CT;

11. I2n

Secondary rated current of CT;

12. Equip_ID

The identity of substation or plant;

13. En_Net_Print

“1” means that the printer is shared, otherwise, it should be set to “0”;

14. En_Auto_Print

Enable automatic printing;

“1” means that even report (such as trip, alarm and so on) will be automatically printed after a new
event occurs; otherwise, it should be set as “0”;

15. Protocol

Communication protocol;

0: IEC-60870-5-103 or IEC-61850

Depended on COM module, if type 5A or type 5B is used, IEC-60870-5-103 is selected as


communication protocol. If type 5C is used, IEC-61850 is selected as communication protocol.

40 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 7 Settings

1: LFP protocol, a proprietary protocol developed by NARI-RELAYS

16. GPS_Pulse

“1” means minute pulse for time synchronism, “0” means second pulse for time synchronism.

17. En_Remote_Cfg

“1” means that settings can be remotely configured via SCADA or RTU, otherwise, it should be set
to “0”.

7.2 Protection Settings


All settings of protection are based on secondary ratings of VT and CT.

Table 7.2-1 Protection settings

No. Item Remark Range


1 k_Corr_CT1 Adjustment coefficient of CT ratio for CT1 0.01~4
2 k_Corr_CT2 Adjustment coefficient of CT ratio for CT2 0.01~4
3 k_Corr_CT3 Adjustment coefficient of CT ratio for CT3 0.01~4
4 I_Pkp_PcntDiff Pick-up setting of percentage differential protection 0.1 ~1.0A×In
5 Slope_PcntDiff Slope of percentage differential protection 0.3~1.0
6 I_EFP1 Current setting for stage 1 of end fault protection 0.1~20A×In
7 t_EFP1 Time delay for stage 1 of end fault protection 0.01~10S
8 I_EFP2 Current setting for stage 1 of end fault protection 0.1~20A×In
9 t_EFP2 Time delay for stage 1 of end fault protection 0.01~10S
10 I_OC Current setting for overcurrent protection 0.1~20A×In
11 t_OC Time delay for overcurrent protection 0.01~10S
12 Line_ID Number of the line 0~65535

² Settings description

1. K_Corr_CT1/K_Corr_CT2/K_Corr_CT3

CT ratio correction

The ratios of CT1, CT2 and CT3 different. They could be corrected by setting [k_Corr_CT1],
[k_Corr_CT2] and [k_Corr_CT3].

Setting principle: take primary rated value of any CT as reference value, and set its correction
coefficient as “1”. The other two correction coefficients of CTs are ratio between its primary rated
value and reference value. In order to ensure accuracy, the difference of ratio among these
primary rated value should not be greater than 4. System capacity of short circuit should be
greater than 0.2IN and less than 125IN after reducting to secondary of reference CT.

For example:

TA1: CT ratio=1500 : 5, TA2: CT ratio=2000 : 5, TA3: CT ratio=2000 : 5

[k_Corr_CT]=0.75; [k_Corr_CT2]=1.00; [k_Corr_CT3]=1.00

NANJING NARI-RELAYS ELECTRIC CO., LTD 41


Chapter 7 Settings

or

[k_Corr_CT]=1.00; [k_Corr_CT2]=1.33; [k_Corr_CT3]=1.33

Note!

All settings are set based on reference CT. and all currents is displayed after reducting to
reference value.

2. I_Pkp_PcntDiff

Pick-up setting of percentage differential protection;

Setting step: 0.01A

Setting principle: it should be greater than maximum unbalanced current. When percentage
differential protection is disabled, it is still taken as auxiliary criterion for releasing or blocking end
fault protection, which can prevent undesired trip from end fault protection resulting from failure in
auxiliary contact of line disconnector.

3. Slope_PcntDiff

Slope of percentage differential protection;

Setting step: 0.01

Setting principle: It should be calculated based on characteristic of CT and ratio tolerance .

4. I_EFP1

Current setting for stage 1 of end fault protection

Setting step: 0.01A

5. t_EFP1

Time delay for stage 1 of end fault protection

Setting step: 0.01S

6. I_EFP2

Current setting for stage 2 of end fault protection

Setting step: 0.01A

7. t_EFP2

Time delay for stage 1 of end fault protection

Setting step: 0.01S

8. I_OC

Current setting for stage 2 of end fault protection

42 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 7 Settings

Setting step: 0.01A

9. t_OC

Time delay for overcurrent protection

Setting step: 0.01S

10. Line_ID

Number of the line;

The actual identification number of the transmission line in site, used for report.

7.3 Logic Settings


Many logic settings are used for configuration of the protective device. “1” means “enabled”, “valid”
or “yes” while “0” means “disabled”, “invalid” or “no”.

Table 7.3-1 Logic settings

No. Logic Setting Remark


1 En_PcntDiff Enable percentage differential protection
2 En_EFP1 Enable stage 1 of end fault protection
3 En_EFP2 Enable stage 2 of end fault protection
4 En_OC Enable overcurrent protection

² Logic settings description

1. En_PcntDiff

Percentage differential protection;

“1”: enable

“0”: disable

2. En_EFP1

Stage 1 of end fault protection;

“1”: enable

“0”: disable

3. En_EFP2

Stage 2 of end fault protection;

“1”: enable

“0”: disable

4. En_OC

Overcurrent protection;

“1”: enable

NANJING NARI-RELAYS ELECTRIC CO., LTD 43


Chapter 7 Settings

“0”: disable

7.4 Virtual Binary Input


Virtual binary input is a kind of special logic setting to enable protection functions. These virtual
binary inputs can be configured through local HMI or remote PC, no matter logic setting
[En_Remote_Cfg] is 1 or not.

Table 7.4-1 Virtual binary input

No. Virtual binary Input Remark


1 VEBI_PcntDiff Enable percentage differential protection
2 VEBI_EFP Enable end fault protection
3 VEBI_OC Enable overcurrent protection

Logic relation between above virtual binary input 1~3 and corresponding real binary input is AND.
If it is needed to configure the equipment by these virtual binary input, corresponding binary
input shall be energized. On the other hand, if it is needed to configure the equipment by real
binary input only, these eight virtual binary inputs shall be set as “1”.

These virtual binary inputs provide a convenient way for the operator to put the function in/out
remotely away from an unattended substation.

For attended substation, the operator on duty can do it by conntecting/unconntecting link on


protection panel to energize/de-energize corresponding enabling binary inputs.

7.5 IP ADDRESS
The setting is used to set the communication rate of COM module, please see Table 7-5 for
details.

Table 7.5-1 IP address

Equipment parameter Ethernet parameter


Type
Baud rate of Port 1 Baud rate of Port 2 IP Addr1 IP Addr2 IP Addr3 IP Addr4
5A RS-485-1 RS-485-2 Invalid Invalid Invalid Invalid
5B Optic fibre-1 Optic fibre-1 Invalid Invalid Invalid Invalid
5C RS-485 Ethernet-1 Ethernet-2 Invalid Invalid
5D RS-485 Ethernet-1 Ethernet-2 Invalid Invalid
5E RS-485 Ethernet-1 Ethernet-2 Ethernet-3 Ethernet-4
Don’t modify
RS-485-1
5F RS-485-4 RS-485-2 Invalid Invalid Invalid
RS-485-3

For type 5F COM module, whose first three RS-485 ports use the first three groups number of IP
Addr 1 as corresponding baud rate. The corresponding relation between them is:

001=4.8kbit/s,

002=9.6kbit/s,

44 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 7 Settings

003=19.2kbit/s

004=38.4kbit/s,

005=57.6kbit/s

others=9.6kbit/s.

For example, IP_Addr 1 is set to “001.002.003.xxx”, which means the baud rate of port 1 is
4.8kbit/s, the baud rate of port 2 is 9.6kbit/s, the baud rate of port 3 is 19.2kbit/s. The baud rate of
port 4 is set in equipment parameter by setting [COM1_Baud].

Note!

The baud rate of serial port is recommended to set to 4.8kbit/s or 9.6kbit/s. If no Ethernet
port is provided, these setting need not be set.

NANJING NARI-RELAYS ELECTRIC CO., LTD 45


Chapter 7 Settings

46 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 8 Human Machine Interface Operation

Chapter 8 Human Machine Interface Operation


The user can access the relay from the front panel of the device. Local communication with the
relay is also possible using a computer (PC) with the RCSPC software via an RS232 port on the
front panel. Furthermore, remote communication is also possible using a PC with the RCS-9700
Substation Automation System via an RS485 port.

This chapter describes human machine interface (HMI), HMI menu tree and LCD display. At the
same time how to input settings through keypad is described in details.

8.1 Human Machine Interface Overview


8.1.1 Design
The human-machine interface consists of a human-machine interface (HMI) module which allows
a communication as simple as possible for the user. The HMI module helps to draw your attention
to something that has occurred which may activate a LED or a report displayed on the LCD.
Operator can locate the data of interest by navigate keypad.

The HMI module includes:

n The human-machine interface (HMI) LCD display

A 128×64 dot matrix backlight LCD display visible in dim lighting conditions, which is used for
programming, monitoring, fault diagnostics and setting, etc. when there is a trip or alarm condition,
diagnostic messages are displayed.

n The LED

n Numeric keypad and command keys allow for full access to the relay

1 2 3

HEALTHY

LINE OUT
RCS-924
STUB DIFFERENTIAL RELAY
TRIP

TRFR TRIP

TARGET RESET

5 4

Figure 8.1-1 The front panel

NANJING NARI-RELAYS ELECTRIC CO., LTD 47


Chapter 8 Human Machine Interface Operation

No. Item
1 LCD display
2 Status indication LEDs
3 ENT, ESC, GRP and Navigation buttons
4 DB9 port and DB15 port
5 Device type, name and Manufacturer

8.1.2 Keypad operation

P
GR
ESC

Figure 8.1-2 Keypad buttons

No. Item Function


1 “▲” and “▼” move cursor left-fight among selectable target
2 “◄” and “►” move cursor up-down among selectable target
3 “+” and “-” add or subtract in the digit
4 ENT provide Enter/Execute function
5 GRP setting Group selection
5 ESC exit the present menu or return to the upper menu

Note!

Any setting change operation should complete with simply pressing “+”, “◄”, “▲”,and “-” in
sequence, as a password. Without the operation, modifying settings is invalid.

Report delete operation should executed by pressing “+”, “-”, “+”, “-”, “ENT” in sequence
after exiting the main menu.

48 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 8 Human Machine Interface Operation

8.1.3 LED indications

Figure 8.1-3 LED indications

1. The “HEALTHY” LED indicates the normal running state of the equipment. It may be turned
off when the equipment is blocked because of some abnormalities.

2. The “LINE OUT” LED will be turned on as long as line is out of service, which means binary
input [BI_DS_Line] is energized. When line is in service, it will go out.

3. The “TRIP” LED is turned on once any protection element operates and remains lit even after
the trip command is over. The purpose is to inform the operator continuously. It can be turned
off by pressing “TARGET RESET”.

4. The “TRFR TRIP” LED is lit once 3-terminal differential protection or end fault protection
operates to initiate transfer trip and remains lit even after the tripping command is over. It can
be turned off by pressing “TARGET RESET”.

