Guidance Note 1
Selection & Erection
(Including Amd No 1 : 2002)
BS 7671 : 2001 Requirements for Electrical InstallationsPublished by: The Institution of Electrical Engineers, Savoy Place,
LONDON, United Kingdom WC2R OBL.
©2002: The Institution of Electrical Engineers, London
Issued August 1992
Reprinted April 1993, with amendments
2nd edition incorporating Amendment No 1 to BS 7671 - 1996
3rd edition incorporating Amendment No 2 to BS 7671 - 1999
4th edition incorporating Amendment No 1 to BS 7671 - 2001
Copies may be obtained from:
The Institution of Electrical Engineers
PO Box 96, STEVENAGE,
United Kingdom. SG1 25D
Tel: +44 (0)1438 767 328
Fax: +44 (0)1438 742 792
Email:
[email protected]
httpy/www.iee.org.uk/publish/books!
All rights reserved. No part of this publication may be
reproduced, stored in a retrieval system or transmitted in any
form or by any means — electranic, mechanical, photocopying,
recording or otherwise — without the prior written permission
of the publisher.
While the author, publisher and contributors believe
that the information and guidance given in this work
is correct, all parties must rely upon their own skill
and judgement when making use of it. Neither the
author, the publisher or any contributor assume any
liability to anyone for any loss or damage caused by
any error or omission in the work, whether such error
or omission is the result of negligence or any other
cause. Where reference is made to legislation it is not
to be considered as legal advice. Any and all such
Viability is disclaimed.
ISBN 0 85296 989 9, 2002Contents
ACKNOWLEDGEMENTS
PREFACE
INTRODUCTION
SECTION 1 THE GENERAL REQUIREMENTS
1.1. General
1.2. Equipment
1.3. Electricity at Work Regulations 1989
1.4 The Construction (Design and Management)
Regulations 1994
1.5. The Building Regulations 2000
1.6 Competence
SECTION 2 SELECTION AND ERECTION OF EQUIPMENT
2.1. Selection and erection of equipment
2.2 Operational conditions and external influences
2.3 Compliance with standards
24 Operational conditions and external influences
25 Identification
2.6 Mutual detrimental influence
2.7 Compatibility
2.8 ‘Clean’ (low noise) earths
2.9 LV switchgear and controlgear assemblies
SECTION3 PROTECTION AGAINST OVERCURRENT,
ELECTRIC SHOCK AND OVERVOLTAGE
3.1. Protective devices
3.2 Overcurrent protective devices
3.3 Fuses
3.4. Circuit-breakers
3.5. Insulation monitoring devices
3.6 Residual current operated devi
3.7 _Earthed equipotential bon
disconnection of supply
3.8. Protection against overvoltage
s (RCs)
g and automatic
10
11
13
1B
13
14
14
15
7
19
19
19
19
21
22
30
30
32 |
33
40
40
4
43
a7
48
59
67 |SECTION 4
SECTION 5
SECTION 6
SECTION 7
SECTION 8
EXTERNAL INFLUENCES
4.1 External influences
4.2 Ambient temperature (AA)
4.3 Solar radiation (AN) and ultra-violet radiation
44 The IP and IK classifications
4.5 Presence of water (AD) or high humidity (AB)
4.6 Presence of solid foreign bodies (AE)
4.7 Presence of corrosive or polluting substances (AF)
48 Impact (AG), vibration (AH) and other mechanical
stresses (AJ)
4.3 Presence of fauna (AL), flora and/or mould
growth (AK)
4.10 Potentially explosive atmospheres
4.11 Choice of protective measures as a function of
external influences
INSTALLATION OF CABLES
5.1 Cable selection
5.2 Cable concealed in structures
5.3. Cable routes and livestock
5.4 Capacity of conduit and trunking
5.5. Selection of cables and wiring systems with low
‘emission of smoke and corrosive gases when
affected by fire
5.6 ‘Section 20°
5.7 Buried cables
5.8. Sealing and fire stopping
‘SIZING OF CABLES
6.1 Current-carrying capacity and voltage drop
6.2 Diversity
6.3 Neutral conductors
6.4 Voltage drop in consumers’ installations
OTHER INFLUENCES
7.1 Electrical connections
7.2. Cables in contact with thermal insulation
7.3, Mutual or individual deterioration
7.4 Proximity to other services
7.5 Placisticiser migration from pvc insulation to the
conductor surface
INSTALLATION OF EQUIPMENT
8.1 Equipment having a high protective conductor
current
8.2 Water heating
83. Safety services
84 Other equipment
8.5 Luminaires
8.6 Selection and erection in relation to operation
and maintainability
71
n
R
B
74
4
1s
76
78
79
80
80
84
88
1
92
92
94
96
99
101
101
101
102
104
106
106
108
wt
12
14
116
116
7
118
118
120
122APPENDICES
APPENDIX A:
APPENDIX B:
APPENDIX C:
APPENDIX D:
APPENDIX E:
APPENDIX F:
APPENDIX
APPENDIX
APPENDIX I:
APPENDIX J:
APPENDIX
APPENDIX L:
INDEX
CABLE CAPACITIES OF CONDUIT AND TRUNKING
a) General
b) Single-core thermoplastic (pve) insulated cables i
of conduit not exceeding 3 m in length
©) Single-core thermoplastic (pve) insulated cables; in straight runs
of conduit exceeding 3 m in length or in runs of any length
incorporating bends or sets
4) Single-core thermoplastic (pve) insulated cables in trunking
@) For other sizes and types of cable in conduit or trunking,
including flexible conduit
) Background to the tables
DEGREES OF PROTECTION PROVIDED BY ENCLOSURES
IP code for ingress protection
Ik code for impact protection
CONVENTIONAL CIRCUIT ARRANGEMENTS AND THE
PROVISION OF SOCKET-OUTLETS
a) General
b) Final circuits using socket-outlets complying with BS 1363 and
fused connection units
©. Final radial circuits using 16 A socket-outlets complying with
BS 4343 (BS EN 60309-2)
4) Cooker final circuits in household premises
) Water heating and electric shower final circuits in household
premises .
) Provision of socket-outlets
9) Mounting heights of accessories
LIMITATION OF EARTH FAULT LOOP IMPEDANCE FOR
COMPLIANCE WITH REGULATION 543-01-01
straight runs
RESISTANCE AND IMPEDANCE OF COPPER AND
ALUMINIUM CONDUCTORS UNDER FAULT CONDITIONS
SELECTION AND ERECTION OF Wi
ING SYSTEMS
NOTES ON METHODS OF SUPPORT FOR CABLES,
CONDUCTORS AND WIRING SYSTEMS
MAXIMUM DEMAND AND DIVERSITY
MINIMUM SEPARATING DISTANCES BETWEEN
ELECTRICITY SUPPLY CABLES AND
TELECOMMUNICATIONS OR CONTROL CABLES
PERMITTED PROTECTIVE CONDUCTOR CURRENTS
STANDARD SYMBOLS, UNITS AND GRAPHICAL
SYMBOLS FOR GENERAL ELECTRICAL PURPOSES
ADDRESSES OF ASSOCIATED BODIES AND
IDENTIFICATION SYMBOLS
125
126
126
128
128
129
131
133
135
135
141
143
143
144
148,
148
149
149
152
155
176
184
191
199
204
208
209
217
225Co-operating Organisations
The Institution of Electrical Engineers acknowledges the cont
organisations in the preparation of this Guidance Note.
n made by the following
Association of Manufacturers of Domestic Appliances
SA MacConnacher BSc CEng MIEE
British Cables Association
CK Reed | Eng MIIE
British Electrotechnical & Allied Manufacturers Association Ltd
R Lewington Associate IEE
British Electrotechnical Approvals Board
PD Stokes MA CEng MRAeS.
British Standards Institution
WE Fancourt
City & Guilds of London Institute
HR Lovegrove lEng FIIE
Electrical Contractors’ Association
D Locke IEng MIIE ACIBSE
Electrical Contractors’ Association of Scotland t/a SELECT
D Millar lng MIIE MILE
Electrical installation Equipment Manufacturers’ Association Ltd
Eur Ing MH Mullins BA CEng MIEE FIIE
Electricity Association Limited
D J Start BSc CEng MIEE
ERA Technology Ltd
MW Coates B Eng
Federation of the Electronics industry
FW Pearson CEng MIE
‘The GAMBICA Association Ltd
K A Morriss BSc CEng MIEE MinstMc
Health & Safety Executive
Eur Ing J A McLean BSc(Hons) CEng FIEE FIOSM
Institution of Electrical Engineers
WR Allan BEng(Hons) CEng MIEE (Editor)
PRL Cook CEng FIEE MCIBSE
P E Donnachie BSc CEng FIEE
B J Lewis BSc Mphil CEng FIEE
L Markwell BSc CEng MIEE MCIBSE LCGI
Institution of Incorporated Engineers
P Tootill lEng MIIE
Lighting Association
KR Kearney lEng MIIE
National House Building Council
PCrane
National inspection Council for Electrical installation Contracting
Safety Assessment Federation Limited
J Gorman BSc(Hons) CEng MIEE
Society of Electrical and Mechanical Engineers serving Local Government
C Tanswell CEng MIEE MCIBSEAcknowledgements
References to British Standards, CENELEC
Harmonisation Documents and International
Electrotechnical Committee standards are made with
the kind permission of BSI. Complete copies can be
obtained by post from:
BS! Customer Services
389 Chiswick High Road
London W4 4AL
Tel: General Switchboard: 020 8996 9000
For ordering: 020 8996 7000
For information or advice: 020 8996 7111
For membership: 020 8996 7002
Fax: For orders: 020 8996 7001
For information or advice: 020 8996 7048
BSI operates an export advisory service — Technical Help
to Exporters — which can advise on the requirements of
foreign laws and standards.
The BSI also maintains stocks of international and
foreign standards, with many English translations.
Up-to-date information on BSI standards can be obtained
from the BSI website http:/www.bsi-global.com/
RCD terminology and information provided by the
Low Voltage Circuit Breaker Division of EIEMA and is
taken from the EIEMA Code of Practice for the
Selection and Application of Residual Current Devices
currently being prepared for publication.
Illustrations and information of the forms of
separation of LV switchgear were provided by The
Low Voltage Distribution Switchboard Division of
EIEMA.The EIEMA booklet ‘Guide to forms of separation’ can
be obtained from:
EIEMA
Westminster Tower
3 Albert Embankment
London SE1 7SL.
Tel: 020 7793 3013
Extracts from NHBC Standards, Chapter 8.1, for
internal services, on the requirement for notches and
holes in joists are reproduced with permission from
The National House Building Council (NHBC),
Buildmark House, Chiltern Avenue, Amersham, Bucks,
HP6 SAP.
Extracts from the LDSA document ‘Fire safety guide
No 1’ on Section 20 buildings are reproduced with
permission from The London District Surveyors
Association, PO Box 266, London, BR2 9ZN.
Guidance on cable separation in Appendix | was
reproduced from The Electrical Contractors
Association document ‘Recommended cable
separations to achieve electromagnetic compatibility
(EMO) in buildings’ with the permission of the ECA,
ESCA House, 34 Palace Court, London, W2 4HY.
The table on colour identification of buried services is
reproduced with the permission of The National Joint
Utilities Group, 30 Millbank, London, SW1P 4RD,
The tables on cable references in Appendix F were
reproduced with permission of Anixter (UK) Ltd, 15
Chesford Grange, Woolston, Warrington, Cheshire,
WAT 4RQ.
Copies of Health and Safety Executive documents and
approved codes of practice (ACOP) can be obtained
from:
HSE Books
PO Box 1999
Sudbury
Suffolk CO10 6FS
Tel: 01787 881165
Fax: 01787 313995Health and Safety Executive telephone enquiries can
be made to:
HSE Info Line on : 08701 545500
Fax and postal enquiries can be made to:
HSE Information Centre
Broad Lane
Sheffield $3 7HQ
Tel: 01142 892345.10
Preface
This Guidance Note is part of a series issued by the
Wiring Regulations Policy Committee of the
Institution of Electrical Engineers to enlarge upon and
simplify some of the requirements in BS 7671 : 2001
inc Amd No 1 (formerly the Sixteenth Edition of the
IEE Wiring Regulations).
Note that this Guidance Note does not ensure
compliance with BS 7671. It is a guide to some of the
requirements of BS 7671 but electricians should
always consult BS 7671 to satisfy themselves of
compliance.
The scope generally follows that of the Regulations
and the principal Section numbers are shown on the
left. The relevant Regulations and Appendices are
noted in the right-hand margin. Some Guidance Notes
also contain material not included in BS 7671
but which was included in earlier editions. All of the
Guidance Notes contain references to other relevant
sources of information.
Electrical installations in the United Kingdom which
comply with BS 7671 are likely to satisfy the relevant
aspects of Statutory Regulations such as the Electricity
at Work Regulations 1989, but this cannot be
guaranteed. It is stressed that it is essential to
establish which Statutory and other Regulations apply
and to install accordingly. For example, an installation
in premises subject to licensing may have requirements
different from, or additional to, BS 7671, and those
requirements will take precedence.Introduction
This Guidance Note is concerned principally with Part
5 of BS 7671 — Selection and Erection of Equipment.
Neither BS 7671 nor the Guidance Notes are design
guides. It is essential to prepare a full design and
specification prior to commencement or alteration of
an electrical installation. Compliance with the relevant
standards should be required.
The design and specification should set out the
requirements and provide sufficient information to
enable competent persons to carry out the
installation and to commission it. A good specification
must include a description of how the system is to
operate and all the design and operational
parameters. It must provide for all the commissioning
procedures that will be required and for the provision
of adequate information to the user. This will be by 514-09,
means of an operational manual or schedule, and ‘as
fitted’ drawings if necessary.