Note!

The LED [HEALTHY] can only be lit by supplying DC to equipment without alarms blocking
equipment.

The LEDs [TRIP] and [TRFR TRIP] will be lit once the corresponding relays operate and
remain lit even after the trip commands go off. The LEDs can be turned off by pressing
TAEGET RESET button on faceplate, or by pressing the RESET button on the protection
panel to energized binary input [BI_RstTarg].

The LEDs [LINE OUT] is lit as long as binary input [BI_DS_Line] is energized. When the
binary input is de-energized, it can be turned off automatically at once.

NANJING NARI-RELAYS ELECTRIC CO., LTD 49


Chapter 8 Human Machine Interface Operation

8.1.4 Communication port

Figure 8.1-4 Communication ports

No. Item
1 DB9 RS232 port for communication with a PC for local communication.
2 DB 15 port for analog test signal injection from HELP-90A tester.

8.2 Understand The HMI Menu Tree


8.2.1 Overview
Please see the total command menu in following diagram which will be introduced in details.

In order to enter the main menu, please press “▲” arrow button under the default display condition.
If the current display is the latest report display, please press “TARGET RESET” button to return to
the default display condition, and then press “▲” arrow button to enter the main menu.

Please use the “▲” and ”▼“ button to scroll between the submenus, press “ENT” to enter the item
chosen or press “ESC” to directly return to the upper level.

50 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 8 Human Machine Interface Operation

Figure 8.2-1 Menu tree for RCS-924

8.2.2 VALUES
This menu displays the sampling value of current and voltage, and status binary input value which
fully reflect the operation status of the equipment. Under normal conditions these displayed values
should be consistent with the real values injected.

This menu comprises the following submenus:

n DSP METERING

This submenu displays the values of current and voltage sampled and calculated by the DSP chip.
These values includes:

n Three phase current of CT1

NANJING NARI-RELAYS ELECTRIC CO., LTD 51


Chapter 8 Human Machine Interface Operation

Ia1, Ib1, Ic1,

n Three phase current of CT2

Ia2, Ib2, Ic2

n Three phase current of CT3

Ia3, Ib3, Ic3

n Three phase differential current

Id_a, Id_b and Id_c

n CPU METERING

This submenu displays the values of current and/or voltage sampled and calculated by the CPU
chip. These values includes:

n Three phase current of CT1

Ia1, Ib1, Ic1,

n Three phase current of CT2

Ia2, Ib2, Ic2

n Three phase current of CT3

Ia3, Ib3, Ic3

n Three phase differential current

Id_a, Id_b and Id_c

n PHASE ANGLE

This submenu displays the phase angles of current and voltage:

n The phase angles between two phase of CT1

(Ia1-Ib1), (Ib1-Ic1), (Ic1-Ia1)

n The phase angles between two phase of CT2

(Ia2-Ib2), (Ib2-Ic2), (Ic2-Ia2)

n The phase angles between two phase of CT3

(Ia3-Ib3),(Ib3-Ic3), (Ic3-Ia3)

n The phase angles between CT1 and CT2

(Ia1-Ia2), (Ib1-Ib2), (Ic1-Ic2)

n The phase angles between CT1 and CT3

(Ia1-Ia3), (Ib1-Ib3), (Ic1-Ic3)

52 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 8 Human Machine Interface Operation

n The phase angles between CT2 and CT3

(Ia2-Ia3), (Ib2-Ib3), (Ic2-Ic3)

n BI STATE

This submenu displays the status of binary inputs. If a certain binary input appears to be “1”, it
means that an external binary input signal is energized or a corresponding function/element of the
equipment is enabled. On the other hand if a certain binary input appears to be “0”, it means that
the external binary input signal is de-energized or the corresponding function/element of the
equipment is disabled. These binary inputs are listed in the following table.

Table 8.2-1 BI STATE

No. Item Description


1 EBI_PcntDiff enable current percent differential protection
2 EBI_EFP enable end fault protection
3 EBI_OC enable overcurrent protection
4 BI_DS_Line auxiliary contact of disconnect switch of line
5 VEBI_PcntDiff enable current percent differential protection (virtual)
6 VEBI_EFP enable end fault protection (virtual)
7 VEBI_OC enable overcurrent protection (virtual)
8 BI_Pulse_GPS receiving pulse signal for time synchronism from GPS
9 BI_Print trigger printing report
10 BI_BlkComm interrupt communication between equipment with the SCADA system
11 BI_RstTarg input for reset of latching signal relay and LCD displaying

8.2.3 REPORT
This menu displays the information recorded by the RCS-924 for the tripping reports, alarm
message reports and status change of binary input reports etc.. All the reports are stored in
non-volatile memory.

No. Item Description


1 TRP REPORT operation report such as tripping or reclosing
2 ALM REPORT self supervision and abnormal report
3 BI CHG REPORT status change of binary input report
4 MISC REPORT other report

Please use “▲” and ”▼“ to choose the report under concern, and press “ENT” to display the
chosen report.

In the report display submenu, the latest report shall be displayed first. Press “-” button to display
the previous report, and press “+” to display the next report.

In case that a report is too long to be fully displayed on the LCD, you should press “▲” or “▼” to
display the other parts of the report.

In order to return to the upper submenu, simply press “ESC” button.

NANJING NARI-RELAYS ELECTRIC CO., LTD 53


Chapter 8 Human Machine Interface Operation

8.2.4 PRINT
The settings list, wave recorder, tripping report, operation report, abnormality report and status
change of binary input can be printed by this submenu.

No. Item Description


1 SETTINGS equipment setup, protection setting and virtual binary input
2 TRP REPORT operation report such as tripping or reclosing
3 ALM REPORT self supervision and abnormal information
4 BI CHG REPORT status change of binary input
5 PRESENT VALUE the voltage and current value sampled
6 VERSION the information of software version
7 MISC REPORT other report

Please use “▲” and “▼” to choose the item under concern, and press “ENT” to execute printing.

8.2.5 SETTINGS
Use this menu to select and set the different parameters for protection and control functions in the
RCS-924. There are 30 selectable and editable setting groups, each independent of the other, to
structure desired functions and applications.

This menu comprises the following submenus:

No. Item Description


1 EQUIP SETUP equipment settings
2 PROT SETTINGS protection settings
3 VEBI SETTINGS virtual binary inputs
4 IP ADDRESS Ethernet settings
5 COPY SETTINGS copy active setting group to other setting group

Please use “▲” or “▼” to choose the setting under concern, and press “◄” or “►” to move the
cursor to the digit to be changed. Press “+” or “-” button to change the data and then press “ENT”
to confirm the setting change.

If the setting change shall be terminated , simply press “ESC” to return, and the setting will remain
unchanged.

8.2.6 CLOCK
The internal clock for the RCS-924 can be viewed here. The time is displayed in the form
YYYY-MM-DD and hh:mm:ss. All values are presented in digits.

Please use “▲” , “▼”, “◄” or “►” to move the cursor to the digit to be changed. Press “+” or “-”
button to change the data and then press “ENT” to confirm the change.

If the setting change shall be terminated , simply press “ESC” to return, and the setting will remain
unchanged.

8.2.7 VERSION
This menu displays the version, verification code and creating time of the software applied in the

54 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 8 Human Machine Interface Operation

equipment.

8.3 Understand the LCD Display


8.3.1 Main display under normal operation condition
When the equipment is running normally, scrolling display of average current of three side CTs
(CT1, CT2, CT3) will be showed as following:

01-02 21:20:50: shows that the current time and date in format: MM-DD hh;mm:ss.

I1: average value of three phase current of CT1

I2: average value of three phase current of CT2

ActiveGrp 01: shows the active setting group

:shows the communication with SCADA system normal

8.3.2 Display tripping report


When the equipment tripping output operates, the LCD will display the report of the latest tripping
action.

OP000: shows the serial number of the tripping operation.

07-02-27: shows that the date of the tripping operation in format YY-MM-DD.

14:21:51:115MS: shows the absolute tripping time in format hh:mm:ss:ms.

Op_PcntDiff: shows the tripping element.

0015 MS: shows the time difference between pickup time of fault detector and pickup time of the

NANJING NARI-RELAYS ELECTRIC CO., LTD 55


Chapter 8 Human Machine Interface Operation

tripping element, operation time of output relay not included.

All operating elements are listed in the following table:

Table 8.3-1 Operating elements

No. Item Description

1 Op_PcntDiff percent differential protection

2 Op_EFP1 stage 1 of end fault protection

3 Op_EFP2 stage 2 of end fault protection

4 Op_OC overcurrent protection

8.3.3 Display abnormal report


When hardware failure is detected during self-check or a abnormality of system happens a new
report will be automatically displayed on LCD as follows.

ALM052: serial number of the report.

07-02-26: shows the happening date of abnormality in format YY-MM-DD.

12:06:03:063MS: shows the absolute pickup time of abnormality element in format hh:mm:ss:ms.

Alm_CTS: shows abnormality detective element.

All possible abnormality information include:

Table 8.3-2 Abnormality information

No. Item Description

1 Alm_Smpl_DSP DSP chip is damaged or DSP sampling is wrong

2 Alm_Smpl_CPU CPU chip sample differs too much from DSP sampling

3 Alm_TrpOut output circuit controlling chips is damaged

4 Alm_Setting invalid settings in active setting group

5 Alm_EEPROM invalid settings in any setting group

6 Alm_InvaldiGrp Invalid settings in active setting group

7 Alm_Pwr_DC loss of DC power supply

8 Alm_ROM ROM chip on CPU module is damaged

56 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 8 Human Machine Interface Operation

9 Alm_RAM RAM chip on CPU module is damaged

10 Alm_PersistFD general fault detector on CPU operates for longer than 50s

11 Alm_Pwr_Opto loss of Opto-coupler power supply

12 Alm_CTS CT failure supervision alarm

binary input [BI_DS_Line] is energized and current of the line detected


13 Alm_BI_DS_Line
by the relay simultaneously.

8.3.4 Display status change of binary input


The LCD will automatically display a status change of binary inputs.

BI 034: serial number of the report.

07-02-26: date in format of YY-MM-DD.

12:06:03:441MS: shows the absolute pickup time of status change in format of hh:mm:ss:ms.

EBI_PcntDiff 0→1: shows binary input name and status change action.

8.3.5 View the settings


Press “▲” enter the main menu at first. Press key “▼” to select the item “SETTINGS” by scrolling
the cursor downward, and then pressing key “ENT” will enter the submenu.

Press key “▼” to select the item “PROT SETTINGS” by scrolling the cursor downward. Press key
“ENT” to display the setting symbols and parameters of the submenu. Please press key “▲” or
“▼” to locate the setting. Simply press “ESC” to return without changing, and press “ENT” to input
password to confirm the change.

NANJING NARI-RELAYS ELECTRIC CO., LTD 57


Chapter 8 Human Machine Interface Operation

8.3.6 View Records


The RCS-924 provides the following recording functions:

n Event recording

Event recording are recorded in form of report and can be viewed through LCD or by printing.

n Disturbance recording

Disturbance recording is recorded in form of both report and waveform, so report can be display as
event report. However waveform must to be printed or displayed with proper software.