It must be noted that it is a matter of contract as to
which person or organisation is responsible for the
production of the parts of the design, specification
installation and any operational information. The
persons or organisations who may be concerned in
the preparation of the works include:
The Designer
The Planning Supervisor
The Installer (or Contractor)
The Supplier of Electricity
The installation Owner (Client) and/or User
The Architect
The Fire Prevention Officer
Any Regulatory Authority
Any Licensing Authority
The Health and Safety Executive
”2
In producing the design and specification advice
should be sought from the installation owner and/or
user as to the intended use. Often, as in a speculative
building, the intended use is unknown. In such cases
the specification and/or the operational manual must
set out the basis of use for which the installation is
suitable.
Precise details of each item of equipment specified
should be obtained from the manufacturer and/or
supplier and compliance with appropriate standards
confirmed.
The operational manual must include a description of
how the system as installed is to operate and all
commissioning records. The manual should also
include manufacturers’ technical data for all items of
electrical equipment, wiring, switchgear, accessories,
etc. and any special instructions that may be needed.
The Health and Safety at Work etc. Act 1974 (HSWA)
Section 6, and the Construction (Design and
Management) Regulations (CDM) are concerned with
the provision of information. Guidance on the
preparation of technical manuals is given in BS 4884
and BS 4940. The size and complexity of the
installation will dictate the nature and extent of the
manual.
131-01-01
132-01-01
511Section 1 — The General Requirements
141
1.2
General
132
510
511
Equipment
120
130
131
132
133
510
511
‘Equipment’ is short for ‘electrical equipment! and is
defined as:
“Any item for such purposes as generation,
conversion, transmission, distribution or utilisation of
electrical energy, such as machines, transformers,
apparatus, measuring instruments, protective devices,
wiring systems, accessories, appliances and
luminaires.’
Installation designers may need information from the
manufacturer as to the suitability of equipment for its
intended use. It is not the intention of BS 7671 : 2001
to stifle innovation or new techniques but the
Standard only recognises and considers established
materials and techniques.
The designer is responsible for the safety of the
design. All departures from BS 7671, although the
designer is confident regarding safety, must be
recorded in the Electrical Installation Certificate.
Chapter 13 of BS 7671 : ‘Fundamental principles’
outlines basic requirements. Later Chapters describe in
more detail particular means of compliance with
Chapter 13. Chapter 13 is normally referred to only
where it is intended to adopt a method not
recognised in later Chapters. The terms allow for
interpretation to suit special cases.
The phrase ‘so far as is reasonably practicable’ is used
in several Regulations. It should be borne in mind
that methods described in later Chapters are
considered reasonably practicable in most
circumstances.
Part 2
120-02-01
132-01-01
132-01-02
511-01-01
511-01-02
Chap 13
Chap 13
Where methods are used which are not described in later
Chapters, then the designer has an onus to confirm that the
degree of safety is not less than that required by Chapter 13.
81.3
Electricity
at Work
Regulations
1989
1.4 The
Construction
(Design and
Management)
Regulations
1994
The requirements of the Electricity at Work
Regulations (1989) are intended to provide for the
safety of persons gaining access to or working with
electrical equipment.
The Memorandum of Guidance on the Electricity at
Work Regulations (1989) (Health and Safety Executive
Publication HSR25) should be carefully studied and it
should be borne in mind that the Electricity at Work
Regulations (1989) (the EAW Regulations) apply to
designers, installers and users of installations alike.
BS 7671 is intended for designers, installers and those
verifying electrical installations and thus includes the
design of the installation and the selection and
erection of electrical equipment. The user has the
responsibility for ensuring that equipment is properly
operated and maintained when necessary. The
installation designer should assess the expected
maintenance and the initial design should make
provision for maintenance to be carried out.
Within the EAW Regulations is the requirement for
adequate maintenance to prevent danger, and the
memorandum to the EAW Regulations advises that
regular inspection of electrical systems (supplemented
by testing as necessary) is an essential part of any
preventive maintenance programme. Regular
Operational functional testing of safety circuits
(emergency switching/stopping etc) may be required
— because unlike functional circuits they may be
infrequently used. Comprehensive records of all
inspections and tests should be made, retained and
reviewed for any trends that may arise. The IEE
Guidance Note 3 on Inspection and Testing gives
guidance on initial and periodic inspection and
testing of installations.
The Construction (Design and Management)
Regulations 1994 (the CDM Regulations) made under
the Health and Safety at Work Act 1974 place
responsibilities on most installation owners and their
professional design teams to ensure a continuous
consideration of health and safety requirements
during the design, construction, and throughout the
life of an installation, including maintenance, repair
and demolition. This includes design of the electrical
installation, and selection and erection of electrical
131-12-04
341-01-01equipment for health and safety in installation and
general operation. Design work should take into
account the practicalities of installation and adequate
installation and operation access and maintenance
requirements for all equipment. It is important that all
those who can contribute to the health and safety of
a construction project, particularly clients (the
installation users) and designers, understand what
they and others need to do under the CDM
Regulations, and discharge their responsibilities
accordingly.
Designers must consider the need to design in a way
which avoids foreseeable risks to health and safety or
reduces these risks as far as practicable so that
projects they design can be constructed, operated and
maintained safely. Where risks cannot altogether be
avoided, information on them has to be provided for
inclusion in the project health and safety plan. The
designer must also co-operate with others to enable
all parties to comply with relevant statutory
requirements and prohibitions placed on them.
A series of Approved Documents have been published
for the purpose of providing practical guidance to the
requirements of the Building Regulations 2000.
Approved Documents of particular interest to
designers and installers of electrical installations are
* Approved Document L1 - Conservation of fuel and
power in dwellings,
* Approved Document L2 - Conservation of fuel and
power in buildings other than dwellings
* Approved Document M - Access and facilities for
disabled people.
Approved Document L1 contains a requirement that
reasonable provision must be made for occupiers to
obtain the benefits of efficient lighting.
Approved Document M includes requirements for the
mounting heights of accessories, and these are
referred to in Appendix C of this Guidance Note.
Internal lighting
One way of demonstrating compliance with Approved
Document L1 would be to install, at a reasonable
number of locations, where lighting can be expected
to have most use, fixed lighting (either lampholders
1131-12-01
18or complete luminaires) which only take lamps having
a luminous efficacy greater than 40 lumens per circuit
watt. Examples of lamps which achieve this efficacy
are fluorescent lamps and compact fluorescent lamps.
‘Away of ascertaining the number of locations which
require energy efficient lighting would be to follow
the recommendations in Table 1.1 below.
Table 1.1 Method for determining the number of
locations to be equipped as a reasonable provision
for efficient lighting
Number of rooms] Recommended minimum
created ' number of locations *
1-3 1
4-6 2
7-3 3
10-12 4
Notes
"Hall, stairs and landing(s) count as one room (but
may contain more than one fitting)
7 Excludes garages, lofts and outhouses
Reproduced by kind permission of the DTLR
External lighting
External lighting includes lighting in porches but does
not include lighting in garages and carports.
Reasonable provision must be made to enable
effective control (for example, a system which will
switch the light off when there is sufficient daylight
and when not required at night) and/or the use of
efficient lamps (such as a system which can only be
used with lamps having an efficacy greater than 40
lumens per watt).
Approved Document L2 contains requirements for
general lighting efficacy in offices, industrial and
storage buildings. Lighting systems in such buildings
must be provided with reasonably efficient
lamp/luminaire combinations. A way of complying
with the requirements would be to provide lighting
with an initial efficacy, averaged over the whole
building, of not less than 40 luminaire — lumens pet
circuit watt. Approved Document L also includes
requirements for display lighting.1.6 Competence
For further information, the Approved Document
should be consulted.
{tis currently envisaged that an electrical safety
requirement applying to ‘dwellings’ (ie. houses and
flats) will be included in the Building Regulations for
England and Wales as Approved Document P -
Electrical safety. This is expected to state that a way of
meeting the requirements for electrical installations is
to comply with the requirements of BS 7671 : 2001.
The Building Regulations (Scotland)
The Building Regulations 2000 are not applicable in
Scotland, where the Building Regulations (Scotland)
apply. The detailed requirements are given in the
Technical Standards for compliance with the Building
Standards (Scotland) Regulations.
These standards also contain requirements for
conservation of fuel and power but have no
requirement for mounting heights of accessories.
With regard to electrical installations in Scotland, the
requirements of the above Building Regulations are
deemed to be satisfied by complying with BS 7671.
BS 7671 requires that an assessment be made of the 300-01-01
external influences to which the installation is Appx 5
exposed. Amongst these, as indicated in Appendix 5
of BS 7671, is Category BA —classification of the
capability of persons. This recognises different levels,
from an ordinary person to a skilled person. It must be
remembered that a skilled person will not be skilled in
all facets of electrical work and consequently will not
be competent in all works.
‘A competent person has sufficient knowledge and
experience to carry out the work without danger to
him/herself or to ather people.
Persons performing electrical work must have 731-01-03
sufficient technical knowledge or experience orbe —741-01-04
adequately supervised such that danger or injury are
prevented. The object is that persons dealing with
electrical equipment are not placed at risk due to a
lack of skills on their own part, or on the part of
others. Technical knowledge or experience may
include basic knowledge of electricity, experience of
electrical work, understanding of the system to be
worked on, understanding of the hazards and the18
necessary precautions and the ability to recognise at
all times whether it is safe for work to continue.
Competence also includes a knowledge of safety and
safe working practice, and practical skills were
needed.
A person possessing technical knowledge or sufficient
experience to enable him/her to avoid danger is
recognised by BS 7671 asa ‘skilled person’ and a
person adequately advised or supervised by one or Part 2
more skilled persons to enable him/her to avoid the
dangers that electricity may create is an ‘instructed
person’.
To require, or allow, a person who is not competent
to undertake electrical work may be a breach of the
statutory Health and Safety legislation, including the © EWR
Electricity at Work Regulations 1989. Regulation 16Section 2 — Selection and Erection of
24
equipment
510
2.2 Operational
conditions and
external
influences
512
2.3 Compliance
with standards
511
Equipment
Chapter 51 gives the basic common rules to which
every installation must comply.
An assessment by the designer of installation
characteristics and conditions will be necessary,
including all the requirements of Part 3 of BS 7671:
2001. The installation must be designed to be suitable
for all the relevant conditions and external influences
foreseen, including electricity supply effects or effects
on the supply.
Appendix 5 of BS 7671 details the system of
classification of external influences developed in IEC
60364-3, and the classification is indicated in parts of
Chapter 52. This system is not in general use in the UK
but certain parts can serve as a reminder of conditions
to be considered.
All equipment must be selected to accommodate the
worst foreseeable conditions of service that can be
encountered even if such conditions happen rarely.
BS 7671 recognises equipment which complies with a
British Standard or Harmonised Standard appropriate
to the intended use of the equipment without further
qualification. A Harmonised Standard is defined in
Part 2 as ‘A standard which has been drawn up by
common agreement between national standards
bodies notified to the European Commission by all
member states and published under national
procedures’.
There is a statutory definition of a Harmonised
Standard in Health and Safety Statutory Instrument
510-01-01
Part3
512
510-01-01
331-01-01
Chap 32
Chap 52
Appx 5
510-01-01
511-01-01
Part 220
No 1856 (1992) ‘The Supply of Machinery (Safety)
Regulations 1992’. This states:
‘Harmonised standard’ means a technical
specification adopted by the European Committee for
Standardisation (CEN) or the European Committee for
Electrotechnical Standardisation(CENELEC) or both,
upon a mandate from the Commission in accordance
with Council Directive 83/189/EEC of 28 March 1983
laying down a procedure for the provision of
information in the field of technical standards and
regulations, and of which the reference number is
published in the Official Journal of the European
Communities.
EUROPEAN NORMS (ENs)
European Norm EN standards are standards that are
required to be adopted by all CENELEC members and
to be published with identical text by all members,
without any additions, deletions or further technical
amendments. Such EN standards then supersede the
relevant national standards which are withdrawn to
an agreed timescale. They are published as BS ENs in
the UK.
HARMONISATION DOCUMENTS (HDs)
Harmonisation Documents (HDs) forming the
CENELEC 384 standard are documents based on IEC
60364. Harmonised Standards are standards that have
been agreed by all CENELEC members (possibly with
national modifications); a National Standard may
have further technical additions (so long as they are
not in conflict with the HO — but not deletions —
made by the relevant national standards committee.
BS 7671 is based on a number of CENELEC HDs within
the 384 series (see the Preface of BS 7671 on page 7)
with extra specific technical material added.
Equipment is sometimes satisfactory only when used
in a particular way or with other matching
equipment. Certain equipment complying with a
foreign standard may be safe when used, for
example, with a foreign wiring system, but may not
be safe when used in conjunction with traditional UK 511-01-01
practice. Where equipment complying with a foreign 511-01-02
standard based on an IEC standard is specified, the
designer or specifier must verify that the equipment is
at least as safe as similar equipment complying with24
Operational
the relevant British or Harmonised Standard. It is the
designer's responsibility to ensure that equipment the
designer specifies which is not to a British or
Harmonised Standard provides the required
performance and degree of protection.
Note that BS 7671 does not insist on approval or
certification of the equipment to the relevant
Standard, but this may be required in some cases by
legislation or by the client.
Equipment of ali types must be suitable for its
situation and use.
Regulation 331-01-01 lists some examples of 331-01-01
characteristics which may adversely affect the
equipment to be installed or the electricity supply or
other services. This list is not exhaustive but shows
some details of what the designer should consider.
Equipment must operate safely and should be
efficient and correctly selected .