No. Item Description


1 TRP REPORT operation report such as tripping or reclosing
2 ALM REPORT self supervision and abnormal report
3 BI CHG REPORT status change of binary input report
4 MISC REPORT other report

These recording reports can also be displayed through software by the local or remote PC.

Press “▲” enter the main menu at first. Press key “▼” to select the item “REPORT” by scrolling
the cursor downward, and then pressing key “ENT” will enter the submenu. Press key “▼” to
select the target item by scrolling the cursor downward, and press key “ENT” to the next submenu.

Then press key “▼” to select “TRP REPORT”, “ALM REPORT” or “BI CHG REPORT” by scrolling
the cursor downward. Press key “ENT” to display the report selected. The latest report will be
displayed firstly. Pressing key “+”or “-” will display next or previous report. If the report cannot be
fully displayed in one screen, key “▲” or “▼” can be used to display the rest of it. Simply press key
“ESC” or “ENT” to return the upper submenu. Take the “ALM REPORT” as an example.

58 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 8 Human Machine Interface Operation

8.3.7 Printing reports and waveform


Press “▲” enter the main menu at first. Press key “▼” to select the item “PRINT” by scrolling the
cursor downward, and then pressing key “ENT” will enter the submenu. Press key “▼” to select
the target item by scrolling the cursor downward, and press key “ENT” to the next submenu.

Then press key “▼” to select “SETTINGS”, “TRP REPORT”, “ALM REPORT”, “BI CHG REPORT”,
“PRESENT VALUES”, “VERSION” or “MISC REPORT” by scrolling the cursor downward. Press
key “ENT” to print the report selected. Press key “+” or “-” to select next or previous report and
press key “ENT”. Simply press key “ESC” to return the upper submenu. Take the “ALM REPORT”
as an example.

Press “ENT” to print if there is a printer connected to the relay. If no printer is connected, the
following information will be shown “NO Printer”.

NANJING NARI-RELAYS ELECTRIC CO., LTD 59


Chapter 8 Human Machine Interface Operation

8.4 Input Operation Through Keypad


8.4.1 Change the settings
Press key “◄” or “►” to move the cursor to locate the setting you want to change by operating the
keypad to modified it. Press key “+” and “-” to change the digit. Press key “ESC” to return to the
upper level menu with the setting remain unchanged. Press key “ENT”, the LCD will prompt typing
of password.

Press keys “+”, “◄”, “▲” and “–” sequentially, then the equipment will check the password
automatically. If the password input is correct, modification of setting will be confirmed and the
interface will return to submenu.

If one or some settings input are detected to be off-limits, the cursor will locate where the first
wrong setting is and the LCD will display “xxxxx SetInvalid”. (For example, “I_Pkp_PcntDiff
SetInvalid”)

Note!

If the active group number or protection system parameter is changed, protective settings
will be invalid and have to be configured again.

8.4.2 Copy settings


The relay stores 30 setting groups from No.0 to No.29. Only present setting group is active, others
are provided for different operating conditions. The equipment settings are common for all these
setting groups, but the protection settings are independent. Generally the equipment is delivered
with default settings stored in active setting group “0”. The contents of other setting groups may be
invalid. Therefore after application-specific settings for group No.0 have been ready, it is
necessary to copy settings of group No.0 to all the other setting groups, and make some
modification afterwards when necessary, so as to avoid entering all settings one by one.

Press key “▲” to enter the main menu at first. Move cursor to the item “SETTINGS” and press key
“ENT” to enter submenu. Press key “▼” and move cursor to the item “COPY SETTINGS” item and
press “ENT” to display following interface.

60 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 8 Human Machine Interface Operation

Press key “+” and “-” to change digit where the cursor stays. Press “ENT” to confirm, then settings
group 0 will be totally copied to settings group 1.

8.4.3 Switch active setting group


Sometimes it is necessary to switch among different setting groups to fit the different operating
conditions. Press key “GRP” to display following interface.

Press key “+” and “-” to change digit where the cursor stays. Press “ENT” to confirm. If the new
active setting group is valid, LCD will display main configuration diagram. Otherwise, an alarm
[Alm_InvalidGrp] will be issued and LED “HEALTHY” will go off. Then please modify this group
settings to make them valid.

8.4.4 Delete fault records and event records


If you want to delete the content of fault records or event records, press key “▲” to enter the main
menu at first and press “+”, “-”, “+”, “-”, “ENT” in sequence after exiting the main menu, then LCD
display following interface.

NANJING NARI-RELAYS ELECTRIC CO., LTD 61


Chapter 8 Human Machine Interface Operation

Note!

You have no choice to select which kind of records or which one record to be deleted but to
delete all records.

Press key “ENT” to delete all records and LCD will display “RptClearing...” then the reports will be
deleted, or press key “ESC” to exit to main menu without deletion.

8.4.5 Adjusting the clock


If the clock of the equipment is not correct, please adjust it. Press key “▲” to enter the main menu
at first. Move cursor to the item “CLOCK” and press key “ENT” to display following interface.

2005 06 25: shows the data in format of YYYY-MM-DD.

09 08 39: shows the time in format of hh:mm:ss.

Press keys “▲”, “▼”, “◄” and “►” to select the digit to be modified. Pressing key “+” and “-” to
modify data. Pressing key “ESC” to return without modification. Pressing key “ENT” to confirm the
modification and return to main menu.

8.4.6 View software version


Press key “▲” to enter the main menu at first. Move cursor to the item “VERSION” and press key
“ENT” to display following interface and then press key “ESC” to exit.

62 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 8 Human Machine Interface Operation

RCS-924A

Project : 080110

Ver : 2.00

CRC : F4B1

RCS-924A

CRC : F4B1

2008-03-20 20 : 24

SUBQ : 00038913

RCS-924A: shows the name of the protection program.

Project: 080110: shows the project number is 070050.

Ver: 2.00: shows the program version number

CRC: F4B1: shows CRC (check code) of the program.

2008-03-20 20:24: shows the creating time of the program in format of YY-MM-DD HH:MM

SUBQ: 00038913: shows management sequential number of the program.

Note!

What above figure shows is just an example to introduce the meaning of LCD display of
software version, the actual version for user is application-specific.

8.5 Understand the Alarms


Hardware circuit and operation condition of the equipment are self-supervised continuously. If any
abnormal condition is detected, information or report will be displayed and a corresponding alarm
will be issued.

A common abnormality may block a certain number of protections functions while the other
functions can still work. However, if serious hardware failure or abnormality were detected, all
protection functions will be blocked and the LED “HEALTHY” will turn off.

When hardware failure is detected, all protection functions will be blocked and “equipment
failure” alarm signal will be given by contacts output BSJ. The equipment then cannot work
normally and maintenance is required to eliminate the failure.

NANJING NARI-RELAYS ELECTRIC CO., LTD 63


Chapter 8 Human Machine Interface Operation

Note!

If the equipment is blocked or alarm signal is issued during operation, do please find out its
reason with the help of submenu “ALM REPORT”. If the reason can not be found on site,
please inform the factory NARI-RELAYS. Please do not simply press key “TARGET
RESET” button on faceplate of the equipment, press “RESET” button on the protection
panel to energize the binary input [BI_RstTarg] or reboot the equipment.

64 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 9 Communications

Chapter 9 Communications
9.1 Communication with Substation Automation System
The remote communication can be used for different purposes to enable better access to the
information stored in the relay. Normally, Serial port access and Ethernet are used in the case.
Three communication media are supported by the equipment.

n RS-485 serial port

This port supports full local or remote protection and control access by substation automation
system or other proper software. The protocol IEC60870-5-103 is used for this port. please make
sure that [Protocol] is set as “0” to select the correct protocol.

Screened twisted pair cable should be used for the connection. Of the three connections, two are
for the signal connections, and the other for the earth shield of the cable. Make sure that the
correct polarity terminal is connected. If the master fails to communicated with the relay, and the
communication parameters match, then it is possible that the two-wire connection is reversed.
Both ends of the cable should be terminated with a 120 ohms 1/2 watt resistor. The screen must
be continuous and connected to ground at one end, normally at the master connection point, and
connected to ground through a 0.1uF/1kV capacitor at the other end.
communication controller

Figure 9.1-1 Diagram of connection for RS-485 serial port

n Optical port

An optional fiber optic is available in this product. This coverts the EIA(RS)485 protocol into a fiber
optic output.

9.2 Messages Description For IEC60870-5-103 Protocol


n Standard:

IEC 60870-5-103:1997 Telecontrol equipment and systems - Part 5-103: Transmission protocols -
Companion standard for the informative interface of protection equipment

n Physical Layer Setup:

NANJING NARI-RELAYS ELECTRIC CO., LTD 65


Chapter 9 Communications

RS485, 1 start bit,8 data bits, even parity,1 stop bit

n Baud Rate:

configurable.

The following IEC 60870-5-103 facilities are supported by this relay:

1) Initialization (Reset)

2) Time synchronization

3) Event Record Extraction

4) General Interrogation

5) General Commands

6) Cyclic Measurements are not supported

9.2.1 Generic Service


Settings are transferred via Generic Service.

Table 9.2-1 Generic service

Group num Group type


0 Device information
1 Device settings
2 Settings group
3 Protect setting
6 VEBI Setting
9 Protection measure
11 Net settings

Note!

If the item [En_Remote_Cfg] in Equipment Settings is set as 0, to modify protection


settings remotely will not be allowed. Moreover, equipment setup are not allowed to be
modified remotely whether the item [En_Remote_Cfg] is true (=1) or not.

9.2.2 Function and Information


Operation elements are sent by ASDU2, and binary input and self supervision status are sent by
ASUD1.

Table 9.2-2 Function and information

FUN INF CONTENT TYPE


184 62 Op_PcntDiff Operation element
184 129 Op_EFP1 Operation element
184 130 Op_EFP2 Operation element

66 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 9 Communications

184 63 Op_OC Operation element


184 27 EBI_PcntDiff Binary input
184 2 EBI _EFP Binary input
184 3 EBI _OC Binary input
184 201 BI_DS_Line Binary input
184 152 VEBI_PcntDiff Binary input
184 161 VEBI_EFP Binary input
184 184 VEBI_OC Binary input
184 194 Alm_RAM Alarm element
184 195 Alm_ROM Alarm element
184 196 Alm_EEPROM Alarm element
184 246 Alm_InvalidGrp Alarm element
184 197 Alm_Smpl_CPU Alarm element
184 189 Alm_PersistI0 Alarm element
184 214 Alm_PersistFD Alarm element
184 197 Alm_Smpl_DSP Alarm element
184 212 Alm_TrpOut Alarm element
184 222 Alm_Setting Alarm element
184 245 Alm_Pwr_DC Alarm element
184 202 Alm_Pwr_Opto Alarm element
184 206 Alm_CTS Alarm element
184 251 Alm_BI_DS_Line Alarm element
184 249 BI_BlkComm Binary input

9.2.3 Disturbance ACC (Actual Channel)


Disturbance records stored by the relay can be extracted using mechanism defined in the IEC
60870-5-103 standard

Table 9.2-3 Disturbance ACC

ACC Content
1 Ia1
2 Ib1
3 Ic1
4 Ia2
5 Ib2
6 Ic2
7 Ia3
8 Ib3
9 Ic3
10 Id_a
11 Id_b
12 Id_c

NANJING NARI-RELAYS ELECTRIC CO., LTD 67


Chapter 9 Communications

9.2.4 Metering
The data are sent in primary values. The settings [U1n], [U2n], [I1n], [I2n] shall be configured
correctly. The meterings are sent via Generic Service.

9.2.5 Blocking of monitoring direction


FUN = 184; INF = 249
When binary input [BI_BlkComm] is energized, all information except this ASDU will not be sent
to the host.

9.2.6 Control Command


ASDU 10
Reset Target: INF = 19

9.3 Messages Description For IEC61850 Protocol


9.3.1 Overview
The IEC 61850 standard is the result of years of work by electric utilities and vendors of electronic
equipment to produce standardized communications systems. IEC 61850 is a series of standards
describing client/server and peer-to-peer communications, substation design and configuration,
testing, environmental and project standards. The complete set includes:

n IEC 61850-1: Introduction and overview

n IEC 61850-2: Glossary

n IEC 61850-3: General requirements

n IEC 61850-4: System and project management

n IEC 61850-5: Communications and requirements for functions and device models

n IEC 61850-6: Configuration description language for communication in electrical


substations related to IEDs

n IEC 61850-7-1: Basic communication structure for substation and feeder equipment -
Principles and models

n IEC 61850-7-2: Basic communication structure for substation and feeder equipment -
Abstract communication service interface (ACSI)

n IEC 61850-7-3: Basic communication structure for substation and feeder equipment –
Common data classes

n IEC 61850-7-4: Basic communication structure for substation and feeder equipment –
Compatible logical node classes and data classes

n IEC 61850-8-1: Specific Communication Service Mapping (SCSM) – Mappings to MMS


(ISO 9506-1 and ISO 9506-2) and to ISO/IEC 8802-3

n IEC 61850-9-1: Specific Communication Service Mapping (SCSM) – Sampled values


over serial unidirectional multidrop point to point link

68 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 9 Communications

n IEC 61850-9-2: Specific Communication Service Mapping (SCSM) – Sampled values


over ISO/IEC 8802-3

n IEC 61850-10: Conformance testing

These documents can be obtained from the IEC (http://www.iec.ch). It is strongly recommended
that all those involved with any IEC 61850 implementation obtain this document set.

9.3.2 Communication profiles


The RCS-900 series relay supports IEC 61850 server services over TCP/IP communication
protocol stacks. The TCP/IP profile requires the RCS-900 series to have an IP address to
establish communications. These addresses are located in the submenu “SETTINGS-IP
ADDRESS”. Please refer to 7.5 for further details.

1. MMS protocol

IEC 61850 specifies the use of the Manufacturing Message Specification (MMS) at the upper
(application) layer for transfer of real-time data. This protocol has been in existence for a number
of years and provides a set of services suitable for the transfer of data within a substation LAN
environment. Actual MMS protocol services are mapped to IEC 61850 abstract services in
IEC61850-8-1.

2. Client/server

This is a connection-oriented type of communication. The connection is initiated by the client, and
communication activity is controlled by the client. IEC61850 clients are often substation computers
running HMI programs or SOE logging software. Servers are usually substation equipment such
as protection relays, meters, RTUs, transformer, tap changers, or bay controllers.

3. Peer-to-peer

This is a non-connection-oriented, high speed type of communication usually between substation


equipment, such as protection relays. GOOSE is the method of peer-to-peer communication.

4. Substation configuration language (SCL)

A substation configuration language is a number of files used to describe the configuration of


substation equipment. Each configured device has an IEC Capability Description (ICD) file and a
Configured IED Description (CID) file. The substation single line information is stored in a System
Specification Description (SSD) file. The entire substation configuration is stored in a Substation
Configuration Description (SCD) file. The SCD file is the combination of the individual ICD files
and the SSD file.

9.3.3 Server data organization


IEC61850 defines an object-oriented approach to data and services. An IEC61850 physical device
can contain one or more logical device(s) (for proxy). Each logical device can contain many logical
nodes. Each logical node can contain many data objects. Each data object is composed of data
attributes and data attribute components. Services are available at each level for performing
various functions, such as reading, writing, control commands, and reporting.

NANJING NARI-RELAYS ELECTRIC CO., LTD 69


Chapter 9 Communications

Each IED represents one IEC61850 physical device. The physical device contains one logical
device, and the logical device contains many logical nodes. The logical node LPHD contains
information about the IED physical device. The logical node LLN0 contains information about the
IED logical device.

9.3.3.1 Digital status values

The GGIO logical node is available in the RCS-900 series relays to provide access to digital status
points (including general I/O inputs and warnings) and associated timestamps and quality flags.
The data content must be configured before the data can be used. GGIO provides digital status
points for access by clients. It is intended that clients use GGIO in order to access digital status
values from the RCS-900 series relays. Clients can utilize the IEC61850 buffered reporting
features available from GGIO in order to build sequence of events (SOE) logs and HMI display
screens. Buffered reporting should generally be used for SOE logs since the buffering capability
reduces the chances of missing data state changes. All needed status data objects are transmitted
to HMI clients via buffered reporting, and the corresponding buffered reporting control block
(BRCB) is defined in LLN0.

9.3.3.2 Analog values

Most of analog measured values are available through the MMXU logical nodes, and metering
values in MMTR, the else in MMXN, MSQI and so on. Each MMXU logical node provides data
from a IED current/voltage “source”. There is one MMXU available for each configurable source.
MMXU1 provides data from CT/VT source 1(usually for protection purpose), and MMXU2 provides
data from CT/VT source 2 (usually for monitor and display purpose). All these analog data objects
are transmitted to HMI clients via unbuffered reporting periodically, and the corresponding
unbuffered reporting control block (URCB) is defined in LLN0. MMXUx logical nodes provide the
following data for each source:

n MMXU.ST.Hz: frequency

n MMXU.ST.PPV.phsAB: phase AB voltage magnitude and angle

n MMXU.ST.PPV.phsBC: phase BC voltage magnitude and angle

n MMXU.ST.PPV.phsCA: Phase CA voltage magnitude and angle

n MMXU.ST.PhV.phsA: phase AG voltage magnitude and angle

n MMXU.ST.PhV.phsB: phase BG voltage magnitude and angle

n MMXU.ST.PhV.phsC: phase CG voltage magnitude and angle

n MMXU.ST.A.phsA: phase A current magnitude and angle

n MMXU.ST.A.phsB: phase B current magnitude and angle

n MMXU.ST.A.phsC: phase C current magnitude and angle

9.3.3.3 Protection logical nodes

The following list describes the protection elements for all RCS-900 series relays. The specified

70 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 9 Communications

relay will contain a subset of protection elements from this list.

n PDIF: current differential and transfer trip

n PDIS: phase-to-phase distance, phase-to-ground distance and SOTF distance

n PTUC: undercurrent

n PTOC: phase overcurrent, zero sequence overcurrent and overcurrent when CTS

n PTUV: undervoltage

n PTUF: underfrequency

n PTOV: overvoltage and auxiliary overvoltage

n RREC: automatic reclosing

The protection elements listed above contain start (pickup) and operate flags, instead of any
element has its own start (pickup) flag separately, all the elements share a common start (pickup)
flags “PTRC.ST.Str.general”. The operate flag for PTOC1 is “PTOC1.ST.Op.general”. For the
RCS-900 series relay protection elements, these flags take their values from related module for
the corresponding element. Similar to digital status values, the protection trip information is
reported via BRCB, and it also locates in LLN0.

9.3.3.4 LLN0 and other logical nodes

Logical node LLN0 is essential for an IEC61850 based IED. This LN shall be used to address
common issues for Logical Devices. Most of the public services, the common settings, control
values and some device oriented data objects are available here. The public services may be
BRCB, URCB and GSE control blocks and similar global defines for the whole device; the
common settings include all the setting items of communication settings. System settings and
some of the protection setting items, which can be configured to two or more protection elements
(logical nodes). In LLN0, the item Loc is a device control object, this Do item indicates the local
operation for complete logical device, when it is true, all the remote control commands to the IED
will be blocked and those commands make effective until the item Loc is changed to false. In
RCS-900 series relays, besides the logical nodes we describe above, there are some other logical
nodes below in the IEDs:

n LPHD: Physical device information, the logical node to model common issues for physical
device.

n PTRC: Protection trip conditioning, it shall be used to connect the “operate” outputs of one or
more protection functions to a common “trip” to be transmitted to XCBR. In addition or
alternatively, any combination of “operate” outputs of protection functions may be combined to
a new “operate” of PTRC.

n RDRE: Disturbance recorder function. It triggers the fault wave recorder and its output refers
to the “IEEE Standard Format for Transient Data Exchange (COMTRADE) for Power System”
(IEC 60255-24). All enabled channels are included in the recording, independently of the
trigger mode.

NANJING NARI-RELAYS ELECTRIC CO., LTD 71


Chapter 9 Communications

9.3.4 Server features and configuration


9.3.4.1 Buffered/unbuffered reporting

IEC61850 buffered and unbuffered reporting control blocks locate in LLN0, they can be configured
to transmit information of protection trip information (in the Protection logical nodes), binary status
values (in GGIO) and analog measured/calculated values (in MMXU, MMTR and MSQI). The
reporting control blocks can be configured in CID files, and then be sent to the IED via an
IEC61850 client. The following items can be configured.

n TrgOps: Trigger options. The following bits are supported by the RCS-900 series
relays:

- Bit 1: Data-change

- Bit 4: Integrity

- Bit 5: General interrogation

n OptFlds: Option Fields. The following bits are supported by the RCS-900 series relays:

- Bit 1: Sequence-number

- Bit 2: Report-time-stamp

- Bit 3: Reason-for-inclusion

- Bit 4: Data-set-name

- Bit 5: Data-reference

- Bit 6: Buffer-overflow (for buffered reports only)

- Bit 7: EntryID (for buffered reports only)

- Bit 8: Conf-revision

- Bit 9: Segmentation

n IntgPd: Integrity period.

n BufTm: Buffer time.

9.3.4.2 File transfer

MMS file services are supported to allow transfer of oscillography, event record or other files from
a RCS-900 series relay.

9.3.4.3 Timestamps

The timestamp values associated with all IEC61850 data items represent the time of the last
change of either the value or quality flags of the data item.

9.3.4.4 Logical node name prefixes

IEC61850 specifies that each logical node can have a name with a total length of 11 characters.

72 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 9 Communications

The name is composed of:

n A five or six-character name prefix.

n A four-character standard name (for example, MMXU, GGIO, PIOC, etc.).

n A one or two-character instantiation index.

Complete names are of the form xxxxxxPTOC1, where the xxxxxx character string is configurable.
Details regarding the logical node naming rules are given in IEC61850 parts 6 and 7-2. It is
recommended that a consistent naming convention be used for an entire substation project.