The assessment of general characteristics requiresa 300-01-01
thorough consideration of the purpose of the 512-01-01
installation, the building and installation structure 512-02-01
and the electricity supply characteristics including 512-03-01
voltage, current and frequency, which must be noted
during the first part of the design. If, for example,
there is doubt that a switch or circuit-breaker can be
used with inductive or capacitive circuits (e.g. motors,
transformers or fluorescent lighting) advice should be 512-05-01
obtained from the manufacturer. 331-01-01
MOTORS
Electric motors may have similar power ratings but, 512-04-01
different applications, Motors for lifts, industrial plant
and machinery, propulsion or ventilation will have
differing duty cycles, and will usually be the subject of
a Standard. The fixed wiring must be able to match
the duty cycles of the connected load. infrequently
used motor-driven equipment with brakes will have 52-01-01
different demands on the fixed wiring when
compared with, say, a hydro extractor which uses
‘plugging’ as a method of braking the equipment
frequently. The demands on the fixed wiring should
be established from the manufacturer's installation
instructions. These details will form part of the
2425
22
Identification
514
installation manual. (See Guidance Note 6 for detailed
information on cable selection for motor circuits.)
ELECTROMAGNETIC COMPATIBILITY (EMC)
All equipment must be selected and erected so as to
allow safe working, prevent harmful effects to other
equipment and not impair the supply arrangements.
This includes the consideration of electromagnetic
compatibility (EMC) effects, as well as more
straightforward considerations such as loading, 515-02
current and voltage rating, circuit arrangements, etc.
Regulation 515-02 specifically requires consideration
of EMC when selecting and installing equipment.
Both electromagnetic immunity (EMI), the
protection of equipment from other electromagnetic
influences (Regulation 515-02-01), and electromagnetic
emission, the production and emission of
electromagnetic interference by the proposed
equipment (Regulation 515-02-02), must be
considered. This is a specialist application and advice
from the equipment manufacturer should generally
be taken. (See Appendix | for further information on
cable separation.)
HARMONICS
Harmonics are an aspect of EMC. Harmonic voltages
and currents can cause interference with the normal
operation of equipment and overload cables in
certain cases (see Sections 2.6 and 6 also).
‘CABLES
The identification colours for non-flexible cables for
fixed wiring are given in Table 51A of BS 7671 — Table 514
reproduced here as Table 2.1 for convenience. These
colours will be revised after 2004.
Flexible cables and flexible cords may be used for 521-01-04
fixed wiring, subject to the relevant provisions of the
Regulations being met. These provisions are generally
considered to relate to physical installation criteria
but it should be remembered that the core colours of
flexible cables and cords are not the same as those for
fixed cables in Table 51A and are laid down in Table
51B. Table 51B
There is no definition of a "fixed" cable and, as the
colour coding for flexible cables is by now wellunderstood, there is no need to identify the cores of
flexible cables or cords when their colour and function
comply with Table 51B - even if they have been fixed.
Any other colour identification of the cores of a
flexible cord or cable is a deviation from the
requirements of BS 7671 and should only be done
after careful consideration as to whether in the
circumstances it is impossible to comply with the
requirements, and the level of safety provided is not
less than that by compliance.
The notes of Table 51B say that if the blue core is used
for another purpose or it is necessary to identify the
phases this is to be done by letters ie. L1, L2 or L3. A
blue core may be used as a phase conductor if the
circuit does not have a neutral and this should be
identified by means of a suitable letter.
If, after consideration, it is decided that a core Is to be
used for a function for which its colour is not
recognised by Table 51B then its function is to be
identified by a letter. A brown core used as a neutral
should be identified with an N and a blue core used as
a phase conductor should be identified by L1 or L2 or
3. It is better, however, to select the correct cable
and identification colours for an installation.
Itis a deviation to apply colours to flexible cores to
identify them as being used for a purpose other than
that which their original colour indicates - if, after due
consideration, colours are applied the deviation must
be clearly recorded on the Electrical Installation
Certificate and in the construction record documentation.
There is also a current installation trend to supply and
install multicore cables complying with HD 324: 1977
that have blue insulation on the neutral conductor. It
must be noted that this may comply with Regulation
$11-01-01 but not with Table 51A. Such cables should
be correctly identified at their terminations.
The colour combination green-and-yellow is reserved
exclusively for identification of protective conductors
and cannot be used for any other purpose. Bare
conductors and busbars which are to be used as
protective conductors may be identified using green-
and-yellow sleeving or tape.
511-01-01
514-06-01
23CIRCUITS
A diagram, chart or table giving details of the circuits
is required. These details must be used by the person
verifying compliance with BS 7671; for example,
details of the selection and characteristics of the
protective devices are needed for verifying protection
against overcurrent and electric shock. The same
details will be needed for periodic inspection and
testing later on.
A durable copy of the details should be fixed in or
near the distribution board which serves the area.
For simple installations, the Electrical Installation
Certificate, together with the Schedule of Test Results,
and the Schedule of Inspections, will meet BS 7671
provided each circuit is identified in the distribution
board.
SWITCHGEAR
Labelling of switchgear is very important particularly
where the route of the final circuit cables is not
obvious. If there is a possibility of confusion some
reliable means of identification must be clearly
visible, It is necessary for the protective devices to be
marked so that they can be identified easily by the
user (see BS EN 60439).
Fig 2.1 is a diagram of a typical installation showing
the information needed to comply with BS 7671. The
method of presentation will depend upon the size
and complexity of the installation.
Complex installations demand greater detail. Details
of protective measures and cables should be provided
as part of the ‘As installed’ information. When the
occupancy of the premises changes the new occupier
should have sufficient information to properly
operate the electrical installation. Diagrams, charts,
tables and schedules should be kept up to date. Such
items are essential aids in the maintenance and
periodic inspection and testing of an installation.
WARNING NOTICES
The notices called for in Section 514 of BS 7671 are
intended to warn persons about the risk of working
on or near live parts which may be thought to be
isolated.
514-09-01
712-01-03(xvii)
514-08-01
514-09-01
741-01-01
742-01-01
514-09-01WARNING NOTICES - voltage 514-10-01
The warning notices regarding voltage concern three
different situations:
1. inside an item of equipment or enclosure
Where the nominal voltage (Uo) within an item of
equipment or enclosure exceeds 230 volts (e.g. if a
non-standard voltage such as 650 V was present),
and where the presence of such a voltage would
not normally be expected, before access is gained
toa live part, there must be a clearly visible
warning of the maximum voltage present.
2, between simultaneously accessible items of
equipment or enclosures
Where simultaneously accessible terminals or other
fixed live parts have a nominal voltage (Uo)
between them which exceeds 230 volts (such as
where the voltages are from different systems),
then a warning notice must be fixed in such a
position that anyone, before gaining access to such
live parts, is warned of the maximum voltage which
exists between those parts.
w
. where different nominal voltages exist
The means of access to all live parts of switchgear
and other fixed live parts where different nominal
voltages exist (e.g. if different nominal voltages
such as 110 V and 230 V were present either within
or between switchgear or other fixed live parts),
must be marked to indicate the voltages present.