9.3.4.5 GOOSE services

IEC61850 specifies the type of peer-to-peer data transfer services: Generic Object Oriented
Substation Events (GOOSE). IEC61850 GOOSE services provide virtual LAN (VLAN) support,
Ethernet priority tagging, and Ether-type Application ID configuration. The support for VLANs and
priority tagging allows for the optimization of Ethernet network traffic. GOOSE messages can be
given a higher priority than standard Ethernet traffic, and they can be separated onto specific
VLANs. Devices that transmit GOOSE messages also Devices that transmit GOOSE messages
also function as servers. Each GOOSE publisher contains a “GOOSE control block” to configure
and control the transmission.

The transmission is also controlled via device setting “GOOSE Group ID” in the setting submenu
“EQUIP SETUP”. The “GOOSE Group ID” setting item defines a definite IED group in which the
IED can communicate with each other via GOOSE protocol, and if GOOSE Group ID is configured
to “0”, GOOSE service is blocked in this IED. IEC61850 recommends a default priority value of 4
for GOOSE. Ethernet traffic that does not contain a priority tag has a default priority of 1. More
details are specified in IEC61850 part 8-1. IEC61850 recommends that the Ether-type Application
ID number be configured according to the GOOSE source.

The RCS-924 series relays support IEC61850 Generic Object Oriented Substation Event
(GOOSE) communication. All GOOSE messages contain IEC61850 data collected into a dataset.
It is this dataset that is transferred using GOOSE message services. The GOOSE related dataset
is configured in the CID file and it is recommended that the fixed GOOSE be used for
implementations that require GOOSE data transfer between RCS-900 series relays.

IEC61850 GOOSE messaging contains a number of configurable parameters, all of which must be
correct to achieve the successful transfer of data. It is critical that the configured datasets at the
transmission and reception devices are an exact match in terms of data structure, and that the
GOOSE addresses and name strings match exactly.

The general steps required for transmission configuration are:

1. Configure the transmission dataset.

2. Configure the GOOSE service settings.

3. Configure the data.

The general steps required for reception configuration are:

NANJING NARI-RELAYS ELECTRIC CO., LTD 73


Chapter 9 Communications

1. Configure the reception dataset.

2. Configure the GOOSE service settings.

3. Configure the data.

9.3.5 ACSI conformance


9.3.5.1 ACSI basic conformance statement

Services Client Server RCS-900 Series


Client-Server Roles
B11 Server side (of Two-party Application-Association) - C1 Y
B12 Client side (of Two-party Application-Association) C1 - N
SCSMS Supported
B21 SCSM: IEC 61850-8-1 used N N Y
B22 SCSM: IEC 61850-9-1 used N N N
B23 SCSM: IEC 61850-9-2 used N N N
B24 SCSM: other N N N
Generic Substation Event Model (GSE)
B31 Publisher side - O Y
B32 Subscriber side O - Y
Transmission Of Sampled Value Model (SVC)
B41 Publisher side - O N
B42 Subscriber side O - N

Where:

C1: Shall be "M" if support for LOGICAL-DEVICE model has been declared

O: Optional

M: Mandatory

Y: Supported by RCS-900 series relays

N: Currently not supported by RCS-900 series relays

9.3.5.2 ACSI models conformance statement

Services Client Server RCS-900 Series


M1 Logical device C2 C2 Y
M2 Logical node C3 C3 Y
M3 Data C4 C4 Y
M4 Data set C5 C5 Y
M5 Substitution O O Y
M6 Setting group control O O Y
Reporting
M7 Buffered report control O O Y

74 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 9 Communications

M7-1 sequence-number Y Y Y
M7-2 report-time-stamp Y Y Y
M7-3 reason-for-inclusion Y Y Y
M7-4 data-set-name Y Y Y
M7-5 data-reference Y Y Y
M7-6 buffer-overflow Y Y Y
M7-7 entryID Y Y Y
M7-8 BufTm N N N
M7-9 IntgPd Y Y Y
M7-10 GI Y Y Y
M8 Unbuffered report control M M Y
M8-1 sequence-number Y Y Y
M8-2 report-time-stamp Y Y Y
M8-3 reason-for-inclusion Y Y Y
M8-4 data-set-name Y Y Y
M8-5 data-reference Y Y Y
M8-6 BufTm N N N
M8-7 IntgPd N Y Y
Logging
M9 Log control O O N
M9-1 IntgPd N N N
M10 Log O O N
GSE
M12 GOOSE O O Y
M13 GSSE O O N
M14 Multicast SVC O O N
M15 Unicast SVC O O N
M16 Time M M Y
M17 File transfer O O Y

Where:

C2: Shall be "M" if support for LOGICAL-NODE model has been declared

C3: Shall be "M" if support for DATA model has been declared

C4: Shall be "M" if support for DATA-SET, Substitution, Report, Log Control, or Time
models has been declared

C5: Shall be "M" if support for Report, GSE, or SMV models has been declared

M: Mandatory

Y: Supported by RCS-900 series relays

N: Currently not supported by RCS-900 series relays

NANJING NARI-RELAYS ELECTRIC CO., LTD 75


Chapter 9 Communications

9.3.5.3 ACSI Services conformance statement

Service Server/Publisher RCS-900 Series


Server
S1 ServerDirectory M Y
Application association
S2 Associate M Y
S3 Abort M Y
S4 Release M Y
Logical device
S5 LogicalDeviceDirectory M Y
Logical node
S6 LogicalNodeDirectory M Y
S7 GetAllDataValues M Y
Data
S8 GetDataValues M Y
S9 SetDataValues M Y
S10 GetDataDirectory M Y
S11 GetDataDefinition M Y
Data set
S12 GetDataSetValues M Y
S13 SetDataSetValues O
S14 CreateDataSet O
S15 DeleteDataSet O
S16 GetDataSetDirectory M Y
Substitution
S17 SetDataValues M Y
Setting group control
S18 SelectActiveSG M/O Y
S19 SelectEditSG M/O Y
S20 SetSGValuess M/O Y
S21 ConfirmEditSGValues M/O Y
S22 GetSGValues M/O Y
S23 GetSGCBValues M/O Y
Reporting
Buffered report control block
S24 Report M Y
S24-1 data-change M Y
S24-2 qchg-change M Y
S24-3 data-update M Y
S25 GetBRCBValues M Y
S26 SetBRCBValues M Y
Unbuffered report control block

76 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 9 Communications

S27 Report M Y
S27-1 data-change M Y
S27-2 qchg-change M Y
S27-3 data-update M Y
S28 GetURCBValues M Y
S29 SetURCBValues M Y
Logging
Log control block
S30 GetLCBValues O
S31 SetLCBValues O
Log
S32 QueryLogByTime O
S33 QueryLogAfter O
S34 GetLogStatusValues O
Generic substation event model (GSE)
GOOSE control block
S35 SendGOOSEMessage M Y
S36 GetGoReference O
S37 GetGOOSEElementNumber O Y
S38 GetGoCBValues M Y
S39 SetGoCBValuess M Y
Control
S51 Select O
S52 SelectWithValue M Y
S53 Cancel M Y
S54 Operate M Y
S55 Command-Termination O Y
S56 TimeActivated-Operate O
File transfer
S57 GetFile M/O Y
S58 SetFile O Y
S59 DeleteFile O
S60 GetFileAttributeValues M/O Y
Time
SNTP M Y

9.3.6 Logical nodes


9.3.6.1 Logical nodes table

The RCS-900 series relays support IEC61850 logical nodes as indicated in the following table.
Note that the actual instantiation of each logical node is determined by the product order code.

Nodes RCS-900 Series

NANJING NARI-RELAYS ELECTRIC CO., LTD 77


Chapter 9 Communications

L: System Logical Nodes


LPHD: Physical device information YES
LLN0: Logical node zero YES
P: Logical Nodes For Protection Functions
PDIF: Differential YES
PDIR: Direction comparison -
PDIS: Distance -
PDOP: Directional overpower -
PDUP: Directional underpower -
PFRC: Rate of change of frequency -
PHAR: Harmonic restraint -
PHIZ: Ground detector -
PIOC: Instantaneous overcurrent YES
PMRI: Motor restart inhibition -
PMSS: Motor starting time supervision -
POPF: Over power factor -
PPAM: Phase angle measuring -
PSCH: Protection scheme -
PSDE: Sensitive directional earth fault -
PTEF: Transient earth fault -
PTOC: Time overcurrent YES
PTOF: Overfrequency -
PTOV: Overvoltage -
PTRC: Protection trip conditioning YES
PTTR: Thermal overload -
PTUC: Undercurrent -
PTUV: Undervoltage -
PUPF: Underpower factor -
PTUF: Underfrequency -
PVOC: Voltage controlled time overcurrent -
PVPH: Volts per Hz -
PZSU: Zero speed or underspeed -
R: Logical Nodes For Protection Related Functions
RDRE: Disturbance recorder function YES
RADR: Disturbance recorder channel analogue -
RBDR: Disturbance recorder channel binary -
RDRS: Disturbance record handling -
RBRF: Breaker failure -
RDIR: Directional element -
RFLO: Fault locator -
RPSB: Power swing detection/blocking -
RREC: Autoreclosing -

78 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 9 Communications

RSYN: Synchronism-check or synchronizing -


C: Logical Nodes For Control
CALH: Alarm handling YES
CCGR: Cooling group control -
CILO: Interlocking YES
CPOW: Point-on-wave switching -
CSWI: Switch controller YES
G: Logical Nodes For Generic References
GAPC: Generic automatic process control -
GGIO: Generic process I/O YES
GSAL: Generic security application -
I: Logical Nodes For Interfacing And Archiving
IARC: Archiving -
IHMI: Human machine interface YES
ITCI: Telecontrol interface -
ITMI: Telemonitoring interface -
A: Logical Nodes For Automatic Control
ANCR: Neutral current regulator -
ARCO: Reactive power control -
ATCC: Automatic tap changer controller -
AVCO: Voltage control -
M: Logical Nodes For Metering And Measurement
MDIF: Differential measurements -
MHAI: Harmonics or interharmonics -
MHAN: Non phase related harmonics or interharmonic -
MMTR: Metering -
MMXN: Non phase related measurement -
MMXU: Measurement YES
MSQI: Sequence and imbalance -
MSTA: Metering statistics -
S: Logical Nodes For Sensors And Monitoring
SARC: Monitoring and diagnostics for arcs -
SIMG: Insulation medium supervision (gas) -
SIML: Insulation medium supervision (liquid) -
SPDC: Monitoring and diagnostics for partial discharges -
X: Logical Nodes For Switchgear
TCTR: Current transformer -
TVTR: Voltage transformer -
Y: Logical Nodes For Power Transformers
YEFN: Earth fault neutralizer (Peterson coil) -
YLTC: Tap changer -
YPSH: Power shunt -

NANJING NARI-RELAYS ELECTRIC CO., LTD 79


Chapter 9 Communications

YPTR: Power transformer YES


Z: Logical Nodes For Further Power System Equipment
ZAXN: Auxiliary network -
ZBAT: Battery -
ZBSH: Bushing -
ZCAB: Power cable -
ZCAP: Capacitor bank -
ZCON: Converter -
ZGEN: Generator -
ZGIL: Gas insulated line -
ZLIN: Power overhead line -
ZMOT: Motor -
ZREA: Reactor -
ZRRC: Rotating reactive component -
ZSAR: Surge arrestor -
ZTCF: Thyristor controlled frequency converter -
ZTRC: Thyristor controlled reactive component -

9.4 Communication with printer


There are parameters need to be set in RCS-924 for communication with printer, [Printer_Baud],
[En_Auto_Print] and [En_Net_Print], the first one decides the communication rate and the
second one decides the printer’s activating way and sharing way, they are set as “0” normally.
Please refer to 7.1 for detail. [BI_Print] shall be energized if printing need to be triggered manually.