Note.
Three-phase 400 V (U) systems have a nominal phase
to earth voltage (Uo) of 230 V and do not normally
require a warning notice.
OTHER NOTICES
Other notices required by Section 514 are:
* in each position where there are live parts which 514-11-01
are not capable of being isolated by a single device
* regarding periodic inspection and testing 514-12-01
regarding earthing and bonding connections 514-13
25Where protection by earth-free local equipotential
bonding or protection by electrical separation is used,
the bonding conductors must not be connected to
Earth. A warning notice to this effect, as specified in
Regulation 514-13-02, must be fitted.
SAFETY SIGNS
Item 9 of Appendix 2 of BS 7671 refers to the
provision of safety signs as required by the Safety
Signs Regulations 1996. Risks should be minimised at
the design of an installation and warning signs only
used where other methods of avoiding danger are
not practical to implement.
WARNING NOTICES and IDENTIFICATION LABELS
Table 2.2 lists the requirements for warning notices
and identification labels given in BS 7671. Labels and
warning notices should be of a size and type suitable
for the location and installed such that they will not
be painted over or easily removed or defaced. Labels
etc. should be permanently fixed, e.g. by suitable
screws or rivets, or resin glues, taking care not to
damage equipment, invalidate IP ratings or block
vents. Stick-on labels are not advisable and should
only be used where heat or damp is not expected, as
they cannot be considered permanent.
PIPES AND DUCTS
BS 1710 : 1984 (1991)prescribes a system for the
identification of piped services, ducts and electrical
conduits by colour. In the system, red is reserved as a
safety colour for fire fighting and yellow for warning.
Electrical conduits can be identified by completely
painting the conduit or painting bands (150 mm in
length). The colour for electrical services is orange
(O6E51 in BS 4800)
AT1-11-01 |
A71-12-01
514-13-02
Appx 2
514-02-01Fig 2.1: Typical installation
structure
final circuits fina creuts wiring INSTALLATION final circuits
cable sizes 2 e* —cablosizos A A bonging A cable sizes +
cuit duty cai ty information uit duty 7
eee
rou rating
‘design current
conductors
breaking capacity
aking capac
type & configuration
‘nal cistrbuion board
[fina distbation
ple
breaking capacy
rating
function
switch
rating
function
switch
pe
breaking capacity
protective conductors
size
‘main equipotental
‘Groull rang
‘design current
breaking eapaciy
inal astributon boa
ROD
ple
breaking capacity
4 rating
‘oarthing function
ea switch
IP code as
required
B
bonding conductors TL trsystem |
sue ;
vaing valng valng separate instalation
Sesign current | | design curent | [design current
pte pic pic
breaking capacity | | breaking capacity! | breaking capacity installation ‘conductors
| protective device | rotecth earth electrode, type & configuration
protective device |_| protective device | _ [protective device a
busbar - aia =D
rating
design curont protective conductors size
tovel of protection - ——
1 codo as main swichand proteclve device fraigeguiptenl
requted bond
INSTALLATION size & type ot —
ia meter tals
ple = prospective fault current
nd = maximum demand
pominal voltage/md current
pte ‘extemal impedance
earthing system value
suppliers final dstibution
Y
‘energy source
‘means of earthing28
TABLE 2.1 (From TABLE 51A of BS 7671)
Colour identification of cores of non-flexible cables
and bare conductors for fixed wiring
Function Colour identification
Protective (inclu
circuits
19 earthing) conductor and | green-and-yellow
Phase of a.c. single-phase circuit red)
Neutral of a.c. single- or three-phase circuit | black
Phase R of three-phase a.c. circuit red
Phase Y of three-phase ac. circuit yellow
Phase B of three-phase a.c. circuit blue
Three-wire 460/230 V single-phase a.c. circuits
(Centre conductor earthed)
Outer, phase conductors (either conductor) | red
Centre neutral conductor black
‘Two-wire unearthed d.c. circuits
Positive of d.c. two-wire circuit red
Negative of d.c. two-wire circuit black
Three-wire d.c. circuits
Outer (positive or negative) of d.c. two-wire
circuit derived from three-wire system red
Positive of three-wire d.c. circuit red
Middle wire of three-wire d.c. circuit 2) black
Negative of three-wire d.c. circuit blue
‘Two-wire earthed d.c. circuits
positive (of negative earthed) circuit red
negative (of negative earthed) circuit black
positive (of positive earthed) circuit black
negative (of positive earthed) circuit blue
Functional Earth cream
Notes:
(9) As alternatives to the use of red, if desired, in large
installations, for the supply cables to final distribution boards
yellow and blue may also be used. All single-phase final
circuit non-flexible fixed wiring must be red and black.
2) Only the middle wire of three-wire circuits may be earthed.
(3) The colours in Table 2.1 only apply to fixed installations in
buildings and not necessarily to installations in factory built
‘equipment which is excluded from BS 7671 (see Regulation
1110-03-01). BS EN 60204-1 details colours for the electrical
equipment of machines
(4) These colours will be revised after 2004.TABLE 2.2
Warning notices and ident
ation labels required by BS 7671
Notice, label or identification Regulation
Isolating device and its installation or circuit (if not obvious) 4461-01-05
‘Switching device for mechanical maintenance (indication of 462-01-02
operation) 537-03-02
Protection by electrical separation 47-12-01
Protection by earth-free local equipotential bonding 47-11-01
514-13-02
‘Areas reserved for skilled or instructed persons 4471-13-03
514-13-02
Fireman’s switch 4476-03-07
537-04-06
Purpose of switchgear and controlgear (if not obvious) 514-01-01
Conduit, identification, where required 514-02-01
Bare protective conductors 514-03-01
Diagrams, charts etc. for installation information 514-09-01
Marking voltages present on means of access 514-10-01
Voltages exceeding 230 V 3514-10-01
Live parts not capable of being isolated by a single device 461-01-03
514-11-01
Periodic inspection and testing (see Regulation 611-04-04) 3514-12-01
Quarterly test of a residual current device (see Chapters 71 and 73) | 514-12-02
Earthing and equipotential bonding connections 514-13-01
42-03-03
Earth-free equipotential bonding 5914-13-02
Cables buried in the ground 522-06-03
Caravan inlet 608-07-03
Caravan instructions for supply and periodic inspection and testing | 608-07-05
Identification of highway power supply cables 611-04-03
Highway temporary supply unit (identification by marking etc.) 61-06-02
292.6
27
30
Mutual
detrimental
influence
515
Compatil
512
331
Regulation 515-01 requires that there be no harmful
effect between electrical and other installations. The
best approach, where practicable, is to arrange that
the installations are kept separated. Damage can be
caused by such influences as thermal effects,
electrolysis or corrosion. The thermal effects of other
installations — such as hot water systems — must be
considered and equipment either designed to operate
properly at elevated temperatures or reduced
temperatures, or be protected from such effects.