9.5 Communication with computer


When communicating locally with computer using the front serial port, the hardware needed is:

n a cable with two DB-9 connectors at both ends

n a personal computer

There is one parameter need to be set in RCS-924 for local communication with PC
[Debuger_Baud].

There are two parameters that can be set for remote communication. These two are the
[Comm_Addr] and [COM1_Baud]/[COM2_Baud]. These can for obvious reasons only be set on
the built-in HMI.

9.6 Communication with external clock


The clock function (Calendar clock) is used for time-tagging for the following purposes:

n Event records

n Disturbance records/Fault records

n Metering

80 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 9 Communications

n Automatic supervision

n Display of the system quantities in LCD

n Display of the fault records in LCD

n Display of the automatic monitoring results in LCD

When the relays are connected to the GPS clock, all the relay clocks are synchronized with the
external clock. There are two way to adjust the relay clock.

1) time synchronization message via RS-485 serial port

2) time synchronization pulse via binary input [BI_Pulse_GPS], pulse per second or pulse per
minute could be selected, and the setting [GPS_Pulse] shall be set correctly.

NANJING NARI-RELAYS ELECTRIC CO., LTD 81


Chapter 9 Communications

82 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 10 Installation And Commissioning

Chapter 10 Installation And Commissioning


10.1 Introduction
The chapter contains instructions on how to install, commission and maintenance the protection
equipment. It can also be used as a reference if a periodic test is performed. The chapter covers
procedures for mechanical and electrical installation, energizing and checking of external circuitry,
setting and configuration as well as verifying settings and performing a directionality test.

The chapter contains the following information:

1) The “Safety information” presents warning and note signs, which the user should draw
attention to.

2) The “Overview” gives an overview over the major task when installing and commissioning the
protection equipment.

3) The “Unpacking and checking the protection equipment” contains instructions on how to
receive the protection equipment.

4) The “Installing the protection equipment” contains instructions on how to install the
protection equipment.

5) The “Checking the external circuitry” contains instructions on how to check that the
protection equipment is properly connected to the protection system.

6) The “Energizing the protection equipment” contains instructions on how to start-up the
protection equipment.

7) The “Setting the protection equipment” contains instructions on how to download settings
and configuration to the protection equipment.

8) The “Establishing connection and verifying communication” contains instructions on how


to verify the communication.

9) The “Verifying settings by secondary injection” contains instructions on how to verify that
each included function operates correctly according to the set value.

10) The “Verifying the internal configuration” contains instructions on how verify that the
protection equipment is properly configured.

The chapter is addressing the installation, commissioning and maintenance personnel responsible
for taking the protection into normal service and out of service. The installation personnel must
have a basic knowledge in handling electronic equipment. The commissioning and maintenance
personnel must be well experienced in using protection equipment, test equipment, protection
functions and the configured functional logics in the protection.

10.2 Safety Information


This section contains safety information. Warning signs are presented which attend the user to be
careful during certain operations in order to avoid human injuries or damage to equipment.

NANJING NARI-RELAYS ELECTRIC CO., LTD 83


Chapter 10 Installation And Commissioning

1. Warning signs

Warning!

n Strictly follow the company and country safety regulations. Working in a high voltage
environment requires serious approach to avoid human injuries and damage to
equipment.

n Do not touch circuitry during operation. Potentially lethal voltages and currents are
present.

n Always avoid to touch the circuitry when the cover is removed. The product contains
electronic circuitries which can be damaged if exposed to static electricity (ESD). The
electronic circuitries also contain high voltage which is lethal to humans.

n Always use suitable isolated test pins when measuring signals in open circuitry.
Potentially lethal voltages and currents are present.

n Never connect or disconnect a wire and/or a connector to or from a protection equipment


during normal operation. Hazardous voltages and currents are present that may be lethal.
Operation may be disrupted and protection equipment and measuring circuitry may be
damaged.

n Always connect the protection equipment to protective ground, regardless of the


operating conditions. This also applies to special occasions such as bench testing,
demonstrations and off-site configuration. Operating the protection equipment without
proper grounding may damage both terminal and measuring circuitry, and may cause
injuries in case of an accident.

n Never disconnect a secondary connection of current transformer circuit without


short-circuiting the transformer’s secondary winding. Operating a current transformer
with the secondary winding open will cause a massive potential build-up that may
damage the transformer and may cause injuries to humans.

n Never unmount the front or back cover from a powered equipment or from a protection
equipment connected to powered circuitry. Potentially lethal voltages and currents are
present.

2. Caution signs

Caution!

n Always transport modules using certified conductive bags. Always handle modules using
a conductive wrist strap connected to protective ground and on a suitable antistatic
surface. Electrostatic discharge (ESD) may cause damage to the module.

n Do not connect live wires to the protection equipment. Internal circuitry may be damaged.

n Always use a conductive wrist strap connected to protective ground when replacing

84 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 10 Installation And Commissioning

modules. Electrostatic discharge (ESD) may damage the module and protection
equipment circuitry.

n Take care to avoid electrical shock if accessing wiring and connection protection
equipment when installing and commissioning.

3. Note signs

Note!

n Changing the active setting group will inevitably change the protection equipment’s
operation. Be careful and check regulations before making the change.

n The protection assembly is designed for a maximum continuous current of four times
rated value.

n Activating the other setting group without proper configuration may seriously affect the
protection equipment’s operation.

10.3 Overview
The settings for each function must be calculated before the commissioning task can start. A
configuration, made in the configuration and programming tool, must also be available if the
protection equipment does not have a factory configuration downloaded.

The protection equipment is unpacked and visually checked. It is preferably mounted in a cubicle.
The connection to the protection system has to be checked in order to verify that the installation
was successful.

The installation and commissioning task starts with configuring the digital communication modules,
if included. The protection equipment can then be configured and set, which means that settings
and a configuration has to be applied if the protection equipment does not have a factory
configuration downloaded. Then the operation of each included function according to applied
settings has to be verified by secondary injection. A complete check of the configuration can then
be made. A conformity test of the secondary system has also to be done. When the primary
system has been energized a directionality check should be made.

10.4 Unpacking And Checking The Protection Equipment


Procedure

1) Remove the transport casing.

2) Visually inspect the protection equipment.

n Carefully examine the protection panel, protection equipment inside and other parts
inside to see that no physical damage has occurred since installation.

n The rating information should be given for the protection equipment.

n The rating information of other auxiliary protections should be checked to ensure it is


correct for the particular installation.

NANJING NARI-RELAYS ELECTRIC CO., LTD 85


Chapter 10 Installation And Commissioning

Panel wiring:

Check the conducting wire used in the panel to assure that their cross section meet the
requirement. Carefully examine the wiring to see that they are no connection failure exists.

Label:

Check all the isolator links, terminal blocks, ferrules, indicators, switches and push buttons to
make sure that their labels meet the requirements of this project.

Equipment plug-in modules:

Check each plug-in module of the equipments on the panel to make sure that they are well
installed into the equipment without any screw loosened.

Earthing cable:

Check whether the earthing cable from the panel terminal block is safely screwed to the panel
steel sheet.

Switch, keypad, isolator links and push button:

Check whether all the switches, equipment keypad, isolator links and push buttons work normally
and smoothly.

3) Check that all items are included in accordance with the delivery documents.

The user is requested to check that all software functions are included according to the delivery
documents after the terminal has been energized.

4) Check for transport damages.

These product checks cover all aspects of the protection, which should be checked to ensure that
the protection not only has not been physically damaged prior to commissioning but also functions
correctly and all input quantity measurements are within the stated tolerances.

10.5 Installing The Protection Equipment


10.5.1 Overview
The mechanical and electrical environmental conditions at the installation site must be within
permissible range according to the technical data of the protection equipment. Dusty, damp places,
places liable to rapid temperature variations, powerful vibrations and shocks, surge voltages of
high amplitude and fast rise time, strong induced magnetic fields or similar extreme conditions
should be avoided. Please refer to Chapter 2 for details.

Sufficient space must be available in front of and at rear of the protection panel to allow access for
maintenance and future modifications. Flush mounted protection equipment should be mounted
so that equipment modules can be added and replaced without excessive demounting.

10.5.2 Dimensions
The equipment adopts IEC standard chassis and is rack with modular structure. It uses an integral
faceplate and plug terminal block on backboard for external connections. RCS-924 is IEC 4U high

86 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 10 Installation And Commissioning

and 19” wide. Figure 10.5-1 shows its dimensions and Figure 10.5-2 shows the panel cut-out.

GRP
ESC
101.6
177.0

Figure 10.5-1 Dimensions of RCS-924


101.6

179.0
Figure 10.5-2 panel cut-out of RCS-924

10.5.3 Making the electrical connections


Always make sure established guidelines for this type of terminal is followed during installation.
When necessary use screened twisted-pair cables to minimize susceptibility. Otherwise, use any
kind of regular nonscreened tinned RK cable or equivalent.

When using screened cabling always use 360° full screen cable bushing to ensure screen
coupling. Ensure that all signals of the single circuit are in the same single cable. Avoid mixing
current and voltage measuring signals in the same cable. Also use separate cables for control and
measuring circuits.

1) Connecting the CT circuits:

Heavy-duty terminal block, M4 threaded terminal ends for wire cross sections from 1.5 to 2.5 mm 2.

2) Connecting the auxiliary power:

NANJING NARI-RELAYS ELECTRIC CO., LTD 87


Chapter 10 Installation And Commissioning

Auxiliary power cords cross with cross sections from 1.5 to 2.5 mm 2 can be directly screw fixed on
the rear panel of DC board. Refer to 6.3.1

3) Input/output signal connectors:

Welding terminals for wire cross sections from 1.5 to 2.5 mm 2. Those devices are supplied with
sufficient M4 screws for making connections to the rear mounted terminal blocks using ring
terminals, with a recommended maximum of two ring terminals per relay terminal.

To meet the insulation requirements of the terminal block, for the sake of safety, an insulating
sleeve should be fitted over the ring terminal after crimping.

The wire used for all connections to the welding terminal blocks and heavy duty terminal blocks,
except the EIA(RS)485 port, should have a minimum voltage rating of 300Vrms.

It is recommended that the auxiliary power circuit wiring should be protected by using a 16A high
rupture capacity (HRC) fuse of type NIT or TIA. For safety reasons, current transformer circuits
must never be open.

4) Connecting to protective ground:

Connect the unit to the grounding bar of the cubicle with green/yellow conductor; cross section at
least 4.0 mm 2, connected to the protective Earthing terminal at the back of the DC board. Refer to
6.3.1. Attend that the earth wire must be as short as possible. All cautions have to be taken to
ensure the best electrical conductivity, particularly the contact quality, stainless conductor. The
impedance between the relay Earthing terminal and the Earth must be less than 20mΩ under
12Volt, 50Hz. What matters is that the device has to be only grounded at one point. Loop
grounding from unit to unit is not allowed.

5) Installing the optic fibres

Connectors are generally color coded; connect blue or dark grey cable connectors to blue or dark
grey (receive) back-side connectors. Connect black or grey cable connectors to black or grey
(transmit) back-side connectors.

Fiber optical cables are sensitive to handling. Do not bend too sharply. The minimum curvature
radius is 15 cm for plastic fibers and 25 cm for glass fibers. If cable straps are used, apply with
loose fit.

Note!

Always hold the connector, never the cable, when connecting or disconnecting optical
fibres. Do not twist, pull or bend the fibre. Invisible damage may increase fibre damping
thus making communication impossible.

6) Installing the RS-485 serial port communication cables:

When using galvanic connection between protective relay and communication equipment or
point-to-point galvanic connection between two protective relays it is essential that the cable
installation is carefully done. This is true regardless of type of module used, only the possible

88 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 10 Installation And Commissioning

length of the cable differs. The factors that must be taken into account is the susceptibility for noise
disturbance, due to that the levels of the communication signal are very low. For a best result, a
cable with twisted pairs with screen should be used.

RS485 serial communication interface, a termination 120-ohm resistor has to be connected at


each extremity of the bus. Refer to Chapter 9.

10.6 Check The External Circuitry


The user must check the installation, which includes verifying that the relay is connected to the
other parts of the protection system. This is done with the relay and all connected circuits
de-energized.

1) Checking the CT circuits

Check that the wiring is in strict accordance with the supplied wiring diagram.

Test the circuitry. The following tests are recommended:

n Polarity check

n CT circuit current measurement (primary injection test)

n Grounding check

The polarity check verifies the integrity of the circuits and the phase relationship. The check should
be performed as close as possible to the relay. The primary injection test verifies the CT ration and
the wiring all the way through from the primary system to the relay. Injection must be performed for
each phase-to-neutral circuit and each phase-to-phase pair. In each case currents in all phases
and the neutral line are measured.

2) Checking the power supply

Check that the value of the auxiliary supply voltage remains with the permissible range under all
operating conditions. Check that the polarity is correct according to the instruction manual on the
rear plate of DC board. Refer to 6.3.1.

3) Checking binary input circuits

Preferably, disconnect the binary input connector form the binary input cards. Check all connected
signals so that both input level and polarity are in accordance with the relay’s specifications.

Note!

The binary inputs may be energized from an external dc auxiliary supply (e.g. the station
battery) in some installations. Check that this is not the case before connecting the field
voltage otherwise damage to the protection may result. The status of each binary input can
be viewed using either RCSPC software installed in a portable PC or by checking the front
man-machine interface LCD. When each binary input is energized the display will change
to indicate the new state of the inputs.

4) Checking binary output circuits

NANJING NARI-RELAYS ELECTRIC CO., LTD 89


Chapter 10 Installation And Commissioning

Preferably, disconnect the binary output connector form the binary output cards. Check all
connected signals so that both load and polarity are in accordance with the relay’s specifications.

10.7 Energizing the Protection Equipment


Before the procedures in this section can be carried out the connection to external circuitry must
have been checked which ensures that the installation was made correctly.

The user must energies the power supply to the relay to start it up. This could be done in a
numerous of ways, from energizing a whole cubicle to energizing a single relay. The user should
reconfigurate the relay settings. The relay time must be set. The self-supervision function should
also be checked to verify that the relay unit operates properly. The user could also check the
software version, the relay’s serial number, the installed modules, and their ordering number to
ensure that the relay is according to delivery and ordering specifications.

1) Setting the relay time

Refer to 8.4.5 for detailed procedures.

2) Checking the self-supervision function

Refer to Chapter 4 for detailed description.

10.8 Setting The Protection Equipment


The customer specific values for each setting parameter have to be available. Each function
included in the relay has several setting parameters which has to be set in order to make the relay
behave as intended. A default value is provided for each parameter from factory.

All settings can be:

n Download from a PC or laptop with RCSPC software or remotely by SCADA. (Refer to 12.4.2).
Front port communication has to be established before the settings can be downloaded.

n Input manually through the local HMI (refer to 8.2.5)

To change settings through the local HMI need a password which is “+”, “◄”, “▲” and “-” keyboard
on the front panel.

Unless previously agreed to the contrary, the customer will be responsible for determining the
application-specific settings to be applied to the protection and for testing of any scheme logic
applied by external wiring and/or configuration of the protection’s internal programmable scheme
logic.

10.9 Establishing Connection And Verifying Communication


This test should only be performed where the protection is to be accessed from a remote location
and will vary depending on the communications standard being adopted.

It is not the intention of the test to verify the operation of the complete system from the relay to the
remote location, just the protection’s rear communications port and any protocol converter
necessary.

90 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 10 Installation And Commissioning

10.10 Verifying settings by secondary injection


Required tools for testing of a relay:

n Calculated settings

n Substation configuration diagram

n The relay diagram

n This instruction manual

n Three-phase test equipment

The relay has to be set before the testing can start. Only the functions that are used should be
tested.

The response from a test can be viewed in different ways:

n Binary output signals

n Service values in the local HMI

n A PC with RCSPC software or SCADA or master station

All used setting groups should be tested. The user can release the functions to be tested and
prevent other functions from operation by setting the corresponding parameters. The user could
also energize the binary input [BI_BlkComm] to disable communication function to ensure that no
events are reported to remote station during the test.

The setting checks ensure that all of the application-specific protection settings (i.e. both the
protection’s function and programmable scheme logic settings), for the particular installation, have
been correctly applied to the protection.

10.10.1 AC measurement check


1. Current measurement check

This test verifies that the accuracy of current measurement is within the acceptable tolerances.

Checking its magnitude using a multimeter. The corresponding reading can then be checked
either in the protection’s submenu [DSP METERING] column or a portable computer connected to
the front communication port with software RCSPC.

The measurement accuracy of the protection is ± 5%. However, an additional allowance must be
made for the accuracy of the test equipment being used.

Note!

The trip circuit should remain isolated during these checks to prevent accidental operation
of the associated circuit breaker.

The applied current and/or voltage should be big enough to ensure that both general fault
detector and protective fault detector can operate.

NANJING NARI-RELAYS ELECTRIC CO., LTD 91


Chapter 10 Installation And Commissioning

10.10.2 Percentage differential protection check


1. 3-terminal differential protection

1) Enable percentage differential protection

n Energize the binary input [EBI_PcntDiff] and de-energize binary input [BI_DS_Line].

n Set the logic setting [En_PcntDiff] and virtual binary input [VEBI_PcntDiff] as “1”.

2) Simulate an external fault

n Inject two in-phase currents to CT1 and CT2 from positive polarity respectively.

n Inject total current of CT1 and CT2 to CT3 from negative polarity.

n Simulating single-phase or multi-phase fault, percentage differential protection doesn’t


operate.

3) Simulate an internal fault

n Inject three in-phase currents to CT1, CT2 and CT3 from positive polarity respectively. Must
make sure the summation of three currents from CT1, CT2 and CT3 is greater than
[I_Pkp_PcntDiff].

n Simulating single-phase or multi-phase fault, percentage differential protection operates and


the LED “TRIP” and LED “TRFR TRIP” are lit with operation report “Op_PcntDiff” showed on
LCD.

4) Check percentage restraint characteristic

n Inject two in-phase currents to CT1 and CT2 from positive polarity respectively.

n Inject one out-phase current to CT3 from positive polarity. another adjustable I2, same phase
to I1, to opposite polarity terminal of CT3.

n Fix current of CT1 and CT2 and adjust current of CT3.

n Increase or decrease to check pickup setting [I_Pkp_PcntDiff] and restraint slope


[Slope_PcntDiff].

2. 2-terminal differential protection

1) Enable percentage differential protection

n Energize the binary input [EBI_PcntDiff] and binary input [BI_DS_Line].

n Set the logic setting [En_PcntDiff] and virtual binary input [VEBI_PcntDiff] as “1”.

2) Simulate an external fault

n Inject two out-phase currents to CT1 and CT2 with like polarity respectively.

n Simulating single-phase or multi-phase fault, percentage differential protection does not


operate.

92 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 10 Installation And Commissioning

3) Simulate an internal fault

n Inject two in-phase currents to CT1 and CT2 with like polarity respectively.

n Simulating single-phase or multi-phase fault, percentage differential protection operates and


the LED “TRIP” is lit with operation report “Op_PcntDiff” showed on LCD.

4) Check percent restraint characteristic

n Inject two out-phase currents to CT1 and CT2 witch like polarity.

n Fix the current of CT1 and adjust the current of CT2.

Increasing or decreasing the current of CT2 to check the setting [I_Pkp_PcntDiff] and restraint
slope [Slope_PcntDiff].

10.10.3 End fault protection check

Note!

The duration of AC input to simulate a fault should last longer than the time setting of
related protection element under testing. CT1 and CT2 mentioned here is the same with
that mentioned above.

1) Enable end fault protection

n Energizing the binary inputs [EBI_EFP] and [BI_DS_Line]

n Set logic setting [En_EFP1] and virtual binary input [VEBI_EFP] and as “1”.

2) Inject current I=1.05×[I_EFP1] to CT3 with time delay [t_EFP1], stage 1 of end fault
protection operates and the LED “TRFR TRIP” is lit with operation report “Op_EFP1” showed
on LCD.

3) Inject current I=0.95×[I_EFP1] to CT3, stage 1 of end fault protection does not operate.

4) Repeat step 1 to step 3 to check stage 2 of end fault protection.

10.10.4 Overcurrent protection check

Note!

The duration of AC input to simulate a fault should last longer than the time setting of
related protection element under testing. CT1 and CT2 mentioned here is the same with
that mentioned above.

1) Enable overcurrent protection

n Energize the binary input [EBI_OC]=1.

n Set logic setting [En_OC] and vitrual binary input setting [VEBI_OC] as ”1”.

2) Inject current I=1.05×[I_OC] to CT1 or CT2 with time delay [t_OC], overcurrent protection
operates and the LED “TRIP” is lit with operation report “Op_OC” showed on LCD.

NANJING NARI-RELAYS ELECTRIC CO., LTD 93


Chapter 10 Installation And Commissioning

3) Inject current I=0.95×[I_OC] to CT1 or CT2, overcurrent protection does not operate.

10.10.5 Binary input check


Energize every binary input respectively, check there state changes. Refer to 6.3.6.

10.10.6 Output contact check


1) Cut-off the DC power supply of the equipment, the normally closed contacts (901-902) and
(906-907) are closed. Under the normal condition, they are open.

2) When CT circuit failure, the normally open contacts (901-903) and (906-908) are closed.