Electrolysis may result from leakage currents, or from
contact between dissimilar metals in damp conditions,
while corrosion may result for example in rusting of
unprotected steelwork. Action needs to be taken to
obviate these risks.
The Electromagnetic Compatibility (EMC) Regulations
place a statutory requirement on designers and
constructors to design/construct electrical equipment
and systems so that they do not cause excessive
electromagnetic interference (emissions) and are not
unduly affected by electromagnetic interference from
other electrical equipment or systems. Harmonic
production and interference, electrostatic discharges,
mains-borne signals etc are all types of EM
interference to be considered, but the subject is too
wide for this Guidance Note and requires specialist
advice (see Section 7, and Appendix | for some further
information).
The protection provided should form a prominent
feature of the Building Services Manual. Guidance in
the preparation of the manual can be found in
BS 4884, BS 4940 and Section 6 of the Health and
Safety at Work etc. Act 1974 (HSW Act).
Manufacturers’ leaflets for switchgear, luminaires,
electrical equipment, accessories, and any special
instructions, should be included.
‘The HSW Act, the Consumer Protection Act and the
Construction (Design and Management) Regulations
1994 provide specific requirements for information to
be provided.
All equipment should be selected and erected so that
it will not be susceptible to interference from, or
cause harmful effects to, other equipment when used
for the purpose for which it was intended, nor impair
131-11
515-01
528-02
515-02
132-01-08
331-01-01
512-05the supply during normal service, including switching
operations (see Section 2.4 and 2.6).
Regulation 31-01-01 is of particular importance 33-01-01
when considering supplies to information technology
equipment. This includes computers, electronic office
equipment, data transmission equipment and point-
of-sale terminals. The power supply units of this type
of equipment are particularly well known for causing
harmonic generation problems.
Whenever electrical equipment is switched on or off,
particularly where inductive loads are involved, high
frequency voltage transients occur. This so-called
mains-borne noise may cause malfunction in
information technology equipment. The capacitance
of the circuit cables and the filters incorporated in
most information technology equipment attenuate
this mains-borne noise. It is good practice to ensure
that sources likely to give rise to significant noise (e.g.
motors and thermostatically controlled equipment)
are kept apart from sensitive equipment. Susceptible
electronic equipment should be fed by separate
circuits from the incoming supply point of the
building. Additional filters (sometimes called ‘power
conditioners’) may be used to reduce this transient
noise on existing circuits, and surge protection devices
can be installed to divert or absorb transients. (See
Section 3.8)
Large switch-on (inrush) current surges which occur
with transformers, motors and mains rectifier circuits,
can cause excessive short-time voltage drop in the
circuit conductors (dips). Inrush currents affect other
Circuits also and may require larger cable sizes, or the
equipment to be put on separate circuits. It should be
borne in mind that information technology
equipment itself can cause the same problem if
switched on in large groups.
Where the maintenance of the supply voltage to
especially sensitive equipment such as information
technology equipment is considered of importance,
the user may need a device such as a motor alternator
or uninterruptible power supply (UPS).
312.8
32
‘Clean’ (low
noise) earths
When information technology equipment is planned
functional earthing and a ‘clean’ (low-noise) earth
must be considered. Information on functional
earthing is contained in Section 5.5 of Guidance Note 5.
Information on earthing requirements for the
installation of equipment having high protective
conductor currents is located in Chapter 7 of
Guidance Note 7. (See also Section 8.1 of this
Guidance note).
The protective conductors in a building are subject to
transient voltages relative to the general mass of
earth. These transients are termed ‘earth noise’ and
are usually caused by load switching. They may be
generated by the charging of an equipment frame via
the stray capacitance from the mains circuit, or
mains-borne transients may be coupled into the earth
conductor or frame from mains conductors.
As ‘earth noise’ can cause malfunction, manufacturers
of large computer systems usually make specific
recommendations for the provision of a ‘clean’ mains
supply and a ‘clean’ earth. The equipment
manufacturer's guidance must be taken for such
installations.
A dedicated earthing conductor may be used for a
computer system, provided that:
(i) all accessible exposed-conductive-parts of the
computer system are earthed, the computer
system being treated as an ‘installation’ where
applicable
(ii) the main earthing terminal or bar of the
computer system (‘installation’) is connected
directly to the building main earthing terminal
by a protective conductor
(iii) extraneous-conductive-parts within reach of the
computer systems are earthed, but not via the
protective conductor referred to in (ii) above.
Supplementary bonding between extraneous-
conductive-parts and the accessible conductive parts
of the computer system is not necessary.
542-04
607-02
543-01
413-02-032.9 LV switchgear BS EN 60439-1 : 1999 gives guidance on the forms of
and controlgear separation applicable to factory-built switchgear and
assemblies _controlgear assemblies (switchboards, motor control
centres, distribution boards, busbar trunking systems
etc.), known as type-tested and partially type-tested
assemblies. These forms of separation provide
protection against contact with live parts belonging
to adjacent devices and protection from the
probability of initiating arcing faults and the passage
of foreign bodies between units of the assembly. The
Standard also gives guidance on other requirements
for protection against electric shock.
Definitions given in BS EN 60439-1 are:
Type-tested low voltage switchgear and controlgear
assembly (TTA)
A low voltage switchgear and controlgear assembly
‘conforming to an established type or system without
deviations likely to significantly influence the
performance from the typical ASSEMBLY verified to
be in accordance with this standard.
For various reasons, for example transport or
production, certain steps of assembly may be made in
a place outside the factory of the manufacturer of the
type-tested ASSEMBLY. Such an ASSEMBLY is
considered as a type-tested ASSEMBLY provided the
site assembly is carried out in accordance with the
manufacturer's instructions which should be retained
for future information. The instructions will include
any requirements for submission of the ASSEMBLY to
further applicable routine test.
Partially type-tested low voltage switchgear and
controlgear assembly (PTTA)
A low voltage switchgear and controlgear assembly,
containing both type-tested and non-type-tested
arrangements provided that the latter are derived
(e.g, by calculation) from type-tested arrangements
which have complied with the relevant tests.
It should be noted that the forms of separation have
no bearing on the overall ingress protection (IP rating
or classification) for the external frame and enclosure
of the switchgear assembly etc. This should be
specified to the required IP rating (see Appendix B).a4
BS EN 60439-1 : 1999 is identical to IEC 60439-1 : 1999
with the exception of the additional information
given in National Annex NA. Designers and specifiers
working on international projects should clarify
specific requirements with the manufacturer.
FORMS OF SEPARATION
Four forms of separation are indicated in the maii
text of BS EN 60439-1 : 1999, but there is no specific
detail given on how these forms are to be achieved. It
is stated in the BS EN that the form of separation
should be agreed between manufacturer and
designer/user. It must be remembered that higher
forms of separation specified will increase costs but
will give better operational flexibility regarding safe
working when connecting in additional circuits or
carrying out maintenance. This ‘trade off’ must be
carefully assessed.
The four forms given have basic definitions and
applications, but Forms 2 to 4 can be further
subdivided into more specific “Types” (applications)
by discussion and agreement with manufacturers.
Further examples beyond the basic definitions in the
main text of the standard are given in the National
Appendix NA and are described in Form 1 to Form 4
below.
Form 1
This form provides for an enclosure to provide
protection against direct contact with live parts, but
does not provide any internal separation of switching,
isolation or control items or terminations. These
overall assemblies are often known as ‘wardrobe’ type
with large front opening doors, usually with an
integral door interlocked isolator. Operating the
isolator interrupts all functions but allows the door to
be opened to gain access to the assembly for
installation or maintenance. Such assemblies normally
have lower fault withstand and it may be
inconvenient to shut down a whole plant or system
for a simple maintenance or repair operation.
(See Fig 2.2)Fig 2.2: Form 1 Construction
outgoing
outgoing
ue
incoming
‘nit
Form 1 - Common Enclosure
a SS
conductors connecing the busbars ————(") terminal
tothe outgoing circus oS
Form 2
The overall assembly enclosure provides protection
against direct contact with live parts; separation is
provided between the busbar assembly and
switching, isolation, control items and terminations.
There is very little advantage of this over Form 1, and
the style is similar. Form 2 can be further subdivided
into:
—Type 1, in which the busbars are separated by
insulation of the bars.
— Type 2, in which the busbars are separated by
metallic or non-metallic rigid barriers.
35Form3
The enclosure provides protection against direct
contact with live parts, and also separation is provided
between the busbars and switching, isolation or
control items, and between alll these items. Outgoing
terminals are not separated from each other, or
perhaps from the busbars. Form 3 can be further
subdivided into:
—— Form 3a, in which outgoing terminals are not
separated from the busbars.
— Form 3b, in which outgoing terminals are
separated from the busbars.
Form 3b can be further subdivided into:
—Type 1, in which the busbars are insulated for
separation.
—Type 2, in which busbar separation is by metallic or
non-metallic rigid barriers or partitions.
Form4
The enclosure provides protection against direct
contact with live parts, and internal separation of the
busbars from all switching, isolation and control items
and outgoing terminations, and separation of all
items and outgoing terminations from each other.
This allows for access to any single item, such as a
switch-fuse or starter, and its outgoing terminations,
to enable work to be carried out whilst the assembly
remains operational. Protection is also provided
against an arcing fault in one device affecting other
items. This is the usual form specified for commercial
and industrial switchgear and controlgear assemblies,
but the designer has to consider whether due to the
extra cost such requirements are necessary or justified.
Form 4 can be further subdivided into seven types:
—Type 1, in which the busbars are separated by
insulation coverings. Terminals for external
conductors are in the same compartment as the
associated item of switchgear etc., but cables may
be glanded elsewhere.
—Type 2, in which the busbars are separated by
metallic or non-metallic rigid barriers or partitions.
Terminals for external conductors are in the samecompartment as the associated item of switchgear
etc., but cables may be glanded elsewhere.
— Type 3, in which separation requirements are by
metallic or non-metallic rigid barriers or partitions.
Terminals for external conductors are in the same
compartment as the associated item of switchgear
etc,, and each item has its own integral cable
glanding facility.
— Type 4, in which the busbars are separated by
insulated coverings. Terminals for external
conductors are not in the same compartment as the
associated item of switchgear etc., but in separate
enclosed spaces, but cables may be glanded
elsewhere.
— Type 5, in which busbars are separated by metallic
or non-metallic rigid barriers or partitions.
Terminals for external conductors are not in the
same compartment as the associated item of
switchgear etc,, but in separate enclosed spaces,
and terminals may be separated by insulated
coverings. Cables may be glanded in common
cabling chambers.
— Type 6, in which all separation requirements are by
metallic or non-metallic rigid barriers or partitions.
Terminals for external conductors are not in the
same compartment as the associated item of
switchgear etc., but in separate enclosed spaces,
and cables are glanded in common cabling
chambers.
— Type 7 in which all separation requirements are by
metallic or non-metallic rigid barriers or partitions.
Terminals for external conductors are not in the
same compartment as the associated item of
switchgear etc., but in separate enclosed spaces,
and the termination for each item has its own
integral glanding facility. (See Fig 2.3)
Switchboard manufacturers therefore cannot give all-
embracing assurances for safe working, according to
the form of separation with parts of the assembly
energised. Specifying a particular form of separation
will not guarantee this for any given form number.
aFig 2.3: Form 4 Construction (Type 7)
Incoming
T T
urging units outgeing units
terminal
enclosure
rooming
ml (GQ |G some. ages
GENERAL
Assemblies are to be designed and constructed so as
to be able to withstand the thermal and dynamic
stresses resulting from fault currents up to their rated
values. The designer must specify the prospective fault
current conditions at the point of installation.
Busbar systems for switchgear and controlgear should
be adequately rated for the normal duty and
maximum fault current level expected, and should be
well supported and braced, as the electromechanical
stresses under fault conditions can be severe.
However, thermal movement must be allowed for. \t
is usual for manufacturers to prove their busbar
designs with a full short-circuit test by an
independent test station up to the rated fault current
level on a sample construction. The busbar
arrangement can then be certified as a ‘type-tested’
busbar system.Tests, as detailed in BS EN 60439 : Part 1, are applied
to the complete assembly as relevant at manufacture,
including continuity, insulation resistance and
perhaps a flash test at high voltage. The designer and
installer must be aware that there are statutory
requirements under the Electricity at Work
Regulations and the CDM Regulations etc. for the safe
design, construction, operation and provision for
maintenance of electrical equipment assemblies.
Adequate access, working space and lighting must be
provided where work is to be carried out on or near
equipment, in order that persons may work safely.
It must also be realised that Regulation 8 of the
Electricity at Work Regulations places an absolute
requirement (one that must be met regardless of cost
or any other consideration) on protective conductor
connections to earth: “a conductor shall be regarded
as earthed when it is connected to the general mass
of earth by conductors of sufficient strength and
current-carrying capability to discharge electrical
energy to earth”. It may be questioned whether the
termination of steel or aluminium wire armour (where
used as a protective conductor) with glands into metal
gland plates, which themselves may only be bolted to
the switchgear or controlgear frame, is an adequate
connection. Cable gland “earth tags” and
supplementary connections to the equipment earth
terminals may be necessary. In any case it should be
ensured that any paint or other surface finish on the
switchgear does not prevent effective electrical
continuity between the adjacent parts.
During site installation and commissioning, tests as
required by BS 7671 Part 7 should be carried out on
the complete assembly, plus any other specific tests
advised by the manufacturer or required by the client,
user or engineer. It is not usual to carry out a repeat
of specialist tests such as a flash test at site, and in the
event of a requirement the manufacturer's advice
should be sought.
39