3) Open the circuit of tripping output to CB and enable current differential protection or end fault
protection. When simulate an internal fault, the following normally open contacts are closed;

Signal contacts: (901-904) and (901-905);

Tripping contacts: (906-910), (917-918), (919-920) and (925-926);

Initiating transfer trip contacts: (913-915), (906-912) and (914-916);

10.10.7 Print fault report


In order to acquire the details of protection operation, it is convenient to print the fault report of
protection device. The printing work can be easily finished when operator presses the print button
on panel of protection device to energize binary input [BI_Print] or operate control menu. What
should be noticed is that only the latest fault report can be printed if operator presses the print
button. A complete fault report includes the content shown as follows.

1) Trip event report

2) Binary input when protection devices start

3) Self-check and the transition of binary input in the process of devices start

4) Fault wave forms compatible with COMTRADE

5) The setting value when the protection device trips

10.11 Final Check


After the above tests are completed, remove all test or temporary shorting leads, etc. If it has been
necessary to disconnect any of the external wiring from the protection in order to perform the
wiring verification tests, it should be ensured that all connections are replaced in accordance with
the relevant external connection or scheme diagram.

Ensure that the protection has been restored to service.

If the protection is in a new installation or the circuit breaker has just been maintained, the circuit
breaker maintenance and current counters should be zero. If a test block is installed, remove the
test plug and replace the cover so that the protection is put into service.

Ensure that all event records, fault records, disturbance records and alarms have been cleared
and LED’s has been reset before leaving the protection.

94 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 11 Maintenance

Chapter 11 Maintenance
NARI-RELAYS numerical relay RCS-924 is designed to require no special maintenance. All
measurement and signal processing circuit are fully solid state. All input modules are also fully
solid state. The output relays are hermetically sealed.

Since the device is almost completely self-monitored, from the measuring inputs to the output
relays, hardware and software defects are automatically detected and reported. The
self-monitoring ensures the high availability of the device and generally allows for a corrective
rather than preventive maintenance strategy. Therefore, maintenance checks in short intervals are
not required.

Operation of the device is automatically blocked when a hardware failure is detected. If a problem
is detected in the external measuring circuits, the device normally only provides alarm messages.

11.1 Appearance Check


1. The relay case should be clean without any dust stratification. Case cover should be sealed
well. No component has any mechanical damage and distortion, and they should be firmly
fixed in the case. Relay terminals should be in good condition. The keys on the front panel
with very good feeling can be operated flexibly.

2. It is only allowed to plug or withdraw relay board when the supply is reliably switched off.
Never allow the CT secondary circuit connected to this equipment to be opened while the
primary system is live when withdrawing an AC module. Never try to insert or withdraw the
relay board when it is unnecessary.

3. Check weld spots on PCB whether they are well soldered without any rosin joint. All dual
inline components must be well plugged.

11.2 Failure Tracing And Repair


Failures will be detected by automatic supervision or regular testing.

When a failure is detected by supervision, a remote alarm is issued and the failure is indicated on
the front panel with LED indicators and LCD display. It is also recorded in the event record.
Failures detected by supervision are traced by checking the “ALM REPORT” screen on the LCD.

Table 11.2-1 Repairment suggestion for alarms information

No. Alarm Solution


1 Alm_Smpl_DSP Replace the CPU module or notify the manufacturer
2 Alm_Smpl_CPU Replace the CPU module or notify the manufacturer
3 Alm_TrpOut Replace the OUT module or notify the manufacturer
Check the setting, reconfigure the setting and press “ENT” to
4 Alm_Setting confirm, If alarm still appears, replace the CPU module or notify the
manufacturer

NANJING NARI-RELAYS ELECTRIC CO., LTD 95


Chapter 11 Maintenance

Check the setting, reconfigure the setting and press “ENT” to


5 Alm_EEPROM confirm, If alarm still appears, replace the CPU module or notify the
manufacturer
Check the setting, reconfigure the setting and press “ENT” to
6 Alm_InvalidGrp confirm, If alarm still appears, replace the CPU module or notify the
manufacturer
7 Alm_ROM Replace the CPU module or notify the manufacturer
8 Alm_RAM Replace the CPU module or notify the manufacturer
Check the sampled values and the connection of AC secondary
9 Alm_PersistFD
current circuit
10 Alm_CTS Check the sampled values and the CT secondary circuit
11 Alm_BI_DS_Line Check the auxiliary contact of disconnect switch of line
Check Field voltage from DC module terminal 104-105 and wiring
12 Alm_Pwr_Opto between DC module and OPT module. Replace the DC module or
OPT module
13 Alm_Pwr_DC Check Power supply voltage level, or replace DC module.

When a failure is detected during regular testing, confirm the following:

n Test circuit connections are correct

n Modules are securely inserted in position

n Correct DC power voltage is applied

n Correct AC inputs are applied

n Test procedures comply with those stated in the manual

11.3 Replace Failed Modules


If the failure is identified to be in the relay module and the user has spare modules, the user can
recover the protection by replacing the failed modules.

Repair at the site should be limited to module replacement. Maintenance at the component level is
not recommended.

Check that the replacement module has an identical module name (AC, DC, CPU, SIG, OPT, OUT,
etc.) and hardware type-form as the removed module. Furthermore, the CPU module replaced
should have the same software version. And the AC and DC module replaced should have the
same ratings.

The module name is indicated on the top front of the module. The software version is indicated in
LCD menu “VERSION”.

Caution!

When handling a module, take anti-static measures such as wearing an earthed wrist band
and placing modules on an earthed conductive mat. Otherwise, many of the electronic

96 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 11 Maintenance

components could suffer damage. After replacing the CPU module, check the settings.

1) Replacing a module

n Switch off the DC power supply

n Disconnect the trip outputs

n Short circuit all AC current inputs and disconnect all AC voltage inputs

n Unscrew the module.

Warning!

Hazardous voltage can be present in the DC circuit just after switching off the DC power
supply. It takes approximately 30 seconds for the voltage to discharge.

2) Replacing the Human Machine Interface Module (front panel)

n Open the relay front panel

n Unplug the ribbon cable on the front panel by pushing the catch outside.

n Detach the HMI module from the relay

n Attach the replacement module in the reverse procedure.

3) Replacing the AC, DC, CPU, OPT or OUT module

n Unscrew the module connector

n Unplug the connector from the target module.

n Unscrew the module.

n Pull out the module

n Inset the replacement module in the reverser procedure.

n After replacing the CPU module, input the application-specific setting values again.

11.4 Replace Button Battery


When the voltage of button Battery on CPU board is below 3 volts (nominal voltage is 3.6 volts),
please replace the button battery to ensure internal clock of CPU board running correctly.

11.5 Cleaning
Before cleaning the relay, ensure that all AC/DC supplies, current transformer connections are
isolated to prevent any chance of an electric shock whilst cleaning.

Front panel cleaning: use a smooth cloth. Do not use abrasive material or detergent chemicals.

11.6 Storage
The spare relay or module should be stored in a dry and clean room. Based on IEC standard

NANJING NARI-RELAYS ELECTRIC CO., LTD 97


Chapter 11 Maintenance

60255-6 the storage temperature should be from –40oC to 70oC, but the temperature of from 0oC
to 40oC is recommended for long-term storage.

98 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 12 Software RCSPC

Chapter 12 Software RCSPC


12.1 General Description
Software RCSPC program (user version) is developed for the user to download program,
read and modify settings, display sampled value, tripping report, change of binary input
and abnormality and maintain line differential relay RCS-924 on site. Double click the
executable file and run the software RCSPC, when the connection succeeds between
RCS-924 with computer via RS232 port, the screen will show the following figure, please
see Figure 12.1-1.

Figure 12.1-1 Display of connection with RCS-924 using RCSPC

12.2 Connection Between RCS-924 And Computer


A 9-pin female RS232 serial port is located on the front panel of equipment for
communication with computer. Connect RS232 serial port of equipment with computer
using a serial cable with a DB9 female serial connector on one end, while a DB9 male
serial connector on the other end. Each serial connector generally has two screws
measuring 0.3mm allow the serial connection to be securely connected to RCS-924.
Please refer to the following figure for correct connection.

NANJING NARI-RELAYS ELECTRIC CO., LTD 99


Chapter 12 Software RCSPC

GRP
ESC

Figure 12.2-1 Diagram of connection with RCS-924 via RS232 port

12.3 Parameter Configuration


12.3.1 Equipment configuration
Set the setting [Debug_Baud]=9600 in the menu EQUIP SETUP.

12.3.2 Software configuration


There are 3 bars, which are from top to bottom:

n Title bar

n Menu bar

n Tool bar

Shown as Figure 12.3-1.

Figure 12.3-1 Title bar, menu bar and tool bar of RCSPC

Click the icon of tool bar “Parameter”, dialog box of parameter configuration for
communication is displayed, shown as Figure 13-4. Only the parameter “COM port” shall
be configured as same as the port of computer which is actually connected with the
equipment, all other parameters shall be configured as same as displayed in Figure
12.3-2.

100 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 12 Software RCSPC

Figure 12.3-2 Parameter configuration

Baud rate: 9600

Data bit: 8

Stop bit: 1

Parity bit: No parity

Download baud rate: 57600

Device type address: FDFFD0

CPU No: 1

Mainboard frequency: 20

Mainboard chip type: INTEL80296+ADSP2181

NANJING NARI-RELAYS ELECTRIC CO., LTD 101


Chapter 12 Software RCSPC

12.4 Usage Instruction For RCSPC


12.4.1 Description for tool bar

Figure 12.4-1 Description of tool bar

12.4.2 Device settings


After connecting with equipment successfully, click the icon of tool bar “Device setting”,
the following figure will be displayed.

Figure 12.4-2 The diagram of showing device settings

User can finish upload current settings from the equipment by “UPLOAD”, download
current settings to the equipment by “DOWNLOAD”, save current settings as a file by
“SAVE”, read setting from a file by “READ”, print current setting by “PRINT” and restore to
default settings by “DEFAULT”.

102 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 12 Software RCSPC

12.4.3 Show device status


After connecting with equipment successfully, click the icon of tool bar “Show device
status”, the following figure will be displayed.

Figure 12.4-3 The diagram of showing device status

User can observe real time sampled data and binary inputs status, and save them as a
file.

12.4.4 Show device report


After connecting with equipment successfully, click the icon of tool bar “Show device
report”, the following figure will be displayed.

NANJING NARI-RELAYS ELECTRIC CO., LTD 103


Chapter 12 Software RCSPC

Figure 12.4-4 The diagram of showing device report

User can display tripping report, abnormality and change of binary input. They can be
saved as recorder files respectively. For tripping report, select a recorder to record with
the format of COMTRADE, and then generator four files, which are “*.cfg”, “*.hdr”, “*.dat”
and “*. CMT”. They can be analyzed and display wave by the auxiliary analyze software.

12.4.5 Signal reset


After connecting with equipment successfully, click the icon of tool bar “Signal reset”, all
magnetic latched output relays and signal relays will be reset.

104 NANJING NARI-RELAYS ELECTRIC CO., LTD

You might also like